Fluke DSX CableAnalyzer - 9830384-B-En
Fluke DSX CableAnalyzer - 9830384-B-En
Fluke DSX CableAnalyzer - 9830384-B-En
Users Manual
Title Page
Introduction .....................................................................................................1
Kit Contents ......................................................................................................1
DSX-PC5ES ................................................................................................... 1
DSX-PC6S ..................................................................................................... 1
DSX-PC6AS .................................................................................................. 1
Contacting Fluke Networks .............................................................................2
Additional Resources for Cable Testing Information ....................................2
WSafety Information ..................................................................................2
DSX Software Requirements ...........................................................................3
Characterize the Performance of the Adapters .............................................3
How to Do Tests on Patch Cords .....................................................................3
How to Set Up the Tester ........................................................................... 3
How to Do the Patch Cord Test ................................................................. 5
Patch Cord Test Results ....................................................................................6
Why Patch Cords Fail .................................................................................. 6
Wire Map Failures .................................................................................7
Return Loss Failures ...............................................................................7
NEXT Failures .........................................................................................7
Is the Cable Bad or is the Plug Bad? .......................................................... 8
Mechanical Stress Tests for Patch Cords .........................................................10
When to Replace the Jacks in the Adapters ...................................................10
How to Monitor the Number of Insertions for a Jack .............................. 11
How to Order Replacement Jacks .............................................................. 11
i
DSX-PCxx Patch Cord Adapters
Users Manual
ii
Introduction
The DSX-PCxx Patch Cord Adapters let you use a DSX CableAnalyzer™ tester to
make sure that patch cords comply with ANSI/TIA and ISO/IEC standards. The
adapters have RJ45 jacks that Fluke Networks selects specifically for tests on Cat
5e and 6 patch cords as specified in TIA-568-C.2 and IEC 61935-2, and Cat 6A patch
cords as specified in IEC 61935-2.
Note
Standards organizations can add amendments to standards.
Contact the applicable standards organization for details. For
general information on standards and for DSX software
updates that include updated standards, contact Fluke
Networks.
Kit Contents
A DSX-PCxxS Patch Cord Adapter Set comes with these items:
DSX-PC5ES
Two DSX-PC5E Cat 5e Patch Cord Adapters
DSX-PCxxS Product Manuals CD-ROM
DSX-PC6S
Two DSX-PC6 Cat 6 Patch Cord Adapters
DSX-PCxxS Product Manuals CD-ROM
DSX-PC6AS
Two DSX-PC6A Cat 6A Patch Cord Adapters
DSX-PCxxS Product Manuals CD-ROM
If something is missing or damaged, contact the place of purchase immediately.
1
DSX-PCxx Patch Cord Adapters
Users Manual
www.flukenetworks.com/support
[email protected]
1-800-283-5853, +1-425-446-5500
Fluke Networks
6920 Seaway Boulevard, MS 143F
Everett WA 98203 USA
Fluke Networks operates in more than 50 countries worldwide. For more contact
information, go to our website.
WSafety Information
WWarningX
To prevent possible fire, electric shock, personal injury,
damage to equipment, or inaccurate test results, read the
safety information in the Versiv Series manuals before you
use the tester.
2
DSX Software Requirements
The latest DSX software version is available at no charge on the Fluke Networks
web site. Download the update file from the website, then use LinkWare™
software to install new software into the DSX testers. See the Versiv Series
manuals or the online help in LinkWare for instructions.
-continued-
3
DSX-PCxx Patch Cord Adapters
Users Manual
4 On the TEST SETUP screen, tap Cable Type, then tap the correct cable type,
Cat 5e, 6, or 6A.
5 On the TEST SETUP screen, tap Test Limit, then tap the correct patch cord test
limit, Cat7A Patch Cords, Cat7 Patch Cords, Cat6A Patch Cords, Cat6 Patch
Cords, or Cat5e Patch Cords.
If you do not see the correct patch cord test limit, tap MORE, tap Patch Cords,
then tap the correct limit.
6 The TEST LIMIT - Patch Cords screen shows a list of patch cords that have
different lengths.
On the TEST LIMIT - Patch Cords screen, tap the correct patch cord.
Notes
TIA limits that have “(LA)” in the limit name are used only
with DSX Lab Adapters in Fluke Networks service centers.
If the patch cord's length is not in the list, select a limit with
the next longest length. For example, if the patch cord is
2.2 m long, select a limit for a 2.5 m patch cord.
Outlet Configuration: Select the correct wire map for the patch cords.
8 On the TEST SETUP screen, tap SAVE when your test setup is completed.
9 On the CHANGE TEST screen, make sure the button next to the test is
selected, then tap USE SELECTED.
10 If you want to make a list of cable IDs or change the Auto Save setting, tap
the Next ID panel on the home screen.
4
How to Do Tests on Patch Cords
1 Connect the patch cord to the main and remote testers, as shown in Figure 1.
2 Turn on both testers, then tap TEST on the main tester or press on the
main or remote tester.
Note
The main tester will not turn on a remote tester when they
are connected through patch cord adapters.
DSX-PC6
DSX main tester with WCaution DSX remote tester with
DSX-PCxx patch cord To help ensure accurate test results, DSX-PCxx patch cord
adapter do not bend the patch cord during adapter
the test.
C01.EPS
5
DSX-PCxx Patch Cord Adapters
Users Manual
6
Patch Cord Test Results
NEXT Failures
NEXT failures are typically caused by these problems:
Wire pairs untwisted too much at the plug. Most NEXT failures occur at plugs,
where the wire pairs are untwisted.
Poor quality plug
Poor quality cable
Poorly matched plug and jack
Distortions in the cable, such as pinches or kinks
Too much electrical noise near cabling under test.
Wrong test limit selected
7
DSX-PCxx Patch Cord Adapters
Users Manual
C02.EPS
HDTDX plots for a bad cable show high Bad cable often causes return loss failures at
crosstalk along the cable. low frequencies (below 50 MHz)
8
Patch Cord Test Results
C05.EPS
HDTDX plots for a bad plug show high A bad plug often causes return loss failures
crosstalk at the plug. at high frequencies. Typically, the test fails
or has the worst margin at the end with the
bad plug.
9
DSX-PCxx Patch Cord Adapters
Users Manual
WCaution
If you do tests on patch cords that have poorly crimped
plugs, you can reduce the life of the patch cord adapter's
jacks or make them unusable.
Replace the jacks in the adapters when any of these conditions occur:
Margins for patch cord tests begin to get smaller.
Patch cord tests, especially wire map or return loss tests, begin to give
inconsistent results.
You have connected patch cords to the jacks more than 5000 times.
The characterization test given in Appendix A fails or the results are very
different from the results you saw when the adapters were new.
10
When to Replace the Jacks in the Adapters
Replacement Parts
Table 1. Replacement Parts
Fluke Networks
Description Model Number
11
DSX-PCxx Patch Cord Adapters
Users Manual
Replace the jacks only with jacks of the same type. For
example, do not put Cat 5e jacks onto Cat 6 circuit boards.
Note
To ensure reliable operation, replace the DSX-PCxx patch
cord adapter after you have replaced the RJ45 jack 10 times.
1 Use a TORX PLUS® driver, size T-7, to remove the three screws from the back
of the patch cord adapter.
2 Take the adapter case apart and remove the circuit board from the case.
3 Pull the RJ45 jack off of the circuit board (Figure 4).
4 Align the new RJ45 jack on the connectors on the circuit board. See in Figure
4 how the insulation displacement connectors in the jack slide into the
connectors on the circuit board.
5 Push the RJ45 jack onto the connectors on the board. If firm pressure does
not push the jack onto the connectors, realign the jack before you try again.
7 If you want to monitor the number of tests you do with the new jack, reset
the Current Series count for the adapter. See "How to Monitor the Number
of Insertions for a Jack" on page 11.
12
Specifications
Insulation displacement
connections on the jack
C03.EPS
Specifications
The DSX CableAnalyzer testers and adapters comply with these accuracy
requirements at these categories of permanent link and channel pass/fail limits:
Level IIe requirements at ANSI/TIA and ISO/IEC Cat 5e patch cord test limits.
Level III requirements at ANSI/TIA and ISO/IEC Cat 6 patch cord test limits.
Level IIIe requirements at ISO/IEC Cat 6A patch cord test limits.
For more DSX-PCxx Patch Cord Adapter specifications, contact Fluke Networks.
For DSX CableAnalyzer specifications, refer to the Versiv Series Technical
Reference Handbook available on the Fluke Networks website.
13
DSX-PCxx Patch Cord Adapters
Users Manual
14
Appendix A: How to Characterize and
Verify the Adapters’ Performance
Introduction
This appendix tells how to characterize the performance of the DSX-PCxx
adapters. Later, you can do the test again to see if the adapters are operating
correctly.
2 Get several patch cords of the same length that are possibly good.
3 On the main DSX tester, select a patch cord test limit that is applicable to the
patch cords.
4 Do an Autotest on the patch cords to find one that passes. A PASS* result is
sufficient. Select two good patch cords to be your reference patch cords.
Note
When you do the Autotest, keep the patch cord straight as
shown in Figure 1 on page 5.
5 Save the test results from the reference patch cord, then upload the results to
LinkWare. Keep the results where you can find them later.
-continued-
15
DSX-PCxx Patch Cord Adapters
Users Manual
6 Mark the reference patch cord ends with “main” and “remote” as it was
connected for the test. Keep the reference patch cord to use later for
performance tests on the adapters.
WCaution
For consistent return loss measurements from the reference
patch cord, do not put mechanical stress on the cord during
tests or storage. Patch cord performance can change when
you bend or twist the cord.
Note
When you do a test on the reference patch cord later, you
will use the same main and remote DSX testers you used for
the initial test. The test results include the serial numbers of
the testers.
2 Get the same main and remote DSX testers you used for the initial test.The
serial numbers are in the test results.
4 Connect the reference patch cord between the main and remote DSX testers.
Make sure to connect the ends of the patch cord to the correct testers.
5 On the DSX tester, select the same patch cord test limit you used for the initial
test.
7 Use the plots on the DSX and in LinkWare to compare the NEXT and RL
margins in the areas nearest the limit line. For a good adapter and jack, the
old and new NEXT and RL margins should be very similar.
16
Note
If you replaced the jacks on the adapters, the difference
between the old and new margins can be more than 0.5 dB.
If the difference is more than a few dB, make sure the new
jacks are installed correctly and the adapters show no
damage.
8 If the old and new margins are not similar, replace the RJ45 jacks on the
adapters. See "When to Replace the Jacks in the Adapters" on page 10 for
details.
9 If you did this procedure to verify the performance of new jacks on the
adapters, keep the results as the new characterization results for the
adapters.
17
DSX-PCxx Patch Cord Adapters
Users Manual
18