0% found this document useful (0 votes)
30 views1 page

Untitled 123

This document is a bid form from a cooling tower supplier for a project in Bangladesh. It provides specifications for a counterflow induced draft cooling tower with 4 cells and 4 fans. Key details include a heat rejection rate of 84,375,000 kcal/hr, circulating water flow of 5,625 cubic meters per hour, and dimensions of 40,150x10,150x10,400 mm. Materials of construction are listed as fiberglass reinforced plastic for the framework and casings.

Uploaded by

Ashik Hasan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
30 views1 page

Untitled 123

This document is a bid form from a cooling tower supplier for a project in Bangladesh. It provides specifications for a counterflow induced draft cooling tower with 4 cells and 4 fans. Key details include a heat rejection rate of 84,375,000 kcal/hr, circulating water flow of 5,625 cubic meters per hour, and dimensions of 40,150x10,150x10,400 mm. Materials of construction are listed as fiberglass reinforced plastic for the framework and casings.

Uploaded by

Ashik Hasan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Form : SM-F05C-00

Eff Date: 13/9/2010


Page : 1 of 2

Cooling Tower Bid Form C


CUSTOMER Our Ref. : TAP/5514/2020R0
UNITED ENTERPRISES & CO., LTD Date Orig. : 09.01.2020
PROJECT Your Job No:
UNITED PAYRA POWER LTD (UPPL) Date Orig. :

GENERAL Selection CF Series


Tower Model CFF 333328-224
Number of Cells Four (4) (4 Running + 0 Standby)
Heat Rejection (kcal/hr) 84,375,000.00 kcal/hr
Type Induced Draft, Counterflow, FRP Pultruded Structure

DESIGN & OPERATING CONDITIONS


3
Circulating Water Flow 5,625.0 m /hr/total 1,406.25 m3/hr/cell
Hot (Inlet) Water Temperature 47.0 °C
Cold (Outlet) Water Temperature 32.0 °C
Wet Bulb Temperature 29.0 °C
Tower Pump Head 6.9 m
Total Fan B.H.P. 77.7 kW
Drift Loss 0.005 % of Circulating Flow
Evaporation Loss (at Design) 2.295 % of Circulating Flow
Blowdown Loss (COC 5) 0.575 % of Circulating Flow
Make-up Water Loss 2.875 % of Circulating Flow
Design Wind Load 70 mph
Design Seismic Load NA %G
Tower Site Ground Level
Tower Exposure Unobstructed
STRUCTURAL DETAILS
Number of Cells Four (4)
Fans per Cell One (1)
Total Number of Fans Four (4)
Nominal Cell Dimension, Length x Width 10,000 x 10,000 mm
Overall Tower Dimension, Length x Width 40,150 x 10,150 mm
Height, Basin Curb to Fan Deck 8,400 mm
Fan Stack Height 2,000 mm
Overall Tower Height 10,400 mm
Inside Basin Dimension, Length x Width 41,000 x 12,000 mm
Column Extension, Perimeter 300 mm
Below Basin Curb, Interior 300 mm
Anchorage Perimeter
Hot Water Inlet, Number Four (4)
Nominal Diameter 500 mm
Description Terminate 300 mm Outside of Tower With Standard
150 lb RF Flange
Height Inlet Above Basin Curb 6,000 mm
Access to Top of Tower Stairway
Approximate Shipping Weight TBA kg
Approximate Operating Weight TBA kg
MATERIALS OF CONSTRUCTION
Framework Members FRP Pultruded
Casing FRP
Louver FRP
Fill Media PVC
Fill Support FRP Pultruded
Drift Eliminator PVC
Spacer N/A
Fan Stack FRP
Fan Deck FRP Pultruded (Non-Slip)
Partition FRP