FlowCon FN02 02-BUS 04 Instruction
FlowCon FN02 02-BUS 04 Instruction
4
1B95080 - 01/2023
Figure 1
Do not connect power to the actuator unless
the actuator is already fitted on the valve
and NEVER install the actuator in closed
position - this may damage the valve. Actu-
ator is supplied in open position to ensure
easy commissioning of the system.
Figure 3
Wiring
FlowCon FN (analog)
FN.0.2 Actuator FN.0.2-BUS Actuator
0(2)-10V modulating Yellow RS-485 Serial
Brown
Yellow
Green
Green
White
Black
Violet
Grey
Grey
Blue
Pink
Red
Input signal Feedback signal
0(2)-10V DC 0(2)-10V DC
<0.5mA
D+ D- P1 P2
Power 24V AC/DC Power 24V AC/DC
Ground/common Ground/common
Signal ground
FlowCon FN (digital)
FN.0.4 Actuator FN.0.4 Actuator
2-Position, Normally Closed 3-Point Floating, Normally Closed
Brown
Brown
Grey
Grey
Blue
Blue
Stop
Close Open Close Open
Ground/common Ground/common
Override
For FN.0.2 and FN.0.4 electrical override is acti-
vated by moving DIP switch #6 from OFF to ON.
Then the valve will open fully. During override
mode the LED indicator will blink red and green.
When DIP switch #6 is moved back to OFF, the
actuator will re-calibrate and thereafter go into
normal operation mode. Electrical override is
performed with power supply on.
#3 % Normally Open %
% % % 3 % Normally Closed
2
#2 Control signal 2-10V Control signal 0-10V
1
#1 Auto cycle ON Auto cycle OFF
#5 1 BIT 4 = 1 5 0 BIT 4 = 0
#4 1 BIT 3 = 1 4 0 BIT 3 = 0
3
#3 1 BIT 2 = 1 0 BIT 2 = 0
2
#2 1 BIT 1 = 1 0 BIT 1 = 0
1
#1 1 BIT 0 = 1 0 BIT 0 = 0
LED Status
The LED indicator is visible through the dark colored transparent connection cover.
The LED indication will give the following statuses.
Re-Calibration
FN.0.2
Re-calibration can be achieved in one of 2 ways:
1. Forced individual actuator re-calibration can also be performed by flipping DIP switch #6
from OFF to ON and back to OFF on the relevant actuator.
2. Forced concurrent re-calibration for all modulating actuators is electrically possible. Within 60
sec. provide the following electrical control signal sequence to the grey wire: 10V-2V-10V-2V-
10V-2V to achieve re-calibration.
After re-calibration the actuator will go into normal operation mode.
FN.0.2-BUS
For FN.0.2-BUS change MSV.1 to 2 (BACnet) or register 138 to 1 (Modbus).
After re-calibration the actuator will go into normal operation mode.
FN.0.4
Forced individual actuator re-calibration can also be performed by flipping DIP switch #6 from OFF
to ON and back to OFF on the relevant actuator.
After re-calibration the actuator will go into normal operation mode.
FlowCon International assumes no responsibility for mistakes, if any, in any printed material.