Fire Flow Requirement
Fire Flow Requirement
In accordance with NFPA 1, 2015 with an example calculation for the ISO
method
Mehboob Shaikh
Its is used to calculate available fire department fire flow for fire-
fighting purposes and does not take into account fire suppression
systems or hose stream requirements required by some codes and
standards
It should not be confused with Sprinkler Demand of the system both are
different or simply its not the volume of water required for the sprinkler
System Mechsoft Engg. Design and Consultancy 2
Fire Flow Calculations
What…?
Why…?
As defined in IFC Section B102
“The flow rate of a water supply, measured at 20 pounds per square inch (psi) (138 kPa) residual pressure, that is available
for fire fighting”
Shouldn’t be confused with water needed for manual fire fighting(Hose streams) while the
sprinkler system is still in operation inside the building
Fire flow encompasses the water demand for the entire building on the fire solely for
EXTERIOR FIRE FIGHTING
Methods
Where,
The AHJ is permitted to use discretion in reducing the required fire flow in rural areas with
isolated buildings where development of the full fire flow is impractical. It is important to
note that reducing the fire flow is at the sole discretion of the AHJ. Before reducing the fire
flow, the AHJ should determine if the site conditions warrant a reduction and if additional
protection methods, such as fire sprinkler protection, are necessary to justify a reduction
while maintaining a reasonable level of property and life safety protection
18.4.4.1 – General
• The fire flow area shall be the total floor area of all floor levels of a
building except as modified in 18.4.4.1.1.
18.4.4.1.1- The fire flow area of a building constructed of Type I (443),
Type I (332), and Type II (222) construction shall be the area of the
three largest successive floors
18.4.5.1 – One & Two Family dwelling units- Less than 5000 Sq ft.
• 18.4.5.1.1 - The minimum fire flow and flow duration requirements for one- and
two-family dwellings having a fire flow area that does not exceed 5000 ft2 (334.5
m2) shall be 1000 gpm (3785 L/min) for 1 hour.
18.4.5.2 – One & Two Family dwelling units- More than 5000 Sq ft.
• 18.4.5.2.1 - The minimum fire flow and flow duration for buildings other than one- and two-
family dwellings shall be as specified in Table 18.4.5.2.1
• 18.4.5.2.4 – Required Fire flow for one and two family dwelling protected by an approved
automatic sprinkler System shall not exceed 2000 GPM for 1 Hour
For a building with an approved fire sprinkler systems, the fire flow
demand and the fire sprinkler systems demand shall not be required to
be added together. The water supply shall be capable of delivering the
larger of the individual demands.
The calculated fire flow of 875 gpm (3312 L/min) is less than
1000 gpm (3785 L/min), the minimum permitted
by 18.4.5.2.1.
Mechsoft Engg. Design and Consultancy 24
Thank You