(Con Nuevas Modificaciones) Power Calculations

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 52

Power

SUBSTATION SUPPLY BY Transformer kW POWER SUPPLY


(kVA)
Substation 01 TR-01.01 500 371.2 Port Workshop and Warehouse
Fence Lighting

Road Lighting

Tower Lighting

Substation 02 MV - 1,100.00 STS 01


MV - 1,100.00 STS 02
TR-02.01 2,000 999.00 Grasshopper 01
Grasshopper 02.01/02
Grasshopper 03.01/02
Grasshopper 04.01/02
Grasshopper 05.01/02
Grasshopper 06.01/02
Grasshopper 07.01
RGT 01
RGT 02
TR-02.02 2,000 1,269.73 RGT 03
RGT 04
Multipurpose Building
Admin. Building
Access Control
Road Lighting

Tower Lighting

Substation 03 MV - 2,400.00 STS 03


MV - 1,800.00 Transference Tower
TR-03.01 1,000 561.76 Pipe Conveyor
Conveyor Belt (CDRI-PELLET)
Conveyor Belt (OIP)
Water Tank
Water Tratament
Emergency Exit
Road Lighting
Fence Lighting

Tower Lighting

TR's 5,500
MV 6,400.00

TOTAL INSTALLED 10,800 MW


13500 MVA
ASSUPMTION
Installed Consumption
CONCEPT (Electrical Line) Power Diversity Power
Factor
(kW) (kW)
Line Workshop 166.000 0.8 113.400
FL1C1 1.725 1 1.725
FL1C2 1.380 1 1.380
FL1C3 1.380 1 1.380
FL1C4 1.035 1 1.035
FL1C5 0.690 1 0.690
FL1C6 0.690 1 0.690
FL2C1 3.728 1 3.728
FL2C2 3.728 1 3.728
FL2C3 3.728 1 3.728
H01RL1C1 2.616 1 2.616
H01RL1C2 1.744 1 1.744
H01RL1C3 1.744 1 1.744
V04RL2C1 4.271 1 4.271
V04RL2C2 4.271 1 4.271
V04RL2C3 4.271 1 4.271
V04RL3C1 4.271 1 4.271
V04RL3C2 4.271 1 4.271
V04RL3C3 4.271 1 4.271
V04RL4C1 3.783 1 3.783
V04RL4C2 3.783 1 3.783
V04RL4C3 3.783 1 3.783
TL1L1C1/24 24.000 1 24.000
TL2C1L1/24 24.000 1 24.000
TL11C1L1/24 24.000 1 24.000
TL13C1L1/24 24.000 1 24.000
TL15C1L1/24 24.000 1 24.000
TL16C1L1/24 24.000 1 24.000

STS 01 Line 1,100.000 0.8 880.000


STS 02 Line 1,100.000 0.8 880.000
GH01 47.000 0 0.000
GH02.01/02 47.000 0 0.000
GH03.01/02 47.000 0 0.000
GH04.01/02 47.000 0 0.000
GH05.01/02 47.000 0 0.000
GH06.01/02 47.000 0 0.000
GH07.01 47.000 0 0.000
RTG 01 Line 335.000 0.8 268.000
RTG 02 Line 335.000 0.8 268.000
RTG 03 Line 335.000 0.8 268.000
RTG 04 Line 335.000 0.8 268.000
Multipurpose Line 170.000 0.8 136.000
Adm. Building Line 110.000 0.8 88.000
Control Access Line 10.000 0.8 8.000
H02RL1C1 3.651 1 3.651
H02RL1C2 1.826 1 1.826
H02RL1C3 3.651 1 3.651
H03RL1C1 4.067 1 4.067
H03RL1C2 4.067 1 4.067
H03RL1C3 6.100 1 6.100
V03RL1C1 4.067 1 4.067
V03RL1C2 4.067 1 4.067
V03RL1C3 2.033 1 2.033
V03RL2C1 4.067 1 4.067
V03RL2C2 4.067 1 4.067
V03RL2C3 4.067 1 4.067
TL3L1C1/24 24.000 1 24.000
TL4L1C1/24 24.000 1 24.000
TL5L1C1/24 24.000 1 24.000
TL6L1C1/24 24.000 1 24.000
TL7L1C1/24 24.000 1 24.000
TL8L1C1/24 24.000 1 24.000
TL12L1C1/24 24.000 1 24.000
TL14L1C1/24 24.000 1 24.000
TL17L1C1/24 24.000 1 24.000
TL18L1C1/24 24.000 1 24.000
TL19L1C1/24 24.000 1 24.000

STS 03 Line 2,400.000 0.8 1,920.000


Transference Tower Line 1,800.000 0.8 1,440.000
Pipe Conveyor 50.000 0.8 40.000
Conveyor Belt (CDRI-PELLET) 177.000 0.8 141.600
Conveyor Belt (OIP) 88.000 0 0.000
Water Tank 18.000 0.8 14.400
Water Tratament 100.000 0.8 80.000
Emergency Exit 1.000 0 0.000
V04RL6C1 3.881 1 3.881
V04RL6C2 3.881 1 3.881
V04RL6C3 3.881 1 3.881
V04RL7C1 3.881 1 3.881
V04RL7C2 3.881 1 3.881
V04RL7C3 3.881 1 3.881
V04RL8C1 3.881 1 3.881
V04RL8C2 3.881 1 3.881
V04RL8C3 3.881 1 3.881
V04RL9C1 3.881 1 3.881
V04RL9C2 3.881 1 3.881
H04RL1C1 3.114 1 3.114
H04RL1C2 3.114 1 3.114
H04RL1C3 3.114 1 3.114
H04RL2C1 4.671 1 4.671
H04RL2C2 3.114 1 3.114
H04RL2C3 3.114 1 3.114
FL2C10 3.288 1 3.288
FL2C11 3.288 1 3.288
FL2C12 1.644 1 1.644
FL3C1 0.956 1 0.956
FL3C2 0.956 1 0.956
FL3C3 0.956 1 0.956
FL3C4 0.956 1 0.956
FL3C5 0.956 1 0.956
FL3C6 0.956 1 0.956
FL3C7 0.956 1 0.956
FL3C8 0.956 1 0.956
FL3C9 0.956 1 0.956
TL9L1C1/24 24.000 1 24.000
TL10L1C1/24 24.000 1 24.000

7,456.05 kW
9,601.65 kw
10
Substation 01 Electrical Consumer

POWER
POWER LV LENGTH nº
CIRCUITS MV
(KW) (m) Luminaires
(KVA)

Line Workshop - 166.000 187 -


FL1C1 - 1.725 258 5
FL1C2 - 1.380 219 4
FL1C3 - 1.380 178 4
FL1C4 - 1.035 125 3
FL1C5 - 0.690 115 2
FL1C6 - 0.690 95 2
FL2C1 - 3.728 192 2
FL2C2 - 3.728 212 2
FL2C3 - 3.728 232 2
H01RL1C1 - 2.616 217 3
H01RL1C2 - 1.744 237 2
H01RL1C3 - 1.744 257 2
V04RL2C1 - 4.271 59 1
V04RL2C2 - 4.271 98 1
V04RL2C3 - 4.271 138 1
V04RL3C1 - 4.271 177 1
V04RL3C2 - 4.271 216 1
V04RL3C3 - 4.271 257 1
V04RL4C1 - 3.783 257 1
V04RL4C2 - 3.783 95 1
V04RL4C3 - 3.783 136 1
TL1L1C1/24 - 24.000 307 24
TL2C1L1/24 - 24.000 357 24
TL11C1L1/24 - 24.000 254 24
TL13C1L1/24 - 24.000 200 24
TL15C1L1/24 - 24.000 177 24
TL16C1L1/24 - 24.000 228 24
0 463.952 kVA

Total Power Substation 0.46 MVA

Electrical Consumer

POWER
Substation 02 MV POWER LV LENGTH
(KW) (m)
(KVA)

STS 01 Line 1,100.00 - 212


STS 02 Line 1,100.00 212
Grasshopper 01 - 47.00 201
Grasshopper 02.01 - 47.00 214
Grasshopper 02.02 - 47.00 188
Grasshopper 03.01 - 47.00 252
Grasshopper 03.02 - 47.00 228
Grasshopper 04.01 - 47.00 288
Grasshopper 04.02 - 47.00 268
Grasshopper 05.01 - 47.00 324
Grasshopper 05.02 - 47.00 308
Grasshopper 06.01 - 47.00 366
Grasshopper 06.02 - 47.00 348
Grasshopper 07 - 47.00 388
RTG 01 Line - 335.00 355
RTG 02 Line 335.00 318
RTG 03 Line - 335.00 311
RTG 04 Line 335.00 274
Multipurpose Line - 170.00 20
Adm. Building Line - 110.00 108
Control Access Line - 10.00 253
H02RL1C1 - 3.651 169 2
H02RL1C2 - 1.826 129 1
H02RL1C3 - 3.651 115 2
H03RL1C1 - 4.067 147 2
H03RL1C2 - 4.067 187 2
H03RL1C3 - 6.100 195 3
V03RL1C1 - 4.067 176 2
V03RL1C2 - 4.067 216 2
V03RL1C3 - 2.033 136 1
V03RL2C1 - 4.067 128 2
V03RL2C2 - 4.067 168 2
V03RL2C3 - 4.067 206 2
TL3L1C1/24 - 24.000 296 24
TL4L1C1/24 - 24.000 247 24
TL5L1C1/24 - 24.000 197 24
TL6L1C1/24 - 24.000 165 24
TL7L1C1/24 - 24.000 213 24
TL8L1C1/24 - 24.000 259 24
TL12L1C1/24 - 24.000 145 24
TL14L1C1/24 - 24.000 91 24
TL17L1C1/24 - 24.000 237 24
TL18L1C1/24 - 24.000 186 24
TL19L1C1/24 - 24.000 135 24
2200 2,835.91 kVA

Total Power Substation 5.74489 MVA

Electrical Consumer
POWER
POWER LV LENGTH
Substation 03 MV
(KW) (m)
(KVA)

STS 03 Line 2,400.00 - 285


Transference Tower Line 1,800.00 1800 166
Pipe Conveyor - 50 274
Conveyor Belt (CDRI-PELLET) 177 283
Conveyor Belt (OIP) - 88 283
Water Tank - 18 98
Water Tratament - 100 126
Emergency Exit - 1 133
V04RL6C1 - 3.881 214 1
V04RL6C2 - 3.881 176 1
V04RL6C3 - 3.881 143 1
V04RL7C1 - 3.881 107 1
V04RL7C2 - 3.881 67 1
V04RL7C3 - 3.881 32 1
V04RL8C1 - 3.881 221 1
V04RL8C2 - 3.881 184 1
V04RL8C3 - 3.881 146 1
V04RL9C1 - 3.881 108 1
V04RL9C2 - 3.881 71 1
H04RL1C1 - 3.114 184 2
H04RL1C2 - 3.114 107 2
H04RL1C3 - 3.114 67 2
H04RL2C1 - 4.671 184 3
H04RL2C2 - 3.114 147 2
H04RL2C3 - 3.114 107 2
FL2C10 - 3.288 184 2
FL2C11 - 3.288 147 2
FL2C12 - 1.644 107 1
FL3C1 - 0.956 184 2
FL3C2 - 0.956 147 2
FL3C3 - 0.956 107 2
FL3C4 - 0.956 184 2
FL3C5 - 0.956 147 2
FL3C6 - 0.956 107 2
FL3C7 - 0.956 184 2
FL3C8 - 0.956 147 2
FL3C9 - 0.956 107 2
TL9L1C1/24 - 24.000 278 24
TL10L1C1/24 - 24.000 278 24
2,400.00 2952.198 kVA

Total Power Substation 5.352198 MVA

MT BT
4,600.00 KVA (MV) 6,252.062 KVA (LV)

Total 11.56 MW
mer CABLE

CABLE
VOLTAGE CURRENT Cross section Ampacity Drop V.
Cross Section nº Cables
(V) (A) (mm2) (A) (V)
(AWG)

400 239.60 600 304.00 475.00 1.00 5.32


231 7.47 2 33.62 130.00 1.00 2.39
231 5.97 2 33.62 130.00 1.00 1.62
231 5.97 2 33.62 130.00 1.00 1.32
231 4.48 10 5.26 40.00 1.00 4.44
231 2.99 10 5.26 40.00 1.00 2.72
231 2.99 10 5.26 40.00 1.00 2.25
231 16.14 2 33.62 130.00 1.00 3.84
231 16.14 2 33.62 130.00 1.00 4.24
231 16.14 2 33.62 130.00 1.00 4.64
231 11.32 4 21.15 95.00 1.00 4.84
231 7.55 4 21.15 95.00 1.00 3.53
231 7.55 4 21.15 95.00 1.00 3.82
231 18.49 4 21.15 95.00 1.00 2.15
231 18.49 4 21.15 95.00 1.00 3.57
231 18.49 4 21.15 95.00 1.00 5.03
231 18.49 2 33.62 130.00 1.00 4.06
231 18.49 2 33.62 130.00 1.00 4.95
231 18.49 2 33.62 130.00 1.00 5.89
231 16.38 2 33.62 130.00 1.00 5.22
231 16.38 2 33.62 130.00 1.00 1.93
231 16.38 2 33.62 130.00 1.00 2.76
400 34.64 2 33.62 130.00 1.00 11.41
400 34.64 1 42.40 150.00 1.00 10.52
400 34.64 2 33.62 130.00 1.00 9.44
400 34.64 4 21.15 95.00 1.00 11.82
400 34.64 4 21.15 95.00 1.00 10.46
400 34.64 2 33.62 130.00 1.00 8.48
712.21

mer CABLE

VOLTAGE CURRENT CABLE Cross section Ampacity nº Cables Drop V.


(V) (A) Cross Section (mm2) (A) (V)

13800 46.02 35.00 1.00 10.06


13800 46.02 35.00 1.00 10.06
400 67.84 2.00 33.62 130.00 1.00 14.64
400 67.84 2.00 33.62 130.00 1.00 15.58
400 67.84 2.00 33.62 130.00 1.00 13.69
400 67.84 2.00 33.62 130.00 1.00 18.35
400 67.84 2.00 33.62 130.00 1.00 16.60
400 67.84 1.00 42.40 150.00 1.00 16.63
400 67.84 1.00 42.40 150.00 1.00 15.47
400 67.84 1.00 42.40 150.00 1.00 18.71
400 67.84 1.00 42.40 150.00 1.00 17.78
400 67.84 1/0 53.49 170.00 1.00 16.75
400 67.84 1/0 53.49 170.00 1.00 15.93
400 67.84 1/0 53.49 170.00 1.00 17.76
400 483.53 750.00 380.00 535.00 1.00 16.30
400 483.53 750.00 380.00 535.00 1.00 14.60
400 483.53 750.00 380.00 535.00 1.00 14.28
400 483.53 750.00 380.00 535.00 1.00 12.58
400 245.37 300.00 152.00 320.00 1.00 1.17
400 158.77 300.00 152.00 320.00 1.00 4.07
400 14.43 2.00 33.62 130.00 1.00 3.92
231 15.81 4 21.15 95.00 1.00 5.26
231 7.90 4 21.15 95.00 1.00 2.01
231 15.81 4 21.15 95.00 1.00 3.58
231 17.61 4 21.15 95.00 1.00 5.10
231 17.61 4 21.15 95.00 1.00 6.49
231 26.41 2 33.62 130.00 1.00 6.38
231 17.61 4 21.15 95.00 1.00 6.10
231 17.61 2 33.62 130.00 1.00 4.71
231 8.80 4 21.15 95.00 1.00 2.36
231 17.61 4 21.15 95.00 1.00 4.44
231 17.61 4 21.15 95.00 1.00 5.83
231 17.61 2 33.62 130.00 1.00 4.49
400 34.64 2 33.62 130.00 1.00 11.01
400 34.64 2 33.62 130.00 1.00 9.18
400 34.64 2 33.62 130.00 1.00 7.32
400 34.64 2 33.62 130.00 1.00 6.13
400 34.64 2 33.62 130.00 1.00 7.92
400 34.64 2 33.62 130.00 1.00 9.63
400 34.64 2 33.62 130.00 1.00 5.39
400 34.64 2 33.62 130.00 1.00 3.38
400 34.64 2 33.62 130.00 1.00 8.81
400 34.64 2 33.62 130.00 1.00 6.92
400 34.64 2 33.62 130.00 1.00 5.02

mer CABLE
VOLTAGE CURRENT CABLE Cross section Ampacity Drop V.
nº Cables
(V) (A) (AWG or Kcmil) (mm2) (A) (V)

13800 100.41 35.00 1.00 29.50


13800 75.31 35.00 1.00 12.89
400 72.17 1.00 42.40 150.00 1.00 16.83
400 255.48 300.00 152.00 320.00 1.00 17.16
400 127.02 2/0 67.44 195.00 1.00 19.23
400 25.98 4.00 21.15 95.00 1.00 4.34
400 144.34 250.00 127.00 290.00 1.00 5.17
400 1.44 8.00 8.37 110.00 2.00 0.41
231 16.80 2 33.62 130.00 1.00 4.46
231 16.80 2 33.62 130.00 1.00 3.66
231 16.80 2 33.62 130.00 1.00 2.98
231 16.80 6 13.30 75.00 1.00 5.63
231 16.80 6 13.30 75.00 1.00 3.53
231 16.80 6 13.30 75.00 1.00 1.68
231 16.80 2 33.62 130.00 1.00 4.60
231 16.80 2 33.62 130.00 1.00 3.83
231 16.80 2 33.62 130.00 1.00 3.04
231 16.80 6 13.30 75.00 1.00 5.68
231 16.80 6 13.30 75.00 1.00 3.74
231 13.48 4 21.15 95.00 1.00 4.89
231 13.48 4 21.15 95.00 1.00 2.84
231 13.48 4 21.15 95.00 1.00 1.78
231 20.22 2 33.62 130.00 1.00 4.61
231 13.48 2 33.62 130.00 1.00 2.46
231 13.48 2 33.62 130.00 1.00 1.79
231 14.24 4 21.15 95.00 1.00 5.16
231 14.24 4 21.15 95.00 1.00 4.12
231 7.12 4 21.15 95.00 1.00 1.50
231 4.14 8 8.37 55.00 1.00 3.79
231 4.14 8 8.37 55.00 1.00 3.03
231 4.14 8 8.37 55.00 1.00 2.20
231 4.14 8 8.37 55.00 1.00 3.79
231 4.14 8 8.37 55.00 1.00 3.03
231 4.14 8 8.37 55.00 1.00 2.20
231 4.14 8 8.37 55.00 1.00 3.79
231 4.14 8 8.37 55.00 1.00 3.03
231 4.14 8 8.37 55.00 1.00 2.20
400 34.64 2 33.62 130.00 1.00 10.34
400 34.64 2 33.62 130.00 1.00 10.34
Max. Allowable
%Drop V.
V. Drop COMPLIANT
(V)
(%)

1.33% 1.5% OK
1.03% 3.0% OK
0.70% 3.0% OK
0.57% 3.0% OK
1.92% 3.0% OK
1.18% 3.0% OK
0.97% 3.0% OK
1.66% 3.0% OK
1.84% 3.0% OK
2.01% 3.0% OK
2.10% 3.0% OK
1.53% 3.0% OK
1.65% 3.0% OK
0.93% 3.0% OK
1.55% 3.0% OK
2.18% 3.0% OK
1.76% 3.0% OK
2.14% 3.0% OK
2.55% 3.0% OK
2.26% 3.0% OK
0.83% 3.0% OK
1.19% 3.0% OK
2.85% 3.0% OK
2.63% 3.0% OK
2.36% 3.0% OK
2.96% 3.0% OK
2.62% 3.0% OK
2.12% 3.0% OK

Max. Allowable
%Drop V. V. Drop COMPLIANT
(V)
(%)

0.07% 1.5% OK
0.07% 1.5% OK
3.66% 5.0% OK
3.90% 5.0% OK
3.42% 5.0% OK
4.59% 5.0% OK
4.15% 5.0% OK
4.16% 5.0% OK
3.87% 5.0% OK
4.68% 5.0% OK
4.45% 5.0% OK
4.19% 5.0% OK
3.98% 5.0% OK
4.44% 5.0% OK
4.08% 5.0% OK
3.65% 5.0% OK
3.57% 5.0% OK
3.15% 5.0% OK
0.29% 1.5% OK
1.02% 1.5% OK
0.98% 1.5% OK
2.28% 3.0% OK
0.87% 3.0% OK
1.55% 3.0% OK
2.21% 3.0% OK
2.81% 3.0% OK
2.76% 3.0% OK
2.64% 3.0% OK
2.04% 3.0% OK
1.02% 3.0% OK
1.92% 3.0% OK
2.52% 3.0% OK
1.95% 3.0% OK
2.75% 3.0% OK
2.30% 3.0% OK
1.83% 3.0% OK
1.53% 3.0% OK
1.98% 3.0% OK
2.41% 3.0% OK
1.35% 3.0% OK
0.85% 3.0% OK
2.20% 3.0% OK
1.73% 3.0% OK
1.25% 3.0% OK
Max. Allowable
Drop V.
V. Drop COMPLIANT
(%)
(%)

0.21% 1.5% OK
0.09% 1.5% OK
4.21% 5.0% OK
4.29% 5.0% OK
4.81% 5.0% OK
1.09% 1.5% OK
1.29% 1.5% OK
0.10% 0.5% OK
1.93% 3.0% OK
1.59% 3.0% OK
1.29% 3.0% OK
2.44% 3.0% OK
1.53% 3.0% OK
0.73% 3.0% OK
1.99% 3.0% OK
1.66% 3.0% OK
1.32% 3.0% OK
2.46% 3.0% OK
1.62% 3.0% OK
2.12% 3.0% OK
1.23% 3.0% OK
0.77% 3.0% OK
2.00% 3.0% OK
1.06% 3.0% OK
0.77% 3.0% OK
2.23% 3.0% OK
1.78% 3.0% OK
0.65% 3.0% OK
1.64% 3.0% OK
1.31% 3.0% OK
0.95% 3.0% OK
1.64% 3.0% OK
1.31% 3.0% OK
0.95% 3.0% OK
1.64% 3.0% OK
1.31% 3.0% OK
0.95% 3.0% OK
2.58% 3.0% OK
2.58% 3.0% OK
Equipment

Transformer 1
transformer 1 (multipurpose building
transformer 2 (multipurpose building
transformer 1
Transformer 1
Transformer 1 (near to silo tower)
Voltage
Area Relation kVp/kVs Power (MVA) type location medium-low<-13,8/04
medium-medium<-35,5/13,8
Substation 01 13,08/0,4 0.5 oil indoor medium-low
Substation 02 13,08/0,4 2 dry indoor medium-low
Substation 02 13,08/0,4 2 dry indoor medium-low
Substation 03 13,08/0,4 1 oil indoor medium-low
Substation 03 34,5/13,08 12 oil outdoor medium-medium
- 13,08/0,4 1 oil outdoor medium-low
Icu
(kA)

54.13
144.34
144.34
86.6
Substation 02 Circuits

POWER LV POWER LV LENGTH


CIRCUITS (KVA) Cos (α) (KW) (m)

Substation 02 1.24 0.97 1.20 79


Conv. Belt CDRI 1.1 221.65 0.97 215.00 79
Conv. Belt CDRI 1.2 221.65 0.97 215.00 79
Conv. Belt IOP 1.1 111.34 0.97 108.00 79
Conv. Belt IOP 1.2 111.34 0.97 108.00 79
LT09 13.61 0.97 13.20 143
LT10 13.61 0.97 13.20 93
LT11 13.61 0.97 13.20 65
FDAS-4 6.598 0.97 6.400 320
FDAS-5 4.948 0.97 4.800 302
FDAS-6 4.948 0.97 4.800 382
FDAS-7 4.948 0.97 4.800 263
FDAS-8 4.948 0.97 4.800 283
FDAS-9 4.948 0.97 4.800 243
Grasshopper 1.04 100.00 0.90 90.00 130.51
Grasshopper 1.05 100.00 0.90 90.00 85.75

939.381 kVA 897.20 kW

Substation 03 Circuits

POWER LV POWER LV LENGTH


CIRCUITS Cos (α)
(KVA) (KW) (m)

Substation 03 1.24 0.97 1.20 79


Transfer Tower 1,066.67 0.90 960.00 79

1,067.90 kVA 961.20 kW

Substation 04 Circuits

POWER LV POWER LV LENGTH


CIRCUITS Cos (α)
(KVA) (KW) (m)

Substation 04 1.24 0.97 1.20 79


Substation 05 1.33 0.90 1.20 242
Workers Restroom 11.11 0.90 10.00 79
Multipurpose Building 188.48 0.90 169.63 79
Admin. Building 219.36 0.90 197.42 79
BA-1 4.12 0.97 4.00 189
BA-2 8.041 0.97 2.80 189
BA-3 8.041 0.97 3.00 189
BA-4 8.041 0.97 3.60 189
BA-5 4.330 0.97 0.80 189
BA-6 3.711 0.97 2.60 189
FDAS-7 3.711 0.97 3.20 163
FDAS-8 8.041 0.97 1.00 143
FDAS-9 8.041 0.97 1.00 123
Grasshopper 1.01 100.00 0.90 90.00 182.58
Grasshopper 1.02 100.00 0.90 90.00 272.56
Grasshopper 1.03 100.00 0.90 90.00 175.1
Grasshopper 2.06 100.00 0.90 90.00 141.08
LT07 13.608 0.97 13.20 130.64
LT08 13.608 0.97 13.20 183.04

904.81 kVA 787.85 kW

Substation 05 Circuits

POWER LV POWER LV LENGTH


CIRCUITS Cos (α)
(KVA) (KW) (m)

STS 01 1,222.22 0.90 1,100.00 400


STS 02 1,222.22 0.90 1,100.00 400
STS 03 2,444.44 0.90 2,200.00 400

4,888.89 kVA 4,400.00 kW

Substation 06 Circuits

POWER LV POWER LV LENGTH


CIRCUITS Cos (α)
(KVA) (KW) (m)

0.00 kVA 0.00 kW

Substation 07 Circuits

POWER LV POWER LV LENGTH


CIRCUITS Cos (α)
(KVA) (KW) (m)

Substation 07 1.24 0.97 1.20 79


Grasshopper 2.02 100.00 0.90 90.00 160
Grasshopper 2.01 100.00 0.90 90.00 71.81
Mobile Radial Telesc. 388.89 0.90 350.00 85.82
H01 1.24 0.97 1.20 240
LT01 13.61 0.97 13.20 72.92
LT02 13.61 0.97 13.20 20
LT03 13.61 0.97 13.20 42.03
LT04 13.61 0.97 13.20 112.97
LT05 13.61 0.97 13.20 147.16
LT06 13.61 0.97 13.20 191.67
PLS1-01 8.041 0.97 7.80 285
PLS2_02 8.041 0.97 7.80 285
PLS3_03 8.041 0.97 7.80 310
PLS4_04 8.041 0.97 7.80 310
PLS5_05 4.330 0.97 4.20 330
PLS6_06 3.711 0.97 3.60 330

713.219 kVA 650.60 kW

Substation 08 Circuits

POWER LV POWER LV LENGTH


CIRCUITS Cos (α)
(KVA) (KW) (m)

Substation 08 1.24 0.97 1.20 79


RTG 04 372.22 0.90 335.00 177.43
RTG 03 372.22 0.90 335.00 137.46
Grasshopper 2.04 100.00 0.90 90.00 121.74
Grasshopper 2.05 100.00 0.90 90.00 163.97

945.68 kVA 851.20 kW

Substation 09 Circuits

POWER LV POWER LV LENGTH


CIRCUITS Cos (α)
(KVA) (KW) (m)

Substation 09 1.24 0.97 1.20 79


RTG 01 372.22 0.90 335.00 45.65
RTG 02 372.22 0.90 335.00 85.06
Grasshopper 2.03 100.00 0.90 90.00 89.03

845.682 kVA 761.20 kW

Substation 10 Circuits
POWER LV POWER LV LENGTH
CIRCUITS Cos (α)
(KVA) (KW) (m)

Substation 10 1.24 0.97 1.20 79


Workshop 199.356 0.90 179.42 63.2
ACCESS 65.422 0.90 58.88 63.2
FLN-A 7.422 0.97 7.20 292
FLN1 2.474 0.97 2.40 125
FLN2 2.474 0.97 2.40 125
FLN3 2.474 0.97 2.40 125
FLN-B 7.422 0.97 7.20 292
FLN4 2.474 0.97 2.40 125
FLN5 2.474 0.97 2.40 125
FLN6 2.474 0.97 2.40 125
FLE-A 6.186 0.97 6.00 231
FLE1 2.062 0.97 2.00 114
FLE2 2.062 0.97 2.00 114
FLE3 2.062 0.97 2.00 114
FLE-B 5.361 0.97 5.20 231
FLE4 2.062 0.97 2.00 114
FLE5 1.649 0.97 1.60 114
FLE6 1.649 0.97 1.60 114
FLE-C 5.361 0.97 5.20 334
FLE4 2.062 0.97 2.00 103
FLE5 1.649 0.97 1.60 103
FLE6 1.649 0.97 1.60 103
FLE-D 5.361 0.97 5.20 334
FLE4 2.062 0.97 2.00 103
FLE5 1.649 0.97 1.60 103
FLE6 1.649 0.97 1.60 103
FLS-A 7.423 0.97 7.20 472
FLS1 2.474 0.97 2.40 123
FLS2 2.474 0.97 2.40 123
FLS3 2.474 0.97 2.40 123
FLS-B 7.423 0.97 7.20 472
FLS4 2.474 0.97 2.40 123
FLS5 2.474 0.97 2.40 123
FLS6 2.474 0.97 2.40 123
LT12 13.608 0.97 13.20 136
LT13 13.608 0.97 13.20 207
FDAN-1 2.268 0.97 2.200 320
FDAN-2 2.268 0.97 2.200 302
FDAN-3 2.371 0.97 2.300 382
FDAN-4 2.165 0.97 2.100 263
FDAN-5 2.268 0.97 2.200 283
FDAN-6 1.546 0.97 1.500 243
FDANE-1 1.856 0.97 1.800 290
FDANE-2 1.856 0.97 1.800 270
FDANE-3 1.856 0.97 1.800 250
FDANE-4 2.680 0.97 2.600 263
FDANE-5 2.062 0.97 2.000 283
FDANE-6 2.062 0.97 2.000 243
PKE-1.01 4.330 0.97 4.200 163
PKE-2.01 4.330 0.97 4.200 183
PKE-3.01 4.330 0.97 4.200 203
ACE-1 4.330 0.97 4.200 163

439.722 kVA 408.00 kW

Substation 11 Circuits

POWER LV POWER LV LENGTH


CIRCUITS Cos (α)
(KVA) (KW) (m)

Substation 10 1.24 0.97 1.20 79


Substation 01 1.333 0.90 1.200 203
Water Treatment Plant 24.778 0.90 22.300 183
Pumping Station 6.211 0.90 5.590 203
Emergency Exit 1.667 0.90 1.500 183
Pipe Conveyor 888.889 0.90 800.000 203
FDASE-1 3.505 0.97 3.400 183
FDASE-2 3.093 0.97 3.000 203
FDASE-3 3.093 0.97 3.000 203
FDASE-4 6.186 0.97 6.000 183
FDASE-5 4.330 0.97 4.200 203
FDASE-6 4.330 0.97 4.200 203
FDAS-1 4.948 0.97 4.800 183
FDAS-2 4.948 0.97 4.800 203
FDAS-3 3.299 0.97 3.200 203

961.847 kVA 868.39 kW

(2) Buried installation, directly or under a tube (25ºC) with standard ground thermal resistivity of 2.5k.m/W.
TOTAL 11,707.14 KVA 10,585.64 kW
s MCCB Cable Cross Section (mm2) Ampacity

BREAKER CABLE Ampacity


VOLTAGE CURRENT Allowable current Number of
(V) (A) 36kA Cross Section (directly buried) (2) circuits max. Adm.
GAUGE (mm2) (A)

400 1.79 16.00 16.00 75.00 1.00 61.50


400 319.92 630.00 400.00 430.00 1.00 352.60
400 319.92 630.00 400.00 430.00 1.00 352.60
400 160.71 200.00 120.00 230.00 1.00 188.60
400 160.71 200.00 95.00 202.00 1.00 165.64
400 19.64 25.00 35.00 117.00 1.00 87.75
400 19.64 25.00 35.00 117.00 1.00 87.75
400 19.64 25.00 35.00 117.00 1.00 87.75
400 9.52 16.00 25.00 96.00 1.00 72.00
400 7.14 16.00 25.00 96.00 1.00 72.00
400 7.14 16.00 25.00 96.00 1.00 72.00
400 7.14 16.00 25.00 96.00 1.00 72.00
400 7.14 16.00 25.00 96.00 1.00 72.00
400 7.14 16.00 25.00 96.00 1.00 72.00
400 144.34 200.00 95.00 202.00 1.00 165.64
400 144.34 200.00 95.00 202.00 1.00 165.64

s MCCB Cable Cross Section (mm2) Ampacity

BREAKER CABLE Ampacity


VOLTAGE CURRENT Allowable current Number of
36kA Cross Section max. Adm.
(V) (A) (directly buried) (2) circuits
GAUGE (mm2) (A)

400 1.79 16.00 16.00 75.00 1.00 61.50


400 630.00 800.00 630.00 2,208.00 4.00 1,810.56

s MCCB Cable Cross Section (mm2) Ampacity

BREAKER CABLE Ampacity


VOLTAGE CURRENT Allowable current Number of
36kA Cross Section max. Adm.
(V) (A) (directly buried) (2) circuits
GAUGE (mm2) (A)

400 1.79 16.00 16.00 75.00 1.00 61.50


400 1.92 16.00 95.00 202.00 1.00 165.64
400 16.04 25.00 16.00 75.00 1.00 61.50
400 272.04 400.00 300.00 380.00 1.00 311.60
400 316.61 400.00 400.00 430.00 1.00 352.60
400 5.95 16.00 25.00 96.00 1.00 72.00
400 11.61 16.00 25.00 96.00 1.00 72.00
400 11.61 16.00 25.00 96.00 1.00 72.00
400 11.61 16.00 25.00 96.00 1.00 72.00
400 6.25 16.00 25.00 96.00 1.00 72.00
400 5.36 16.00 25.00 96.00 1.00 72.00
400 5.36 16.00 25.00 96.00 1.00 72.00
400 11.61 16.00 25.00 96.00 1.00 72.00
400 11.61 16.00 25.00 96.00 1.00 72.00
400 144.34 200.00 120.00 230.00 1.00 188.60
400 144.34 200.00 120.00 230.00 1.00 188.60
400 144.34 200.00 95.00 202.00 1.00 165.64
400 144.34 200.00 95.00 202.00 1.00 165.64
400 19.64 25.00 35.00 117.00 1.00 87.75
400 19.64 25.00 35.00 117.00 1.00 87.75

s Cubicle MV Cable Cross Section (mm2) Ampacity

Transf. CABLE Ampacity


VOLTAGE CURRENT Allowable current Number of
Protection by Cross Section max. Adm.
(V) (A) Cubicle MV (mm2) (directly buried) (2) circuits (A)

13800 51.13 25 kV 95.00 202.00 1.00 165.64


13800 51.13 25 kV 95.00 202.00 1.00 165.64
13800 102.27 25 kV 95.00 202.00 1.00 165.64

s MCCB Cable Cross Section (mm2) Ampacity

BREAKER CABLE Ampacity


VOLTAGE CURRENT Allowable current Number of
36kA Cross Section (directly buried) (2) max. Adm.
(V) (A) circuits
GAUGE (mm2) (A)

s MCCB Cable Cross Section (mm2) Ampacity

BREAKER CABLE Ampacity


VOLTAGE CURRENT Allowable current Number of
36kA Cross Section (directly buried) (2) max. Adm.
(V) (A) circuits
GAUGE (mm2) (A)

400 1.79 16.00 16.00 75.00 1.00 61.50


400 144.34 200.00 240.00 336.00 1.00 275.52
400 144.34 200.00 95.00 202.00 1.00 165.64
400 561.31 630.00 300.00 760.00 2.00 623.20
400 1.79 16.00 300.00 760.00 2.00 623.20
400 19.64 25.00 35.00 117.00 1.00 87.75
400 19.64 25.00 35.00 117.00 1.00 87.75
400 19.64 25.00 35.00 117.00 1.00 87.75
400 19.64 25.00 35.00 117.00 1.00 87.75
400 19.64 25.00 35.00 117.00 1.00 87.75
400 19.64 25.00 35.00 117.00 1.00 87.75
400 11.61 16.00 35.00 117.00 1.00 87.75
400 11.61 16.00 35.00 117.00 1.00 87.75
400 11.61 16.00 35.00 117.00 1.00 87.75
400 11.61 16.00 35.00 117.00 1.00 87.75
400 6.25 16.00 35.00 117.00 1.00 87.75
400 5.36 16.00 35.00 117.00 1.00 87.75

s MCCB Cable Cross Section (mm2) Ampacity

BREAKER CABLE Ampacity


VOLTAGE CURRENT Allowable current Number of
36kA Cross Section max. Adm.
(V) (A) GAUGE (mm2) (directly buried) (2) circuits (A)

400 1.79 16.00 16.00 75.00 1.00 61.50


400 537.26 630.00 400.00 860.00 2.00 705.20
400 537.26 630.00 400.00 860.00 2.00 705.20
400 144.34 200.00 95.00 202.00 1.00 165.64
400 144.34 200.00 95.00 202.00 1.00 165.64

s MCCB Cable Cross Section (mm2) Ampacity

BREAKER CABLE Ampacity


VOLTAGE CURRENT Allowable current Number of
36kA Cross Section (directly buried) (2) max. Adm.
(V) (A) circuits
GAUGE (mm2) (A)

400 1.79 16.00 16.00 75.00 1.00 61.50


400 537.26 630.00 400.00 860.00 2.00 705.20
400 537.26 630.00 400.00 860.00 2.00 705.20
400 144.34 200.00 95.00 202.00 1.00 165.64

s MCCB Cable Cross Section (mm2) Ampacity


BREAKER CABLE Ampacity
VOLTAGE CURRENT Allowable current Number of
36kA Cross Section max. Adm.
(V) (A) (directly buried) (2) circuits
GAUGE (mm2) (A)

400 1.79 16.00 16.00 75.00 1.00 61.50


400 287.74 400.00 240.00 672.00 2.00 504.00
400 94.43 125.00 240.00 672.00 2.00 504.00
400 10.71 16.00 95.00 202.00 1.00 151.50
230 10.76 16.00 25.00 96.00 1.00 72.00
230 10.76 16.00 25.00 96.00 1.00 72.00
230 10.76 16.00 25.00 96.00 1.00 72.00
400 10.71 16.00 95.00 202.00 1.00 151.50
230 10.76 16.00 25.00 96.00 1.00 72.00
230 10.76 16.00 25.00 96.00 1.00 72.00
230 10.76 16.00 25.00 96.00 1.00 72.00
400 8.93 16.00 50.00 138.00 1.00 103.50
230 8.96 16.00 25.00 96.00 1.00 72.00
230 8.96 16.00 25.00 96.00 1.00 72.00
230 8.96 16.00 25.00 96.00 1.00 72.00
400 7.74 16.00 50.00 138.00 1.00 103.50
230 8.96 16.00 25.00 96.00 1.00 72.00
230 7.17 16.00 25.00 96.00 1.00 72.00
230 7.17 16.00 25.00 96.00 1.00 72.00
400 7.74 16.00 95.00 202.00 1.00 151.50
230 8.96 16.00 25.00 96.00 1.00 72.00
230 7.17 16.00 25.00 96.00 1.00 72.00
230 7.17 16.00 25.00 96.00 1.00 72.00
400 7.74 16.00 95.00 202.00 1.00 151.50
230 8.96 16.00 25.00 96.00 1.00 72.00
230 7.17 16.00 25.00 96.00 1.00 72.00
230 7.17 16.00 25.00 96.00 1.00 72.00
400 10.71 16.00 95.00 202.00 1.00 151.50
230 10.76 16.00 25.00 96.00 1.00 72.00
230 10.76 16.00 25.00 96.00 1.00 72.00
230 10.76 16.00 25.00 96.00 1.00 72.00
400 10.71 16.00 95.00 202.00 1.00 151.50
230 10.76 16.00 25.00 96.00 1.00 72.00
230 10.76 16.00 25.00 96.00 1.00 72.00
230 10.76 16.00 25.00 96.00 1.00 72.00
400 19.64 25.00 25.00 96.00 1.00 72.00
400 19.64 25.00 50.00 138.00 1.00 103.50
400 3.27 16.00 16.00 75.00 1.00 56.25
400 3.27 16.00 16.00 75.00 1.00 56.25
400 3.42 16.00 16.00 75.00 1.00 56.25
400 3.12 16.00 16.00 75.00 1.00 56.25
400 3.27 16.00 16.00 75.00 1.00 56.25
400 2.23 16.00 16.00 75.00 1.00 56.25
400 2.68 16.00 16.00 75.00 1.00 56.25
400 2.68 16.00 16.00 75.00 1.00 56.25
400 2.68 16.00 16.00 75.00 1.00 56.25
400 3.87 16.00 16.00 75.00 1.00 56.25
400 2.98 16.00 16.00 75.00 1.00 56.25
400 2.98 16.00 16.00 75.00 1.00 56.25
400 6.25 16.00 16.00 75.00 1.00 56.25
400 6.25 16.00 16.00 75.00 1.00 56.25
400 6.25 16.00 16.00 75.00 1.00 56.25
400 6.06 16.00 16.00 75.00 1.00 56.25

s MCCB Cable Cross Section (mm2) Ampacity

BREAKER CABLE Ampacity


VOLTAGE CURRENT Allowable current Number of
36kA Cross Section max. Adm.
(V) (A) (directly buried) (2) circuits
GAUGE (mm2) (A)

400 1.79 16.00 16.00 75.00 1.00 61.50


400 1.92 16.00 16.00 75.00 1.00 56.25
400 35.76 40.00 50.00 138.00 1.00 103.50
400 8.96 16.00 25.00 96.00 1.00 72.00
400 2.41 16.00 16.00 75.00 1.00 56.25
400 1,283.00 1,600.00 500.00 1,932.00 4.00 1,449.00
400 5.06 16.00 16.00 75.00 1.00 56.25
400 4.46 16.00 16.00 75.00 1.00 56.25
400 4.46 16.00 16.00 75.00 1.00 56.25
400 8.93 16.00 16.00 75.00 1.00 56.25
400 6.25 16.00 16.00 75.00 1.00 56.25
400 6.25 16.00 16.00 75.00 1.00 56.25
400 7.14 16.00 16.00 75.00 1.00 56.25
400 7.14 16.00 16.00 75.00 1.00 56.25
400 4.76 16.00 16.00 75.00 1.00 56.25

und thermal resistivity of 2.5k.m/W.


Drop V.
Ampacity Coduit (V)
Max.
Electrical cable Electrical conduit Drop V. %Drop V. Allowable V. COMPLIANT
diameter (mm) diameter (mm) (V) (V) Drop
(%)
46.00 249.00 0.32 0.08% 1.5% OK
174.00 250.00 2.28 0.57% 3.0% OK
174.00 250.00 2.28 0.57% 3.0% OK
97.00 200.00 3.82 0.95% 3.0% OK
87.00 200.00 4.82 1.21% 3.0% OK
59.50 160.00 2.90 0.72% 1.5% OK
59.50 160.00 1.88 0.47% 1.5% OK
59.50 160.00 1.32 0.33% 1.5% OK
54.00 160.00 4.40 1.10% 1.5% OK
54.00 160.00 3.11 0.78% 1.5% OK
54.00 160.00 3.94 0.98% 1.5% OK
54.00 160.00 2.71 0.68% 1.5% OK
54.00 160.00 2.92 0.73% 1.5% OK
54.00 160.00 2.51 0.63% 1.5% OK
87.00 250.00 7.16 1.79% 3.0% OK
87.00 250.00 4.70 1.18% 3.0% OK

Drop V.
Ampacity Coduit (V)
Max.
Electrical cable Electrical conduit Drop V. %Drop V. Allowable V. COMPLIANT
diameter (mm) diameter (mm) (V) (V) Drop
(%)
46.00 249.00 0.32 0.08% 1.5% OK
218.50 315.00 0.71 0.18% 3.0% OK

Drop V.
Ampacity Coduit (V)
Max.
Electrical cable Electrical conduit Drop V. %Drop V. Allowable V. COMPLIANT
diameter (mm) diameter (mm) (V) (V) Drop
(%)
46.00 249.00 0.32 0.08% 1.5% OK
87.00 110.00 0.18 0.04% 3.0% OK
46.00 160.00 2.86 0.71% 3.0% OK
151.00 250.00 2.59 0.65% 3.0% OK
174.00 250.00 2.26 0.56% 3.0% OK
54.00 160.00 1.62 0.41% 1.5% OK
54.00 160.00 3.17 0.79% 1.5% OK
54.00 160.00 3.17 0.79% 1.5% OK
54.00 160.00 3.17 0.79% 1.5% OK
54.00 160.00 1.70 0.43% 1.5% OK
54.00 160.00 1.46 0.37% 1.5% OK
54.00 160.00 1.26 0.32% 1.5% OK
54.00 160.00 2.40 0.60% 1.5% OK
54.00 160.00 2.06 0.52% 1.5% OK
97.00 200.00 7.92 1.98% 3.0% OK
97.00 250.00 11.83 2.96% 3.0% OK
87.00 250.00 9.60 2.40% 3.0% OK
87.00 250.00 7.73 1.93% 3.0% OK
59.50 110.00 2.65 0.66% 1.5% OK
59.50 110.00 3.71 0.93% 1.5% OK

Drop V.
Ampacity Coduit (V)
Max.
Electrical cable Electrical conduit Drop V. %Drop V. Allowable V. COMPLIANT
diameter (mm) diameter (mm) (V) (V) Drop
(%)
87.00 200.00 7.77 0.06% 3.0% OK
87.00 200.00 7.77 0.06% 3.0% OK
87.00 200.00 15.54 0.11% 3.0% OK

Drop V.
Ampacity Coduit (V)
Max.
Electrical cable Electrical conduit Drop V. %Drop V. Allowable V. COMPLIANT
diameter (mm) diameter (mm) (V) (V) Drop
(%)

Drop V.
Ampacity Coduit (V)
Max.
Electrical cable Electrical conduit Drop V. %Drop V. Allowable V. COMPLIANT
diameter (mm) diameter (mm) (V) (V) Drop
(%)
46.00 249.00 0.32 0.08% 1.5% OK
133.00 250.00 3.47 0.87% 3.0% OK
87.00 200.00 3.94 0.98% 3.0% OK
151.00 250.00 2.90 0.72% 3.0% OK
151.00 251.00 0.03 0.01% 1.5% OK
59.50 110.00 1.48 0.37% 1.5% OK
59.50 110.00 0.41 0.10% 1.5% OK
59.50 110.00 0.85 0.21% 1.5% OK
59.50 110.00 2.29 0.57% 1.5% OK
59.50 110.00 2.98 0.75% 1.5% OK
59.50 110.00 3.88 0.97% 1.5% OK
59.50 110.00 3.41 0.85% 1.5% OK
59.50 110.00 3.41 0.85% 1.5% OK
59.50 110.00 3.71 0.93% 1.5% OK
59.50 110.00 3.71 0.93% 1.5% OK
59.50 110.00 2.13 0.53% 1.5% OK
59.50 110.00 1.82 0.46% 1.5% OK

Drop V.
Ampacity Coduit (V)
Max.
Electrical cable Electrical conduit Drop V. %Drop V. Allowable V. COMPLIANT
diameter (mm) diameter (mm) (V) (V) Drop
(%)
46.00 249.00 0.32 0.08% 1.5% OK
174.00 250.00 4.30 1.07% 3.0% OK
174.00 250.00 3.33 0.83% 3.0% OK
87.00 250.00 6.67 1.67% 3.0% OK
87.00 250.00 8.99 2.25% 3.0% OK

Drop V.
Ampacity Coduit (V)
Max.
Electrical cable Electrical conduit Drop V. %Drop V. Allowable V. COMPLIANT
diameter (mm) diameter (mm) (V) (V) Drop
(%)
46.00 249.00 0.32 0.08% 1.5% OK
174.00 250.00 1.11 0.28% 3.0% OK
174.00 250.00 2.06 0.52% 3.0% OK
87.00 250.00 4.88 1.22% 3.0% OK

Drop V.
Ampacity Coduit (V)

COMPLIANT
Max.
Electrical cable Electrical conduit Drop V. %Drop V. Allowable V. COMPLIANT
diameter (mm) diameter (mm) (V) (V) Drop
(%)
46.00 249.00 0.32 0.08% 1.5% OK
133.00 250.00 1.37 0.34% 3.0% OK
133.00 250.00 0.45 0.11% 3.0% OK
87.00 200.00 1.19 0.30% 1.5% OK
54.00 160.00 2.24 0.97% 1.5% OK
54.00 160.00 2.24 0.97% 1.5% OK
54.00 160.00 2.24 0.97% 1.5% OK
87.00 200.00 1.19 0.30% 1.5% OK
54.00 160.00 2.24 0.97% 1.5% OK
54.00 160.00 2.24 0.97% 1.5% OK
54.00 160.00 2.24 0.97% 1.5% OK
67.50 160.00 1.49 0.37% 1.5% OK
54.00 160.00 1.70 0.74% 1.5% OK
54.00 160.00 1.70 0.74% 1.5% OK
54.00 160.00 1.70 0.74% 1.5% OK
67.50 160.00 1.29 0.32% 1.5% OK
54.00 160.00 1.70 0.74% 1.5% OK
54.00 160.00 1.36 0.59% 1.5% OK
54.00 160.00 1.36 0.59% 1.5% OK
87.00 200.00 0.98 0.25% 1.5% OK
54.00 160.00 1.54 0.67% 1.5% OK
54.00 160.00 1.23 0.54% 1.5% OK
54.00 160.00 1.23 0.54% 1.5% OK
87.00 200.00 0.98 0.25% 1.5% OK
54.00 160.00 1.54 0.67% 1.5% OK
54.00 160.00 1.23 0.54% 1.5% OK
54.00 160.00 1.23 0.54% 1.5% OK
87.00 200.00 1.92 0.48% 1.5% OK
54.00 160.00 2.21 0.96% 1.5% OK
54.00 160.00 2.21 0.96% 1.5% OK
54.00 160.00 2.21 0.96% 1.5% OK
87.00 200.00 1.92 0.48% 1.5% OK
54.00 160.00 2.21 0.96% 1.5% OK
54.00 160.00 2.21 0.96% 1.5% OK
54.00 160.00 2.21 0.96% 1.5% OK
54.00 160.00 3.86 0.96% 1.5% OK
67.50 160.00 2.93 0.73% 1.5% OK
46.00 160.00 2.36 0.59% 1.5% OK
46.00 160.00 2.23 0.56% 1.5% OK
46.00 160.00 2.95 0.74% 1.5% OK
46.00 160.00 1.85 0.46% 1.5% OK
46.00 160.00 2.09 0.52% 1.5% OK
46.00 160.00 1.22 0.31% 1.5% OK
46.00 160.00 1.75 0.44% 1.5% OK
46.00 160.00 1.63 0.41% 1.5% OK
46.00 160.00 1.51 0.38% 1.5% OK
46.00 160.00 2.29 0.57% 1.5% OK
46.00 160.00 1.90 0.47% 1.5% OK
46.00 160.00 1.63 0.41% 1.5% OK
46.00 160.00 2.30 0.57% 1.5% OK
46.00 160.00 2.58 0.64% 1.5% OK
46.00 160.00 2.86 0.72% 1.5% OK
46.00 160.00 2.23 0.56% 1.5% OK

Drop V.
Ampacity Coduit (V)
Max.
Electrical cable Electrical conduit
Drop V. %Drop V. Allowable V. COMPLIANT
diameter per diameter per
(V) (V) Drop
Circuit (mm) Circuit(mm)
(%)
46.00 249.00 0.32 0.08% 1.5% OK
46.00 160.00 0.88 0.22% 3.0% OK
67.50 160.00 4.72 1.18% 3.0% OK
54.00 160.00 2.63 0.66% 3.0% OK
46.00 160.00 0.99 0.25% 3.0% OK
195.50 250.00 4.70 1.17% 3.0% OK
46.00 160.00 2.09 0.52% 1.5% OK
46.00 160.00 2.04 0.51% 1.5% OK
46.00 160.00 2.04 0.51% 1.5% OK
46.00 160.00 3.68 0.92% 1.5% OK
46.00 160.00 2.86 0.72% 1.5% OK
46.00 160.00 2.86 0.72% 1.5% OK
46.00 160.00 2.95 0.74% 1.5% OK
46.00 160.00 3.27 0.82% 1.5% OK
46.00 160.00 2.18 0.54% 1.5% OK
Port Admin Building
EQUIPMENT
Electrical Equipment
Automatic sliding door, in aluminum and glass, for pedestrian access, with central opening system, with two
sliding leaves of 100x210 cm and two fixed leaves of 120x210 cm.
Electric hand dryers
HVAC
VRF outdoor condensing unit
Air handling unit AHU-01
SPLIT 3kW. Electric refrigeration unit.
Extraction Fan ( Q=100 m3/h, Available static pressure =150 Pa) 1Φ
Extraction Fan ( Q=200 m3/h, Available static pressure =150 Pa) 1Φ
Extraction Fan ( Q=400 m3/h, Available static pressure =150 Pa) 1Φ
Lighting
Offices - Meeting Room - Toilets - Kitchen - Administration
Corridors and Halls
Emergency Lighting
Socket Supply
WP1, Work station Socket
UPS Work station Socket
Socket general uses
Toaster
Refrigerator
Microwave Oven
Office coffee maker
IT Supply
Electronic planels supply and UPS

Port Multipurpose Building


EQUIPMENT
Electrical Equipment
Electric hand dryers
Kitchen
Electrical Equipment
HVAC
Rooftop packaged. Supply air flow of 3692 m3/h-total cooling of 22.7 kW.
Rooftop packaged. Supply air flow of 3402 m3/h-total cooling of 19.7 kW.
Rooftop packaged. Supply air flow of 3740.4 m3/h-total cooling of 13.6 kW.
SPLIT 3 kW. Electric refrigeration unit.
SPLIT 7.5 kW. Electric refrigeration unit.
Extraction Fan ( Q=100 m3/h, Available static pressure =150 Pa) 1Φ
Extraction Fan ( Q=200 m3/h, Available static pressure =150 Pa) 1Φ
Extraction Fan ( Q=400 m3/h, Available static pressure =150 Pa) 1Φ
Lighting
Offices - Meeting Room - Toilets - Kitchen - Administration
Corridors and Halls
Emergency Lighting
technical roof Lighting
Socket Supply
WP1, Work station Socket
UPS Work station Socket
Socket general uses
Toaster
Refrigerator
Microwave Oven
Office coffee maker
IT Supply
Electronic planels supply and UPS

Workers Restroom
EQUIPMENT
Electrical Equipment
Electric hand dryers
Socket Supply
Socket general uses
Lighting
Toilets
Emergency Lighting

Port Workshop-Warehouse
EQUIPMENT
Electrical Equipment
Electric hand dryers
Brich Craner 5-10 Tn
HVAC
Rooftop packaged. Supply air flow rate of 19187.25 m3/h-total cooling of 74.8 kW.
SPLIT 3 kW. Electric refrigeration unit.
SPLIT 6 kW. Electric refrigeration unit.
SPLIT 7.5 kW. Electric refrigeration unit.
Extraction Fan ( Q=100 m3/h, Available static pressure =150 Pa) 1Φ
Extraction Fan ( Q=200 m3/h, Available static pressure =150 Pa) 1Φ
Extraction Fan ( Q=400 m3/h, Available static pressure =150 Pa) 1Φ
Lighting
Offices - Meeting room - Toilets - Kitchen - Administration.
Corridors and halls
Warehouse
Emergency Lighting
Socket Supply
WP1, Work station Socket
UPS Work station Socket
Socket general uses
Refrigerator
Office coffee maker
IT Supply
Electronic planels supply and UPS

Port Gates & Access Contro


EQUIPMENT
HVAC
SPLIT 3 kW. Electric refrigeration unit.
SPLIT 5 kW. Electric refrigeration unit.
Extraction Fan ( Q=100 m3/h, Available static pressure =150 Pa) 1Φ
Extraction Fan ( Q=400 m3/h, Available static pressure =150 Pa) 1Φ
Lighting
Offices - Meeting Room - Toilets - Kitchen - Administration
Corridors and Halls
Warehouse
Emergency Lighting
Socket Supply
WP1, Work Station Socket
UPS Work Station Socket
Socket general uses
Toaster
Refrigerator
Microwave Oven
Office coffee maker
IT Supply
Electronic planels supply and UPS

Port Water Treatment Plant

EQUIPMENT
Electrical Equipment
Electric hand dryers
HVAC
SPLIT 5 kW. Electric refrigeration unit.
Extraction Fan ( Q=100 m3/h, Available static pressure =150 Pa) 1Φ
Roof Extraction Fan (Q=5000 m3/h, Static pressure available =100 Pa) 3Φ
Lighting
Office, Toliet, Entrance to the plant
Water Treatment Plant
Emergency Lighting
Socket Supply
WP1, Work station Socket
UPS Work station Socket
Socket general uses
Refrigerator
Office coffee maker
IT Supply
Electronic planels supply and UPS

Port Pumping Plant


EQUIPMENT
Lighting
Entrance to the plant
Water Treatment Plant
Emergency Lighting
Socket Supply
WP1, Work station Socket
UPS Work station Socket
Socket general uses
IT Supply
Electronic planels supply and UPS
n Building
QTY POWER (W) TOTAL POWER (W) Total kW
6.24
2 120 240
2 3000 6000
142.124
1 68000 68000
1 68000 68000
2 3000 6000
2 29 58
1 22 22
1 44 44
5.108
83 32 2656
52 46 2392
24 2.5 60
35.45
50 200 10000
25 200 5000
70 200 14000
1 1050 1050
2 250 500
2 1200 2400
2 1250 2500
8.50
1 8500 8500
TOTAL BUILDING 197.42
pose Building
QTY POWER (W) TOTAL POWER (W) Total kW
21.00
7 3000 21000
m2 Rate (W/m2) 31.88
53.14 600 31884
89.44
1 22700 22700
2 19700 39400
1 13600 13600
2 3000 6000
1 7500 7500
3 29 87
1 22 22
3 44 132
5.56
103 32 3296
30 46 1380
32 2.5 80
8 100 800
17.25
10 200 2000
5 200 1000
39 200 7800
1 1050 1050
2 250 500
2 1200 2400
2 1250 2500
4.50
1 4500 4500
TOTAL BUILDING 169.63

Restroom
QTY POWER (W) TOTAL POWER (W) Total kW
9.00
3 3000 9000
1.00
5 200 1000
0.30
9 32 288
3 2.5 7.5
TOTAL BUILDING 10.30

op-Warehouse
QTY POWER (W) TOTAL POWER (W) Total kW
24.00
3 3000 9000
1 15000 15000
128.55
4 22700 90800
2 3000 6000
4 6000 24000
1 7500 7500
4 29 116
4 22 88
1 44 44
7.17
82 32 2624
38 46 1748
27 100 2700
39 2.5 97.5
16.20
2 200 400
1 200 200
63 200 12600
2 250 500
2 1250 2500
3.50
1 3500 3500
TOTAL BUILDING 179.42
Access Control
QTY POWER (W) TOTAL POWER (W) Total kW
26.16
2 3000 6000
4 5000 20000
4 29 116
1 44 44
7.17
82 32 2624
38 46 1748
27 100 2700
39 2.5 97.5
21.05
2 200 400
1 200 200
70 200 14000
2 250 500
2 1200 2400
1 1050 1050
2 1250 2500
4.50
1 4500 4500
TOTAL BUILDING 58.88

eatment Plant

QTY POWER (W) TOTAL POWER (W) Total kW


3.00
1 3000 3000
5.61
1 5000 5000
2 29 58
1 550 550
3.99
12 32 384
36 100 3600
4 2.5 10
7.20
2 200 400
1 200 200
18 200 3600
2 250 500
2 1250 2500
2.50
1 2500 2500
TOTAL BUILDING 22.30
ping Plant
QTY POWER (W) TOTAL POWER (W) Total kW
0.89
2 42 84
8 100 800
2 2.5 5
2.20
2 200 400
1 200 200
8 200 1600
2.50
1 2500 2500
TOTAL BUILDING 5.59
Cable XLPE Cu 1000V suitable for direct buiral
(Resistant to humidity, solar radiation and high temperatures)

CABLE Cross section External Diameter


nº Wires
(AWG or Kcmil) (mm2) (mm)

14 2.08 19 4.84
12 3.31 19 5.34
10 5.261 19 5.93
8 8.367 19 7.68
6 13.3 19 8.62
4 21.15 19 9.81
2 33.62 19 11.31
1 42.4 19 12.96
1/0 53.49 19 13.97
2/0 67.44 19 15.09
3/0 85.02 19 16.35
4/0 107.2 19 17.77
250 127 37 20.2
300 152 37 21.58
350 177 37 22.88
400 203 37 24.07
500 253 37 26.24
600 304 61 29.04
750 380 61 31.71
1000 507 61 35.62

Cable XLPE Cu 0,6/1 kV suitable for direct buiral


RV-K / FXV - ESTANDAR DE PVC 0,6/1 kV (UNE 21123,2/IEC 60502-1)

Número de Diámetro nominal Peso nominal Radio mínimo de


conductores x
sección 1x(mm2) exterior (mm) (Kg/km) curvatura (mm)

1.5 5.7 45 25
2.5 6.1 60 25
4 6.7 75 30
6 7.2 95 30
10 8.2 140 35
16 9.2 195 40
25 10.8 285 45
35 11.9 380 50
50 13.5 520 55
70 15.6 715 65
95 17.4 925 70
120 19.4 1165 80
150 21.4 1440 90
185 23.3 1740 95
240 26.6 2295 135
300 30.2 2895 155
400 34.8 3930 175
500 39.1 5015 200
630 43.7 6585 220

(1) Instalación en bandeja al aire (40ºC).


(2) Instalación enterrada, durectamente o bajo tubo (25ºC) con resistividad termica del terreno estandar de

Diám. nominal DN Diám. Ext. Medio Diám. Inter. Medio


(mm) (mm) (mm)

40 40,0-40,8 31
50 50,0-51,0 40
63 63,0-64,2 50
90 90,0-91,7 75
Rollos 110 110,0-112,0 94
125 125,0-127,3 108
160 160,0-162,9 134
200 200,0-203,6 174
250 250,0-254,5 222
Barra 315 - 272
atures)

Ampacity
(A)

25
30
40
55
75
95
130
150
170
195
225
260
290
320
350
380
430
475
535
615

for direct buiral En la norma francesa


UNE 21123,2/IEC 60502-1) reglamento portug

Allowable Caída de
Allowable current tensión Nº
current (directly Conductores
buried) (1) (directly cos0=0,8 Verticales
buried) (2) (V/A·Km)
21 21 27.31 1
30 27.5 14.24 2
40 35 8.873 3
52 44 5.95 4
72 58 3.484 5
97 75 2.24 6
122 96 1.476
153 117 1.073
188 138 0.773
243 170 0.568
298 202 0.449
350 230 0.368
401 260 0.311
460 291 0.27
545 336 0.223
630 380 0.193
749 430 0.164
861 483 0.146
990 552 0.128

mica del terreno estandar de 2,5k.m/W.

CALIBRES DE PROTECCIONES

MCCB ACB

16 800
25 1000
32 1250
40 1600
50 2000
63 2500
80 3200
100 4000
125 5000
160 6300
200
250
400
630
800
1000
1250
1600
2000
2500
3200
4000
5000
6300
En la norma francesa NF C 15-100 (tablas 52P y 52Q) y en el
reglamento portugués (tabla 52-E3, ver a continuación)
Nº Conductore horizontales

1 2 3 4 5 6

0.95 - - - - -
0.92 0.87 0.84 0.81 0.8 0.79
0.85 0.81 0.78 0.76 0.75 0.74
0.82 0.78 0.74 0.73 0.72 0.72
0.8 0.76 0.72 0.71 0.7 0.7
0.79 0.75 0.71 0.7 0.69 0.68

You might also like