SIPROTEC 7SA86
Distance protection
www.siemens.com/siprotec
Description
The SIPROTEC 7SA86 distance protection has been de-
signed specifically for the protection of lines. With its mod-
ular structure, flexibility and the high-performance DIGSI 5
engineering tool, the SIPROTEC 7SA86 device offers fu-
ture-oriented solutions for protection, control, automa-
tion, monitoring, and Power Quality – Basic.
Main function Distance Protection
Interoperability of SIPROTEC 4 and
SIPROTEC 5 line protection devices
SIPROTEC 5 Device with Expansion Module
Tripping 3-pole, minimum tripping time: 9 ms • Detection and recording of power-quality data in the
Inputs and out- 12 predefined standard variants with 4/4
mediumvoltage and subordinate low-voltage power
puts or 8/8 current transformers/voltage trans- system
formers, 5 to 31 binary inputs, 8 to 46 bi- Functions
nary outputs
DIGSI 5 permits all functions to be configured and com-
Hardware Flexibly adjustable I/O quantity structure bined as required.
quantity within the scope of the SIPROTEC 5 modu-
structure lar system • Minimum tripping time: 9 ms
Housing width 1/3 × 19 inch to 2/1 × 19 inch • 6 independent measuring loops (6-system distance
protection)
Applications
• Several distance-protection functions can be selected:
• Detection and selective 3-pole tripping of short cir- Classic, reactance method (RMD), impedance protec-
cuits in electrical equipment of star networks, lines tion for transformers
with infeed at one or 2 ends, parallel lines, and open-
circuited or closed ring systems of all voltage levels • Directional backup protection and various additional
functions
• Detection of ground faults in isolated or arc-suppres-
sion-coilground systems in star, ring, or meshed ar- • Detection of ground faults of any type in compensa-
rangement ted or isolated electrical power systems using the
following functions: 3I0>, V0>, transient ground fault,
• Serial protection communication with SIPROTEC 5 and cos φ, sin φ, dir. detection of intermittent ground
SIPROTEC 4 devices over different distances and physi- faults, harmonic detection, and admittance measure-
cal media, such as optical fiber, two-wire connections, ment
and communication networks
• Ground-fault detection using the pulse-detection me-
• Backup protection for differential protection devices thod
of all kind for lines, transformers, generators, motors,
and busbars • Adaptive power-swing blocking, out-of-step protec-
tion
• Phasor Measurement Unit (PMU)
Efficient and modular
• Detection of current-transformer saturation for fast • Serial protection communication via optical fibers,
tripping with high accuracy two-wire connections, and communication networks
(IEEE C37.94 and others), including automatic switch-
• Fault locator plus for accurate fault location with in-
over between ring feeder and chain topology
homogenous line sections and targeted automatic
overhead line section reclosing (AREC) • Reliable data transmission via PRP and HSR redun-
dancy protocols
• Arc protection
• Extensive cybersecurity functionality, such as role-
• Automatic frequency relief for underfrequency load
based access control (RBAC), logging of security-re-
shedding, taking changed infeed conditions due to
lated events, signed firmware, or authenticated IEEE
decentralized power generation into consideration
802.1X network access.
• Power protection, configurable as active or reactive-
• Simple, fast, and secure access to the device via a
power protection
standard Web browser to display all information and
• Directional reactive-power undervoltage protection diagnostic data, vector diagrams, single-line and de-
(QU protection) vice display pages
• Detection of current and voltage signals up to the • Phasor Measurement Unit (PMU) for synchrophasor
50th harmonic with high accuracy for selected protec- measured values and IEEE C37.118 protocol
tion functions (such as thermal overload protection)
• Time synchronization using IEEE 1588
and operational measured values
• High-performance fault recording (buffer for a max.
• PQ – Basic: Voltage unbalance; voltage changes: over-
record time of 80 s at 8 kHz or 320 s at 2 kHz)
voltage, dip, interruption; TDD, THD, and harmonics
• Auxiliary functions for simple tests and commission-
• 3-pole automatic reclosing function
ing
• Control, synchrocheck, and switchgear interlocking
• Flexibly adjustable I/O quantity structure within the
protection
scope of the SIPROTEC 5 modular system
• Graphical logic editor to create high-performance au- Benefits
tomation functions in the device
• Safety due to powerful protection functions
• Single-line representation in the small or large display
• Purposeful and easy handling of devices and software
• Fixed integrated electrical Ethernet RJ45 interface for thanks to a user-friendly design
DIGSI 5 and IEC 61850 (reporting and GOOSE)
• Cybersecurity in accordance with NERC CIP and BDEW
• Up to 4 optional, pluggable communication modules, Whitepaper requirements
usable for different and redundant protocols (IEC
61850-8-1, IEC 61850-9-2 Client, IEC 60870-5-103, • Highest availability even under extreme environmen-
IEC 60870-5-104, Modbus TCP, DNP3 serial and TCP, tal conditions by standard coating of the modules
PROFINET IO, PROFINET IO S2 redundancy)
• Full compatibility between IEC 61850 Editions 1, 2.0,
• Virtual network partitioning (IEEE 802.1Q - VLAN) and 2.1
For all products using
security features of
Siemens 2020 For the U.S. published by OpenSSL, the
Siemens Industry Inc. following shall apply:
Smart Infrastructure
Digital Grid 100 Technology Drive This product includes
software developed
Humboldtstrasse 59 Alpharetta, GA 30005
by the OpenSSL Pro-
90459 Nuremberg, United States ject for use in the
Germany OpenSSL Toolkit
(www.openssl.org),
Customer Support: http://www.siemens.com/csc cryptographic soft-
ware written by Eric
Young
© Siemens 2020. Subject to changes and errors. (
[email protected])
SIPROTEC 7SA86_Profile V1.docx_12.20 and software devel-
oped by Bodo
Moeller.