Standard Design Fire Station Mar2021
Standard Design Fire Station Mar2021
Standard Design Fire Station Mar2021
Fire Stations
60
Reviewed (March-2021)
1
Standard Design Criteria
Fire Stations
2
Standard Design Criteria
Fire Stations
3
Standard Design Criteria
Fire Stations
1. General Requirements:
• The Fire Stations are comprised of three main essential elements: Apparatus Equipment
& Maintenance, Administrative & Training, and Living Areas.
• All Fire Stations will have either the Fire Extinguisher Inspection (Non Flight Line/ Flight
Line) Room, Clean-Up Room, or PPE Gear Storage Room based on Installation
requirements. If a PPE Gear Storage Room is required, the air quality requirements for
PPE storage in the Apparatus Bay will no longer be applicable.
• All Fire Station facilities shall be protected by an automatic fires suppression system and
full detection system. Provide carbon monoxide (CO) detection in all sleeping and living
areas defined as the individual dorm rooms, the dorm room access hallway(s), and the
entire day/training room. Activation of detectors shall sound a local alarm. If monitored by
the building fire alarm system, CO detectors shall be monitored as a non-latching
supervisory alarm initiating device. Activation of CO detectors shall not sound a general
building alarm. Provide fire alarm system smoke detectors in the individual dorm rooms
and the dorm room access hallway(s) only. Do not provide detection in the apparatus bay
or other areas where exhaust fumes may be present. Activation of smoke detectors shall
sound a general building fire alarm.
• Walls separating the living and administrative portions of the building from the apparatus
bay and maintenance spaces shall be completely sealed to prevent passage of exhaust
emissions and the resulting exposure to building occupants and contamination of spaces.
• Provide simultaneous light and audible control for the following spaces when the
firefighter alert system is activated: To the outside, Dorm Room dedicated alert lights,
corridor lights from Dorm Rooms to the Apparatus Bay, and the Apparatus Bay lights.
• Unless noted otherwise in this document, all ceiling heights shall be a nominal 8’-0”.
• Unless noted otherwise in this document, interior walls between rooms shall be provided
with acoustical batt insulation or other approved system, to obtain an STC rating of at
least 40. CAC shall be a minimum of 38.
• Provide steel doors with vision panels except at storage, janitorial, dorm,
electrical/mechanical and toilet areas.
• Where exterior windows are provided the following requirements shall be met. Shall
comply with ATFP requirements. Salient characteristics include easy to clean and able to
withstand continuous use. Individual windows shall be operable and screens shall be
provided.
• All interior glass shall be tempered safety glass and mirrors must be constructed with
break-resistant materials.
• Mounting height of all electrical outlets will be in accordance with industry standards.
• Unless noted otherwise in this document, all interior flooring material shall be resilient.
4
Standard Design Criteria
Fire Stations
• In storage rooms where shelves are provided, interior shall be marked with a red line 1
inch in width and located 18 inches below the lowest point of the sprinkler head.
• All caulking used inside the building shall be USDA or NSF approved caulking.
• Provide 100% capacity emergency generator back-up power for all Fire Stations.
• Provide site entrances, exits, service drives and any special circulation areas sized to
accommodate the largest vehicle that uses the area. The service drive shall have a
controlled access point.
• Based on the electrical design and mechanical/electrical loads, additional electrical room
may be added near the apparatus bay and/or second floor. It is the electrical designer
responsibility to coordinate with the architectural designer to accommodate additional
electrical room square footage requirements and location.
2. Apparatus Bay:
• FUNCTIONAL DESCRIPTION: The Apparatus Bays house the fire fighting and
emergency response vehicles. All bays must accommodate the latest and largest
structural and ARFF vehicles. Each bay of the Apparatus Room must include the required
support utilities (drops) for vehicles such as exhaust, compressed air, hot and cold water,
lighting, and power. Clear spans are preferred for the Apparatus Bays.
• ADJACENCIES: Located at the end of Fire Station structure for future expansion.
Adjacent to and direct access from Apparatus Bay Support areas and corridor access
from Administrative and Living areas.
• OCCUPANTS: Fire Station users and Fire fighting and emergency response vehicles
storage.
• MINUMUM AREA:
A Standard Structural Apparatus for a One-Company Fire Station shall be 45 ft. Wide X
91 ft. long (4,095 SF) net.
A Standard ARFF Apparatus for a One-Company Fire Station shall be 50 ft. Wide X 91
ft. long (4,550 SF) net.
A Standard Structural Apparatus for a Two and Three-Company Fire Station shall be 62
ft. Wide X 91 ft. long (5,642 SF) net.
A Standard ARFF Apparatus for a Two and Three-Company Fire Station shall be 70 ft.
Wide X 91 ft. long (6,370 SF) net.
An additional Structural bay shall be 17 ft. Wide X 91 ft. Length (1,547 SF) net.
An additional Structural bay shall be 20 ft. Wide X 91 ft. Length (1,820 SF) net.
5
Standard Design Criteria
Fire Stations
• PLUMBING: Provide minimum 3-in. diameter water service with 2.5-in. diameter
National Standard Threads ball-valve outlets, one (1) at the front of each bay and one (1)
at the rear of each bay. Provide an emergency eye wash fountain and shower. Provide
foot-operated mop sink with mop hanging rack. Provide connection for ice machine.
Provide standard cold water hose bibb for every two truck bays. Provide floor trench
drains to accommodate all vehicles. All apparatus room drains should connect to an
approved oil/water separator prior to discharge. If an exterior wash area is provided, size
the separator for the total volume and connect the exterior drain to this separator.
A complete Apparatus Bay Air Cleaning System shall be utilized consisting of exhaust
filtration for apparatus and for off-gassing from PPE. A hose based Fire Apparatus
Vehicle Exhaust Removal System (FAVERS) system may be used in conjunction with the
filtration system.
A Fire Apparatus Vehicle Exhaust Removal System (FAVERS) in compliance with NFPA
1500 to eliminate 100% of vehicle exhaust emissions. A direct vent system that
evacuates vehicle exhaust directly to the outside is the preferred FAVERS. Makeup air
should be distributed so as to minimize drafts and be introduced above apparatus level
6
Standard Design Criteria
Fire Stations
since diesel exhaust is heavier than air. In this way, the make-up air flow downward will
assist in pushing the exhaust fumes out the Apparatus bay doors when open.
Provide compressed air system on self-retracting lines at each vehicle bay. Consider
providing a floor radiant heating element at each bay door in colder climates to prevent
the door from freezing to the pavement.
• ELECTRICAL: Provide outlets per current codes. Locate all outlets at 36 in. above
finished floor. Provide self-retracting electric drop cords between vehicles that can reach
to either end of the bay. Provide backup power sized to provide full unobstructed
operation capability of the apparatus bays. Provide power to each retractable bay door.
• LIGHTING: Provide per current codes. Provide energy efficient lighting with instant-start
feature. Provide doors with a signaling system to indicate fully raised doors. A red/green
indicator should be located on the driver’s side at 72 in. above finished floor.
• COMMUNICATION:
CCTV. None required.
CATV/Internal Video. None required.
PA/Audio. Provide speakers and horns with visual element.
Telephone. Provide one line with internal two-way communication.
Data. Provide data drops as required by equipment. Security.
None required.
• ACOUSTICS: None
• SPECIAL REQUIREMENTS:
For Structural bays provide 14 ft. by 14 ft. apparatus bay doors with electric eye and/or
automatic reverse device. For ARFF bays provide 18 ft. by 18 ft. doors as ecommended
by NFPA 403. Even if ARFF vehicles are only intended to be housed on one side of a
double bay, provide the 18 ft. by 18 ft. doors on both sides to permit drive through and to
allow flexibility of use. Provide manual means to open doors in case of power failure. If
solid door panels are used, provide insulated doors. Consider providing doors with radio
operated closing devices that can be activated from the vehicle.
Ensure both the internal floor slope and the approach drive slope allow the fire protection
vehicles to transition into and out of the Apparatus Bay without bottoming out or without
impeding driver sightlines.
7
Standard Design Criteria
Fire Stations
• MINIMUM AREA:
Station Captain’s Suite: 120 SF, Net.
Private Dorm Room: 85 SF, Net.
• PLUMBING: None.
• FIRE PROTECTION: Provide per current codes. Provide smoke and CO detectors.
• ELECTRICAL: Provide outlets per current codes. Multiple electrical and data outlets to
be provided to accommodate computers and other office equipment.
8
Standard Design Criteria
Fire Stations
• LIGHTING: Provide per current codes. Provide residential-style fixtures and task lighting
at individual desks. In addition to the ambient and task lighting fixtures, provide a
dedicated alert light fixture that is controllable from the Watch Desk/Dispatch and tied into
the firefighting alert system with a red-tinted bulb or lens.
• COMMUNICATION:
CCTV. None required.
CATV/Internal Video. Provide one outlet in the office area and one outlet in the bedroom
area.
PA/Audio. Provide speaker.
Telephone. Provide one line with internal two-way communication.
Data. Provide data drops as required by equipment. Security.
None required.
• ACOUSTICS: Provide partition and door construction with a minimum STC rating of 52.
• SPECIAL REQUIREMENTS: The Station Captain’s Suite will be located off of the
Apparatus Bay. Walls shared with the Administrative & Training areas are allowed to be
of materials other than CMU.
• FUNCTIONAL DESCRIPTION: This area provides storage for the firefighters’ protective
gear. A well-ventilated locker is assigned to each member of the firefighting crew.
Sufficient floor area in front of each locker is required for easy access during
emergencies.
• ADJACENCIES: Located along the side walls of the Apparatus Bay. Should be directly
accessible from the Apparatus Bay if required to be a room.
• MINIMUM AREA: Room: 160 SF, Net. If part of Apparatus Bay, area is included in the
Apparatus Bay net area.
• CEILING HEIGHT: 8 ft. minimum. If part of Apparatus Bay, shall meet the Apparatus
Bay ceiling requirements.
9
Standard Design Criteria
Fire Stations
• PLUMBING: A floor drain is required in this area that shall be self priming, or designed
to prevent sewer gases from entering the occupied space by a proven and maintenance
free design. If part of Apparatus Bay, provide hose bib.
• HVAC: The area shall be kept under constant negative pressure to evacuate gaseous
emissions from stored gear to the outside or filtration equipment that is designed to filter
and remove gaseous emissions from PPE shall be provided. If part of Apparatus Bay, the
area shall have an air quality system to filter and remove gaseous emissions from stored
gear.
• LIGHTING: Provide per current codes. Provide 50 ft. candles (540 Lux) with fluorescent
energy efficient light fixtures.
• COMMUNICATION:
CCTV. None required.
CATV/Internal Video. None required.
PA/Audio. Provide speakers and horns with visual element.
Telephone. None required.
Data. None required.
Security. None required.
• ACOUSTICS: None.
• SPECIAL REQUIREMENTS: Locker layout should permit free air circulation around and
throughout clothing.
10
Standard Design Criteria
Fire Stations
5. Hose Storage:
• FUNCTIONAL DESCRIPTION: This area provides for storage of hoses. Hoses are
rolled and stored on mobile storage racks.
• DOORS/FRAME: None
• PLUMBING: A floor drain is required in this area that shall be self priming, or designed
to prevent sewer gases from entering the occupied space by a proven and maintenance
free design. Provide hose bib.
• ELECTRICAL: Provide outlets per current codes. Dedicated outlets required to support
drying equipment (if provided).
• LIGHTING: Provide per current codes. Provide 50 ft. candles (540 Lux) with fluorescent
energy efficient light fixtures.
• COMMUNICATION:
CCTV. None required.
CATV/Internal Video. None required.
PA/Audio. Provide a speaker.
11
Standard Design Criteria
Fire Stations
• ACOUSTICS: None.
• SPECIAL REQUIREMENTS: Layout should permit free air circulation around the hoses.
• ADJACENCIES: Accessible from Apparatus Bay and shall have direct access to the
SCBA Compressor Room.
12
Standard Design Criteria
Fire Stations
• PLUMBING: A floor drain for condensate is required in this area that shall be self
priming, or designed to prevent sewer gases from entering the occupied space by a
proven and maintenance-free design.
• HVAC: The area shall be kept under constant negative pressure to evacuate gaseous
emissions from stored gear to the outside or filtration equipment that is designed to filter
and remove gaseous emissions from equipment shall be provided. Provide any additional
ventilation requirements for compressor equipment.
• ELECTRICAL: Provide outlets per current codes. Provide additional outlets and power
as required by equipment.
• LIGHTING: Provide per current codes. Provide 50 ft. candles (540 Lux) with fluorescent
energy efficient light fixtures. Provide task lighting for the work/service bench.
• COMMUNICATION:
CCTV. None required.
CATV/Internal Video. None required.
PA/Audio. Provide a speaker.
Telephone. Provide one line with internal two-way communication.
Data. Provide data drops as required by equipment. Security.
None required.
• ACOUSTICS: Provide partition and door construction with a minimum STC rating of 52.
13
Standard Design Criteria
Fire Stations
• PLUMBING: Provide compressed air lines to Apparatus Bay and SCBA Maintenance
Room. A floor drain for condensate is required in this area that shall be self priming, or
designed to prevent sewer gases from entering the occupied space by a proven and
maintenance-free design.
• HVAC: The area shall be kept under constant negative pressure to evacuate gaseous
emissions from stored gear to the outside or filtration equipment that is designed to filter
and remove gaseous emissions from equipment shall be provided. Provide any additional
ventilation requirements for compressor equipment.
• ELECTRICAL: Provide outlets per current codes. Provide additional outlets and power
as required by equipment.
• LIGHTING: Provide per current codes. Provide 50 ft. candles (540 Lux) with fluorescent
energy efficient light fixtures.
• COMMUNICATION:
CCTV. None required.
CATV/Internal Video. None required.
PA/Audio. Provide a speaker.
Telephone. None required.
Data. None required.
Security. None required.
• ACOUSTICS: Provide partition and door construction with a minimum STC rating of 52.
14
Standard Design Criteria
Fire Stations
• SPECIAL REQUIREMENTS: Provide double door access for installation of the main
compressor unit to the exterior.
• ADJACENCIES: Provide direct access through the Apparatus Bay to the exterior. If a
Clean-Up Room is provided, the Protective Clothing Laundry Room shall be adjacent to
the Clean-Up room and a service window provided.
• MINIMUM AREA: One-Company: 100 SF, Net. Two-Company: 180 SF, Net. Three
Company: 150 SF, Net.
• PLUMBING: Provide water supply and drain to each washer. A floor drain is required in
this area that shall be self priming, or designed to prevent sewer gases from entering the
occupied space by a proven and maintenance-free design.
15
Standard Design Criteria
Fire Stations
• HVAC: The area shall be kept under constant negative pressure to evacuate gaseous
emissions from stored gear to the outside or filtration equipment that is designed to filter
and remove gaseous emissions from equipment shall be provided.
• ELECTRICAL: Provide outlets per current codes. Provide additional outlets and power
as required by equipment.
• LIGHTING: Provide per current codes. Provide 50 ft. candles (540 Lux) with fluorescent
energy efficient light fixtures.
• COMMUNICATION:
CCTV. None required.
CATV/Internal Video. None required.
PA/Audio. Provide a speaker.
Telephone. None required.
Data. None required.
Security. None required.
• ACOUSTICS: Provide partition and door construction with a minimum STC rating of 52.
9. Equipment Wash/Disinfection:
16
Standard Design Criteria
Fire Stations
conditions, dirty conditions, and spills related to the chemicals within), easily repairable,
easy to maintain, and slip resistant.
• PLUMBING: Provide floor mop sink, with hose and spray nozzle. Provide a minimum
three-compartment stainless steel sink and a drip dryer rack. Provide an oil-water
separator with holding tank for wastewater from drains. Provide compressed air supply. A
floor drain is required in this area that shall be self priming, or designed to prevent sewer
gases from entering the occupied space by a proven and maintenance-free design.
• HVAC: The area shall be kept under constant negative pressure to evacuate gaseous
emissions from stored gear to the outside or filtration equipment that is designed to filter
and remove gaseous emissions from equipment shall be provided.
• LIGHTING: Provide per current codes. Provide 50 ft. candles (540 Lux) with fluorescent
energy efficient light fixtures.
• COMMUNICATION:
CCTV. None required.
CATV/Internal Video. None required.
PA/Audio. Provide a speaker.
Telephone. None required.
Data. None required.
Security. None required.
• ACOUSTICS: Provide partition and door construction with a minimum STC rating of 52.
17
Standard Design Criteria
Fire Stations
• PLUMBING: Provide an oil-water separator with holding tank for wastewater from
drains. Provide compressed air supply. A floor drain is required in this area that shall be
self priming, or designed to prevent sewer gases from entering the occupied space by a
proven and maintenance-free design.
• HVAC: The area shall be kept under constant negative pressure to evacuate gaseous
emissions from stored gear to the outside or filtration equipment that is designed to filter
and remove gaseous emissions from equipment shall be provided.
• ELECTRICAL: Provide outlets per current codes. Provide additional outlets and power
as required by equipment.
18
Standard Design Criteria
Fire Stations
• LIGHTING: Provide per current codes. Provide 50 ft. candles (540 Lux) with fluorescent
energy efficient light fixtures. Provide task lighting for work/service bench.
• COMMUNICATION:
CCTV. None required.
CATV/Internal Video. None required.
PA/Audio. Provide a speaker.
Telephone. Provide one line with internal two-way communication.
Data. None required.
Security. None required.
• ACOUSTICS: Provide partition and door construction with a minimum STC rating of 52.
• FUNCTIONAL DESCRIPTION: Utilized for the storage of basic first aid supplies. The
Lockable Medical Storage Cabinet is often a cabinet or subspace within the EMT Storage
area and is for storage of drugs, needles, and other restricted medical supplies. Access
to EMT Storage is restricted and controlled to prevent theft and abuse of controlled
substances.
• ADJACENCIES: Shall be accessible from the Apparatus Bay. The EMS Equipment
Storage is located in the HAZMAT/ CBRNE storage area in Headquarters Fire Stations.
• MINIMUM AREA: 25 SF, Net. Area added to the HAZMAT/ CBRNE storage area in
Headquarters Fire Stations.
19
Standard Design Criteria
Fire Stations
industrial latex or epoxy paint. Salient characteristics include durable and shall provide an
aesthetically pleasing surface, free of sags or other defects.
• PLUMBING: None.
• ELECTRICAL: Provide outlets per current codes. Provide additional outlets and power
as required by equipment.
• LIGHTING: Provide per current codes. Provide 50 ft. candles (540 Lux) with fluorescent
energy efficient light fixtures.
• COMMUNICATION:
CCTV. None required.
CATV/Internal Video. None required.
PA/Audio. None required.
Telephone. None required.
Data. None required.
Security. None required.
• ACOUSTICS: Provide partition and door construction with a minimum STC rating of 52.
• SPECIAL REQUIREMENTS: In the Satellite Fire Stations provide a keyed lock set at the
access point to the space.
• ADJACENCIES: Shall be accessible from the Apparatus Bay. The EMS Equipment
Storage and Logistics’ Office is located in the HAZMAT/ CBRNE storage area in
Headquarter Fire Stations.
20
Standard Design Criteria
Fire Stations
• PLUMBING: None.
• HVAC: The area shall be kept under constant negative pressure to evacuate gaseous
emissions from stored gear to the outside or filtration equipment that is designed to filter
and remove gaseous emissions from equipment shall be provided.
• LIGHTING: Provide per current codes. Provide 50 ft. candles (540 Lux) with fluorescent
energy efficient light fixtures.
• COMMUNICATION:
CCTV. None required.
CATV/Internal Video. None required.
PA/Audio. None required.
Telephone. None required.
Data. None required.
Security. None required.
• ACOUSTICS: Provide partition and door construction with a minimum STC rating of 52.
21
Standard Design Criteria
Fire Stations
• SPECIAL REQUIREMENTS: Provide sufficient floor and open shelf storage areas.
Entrance shall be double doors.
• ADJACENCIES: Shall be accessible from the Apparatus Bay. The Logistics’ Office is
located in the HAZMAT/ CBRNE storage area in Headquarter Fire Stations.
• MINIMUM AREA: 80 SF, Net. Area added to the HAZMAT/ CBRNE storage area.
• PLUMBING: None.
• HVAC: The area shall be kept under constant negative pressure to evacuate gaseous
emissions from stored gear to the outside or filtration equipment that is designed to filter
and remove gaseous emissions from equipment shall be provided.
22
Standard Design Criteria
Fire Stations
• ELECTRICAL: Provide outlets per current codes. Multiple electrical and data outlets to
be provided to accommodate computers and other office equipment.
• LIGHTING: Provide per current codes. Provide task lighting at workstation. In addition to
the ambient and task lighting fixtures, provide a dedicated alert light fixture that is
controllable from the Watch Desk/Dispatch and tied into the firefighting alert system with
a red-tinted bulb or lens.
• COMMUNICATION:
CCTV. None required.
CATV/Internal Video. Provide one outlet in the office area.
PA/Audio. Provide a speaker.
Telephone. Provide one line with internal two-way communication.
Data. Provide data drops as required by equipment. Security.
None required.
• ACOUSTICS: Provide partition and door construction with a minimum STC rating of 52.
23
Standard Design Criteria
Fire Stations
• PLUMBING: Provide a hose bibb and eye wash fountain. A floor drain is required in this
area that shall be self priming, or designed to prevent sewer gases from entering the
occupied space by a proven and maintenance-free design.
• HVAC: The area shall be kept under constant negative pressure to evacuate gaseous
emissions from stored gear to the outside or filtration equipment that is designed to filter
and remove gaseous emissions from equipment shall be provided. Provide a
compressed air system with self-retracting lines at the work bench.
• LIGHTING: Provide per current codes. Provide 50 ft. candles (540 Lux) with fluorescent
energy efficient light fixtures. Provide task lighting at workstation.
• COMMUNICATION:
CCTV. None required.
CATV/Internal Video. Provide one outlet in the office area.
PA/Audio. Provide a speaker.
Telephone. Provide one line with internal two-way communication.
Data. Provide quad outlet at work bench and in locations where required to
accommodate equipment.
Security. None required.
• ACOUSTICS: Provide partition and door construction with a minimum STC rating of 52.
24
Standard Design Criteria
Fire Stations
• PLUMBING: Provide a hose bibb and eye wash fountain. A floor drain is required in this
area that shall be self priming, or designed to prevent sewer gases from entering the
occupied space by a proven and maintenance-free design.
• HVAC: The area shall be kept under constant negative pressure to evacuate gaseous
emissions from stored gear to the outside or filtration equipment that is designed to filter
and remove gaseous emissions from equipment shall be provided. Provide a
compressed air system with self-retracting lines at the work bench.
• LIGHTING: Provide per current codes. Provide 50 ft. candles (540 Lux) with fluorescent
energy efficient light fixtures. Provide task lighting at workstation.
25
Standard Design Criteria
Fire Stations
• COMMUNICATION:
CCTV. None required.
CATV/Internal Video. Provide one outlet in the office area.
PA/Audio. Provide a speaker.
Telephone. Provide one line with internal two-way communication.
Data. Provide quad outlet at work bench and in locations where required to
accommodate equipment.
Security. None required.
• ACOUSTICS: Provide partition and door construction with a minimum STC rating of 52.
• FUNCTIONAL DESCRIPTION: This area provides showers and lockers for the fire
station staff to decontaminate themselves before entering the Living portion of the Fire
Station. A service window shall be provided to the Protective Clothing Laundry room.
• ADJACENCIES: Shall be directly accessible from the Apparatus Bay. The Clean-Up
Room shall be adjacent to Protective Clothing Laundry Room and a service window
provided.
26
Standard Design Criteria
Fire Stations
• PLUMBING: Provide private shower stalls. See Special Requirements below for
distribution. A floor drain is required in this area that shall be self priming, or designed to
prevent sewer gases from entering the occupied space by a proven and maintenancefree
design.
• COMMUNICATION:
CCTV. None required.
CATV/Internal Video. None required.
PA/Audio. Provide a speaker.
Telephone. None required.
Data. None required.
Security. None required.
• ACOUSTICS: Provide partition and door construction with a minimum STC rating of 52.
• SPECIAL REQUIREMENTS: Provide sufficient floor areas for lockers. The following
shall be provided:
Minimum two private showers w/ changing areas and full privacy doors shall be provided
for One-Company Fire Stations.
Minimum two private showers w/ changing areas and full privacy doors shall be provided
for Two-Company Fire Stations.
Minimum three private showers w/ changing areas and full privacy doors shall be
provided for Three-Company Fire Stations.
27
Standard Design Criteria
Fire Stations
• ADJACENCIES: Shall be separate from the Fire Station building and located along the
drive leading into the Apparatus Bay.
• PLUMBING: Provide a hose bibb and floor drain. Provide eye wash fountain.
• HVAC: Provide per current codes. The area shall be kept under constant negative
pressure to evacuate gaseous emissions from stored gear to the outside.
• LIGHTING: Provide per current codes. Provide 50 ft. candles (540 Lux) with fluorescent
energy efficient light fixtures.
28
Standard Design Criteria
Fire Stations
• COMMUNICATION:
CCTV. None required.
CATV/Internal Video. Provide one outlet in the office area.
PA/Audio. Provide a speaker.
Telephone. Provide one line with internal two-way communication.
Data. Provide quad outlet at work bench and in locations where required to
accommodate equipment.
Security. None required.
• ACOUSTICS: Provide partition and door construction with a minimum STC rating of 52.
• FUNCTIONAL DESCRIPTION: The area includes a typical office space and workstation.
An adjacent private bedroom and private toilet/shower should be directly accessible from
the Fire Chief’s Office.
• ADJACENCIES: This area is in the Administrative Office area of the Fire Station. Shall
be adjacent to the Deputy Chief's Office and directly off the Lobby.
• MINIMUM AREA:
Fire Chief’s Office: 200 SF, Net.
Fire Chief’s Dorm Room: 85 SF, Net.
Fire Chief’s Toilet/Shower: 60 SF, Net.
29
Standard Design Criteria
Fire Stations
and easy to clean, repairable, and easy to maintain. Consider providing vinyl wall
coverings in the toilet/showers.
• PLUMBING: Provide water closet, shower, and lavatory. Consider providing floor drain.
• FIRE PROTECTION: Provide per current codes. Provide smoke and CO detectors.
• ELECTRICAL: Provide outlets per current codes. Multiple electrical and data outlets to
be provided to accommodate computers and other office equipment.
• LIGHTING: Provide per current codes. Provide residential-style fixtures and task lighting
at desk. In addition to the ambient and task lighting fixtures, provide a dedicated alert
light fixture that is controllable from the Watch Desk/Dispatch and tied into the firefighting
alert system with a red-tinted bulb or lens.
• COMMUNICATION:
CCTV. None required.
CATV/Internal Video. Provide one outlet in the office area and one outlet in the bedroom
area.
PA/Audio. Provide speaker.
Telephone. Provide one line with internal two-way communication.
Data. Provide data drops as required by equipment. Security.
None required.
• ACOUSTICS: Provide partition and door construction with a minimum STC rating of 52.
30
Standard Design Criteria
Fire Stations
• FUNCTIONAL DESCRIPTION: The area includes a space for a small conference table
for 8 to 10 people.
• ADJACENCIES: Directly accessible from the corridor in the Administrative Office area.
• PLUMBING: None.
• ELECTRICAL: Provide outlets per current codes. Multiple electrical and data outlets to
be provided to accommodate computers and other office equipment.
• LIGHTING: Provide per current codes. Provide 50 ft. candles (540 Lux) with fluorescent
energy efficient light fixtures. In addition to the ambient lighting fixtures, provide a
dedicated alert light fixture that is controllable from the Watch Desk/Dispatch and tied into
the firefighting alert system with a red-tinted bulb or lens.
• COMMUNICATION:
CCTV. None required.
CATV/Internal Video. Provide one outlet.
PA/Audio. Provide speaker.
Telephone. Provide one line with internal two-way communication.
Data. Provide data drops as required by equipment.
31
Standard Design Criteria
Fire Stations
Visual. Provide outlets and data drops for an overhead projector and electric overhead
projector screen. Security. None required.
• ACOUSTICS: Provide partition and door construction with a minimum STC rating of 52.
• ADJACENCIES: This area is in the Administrative Office area of the Fire Station. Shall
be adjacent to the Fire Chief’s Suite and directly off the Lobby.
32
Standard Design Criteria
Fire Stations
• PLUMBING: None.
• ELECTRICAL: Provide outlets per current codes. Multiple electrical and data outlets to
be provided to accommodate computer and other office equipment.
• LIGHTING: Provide per current codes. Provide residential-style fixtures and task lighting
at desk. In addition to the ambient and task lighting fixtures, provide a dedicated alert light
fixture that is controllable from the Watch Desk/Dispatch and tied into the firefighting alert
system with a red-tinted bulb or lens.
• COMMUNICATION:
CCTV. None required.
CATV/Internal Video. Provide one outlet in the office area and one outlet in the bedroom
area.
PA/Audio. Provide speaker.
Telephone. Provide one line with internal two-way communication.
Data. Provide data drops as required by equipment. Security.
None required.
• ACOUSTICS: Provide partition and door construction with a minimum STC rating of 52.
• FUNCTIONAL DESCRIPTION: This room provides space for the station officer and/or
company officers to perform their administrative functions. The Station Officer’s office
may serve to control public access to the station. If a Watch Desk function is required, it is
typically included in the Station Officer’s Office. The Watch Desk receives emergency
calls from the Dispatch and contains the security monitors for the station. It is usually
occupied 24 hours a day/7 days a week. The room includes a typical office space and
workstations for two people.
• ADJACENCIES: This area is in the Administrative Office area of the Fire Station. Shall
be located directly off the Lobby.
33
Standard Design Criteria
Fire Stations
• PLUMBING: None.
• ELECTRICAL: Provide electrical and data outlets per current codes and as needed to
support the extensive equipment required. Provide two additional quad outlets at the
control center console. Provide a switch controlling operation of Apparatus Bay doors.
• Cdccvv
• LIGHTING: Provide per current codes. Provide 50 ft. candles (540 Lux) with
fluorescent energy efficient light fixtures. Provide task lighting at control desk.
• COMMUNICATION:
CCTV. If CCTV is provided monitors for the facility cameras will be located here. Provide
outlets required to support equipment.
CATV/Internal Video. Provide outlets required to support required equipment.
PA/Audio. Provide simultaneous light and audible control for the entire fire station.
Telephone. Provide regular and secure multi-telephone line required to support switch board
operation, telephone, and fax.
Data. Provide regular and secure data outlets to support required equipment.
Security. Provide vision panel to the Apparatus Bay. Provide pin pad/cipher electric lock with
remote push button release and manual key override.
• ACOUSTICS: Provide partition and door construction with a minimum STC rating of 45.
34
Standard Design Criteria
Fire Stations
• SPECIAL REQUIREMENTS:
Firefighter Alert System: Provide light and audible control for the following elements when
the firefighter alert system is activated: Dorm Room lights (the dedicated alert light), corridor
lights from Dorm Rooms to Apparatus Bay, and the Apparatus Bay lights.
Provide a 36 in. (920 mm) free access area around the entire control console. Provide space
for Emergency Information Systems computer. Provide tinted widows.
• FUNCTIONAL DESCRIPTION: The area includes a typical office space and workstation.
An adjacent private bedroom and private toilet /shower shall be directly accessible from
the Assistant Chief’s Office.
• ADJACENCIES: This area is in the Administrative Office area of the Fire Station. Shall
be adjacent to the Station’s Captain Suite and directly accessible from the corridor in the
Administrative Office area. The private toilet/shower shall accessible from the Station’s
Captain Dorm room, also.
• MINIMUM AREA:
Assistant Chief/Shift Supervisor’s Suite: 120 SF, Net.
Assistant Chief/Shift Supervisor’s Dorm Room: 85 SF, Net.
Assistant Chief/Shift Supervisor’s Toilet/Shower: 60 SF, Net.
35
Standard Design Criteria
Fire Stations
toilet/shower. A base material, appropriate for the flooring material used, is required.
Base shall be sealed to the flooring in the toilet/shower. Salient characteristics include
durable and easy to clean, repairable, easy to maintain, and slip resistant.
• PLUMBING: Provide water closet, shower, and lavatory. Consider providing floor drain.
• FIRE PROTECTION: Provide per current codes. Provide smoke and CO detectors.
• ELECTRICAL: Provide outlets per current codes. Multiple electrical and data outlets to
be provided to accommodate computers and other office equipment.
• LIGHTING: Provide per current codes. Provide residential-style fixtures and task lighting
at desk. In addition to the ambient and task lighting fixtures, provide a dedicated alert
light fixture that is controllable from the Watch Desk/Dispatch and tied into the firefighting
alert system with a red-tinted bulb or lens.
• COMMUNICATION:
CCTV. None required.
CATV/Internal Video. Provide one outlet in the office area and one outlet in the bedroom
area.
PA/Audio. Provide speaker.
Telephone. Provide one line with internal two-way communication.
Data. Provide data drops as required by equipment. Security.
None required.
36
Standard Design Criteria
Fire Stations
• ACOUSTICS: Provide partition and door construction with a minimum STC rating of 52.
• FUNCTIONAL DESCRIPTION: This area is general storage for office supplies and other
supplies.
• ADJACENCIES: This area is in the Administrative Office area of the Fire Station. Shall
be directly accessible from the corridor and/or Lobby in the Administrative Office area.
• PLUMBING: None.
37
Standard Design Criteria
Fire Stations
• LIGHTING: Provide per current codes. Provide 50 ft. candles (540 Lux) with fluorescent
energy efficient light fixtures.
• COMMUNICATION:
CCTV. None required.
CATV/Internal Video. None required.
PA/Audio. None required.
Telephone. None required.
Data. None required.
Security. None required.
• ACOUSTICS: Provide partition and door construction with a minimum STC rating of 40.
24. Lobby:
• FUNCTIONAL DESCRIPTION: This area serves as the entrance to the facility and a
gathering/waiting space for the visiting public. The Lobby should be recognizable from the
outside as a well-lit, inviting space.
• ADJACENCIES: This area is in the Administrative Office area of the Fire Station and is
the main entrance into the Fire Station.
38
Standard Design Criteria
Fire Stations
and easy to clean, repairable, and easy to maintain. Consider providing vinyl wall
coverings.
• ELECTRICAL: Provide outlets per current codes. Consider outlets for display cases.
• LIGHTING: Provide per current codes. Consider decorative lighting fixtures and task
lighting.
• COMMUNICATION:
CCTV. None required.
CATV/Internal Video. None required.
PA/Audio. Provide speaker.
Telephone. Consider providing one line for local and toll-free calls or a pay phone.
Data. None required.
Security. None required.
• ACOUSTICS: None.
• SPECIAL REQUIREMENTS:
Provide airlock at main entrance when necessary.
• FUNCTIONAL DESCRIPTION: This area shall be an ABA compliant toilet area for
visitors.
39
Standard Design Criteria
Fire Stations
• ADJACENCIES: This area is in the Administrative Office area of the Fire Station.
Public toilets shall be located directly adjacent to the Lobby. Staff toilets shall be
accessible from the corridors, and should be spread out around the facility.
• OCCUPANTS: Visitor.
• PLUMBING: 1 ABA compliance water closet, and 1 ABA compliant lavatory. A floor
drain is required in this area that shall be self priming, or designed to prevent sewer
gases from entering the occupied space by a proven and maintenance-free design.
• HVAC: Provide per current codes. Local exhaust vent above toilet.
• COMMUNICATION:
CCTV. None required.
CATV/Internal Video. None required.
PA/Audio. None required.
Telephone. None required.
Data. None required.
40
Standard Design Criteria
Fire Stations
• ACOUSTICS: None.
• FUNCTIONAL DISCRIPTION: The main access control point with direct visual contact
with the entry, lobby, and public toilet. Responsible for receiving and dispatching fire
related emergency calls. This area contains the security monitors for the station and is
occupied 24 hours a day, 7 days a week. Provide a dedicated toilet and kitchenette, and
dedicated IT room directly adjacent to and accessible from the Dispatch Room for staff
use. Provide tinted windows. If possible, operators should be able to see exterior
conditions.
• ADJACENCIES: This area is in the Administrative Office area of the Fire Station. This
area is adjacent to lobby area. Shall have direct visual control service window to and
direct access to the Lobby.
• MINIMUM AREA:
Dispatch’s Suite: 256 SF, Net.
Dispatch’s Toilet: 48 SF, Net.
Dispatch’s Kitchenette: 20 SF, Net.
41
Standard Design Criteria
Fire Stations
• PLUMBING: Provide an ABA-accessible toilet with a lavatory and water closet. Provide
a kitchenette with a kitchen sink and disposal.
• ELECTRICAL: Provide outlets per current codes and as needed to support all
equipment, including charging equipment for handhelds. Provide a switch controlling
open only operation of Apparatus Bay doors.
• LIGHTING: Provide per current codes. Provide 50 ft. candles (540 Lux) with fluorescent
energy efficient light fixtures and emergency battery back-up. Consider providing task
lighting at control desk.
• COMMUNICATION:
CCTV. If CCTV is provided, monitors for the facility cameras will be located here.
Provide outlets required. to support equipment.
CATV/Internal Video. Provide outlets required to support equipment.
PA/Audio. Provide a speaker and a microphone.
Telephone. Provide regular and secure multi-telephone line required to support
switchboard operation, telephone, and fax.
Data. Provide regular and secure data outlets to support required equipment. Security.
Provide pin pad/cipher electric lock with remote push button release and manual key
override.
• ACOUSTICS: Provide partition and door construction with a minimum STC rating of 49.
• SPECIAL REQUIREMENTS:
Comply with the requirements for “Communication Centers” in NFPA 1221.
42
Standard Design Criteria
Fire Stations
Note that some equipment requires free access area around the entire control console.
Design this space appropriate to the equipment being provided. Note any special
requirements for the E911 system, if appropriate. If required for selected equipment,
provide a conduit to the roof for a roof mounted antennae.
Firefighter Alert System: Provide light and audible control for the following elements
when the firefighter alert system is activated: Dorm Room lights (the dedicated alert light),
corridor lights from Dorm Rooms to Apparatus Bay, and the Apparatus Bay lights.
The generator must provide back-up power for all Dispatch Room systems. In addition,
provide uninterrupted power supply (UPS) for the dispatch equipment.
• FUNCTIONAL DISCRIPTION: This room houses the equipment racks for the Dispatch
or Station Officer’s Office/Watch Desk area’s computer networks, telephone,
communication feeds, and an Uninterrupted Power Source (UPS).
• ADJACENCIES: This area is in the Administrative Office area of the Fire Station. UPS
room shall be provided adjacent to and accessible from the Dispatch or Station Officer’s
Office/Watch Desk area.
• OCCUPANTS: Dispatch staff/Station Officer.
43
Standard Design Criteria
Fire Stations
• PLUMBING: None.
• ELECTRICAL: Provide outlets per current codes and as needed to support the
extensive equipment required. Provide two additional quad outlets. Provide a transient
voltage surge suppression panel board.
• ACOUSTICS: None.
• FUNCTIONAL DISCRIPTION: This room shall be used for the termination of all data
and communication utilities in the facility. The equipment racks for the facility’s computer
networks, telephone, communication feeds, and Uninterrupted Power Source (UPS) are
housed in this room.
• ADJACENCIES: This area is in the Administrative Office area of the Fire Station. Shall
be directly accessible from the corridor in the Administrative Office area and preferably
centrally located in the facility.
• OCCUPANTS: Fire Station Staff.
44
Standard Design Criteria
Fire Stations
• PLUMBING: None.
• ELECTRICAL: Provide outlets per current codes and as needed to support the
extensive equipment required. Provide two additional quad outlets. Provide a transient
voltage surge suppression panel board.
• ACOUSTICS: None.
• ADJACENCIES: This area is in the Administrative Office area of the Fire Station. Shall
be adjacent to and directly off the Fire Inspectors’ Office.
45
Standard Design Criteria
Fire Stations
repairable, and easy to maintain. A base material, appropriate for the flooring material
used, is required.
• PLUMBING: None.
• ELECTRICAL: Provide outlets per current codes. Multiple electrical and data outlets to
be provided to accommodate computer and other office equipment.
• LIGHTING: Provide per current codes. Provide residential-style fixtures and task lighting
at desk.
• ACOUSTICS: Provide partition and door construction with a minimum STC rating of 39.
• ADJACENCIES: This area is in the Administrative Office area of the Fire Station. Shall
be adjacent to Fire Inspectors’ Office. Shall be directly accessible from the corridor in the
Administrative Office area.
• MINIMUM AREA:
46
Standard Design Criteria
Fire Stations
• PLUMBING: None.
• ELECTRICAL: Provide outlets per current codes. Multiple electrical and data outlets to
be provided to accommodate computer and other office equipment.
• COMMUNICATION:
CCTV. None required.
CATV/Internal Video. Provide one outlet.
PA/Audio. Provide speaker.
Telephone. Provide one line with internal two-way communication per Fire Inspector’s
workstation.
Data. Provide data outlets as required by equipment. Security.
None required.
47
Standard Design Criteria
Fire Stations
• ACOUSTICS: Provide partition and door construction with a minimum STC rating of 39.
• ADJACENCIES: This area is in the Administrative Office area of the Fire Station. Shall
be directly accessible from the corridor in the Administrative Office area. Shall be
adjacent to the Department Training Room and Computer Training/Testing Room with an
observation window to each room.
• PLUMBING: None.
48
Standard Design Criteria
Fire Stations
• ELECTRICAL: Provide outlets per current codes. Multiple electrical and data outlets to
be provided to accommodate computer and other office equipment.
• LIGHTING: Provide per current codes. Provide residential-style fixtures and task lighting
at desk.
• COMMUNICATION:
CCTV. None required.
CATV/Internal Video. Provide one outlet.
PA/Audio. Provide speaker.
Telephone. Provide one line with internal two-way communication.
Data. Provide data outlets as required by equipment. Security.
None required.
• ACOUSTICS: Provide partition and door construction with a minimum STC rating of 39.
• ADJACENCIES: This area is in the Administrative Office area of the Fire Station. Shall
be directly accessible from the corridor in the Administrative Office area. Shall be
adjacent to and have direct access to Training Room Storage room. Shall be adjacent to
the Training Officer’s Office and Computer Training/Testing Room with an observation
window from the Training Officer’s Office.
• MINIMUM AREA:
One Company Headquarters: 420 SF, Net. Two
Company Headquarters: 700 SF, Net.
Three Company Headquarters: 980 SF, Net.
49
Standard Design Criteria
Fire Stations
repairable, and easy to maintain. A base material, appropriate for the flooring material
used, is required.
• PLUMBING: None.
• ELECTRICAL: Provide outlets per current codes. Providing direct power to each work
table.
• COMMUNICATION:
CCTV. None required.
CATV/Internal Video. Provide one outlet.
PA/Audio. Provide speaker.
Telephone. Provide one line with internal two-way communication.
Data. Provide data outlets to every workstation. Provide outlets and data drops for an
overhead projector and electric overhead projector screen. Security. None required.
• ACOUSTICS: Provide partition and door construction with a minimum STC rating of 45.
50
Standard Design Criteria
Fire Stations
• ADJACENCIES: This area is in the Administrative Office area of the Fire Station. Shall
be directly accessible from the Department Training Room.
• PLUMBING: None.
• LIGHTING: Provide per current codes. Provide 50 ft. candles (540 Lux) with fluorescent
energy efficient light fixtures.
• COMMUNICATION:
CCTV. None required.
CATV/Internal Video. None required.
PA/Audio. None required.
Telephone. None required.
Data. None required.
Security. None required.
51
Standard Design Criteria
Fire Stations
• ACOUSTICS: Provide partition and door construction with a minimum STC rating of 40.
• FUNCTIONAL DESCRIPTION: This area is utilized for Computer Training and Testing
consisting of space for carrels for study and testing.
• ADJACENCIES: This area is in the Administrative Office area of the Fire Station. Shall
be directly accessible from the corridor in the Administrative Office area. Shall be
adjacent to the Training Officer’s with an observation window from the Training Officer’s
Office.
• PLUMBING: None.
52
Standard Design Criteria
Fire Stations
• ELECTRICAL: Provide outlets per current codes. Provide direct power to each
computer/study carol and printer.
• LIGHTING: Provide per current codes. Provide 50 ft. candles (540 Lux) with fluorescent
energy efficient light fixtures.
• COMMUNICATION:
CCTV. Provide video camera with monitor located in Training Officer’s Office.
CATV/Internal Video. None required.
PA/Audio. Provide speaker.
Telephone. None required.
Data. Provide data outlets to all workstations and equipment. Security.
None required.
• ACOUSTICS: Provide partition and door construction with a minimum STC rating of 49.
• FUNCTIONAL DESCRIPTION: The room includes a typical office space and workstation
• ADJACENCIES: This area is in the Administrative Office area of the Fire Station. Shall
be directly accessible from the corridor in the Administrative Office area.
53
Standard Design Criteria
Fire Stations
• PLUMBING: None.
• ELECTRICAL: Provide outlets per current codes. Multiple electrical and data outlets to
be provided to accommodate computer and other office equipment.
• LIGHTING: Provide per current codes. Provide residential-style fixtures and task lighting
at desk.
• COMMUNICATION:
CCTV. None required.
CATV/Internal Video. Provide one outlet.
PA/Audio. Provide speaker.
Telephone. Provide one line with internal two-way communication.
Data. Provide data outlets as required by equipment. Security.
None required.
• ACOUSTICS: Provide partition and door construction with a minimum STC rating of 39.
• FUNCTIONAL DESCRIPTION: The room includes a typical office space and workstation
• ADJACENCIES: This area is in the Administrative Office area of the Fire Station. Shall
be directly accessible from the corridor in the Administrative Office area.
54
Standard Design Criteria
Fire Stations
• PLUMBING: None.
• ELECTRICAL: Provide outlets per current codes. Multiple electrical and data outlets to
be provided to accommodate computer and other office equipment.
• LIGHTING: Provide per current codes. Provide residential-style fixtures and task lighting
at desk.
• COMMUNICATION:
CCTV. None required.
CATV/Internal Video. Provide one outlet.
PA/Audio. Provide speaker.
Telephone. Provide one line with internal two-way communication.
Data. Provide data outlets as required by equipment. Security.
None required.
• ACOUSTICS: Provide partition and door construction with a minimum STC rating of 39.
55
Standard Design Criteria
Fire Stations
• FUNCTIONAL DESCRIPTION: The room shall be configured and furnished like a large
residential kitchen/dining/living room. The dining area shall be flexible to accommodate
various functions such as informal meetings and group training for the number of
companies on duty. Provide means of natural light in the Dining area. Shall have
comfortable seating for TV watching, reading, and relaxation in the living room area.
Kitchen shall be sized to provide ample room for meal preparation for the entire facility’s
overnight population. All kitchen appliances shall be light commercial grade. Separate dry
and cold food storage shall be provided for each shift.
• ADJACENCIES: This area is in the Living Area of the Fire Station. Shall be directly
accessible from the corridor in the Living Area.
• MINIMUM AREA:
One Company: 648 SF, Net.
Two Company: 1,296 SF, Net.
Three Company: 1,944 SF, Net.
• PLUMBING: Provide two-basin, deep kitchen sink. Provide connections for the
dishwashers, coffee and ice makers. A floor drain is required in this area that shall be self
priming, or designed to prevent sewer gases from entering the occupied space by a
proven and maintenance-free design.
56
Standard Design Criteria
Fire Stations
• HVAC: Provide per current codes. Provide exhaust hood over kitchen stoves appropriate
to the grade of equipment provided.
• FIRE PROTECTION: Provide per current codes. Refer to NFPA 96 to confirm fire
protection requirements for the grade of kitchen equipment provided. Provide carbon
monoxide and smoke detectors.
• ELECTRICAL: Provide outlets per current codes and to accommodate all kitchen
equipment. Provide dedicated circuits as necessary to minimize power interruptions.
• LIGHTING: Provide per current codes. Provide 50 ft. candles (540 Lux) with
incandescent energy efficient light fixtures. Consider residential-style lighting fixtures.
Consider providing dimmers for all light fixtures.
• COMMUNICATION:
CCTV. None required.
CATV/Internal Video. Provide at least one outlet in the Day Room area.
PA/Audio. Provide speaker.
Telephone. Provide one line with internal two-way communication.
Data. Provide at least one outlet in the dining/training area. Consider providing outlets in
the living room area. In Satellite stations, provide outlets and data drops for an overhead
projector and electric overhead projector screen.
Security. None required.
• ACOUSTICS: Provide partition and door construction with a minimum STC rating of 45.
• CASEWORKS/BUILT-IN EQUIPMENT: Provide base and wall cabinets with 24-in. deep
solid surface work counter. Provide a minimum of two separate dry storage closets or
pantries (one for each of two shifts).
• SPECIAL REQUIREMENTS:
Kitchen area: Provide space for a large-capacity dishwasher, stove/range, exhaust hood,
and free-standing ice maker. Provide space for a minimum of two separate refrigerators
with freezers (one for each of two shifts), microwave oven, commercial-grade coffee
maker, and toaster oven. All equipment shall be commercial grade.
Dining/Training area: Provide space for dining table with chairs. In the Satellite stations,
provide retractable overhead screen and overhead projector mount.
Living Room area: Provide space for recliner armchairs, side tables, entertainment
center, large-screen TV, VCR, and DVD player. Consider providing space for
bookshelves and coffee table(s).
57
Standard Design Criteria
Fire Stations
• FUNCTIONAL DESCRIPTION: The rooms are the private quarters of the firefighters and
are used for sleeping during 24-hour shifts. The room is shared between two firefighters
of different crews/shifts so that the room is never occupied simultaneously. Shall provide
space for individual wardrobes for each firefighter. Shall provide space for a two-bed
arrangement, giving each firefighter an individual bed and nightstand. The Dorm Rooms
should be a comfortable, inviting space that promotes relaxation. Acoustical privacy
between rooms is important. Provide means of natural light in every room.
• ADJACENCIES: This area is in the Living Area of the Fire Station. Shall be directly
accessible from the private corridor in the Living Area.
• PLUMBING: None.
• HVAC: Provide per current codes. Providing independent thermostat for each Dorm
Room.
• FIRE PROTECTION: Provide per current codes. Provide carbon monoxide and smoke
detectors.
58
Standard Design Criteria
Fire Stations
• LIGHTING: Provide per current codes. In addition to the ambient and task lighting
fixtures, provide a dedicated alert light fixture that is controllable from the Watch
Desk/Dispatch and tied into the firefighting alert system with a red-tinted bulb or lens.
• COMMUNICATION:
CCTV. None required.
CATV/Internal Video. Provide one outlet.
PA/Audio. Provide speaker.
Telephone. Provide one line with internal two-way communication.
Data. Provide a data outlet.
Security. None required.
• ACOUSTICS: Provide partition and door construction with a minimum STC rating of 52.
• SPECIAL REQUIREMENTS: Provide space for extra-long twin bed, night table, two
wardrobes, desk and desk chair, desk light, and alarm clock.
• FUNCTIONAL DESCRIPTION: This area shall contain private water closets, lavatory
and shower stalls with private changing areas for firefighters.
•
• ADJACENCIES: This area is in the Living Area of the Fire Station. Shall be directly
accessible from the corridor in the Living Area.
• MINIMUM AREA:
One Company: 250 SF, Net.
Two Company: 325 SF, Net.
Three Company: 350 SF, Net.
59
Standard Design Criteria
Fire Stations
• PLUMBING: Provide shower stalls, lavatories, and water closets. A floor drain is
required in this area that shall be self priming, or designed to prevent sewer gases from
entering the occupied space by a proven and maintenance-free design. Provide a hot
water hose bibb under sink area to assist in disinfection.
One-Company Station: Provide 2 water closets, 2 showers, and 2 lavatories.
Two-Company Station: Provide 4 water closets, 4 showers, and 3 lavatories.
Three-Company Station: Provide 4 water closets, 4 showers, and 4 lavatories.
• COMMUNICATION:
CCTV. None required.
CATV/Internal Video. None required.
PA/Audio. Speaker required.
Telephone. None required.
Data. None required.
Security. None required.
• ACOUSTICS: None.
60
Standard Design Criteria
Fire Stations
• FUNCTIONAL DESCRIPTION: This area shall contain private water closets, lavatory
and shower stalls with private changing areas for firefighters.
•
• ADJACENCIES: This area is in the Living Area of the Fire Station. Shall be directly
accessible from the corridor in the Living Area.
• MINIMUM AREA:
All Fire Stations: 150 SF, Net.
• PLUMBING: Provide shower stalls, lavatories, and water closets. A floor drain is
required in this area that shall be self priming, or designed to prevent sewer gases from
entering the occupied space by a proven and maintenance-free design. Provide a hot
water hose bibb under sink area to assist in disinfection.
All Fire Stations: Provide a 1 water closet, 1 shower, and 1 lavatory.
61
Standard Design Criteria
Fire Stations
• COMMUNICATION:
CCTV. None required.
ATV/Internal Video. None required.
PA/Audio. Speaker required.
Telephone. None required.
Data. None required.
Security. None required.
• ACOUSTICS: None.
• ADJACENCIES: This area is in the Living Area of the Fire Station. Shall be directly
accessible from the corridor in the Living Area and shall be adjacent to, or in the proximity
of, the Bathroom/Showers/Changing area.
62
Standard Design Criteria
Fire Stations
above ceiling, durable, and shall provide an aesthetically pleasing surface, free of sags or
other defects.
• PLUMBING: None.
• HVAC: Provide per current codes. In addition, provide 68 F (20 C) minimum, 74 F (23 C)
maximum, less than 60% relative humidity, 20 cfm/person outside air and use CO2
sensors to control outside air. Provide multi-speed ceiling fans.
• FIRE PROTECTION: Provide per current codes. Provide carbon monoxide and smoke
detectors.
• ELECTRICAL: Provide outlets per current codes and provide wall or floor outlets to
accommodate fitness machines such as treadmills, bikes, and stair-step machines.
• COMMUNICATION:
CCTV. None required.
CATV/Internal Video. Provide at least one outlet in for wall mounted unit.
PA/Audio. Provide speaker.
Telephone. Provide one line with internal two-way communication. Data.
None required.
Security. None required.
• ACOUSTICS: Provide partition and door construction with a minimum STC rating of 52.
• FUNCTIONAL DESCRIPTION: This area shall be lavatory, water closet, and shower
area for Fire Station staff.
• ADJACENCIES: This area is in the Living Area of the Fire Station. Shall be directly
accessible from the corridor in the Living Area.
63
Standard Design Criteria
Fire Stations
• PLUMBING: Provide water closet, shower, and lavatory. A floor drain is required in this
area that shall be self priming, or designed to prevent sewer gases from entering the
occupied space by a proven and maintenance-free design.
• HVAC: Provide per current codes. Local exhaust vent above toilet.
• COMMUNICATION:
CCTV. None required.
CATV/Internal Video. None required.
PA/Audio. None required.
Telephone. None required.
Data. None required.
Security. None required.
• ACOUSTICS: None.
64
Standard Design Criteria
Fire Stations
• ADJACENCIES: This area is in the Living Areas of the Fire Station. Shall be directly
accessible from the corridor in the Living areas.
• MINIMUM AREA:
One Company: 80 SF, Net.
Two Company: 160 SF, Net.
Three Company: 240 SF, Net.
• PLUMBING: Provide water supply and drain to each washer. Provide a deep laundry
sink. A floor drain is required in this area that shall be self priming, or designed to prevent
sewer gases from entering the occupied space by a proven and maintenance free
design.
65
Standard Design Criteria
Fire Stations
• ELECTRICAL: Provide outlets per current codes. Provide an additional outlet at the
folding table.
• COMMUNICATION:
CCTV. None required.
CATV/Internal Video. None required.
PA/Audio. Provide a speaker.
Telephone. None required.
Data. None required.
Security. None required.
• ACOUSTICS: None.
• SPECIAL REQUIREMENTS: Dryer vents shall be individually and directly vented to the
outside. A booster fan will be provided in the dryer vent when the travel distance
exceeds 20 feet to the exterior.
• ADJACENCIES: This area is in the Living Area of the Fire Station. Shall be directly
accessible from the corridor in the Living Area and shall be adjacent to, or in the proximity
of, the Bathroom/Showers/Changing area. A Janitor’s Room shall be provided on the
first floor of a Two-Story Fire Station directly accessible from the Administrative Area’s
corridor also.
• MINIMUM AREA:
One-Story Fire Station: 48 SF, Net.
Two-Story Fire Station: 48 SF, Net.
First Floor and Second Floor 48 SF, Net.
66
Standard Design Criteria
Fire Stations
characteristics include durable and easy to clean, repairable, easy to maintain, and slip
resistant. A base material, appropriate for the flooring material used, is required. Base
shall be sealed to the flooring.
• PLUMBING: A utility (mop) sink is required. A floor drain is required in this area that
shall be self priming, or designed to prevent sewer gases from entering the occupied
space by a proven and maintenance-free design.
• COMMUNICATION:
CCTV. None required.
CATV/Internal Video. None required.
PA/Audio. None required.
Telephone. None required.
Data. None required.
Security. None required.
• ACOUSTICS: Provide partition and door construction with a minimum STC rating of 45.
67
Standard Design Criteria
Fire Stations
• ADJACENCIES: This area is in the Living Area of the Fire Station. Shall be directly
accessible from the corridor in the Living Area and shall be adjacent to, or in the proximity
of, the Day/Training Room.
• PLUMBING: None.
• FIRE PROTECTION: Provide per current codes. Provide carbon monoxide and smoke
detectors.
• LIGHTING: Provide per current codes. Provide 50 ft. candles (540 Lux) with
incandescent energy efficient light fixtures. Consider residential-style lighting fixtures.
68
Standard Design Criteria
Fire Stations
• COMMUNICATION:
CCTV. None required.
CATV/Internal Video. Provide at least one outlet. Consider height of outlet for a wall
mounted television.
PA/Audio. Provide speaker.
Telephone. Provide one line with internal two-way communication.
Data. None required.
Security. None required.
• ACOUSTICS: Provide partition and door construction with a minimum STC rating of 52.
46. Corridor:
• MINIMUM AREA:
One-Story Fire Station: Portion of Net-To-Gross Ratio= 22%.
Two-Story Fire Station: Portion of Net-To-Gross Ratio= 30%.
69
Standard Design Criteria
Fire Stations
• ELECTRICAL: Provide outlets per current codes. Consider outlets for display cases.
• LIGHTING: Provide per current codes. Provide 20 ft. candles (215 Lux) with fluorescent
energy efficient light fixtures.
• COMMUNICATION:
CCTV. Provide at least one outlet.
CATV/Internal Video. None required.
PA/Audio. Provide speaker.
Telephone. None required Data.
None required.
Security. None required.
• ACOUSTICS: Provide partition and door construction with a minimum STC rating of 45.
47. Vending:
• ADJACENCIES: One location off of Corridor. Can be located in the Recreation Room.
70
Standard Design Criteria
Fire Stations
• PLUMBING: None.
• ELECTRICAL: Provide outlets per current codes. Provide outlets and power required by
vending machines.
• LIGHTING: Provide per current codes. Provide 20 ft. candles (215 Lux) with fluorescent
energy efficient light fixtures.
• COMMUNICATION:
CCTV. Provide at least one outlet.
CATV/Internal Video. None required.
PA/Audio. Provide speakers and horns with visual element.
Telephone. None required.
Data. None required.
Security. None required.
• ACOUSTICS: None.
71
Standard Design Criteria
Fire Stations
• PLUMBING: None.
• ELECTRICAL: Provide outlets per current codes and to support all equipment.
72
Standard Design Criteria
Fire Stations
• COMMUNICATION:
CCTV. Provide outlets required to support equipment.
CATV/Internal Video. Provide outlets required to support equipment.
PA/Audio. Provide a speaker and a microphone.
Telephone. Provide regular and secure multi-telephone line required to support telephone
and fax.
Data. Provide regular and secure data outlets to support required equipment. Security.
None required.
• ACOUSTICS: Provide partition and door construction with a minimum STC rating of 49.
• FUNCTIONAL DESCRIPTION: An accessible area that serves the entire building and is
dedicated to the collection and storage of non-hazardous materials for recycling, including
at a minimum: paper, corrugated cardboard, glass, plastics, and metals.
• ADJACENCIES: Shall be directly accessible from the corridor of the Fire Station.
73
Standard Design Criteria
Fire Stations
• PLUMBING: None.
• COMMUNICATION:
CCTV. None required.
CATV/Internal Video. None required.
PA/Audio. Provide speaker.
Telephone. None required.
Data. None required.
Security. None required.
• ACOUSTICS: None.
• MINIMUM AREA:
One-Story Fire Station: Portion of Net-To-Gross Ratio= 22%.
Two-Story Fire Station: Portion of Net-To-Gross Ratio= 30%.
74
Standard Design Criteria
Fire Stations
• COMMUNICATION:
CCTV. None required.
CATV/Internal Video. None required.
PA/Audio. None required.
Telephone. None required.
Data. None required.
Security. None required.
• FUNCTIONAL DESCRIPTION: This area supports the Fire Station’s electrical functions.
75
Standard Design Criteria
Fire Stations
• MINIMUM AREA:
One-Story Fire Station: Portion of Net-To-Gross Ratio= 22%.
Two-Story Fire Station: Portion of Net-To-Gross Ratio= 30%.
• COMMUNICATION:
CCTV. None required.
CATV/Internal Video. None required.
PA/Audio. None required.
Telephone. None required.
Data. None required.
Security. None required.
52. Patio:
• FUNCTIONAL DESCRIPTION: This area shall be provided for firefighters to relax and
grill.
76
Standard Design Criteria
Fire Stations
• MINIMUM AREA:
One or Two Company Fire Station: 150 SF, Net.
Three Company Fire Station: 250 SF, Net.
• DOORS/FRAME: None.
• PLUMBING: Provide per current codes. Provide hose bibb and if natural gas is available
provide a gas connection for an external grill.
• HVAC: None.
• FIRE PROTECTION: None. If an attached awning is provided, refer to NFPA 13 for the
requirements.
• ELECTRICAL: Provide exterior outlets per current codes. Provide minimum of four
weatherproof GFCI outlets.
• LIGHTING: Provide per current codes. Provide .5 ft. candles (11 Lux) with energy
efficient outdoor light fixtures.
• COMMUNICATION:
CCTV. None required.
CATV/Internal Video. None required.
PA/Audio. Provide a speaker.
Telephone. None required.
Data. None required.
Security. None required.
• ACOUSTICS None.
77
Standard Design Criteria
Fire Stations
53. Canopy:
• FUNCTIONAL DESCRIPTION: This area shall be provided for weather protection at the
main entrance to the Fire Station
• ADJACENCIES: Shall be directly off of the Lobby entrance of the Fire Station.
• MINIMUM AREA: 40 SF, Net. (Half of 80 SF, per US Army Technical Instructions 80001
(TI 800-01), Design Criteria).
• DOORS/FRAME: None.
• PLUMBING: None.
• COMMUNICATION:
CCTV. None required.
CATV/Internal Video. None required.
PA/Audio. Provide speaker.
Telephone. None required.
Data. None required.
Security. None required.
• ACOUSTICS: None.
78
Standard Design Criteria
Fire Stations
• FUNCTIONAL DESCRIPTION: This area serves as the entrance/exit to the facility. The
Vestibule should be recognizable from the outside as a well-lit, inviting space.
• ADJACENCIES: This area is in the Administrative Office area of the Fire Station and is
the main entrance into the Fire Station.
• PLUMBING: None.
• LIGHTING: Provide per current codes. Consider decorative lighting fixtures and task
lighting.
79
Standard Design Criteria
Fire Stations
• COMMUNICATION:
CCTV. None required.
CATV/Internal Video. None required.
PA/Audio. None required.
Telephone. None required.
Data. None required.
Security. None required.
• ACOUSTICS: None.
• SPECIAL REQUIREMENTS:
Provide airlock at main entrance when necessary.
Consider a recessed, built-in mat at entry.
• The layout of the parking lot and traffic circulation must consider the safety of the Fire
Station staff and visitors when entering and departing the facility. Access drives to staff
and public parking should not cross the vehicle access drive out of the Apparatus Bay. If
the parking lot design requires crosswalks, as a minimum, these must be painted and
identifiable with signage in appropriate locations to ensure the safety of the personnel
and visitors.
• Provide parking for authorized Fire Station staff. Parking area shall be sized to
accommodate two shifts. Visitor parking shall be separate from staff parking.
80