Eclipse Pra6 Rotary Actuator Manual
Eclipse Pra6 Rotary Actuator Manual
Eclipse Pra6 Rotary Actuator Manual
7/24/06
Eclipse Programmable
Rotary Actuator
Series PRA6
Version 1
Copyright Copyright 2006 by Eclipse, Inc. All rights reserved
worldwide. This publication is protected by federal
regulation and shall not be copied, distributed,
transmitted, transcribed or translated into any
human or computer language, in any form or
by any means, to any third parties, without the
express written consent of Eclipse, Inc.
Audience This manual has been written for the people who
will install the product and the technicians who
work on it. They are expected to have previous
experience with this kind of equipment.
Important notices • Read this manual carefully. Make sure that you
understand the structure and contents of this
manual.
• Obey all the safety instructions.
• Do not deviate from any instructions or applica-
tion limits in this manual without written consent
from Eclipse, Inc.
• If you do not understand any part of the infor-
mation in this manual, do not continue. Con-
tact your Eclipse sales office or Eclipse, Inc.
1 Introduction ................................................. 7
Product Description............................................. 7
2 Installation .................................................... 8
Introduction........................................................... 8
Handling and Storage........................................... 8
Approval of Components.................................... 9
Electrical wiring................................................. 9
Where to get the standards........................... 9
Checklist Before Installation............................... 9
A Note on Safety.................................................. 10
Actuator Mounting............................................... 11
Mount Actuator to Butterfly Valve ................... 12
Actuator Wiring.................................................... 15
Power supply...................................................... 16
Auxiliary contacts............................................. 16
Low fire wiring.................................................. 16
High fire wiring.................................................. 17
Control signal wiring........................................ 17
Disable settings wiring..................................... 17
4 Specifications .............................................. 30
Dimensions............................................................. 31
Keypad orientations.............................................. 32
Appendix ........................................................ 35
Table 1: Actuator Parameter Record ............. 35
Table 2: Model Number Configuration ......... 35
Note:
These instructions apply to heating applications
where a maximum output from the tempera-
ture controler drives a butterfly valve up to its
maximum flow position.
Caution:
Installation and maintenance must conform
with the National Electrical Code and all other
national and local codes and authorities having
jurisdiction.The actuator must be installed by a
qualified, licensed technician.
Storage
1. Make sure that the actuator is clean and in
good condition.
2. After you have made sure that everything is
present and in good condition, keep the actua-
tor in the original package as long as possible.
3. Store the actuator in a cool, clean, dry room.
Environment
Make sure that the local environment matches
the original operating specifications. Check the
following items:
• voltage, frequency and stability of the
electrical power
• humidity, altitude and temperature of air
• presence of damaging corrosive gases in the
air.
Ratio Burner
Ratio Regulator
Fuel Flow
Control Valve
Burner
Blower
Caution:
Use of this product in the European community
shall only be deployed in a manner that meets
the applicable EC directives and laws.
Shaft Detail
3mm
(0.12”) Dia.
Caution:
Prevent water from condensation flowing into
the actuator housing through the wiring con-
duits. Keep conduits oriented such that gravity
will cause water to flow away from the actua-
tor or provide a watertight seal in the conduit
near the actuator.
Warning
Local regulations may require guards
and/or warnings when connecting the
actuator to a component with linkage
that could cause finger pinching. The
actuator stall torque is at least 3.9 n-m
(35 lb-in).
Warning:
Risk of electric shock. Removal of the
cover plate allows access to conductors
carrying hazardous voltages.
Remove these
two screws to
expose terminal
connections at right
Note:
These digital signals override the 4-20mA and
0-10Vdc analog positioning signals.
G 1 2 3 4 5 6 1 2 3 4 5 6 G
P2
P1
Earth
Neutral
Line
HF Com
HF Switch
LF Com
LF Switch
Com (-)
4-20mA
0-10V
High Fire
Low Fire
LC
Shield
+ +
Input
120 or 230 VAC Contact Outputs – – HF LF
Power Supply
Note:
1. Separate low voltage signal wiring from high voltage signal wiring.
2. Control circuit wires must:
a) meet 90°C (194°F) specification minimum;
b) recommended range from 22 to 16 AWG (.5 to 1.5mm2), and
c) be in accordance with all applicable codes.
3. Insert only one wire per terminal.
4. Provide power supply circuit protection.
5. P2-G and P1-G are internally connected
Note:
The following diagram is an example of how to use the actua-
tor’s various inputs and outputs. Some devices shown may be
omitted or changed, depending on your application.
L1 GND L2
Power
Off On 5A Fuse
Temperature
Controller
L1
L2
GND
+
T/C Sensor
–
Actuator
+ P1-2
4-20mA Start 1 2
– P1-1
P1-4
High Fire 1
P1-5
Low Fire 1
P2-G
P2-1
P2-2
P2-3 shaft at
high position
P2-4
Coil 1
P2-5 shaft at
low position
P2-6
1 These components relate to burner sequence (not shown); Coil 1
2 See “Control Signal Loss (LO)” on page 22.
Low fire stop This parameter sets the minimum shaft travel position:
(LF) 1. Press the ENTER key; the message “SC” will ap-
pear on the display.
2. Press either the UP or DOWN key until the
1 2 number “15” appears on the display.
3. Press the RESET key; the message “PG” will ap-
pear on the display.
4. Press the DOWN key; the message “LF” will ap-
3 4 pear on the display.
5. Press either the UP or DOWN key until your
desired number (the desired degree of shaft rota-
tion) appears on the display.
5 6
6. Press the RESET key to complete the sequence.
Control signal This parameter sets the position when the analog con-
loss (LO) trol signal is zero. It can be used to set a control valve
at some intermediate position above LF for burner
start-up (see Figure 4 on page 19):
Note:
1 2 Set LO to the same value as LF if you want the
actuator to drive to the Low Fire Stop position (LF)
when the control signal is zero.
Low fire contact This description of the contact state is for the nor-
sense (LS) mally open mode. As the shaft travels from high
to low, the LS parameter sets where the low fire
contact closes. For most applications this value
should be kept at least five degrees above LF or
1 2 LO, whichever is higher.
1. Press the ENTER key; the message “SC” will
appear on the display.
3 4 2. Press either the UP or DOWN key until the
number “16” appears on the display.
3. Press the RESET key; the message “PG” will ap-
pear on the display. (Continued on page 25)
5 6
Eclipse Rotary Actuator Instruction Manual 904- 7/24/06 23
Figure 5 Auxiliary Contact Positions in Relation to Shaft Rotation
Note:
In the following examples:
1) 0°and 90° represent the actuator shaft’s range of travel rather than the
shaft’s alignment (therefore, 0° does not equal vertical and 90° does not
equal horizontal).
2) The operating mode is normally open, but the values LL, LS, HS and HH
have been changed from the default setpoints shown on page 29. The set
values are: LL=10, LS=20, HS=75 and HH=85
Low Auxiliary Contact (P2-5 & 6)
Angular Diagram
o For the settings of note 2,
o LL=10
0 o the low contact is closed
LS=20 when the shaft is between
10 and 20 degrees.
Key
Contact Closed
o
90 Contact Open
Ac
tuat Shaft
or
OPEN
LL LS
High Auxiliary Contact (P2-3 & 4)
Angular Diagram
0
o For the settings of note 2,
the high contact is closed
when the shaft is between
o 75 and 85 degrees.
HS=75
o
HH=85 Key
o
90 Contact Closed
Ac Contact Open
tuat Shaft
or
OPEN
HS HH
Eclipse Rotary Actuator Instruction Manual 904- 7/24/06
24
4. Press the DOWN key; the message “LS” will
appear on the display.
5. Press either the UP or DOWN key until your
desired number (the desired degree of shaft
rotation) appears on the display; this number
must be of greater value than the desired low
fire contact release (LL) number.
6. Press the RESET key to complete the sequence.
Note:
Please refer to Figure 5 on page 24 for an illustra-
tion of the next two parameters.
High fire contact This description of the contact state is for the
sense (HS) normally open mode. As the shaft travels from
low to high, the HS parameter sets where the
high fire contact closes. For most applications this
value should be kept at least 5 degrees below HF.
1 2 1. Press the ENTER key; the message “SC” will
appear on the display.
2. Press either the UP or DOWN key until the
number “16” appears on the display.
3 4
3. Press the RESET key; the message “PG” will ap-
pear on the display.
4. Press the UP key; the message “HS” will appear
5 6 on the display.
5. Press either the UP or DOWN key until your
desired number (the desired degree of shaft
rotation) appears on the display; this number
must be of lesser value than the desired high
fire contact release (HH) number.
6. Press the RESET key to complete the sequence.
Manual position This parameter puts the actuator in the manual positioning
select mode. It allows the operator to manually position the shaft
anywhere between low and high fire stop settings with the
UP and DOWN keys:
1. Press the ENTER key; the message “SC” will appear
1 2 on the display.
2. Press either the UP or DOWN key until the num-
ber “05” appears on the display.
3 3. Press the RESET key to complete the sequence.
3
Auxiliary contact This parameter allows the operator to return the
select– auxiliary contact’s default setting to normally open
normally open (NO) if ever changed:
1. Press the ENTER key; the message “SC” will
appear on the display.
1 2 2. Press either the UP or DOWN key until the
number “08” appears on the display.
3. Press the RESET key to complete the sequence.
3
Note:
The next two parameters describe shaft rotation
when facing the keypad.
Warning:
Disconnect shaft coupling before
changing. The shaft will reposition as
such that 0 becomes 90 degrees.
3
This parameter allows the shaft to travel counter-
Counterclockwise
clockwise when the input signal increases:
rotation select
1. Press the ENTER key; the message “SC” will
appear on the display.
2. Press either the UP or DOWN key until the
1 2
number “11” appears on the display.
3. Press the RESET key to complete the sequence.
Examine setpoints Pushing the reset key twice allows the various
setpoints to be examined. Once activated, the
display will indicate a two-letter parameter code
followed by its value in the following sequence:
1 2
a. software version;
b. low fire stop position (LF);
c. high fire stop position (HF);
3
d. contact signal loss position (LO);
e. low fire contact release position (LL);
f. low fire contact sense position (LS);
g. high fire contact sense position (HS);
h. high fire contact release position (HH);
i. manual (C5) or automatic (C6):
j. aux. contact mode N.O. (C8) or N.C. (C7);
k. rotation CW (CO) or CCW (C1)
The display will show each function's setpoint for
two seconds before scrolling to the next one.
206mm
(8.11") 164mm
(6.46”)
35mm 6.35mm
(1.38”) (0.25”)
Diameter Shaft
146mm
(5.75”) M6
Threaded
Mounting Hole
12mm Deep
25mm
(0.98”)
Back View
Eclipse Rotary Actuator Instruction Manual 904- 7/24/06
31
Dimensions (continued)
Holes (2)
19mm (0.75") 36.53mm
each (1.44”)
27mm
(1.06") 6.35mm
(0.25”)
10mm
(0.39”) 11mm
(0.43")
26.5mm 3mm
(1.045”) (0.12”) Dia.
Keypad Orientation
Upright (Standard) Inverted
Note:
The monthly and yearly lists are for average
intervals. If your environment is dirty, then the
intervals may be shorter.
Actuator will not move • Stalled motor; “oo” message Correct the mechanical
with signal. on display. problem; see “Stalled
Motor” on page 29.
Actuator will not move • Manual mode not selected Select manual mode;
with keypad. see “Manual Position
Select” on page 26.
PRA6
o
A- 120 VAC A - 90 stroke
o
B- 230 VAC D - 75 stroke
o
1- Standard .... 0 A- PG11 liquidtite flexible cord connector
o
2- Inverted ...... 180 B- 3/8" straight liquidtite conduit connector
o
3- RH .............. 90 C- 1/2" Female NPT adapter
o
4- LH .............. 270