Ewcm4180 Eng

The document summarizes an EWCM 4180 compressor rack controller model. It has the following key features: - Controls inverter compressors and condenser capacity with frequency modulation. - Balances operating hours of compressors and fans. - Controls temperature/pressure with up to four output levels or variable frequency. - Displays pressure, suction temperature, or condensing temperature in user-selected units. - Configurable start sequence, compressor selection, alarm history, and two-level password protected programming.

Uploaded by

SNOOPY YT
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
57 views2 pages

Ewcm4180 Eng

The document summarizes an EWCM 4180 compressor rack controller model. It has the following key features: - Controls inverter compressors and condenser capacity with frequency modulation. - Balances operating hours of compressors and fans. - Controls temperature/pressure with up to four output levels or variable frequency. - Displays pressure, suction temperature, or condensing temperature in user-selected units. - Configurable start sequence, compressor selection, alarm history, and two-level password protected programming.

Uploaded by

SNOOPY YT
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

CRN TECNOPART, S.A.

Sant Roc 30
08340 VILASSAR DE MAR (Barcelona)
K Tel 902 404 748 - 937 591 484 Fax 937 591 547 EW-090.20E
e-mail:[email protected] http:// www.crntecnopart.com

EWCM 4180
COMPRESSOR RACK CONTROLLERS

MODEL VOLTAGE
EWCM 4180 12V
ACCESSORIES
TRANSFORMER 230/12 V 5.6 VA
CONNECTING CABLE DIGITAL OUTPUTS 9V
16V INPUT CABLE CONNECTION
ANALOG OUTPUT CABLE CONNECTION

»Control inverter compressor.


'Control of condensation with frequency.
"Balanced the operating hours of compressors and / or fans.
"Control of temperature / pressure suction 4escalones up to power, compressors or without
with capacity regulation and even possibility of using a compressor with variable frequency.
"Pressure control of condemnation by a frequency or up to four output levels
»Ability to view the pressure / suction temperature or condensation in Bar / PSI or º C / º F as probe
regulation (Pressure / Temperature).
"Possibility of configuring the default display in suction pressure, discharge pressure, set regulatory
Time ...
"Starting in fixed sequence compressor / saturation / balance.
"Selection and deselection of compressors from the keyboard. Compressors online or offline.
»History of alarms to a maximum of 100 events. Each event logs: the alarm type, date and time
initiation of alarm, date and time of order, type of alarm.
»Protocol ModBus and Televis
"Two levels of access to password-protected programming.

TECHNICAL DATA
»Voltage 12Vac INSTRUMENT IMPUT INSTRUMENT OUTPUT
»Dimensions: 76.4 x 35 x 67mm Input high ON / OFF compressor /
»Standard mounting hole 29x71mm. 1 pressure alarm 10 power step 1
VDegree of protection IP65 Input low pressure ON / OFF compressor /
"Analog inputs configurable as two 2 alarm 11 power stage 2
NTC temperature probe,
Input current 4 ... 20mA Compressor 1 ON / OFF compressor /
3 thermal input 12 power step 4
entry into voltage 0 ... 5V, 0 ... 10V
or a free digital input power Compressor 2 ON / OFF Compressor /
4 thermal input 13 Power Step 3
»7 digital inputs free of tension
»5 digital outputs 2A Compressor 3 Alarm ON / OFF (EWCM
»A low-voltage digital output (open collector) 5 thermal input 17 4180)
for external relay Entry thermal
»2 Analog outputs PWM / Open collector 6 compressor 4
»Internal clock with calendar year Entry block
»TTL connector for connection-card Copy 7 machine
or for connection Televis System / ModBus RTU
by BusAdapter Condensing
8 pressure probe
Suction pressure
9 probe
WIRING DIAGRAM

[12 Vac] Power supply 12Vac


[5 Vcc] Power trasducer 5 Vcc
[12 Vdc] Auxiliary power output available for A01
and D05 12Vdc
[D01]...[D06] Output relay 230 Vac
[N] Neuter
[TC] Output Triac 2A 230Vac
[A01]/[A02] Output PWM open collector for external
fan module
[A03] Analog output 0/10V 4-20mA, 0-20mA for
external fan module
[D05] Output opencollector use 12 V
[D11]...[D15] Digital Inputs voltage free( isolate from
electrical supply to ground closure 0,5
mA)

[A11 (D16)] Digital Input voltage free


[A12 (D17)]

[GND] Ground
[TTL] Serial output for Copy card, Param
Manager or Televis
KEY unutilized