How To Diagnose Differential Protection Issues When All Protective
How To Diagnose Differential Protection Issues When All Protective
Description: Alternative method for troubleshooting differential protection for Arc Flash.
Category: Arc Flash, One-Line display options, CT component In/Out of Service display.
Type: Informative
Keywords: Display Options, Arc Flash, CT, differential, 87 relay function.
Answer
1) When differential elements (87 relay function) protecting a zone are not tripping as
expected and all of the setup options inside the Protective Devices have been double
checked, please make sure the CT components are in service. This can be done by
enabling the display option PT & CT > “ID” in the One-Line, this will display the grayed
out CT name for components that are “Out of Service”.
This document is confidential and proprietary to Operation Technology, Inc. and may not be reproduced, published or disclosed to
others without the written authorization of Operation Technology, Inc., 17 Goodyear, Suite 100, Irvine, CA 92618, USA. © 2011 by
Operation Technology, Inc. All Rights Reserved.
2) Another option to check when Differential Functions are not tripping as expected under
Arc Flash is the “Current Summer” option. Please make sure this option is unchecked
under the “Input” tab of the Relay Editor window.