Factory Testing
Factory Testing
Factory Testing
Vivek Bhatt
[email protected]
Design Tests
Design tests shall be made to determine the adequacy of the design of a particular type, style, or model of
transformer or its component parts. Test data from previous similar designs may be used for current designs,
where appropriate. Once made, the tests need not be repeated unless the design is changed to modify
performance.
Other Tests
Other tests are identified in product specifications and may be specified by the purchaser in addition to
routine tests
Waukesha Waukesha
1Φ Excitation test
Routine Routine
Waukesha Waukesha
CT Ratio & Polarity
Routine Routine
Control Wiring Checks
Routine Routine
& Hi-pot
Waukesha
Auxiliary Losses Routine
Routine
Leak Test
• 10 PSI for 10 hours minimum
• Typically Tested during Manufacturing before release to Test
Between
Windings
To Ground
Positive Sequence
Routine Routine
Impedance
Zero Sequence
Special Routine
Impedance
Test Circuit
• Transformer is excited from either TV/LV or HV side at 60
Hz with a variable voltage sinusoidal source
• All other terminals are left open
• Applied voltage is slowly increased to test voltage 90%,
100%, 110%
• Need high precision measurement System
• Losses corrected to 20oC
Prolec GE Waukesha / Proprietary and Confidential
Load Losses and % Impedance
• Stray loss depends on % impedance, winding dimensions and clearance to tank and clamps
Impedance
• % Impedance = VOLTAGE FOR RATED CURRENT X 100
RATED VOLTAGE
Measurement
With the help of a precision loss measurement system load current, voltage and losses are measured:
• Transformer Neutrals
‒ 1 RFW
‒ 2 FW
‒ 1 FW*
Multiplier Circuit
RC circuit with circuit Inductance
Multiplier circuit introduced by
Prof. Marx
Impulse capacitor Cs are charged in
parallel and discharged in series after
firing the switching gaps F
Front Time T1 is determined by Rd
whereas time to half value is
determined by Re
Test Circuit
• Test for each HV Line terminal
For example:
Equivalent applied test voltage for 230kV ( 750,825,900 BIL) is 345kV
• For Wye connected windings, the applied test voltage is limited to the
BIL of Neutral
For example:
If line end BIL is 550kV and neutral end BIL is 150kV, then equivalent
applied test voltage is limited to 50kV (equivalent for 150 BIL)
• Test duration is 7200 Hz; if test frequency is 180 Hz then test duration = 7200/180 = 40 seconds
• Test is considered to be passed if no collapse of voltage occurs or no audible internal sound is present
Hot Spot
Gradient
R
Location
V
Ambient Oil Winding
W Avg. Winding
T D COM SER Avg. Gradient
V G