TNVAMC - EN003 A Using SPA ZC 17 With VAMP Relays

SPA-ZC 17 is a bus connection module that has its own internal power supply and connects to devices like VAMP relays via a 9-pin cable. When connecting SPA-ZC 17 to a VAMP relay, the wire in pin number 4 of the cable must be cut as VAMP relays use a TTL interface for their remote ports unlike the SPA-ZC 17 module. This technical note provides guidance on using SPA-ZC 17 modules with VAMP series protection relays but not for arc protection relays.

Uploaded by

Magdi Abdelhalim
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
59 views1 page

TNVAMC - EN003 A Using SPA ZC 17 With VAMP Relays

SPA-ZC 17 is a bus connection module that has its own internal power supply and connects to devices like VAMP relays via a 9-pin cable. When connecting SPA-ZC 17 to a VAMP relay, the wire in pin number 4 of the cable must be cut as VAMP relays use a TTL interface for their remote ports unlike the SPA-ZC 17 module. This technical note provides guidance on using SPA-ZC 17 modules with VAMP series protection relays but not for arc protection relays.

Uploaded by

Magdi Abdelhalim
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

[ Technical note ] Using SPA-ZC 17 with VAMP relays

Using SPA-ZC 17 with VAMP relays

This Technical note applies to VAMP 200 series protection relays (not Arc
protection)

ABB's SPA-ZC 17 is a Bus connection module, which is not powered from the SPA device
(e.g. VAMP relay) but instead it has its own internal power supply. SPA-ZC 17 is normally
connected to a SPA device with a cable which has 9-pin D-connectors in both ends and
direct connection between pins 1, 2, 3, 4, 7 and 9.

When SPA-ZC 17 is connected to a VAMP relay (REMOTE port with TTL interface) the
wire in pin number 4 must be cut.

Schneider Electric
35 rue Joseph Monier
92506 Rueil-Malmaison
© 2018 Schneider Electric Industries SAS - All rights reserved.
FRANCE
Electrical equipment should be installed, operated, serviced,
Phone: +33 (0) 1 41 29 70 00 and maintained only by qualified personnel. No responsibility
Fax: +33 (0) 1 41 29 71 00 is assumed by Schneider Electric for any consequences
arising out of the use of this material.
www.schneider-electric.com

Publishing: 09/2018

1 TNVAMCEN.EN003_A

You might also like