SIP4 Timer Gate - CFC
SIP4 Timer Gate - CFC
Customer NTPC
Reported query If we want the output to remain high for at least 100ms and reset only when input get reset,
then please provide the logic for same.
IED Details 7UM6
2. Timer
3. Short Timer
KAMRAN ANSARI
Siemens Customer Support
Technical/ Warranty Hotline support (24x7): [email protected] |Toll free( India): 1800 266 7480 | Page 1
Different types of TIMER GATE in SIP 4 16th March 2023
Timer QT2:
• Signal BI used as a Input at S and signal BO interconnected to QT2.
• T2 time- 10000ms or 10s.
CFC Logic:
Spontenous Events:
Timer QT1:
CFC Logic:
KAMRAN ANSARI
Siemens Customer Support
Technical/ Warranty Hotline support (24x7): [email protected] |Toll free( India): 1800 266 7480 | Page 2
Different types of TIMER GATE in SIP 4 16th March 2023
Spontenous Events:
Timer Q:
Condition 1: Gate Input Reset before Time in T1.
CFC Logic:
Spontenous Events:
Spontenous Events:
• Output gets high after time T1 and reset when input get low.
KAMRAN ANSARI
Siemens Customer Support
Technical/ Warranty Hotline support (24x7): [email protected] |Toll free( India): 1800 266 7480 | Page 3
Different types of TIMER GATE in SIP 4 16th March 2023
Short Timer Q:
CFC Logic:
Spontenous Events:
• In short Timer Gate Output Q needs reset signal to reset the Output.
• BO gets high after the T1 time and remain high as there is no reset signal.
KAMRAN ANSARI
Siemens Customer Support
Technical/ Warranty Hotline support (24x7): [email protected] |Toll free( India): 1800 266 7480 | Page 4
Different types of TIMER GATE in SIP 4 16th March 2023
NTPC Requirement:
Condition 1: As the Input gets high gate output should remain high for the given time in T1, even if input gets low before T1.
CFC Logic:
Spontenous Events:
Condition 2: Output should reset only after the input get low but not before time mentioned in T1.
KAMRAN ANSARI
Siemens Customer Support
Technical/ Warranty Hotline support (24x7): [email protected] |Toll free( India): 1800 266 7480 | Page 5