Installation Instructions
• Ensure the engine is at rest and the module is in STOP mode by pressing the
(Stop/Reset) button.
• The first ‘#’ changes to ‘0’. Press the (Up) or (Down) button to adjust it to the correct value.
• Press the (Right) button when the first digit is correctly entered. The digit previously entered now shows ‘#’ for security.
• Repeat this process for the other digits of the PIN number. Press the (Left) button to move back to adjust one of the previous
DSE7310 MKII & DSE7320 MKII digits.
• When the (Tick) button is pressed after editing the final PIN digit, the PIN is checked for validity. If the number is not correct,
the PIN must be re-entered.
• If the PIN has been successfully entered (or the module PIN has not been enabled), the editor is
displayed:
EDITING A PARAMETER
• Enter the editor as described above.
• Press the (Up) or (Down) buttons to select the parameter to view/change within the currently selected section.
• To edit the parameter, press the (Tick) button to enter edit mode. The parameter begins to flash to indicate editing.
• Press the (Up) or (Down) buttons to change the parameter to the required value.
• Press the (Tick) button to save the value. The parameter ceases flashing to indicate that it has been saved.
NOTE: Terminals 38, 39, 40 & 41 are not fitted to the DSE7310 MKII. • To exit the editor and save the changes, press and hold the (Tick) button.
NOTE: A larger version of the Typical Wiring Diagram is available in the product’s operator manual, refer to • To exit the editor and not save the changes, press and hold the (Stop/Reset) button.
DSE Publication: 057-253 DSE7310 MKII & DSE7320 MKII Operator Manual available from www.deepseaplc.com for more
information.
NOTE: If the editor is left inactive for the duration of the LCD Page Timer, it is automatically exited to ensure security.
Deep Sea Electronics Plc. Deep Sea Electronics Inc. NOTE: The PIN number is automatically reset when the editor is exited (manually or automatically) to ensure security.
Tel:+44 (0)1723 890099 Tel: +1 (815) 316 8706
Fax: +44 (0)1723 893303 Fax: +1 (815) 316 8708 NOTE: Comprehensive module configuration is possible using the DSE Configuration Suite PC Software, refer to DSE
Email: [email protected] Email: [email protected] publication 057-243 DSE7310 MKII & DSE7320 MKII Configuraiton Suite PC Software Manual available from
Web: www.deepseaplc.com Web: www.deepseausa.com www.deepseaplc.com.