Mulit-Stage: Multi-Pressure Systems
Mulit-Stage: Multi-Pressure Systems
Compression
Refrigeration Systems
1
The objectives of this lesson are to:
1. Introduction
A single stage vapour compression refrigeration system has one low side pressure
(evaporator pressure) and one high side pressure (condenser pressure). The performance of
single stage systems shows that these systems are adequate as long as the temperature
difference between evaporator and condenser (temperature lift) is small. However, there are
many applications where the temperature lift can be quite high. The temperature lift can
become large either due to the requirement of very low evaporator temperatures and/or due to
the requirement of very high condensing temperatures. For example, in frozen food industries
the required evaporator can be as low as –40oC, while in chemical industries temperatures as
low as –150oC may be required for liquefaction of gases. On the high temperature side the
required condensing temperatures can be very high if the refrigeration system is used as a
heat pump for heating applications such as process heating, drying etc. However, as the
temperature lift increases the single stage systems become inefficient and impractical. For
example, Fig. 1 shows the effect of decreasing evaporator temperatures on T s and P h
diagrams. It can be seen from the T s diagrams that for a given condenser temperature, as
evaporator temperature decreases:
2
i. Throttling losses increase
ii. Superheat losses increase
iii. Compressor discharge temperature increases
iv. Quality of the vapour at the inlet to the evaporator increases
v. Specific volume at the inlet to the compressor increases
As a result of this, the refrigeration effect decreases and work of compression increases as
shown in the P h diagram. The volumic refrigeration effect also decreases rapidly as the
specific volume increases with decreasing evaporator temperature. Similar effects will occur,
though not in the same proportion when the condenser temperature increases for a given
evaporator temperature. Due to these drawbacks, single stage systems are not recommended
when the evaporator temperature becomes very low and/or when the condenser temperature
becomes high. In such cases multi-stage systems are used in practice. Generally, for
fluorocarbon and ammonia based refrigeration systems a single stage system is used upto an
evaporator temperature of –30oC. A two-stage system is used upto –60oC and a three-stage
system is used for temperatures below –60oC.
Apart from high temperature lift applications, multi-stage systems are also used in
applications requiring refrigeration at different temperatures. For example, in a dairy plant
refrigeration may be required at –30oC for making ice cream and at 2oC for chilling milk. In
such cases it may be advantageous to use a multi-evaporator system with the low temperature
evaporator operating at –30oC and the high temperature evaporator operating at 2oC
3
T
2’’
2’
2
4
1
4’
1’
4’’
1’’
Ss
3 2 2’ 2’’
4 1
4’ 1’
1’’
4’’
4
A multi-stage system is a refrigeration system with two or more low-side pressures. Multi-
stage systems can be classified into:
a) Multi-compression systems
b) Multi-evaporator systems
c) Cascade systems, etc.
Two concepts which are normally integral to multi-pressure systems are, i) flash gas
removal, and ii) intercooling. Hence these concepts will be discussed first.
5
3
6 From To compressor
condenser
Flash tank
8
9
To evaporator
Expansion valve
Pc
6
Pi 8 3
7
Pe
9 9’
2
æ n ö é æ P ö (n-1) / n ù
w = -ò v.dP =ç ÷P1v1 ê1- ç 2 ÷ ú (2.1)
1 è n - 1ø êë è P1 ø úû
6
where P1 and P2 are the inlet and exit pressures of the compressor, v1 is the specific volume
of the refrigerant vapour at the inlet to the compressor and n is the polytropic exponent. From
the above expression, it can be seen that specific work input reduces as specific volume, v1 is
reduced. At a given pressure, the specific volume can be reduced by reducing the
temperature. This is the principle behind intercooling in multi-stage compression. Figures
2.4 (a) and (b) show the process of intercooling in two-stage compression on Pressure-
specific volume (P-v) and P-h diagrams.
P
4 2’
Savings in
sp. work 4
2’
P 2
3 3
2
1
1
h
v
As shown in the figures, in stead of compressing the vapour in a single stage from state 1 to
state 2’, if the refrigerant is compressed from state 1 to an intermediate pressure, state 2,
intercooled from 2 to 3 and then compressed to the required pressure (state 4), reduction in
work input results. If the processes are reversible, then the savings in specific work is given
by the shaded area 2-3-4-2’ on P-v diagram. The savings in work input can also be verified
from the P-h diagram. On P-h diagram, lines 1-2-2’ and 3-4 represent isentropes. Since the
slope of isentropes on P-h diagram reduces (lines become flatter) as they move away from the
saturated vapour line,
7
4
Refrigerant
liquid from 3
condenser
2 High-stage
compressor
Flash
tank Low-stage
compressor
4
Water out Water in
High-stage
2 Compressor
Water-cooled
heat exchanger
1
Low-stage
Compressor
Intercooling using liquid refrigerant from condenser in the flash tank may or may not
reduce the power input to the system, as it depends upon the nature of the refrigerant. This is
due to the fact that the heat rejected by the refrigerant during intercooling generates
additional vapour in the flash tank, which has to be compressed by the high stage compressor.
Thus the mass flow rate of refrigerant through the high stage compressor will be more than
that of the low stage compressor. Whether total power input to the system decreases or not
depends on whether the increased power consumption due to higher mass flow rate is
8
compensated by reduction in specific work of compression or not. For ammonia, the power
input usually decreases with intercooling by liquid refrigerant, however, for refrigerants such
as R12, R22, the power input marginally increases. Thus intercooling using liquid refrigerant
is not effective for R12 and R22. However, as mentioned one benefit of intercooling is the
reduction in compressor discharge temperature, which leads to better compressor lubrication
and its longer life.
where Plow and Phigh are the inlet pressure to the low-stage compressor and exit pressure from
the high-stage compressor, respectively. The above relation is found to hold good for ideal
gases. For refrigerants, correction factors to the above equation are suggested, for example
one such relation for refrigerants is given by:
Tc
Pi,opt = Pe.P c (2.4)
Te
where Pe and Pc are the evaporator and condenser pressures, and Tc and Te are condenser and
evaporator temperatures (in K).
Several combinations of multi-stage systems are used in practice. Some of them are
discussed below.
9
Qc B B
Condenser
5
6
4 Compressor - II
3 WII
7
Flash
chamber Water intercooler
Qi
2
8
1 Compressor - I
9
Evaporator WI
Qe
Fig.2.6(a): Two-stage vapour compression refrigeration system with flash gas removal using a
flash tank and intercooling
Pc 6
5
8 7 4 3
Pi
2
Pe
9 1
h
Fig.2.6(b): Two-stage vapour compression refrigeration system with flash gas removal using a
flash tank and intercooling – P-h diagram
10
From mass and energy balance across expansion valve,
. .
m8 = m9 (2.7)
h8 = h9 (2.8)
From mass and energy balance across evaporator:
. .
m 9 = m1 (2.9)
.
Q e = m 1 (h 1 - h 9 ) (2.10)
where QI is the heat transferred by the refrigerant to the cooling water in the intercooler.
From the above set of equations, it can be easily shown that for the flash tank:
. . .
m 7 = m 4 = m II (2.21)
. . .
m3 = m8 = mI (2.22)
. . éh - h ù
3 8
m II = m I ê ú (2.23)
ëh4 - h7 û
11
It can be seen from the above expression that the refrigerant flow through the high-
.
stage compression mII can be reduced by reducing the enthalpy of refrigerant vapour entering
into the flash tank, h3 from the water-cooled intercooler.
. . éh - h ù
m gen = m I ê 3 4
ú (2.24)
ëh4 - h8 û
.
Thus the vapour generated m gen will be zero, if the refrigerant vapour is completely de-
superheated in the water-cooled intercooler itself. However, this may not be possible in
practice.
a) Quality of refrigerant entering the evaporator reduces thus giving rise to higher
refrigerating effect, lower pressure drop and better heat transfer in the evaporator
b) Throttling losses are reduced as vapour generated during throttling from Pc to Pi is
separated in the flash tank and recompressed by Compressor-II.
c) Volumetric efficiency of compressors will be high due to reduced pressure ratios
d) Compressor discharge temperature is reduced considerably.
However, one disadvantage of the above system is that since refrigerant liquid in the flash
tank is saturated, there is a possibility of liquid flashing ahead of the expansion valve due to
pressure drop or heat transfer in the pipelines connecting the flash tank to the expansion
device. Sometimes this problem is tackled by using a system with a liquid subcooler. As
shown in Fig.2.7, in a liquid subcooler the refrigerant liquid from the condenser is
subcooled by exchanging heat with the refrigerant liquid in the flash tank. As a result, a small
amount of refrigerant vapour is generated in the flash tank, which needs to be compressed in
the high-stage compressor. Compared to the earlier system, the temperature of refrigerant
liquid from the subcooler will be higher than the saturated refrigerant temperature in the flash
tank due to indirect contact heat transfer. However, since the refrigerant at the inlet to the
expansion valve is at high pressure and is subcooled, there is less chance of flashing of liquid
ahead of expansion valve.
12
From
6 condenser To high-stage
3 compressor
Liquid
subcooler
8 To
Expansion evaporator
valve
Fig.2.7: Refrigeration system with liquid subcooler
13
Condenser
6 5
3 4 Compressor - II
7 Flash
chamber
8 1 Compressor - I
9
Evaporator
6
5
8 7 3
4 2
9 1
Fig.2.8: A two-stage compression system with flash tank for flash gas removal only
(a) System schematic; (b) Cycle on P-h diagram
14
Condenser
5 4
3 Compressor - II
6
Flash
chamber
1 Compressor - I
7
Evaporator
5
4 2'
6 3
2
7 1
Fig.2.9: A two-stage compression system with the flash tank used for intercooling only
(a) System schematic (b) Cycle on P-h diagram
15
Questions:
1. When the temperature lift of a single stage vapour compression refrigeration system
increases:
Ans.: b)
Ans.: a) and c)
Ans.: a) , c) and d)
Ans.: b)
Ans.: a) and b)
16
6. Assuming the refrigerant vapour to behave as an ideal gas and with perfect intercooling,
the optimum intermediate pressure of a refrigeration system that operates between 4 bar and
16 bar is equal to:
a) 10 bar
b) 8 bar
c) 6 bar
d) 12 bar
Ans.: b)
Ans. b)
a) Refrigerant mass flow rates in both low and high stage compressors are equal
b)Refrigerant mass flow rates in high stage compressors is greater than that in low stage
compressor
c)Refrigerant mass flow rates in high stage compressors is smaller than that in low stage
compressor
d)Mass flow rates in low and high stage compressors are equal if the pressure ratios are
equal
Ans.: b)
Ans.: b) and c)
17
10. The required refrigeration capacity of a vapour compression refrigeration system (with R-
22 as refrigerant) is 100 kW at –30oC evaporator temperature. Initially the system was single-
stage with a single compressor compressing the refrigerant vapour from evaporator to a
condenser operating at 1500 kPa pressure. Later the system was modified to a two-stage
system operating on the cycle shown below. At the intermediate pressure of 600 kPa there is
intercooling but no removal of flash gas. Find a) Power requirement of the original single-
stage system; b) Total power requirement of the two compressors in the revised two-stage
system. Assume that the state of refrigerant at the exit of evaporator, condenser and
intercooler is saturated, and the compression processes are isentropic.
condenser
1500 kPa
intercooler
-18oC
1st1stage
st
stage
evaporator compressor
compressor
(100 kW)
Ans.:
From refrigerant property data, the following values are obtained for R 22:
18
a) Single stage system:
3 2
4 1
3 2’” 2
4’ 2’
2”
4 1
h
Required refrigerant mass flow rate through evaporator and 1st stage compressor
(mr,1) is same as that of single stage system, i.e.,
19
Power input to 1st stage compressor, Wc,1 is given by:
Wc,1 = mr,1(h2’ - h1) = 0.693(424.4 - 392.7) = 21.97 kW
The mass flow rate of refrigerant vapour through 2nd stage compressor (mr,2) is
obtained from energy balance across intercooler:
From property data, the discharge temperatures at the exit of 1st and 2nd stage
compressors are given, respectively by:
T2’ = 28.94oC
T2’” = 53.55oC
Comments:
It is observed from the above example that for the given input data, though
the use of a two-stage system with intercooling in place of a single stage system
does not increase the COP significantly (» 1.2 %), there is a significant reduction in
the maximum compressor discharge temperature (» 24oC). The results would be
different if the operating conditions and/or the refrigerant used is different.
20