Instrumentation Cable BS
Instrumentation Cable BS
Instrumentation Cable BS
The high growth of automation in process industry, especially process control across large user sites like oil refining and
petrochemical plants, the steel industry, power stations etc. necessitates the reliable transmission of electrical signals,
process data and control information.
Today, in a continuous process plants like refinery, fertilizer, cement, steel, etc. Various parameters like temprature,
pressure flow, level etc are converted in to electrical signals which are fed to the control room. In control room these
signals are analyzed and suitable commands are sent to the field to take corrective action. The control room has become
the brain of the plant and instrumentation cables are the arteries.
Polycab’s instrumentation cables are preferred choice by the majority of indian industry, leading EPC contractors, and
electrical consultans.
The shielded and screened type of instrumentation cables designed and manufactured by POLYCAB, reduces the external
noise pick up in the circuit, there by reduces the interference. These cables are also offered with GI armour wire for
protected application.
POLYCAB is a leading manufacturer of a instrumentation cable having wide product range conforming to BS EN 50288,
UL 2250 (Certified) & BS 7629 (LPCB Approved) and other different national and international specifications as well as
customised specification which conforms to extreme fire properties under temperature rating from 60 deg to 105 deg.
Presently Polycab
Caution: Instrumentation cables are not designed for use with power supplies and should not be connected to then
mains power.
Conductor: High conductivity annealed plain/tinned stranded copper conductor produced in-house from state-of-the art
machine.
Insulation: In-house developed PVC/XLPE insulation compound having high insulation properties.
Individual screen: Shielding type for twisted pair/triad, Aluminium-Mylar tape with tinned copper drain wire. Drain wire
will continuous contact with aluminum side of the tape. Shielding with ATC braiding can also be provided to meet the
specific requirements.
Pair/triad Identification: Identification of pair/triad by number printing or by numbered polyster tape over each pair/triad.
Also idenfication is availabe with different color coding.
Collective screen: Aluminium-Mylar tape along with tinned copper drain wire to be applied over the pair/triad assembly.
Drain wire will continuous contact with aluminum side of the tape. Shielding with ATC braiding can also be provided to
meet specific requirements.
Inner Sheath: In-house developed thermoplastic compound having low emission of smoke and corrosive gases when
exposed to fire and also ensures circular shape of cable.
Outer Sheath: In-house developed thermoplastic compound having low emission of smoke and corrosive gases when
exposed to fire.
Intrumentation_Core_300V_Ovr_BS-50288 Intrumentation_Core_500V_Ovr_BS-50288
Intrumentation_Pair_300V_Ind_Ovr_BS-50288 Intrumentation_Pair_300V_Ovr_BS-50288
Intrumentation_Pair_500V_Ind_Ovr_BS-50288 Intrumentation_Pair_500V_Ovr_BS-50288
Intrumentation_Triad_300V_Ind_Ovr_BS-50288 Intrumentation_Triad_300V_Ovr_BS-50288
Intrumentation_Triad_500V_Ind_Ovr_BS-50288 Intrumentation_Triad_500V_Ovr_BS-50288
POLYCAB INSTRU 300 MC
Instrumentation cable PVC/PE Insulated Overall shielded 300V
Application
POLYCAB INSTRU 300 MC, insulated with PVC/PE, Overall, al-mylar shielded, armoured/unarmoured and
PVC/LSZH sheathed cable confirming to BS EN 50288-7 are designed for transmission of analogue and digital
signals in instrument and control systems. POLYCAB INSTRU 300 MC cables are used for diverse applications
within industrial process for control, communication, data & voice transmission in oil, gas & petrochemical
industries, cement, steel, fertilizers etc.
Construction Compliance
Stranded Copper conductor as per EN 60228 Conductor resistance - EN 60228
Insulated with PVC/PE as per EN 50288-7 Insulation resistance - EN 50288-7
Collective screen Al/PET (Aluminium L/R Ratio - EN 50288-7
/Polyester tape) with drain wire of tinned Mutual capacitance - EN 50288-7
Cu/Tinned copper braiding.
Note: Outer sheath also available with PE & FRLS on
Extruded inner sheath with PVC/LSZH to request.
EN 50290-2-22/27
Armoured with Galvanised Steel
Strip/Round as per EN 50288-7
Sheathed with Extruded PVC/LSZH to EN
50290-2-22/27
Core Identification
White/Grey core with number printing.
0.5 4 0.26 0.8 0.9 1.3 10.3 210 215 0.8 5.9 53 57
0.5 5 0.26 0.9 0.9 1.3 11.0 235 240 0.9 6.6 63 67
0.5 6 0.26 0.9 0.9 1.3 11.5 260 265 0.9 7.1 73 78
0.5 7 0.26 0.9 0.9 1.3 11.5 260 270 0.9 7.1 76 82
0.5 8 0.26 0.9 0.9 1.3 12.3 285 295 0.9 7.9 85 92
0.5 10 0.26 0.9 0.9 1.4 13.4 330 340 0.9 8.8 100 110
0.5 12 0.26 0.9 0.9 1.4 13.7 345 355 0.9 9.1 115 125
0.5 16 0.26 1.0 0.9 1.4 14.8 410 425 1.0 10.2 150 165
0.5 18 0.26 1.0 0.9 1.4 15.3 435 450 1.0 10.7 165 180
0.5 19 0.26 1.0 0.9 1.4 15.3 440 455 1.0 10.7 170 185
0.5 20 0.26 1.0 0.9 1.4 15.9 465 485 1.0 11.3 185 200
0.5 24 0.26 1.0 0.9 1.4 17.0 510 540 1.0 12.4 205 230
0.5 30 0.26 1.1 0.9 1.5 18.1 590 620 1.1 13.3 255 280
0.5 37 0.26 1.1 0.9 1.5 19.1 660 690 1.1 14.3 300 335
0.75 2 0.26 0.8 0.9 1.3 10.1 195 200 0.8 5.7 46 48
0.75 5 0.26 0.9 0.9 1.3 11.6 265 270 0.9 7.2 79 84
0.75 6 0.26 0.9 0.9 1.3 12.2 290 295 0.9 7.8 92 98
0.75 7 0.26 0.9 0.9 1.3 12.2 290 300 0.9 7.8 96 105
0.75 8 0.26 0.9 0.9 1.4 13.2 330 340 0.9 8.6 110 115
0.75 10 0.26 1.0 0.9 1.4 14.5 390 400 1.0 9.9 135 145
0.75 12 0.26 1.0 0.9 1.4 14.8 410 420 1.0 10.2 155 165
0.75 16 0.26 1.0 0.9 1.4 15.8 475 490 1.0 11.2 195 215
0.75 18 0.26 1.0 0.9 1.4 16.4 510 530 1.0 11.8 220 235
0.75 19 0.26 1.0 0.9 1.4 16.4 510 530 1.0 11.8 220 245
0.75 20 0.26 1.0 0.9 1.4 17.0 550 570 1.0 12.4 240 265
0.75 24 0.26 1.1 0.9 1.5 18.7 630 650 1.1 13.9 280 305
POLYCAB INSTRU 300 MC
Instrumentation cable PVC/PE Insulated Overall shielded 300V
0.75 30 0.26 1.1 0.9 1.5 19.5 700 730 1.1 14.7 340 370
0.75 37 0.26 1.1 0.9 1.5 20.6 800 840 1.1 15.8 405 445
1 5 0.26 0.9 0.9 1.3 12.1 290 295 0.9 7.7 94 100
1 6 0.26 0.9 0.9 1.3 12.7 320 330 0.9 8.3 110 120
1 7 0.26 0.9 0.9 1.3 12.7 325 335 0.9 8.3 115 125
1 8 0.26 0.9 0.9 1.4 13.8 370 380 0.9 9.2 130 140
1 20 0.26 1.1 0.9 1.5 18.4 650 670 1.1 13.6 305 330
1 24 0.26 1.1 0.9 1.5 19.8 720 750 1.1 15 350 380
1 30 0.26 1.1 0.9 1.5 20.6 810 850 1.1 15.8 420 455
1 37 0.26 1.2 0.9 1.5 22.1 940 980 1.2 17.3 510 560
1.5 2 0.35 0.9 0.9 1.3 11.6 260 265 0.9 7.2 74 78
1.5 4 0.35 0.9 0.9 1.4 12.9 330 335 0.9 8.3 115 120
1.5 5 0.35 0.9 0.9 1.4 13.6 360 370 0.9 9 130 140
1.5 8 0.35 1 0.9 1.4 15.8 470 485 1 11.2 190 205
1.5 10 0.35 1.1 0.9 1.5 17.6 560 580 1.1 12.8 235 255
1.5 12 0.35 1.1 0.9 1.5 18 600 630 1.1 13.2 275 295
1.5 16 0.35 1.1 0.9 1.5 19.4 710 740 1.1 14.6 350 380
1.5 18 0.35 1.1 0.9 1.5 20.2 780 810 1.1 15.4 395 425
1.5 19 0.35 1.1 0.9 1.5 20.2 790 820 1.1 114 400 438
1.5 20 0.35 1.2 0.9 1.5 21.2 850 890 1.2 16.4 445 480
1.5 24 0.35 1.2 1.25 1.6 23.9 1090 1140 1.2 18.2 510 550
POLYCAB INSTRU 300 MC
Instrumentation cable PVC/PE Insulated Overall shielded 300V
1.5 30 0.35 1.3 1.25 1.6 25.1 1250 1300 1.3 19.4 630 680
1.5 37 0.35 1.3 1.25 1.7 26.9 1430 1500 1.3 21 750 820
For Cables of sizes or cores not listed above the product data is available on request
Dimensions & Weights are representative figures and may vary
Electrical Parameter
Max. DC
Max. DC
resistance of Insulation Insulation Inductance to
Area of resistance of Mutual
conductor at 20°C resistance resistance resistance
Conductor conductor at 20°C capacitance
Metal coated (PVC) (PE/XLPE) ratio(L/R)
Plain wires
wires
Sqmm Ohm/km Ohm/km MΩ/Km MΩ/Km nf/Km μH/Ω
0.5 36 36.7 10 1000 < 250 < 25
0.75 24.5 24.8 10 1000 < 250 < 25
1 18.1 18.2 10 1000 < 250 < 25
1.5 12.1 12.2 10 1000 < 250 < 40
2.5 7.41 7.56 10 1000 < 250 < 60
POLYCAB INSTRU 500 MC
Instrumentation cable PVC/PE Insulated Overall shielded 500V
Application
POLYCAB INSTRU 500 MC, insulated with PVC/PE, Overall, al-mylar shielded, armoured/unarmoured and
PVC/LSZH sheathed cable confirming to BS EN 50288-7 are designed for transmission of analogue and
digital signals in instrument and control systems. POLYCAB INSTRU 500 MC cables are used for diverse
applications within industrial process for control, communication, data & voice transmission in oil, gas &
petrochemical industries, cement, steel, fertilizers etc.
Construction Compliance
Stranded Copper conductor as per EN Conductor resistance - EN 60228
60228 Insulation resistance - EN 50288-7
Insulated with PVC/PE as per EN 50288-7 L/R Ratio - EN 50288-7
Collective screen Al/PET (Aluminium Mutual capacitance - EN 50288-7
/Polyester tape) with drain wire of tinned
Cu/Tinned copper braiding Note: Outer sheath also available with PE & FRLS on
request.
Extruded inner sheath with PVC/LSZH to
EN 50290-2-22/27
Armoured with Galvanised Steel
Strip/Round as per EN 50288-7
Sheathed with Extruded PVC/LSZH to EN
50290-2-22/27
Core Identification
White/Grey core with number printing.
Electrical Parameter
Max. DC
Max. DC
resistance of Insulation Insulation Inductance to
Area of resistance of Mutual
conductor at 20°C resistance resistance resistance
Conductor conductor at 20°C capacitance
Metal coated (PVC) (PE/XLPE) ratio(L/R)
Plain wires
wires
Sqmm Ohm/km Ohm/km MΩ/Km MΩ/Km nf/Km μH/Ω
0.5 36 36.7 10 1000 < 250 < 25
0.75 24.5 24.8 10 1000 < 250 < 25
1 18.1 18.2 10 1000 < 250 < 25
1.5 12.1 12.2 10 1000 < 250 < 40
2.5 7.41 7.56 10 1000 < 250 < 60
POLYCAB INSTRU 300 MP
Instrumentation cable PVC/PE Insulated Individual & Overall shielded 300V
Application
POLYCAB INSTRU 300MP, Stranded copper conductor, PVC/PE insulated, Individual & overall al-mylar
shielded, armoured/unarmoured and PVC/LSZH sheathed cable confirming to BS EN 50288-7 are designed for
transmission of analogue and digital signals in instrument and control systems. POLYCAB INSTRU 300MP
cables are used for diverse applications within industrial process for control, communication, data & voice
transmission in oil, gas & petrochemical industries, cement, steel, fertilizers etc.
Construction Compliance
Stranded Copper conductor as per EN 60228 Conductor resistance - EN 60228
Insulated with PVC/PE as per EN 50288-7 Insulation resistance - EN 50288-7
Individual & Collective screen Al/PET L/R Ratio - EN 50288-7
(Aluminium/Polyester tape) with drain wire Mutual capacitance - EN 50288-7
of tinned Cu/ Tinned copper braiding.
Extruded inner sheath with PVC/LSZH to Note: Outer sheath also available with PE & FRLS on
request.
EN 50290-2-22/27
Armoured with Galvanised Steel
Strip/Round as per EN 50288-7
Sheathed with Extruded PVC/LSZH to EN
50290-2-22/27
Core Identification
White & Blue for Pair
0.5 4 0.26 1.0 0.9 1.4 14.8 385 390 1.0 10.2 130 135
0.5 5 0.26 1.0 0.9 1.4 15.7 430 440 1.0 11.1 155 165
0.5 6 0.26 1.0 0.9 1.4 16.7 480 490 1.0 12.1 180 190
0.5 8 0.26 1.1 0.9 1.5 18.6 580 590 1.1 13.8 230 245
0.5 10 0.26 1.1 0.9 1.5 20.4 670 680 1.1 15.6 280 300
0.5 12 0.26 1.2 0.9 1.5 21.1 730 750 1.2 16.3 330 350
0.5 16 0.26 1.2 1.25 1.6 23.8 1000 1030 1.2 18.1 420 445
0.5 18 0.26 1.3 1.25 1.6 24.9 1080 1120 1.3 19.2 470 500
0.5 19 0.26 1.3 1.25 1.6 24.9 1100 1140 1.3 19.2 490 530
0.5 20 0.26 1.3 1.25 1.7 26.2 1170 1210 1.3 20.3 520 550
0.5 24 0.26 1.4 1.25 1.7 28.6 1340 1390 1.4 22.7 620 660
0.5 30 0.26 1.4 1.25 1.7 30.0 1510 1570 1.4 24.1 750 800
0.5 37 0.26 1.5 1.25 1.8 32.3 1760 1830 1.5 26.2 910 980
0.75 2 0.26 1.0 0.9 1.4 14.1 345 350 1.0 9.5 98 100
0.75 4 0.26 1.0 0.9 1.4 15.7 435 440 1.0 11.1 155 165
0.75 5 0.26 1.0 0.9 1.5 16.9 495 500 1.0 12.1 185 195
0.75 6 0.26 1.1 0.9 1.5 18.2 560 570 1.1 13.4 225 238
0.75 8 0.26 1.1 0.9 1.5 19.8 660 680 1.1 15.0 280 300
0.75 10 0.26 1.2 0.9 1.6 22.3 790 810 1.2 17.3 350 370
0.75 12 0.26 1.2 1.25 1.6 23.5 970 1000 1.2 17.8 405 430
0.75 16 0.26 1.3 1.25 1.7 25.9 1180 1210 1.3 20.0 520 560
0.75 18 0.26 1.3 1.25 1.7 27.0 1260 1300 1.3 21.1 580 620
0.75 19 0.26 1.3 1.25 1.7 27.0 1290 1330 1.3 21.1 610 650
0.75 20 0.26 1.4 1.25 1.7 28.4 1370 1410 1.4 22.5 650 690
0.75 24 0.26 1.4 1.25 1.8 31.1 1570 1630 1.4 25.0 770 820
0.75 30 0.26 1.5 1.25 1.8 32.8 1800 1870 1.5 26.7 940 1000
0.75 37 0.26 1.6 1.25 1.9 35.3 2090 2170 1.6 29.0 1140 1220
1.0 2 0.26 1.0 0.9 1.4 14.8 365 370 1.0 10.2 110 115
1.0 4 0.26 1.0 0.9 1.4 16.5 475 485 1.0 11.9 180 190
1.0 5 0.26 1.1 0.9 1.5 18.0 560 570 1.1 13.2 225 235
POLYCAB INSTRU 300 MP
Instrumentation cable PVC/PE Insulated Individual & Overall shielded 300V
1.0 6 0.26 1.1 0.9 1.5 19.2 620 640 1.1 14.4 260 275
1.0 8 0.26 1.2 0.9 1.5 21.1 740 760 1.2 16.3 340 360
1.0 10 0.26 1.2 1.25 1.6 24.2 1010 1030 1.2 18.5 415 435
1.0 12 0.26 1.3 1.25 1.6 25.1 1100 1130 1.3 19.4 485 510
1.0 16 0.26 1.3 1.25 1.7 27.4 1320 1350 1.3 21.5 620 660
1.0 18 0.26 1.4 1.25 1.7 28.8 1440 1480 1.4 22.9 700 740
1.0 19 0.26 1.4 1.25 1.7 28.8 1470 1510 1.4 22.9 730 780
1.0 20 0.26 1.4 1.25 1.7 30.1 1540 1590 1.4 24.2 770 820
1.0 24 0.26 1.5 1.25 1.8 33.2 1790 1850 1.5 27.1 920 980
1.0 30 0.26 1.5 1.25 1.8 34.8 2040 2110 1.5 28.7 1120 1190
1.0 37 0.26 1.6 1.6 1.9 38.3 2590 2670 1.6 31.3 1360 1450
1.5 2 0.35 1.0 0.9 1.5 16.8 450 460 1.0 12.0 145 155
1.5 4 0.35 1.1 0.9 1.5 19.0 600 620 1.1 14.2 245 260
1.5 5 0.35 1.2 0.9 1.5 20.6 700 720 1.2 15.8 305 325
1.5 6 0.35 1.2 1.25 1.6 22.9 910 930 1.2 17.2 355 375
1.5 8 0.35 1.3 1.25 1.7 25.5 1100 1130 1.3 19.6 460 490
1.5 10 0.35 1.4 1.25 1.7 28.4 1300 1330 1.4 22.5 570 610
1.5 12 0.35 1.4 1.25 1.7 29.2 1410 1460 1.4 23.3 660 710
1.5 16 0.35 1.5 1.25 1.8 32.2 1700 1760 1.5 26.1 860 920
1.5 18 0.35 1.5 1.25 1.8 33.6 1840 1910 1.5 27.5 960 1030
1.5 19 0.35 1.5 1.25 1.8 33.6 1880 1950 1.5 27.5 1000 1070
1.5 20 0.35 1.6 1.6 1.9 36.4 2230 2300 1.6 29.4 1070 1140
1.5 24 0.35 1.7 1.6 2.0 40.0 2570 2660 1.7 32.8 1280 1370
1.5 30 0.35 1.8 1.6 2.0 42.2 2950 3060 1.8 35.0 1560 1680
1.5 37 0.35 1.9 1.6 2.1 45.5 3420 3560 1.9 38.1 1900 2040
For Cables of sizes or pairs not listed above the product data is available on request
Dimensions & Weights are representative figures and may vary
POLYCAB INSTRU 300 MP
Instrumentation cable PVC/PE Insulated Individual & Overall shielded 300V
Electrical Parameter
Max. DC
Max. DC
resistance of Insulation Insulation Inductance to
Area of resistance of Mutual
conductor at 20°C resistance resistance resistance
Conductor conductor at 20°C capacitance
Metal coated (PVC) (PE/XLPE) ratio(L/R)
Plain wires
wires
Sqmm Ohm/km Ohm/km MΩ/Km MΩ/Km nf/Km μH/Ω
0.5 36 36.7 10 1000 < 250 < 25
0.75 24.5 24.8 10 1000 < 250 < 25
1 18.1 18.2 10 1000 < 250 < 25
1.5 12.1 12.2 10 1000 < 250 < 40
POLYCAB INSTRU 500 MP
Instrumentation cable PVC/PE Insulated Individual & Overall shielded 500V
Application
POLYCAB INSTRU 500 MP, Stranded copper conductor, PVC/PE insulated, Individual & overall al-mylar
shielded, armoured/unarmoured and PVC/LSZH sheathed cable confirming to BS EN 50288-7 are designed for
transmission of analogue and digital signals in instrument and control systems. POLYCAB INSTRU 500 MP cables
are used for diverse applications within industrial process for control, communication, data & voice transmission in
oil, gas & petrochemical industries, cement, steel, fertilizers etc.
Construction Compliance
Stranded Copper conductor as per EN 60228 Conductor resistance - EN 60228
Insulated with PVC/PE as per EN 50288-7 Insulation resistance - EN 50288-7
Individual & Collective screen Al/PET L/R Ratio - EN 50288-7
(Aluminium/Polyester tape) with drain wire Mutual capacitance - EN 50288-7
of tinned Cu/Tinned copper braiding.
Extruded inner sheath with PVC/LSZH to Note: Outer sheath also available with PE & FRLS on
request.
EN 50290-2-22/27
Armoured with Galvanised Steel
Strip/Round as per EN 50288-7
Sheathed with Extruded PVC/LSZH to EN
50290-2-22/27
Core Identification
White & Blue for Pair
Electrical Parameter
Max. DC
Max. DC
resistance of Insulation Insulation Inductance to
Area of resistance of Mutual
conductor at 20°C resistance resistance resistance
Conductor conductor at 20°C capacitance
Metal coated (PVC) (PE/XLPE) ratio(L/R)
Plain wires
wires
Sqmm Ohm/km Ohm/km MΩ/Km MΩ/Km nf/Km μH/Ω
0.5 36 36.7 10 1000 < 250 < 25
0.75 24.5 24.8 10 1000 < 250 < 25
1 18.1 18.2 10 1000 < 250 < 25
1.5 12.1 12.2 10 1000 < 250 < 40
2.5 7.41 7.56 10 1000 < 250 < 60
POLYCAB INSTRU 300 SINGLE & MP
Instrumentation cable PVC/PE Insulated Overall shielded 300V
Application
POLYCAB INSTRU 300 SINGLE & MP, Stranded copper conductor, PVC/PE insulated, Overall, al-mylar
shielded, armoured/unarmoured and PVC/LSZH sheathed cable confirming to BS EN 50288-7 are designed for
transmission of analogue and digital signals in instrument and control systems. POLYCAB INSTRU 300
SINGLE &MP cables are used for diverse applications within industrial process for control, communication,
data & voice transmission in oil, gas & petrochemical industries, cement, steel, fertilizers etc.
Construction Compliance
Stranded Copper conductor as per EN 60228 Conductor resistance - EN 60228
Insulated with PVC/PE as per EN 50288-7 Insulation resistance - EN 50288-7
Collective screen Al/PET (Aluminium L/R Ratio - EN 50288-7
/Polyester tape) with drain wire of tinned Mutual capacitance - EN 50288-7
Cu/ Tinned copper braiding.
Extruded inner sheath with PVC/LSZH to Note: Outer sheath also available with PE & FRLS on
request.
EN 50290-2-22/27
Armoured with Galvanised Steel
Strip/Round as per EN 50288-7
Sheathed with Extruded PVC/LSZH to EN
50290-2-22/27
Core Identification
White & Blue for Pair
Min.
ARMOURED CABLES UNARMOURED CABLES
Area of thickness Nominal Approx. Approx. Nominal Approx.
No.of Diameter Nominal Nominal Nominal weight-
conduc of thicknes weight- weight thicknes weight
pair of diamete overall overall PE
tor insulatio s of PE -PVC s of -PVC
G.l.armou r over diamete diamete insulatio
n inner insulatio insulatio outer insulatio
r wire armour r r n
sheath n n sheath n
Sqmm mm mm mm mm mm Kg/Km Kg/Km mm mm Kg/Km Kg/Km
0.5 1 0.26 0.8 0.9 6.99 9.6 175 180 0.8 5.2 35 37
0.5 2 0.26 0.9 0.9 9.37 12.0 255 260 0.9 7.6 60 64
0.5 4 0.26 0.9 0.9 10.54 13.4 315 320 0.9 8.8 89 97
0.5 5 0.26 1.0 0.9 11.52 14.4 355 365 1.0 9.8 110 120
0.5 6 0.26 1.0 0.9 12.35 15.2 395 405 1.0 10.6 125 135
0.5 8 0.26 1.0 0.9 13.61 16.5 450 465 1.0 11.9 155 170
0.5 10 0.26 1.1 0.9 15.34 18.4 530 550 1.1 13.6 195 215
0.5 12 0.26 1.1 0.9 15.79 18.8 580 600 1.1 14.0 220 245
0.5 16 0.26 1.1 0.9 17.29 20.3 660 690 1.1 15.5 280 305
0.5 18 0.26 1.1 0.9 18.13 21.2 710 740 1.1 16.4 305 340
0.5 19 0.26 1.1 0.9 18.13 21.2 720 760 1.1 16.4 320 355
0.5 20 0.26 1.2 0.9 19.25 22.5 790 820 1.2 17.5 345 380
0.5 24 0.26 1.2 1.25 21.82 25.1 1020 1060 1.2 19.4 405 445
0.5 30 0.26 1.3 1.25 23.16 26.4 1150 1200 1.3 20.7 490 550
0.5 37 0.26 1.3 1.25 24.81 28.3 1310 1380 1.3 22.4 590 650
0.75 1 0.26 0.8 0.9 7.41 10.1 190 195 0.8 5.7 42 44
0.75 2 0.26 0.9 0.9 10.05 12.9 290 295 0.9 8.3 73 78
0.75 4 0.26 1.0 0.9 11.57 14.4 365 375 1.0 9.8 120 125
0.75 5 0.26 1.0 0.9 12.45 15.3 410 420 1.0 10.7 140 150
0.75 6 0.26 1.0 0.9 13.39 16.2 455 465 1.0 11.6 160 175
0.75 8 0.26 1.1 0.9 15.0 18.0 540 560 1.1 13.2 210 225
0.75 10 0.26 1.1 0.9 16.72 19.8 620 650 1.1 15 255 275
0.75 12 0.26 1.1 0.9 17.22 20.3 680 700 1.1 15.5 290 315
0.75 16 0.26 1.2 0.9 19.11 22.4 810 850 1.2 17.4 375 410
0.75 18 0.26 1.2 1.25 20.75 24.0 1000 1040 1.2 18.3 415 455
0.75 19 0.26 1.2 1.25 20.75 24.0 1020 1060 1.2 18.3 435 475
0.75 20 0.26 1.2 1.25 21.79 25.0 1070 1110 1.2 19.3 455 500
0.75 24 0.26 1.3 1.25 24.01 27.5 1240 1290 1.3 21.6 550 600
0.75 30 0.26 1.4 1.25 25.57 29.0 1410 1470 1.4 23.1 670 730
0.75 37 0.26 1.4 1.25 27.42 30.9 1600 1680 1.4 25 800 880
1.0 1 0.26 0.8 0.9 7.77 10.4 205 210 0.8 6.0 49 51
1.0 2 0.26 0.9 0.9 10.65 13.5 315 320 0.9 8.9 86 91
POLYCAB INSTRU 300 SINGLE & MP
Instrumentation cable PVC/PE Insulated Overall shielded 300V
Min.
ARMOURED CABLES UNARMOURED CABLES
Area of thickness Nominal Approx. Approx. Nominal Approx.
No.of Diameter Nominal Nominal Nominal weight-
conduc of thicknes weight- weight thicknes weight
pair of diamete overall overall PE
tor insulatio s of PE -PVC s of -PVC
G.l.armou r over diamete diamete insulatio
n inner insulatio insulatio outer insulatio
r wire armour r r n
sheath n n sheath n
Sqmm mm mm mm mm mm Kg/Km Kg/Km mm mm Kg/Km Kg/Km
1.0 4 0.26 1.0 0.9 12.28 15.1 405 415 1.0 10.5 145 150
1.0 5 0.26 1.0 0.9 13.24 16.1 455 465 1.0 11.5 170 180
1.0 6 0.26 1.0 0.9 14.27 17.1 510 520 1.0 12.5 195 210
1.0 8 0.26 1.1 0.9 16.02 19.1 610 630 1.1 14.3 255 275
1.0 10 0.26 1.1 0.9 17.90 20.9 710 740 1.1 16.1 310 335
1.0 12 0.26 1.2 0.9 18.65 21.7 780 810 1.2 16.9 365 395
1.0 16 0.26 1.2 1.25 21.20 24.4 1060 1100 1.2 18.7 465 510
1.0 18 0.26 1.2 1.25 22.23 25.5 1140 1190 1.2 19.8 520 560
1.0 19 0.26 1.2 1.25 22.23 25.5 1170 1210 1.2 19.8 540 590
1.0 20 0.26 1.3 1.25 23.6 26.8 1250 1290 1.3 21.1 580 630
1.0 24 0.26 1.3 1.25 25.9 29.3 1430 1490 1.3 23.4 680 740
1.0 30 0.26 1.4 1.25 27.5 30.9 1630 1700 1.4 25.0 840 910
1.0 37 0.26 1.5 1.25 29.7 33.3 1900 1990 1.5 27.2 1020 1110
1.5 1 0.35 0.9 0.9 8.97 11.6 255 260 0.9 7.2 67 71
1.5 2 0.35 1.0 0.9 12.49 15.3 390 400 1.0 10.7 120 130
1.5 4 0.35 1.1 0.9 14.47 17.5 530 540 1.1 12.7 205 220
1.5 5 0.35 1.1 0.9 15.66 18.7 590 610 1.1 13.9 245 260
1.5 6 0.35 1.1 0.9 16.93 20.0 660 680 1.1 15.2 285 305
1.5 8 0.35 1.2 0.9 19.04 22.3 810 830 1.2 17.3 370 400
1.5 10 0.35 1.3 1.25 22.28 25.5 1090 1120 1.3 19.8 460 495
1.5 12 0.35 1.3 1.25 22.96 26.4 1200 1240 1.3 20.5 530 580
1.5 16 0.35 1.4 1.25 25.45 28.9 1430 1490 1.4 23.0 690 750
1.5 18 0.35 1.4 1.25 26.70 30.20 1540 1610 1.4 24.3 770 830
1.5 19 0.35 1.4 1.25 26.70 30.20 1580 1650 1.4 24.3 800 870
1.5 20 0.35 1.5 1.25 28.30 32.0 1690 1770 1.5 25.9 850 930
1.5 24 0.35 1.5 1.25 31.2 34.8 1930 2020 1.5 28.7 1010 1100
1.5 30 0.35 1.6 1.6 33.8 37.7 2440 2550 1.6 30.7 1240 1350
1.5 37 0.35 1.7 1.6 36.5 40.6 2820 2960 1.7 33.4 1510 1640
For Cables of sizes or pairs not listed above the product data is available on request
Dimensions & Weights are representative figures and may vary
POLYCAB INSTRU 300 SINGLE & MP
Instrumentation cable PVC/PE Insulated Overall shielded 300V
Electrical Parameter
Max. DC
Max. DC
resistance of Insulation Insulation Inductance to
Area of resistance of Mutual
conductor at 20°C resistance resistance resistance
Conductor conductor at 20°C capacitance
Metal coated (PVC) (PE/XLPE) ratio(L/R)
Plain wires
wires
Sqmm Ohm/km Ohm/km MΩ/Km MΩ/Km nf/Km μH/Ω
0.5 36 36.7 10 1000 < 250 < 25
0.75 24.5 24.8 10 1000 < 250 < 25
1 18.1 18.2 10 1000 < 250 < 25
1.5 12.1 12.2 10 1000 < 250 < 40
2.5 7.41 7.56 10 1000 < 250 < 60
POLYCAB INSTRU 500 SINGLE & MP
Instrumentation cable PVC/PE Insulated Overall shielded 500V
Application
POLYCAB INSTRU 500 SINGLE & MP, Stranded copper conductor, PVC/PE insulated, Overall, al-mylar
shielded, armoured/unarmoured and PVC/LSZH sheathed cable confirming to BS EN 50288-7 are designed for
transmission of analogue and digital signals in instrument and control systems. POLYCAB INSTRU 500 SINGLE
& MP cables are used for diverse applications within industrial process for control, communication, data & voice
transmission in oil, gas & petrochemical industries, cement, steel, fertilizers etc.
Construction Compliance
Stranded Copper conductor as per EN 60228 Conductor resistance - EN 60228
Insulated with PVC/PE as per EN 50288-7 Insulation resistance - EN 50288-7
Collective screen Al/PET(Aluminium L/R Ratio - EN 50288-7
/Polyester tape) with drain wire of tinned Mutual capacitance - EN 50288-7
Cu/ Tinned copper braiding.
Extruded inner sheath with PVC/LSZH to Note: Outer sheath also available with PE & FRLS on
request.
EN 50290-2-22/27
Armoured with Galvanised Steel
Strip/Round as per EN 50288-7
Sheathed with Extruded PVC/LSZH to EN
50290-2-22/27
Core Identification
White & Blue for Pair
For Cables of sizes or pair not listed above the product data is available on request
Dimensions & Weights are representative figures and may vary
Electrical Parameter
Max. DC
Max. DC
resistance of Insulation Insulation Inductance to
Area of resistance of Mutual
conductor at 20°C resistance resistance resistance
Conductor conductor at 20°C capacitance
Metal coated (PVC) (PE/XLPE) ratio(L/R)
Plain wires
wires
Sqmm Ohm/km Ohm/km MΩ/Km MΩ/Km nf/Km μH/Ω
0.5 36 36.7 10 1000 < 250 < 25
0.75 24.5 24.8 10 1000 < 250 < 25
1 18.1 18.2 10 1000 < 250 < 25
1.5 12.1 12.2 10 1000 < 250 < 40
2.5 7.41 7.56 10 1000 < 250 < 60
POLYCAB INSTRU 300 MT
Application
POLYCAB INSTRU 300 MT, Stranded copper conductor, PVC/PE insulated, Individual & overall al-mylar
shielded, armoured/unarmoured and PVC/LSZH sheathed cable confirming to BS EN 50288-7 are designed
for transmission of analogue and digital signals in instrument and control systems. POLYCAB INSTRU 300
MT cables are used for diverse applications within industrial process for control, communication, data & voice
transmission in oil, gas & petrochemical industries, cement, steel, fertilizers etc.
Construction Compliance
Stranded Copper conductor as per EN 60228 Conductor resistance - EN 60228
Insulated with PVC/PE as per EN 50288-7 Insulation resistance - EN 50288-7
Individual & Collective screen L/R Ratio - EN 50288-7
Al/PET(Aluminium/Polyester tape) with Mutual capacitance - EN 50288-7
drain wire of tinned Cu/ Tinned copper
braiding. Note: Outer sheath also available with PE, FRLS & LSZH
Extruded inner sheath with PVC/LSZH to on request.
EN 50290-2-22/27
Armoured with Galvanised Steel
Strip/Round as per EN 50288-7
Sheathed with Extruded PVC/LSZH to EN
50290-2-22/27
Core Identification
White, Blue & Brown for Triad
0.5 5 0.16 1.0 0.9 1.4 16.9 495 510 1.0 12.3 190 205
0.5 6 0.16 1.1 0.9 1.5 18.4 570 580 1.1 13.6 230 245
0.5 8 0.26 1.1 0.9 1.5 20.1 670 690 1.1 15.3 290 310
0.5 10 0.26 1.2 0.9 1.6 22.5 800 830 1.2 17.5 360 390
0.5 12 0.26 1.2 1.25 1.6 23.8 1000 1030 1.2 18.1 415 450
0.5 14 0.26 1.3 1.25 1.6 24.9 1090 1130 1.3 19.2 480 520
0.5 16 0.26 1.3 1.25 1.7 26.2 1190 1240 1.3 20.3 540 580
0.5 19 0.26 1.3 1.25 1.7 27.3 1320 1370 1.3 21.4 620 680
0.5 20 0.26 1.4 1.25 1.7 28.8 1400 1460 1.4 22.9 670 720
0.5 24 0.26 1.4 1.25 1.8 31.4 1610 1680 1.4 25.3 790 850
0.5 30 0.26 1.5 1.25 1.8 33.2 1830 1920 1.5 27.1 960 1050
0.5 37 0.26 1.6 1.25 1.9 35.8 2130 2130 1.6 29.5 1170 1280
0.75 2 0.26 1.0 0.9 1.4 15.1 385 390 1.0 10.5 110 US
0.75 4 0.26 1.0 0.9 1.5 17.1 510 520 1.0 12.3 195 210
0.75 5 0.26 1.1 0.9 1.5 18.4 580 600 1.1 13.6 245 260
0.75 6 0.26 1.1 0.9 1.5 19.7 650 670 1.1 14.9 18S 305
0.75 8 0.26 1.2 0.9 1.6 22.0 800 820 1.2 17.0 370 39S
0.75 10 0.26 1.3 1.25 1.6 25.1 1080 1120 1.3 19.4 460 490
0.75 12 0.26 1.3 1.25 1.7 26.0 1180 1220 1.3 20.1 SJ0 570
0.75 14 0.26 1.3 1.25 1.7 27.0 1290 1330 1.3 21.1 610 6'i0
0.75 16 0.26 1.4 1.25 1.7 28.4 1410 1460 1.4 22.5 690 740
0.75 19 0.26 1.4 1.25 1.7 29.7 1560 1620 1.4 23.8 800 860
0.75 20 0.26 1.4 1.25 1.8 31.3 1650 1720 1.4 2S.2 840 910
0.75 24 0.26 1.5 1.25 1.8 34.2 1920 2000 1.S 28.1 1010 1090
0.75 30 0.26 1.6 1.6 1.9 37.0 2420 2520 1.6 30.0 1240 1J30
0.75 37 0.26 1.7 1.6 2.0 39.9 2800 2920 1.7 32.7 1510 1630
1.0 2 0.26 1.0 0.9 1.4 15.8 425 430 1.0 11.2 140 150
1.0 4 0.26 1.1 0.9 1.5 18.1 580 590 1.1 13.3 240 255
1.0 5 0.26 1.1 0.9 1.5 19.4 650 670 1.1 14.6 290 305
POLYCAB INSTRU 300 MT
1.0 8 0.26 1.2 1.25 1.6 23.9 1020 1050 1.2 18.2 440 470
1.0 10 0.26 1.3 1.25 1.7 26.8 1230 1260 1.3 20.9 550 590
1.0 12 0.26 1.3 1.25 1.7 27.5 1330 1370 1.3 21.6 640 680
1.0 14 0.26 1.4 1.25 1.7 28.8 1470 1520 1.4 22.9 740 790
1.0 16 0.26 1.4 1.25 1.7 30.1 1600 1660 1.4 24.2 830 890
1.0 19 0.26 1.5 1.25 1.8 31.9 1810 1880 1.5 25.8 980 1050
1.0 20 0.26 1.5 1.25 1.8 33.4 1910 1980 1.5 27.3 1030 1100
1.0 24 0.26 1.6 1.6 1.9 37.5 2440 2520 1.6 30.5 1230 1320
1.0 30 0.26 1.7 1.6 2.0 39.7 2800 2910 1.7 32.5 1510 1620
1.0 37 0.26 1.7 1.6 2.0 42.4 3210 3340 1.7 35.2 1830 1960
1.5 2 0.35 1.1 0.9 1.5 18.3 530 540 1.1 13.5 195 205
1.5 4 0.35 1.2 0.9 1.5 20.8 730 7'i0 1.2 16.0 330 355
1.5 5 0.35 1.2 1.25 1.6 23.2 970 1000 1.2 17.5 400 430
1.5 6 0.35 1.3 1.25 1.6 25.1 1090 1120 1.3 19.4 480 510
1.5 8 0.35 1.4 1.25 1.7 28.0 1330 1380 1.4 22.1 620 670
1.5 10 0.35 1.5 1.25 1.8 31.4 1600 1650 1.5 25.3 780 830
1.5 12 0.35 1.5 1.25 1.8 32.3 1750 1820 1.5 26.2 900 970
1.5 14 0.35 1.5 1.25 1.8 33.7 1920 2000 1.5 27.6 1030 1110
1.5 16 0.35 1.6 1.6 1.9 36.4 2330 2420 1.6 29.4 1170 1260
1.5 19 0.35 1.6 1.6 1.9 38.0 1S90 1690 1.6 31.0 1360 1470
1.5 20 0.35 1.7 1.6 2.0 40.3 2770 2880 1.7 33.1 1450 1560
1.5 24 0.35 1.8 1.6 2.1 44.4 3210 3340 1.8 37.0 1740 1870
1.5 30 0.35 1.9 1.6 2.1 46.8 3700 3860 1.9 39.4 2130 2300
1.5 37 0.35 2.0 2.0 2.1 51.3 4650 4850 2.0 41.9 2590 2800
For Cables of sizes or triad not listed above the product data is available on request
Dimensions & Weights are representative figures and may vary
POLYCAB INSTRU 300 MT
Electrical Parameter
Max. DC
Max. DC
resistance of Insulation Insulation Inductance to
Area of resistance of Mutual
conductor at 20°C resistance resistance resistance
Conductor conductor at 20°C capacitance
Metal coated (PVC) (PE/XLPE) ratio(L/R)
Plain wires
wires
Sqmm Ohm/km Ohm/km MΩ/Km MΩ/Km nf/Km μH/Ω
0.5 36 36.7 10 1000 < 250 < 25
0.75 24.5 24.8 10 1000 < 250 < 25
1 18.1 18.2 10 1000 < 250 < 25
1.5 12.1 12.2 10 1000 < 250 < 40
2.5 7.41 7.56 10 1000 < 250 < 60
POLYCAB INSTRU 500 MT
Instrumentation cable PVC/PE Insulated Individual & Overall shielded 500V
Application
POLYCAB INSTRU 500 MT, Stranded copper conductor, PVC/PE insulated, Individual & overall al-mylar
shielded, armoured/unarmoured and PVC/LSZH sheathed cable confirming to BS EN 50288-7 are designed
for transmission of analogue and digital signals in instrument and control systems. POLYCAB INSTRU 500
MT cables are used for diverse applications within industrial process for control, communication, data & voice
transmission in oil, gas & petrochemical industries, cement, steel, fertilizers etc.
Construction Compliance
Stranded Copper conductor as per EN 60228 Conductor resistance - EN 60228
Insulated with PVC/PE as per EN 50288-7 Insulation resistance - EN 50288-7
Individual & Collective screen L/R Ratio - EN 50288-7
Al/PET(Aluminium/Polyester tape) with Mutual capacitance - EN 50288-7
drain wire of tinned Cu/ Tinned copper
Note: Outer sheath also available with PE & FRLS on
braiding.
request.
Extruded inner sheath with PVC/LSZH to
EN 50290-2-22/27
Armoured with Galvanised Steel
Strip/Round as per EN 50288-7
Sheathed with Extruded PVC/LSZH to EN
50290-2-22/27
Core Identification
White, Blue & Brown for Triad
Electrical Parameter
Max. DC
Max. DC
resistance of Insulation Insulation Inductance to
Area of resistance of Mutual
conductor at 20°C resistance resistance resistance
Conductor conductor at 20°C capacitance
Metal coated (PVC) (PE/XLPE) ratio(L/R)
Plain wires
wires
Sqmm Ohm/km Ohm/km MΩ/Km MΩ/Km nf/Km μH/Ω
0.5 36 36.7 10 1000 < 250 < 25
0.75 24.5 24.8 10 1000 < 250 < 25
1 18.1 18.2 10 1000 < 250 < 25
1.5 12.1 12.2 10 1000 < 250 < 40
2.5 7.41 7.56 10 1000 < 250 < 60
POLYCAB INSTRU 300 SINGLE & MT
Instrumentation cable PVC/PE Insulated Overall shielded 300V
Application
POLYCAB INSTRU 300 SINGLE & MT, Stranded copper conductor, PVC/PE insulated, Overall al-mylar
shielded, armoured/unarmoured and PVC/LSZH sheathed cable confirming to BS EN 50288-7 are designed for
transmission of analogue and digital signals in instrument and control systems. POLYCAB INSTRU 300
SINGLE & MT cables are used for diverse applications within industrial process for control, communication,
data & voice transmission in oil, gas & petrochemical industries, cement, steel, fertilizers etc.
Construction Compliance
Stranded Copper conductor as per EN 60228 Conductor resistance - EN 60228
Insulated with PVC/PE as per EN 50288-7 Insulation resistance - EN 50288-7
Collective screen Al/PET (Aluminium L/R Ratio - EN 50288-7
/Polyester tape) with drain wire of tinned Cu/ Mutual capacitance - EN 50288-7
Tinned copper braiding.
Extruded inner sheath with PVC/LSZH to EN Note: Outer sheath also available with PE & FRLS on
50290-2-22/27 request.
Armoured with Galvanised Steel Strip/Round
as per EN 50288-7
Sheathed with Extruded PVC/LSZH to EN
50290-2-22/27
Core Identification
White, Blue & Brown for Triad
0.5 2 0.26 0.9 0.9 1.3 12.8 285 290 0.9 8.4 76 81
0.5 4 0.26 1.0 0.9 1.4 14.5 375 385 1.0 9.9 120 135
0.5 5 0.26 1.0 0.9 1.4 15.4 415 430 1.0 10.8 145 160
0.5 6 0.26 1.0 0.9 1.4 16.4 460 475 1.0 11.8 170 185
0.5 8 0.26 1.1 0.9 1.5 18.2 560 580 1.1 13.4 220 140
0.5 10 0.26 1.1 0.9 1.5 19.9 640 670 1.1 15.1 265 190
0.5 12 0.26 1.1 0.9 1.5 20.4 690 720 1.1 15.6 300 335
0.5 14 0.26 1.1 0.9 1.5 21.2 750 790 1.1 16.4 345 380
0.5 16 0.26 1.2 0.9 1.6 22.6 840 880 1.2 17.6 390 435
0.5 19 0.26 1.2 0.9 1.6 23.5 920 970 1.2 18.5 450 500
0.5 20 0.26 1.2 1.25 1.6 25.3 1100 1160 1.2 19.6 475 530
0.5 24 0.26 1.3 1.25 1.7 27.8 1280 1340 1.3 21.9 570 640
0.5 30 0.26 1.3 1.25 1.7 29.1 1430 1510 1.3 23.2 690 770
0.5 37 0.26 1.4 1.25 1.7 31.2 1640 1750 1.4 25.3 840 940
0.75 1 0.26 0.8 0.9 1.3 10.4 210 210 0.8 6.0 52 55
0.75 2 0.26 0.9 0.9 1.4 13.8 330 340 0.9 9.2 95 100
0.75 4 0.26 1.0 0.9 1.4 15.5 430 440 1.0 10.9 160 170
0.75 5 0.26 1.0 0.9 1.4 16.5 480 500 1.0 11.9 190 205
0.75 6 0.26 1.1 0.9 1.5 18.0 560 580 1.1 13.2 225 245
0.75 8 0.26 1.1 0.9 1.5 19.6 660 680 1.1 14.8 285 310
0.75 10 0.26 1.2 0.9 1.5 21.7 770 810 1.2 16.9 355 390
0.75 12 0.26 1.2 0.9 1.6 22.5 850 890 1.2 17.5 410 450
0.75 14 0.26 1.2 1.25 1.6 24.1 1050 1100 1.2 18.4 470 510
0.75 16 0.26 1.2 1.25 1.6 25.1 1150 1200 1.2 19.4 530 580
0.75 19 0.26 1.3 1.25 1.6 26.4 1270 1330 1.3 20.7 620 680
0.75 20 0.26 1.3 1.25 1.7 27.8 1360 1420 1.3 21.9 650 720
0.75 24 0.26 1.4 1.25 1.7 30.4 1560 1640 1.4 24.5 780 860
0.75 30 0.26 1.4 1.25 1.8 32.0 1780 1880 1.4 25.9 950 1040
0.75 37 0.26 1.5 1.25 1.8 34.3 2060 2180 1.5 28.2 1150 1270
POLYCAB INSTRU 300 SINGLE & MT
Instrumentation cable PVC/PE Insulated Overall shielded 300V
1.0 2 0.26 1.0 0.9 1.4 14.6 370 380 1.0 10.0 120 125
1.0 4 0.26 1.0 0.9 1.4 16.3 485 500 1.0 11.7 195 205
1.0 5 0.26 1.0 0.9 1.5 17.6 560 570 1.0 12.8 230 250
1.0 6 0.26 1.1 0.9 1.5 18.9 630 650 1.1 14.1 280 300
1.0 8 0.26 1.1 0.9 1.5 20.7 750 780 1.1 15.9 355 385
1.0 10 0.26 1.2 0.9 1.6 23.2 900 940 1.2 18.2 440 480
1.0 12 0.26 1.2 1.25 1.6 24.6 1110 1150 1.2 18.9 510 560
1.0 14 0.26 1.3 1.25 1.6 25.7 1230 1280 1.3 20.0 590 640
1.0 16 0.26 1.3 1.25 1.7 27.1 1350 1410 1.3 21.2 670 730
1.0 19 0.26 1.3 1.25 1.7 28.2 1500 1560 1.3 22.3 780 840
1.0 20 0.26 1.4 1.25 1.7 29.7 1590 1660 1.4 23.8 830 900
1.0 24 0.26 1.4 1.25 1.8 32.5 1830 1920 1.4 26.4 980 1070
1.0 30 0.26 1.5 1.25 1.8 34.3 2110 2220 1.5 28.2 1200 1310
1.0 37 0.26 1.6 1.25 1.9 37.0 2470 2600 1.6 30.7 1470 1600
1.5 1 0.35 0.9 0.9 1.3 12.0 280 285 0.9 7.6 86 91
1.5 2 0.35 1.0 0.9 1.4 16.5 455 465 1.0 11.9 160 170
1.5 4 0.35 1.1 0.9 1.5 18.9 630 650 1.1 14.1 280 300
1.5 5 0.35 1.1 0.9 1.5 20.3 720 750 1.1 15.5 335 365
1.5 6 0.35 1.1 0.9 1.6 22.1 840 870 1.1 17.1 400 435
1.5 8 0.35 1.3 1.25 1.6 25.2 1150 1190 1.3 19.5 520 570
1.5 10 0.35 1.3 1.25 1.7 28.1 1350 1410 1.3 22.2 640 700
1.5 12 0.35 1.4 1.25 1.7 29.1 1500 1560 1.4 23.2 760 820
1.5 14 0.35 1.4 1.25 1.7 30.3 1640 1720 1.4 24.4 870 940
1.5 16 0.35 1.5 1.25 1.8 32.1 1830 1910 1.5 26.0 990 1080
1.5 19 0.35 1.5 1.25 1.8 33.5 2030 2140 1.5 27.4 1150 1250
1.5 20 0.35 1.5 1.25 1.8 35.1 2140 2250 1.5 29.0 1210 1320
1.5 24 0.35 1.7 1.6 2.0 39.8 2760 2890 1.7 32.6 1470 1600
1.5 30 0.35 1.7 1.6 2.0 41.8 3140 3310 1.7 34.6 1780 1950
1.5 37 0.35 1.8 1.6 2.1 45.1 3670 3880 1.8 37.7 2170 2380
For Cables of sizes or triad not listed above the product data is available on request
Dimensions & Weights are representative figures and may vary
POLYCAB INSTRU 300 SINGLE & MT
Instrumentation cable PVC/PE Insulated Overall shielded 300V
Electrical Parameter
Max. DC
Max. DC
resistance of Insulation Insulation Inductance to
Area of resistance of Mutual
conductor at 20°C resistance resistance resistance
Conductor conductor at 20°C capacitance
Metal coated (PVC) (PE/XLPE) ratio(L/R)
Plain wires
wires
Sqmm Ohm/km Ohm/km MΩ/Km MΩ/Km nf/Km μH/Ω
0.5 36 36.7 10 1000 < 250 < 25
0.75 24.5 24.8 10 1000 < 250 < 25
1 18.1 18.2 10 1000 < 250 < 25
1.5 12.1 12.2 10 1000 < 250 < 40
2.5 7.41 7.56 10 1000 < 250 < 60
POLYCAB INSTRU 500 SINGLE & MT
Instrumentation cable PVC/PE Insulated Overall shielded 500V
Application
POLYCAB INSTRU 500 SINGLE & MT, Stranded copper conductor, PVC/PE insulated, Overall al-mylar
shielded, armoured/unarmoured and PVC/LSZH sheathed cable confirming to BS EN 50288-7 are designed for
transmission of analogue and digital signals in instrument and control systems. POLYCAB INSTRU 500 SINGLE
& MT cables are used for diverse applications within industrial process for control, communication, data & voice
transmission in oil, gas & petrochemical industries, cement, steel, fertilizers etc.
Construction Compliance
Stranded Copper conductor as per EN 60228 Conductor resistance - EN 60228
Insulated with PVC/PE as per EN 50288-7 Insulation resistance - EN 50288-7
Collective screen Al/PET (Aluminium L/R Ratio - EN 50288-7
/Polyester tape) with drain wire of tinned Cu/ Mutual capacitance - EN 50288-7
Tinned copper braiding.
Extruded inner sheath with PVC/LSZH to EN Note: Outer sheath also available with PE & FRLS on
50290-2-22/27 request.
Armoured with Galvanised Steel Strip/Round
as per EN 50288-7
Sheathed with Extruded PVC/LSZH to EN
50290-2-22/27
Core Identification
White, Blue & Brown for Triad
Electrical Parameter
Max. DC
Max. DC
resistance of Insulation Insulation Inductance to
Area of resistance of Mutual
conductor at 20°C resistance resistance resistance
Conductor conductor at 20°C capacitance
Metal coated (PVC) (PE/XLPE) ratio(L/R)
Plain wires
wires
Sqmm Ohm/km Ohm/km MΩ/Km MΩ/Km nf/Km μH/Ω
0.5 36 36.7 10 1000 < 250 < 25
0.75 24.5 24.8 10 1000 < 250 < 25
1 18.1 18.2 10 1000 < 250 < 25
1.5 12.1 12.2 10 1000 < 250 < 40
2.5 7.41 7.56 10 1000 < 250 < 60