Learn-/Training

DocumentSiemens Automation
Cooperates with Education (SCE) | From Version
V14 SP1
TIA Portal Module 011-100
Unspecified Hardware Configuration
with SIMATIC S7-1200

siemens.com/sce

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved.
Learn-/Training Document | TIA Portal Modul 011-100, Edition 2018 | Digital Factory, DF FA

Matching SCE Trainer Packages for these Learn-/Training Document


• SIMATIC S7-1200 AC/DC/RELAY (set of 6) "TIA Portal"
Order no.: 6ES7214-1BE30-4AB3
• SIMATIC S7-1200 DC/DC/DC (set of 6) "TIA Portal"
Order no.: 6ES7214-1AE30-4AB3
• Upgrade SIMATIC STEP 7 BASIC V14 SP1 (for S7-1200) (set of 6) "TIA Portal"
Order no.: 6ES7822-0AA04-4YE5

Note that these trainer packages are replaced with successor packages when necessary.
An overview of the currently available SCE packages is available at: siemens.com/sce/tp

Continued training
For regional Siemens SCE continued training, get in touch with your regional SCE contact
siemens.com/sce/contact

Additional information regarding SCE


siemens.com/sce

Information regarding use


The SCE Learn-/Training Document for the integrated automation solution Totally Integrated Automation
(TIA) was prepared for the program "Siemens Automation Cooperates with Education (SCE)" specifically
for training purposes for public educational facilities and R&D institutions. Siemens AG does not
guarantee the contents.

This document is to be used only for initial training on Siemens products/systems, which means it can be
copied in whole or part and given to those being trained for use within the scope of their training.
Circulation or copying this Learn-/Training Document and sharing its content is permitted within public
training and advanced training facilities for training purposes.

Exceptions require written consent from the Siemens AG contact person: Roland Scheuerer
[email protected].

Offenders will be held liable. All rights including translation are reserved, particularly if a patent is granted
or a utility model or design is registered.

Use for industrial customer courses is explicitly not permitted. We do not consent to commercial use of
the Learn-/Training Document.

We wish to thank the TU Dresden, particularly Prof. Dr.-Ing. Leon Urbas and the Michael Dziallas
Engineering Corporation and all other involved persons for their support during the preparation of this
Learn-/Training Document.

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 2

667152176.docx
Learn-/Training Document | TIA Portal Modul 011-100, Edition 2018 | Digital Factory, DF FA

Table of contents
1 Goal..................................................................................................................................................... 5

2 Prerequisite........................................................................................................................................ 5

3 Required hardware and software...................................................................................................... 6

4 Theory................................................................................................................................................. 7

4.1 SIMATIC S7-1200 automation system......................................................................................... 7

4.1.1 Range of modules................................................................................................................ 8

4.2 Operator control and display elements of the CPU 1214C DC/DC/DC......................................10

4.2.1 Front view of the CPU 1214C DC/DC/DC..........................................................................10

4.2.2 SIMATIC memory card (MC)..............................................................................................11

4.2.3 Operating states of the CPU.............................................................................................. 11

4.2.4 Status and error displays................................................................................................... 12

4.3 STEP 7 Basic V14 (TIA Portal V14) programming software......................................................13

4.3.1 Project................................................................................................................................ 13

4.3.2 Hardware configuration...................................................................................................... 13

4.3.3 Planning the hardware....................................................................................................... 14

4.3.4 TIA Portal – Project view and portal view...........................................................................15

4.3.5 Basic settings for the TIA Portal......................................................................................... 17

4.3.6 Set the IP address on the programming device.................................................................19

4.3.7 Set the IP address in the CPU...........................................................................................22

4.3.8 Restore the factory settings of the CPU.............................................................................25

5 Task.................................................................................................................................................. 26

6 Planning............................................................................................................................................ 26

7 Structured step-by-step instructions...............................................................................................27

7.1 Create a new project.................................................................................................................. 27

7.2 Read the hardware of SIMATIC S7-1200..................................................................................28

7.3 Configure the Ethernet interface of the CPU 1214C..................................................................34

7.4 Configure the address areas...................................................................................................... 36


For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 3

667152176.docx
Learn-/Training Document | TIA Portal Modul 011-100, Edition 2018 | Digital Factory, DF FA

7.5 Save and compile the hardware configuration...........................................................................37

7.6 Download the hardware configuration to the device..................................................................38

7.7 Archive the project..................................................................................................................... 43

7.8 Checklist.................................................................................................................................... 44

8 Additional information...................................................................................................................... 45

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 4

667152176.docx
Learn-/Training Document | TIA Portal Modul 011-100, Edition 2018 | Digital Factory, DF FA

Unspecified Hardware Configuration –


for a SIMATIC S7-1200
1 Goal
In this chapter, you will first learn how to create a project. Next you will be shown how you can
use the TIA Portal to detect hardware already installed and add it to a project. This hardware
will then be configured.

The SIMATIC S7 controllers listed in Chapter 3 can be used.

2 Prerequisite
You do not need any previous knowledge from other chapters to successfully complete this
chapter. You only need an S7-1200 controller and a PC with the STEP 7 Basic V14 (TIA Portal
V14) software.

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 5

667152176.docx
Learn-/Training Document | TIA Portal Modul 011-100, Edition 2018 | Digital Factory, DF FA

3 Required hardware and software

1 Engineering station: requirements include hardware and operating system (for additional
information, see Readme on the TIA Portal Installation DVDs)

2 SIMATIC STEP 7 Basic software in TIA Portal – as of V14 SP1

3 SIMATIC S7-1200 controller, e.g. CPU 1214C DC/DC/DC with ANALOG OUTPUT SB1232 signal
board, 1 AO – Firmware as of V4.2.1

4 Ethernet connection between engineering station and controller

2 SIMATIC STEP 7
1 Engineering Station Basic (TIA Portal) as of
V14 SP1

4 Ethernet connection

3 SIMATIC S7-1200 controller

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 6

667152176.docx
Learn-/Training Document | TIA Portal Modul 011-100, Edition 2018 | Digital Factory, DF FA

4 Theory
4.1 SIMATIC S7-1200 automation system
The SIMATIC S7-1200 automation system is a modular microcontroller system for the lower
performance range.

A comprehensive range of modules is available to optimally adapt the system to the automation
task.

The S7 controller consists of a power supply and a CPU with integrated inputs and outputs or
additional input and output modules for digital and analog signals.

If necessary, communication processors and function modules are also used for special tasks
such as stepper motor control.

The programmable logic controller (PLC) uses the S7 program to monitor and control a machine
or process. In doing so, the IO modules are scanned in the S7 program using input addresses
(%I) and addressed using output addresses (%Q).

The system is programmed with the TIA Portal Basic or Professional software.

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 7

667152176.docx
Learn-/Training Document | TIA Portal Modul 011-100, Edition 2018 | Digital Factory, DF FA

4.1.1 Range of modules


The SIMATIC S7-1200 is a modular automation system and offers the following range of
modules:

Central processing units (CPUs) with different performance, integrated inputs/outputs, and
PROFINET interface (e.g. CPU 1214C)

Power supply module (PM) with input 120/230 V AC, 50 Hz / 60 Hz, 1.2 A / 0.7 A and output 24 V
DC / 2.5 A

Signal boards (SBs) for adding analog or digital inputs/outputs, in which case the size of the CPU
remains unchanged. (Signal boards can be used with CPUs 1211C / 1212C and 1214C.)

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 8

667152176.docx
Learn-/Training Document | TIA Portal Modul 011-100, Edition 2018 | Digital Factory, DF FA

Signal modules (SMs) for digital and analog inputs and outputs (a maximum of 2 SMs can be
used for CPU 1212C and a maximum of 8 SMs for CPU 1214C.)

Communication modules (CMs) for serial communication RS232 / RS 485 (Up to 3 CMs can be
used for CPUs 1211C / 1212C and 1214C.)

Compact switch module (CSM) with 4x RJ45 sockets 10/100 Mbps

SIMATIC memory cards from 2 MB to 32 MB for storing program data and for easy exchange of
CPUs during maintenance.

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 9

667152176.docx
Learn-/Training Document | TIA Portal Modul 011-100, Edition 2018 | Digital Factory, DF FA

Note: Only a single CPU (any type) with integrated digital inputs and digital outputs is needed for
this module.

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 10

667152176.docx
Learn-/Training Document | TIA Portal Modul 011-100, Edition 2018 | Digital Factory, DF FA

4.2 Operator control and display elements of the CPU 1214C


DC/DC/DC

4.2.1 Front view of the CPU 1214C DC/DC/DC


With integrated power supply (24 V connection) and integrated inputs and outputs, the CPU
1214C DC/DC/DC is immediately ready for use without any other components.

The CPU has an integrated TCP/IP connection for communication with a programming device.

The CPU can thus communicate with HMI devices or other CPUs via an Ethernet network.

 24 V connection

 Plug-in terminal block for user wiring (behind the cover flaps)

 Status LEDs for the integrated IO and the operating state of the CPU

 TCP/IP connection (on the underside of the CPU)

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 11

667152176.docx
Learn-/Training Document | TIA Portal Modul 011-100, Edition 2018 | Digital Factory, DF FA

4.2.2 SIMATIC memory card (MC)


The optional SIMATIC memory card (MC) stores a program as well as data, system data, files
and projects. It can be used for:

– Transferring a program to multiple CPUs

– Firmware update of CPUs, signal modules (SMs) and communication modules (CMs)

– Easy replacement of the CPU

4.2.3 Operating states of the CPU


The CPU can have the following three operating states:

– In the STOP operating state, the CPU is not executing the program and you can download a
project.

– In the STARTUP operating state, the CPU is starting up.

– In the RUN operating state, the program is cyclically executed.

The CPU does not have a physical switch for changing the operating state.

You use the button on the operator panel of the STEP 7 Basic software to change the operating
state (STOP or RUN). The operator panel also contains an MRES button for performing a
memory reset and displays the status LEDs of the CPU.

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 12

667152176.docx
Learn-/Training Document | TIA Portal Modul 011-100, Edition 2018 | Digital Factory, DF FA

4.2.4 Status and error displays

The RUN/STOP status LED on the front side of the CPU indicates the current operating state of
the CPU by the color of the display.

– Yellow light indicates STOP


operating state.

– Green light indicates RUN


operating state.

– A flashing light indicates


STARTUP operating state.

There are two additional LEDs here: ERROR LED for indicating errors and MAINT LED for
indicating that maintenance is required.

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 13

667152176.docx
Learn-/Training Document | TIA Portal Modul 011-100, Edition 2018 | Digital Factory, DF FA

4.3 STEP 7 Basic V14 (TIA Portal V14) programming software


The STEP 7 Basic V14 (TIA Portal V14) software is the programming tool for the following
automation systems:
– SIMATIC S7-1200

– Basic Panels

STEP 7 Basic V14 provides the following functions for automation of a system:
– Configuration and parameter assignment of the hardware

– Specification of the communication

– Programming

– Testing, commissioning and servicing with operational/diagnostic functions

– Documentation

– Creation of visualizations for SIMATIC Basic Panels using the integrated WinCC Basic
software

– Support is provided for all functions through detailed online help.

4.3.1 Project
To implement a solution for an automation and visualization task, you create a project in the TIA
Portal. A project in the TIA Portal contains the configuration data for the configuration and
internetworking of devices as well as the programs and the configuration of the visualization.

4.3.2 Hardware configuration


The hardware configuration includes the configuration of the devices, consisting of the hardware
of the automation system, the field devices on the PROFINET bus system and the hardware for
visualization. The configuration of the networks specifies the communication between the various
hardware components. Individual hardware components are inserted in the hardware
configuration from catalogs.

The hardware of SIMATIC S7-1200 automation systems comprises the controller (CPU), the
signal modules for input and output signals (SMs), the communication modules (CMs) and other
special-purpose modules.

The signal modules and the field devices connect the input and output data of the process to be
automated and visualized to the automation system.

The hardware configuration enables the downloading of automation and visualization solutions to
the automation system and access to the connected signal modules by the controller.
For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 14

667152176.docx
Learn-/Training Document | TIA Portal Modul 011-100, Edition 2018 | Digital Factory, DF FA

4.3.3 Planning the hardware


Before you can configure the hardware, you must plan it (hardware planning). In general, you
begin by selecting which controllers are needed and how many. You then select the
communication modules and signal modules. The selection of signal modules is based on the
number and type of inputs and outputs needed. As the final step, a power supply that ensures the
necessary power supply must be selected for each controller or field device.

The functionality required and the ambient conditions are of vital importance for planning the
hardware configuration. For example, the temperature range in the application area sometimes
limits which devices are available for selection. Fail-safe operation might be another requirement.

The TIA Selection Tool (Select automation technology  TIA Selection Tool and follow the
instructions) provides you support. Note: The TIA Selection Tool requires Java.

Note for online research: If more than one manual is available, you should look for the
description "Device Manual", "Product Manual" or simply "Manual" (as opposed to "Function
Manual", "List Manual", "System Manual", etc.) in order to find the device specifications.

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 15

667152176.docx
Learn-/Training Document | TIA Portal Modul 011-100, Edition 2018 | Digital Factory, DF FA

4.3.4 TIA Portal – Project view and portal view


The TIA Portal has two important views. When started, the TIA Portal displays the portal view by
default. This view makes getting started easier, especially for beginning users.

The portal view provides a task-oriented view of the tools for working on the project. Here, you
can quickly decide what you want to do and open the tool for the task at hand. If necessary, a
change to the project view takes place automatically for the selected task.

Figure 1 shows the portal view. At the bottom left, there is an option to switch between this view
and the project view.

Figure 1: Portal view

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 16

667152176.docx
Learn-/Training Document | TIA Portal Modul 011-100, Edition 2018 | Digital Factory, DF FA

The project view, as shown in Figure 2, is used for hardware configuration, programming,
creation of the visualization and many other tasks.

By default, the project view displays the menu bar with the toolbars at the top, the project tree
with all components of a project on the left and the so-called "task cards" with instructions and
libraries, for example, on the right.

If an element (for example, the device configuration) is selected in the project tree, it is displayed
in the center and can be worked on there.

Figure 2: Project view

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 17

667152176.docx
Learn-/Training Document | TIA Portal Modul 011-100, Edition 2018 | Digital Factory, DF FA

4.3.5 Basic settings for the TIA Portal

 Users can specify their own default settings for certain settings in the TIA Portal. A few
important settings are shown here.

 In the project view, select the ® "Options" menu and then ® "Settings".

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 18

667152176.docx
Learn-/Training Document | TIA Portal Modul 011-100, Edition 2018 | Digital Factory, DF FA

 One basic setting is the selection of the user interface language and the language for the
program display. In the curriculums to follow, "English" will be used for both settings.

 Under "General" in "Settings", select ® "User interface language ® English" and "Mnemonic
® International".

Note: These settings can always be changed.

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 19

667152176.docx
Learn-/Training Document | TIA Portal Modul 011-100, Edition 2018 | Digital Factory, DF FA

4.3.6 Set the IP address on the programming device

To program the SIMATIC S7-1200 controller from the PC, the programming device or a laptop,
you need a TCP/IP connection or an optional PROFIBUS connection.

For the PC and SIMATIC S7-1200 to communicate with each other via TCP/IP, it is important that
the IP addresses of both devices match.

First, we show you how to set the IP address of a PC with Windows 7 operating system.

 Locate the network icon in the taskbar at the bottom and click ® "Open Network and
Sharing Center".

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 20

667152176.docx
Learn-/Training Document | TIA Portal Modul 011-100, Edition 2018 | Digital Factory, DF FA

 In the open Network and Sharing Center window, click ® "Change adapter settings".

 Select the desired ® "Local Area Connection" that you want to use to connect to the
controller and click ® "Properties".

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 21

667152176.docx
Learn-/Training Document | TIA Portal Modul 011-100, Edition 2018 | Digital Factory, DF FA

 Next, select ® "Properties" for ® "Internet Protocol Version 4 (TCP/IP)".

 You can use the following address, for example ® IP address: 192.168.0.99 ® Subnet mask
255.255.255.0 and accept the settings (® "OK")

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 22

667152176.docx
Learn-/Training Document | TIA Portal Modul 011-100, Edition 2018 | Digital Factory, DF FA

4.3.7 Set the IP address in the CPU


The IP address of SIMATIC S7-1200 is set as follows.

 Select the Totally Integrated Automation Portal for this, which is opened here with a double-
click (®® TIA Portal V14)

 Select  "Online & diagnostics", and open the "project view".

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 23

667152176.docx
Learn-/Training Document | TIA Portal Modul 011-100, Edition 2018 | Digital Factory, DF FA

 In the project tree under  "Online access", select the network adapter that was set
previously. If you click  "Update accessible devices" here, you see the IP address (if
previously set) or the MAC address (if IP address not yet assigned) of the connected
SIMATIC S7-1200. Select  "Online & diagnostics" here.

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 24

667152176.docx
Learn-/Training Document | TIA Portal Modul 011-100, Edition 2018 | Digital Factory, DF FA

 Under "Functions", you now find the  "Assign IP address" item. Enter the following IP
address here (example): ® IP address: 192.168.0.1 ® Subnet mask 255.255.255.0. Click 
"Assign IP address" and this new address will be assigned to your SIMATIC S7-1200.

 If the IP address was not successfully assigned, you will receive a message in the  "Info"
window under  "General".

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 25

667152176.docx
Learn-/Training Document | TIA Portal Modul 011-100, Edition 2018 | Digital Factory, DF FA

4.3.8 Restore the factory settings of the CPU

 If the IP address could not be assigned, the program data on the CPU must be deleted. This
is done by resetting the CPU. To reset the controller, select the  "Reset to factory settings"
function and click  "Reset".

 Confirm the prompt asking if you really want to reset the module with  "Yes".

 If necessary, stop the CPU. ( "Yes")

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 26

667152176.docx
Learn-/Training Document | TIA Portal Modul 011-100, Edition 2018 | Digital Factory, DF FA

5 Task
Create a project and add the modules of the existing hardware (here: Trainer Package SIMATIC
S7-1200 with CPU 1214C) by using the automatic hardware detection of the TIA Portal. The
following modules must be detected:

– SIMATIC S7-1200, CPU 1214C DC/DC/DC


(Order number: 6ES7 214-1AG40-0XB0)

– 1X SIMATIC S7-1200, signal board ANALOG OUTPUT SB1232, 1 AO


(Order number: 6ES7 232-4HA30-0XB0)

6 Planning
Because this is a new system, a new project must be created.

The hardware for this project is already specified by the existing hardware (here: SIMATIC S7-
1200 Trainer Package). Therefore, a selection does not have to be made. Instead, the listed
modules of the Trainer Package are detected directly. The order numbers (see Task or Table 1)
can be used for checking purposes.

The Ethernet interface must be set for the configuration of the CPU. For the digital and analog
inputs and outputs, the address areas corresponding to Table 1 will be set.

Module Order number Slot Address area

CPU 1214C DC/DC/DC 6ES7 214-1AG40-0XB0 1 DI 0.0 -1.5

DQ 0.0 - 1.1

AI 64 / 66

SB1232, 1 AO 6ES7 232-4HA30-0XB0 AO 64


Table 1: Overview of the planned configuration

As the final step, the hardware configuration must be compiled and downloaded. Any errors
present can be detected during compiling and incorrect modules can be detected when the
controller is started (only possible when hardware is present and installed identically).

The tested project must be saved and archived.

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 27

667152176.docx
Learn-/Training Document | TIA Portal Modul 011-100, Edition 2018 | Digital Factory, DF FA

7 Structured step-by-step instructions


You can find instructions on how to carry out planning below. If you already have the relevant
previous knowledge, it will be sufficient to focus on the numbered steps. Otherwise, simply follow
the steps in the instructions.

7.1 Create a new project


 Select the Totally Integrated Automation Portal for this, which is opened here with a double-
click (®® TIA Portal V14)

 In the portal view under the "Start" menu, select the command  "Create new project".

 Modify Project name, Path, Author and Comment as appropriate and click  "Create".

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 28

667152176.docx
Learn-/Training Document | TIA Portal Modul 011-100, Edition 2018 | Digital Factory, DF FA

 The project will be created and opened and the menu "Start", "First steps" will open
automatically.

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 29

667152176.docx
Learn-/Training Document | TIA Portal Modul 011-100, Edition 2018 | Digital Factory, DF FA

7.2 Read the hardware of SIMATIC S7-1200


 In the  "Start" portal, select  "First steps"  "Devices & Networks"  "Configure a
device".

 The "Show all devices" menu opens in the "Devices & Networks" portal.

 Switch to the "Add new device" menu.

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 30

667152176.docx
Learn-/Training Document | TIA Portal Modul 011-100, Edition 2018 | Digital Factory, DF FA

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 31

667152176.docx
Learn-/Training Document | TIA Portal Modul 011-100, Edition 2018 | Digital Factory, DF FA

 Create a new CPU. Use an unspecified model of the S7-1200 CPU with order number 6ES7
2XX-XXXXX-XXXX for this.

 (Controllers  SIMATIC S7-1200  CPU  Unspecified CPU 1200  6ES7 2XX-XXXXX-


XXXX  V4.2)

 Assign a device name (Device name  "CPU_1200").

 Select "Open device view".

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 32

667152176.docx
Learn-/Training Document | TIA Portal Modul 011-100, Edition 2018 | Digital Factory, DF FA

 Click "Add".

 The TIA Portal now switches automatically to the project view and displays a notice there that
this device is not specified. In order to have the hardware configuration automatically
detected, start detection by clicking "detect" in the yellow information box ( detect).

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 33

667152176.docx
Learn-/Training Document | TIA Portal Modul 011-100, Edition 2018 | Digital Factory, DF FA

 Select the type of your PG/PC interface ( Type of the PG/PC interface: PN/IE).

 You can now select the network adapter you want to use to establish an Ethernet connection
with the PLC ( PG/PC interface: Intel(R) Ethernet Connection (4) I219-LM).

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 34

667152176.docx
Learn-/Training Document | TIA Portal Modul 011-100, Edition 2018 | Digital Factory, DF FA

 The search for devices in the network must be started by clicking the  button.

 All accessible nodes are found and listed. If you have selected the correct CPU, the
corresponding CPU and all the connected modules will be detected when you click "detect".

Note: If the list does not contain your CPU, ensure that you have selected the correct network
adapter and have established a connection between the laptop and CPU.

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 35

667152176.docx
Learn-/Training Document | TIA Portal Modul 011-100, Edition 2018 | Digital Factory, DF FA

 The TIA Portal shows the complete device configuration of the selected CPU with signal
board SB1232, 1 AO.

Note: You can now configure the CPU according to your specifications there. Possible settings
include the PROFINET interface, startup characteristics, cycle, password protection,
communication load and many more.

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 36

667152176.docx
Learn-/Training Document | TIA Portal Modul 011-100, Edition 2018 | Digital Factory, DF FA

7.3 Configure the Ethernet interface of the CPU 1214C


 Select the CPU with a double-click

 Under  "Properties", open the  "PROFINET interface [X1]" menu and select the 
"Ethernet addresses" entry.

 Under "Interface networked with", only the "Not networked" entry is available.

 Add an Ethernet subnet with the  "Add new subnet" button.

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 37

667152176.docx
Learn-/Training Document | TIA Portal Modul 011-100, Edition 2018 | Digital Factory, DF FA

 Keep the preassigned "IP address" and "Subnet mask".

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 38

667152176.docx
Learn-/Training Document | TIA Portal Modul 011-100, Edition 2018 | Digital Factory, DF FA

7.4 Configure the address areas


 The next step is to check the address areas of the inputs and outputs and adapt them if
necessary. DI/DO should have an address area of 0…1 and AI/AO should have an address
area of 64…67 and 64…65, respectively. ( Device overview  DI 14/DQ 10_1  I
address: 0..1 Q address: 0...1  AI 2_1  I address: 64…67  AQ 1x12BIT_1  Q
address: 64…65)

Note: To show and hide the Device overview, you need to click the small arrow next to "Device
data" on the right side of the hardware configuration.

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 39

667152176.docx
Learn-/Training Document | TIA Portal Modul 011-100, Edition 2018 | Digital Factory, DF FA

7.5 Save and compile the hardware configuration


 Before you compile the configuration, you should save your project by clicking the ®®

button. To compile your CPU with the device configuration, first select the 

"CPU_1200 [CPU1214C DC/DC/DC]" folder and click the  "Compile" icon.

Note: "Save project" should be used again and again when working on a project since this does
not happen automatically. A prompt to save the project only occurs when the TIA Portal is closed.

 If the project was compiled without errors, you see the following screen.

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 40

667152176.docx
Learn-/Training Document | TIA Portal Modul 011-100, Edition 2018 | Digital Factory, DF FA

7.6 Download the hardware configuration to the device


 To download your entire CPU, select the  "CPU_1200 [CPU1214C DC/DC/DC]" folder and

click the  "Download" icon.

 The manager for configuring the connection properties (extended download) opens.

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 41

667152176.docx
Learn-/Training Document | TIA Portal Modul 011-100, Edition 2018 | Digital Factory, DF FA

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 42

667152176.docx
Learn-/Training Document | TIA Portal Modul 011-100, Edition 2018 | Digital Factory, DF FA

 First, the interface must be correctly selected. This happens in three steps.

 Type of the PG/PC interface  PN/IE

 PG/PC interface  here: Intel(R) Ethernet Connection I217-LM

 Connection to interface/subnet  "PN/IE_1"

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 43

667152176.docx
Learn-/Training Document | TIA Portal Modul 011-100, Edition 2018 | Digital Factory, DF FA

 The  "Show all compatible devices" check box must be selected. The search for devices in

the network is started by clicking the  button.

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 44

667152176.docx
Learn-/Training Document | TIA Portal Modul 011-100, Edition 2018 | Digital Factory, DF FA

 If your CPU is shown in the "Compatible devices in target subnet" list, you must select it. The
download can then be started ( CPU 1214C DC/DC/DC  "Load").

 You first obtain a preview. Confirm the prompt  "Overwrite all" and continue with  "Load".

Note: The symbol should be visible in every line of the "Load preview". You can find additional
information in the "Message" column.
For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 45

667152176.docx
Learn-/Training Document | TIA Portal Modul 011-100, Edition 2018 | Digital Factory, DF FA

 The  "Start all" option will be selected next before the download operation can be
completed with  "Finish".

 After a successful download, the project view will open again automatically. A loading report
appears in the information field under "General". This can be helpful when troubleshooting an
unsuccessful download.

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 46

667152176.docx
Learn-/Training Document | TIA Portal Modul 011-100, Edition 2018 | Digital Factory, DF FA

7.7 Archive the project


 To archive the project, select the  "Archive ..." command in the  "Project" menu.

 Confirm the prompt to save the project with  "Yes".

 Select a folder where you want to archive your project and save it as file type "TIA Portal
project archive" ( "TIA Portal project archive"  "SCE_EN_011-100_Unspecified hardware
configuration_S7-1200"  "Save").

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 47

667152176.docx
Learn-/Training Document | TIA Portal Modul 011-100, Edition 2018 | Digital Factory, DF FA

7.8 Checklist

No. Description Completed


1 Project was created
2 Slot 1: CPU with correct order number
3 Slot 1: CPU with correct firmware version
4 Signal board: Analog module AQ 1x12BIT with correct order number
5 Signal board: Analog module AQ 1x12BIT with correct firmware version
6 Address areas correct
7 Hardware configuration was compiled without error message
8 Hardware configuration was downloaded without error message
9 Project was successfully archived

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 48

667152176.docx
Learn-/Training Document | TIA Portal Modul 011-100, Edition 2018 | Digital Factory, DF FA

8 Additional information

More information for further practice and consolidation is available as orientation, for example:
Getting Started, videos, tutorials, apps, manuals, programming guidelines and trial software /
firmware, under the following link:

www.siemens.com/sce/s7-1200

Preview „Additional information“

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 49

667152176.docx
Learn-/Training Document | TIA Portal Modul 011-100, Edition 2018 | Digital Factory, DF FA

Further Information

Siemens Automation Cooperates with Education


siemens.com/sce
SCE Learn-/Training Documents
siemens.com/sce/documents
SCE Trainer Packages
siemens.com/sce/tp
SCE Contact Partners
siemens.com/sce/contact
Digital Enterprise
siemens.com/digital-enterprise
Industrie 4.0
siemens.com/future-of-manufacturing
Totally Integrated Automation (TIA)
siemens.com/tia
TIA Portal
siemens.com/tia-portal
SIMATIC Controller
siemens.com/controller
SIMATIC Technical Documentation
siemens.com/simatic-docu
Industry Online Support
support.industry.siemens.com
Product catalogue and online ordering system Industry Mall
mall.industry.siemens.com

Siemens AG
Digital Factory
P.O. Box 4848
90026 Nuremberg
Germany

Subject to change and errors


© Siemens AG 2018

siemens.com/sce

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 3