Compact NSX - 630A - LV430775 - 160A

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

Product datasheet

Specifications

circuit breaker Compact NSX160N,


50 kA at 415 VAC, Micrologic 2.2
trip unit 160 A, 3 poles 3d
LV430775

Discontinued on: 31 December 2022

To be discontinued

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range ComPact

Product name ComPact NSX

Range of product ComPact NSX100...250

Device short name NSX160N

Product or component type Circuit breaker

Device application Distribution

Number of poles 3P

Protected poles description 3t

[In] rated current 160 A at 40 °C

[Ue] rated operational voltage 690 V AC 50/60 Hz

Network type AC

Network frequency 50/60 Hz

Suitability for isolation Yes conforming to EN/IEC 60947-2

Utilisation category Category A

[Icu] rated ultimate short-circuit 10 kA at 600 V AC 50/60 Hz conforming to UL 508


breaking capacity 85 kA at 240 V AC 50/60 Hz conforming to UL 508
10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 480 V AC 50/60 Hz conforming to UL 508
36 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
90 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2

Performance level N 50 kA 415 V AC

Trip unit name MicroLogic 2.2

Trip unit technology Electronic

Trip unit protection functions LSoI

Control type Toggle

Circuit breaker mounting mode Fixed

Complementary
[Ui] rated insulation voltage 800 V AC 50/60 Hz

11 May, 2023 1
[Uimp] rated impulse withstand 8 kV
voltage

[Ics] rated service short-circuit 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
breaking capacity 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
36 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
90 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2

Mechanical durability 40000 cycles

Electrical durability 7500 cycles at 690 V In


15000 cycles at 690 V In/2
20000 cycles at 440 V In
40000 cycles at 440 V In/2

Mounting support Backplate

Upside connection Front

Downside connection Front

Connection pitch 35 mm

Protection type L : for overload protection (long time)


So : for short time short-circuit protection with fixed delay
I : for instantaneous short-circuit protection

Trip unit rating 160 A at 40 °C

Long-time pick-up adjustment Adjustable 9 settings


type Ir (thermal protection)

[Ir] long-time protection pick-up 63...160 A


adjustment range

Long-time protection delay Fixed


adjustment type tr

[Tr] long-time protection delay 11 s at 7.2 x Ir


adjustment range 16 s at 6 x Ir
400 s at 1.5 x Ir

Thermal memory 20 minutes before and after tripping

Short-time protection pick-up Adjustable 9 settings


adjustment type Isd

[Isd] Short-time protection pick- 1.5...10 x Ir


up adjustment range

Short-time protection delay Fixed


adjustment type tsd

Instantaneous protection pick- Fixed


up adjustment type Ii

[Ii] instantaneous protection 2400 A


pick-up adjustment range

Earth-leakage protection Without

Zone selective interlocking ZSI Without

Number of slots for electrical 5 slot(s)


auxiliaries

Local signalling Flashing LED (green) for ready to operate


LED 105 % Ir (red) for overload
LED 90 % Ir (orange) for overload

Width (W) 105 mm

Height (H) 161 mm

Depth (D) 86 mm

Net weight 2.2 kg

Environment
Standards EN/IEC 60947

Product certifications CCC

2
11 May, 2023
EAC
Marine

Overvoltage category Class II

Electrical shock protection Class II


class

Pollution degree 3 conforming to IEC 60664-1

IP degree of protection IP40 conforming to IEC 60529

IK degree of protection IK07 conforming to IEC 62262

Ambient air temperature for -25…70 °C


operation

Ambient air temperature for -50…85 °C


storage

Relative humidity 0…95 %

Operating altitude 0...2000 m without derating


2000 m...5000 m with derating

Packing Units
Unit Type of Package 1 PCE

Number of Units in Package 1 1

Package 1 Height 14.4 cm

Package 1 Width 11.6 cm

Package 1 Length 19.2 cm

Package 1 Weight 1.874 kg

Unit Type of Package 2 S04

Number of Units in Package 2 12

Package 2 Height 30.0 cm

Package 2 Width 40.0 cm

Package 2 Length 60.0 cm

Package 2 Weight 23.254 kg

Offer Sustainability
Sustainable offer status Green Premium product

REACh Regulation REACh Declaration

EU RoHS Directive Compliant


EU RoHS Declaration

Mercury free Yes

China RoHS Regulation China RoHS declaration


Product out of China RoHS scope. Substance declaration for your information

RoHS exemption information Yes

Environmental Disclosure Product Environmental Profile

Circularity Profile End of Life Information

WEEE The product must be disposed on European Union markets following specific waste collection and
never end up in rubbish bins

Contractual warranty
Warranty 18 months

Recommended replacement(s)

11 May, 2023 3
LV430775 is replaced by:

Circuit breaker, ComPacT NSX160N, 50kA/415VAC, 3 poles, MicroLogic 2.2 trip unit
1x 160A
C16N32D160

4
11 May, 2023