Process Control Lab Manual
Process Control Lab Manual
List of experiments:-
1. To study of open loop response (manual control)
2. To study of on/off controller.
3. To study of proportional controller
4. To study of proportional integral controller
5. To study of proportional derivative controller
6. To study of proportional integral derivative controller
7. To tuning of controller (open loop method)
8. To tuning of controller (closed loop method)
9. To tuning of controller (using auto tuning method)
10. To study stability of the system (Bode plot)
1
Department of Chemical Engineering, Veer Surendra Sai University of Technology Burla
Rotameter
Temperature
Controller
Temperature Sensor
Water Supply
Drain
Procedure
Start up set up as explained in general instructions.
Click Select Experiment, select Open Loop and click Start
Decrease the controller output to 0%. Note down steady state process value.
Apply the step change by 10% to controller output and wait for the temperature to reach
2
Department of Chemical Engineering, Veer Surendra Sai University of Technology Burla
From the above data, note the output required for maintaining the temperature at desired
set points.
Apparatus required:-
Temperature Control Trainer
THEORY: - :- Temperature control trainer is designed for understanding the basic temperature
control principles. The process setup consists of heating tank fitted with SSR controlled heater for
on-line heating of the water. The flow of water can be manipulated and measured by rotameter.
Temperature sensor (RTD) is used for temperature sensing. The process parameter (Temperature) is
controlled by microprocessor based digital indicating controller which manipulates heat input to
the process. These units along with necessary piping and fitting are mounted on support frame
designed for tabletop mounting.
3
Department of Chemical Engineering, Veer Surendra Sai University of Technology Burla
Rotameter
Temperature
Controller
Temperature Sensor
Water Supply
Drain
Procedure:-
Start up set up as explained in general instructions.
Click Select Experiment, select On-Off Mode and click Start
Change Hysteresis value to 1 %.( Range 0.1-10%)
Change the values of the set point and observe the On-Off control operation.
4
Department of Chemical Engineering, Veer Surendra Sai University of Technology Burla
Observations
Observe that if process value exceeds the set point and increases than the value of (0.5x
Hysteresis), controller switches off the SSR and if process value decreases below the set point by
(0.5 x Hysteresis), SSR switches on i.e. controller operates like On/Off switch.
5
Department of Chemical Engineering, Veer Surendra Sai University of Technology Burla
Rotameter
Temperature
Controller
Temperature Sensor
Water Supply
Drain
Procedure
Start up set up as explained in general instructions.
Click Select Experiment, select P Mode and click Start
Keep the set point to 40%. (Set point should be 10% more than inlet water temperature)
Change output mode to Manual. Adjust output value so as to match the process value with
set point and apply this output value as bias value to the controller. Adjust the proportional
band to 50%.
Switch the controller to Auto mode.
Apply step change to set point, step change should be of 2 to 3 % and observe the response.
6
Department of Chemical Engineering, Veer Surendra Sai University of Technology Burla
Switch the controller to Manual mode. Decrease proportional band to half of the previous
value & then shift controller to Auto mode. With each decrease, obtain a new response of
the step change. Ensure that the set point changes are around the same operating point (@ 2-
3% only).
Using trial and error approach, find a value of proportional band so that the response to a
step change has at most one overshoot and one undershoot.
Set the controller to the settings obtained in the above step and wait for the system to reach at
steady state.
Observations
Observe steady state error decreases as proportional band decreases.
Observe the effect of very low proportional band values (system works in oscillatory mode).
Observe the response of the system to load change. Load change can be given by slightly
varying the inlet flow rate.
7
Department of Chemical Engineering, Veer Surendra Sai University of Technology Burla
Rotameter
Temperature
Controller
Temperature Sensor
Water Supply
Drain
Procedure
Start up set up as explained in general instructions.
Click Select Experiment, select PI Mode and click Start
Adjust the process value by changing the output of controller in manual mode to a particular
temperature (set point =40%).
Set the proportional band estimated from Proportional control (from previous experiment).
Start with derivative time=0 and integral time=1000 sec., which will cut off the derivative
action and widen the effect of integral action.
Allow the process to reach at steady state. Record the steady state error.
8
Department of Chemical Engineering, Veer Surendra Sai University of Technology Burla
Switch on the controller to manual mode. Reduce the integral time to half of the previous
value. Switch to Auto mode and apply step change to the set point by 2 to 3%. Note the
response of the system.
Using trial and error, find out an integral time, which gives satisfactory response to the step
change in set point.
Observations
Observe the effect of reducing integral time on offset and on the response of the process.
9
Department of Chemical Engineering, Veer Surendra Sai University of Technology Burla
Rotameter
Temperature
Controller
Temperature Sensor
Water Supply
Drain
Procedure
Start up set up as explained in general instructions.
Click Select Experiment, select PD Mode and click Start
Set the proportional band estimated from Proportional control (P only). Start with derivative
time=0 and integral time=6000 sec., which will cut off the derivative action and widen the
effect of integral action.
Set the set point to desired temperature (@40%). Allow the process to reach at steady state.
10
Department of Chemical Engineering, Veer Surendra Sai University of Technology Burla
Observations
Observe the effect of increasing derivative time. Also note that the process may show offset
as effect of integral action is cut off.
11
Department of Chemical Engineering, Veer Surendra Sai University of Technology Burla
Rotameter
Temperature
Controller
Temperature Sensor
Water Supply
Drain
12
Department of Chemical Engineering, Veer Surendra Sai University of Technology Burla
Procedure
Start up set up as explained in general instructions.
Click Select Experiment, select PID mode and click Start
Switch the controller to manual mode.
Change the proportional band to the value that estimated in proportional controller. Set
integral time and derivative time based on the responses in previous experiments.
Change the controller to Auto mode. Apply step change by 2 to 3% to the set point and
observe the response of the process.
Change the proportional band, integral time, derivative time and observe the response of
the process for step change for each change in setting.
Observations
Compare the steady state response of the PID controller with P, PI and PD controller
obtained in the previous experiments.
13
Department of Chemical Engineering, Veer Surendra Sai University of Technology Burla
Rotameter
Temperature
Controller
Temperature Sensor
Water Supply
Drain
14
Department of Chemical Engineering, Veer Surendra Sai University of Technology Burla
Procedure
Start up set up as explained in general instructions.
Click Select Experiment, select Process Reaction and click Start
Adjust the controller output and bring the process near set point of 40%.
Allow the system to reach steady state. Start data logging.
With the controller still in manual mode impose a step change of 30 - 40 % in
controller output. Record the step response. Wait for the steady state. Stop data
logging.
Plot the step response (Process reaction curve) from stored data. Find out the value of slope at
the point of inflection and time lag.
Calculate P I D settings for different modes.
Select PID Mode option for control from software. (Click on “Change Expt.” Button, click
on “Change”, Click on “PID Mode” button.) Switch on the controller to manual mode and
Keep the set point to 40%. Adjust output value so as to match the process value to set
point.
Set the PID values obtained from the calculations. Switch on the controller to Auto mode.
Apply the step change & observe the response of the system. Allow the system to reach
steady state.
Observations
(Refer Theory process control for formula.)
Step change to the system P = Initial output- Final output of the controller.
Plot the graph of process value Vs Time on a graph paper.
From process reaction curve:
o Slope of the process reaction curve R =
o Time lag L=
Calculate P, PI, and PID setting from above values.
Observe response of the system for different PID settings.
15
Department of Chemical Engineering, Veer Surendra Sai University of Technology Burla
Rotameter
Temperature
Controller
Temperature Sensor
Water Supply
Drain
Procedure
Start up set up as explained in general instructions.
Click Select Experiment, select Close Loop and click Start
Set the proportional band value to maximum (Say 100). Set the controller to manual mode
and adjust the output so that the process is nearly at set point 40%.
Set controller to auto mode and impose step on the process by moving the set point for a
few seconds & then return to its original value (or apply the step change to the set point of
2%). Wait for some time & observe the response.
17-04-2017 16 Im314A
Department of Chemical Engineering, Veer Surendra Sai University of Technology Burla
Decrease the proportional band to the half of previous and impose step on the process as
mentioned above. Wait for some time & observe the response.
Repeat the above procedure and find out correct value of proportional band for which the
system just goes unstable i.e. continuous oscillations are observed in the output of
controller.
Record the ultimate proportional band and ultimate period from the response.
Calculate the PID values from the table. Select the PID controller and apply the parameter
values obtained from the above steps. Observe the response of the process to a step change
with these settings.
Observations
Record the ultimate proportional band (Pbu) and ultimate period (Tu) from above
experiment.
Calculate PID values by referring theory part for different control actions.
Observe the process response for these settings.
Compare the values obtained with open loop response me
17-04-2017 17 Im314A
Department of Chemical Engineering, Veer Surendra Sai University of Technology Burla
Apparatus required:-
Temperature control trainer
Theory: - Temperature control trainer is designed for understanding the basic temperature control
principles. The process setup consists of heating tank fitted with SSR controlled heater for on-line
heating of the water. The flow of water can be manipulated and measured by rotameter.
Temperature sensor (RTD) is used for temperature sensing. The process parameter (Temperature) is
controlled by microprocessor based digital indicating controller which manipulates heat input to
the process. These units along with necessary piping and fitting are mounted on support frame
designed for tabletop mounting.
Rotameter
Temperature
Controller
Temperature Sensor
Water Supply
Drain
The controller can be connected to computer through Ethernet / USB port for monitoring
the process in SCADA mode.
17-04-2017 18 Im314A
Department of Chemical Engineering, Veer Surendra Sai University of Technology Burla
Procedure:-
Start up set up as explained in general instructions.
Click Select Experiment, select Autotune and click Start
Wait Till Auto tune is complete. (Blinking of green LED stops).
Controller automatically finds the PB, IT & DT values.
Find out PID values at different set points /flow rates.
Observations
The controller has preprogrammed logic for finding “Auto tune” values. Based on the
response of the process the controller calculates PID values or comes out without finding the
“Auto tune” values.
17-04-2017 19 Im314A
Department of Chemical Engineering, Veer Surendra Sai University of Technology Burla
Temperature Sensor
Water Supply
Drain
The controller can be connected to computer through Ethernet / USB port for monitoring
the process in SCADA mode.
Procedure
Start up set up as explained in general instructions.
Click Select Experiment, select Stability analysis and click Start
17-04-2017 20 Im314A
Department of Chemical Engineering, Veer Surendra Sai University of Technology Burla
Select function generator to apply the sinusoidal input to the output of the controller.
Enter Reference point, Amplitude and Period.
Observe the sinusoidal output of the controller and sinusoidal response of the process.
Log the data for records.
Change the period and repeat the observation for 3-4 different values of the period.
Note: As the temperature process is very slow responsive, the amplitude and period for the
sinusoidal input should be large enough to observe response.
Observations
Form the data file stored note down the
Observe the output response of the process and note down the output amplitude. Measure
output wave period and note down as T sec. Measure the phase lag x and note down in sec.
Obs. Input Output Output Period Lag X Frequency
No. amplitude amplitude T in sec In sec
A1 % A2 %
Calculations
Calculate for each observation
Magnitude ratio as M =
A2/A1 Phase angle = (X/T)
x 360 Frequency = 1/T
cycles / sec.
17-04-2017 21 Im314A
Department of Chemical Engineering, Veer Surendra Sai University of Technology Burla
1. Aim of experiment:-
To Study of open loop response (Manual control)
Apparatus Required:-
Pressure control Trainer I/P Converter
Air Regulator
Theory: - Pressure control trainer is
designed for understanding the basic
Air Supply
principles of pressure control. The process
set up consists of pressure vessel fitted with
Supply Signal
pneumatic control valve. Pressure Pressure Pressure
17-04-2017 22 Im314A
Department of Chemical Engineering, Veer Surendra Sai University of Technology Burla
process value.
Apply the step change by 10% to controller output and wait for the process value to reach the
steady state value. Note down the process value.
Repeat the above step until the controller output reaches to minimum 0%.
Observations
Tabulate the observations as follows
From the above data, note the output required for maintaining the process at desired set
points. (For particular vent valve opening).
Set the output of the controller to the noted value and at steady state apply the load change to the
process. Load change can be given by slightly varying the vent valve. Observe new steady state
process value.
17-04-2017 23 Im314A
Department of Chemical Engineering, Veer Surendra Sai University of Technology Burla
Procedure:-
17-04-2017 24 Im314A
Department of Chemical Engineering, Veer Surendra Sai University of Technology Burla
Observations
Observe that if process value exceeds the set point and increases above the value of (0.5x
Hysteresis), control valve is full open and if process value decreases below the set point by (0.5
x Hysteresis), the control valve closes fully i.e. controller operates like On/Off switch.
17-04-2017 25 Im314A
Department of Chemical Engineering, Veer Surendra Sai University of Technology Burla
17-04-2017 26 Im314A
Department of Chemical Engineering, Veer Surendra Sai University of Technology Burla
step change. Ensure that the set point changes are around the same operating point (@ 5-10%
only).
Using trial and error approach, find a value of proportional band so that the response to a step
change has at most one overshoot and one undershoot.
Set the controller to the settings obtained in the above step and wait for the system to reach at
steady state.
Observations
Observe steady state error decreases as proportional band decreases.
Observe the effect of very low proportional band values (system works in oscillatory mode).
Observe the response of the system at load change. Load change can be given by slightly
manipulating the vent valve of the tank.
Study of proportional integral controller
17-04-2017 27 Im314A
Department of Chemical Engineering, Veer Surendra Sai University of Technology Burla
17-04-2017 28 Im314A
Department of Chemical Engineering, Veer Surendra Sai University of Technology Burla
Switch on the controller to manual mode. Reduce the integral time to half of the previous
value. Switch to Auto mode and apply step change to the set point by 2 to 3%. Note the
response of the system.
Using trial and error, find out an integral time, which gives satisfactory response to the step
change in set point.
Observations
Observe the effect of reducing integral time on offset and on the response of the process.
17-04-2017 29 Im314A
Department of Chemical Engineering, Veer Surendra Sai University of Technology Burla
17-04-2017 30 Im314A
Department of Chemical Engineering, Veer Surendra Sai University of Technology Burla
system.
Increase the derivative time gradually and observe the process response for step change.
Observations
Observe the effect of increasing derivative time. Also note that the process may show offset as
effect of integral action is cut off.
17-04-2017 31 Im314A
Department of Chemical Engineering, Veer Surendra Sai University of Technology Burla
17-04-2017 32 Im314A
Department of Chemical Engineering, Veer Surendra Sai University of Technology Burla
Observations
Compare the steady state response of the PID controller with P, PI and PD controller
obtained in the previous experiments.
17-04-2017 33 Im314A
Department of Chemical Engineering, Veer Surendra Sai University of Technology Burla
17-04-2017 34 Im314A
Department of Chemical Engineering, Veer Surendra Sai University of Technology Burla
17-04-2017 35 Im314A
Department of Chemical Engineering, Veer Surendra Sai University of Technology Burla
17-04-2017 36 Im314A
Department of Chemical Engineering, Veer Surendra Sai University of Technology Burla
Repeat the above procedure and find out correct value of proportional band for which the
system just goes unstable i.e. continuous oscillations are observed in the output of
controller.
Record the ultimate proportional band and ultimate period from the response.
Calculate the PID values from the table. Select the PID controller and apply the parameter
values obtained from the above steps. Observe the response of the process to a step change with
these settings.
Observations
Record the ultimate proportional band (Pbu) and ultimate period (Tu) from above
experiment.
Calculate PID values by referring theory part for different control actions.
Observe the process response for these settings.
Compare the values obtained with open loop response method.
17-04-2017 37 Im314A
Department of Chemical Engineering, Veer Surendra Sai University of Technology Burla
17-04-2017 38 Im314A
Department of Chemical Engineering, Veer Surendra Sai University of Technology Burla
17-04-2017 39 Im314A
Department of Chemical Engineering, Veer Surendra Sai University of Technology Burla
10. Aim of the experiment:-
To study stability of the system (Bode plot)
I/P Converter
Apparatus required:-
Pressure control trainer
Air Regulator
Theory: - Pressure control trainer is
designed for understanding the basic
Air Supply
principles of pressure control. The process
set up consists of pressure vessel fitted with
Supply Signal
pneumatic control valve. Pressure
Pressure Pressure
transmitter is used for pressure sensing.
The process parameter (Pressure) is
controlled by microprocessor based digital Pressure Controller
instructions.
17-04-2017 40 Im314A
Department of Chemical Engineering, Veer Surendra Sai University of Technology Burla
Observations
Form the data file stored note down the
Observe the output response of the process and note down the output amplitude. Measure
output wave period and note down as T sec. Measure the phase lag x and note down in sec.
Obs. Input Output Output Period Lag X Frequency
No. amplitude amplitude T in sec In sec
A1 % A2 %
Calculations
Calculate for each observation
Magnitude ratio as M = A2/A1
Phase angle = (X/T) x 360
Frequency = 1/T cycles / sec.
Draw the graphs of: Magnitude Vs frequency on log - log scale
Phase angle Vs frequency on semi-log coordinates.
Study the graph for stability conditions mentioned in theory
17-04-2017 41 Im314A
Department of Chemical Engineering, Veer Surendra Sai University of Technology Burla
Theory: - Level control trainer is designed for understanding the basic principles of level
control. The process setup consists of supply water tank fitted with pump for water
circulation. The level transmitter used for level sensing is fitted on transparent process tank.
The process parameter (level) is controlled by microprocessor based digital indicating
controller which manipulates pneumatic control valve through I/P converter. A pneumatic
control valve adjusts the water flow in to the tank. These units along with necessary piping are
fitted on support housing designed for tabletop mounting.
The controller can be connected to computer through Ethernet / USB port for monitoring the
process in SCADA mode.
LT Pump
Outlet Valve
Control Valve
Procedure:-
Start up set up as explained in general instructions.
Click Select Experiment, select Open Loop and click Start
Open the control valve fully by decreasing the controller output to 0%. (Click on
Auto, Change it to Man then change OP to 0%)
Adjust the tank drain valve such that the tank level shall remain between 90 and 100%
Change the controller to Auto mode
Close the control valve by increasing the controller output to 100%.
17-04-2017 42 output in manual mode, wait for theIm314A
Apply the step change by 10% to controller level
Department of Chemical Engineering, Veer Surendra Sai University of Technology Burla
to reach the steady state value.
Repeat the above step until the controller output reaches to minimum i.e. 0%.
Observations
Tabulate the results as follows
…
0
From the above data, note the output required for maintaining the level at desired set
points. (For particular drain valve opening).
Set the output of the controller to the noted value and at steady state apply the load change
to the process. Load change can be given by slightly varying the drain valve. Observe new
steady state process value.
17-04-2017 43 Im314A
Department of Chemical Engineering, Veer Surendra Sai University of Technology Burla
2.Aim of the experiment:--
To Study of on/off controller
Apparatus Required:-
Level control Trainer
Theory: - - Level control trainer is designed for understanding the basic principles of level
control. The process setup consists of supply water tank fitted with pump for water
circulation. The level transmitter used for level sensing is fitted on transparent process tank.
The process parameter (level) is controlled by microprocessor based digital indicating
controller which manipulates pneumatic control valve through I/P converter. A pneumatic
control valve adjusts the water flow in to the tank. These units along with necessary piping are
fitted on support housing designed for tabletop mounting.
The controller can be connected to computer through Ethernet / USB port for monitoring the
process in SCADA mode.
LT Pump
Outlet Valve
Control Valve
Procedure:-
Start up set up as explained in general instructions.
Click Select Experiment, select On-Off Mode and click Start
Open the control valve fully by decreasing the controller output to 0%. (Click on Auto,
Change it to Man then change OP to 0%)
Adjust the tank drain valve such that the tank level shall remain between 90 and 100% Change
the controller to Auto mode
Change Hysteresis value to 5%.(Range 0.1-10%)
Change the values of the set point and observe the On-Off control operation.
17-04-2017 44 Im314A
Department of Chemical Engineering, Veer Surendra Sai University of Technology Burla
Observations
Observe that if process value exceeds the set point and increases above the value of (0.5x
Hysteresis), control valve is fully closed and if process value decreases below the set point by
(0.5 x Hysteresis), the control valve opens fully i.e. controller operates like On/Off switch.
17-04-2017 45 Im314A
Department of Chemical Engineering, Veer Surendra Sai University of Technology Burla
3. Aim of the experiment:-
Study of proportional controller
Apparatus Required:-
Level control Trainer
Theory: - Level control trainer is designed for understanding the basic principles of level
control. The process setup consists of supply water tank fitted with pump for water
circulation. The level transmitter used for level sensing is fitted on transparent process tank.
The process parameter (level) is controlled by microprocessor based digital indicating
controller which manipulates pneumatic control valve through I/P converter. A pneumatic
control valve adjusts the water flow in to the tank. These units along with necessary piping are
fitted on support housing designed for tabletop mounting.
The controller can be connected to computer through Ethernet / USB port for monitoring the
process in SCADA mode.
LT Pump
Outlet Valve
Control Valve
Procedure:-
Start up set up as explained in general instructions.
Click Select Experiment, select P Mode and click Start
Open the control valve fully by decreasing the controller output to 0%. (Click on Auto,
Change it to Man then change OP to 0%)
Adjust the tank drain valve such that the tank level shall remain between 90 and 100% Change
the controller to Auto mode
Adjust the process value by switching the controller to manual mode to a particular level (say 50
%) on the screen and apply output of the controller as bias value. Change the proportional band
to 100%.
Switch the controller to auto mode.
17-04-2017
Apply step change of 10% to set point. 46 Im314A
Department of Chemical Engineering, Veer Surendra Sai University of Technology Burla
Switch the controller to manual mode. Decrease proportional band to half of the previous
value. With each decrease, obtain a new response of the step change. Ensure that the set
point changes are around the same operating point (Say 50%).
Observations
Observe the effect of very low proportional band values (system works as on-off control).
Observe the response of the system at load change. Load change can be given by slightly
manipulating the drain valve of the tank.
17-04-2017 47 Im314A
Department of Chemical Engineering, Veer Surendra Sai University of Technology Burla
4 .Aim of the Experiment:-
Study of proportional integral controller
Apparatus Required:-
Level Control Trainer
Theory: - Level control trainer is designed for understanding the basic principles of level
control. The process setup consists of supply water tank fitted with pump for water
circulation. The level transmitter used for level sensing is fitted on transparent process tank.
The process parameter (level) is controlled by microprocessor based digital indicating
controller which manipulates pneumatic control valve through I/P converter. A pneumatic
control valve adjusts the water flow in to the tank. These units along with necessary piping are
fitted on support housing designed for tabletop mounting.
The controller can be connected to computer through Ethernet / USB port for monitoring the
process in SCADA mode.
LT Pump
Outlet Valve
Control Valve
Procedure:-
Observations
Observe the effect of reducing integral time on the response of the process.
17-04-2017 49 Im314A
Department of Chemical Engineering, Veer Surendra Sai University of Technology Burla
5. Aim of the Experiment:-
Study of proportional derivative controller
Apparatus Required:-
Level control trainer
Theory: - Level control trainer is designed for understanding the basic principles of level
control. The process setup consists of supply water tank fitted with pump for water
circulation. The level transmitter used for level sensing is fitted on transparent process tank.
The process parameter (level) is controlled by microprocessor based digital indicating
controller which manipulates pneumatic control valve through I/P converter. A pneumatic
control valve adjusts the water flow in to the tank. These units along with necessary piping are
fitted on support housing designed for tabletop mounting.
The controller can be connected to computer through Ethernet / USB port for monitoring the
process in SCADA mode.
LT Pump
Outlet Valve
Control Valve
Procedure:-
Observations
Compare the steady state response of the PD controller with PI controller obtained in the
previous experiment.
17-04-2017 51 Im314A
Department of Chemical Engineering, Veer Surendra Sai University of Technology Burla
6. Aim of the experiment:-
Study of proportional integral derivative controller
Apparatus Required:-
Level control Trainer
Theory: - Level control trainer is designed for understanding the basic principles of level
control. The process setup consists of supply water tank fitted with pump for water
circulation. The level transmitter used for level sensing is fitted on transparent process tank.
The process parameter (level) is controlled by microprocessor based digital indicating
controller which manipulates pneumatic control valve through I/P converter. A pneumatic
control valve adjusts the water flow in to the tank. These units along with necessary piping are
fitted on support housing designed for tabletop mounting.
The controller can be connected to computer through Ethernet / USB port for monitoring the
process in SCADA mode.
LT Pump
Outlet Valve
Control Valve
Procedure:-
Observations:-
Compare the steady state response of the PID controller with P. PI and PD controller
obtained in the above experiment.
17-04-2017 53 Im314A
Department of Chemical Engineering, Veer Surendra Sai University of Technology Burla
7. Aim of the Experiment:-
Tuning of controller (Open loop method)
Apparatus Required:-
Level control trainer
Theory: - Level control trainer is designed for understanding the basic principles of level
control. The process setup consists of supply water tank fitted with pump for water
circulation. The level transmitter used for level sensing is fitted on transparent process tank.
The process parameter (level) is controlled by microprocessor based digital indicating
controller which manipulates pneumatic control valve through I/P converter. A pneumatic
control valve adjusts the water flow in to the tank. These units along with necessary piping are
fitted on support housing designed for tabletop mounting.
The controller can be connected to computer through Ethernet / USB port for monitoring the
process in SCADA mode.
LT Pump
Outlet Valve
Control Valve
Procedure:-
Observations
(Refer Theory process control for formulae.)
Step change to the system P = Initial output - Final output of the controller.
Plot the graph of process value Vs Time on a graph paper.rom process reaction curve:
Slope of the process reaction curve R =
Time lag L=
Calculate P, PI, and PID setting from above values.
Observe response of the system for different PID settings.
17-04-2017 55 Im314A
Department of Chemical Engineering, Veer Surendra Sai University of Technology Burla
8. Aim of the experiment:-
Tuning of controller (Closed loop method)
Apparatus Required:-
Level control Trainer
Theory: - Level control trainer is designed for understanding the basic principles of level
control. The process setup consists of supply water tank fitted with pump for water
circulation. The level transmitter used for level sensing is fitted on transparent process tank.
The process parameter (level) is controlled by microprocessor based digital indicating
controller which manipulates pneumatic control valve through I/P converter. A pneumatic
control valve adjusts the water flow in to the tank. These units along with necessary piping are
fitted on support housing designed for tabletop mounting.
The controller can be connected to computer through Ethernet / USB port for monitoring the
process in SCADA mode.
LT Pump
Outlet Valve
Control Valve
Procedure:-
Observations
Record the ultimate proportional band (Pbu) and ultimate period (Tu) from above
experiment.
Calculate PID values by referring theory part for different control actions.bserve the process
response for these settings.
Compare the values obtained with open loop response method.
17-04-2017 57 Im314A
Department of Chemical Engineering, Veer Surendra Sai University of Technology Burla
9. Aim of the experiment:-
Tuning of controller (Using Auto Tuning method)
Apparatus Required:-
Level Control Trainer
Theory: - Level control trainer is designed for understanding the basic principles of level
control. The process setup consists of supply water tank fitted with pump for water
circulation. The level transmitter used for level sensing is fitted on transparent process tank.
The process parameter (level) is controlled by microprocessor based digital indicating
controller which manipulates pneumatic control valve through I/P converter. A pneumatic
control valve adjusts the water flow in to the tank. These units along with necessary piping are
fitted on support housing designed for tabletop mounting.
The controller can be connected to computer through Ethernet / USB port for monitoring the
process in SCADA mode.
LT Pump
Outlet Valve
Control Valve
Procedure:-
17-04-2017 58 Im314A
Department of Chemical Engineering, Veer Surendra Sai University of Technology Burla
Observations
The controller has preprogrammed logic for finding “Auto tune” values. Based on the
response of the process the controller calculates PID values or comes out without finding the
“Auto tune” values.
17-04-2017 59 Im314A
Department of Chemical Engineering, Veer Surendra Sai University of Technology Burla
10. Aim of the Experiment:-
To study stability of the system (Bode plot)
Apparatus required:-
Level Control Trainer
Theory: - Level control trainer is designed for understanding the basic principles of
level control. The process setup consists of supply water tank fitted with pump for
water circulation. The level transmitter used for level sensing is fitted on transparent
process tank. The process parameter (level) is controlled by microprocessor based
digital indicating controller which manipulates pneumatic control valve through I/P
converter. A pneumatic control valve adjusts the water flow in to the tank. These units
along with necessary piping are fitted on support housing designed for tabletop
mounting.
The controller can be connected to computer through Ethernet / USB port for
monitoring the process in SCADA mode.
LT Pump
Outlet Valve
Control Valve
Procedure:-
17-04-2017 60 Im314A
Department of Chemical Engineering, Veer Surendra Sai University of Technology Burla
Enter Reference point, Amplitude and Period.
Observe the sinusoidal output of the controller and sinusoidal response of the process.
Log the data for records.
Change the period and repeat the observation for 3-4 different values of the period.
Repeat above procedure for different amplitude and period values.
Observations
From the data file stored observe the output response of the process and note
down the output amplitude.
Measure output wave period and note down as T sec. Measure the phase lag x and
note down in sec.
17-04-2017 61 Im314A