4 15 2 LFAA 102 SM
4 15 2 LFAA 102 SM
4 15 2 LFAA 102 SM
Auto-Reclose Relay
Service Manual
ALSTOM T&D Protection & Control Ltd, St Leonards Works, Stafford ST17 AU(, England
Tel: +44 (0) 1785 22325 1 Fax: +44 (0)1785 2 12232
SAFEN SECTION
This Safety Section should be read before commencing any work on the
equipment.
Hëalth and safety
The information in the Safety Section of the product documentation is intended to
ensure that products are properly installed and handled in order to maintain them
in a safe condition. It is assumed that everyone who will be associated with the
equipment will be familiar with the contents of the Safety Section.
Explanation of symbols and labels
The meaning of symbols and labels which may be used on the equipment or in the
product documentation, is given below.
-1
=
Note: thir symbol rnay also be used for a protedive/
safety earth terminal if that terminal is part of a
terminal block or sub-assembly eg. power supply.
y-.
*Note:The term earth used throughout the product documentation is the direct
equivalent of the North American term ground.
A Equipment connections
Personnel undertaking installation, commissioning or servicing work on this
equipment should be aware of the correct working procedures to ensure safeiy.
The product documentation should be consulted before installing, commissioning or
servicing the equipment.
Terminals exposed during installation, cornmissioning and maintenance may
present a hazardous voltage unless the equipment is electricaHy isolated.
If there is unlocked access to the rear of the equipment, care should be taken by al1
personnel to avoid electric shock or energy hazards.
Voltage and current connections should be made using insulated crimp
terminations to ensure that terminal block insulation requirements are maintained
for safety. To ensure that wires are correctly terminated, the correct crimp terminal
and tool for the wire size should be used.
Before energising the equipment it must be earthed using the protective earth
terminal, or the appropriate termination of the supply plug in the case of plug
connected equipment. Omitting or disconnecting the equipment earth may
cause a safety hazard.
The recommended minimum earth wire size is 2.5 mm2, unless otherwise
stated in the technical data section of the product documentation.
Before energking the equipment, the following should be checked:
Voltage rating and ~olarity;
CT circuit rating and integriîy of connections;
Protective fuse rating;
Integrity of earth connection (where applicable)
A
) Where external resistors are fitted to relays, these may present a risk of electric
shock or burns, if touched.
Batîery replacement
Where interna1 batteries are fitted they should be replaced with the recornmended
A
) iype and be installed with the correct polarity, to avoid possible damage to the
equipment.
lnsulation and dielectric strength testing
A These must not be inserted into or withdrawn from equipment whilst it is energised,
since this may result in darnage.
Fibre optic communication
A
)
Where fibre optic communication devices are fitted, these should not be viewed
directly. Optical power meters should be used to deterrnine the operation or signal
level of the device.
Older Products
Electrical adjustments
A
A
Pieces of equipment which require direct physical adjustments to their operating
mechanism to change current or voltage settings, should have the electrical power
removed M o r e making the change, to avoid any risk of electric shock.
Mechanical adjustrnents
The electrical power to the relay contacts should be removed before checking any
mechanical settings, to avoid any risk of electric shock.
Draw out case relays
A
Removal of the cover on equipment incorporating electromechanical operating
elements, may expose hazardous live parts such as relay contacts.
insertion and withdrawal of extender cards
A
A
When using an extender card, this should not be inserted or withdrawn from the
equipment whilst it is energised. This is to avoid possible shock or damage
hazards. Hazardous Iive voltages may be accessible on the extender card.
Insertion and withdrawal of heavy current test plugs
A- When using a heavy current test plug, CT shorting links must be in place before
insertion or removal, to avoid potentially lethal voltages.
PUBLICATION R4076
cHAJ?TER 1 GENERAL DESCRIPTION
CHAPTER 2 APPLICATION NOTES
CHAPTER 3 INSTALLATION AND HANDLING
CHAPTER 4 HARDWARE DESCRTPTION
CHAPTER 5 FUNCïIONAL DESCRIPTION
CHAPTER 6 SOFTWARE DESCRIF'TION
CHAPTER 7 OPERATING INSTRUCTIONS
îHAPTER 8 COMMISSIONING INSTRUCTIONS
CHAPTER 9 FAULT FINDING
CHAPTER 10 APPENDIX
WAAlO2
SERVICE MANUAL
CHAPTER 1
GENERAL DESCRIPTION
LFAA102 R-5930
Service Manual Chapter 1
Page 1 of 1
The LFAA relays are a range of auto-reclose relays providing facilities for single or
two shot reclosing of one or two circuit breakers. The scheme logic is produced,
documented and encoded in software as a ladder diagram, using an IBM Personal
Cornputer.
The LFAA relays are briefly described in publication R4076.A Nler description of
each pariicular scheme is given in the appropriate scherne documentation,c o n s i s ~ g
of a ladder diagram and description. The hardware and operational aspects of the
relays are covered in the appropriate section of this manual.
Types LFAA 1O 1, 102
Auto-RecIose Relay
Midos Types LFAA 10 1, 102 9
Auto-Reciose Relay
Figure I : LFAA relay with hinged front cover open to show the modular construction
4
Features Models Available Benefits ba
a-2
Serial &
LED
indications pOrallei
\/O ports
A
K oux~hary + "
t195V
~UPP'Y DC/DC converter -1 9 5V Operotor ~nterface 4
vx 1 - t24V 4
ov
LCD Keypod
I-
------
- -
Figure 2 LFAA relay block dragram
Application phase auto-reclose if protection two pole trip of the circuit breaker into
re-operates during the reclaim time a three pole trip.
The LFAA auto-reclose relay provides after the first reclose LFAA 102
facilities for single or twc-shot
Two breaker schemes (LFAA 102) Single phase outc-reclosures can be
reclosures of one or two circuit
either of the simultaneous or
breakers following their tripping for a Combinations of single and three
sequential type depending on the
fault on an overhead line. The phase auto-reclose as above
programme selected. Whenever
reclosures con be selected to be either Circuit breakers con be closed simultaneous reclosure is selected,
high speed single-phase, or high simultaneously or sequentially on both circuit breakers will trip single
speed or delayed three-phase. the first shot and reclose simultaneously
When three-phase reclosure is desired
A block diagram i s shown in Figure 2. aber the single phase dead time.
the equipment will convert any single
Whenever sequential reclosure i s
or two-phase tripping into three-phase
tripping before initiating the reclosure.
Description - Srhcme selected, the leader circuit breaker
will trip single phase and reclose after
For schemes with two circuit breakers Scheme initiation enabling conditions the single phase dead time but the
the reclosure of the second circuit follower circuit breaker will grip three
An auto-reclose cycle is initiated by
breaker can be either simultaneous phase and reclose after the selected
protection operation. Auto-reclose of a
with the first circuit breaker or it con follower circuit breaker delay time has
specific circuit breaker i s enabled
be sequential. In the latter case the
provided that, immediately prior to the elapsed.
reclosure of the second circuit breaker
protection operation: Three phase auto-reclose
=
-- must naturaily be a delayed three
phase reclosure. - the circuit breaker is closed Three phase auto-reclose can be
- The 'Energy' input from that circuit initiated by single phase faults only,
Different operating cycles can be
breaker indicates sufficient stored multi-phase faults only or any fault
selected using the keypad on the relay
energy to perform an auto-reclose depending on the scheme selected
front-plate. These allow the relay to
cycle and whether the auto-reclosure is first
perform various combinations of the
.or second shot. In the case of faults
following cycles: - auto-reclose for that circuit breaker i s
which result in the tripping of one or
not switched out of service and is not
One breaker schemes (LFAA 1O1) two poles of the circuit breaker, the
locked out
reloy will convert the single or two
-Single shot scheme:
Scheme initiation pole trip into a three pole trip before
- single phase auto-reclose
initiating three phase reclosing.
- single phase or three phase - auto Single phase auto-reclose
reclose, depending on type of LFAA 10 1 and LFAA 102 LFAA102: auto-reclose of follower
fault For single phase outo-relose, a phase- circuit breaker
- three phase auto-reclose for al1 to-earth fault on ony one phase will The follower circuit breaker can be
types of fault initiate single phase tripping and auto. automatically switched to the auto-
~Two shot scheme: reclose of the faulty phase only. A reclose programme originally selected
any of the obove cycles for the first fault involving two of more phases will for the leader circuit breaker if any
shot, followed by delayed three- result in three phase tripping. For this one of the initiation enobling
purpose the scheme will convert any
conditions for the leader circuit
breaker i s not satisfied. In the
t DC auxilliary supply Vx2-
sequential single phase or single and 1
k-' IWitCh
in
81
i l 1
-
three phase auto-reclose programme, 1
I
one or two shot, the follower circuit Swikh out 83
2
breaker will be autornatically switched
to perform a single phase trip on
scheme initiation if any one of the
'AIR initiote'
above conditions exists. Single phase signols
reclosure of the follower circuit [rom
breaker will occur at the end of the protection
Scheme reset
sync check - 820
- i 26
,
I
C B A/R lwkout
indicotion
O 'Autoreciose
~4
in Progresr'
indication CB2 'phases no1
togetherl protn.
inhibit
~4 Direction01 eorth
fauh protection
inhibit . Trip CB2
3 phase
inhibit power
swing blocking
___.
: inhibit
zone 1 extension
CB2 close'
4
-0 indication
,
voltage
4 in service' 4 selection CB2
- G23
CBl maintenonce
rimer test
do
-
olorm CB2 maintenance
alarm
G27
-0 CBl mointenonce
lockout E27 CB2 maintenonce
I~kout
r a t the end of the three dead -if the protection relay has not reset
Scheme lockout
time the correct voltage monitor or or the circuit breaker has not
Single breaker schemes (LFAA 101 ) tripped within the trip fail time
check synchronism conditions are
Scheme lockout will block scheme not satisfied within the preclosing
initiation and operation, preventing check time
automatic reclosure. It occurs for any
-if the closing pulse ends without
of the following conditions:
interruption and the circuit breaker
@thecircuit breaker is in the open i s in the open position
position at the end of the reclaim
-auto-reclose blocking i s initiated
time
-for certain conditions after an
*the protection operates during the
interruption of dc supply
reclaim time following the final shot
Two breaker schemes (LFAA 102)
Circuit breaker lockout will block
scheme initiation and operation of the
relevant breaker, preventing
automatic reclosure; it occurs for any
of the following conditions: l AUTO RECLOSE
1. TERMINAL B 1 : breaker CB1. For circuit breakers with 27. TERMINAL B22:
When this input is energised, either three separate single pole 28. TERMINAL 824:
momentarily or permanently, the auto- mechanisms, input 17 should be
Similar to corresponding inputs 17 to
reclose scheme is switched in to energised either by three 52a
22 but for CB2.
service, provided input terminal 83 is contacts (one from each pole)
connected in series, or by three 52b 29. TERMINAL B26:
not also energised.
contacts connected in parallel. When iwo adjacent circuits in the
2. TERMINAL 83: same boy of a one and a half switch
Software function FNCT 14 should be
When this input is energised, either S/S are each controlled by an
set ON if 52a contacts are used, or
momentarily or permanently, the auto- LFAA 102 reluy, the 'CB2 CONTROL'
OFF if 526 contacts are used.
reclose scheme i s switched out of output (E7 - E8) on each relay should
service. 1 8. TERMINAL B4:
be connected to energise input 29
This input may be energised by a
3. TERMINAL B5: (826) on the adjacent relay. This
normally open or normally closed
4. TERMINAL 87: ensures that in the event of concurrent
contact which indicates that the circuit
auto-reciose cycles on both circuits,
5. TERMINAL B9: breaker CB1 has sufficient stored
the middle CB (CB2) can reclose only
6. TERMINAL B11 energy (eg, oil or gas pressure, or
when the required conditions are
spring fully charged) to perform a
These inputs are energised by single satisfied for both LFAA relays.
complete trip/auto-reclose cycle.
phase or three phase trip repeat (A/R
Software function FNCT 15 should be
initiation) contacts on the protective
set ON or OFF depending on the
relays. If the protection does not have
operating mode of the energy contact.
a separate '3PH trip' output, input 6
if no such contact i s available on the
to terminal B1 1 i s not required.
circuit breaker, this input may be left
7. TERMINAL B13: deenergised, and FNCT 15 set O N .
This input may be energised by a
19. TERMINAL B6:
contact on an intertrip receive repeat
This input in energised by a normally
relay if a direct intertripping scheme is
open output contact on a voltage
in use. If this input is energised, the
monitor (dead line charge, dead bus
auto-reclose reloy will treot it as a
charge or synchronism check) relay,
three phase fault.
and rnust be live at the end of a three
8. TERMINAL B I 5: phase dead time (optional for first
This input is energised by the Block shot - see FNCT 1 1) before the CB
A/R contact of the feeder main close output con be given for CB1.
protection (eg, output 9 6 on
20. TERMINAL B8:
Micrornho, Quadramho or Optimho].
This input may be energised by a
If 81 5 is energised at any time during
norrnally open output contact on a
an auto-reclose cycle, the scherne
separote synchronism check relay, if
locks out.
fast synchronising is required for CB1
9. TERMINAL B 1 7: - see publication R4085 or R4094 for
This input con be energised by a full details.
normally open or normally closed
contact on a line voltage rnonitor
-
Description Hardware User Interface Description - Software
p9
The relay i s housed in a 4U (178mm) The front panel operator interface, The relay software i s divided into
high case suitable for either rack or shown in Figure 5, consists of a 2 row three main groups: the system
panel mounting. The relay uses plug-in 16 character alphanumeric liquid software, the logic controller software,
modules which are individually tested crystal display (Icd] together with a and the scheme logic.
and calibrated in the factory. If seven push-button keypad. With the The system software i s independent of
necessary, modules con be relay cover in position only the the application and is common to oll
exchanged without any need to SELECT/RESET and ACCEPT/READ multi-modular hardware applications.
recalibrate the relay. keys are accessible. Using just these It consists of various diagnostic,
A power supply module converts two keys, it i s possible to view system debugging, input/output, and multi-
power from a dc supply to interna1 details, view (and clear) alarms, view tasking handling facilities. It provides
voltage rails. A power failure counters, view settings, view the status a common software environment
monitoring circuit with alarm output of al1 opto-inputs and output relays within which different application
contact is provided. and perform a timer test. A menu programmes can be developed and
approach has been adopted such that operated.
A status input module receives
the operator, using the Icd, con easily
external plant status and protection The logic controller operating system
andefficiently access a whole range
equipment status signals via opto- interfaces between the system
of useful information.
isolated inputs. software and the scheme logic of the
Burdens (maximum)
Vx(1) or Aux supply (W) Add to auxiliary supply burden ( W ]
Carry continuously 5A ac or dc
Break AC 250VA
DC 5 0 W resistive
2 5 W inductive, L/R = 40ms
(Subject to maxima of 5 A or 300V)
Durability
Loaded contact 10,000 operations, minimum
Unloaded contact 100,000 operations minimum
Electrical environment
High frequency disturbance
IEC 255-22-1: 1988 Class III 2.5 kV peak between independent circuits
and independent circuits and case earth.
1 .O kV peak across terminals of the same
circuit (except metallic contacts).
- -----
Electrostatic discharge
IEC 255-22-2:1989 Class III 8.0kV - discharge in air with cover in place.
DC supply interruption
IEC 255-1 1 :1979 The unit will withstand a 1 0ms interruption
- in the auxiliary supply, under normal
operating conditions, without deenergising.
EMC compliance
89/336/EEC Compliance with the European
Commission Directive on EMC is claimed
via the Technical Construction File route.
Generic standards were used to establish
conformity.
Product safety
72/23/EEC Compliance with European Commission
Low Voltage Directive
Cornpliance is demonstrated by
F
reference to generic safety standards.
-
Atmospheric environment
Temperature
IEC 255-6: 1988 Storage and transit -25°C to +70°C
Operating -25°C to +55"C
IEC 68-2-1:1990 Cold
IEC 68-2-2: 1974 Dry Heat
Humidity
IEC 68-2-3:1969 5 6 daYs at 93% RH and 40°C
Enclosure protection
IEC 529: 1989 IP50 (dust protected)
Mechanical environment
Vibration
IEC 255-21-1: 1988 Response Ciass 1
Seismic
IEC 255-2 1-3:1993
Hinged front
Removable Push buiion
caver
1771 mol ol ,6
oroiection lOmrn rnax
u
t
scale
U=44,45
~olerancébetween
any iwo holes
~. terminal block 8 wiring within a distance
Front S~de of 1 mrn10,4
440
L 443 3
terminal block & wiring
Front Side
All dimensionsin mm Terminal screws. M 4 x 8 biass cheese heod with lockwoshers are ~rovided Mounting screws are not ~rovided
Publication R4076G
CHAPTER 2
APPLICATION NOTES
LFAA102 R5930
Service Manual Chapter 2
Page 1 of 1
The LFAA relays obtain information about the status of the circuit breakers, protection
relays and auxiliary plant by way of auxiliary contacts on the equipment. These
contacts switch a dc voltage to the LFAA which is fltered and stored to indicate the
state (open or closed) of the extemal contact. This information is used in the ladder
diagram software to determine the sequence and timing of the operation of the output
relays. The output relay contacts are voltage free and can be nomally open, normally
closed or change over.
Consult the scheme description for details of the application of any particular scheme.
LFAA102
SERVICE MANUAL
CHAPTER 3
INSTALLATION AND HANDLING
LFAA 102 R-5930
SERVICE MANUAL C W R3
CONTENTS
HANDLING
STORAGE
INSTALLATION
Rack Mounihg
Panel Mounting
Section 1 RECEIVING
Remove the relay from its container and inspect for obvious damage. If damage has
been sustained in transit, a claim should be made immediately to the transport
comanv concerned and a report sent to GEC Measurements, St. Leonards Avenue,
Section 2 HANDLING
The relay in its case is extremely robust and no special precautions are necessary.
However, to prevent the ingress of dirt, it is smngly advised that modules are not
removed from the case.
Section 3 STORAGE
If not required for immediate use, r e t m the relay to its original wrapper and carton
and store in a clean dry place. The silica gel unit supplied with relays delivered outside
the United Kingdom should be heated at 60 - 70°C for one hour before being replaced.
Section 4 INSTALLATION
Relays should be installed in a location free from excessive vibration. The relay cases
can be supplied for either rack or panel mounting.
4.1 Rack Mounting
Relays for rack mounting are supplied in cases designed for housing in standard
483mm (19 inch) racks.
4.2 Panel Mounting
Relays can be supplied for flush or semi-projecting panel mounting. Panels should be
vertical to within 5'. Dimensions, fixing details and cutout sizes for the cases are
shown in the relevant case outline drawing GM0008.
Flush mounted relays are inserted h m the front into the panel cutout and secured by
means of the M5 screws provided.
Semi-projecting mounting relays are fined with an extending collar and are secured
using the same M5 screws as those described for flush mounted relays.
When installation is complete the relay must be set up and cornrnissioned as described
in Section 8.
LFAA 102 R5930
Service Manual Chapter 3
Page 2 of 2
Section 5 EARTHING
Thë relay case earthing terminal on the rear of the relay case must be connected to
earth (ground).
Section 6 SPECIAL HANDLING PRECAUTIONS AGAINST
ELECTROSTATIC DISCHARGE
CHAPTER 4
HARDWARE DESCRIPTION
LFAA102 R-5930
SERVICE MANUAL cHAPTER4
CONTENTS
1 REMY IDENTIFICATION
1.1 Cases
1.2 Schemes
1.3 Modules
MODULE DESCRIPTION
3.1 Power Supply
3.2 Relay Output
3.3 Microcornputer
*-. 3.4 Starus Input
3.5 Front Panel Operator Interface
Table 4 Pin-Out Table for the Front Panel RS232 Serial Connector
Table 5 Pin Connections for the Front Panel Parallel Port for Parallel Printer
and Test Port Connections
4 LINK SETIINGS
4.1 Relay Output Module Link Positions
4.2 Microcomputer Module Link Positions
4.3 Staus Input Module Link Positions
4.4 Front Panel Operator Interface Link Positions
LFAAlCn R-5930
Service Manual Chapter 4
Page 1 of 12
The identifier is marked on a strip fitted into the lower front extrusion of the module.
The first two characiers are always GM for the M4 Muiti-modular Hardware.
Together with the next 4 digits they specify the type of the module. The next 3
characters represent a sequential number and vary according to minor variations such
as the rating of the module. The last letter is a design suffm letter.
The position of a module in a subrack is designated by a number. Module 1 in an
equipment is the module at the left-rnost position of the top subrack, viewing h m the
fiont of the equipment. The remaining modules are numbered sequentially from left to
right, and then f m top to bottom of the case. The module number is marked on a
smp fitted into the top front extrusion of the module. The case also has numbered
smps fitted which indicate the position of each module.
LFAA102 R-5930
Service Manuai Chapter 4
Page 2 of 12
Relevant drawings:
G M 0008 -
Outline and mounting details of 4U modular case rack and panel
mounting
GM 0054 014 LFAAlOl arrangement diagram - rack mounting
GM 0055 014 LFAAlOl arrangement diagram - panel mounting
GM 0054 O15 IJFAA102 arrangement diagram - rack mounting
GM 0055 015 LFAA102 arrangement diagram - panel mounting
The WAA relays are housed in a single tier, 4U (178mm) high, rack or panel
munting case. The case has been particularly designed for adequate screening of high
speeû e l m n i c circuitxy. The whole case including the front cover is made in steel. A-
The relay is of modular design and modules are locaîed and slide in grooves in plastic
insulating material. Interposed between the plastic grooves and the outer case are two
N1size upper and lower aluminium plates which are insulated from the outer case.
Each module has a complete aluminium side plate which provides both mechanical
strength and electrical screening to the electronic circuitry. The side plates are
elecmcally connecta! to the upper and lower plates by means of spring clips. This
interna1 screen is wmected to the case at a single earthing point at the top of a terminal
block. The arrangement gives a Faraday cage effect within the outer case. The purpose
is to divert ail electromagnetic noise and interference h m inter-module couplhg via a
low impedance path to a single earthing point.
The LFAAlOl consists of 5, and the LFAA102 of 6, modules and a hinged front
panel:
Module Number Function
Power supply unit
Output module 1
Output module 2
Output module 3
Micmcanputer
96 Status input module
Front panel Operator interface
The arrangement diagrams show the relative positions of the modules within the case.
Extemal connections for output contacts and status inputs are made via standard 28
way MIDûS connectors mounted on the rear of the relay.
There is no back plane wiring in the relay. All inter module wiring is done by means
of a 64 way ribbon cable (the UO bus) behind the hinged front panel. By this means
ail the electronic signals and intemal power rails between modules are spaced as far as
possible fiom the incoming wiring. As show in Figure 1, appendix the VO bus mns
dong the front of the modules and is terminated at the frontpanel assembly.
Connections are made to the modules by a two part hsulation displacement connecter
(IDC). Modules are locked in position by two horizontal bars mounted on the rear of
the front plate.
The hardware architecture is shown in Figure 2, Appendix .The microp~~~essor
module controls all the modules on the I/O bus.
LFAA102 R-5930
Service Manuai Chapter 4
Page 3 of 12
The power supply module (Figure 3, Appendix) is a size 2 module containing one
printed circuit board.
The function of the module is to supply four internal dc voltage rails from the single
auxiliary dc input supply. It is a switched mode power supply design and the output
rails are N l y isolated h m the input.
Externai connections are made via a 28 way MIDOS comector. The power supply
output rails are distributed to the other modules in the equiprnent via the VO bus. The
four internai voltage rails are:
+6.5V This is regulated to +5 V locdly in each of the inputIoutput modules to
power the logic circuitry.
f19.W The dual voltages used in other relays in the standard hardware range,
where they are regulated in respective modules where necessary to
fl5V for analogue circuitxy (not used in the LFAA relays), or to
f12V for the RS-232 interface and some fibre optic devices in other
relays.
+UV This is used unregulated to switch the output relays.
An under-voltage monitoring circuit is ernployed within the power supply module. If
the voltage on any rail is out of tolerance, a power supply fail signal is asserted on the
VO bus to disable the relay. An alarm output relay inside the power supply module is
also de-energized. The alarm output relay has one nonnally open contact and one
normaily closed contact which are brought out to the MIDOS connecter.
WAA102 R-5930
Service Manual Chapter 4
Page 4 of 12
The module takes the +6.5 V and +24V supplies from the VO bus. The +6.5 V is
regulated to +5 V for Iogic circuitry on the board The +24V is used to drive the
output relays.
AU the output relays are held de-energized during power failure or hardware reset
conditions. This prevents incorrect contact operations during power-up, powerdown
and reset conditions.
LFAA102 R-5930
Service Manual Chapter 4
Page 5 of 12
The micmcomputer module controls the I/O bus. All modules connected to the bus
work as slave I/O modules to the rnicrocomputer module. The module is powered
from the +6.5 V and fl9SV rails of the UO bus.
Table 2 - &-Out Table for the Rear Mounted RS232 Serial Connecta
I I
Function
Protective Gmund
Transmitted Data
Received Data
Request To Send
Clear To Send
Data Set Ready
Signal ûround
+12 v
-12 v
Data Temiinal Ready
Note: The protective ground is connected to the case.
Pins 5 and 6 are intemally pulled up to +12V through 3.9mresistors.
The f12V supplies brought out to pins 9 and 10 cm be used to power
an extemal RS-232 optical converter or a line driver. The current drain
however should be kept to within 2ûûm.A.
Other pins on the 25 way connecter are not connected.
The module as show in Figure 6 is a size 2 module and contains two identical printed
circuit boards.
LFAA102 R-5930
Service Manuai Chapter 4
Page 7 of 12
The input module of the LFAA has 26 inputs on 2 printed circuit boards. Opto-
isolated couplers are used to provide isolation between the external supply and the
relay intemal supply. To reduce power dissipation caused by current flowing in the
opto-input circuitry a strobing technique is adopted which only allows current to flow
into the opto-input circuitry when the stanis inputs are being read Each module
consists of 2 printed circuit boards of 13 inputs and one common r e m . Each board
also has 3 dummy inputs,set by plugs and sockets on the board, to make the total 16,
which is the size of the relay data bus. The numbering of the inputs on the second
board therefore starts at 17. Connections to extemal wiring are made via a 28 way
m s COMectOC
Please see the appropriate relay extemal conneetion diagram for detaiis of input
function assignment.
The module is powered from the +6SV rail of the UO bus.
Terminal allocation of the input modi e is:
Terminal Function
Status input 1 (+ve) Status input 17 (+ve)
Stms input 2 (+ve) Status input 18 (+ve)
Status input 3 (+ve) Status input 19 (+ve)
Status input 4 (+ve) Status input 20 (+ve)
Status input 5 (+ve) Smtus input 21 (+ve)
Status input 6 (+ve) Status input 22 (+ve)
Status input 7 (+ve) Status input 23 (+ve)
Status input 8 (+ve) Status input 24 (+ve)
Status input 9 (+ve) Status input 25 (+ve)
Status input 10 (+ve) Status input 26 (+ve)
Status input 11 (+ve) Status input 27 (+ve)
Status input 12 (+ve) Status input 28 (+ve)
Status input 13 (+ve) Status input 29 (+ve)
Common rem(-ve) Cornrnon r e m (-ve)
One status input module is fitted in the WAA101 and LFAAIû2. Please see the
scheme documentation for the particular scheme for details of status input functions.
Front Panel Operator Interface
Mode1 No : GM0025.nnn
CircwtDiagram: L 1GM0025
PCB No : 2230797
Versions: One
The operator interface (Figure 7) is mounted in the hinged front panel. It consists of a
2 row x 16character alpha numeric iiquid crystal display (lcd) and a 7 key keypd
With the glass cover in position, only two of the seven push-button keys are
accessible. Also included in the front panel operator interface are four indication light-
emitting diodes (leds) and two 25 pin D-type sockets. One of the sockets marked
'SERIAL' is for RS-232 serial communication with the relay. The pin-outs of the
serial port are configured for direct connections to data teminal equipment @TE). No
handshaking control signal is provided but XONKOFF control is supported.
LFAA102 R-5930
Service Manuai Chapter 4
Page 8 of 12
Table 4 - Pin-Out Table for the Front Panel RS232 Serial Connecta
I I
Table 5 - Pin connections for the front panel parallel port for parallel printer and
test port connections
Pin Paralle1Printer Test Port
Humber nnection
Strobe Do Not Connect
Data Bit O Not used
Data Bit 1 Not used
Data Bit 2 Not used
Data Bit 3 Not used
Data Bit 4 Not used
Data Bit 5 Not used
Data Bit 6 Not used
Data Bit 7 Not used
Do Not Connect SELECURESET Key
Busy Do Not Connect
Do Not Connect ACCEPT/READ Key
Do Not Connect SET Key
Do Not Connect Left arrow Key
Do Not Connect Down Key
Do Not Connect Right Key
Do Not Connect UP Key
Do Not Connect +6.5 V
Do Not Connect +19.5v
Do Not Connect - l9.W
Do Not Connect +24V
Ground Ground
Ground Ground
Ground Ground
Ground Ground
The interface cables for the serial port and the parallel port should be of 24 AWG
gauge and shielded. The cables should be provided with a metal or metal-impregnated
comector hood We recommend the cable shield to be ~ 0 ~ e C t to e dthe frame
@rotective) ground of the comecting equipment. There is no elecmcal isolation on the
seriai port and the p d e l port. An external isolation barrier with transient suppressors
should be used if the communication is to be over a long distance or if the earth
potential of the connected equipment can differ h m that of the relay.
A potentiometer is made available through a small circular hole adjacent to the lcd. It
is used as a contrast control for the lcd and may be trimmed to optimise the lcd
viewing angle.
The front panel operator interface is pwered by the +6SV rail of the VO bus.
Section 4. LINK SETTINGS -
The modules used in the LFAA relays are selected from a standard hardware range.
Many of the modules have a number of jumper links which must be set to allow them
to be used in a particular appiication.
The following section lists the link positions required in the LFAA relays.
All linksmust be fitted as shown with the exception of links marked USER
SELECTABLE which may be set by the user to select a pamcular feature.
The power supply module does not have any jumper links:
4.1 Relay Output Module Link Positions
Address Decode (Coarse)
CHAPTER 5
FUNCTIONAL DESCRIPTION
LFAA102 R-5930
SERVICEMANUAL (2HAFm=5
CONTENTS
FUNCTIONAL DESCRIPTION
SELF MONlTORING
TEST FACILITIES
Thé functional aspects of the relays are govemed by the scheme logic,which is
encoded in software in the fom of a ladder diagram. Cornmon elements of the relay
operation, such as reading data h m the status inputs, driving the output relays,
running the tllners and handling the user interface are perfonned by the operating
system software. For a functional description of a particular scheme, see the
appropriate scheme documentation.
In addition to the scheme logic the LFAA relays include self m o n i t o ~ gand test
facilities and remote access via an RS-232 serial link
Section 2 SELF MONITORING
The LFAA relays include a number of self monitoring features designed to prevent
hardware or other fatal mrs causing maloperation of the relay. The self monitoring
software locks out the relay and reports the enor when a fatal e m r is detected. The
watchdog timer and self monitoring software also detect temporary non-fatal emrs
and recover the relay operation by resetting the system.
Power-on diagnostic tests are carried out automatically by the relay when it is first
switched on. Fmtly there are system checks on the main relay components, i.e.
watchdog timer, mimprocessor, interrupt controller, DMA conîroller and timers.
Configuration checks are then canied out on memory components to ensure the
c m type of memory is present and properly located Randorn access m e m q
(RAM) is then checked by readfwrite tests to each location. Erasable programmable
read only memory (EPROM) is checked by checksum tests. Electrically erasable
programmable read only memory (EEPROM) is checked by fmt loading the contents
to RAM, then copying the data back to EEPROM. The power fail software relays and
none volatile counters are then checked by a direct comparison between RAM and
EEPROM, and the settings by checksum tests on the EEPROM. Any error detected
results in a message appearing on the relay display, and the software will wait for the
left arrow key to be pressed before continuing.
In addition to the power-on diagnostic tests, there are a number of system checks
which monitor the operation of the relay on a continuous basis. These include RAM
and EEPROM readlwrite tests and EPROM and EEPROM checksum tests.
Once an error has been detected in RAM or EPROM, a message containing an error
code is reported on the h n t panel liquid crystal display (lcd). The relay inoperarive
alarm output contact also closes to indicate the failure. The system must then either
lock out or attempt a recovery depending on the type of error. In either case the self
monitoring software forces a system reset via the watchdog circuitry so that the
system can be brought back to a defined starting state. If an e m r is detected in
EEPROM, a message stating the area of EEPROM affected is displayed on the lcd, but
the relay continues to operate.
Please read Chapter 9 for details of the error codes for the various causes of failure
and actions to be taken when failure occurs.
LFAA102 R-5930
Service Manual Qiapter 5
Page 2 of 2
A number of manually operated test facilities are pmvided through the front panel
operator interface. The States (on/off) of each status input and output relay can be
displayed without removing the h n t cover, and the state of each output relay can be
changed with the front cover removed and provided conditions in the ladder software
release a security interlock.
The test socket also has eight ïTL inputs. Seven of these input lines are connected in
parallel with the seven keys at the front panel. This can be used to emulate keystrokes
at the front panel. This pennits the use of a programmable secondary injection test set
to issue operator comrnands for data dumps or setting changes in an interactive
manner. Most commissioning,routine testing and fault finding operations cm then be
performed automatidy to Save Iine outage time. Please see Chapter 4 for detailed pin
comections of the test socket. &
Wonnation stored in the relay can be p ~ t e out d via the parallel port or the serial port
at the front panel, or the serial port at the rear of the relay by issuing a print command
(See Chapter 6 for operating details and Chapter 4 for the pin-outs of the parallel and
A remote access facility is provided which allows an operator to communicate with the
relay using a visual display unit (VDU)or a personal computer. The facility exnulates
the front panel keypad and Icd and so allows access to the command menu. This
means the user may intenogate the relay rernotely for infanation and to change the
settings.
The LFAA relays have an RS-232serial port. Two 25-way D-type connectors axe
provided for the serial port, one on the front panel and the other at the back of the
relay. The serial port is normally connected to the front panel connector. The relay
glass cover needs to be rernoved to gain access to the front panel serial port.
For permanent connection to a personal computer or visual display terminal, either
directly or via a modem, the position of a jumper on the microcornputer module (see
Chapter 4 for de&) can be changed to divert the serial port to the connector at the
back. The serial port can also be used to drive a serial printer.
Please see Chapter 4 for pin connections of the front and rear serial interface
connectors and Chapter 7 for details of the remote access facility.
The RS232 seriai port is not electrically isolated For permanent connections extemal
transient suppressors or isolation barriers should be used.
LFAA102
R-5930
SERVICE MANUAL CHAPTER 6
CHAPTER 6
SOFTWARE DESCRIPTION
LFAA102 R-5930
SERVICE MANUAL CHAPTER6
CONTENTS
1 INTRODUCTION
2 SYSTEM SOFTWARE
2.1 Multi-Tasking Executive
2.2 Basic Input/Output System
2.3 Power-On Diagnostics/Self-Monitoring
2.4 Real-Time Monitor
2.5 Off-Line Monitor
4 SCHEME LOGIC
Inputs
Outputs
Relays
Light Emitting Diodes
Software Relays
Noxmal Software Relays
Power Fail Software Relays
Blocking Software Relays
Block Settings Software Relay
Block Resets Software Relay
Block Output Test Software Relay
Function Links
Timers
Counters
Counter Coils
Cornparisons
LFAA 102 R-5930
Service Manual Chapter 6
Page 1 of 8
Section 1 INTRODUCTION
The WAA auto reclose relay software is divided into 3 main groups: the system
software, the logic controller software and the scheme logic. The system software is
not application dependent and is used for aU multi-rnodular hardware applications. It
consists of various diagnostic, debugging, inpuî/output and multi-tasking handling
facilities. It provides a common software environment within which different
application programs can be developed and operated
The logic controller software acts as the interface between the ladder diagram and the
system software, handling the input and output data, calls to the ladder diagram,
tirning functions and the user interface.
The ladder diagram defines the scheme logic and the application specific text for the
user interface.
---
Section 2 SYSTEM SOFTWARE
The off-line monitor provides a number of off-line debugging facilities. It allows the
user to examine and to modify the contents of registers, mernory and VO ports, to set
break points, to single step and to execute a program.
The off-line monitor is used mainly during the software development phase. Special
instructions are required for gaining access to the off-line monitor functions. The off
line monitor is therefore transparent to the user.
Section 3 LOGIC CONTROLLER SOFTWARE
The logic controller operating system handles the interface between the scheme logic
and the system software. It processes the status input information, updates the relay
outputs and conuols the timing and operator interface. It also performs checks on the
electrically erasable programmable read only memory (EEPROM).
The timer routines are run every 10 ms, before the slow section of the ladder diagram
is enabled. The ladder diagram software sets or clears flags to enable, start and stop
the timers. Each tirner has three flags: input, output and status. There are three types
of timer, each with different behaviour: delayed pick-up, delayed drop-off and pulse.
When the input to the timer is off, the ladder sets all three flags off. Only the Input
flag is turned on by the ladder. When the b e r routine detects that the Input flag is on
it tests the Output flag and if this is off it tests the status flag. If the Status flag is off it
loads the setting into the timer value area in memory, turns the Status flag on and
decrements the timer value. If the status flag is on, the timer value is decremented.
This process is repeated every lOms until the b e r value is zero, or the ladder tums --
the timer off. When the timer value reaches zero and the Input fiag is still on, the
output is tumed on. The ladder diagrarn reads the output flag as the input to the next
element of ladder code.
3-2.3.2 Delayed dropoff
When the input to the timer is on, the ladder sets al1 three flags on. Only the input flag
is turned off by the ladder. When the timer routine detects that the input flag is off it
tests the output flag and if this is on it tests the status flag. If the status fiag is on it
loads the setting into the tirner value area in memory, turns the status fiag off and
decrements the timer value. If the status flag is off, the tirner value is decremented.
This process is repeated every lOms until. the timer value is zero, or the ladder turns
the timer on. When the timer value reaches zero and the input flag is still off, the
output is tumed off. The ladder diagram reads the output flag as the input to the next
element of ladder code.
R-5930
Chapter 6
Page 5 of 8
3.2.3.3 Pulse
When the input to the timer is on, the ladder sets the input flag on and tests the status
flag. If the status flag is off the output flag is tumed on. Only the input flag is turned
off by the ladder. When the timer routine detects that the output flag is on it tests the
status flag. If the status flag is off it loads the setting into the timer value area in
memory, tums the status flag on and decrements the timer value. If the status flag is
on, the timer value is decrementeà This p e s s is repeated every lOms until the timer
value is zero. When the tirner value reaches zero the output flag is turned off. If both
the input and output flags are off the status flag is tumed off. The ladder diagram
rads the output fïag as the input to the next element of ladder code.
Operata Interface
The operator interface software reads the front panel keypad and displays messages on
the liquid crystal display. It operates on a menu principle. As a key is pressed, the
input is software de-bounced and checked for validity. The keypad input selects the
menu comrnand and controls the movement around the menu. The lcd is updated
when a key is pressed, or every 250111s if no key is pressed. A full description of the
operator interface is given in Chapter 7.
Front Panel, lcd and Keypad
The front panel irnplementation covers the pressing of keys and the display of data on
the liquid crystal display. The software waits for a key to be pressed and then calls the
correspondingkey checking software which will implement that key input by giving
the relevant display and/or action.
Paralle1Port
The parallel port allows relay data to be sent to a parallel printer. The software
supports the Centronic parailel printer protocol. The user selects the parallel port. The
software checks if the printer is connected and working during printing. If the printer
is disconnected or fails, a message to this effect is displayed, and the software waits
until the printer is wmking again, the left m w key is pressed or the software times
out after 15 minutes.
When not in the pnnt cornmand mode, the parallel port works as a parallel
input/output port for testing purposes. The test port is intended for working with
computer based injection test equipment. Seven input lines are pmvided to allow the 7
fiont panel keys to be emulated.
The serial port can be used to drive a serial printer. It also allows a user to log on to
the relay and to interrogate the relay using a personal computer or visual display
terminal instead of using the front panel keypad and display. Once logged on, the port
is irnplemented as ifit was the h n t panel. The software redirects the output to the
port and translates remote key presses into front panel keypad inputs. This can be
viewed therefore as an emulation of the front an el oDerator interface.
LFAAlûî R-5930
Service Manual Chapter 6
Page 6 of 8
The scheme logic (i.e. what the relay does) is presented in the form of a ladder
diagram. The ladder diagram is produced on a separate piece of software running on
an IBM PC.It presents the scheme logic in the form of contacts, coils, counters and
timers which the scheme designer can arrange to effect any desired scheme.
The ladder is arranged in a series of pages of 6 rows by 7 columns of elements. In
operation, the software scans each page, starting at the top left hand corner and
proceeding down column 1, then moving on to colurnn 2 etc. until the bottom right
hand element is reached. The right hand colurnn consists of coils :ie. the software
representation of output relays and le&, software relays and counter coils. The
remaining 6 colurnns contain software contacts, counter comparisons and timers
In operation the left hand side of the page can be considered as a positive supply rail,
_--.
and any contact which is made, any timer whose output flag is on or any counter
cornparison which is m e will comect the positive to the next element on the right.
Any contact which is open, any timer whose output flag is off or any counter
cornpanson which is not m e will not connect the positive to the next element on the
right, which will therefore be off. When the right hand column is reached, the result
of al1 the elements to its left is applied to the coil, i.e. it is turned on or off, or a
counter value may be changed
Inputs
Up to 96 inputs (3 modules of 2 x 16 channels each) can be accomrnodated in the
ladder. They appear as open or closed contacts, the contact king represented by a
filled in circle. The contact position is for the input not energized
There are two types of output in the ladder: Relays and Light Emimng Diodes (ied).
Relays
Up to 96 relay outputs (6 modules of 16 relays each) can be accomrnodated. Note that
not al1 the output contacts are available as each module is wired out through the 28
way MIDOS terminal block. The coil is represented by a symbol in the ladder
diagram, which shows the output relay name and the relay reference number in
hardware. Contacts are shown in the ladder as normally open or normally closed, the
contact being represented by an open circle. The contact position is for the output not
energised Note that the contacts in the ladder diagram do not correspond to any actual
relay contacts.
Light emitting diodes
Two leds are available in the ladder. The OUT OF SERVICE led will normally be
associated with an out of service relay and inputs to switch the LFAA in and out of
service. The RELAY HEALTHY led wili normally be connected directly across the
ladder, so as to be permanently on. If a hardware or software failure occurs,so that the
ladder software does not run, the led will go out.
LFAAlo2 R-5930
Service Manual Chapter 6
Page 7 of 8
There are three blocking software relays: settings, resets and outputs. When on they
effect the foliowing menu functions:
4.3.3.1 Block settings software relay
Revents access to the change semngs group of the user interface, or if the menu is
aùeady in this group (ie. semngs are being changed) when the block settings sofnivare
relay turns on, the new settings cannot be updated on leaving the group.
4.3.3.2 Block resets software relay
Prevents access to the reset counters group of the user interface, or, if the menu is
already in this group (Le. counters are king enabled for resetting) when the block
resets software relay nuns on, counters cannot be reset on leaving the group.
4.3.3.3 Block output test software relay
Prevents the output relays being tested. The state of the relay is still shown on the
upper line of the display, but the lower line displays TEST BLOCKED and the relay
state cannot be changed. If an output relay is being tested when the block output test
softwarerelay tums on, the output relay under test will imrnediately revert to its
correct state.
4.4 Function Links
Up to 64 function links are available. They appear as contacts in the ladder diagram
which can be changed by entering the appropriate key presses through the keypad.
They are used to configurethe scheme logic to a particular requirement.
Up to 48 b e r s are available. A timer can be either delayed pick up, delayed drop off
or pulse, and settings can be either fixed or user adjustable with setting entry through
the keypad.
LFAA102 R-5930
Service Manual Chapter 6
Page 8 of 8
4.6 Counters
Counters have 2 sections: coils, which consist of a value which can be changed by an
action in the ladder, and comparisons, where a coil value is wmpared with a setting
and an action performed if the cornparison is me.
4.6.1 Counter coiis
Up to 48 coils are available. 24 are volatile, the contents of which are lost in the event
of power being removed from the relay, and 24 are non-volatile, the contents being
saved when power is removed and restored when power is re-applied to the relay.
Counter mils only appear in column 7 of the ladder.
4.6.2 Cornparisons
The coil value can be compared with target settings that can be either fixed or user
adjustable with setting entry through the keypad. The cornparison can be for the value 4-
to be qua1 to, p a t e r than or equal to, or less than or qua1 to the target value.
Counter comparisons can appear in colurnns 1 to 6 of the ladder.
LFAA102
SERVICE MANUAL
CHAPTER 7
OPERATING INSTRUCTIONS
LFAA102 R-5930
SERVICE MANUAL CHAPTER 7
CONTENTS
MENU SYSTEM
Actions
Settings
AlaIms
Status 1 Alarrns
Compound Alarms
Status 2 A~~MIS
Change Alarms
EEPROM Storage .
Remote Access
Section 1 INTRODUCTION
The operator interface of the LFAA relays consists of a 2 line by 16character liquid
crystal display (lcd), a 7 key keypad and a set of 4 indicating light ernitting diodes
(leds). The layout of the front panel is show in Figure 12, Appendix.
The lui displays the majority of information for the operamr interface. It displays the
text of alarm messages, settings etc..
The keypad is used to implement the operator interface commands which will be
described later. The seven keys consist of 4 direction keys, up, down, left and right, a
SET key, a SELECï/RESET key and an ACCEPT/READ key. With the front cover in
position only the SELECï/RESETkey and the ACCEFVREAD key are accessible.
The depression of any key will generate one action of that key. However if the key is
held depressed, it will automatically repeat the action after a short time interval. The
function of each of the keys is as follows:
Up key: move up in the menu, select previous setting item or increase setting
value.
Down key: move down in the menu, select next setting item or decrease setting
value.
Left key: move left in the menu.
Right key: move right in the menu.
SET key: update setting changes or confimi actions.
A C C E F T W key: select alaxms, counters, semngs, input or output states or the
test timer option.
SELECT key: Consecutively display enabled alarms, counters, settings, input or
output states or select the timer for the test timer option.
RESET key: Ignore semng changes.
The indicating lamps are used to indicate the state of the relay at any time. They
consist of a relay healthy lamp, an out of service lamp and two a l m lamps.
The relay healthy lamp appears in the ladder diagrarn, arranged so that it is always on,
unless special circumstances require it to be turned off. Provided it is on in the ladder,
it is triggered regularly by the mimprocessor and will rernain on unless there is a
failure of an interna1 component or software which causes the rnimprocessor to
operate incomtly when this lamp will turn off.
The out of service lamp is tmed on and off within the ladder diagrarn. To indicate
that the relay has been taken out of service by an external input it will be stably on.
The two alarm lamps can be stably on or flashing, to indicate that an alann in any one
of four sets of alanns has been enabled.
LFAA102 R-5930
Service Manual Chapter 7
Page 2 of 35
The operator interface operaies on a menu type system which uses a harizontal inx-
like structure with the various functions grouped under their relevant branch. This
allows easy access to any function without total knowledge of the capabilities of the
relay. The default level is the top of the tree and displays the relay title as entered in the
ladder diagram. The menu will change to the default level after fifteen minutes of
inactivity on the keypad. This movement to the default position will abort any changes
that were current at the time.
The menu consists of 5 levels, these k i n g &fault level, group level, function level,
attribute level and change level. At each of these levels the menu may have several
options or branches. The user may change option or branch by using the up and down
arrow keys and may change levels by using the left and right arrow keys. The group
level divides the menu into groups of common functions. The function level gives the --.
,
functions in a group. The amibute level gives the value or setting of the selected
function and the change level allows the value or setting to be changed.
The lcd indicates the current position of the menu, in the form of a text message.
If the right arrow key is pressed at the default level then the menu will move to the
first group. The user then has the option of changing groups (up or down) or entering
the current group (right). When moWig up or down in the menu, if there are no more
options above or below then the menu wraps round to the lowest or highest option
respectively in the given function or group. When the group is entered the menu will
be at the fmt option in the group. Again the options are to move up or down the
options or into a function. This procedure continues until the right hand edge of the
menu is reached. Different functions have different right hand limits.
If the left arrow key is pressed the menu will move to the previous level. Thus at a
given function, pressing the left arrow key wili move to the group of which that
function is a member. Continued depression of the left arrow key will move to the
default level.
If the ACCEPT/READ key is pressed at the default level the menu moves to the
viewing group which allows the following operations to be perfonned using a
combination of the AC(3EPT/READ and SELE(JT/RESETkeys:
Read any enabled alarms
Read counter contents
Read settings
Read input States
Read output States
Test timers
Figures 13 and 14, appendix, show part of a typical operator interface tree menu
structure.
R-5930
Chapter 7
Page 3 of 35
Example 1
To read the setting of timer 2 the following steps are required. Starting h m the
ciefault level on the lcd:
COMMUNICATIONS +
PRESS I) DISPLAY READS SET TIMERS i)
COUNTERS +
PRESS I) TYPICAL DISPLAY INTER TRIP TIME
READS 1.O0
If the amber alarm lamp (ALARMS 2) is stably lit, to read the associated alarm
messages, starting from the default display:
PRESS ACCEPT/READ DISPLAY READS S-REDALARMS
A-NEXT (FLASHING)
PRESS AmlREAD DISPLAY READS %RED FLASHING
A-= (AMBER)
PRESS ACCEPT/READ DISPLAYREADS S-AMBER ALARMS
A-NEXT (FLASHING)
PRESS SELECï/RESET DISPLAY SHOWS Alarm message text
Repeated presses of SELECI'/RESET will display ail the enabled alamis which are
associated with the amber l e . when stably lit. When all the enabled alarrns have been
displayed (orimmediately if none are enabled) the display will show:
S-RED FLASHING
A-NEXT (AMBER)
(ie.the previous selection display). Pressing the ACCEPT/READ key at any time
while a message is king displayed will r e m the display to:
S-AMBER ALARMS
A-NEXT (FLASHING)
(ie. the current selection display).
R-5930
Chapter 7
Page 4 of 35
Repeated presses of the ACCEPT/READ key will then scroll through all the remaining
options and r e m to the default display.
Thë vanous positions of the menu have different purposes and these are as follows:
Indications -These positions indicate the group or function position of the menu or the
current state of the measurand or statistic. Where a value or state that is
changing is displayed, the display will refresh with a new value every
250 milliseconds.
Settings - ïhese positions indicate the c m n t value of a relay setting and allow the
setting to be changed. The indication of whether a change rnay be made
is by means of either a flashing underline altemating with the value, or a
flashing up and down arrow.
Actions - These positions indicate than an action will be performed when a
particular key is pressed. In most cases the action will be confirmed by
-
pressing another key afterwards. The menu will prompt the user to press
the appropriate key to c o d m the action, or another key if the action is
not to be canied out. This prevents commands king executed
inadvertently.
Accepting - These positions generally follow setting changes, before updating or
ignoring the changes.
The operation of each type of position will be described in more detail later.
Actions
Where certain cxrmmands are to be actioned the menu will indicate that the right arrow
key should be pressed. In some commands there is a check to c o n b that the
command is to be actioned. This requires the user to press the SET key. Once
actioned, the menu will retum to the display that indicates the cornmancl may be
performed.
Semngs
The relay settings are found at the right hand edge of the menu in the relevant group.
On entering the attribute level of the function the setting title and value will be
displayed. When a setting is king displayed a further depression of the nght arrow
key will allow the setting to be changed, indicated either by the value alternating with
an underline, or by a flashing up or down mow. Changing the setting is canied out
by using the up key to increase the value or the d o m key to reduce the value. When
the maximum or minimum value is reached, the minimum or maximum value,
respectively, is indicated.
When the desired new value of the setting has been reached, it is saved in temparary
memory by pressing the SET key .This allows al1 settings in a group to be updated
into the working memory together. At the same time the display will cease to flash,
and other settings in the group will become available.
WAA102 R-5930
Service Manuai Qiapter7
Page 5 of 35
When a l l changes have been made to the settuigs, a further press of the left key will
attempt to leave the group. If any of the temporary settings differ h m the
corfesponding working values, the user is prompted to press either the SET key to
update the working memofy,or the RESET key to abandon the changes. Alternatively
the right m w key can be pressed to re-enter the group. If the changes are updated or
ignore. a message to this effect is displayed on the I d
The relay settings cannot be updated if the BLOCK SETTINGS softwm relay is on,
the group can only be lefi by pressing the RESET key to abandon the changes. The
communication settings and user identifier can be updated at any time.
If the access level is set to limiteci, no settings can be changed over the serial
communications link.
Setting ranges:
The setting range for the timers is 0.01 seconds to 9999 seconds. The setting
resolution is 0.01 seconds between 0.01 seconds and 99.99 seconds, 0.1 second
between 100.0 seconds and 999.9 seconds, and 1 second between 1000 seconds and
9999 seconds.
The setting range for the counter targets is 1 to 9999, with a resolution of 1.
Timers and counter targets can have their maximum and minimum limits reduced and
increased respectively in the ladder diagram, to prevent unrealistic values being
entered.
The function links can only be on or off.
Each user adjustable item has associated with it text which is entered in the ladder
diagram, and appears on the Icd when the pariicular item is king set. In the case of
timers and counter targets, the text is the name of the item, e.g.
timea DELAY DEAD TIME counter MAINT.ALARM
1.23 target 30
The value of the setting is displayed on the lower line of the display.
In the case of the function links, the top line of the display will show FUNCT n = ON
(or OFF)where n is the function number. Functions have two associated lines of text,
one for the on case and one for off.
Conditions which cause an alarrn to be given are determined in the ladder diagram.
Each alarm is attached to a coil (i.e. an output, software relay or memory software
relay) in the ladder and is enabled when the appropriate conditions are met. The
condition to enable the alarm is indicated by the comrnand of the alarm entry table in
the ladder diagram. If the comrnand is + the alarm is enabled either by the coil turning
on or king on, and if the comrnand is - the alam is enabled either by the coi1 tming
off or being off. Text for the alarm.messagesis also set in the ladder diagram.
There are 4 groups of alarms, indicated by the ALARMS 1 or ALARMS 2 leds being
either stably lit or flashing. The condition to set and reset each group of alarms is as
follows:
status 1 Alarms
Indicated by the ALARMS 1 (rd) led king stably lit
If the command is + the alam is enabled while the designated mil is on and disabled
while the designated coil is off.
If the command is - the alarm is enabled while the designated coil is off and disabled
while the designated coil is on.
2.3-2 Compound Alarms
Indicated by the ALARMS 1 (rd) led flashing
N.B. If any status 1 alarms are also enabled, the led will be stably lit, and the flashing
will be masked.
If the commanti is + the alam is enabled while the designated coil is on and reset
when the alarm message is read, provided that the designated coil is now off. If the
coi1 is on when the message is read, the a l m will still be enabled.
If the command is - the a l a m is enabled while the designated coil is off and reset
when the alarm message is read, provided that the designated coil is now on. If the
coil is off when the message is read, the alarm will still be enabled.
2.3.3. Status 2 Alarms
Indicated by the ALARMS 2 (amber) led being stably lit
If the command is + the alann is enabled while the designated coil is on and disabled
while the designated coil is off.
If the command is - the alarrn is enabled while the designated coil is off and disabled
while the designated coil is on.
2.3.4. Change Alarms
Indicated by the ALARMS 2 (amber) led flashing
--y
N.B. If any status 2 alarms are also enabled,the led will be stably lit, and the flashing wiil
be masked.
LFAA 102 R-5930
Service Manuai Chapter7
Page 7 of 35
If the command is + the alarm is enabled while the designated coi1 is on and reset
when the alann message is read. The alarm will not be enabled again until the coi1has
tumed off then on again
If the command is - the alann is enabled while the designated mil is off and met
when the alarm message is read. The alarm will not be enabled again until the coi1has
tumed on then off again
The type of alarm is described on the relay display by the appearance of the leds, i.e.
Status 1 alarms are described as RED ALARMS
Compound alarms are described as RED FLASHING
Status 2 alarms are described as AMBER ALARMS
Change alarms are described as AMBER FLASHING
The relay is equipped with EEPROM storage for the settings, non-volatile counm
and mernory software relays. The settings are updated whenever a change is made and
the set key is pressed on leaving the group. When a non-volatile counter is changed, a
flag is set in memory which is tested by the routine which saves the counters and the
memory software relays. This routine runs every 10 ms, and compares the memory
software rdays, and none volatile counters if the flag is set, in RAM with the
quivalent value in EEPROM.If a value differs, it is copied from RAM to EEPROM.
The values are loaded from the EEPROM whenever the relay is powered on. In this
event the settings are checked against the maximum and minimum values entered in
the ladder diagram. If a setting is out of range the minimum value will be loaded.
The EEPROM is checked during the initialisation process, and at regular intervals
during normal operation. If an error is found, and the display is showing the default
text, the display will change to:
The menu system is also available via the serial port. The user identifier, which is not
echoed back to the tenninal, must first be mectly entered, followed by a carxiage
r e m , whereupon the relay will respond by sending GECAM to the remte terminal.
The user must then enter LOGON ,which is echoed back to the terrninalfollowed by a
carriage return, and the relay will send the default display to the terminal. Thereafter
the displays and key operations on the remote terminal or computer are exactly the
same as those on the lui, except for those associated with changing settings. If the
remote access level is set to FULL, the remote terminal duplicates fully the lcd and
keypad. If the remote access level is set to LIMITED, the following operations cannot
be prefomied:
changing any semng (including communications and user identifier)
resetting counters
testing output relays
This means that the user may interrogate and change the relay from a remote point
subject to the relevant iink king installed. The implementation of the port assumes
that the terminal connected is an ANS1 or VTlOO type. Most modem terminais and
cornputers can emulate one of these types of operation.
The remote port can only gain access to the menu when it is at the default position.
When the user identifier has been correctly entered at any other position, the remote
port receives a message that the menu is unavailable.
When the remote port is logged on, the lcd displays a message to this effect and the
keys, except for the SELECT/RESET key, are disabled.
The remote port may be logged off by one of three means:
1 The SELECT/RESET key on the relay can be pressed.
2 The Q key on the remote terminal keyboard can be pressed.
3 The rernote part can be left inactive for fifteen minutes.
When a log-off occurs a message is sent to the remote terminal stating the cause of the
log-off, and the lcd reverts to the default display and control returns to the local keys.
When the user is logged on to the remote port the implementation of the keys is as
follows:
UP k e ~ 8
Dom key 2
Right key 6
Left key 4
SET key 5
SELECURESET key 1
READ/ACCEPT key 3
These represent a similar layout to those on the front panel when using a nurneric
keypad.
Some tenninals cannot display up and down arrows, so these are replaced by a ?
symbol on the remote terminal.
LFAA102 R-5930
Sexvice Manual Chapm7
Page 9 of 35
&-.
The layout of the menu is given in figure 15, appendix. The sections of the menu are
described in detail in this section
The menu is divided into 7 groups :
COMMUNICATIONS
TEST OUTPUTS
This group contains options to send information contained in the relay to either the
parallel port or the serial port. The port is selected as the fmt option on entering the
print group. If the parallel port is selected and the printer is not CO ME^^^, off line or
out of paper, the display will show:
PRINTER NOT
READY
If the parallel port is selected and the pinter is ready, or the seriai port is selected, the
display will show:
HEADING 3
SETIWGS4
LFAA102 R-5930
Service Manuai Chapter 7
Page 10of 35
Once the option to be printed has been selected, the display will show
PRINTING
IN PROGRESS
While printing is in progress, and will revert to the selection menu when pnnîing is
complete.
If the parallel port is selected and the printer becomes disconnected, is swiched off line
or runs out of paper during printing, the display will change to:
PRINTER NOT
READY
after up to 5 seconds
Printing will continue when the condition which caused it to halt is corrected.
WAA102 R-5930
Service Manuai Chapter 7
Page 11of 35
The menu will wait for the condition to be comted for 15 minutes, after which time
the menu will be reset to the default display, or until the left key is pressed, when the
display will r e m to
HEADING *
SE'ITINGS +
Pressing the right key will send the relay default display, the user identifier and the
software refmnce numbers to the selected printer.
3.1.2 Printing the settings
Press the right key
. = =
PRINT i)
SETTINGS 4
Press the right key
SERIALPORT *
PAMLLEL PORT C
Press the right or d o m key to select the required port.
HEADING +
SETI'INGS C
R-5930
Chapter 7
Page 12 of 35
-
' /
,
SEïTINGS =b
ALARMS C
Pressing the right key will send the relay settings to the selected printer.
3.1.3 Printing the damis
Proceed as above until the display shows
SErnGS +
ALARMS C
Pressing the right key will send the relay d a m s to the selected printer.
3.1.4 Printing the counters
Proceed as above until the display shows
ALARMS *
COUNTERS C
Press the d o m key.
COUNTERS .,
INPUT STATES +
Pressing the right key will send the relay counters to the selected printer.
3.1.5 Printing the input States
Proceed as above until the display shows
COUNTERS
INPUT STATES +
Press the down key.
INPUTSTATES =b
OUTPUT STATES C
Pressing the right key will send the States of the status inputs to the selected printer. --.Y
LFAAlû2 R-5930
Service Manuai chapm7
Page 13 of 35
INPUTSTATES
OUTPUT STATES
Press the down key
OUTPUT STATES *
ALi'OrnONS +
ess sin^ the right key will send the sÿ<tesof the output relays to the selected printer.
P
3.1.7 Printing a i i the above options
Proceed as above until the display shows
OUTPUT STATES *
ALLOPTIONS C
ALL OPTIONS
HEADING +
Pressing the right key will send the al1 the above options to the selected printer in tum.
Note that the display
ALL OPTIONS *
HEADING C
HEADING *
SE'ITINGS 4
by pressing the Up key.
3.2 Setting Group
This group contains options to set up the operating parameters of the relay. The group
is divided into 3 fwictions;Timers, which contains the semngs for the user adjustable
timers, Counters, which contains the settings for the user adjustable counter targets,
and Functions, which contains the settings for the function links. The text which
appew on the relay lcd, and the limits for the tuner and counter target settings, are
entered in the ladder diagram, hence any such text here is only typical.
LFAA102 R-5930
Service Manual Chapter 7
Page 14 of 35
Entry to the setiing group will be blocked if the block settings software relay is on. In
this case the display shows:
PRINT i)
SErnGS C
Press the down key
SET TIMERS i )
COUNTERS +
Press the right key
When the desired value is displayed on the lcd, press the SET key. The new value is
saved in temporary memoxy and the alternating underscores stop. Pressing d o m or
up will now enable each timer setting to be viewed in rotation, and changed if
neCëssary, as before.
3.2.2 Setting counters targets
Starting fkom the default display on the lcd
Press the right key
SETI2NGS i)
COMMUNICATIONS Z
Press the right key
SET TIMERS =b
COUNTERS +
Press the down key
SET COUNTERS =b
FUNCIlONS +
Press the right key
MAINT-
1
Press the d o m key
MAINT. LOCKOUT
1
Continue pressing down or up until the desired counter target is found
To change the counter target setting, press the right arrow key. The value will now
alternate with underscores while no key is pressed. Pressing the d o m or up key will
decrement or increment the value, and the alternating underscores will not occur as
long as the key is pressed. This last step will not be possible if a remote terminal is in
use and the access level is set to LIMITED
The speed up routine described above operates for counter target settings.
When the desired value is displayed on the lcd, press the SET key. The new value is
saved in temporary memary and the alternating underscores stop. Pressing down or
up will now enable each counter target setting to be viewed in rotation, and changed if
necessary, as before.
R-5930
Chapter 7
Page 16 of 35
SETTINGS -b
COMMUNICAïïONS C
Press the right key
SET TIMERS -b
COUNTERS C
Press the down key
SET FUNCTIONS +
TIMERS 4
Press the right key
ma'
1 = OFF
TWO SHOT
Press the down key
To change the function setting, press the right key. A flashing mow, pointing
altemately up or down, indicates that the up or d o m key should be pressed to change
the seuing. This 1st step will not be possible if a remote texminal is in use and the
access level is set to LIMITED.
When the desired value is displayed on the lcd, press the SET key. The new value is
saved in temporary mernory and the flashing arrow disappears. Pressing d o m or up
will now enable al1 the function settings to be viewed in rotation, and changed if
necessary, as before.
When ail setting changes have been made, after 2 presses of the left key îhe display
will show either
UPDATE SE'ITXNGS
sET/REsET
if the block setiings software relay is off or:
SElTINGS BLOCKED
RESET OR w m
if the block settings software relay is on.
If the display shows
UPDATE SE'ITXNGS
SET/RESET
the operator is free to update the settings and has two options at this point:
The operator presses the SET key and the working mernory is updated and the
changes are written to the EEPROM. The display shows
The operatm presses the RESET key to abandon the setting changes. The
display shows
LFAA102 R-5930
Service Manual Chapter 7
Page 18 of 35
The operator cannot update the settings and has two options at this point:
(i) Wait until the conditions which have caused the blocking software relay to be
picked up case to apply, whereupon the settings can be updated
(ii) The operator presses the reset key to abandon the setting changes.
The display shows
SErnGS
RESTORED
-4
The condition which has caused the blocking software relay to be picked up can then
be investigated, and suitable action taken.
Communications Group
This group contains options to set up the operating parameters of the serial
communicationslink. The group contains three settings, these being access level,
baud rate and data fcnmat.
Setting access level
Starting from the default display on the lcd
Press the right key
COMMUNICATIONS *
IDENTIFERS C
To change the access level setting, press the right key. A flashing m w , pointing
alternately up or down, indicates that the up or d o m key should be pressed to change
the-setting. This last step will not be possible if a remote texminal is in use and the
access level is set to LIMITED
When the desired setting is displayed on the Icd, press the SET key. The new value is
saved in temporary memory and the flashing arrow disappears.
3.3.2 Setting the baud rate
Proceed as in section 3.3.1 until the display shows
ACCESS LEVEL
IAlhanm
Press the down key
BAUD RATE
2400
To change the baud rate, press the nght key. The value will now altemate with
underscores while no key is pressed. Pressing the down or up key will change the
value, and the altemating underscores will not occur as long as the key is pressed.
This last step will n a be possible if a remote terminal is in use and the access level is
settoIAMrIED
When the desired value is displayed on the lcd, press the SET key. The new value is
saved in temporary memory and the altemating underscores stop.
3 -3.3 Sening the data farmat
Proceed as in section 3.3.2 until the display shows
BAUD RATE
2400
Press the down key
DATA PARITY STOP
8 NONE 1
To change the data format setting press the right key. A flashing m w , pointing
alternately up or down, indicates that the up or down key should be pressed to change
the setting. This last step will not be possible if a remote t d n a l is in use and the
access level is set to LIMiTED
LFAAlO2 R-5930
Service Manuai Chapter 7
Page 20 of 35
When the desired settings are displayed on the lcd, press the SET key. The new
settings are saved in temporary memory and the flashing arrow disappears.
When all setting changes have been made, press the left key. The display will show :
The operator can now update the settings and has two options at this point:
(i) The operator presses the SET key and the working rnemory is updated and the
changes are written to the EEPROM. The display shows
(ii) The operator presses the RESET key to abandon the setting changes. The
display shows
SETTINGS
RESTORED
3.4 Identifiers Group
This group contains items to identify the particular relay. The group contains three
items; one user identifier and two manufacturing identifies The user may set the user
identifier to to be any 32 character combination of alphanumeric and certain
punctuation characters. The manufacturing identifier5 are factary set software
reference numbers to identie the versions of the relay software, and are not settable
by the user.
3.4.1 Setting the user identifier
Starting h m the default display on the lcd
Press the right key
S m G S +
COMMUNICATIONS 4
Press the down key
COMMUNlCATIONS I,
IDENTIFIERS +
R-5930
Chapter 7
Page 21 of 35
USER I.D. =b
SOFTWARE No.S 4
Press the nght key
USER IDENTDFIER
-+=-a NOT DEFINED
The relay is despatched with the above user identifier.
To change the user identifier, press the nght key. The first character will begin to
flash, alternahg between the character and an underscore. This 1 s t step will not be
possible if a remote terminal is in use and the access level is set to L m
Use of the left and nght keys allows the user to move dong the identifier a> the desired
character. Pressing the left key at the first character or the nght key at the 32nd
character causing the selected character to rnove to the 32nd or first character
respectively.
The up and down keys can now be used to change the character, stepping through the
ASCII table as given in section 4.4.
When the desired user identifier has been entered, pressing the SET key will move out
of setting mode. A further press of the left key will then give the option of updating or
ignoring the user identifier change.
* =
3 -4.2 Manufa~turersidentifia
M e n the display shows:
USER LD. i)
SOFTWARE No.S
pressing the up or d o m key will display the manufactures identifia. These consist
of the operating system number, displayed as:
OPERATING SYSTEM
18 LFAA 001 A
and the scheme reference number, displayed as
SCHEME No. 10101
18 LFAA 002A
LFAAlû2 R-5930
Service Manual Chapter7
Page 22 of 35
Pressing the up or down key will change between the two displays, and pressing the
left key wiil r e m to
USER LD. i)
SOFLWARE N0.S .C
3.5 Counter Reset Group
In this group counters can be reset to zero. To be available for resetting a counter must
have some valid text entered in the DISPLAY NAME area in the ladder diagram. It
will not be possible to reset a counter if its display name is blank or al1 dots.
Entry to the counter reset group will be blocked if the block counter resets software
relay is on. In this case the display shows: -9;
ENTRY BLOîKED TO
COUNTER RESETS
Starting h m the defauit display on the lcd
PRINT *
SETI'INGS a
Press the nght key
SElTINGS i)
COMMUNICATIONS C
Press the down key
COMMUNICATIONS *
IDENTlFIERS 4
RESET CDUNTERS *
TEST RELAYS C
The operator is free to reset the counters and has two options at this point:
(i) The operata presses the SET key and the selected counters are reset in working
memory and changes are written to the EEPROM for the non-volatile
counters.The display shows
(ii) The operator presses the RESET key to retain the current counter contents.
The display shows
COUNTERS NOT
RESET
If the display shows
The operator cannot met the counters and has two options at this point:
(i) Wait until the conditions which have caused the block counter resets
software relay to be on cease to apply, whereupon the counters can be reset.
(5) The operator presses the RESET key to abandon the counter resetting changes.
The display shows
COUNTERS NOT
RESET
Further presses of the left key wiil retum to the default display, then the condition
which has caused the blocking alaxm to be enabled can be determined and suitable
action taken.
-- k
If the block output test software relay is on or a remote terminal is king used and the
access level is set to LIMlTED, the typical display will be:
OUTPUT 1 1s ON
TEST BLOCKED
If the block output test softwarerelay is off and, if a remote terminal is king used,
and the access level is full
OUTPUT 1 1s ON
PUSH *TO OPEN
Pressing up or down will now allow al1 th,eoutput relays to be viewed in rotation, and
testai as before.
If àremote terminal is in use, there is a delay of about 1 second between releasing the
key and the output relay reverting to its normal state.
Seventh press
S-VIEW INPUTS
A-NEXT (OUTPUTS)
Eighth press
S-VIEW OUTPUTS
A-TEST TIMERS
Ninth press
S-TEST TIMERS
A-DEFAULT
The tenth press ~ t m tos the default display.
At any of the above options the SELECT/RESET key will select the option
on the top line. The menu will behave as follows for each option :
3.7.1 Status 1Alarms (Red led stably lit)
When the display shows:
S-RED ALARIbG
A-NEXT(FLASH1NG)
Pressing the SELECI'IRESET key will allow any Status 1 alarrns which are enabled to
be viewed. On the fmt press of SELECT/RESET the fmt enabled alm,or if no
a l a . are enabled the message NO ALARMS ENABLED, is displayed. On the
second press of SELECï/RESET the second enabled d m is displayed and so on
until the last enabled alam is king displayed. The next press of SELECTtRESET (or
the second if no status 1 alarms are enabled) will cause the menu to r e m to the
previous selection option, in this case the default display. If the ACCEPT/READ key
is pressed at any point in this option the menu will r e m to the top of the option, ie
Pressing the ACCEPT/READ key again will move on to the compound alanns option.
3 -7.2 Compound Alarrns (Red led flashing)
When the display shows:
S-RED FLASHING
A-NEXT (AMBER)
R-5930
Chapter 7
Page 28 of 35
Pressing the SELECT/RESETkey will allow any cornpound dams which are enabled
to be viewed. On the fmt press of SELECT/RESETthe frst enabled alarm ,or if no
a i e are enabled the message NO ALARMS ENABLED, is displayed. On the
second press of SELECT/RESEX the second enabled alm is displayed and so on
until the last enabled alaxm is king displayed. The next press of SELECT/RESET(or
the second if no compound darrns are enabled) will cause the menu to return to the
previous selection option, in this case :
S-RED ALARMS
A-NEXT(FLASHMG)
If the ACCEPT/READ key is pressed at any point in this option, the menu will r e m
to the top of the option, ie.
S-RED FLASHING
A-NEXT (AMBER)
Pressing the ACCEPT/READ key again will move on to the status 2 alarrns option.
3.7 -3 Status 2 Alamis (amber led stably lit)
When the display shows:
S-AMBER ALARMS
A-NEXT(FLASHING)
Pressing the SELECï/RESET key will allow any Status 2 alarrns which are enabled to
be viewed. On the fmt press of SELECT/RESETthe fmt enabled alam, or if no
alarms are enabled the message NO ALARMS ENABLED, is displayed. On the
second press of SELECï/RESET the second enabled d m is displayed and so on
d l the last enabled alarm is king displayed. The next press of SELECT/RESET (or
the second if no status 2 alarms are enabled) will cause the menu to r e m to the
previous selection option, in this case :
S-RED FLASHING
A-NEXT (AMBER)
If the ACCEPT/READ key is pressed at any point in this option, the menu will r e m
to the top of the option, ie
S-AMBER ALARMS
A-NEXTÇFLASHING)
Pressing the ACCEPT/READ key again will move on to the change alanns option.
LFAA102 R-5930
Service Manuai Chapter 7
Page 29 of 35
3.7.4 Change-
When the display shows:
S-AMBER FLASHING
A-NEXT(C0UNTERS)
Pressing the SELECï/RESET key will allow any change a l a m which are enabled to
be viewed. On the fmt press of SELECT/RESET the first enabled alam, or if no
alarms are enabled the message NO ALARMS ENABLED, is displayed. On the
second press of SELECURESET the second enabled alam is displayed and so on
until the last enabled alam is king displayed. The next press of SELECI'/RESET (or
the second if no change alarms are enabled) will cause the menu to r e ~ to
n the
previous selection option, in this case :
S-AMBERALARMS
A-NEXT(FLASHING)
If the ACCEPT/READ key is wssed at any point in this option, the menu will r e m
to the top of the option, ie
S-AMBER FLASHING
A-NEXT(C0UNTERS)
Pressing the ACCEPT/READ key again will move on to the counters option.
Pressing the SELECï/RESET key will display the first counter, in the form of the
counter message as entami in the ladder diagram in the counter messages section, on
the top line of the lui, and the value on the lower line. The value consists of the
difference between two operands, each of which can be either a fixed value, a counter
coi1value or a user adjustable counter target value. On the second press of
SECT/RESET the second counter is displayed and so on until the last counter is
king displayed. The next press of SELECT/RESET (or the first if no counter
messages have been entered in the ladder diagram) will cause the menu to rem to the
previous selection option, in this case :
S-AMBER FLASHING
A-rn(C0UNTERS)
If the AC(Xl"ï/READ key is pressed at any point in this option, the menu will rem
to the top of the option.
Pressing the ACCEPT/READ key again will move on to the settings option.
LFkAl02 R-5930
Service Manual Chapter 7
Page 30 of 35
The next press of SELECï/RESET will cause the menu to move to the previous
option display, in this case.
S-VIEW SETITNGS
A-NEXT (INPUTS)
Pressing the ACCEPT/READ key at any point dunng the view inputs option will
cause the menu to move to the top of this option, ie
S-VIEW INPUTS
A-NEXT (OUTPUTS)
Note: Inputs 14,15 and 16 on each printed circuit board are not available on the relay case
terminais, but are dummies, connected to plugs and sockets on the pnnted circuit
board, The plugs and sockets are set in the factory to simulate the input king on,
therefore the input displays for them will always be on also. ex
The ladder diagram software contains the number of input pnnted circuit boards used
in the scheme. The menu system uses this information to only display those sets of
inputs which are used. Hence if up to 13 inputs are used, the first 16 will be
displayed, or if between 13 and 26 are used, 32 wili be displayed etc..
CHAPTER 8
COMMISSIONING INSTRUCTIONS
LFAA102 R-5930
SERVICE MANUAL CXbWïER 8
CONTENTS
DESCRIPTION
Application
Features
COMMISSIONING PRELIMINARIES
Handling of Electronic Equipment
Earthing
Inspection
Wiring
Insulation
COMMISSIONING TESTS
Test Equipment
DC Auxiliary Supply
Relay Setrings
Functions
Counter Targets
Relay Tirners
Functional Checks
Initial Checks
Test Output Relays
Test T i r n a
Test Inputs
Indications and Alarrns
Status 1 Alanris
Compound Alarms
Status 2 Alarms and Change Alarms
Resetting of Indications and Alarms
Checks with Circuit Breaker
LFAAIO;! R-5930
Service Manual Chapter 8
Page 1 of 12
Section 1 DESCRIPTION
1.1 Application
The W U 1 0 2 is designed for application at a line end switched by two circuit
breakers, typically at a one and a half switch substation. The designated leader circuit
breaker CBl can be selected to perform a single shot or two shot, single phase, three
phase or singldthree phase auto-reclose cycle. The follower circuit breaker CB2 is
n o d y arranged to perfonn a three phase reclosure when CB 1 has reclosed and
remained closed for a set "follower Cl3 time". For single phase auto-reclose cycles,
CB2 can be selected to trip single phase and reclose simultaneously with CBl.
Another user-selectable option is for CB2 to automatically take over the selected CB 1
duty cycle if CB 1 is not available for auto recloshg.
When a three phase reclosure is desired the equipment will convert any single or two
phase tripping tothree phase before initiating the reclosure. The LFAA102 relay
obtains information about the status of the circuit breakers, protection relays and
auxiliary plant by way of auxiliary contacts on the equipment. These contacts switch a
dc voltage to the LFAA which is Ntered and stored to indicate the state (open or
closed) of the extemal contacts. This information is used in a ladder diagram software
to determine the sequence and timing of the operation of the output relays. The output
relay contacts are voltage free and cm be norrnally open, n o d y closed or change
over.
1.2 Features
Selectable single andlor three phase autcmxlosing.
Suitable for feeders controlied by two circuit breakers.
AU timers are independantiy adjustable
Scheme logic options can be selected.
User friendly inbuilt keypad and menu system.
Built in test facilities
Section 2 COMMISSIONING PRELIMINARIES
I -
2.1 HandlÛig of Electronic Equipment
. Refer to Chapter 3 before handling electronic circuits which rnay be sensitive to
electrostatic voltage discharges. With the front panel closed the relay is completely safe
h m electrostatic discharges.
Open the front panel and inspect the relay modules prior to commissioning the relay.
Before this inspection, the operator should touch the earthed panel to discharge any
electrostatic voltages.
If modules are removed from the case, they should be handled by the front plate frame
or edges of the printed circuit boards to avoid contact with elecmcal componenets or
connections. Always store and transport modules in electx-ically conductive anti-static
bags.
If it is necessary to work on a module, then the module should be placed on an anti-
static surface and a conductive wrist smp should be worn, both should be earthed.
LFAA102 R-5930
Service Manual Chapter 8
Page 2 of 12
Ensure that the case earth tenninal above the rear terminal block H is used to connect
the relay to the local earth bar.
2.3 Inspection
With no dc auxiliary voltage connected, carefully examine the relay to ensure that no
damage has occurred during transit. Check on the h n t name plate label that the model
number and rating information are correct.
Vx (1) - Rated voltage of auxiliary supply to the power supply module.
Vx(2) - Rated voltage of auxiliary supply to the opto-isolated status inputs.
Remove the relay wver and open the front panel by undoing the large screw on the
right hand side of the font plate. The equipment label on the back of the front panel
contains infomiation on model number, serial number, fïmware reference, external
connection diagram number and details of the h n t panel and modules fitted in the
relay. Check that the moduie references are correct and the modules are fitted into the
carrectpositions and complete the comrnissioning test record details as printed.
Close the front panel and tighten the front panel screw.
Check that the extemal wiring is correct to the relevant external connection diagram
a n d h scheme diagram.
The insulation of the relay and its associateci wiring may be tested betweem-
(a) all electricaily isolated circuits.
(b) all circuits and earth.
An elecmnic or bmshless insulation tester having a voltage not exceeding lûûûV dc
should be used Accessible terminais of the same circuit should first be strapped
together. Deliberate circuit earthing links removed for the tests must be subsequently
replaced.
LFAA 102 R-5930
Service Manual Chapter 8
Page 3 of 12
then
?
( * = + and C flashing altemately.)
Table 1
Fauit m f o r Fadt type for Fadt type for Set Function Lin
1Ph AR 3Ph 3Ph ( 1 4 N MFF)
High Speed ARDelayed AR 1 2 3 4 5
Single Phase Single Phase - -
Auto-Reclose Oniy 1 1 0 0 0
Three Phase Single Phase
Auto-Reclose - WY - 1 0 0 1 0
Type A
Three Phase
Auto-Reclose - Any Fauit - 1 0 1 1 0
Type B
Three Phase Single Phase
Auto-Reclose - MY Multi-Phase 1 O O 1 O
Twe C 1 I I I
AR Program Fault type for Fault type for Fault type for Set Function Links
1st shot 1st shot 3Ph 2nd shot 3Ph ( 1 4 N WFF)
1Ph AR HighSpeedAIQDelayedAR 1 2 3 4 5 6
Three Phase Single Ph Single Ph
Auto-Reclose - O ~ Y
'
O~IY O 0 0 1 1 0
Type A
Three Phase Single Phase
Auto-Reclose - O ~ Y Any Fault O 0 0 1 0 0
Type B -*
II.
DEAD TIME
High Speed Single Phase 32% or
Reclosing 0.01 - 2.0 seconds -10 + 20ms
High Speed Three Phase 52% or /-*
The relay should be checked for correct operation before being allowed to function
with the circuit breaker.
(b) Isolate the CB mp and close output contacts, either by removing the CB trip and
close circuit fuses, or by disconnecring the leads on tennina1s:-
G10, G12
E9, E l l , E13, E15, E17, El9
E10, El2
Dg,D11, D13, D15,D17, Dl9 }
D10, D12, D14, D16, D26, D28) If applicable
3A.2 Test Output Relays
The output relays can be tested starring fiom the message LFAA102 AUTO-
RECLOSE on the lcd as foilows:-
SETIWGS C
NOTE change of state of Output 1, release SET button, display should revert back
t0;-
DISPLAY READS OUTPUT 1 is OFF
PUSH *
y-.
Pressing C or t will allow al1 the output relays to be viewed in rotation and tested as
before.
WAA102 R-5930
Service Manual Chapter 8
Page 10 of 12
Start -
- F27
timer 1
External Timer
F25
I
> A ,
I !
Select Menu to TEST TIMERS on lcd by means of the ACCEPT/READ key. The
display should read
S-TEST TlMERS
A-DEFAULT
PRESS SELECï/RESET DISPLAY READS INTER TRIP TIME
(typical setting) 20.00
PRESS ACCEeT/READ DISPLAY READS INTERTRIPTlME
READY 20.00
Operate external double switch DISPLAY READS INTERTRTPTIME
(starts external timer and and counts down RUNNING
intemal timer) time
On completion of timer setting count dom, external timer reads timer setting and lcd
reads:-
INTER TRIP TIME
COMPLETE 0.00
The rernaining timers can be checked by following the above steps unaï the display
reads:-
S-TEST TIMERS
A-DEFAULT
then pressing the SELECT/READ button which allows the tirners to be viewed in
rotation and then test as before.
R-5930
Chapter 8
Page I l of 12
(a) Status l alarms, indicated by the red led king stably lit
(Lockout CB 1 and Lockout CB2).
(c) Status 2 Alarms, indicated by the amber led king stably lit
(Auto-Reclose in Progress ).
/-.
3 S. 1 Status 1 Alarms (red led stably lit)
Starthg with the lui reading the message LFAA102 AUTO-REOSEm l 1 through
the menu by pressing the ACCEPT/READ button until the lcd reads:-
S-RED ALARMS
A-NEXT (FLASHING)
By pressing SELECURESET button allows any Status 1 Alarms which are enabled to
be viewed eg Lockout CB 1.
If Status 1 Alarm is not lit then by following the procedure above the lcd will read:-
R-5930
Chapter 8
Page 12 of 12
The next press of the SELECT/RJ3ET button will cause the menu to retum to the
previous selection option, in this case LFAA102 Auto-Reclose. If the
ACCEPT/READ button is pressed at any point in this option, the menu will return to
the top of the option, ie
S-RED ALARMS
A-NEXT (FLASHING)
Pressing the ACCEPT/READ button again will move on to the Compound Alarrns
Option.
3.5.2 Compound Alarms ( r d led flashing)
Scroll through the menu by means of the ACCEPT/READ button until the display
reads:-
S-RED FLASHING
A-NEXT (AMBER)
The procedure is then as previously described for the Status 1 A l m for viewing the
enabled alaxms, e.g. Maintenance Lockout CB 1.
3.5.3 Status 2 Alarms (amber led stably lit) and Change Alarms (amber led flashing)
These are viewed in the same way as previously described for viewing the enabled
dams, e.g. Status 2 Alarm - Auto reclose in progress and Change A l m s -
Maintenance A l m @re-lockout warning).
3.5.4 Resetting of Indications and Alarrns
Status 1 Alarm - red led stably lit.
Connect the correct dc auxiiiary voltage Vx(2) to relay tenninals BI0 and
B22(+ve) and B28(-ve) via a single pole switch. Close the switch and the alarm
resets (mi led extinguishes).
Compound Alarms - red led flashing
Connect the correct dc auxiliary voltage Vx(2) to relay terminais B12 and B24
(+ve) and B28(-ve) via a single pole switch. Close the switch and then view the
compound alarms messages as described in 3.5.2. The red led will then be
extinguished.
Status 2 Alam - Amber led stably lit
This d m is only lit whilst auto-reclose is in progress. On completion the led
extinguishes.
Change Alarms - amber led flashing
This indication is cancelled by viewing the change alarms messages, as
described in 3.5.3.
3.6 Checks with the Circuit Breaker
Remove test connections and reconnect al1 the back wiring that has been removed for
testing. If the system conditions allow circuit breaker operation to take place, final - --
operation sequence checks should be carried out initiated by o p t i o n of protection
contacts.
LFAAlO2
SERVICE MANUAL
CHAPTER 9
FAULT FINDING INSTRUCTIONS
WAA102 R-5930
SERVICEMANUAL (XAPTFLR9
CONTENTS
PROBLEM ANALYSIS
Introduction
Fault Finding Procedure
Initialisation Process
POWER UP FAILURES
SELF CHECKING FAILURES
Power On Diagnostics
Diagnostic System Emrs
Error Flags
System Error Codes
OPERATIONALFAILURES
Module Verification
Power Supply Module Verification
Mimprocessor Module Verification
Front Panel Module Verification
Relay Output Modules Verification
Status Input Module Verification
Sena1 Port ExTms
LFAA 102 R-5930
Service Manual Chapter 9
Page 1 of 9
The following fault finding documentation is to enable the user to identify faulty
components of the relay d o m to module level. With the exception of the power
supply fuse there are no user serviceable parts within any module.
The procedure for repair is to identify the faulty module and replace it with the
appropriate spare. The faulty module should be retumed for repair and re-calibration
wiùl as much information regarciing the fault as possible.
When ordenng, and before fitting a new or replacement module, the module assembly
number and,in the case of the mimomputer module, software reference numbers
should be checked against the numbers found on the label on the inside of the front
panel. The assembly number is on the lower labelling smp at the front of the module,
and the software reference numbers on a label on the module sideplate. When the relay
is powered up, the software reference numbers can also be seen in the Identifiers
section of the user interface (Chapter 7 section 3.4.2).
This documentation assumes the user is conversant with the operating instructions and
the hardware arrangement of the relay .
The relay must be de-energized before the hinged front panel is opened and any bus
connections removed. Failure to wmply with this instruction rnay result in damage to
the electronic circuits of the modules or corruption of non-volatile memory.
Modules must be removed fnrm the case with the appropriate extraction tool to prevent
damage to the modules.
With the hinged front panel open electrostatic discharge precautions must be observed.
.---
1.2 Fault Finding Procedure
Problems which arise in the LFAA relay as a result of a faulty module will usually
result in one of the following occuning:-
The relay will fail to power up or initialise correctly.
The diagnostic routines wili lock the relay out.
The relay will not funtion correctly.
The following fault fînding instructions are therefore divided into these 3 main areas:-
Power up failures.
Self checking failures.
General operational failures.
LFAA102 R-5930
Service Manual Chapter 9
Page 2 of 9
Depending on the type of failure found, refer to the relevant section below. Some
sections consist of flow diagram type instructions to locate the faulty module.
** IMPORTANT **
Before beginning any fault finding procedures, visually check al1 connections and link
positions on ail of the modules (See Chapter 3).
Ensure all modules are in their conrect position in the relay case. This is indicated by
the module identification numben corresponding with the module numbers on the
relay case and with the module identification list fixed to the inside of the hinged front
panel.
When replacing modules ensure the replacement has the same module number as that
which it replaces. -
Ensure no modules show signs of obvious damage through improper handling of the
modules.
Check that the nbbon cable bus is connected correctly to each module and that no
socket pins are bent or otherwise damaged.
When the relay powers up normally the following sequence of events should occur
The lcd displays faint black squares.
AEter approximately 3 seconds the message COLDSTART CHECK together with the
diagnostic program version number will be displayed on the top line of the lcd,
followed by a watchdog timer test message.
The top line will then display DIAGNOSTIC CHECK and the bottom line of the lcd
will change to show various diagnostic messages. This takes about 10 seconds.
The logic conmller software is then executed which is indicated by the relay display
name, as entered in the ladder diagram, or an EEPROM error message being displayed
on the lcd. If an EEPROM ermr is detected the software will wait for the left key to be
pressed, after which it will continue. This is to allow the operator the option of having
the EEPROMs replaced or continuing, and checking the items in the section of
EEPROM indicated, as detailed in Chapter 5.
Rovided it is entered in the ladder diagram, the green RELAY HEALTHY led will
light to indicate that the ladder software is running. The other leds may also light,
depending on the state of the relay and any enabled alarms.
LFAAlo2 R-5930
Service Manual Chapter 9
Page 3 of 9
TELI
ch& failures
Q
shortslbreaks. ,supph/ module
Display still
The LFAA relay contains self monitoring and diagnostic routines which are executed
when the relay is energized. These check the main components of the relay to ensure
that there is nothing drastically wrong with the system. This, coupled with the
watchdog feature, ensures that the software should never execute if the relay is faulty.
Obviously every possible fault cannot be guarded against and certain faults will still
enable the relay to function. These faults are covered in Chapter 7
3.1 Power On Diagnostics
When the relay is switched on it performs a number of system diagnostic checks to
ensure the relay is fully operational. These especially concem the main mimprocessor
and memory. During the checks the lcd displays messages to indicate the current test. --
3-2 Diagnostic System Emrs
A diagnostic system error will cause the relay to reset and display a message on the
top line of the llcd of the form RESET C0DE:XYZZ where XY is a 2 digit
hexadecimal number representing various e m r flags, and 22 is a 2 digit hexaàecimal
error code which is used to determine the cause of the emor. Under normal reset
conditions this message only remains on the display for approximately 3 seconds as it
is cleared by the application program when that restarts. In the case of a lockout
situation this message will be visible constantly.
There are 8 error flags available, each of which is represented by a bit in the error fiag
byte which is displayed as a 2 digit hexadecimal number on the lcd. Only 5 flags are
currently used: bits 0,1,2,3 and 7. It is possible for more than one flag to be set which
means the erra flag number can have the values: 00-OFand 8û-8F.
In the descriptions which follow, the possible values for the X and Y error flag
numbers quote&indicate the ermr flag numbers which could be generated by the
relevant bits king set.
Bit 7 - Lockout (enor flags: X=8)
If bit 7 is set the first e m r flag digit will be 8 which indicates that the erra is fatal. If
this occurs the relay will be locked-out, Le. disabled from functioning, and can only
be re-enabled by r e m d g the auxiliary dc supply to the relay. This will also be
indicated by the lcd display altemating between RESETCODE:8YZZ and
LOCKOUTCODE:8 Y Z approximately every 3 seconds.
Bit O - Diagnostic test (error flags: Y=1,3,5,7,9,B,D,F)
R-5930
Chapter 9
Page 5 of 9
If bit O is set the power on diagnostic routines will be executed before the relay
funetion continues. This would normally only occur if the application program
discovers a system error but requires venfication before the relay locks out .This bit
will be cleared on successful completion of the diagnostic tests.
Bit 1 - Watchdog inoperative (emr flags: Y=2,3,6,7,A,B,E,F)
If bit 1 is set it indicates that the watchdog is out of tolerance. This should not prevent
the relay from operating unless it is grossly under tolerance, in which case it may
cause the relay to reset continuously and eventually lock out due to the high number of
resets that have occmed. This bit is usually only changed during the coldstart
diagnostic check.
Bit 2 - Background mor (error flags: Y=4-7, C-F)
If bit 2 is set the error condition was caused by the background self monitoring routine
which regularly checks the system memory. The error code will disclose which type
of memory is faulty.
Bit 3 - Excessive number of soft mors (error flags: Y=8-F)
Bit 3 is set after 100resets have occuned since the last power-on. This also locks the
relay out to prevent any further operations so bit 7 will also be set. The e m r code will
indicate the cause of the last reset which should be investigated. An m r code of 08
will also be generated if no other error code is pending. The relay cm be restarted after
switching off its auxiliary dc supply for a few seconds.
3.2.2 System Esror Codes
The error code number ranges from û0-FFh. Error code nuinbers in the range 01-2Fh
indicate a system enor. Higher e m code numbers indicate an application program
generated error.
Error code 00 - Hardware or no error.
If the errm code is 00, the pmcessor reset was caused by the relay hardware. Probable
causes of this error code would be the watchdog timing out, which may indicate that
the software has crashed; or a non-maskable interrupt (NMI)occuning. This should
not normally cause lockout on its own but normally would be associated with an
excessive number of resets. If this is the case try replacing the microprocessor
module.
Error code 01 - Processor error.
During the power-on diagnostic routine the processor is checked for functionality.
This includes testing all of its registers and flags and conditional jump instructions.
The relay is locked out with an error code of 01 if any of these tests fails. The
mimprocessor module should be replaced by a spare and the faulty module retumed
for repair.
-
E m r code 02 RAM error.
R-5930
Chapter 9
Page 6 of 9
A readlwrite test is done on the entire RAM during the power-on diagnostic RAM
TEST,and the relay is locked out with an error code of 02 if this test fails. The RAM
is also tested regularly whilst the application program is executing and, if this
produces an enw, the relay is reset and the power on diagnostics perfonned. Only if
these also produce an error will the relay be locked out. The microprocessor module
should be replaced by a spare and the faulty module returned for repair.
Error code 03 - EPROM mur.
The E p m s used have a checksum of zero. This checksum is checked during the
power on diagnostic EPROM TEST and also regularly whilst the application program
is executing. The relay is locked out if the checksum test fails during the power-on
diagnostic routine. Two checksum failures are required during the background
EPROM test fur added security as it is unlikely that this test will fail. It is more
probable that the checksum maintained in a RAM variable will fail due to interference. A
If two consecutive checksum tests fail the relay is reset and the power on diagnostics
perfonned Only if these diagnostics fail will the relay lock out. When a checksurn
e m r occurs a message will be displayed on the bottom line of the lcd of the form :
'AAAA-CHKSUM:CCCC' where AAAA indicates the staxting segment of the failed
EPROM and CCCC is the checksum value which the diagnostics detected. The
mimpracessor module should be replaced by a spare and the faulty module retumed
for repair.
Error code O8 - Excessive number of soft errors.
When an excessive number of soft enors occurs, bit 3 of the e m r flags is set and the
relay is locked out. If no other error code is pending at this time, an e m r code of 08
will be generated. Otherwise the mcode will indicate the last reset e m r which
caused the excessive number of resets.
Error code 09 - lcd RAM emr.
The power-on diagnostic routine writes 4 bytes of test data into a RAM location of the
front panel lcd RAM area and reads them back for cornparison. The test detemiines if --..
the lui can be addressed and that the bus connections have no shorts or open-circuits.
The relay will lock out with an error code 09 if the test fails. Check the bus
connections to al1 modules and replace the nbbon bus if necessary.
Error code 11-1A - Conml register read/write emr.
Each control register in the intemipt controller, DMA conmller and timer is tested. If
any of them fail this readtwrite test, the relay is locked out. The microprocessor
module should be replaced by a spare and the faulty module returned for repair. The
error code indicates which register failed as follows:
11- int mask register 16- DMA 1 control register
12- int priority mask register 17- intû control register
13- int status register 18- intl control register
14- timer control register 19- int2 control register
15-DMAO control register 1A- int3 control register
R-5930
Chapter 9
Page 7 of 9
Should the relay be suspected of king faulty, each module cm be tested to verify that
they are workuig correctly. Faulty modules can therefore be identified and replaced.
This procedure is outlined in 4.1.
Module Verification
The input and output modules c m be tested using the test options avaîlable from the
front panel menu stnicture. These can be selected from the mot of the menu structure
by using key sequences given in chapter 7 sections 3.6, 3.7.7 and 3.7.8.
Power Supply Module Verification
The power supply has already been covered in section 2 of this chapter. Check the
voltage rails brought out on the parallel test port as described in that section and that
the power fail relay operates correctly when the supply is switched on and off. A
faulty power supply can also be the cause of spurious resets, which can lock the relay
out when they reach the reset lirnit of 100 resets.
Microprocessar Module Verifcation
The microprocessar module is tested extensively during the power-on diagnostics. To
verify that it is working carrectly therefore, switch off the auxiliary dc supply to the
relay. Then switch it back on and observe the diagnostic check messages on the front
panel Icd. A lockout erra code of 01 or 11-20h indicates a faulty microprocessor
module which should be replaced. In catastrophic cases of failure, the alarm messages
on the Icd may not make immediate sense.
Front Panel Module Verification
A faulty front panel can be identified quite easily by visible inspection and use of the
key pad. Failure of the l i i d crystal display driver may result in maloperation of the
operator interface.
Relay Output Modules Verification
Individual contacts on each relay output module can be changed from the front panel
to venfy that these modules function correctly. Because this function allows any of the
relay contactsto be changed it could cause circuit breakers to trip or close if they are
comected Before using this option, therefore, be aware of the consequences of
changing the contacts and disconnect the output contacts from extemal equipment if
required. This option can only be used if the block output test software relay is off.
Status Input Module Verification
Select the VIEW INPUTS option as outlined in Chapter 7 section 3.7.7. The inputs
can be tested by applying the appropriate auxiliary voltage Vx(2) amss the relevant
status input connections at the rear of the relay and monitoring the lcd. It should be
noted that the status inputs still carry out their normal functions during this test.
Input 14,15 and 16 on each printed circuit board are dummies, controlled by the plugs -A %
in JM 3. The plugs are inserted in the factory, so that these inputs will always be read
as on. If the plugs are removed and the test repeated these inputs should be off.
WAA102 R-5930
Service Manual Chapter 9
Page 9 of 9
POWER SUPPL I
4 D l4
ft Input Filter
Sw Series Switch
In Integraimg Network Power Fail
Sn Voltage Sensor -19.5V
Mn Pulse idt th Modulator
OsPi Oscillator/Frequency Divider
OP Output Stage
Uvm Undervoltage Monitor
y0 BUS
INTERFACE
t t 4 7
RELAY DRIVE
BUFFER
OUTPUT
RELAY
ELEMENT
OUTPUT
RELAY
ELEMENT
MEMORY
INTERFACE
M C
ROCESSOR
H tTtERS
INTERRUPTS
n VOBUS
INTERFACE
,
d
I'
LFAA 102 R-5930
Savice Manual Appendix
Page 5 of 20
INPUT 4 om-
ISOLATED
BUFFERS
INPUTS
I/o
BUS
BUS
CRYSTAL
TERMMATIONS DISPLAY
OUTPUT
A BUFFERS
STANS
BUS INDICATION
INTERFACE
VO
BUS INPUT
BUFFERS
-- Page 11 of 20
AUTO-RECLOSE-
FUNCT 2 = OFF
3 PH AR
COMMUNICATIONS
AUTC
t S-AMBER ALARMS
A-NEXT (FLASHING)
display any enabled dams, then
-
1
, k .
COMMUNICATIONS
......(FIGURE1%)
IDENTIFIERS...................(FIGURE 15d)
1 L TEST RELAYS.................(FIGURE 1 3 )
VIEWNG. ........................(FIGURE 15g)
COUNTERS ....................PRINTING IN
PROGRESS
. T 0.01
timer 2 .......C C
0.01
-SET COUNTERS
-SET
. -
FUNCTIONS
r get 1
target 2
1 PHASE ONLY
.......C C
.......
CC
FUNCT 1 = ON ....... C C
FuNCT2=OFF .......C C
ANY FAULT TYPE
KEY:
** Check block semngs flag when entering and leaving group
? ? Check for setting changes when leaving group
-
C C Indicates this may be changed
-
entered via relay keypad
SOFIWARE NLTMBERS
r SCHEMENO. XXXXX
18LFAA XXX X
OPERATING SYSTEM
18LFAA XXX X
KEY:
? ? Check for setting changes when leaving group
C C Indicates this G y be changed
LFAA102 R-5930
Service Manual Appendix
Page 17 of 20
--a
RESET COUNTERS -,
* ?* counter 1
5
-PRESS
counter 1 ....... R R
DOWN TO RESET
I
counier 1
TOBE RESET 5
-counter
t- counter 2
1O
l
2 ....... R R
PRESS DOWN TO RESET
couxiter 2
TOBERESET 10
KEY:
** Check block mets flag when entering and leaving group
--\
? ? Check for enabled resets when leaving group
R R indicates counter may be reset by pressing the d o m anow key
t * *-OUTPUT2ISON
*
PUSH TO OPEN push SET to
w n f m command
KEY:
** Check block output test software relay when entering function
I
DEFAULT
y~i* scrolls through
enableâ a l m s , then
ALARMS
1 : scrolls through
enable. alarms, then
1
1
3
2
I1
scrolls through
enabled a l m s , then
I
J
1 scrolls through
CHANGE fLARMs enabled alarms, then
2 scrolls through
1 counter displays, then
y SE'XTINGS
2
see sub map (figure 15h)
selects displayed 2
tirner for t e s ~ g
VIEW S r n G S
.-y
\
NOTE
MOUNTING SCREWS
ARE NOT PROVIDEO
TERMINALS
SEE
ARRANGEMENT
DRAWING FOR
NOMINAL HEIGHT 4U
FRONT I
ALLOW A MINIMUM OF 5 0 FOR 1 6 5 . 1 f 1 . 6
TERMINAL BLOCK & WlRlNG
i0.6-l l-- TOLERANCE BETWEEN ANY TWO HOLES
FIXING HOLE DETAII, WlTHlN A DISTANCE OF 1 METRE TO BE f0.4
I REVISION
NOTES: "%MO008
NO
'
'
SHEET
NOTE:
MOUNTING SCREWS
ARE NOT PROVIDED
HINGED FRONT
PANEL PANEL CUT OUT
DETAIL
TERMINALS
DRAWING FOR
DETAIL
I I
64 WAY
1/0 BUS
.
OUTPUT RELAY P.C.B
8 FAST
CIRCUIT DIAC. 01 ZH0929
-t
FLEX CONN.
OUTPUT RELAY P.C.B
6 SLOW
CIRCUIT DIAG. 01 ZH0931
RLO OUTPUT RL1 OUTPUT RL2 OUTPUT RL3 OUTPUT RL8 OUTPUT RL9 OUTPUT RL10 OUTPUT
CONTACTS CONTACTS CONTACTS CONTACTS CONTACTS CONTACTS CON~ACTS
64 WAY
I/O BUS
.
OUTPUT RELAY P.C.8
8 FAST
CIRCUIT DIAG. 0 1 2H0929
-A
FLEX CONN.
OUTPUT RELAY P.C.B
6 SLOW
CIRCUIT DIAG. 01 ZH0931
y-?-T-L-?-?-a-?-?-g-l-
----
-L41 42 43 44 51 5 2 53 54 61 62 63 64 7 1 7 2 73 74
R L l l OUTPUT RL12 OUTPUT
CONTACTS CONTACTS
64 WAY 64 WAY
I/O BUS 1/0 BUS
MODULE TERMINALS
WEN QUOTING THE DRAMNG NUMBER ~YMBOLSGENERALLY A L S T O MTBD PROT'ECTION
(L C O N T R O LLTD
?LEAS€ STATE THE LATEST LETTER OF ISSUE TO B.S.3939 S T LEONARDS WORKS STAFFORD ST17 4LX ENGLAND
0 0 NOT SCALE
. #
DIMENSIONS ARE IN mm
B
THIRD ANGLE --@- a ,
1 REf 1 DESCRIPTION
1 : 1I
6 MICRO COMPUTER
-TUS INPUT
'
1
GM0024
GM0069
- I
REAR VlEW
-2
2 8 WAY MAX
EACH WAY ACCEPTING : -
2 - M4 RlNG TERMINALS
OR
2 - 4,8 x 0.8
SNAP ON TERMINALS
OR
1 - RlNG +
1 - SNAP ON TERMINAL
-28
FOR OUTLINE AND MOUNTING DETAILS REFER TO ORAWING GM0008 SHEET 1 ARRANGEMENT MODULAR M 4 SCHEME ,- RACK MTG
TYPE LFAA102 RELAY
GMDD97 ADDED TO REF 1 CDN R1925 REFERS PRODUCT AUDIT 5 1 1
D NEN "%MO054
NO 01 5.
SWEET
NEXT SHT
' '
ALST0)M
17/09/1998 NAME SDEGG CAD DATA 1: 1 A3 -
-- - - -- - -
IRG No G I ;i5015 SHT No 1 1 DO NOT SCALE fi
I
DIMENSIONS ARE IN m m L# THIRD ANGLE --@ a #
I
7 -
6
7
MICRO COMPUTER
STATUS INPUT
1
1
GM0024
GM0069
REAR VlEW
-2
2 8 WAY MAX
EACH WAY ACCEPTING .-
2 - M4 RING TERMINALS
O O
OR
2 - 4.8 x 0,8
SNAP ON TERMINALS
I I I I I I I OR
1 -
RING +
1 - SNAP ON TERMINAL
I I I I I I I
TERMINAL BLOCK IS NUMBERED 1 TO 2 8
UNLESS OTHERWISE STATED
FRONT VlEW
TERMINAL BLOCK DETAIL
'
, NEXT-SHT ALST(5iM
m Ii ~
L n.7~
n U
untn .
1i . 4I
A7
n4
.--
O
o.,
. .
S. I
LFAA102
SERVICE MANUAL
COUNTER TARGETS
CB1 Maintenance Alarm
CB 1 Maintenance Lockout
CB2 Maintenance Alarm
CB2 Maintenauce Lockout
TIMERS (seconds)
Intertrip Time Manuai Close Time
Preclosing Check Time 1 Pole Dead Time
High Speed Dead Time Delayed Dead Time'
Close Pulse Time Reclaim Time
Trip Fail Lockout Time Foliower CB Tirne
Discriminate T i e
LFAAlO2
SERVICE MANUAL
Foliower CB Time
5 TESTINPUTS