Micronet TMR 1 en
Micronet TMR 1 en
(Revision F)
Original Instructions
MicroNet TMR®
Digital Control
The engine, turbine, or other type of prime mover should be equipped with an
overspeed shutdown device to protect against runaway or damage to the prime
mover with possible personal injury, loss of life, or property damage.
The overspeed shutdown device must be totally independent of the prime mover
control system. An overtemperature or overpressure shutdown device may also
be needed for safety, as appropriate.
Read this entire manual and all other publications pertaining to the work to be performed before
installing, operating, or servicing this equipment. Practice all plant and safety instructions and
precautions. Failure to follow instructions can cause personal injury and/or property damage.
This publication may have been revised or updated since this copy was produced. To verify that
you have the latest revision, be sure to check the Woodward website:
www.woodward.com/pubs/current.pdf
The revision level is shown at the bottom of the front cover after the publication number. The latest
version of most publications is available at:
www.woodward.com/publications
If your publication is not there, please contact your customer service representative to get the
latest copy.
Any unauthorized modifications to or use of this equipment outside its specified mechanical,
electrical, or other operating limits may cause personal injury and/or property damage, including
damage to the equipment. Any such unauthorized modifications: (i) constitute "misuse" and/or
"negligence" within the meaning of the product warranty thereby excluding warranty coverage
for any resulting damage, and (ii) invalidate product certifications or listings.
Woodward Governor Company reserves the right to update any portion of this publication at any time. Information
provided by Woodward Governor Company is believed to be correct and reliable. However, no responsibility is assumed
by Woodward Governor Company unless otherwise expressly undertaken.
© Woodward 2004
All Rights Reserved
Manual 26167V1 MicroNet TMR
Contents
IOLOCK. When a CPU or I/O module fails, watchdog logic drives it into an
IOLOCK condition where all output circuits and signals are driven to a known
de-energized state as described below. The System MUST be designed such that
IOLOCK and power OFF states will result in a SAFE condition of the controlled
device.
CPU and I/O module failures will drive the module into an IOLOCK state.
CPU failure will assert an IOLOCK signal to all modules and expansion
racks to drive them into an IOLOCK state.
Discrete outputs / relay drivers will be non-active and de-energized.
Analog and actuator outputs will be non-active and de-energized with zero
voltage or zero current.
NOTE: Additional watchdog details and any exceptions to these failure states
are specified in the related CPU or I/O module section of the manual.
Woodward i
MicroNet TMR Manual 26167V1
Contents
ii Woodward
Manual 26167V1 MicroNet TMR
Contents
Woodward iii
MicroNet TMR Manual 26167V1
iv Woodward
Manual 26167V1 MicroNet TMR
Woodward v
MicroNet TMR Manual 26167V1
vi Woodward
Manual 26167V1 MicroNet TMR
Woodward vii
MicroNet TMR Manual 26167V1
Regulatory Compliance
European Compliance for CE Marking:
These listings are limited only to those units bearing the CE Marking.
EMC Directive: Declared to 89/336/EEC COUNCIL DIRECTIVE of 03
May 1989 on the approximation of the laws of the
Member States relating to electromagnetic compatibility.
viii Woodward
Manual 26167V1 MicroNet TMR
Woodward ix
MicroNet TMR Manual 26167V1
2. Avoid the build-up of static electricity on your body by not wearing clothing
made of synthetic materials. Wear cotton or cotton-blend materials as much
as possible because these do not store static electric charges as much as
synthetics.
4. Do not remove the printed circuit board (PCB) from the control cabinet
unless absolutely necessary. If you must remove the PCB from the control
cabinet, follow these precautions:
When replacing a PCB, keep the new PCB in the plastic antistatic
protective bag it comes in until you are ready to install it. Immediately
after removing the old PCB from the control cabinet, place it in the
antistatic protective bag.
x Woodward
Manual 26167V1 MicroNet TMR
Chapter 1.
General Information
1.1—Introduction
The MicroNet™ control is a 32-bit microprocessor-based digital controller that is
programmable for many types of applications in the control of:
Gas Turbines
Steam Turbines
Hydro Turbines
Diesel Engines
Gas Engines
The MicroNet platform provides a flexible system to control any prime mover and
its associated processes such as high speed control functions, system
sequencing, auxiliary system control, surge control, monitoring and alarming, and
station control. The MicroNet platform is available in simplex, redundant, and
triple modular redundant (TMR) configurations. This manual covers only TMR
based control configurations. Please refer to MicroNet Plus manual 26166 for
simplex and redundant based control configurations using the MicroNet Plus
CPU. Please refer to manual 26336 for information on VxWorks Operating
System tools used with the TMR5200 CPU module.
Synchronized inputs and outputs (I/O) are available for key control signals while
distributed I/O can be used for other less critical parameters.
Woodward 1
MicroNet TMR Manual 26167V1
The MicroNet TMR control may be expanded to a multi-chassis system using the
Plus8 or Plus14 chassis options. For field upgrades, the expansion racks may
also be the older Simplex6 or Simplex12 chassis. Each expansion chassis has
dedicated power supply, control, and I/O sections located in a single chassis.
The expansion power supply architecture supports simplex or redundant power
supplies.
2 Woodward
Manual 26167V1 MicroNet TMR
Chapter 2.
MicroNet™ TMR Systems
2.1—MicroNet TMR
The TMR Main chassis provides slots for kernel power supplies, CPU’s, and twelve
I/O Modules. This is the basis of the TMR systems whether using the TMR5200
processor or the TMR040 processor. NOTE: Kernel PS modules must be matched
to the type of CPU being used. The system may be expanded to 3 I/O chassis
using RTN networks with the TMR5200 processors. With the RTN each CPU has
access to the I/O so I/O in the expansion chassis is considered Shared I/O.
With the TMR040 processors, Transceiver modules and copper or fiber cables are
used to connect to multiple chassis to accommodate additional system I/O
requirements. In this case, I/O is dedicated to a specific CPU.
MicroNet TMR
Woodward 3
MicroNet TMR Manual 26167V1
4 Woodward
Manual 26167V1 MicroNet TMR
In the TMR Main Chassis, three isolated kernel sections (A, B & C) each house a
Kernel Power Supply module, CPU module, and have 4 VME slots for I/O
modules. A single motherboard supplies nine electrically isolated data paths.
Each CPU has a data path to its VME modules and two separate data paths, one
to each of the other CPU modules. There is a total of six paths between CPUs
allowing for redundancy and error checking.
Each CPU module runs the identical software application as the other two. All
inputs from each kernel are distributed to the other two kernels. Each CPU then
compares the value it read, with the value the other two CPUs read, before
outputting a signal to the application software. Depending on the configuration, a
total of nine values for the same input parameter could be used in the voting logic
to provide the best signal to the application software. Even if a data value has
been corrupted along any one of the data paths shown in Figure 2-1, all CPUs
use the same correct data for their application calculations. All CPUs use the
same voted input signals in the same application calculations to generate the
same outputs.
All output values are exchanged between kernels, the results are voted and the
appropriate value is output from each kernel. Since the system can handle
significant single errors, even multiple errors may not shutdown a kernel section.
In the event of consistent errors from one of the kernel section, an alarm will be
annunciated and that particular kernel will be shut down.
Woodward 5
MicroNet TMR Manual 26167V1
All analog inputs are connected to the control via a TMR FTM. An input’s
termination module is used to terminate customer control wiring and distribute
each input signal to all three kernels. After the control’s kernels double exchange
their input values and vote out any erroneous values, the Application Software
Redundancy Manager then compares each kernel’s voted result to select a value
to be used within the application logic. Figure 2-2 is a graphical view of a
control’s input architecture. Table 2-1 displays the redundancy manager’s input
selection logic for each possible input condition.
An analog input signal is determined to be faulty when the I/O Module or I/O
Channel fails or when it is below its “Fail Low Value” setting, or above its “Fail
High Value” setting. For a 4–20 mA input, these high and low failure level
settings typically correspond to 2 mA and 22 mA respectively. If an input is
determined to be failed, that input is removed from the control’s voting logic.
Input deviation alarms are used to annunciate if any of the input channels or
input legs are sensing a value that is different than the voted-good value used by
the application. If an input channel’s sensed value deviates from the voted-good
value, by a greater margin than its “Max Deviation” setting, an input channel
alarm will be issued. This type of annunciation can be used to indicate when an
input channel, or system transducer is going out of calibration. Max Deviation
settings are typically defaulted to 1% (deviation range = 0.1 to 10%) of the
configured input range. If a deviation alarm condition occurs, the alarmed input is
not removed from the control’s voting logic, and still can be used to control with,
in case all other channels fail.
6 Woodward
Manual 26167V1 MicroNet TMR
All discrete inputs are connected to the control via discrete termination modules
(DTMs). A DTM is used to terminate customer control wiring and distribute each
input signal to all three kernels. After the control’s kernels double exchange their
input values and vote out any erroneous inputs, the Application Software
Redundancy Manager then compares each kernel’s voted result to select a value
to be used within the application logic. Figure 2-3 is a graphical view of the
control’s discrete input architecture.
Woodward 7
MicroNet TMR Manual 26167V1
A discrete input signal is determined to be faulty when the I/O Module or I/O
Channel fails or when it is determined to be different then the voted-good value
used by the application. If an input is determined to be faulty, the input is
removed from the control’s voting logic and an input channel alarm is issued.
Once the input fault is corrected the alarm condition can be reset by issuing a
control “Reset” command.
Precision resistors are used in each channel’s readback circuitry to measure and
verify the health of each output “leg”. If a fault condition is detected, the faulty
output leg is disabled, and the Redundancy Manager redistributes the output
signal to the remaining legs. In a case where two failures are experienced at the
same time within different legs, the single good channel (leg) will drive the entire
output. Figure 2-4 shows a Fault Tolerant Analog Output’s architecture. The
TMR Field Termination Module (FTM) combines each analog output signal from
all three kernels into one signal at the FTM’s terminal blocks.
Typically, an output is considered failed, and an alarm issued, when the I/O
Module or I/O Channel fails or if a channel’s combined output or any leg of the
output measures a difference of more than 10% from the output demand.
With this output architecture, any single output driver failure results in the output
signal only stepping to 66.66% of its original value. The time between when a
failure is sensed and when the control corrects for it by redistributing current
through the other drivers depends on the application software scheduling and the
I/O module response but can be as fast as 5 ms.
Upon the correction of an output failure, and a “Control Reset” command, each
failed output performs a continuity check though the its external load before
current is again redistributed evenly between all output drivers. This continuity
check outputs a small amount of current through the failed driver’s output load
and compares that value to the readback value.
8 Woodward
Manual 26167V1 MicroNet TMR
Actuator Outputs
Each actuator output can withstand up to two failures with no loss of output
functionality. Any leg of an output channel can drive an output’s full current signal
(4–20 mA or 20–160 mA). Each CPU generates an analog output command
using a Redundancy manager and known good output channels. The analog
output commands are voted between the CPUs and the voted value is sent to the
respective output channel.
Precision resistors are used in each channel’s readback circuitry to measure and
verify the health of each output “leg”. If a fault condition is detected, the faulty
output leg is disabled, and the Redundancy Manager redistributes the output
signal to the remaining legs. In a case where two failures are experienced at the
same time within different legs, the lone good channel (leg) will drive the entire
output. Figures 2-6 and 2-7 show a Fault Tolerant Actuator Output’s architecture.
The TMR Field Termination Module (FTM) combines each actuator output signal
from all three kernels into one signal at the FTM’s terminal blocks.
An output is considered failed, and an alarm issued, when the I/O Module or I/O
Channel fails or if a channel’s combined output or any leg of the output measures
a difference of more than 10% from the output demand.
Woodward 9
MicroNet TMR Manual 26167V1
Actuator outputs are treated the same way as the other analog outputs, with the
exception of a an added precision resistor in the actuator output’s return path.
This resistor is used to measure and detect ground loops and coil shortages that
are possible when interfacing to an actuator. If a single coil actuator is being
driven, the dual coil terminal blocks are jumpered (wired) to the single coil
terminal blocks and the redundancy manager shares the current equally between
all three kernels. In the event of a fault, the Redundancy Manager will redistribute
the load.
With this output architecture, any single output driver failure results in the output
signal only stepping to 66.66% of its original value (possibly 50% for dual coil
applications). The time between when a failure is sensed and when the control
corrects for it by redistributing current through the other drivers depends on the
application software scheduling and the I/O module response but can be as fast
as 5 ms.
Upon the correction of an output failure, and a “Control Reset” command, each
failed output performs a continuity check though the actuator before current is
again redistributed evenly between all output drivers. This continuity check
outputs a small amount of current through the failed driver’s output load and
compares that value to the readback value.
10 Woodward
Manual 26167V1 MicroNet TMR
Relay Outputs
A six relay configuration is used to form each fault tolerant relay output. When a
relay output is closed, the contacts of all six relays are closed. Because of the
series-parallel configuration that the relays are in, the failure of any individual
relay will not cause the output to be open. This series-parallel configuration also
allows any single relay of the six relay configuration to be removed and replaced
“on-line” with no affect on the state of the fault tolerant relay output.
When a relay output is open, the contacts of all six relays are open. Because of
the series-parallel configuration that the relays are in, the failure or removal of
any one relay will not cause the output to be closed. The relay output would
continue to be open.
Since this control’s fault tolerant architecture can tolerate a single fault, it is
possible for this fault to go undetected. This is called a latent fault. If a second
fault occurs while a latent fault exists, the state of the fault tolerant relay output
may be affected, possibly resulting in a shutdown condition. This is why it is
important to detect and annunciate latent faults in a fault tolerant system.
Woodward 11
MicroNet TMR Manual 26167V1
Latent fault detection is provided with this control to detect any relay related
failure without effecting the state of the overall relay output. Each individual relay
output can be configured to use or not use latent fault detection. A latent fault
detection test is performed periodically or on command. The period of time
between tests can be set from 1 to 3000 hours.
A relay output is tested by cycling the output’s individual relays closed then open
(or vice-versa depending on the output state), to ensure that they are in the
correct state, and that they can change state. Position readback circuitry allows
the state of each relay contact to be detected. Any failures are annunciated, and
further testing is disabled without affecting the state of the relay output contact or
control operation.
Each fault tolerant relay configuration consists of 6 relays, driven by two discrete
outputs from each kernel (as shown in Figure 2-7). The relays are configured in
three legs of two relays each. Customer circuit power is connected to one side of
the resulting configuration, and customer load to the other side. Field selectable
jumpers, located on system FTMs, are provided to allow each output’s latent fault
detection logic to be compatible with the circuit being interfaced to. Latent fault
detection is used to monitor the actual contact positions of each of the six relays,
and to momentarily change states of each relay one at a time. This verifies each
relay’s “normally open” or “normally closed” contacts.
DTM
PW CIRCUIT
POWER
DISCRETE A1 B2 C2
MOD−A
DISCRETE
MOD−B B1 C1 A2
NO
DISCRETE
MOD−C LOAD
CM
A1 A2 B1 B2 C1 C2
A A B B C C
855−663
02−12−31
Latent fault detection (LFD) is not usable with all applications or circuits. The
control’s LFD logic can only work with circuits using voltages between 18–32
Vdc, 100–150 Vdc, or 88–132 Vac. For latent fault detection to work, a small
leakage current is passed through the circuit’s load. Depending on the size of the
load, the leakage current may be enough to cause a load to be on or active,
when a relay contact is open. In this case, the individual relay’s latent fault
detection logic may be disabled, eliminating the leakage current, or a shunt
resister can be used across the load to reduce the leakage current.
12 Woodward
Manual 26167V1 MicroNet TMR
Each I/O module has connectors on the faceplate. For analog and discrete I/O,
cables connect the module to a Field Terminal module (FTM). The FTM is used to
connect to the field wiring. For communication modules, FTMs are not used.
Cables are connected directly to the faceplate of the communications module. The
following diagram shows the flow of analog and discrete inputs from the field to the
application.
Woodward 13
MicroNet TMR Manual 26167V1
The second level is wiring two external input devices to two separate I/O modules.
See Figure 2-11. In the event of a failure in one of the sensors, connections,
cables, FTMs, or I/ O modules, a valid input is still available.
The value of redundancy is dependent on the ability of the application to detect the
failure. For analog and actuator outputs, current and/or voltage readback is
provided. For discrete outputs, fault detection requires sensing the relay contact
state.
14 Woodward
Manual 26167V1 MicroNet TMR
TMR5200
Load and start the application on each CPU using AppManager.
If the Control is given a CTRL_ID in the SYS_INFO block of the application
software, AppManager can interface with the three CPUs as one system.
AppManager can be used to start the three CPUs together.
Once an application has started, Auto-start will be set. The CPU will
automatically start on CPU initialization (whether from a power up or from a
reset).
TMR040
Load the application on each CPU using a PCMCIA card or Ethernet module.
The application will start once it has been loaded.
After an application has been loaded, the CPU will automatically start on CPU
initialization when the Reset switch is toggled.
2.3—Module Replacement
TMR systems are designed to allow replacement of modules while running (hot-
swap). This is a key to maintaining the high level of availability for critical
applications. The hardware is fully capable of supporting hot-swap but care must
be taken in the application software design to ensure that a module hot-swap does
not adversely affect the application.
Chapter 4 contains additional details for power supply installation and replacement.
Note that power must be removed from the power supply input before a module is
removed or inserted.
Woodward 15
MicroNet TMR Manual 26167V1
ALM: This output displays the status of the Kernels alarms. A true
indicates that the Kernel has an alarm.
ALM_NO: This output displays the Kernels Alarm number. See the
GAP help manual for a list of valid alarms.
PS1_FAIL: This output field goes true when a fault on the MAIN
TMR #1 Power Supply is detected.
PS2_FAIL: This output field goes true when a fault on the MAIN
TMR #2 Power Supply is detected.
16 Woodward
Manual 26167V1 MicroNet TMR
Example of MicroNet TMR040 fault information available from the SYS_INFO
block.
SYS_ALM: The System Alarm Boolean will be set true any time
the operating system detects an alarm. This should be used in your
application for alarm indications.
SYS_FLT: The System Fault Boolean will be set true any time the
operating system detects a critical fault. It will cause an I/O lock to
be asserted.
PS_1_FLT: The Power Supply 1 Boolean will be set true when any
of the outputs from Power Supply 1 fail.
PS_2_FLT: The Power Supply 2 Boolean will be set true when any
of the outputs from Power Supply 2 fail.
FAN_ALM: The Aux. Fans Are Running Boolean will be set true
when the chassis exceeds a preset temperature and the second rack
of fans are on.
A_FAULT: The CPU A Fault Boolean will be set true when CPU
A is not in sync. In a simplex system, A_FAULT, B_FAULT, and
C_FAULT are false.
B_FAULT: The CPU B Fault Boolean will be set true when CPU
B is not in sync. In a simplex system, A_FAULT, B_FAULT, and
C_FAULT are false.
C_FAULT: The CPU C Fault Boolean will be set true when CPU
C is not in sync. In a simplex system, A_FAULT, B_FAULT, and
C_FAULT are false.
Woodward 17
MicroNet TMR Manual 26167V1
Chapter 3.
Chassis Configurations
If an I/O module slot is not occupied, it must be filled with a blanking plate
(3799-301) to maintain proper cooling flow through the chassis.
3.1.1—Specification
The MicroNet™ control is designed around a modular six slot chassis (block).
Each block consists of a premolded cage with a fan for cooling and a
temperature switch for high temperature detection. The chassis are cooled by
forced air, and either a module or a module blank must be installed in every slot
to maintain correct air flow. The fans run whenever power is applied to the
system.
18 Woodward
Manual 26167V1 MicroNet TMR
From a module connector standpoint, any I/O module can be installed in any of
the slots designated for I/O modules. However, when the application software is
designed, each module will be assigned to a specific slot and thereafter, the
software will expect that specific I/O module to always be in its designated slot.
Woodward 19
MicroNet TMR Manual 26167V1
3.1.2—Installation
Figure 3-3 shows the mounting template and fasteners to bulkhead mount the
chassis. Rack mounting is not recommended. For proper airflow, the installation
should allow a 3” air gap above and below the chassis.
20 Woodward
Manual 26167V1 MicroNet TMR
The MicroNet Plus 8-slot chassis offers redundant RTN capability and more I/O
slots than the MicroNet 6, as well as improvements in airflow and overall system
reliability.
Features:
A total of 8 RTN and I/O slots are available for use
A new 2-slot wide, redundant, load sharing power supply is used
Redundant Smart fans are used for early notification of fan-failure
Chassis temperature switches exist on the motherboard and trip at
+65 °C
Redundant, hot-swappable RTN s are supported
3.2.1—Specification
The MicroNet is designed around a modular 6-slot chassis (block). Each block
consists of a premolded cage with a fan for cooling and a temperature switch for
high temperature detection. The chassis are cooled by forced air, and either a
module or a module blank must be installed in every slot to maintain correct air
flow. The fans run whenever power is applied to the system.
Woodward 21
MicroNet TMR Manual 26167V1
The MicroNet Plus 8-slot chassis is composed of two blocks with a motherboard
inserted in the back of the assembly to make connections between the fans,
switches, power supplies, and control modules. See Figure 3-5. The modules
use the VERSAmodule Eurocard (VME) bus standard for connector specification
and data transfer. Slot-to-slot logic and power connections are made through an
etched-circuit motherboard. I/O connections are made through cables from the
front of the modules to field termination modules (FTM’s) the cabinet.
From a module connector standpoint, any I/O module can be installed in any of
the slots designated for I/O modules. However, when the application software is
designed, each module will be assigned to a specific slot and thereafter, the
software will expect that specific I/O module to always be in its designated slot.
For simplex systems, RTN slot A8 can also be used as an I/O module slot.
Live Insertion and removal is supported for field repairability.
RTNs are located under different fan sets to improve reliability, airflow, and
temperature performance.
RTN slots use VME-64 connectors on the RTN module slots for improved
RTN HotSwap capabilities.
22 Woodward
Manual 26167V1 MicroNet TMR
Power supplies are located under different fan sets to improve reliability,
airflow, and temperature performance.
Three different 2-slot wide power supplies are available for use: a low
voltage (24 Vdc input), a high voltage (120 Vac/dc input), and a high voltage
220 Vac input version. Refer to the power-supply section for additional
information.
Woodward 23
Micro
oNet TMR Manual 26167V1
3.2.2
2—Installattion
Figure
e 3-7 shows the
t mounting template and d fasteners to bulkhead mo ount the
chasssis. Rack mou unting is not recommended
d. For proper airflow, the in
nstallation
shouldd allow a 3” air
a gap above and below thhe chassis.
Figure 3-7—
—Mounting Te
emplate of MiccroNet Plus 8-Slot
8 I/O Cha
assis
24 Woodward
Manual 26167V1 MicroNet TMR
The MicroNet Plus 14-slot chassis offers redundant RTN capability and more I/O
slots, as well as improvements in airflow and overall system reliability.
Features:
A total of (14) RTN and I/O slots are available for use
A new 2-slot wide, redundant, load sharing power supply is used
Redundant Smart fans are used for early notification of fan failure
Chassis temperature switches exist on the motherboard and trip at +65 °C
Redundant, hot-swappable RTNs are supported
3.3.1—Specification
The MicroNet is designed around a modular 6-slot chassis (block). Each block
consists of a premolded cage with a fan for cooling and a temperature switch for
high temperature detection. The chassis are cooled by forced air, and either a
module or a module blank must be installed in every slot to maintain correct air
flow. The fans run whenever power is applied to the system.
Woodward 25
MicroNet TMR Manual 26167V1
The MicroNet Plus chassis is composed of three blocks with a motherboard
inserted in the back of the assembly to make connections between the fans,
switches, power supplies, and control modules. See Figure 3-8. The modules
use the VERSAmodule Eurocard (VME) bus standard for connector specification
and data transfer. Slot-to-slot logic and power connections are made through an
etched-circuit motherboard. I/O connections are made through cables from the
front of the modules to field termination modules (FTM’s) the cabinet.
From a module connector standpoint, any I/O module can be installed in any of
the slots designated for I/O modules. However, when the application software is
designed, each module will be assigned to a specific slot and thereafter, the
software will expect that specific I/O module to always be in its designated slot.
For simplex systems, RTN slot A14 can also be used as an I/O module slot.
Live Insertion and removal is supported for field repairability.
RTNs are located under different fan sets to improve reliability, airflow, and
temperature performance.
RTN slots use VME-64 connectors on the RTN module slots for improved
RTN HotSwap capabilities.
26 Woodward
Manual 26167V1 MicroNet TMR
Power supplies are located under different fan sets to improve reliability,
airflow, and temperature performance.
Three different 2-slot wide power supplies are available for use: a low
voltage (24 Vdc input), a high voltage (120 Vac/dc input), and a high voltage
220 Vac input version. Refer to the power-supply section for additional
information.
Woodward 27
MicroNet TMR Manual 26167V1
28 Woodward
Manual 26
6167V1 M
MicroNet TMR
3.3.2—Installation
Fig
gure 3-11 sho
ows the moun nting template
e and fastene
ers to bulkhea ad mount the
ch
hassis. Rack mounting
m is not recommen nded. For propper airflow, th
he installation
sh
hould allow a 3”
3 air gap aboove and beloww the chassiss.
Figure 3-1
11—Mounting
g Template off MicroNet Plu
us 14-Slot I/O
O Chassis
Woodward
d 2
29
MicroNet TMR Manual 26167V1
3.4.1—Specification
The MicroNet control is designed around a modular six slot chassis (block). Each
block consists of a premolded cage with a fan for cooling and a temperature
switch for high temperature detection. The chassis are cooled by forced air, and
either a module or a module blank must be installed in every slot to maintain
correct air flow. The fans run whenever power is applied to the system.
The six slot MicroNet expansion chassis is composed of two blocks with a
motherboard inserted in the back of the assembly to make connections between
the fans, switches, power supplies, and control modules. See Figure 3-13. The
modules use the VERSAmodule Eurocard (VME) bus standard for connector
specification and data transfer. Slot-to-slot logic and power connections are
made through an etched-circuit motherboard. I/O connections are made through
cables from the front of the modules to field termination modules (FTM’s) in the
cabinet.
From a module connector standpoint, any I/O module can be installed in any of
the slots designated for I/O modules. However, when the application software is
designed, each module will be assigned to a specific slot and thereafter, the
software will expect that specific I/O module to always be in its designated slot.
30 Woodward
Manual 26167V1 MicroNet TMR
Woodward 31
Micro
oNet TMR Manual 26167V1
3.4.2
2—Installation
e 3-14 shows
Figure s the mounting g template an
nd fasteners to bulkhead mount
m the
chasssis. Rack mou unting is not recommended d. For proper airflow, the in
nstallation
shouldd allow a 3” air
a gap above and below th he chassis.
Figure 3-1
14—Mounting
g Template off MicroNet 6 Slot
S I/O Chasssis
3.5—
—Expans
sion Micro
oNet Sim
mplex 12-S
Slot I/O
3.5.1—Descrription
This chassis
c contaains twelve slo
ots for remotee transceiver and
a I/O (inputt/output)
moduules. This allowws one Remo ove XCVR or RTN module and eleven I/O
moduules, redundan nt RTN modu ules are not alllowed. In add dition to the 12
XCVR R/RTN – I/O slots,
s wer supply positions are provided, which
two pow h allows for
redun
ndant power in nput. Each poower supply module
m occuppies three slotts of
chasssis space. Wh hen counting power
p supplyy and I/O slotss, the total wid
dth of the
chasssis is 18 slots wide.
If a po
ower supply or
o I/O module slot is not occcupied, it mu
ust be filled wiith a
blanking plate (379
99-301) to ma
aintain properr cooling flow through the chassis.
c
The
T 12 slot ex xpansion chhassis should
d not be used for new
applications.
a The 12 slot expansion chassis
c shouuld only be used in
retrofit
r situattions where the
t chassis isi already ins
stalled.
32 Woodward
Manual 26167V1 MicroNet TMR
3.5.2—Specification
The MicroNet is designed around a modular six slot chassis (block). Each block
consists of a premolded cage with a fan for cooling and a temperature switch for
high temperature detection. The chassis are cooled by forced air, and either a
module or a module blank must be installed in every slot to maintain correct air
flow. The fans run whenever power is applied to the system.
The twelve slot MicroNet expansion chassis is composed of three blocks with a
motherboard inserted in the back of the assembly to make connections between
the fans, switches, power supplies, and control modules. See Figure 3-16. The
modules use the VERSAmodule Eurocard (VME) bus standard for connector
specification and data transfer. Slot-to-slot logic and power connections are
made through an etched-circuit motherboard. I/O connections are made through
cables from the front of the modules to field termination modules (FTM’s) in the
cabinet.
From a module connector standpoint, any I/O module can be installed in any of
the slots designated for I/O modules. However, when the application software is
designed, each module will be assigned to a specific slot and thereafter, the
software will expect that specific I/O module to always be in its designated slot.
Woodward 33
MicroNet TMR Manual 26167V1
34 Woodward
Manual 26
6167V1 M
MicroNet TMR
3..5.3—Insttallation
gure 3-17 sho
Fig ows the moun nting template
e and fastene
ers to bulkhea ad mount the
ch
hassis. Rack mounting
m is not recommen nded. For propper airflow, th
he installation
sh
hould allow a 3”
3 air gap aboove and beloww the chassiss.
Woodward
d 3
35
MicroNet TMR Manual 26167V1
Chapter 4.
Power Supplies
When redundant power supplies are running, current sharing circuitry balances
the load to reduce heat and improve the reliability of the power supplies. In the
event that one supply needs replacement, this feature also ensures hot
replacement of the power supplies without disrupting the operation of the control.
Each main power supply has four LEDs to indicate power supply health (OK,
Input Fault, Overtemperature, and Power Supply Fault). See MicroNet TMR
Power Supply Troubleshooting (Section 4.8) for a description of the LED
indications.
36 Woodward
Manual 26167V1 MicroNet TMR
Input power connections are made to the main power supply through terminals
on the front of the power supplies. A 50-pin ribbon cable is used for connecting
the power supply chassis to the control chassis.
The ribbon cable connects to a connector at the back underside of the TMR Main
Chassis. There are connectors beneath the A and C Kernels – either can be
used. See Figure 4-2. NOTE: It is also possible to use two TMR Power Supply
Chassis and connect one to each connector.
On the Power Supply Chassis, the cable connects toward the back of the upper
side of the Chassis. See Figure 4-3. The Power Supply Ribbon cable is only 1
foot in length so the TMR PS Chassis must be located immediately beneath the
A or C Kernels of the TMR Main Chassis
Woodward 37
MicroNet TMR Manual 26167V1
A second Chassis-to Chassis Power Cable can be used to provide redundant
connections. See Figure 4-4.
The MicroNet TMR Main power supplies must have the input power
removed before installing or removing.
38 Woodward
Manual 26167V1 MicroNet TMR
DC
Operating range: 100 to 150 Vdc
Nominal voltage rating: 111 to 136 Vdc, as on power supply label
Maximum current: 5.8 A
Maximum power: 576 W
Input power fuse/breaker rating: 10 A time delay
Holdup time: 7 ms @ 120 Vdc
Woodward 39
MicroNet TMR Manual 26167V1
DC
Operating range: 200 to 300 Vdc
Nominal voltage rating: 223 to 272 Vac, as on power supply label
Maximum current: 2.9 A
Maximum power: 600 VA
Input power fuse/breaker rating: 10 A time delay
Holdup time: 7 ms @ 200 Vdc
40 Woodward
Manual 26167V1 MicroNet TMR
Note that the control’s power supplies are not equipped with input
power switches. For this reason, some means of disconnecting input
power to each main power supply must be provided for installation
and servicing. A circuit breaker meeting the above requirements or a
separate switch with appropriate ratings may be used for this
purpose. To avoid nuisance trips, use only time-delay fuses or circuit
breakers.
Branch circuit fuses, circuit breakers, and wiring must meet appropriate codes
and authorities having jurisdiction for the specific country (CE, UL, etc). See
Table 4-1 for maximum recommended fuse or breaker ratings. Do not connect
more than one main power supply to any one fuse or circuit breaker. Use only
the wire sizes specified in Table 4-1 which meet local code requirements. Time
delay fuses or circuit breakers must be used to prevent nuisance trips.
Power requirements depend on the number and type of modules supplied for
each system. For a system with a single I/O chassis, size the input power source
according to the rating of the MicroNet TMR main power supply to which the
source is connected. Do not size the supply mains for the sum of the MicroNet
TMR main power supply ratings when redundant supplies are used. MicroNet™
supplies are redundant when installed in the same chassis. Redundant supplies
share the load between them equally, but each must provide for full load in the
event that one of the units is disabled. Table 4-1 gives the maximum overload
protection for supply mains connected to any single or redundant pair of
MicroNet main power supplies. It is not recommended that both MicroNet main
power supplies of a redundant pair be connected to a single source, since failure
of that source would disable the system.
Multiple chassis systems using MicroNet TMR main power supplies may have
power supplies of the same model, but in different chassis, connected to the
same source. In this case, each branch to a chassis must have its own
overcurrent protection sized according to Table 4-1, and the power source must
be sized for the sum of the branches.
Not all systems will require the full load capability of the MicroNet TMR main
power supply. If not otherwise indicated on a cabinet system nameplate, either
use the MicroNet TMR main power supply input ratings for sizing the system’s
source or consult Woodward for determining the minimum source requirements.
Table 4-1 provides fuse and wire size specifications for each power supply.
Woodward 41
MicroNet TMR Manual 26167V1
When a cabinet is not supplied with the system, input power connections are
made through terminals on the front of each main power supply. These terminals
accept wires from 0.5 to 10 mm² (20–8 AWG). For a good connection, the
inserted wires should have the insulation stripped back 8–9 mm (0.33 in). Torque
to 0.5 to 0.6 Nm (0.37 to 0.44 lb-ft).
The 24 Vdc power supply model uses larger copper input terminals to
accommodate the required 10 mm² (8 AWG) wire.
A green/yellow wire connection of at least the same size as the supply wire must
be used for the PE ground.
Kernel Power Supply 5466-318 MUST be used with the TMR040 CPU.
Kernel Power Supply 5466-1049 MUST be used with the TMR5200
CPU.
Each kernel power supply has one LED to indicate kernel power supply health.
See MicroNet TMR Kernel Power Supply Troubleshooting (Section 4.8.2) for a
description of the LED indication.
The MicroNet TMR Kernel Power Supply module must have all
modules in that kernel removed before installing or removing a
Kernel Power Supply module.
42 Woodward
Manual 26167V1 MicroNet TMR
Woodward 43
MicroNet TMR Manual 26167V1
The Kernel Power Supply must be installed in the first module slot
from the left for each sub-chassis (kernel). The Kernel CPU module is
installed in the next module slot directly to the right of each Kernel
Power Supply.
44 Woodward
Manual 26167V1 MicroNet TMR
1. Verify that the entire MicroNet TMR control system has been installed.
2. Turn on the power for one power supply, and verify that the power supply’s
green LED is the only power supply LED that is on.
3. Turn on the power for the second power supply, and verify that the power
supply’s green LED is the only power supply LED that is on.
4. Verify that all of Kernel Power Supply’s red fault LEDs are off. If any of the
LEDs are on see the Kernel Power Supply Troubleshooting in section 4.8.2.
If the system is configured with the CPU_040 perform step #5 and skip step #6. If
the TMR system uses the CPU_5200 skip step #5 and perform step #6.
5. CPU_040: Momentarily toggle two of the CPU’s RESET switches up, then
back to their normal down position. Toggle remaining CPU RESET switch up,
then back to its normal down position. At this point the system will perform
off-line diagnostic testing, which could take several minutes. When all CPUs
have synchronized and completed their diagnostic tests, no red LEDs on the
CPU modules or I/O modules should be on, and the control will begin running
the application program.
6. CPU_5200: Wait until the CPUs finish their off-line diagnostics and the CPUs
are visible in AppManager. If the CPUs were running when the CPUs were
powered off, the CPUs will automatically start the Application that was
running when it was power off. If there was no Application running, select an
Application on each CPU in AppManager and select “Start”. The CPUs will
run the selected Application, synchronize and completed their diagnostic
tests. There should be no red LEDs on the CPU modules or I/O modules and
the control will be running the application program. The Green SYSCON and
RUN LED’s should be on and the Yellow STBY LED should be off.
OK LED—This green LED turns on to indicate that the power supply is operating
and that no faults are present.
Woodward 45
MicroNet TMR Manual 26167V1
INPUT FAULT LED—This red LED turns on to indicate that the input voltage is
either above or below the specified input range. If this LED is on, check the input
voltage, and correct the problem. Long-term operation with incorrect input
voltages may permanently damage the power supply. Once the input voltage is
within the supply’s input specifications, this LED will turn off. Refer to the power
supply input specifications.
If this LED is turned on, verify that the fan in the power supply chassis is turning
and is free of dust and other obstructions, and that the temperature around the
power supply is less that 55 °C. If the power supply is cooled down without delay,
it can recover from this situation without shutting down. This LED will turn off
once the internal power supply heat sink temperature falls below approximately
75 °C.
POWER SUPPLY FAULT LED—This red LED turns on when one of the supply’s
four power converters has shut down. If this LED is on, check for a short circuit
on external devices connected to the control’s power supply. When the short
circuit has been removed, the supply will resume normal operation. If no short
circuit is found, reset the supply by removing input power for one minute. If the
power supply is still not functioning after input power has been restored, verify
that the supply is properly seated to the motherboard connector. If the supply is
properly seated but is not working, then replace the supply.
The following is a troubleshooting guide for checking areas which may present
difficulties. If these checks are made prior to contacting Woodward for technical
assistance, system problems can be more quickly and accurately assessed.
Is the input power within the range of the control’s power supply input?
Is the input power free of switching noise or transient spikes?
Is the power circuit dedicated to the governor only?
Are the control’s supplies indicating that they are OK?
Are the control’s supplies outputting the correct voltage?
KERNEL FAULT LED—This LED indicates that either the 5 V is not functioning
or that the 5 V precharge is not functioning.
The following is a table to assist in troubleshooting the Kernel Power Supply and
the need for replacement.
46 Woodward
Manual 26167V1 MicroNet TMR
When redundant power supplies are running, current sharing circuitry balances
the load to reduce heat and improve the reliability of the power supplies. In the
event that on supply needs to be replaced, the recommended method for
changing Power Modules is with the power off (to the module being removed and
the module being inserted). The system will tolerate this “cold swap” method
without failure.
Each main power supply has four LEDs to indicate power supply health (OK,
Input Fault, Overtemperature, and Power Supply Fault). See MicroNet Plus
Power Supply Troubleshooting (Section 5.5) for a description of the LED
indications.
Input power connections are made to the power supply through a plug/header
assembly on the front of the power supply.
For redundant operation, the control can use any combination of power supplies.
The power supplies can only be installed into slots PS1 (power supply #1) and
PS2 (power supply #2). If redundant power supplies are not needed, blanking
plates must be installed in the slots not being used.
Woodward 47
MicroNet TMR Manual 26167V1
The MicroNet Plus main power supplies must have the input power
removed before installing or removing.
This equipment is suitable for use in Class I, Division 2, Groups A, B,
C, and D or non-hazardous locations only.
Wiring must be in accordance with Class I, Division 2 wiring methods
and in accordance with the authority having jurisdiction.
48 Woodward
Manual 26167V1 MicroNet TMR
DC input
Operating range: 100 to 150 Vdc
Nominal input voltage rating: 111 to 136 Vdc, as on power supply label
Maximum input current: 6A
Maximum input power: 600 W
Input power fuse/breaker rating: 10 A time delay
Note that the control’s power supplies are not equipped with input
power switches. For this reason, some means of disconnecting input
power to each main power supply must be provided for installation
and servicing.
Branch circuit fuses, circuit breakers, and wiring must meet appropriate codes
and authorities having jurisdiction for the specific country (CE, UL, etc). See
Table 4-3 for maximum recommended fuse or breaker ratings. Do not connect
more than one main power supply to any one fuse or circuit breaker. Use only
the wire sizes specified in Table 4-3 which meet local code requirements. Time
delay fuses or circuit breakers must be used to prevent nuisance trips.
Power requirements depend on the number and type of modules supplied for
each system. For a system with a single I/O chassis, size the input power source
according to the rating of the MicroNet Plus power supply to which the source is
connected. Do not size the supply mains for the sum of the MicroNet Plus power
supply ratings when redundant supplies are used. MicroNet Plus supplies are
redundant when installed in the same chassis. Redundant supplies share the
load between them equally, but each must provide for full load in the event that
one of the units is disabled. Table 4-3 gives the maximum overload protection for
supply mains connected to any single or redundant pair of MicroNet Plus main
power supplies. It is not recommended that both MicroNet Plus main power
supplies of a redundant pair be connected to a single source, since failure of that
source would disable the system.
Multiple chassis systems using MicroNet Plus power supplies may have power
supplies of the same model, but in different chassis, connected to the same
source. In this case, each branch to a chassis must have its own overcurrent
protection sized according to Table 4-3, and the power source must be sized for
the sum of the branches.
Not all systems will require the full load capability of the MicroNet Plus power
supply. If not otherwise indicated on a cabinet system nameplate, either use the
MicroNet power supply input ratings for sizing the system’s source or consult
Woodward for determining the minimum source requirements.
Table 4-3 provides fuse and wire size specifications for each power supply.
50 Woodward
Manual 26167V1 MicroNet TMR
When a cabinet is not supplied with the system, input power connections are
made through a plug/header assembly on the front of each main power supply.
The plug accept wires from 0.5 to 16 mm² (20–6 AWG). For a good connection,
the inserted wires should have the insulation stripped back 11-12 mm (0.45 in).
Torque to 0.5 to 0.6 Nm (0.37 to 0.44 lb-ft).
A green/yellow wire connection of at least the same size as the supply wire must
be used for the PE ground.
System Power-Up
If at any time during this procedure the defined or expected result is not
achieved, begin system troubleshooting.
1. Verify that the entire MicroNet Plus control system has been installed.
2. Turn on the power to one power supply and verify that the power supply’s
green LED is the only power supply LED on.
3. Turn off the power to the first power supply and turn on the power to the
second power supply (if a second power supply is present) and verify that the
power supply’s green LED is the only power supply LED on.
4. The RTN_CPUs in the chassis will not start automatically, the CPUs in the
TMR chassis must command them to start. See GAP application program
for details.
Woodward 51
MicroNet TMR Manual 26167V1
INPUT FAULT LED—This red LED turns on to indicate that the input voltage is
either above or below the specified input range. If this LED is on, check the input
voltage, and correct the problem. Long-term operation with incorrect input
voltages may permanently damage the power supply. Once the input voltage is
within the supply’s input specifications, this LED will turn off. Refer to the power
supply input specifications.
If this LED is turned on, verify that the fans in the power supply chassis are
turning and free of dust and other obstructions, and that the temperature around
the power supply is less than 55 °C. If the power supply is cooled down without
delay, it can recover from this situation without shutting down. This LED will turn
off once the internal power supply heat sink temperature falls below
approximately 90 °C.
POWER SUPPLY FAULT LED—This red LED turns on when one of the supply’s
three power converters has shut down or one or more of the supply levels is
below internally specified levels. If this LED is on, check for a short circuit on
external devices connected to the control’s power supply. When the short circuit
has been removed, the supply will resume normal operation (Note that if the 24 V
or 5 V outputs are shorted, these power converters will be latched OFF and can
only be cleared by removing the shorted condition and removing the input power
for 1 minute (or until the front panel LEDs extinguish). If no short circuit is found,
reset the supply by removing input power for one minute. If the power supply is
still not functioning after input power has been restored, verify that the supply is
properly seated to the motherboard connector. If the supply is properly seated
but is not working, then replace the supply.
Is the input power within the range of the control’s power supply input?
Is the input power free of switching noise or transient spikes?
Is the power circuit dedicated to the governor only?
Are the control’s supplies indicating that they are OK?
Are the control’s supplies outputting the correct voltage?
Is the RTN / CPU Low Vcc LED ON?
52 Woodward
Manual 26167V1 MicroNet TMR
When redundant power supplies are running, current sharing circuitry balances
the load to reduce heat and improve the reliability of the power supplies. In the
event that one supply needs replacement, this feature also ensures hot
replacement of the power supplies without disrupting the operation of the control.
Each main power supply has four LEDs to indicate power supply health (OK,
Input Fault, Overtemperature, and Power Supply Fault). See MicroNet Expansion
Power Supply Troubleshooting (Section 4.13.1) for a description of the LED
indications.
Input power connections are made to the power supply through terminals on the
front of the power supply.
For redundant operation, the control can use any combination of power supplies.
The power supplies can only be installed into slots PA1 (power supply #1) and
PA2 (power supply #2). If redundant power supplies are not needed, blanking
plates (3799-301) must be installed in the slots not being used.
For MicroNet TMR installation instructions, see Chapter 14 and Section 3.3 of
this chapter.
The 6/12 slot expansion chassis should not be used for new
applications. The 6/12 slot expansion chassis should only be used in
retrofit situations where the chassis is already installed.
The MicroNet TMR main power supplies must have the input power
removed before installing or removing.
This equipment is suitable for use in Class I, Division 2, Groups A, B,
C, and D or non-hazardous locations only.
Wiring must be in accordance with Class I, Division 2 wiring methods
and in accordance with the authority having jurisdiction.
Woodward 53
MicroNet TMR Manual 26167V1
54 Woodward
Manual 26167V1 MicroNet TMR
DC
Operating range: 100 to 150 Vdc
Nominal voltage rating: 111 to 136 Vdc, as on power supply
label
Maximum current: 5.3 A
Maximum power: 531 W
Input power fuse/breaker rating: 10 A time delay
Holdup time: 7 ms @ 120 Vdc
High Voltage DC
Operating range: 200 to 300 Vdc
Nominal voltage rating: 223 to 272 Vdc, as on power supply
label
Maximum current: 2.7 A
Maximum power: 531 W
Input power fuse/breaker rating: 5 A time delay
Holdup time: 7 ms @ 225 Vdc
Woodward 55
MicroNet TMR Manual 26167V1
Note that the control’s power supplies are not equipped with input
power switches. For this reason, some means of disconnecting input
power to each main power supply must be provided for installation
and servicing. A circuit breaker meeting the above requirements or a
separate switch with appropriate ratings may be used for this
purpose. To avoid nuisance trips, use only time-delay fuses or circuit
breakers.
56 Woodward
Manual 26167V1 MicroNet TMR
Branch circuit fuses, circuit breakers, and wiring must meet appropriate codes
and authorities having jurisdiction for the specific country (CE, UL, etc). See
Table 4-4 for maximum recommended fuse or breaker ratings. Do not connect
more than one main power supply to any one fuse or circuit breaker. Use only
the wire sizes specified in Table 4-4 which meet local code requirements. Time
delay fuses or circuit breakers must be used to prevent nuisance trips.
Power requirements depend on the number and type of modules supplied for
each system. For a system with a single I/O chassis, size the input power source
according to the rating of the MicroNet power supply to which the source is
connected. Do not size the supply mains for the sum of the MicroNet power
supply ratings when redundant supplies are used. MicroNet supplies are
redundant when installed in the same chassis. Redundant supplies share the
load between them equally, but each must provide for full load in the event that
one of the units is disabled. Table 4-4 gives the maximum overload protection for
supply mains connected to any single or redundant pair of MicroNet main power
supplies. It is not recommended that both MicroNet main power supplies of a
redundant pair be connected to a single source, since failure of that source would
disable the system.
Multiple chassis systems using MicroNet power supplies may have power
supplies of the same model, but in different chassis, connected to the same
source. In this case, each branch to a chassis must have its own overcurrent
protection sized according to Table 4-4, and the power source must be sized for
the sum of the branches.
Not all systems will require the full load capability of the MicroNet power supply.
If not otherwise indicated on a cabinet system nameplate, either use the
MicroNet power supply input ratings for sizing the system’s source or consult
Woodward for determining the minimum source requirements.
Table 4-4 provides fuse and wire size specifications for each power supply.
Woodward 57
MicroNet TMR Manual 26167V1
When a cabinet is not supplied with the system, input power connections are
made through terminals on the front of each main power supply. These terminals
accept wires from 0.5 to 10 mm² (20–8 AWG). For a good connection, the
inserted wires should have the insulation stripped back 8–9 mm (0.33 in). Torque
to 0.5 to 0.6 Nm (0.37 to 0.44 lb-ft).
The 24 Vdc power supply model uses larger copper input terminals to
accommodate the required 10 mm² (8 AWG) wire.
A green/yellow wire connection of at least the same size as the supply wire must
be used for the PE ground.
4.12.2—System Power-Up
If at any time during this procedure the defined or expected result is not
achieved, begin system troubleshooting.
1. Verify that the entire MicroNet control system has been installed.
2. Turn on the power to one power supply and verify that the power supply’s
green LED is the only power supply LED on.
3. Turn off the power to the first power supply and turn on the power to the
second power supply (if a second power supply is present) and verify that the
power supply’s green LED is the only power supply LED on.
4. If the RTN_CPUs are being used, they will not start automatically, the CPUs
in the TMR chassis must command them to start. See GAP application
program for details.
INPUT FAULT LED—This red LED turns on to indicate that the input voltage is
either above or below the specified input range. If this LED is on, check the input
voltage, and correct the problem. Long-term operation with incorrect input
voltages may permanently damage the power supply. Once the input voltage is
within the supply’s input specifications, this LED will turn off. Refer to the power
supply input specifications.
58 Woodward
Manual 26167V1 MicroNet TMR
OVERTEMPERATURE LED—This red LED gives an early warning of a thermal
shutdown. The LED turns on to indicate that the internal power supply
temperature has exceeded approximately 80 °C. If the internal supply
temperature rises to approximately 90 °C, the supply will shut down. Because of
the many variables involved (ambient temperature, load, thermal conductivity
variations), there is no accurate way of predicting the time between the indication
of overtemperature (LED illuminated) and power supply shutdown.
If this LED is turned on, verify that the fan in the power supply chassis is turning
and is free of dust and other obstructions, and that the temperature around the
power supply is less than 55 °C. If the power supply is cooled down without
delay, it can recover from this situation without shutting down. This LED will turn
off once the internal power supply heat sink temperature falls below
approximately 75 °C.
POWER SUPPLY FAULT LED—This red LED turns on when one of the supply’s
four power converters has shut down. If this LED is on, check for a short circuit
on external devices connected to the control’s power supply. When the short
circuit has been removed, the supply will resume normal operation. If no short
circuit is found, reset the supply by removing input power for one minute. If the
power supply is still not functioning after input power has been restored, verify
that the supply is properly seated to the motherboard connector. If the supply is
properly seated but is not working, then replace the supply.
Is the input power within the range of the control’s power supply input?
Is the input power free of switching noise or transient spikes?
Is the power circuit dedicated to the governor only?
Are the control’s supplies indicating that they are OK?
Are the control’s supplies outputting the correct voltage?
Woodward 59
MicroNet TMR Manual 26167V1
Chapter 5.
CPUs
The TMR5200 Module is designed for 3-2-0 operation. A TMR system cannot
operate with a single CPU.
This module was designed and rated for –40 to +85 °C operation in the industrial
marketplace.
60 Woodward
Manual 26167V1 MicroNet TMR
For CPU module installation and replacement instructions, see the instructions
for installing the VME module in Chapter 14, and the instructions for replacement
in Chapter 15.
The CPU module runs the GAP application program. Figure 5-2 is a block
diagram of a CPU module. When the power is applied, the CPU module will
perform diagnostic tests, before running the application program.
The CPU module contains a battery to power the real time clock when power to
the control is off. This battery is not user-replaceable. During normal operation,
on-board circuitry keeps the battery charged. Once the battery is fully charged
(taking a maximum of three days), the battery will continue to run the clock for a
minimum of three months without power to the control. If power is removed from
the CPU module for longer than three months, the real time clock may need to be
reset. The resolution of the real time clock is 10 milliseconds.
Woodward 61
MicroNet TMR Manual 26167V1
5.1.2—Module Configuration
Hardware Configuration. The Module Configuration Switch (S2) must be
configured properly for CPU mode (main rack, address 0x000) operation. This
module will be factory configured appropriately.
The Network Type setting on all CPU and Remote RTN modules in
the system must match for proper system operation.
This module has been factory configured with fixed Ethernet IP addresses of
Ethernet #1 (ENET1) = 172.16.100.1, Subnet Mask = 255.255.0.0
Ethernet #2 (ENET2) = 192.168.128.20, Subnet Mask = 255.255.255.0
62 Woodward
Manual 26167V1 MicroNet TMR
Network Configuration Utility (AppManager)
Woodward's AppManager software can be used to load Control software (GAP),
monitor diagnostic faults, and configure Network settings. The AppManager utility
can be downloaded from www.woodward.com/software. A PC connection must
be made to Ethernet #1 (ENET1) using a RJ45 Ethernet cable.
Woodward 63
MicroNet TMR Manual 26167V1
5.1.4—Module Reset
Front Panel Reset Switch. The CPU module has a pushbutton reset switch on
the front panel to reset the module. If a GAP application was successfully running
at the time of reset, the same application will be auto-started and re-initialized.
CPU Remote Reset. Each CPU module will respond to a +24 V remote reset
signal. The chassis provides a terminal-block with inputs RST1+, RST1–, RST2+,
RST2–, RST3+, and RST3– for wiring the remote reset signals to each CPU.
Each reset signal is routed to an opto-isolated input on the appropriate CPU that
requires a +24 V signal to cause a reset.
Reset Notes:
Resetting a CPU or Remote RTN module creates a HealthFault that
immediately sets the WDOG light RED.
The front-panel RUN/RESET led will be RED while reset is held and will turn
GREEN for a few seconds after releasing reset. After turning OFF, it will again
turn GREEN when the operating system starts to boot.
NOTE: When a TMR System is running with only 2 healthy CPUs, Pressing the
reset on either of the running CPUs will drive IOLOCK and IORESET on the
entire TMR system. This will place the Control System and all expansion racks to
a safe condition where all output signals are driven to a known failsafe condition.
5.1.6—RTN Port
In a TMR5200 based system, each Kernel CPU provides Real Time Network
(RTN) capability for expanding to other racks using Ethernet port 4 (RJ45). This
RTN port communicates between the main chassis CPU's and any Remote RTN
modules located in an expansion chassis. The GAP software application defines
the expansion racks, their I/O modules, and the use of the RTN port (GAP block
is RTN).
64 Woodward
Manual 26167V1 MicroNet TMR
Up to two Remote RTN modules may be installed into each MicroNet Plus 8/14
expansion chassis (only one RTN for 6/12 slot expansion chassis). When
initialized by the main chassis CPU, the Remote RTN modules will acquire either
a SYSCON or STANDBY status. The Remote RTN module that becomes
SYSCON will control the expansion chassis it is located in. It will synchronize
with the STANDBY Remote RTN module and perform any redundancy functions
as necessary. Input and output data from all I/O modules will be managed
appropriately and made available to the GAP Application running in the main-
chassis CPUs.
**Refer to the Communications section and the RTN Remote Transceiver module
for additional information to configure expansion racks using either copper or
fiber Ethernet cables.
For debug use, a null-modem cable and 5450–1065 Serial Adapter cable (PS2M
to DB9F) is required to attach this port to a PC. This port is to be used by
trained Field Service personnel only!
Shielded cable is required when connecting to the Service Port. Using shielded
cable will help ensure the robustness of the serial communications.
Woodward 65
MicroNet TMR Manual 26167V1
66 Woodward
Manual 26167V1 MicroNet TMR
*A table of Message ID values as displayed in AppManger:
Description of ID ID Number
Created by the Coder (Evaluate specific Application) 1-99
“sysinit” – Problem in system initialization 184,185,186
VerifyCpuMem -- Problem in verify CPU memory 103
VerifyNVLog -- Problem in verify NV_LOG functions 104,143,145
ExecuteTMRMessageTask -- Freerun task error 101,102
TMRDportDiagnostics -- Problem running DualPort test 105,106,112,113,114
WaitRTNBuffer -- Problem waiting for the RTN messages 146,147
ioRead -- Problem in the ioRead function 142,183
Run_ll_int -- Problem in the Ladder Logic executive 180
SynCmdBuffer – Problem sending messages to RTN chassis 181
CheckSyncCmdBuffer - Problem sending message to RTN 182
Clk_xvstat -- TMR CPU missing in interrupt service routine 604,605
PresInt -- TMR CPU unable to reach previous target 660
CopyToPickup – Problem syncing lost CPU 130,131,132
Re-sync -- Problem syncing lost CPU 133,134,135,136,137,138
Re-sync -- Lost CPU failed to sync properly 139
5.2—CPU_040 Module
5.2.1—Module Description
Woodward 67
MicroNet TMR Manual 26167V1
Every MicroNet TMR® control contains three CPU modules, one located in the
second slot of each kernel, just to the right of the kernel power supply.
For CPU module installation and replacement instructions, see the instructions
for installing the VME module in Chapter 14, and for replacement in Chapter 15.
The CPU modules run the application program. Figure 5-7 is a block diagram of
a CPU module. When the reset switch is toggled to the Run position, the CPU
modules will perform diagnostic tests, sync together, and then run the application
program.
The CPU module contains a battery to power the real time clock when power to
the control is off. This battery is not user-replaceable. During normal operation,
on-board circuitry keeps the battery charged. Once the battery is fully charged
(taking a maximum of three days), the battery will continue to run the clock for a
minimum of three months without power to the control. If power is removed from
the CPU module for longer than three months, the real time clock may need to be
reset. The resolution of the real time clock is 10 milliseconds.
68 Woodward
Manual 26167V1 MicroNet TMR
Woodward 69
MicroNet TMR Manual 26167V1
5.2.3—FTM Reference
No FTM is used with this CPU. However, additional installation and application
information can be found in Chapter 12.
70 Woodward
Manual 26167V1 MicroNet TMR
68040 CPU Off-Line Diagnostics
The following table shows the tests run by off-line diagnostics, and the order in
which they are run. Off-line diagnostics are started immediately after the Reset
has toggled.
Woodward 71
MicroNet TMR Manual 26167V1
If during diagnostics, a particular test fails, testing stops and a message
identifying the cause of the failure will be displayed. Also, the FAILED LED on the
CPU module will periodically repeat bursts of flashes; the number of flashes in
each burst indicates the test that failed as shown in Table 5-2.
72 Woodward
Manual 26167V1 MicroNet TMR
A failure of any one of the on-line tests results in the I/O lock being asserted and
display of a message as shown in Table 5-4. The message will be displayed on
the Service Panel at the time the error occurs, and it also will go into the Fault
Mode Buffer so that it can be displayed in the Fault Mode.
MESSAGE MEANING
Checksum Error Local RAM Failed
System Error (#) Application RAM Failed (ref. Table 5-6)
EEPROM Fault FPU C0-processor Failed
Math Exception The FPU (Co-processor) has received an illegal instruction
Rate Group Slip (#) Rate group # (number) is scheduled to run and it did not complete
its previous scheduled run.
EEPROM Initialization Fault The CPU attempted to program the EEPROMs during system
initialization and failed, or the EEPROM was detected bad
(EEPROM FAULT). The system is not permitted to run because
the EEPROM data is not current.
Exception Error Vector # An error was detected by the processor. The vector number
indicates which exception the 68040 processor took. For an
explanation of exceptions, refer to page 8-5 of Motorola Manual
M 68040 UM/AD, MC68040 Enhanced 32-bit Microprocessor
Users Manual.
Woodward 73
MicroNet TMR Manual 26167V1
When the system detects an error when starting or running an application, the
CPU will flash the FAILED LED on the CPU module with two bursts of flashes
separated by a medium longer pause. The CPU will re-start flashing the fault
codes after a long pause. The number of flashes will match the display message
or it can be determined by counting the two groups of short flashes between the
medium pause. The number of flashes in each burst indicates the detected
failure as shown in Table 5-7.
74 Woodward
Manual 26167V1 MicroNet TMR
Woodward 75
MicroNet TMR Manual 26167V1
CPU_040 Alarms
The possible system alarms are listed in Table 5-8. The numbered system
alarms are listed in Table 5-9.
The ALARMS in Tables 5-8 and 5-9 do not automatically display; they are stored
by the system and to see them, you must use the OPSYS_FAULTS Mode of the
Service Panel.
MESSAGE MEANING
SIO n Configuration Fails A configuration error occurred on Port n of SIO x module.
port x n (1-…) = SIO number
x (1-4) = port number
SIO n Missing SIO n module is not installed.
n (1-…) = SIO number
SIO n Self Test Failed SIO n module failed its self test.
n (1-…) = SIO number
SIO n Initialization Failed SIO n module failed to initialize.
n (1-…) = SIO number
System Alarm # n A numbered system alarm has occurred. The number of the alarm is n
(see Table 20-8, Numbered System Alarms).
Divide by Zero A divide by zero operation was performed.
Real to Int Conversion An Overflow has occurred during a Real-to-integer conversion
Overflow operation.
76 Woodward
Manual 26167V1 MicroNet TMR
Chapter 6.
Communication
The Remote RTN module contains a MPC5200 processor, 128 Mbyte DDR
RAM, 64 MB of flash memory, a Real Time clock, and various communication
peripherals. These peripherals include (3) Real Time Network ports and (1)
service port. This module includes an FPGA to provide VMEbus master/slave
capability, health monitoring, and failover functions necessary for redundant
systems.
This module was designed and rated for –40 to +85 °C operation in the industrial
marketplace. Figure 6-2 is a block diagram of a Remote RTN module.
Woodward 77
MicroNet TMR Manual 26167V1
MicroNet VMEbus
DDR SDRAM DDR SDRAM CONTROLLER
(high) (low) VME
DATA (Master/Slave) VDB(31:0) DATA VD(31:0)
BUFFERS CDB(15:0)
DPRAM XCVR
(3) RJ45 5k x 32
RTN-/A REAL-TIME
RTN1/B NETWORK PORTS
1.8V 2.5V 3.3V CTRL
RTN2/C VCB(11:0) VC(11:0)
XCVR
VMEbus
RS-232 Debug RS-232 Port SLAVE
(MINI-DIN6F) (ISOLATED) Bus Isolation
& XCVR Control
ARBITER
LED DRIVER BTO
SYSCON + STANDBY SYSCON CTRL
SYSCON GR YL STANDBY Low Voltage (LVCC) MOTOROLA XCVR
WGC
P1
IOLOCK Fault FPGA
LVCC RD RD IOLOCK
Module Fault / Code
MPC5200 REDUNDANCY
FAULT RD RD WDOG Watchdog / HealthFault CONTROLLER
WGC
WGC
HEALTH MONITOR MONITOR
MFT, IOLOCK,
FAN MONITOR
Control & Status
MicroNet VMEbus
RTC with 3.3V
Battery
2.5V
RESET*
2.5V 3.3V 3.3V
2.5v
1.5V
LOCAL PWR
MONITOR 1.2V
VME HotSwap
5.0V_FAIL
Front Panel
Isol 5V
1.2V 1.5V 1.8V 2.5V 3.3V
coms, CAN
Remote RTN modules can support simplex, redundant, and TMR systems. Every
RTN expansion chassis contains one Remote RTN module located in the first
slot (CPU1) of the chassis. A redundant configuration using a Plus chassis may
also have a Remote RTN module located in the CPU2 location (slot 8 or slot 14
depending on the chassis used).
For Remote RTN module installation and replacement instructions, see the
instructions for installing the VME module in Chapter 14, and for replacement in
Chapter 15. This module will NOT automatically re-initialize to a running
state after reset. This module is can only be initialized by the main-chassis CPU
when the application starts and upon any application request.
78 Woodward
Manual 26167V1 MicroNet TMR
Operation
For redundant systems, up to two Remote RTN modules may be installed into
each MicroNet Plus 8/14 slot expansion chassis (only one RTN can be installed
in the MicroNet 6/12 slot chassis). When initialized by the main chassis CPU, the
Remote RTN modules will acquire either a SYSCON or STANDBY status. The
Remote RTN module that becomes SYSCON will control the expansion chassis
it is located in. It will synchronize with the STANDBY Remote RTN module and
perform any redundancy functions as necessary. Input and output data from all
I/O modules will be managed appropriately and made available to the GAP
Application running in the main-chassis CPUs.
The Remote RTN module communicates with the I/O modules in the expansion
chassis and also the CPU modules in the main chassis. When the power is
applied, the Remote RTN module will perform diagnostic tests before beginning
communications.
Woodward 79
MicroNet TMR Manual 26167V1
2
2
3
0 1
4
LA1
1
5
DA/STAT
FAULT
DA/STAT
FAULT
LA3
LA4
Switch 4TX/1FX
LA5
+24V*
+24V
1
RTN-A 4 5
Fiber-A
(10' max) (2 Km)
RTN-B
RS2
Fiber-B TX
(2 Km)
RS2-4TX/1FX-SM RS2
LA3
LA4
LA5
+24V*
+24V
RTN-C Fiber-C
MicroNet TMR 4 5
(2 Km)
Main Rack
6.1.3—Module Configuration
Network Configuration. No network configuration is required. Only the RTN
ports are active on this module. Ethernet port (ENET1) is disabled on the Remote
RTN module by the Module Config switch (S2) and no IP address configuration is
necessary.
RTN Mode. The Module Config Switch (S2) is factory configured for RTN
mode, expansion rack X1 operation (address 0x001). It may need to be
re-configured for expansion rack X1-X3 in TMR systems. Note: RTN mode
will disable Ethernet port #1.
80 Woodward
Manual 26167V1 MicroNet TMR
The Network Type setting on all CPU and Remote RTN modules in
the system must match for proper system operation.
Woodward 81
MicroNet TMR Manual 26167V1
6.1.5—Module Reset
Front Panel Reset Switch. The Remote RTN module incorporates a pushbutton
reset switch on the front panel to reset the module. This module will NOT
automatically re-initialize to a running state after reset. The main-chassis CPU
application can re-init this module upon request.
RTN1 and RTN2 Remote Reset. Each Remote RTN module will respond to a
+24 V remote reset signal. The chassis provides a terminal-block with inputs
RST1+, RST1-, RST2+, and RST2- for wiring the remote reset signals to each
RTN. Each reset signal is routed to an opto-isolated input on the appropriate
RTN that requires a +24 V signal to cause a reset.
Reset Notes:
Resetting a Remote RTN module creates a HealthFault that immediately
sets the WDOG light RED.
Any Expansion chassis running with one healthy RTN. Reset detection will
also drive IOLOCK and IORESET to place the expansion rack and all output
signals into a known failsafe condition.
Any Expansion chassis running with two healthy RTNs. Reset detection on
the SYSCON (System Controller) causes an immediate "Failover" to the
other STANDBY RTN who then becomes the new System Controller for this
chassis. Reset detection on the STANDBY unit causes a HealthFault that
removes it from STANDBY mode.
The front-panel RUN/RESET led will be RED while reset is held and will turn
GREEN for a few seconds after releasing reset. After turning OFF, it will
again turn GREEN when the operating system starts to boot.
6.1.6—RTN Ports
Three Real Time Network ports (RJ45) provide communications between the
expansion chassis Remote RTN module and the main-chassis CPU A, B, and C
modules. Through these ports, expansion chassis I/O data is made available to
the GAP Application running in the main-chassis CPUs.
82 Woodward
Manual 26167V1 MicroNet TMR
Configuration Notes:
- A combination of approved copper and fiber optic Ethernet switches are
allowed.
- A maximum of 4 switches and 2 km of fiber cable shall be allowed in any
communication path.
- RTN cables from the main CPU rack to the local RTN switch hardware shall be
3 m (10') max.
Fiber Optic Expansion: Using fiber optic cables and switches, each
expansion rack may be located up to 2 km away from the main CPU
chassis.
Woodward 83
MicroNet TMR Manual 26167V1
For debug use, a null-modem cable and 5450–1065 Serial Adapter cable (PS2M
to DB9F) is required to attach this port to a PC. This port is to be used by
trained Field Service personnel only!
Shielded cable is required when connecting to the Remote RTN module’s serial
port. Using shielded cable will help ensure the robustness of the serial
communications.
84 Woodward
Manual 26167V1 MicroNet TMR
Woodward 85
MicroNet TMR Manual 26167V1
6.2.2—Module Specification
Parallel Interface: High-speed, differential line drivers
operating at VME transmission rate
Cable Interface: 100 pin metal shell Micro-D connector (2
per module)
6.2.3—Installation
The Main XCVR module can be installed in any slot in the Main Chassis.
No jumpers are used to configure this module.
This Transceiver module has no switches or LEDs.
6.2.4—Troubleshooting
1. If the Main XCVR module is not functioning or not functioning properly, verify
cable connections.
2. If the module is still not functioning properly after verifying the cable
connections, replace the cables connecting to module.
3. If the module is still not functioning properly after replacing cables, replace
the module.
86 Woodward
Manual 26167V1 MicroNet TMR
The Remote XCVR module connects to the VME bus of the chassis. The bus
receiver/driver of the Remote Transceiver module interfaces with the VME bus,
exchanging control, data, and address information. The chassis decoder
determines if this chassis is to be accessed, and if so, it activates the
receiver/driver of this chassis' Remote Transceiver module to receive or send
information. Figure 6-8 is a block diagram of the Remote Transceiver module.
Woodward 87
MicroNet TMR Manual 26167V1
Table 6-1 shows the jumpers on the Remote XCVR module used to configure the
chassis ID.
88 Woodward
Manual 26167V1 MicroNet TMR
6.3.2—Module Specification
Parallel Interface: High-speed, differential line drivers
operating at VME transmission rate
Cable Interface: 100 pin metal shell Micro-D connector (2
per module)
6.3.3—Installation
The Remote XCVR module has no switches or LEDs.
All expansion chassis except for the last one in the chain should use the
Remote XCVR module without termination resistors. This module must be
installed in Slot 1.
The last expansion chassis in the chain should use the Remote XCVR
module with termination resistors. This module must be installed in Slot 1.
Woodward 89
MicroNet TMR Manual 26167V1
6.3.4—Troubleshooting
1. If the Remote XCVR module is not functioning or not functioning properly,
verify the cable connections.
2. If the module is still not functioning properly after verifying the cable
connections, replace the cables connecting to module.
3. If the module is still not functioning properly after replacing cables, replace
the module.
6.4—Transceiver Accessories
6.4.1—Description
These accessories are only used with CPU 68040 systems. Each expansion
chassis except the last one should have the T-Module mounted next to it. The
3-foot (0.9 m) cables should connect these expansion chassis to the T-Modules.
Connections from the Main Chassis, the last Expansion Chassis, and
connections between the T-Modules should be made with 10-foot (3 m) cables.
Figure 6-12—Cables
[available in 3 ft (0.9 m) and 10 ft (3 m) lengths]
90 Woodward
Manual 26167V1 MicroNet TMR
6.4.2—Module Specification
Parallel Interface: High-speed, differential line drivers
operating at VME transmission rate
Cable Interface: 100 pin metal shell Micro-D
connector (2 per module)
Woodward 91
MicroNet TMR Manual 26167V1
Figure 6-14—Termination
6.5—Ethernet Module
6.5.1—Module Description
This Ethernet module is only used with CPU 68040 systems. The MicroNet™
Ethernet module is a 32 bit VME bus module which has been integrated into the
MicroNet product family. The module is designed to fully support auto-switching
10/100 Base-TX Ethernet connections, but has been configured to operate at
only 10 Mbps for use with legacy products.
The Ethernet module has a VME adapter board attached to allow its use in a
MicroNet chassis. However, this module is not “hot swappable” due to signal
integrity issues on the VME backplane. When inserted into a powered chassis,
the module will interrupt VME bus backplane communications and cause other
Woodward modules and expansion racks to shut down.
On power-up, the Ethernet board runs a series of self-tests that check the board
hardware. After successful completion of the tests, the red FAIL LED will turn
OFF. The self-tests may last 10–20 seconds.
92 Woodward
Manual 26167V1 MicroNet TMR
Due to addressing conflicts with the Pentium CPU and TMR5200, this
module can be used only with the Motorola 68040 CPU family.
LED Annunciations
The following LEDs annunciate board failure as well as different functions related
to Ethernet communications. When continuous communications are present, the
RX and TX LEDs will be ON continuously.
Woodward 93
MicroNet TMR Manual 26167V1
10BaseT Ethernet
A 10BaseT RJ45 Ethernet connector is available for system use. This connection
is used for control configuration, data gathering, and networking of multiple
controls. In addition, this port may be relied upon for interfacing TCP/IP
Distributed I/O devices into the control system.
6.5.2—Module Specifications
Ethernet Features
Industry Standard 6U, VME-32 format
Network interface conforming to the IEEE 802.3 standard
Configured for 10BaseT communication support
Module failure/reset, Link LED, Transmit, Receive, Collision, and 10/100
Mbps LEDs
Supports Woodward communications such as Modbus, GAP Download, and
Tunable Capture/Download.
Electrical Specifications
Voltage: 5.0 Vdc, 5% tolerance
Power: 15.0 W max (13.5 W typical)
Processor: PowerPC 750, 400 MHz
Memory: 64 MB DRAM, 2 MB boot flash, 32 MB
user flash
Bus Interface: 32 bit VME bus
On board I/O: RJ45 10 Mbps Ethernet port
Hardware Configuration: VME address #1 or #2 configuration for
using 2 modules in a system
6.5.3—Installation
VME Address Configuration
The Ethernet module can be configured for an alternate VME address to support
the use of two modules in a MicroNet system. For dual module operation, both
the Woodward GAP and the module DIP switch must be configured properly.
The DIP switch (S2) is located directly behind the RJ45 Ethernet
connector.
NOT USED
NOT USED
VME1
OFF 1 2 3 4 5 6 7 8
VIS-151
*SWITCH POSITIONS SHOWN AT DEFAULTS 02-27-2001
KDW
94 Woodward
Manual 26
6167V1 M
MicroNet TMR
RJ
J45 Ethernett Pinout
1 TX+
2 TX-
3 RX+
4 ---
5 ---
6 RX-
7 ---
8 ---
S
Shield Chassis GND
D
6..5.4—FTM
M Referen
nce
Etthernet Interfface FTM
Too ensure signaal integrity an
nd robust operation of Ethe
ernet devices, an Ethernet
Intterface FTM (Field
( Termination Module) is required when
w interfaccing Ethernet
de
evices to the CPU.
C The FTM’s primary function is to implement
i EMMI shielding
nd cable shield termination of the Ethern
an net cable. Alo
ong with this FTM,
F double
sh
hielded Ethernnet cables (SS STP) are requuired.
6..5.5—Tro
oubleshoo
oting
1. If the Etherrnet module iss not functioning or not fun nctioning prop perly, verify the
cable connections.
2. If the moduule is still not functioning
f prroperly after verifying
v the cable
c
connectionss, replace the e cables conn necting to mod dule.
3. If the moduule is still not functioning
f prroperly after replacing
r cables, replace
the module e.
Woodward
d 9
95
MicroNet TMR Manual 26167V1
6.6—SIO Module
6.6.1—Module Description
The SIO (Serial In/Out) Module interfaces four serial communication ports to the
VME bus.
Figure 6-17 is a block diagram of the SIO module. The module manages four
serial ports. Port A(J1) and port B(J2) are RS-232 ports. Port C(J3) and Port
D(J4) are for RS-232, RS-422, or RS-485 communication protocols. Ports C and
D must be at the same baud rate when using 38.4 Kbaud or 57.6 Kbaud.
The processor on this module is a 68030. It controls the transfer of data between
the ports and the VME bus.
96 Woodward
Manual 26167V1 MicroNet TMR
6.6.2—Module Specification
Ports 1 and 2: RS-232 @ 110–38.4 Kbaud
Ports 3 and 4: RS-232, RS-422, and RS-485 (software
selectable) @ 110–57.6 Kbaud
Software Support: Modbus RTU
Modbus ASCII
Woodward-specific service interface
Woodward 97
MicroNet TMR Manual 26167V1
6.6.3—Installation
Termination
For RS-422, termination should be located at the receiver when one or more
transmitters are connected to a single receiver. When a single transmitter is
connected to one or more receivers, termination should be at the receiver
farthest from the transmitter. Figure 6-18 is an example.
For RS-485, termination should be at each end of the cable. If termination can't
be located at the end of a cable, put it as close as possible to the ends. Figure
6-22 is an example.
98 Woodward
Manual 26167V1 MicroNet TMR
Woodward 99
MicroNet TMR Manual 26167V1
6.6.4—Troubleshooting
1. If the SIO module is not functioning or not functioning properly, verify the
cable connections.
2. If the module is still not functioning properly after verifying the cable
connections, replace the cables connecting to module.
3. If the module is still not functioning properly after replacing cables, replace
the module.
100 Woodward
Manual 26167V1 MicroNet TMR
Chapter 7.
Discrete I/O Modules
7.1—Introduction
There are five types of discrete I/O modules currently available with the
MicroNet™ system. These include the 24/12 TMR Discrete Combo module (24
discrete inputs, 12 discrete outputs), 48/24 Discrete Combo module (48 discrete
inputs, 24 discrete outputs), 48 Ch DI module, 32 Ch DO module, and the 64 Ch
DO module.
7.2.1—Physical Description
The modules slide into card guides in the control’s chassis and plug into the
motherboard. The modules are held in place by two screws, one at the top and
one at the bottom of the front panel. Also at the top and bottom of the module are
two handles which, when toggled (pushed outward), move the modules out just
far enough for the boards to disengage the motherboard connectors.
Woodward 101
MicroNet TMR Manual 26167V1
7.2.2—Specifications
Discrete Inputs
Number of channels: 24
Update time: 5 ms
Input type: Optically isolated discrete input
24 V Input thresholds: <8 Vdc = “OFF”, at .7 mA
>16 Vdc = “ON”, at 1.2 mA
125 V Input thresholds: < 24 Vdc = “OFF”, at .7 mA
>55 Vdc = « ON », at 4 mA
Input current : 3.5 mA @ 24 Vdc ; 8 mA @ 125 Vdc
External input voltage: 18-32 Vdc (LVD and UL) or
100–150 Vdc (UL)
Isolation voltage: 500 Vdc to earth ground,
1000 Vdc to control common
Time stamping: 1 ms resolution
Isolated 24 Vdc contact supply: 400 mA maximum
Discrete Outputs
Number of channels: 12
Update time: 5 ms
Relay type: Dust-tight, magnetic blow-out
Coil rating: 80 mA @ 24 Vdc, suppressor located on
circuit board
Minimum load: 50 mA @ 125 Vdc
Relay response time: 15 ms (operate and release)
Relay life expectancy: 50,000 operations @ rated load
Replaceability: Relays are socket mounted and retained by
a hold down spring
102 Woodward
Manual 26167V1 MicroNet TMR
Contact ratings:
5.0 A @ 240 Vac, 50/60 Hz (resistive) (meets UL ratings only)
3.0 A @ 240 Vac, 50/60 Hz (inductive)·(meets UL ratings only)
10.0 A @ 120 Vac, 50/60 Hz (resistive) (meets UL ratings only)
6.0 A @ 120 Vac, 50/60 Hz (inductive) (meets UL ratings only)
600 watt @ 120 Vac, 50/60 Hz (lamp) (meets UL ratings only)
3.0 A @ 150 Vdc (resistive) (meets UL ratings only)
1.2 A @ 150 Vdc (inductive) (meets UL ratings only)
10.0 A @ 28 Vdc (resistive) (meets LVD and UL ratings)
3.0 A @ 28 Vdc (inductive) (meets LVD and UL ratings)
In a TMR system, each 24/12 TMR Discrete I/O module is connected through
two high density 62 conductor discrete cables to four FT Relay/Discrete Input
modules. All of the I/O on 24/12 TMR Discrete I/O module is accessible on the
relay modules. See Figure 7-3 for an example.
Woodward 103
MicroNet TMR Manual 26167V1
7.2.4.1—Field Wiring
104 Woodward
Manual 26167V1 MicroNet TMR
7.2.4.2—Discrete Inputs
The 24/12 TMR Discrete I/O Discrete module accepts 24 discrete inputs. Each of
the control’s four FT Relay/Discrete Input modules accepts six contact inputs.
Contact wetting voltage can be supplied by the control or from an external
source. 24 Vdc contact wetting voltage is available on each relay module.
Optionally, an external 18-32 Vdc power source or an external 100–150 Vdc
power source can be used to source the voltage. Because all discrete inputs are
fully isolated, a common reference point must be established between the inputs
and the contact power source. If the 24 Vdc internal power source is used for
contact wetting, jumpers are required between relay module terminals 33, 34,
and 35. If an external power source is used for contact wetting, the external
source’s common must be connected to the relay module’s discrete input
commons (terminals 34 and 35).
The inputs have components which establish a voltage threshold and a current
threshold, to prevent a closed indication due to the leakage current of most solid
state relays. The discrete inputs also have time stamping on a change of state,
with 1 millisecond resolution.
Figures 7-5 and 7-6 illustrate the different discrete input wiring configurations
based on the input voltage.
Woodward 105
MicroNet TMR Manual 26167V1
7.2.4.3—Configuration Notes
106 Woodward
Manual 26167V1 MicroNet TMR
Discrete outputs can be configured to use latent fault detection to identify relay
failures without affecting a relay output’s state. Six individual relays make up one
relay output. When a relay output is closed, the contacts of all six relays are
closed. Because of the series-parallel configuration of the relays, the failure of
any two individual relays will not cause the output to open. The individual relays
are periodically opened and reclosed in pairs to ensure that they are in the
correct state and that they change state.
When a relay output is open, the contacts of all six relays are open. Because of
the series-parallel configuration of the relays, the failure of any one relay will not
cause the output to close. The individual relays are periodically closed and
reopened one by one to ensure that they change state.
Readback circuitry allows the state of each relay contact to be detected. Any
failures are annunciated, and further testing is disabled without affecting the state
of the relay output contact or control operation.
Latent fault detection is not appropriate for all applications or circuits. The
control’s latent fault detection logic can only work with circuits using voltages
between 18-32 Vdc, 100–150 Vdc, or 88-132 Vac. For latent fault detection to
work, a small leakage current is passed through the circuit’s load. Depending on
the size of the load, the leakage current may be enough to cause a load to be on
or active when a relay contact is open. In this case, the individual relay’s latent
fault detection logic may be disabled, eliminating the leakage current.
Woodward 107
MicroNet TMR Manual 26167V1
With latent fault detection, when a relay contact is closed no difference in
operation is experienced; the relay output appears as a closed contact. However,
when a relay contact is open, it appears to the interfaced circuit as a large
resistor instead of an open contact. A small amount of current is leaked to the
load, resulting in a developed voltage across the load. In most cases this has no
bearing on the circuitry, because only a small amount of voltage is developed
across its load. However, when a relay output is used with a very high resistance
load (low current load), enough voltage may be developed across the load to
prevent it from de-energizing.
Verifying That Latent Fault Detection Can Be Used With a Relay Output
1. Verify that the circuit the relay output is used with has a voltage level of 18-
32 Vdc, 100–150 Vdc, or 88-132 Vac.
2. Use graph which corresponds to the circuit’s voltage level to determine if the
voltage developed across the load (due to the leakage current) is lower than
the load’s drop-out voltage level.
Acquire the resistance of the load (relay, motor, solenoid, etc.) to be driven
by the relay.
Acquire the load’s minimum drop-out voltage.
From the bottom of the graph, follow the line corresponding to the load’s
resistance up to the point at which it intersects the circuit power line. At this
point the corresponding voltage level (on the left of the graph) is the level of
voltage that will be developed across the load due to leakage current.
If circuit voltage is acceptable, and the developed load voltage (from the graph) is
less than the load’s drop-out voltage, latent fault detection can be used with the
circuit.
If the developed load voltage is greater than the load’s drop-out voltage, it is
recommended that latent fault detection be disabled or that a resistor be
connected in parallel (shunt) with the load. A correctly sized resistor connected in
parallel with the circuit load will decrease the developed load voltage below the
load’s drop-out voltage level. Using the corresponding latent fault detection graph
and the load’s minimum drop-out voltage, perform the above procedure in
reverse (see Step #2) to determine an acceptable shunt resistance. When
selecting a shunt resistor, also verify that its voltage and wattage ratings meet
that of the circuit.
Using the graph below, the intersection point between the 200 ohm load
resistance line and the 110 Vac line was found. From this intersection point it
was determined that the voltage developed across the load due to leakage
current when the relay is open, is approximately 7.5 Vac. This voltage level is
lower than the load’s 25 Vac drop-out voltage, so latent fault detection can be
used.
If, however, the load resistance were 1200 ohms, the intersection would be
approximately 29.5 Vac, too high for latent fault detection. By following the graph
along the allowable drop-out voltage, 25 Vac, it can be determined that a total
load resistance of 900 Ohms or less is needed. By placing a properly rated 3600
ohm resistor in shunt with the load, (1200 ohms//3600 ohms=>900 ohms) latent
fault detection can be used.
108 Woodward
Manual 26167V1 MicroNet TMR
Woodward 109
MicroNet TMR Manual 26167V1
To retain circuit integrity if an external power supply is used for relay coil power,
the external power supply must be an isolated 24 Vdc source with +5%
regulation. It is recommended that a start-up routine be utilized to remove the
source during system power-up and power-down. This routine will guarantee that
no relay is inadvertently energized due to system power-up surges. (By using the
relay module’s internal relay coil power this start-up routine is automatically
performed.)
Each relay output has two banks of jumpers. One jumper-bank (a set of nine
jumpers) is used to match the latent fault detection circuit with the circuit voltage
to which it is being interfaced. The second jumper bank (a set of four jumpers) is
used to select which set of relay contacts (N.O. or N.C.) is tested by the latent
fault detection logic. During operation, only one set of relay contacts (normally
open or normally closed) can be tested. The set of relay contacts tested should
be same set of relay contacts used by the load. Refer to [Figure 14-11 and 14-
12]. Latent fault detection circuitry can be jumper configured to be compatible
with the following circuit voltages:
18-32 Vdc circuit power
88-132 Vac circuit power
100–150 Vdc circuit power
110 Woodward
Manual 26167V1 MicroNet TMR
After all jumper-banks have been correctly positioned, mark the placement of
each jumper-bank on the FT Relay/Discrete Input module cover labels. See the
figure below.
Configuration Notes
Woodward 111
MicroNet TMR Manual 26167V1
Refer to Figure 7-13 for relay output wiring.
Verify that each set of relay contacts meets the power requirements of the
circuit with which it is being used. Interposing relays are required in cases
where the interfaced circuit demands relay contacts with a higher power
rating. If interposing relays or other inductive loads are required, it is
recommended that interposing relays with surge (inductive kickback)
protection be used. Improper connection could cause equipment damage.
Verify that system power is off before removing or installing any relay
module jumper. Use ESD precautions when removing and installing relay
module jumper-banks.
Select internal or external relay coil power. If the control’s internal power is
used, verify that the relay module’s “Relay Coil Power Jumper” bank is in
the INT. position. If external relay coil power is supplied, move the relay
module’s “Relay Coil Power Jumper” bank to the EXT. position and verify
that the external source is fully isolated. (Mark the module’s label to indicate
jumper position.)
Verify that latent fault detection can be used with each relay output.
If latent fault detection cannot be used with the relay output, verify that the
relay’s latent fault detection jumper-banks are in their disabled positions.
(Mark the module’s label to indicate jumper position.) Alternatively, an
external resistor can be wired in parallel with the load to allow latent fault
detection to be used with the relay output. In this case it is the customer’s
responsibility to calculate the required resistor ratings and install the
resistor.
If latent fault detection can be used with the relay output, move the relay’s
latent fault detection jumper-bank to the correct position for the circuit
power. Also select which set of relay contacts (N.O. or N.C.) are to be tested
by the latent fault detection logic. (Mark the module’s labels to indicate
jumper positions.)
112 Woodward
Manual 26167V1 MicroNet TMR
7.2.4.6—Fault Detection (Module Hardware)
Each 24/12 TMR Discrete I/O module has a red Fault LED that is turned on when
the system is reset. During initialization of a 24/12 TMR Discrete I/O module,
which occurs after every CPU reset, the CPU turns the Fault LED on. The CPU
then tests each 24/12 TMR Discrete I/O module using diagnostic routines built
into the software. If the diagnostic test is not passed, the LED remains on or
blinks. If the test is successful, the LED goes off. If the Fault LED on a 24/12
TMR Discrete I/O module is illuminated after the diagnostics and initialization
have been run, the module may be faulty or may be located in the wrong slot.
Discrete Input Faults. The application software can detect faults by comparing
the inputs from the three kernels.
Discrete Output Faults. The module monitors relay coil voltage and contact
states. The contacts change state periodically to allow latent fault detection. The
application determines the course of action in the event of a fault.
Discrete Inputs
If a discrete input is not functioning properly, verify the following:
Measure the input voltage on the terminal block. It should be in the range of
18-32 Vdc for the low voltage input terminal blocks, or 100–150 Vdc for the
high voltage terminal blocks.
Check the wiring. If the inputs are reading open, look for a loose connection
on the terminal blocks, disconnected or misconnected cables, or a missing
jumper on the terminal block.
Check the software configuration to ensure that the input is configured
properly.
Woodward 113
MicroNet TMR Manual 26167V1
If the other channels on the 24/12 TMR Discrete I/O module are also not
working, check the fuse on the 24/12 TMR Discrete I/O module. See
instructions for module replacement in Chapter 21, Installation and Service.
This fuse is visible and can be changed through the bottom of the module. If
this fuse is blown, fix the wiring problem and replace the fuse with another
fuse of the same type and rating.
After verifying all of the above, remove the 24/12 TMR Discrete I/O module and
exchange the J1 and J2 cables. See instructions for replacing the module in
Chapter 21, Installation and Service. If the problem moves to a different channel,
replace the cable. If not, exchange the cables at the FT Relay/Discrete Input
modules so J1 is driving J2 and vice versa. If the problem moves to a different
input, replace the 24/12 TMR Discrete I/O module. If the fault remains with the
same input, replace the FT Relay/Discrete Input module. See instructions for
replacing the FT Relay/Discrete Input modules in Chapter 21, Installation and
Service.
Discrete Outputs
If a discrete output is not functioning properly, verify the following:
Check the wiring for a loose connection on the terminal blocks and
disconnected or misconnected cables.
Verify that the current through the relay contact does not exceed the contact
rating.
Make sure that if latent fault detection is being used, the trickle current
through the relay is insufficient to energize the relay load. See Figures 15-8
through 15-10.
If the other output channels on the 24/12 TMR Discrete I/O module are also
not working, check the fuse on the 24/12 TMR Discrete I/O module. See
instructions for module replacement in Chapter 21, Installation and Service.
This fuse is visible and can be changed through the bottom of the module. If
this fuse is blown, fix the wiring problem and replace the fuse with another
fuse of the same type and rating.
Check the software configuration to ensure that the output is configured
properly.
After verifying all of the above, remove the 24/12 TMR Discrete I/O module and
exchange the J1 and J2 cables. See instructions for replacing the module in
Chapter 21, Installation and Service. If the problem moves to a different channel,
replace the cable. If not, exchange the cables at the FT Relay/Discrete Input
modules so J1 is driving J2 and vice versa. See instructions for replacing the
module in Chapter 21, Installation and Service. If the problem moves to a
different relay, replace the 24/12 TMR Discrete I/O module or the relay. See
instructions for replacing the FT Relay/Discrete Input modules and relays in
Chapter 21, Installation and Service. If the fault remains with the same relay,
replace the relay or the FT Relay/Discrete Input module.
114 Woodward
Manual 26167V1 MicroNet TMR
Configuration 1 consists of one 48/24 Discrete FTM connected to the 48/24
Discrete Combo module via two High Density Analog/Discrete cables. The 48/24
Discrete FTM is then connected to either two 16 Ch Relay Modules or one 32 Ch
Relay Module via a Low Density Discrete Cable(s).
The discrete inputs are optically isolated and accessible through either the 48/12
Discrete FTM or the 24/12 Discrete FTM depending on the configuration. The
discrete outputs are accessible through either the 24/12 Discrete FTM or the two
16 Ch Relay Modules or the one 32 Ch Relay Module when so configured. See
Figures 7-15 and 7-20 for examples of configurations.
7.3.2—Module Specification
Discrete Inputs
Number of channels: 48
Update time: 5 ms
Input type: Optically isolated discrete input
(galvanically isolated)
Woodward 115
MicroNet TMR Manual 26167V1
48/24 Discrete FTM
Input thresholds:
Low voltage: 8 Vdc at 1.5 mA = “OFF”
> 16 Vdc at 3 mA = “ON”
High voltage: <29 Vdc at 1.8 mA = “OFF”
>67 Vdc at 4 mA = “ON”
Input current: 4 mA @ 24 Vdc; 2.6–5 mA @ 125 Vdc
External input voltage: 18–32 Vdc (UL and LVD), or 100–150
Vdc (UL) w/ high Voltage FTM
Isolation voltage: 500 Vdc to earth ground, 1000 Vdc to
control common
Time stamping: 1 ms resolution
Isolated 24 Vdc contact supply: 400 mA maximum
For the 24/12 Discrete FTM input specifications, see Chapter 12.
Discrete Outputs
Number of channels: 24
Update time: 5 ms
For the 24/12 Discrete FTM, 16 Ch Relay Module, and the 32 Ch Relay Module
output specifications, see Chapter 12.
7.3.3—Installation
The modules slide into card guides in the control's chassis and plug into the
motherboard. The modules are held in place by two screws, one at the top and
one at the bottom of the front panel. Also at the top and bottom of the module are
two handles which, when toggled (pushed outward), move the modules out just
far enough for the boards to disengage the motherboard connectors.
There are two different FTM I/O configurations for the 48/12 Discrete Combo
Module.
Configuration 1
Configuration 1 consists of one 24 Vdc or 125 Vdc 48/24 Discrete FTM
connected to the 48/24 Discrete Combo module via two High Density
Analog/Discrete cables. The top connector on the 48/24 Discrete Combo module,
which is labeled J1, connects to J1 on the 48/24 Discrete FTM, and J2 connects
to J2. There are two versions of the FTM, one for 24 Vdc inputs, and one for 125
Vdc inputs. The LVD applies only to the 24 Vdc version. The 24 Vdc 48/24
Discrete FTM handles 24 Vdc input signals and the 125 Vdc 48/24 Discrete FTM
handles 125 Vdc input signals. Either 48/24 Discrete FTM is then connected to
either two 16 Ch Relay Modules or one 32 Ch Relay Module via a Low Density
Discrete Cable(s) via the third connector. See Figure 7-15 for an example of
configuration.
116 Woodward
Manual 26167V1 MicroNet TMR
J1
P1
J2
P1
Low Density
Discrete Cable
P1
J1
32Ch Relay Module
P2 P2 P2 OR Low Density
J1 J2 J3 Discrete Cable
24VDC 48/24 Discrete FTM or
P1
J1
P1
P2
J1
J2
125VDC 48/24 Discrete FTM
16Ch Relay Module 16Ch Relay Module
All of the discrete inputs on the module are accessible on the FTM, and the
channels are labeled to correspond to their designation in the application
software (discrete input 1 on the FTM will be discrete input 1 in the application
software).
Discrete Inputs
Each 48/24 Discrete Combo module accepts 48 contact inputs. The 48/24
Discrete FTM may supply contact wetting voltage. Optionally, an external 18–32
Vdc power source or an external 100–150 Vdc power source can be used to
source the circuit wetting voltage. If the 24 Vdc internal power source is used for
contact wetting, a jumper is required between FTM terminals 98 and 99. If an
external power source is used for contact wetting, the external source’s common
must be connected to the FTM’s discrete input common, terminal 49. If 125 Vdc
contact inputs are needed, the High Voltage (125 Vdc) FTM must be used. The
FTM provides a common cage-clamp terminal connection for customer field
wiring. Figures 7-16 and 7-17 illustrate different discrete input wiring
configurations based on the input voltage.
Woodward 117
MicroNet TMR Manual 26167V1
Figure 7-17—Discrete Input Interface Wiring to a 125 Vdc 48/24 Discrete FTM
HIGH VOLTAGE—If the high voltage FTM is being used, and there is
125 Vdc on the FTM terminal blocks, there will be 125 Vdc on the FTM
sub D connectors and on the cable when it is connected to the FTM.
For this reason, any power should be removed from the FTM terminal
blocks before installing the 48/24 Discrete Combo module or the
FTM.
Configuration Notes:
Refer to Chapter 12 for Discrete Input wiring.
Each 48/24 Discrete I/O module can only accept one input voltage range, 24
Vdc (LVD and UL) or 125 Vdc (UL only).
All contact inputs accept dry contacts.
24 Vdc FTM only—If the internal 24 Vdc is used, a jumper must be added to
tie the internal 24 Vdc to the bussed power terminal blocks (see Figure
6-16).
24 Vdc FTM only—If an external 24 Vdc is used, the common for the
external 24 Vdc must be tied to the discrete input common (see Figure
6-16). Power for contacts must be supplied by the control’s power supplies,
or the external power supply outputs must be rated to Class II at 30 Vdc or
less and outputs must be fused with appropriately sized fuses (a maximum
current rating of 100 V, where V is the supply’s rated voltage or 5 A,
whichever is less).
High Voltage FTM only—The common for the 125 Vdc must be tied to the
discrete input common (see Figure 7-17).
118 Woodward
Manual 26167V1 MicroNet TMR
Discrete Outputs
For the 48/24 Discrete Combo FTM configuration, there are three types of relay
output boxes that can be used. These consist of the 16 Ch Relay (Phoenix)
Module, 16 Ch Relay Module, and the 32 Ch Relay Module (see Chapter 12 for a
description of the available modules). The relay modules connect to the 48/24
Discrete FTM through individual cables and provide a common cage-clamp
terminal connection for customer field wiring. The discrete outputs on the 48/24
Discrete I/O module are non-isolated; the isolation takes place in the relay boxes.
Discrete outputs 9, 10, 11, 12, 21, 22, 23, and 24, drive two relays per output
(see Table 7-2). Internal wiring on the 48/24 Discrete I/O FTM provides this dual
relay functionality. The application software may use these relays for outputs
where extra relay contacts are needed, such as alarm or shutdown outputs.
Figures 7-18 and 7-19 illustrate examples of different discrete output wiring
configurations.
Woodward 119
MicroNet TMR Manual 26167V1
Configuration Notes
Verify that each set of relay contacts meets the power requirements of the
circuit with which it is being used. Interposing relays are required when the
interfaced circuit demands relay contacts with a higher power rating. If
interposing relays or other inductive loads are required, it is recommended
that interposing relays with surge (inductive kickback) protection be used.
Improper connection could cause serious equipment damage.
Configuration 2
Configuration 2 consist of two 24/12 Discrete FTMs (DIN rail mounted)
connected to the 48/24 Discrete Combo module via two High Density
Analog/Discrete cables. See Figure 7-20 for an example of configuration.
J1
P1
J2
P1
P2
J1
P2
J1
120 Woodward
Manual 26167V1 MicroNet TMR
Both the 48 discrete inputs and 24 discrete outputs are wired to the 24/12
Discrete FTM. An external 24 Vdc source connection to the FTM is required for
discrete input contact sensing and relay coil energizing. For wiring information on
the 24/12 Discrete FTM, see Chapter 12.
Discrete Inputs
Each 24/12 Discrete FTM accepts 24 contact inputs. The 24/12 Discrete FTM
may supply contact wetting voltage. Optionally, an external 18–32 Vdc power
source can be used to source the circuit wetting voltage. If the 24 Vdc internal
power source is used for contact wetting, a jumper is required between FTM
terminals on TB9. If an external power source is used for contact wetting, the
external source’s common must be connected to the FTM’s discrete input
common, terminal 49 (see Figure 7-21).
Internal External
TB6
Channel 1 1
25
Field Contacts
Channel 2 2
26
48/24
Discrete
Combo TB9
Module
Jumper
Optional
TB8 External
Excitation
+24VDC 50 NC
24Ret 49
TB10
Cable
91 Ground to
Sheild
DIN rail
92
Configuration Notes:
Refer to Chapter 12 for Discrete Input wiring.
All contact inputs accept dry contacts.
If the internal 24 Vdc is used, a jumper must be added to tie the internal 24
Vdc to the bussed power terminal blocks (see Figure 7-21).
If an external 24 Vdc is used, the common for the external 24 Vdc must be
tied to the discrete input common (see Figure 7-21). Power for contacts
must be supplied by the control’s power supplies, or the external power
supply outputs must be rated to Class II at 30 Vdc or less and outputs must
be fused with appropriately sized fuses (a maximum current rating of 100/V,
where V is the supply’s rated voltage, or 5 A, whichever is less).
Woodward 121
MicroNet TMR Manual 26167V1
Discrete Outputs
The discrete outputs on the 48/24 Discrete I/O module are non-isolated; the
isolation takes place in the 24/12 Discrete FTM. See Chapter 12 for field wiring of
discrete output relays. Figure 7-22 illustrates an example of a discrete output
wiring configuration.
Internal External
TB1
K1 +V
53
U1
K1 52 Relay 1
Channel 1 51
48/24
Discrete
Load
Combo
Module
K13 K13
IO Lock TB3
47 +24VDC (A)
48 24Ret (A)
49 +24VDC (B)
Optional
50 24Ret (B)
Configuration Notes
Verify that each set of relay contacts meets the power requirements of the
circuit with which it is being used. Interposing relays are required when the
interfaced circuit demands relay contacts with a higher power rating. If
interposing relays or other inductive loads are required, it is recommended
that interposing relays with surge (inductive kickback) protection be used.
Improper connection could cause serious equipment damage.
7.3.4—FTM Reference
See Chapter 12 for detailed wiring of FTMs. See Appendix A for part number
Cross Reference for modules, FTMs, and cables.
7.3.5—Troubleshooting
Fault Detection (Module Hardware)
Each 48/24 Discrete Combo module has a red Fault LED that is turned on when
the system is reset. During initialization of a 48/24 Discrete Combo module,
which occurs after every CPU reset, the CPU turns the Fault LED on. The CPU
then tests each 48/24 Discrete Combo module using diagnostic routines built into
the software. If the diagnostic test is not passed, the LED remains on or blinks. If
the test is successful, the LED goes off. If the Fault LED on a 48/24 Discrete
Combo module is illuminated after the diagnostics and initialization have been
run, the module may be faulty or may be located in the wrong slot.
122 Woodward
Manual 26167V1 MicroNet TMR
Woodward 123
MicroNet TMR Manual 26167V1
Discrete Inputs
If a discrete input is not functioning properly, verify the following:
1. Measure the input voltage on the terminal block. It should be in the range of
16–32 Vdc for the low voltage FTM or 100–150 Vdc for the high voltage
FTM.
2. Check the wiring. If the inputs are reading open, look for a loose connection
on the terminal blocks, disconnected or misconnected cables, or a missing
jumper on the terminal block.
3. Check the application software configuration to ensure that the input is
configured properly.
4. If the other channels on the 48/24 Discrete Combo module are not working
either, check the fuse on the 48/24 Discrete Combo module. See the
instructions in Chapter 15 for replacing the module. This fuse is visible and
can be changed through the bottom of the module. If this fuse is blown, fix
the wiring problem and replace the fuse with another fuse of the same type
and rating.
5. After verifying all of the above, exchange the J1 and J2 cables. If the
problem moves to a different channel, replace the cable. If not, replace the
48/24 Discrete Combo module.
6. If the readings are incorrect on several channels of the 48/24 Discrete
Combo module, corresponding to both cables, replace the 48/24 Discrete
Combo module.
7. If replacing the module does not fix the problem, replace the FTM. See the
instructions in Chapter 15 for replacing the FTM.
Discrete Outputs
If a discrete output is not functioning properly, verify the following:
1. Check the wiring for a loose connection on the terminal blocks, or
disconnected or misconnected cables.
2. Verify that the current through the relay contacts is not greater than the relay
contact rating.
3. If the other output channels on the 48/24 Discrete Combo module are not
working either, check the fuse on the 48/24 Discrete Combo module. See
the instructions in Chapter 15 for replacing the module. This fuse is visible
and can be changed through the bottom of the module. If this fuse is blown,
fix the wiring problem and replace the fuse with another fuse of the same
type and rating.
4. Check the software configuration to ensure that the output is configured
properly.
5. After verifying all of the above, exchange the J1 and J2 cables. If the
problem moves to a different channel, replace the cable. If not, exchange
the cables at the FTM, so J1 is driving J2 and vice versa. If the problem
moves to a different relay, replace the 48/24 Discrete Combo module. If the
fault stays with the same relay, replace the relay or the relay module. See
instructions for replacing the relay modules in Chapter 15. If replacing the
relay module does not fix the problem, replace the cable between the relay
module and the FTM, or replace the FTM itself. See the instructions in
Chapter 15 for replacing the FTM.
124 Woodward
Manual 26167V1 MicroNet TMR
Woodward 125
MicroNet TMR Manual 26167V1
7.4.2—Module Specification
Number of Channels: 48
Input Type: Optically isolated discrete input
Input Thresholds: < 8 Vdc = "OFF"
> 16 Vdc = "ON"
Input Current: 3 mA @ 24 Vdc
Contact Power: Module provides isolated 24 Vdc, 0.3 A
7.4.3—Installation
The modules slide into card guides in the control's chassis and plug into the
motherboard. The modules are held in place by two screws, one at the top and
one at the bottom of the front panel. Also at the top and bottom of the module are
two handles which, when toggled (pushed outward), move the modules out just
far enough for the boards to disengage the motherboard connectors.
J1
P1
J2
P1
P2
J1
24VDC Discrete Input/Output FTM
or
Discrete Input (With LEDS) FTM
P2
J1
24VDC Discrete Input/Output FTM
or
Discrete Input (With LEDS) FTM
126 Woodward
Manual 26167V1 MicroNet TMR
Each 48 Ch DI Module accepts 48 contact inputs. Contact wetting voltage may
be supplied by the 48 Ch DI Module internal power supply. The supply can only
supply 300 mA and therefore should not be used with the Discrete Input (with
LEDs) FTM. If an external power source (18–32 Vdc) is supplied, the Discrete
Input (with LEDs) FTM may be used. Figures 7-26 and 7-27 illustrate different
discrete input wiring configurations based on internal or external power source.
Internal External
TB1
Channel 1 1
Channel 2 2
Field Contacts
Channel 3 3
Channel 4 4
48Ch DI
Module
24Ret 25 NC
26
+24VDC 54
Internal External
TB1
Channel 1 1
Channel 2 2
Field Contacts
Channel 3 3
Channel 4 4
+
48Ch DI
Power
Module
1.21K Source
Ohms
-
24Ret 25
26
+24VDC 54
Configuration Notes:
Refer to Chapter 12 for Discrete Input wiring.
All contact inputs accept dry contacts.
Woodward 127
MicroNet TMR Manual 26167V1
7.4.4—FTM Reference
See Chapter 12 for detailed wiring of FTMs. See Appendix A for part number
Cross Reference for modules, FTMs, and cables.
7.4.5—Troubleshooting
Fault Detection (Module Hardware)
Each 48 Ch DI module has a red Fault LED that is turned on when the system is
reset. During initialization of a 48 Ch DI module, which occurs after every CPU
module reset, the CPU turns the Fault LED on. The CPU module via the VME
bus turns off the Fault LED when the CPU has started execution of the
application program and verified that the board is present.
Figure 7-28 is a block diagram of the Discrete Input module. The module
receives information from as many as 48 field switches and relays. Field wiring is
isolated from the MicroNet circuitry by optical isolators in each channel; the state
of each discrete input is passed through an optoisolator to the buffers. The CPU
then obtains the data for each channel through the VME interface.
128 Woodward
Manual 26167V1 MicroNet TMR
If a discrete input is not functioning properly, verify the following:
1. Measure the input voltage on the terminal block of the FTM. It should be in
the range of 16–32 Vdc.
2. Check the wiring. If the inputs are reading open, look for a loose connection
on the terminal blocks, disconnected or misconnected cables, or a missing
jumper on the terminal block.
3. Check the application software configuration to ensure that the input is
configured properly.
4. If the other channels on the 48 DI module are not working either, check the
fuse on the 48 DI module. See the instructions in Chapter 15 for replacing
the module. This fuse is visible and can be changed through the bottom of
the module. If this fuse is blown, fix the wiring problem and replace the fuse
with another fuse of the same type and rating.
5. After verifying all of the above, exchange the J1 and J2 cables. If the
problem moves to a different channel, replace the cable. If not, replace the
48 DI module.
6. If replacing the module does not fix the problem, replace the FTM. See the
instructions in Chapter 15 for replacing the FTM.
7.5.2—Module Specification
Number of channels: 32
Update time: 5 ms
Output Type: Open drain drivers, intended for use
with Woodward relay interface modules.
Fault Detection Readback: Output channel status, relay status is
not available
System Faults: Outputs are turned off if
communications with the CPU is lost.
For the 16 Ch Relay Module and the 32 Ch Relay Module output specifications,
see Chapter 12.
Woodward 129
MicroNet TMR Manual 26167V1
7.5.3—Installation
The modules slide into card guides in the control's chassis and plug into the
motherboard. The modules are held in place by two screws, one at the top and
one at the bottom of the front panel. Also at the top and bottom of the module are
two handles which, when toggled (pushed outward), move the modules out just
far enough for the boards to disengage the motherboard connectors.
This module receives digital data from the CPU and generates 32 non-isolated
relay driver signals. All discrete output modules in the system interface to one or
more Woodward Relay Modules, each with 16 or 32 relays. The contacts of
these relays then connect to the field wiring.
A separate 24 Vdc power source must be provided for the relays; this module
does not furnish this power. A section of a multi-output Main Power Supply can
be used, or power from a single-output Main Power Supply can be used, as long
as sufficient current is available.
130 Woodward
Manual 26167V1 MicroNet TMR
J1
P1
P2 P2
P1
P2
J2
J1
J1 J1
Figures 7-31 and 7-32 illustrate examples different discrete output wiring
configurations.
Woodward 131
MicroNet TMR Manual 26167V1
Configuration Notes
Verify that each set of relay contacts meets the power requirements of the
circuit with which it is being used. Interposing relays are required when the
interfaced circuit demands relay contacts with a higher power rating. If
interposing relays or other inductive loads are required, it is recommended
that interposing relays with surge (inductive kickback) protection be used.
Improper connection could cause serious equipment damage.
7.5.4—FTM Reference
See Chapter 12 for detailed wiring of relay modules. See Appendix A for part
number Cross Reference for modules, FTMs, and cables.
7.5.5—Troubleshooting
Figure 7-33 is a block diagram of the 32-Channel Discrete Output module. The
CPU sends the address of this module and the address and state of the channel
to be output to this module. This information is received by the VME interface
and passed to the latches. The latch associated with the channel to be output
stores the information and passes it to the drivers. The driver for that channel
then energizes or de-energizes the relay for that channel.
Each channel has a readback buffer that indicates the status of the output driver
(not the relay). The CPU compares this status to the value written to the channel
and generates a fault signal if these two values are different. The relay module
power is turned off if communications with the CPU are lost or a fault is detected.
132 Woodward
Manual 26167V1 MicroNet TMR
RELAY
POWER TO
ENABLE WOODWARD
RELAY
CHANNELS MODULE
1-32
LATCHES DRIVERS
VME
VME
INTER-
BUS
FACE
BUFFERS
FAULT
LED
Woodward 133
MicroNet TMR Manual 26167V1
The MicroNet control can provide discrete outputs to the prime mover from field
wiring. Each of this type Discrete Output (DO) module can individually control 64
outputs according to commands from the CPU module. These modules have no
potentiometers and require no calibration. A module may be replaced with
another module of the same part number without any adjustment. There are
several different FTM I/O configurations for the 64 Ch DO Module. The module
can be connected to two 32 Ch Relay Module, four 16 Ch Relay Modules, or a
combination of the two types (see Chapter 12 for additional information on the
relay modules).
134 Woodward
Manual 26167V1 MicroNet TMR
7.6.2—Module Specification
Number of channels: 64
Update time: 5 ms
Output Type: Open drain drivers, intended for use
with Woodward relay interface modules.
Fault Detection Readback: Output channel status, relay status is
not available
System Faults: Outputs are turned off if
communications with the CPU is lost.
For the 16 Ch Relay Module, and the 32 Ch Relay Module output specifications,
see Chapter 12.
7.6.3—Installation
The modules slide into card guides in the control's chassis and plug into the
motherboard. The modules are held in place by two screws, one at the top and
one at the bottom of the front panel. Also at the top and bottom of the module are
two handles which, when toggled (pushed outward), move the modules out just
far enough for the boards to disengage the motherboard connectors.
This module receives digital data from the CPU and generates 64 non-isolated
relay driver signals. All discrete output modules in the system interface to one or
more Woodward Relay Modules, each with 16 or 32 relays. The contacts of
these relays then connect to the field wiring.
A separate 24 Vdc power source must be provided for the relays; this module
does not furnish this power. A section of a multi-output Main Power Supply can
be used, or power from a single-output Main Power Supply can be used, as long
as sufficient current is available.
Woodward 135
MicroNet TMR Manual 26167V1
J1
P1
J2
P1
P2 P2
P1
P2
J2
J1
J1 J1
32Ch Relay Module 16Ch Relay Module 16Ch Relay Module
(Channels 33-64) (Channels 33-48) (Channels 49-64)
P2
J2
J1
J1 J1
32Ch Relay Module 16Ch Relay Module 16Ch Relay Module
(Channels 1-32) (Channels 1-16) (Channels 17-32)
Figures 7-36 and 7-37 illustrate examples different discrete output wiring
configurations.
136 Woodward
Manual 26167V1 MicroNet TMR
Configuration Notes
Verify that each set of relay contacts meets the power requirements of the
circuit with which it is being used. Interposing relays are required when the
interfaced circuit demands relay contacts with a higher power rating. If
interposing relays or other inductive loads are required, it is recommended
that interposing relays with surge (inductive kickback) protection be used.
Improper connection could cause serious equipment damage.
7.6.4—FTM Reference
The 64 Ch DO Module uses the same relay modules as the 32 Ch DO Module.
See the previous section.
7.6.5—Troubleshooting
The 64 Ch DO Module uses the same relay modules as the 32 Ch DO Module
and therefore has the same troubleshooting approach as the 32 Ch DO Module.
See the previous section.
Woodward 137
MicroNet TMR Manual 26167V1
Chapter 8.
Analog I/O Modules
8.1—Introduction
This chapter contains information on those modules that are classified as analog
I/O modules. There are two types analog I/O modules. There are the single
function type modules and the combination modules. The combination modules
consist of more than one type of input or output. The single type modules consist
of a single type of I/O, such as all 4–20 mA inputs.
The TMR 24/8 Analog module comes in the following configuration: 24 channels
of 4–20 mA inputs with 8 channels of 4–20 mA outputs (2-pole 10 ms filter on all
input channels, except channels 23 and 24, which have 2-pole 5 ms filter).
All 4–20 mA analog inputs may be used with two-wire ungrounded (loop
powered) transducers or isolated (self-powered) transducers. All analog inputs
have 200 Vdc of common mode rejection. If interfacing to a non-isolated device,
which may have the potential of reaching over 200 Vdc with respect to the
control’s common, the use of a loop isolator is recommended to break any return
current paths producing erroneous readings.
Each board has an on-board processor for automatic calibration of the I/O
channels. Each analog input incorporates a time-stamping feature with 5 ms
resolution for two low setpoints and two high setpoints.
138 Woodward
Manual 26167V1 MicroNet TMR
8.3.2—Module Specification
Analog Input Ratings
Number of channels: 24
Update time: 5 ms
Input range: 0–25 mA; software and hardware selectable
The maximum voltage input range may vary between 4.975 and 5.025
Volts from module to module.
The 24 channel analog inputs are divided into two banks, with
channel 1 through channel 12 data gathering at 1.8 ms after the MFT
tick and channel 13 through channel 24 data gathering at 3.7 ms after
the MFT tick.
Woodward 139
MicroNet TMR Manual 26167V1
4–20 mA Output Ratings
Number of channels: 8
Update time: 5 ms
Output Driver: Pulse Width Modulated (PWM)
PWM frequency: 6.14 kHz
Filter: 3 poles at 500 ms
Current output: 4–20 mA
Current output range: 0–25 mA
Isolation: 0 Vrms
Max load resistance: 600 ohms (load + wire resistance)
Current readback: 8 bits
Readback isolation: 60 dB CMRR, 200 Vdc common mode rejection
voltage
Resolution: 11 bits
Accuracy: Software calibrated to 0.2% of 0–25 mA full
scale
Temperature drift: 125 ppm/C, maximum
Readback accuracy: 0.5% of 0–25 mA full scale
Readback temp drift: 400 ppm/C, maximum
8.3.3—Installation
The modules slide into card guides in the control's chassis and plug into the
motherboard. The modules are held in place by two screws, one at the top and
one at the bottom of the front panel. Also at the top and bottom of the module are
two handles which, when toggled (pushed outward), move the modules out just
far enough for the boards to disengage the motherboard connectors.
Three 24/8 Analog I/O modules are connected through six high density 62
conductor analog cables (two from each module) to two 24/8 Analog I/O FTMs.
Each 24/8 Analog I/O module has two sub D connectors on the front panel. The
top sub D connector contains the first half of the channels (analog input channels
1-12 and analog output channels 1-4) and the bottom sub D connector contains
the second half of the I/O channels. See Figure 8-2 for an example.
140 Woodward
Manual 26167V1 MicroNet TMR
Analog Inputs
For a 4–20 mA input signal, the 24/8 Analog Module uses a 200 ohm resistor
across the input located on the 24/8 Analog Module. Each analog input channel
may power its own 4–20 mA transducer. See Figure 8-3 for analog input
connection. This power is protected with a 100 mA fuse on each channel to
prevent an inadvertent short from damaging the module. The 24 Vdc outputs are
capable of providing 24 Vdc with ±10% regulation. The maximum current is 0.8
A. Power connections can be made through terminals located on the 24/8 Analog
FTMs. See Chapter 12 for complete field wiring information for the 24/8 Analog
FTM.
When configuring the AI Combo block in GAP, set Conf. input field to
1 for all inputs when used with the 24/8 Analog FTM. This will allow
the block to use the module factory calibration values for the 4–20
mA inputs that were calibrated with 200 ohm internal resistors on the
24/8 Analog Module.
Woodward 141
MicroNet TMR Manual 26167V1
Analog Outputs
There are 8 analog output channels of 4–20 mA with a full scale range of 0–25
mA. All Analog Outputs can drive a maximum load of 600 ohms (load + wire
resistance). See Figure 8-4 for analog output connection. Each output monitors
the output source current for fault detection. All of the analog outputs may be
individually disabled. When a channel fault or a module fault is detected, the
application program may annunciate the fault, disable the channel and stop using
data in system calculations or control. Care should be taken to prevent ground
loops and other faults when interfacing to non-isolated devices. See Chapter 12
for complete field wiring information for the Analog High Density FTM.
8.3.4—FTM Reference
See Chapter 12 for complete field wiring information for the Analog High Density
FTM. See Appendix A for part number Cross Reference for modules, FTMs, and
cables.
8.3.5—Troubleshooting
Each 24/8 Analog module has a red Fault LED that is turned on when the system
is reset. During initialization of a module, which occurs after every CPU reset, the
CPU turns the Fault LED on. The CPU then tests each module using diagnostic
routines built into the software. If the diagnostic test is not passed, the LED
remains on or blinks. If the test is successful, the LED goes off. If the Fault LED
on a module is illuminated after the diagnostics and initialization have been run,
the module may be faulty or may be located in the wrong slot.
142 Woodward
Manual 26167V1 MicroNet TMR
Fault Detection (I/O)
In addition to detecting the High Density Analog I/O module hardware faults, the
application software may detect I/O faults.
Analog Input Faults: The application software may be set with a high and low
latch setpoint to detect input faults.
Analog Output Driver Faults: The module monitors the source currents and
annunciates faults. The application software determines the course of action in
the event of a fault.
Troubleshooting Guide
If during normal control operation all of a chassis’ 24/8 Analog I/O modules have
Fault LEDs on, check the kernel’s CPU module for a failure. If during normal
control operation only the 24/8 Analog I/O module’s Fault LED is on or flashing,
ensure that it is installed in the correct slot. If it is, then replace that 24/8 Analog
I/O module. See instructions for replacing the module in Chapter 21, Installation
and Service. When a module fault is detected, its outputs should be disabled or
de-energized.
Analog Inputs
If an analog input is not functioning properly, verify the following:
Check that the cable is shielded and the shield is properly grounded per the
section on Shields and Grounding in Chapter 21, Installation and Service.
Measure the input voltage on the terminal block. It should be in the range of
0–5 V.
Look at the individual inputs into each kernel. Each 24/8 Analog I/O module
reads the same input from the FTM, so the application software should
contain three separate numbers, one from each 24/8 Analog I/O module.
The numbers should be within 0.1% of each other unless a high common
mode voltage is present.
If all of the 24/8 Analog I/O modules are reading approximately the same
number, but the reading is incorrect, go to step 1. If two of the 24/8 Analog
I/O modules are reading correctly, but one is reading incorrectly, go to step
2.
Woodward 143
MicroNet TMR Manual 26167V1
1. Check the wiring. If the inputs are reading 0 or the engineering units that
correspond to 0 mA, look for a loose connection on the terminal blocks,
disconnected or misconnected cables, a missing jumper on the terminal
block if the input is a loop powered current input, or a blown fuse on the 24
Vdc on the FTM. See instructions for replacing the fuse on the FTM below. If
all of the inputs are reading high, check to ensure that the 24 Vdc is not
connected across the input directly. Check the fuse on the 24/8 Analog I/O
module. See instructions for replacing the module in Chapter 21, Installation
and Service. This fuse is visible and can be changed through the bottom of
the module. If this fuse is blown, fix the wiring problem and replace the fuse
with a fuse of the same type and rating. Check the application software
configuration to ensure that the input is configured properly. If the
connections and application software are verified and the correct voltage is
present on the terminal block, but all of the 24/8 Analog I/O modules are
reading 0 V, exchange FTM #1 with FTM #2. See instructions for replacing
the FTM in Chapter 15. If the problem follows the FTM, replace the FTM.
The FTM contains only a wire wound 3 W resistor and traces, so failure is
extremely unlikely.
2. If one or two of the 24/8 Analog I/O modules are reading the correct
number, but the other 24/8 Analog I/O module(s) is (are) incorrect, check
the application software configuration of the modules with the non-working
channels, and check to ensure that the cables are connected properly. If the
other channels on the same 24/8 Analog I/O module are not working either,
check the fuse on the 24/8 Analog I/O module. See instructions for replacing
the module in Chapter 21, Installation and Service. This fuse is visible and
can be changed through the bottom of the module. If this fuse is blown, fix
the wiring problem and replace the fuse with a fuse of the same type and
rating. If the reading is still incorrect, but the other readings from the 24/8
Analog I/O module are correct, remove the 24/8 Analog I/O module and
exchange the J1 and J2 cables. If the problem moves to a different channel,
replace the cable. If not, replace the 24/8 Analog I/O module. If the readings
are incorrect on several channels of the 24/8 Analog I/O module,
corresponding to both cables, replace the 24/8 Analog I/O module.
Analog Outputs
If an analog output is not functioning properly, verify the following:
Check that the cable is shielded and the shield is properly grounded Shields
and Grounding section in Chapter 21, Installation and Service.
Check the load resistance to ensure that it is below 600 ohms.
Check to ensure that the load wiring is isolated.
Disconnect the field wiring and connect a resistor across the output. If the
output current is 0 mA, go to step 1. If the output current is correct, but some
of the outputs have a fault, go to step 2.
144 Woodward
Manual 26167V1 MicroNet TMR
1. Check the wiring for a loose connection on the terminal blocks or
disconnected or misconnected cables. If none of the outputs on a given 24/8
Analog I/O module are functioning, check the 24/8 Analog I/O module fuse.
See instructions for replacing the module in Chapter 21, Installation and
Service. This fuse is visible and can be changed through the bottom of the
module. If the fuse is blown, fix the wiring problem and replace the fuse with
a fuse of the same type and rating. Check the application software
configuration to ensure that the output is configured properly. If the
connections and application software are verified, exchange FTM #1 with
FTM #2. See instructions for replacing the FTM in Chapter 15. If the
problem follows the FTM, replace the FTM. The FTM contains only traces
and a few discrete components, so failure is extremely unlikely.
2. If one or two of the 24/8 Analog I/O modules have an output fault, but the
other module(s) does (do) not, check the application software, and check to
ensure that the cables are connected properly. If the other output channels
on the same 24/8 Analog I/O module are also not working, check the fuse
on the 24/8 Analog I/O module. See instructions for replacing the module in
Chapter 21, Installation and Service. This fuse is visible and can be
changed through the bottom of the module. If the fuse is blown, fix the wiring
problem and replace the fuse with a fuse of the same type and rating. If the
output still has a fault, but the other output channels on the 24/8 Analog I/O
module are functioning properly, remove the 24/8 Analog I/O module and
exchange the J1 and J2 cables. If the problem moves to a different channel,
replace the cable. If not, replace the 24/8 Analog I/O module. If the readings
are incorrect on several channels of the 24/8 Analog I/O module,
corresponding to both cables, replace the same 24/8 Analog I/O module.
If power has not been removed from the control system, power will
be active at the module and also at the FTM. Shorting of protected
circuitry could cause a control system shutdown.
2. Remove FTM cover carefully, to prevent contact with any FTM circuitry
under the cover. To remove the FTM cover, pinch the retaining barb and lift
the cover.
3. Locate and replace the fuse with another fuse of the same size, type, and
rating. See Figure 12-12 or Figure 12-13 for channel fuse location.
Woodward 145
MicroNet TMR Manual 26167V1
There are two configurations of the Analog Combo Modules. One has the analog
inputs configured for 4–20 mA and the other is configured for 0–5 V. See
Appendix A for specific part numbers. In a simplex system, either Analog Combo
module is connected through two analog cables to one Analog Combo FTM. All
of the I/O are accessible on the FTM, and the channels are labeled to correspond
to their software locations, e.g. analog input 1 on the FTM will be analog input 1
in the application software.
146 Woodward
Manual 26167V1 MicroNet TMR
8.4.2—Module Specifications
Digital Speed Sensor Inputs
Number of channels: 4
Update time: 5 ms
MPU Input Ratings
Input frequency: 100 - 25000 Hz
Input amplitude: 1-25 Vrms
Input impedance: 2000 Ohms
Isolation voltage: 500 Vrms
Resolution: 12 bits minimum over chosen frequency range
Accuracy: 0.03% full scale, minimum
Proximity Probe Input Ratings
Input frequency: 0.5 - 25000 Hz
Input amplitude: 3.5 - 32 Vdc input to the module
Available power: 12 Vdc or 24 Vdc, 50 mA maximum
Isolation voltage: 0 Vrms
Resolution: 12 bits minimum over chosen frequency range
Accuracy: Software calibrated to 0.03% full scale
Fuse: 24 Vdc 100 mA fuse/channel, 12 Vdc short
circuit protected
Time Stamping: 5 millisecond resolution on low event and low
latch
Analog Input Ratings
Number of channels: 8
Update time: 5 millisecond
Input range: 0–25 mA
The maximum input voltage range may vary between 4.975 and 5.025
Volts from module to module.
88.4.3—Installation
The modules slide into card guides in the control's chassis and plug into the
motherboard. The modules are held in place by two screws, one at the top and
one at the bottom of the front panel. Also at the top and bottom of the module are
two handles which, when toggled (pushed outward), move the modules out just
far enough for the boards to disengage the motherboard connectors.
Three MPU and Analog I/O modules are connected through six analog cables (two
from each module) to two FTMs. Each MPU and Analog I/O module has two sub D
connectors on the front panel. The top sub D connector contains the first half of the
channels (speed sensor channels 1 and 2, actuator channel 1, analog output
channels 1 and 2, and analog input channels 1-4), and the bottom sub D connector
contains the second half of the I/O channels. See Figure 8-6 for an example.
148 Woodward
Manual 26167V1 MicroNet TMR
Field Wiring
See Chapter 12 for complete wiring connections for the TMR Analog Combo
FTM. Wire each channel per the following examples for each type of signal.
Any of the module’s four speed channels accepts passive magnetic pickup units
(MPUs) or proximity probes. Each speed input channel can only accept one MPU
or one proximity probe.
A proximity probe may be used to sense very low speeds. With a proximity
probe, speed can be sensed down to 0.5 Hz. When interfacing to open collector
type proximity probes, a pull-up resistor is required between the supplied
proximity probe voltage and the proximity probe input to the FTM. Individually
fused 12 Vdc and 24 Vdc sources are provided with each speed input to power
system proximity probes (100 mA fuses, located on the FTMs, are used).
External pull-up resistors are required when interfacing with an open collector
type proximity probe. See Figure 8-7 for MPU/proximity probe wiring example.
Channel 1 shows an MPU connection, channel 2 shows a 24 V proximity
connection, and channel 3 is an example of a 12 V proximity connection. Always
jumper the unused MPU connection to eliminate possible noise interference
when connecting a proximity probe.
Woodward 149
MicroNet TMR Manual 26167V1
When a speed sensor input channel has been wired as either MPU or
proximity probe input, the unused MPU/Prox must be jumpered at the
FTM. When an input channel is not used, both the MPU and Prox
inputs must be jumpered. See example in Figure 8-7.
150 Woodward
Manual 26167V1 MicroNet TMR
Analog Inputs
The analog inputs must be current type. See Appendix A for specific part
numbers. All modules use the same cable and FTMs.
All current inputs may be used with two-wire ungrounded (loop powered)
transducers or isolated (self-powered) transducers. All analog inputs have 200
Vdc of common mode rejection. If interfacing to a non-isolated device, which may
have the potential of reaching over 200 Vdc with respect to the control’s
common, the use of a loop isolator is recommended to break any return current
paths that may produce erroneous readings. All current inputs use 200 ohm
resistors across their inputs.
Each current input channel may power its own 4–20 mA transducer. This power
is protected with a 100 mA fuse on each channel to prevent an inadvertent short
from damaging the module. The 24 Vdc outputs are capable of providing 24 Vdc
with ±10% regulation. Power connections can be made through terminals located
on the FTMs. Refer to Figure 8-8 for 4–20 mA Current Input wiring.
Woodward 151
MicroNet TMR Manual 26167V1
Only self-powered voltage transducers should be used on voltage input
channels. The full scale range must not exceed 5 volts. Refer to Figure 8-9 for 0–
5 Vdc voltage transducer input wiring.
TB1
F8
24 NC
68 NC
.01uF
25 Ch. 1
J1 J1
-
9 9 69 -
Anti- Self Powered
AI_01 aliasing Voltage
+ Filter 27 27 26 + Transducer
F7
70 NC
27 NC
.01uF
71 SHLD Ch. 2
-
Anti- 7 7 28 -Input
AI_02 aliasing
+ Filter 25 25 72 +Input
F6
29 NC
73 NC
.01uF
30 SHLD Ch. 3
-
Anti- 5 5 74 -Input
AI_03 aliasing
+ Filter 23 23 31 +Input
F5
75 NC
32 NC
.01uF
76 SHLD Ch. 4
-
Anti- 2 2 33 -Input
AI_04 aliasing
+ Filter 21 21 77 +Input
F4
34 NC
78 NC
.01uF
35 SHLD Ch. 5
J2 J2
-
Anti- 9 9 79 -Input
AI_05 aliasing
+ Filter 27 27 36 +Input
F3
80 NC
37 NC
.01uF
81 SHLD Ch. 6
-
Anti- 7 7 38 -Input
AI_06 aliasing
+ Filter 25 25 82 +Input
F2
13 13 39 NC
J1 J1
13 13 83 NC
.01uF
40 SHLD Ch. 7
J2 J2
-
Anti- 5 5 84 -Input
AI_07 aliasing
+ Filter 23 23 41 +Input
F1
- 15 15 85 NC
11 11
+24VDC J1 J1 42 NC
+ 15 15 .01uF
11 11 86 SHLD Ch. 8
J2 J2
-
Anti- 2 2 43 -Input
AI_08 aliasing
+ Filter 21 21 87 +Input
J1&2 J1&2
20 20 88
152 Woodward
Manual 26167V1 MicroNet TMR
Analog Outputs
The analog outputs are 4–20 mA with a full-scale range of 0–25 mA. Each output
monitors the output source current for fault detection. All of the analog outputs
may be individually disabled. When a channel fault or a module fault is detected,
the application program may annunciate the fault, disable the channel or module,
and stop using the data in system calculations or control.
The Analog Combo module has four 4–20 mA current output drivers. All analog
outputs can drive a maximum load of 600 ohms (load + wire resistance). Care
should be taken to prevent ground loops and other faults when interfacing to non-
isolated devices. See Figure 8-10 for an example of 4–20 mA output wiring.
Actuator Outputs
The actuator outputs may be configured for 4–20 mA or 20–160 mA.
Configuration is done through the application software; no hardware
modifications in the forms of jumpers or switches are necessary. For fault
detection, each output monitors the output source current and the output return
current. All of the actuator outputs may be individually disabled. When a channel
fault or a module fault is detected, the application program may annunciate the
fault, disable the channel or module, and stop using the data in system
calculations or control.
Dither may be provided in the application software for each output. Dither is a low
frequency (25 Hz) signal consisting of a 5 millisecond pulse modulated onto the
DC actuator-drive current to reduce sticking due to friction in linear type
actuators. Woodward TM-type actuators typically require dither. Dither amplitude
is variable through the application software. See Figure 8-10 for an example of
actuator wiring.
Configuration Notes
Maximum impedance for a 4 to 20 mA actuator output driver is 360 ohms
(actuator impedance + wire resistance).
Maximum impedance for a 20 to 160 mA actuator output is 45 ohms
(actuator impedance + wire resistance).
Each actuator driver senses its source and return current to allow
overcurrent and undercurrent alarms and shutdowns.
8.4.4—FTM Reference
See Chapter 12 for complete Analog Combo FTM field wiring information. See
Appendix A for proper Module, FTM, and cable part numbers.
Woodward 153
MicroNet TMR Manual 26167V1
Figure 8-10—Analog Output and Actuator Wiring for an Analog Combo FTM
154 Woodward
Manual 26167V1 MicroNet TMR
8.4.5—Troubleshooting
Fault Detection (Module Hardware)
Each Analog Combo module has a red Fault LED that is turned on when the
system is reset. During initialization of a module, which occurs after every CPU
reset, the CPU turns the Fault LED on. The CPU then tests the module using
diagnostic routines built into the software. If the diagnostic test is not passed, the
LED remains on or blinks. If the test is successful, the LED goes off. If the Fault
LED on a module is illuminated after the diagnostics and initialization have been
completed, the Analog Combo module may be faulty or may be located in the
wrong slot.
Analog Input Faults. The application software may set a high and low latch
setpoint to detect input faults.
Speed Sensor Input Faults. The application software may set a high and low
latch setpoint to detect input faults. The low latch setpoint must be greater than
one fiftieth of the frequency range.
Analog Output Driver Faults. The module monitors the source currents and
annunciates faults. The application determines the course of action in the event
of a fault.
Actuator Driver Or Load Faults. The module monitors the source and return
currents and annunciates faults. The application determines the course of action
in the event of a fault.
Troubleshooting Guide
If during normal control operation all of a chassis’ I/O modules have Fault LEDs
on, check the kernel’s CPU module for a failure. If during normal control
operation only the MPU and Analog I/O module’s Fault LED is on or flashing,
insure that it is installed in the correct slot. If it is, then replace that MPU and
Analog I/O module. See instructions for replacing the module in Chapter 21,
Installation and Service. When a module fault is detected, its outputs should be
disabled or de-energized.
Woodward 155
MicroNet TMR Manual 26167V1
Speed Sensor Inputs
MPUs. If a speed sensor input is not functioning properly, verify the following:
Check that the cable is shielded and the shield is properly grounded per the
Shields and Grounding section in Chapter 21, Installation and Service.
Measure the input voltage on the terminal block. It should be in the range of
1-25 VRMS.
Verify that the signal waveform is clean and void of double zero crossings.
Verify that no ground connection exists and that the resulting 60 Hz signal is
absent.
Measure the frequency. It should be in the range of 100 Hz - 25 kHz.
Look at the individual inputs into each kernel. A and B should read an input,
and C should also read this input if the terminal block jumpers are installed.
The application software should contain three separate numbers, one from
each module. The numbers should be within 0.1% of each other, except
kernel C if the jumpers are not installed.
Verify that any unused MPU/Prox inputs are jumpered per Figure 8-7.
The following actions may shut down the prime mover. If all of the
MPU and Analog I/O modules are reading approximately the same
number, but it is not the right reading, go to step 1. If two of the MPU
and Analog I/O modules are reading correctly, but one is reading
incorrectly, go to step 2.
1. Check the wiring. If the inputs are reading 0, look for a loose connection on
the terminal blocks or disconnected or misconnected cables. Check the
application software configuration to ensure that the input is configured
properly. If the connections and application software are verified and the
correct voltage is present on the terminal block, but all of the MPU and
Analog I/O modules are reading 0 V, exchange FTM #1 with FTM #2. See
instructions for replacing the FTM in Chapter 15. If the problem follows the
FTM, replace the FTM. The FTM contains only traces and a few discrete
components, so failure is extremely unlikely.
2. If one or two of the MPU and Analog I/O modules are reading the correct
number, but the other module(s) is (are) incorrect, check the application
software configuration of the modules with the non-working channels, and
check to ensure that the cables are connected properly. If C kernel is not
working, but A and B are, check to insure that the terminal block jumpers
are installed if the MPU can drive three inputs. If the reading is still incorrect,
but the other readings from the MPU and Analog I/O module are correct,
remove the MPU and Analog I/O module and exchange the J1 and J2
cables. See instructions for replacing the module in Chapter 21, Installation
and Service. If the problem moves to a different channel, replace the cable.
If not, replace the MPU and Analog I/O module. If the readings are incorrect
on several channels of the same MPU and Analog I/O module,
corresponding to both cables, replace the MPU and Analog I/O module.
156 Woodward
Manual 26167V1 MicroNet TMR
Proximity Probes. If a speed sensor input is not functioning properly, verify the
following:
Check that the cable is shielded and the shield is properly grounded per the
Shields and Grounding section in Chapter 21, Installation and Service.
Measure the input voltage on the terminal block. It should be in the range of
3.5 - 32 Vpeak.
Verify that the signal waveform is clean and void of double zero crossings.
Verify that no ground connection exists and that the resulting 60 Hz signal is
absent.
Measure the frequency. It should be in the range of 0.5 Hz, to 25 kHz.
Check the wiring. Look for a loose connection at the terminal blocks,
disconnected or misconnected cables, a missing jumper on the terminal
block, or a blown fuse on the 24 Vdc on the FTM. See Figure 11-21 for FTM
fuse locations.
Check the software configuration to ensure that the input is configured
properly.
Check the fuse on the FTM. See the instructions and fuse locations below.
If the other channels on the MPU and Analog I/O module are also not
working, check the fuse on the MPU and Analog I/O module. This fuse is
visible and can be changed through the bottom of the module. If the fuse is
blown, fix the wiring problem and replace the fuse with another fuse of the
same type and rating.
Look at the individual inputs into each kernel. Each module reads the same
input from the FTM, so the software should contain three separate numbers,
one from each MPU and Analog I/O module. The numbers should be within
0.1% of each other unless a high common mode voltage is present.
Verify that any unused MPU/Prox inputs are jumpered per Figure 8-7.
The following actions may shut down the prime mover. If all of the
MPU and Analog I/O modules are reading approximately the same
number, but it is not the right reading, go to step 1. If two of the
modules are reading correctly, but one is reading incorrectly, go to
step 2.
1. Check the wiring. If the inputs are reading 0, look for a loose connection on
the terminal blocks, disconnected or misconnected cables, a missing jumper
on the terminal block, or a blown fuse on the 24 Vdc on the FTM. See
instructions for replacing the fuse, below. Check the MPU and Analog I/O
module fuse. See instructions for replacing the module in Chapter 21,
Installation and Service. This fuse is visible and can be changed through the
bottom of the module. If the fuse is blown, fix the wiring problem, then
replace the fuse with another fuse of the same type and rating. Check the
application software configuration to ensure that the input is configured
properly. If the connections and application software are verified and the
correct voltage is present on the terminal block, but all of the MPU and
Analog I/O modules are reading 0 V, exchange FTM #1 with FTM #2. See
instructions for replacing the FTM in Chapter 15. If the problem follows the
FTM, replace the FTM. The FTM contains only a wire wound 3 W resistor
and traces, so failure is extremely unlikely.
Woodward 157
MicroNet TMR Manual 26167V1
2. If one or two of the MPU and Analog I/O modules are reading the correct
number, but the other module(s) is (are) incorrect, check the application
software configuration of the modules with the non-working channels, and
check to ensure that the cables are connected properly. If the other
channels on the same MPU and Analog I/O module are also not working,
check the fuse on the MPU and Analog I/O module. See the instructions for
replacing the module in Chapter 21, Installation and Service. This fuse is
visible and can be changed through the bottom of the module. If this fuse is
blown, fix the wiring problem and replace the fuse with a fuse of the same
type and rating. If the reading is still incorrect, but the other readings from
the MPU and Analog I/O module are correct, remove the MPU and Analog
I/O module and exchange the J1 and J2 cables. If the problem moves to a
different channel, replace the cable. If not, replace the MPU and Analog I/O
module. If the readings are incorrect on several channels of the MPU and
Analog I/O module, corresponding to both cables, replace the MPU and
Analog I/O module.
Analog Inputs
If an analog input is not functioning properly, verify the following:
Check that the cable is shielded and the shield is properly grounded per the
Shields and Grounding section in Chapter 21, Installation and Service.
Measure the input voltage on the terminal block. It should be in the range of
0–5 V.
Look at the individual inputs into each kernel. Each module reads the same
input from the FTM, so the application software should contain three
separate numbers, one from each MPU and Analog I/O module. The
numbers should be within 0.1% of each other unless a high common mode
voltage is present.
Check the wiring. If the inputs are reading 0 or the engineering units that
correspond to 0 mA, look for a loose connection on the terminal blocks,
disconnected or misconnected cables, a missing jumper on the terminal
block if the input is a current input, or a blown fuse on the 24 Vdc on the
FTM. See Figure 11-21 for FTM fuse locations.
If all of the inputs are reading high, check that the 24 Vdc is not connected
across the input directly.
Check the software configuration to ensure that the input is configured
properly.
Check the fuse on the FTM. See the instructions and fuse locations below.
The following actions may shut down the prime mover. If all of the
MPU and Analog I/O modules are reading approximately the same
number, but the reading is incorrect, go to step 1. If two of the MPU
and Analog I/O modules are reading correctly, but one is reading
incorrectly, go to step 2.
1. Check the wiring. If the inputs are reading 0 or the engineering units that
correspond to 0 mA, look for a loose connection on the terminal blocks,
disconnected or misconnected cables, a missing jumper on the terminal
block if the input is a loop powered current input, or a blown fuse on the 24
Vdc on the FTM. See instructions for replacing the fuses on the FTM, below.
If all of the inputs are reading high, check to ensure that the 24 Vdc is not
connected across the input directly. Check the MPU and Analog I/O module
fuse. See instructions for replacing the module in Chapter 21, Installation
and Service. This fuse is visible and can be changed through the bottom of
the module. If the fuse is blown, fix the wiring problem, then replace the fuse
with another fuse of the same type and rating. Check the application
software configuration to ensure that the input is configured properly. If the
connections and application software are verified and the correct voltage is
158 Woodward
Manual 26167V1 MicroNet TMR
present on the terminal block, but all of the MPU and Analog I/O modules
are reading 0 V, exchange FTM #1 with FTM #2. See instructions for
replacing the FTM in Chapter 15. If the problem follows the FTM, replace
the FTM. The FTM contains only a wire wound 3 W resistor and traces, so
failure is extremely unlikely.
2. If one or two of the MPU and Analog I/O modules are reading the correct
number, but the other module(s) is (are) incorrect, check the application
software configuration of the modules with the non-working channels, and
check to ensure that the cables are connected properly. If the other
channels on the same MPU and Analog I/O module are not working either,
check the fuse on the MPU and Analog I/O module. See instructions for
replacing the module in Chapter 21, Installation and Service. This fuse is
visible and can be changed through the bottom of the module. If this fuse is
blown, fix the wiring problem and replace the fuse with a fuse of the same
type and rating. If the reading is still incorrect, but the other readings from
the MPU and Analog I/O module are correct, remove the MPU and Analog
I/O module and exchange the J1 and J2 cables. If the problem moves to a
different channel, replace the cable. If not, replace the MPU and Analog I/O
module. If the readings are incorrect on several channels of the MPU and
Analog I/O module, corresponding to both cables, replace the MPU and
Analog I/O module.
Analog Outputs
If an analog output is not functioning properly, verify the following:
Check that the cable is shielded and the shield is properly grounded per the
Shields and Grounding section in Chapter 21, Installation and Service.
Check the load resistance to ensure that it is below 600 ohms.
Check to ensure that the load wiring is isolated.
Check the wiring for a loose connection on the terminal blocks and
disconnected or misconnected cables.
Disconnect the field wiring and connect a resistor across the output. If the
output is correct across the resistor, there is a problem with the field wiring.
If the other output channels on the MPU and Analog I/O module are also not
working, check the fuse on the MPU and Analog I/O module. See
instructions for module replacement in Chapter 21, Installation and Service.
This fuse is visible and can be changed through the bottom of the module. If
the fuse is blown, fix the wiring problem and replace the fuse with a fuse of
the same type and rating.
Woodward 159
MicroNet TMR Manual 26167V1
Check the software configuration to ensure that the output is configured
properly.
The following actions may shut down the prime mover. Disconnect
the field wiring and connect a resistor across the output. If the output
current is 0 mA, go to step 1. If the output current is correct, but
some of the outputs have a fault, go to step 2.
2. If one or two of the MPU and Analog I/O modules have an output fault, but
the other module(s) does (do) not, check the application software, and
check to ensure that the cables are connected properly. If the other output
channels on the same MPU and Analog I/O module are also not working,
check the fuse on the MPU and Analog I/O module. See instructions for
replacing the module in Chapter 21, Installation and Service. This fuse is
visible and can be changed through the bottom of the module. If the fuse is
blown, fix the wiring problem and replace the fuse with a fuse of the same
type and rating. If the output still has a fault, but the other output channels
on the MPU and Analog I/O module are functioning properly, remove the
MPU and Analog I/O module and exchange the J1 and J2 cables. If the
problem moves to a different channel, replace the cable. If not, replace the
MPU and Analog I/O module. If the readings are incorrect on several
channels of the MPU and Analog I/O module, corresponding to both cables,
replace the same MPU and Analog I/O module.
Actuator Outputs
If an actuator output is not functioning properly, verify the following:
Check that the cable is shielded and the shield is properly grounded per the
Shields and Grounding section in Chapter 21, Installation and Service.
Check the load resistance to ensure that it is below the specified limit.
Check to ensure that the load wiring is isolated.
Check the wiring for a loose connection on the terminal blocks or
disconnected or misconnected cables.
Disconnect the field wiring and connect a resistor across the output.
If the other output channels on the MPU and Analog I/O module are also not
working, check the fuse on the MPU and Analog I/O module. See
instructions for module replacement in Chapter 21, Installation and Service.
This fuse is visible and can be changed through the bottom of the module. If
the fuse is blown, fix the wiring problem, and replace the fuse with a fuse of
the same type and rating.
Check the software configuration to ensure that the output is configured
properly
160 Woodward
Manual 26167V1 MicroNet TMR
The following actions may shut down the prime mover. Disconnect
the field wiring and connect a resistor across the output; if the
output current is 0 mA, go to step 1. If the output current is correct,
but some of the outputs have a fault, go to step 2.
2. If one or two of the MPU and Analog I/O modules have an output fault, but
the other module(s) does (do) not, check the application software
configuration, and check to ensure that the cables are connected properly.
Check the wiring for dual coil and single coil actuators, and ensure that the
wiring configuration matches the application software configuration. If the
other output channels on the same MPU and Analog I/O module are also
not working, check the fuse on the MPU and Analog I/O module. See
instructions for replacing the module in Chapter 21, Installation and Service.
This fuse is visible and can be changed through the bottom of the module. If
this fuse is blown, fix the wiring problem and replace the fuse with a fuse of
the same type and rating. If the output still has a fault, but the other output
channels on the MPU and Analog I/O module are functioning properly,
remove the MPU and Analog I/O module and exchange the J1 and J2
cables. If the problem moves to the other channel, replace the cable. If not,
replace the MPU and Analog I/O module. If the readings are incorrect on
several channels of the same MPU and Analog I/O module, corresponding
to both cables, replace the MPU and Analog I/O module.
If power has not been removed from the control system, power will
be active at the module and also at the FTM. Shorting of protected
circuitry could cause a control system shutdown.
2. Remove FTM cover carefully, to prevent contact with any FTM circuitry
under the cover. To remove the FTM cover, pinch the retaining barb and lift
the cover.
3. Locate and replace the fuse with another fuse of the same size and rating.
See Figure 11-20 or Figure 11-21 for channel fuse locations.
Woodward 161
MicroNet TMR Manual 26167V1
8.5.1—Module Description
A 24/8 Analog module contains circuitry for twenty-four analog inputs and eight
4–20 mA outputs. These modules have no potentiometers and require no
calibration. A module may be replaced with another module of the same part
number without any adjustment.
All 4–20 mA analog inputs may be used with two-wire ungrounded (loop
powered) transducers or isolated (self-powered) transducers. All analog inputs
have 200 Vdc of common mode rejection. If interfacing to a non-isolated device,
which may have the potential of reaching over 200 Vdc with respect to the
control’s common, the use of a loop isolator is recommended to break any return
current paths producing erroneous readings.
Each board has an on-board processor for automatic calibration of the I/O
channels. Each analog input incorporates a time-stamping feature with 5 ms
resolution for two low setpoints and two high setpoints.
162 Woodward
Manual 26167V1 MicroNet TMR
8.5.2—Module Specification
Analog Input Ratings
Number of channels: 24
Update time: 5 ms
Input range: 0–25 mA or 0–5 V; software and hardware
selectable
The maximum voltage input range may vary between 4.975 and 5.025
Volts from module to module.
Woodward 163
MicroNet TMR Manual 26167V1
The 24 channel analog inputs are divided into two banks, with
channel 1 through channel 12 data gathering at 1.8 ms after the MFT
tick and channel 13 through channel 24 data gathering at 3.7 ms after
the MFT tick.
8.5.3—Installation
The modules slide into card guides in the control's chassis and plug into the
motherboard. The modules are held in place by two screws, one at the top and
one at the bottom of the front panel. Also at the top and bottom of the module are
two handles which, when toggled (pushed outward), move the modules out just
far enough for the boards to disengage the motherboard connectors.
164 Woodward
Manual 26167V1 MicroNet TMR
J1
P1
J2
P1
P2
J1 24/8 Analog FTM
(Inputs Ch. 12-24)
(Outputs Ch. 5-8)
P2
J1 24/8 Analog FTM
(Inputs Ch. 1-12)
(Outputs Ch. 1-4)
Analog Inputs
For a 4–20 mA input signal, the 24/8 Analog Module uses a 200 ohm resistor
across the input located on the 24/8 Analog Module. Each analog input channel
may power its own 4–20 mA transducer. See Figure 8-14 for analog input
connection. This power is protected with a 100 mA fuse on each channel to
prevent an inadvertent short from damaging the module. The 24 Vdc outputs are
capable of providing 24 Vdc with ±10% regulation. The maximum current is 0.8
A. Power connections can be made through terminals located on the 24/8 Analog
FTMs. See Chapter 12 for complete field wiring information for the 24/8 Analog
FTM.
When configuring the AI Combo block in GAP, set Conf. input field to
1 for all inputs when used with the 24/8 Analog FTM. This will allow
the block to use the module factory calibration values for the 4–20
mA inputs that were calibrated with 200 ohm internal resistors on the
24/8 Analog Module.
Woodward 165
MicroNet TMR Manual 26167V1
Analog Outputs
There are 8 analog output channels of 4–20 mA with a full scale range of 0–25
mA. All Analog Outputs can drive a maximum load of 600 ohms (load + wire
resistance). See Figure 8-15 for analog output connection. Each output monitors
the output source current for fault detection. All of the analog outputs may be
individually disabled. When a channel fault or a module fault is detected, the
application program may annunciate the fault, disable the channel and stop using
data in system calculations or control. Care should be taken to prevent ground
loops and other faults when interfacing to non-isolated devices. See Chapter 12
for complete field wiring information for the Analog High Density FTM.
166 Woodward
Manual 26167V1 MicroNet TMR
8.5.4—FTM Reference
See Chapter 12 for complete field wiring information for the Analog High Density
FTM. See Appendix A for part number Cross Reference for modules, FTMs, and
cables.
8.5.5—Troubleshooting
Each 24/8 Analog module has a red Fault LED that is turned on when the system
is reset. During initialization of a module, which occurs after every CPU reset, the
CPU turns the Fault LED on. The CPU then tests each module using diagnostic
routines built into the software. If the diagnostic test is not passed, the LED
remains on or blinks. If the test is successful, the LED goes off. If the Fault LED
on a module is illuminated after the diagnostics and initialization have been run,
the module may be faulty or may be located in the wrong slot.
Analog Input Faults: The application software may be set with a high and low
latch setpoint to detect input faults.
Analog Output Driver Faults: The module monitors the source currents and
annunciates faults. The application software determines the course of action in
the event of a fault.
Woodward 167
MicroNet TMR Manual 26167V1
Microcontroller Faults: The system monitors a software watchdog, a hardware
watchdog, and a software watchdog on the VME bus communications. All
outputs are shut down in the event of a microcontroller fault.
Troubleshooting Guide
If during normal control operation, all of the 24/8 Analog modules have Fault
LEDs on, check the chassis’ CPU module for a failure. If during normal control
operation only the 24/8 Analog module’s Fault LED is on or flashing, insure that it
is installed in the correct slot. If it is, then replace that module. See instructions
for replacement in Chapter 15. When a module fault is detected, its outputs will
be disabled or de-energized.
Analog Inputs
If an analog input is not functioning properly, verify the following:
1. Check that the cable is shielded and the shield is properly grounded per
the Shields and Grounding section in Chapter 14.
2. Measure the input voltage on the FTM terminal block. It should be in the
range of 0–5 V.
3. Verify that there are no or minimal AC components to the Analog Input
signal. Improper shielding may introduce AC noise on the input
terminals.
4. Check the wiring. If the inputs are reading 0 or the engineering units that
correspond to 0 mA, look for a loose connection on the terminal blocks,
disconnected or misconnected cables, a missing jumper on the terminal
block if the input is a current input, or a blown fuse on the 24 Vdc on the
FTM.
5. If all of the inputs are reading high, check that the 24 Vdc is not
connected across the input directly.
6. Check the software configuration to ensure that the input is configured
properly.
7. If all of the channels on the 24/8 Analog module are not working, check
the fuse on the 24/8 Analog module. See instructions for module
replacement in Chapter 15. This fuse is visible and can be changed
through the bottom of the module. If the fuse is blown, fix the wiring
problem, then replace the fuse with another fuse of the same type and
rating.
8. After verifying all of the above, exchange the J1 and J2 cables. If the
problem moves to a different channel, replace the cable. If not, replace
the module.
9. If the readings are incorrect on several channels of the 24/8 Analog
module, corresponding to both cables, replace the module.
10. If replacing the module does not fix the problem, replace the FTM. The
FTM contains only traces and a few discrete components, so failure is
extremely unlikely. See instructions for replacing the FTM in Chapter 15.
168 Woodward
Manual 26167V1 MicroNet TMR
Analog Outputs
If an analog output is not functioning properly, verify the following:
1. Check that the cable is shielded and the shield is properly grounded per
the Shields and Grounding section in Chapter 14.
2. Check the load resistance to ensure that it is not greater than 600 ohms.
3. Check to ensure that the load wiring is isolated.
4. Check the wiring for a loose connection on the FTM terminal blocks and
disconnected or misconnected cables.
5. Disconnect the field wiring and connect a resistor across the output. If
the output is correct across the resistor, there is a problem with the field
wiring.
6. If all of the channels on the 24/8 Analog module are not working, check
the fuse on the 24/8 Analog module. See instructions for module
replacement in Chapter 15. This fuse is visible and can be changed
through the bottom of the module. If the fuse is blown, fix the wiring
problem, then replace the fuse with another fuse of the same type and
rating.
7. Check the software configuration to ensure that the output is configured
properly.
8. After verifying all of the above, exchange the J1 and J2 cables. If the
problem moves to a different channel, replace the cable. If not, replace
the module.
9. If the readings are incorrect on several channels of the module,
corresponding to both cables, replace the module.
10. If replacing the module does not fix the problem, replace the FTM. The
FTM contains only traces and a few discrete components, so failure is
extremely unlikely. See instructions for replacing the FTM in Chapter 15.
Woodward 169
MicroNet TMR Manual 26167V1
170 Woodward
Manual 26167V1 MicroNet TMR
8.6.2—Specifications
To obtain overall signal input accuracy and bandwidth, the Dataforth FTM (0–5
V) module input accuracy and the Dataforth 24/8 Analog Module must be taken
into account.
** The maximum input voltage range may vary between 4.975 and 5.025 Volts
from Dataforth module to Dataforth module.
Outputs can drive a maximum load of 600 ohms (load + wire resistance).
Woodward 171
MicroNet TMR Manual 26167V1
8.6.3—Installation
The modules slide into card guides in the control's chassis and plug into the
motherboard. The modules are held in place by two screws, one at the top and
one at the bottom of the front panel. Also at the top and bottom of the module are
two handles which, when toggled (pushed outward), move the modules out just
far enough for the boards to disengage the motherboard connectors.
J1
P1
J2
P1
P2
J1
Simplex Dataforth FTM
(Inputs Ch. 12-24)
(Outputs Ch. 5-8)
P2
J1
Simplex Dataforth FTM
(Inputs Ch. 1-12)
(Outputs Ch. 1-4)
Field Wiring
See Chapter 12 for complete wiring connections for the Simplex Dataforth FTM.
Each input channel requires a Dataforth plug-in module per input. Install one of
the five different Dataforth modules into each of the 12 plug-in slots on the FTM.
It is not necessary to have a plug-in module in a slot if not used. With the Simplex
Dataforth FTM connected to J1 of the Dataforth Module, channels 1-12 will be
active. With the Simplex Dataforth FTM connected to J2 of the Dataforth Module,
channels 13-24 will be active. Wire each channel per the following examples for
each type of plug-in module. Install jumpers on FTM module as shown for
specific type of input.
172 Woodward
Manual 26167V1 MicroNet TMR
The cold junction compensation (CJC) is performed by using an NTC thermistor,
externally mounted on the FTM module, as shown in Figure 8-18. The
thermocouple signal will fail high if an open wire is detected.
6
24 RTN 18
Jumper
TB15
1
Fuse
100 mA 250 V
2
Woodward 173
MicroNet TMR Manual 26167V1
MicroNet™ Module Dataforth® FTM
Plug-in
FTM
Module Term Blk
1
0 13
Sense
NTC
Thermistor * 2
3 2 14
- In
+24 V RTD
3
+ V out 4 1 15
+ In
0.01uf, 500V
Com 4
- 5 16
3 5
IN * Note: The thermistor remains present on
Px 2
1 OUT
17 the FTM on all circuits, but has no effect
6 on the accuracy of the measurement.
24 RTN 18
Jumper
TB15
1
Fuse
100 mA 250 V
2
When configuring the AI Combo block in GAP, set Conf. input field to
2 for all 4–20 mA inputs when used with the current input plug-in
module. This will allow the block to use the module factory voltage
calibration values with a gain factor for a 200 ohm external resistor
on the Dataforth FTM.
Plug-in FTM
Module Term Blk
1
0 13
2
3 2 14 4/20 mA (Loop Powered)
+24 V
+ V out 4 1 3
15
+ In -
Sig
0.01uf, 500V
4
4-20mA Transmitter
- Com 5 16
Shield +
+24 V
3 5
IN
Px 2
1 OUT
17
6
18
+24 V
24 RTN
Jumper
TB15
1
Fuse
100 mA 250 V
2
174 Woodward
Manual 26167V1 MicroNet TMR
MicroNet™ Module Dataforth® FTM
3
4-20mA Transmitter
+ V out 4 1
15
+ In +
Sig
0.01uf, 500V
Com 4
- 5 16
Shield
3 5
IN
Px 2
1 OUT
17
6
24 RTN 18
Jumper
TB15
1
Fuse
100 mA 250 V
2
When configuring the AI Combo block in GAP, set Conf. input field to
0 for all voltage inputs when used with the voltage input plug-in
module. This will allow the block to use the module factory voltage
calibration values with the Dataforth FTM.
3
0-5VDC Transmitter
+ V out 4 1
15
+ In +
Sig
0.01uf, 500V
- Com 5 4
16
Shield
3 5
IN
Px 2
1 OUT
17
6
24 RTN 18
Jumper
TB15
1
Fuse
100 mA 250 V
2
Woodward 175
MicroNet TMR Manual 26167V1
Analog Output Connection
The Analog Output circuit doesn’t use a plug-in module. No jumper connections
are required. See Figure 8-23 for an example of wiring a 4–20 mA output device.
+24 V
MicroNet™ Module
I/O Lockout
Analog Output +
Dataforth® FTM
Feedback - FTM
TB1
Analog Output
- Out -
1
Output
Analog Output B + Out + Device
2
0.01uf, 500V
Shield
3
24 COM
TB15
8.6.4—FTM Reference
See Chapter 12 for complete field wiring of the Simplex Dataforth FTM. See
Appendix A for part number Cross Reference for modules, FTMs, and cables.
176 Woodward
Manual 26167V1 MicroNet TMR
8.6.5—Troubleshooting
Each Dataforth 24/8 Analog Module has a red Fault LED that is turned on when
the system is reset. During initialization of a module, which occurs after every
CPU reset, the CPU turns the Fault LED on. The CPU then tests each module
using diagnostic routines built into the software. If the diagnostic test is not
passed, the LED remains on or blinks. If the test is successful, the LED goes off.
If the Fault LED on a module is illuminated after the diagnostics and initialization
have been run, the module may be faulty or may be located in the wrong slot.
Analog Input Faults: The application software may be set with a high and low
latch setpoint to detect input faults.
Analog Output Driver Faults: The module monitors the source currents and
annunciates faults. The application software determines the course of action in
the event of a fault.
Troubleshooting Guide
If during normal control operation all of a chassis’ Dataforth 24/8 Analog Module
have Fault LEDs on, check the chassis’ CPU module for a failure. If during
normal control operation only the Dataforth Module’s Fault LED is on or flashing,
insure that it is installed in the correct slot. If it is, then replace that module. See
instructions for replacement in Chapter 15. When a module fault is detected, its
outputs should be disabled or de-energized.
Thermocouple Inputs
If an Thermocouple input is not functioning properly, verify the following:
1. Verify that the correct Dataforth plug-in module is installed. Swap plug-in
modules on FTM. Replace module if problem follows module.
2. Check that the cable is shielded and the shield is properly grounded per
section Shields and Grounding section in Chapter 14.
Woodward 177
MicroNet TMR Manual 26167V1
3. Verify that there are no or minimal AC components to the Analog Input
signal. AC components can be caused by improper shielding.
4. Check the wiring. If the inputs are reading full scale, look for a loose
connection on the terminal blocks, disconnected or misconnected cables,
a missing jumper on the terminal block, or a blown fuse on the 24 Vdc on
the FTM.
5. Check the software configuration to ensure that the input is configured
properly.
6. Verify that FTM module is within operating limits of +5 to 45 degrees C.
7. If all of the thermocouple channels on the Dataforth Module are not
working, check the fuse on the Dataforth Module. See instructions for
module replacement in Chapter 15. This fuse is visible and can be
changed through the bottom of the module. If the fuse is blown, fix the
wiring problem, then replace the fuse with another fuse of the same type
and rating.
8. If the readings are incorrect on several channels of the Dataforth Module,
after replacing both cables, replace the module. If replacing the module
does not fix the problem, replace the FTM. See instructions for replacing
the FTM in Chapter 15.
RTD Inputs
If an RTD input is not functioning properly, verify the following:
1. Verify that the correct Dataforth plug-in module is installed. Swap plug-in
modules on FTM. Replace module if problem follows module.
2. Check that the cable is shielded and the shield is properly grounded per
section Shields and Grounding section in Chapter 14.
3. Verify that there are no or minimal AC components to the Analog Input
signal. AC components can be caused by improper shielding.
4. Check the wiring. If the inputs are minimum scale or full scale, look for a
loose connection on the terminal blocks, disconnected or misconnected
cables, a missing jumper on the terminal block, or a blown fuse on the 24
Vdc on the FTM.
5. Check the software configuration to ensure that the input is configured
properly.
6. If all of the RTD channels on the Dataforth Module are not working,
check the fuse on the Dataforth Module. See instructions for module
replacement in Chapter 15. This fuse is visible and can be changed
through the bottom of the module. If the fuse is blown, fix the wiring
problem, then replace the fuse with another fuse of the same type and
rating.
7. If the readings are incorrect on several channels of the Dataforth Module,
after replacing both cables, replace the module. If replacing the module
does not fix the problem, replace the FTM. See instructions for replacing
the FTM in Chapter 15.
178 Woodward
Manual 26167V1 MicroNet TMR
4–20 mA Analog Inputs
If a 4–20 mA analog input is not functioning properly, verify the following:
1. Verify that the correct Dataforth plug-in module is installed.
2. Check that the cable is shielded and the shield is properly grounded.
3. Measure the input voltage on the FTM terminal block. It should be in the
range of 0.8-4.0 V.
4. Verify that there are no or minimal AC components to the Analog Input
signal. AC components can be caused by improper shielding.
5. Check the wiring. If the inputs are reading 0 or the engineering units that
correspond to 0 mA, look for a loose connection on the terminal blocks,
disconnected or misconnected cables, a missing jumper on the terminal
block if the input is a current input, or a blown fuse on the 24 Vdc on the
FTM.
6. Check the software configuration to ensure that the input is configured
properly.
7. If all of the 4–20 mA channels on the Dataforth Module are not working,
check the fuse on the Dataforth Module. See instructions for module
replacement in Chapter 15. This fuse is visible and can be changed
through the bottom of the module. If the fuse is blown, fix the wiring
problem, then replace the fuse with another fuse of the same type and
rating.
8. If the readings are incorrect on several channels of the Dataforth Module,
after replacing both cables, replace the module. If replacing the module
does not fix the problem, replace the FTM. The 4–20 mA configured FTM
contains only traces and a few discrete components, so failure is
extremely unlikely. See instructions for replacing the FTM in Chapter 15.
Woodward 179
MicroNet TMR Manual 26167V1
Analog Outputs
If an analog output is not functioning properly, verify the following:
1. Check that the cable is shielded and the shield is properly grounded.
2. Check the load resistance to ensure that it is not greater than 600 ohms.
3. Check to ensure that the load wiring is isolated.
4. Check the wiring for a loose connection on the FTM terminal blocks and
disconnected or misconnected cables.
5. Disconnect the field wiring and connect a resistor across the output. If
the output is correct across the resistor, there is a problem with the field
wiring.
6. If all of the channels on the Dataforth Module are not working, check the
fuse on the Dataforth Module. See instructions for module replacement
in Chapter 15. This fuse is visible and can be changed through the
bottom of the module. If the fuse is blown, fix the wiring problem, then
replace the fuse with another fuse of the same type and rating.
7. Check the software configuration to ensure that the output is configured
properly.
8. After verifying all of the above, exchange the J1 and J2 cables. If the
problem moves to a different channel, replace the cable. If not, replace
the module.
9. If the readings are incorrect on several channels of the module,
corresponding to both cables, replace the module.
10. 1 If replacing the module does not fix the problem, replace the FTM. The
FTM contains only traces and a few discrete components, so failure is
extremely unlikely. See instructions for replacing the FTM in Chapter 15.
180 Woodward
Manual 26167V1 MicroNet TMR
There are two configurations of the Analog Combo Modules. One has the analog
inputs configured for 4–20 mA and the other is configured for 0–5 V. See
Appendix A for specific part numbers. In a simplex system, either Analog Combo
module is connected through two analog cables to one Analog Combo FTM. All
of the I/O are accessible on the FTM, and the channels are labeled to correspond
to their software locations, e.g. analog input 1 on the FTM will be analog input 1
in the application software.
Woodward 181
MicroNet TMR Manual 26167V1
8.7.2—Module Specifications
Digital Speed Sensor Inputs
Number of channels: 4
Update time: 5 ms
The maximum input voltage range may vary between 4.975 and 5.025
Volts from module to module.
182 Woodward
Manual 26167V1 MicroNet TMR
4–20 mA Analog Output Ratings
Number of channels: 4
Update time: 5 ms
Driver: Pulse Width Modulated (PWM)
PWM frequency: 6.14 kHz
Filter: 3 poles at 500 ms
Current output: 4–20 mA current output range: 0 - 25 mA
Isolation: 0 Vrms
Max load resistance: 600 ohms (load + wire resistance)
Current readback: 11 bits
Readback isolation: -60 dB CMRR, 200 Vdc common mode
Resolution: 11 bits
Accuracy: Software calibrated to 0.2%, over 25 mA full
scale
Temperature drift: 125 ppm/C, maximum
Readback accuracy: 0.2%, over 25 mA full scale
Readback temp drift: 400 ppm/C, maximum
8.7.3—Installation
The modules slide into card guides in the control's chassis and plug into the
motherboard. The modules are held in place by two screws, one at the top and
one at the bottom of the front panel. Also at the top and bottom of the module are
two handles which, when toggled (pushed outward), move the modules out just
far enough for the boards to disengage the motherboard connectors.
Woodward 183
MicroNet TMR Manual 26167V1
There are two configurations of the Analog Combo Modules. One has the analog
inputs configured for 4–20 mA and the other is configured for 0–5 V. See
Appendix A for specific part numbers. In a simplex system, each Analog Combo
module is connected through two Low Density analog cables to one Analog
Combo FTM. All of the I/O are accessible on the FTM, and the channels are
labeled to correspond to their software locations. See Figure 8-26 for
configuration.
J1
P1
J2
P1
P2 P2
J1 J2
When a speed sensor input channel has been wired as either MPU or
proximity probe input, the unused MPU/Prox must be jumpered at the
FTM. When an input channel is not used, both the MPU and Prox
inputs must be jumpered. See example in Figure 8-27.
4 Com
35 35 48 +MPU Input
Jumper
34 34 5 -MPU Input
MPU/PROX_2 .01uF
15 15 49
2.1K ohm
+Prox Input + Ch. 2 (Prox.)
17 17 6
3W
PROX #2
50
F11
24/12V 7 NC
Reg.
-
51
J2 J2
37 37 8 +MPU Input
Jumper
36 36 52 -MPU Input
MPU/PROX_3 .01uF
18 18 9
2.1K ohm
+Prox Input + Ch. 3 (Prox.)
19 19 53
J1 J1 3W
PROX #3
15 15 10 NC
11 11 F10
24/12V 54
J2 J2 Reg.
15 15 -
11
11 11
35 35 55 +MPU Input
Jumper
34 34 12 -MPU Input
MPU/PROX_4 .01uF
15 15 56 Shld
2.1K ohm Ch. 4
+Prox Input
17 17 13 +Prox Input (Not Used)
+ F9 3W
57 +24VDC
+24VDC J1 J1 Jumper
13 13 24/12V 14 +12VDC
Reg.
- J2 J2
13 13 58 Com
J1 J1
20 20 88
J2 J2
Ground to DIN Rail
20 20
Woodward 185
MicroNet TMR Manual 26167V1
A proximity probe may be used to sense very low speeds. With a proximity
probe, speed can be sensed down to 0.5 Hz. When interfacing to open collector
type proximity probes, a pull-up resistor is required between the supplied
proximity probe voltage and the proximity probe input to the FTM. Individually
fused 12 Vdc and 24 Vdc sources are provided with each speed input to power
system proximity probes (100 mA fuses, located on the FTMs, are used).
External pull-up resistors are required when interfacing with an open collector
type proximity probe. See Figure 8-27 for MPU/proximity probe wiring example.
Channel 1 shows an MPU connection, channel 2 shows a 24 V proximity
connection, and channel 3 is an example of a 12 V proximity connection. Always
jumper the unused MPU connection to eliminate possible noise interference
when connecting a proximity probe.
Analog Inputs
The analog inputs may be current or voltage type dependent on the part number.
See Appendix A for specific part numbers. Both modules use the same cable and
FTM.
All current inputs may be used with two-wire ungrounded (loop powered)
transducers or isolated (self-powered) transducers. All analog inputs have
200 Vdc of common mode rejection. If interfacing to a non-isolated device, which
may have the potential of reaching over 200 Vdc with respect to the control’s
common, the use of a loop isolator is recommended to break any return current
paths that may produce erroneous readings. All current inputs use
200 ohm resistors across their inputs.
Each current input channel may power its own 4–20 mA transducer. This power
is protected with a 100 mA fuse on each channel to prevent an inadvertent short
from damaging the module. The 24 Vdc outputs are capable of providing 24 Vdc
with ±10% regulation. Power connections can be made through terminals located
on the FTMs. Refer to Figure 8-28 for 4–20 mA Current Input wiring.
186 Woodward
Manual 26167V1 MicroNet TMR
TB1
F8
24 +
Loop Powered
Transducer
68 -
.01uF
25 Ch. 1
J1 J1
-
Anti- 9 9 69 -
200
AI_01 aliasing Ohm
+ Filter 27 27 26 +
F7
70 NC
27 NC
.01uF
71 Ch. 2
-
7 7 28 -
Anti-
200 Self Powered
AI_02 aliasing Ohm Transducer
+ Filter 25 25 72 +
F6
29 +24V
73 COM
.01uF
30 SHLD Ch. 3
-
Anti- 5 5 74 -Input
200
AI_03 aliasing Ohm
+ Filter 23 23 31 +Input
F5
75 +24V
32 COM
.01uF
76 SHLD Ch. 4
-
Anti- 2 2 33 -Input
200
AI_04 aliasing Ohm
+ Filter 21 21 77 +Input
F4
34 +24V
78 COM
.01uF
35 SHLD Ch. 5
J2 J2
-
Anti- 9 9 79 -Input
200
AI_05 aliasing Ohm
+ Filter 27 27 36 +Input
F3
80 +24V
37 COM
.01uF
81 SHLD Ch. 6
-
Anti- 7 7 38 -Input
200
AI_06 aliasing Ohm
+ Filter 25 25 82 +Input
F2
13 13 39 +24V
J1 J1
13 13 83 COM
.01uF
40 SHLD Ch. 7
J2 J2
-
Anti- 5 5 84 -Input
200
AI_07 aliasing Ohm
+ Filter 23 23 41 +Input
F1
- 15 15 85 +24V
11 11
+24VDC J1 J1 42 COM
+ 15 15 .01uF
11 11 86 SHLD Ch. 8
J2 J2
-
Anti- 2 2 43 -Input
200
AI_08 aliasing Ohm
+ Filter 87
21 21 +Input
J1&2 J1&2
20 20 88
Woodward 187
MicroNet TMR Manual 26167V1
Only self-powered voltage transducers should be used on voltage input
channels. The full scale range must not exceed 5 volts. Refer to Figure 8-29 for
0–5 Vdc voltage transducer input wiring.
TB1
F8
24 NC
68 NC
.01uF
25 Ch. 1
J1 J1
-
9 9 69 -
Anti- Self Powered
AI_01 aliasing Voltage
+ Filter 27 27 26 + Transducer
F7
70 NC
27 NC
.01uF
71 SHLD Ch. 2
-
Anti- 7 7 28 -Input
AI_02 aliasing
+ Filter 25 25 72 +Input
F6
29 NC
73 NC
.01uF
30 SHLD Ch. 3
-
Anti- 5 5 74 -Input
AI_03 aliasing
+ Filter 23 23 31 +Input
F5
75 NC
32 NC
.01uF
76 SHLD Ch. 4
-
Anti- 2 2 33 -Input
AI_04 aliasing
+ Filter 21 21 77 +Input
F4
34 NC
78 NC
.01uF
35 SHLD Ch. 5
J2 J2
-
Anti- 9 9 79 -Input
AI_05 aliasing
+ Filter 27 27 36 +Input
F3
80 NC
37 NC
.01uF
81 SHLD Ch. 6
-
Anti- 7 7 38 -Input
AI_06 aliasing
+ Filter 25 25 82 +Input
F2
13 13 39 NC
J1 J1
13 13 83 NC
.01uF
40 SHLD Ch. 7
J2 J2
-
Anti- 5 5 84 -Input
AI_07 aliasing
+ Filter 23 23 41 +Input
F1
- 15 15 85 NC
11 11
+24VDC J1 J1 42 NC
+ 15 15 .01uF
11 11 86 SHLD Ch. 8
J2 J2
-
Anti- 2 2 43 -Input
AI_08 aliasing
+ Filter 21 21 87 +Input
J1&2 J1&2
20 20 88
188 Woodward
Manual 26167V1 MicroNet TMR
Analog Outputs
The analog outputs are 4–20 mA with a full-scale range of 0–25 mA. Each output
monitors the output source current for fault detection. All of the analog outputs
may be individually disabled. When a channel fault or a module fault is detected,
the application program may annunciate the fault, disable the channel or module,
and stop using the data in system calculations or control.
The Analog Combo module has four 4–20 mA current output drivers. All analog
outputs can drive a maximum load of 600 ohms (load + wire resistance). Care
should be taken to prevent ground loops and other faults when interfacing to non-
isolated devices. See Figure 8-30 for an example of 4–20 mA output wiring.
Actuator Outputs
The actuator outputs may be configured for 4–20 mA or 20–160 mA.
Configuration is done through the application software; no hardware
modifications in the forms of jumpers or switches are necessary. For fault
detection, each output monitors the output source current and the output return
current. All of the actuator outputs may be individually disabled. When a channel
fault or a module fault is detected, the application program may annunciate the
fault, disable the channel or module, and stop using the data in system
calculations or control.
Dither may be provided in the application software for each output. Dither is a low
frequency (25 Hz) signal consisting of a 5 millisecond pulse modulated onto the
DC actuator-drive current to reduce sticking due to friction in linear type
actuators. Woodward TM-type actuators typically require dither. Dither amplitude
is variable through the application software. See Figure 8-30 for an example of
actuator wiring.
Configuration Notes
Maximum impedance for a 4 to 20 mA actuator output driver is 360 ohms
(actuator impedance + wire resistance).
Maximum impedance for a 20 to 160 mA actuator output is 45 ohms
(actuator impedance + wire resistance).
Each actuator driver senses its source and return current to allow
overcurrent and undercurrent alarms and shutdowns.
8.7.4—FTM Reference
See Chapter 12 for complete Analog Combo FTM field wiring information. See
Appendix A for proper Module, FTM, and cable part numbers.
Woodward 189
MicroNet TMR Manual 26167V1
J1 J1 16 SHLD
I/O Lockout
33 33 15 +Output Ch. 1
Analog AO_01
+
Output 32 32 59 -Output
- .01uF
Feedback
61
Analog
B +
Output 31 31 17 Ch. 2
Output
AO_02 Device
30 30 60 -
.01uF
24 COM
19 SHLD
J2 J2
33 33 18 +Output Ch. 3
AO_03
32 32 62 -Output
.01uF
64 SHLD
31 31 63 +Output Ch. 4
AO_04
30 30 20 -Output
22 SHLD
J1 J1 .01uF
29 29 21 +Output Ch. 1
ACT_01
28 28 65 -Output
.01uF
67 SHLD
J2 J2
29 29 66 +Output Ch. 2
ACT_02
28 28 23 -Output
J1&2 J1&2
20 20 88
Figure 8-30—Analog Output and Actuator Wiring for an Analog Combo FTM
8.7.5—Troubleshooting
Fault Detection (Module Hardware)
Each Analog Combo module has a red Fault LED that is turned on when the
system is reset. During initialization of a module, which occurs after every CPU
reset, the CPU turns the Fault LED on. The CPU then tests the module using
diagnostic routines built into the software. If the diagnostic test is not passed, the
LED remains on or blinks. If the test is successful, the LED goes off. If the Fault
LED on a module is illuminated after the diagnostics and initialization have been
completed, the Analog Combo module may be faulty or may be located in the
wrong slot.
190 Woodward
Manual 26167V1 MicroNet TMR
Fault Detection (I/O)
In addition to detecting module hardware faults, the application program may
detect I/O faults.
Analog Input Faults. The application software may set a high and low latch
setpoint to detect input faults.
Speed Sensor Input Faults. The application software may set a high and low
latch setpoint to detect input faults. The low latch setpoint must be greater than
one fiftieth of the frequency range.
Analog Output Driver Faults. The module monitors the source currents and
annunciates faults. The application determines the course of action in the event
of a fault.
Actuator Driver Or Load Faults. The module monitors the source and return
currents and annunciates faults. The application determines the course of action
in the event of a fault.
Troubleshooting Guide
If during normal control operation all of a chassis’ Analog Combo modules have
Fault LEDs on, check the chassis’ CPU module for a failure. If during normal
control operation only the Analog Combo module’s Fault LED is on or flashing,
insure that it is installed in the correct slot. If it is, then replace that Analog
Combo module. See instructions for replacement in Chapter 15. When a module
fault is detected, its outputs should be disabled or de-energized.
Woodward 191
MicroNet TMR Manual 26167V1
11. If replacing the module does not fix the problem, replace the FTM. See
instructions for replacing the FTM in Chapter 15. The FTM does not
contain any active components on the MPU inputs, so replacing it should
be the last option.
Proximity Probes
If a proximity probe input is not functioning properly, verify the following:
1. Check that the cable is shielded and the shield is properly grounded per
the Shields and Grounding section in Chapter 14.
2. Measure the input voltage on the terminal block. It should be in the range
of 3.5 – 32 Vpeak.
3. Verify that the signal waveform is clean and void of double zero
crossings.
4. Verify that no ground connection exists and that the resulting 60 Hz
signal is absent.
5. Measure the frequency. It should be in the range of 0.5 Hz to 25 kHz.
6. Verify that any unused MPU/Prox inputs are jumpered per Figure 8-27.
7. Check the wiring. Look for a loose connection at the terminal blocks,
disconnected or misconnected cables, a missing jumper on the terminal
block, or a blown fuse on the 24 Vdc on the FTM.
8. Check the software configuration to ensure that the input is configured
properly.
9. After verifying all of the above, exchange the J1 and J2 cables. If the
problem moves to a different channel, replace the cable. If not, replace
the Analog Combo module.
10. If the readings are incorrect on several channels of the Analog Combo
module, corresponding to both cables, replace the Analog Combo
module.
11. If replacing the module does not fix the problem, replace the FTM. See
instructions for replacing the FTM in Chapter 15. The FTM contains only
a wire-wound 3 W resistor and traces, so failure is extremely unlikely and
replacing it should be the last option.
Analog Inputs
If an analog input is not functioning properly, verify the following:
1. Check that the cable is shielded and the shield is properly grounded per
the Shields and Grounding section in Chapter 14.
2. Measure the input voltage on the terminal block. It should be in the range
of 0–5 V.
3. Verify that there are no or minimal AC components to the Analog Input
signal. AC components can be caused by improper shielding.
4. Check the wiring. If the inputs are reading 0 or the engineering units that
correspond to 0 mA or volts, look for a loose connection on the terminal
blocks, disconnected or misconnected cables, a missing jumper on the
terminal block if the input is a current input, or a blown fuse on the
24 Vdc on the FTM.
5. If all of the inputs are reading high, check that the 24 Vdc is not
connected across the input directly.
6. Check the software configuration to ensure that the input is configured
properly.
7. Check the fuse on the FTM. See the instructions and fuse locations
below.
192 Woodward
Manual 26167V1 MicroNet TMR
8. If the other channels on the Analog Combo module are not working
either, check the fuse on the Analog Combo module. See instructions for
module replacement in Chapter 15. This fuse is visible and can be
changed through the bottom of the module. If the fuse is blown, fix the
wiring problem, then replace the fuse with another fuse of the same type
and rating.
9. After verifying all of the above, exchange the J1 and J2 cables. If the
problem moves to a different channel, replace the cable. If not, replace
the Analog Combo module.
10. If the readings are incorrect on several channels of the module,
corresponding to both cables, replace the Analog Combo module.
11. If replacing the module does not fix the problem, replace the FTM. See
instructions for replacing the FTM in Chapter 15. The FTM does not
contain any active components on the MPU inputs, so replacing it should
be the last option.
Analog Outputs
If an analog output is not functioning properly, verify the following:
1. Check that the cable is shielded and the shield is properly grounded per
the Shields and Grounding section in Chapter 14.
2. Check the load resistance to ensure that it is not greater than 600 ohms.
3. Check to ensure that the load wiring is isolated.
4. Check the wiring for a loose connection on the terminal blocks and
disconnected or misconnected cables.
5. Disconnect the field wiring and connect a resistor across the output. If
the output is correct across the resistor, there is a problem with the field
wiring.
6. If the other output channels on the Analog Combo module are also not
working, check the fuse on the Analog Combo module. See instructions
for module replacement in Chapter 15. This fuse is visible and can be
changed through the bottom of the module. If the fuse is blown, fix the
wiring problem and replace the fuse with a fuse of the same type and
rating.
7. Check the software configuration to ensure that the output is configured
properly.
8. After verifying all of the above, exchange the J1 and J2 cables. If the
problem moves to a different channel, replace the cable. If not, replace
the Analog Combo module.
9. If the readings are incorrect on several channels of the module,
corresponding to both cables, replace the Analog Combo module.
10. If replacing the module does not fix the problem, replace the FTM. See
instructions for replacing the FTM in Chapter 15. The FTM does not
contain any active components on the MPU inputs, so replacing it should
be the last option.
Woodward 193
MicroNet TMR Manual 26167V1
Actuator Outputs
If an actuator output is not functioning properly, verify the following:
1. Check that the cable is shielded and the shield is properly grounded per
the Shields and Grounding section in Chapter 14.
2. Check the load resistance to ensure that it is below the specified limit.
3. Check to ensure that the load wiring is isolated.
4. Check the wiring for a loose connection on the terminal blocks or
disconnected or misconnected cables.
5. Disconnect the field wiring and connect a resistor across the output.
6. If the other output channels on the Analog Combo module are also not
working, check the fuse on the Analog Combo module. See instructions
for module replacement in Chapter 15. This fuse is visible and can be
changed through the bottom of the module. If the fuse is blown, fix the
wiring problem, and replace the fuse with a fuse of the same type and
rating.
7. Check the software configuration to ensure that the output is configured
properly.
8. After verifying all of the above, exchange the J1 and J2 cables. If the
problem moves to a different channel, replace the cable. If not, replace
the Analog Combo module.
9. If the readings are incorrect on several channels of the module,
corresponding to both cables, replace the Analog Combo module.
10. If replacing the module does not fix the problem, replace the FTM. See
instructions for replacing the FTM in Chapter 15. The FTM does not
contain any active components on the MPU inputs, so replacing it should
be the last option.
If power has not been removed from the control system, power will
be active at the module and also at the FTM. Shorting of protected
circuitry could cause a control system shutdown.
2. Remove FTM cover carefully, to prevent contact with any FTM circuitry
under the cover. To remove the FTM cover, pinch the retaining barb and
lift the cover.
3. Locate and replace the fuse with another fuse of the same size and
rating.
4. Replace the FTM cover.
194 Woodward
Manual 26167V1 MicroNet TMR
Woodward 195
MicroNet TMR Manual 26167V1
8.8.2—Module Specifications
Thermocouple/4–20 mA Analog Inputs
Number of channels: 24
Current range: 0-24 mA (if configured for 4–20 mA)
Voltage range: ±72.8 mV (if configured for thermocouple)
Input impedance: 103 ohms (±1%) for 4–20 mA inputs
196 Woodward
Manual 26167V1 MicroNet TMR
Thermocouple Accuracy
The overall accuracy of the thermocouple measurement is dependent on the
ambient temperature of the board. The following accuracies are based on a
board temperature between 0 and 55C. All accuracies are in percent of full scale
range for the type of thermocouple and the range specified.
CJ Update time: 5 ms
CJ accuracy: ±3 C
Latency
odd numbered channels: 1 ms
even numbered channels: 3 ms
Failure detection: Open wire detection provided for thermocouples
Isolation: All input channels are isolated from the rest of
the MicroNet platform to 500 Vdc, however they
are not isolated from each other. The inputs are
differential, with a high impedance between
channels.
Woodward 197
MicroNet TMR Manual 26167V1
RTD Range
(Must conform to DIN (Deutsche Institut for Normung) standard for 100 or 200
ohm European curve (Alpha = .00385) or American curve 100 or 200 ohm curve
(Alpha = .00392))
100 RTD (European Curve): 18.49 (–200 C/–328 F) to 390.48 (850
C/1562 F)
200 RTD (European Curve): 37.04 (–200 C/–328 F) to 533.10 (457
C/854.6 F)
100 RTD (American Curve): 59.57 (–100 C/–148 F) to 269.35 (457
C/854.6 F)
200 RTD (American Curve): 119.14 (–100 C/–148 F) to 538.70
(457 C/854.6 F)
RTD Accuracy
The overall accuracy of the RTD measurement is dependent on the ambient
temperature of the board. The following accuracies are based on a board
temperature between 0 and 55C. All accuracy are in percent of full scale range
for the type of RTD specified.
Update time: 5 ms
I/O Latency: 1 ms
Isolation: All input channels are isolated from the rest of the MicroNet platform to
500 Vdc, however inputs are not isolated from each other.
8.8.3—Installation
The modules slide into card guides in the control's chassis and plug into the
motherboard. The modules are held in place by two screws, one at the top and
one at the bottom of the front panel. Also at the top and bottom of the module are
two handles which, when toggled (pushed outward), move the modules out just
far enough for the boards to disengage the motherboard connectors.
198 Woodward
Manual 26167V1 MicroNet TMR
In a Simplex system, each 34 Ch HDVIM module is connected through two high
density 62 conductor analog cables to two 34 Ch HDVIM FTMs. All inputs on the
module are accessible on the FTM, and the channels are labeled to correspond
to their software locations (e.g., analog input 1 on the FTM will be analog input 1
in the application software). See Figure 8-32. for an example.
J1
P1
J2
P1
P2
34Ch HDVIM FTM
J1 (AI/TC Ch. 1-12)
(RTD Ch. 1-4)
Loop power for the Analog inputs must be supplied by an external supply, if
needed. This supply should be wired to terminals 40 and 81 on each FTM. The
FTM will fuse and distribute the power to 9 sets of terminals on the FTM. The 4–
20 mA, thermocouple, or RTD configurable inputs are selected in the GAP block
software, for each input. The GAP block configuration sets input gain via
software. The maximum wire size that the FTM can accept is one 16 AWG or two
20 AWG wires.
Woodward 199
MicroNet TMR Manual 26167V1
200 Woodward
Manual 26167V1 MicroNet TMR
4–20 mA Inputs
For a 4–20 mA input signal, the 34 Ch HDVIM module uses a 100 ohm resistor
across the input. All 4–20 mA inputs may be used with two-wire ungrounded
(loop powered) transducers or isolated (self-powered) transducers. All Analog
inputs have 11 Vdc of common mode rejection. If interfacing to a non-isolated
device, which may have the potential of reaching over 11 Vdc with respect to the
control’s common, the use of a loop isolator is recommended to break any return
current paths, which could produce erroneous readings. 0–5 V inputs are not
supported by this module. No loop power is provided by the MicroNet module. An
external supply must be connected to the FTM for powering loop powered inputs.
RTD Inputs
RTD inputs must be configured to use either the European or American curve in
software. Only 100 and 200 ohm platinum RTDs are supported. 200 ohm RTDs
are limited to the maximum temperature on the American curve, even when the
European curve is used. The RTD source current is 2 mA, and the RTD sense
input should be tied to the negative side of the RTD, at the RTD.
Thermocouple Inputs
See Module Specifications for supported thermocouple types. A cold junction
sensor is provided on the 34 Ch HDVIM FTM. If the actual cold junction in the
field wiring occurs elsewhere, the temperature of that junction must be brought
into the control as a thermocouple, RTD, or 4–20 mA input, and the application
software must be configured to use the appropriate cold junction temperature.
The thermocouple and cold junction input units (C or F) should be consistent in
the application software.
The first 12 Analog inputs on each FTM are isolated as a group from control
common, earth ground, and the rest of the Analog inputs. The next 4 or 6 Analog
inputs on the FTM are also isolated as a group from control common, earth
ground, and the rest of the Analog inputs. This results in 4 isolated groups of
inputs on each module.
8.8.4—FTM Reference
See Chapter 12 for complete 34 Ch HDVIM FTM field wiring information. See
Appendix A for proper Module, FTM, and cable part numbers.
Woodward 201
MicroNet TMR Manual 26167V1
Figure 8-37—RTD Input Interface Wiring to the 34 Ch HDVIM Module for RTDs
on 4–20 mA/RTD Inputs
202 Woodward
Manual 26167V1 MicroNet TMR
8.8.5—Troubleshooting
Each 34 Ch HDVIM module has a red fault LED that is turned on when the
system is reset. During initialization of a board, which occurs after every CPU
reset, the CPU turns the Fault LED on. The CPU then tests the board using
diagnostic routines built into the software. If the diagnostic test is not passed, the
LED remains on or blinks. If the test is successful, the LED goes off. If the fault
LED on a board is illuminated after the diagnostics and initialization have been
completed, the 34 Ch HDVIM module may be faulty.
Analog Input Faults. The application software may set a high and low latch
setpoint to detect input faults. For thermocouple inputs, open wire detection is
provided.
Woodward 203
MicroNet TMR Manual 26167V1
Troubleshooting Guide
If an Analog input is not functioning properly, verify the following:
1. Check that the cable is shielded and the shield is properly grounded per
the Shields and Grounding section in Chapter 14.
2. Measure the input voltage on the terminal block. It should be in the range
of 0–5 V for 4–20 mA inputs. RTD inputs have a 2 mA current source.
Thermocouple inputs should have the appropriate millivolt signal.
3. Verify that there are no or minimal AC components to the Analog Input
signal. AC components can be caused by improper shielding.
Thermocouple inputs are extremely sensitive to signal fluctuations.
4. Check the wiring. For a 4–20 mA input if the input is reading 0 or the
engineering units that correspond to 0 mA, look for a loose connection at
the terminal blocks and disconnected or misconnected cables.
5. For RTD inputs, check for proper connection of the sense line.
6. For thermocouple inputs, check for proper cold junction location.
7. If the input is reading high, check that the power is not connected across
the input directly.
8. Check the software configuration to ensure that the input is configured
properly. Ensure that the proper RTD or thermocouple type is selected, if
applicable.
9. After verifying all of the above, exchange the J1 and J2 cables. If the
problem moves to a different channel, replace the cable. If not, replace
the 34 Ch HDVIM module.
10. If the readings are incorrect on several channels of the 34 Ch HDVIM
module, corresponding to both cables, replace the 34 Ch HDVIM
module.
11. If replacing the module does not fix the problem, replace the FTM. See
the instructions in Chapter 15 for replacing the FTM. The FTM contains
only traces and a few discrete components, so failure is extremely
unlikely.
204 Woodward
Manual 26167V1 MicroNet TMR
Woodward 205
MicroNet TMR Manual 26167V1
8.10.2—Specification
Number of Channels: 8
Input Range: 0–25 mA
Accuracy: 0.5% of full scale
Temperature Coefficient: 12 ppm/degrees C
Anti-aliasing filter 2 poles at 12 ms (Channels 1-8)
Module interface: VMEbus
Resolution: 16 bit converter
Isolation: 1500 Vac continuous (channel input to control
common)
CMRR: -90 db
Input Impedance: 249 ohms
Status Indication: RED LED - channel fault or board fault
8.10.3—Installation
The modules slide into card guides in the control's chassis and plug into the
motherboard. The modules are held in place by two screws, one at the top and
one at the bottom of the front panel. Also at the top and bottom of the module are
two handles which, when toggled (pushed outward), move the modules out just
far enough for the boards to disengage the motherboard connectors.
J1
P1
P2
J1
206 Woodward
Manual 26167V1 MicroNet TMR
Field Wiring
See Chapter 12 for complete wiring connections for the Analog Input FTM. See
Figure 8-40 for transducer wiring.
All analog inputs may be used with two-wire ungrounded (loop powered)
transducers or isolated (self-powered) transducers. Loop powered or self
powered 4–20 mA transducers may be connected to the current input modules
via the Analog Input FTM shown in Figure 8-40.
8.10.4—FTM Reference
See Chapter 12 for complete Analog Input FTM field wiring. See Appendix A for
proper Module, FTM, and cable part numbers.
8.10.5—Troubleshooting
The input MUX (multiplexer) permits the module to read either the value of the
precision-voltage reference for this channel, or the sensed input for this channel.
The MUX receives the current input and, under the control of the microcontroller,
passes the value through the Gain amplifier to the Isolation Amplifier. The output
of the Isolation Amplifier goes to one input of the channel-selecting MUX.
Woodward 207
MicroNet TMR Manual 26167V1
J2 J1 TB1
-15V +15V
19 19 1 +
15V1
.01uF Loop Powered
Gnd - Transducer
18 18 2
A1
+ 7.5V
Anti- 37 37 20
249
AI_01 aliasing Ohm
- Filter 36 36 21
-15V +15V
15V2 17 17 3
.01uF
Gnd
16 16 4
A2
+ 7.5V
35 35 22 +
Anti-
249 Self Powered
AI_02 aliasing Ohm Transducer
- Filter 34 34 23 -
-15V +15V
15V3 15 15 5 +15V
.01uF
Gnd
14 14 6 SHLD
7.5V
A3
Ch. 3
+
Anti- 33 33 24 +Input
249
AI_03 aliasing Ohm
- Filter 32 32 25 -Input
-15V +15V
15V4 13 13 7 +15V
.01uF
Gnd
12 12 8 SHLD
7.5V
A4
Ch. 4
+
Anti- 31 31 26 +Input
249
AI_04 aliasing Ohm
- Filter 30 30 27 -Input
-15V +15V
15V5 11 11 9 +15V
.01uF
Gnd
10 10 10 SHLD
7.5V
A5
Ch. 5
+
Anti- 29 29 28 +Input
249
AI_05 aliasing Ohm
- Filter 28 28 29 -Input
-15V +15V
15V6 9 9 11 +15V
.01uF
Gnd
8 8 12 SHLD
7.5V
A6
Ch. 6
+
Anti- 27 27 30 +Input
249
AI_06 aliasing Ohm
- Filter 26 26 31 -Input
-15V +15V
15V7 7 7 13 +15V
.01uF
Gnd
6 6 14 SHLD
7.5V
A7
Ch. 7
+
Anti- 25 25 32 +Input
249
AI_07 aliasing Ohm
- Filter 24 24 33 -Input
-15V +15V
15V8 5 5 15 +15V
.01uF
Gnd
4 4 16 SHLD
7.5V
A8
Ch. 8
+
Anti- 23 23 34 +Input
249
AI_08 aliasing Ohm
- Filter 22 22 35 -Input
3 3 17
2 2 18
1 1 19
21 21 36
20 20 37
Ground to DIN Rail
J1 Outer Shell 38
Figure 8-40—Analog Input Wiring for an 8 Ch Current Input (0–25 mA) Module
208 Woodward
Manual 26167V1 MicroNet TMR
This MUX, under control of the microprocessor, selects the channel to be read.
The analog output of this MUX is converted to a digital value by the A/D
converter, and passed to the microcontroller. The microcontroller makes any
necessary corrections to this value and stores the result in the Dual-Port RAM.
The CPU can then access the values stored in Dual-Port RAM through the VME
interface and bus. See Figure 8-41 for block diagram of module.
During initialization, which occurs after every reset, the CPU turns the FAULT
LEDs on. The CPU then tests each I/O module using diagnostic routines built
into software. If the diagnostic test is not passed, the LED remains on. If the test
is successful, the LED goes off.
During initialization of the module, the module's micro-controller turns the LED off
after power-on self tests have passed and the CPU has initialized the module.
The CPU also tells this module in which rate group each channel is to run, as
well as special information. At run time, the CPU then periodically broadcasts a
"key" to all I/O cards, telling them which rate groups are to be updated at that
time. Through this initialization/key broadcast system, each I/O module handles
its own rate-group scheduling with minimal CPU intervention.
This module also has on-card on-line fault detection and automatic
calibration/compensation. Each input channel has its own precision voltage
reference. Once per minute, while not reading inputs, the on-board
microcontroller reads this reference. The microcontroller then uses this data read
from the voltage reference for both fault detection and automatic temperature
compensation/calibration.
Woodward 209
MicroNet TMR Manual 26167V1
Limits have been set for the expected readings when the on-board
microcontroller reads each voltage reference. If the reading obtained is outside
these limits, the system determines that the input channel, A/D converter, or the
channel's precision-voltage reference is not functioning properly. If this happens,
the micro-controller flags that channel as having a fault condition. The CPU will
then take whatever action the application engineer has provided for in the
application program.
The readings from the precision-voltage reference are also used for on-line
temperature compensation and automatic calibration for the module. The
readings of the precision-voltage reference, obtained from the A/D converter, are
used by the microcontroller to determine software scaling- and offset-constants
for each channel. These scaling-and offset-constants are respectively multiplied
by and added to each channel reading to provide corrected channel readings.
The module therefore includes no potentiometers and needs no calibration.
Each I/O module has a fuse on it; this fuse is visible and can be changed through
a cutout in the plastic cover of the module. If this fuse is blown, replace it with a
fuse of the same type and size.
Troubleshooting Guide
If a current input is not functioning properly, verify the following:
1. Check that the cable is shielded and the shield is properly grounded per
the Shields and Grounding section in Chapter 14.
2. Measure the input voltage across the + and – inputs on the terminal
block. It should be in the range of 0–5 V.
3. Verify that there are no or minimal AC components to the Analog Input
signal. AC components can be caused by improper shielding.
4. Check the wiring. If the inputs are reading 0 or the engineering units that
correspond to 0 mA, look for a loose connection on the terminal blocks,
disconnected or misconnected cables.
5. Check the software configuration to ensure that the input is configured
properly.
6. If the other channels on the module are not working either, check the
fuse on the 8 Ch Current Input (0–25 mA) module. This fuse is visible
and can be changed through the bottom of the module. If the fuse is
blown, fix the wiring problem, then replace the fuse with another fuse of
the same type and rating.
7. If the problem remains,, swap out the 8 Ch Current Input (0–25 mA)
module with another module of the same part number. If the problem
remains, replace the cable.
8. If the problem remains, replace the FTM. The FTM contains only traces
and a few discrete components, so failure is extremely unlikely. See
instructions for replacing the FTM in Chapter 15.
210 Woodward
Manual 26167V1 MicroNet TMR
Woodward 211
MicroNet TMR Manual 26167V1
8.11.2—Specification
Number of Channels: 8
Input Range: 0–25 mA
Accuracy: 0.5% of full scale
Temperature Coefficient: 12 ppm/degrees C
Anti-aliasing filter 2 poles at 12 ms (Channels 1-6)
Anti-aliasing filter 2 poles at 5 ms (Channels 7-8)
(Channel 8 is the derivative of channel 7.)
Module interface: VMEbus
Resolution: 16 bit converter
Isolation: 1500 Vac continuous (channel input to control
common)
CMRR: -90 db
Input Impedance: 249 Ohms
Status Indication: RED LED - channel fault or board fault
8.11.3—Installation
The modules slide into card guides in the control's chassis and plug into the
motherboard. The modules are held in place by two screws, one at the top and
one at the bottom of the front panel. Also at the top and bottom of the module are
two handles which, when toggled (pushed outward), move the modules out just
far enough for the boards to disengage the motherboard connectors.
J1
P1
P2
J1
Non-Standard
Analog Input FTM
212 Woodward
Manual 26167V1 MicroNet TMR
Field Wiring
See Chapter 12 for complete wiring connections for the Non-standard Analog
Input FTM. See Figure 8-44 for transducer wiring.
The first six analog inputs may be used with two-wire ungrounded (loop powered)
transducers or isolated (self-powered) transducers. The seventh channel can be
used with a self powered transducer only. Channel eight should not be
connected to any field wiring. Loop powered or self powered 4–20 mA
transducers may be connected to the current input modules via the Non-
Standard Analog Input FTM shown in Figure 8-44.
8.11.4—FTM Reference
The output from channel seven is split and fed to channel seven on the Non-
Standard Current Input (4–20 mA) Module and also fed through a derivative
circuit on the FTM to channel eight on the Non-Standard Current Input (4–20 mA)
Module. See Chapter 12 for complete field wiring information for the Non-
Standard Analog Input FTM. See Appendix A for proper Module, FTM, and cable
part numbers.
8.11.5—Troubleshooting
The input MUX (multiplexer) permits the module to read either the value of the
precision-voltage reference for this channel, or the sensed input for this channel.
The MUX receives the current input and, under the control of the microcontroller,
passes the value through the Gain amplifier to the Isolation Amplifier. The output
of the Isolation Amplifier goes to one input of the channel-selecting MUX.
Woodward 213
MicroNet TMR Manual 26167V1
MicroNet Module CABLE FTM
J2 J1 TB1
-15V +15V
19 19 1 +
15V1
.01uF Loop Powered
Gnd - Transducer
18 18 2
A1
+ 7.5V
Anti- 37 37 20
249
AI_01 aliasing Ohm
- Filter 36 36 21
-15V +15V
15V2 17 17 3
.01uF
Gnd
16 16 4
A2
+ 7.5V
35 35 22 +
Anti-
249 Self Powered
AI_02 aliasing Ohm Transducer
- Filter 34 34 23 -
-15V +15V
15V3 15 15 5 +15V
.01uF
Gnd
14 14 6 SHLD
7.5V
A3
Ch. 3
+
Anti- 33 33 24 +Input
249
AI_03 aliasing Ohm
- Filter 32 32 25 -Input
-15V +15V
15V4 13 13 7 +15V
.01uF
Gnd
12 12 8 SHLD
7.5V
A4
Ch. 4
+
Anti- 31 31 26 +Input
249
AI_04 aliasing Ohm
- Filter 30 30 27 -Input
-15V +15V
15V5 11 11 9 +15V
.01uF
Gnd
10 10 10 SHLD
7.5V
A5
Ch. 5
+
Anti- 29 29 28 +Input
249
AI_05 aliasing Ohm
- Filter 28 28 29 -Input
-15V +15V
15V6 9 9 11 +15V
.01uF
Gnd
8 8 12 SHLD
7.5V
A6
Ch. 6
+
Anti- 27 27 30 +Input
249
AI_06 aliasing Ohm
- Filter 26 26 31 -Input
-15V +15V
15V7 7 7 13 +15V
.01uF
Gnd
6 6 14 SHLD
7.5V
A7
Ch. 7
+ Special 25 25 32 +Input
Anti- 249
AI_07 aliasing Ohm
- 24 24 33 -Input
Filter
+15V In
Derivative
Circuit
-15V Out
-15V +15V
15V8 5 5 15 NC
.01uF
Gnd
4 4 16 NC
7.5V
A8
Ch. 8
+ Special 23 23 34 NC
Anti- 249
AI_08 aliasing Ohm
- 22 22 35 NC
Filter
3 3 17
2 2 18
1 1 19
21 21 36
20 20 37
Ground to DIN Rail
J1 Outer Shell 38
214 Woodward
Manual 26167V1 MicroNet TMR
This MUX, under control of the microprocessor, selects the channel to be read.
The analog output of this MUX is converted to a digital value by the A/D
converter, and passed to the microcontroller. The microcontroller makes any
necessary corrections to this value and stores the result in the Dual-Port RAM.
The CPU can then access the values stored in Dual-Port RAM through the VME
interface and bus. See Figure 8-41 for block diagram of module.
During initialization, which occurs after every reset, the CPU turns the FAULT
LEDs on. The CPU then tests each I/O module using diagnostic routines built
into software. If the diagnostic test is not passed, the LED remains on. If the test
is successful, the LED goes off.
During initialization of the module, the module's micro-controller turns the LED off
after power-on self tests have passed and the CPU has initialized the module.
The CPU also tells this module in which rate group each channel is to run, as
well as special information. At run time, the CPU then periodically broadcasts a
"key" to all I/O cards, telling them which rate groups are to be updated at that
time. Through this initialization/key broadcast system, each I/O module handles
its own rate-group scheduling with minimal CPU intervention.
This module also has on-card on-line fault detection and automatic
calibration/compensation. Each input channel has its own precision voltage
reference. Once per minute, while not reading inputs, the on-board
microcontroller reads this reference. The microcontroller then uses this data read
from the voltage reference for both fault detection and automatic temperature
compensation/calibration.
Limits have been set for the expected readings when the on-board
microcontroller reads each voltage reference. If the reading obtained is outside
these limits, the system determines that the input channel, A/D converter, or the
channel's precision-voltage reference is not functioning properly. If this happens,
the micro-controller flags that channel as having a fault condition. The CPU will
then take whatever action the application engineer has provided for in the
application program.
The readings from the precision-voltage reference are also used for on-line
temperature compensation and automatic calibration for the module. The
readings of the precision-voltage reference, obtained from the A/D converter, are
used by the microcontroller to determine software scaling- and offset-constants
for each channel. These scaling-and offset-constants are respectively multiplied
by and added to each channel reading to provide corrected channel readings.
The module therefore includes no potentiometers and needs no calibration.
Each I/O module has a fuse on it; this fuse is visible and can be changed through
a cutout in the plastic cover of the module. If this fuse is blown, replace it with a
fuse of the same type and size.
Woodward 215
MicroNet TMR Manual 26167V1
Troubleshooting Guide
If a current input is not functioning properly, verify the following:
1. Check that the cable is shielded and the shield is properly grounded per
the Shields and Grounding section in Chapter 14.
2. Measure the input voltage across the + and – inputs on the terminal
block. It should be in the range of 0–5 V.
3. Verify that there are no or minimal AC components to the Analog Input
signal. AC components can be caused by improper shielding.
4. Check the wiring. If the inputs are reading 0 or the engineering units that
correspond to 0 mA, look for a loose connection on the terminal blocks,
disconnected or misconnected cables.
5. Check the software configuration to ensure that the input is configured
properly.
6. If the other channels on the module are not working either, check the
fuse on the Non-Standard 8 Ch Current Input (0–25 mA) module. This
fuse is visible and can be changed through the bottom of the module. If
the fuse is blown, fix the wiring problem, then replace the fuse with
another fuse of the same type and rating.
7. If the problem remains,, swap out the Non-Standard 8 Ch Current Input
(0–25 mA) module with another module of the same part number. If the
problem remains, replace the cable.
8. If the problem remains, replace the FTM. The FTM contains only traces
and a few discrete components, so failure is extremely unlikely. See
instructions for replacing the FTM in Chapter 15.
216 Woodward
Manual 26167V1 MicroNet TMR
8.13.2—Specification
Number of Channels: 8
Input Range: 0–10 Volts
Accuracy: 0.5% of full scale
Temperature Coefficient: 12 ppm/degrees C
Anti-aliasing filter 2 poles at 12 ms (Channels 1-8)
Module interface: VMEbus
Resolution: 16 bit converter
Isolation: 1500 Vac continuous (channel input to control
common)
CMRR: -90 db
Input Impedance: 2 MΩ
Status Indication: RED LED - channel fault or board fault
8.13.3—Installation
The modules slide into card guides in the control's chassis and plug into the
motherboard. The modules are held in place by two screws, one at the top and
one at the bottom of the front panel. Also at the top and bottom of the module are
two handles which, when toggled (pushed outward), move the modules out just
far enough for the boards to disengage the motherboard connectors.
Woodward 217
MicroNet TMR Manual 26167V1
In a simplex system, each 8 Ch Voltage Input module is connected through one
analog cable to one FTM. All of the I/O are accessible on the FTM.
J1
P1
P2
J1
Field Wiring
See Chapter 12 for complete wiring connections for the Analog Input FTM. See
Figure 8-47 for transducer wiring.
8.13.4—FTM Reference
See Chapter 12 for complete field wiring information for the Voltage Input (0–10
Vdc) FTM. See Appendix A for part number Cross Reference for modules, FTMs,
and cables.
8.13.5—Troubleshooting
The input MUX (multiplexer) permits the module to read either the value of the
precision-voltage reference for this channel, or the sensed input for this channel.
The MUX receives the voltage input and, under the control of the microcontroller,
passes the value through the Gain amplifier to the Isolation Amplifier. The output
of the Isolation Amplifier goes to one input of the channel-selecting MUX.
218 Woodward
Manual 26167V1 MicroNet TMR
J2 J1 TB1
19 19 1 NC
.01uF
18 18 2
+
37 37 20 +
Anti-
0-10VDC
AI_01 aliasing
Transducer
- Filter 36 36 21 -
17 17 3 NC
.01uF
16 16 4 SHLD
+
Anti- 35 35 22 +Input Ch. 2
AI_02 aliasing
- Filter 34 34 23 -Input
15 15 5 NC
.01uF
14 14 6 SHLD
+
Anti- 33 33 24 +Input Ch. 3
AI_03 aliasing
- Filter 32 32 25 -Input
13 13 7 NC
.01uF
12 12 8 SHLD
+
Anti- 31 31 26 +Input Ch. 4
AI_04 aliasing
- Filter 30 30 27 -Input
11 11 9 NC
.01uF
10 10 10 SHLD
+
Anti- 29 29 28 +Input Ch. 5
AI_05 aliasing
- Filter 28 28 29 -Input
9 9 11 NC
.01uF
8 8 12 SHLD
+
Anti- 27 27 30 +Input Ch. 6
AI_06 aliasing
- Filter 26 26 31 -Input
7 7 13 NC
.01uF
6 6 14 SHLD
+
Anti- 25 25 32 +Input Ch. 7
AI_07 aliasing
- Filter 24 24 33 -Input
5 5 15 NC
.01uF
4 4 16 SHLD
+
Anti- 23 23 34 +Input Ch. 8
AI_08 aliasing
- Filter 22 22 35 -Input
3 3 17
2 2 18
1 1 19
21 21 36
20 20 37
Ground to DIN Rail
J1 Outer Shell 38
Figure 8-47—Voltage Input Wiring for an 8 Channel Voltage Input (0–10 Vdc)
Module
Woodward 219
MicroNet TMR Manual 26167V1
This MUX, under control of the microprocessor, selects the channel to be read.
The analog output of this MUX is converted to a digital value by the A/D
converter, and passed to the microcontroller. The microcontroller makes any
necessary corrections to this value and stores the result in the Dual-Port RAM.
The CPU can then access the values stored in Dual-Port RAM through the VME
interface and bus. See Figure 8-48 for block diagram of module.
During initialization, which occurs after every reset, the CPU turns the FAULT
LEDs on. The CPU then tests each I/O module using diagnostic routines built
into software. If the diagnostic test is not passed, the LED remains on. If the test
is successful, the LED goes off.
During initialization of the module, the module's micro-controller turns the LED off
after power-on self tests have passed and the CPU has initialized the module.
The CPU also tells this module in which rate group each channel is to run, as
well as special information. At run time, the CPU then periodically broadcasts a
"key" to all I/O cards, telling them which rate groups are to be updated at that
time. Through this initialization/key broadcast system, each I/O module handles
its own rate-group scheduling with minimal CPU intervention.
This module also has on-card on-line fault detection and automatic
calibration/compensation. Each input channel has its own precision voltage
reference. Once per minute, while not reading inputs, the on-board
microcontroller reads this reference. The microcontroller then uses this data read
from the voltage reference for both fault detection and automatic temperature
compensation/calibration.
220 Woodward
Manual 26167V1 MicroNet TMR
Limits have been set for the expected readings when the on-board
microcontroller reads each voltage reference. If the reading obtained is outside
these limits, the system determines that the input channel, A/D converter, or the
channel's precision-voltage reference is not functioning properly. If this happens,
the micro-controller flags that channel as having a fault condition. The CPU will
then take whatever action the application engineer has provided for in the
application program.
The readings from the precision-voltage reference are also used for on-line
temperature compensation and automatic calibration for the module. The
readings of the precision-voltage reference, obtained from the A/D converter, are
used by the microcontroller to determine software scaling- and offset-constants
for each channel. These scaling-and offset-constants are respectively multiplied
by and added to each channel reading to provide corrected channel readings.
The module therefore includes no potentiometers and needs no calibration.
Each I/O module has a fuse on it; this fuse is visible and can be changed through
a cutout in the plastic cover of the module. If this fuse is blown, replace it with a
fuse of the same type and size.
Troubleshooting Guide
If a voltage input is not functioning properly, verify the following:
1. Check that the cable is shielded and the shield is properly grounded per
the Shields and Grounding section in Chapter 14.
2. Measure the input voltage across the + and – inputs on the terminal
block. It should be in the range of 0–5 V.
3. Verify that there are no or minimal AC components to the Analog Input
signal. AC components can be caused by improper shielding.
4. Check the wiring. If the inputs are reading 0 or the engineering units that
correspond to 0 V, look for a loose connection on the terminal blocks,
disconnected or misconnected cables.
5. Check the software configuration to ensure that the input is configured
properly.
6. If the other channels on the module are not working either, check the
fuse on the 8 Ch Voltage Input (0–10 Vdc) module. This fuse is visible
and can be changed through the bottom of the module. If the fuse is
blown, fix the wiring problem, then replace the fuse with another fuse of
the same type and rating.
7. If the problem remains,, swap out the 8 Ch Voltage Input (0–10 Vdc)
module with another module of the same part number. If the problem
remains, replace the cable.
8. If the problem remains, replace the FTM. The FTM contains only traces
and a few discrete components, so failure is extremely unlikely. See
instructions for replacing the FTM in Chapter 15.
Woodward 221
MicroNet TMR Manual 26167V1
222 Woodward
Manual 26167V1 MicroNet TMR
8.15.2—Specification
Number of Channels: 8
Current range: 0–25 mA
Maximum load resistance: 600 ohms max.
Analog Channel bandwidth: 500 Hz min.
Module interface: VMEbus
Output update time: 1 ms
Resolution: 12 bit
Accuracy: 0.1% of full scale @25 degrees C
Maximum Drift: 50 ppm/degrees C
Status Indication: RED LED - channel fault or board fault
Channel faults: Output current monitored
Microcontroller faults: System monitors a software watchdog
System faults: All outputs are set to zero if MFT is lost.
Operating Temp: 0 to 70 °C
Isolation: None
8.15.3—Installation
The modules slide into card guides in the control's chassis and plug into the
motherboard. The modules are held in place by two screws, one at the top and
one at the bottom of the front panel. Also at the top and bottom of the module are
two handles which, when toggled (pushed outward), move the modules out just
far enough for the boards to disengage the motherboard connectors.
J1
P1
P2
J1
Woodward 223
MicroNet TMR Manual 26167V1
There are 8 analog output channels of 4–20 mA with a full scale range of 0–25
mA. All Analog Outputs can drive a maximum load of 600 ohms (load + wire
resistance). See Figure 8-51 for analog output connection. Each output monitors
the output source current for fault detection. All of the analog outputs may be
individually disabled. When a channel fault or a module fault is detected, the
application program may annunciate the fault, disable the channel and stop using
data in system calculations or control. Care should be taken to prevent ground
loops and other faults when interfacing to non-isolated devices.
8.15.4—FTM Reference
See Chapter 12 for complete field wiring information for the 8 Ch Current Output
(4–20 mA) FTM. See Appendix A for part number Cross Reference for modules,
FTMs, and cables.
8.15.5—Troubleshooting
The system writes output values to the Dual-Port RAM through the VME bus and
interface. The microcontroller scales the data using calibration constants stored
in EEPROM, and schedules outputs to occur at the proper time.
224 Woodward
Manual 26167V1 MicroNet TMR
J2 J1 TB1
19 19 1 NC
+24 .01uF
V
18 18 2 SHLD
37 37 20 +Output Ch. 1
I/O Lockout AO_01
36 36 21 -Output
Analog
+
Output 17 17 3 NC
- .01uF
Feedback
16 16 4
Analog
B +
Output 35 35 22 Ch. 2
Output
AO_02 Device
34 34 23 -
24 COM
15 15 5 NC
.01uF
14 14 6 SHLD
33 33 24 +Output Ch. 3
AO_03
32 32 25 -Output
13 13 7 NC
.01uF
12 12 8 SHLD
31 31 26 +Output Ch. 4
AO_04
30 30 27 -Output
11 11 9 NC
.01uF
10 10 10 SHLD
29 29 28 +Output Ch. 5
AO_05
28 28 29 -Output
9 9 11 NC
.01uF
8 8 12 SHLD
27 27 30 +Output Ch. 6
AO_06
26 26 31 -Output
7 7 13 NC
.01uF
6 6 14 SHLD
25 25 32 +Output Ch. 7
AO_07
24 24 33 -Output
5 5 15 NC
.01uF
4 4 16 SHLD
23 23 34 +Output Ch. 8
AO_08
22 22 35 -Output
3 3 17 NC
2 2 18 NC
1 1 19 NC
21 21 36 NC
20 20 37
Ground to DIN Rail
J1 Outer Shell 38
Figure 8-51—Analog Output Wiring for an 8 Channel Current Output (4–20 mA)
Module
Woodward 225
MicroNet TMR Manual 26167V1
The microcontroller monitors the output current of each channel and alerts the
system if a fault is detected. The current-output drivers can be disabled by the
system. If a fault, which prevents the entire card from operating is detected by
either the microcontroller or the system, the FAULT LED will illuminate. See
Figure 8-52 for module block diagram.
226 Woodward
Manual 26167V1 MicroNet TMR
Woodward 227
MicroNet TMR Manual 26167V1
8.16.2—Specification
Number of Channels: 8
Current range: 0 – 1.25 mA
Maximum load resistance: 10 k max.
Analog Channel bandwidth: 500 Hz min.
Module interface: VMEbus
Output update time: 1 ms
Resolution: 12 bit
Accuracy: 0.1% of full scale @25 °C
Maximum Drift: 50 ppm/degrees C
Status Indication: RED LED - channel fault or board fault
Channel faults: Output current monitored
Microcontroller faults: System monitors a software watchdog
System faults: All outputs are set to zero if MFT is lost.
Operating Temp: 0 to 70 °C
Isolation: None
8.16.3—Installation
See 8 Ch Current Output (4–20 mA) Module.
8.16.4—FTM Reference
See Chapter 12 for complete field wiring information for the 8 Ch Current Output
(0–1 mA) FTM. See Appendix A for part number Cross Reference for modules,
FTMs, and cables.
8.16.5—Troubleshooting
See 8 Ch Current Output (4–20 mA) Module.
228 Woodward
Manual 26167V1 MicroNet TMR
Woodward 229
MicroNet TMR Manual 26167V1
8.18.2—Specification
Number of Channels: 8
Current range: 0–6.25 V
Minimum load resistance: 500 ohms
Analog Channel bandwidth: 500 Hz min.
Module interface: VMEbus
Output update time: 1 ms
Resolution: 12 bit
Accuracy: 0.1% of full scale @25 °C
Maximum Drift: 50 ppm/degrees C
Status Indication: RED LED - channel fault or board fault
Channel faults: Output current monitored
Microcontroller faults: System monitors a software watchdog
System faults: All outputs are set to zero if MFT is lost.
Operating Temp: 0 to 70 °C
Isolation: None
8.18.3—Installation
The modules slide into card guides in the control's chassis and plug into the
motherboard. The modules are held in place by two screws, one at the top and
one at the bottom of the front panel. Also at the top and bottom of the module are
two handles which, when toggled (pushed outward), move the modules out just
far enough for the boards to disengage the motherboard connectors.
J1
P1
P2
J1
230 Woodward
Manual 26167V1 MicroNet TMR
There are 8 analog output channels of 0–5 Vdc with a full scale range of
0-6.25 Vdc. All Analog Outputs can drive a minimum load of 500 ohms (load +
wire resistance). See Figure 8-56 for analog output connection. Each output
monitors the output source voltage for fault detection. All of the analog outputs
may be individually disabled. When a channel fault or a module fault is detected,
the application program may annunciate the fault, disable the channel and stop
using data in system calculations or control. Care should be taken to prevent
ground loops and other faults when interfacing to non-isolated devices.
8.18.4—FTM Reference
See Chapter 12 for complete field wiring information for the 8 Ch Voltage Output
(0–5 Vdc) FTM. See Appendix A for part number Cross Reference for modules,
FTMs, and cables.
8.18.5—Troubleshooting
Figure 8-57 is a block diagram of the Voltage Output Module with eight 0–5 Vdc
outputs.
The system writes output values to the Dual-Port RAM through the VME bus and
interface. The microcontroller scales the data using calibration constants stored
in EEPROM, and schedules outputs to occur at the proper time.
The microcontroller monitors the output voltage of each channel and alerts the
system if a fault is detected. If a fault, which prevents the entire card from
operating is detected by either the microcontroller or the system, the FAULT LED
will illuminate.
Woodward 231
MicroNet TMR Manual 26167V1
J2 J1 TB1
19 19 1 NC
+24 V .01uF
18 18 2 SHLD
37 37 20 +Output Ch. 1
I/O Lockout AO_01
36 36 21 -Output
Analog 17 17 3 NC
Output B
.01uF
16 16 4
35 35 22 + Ch. 2
Analog Output
+ AO_02
Output - - Device
34 34 23
Feedback
24 COM 15 15 5 NC
.01uF
14 14 6 SHLD
33 33 24 +Output Ch. 3
AO_03
32 32 25 -Output
13 13 7 NC
.01uF
12 12 8 SHLD
31 31 26 +Output Ch. 4
AO_04
30 30 27 -Output
11 11 9 NC
.01uF
10 10 10 SHLD
29 29 28 +Output Ch. 5
AO_05
28 28 29 -Output
9 9 11 NC
.01uF
8 8 12 SHLD
27 27 30 +Output Ch. 6
AO_06
26 26 31 -Output
7 7 13 NC
.01uF
6 6 14 SHLD
25 25 32 +Output Ch. 7
AO_07
24 24 33 -Output
5 5 15 NC
.01uF
4 4 16 SHLD
23 23 34 +Output Ch. 8
AO_08
22 22 35 -Output
3 3 17 NC
2 2 18 NC
1 1 19 NC
21 21 36 NC
20 20 37
Ground to DIN Rail
J1 Outer Shell 38
Figure 8-56—Analog Output Wiring for an 8 Channel Voltage Output (0–5 Vdc)
Module
232 Woodward
Manual 26167V1 MicroNet TMR
Woodward 233
MicroNet TMR Manual 26167V1
234 Woodward
Manual 26167V1 MicroNet TMR
8.19.2—Specification
Number of Channels: 8
Current range: 0 – 12.5 V
Maximum load resistance: 500 ohms min.
Analog Channel bandwidth: 500 Hz min.
Module interface: VMEbus
Output update time: 1 ms
Resolution: 12 bit
Accuracy: 0.1% of full scale @ 25 °C
Maximum Drift: 50 ppm/degrees C
Status Indication: RED LED - channel fault or board fault
Channel faults: Output current monitored
Microcontroller faults: system monitors a software watchdog
System faults: All outputs are set to zero if MFT is lost.
Operating Temp: 0 to 70 °C
Isolation: None
8.19.3—Installation
See 8 Ch Voltage Output (0–5 Vdc) Module.
8.19.4—FTM Reference
See Chapter 12 for complete field wiring information for the 8 Ch Voltage Output
(0–10 Vdc) FTM. See Appendix A for part number Cross Reference for modules,
FTMs, and cables.
8.19.5—Troubleshooting
See 8 Ch Voltage Output (0–5 Vdc) Module.
Woodward 235
MicroNet TMR Manual 26167V1
236 Woodward
Manual 26167V1 MicroNet TMR
8.21.2—Specification
Number Channels: 8 double ended, fully isolated, thermocouple
input channels
1 cold junction channel.
8.21.3—Installation
The modules slide into card guides in the control's chassis and plug into the
motherboard. The modules are held in place by two screws, one at the top and
one at the bottom of the front panel. Also at the top and bottom of the module are
two handles which, when toggled (pushed outward), move the modules out just
far enough for the boards to disengage the motherboard connectors.
Woodward 237
MicroNet TMR Manual 26167V1
J1
P1
P2
J1
TC Input FTM
8.21.4—FTM Reference
See Chapter 12 for TC Input FTM information. See Appendix A for proper
Module, FTM, and cable part numbers.
238 Woodward
Manual 26167V1 MicroNet TMR
J2 J1 TB1
19 19 1 NC
.01uF
18 18 2
+
37 37 20 +
Anti-
TC_01 aliasing
- Filter 36 36 21 -
17 17 3 NC
.01uF
16 16 4 SHLD
+
Anti- 35 35 22 +Input Ch. 2
TC_02 aliasing
- Filter 34 34 23 -Input
15 15 5 NC
.01uF
14 14 6 SHLD
+
Anti- 33 33 24 +Input Ch. 3
TC_03 aliasing
- Filter 32 32 25 -Input
13 13 7 NC
.01uF
12 12 8 SHLD
+
Anti- 31 31 26 +Input Ch. 4
TC_04 aliasing
- Filter 30 30 27 -Input
11 11 9 NC
.01uF
10 10 10 SHLD
+
Anti- 29 29 28 +Input Ch. 5
TC_05 aliasing
- Filter 28 28 29 -Input
9 9 11 NC
.01uF
8 8 12 SHLD
+
Anti- 27 27 30 +Input Ch. 6
TC_06 aliasing
- Filter 26 26 31 -Input
7 7 13 NC
.01uF
6 6 14 SHLD
+
Anti- 25 25 32 +Input Ch. 7
TC_07 aliasing
- Filter 24 24 33 -Input
5 5 15 NC
.01uF
4 4 16 SHLD
+
Anti- 23 23 34 +Input Ch. 8
TC_08 aliasing
- Filter 22 22 35 -Input
+15V 3 3 17 NC
Cold
CJ_09 2 2 AD590 18 NC
Junction
GND 1 1 19 NC
21 21 36 NC
20 20 37
Ground to DIN Rail
J1 Outer Shell 38
Woodward 239
MicroNet TMR Manual 26167V1
8.21.5—Troubleshooting
The board performs on-line temperature compensation and hardware
diagnostics. To do this, once per minute, it reads two known voltages for each
channel. These values are checked against certain limits to determine if a
hardware fault has occurred. These values are also used to determine software
scaling constants used for temperature compensation. The MUX receives the
thermocouple input and, under the control of the microcontroller, passes the
value through the gain amplifier to the isolation amplifier. The output of the
isolation amplifier goes to one input of the channel-selecting MUX.
This MUX, under control of the microprocessor, selects the channel to be read.
The analog output of this MUX is converted to a digital value by the A/D
converter, and passed to the microcontroller. The microcontroller uses a lookup
table to linearize the thermocouple readings and stores the result in the Dual-Port
RAM. The CPU can then access the values stored in Dual-Port RAM through the
VME interface and bus. Upon detection of an open wire on the input, the channel
will indicate a minimum scale reading. See Figure 8-62 for module block
diagram.
During initialization, which occurs after every reset, the CPU turns the FAULT
LEDs on. The CPU then tests each I/O module using diagnostic routines built
into software. If the diagnostic test is not passed, the LED remains on. If the test
is successful, the LED goes off.
During initialization of the module, the module's micro-controller turns the LED off
after power-on self tests have passed and the CPU has initialized the module.
240 Woodward
Manual 26167V1 MicroNet TMR
The CPU also tells this module in which rate group each channel is to run, as
well as special information. At run time, the CPU then periodically broadcasts a
"key" to all I/O cards, telling them which rate groups are to be updated at that
time. Through this initialization/key broadcast system, each I/O module handles
its own rate-group scheduling with minimal CPU intervention.
This module also has on-card on-line fault detection and automatic
calibration/compensation. Each input channel has its own precision voltage
reference. Once per minute, while not reading inputs, the on-board
microcontroller reads this reference. The microcontroller then uses this data read
from the voltage reference for both fault detection and automatic temperature
compensation/calibration.
Limits have been set for the expected readings when the on-board
microcontroller reads each voltage reference. If the reading obtained is outside
these limits, the system determines that the input channel, A/D converter, or the
channel's precision-voltage reference is not functioning properly. If this happens,
the micro-controller flags that channel as having a fault condition. The CPU will
then take whatever action the application engineer has provided for in the
application program.
The readings from the precision-voltage reference are also used for on-line
temperature compensation and automatic calibration for the module. The
readings of the precision-voltage reference, obtained from the A/D converter, are
used by the microcontroller to determine software scaling- and offset-constants
for each channel. These scaling-and offset-constants are respectively multiplied
by and added to each channel reading to provide corrected channel readings.
The module therefore includes no potentiometers and needs no calibration.
Each I/O module has a fuse on it; this fuse is visible and can be changed through
a cutout in the plastic cover of the module. If this fuse is blown, replace it with a
fuse of the same type and size.
Troubleshooting Guide
If an Thermocouple input is not functioning properly, verify the following:
1. Check that the cable is shielded and the shield is properly grounded per
the Shields and Grounding section in Chapter 14.
2. Measure the input voltage on the terminal block. It should be in the range
of appropriate millivolt signal.
3. Verify that there are no or minimal AC components to the Analog Input
signal. AC components can be caused by improper shielding.
Thermocouple inputs are extremely sensitive to signal fluctuations.
4. If the input is reading minimum range, look for a loose connection at the
terminal blocks and disconnected or misconnected cables.
5. If all the temperature measurements are offset by a fixed amount , check
for proper cold junction location. Replace the FTM.
6. Check the software configuration to ensure that the input is configured
properly. Ensure that the proper thermocouple type is selected.
7. After verifying all of the above, replace the 8 Ch TC module.
Woodward 241
MicroNet TMR Manual 26167V1
8.22.2—Specification
Number Channels: 8 double ended, fully isolated, thermocouple
input channels
1 cold junction channel.
242 Woodward
Manual 26167V1 MicroNet TMR
Thermocouple Types and ranges:
8.22.3—Installation
See 8 Ch TC (Fail Low) Module.
8.22.4—FTM Reference
See Chapter 12 for complete field wiring information for the 8 Ch TC (Fail High)
FTM. See Appendix A for part number Cross Reference for modules, FTMs, and
cables.
8.22.5—Troubleshooting
See 8 Ch TC (Fail Low) Module.
Woodward 243
MicroNet TMR Manual 26167V1
T=(R*25.95)-(234.5)
244 Woodward
Manual 26167V1 MicroNet TMR
8.24.2—Specification
Number of Channels: 8 semi-isolated, RTD channels
Input Type: 3 wire
(Must conform to 10 ohm copper RTD temperature/resistance relationship (Alpha
= .00427))
8.24.3—Installation
The modules slide into card guides in the control's chassis and plug into the
motherboard. The modules are held in place by two screws, one at the top and
one at the bottom of the front panel. Also at the top and bottom of the module are
two handles which, when toggled (pushed outward), move the modules out just
far enough for the boards to disengage the motherboard connectors.
In a simplex system, each 8 Ch RDT Input Module is connected through one low
Density analog cable to one Analog Input FTM. All of the I/O are accessible on
the FTM.
J1
P1
P2
J1
Woodward 245
MicroNet TMR Manual 26167V1
8.24.4—FTM Reference
See Chapter 12 for complete field wiring information for the 8 Ch RTD Input (10
ohm) FTM. See Appendix A for part number Cross Reference for modules,
FTMs, and cables.
8.24.5—Troubleshooting
The board performs on-line temperature compensation and hardware
diagnostics. To do this, once per minute, it reads two known voltages for each
channel. These values are checked against certain limits to determine if a
hardware fault has occurred. These values are also used to determine software
scaling constants used for temperature compensation. The MUX receives the
RTD input and, under the control of the microcontroller, passes the value through
the gain amplifier to the isolation Amplifier. The gain amplifier introduces the
proper gain for the type of RTD used. The output of the isolation amplifier goes to
one input of the channel-selecting MUX.
246 Woodward
Manual 26167V1 MicroNet TMR
J2 J1 TB1
19 19 1
.01uF
18 18 2
+ +
Current
Source
37 37 20
RTD_01 RTD
- 36 36 21 -
17 17 3 Sense
.01uF
16 16 4 Shld
Ch. 2
+ Current
Source
35 35 22 +Input
RTD_02
- 34 34 23 -Input
15 15 5 Sense
.01uF
14 14 6 Shld
Ch. 3
+ Current
Source
33 33 24 +Input
RTD_03
- 32 32 25 -Input
13 13 7 Sense
.01uF
12 12 8 Shld
Ch. 4
+ Current
Source
31 31 26 +Input
RTD_04
- 30 30 27 -Input
11 11 9 Sense
.01uF
10 10 10 Shld
Ch. 5
+ Current
Source
29 29 28 +Input
RTD_05
- 28 28 29 -Input
9 9 11 Sense
.01uF
8 8 12 Shld
Ch. 6
+ Current
Source
27 27 30 +Input
RTD_06
- 26 26 31 -Input
7 7 13 Sense
.01uF
6 6 14 Shld
Ch. 7
+ Current
Source
25 25 32 +Input
RTD_07 - 24 24 33 -Input
5 5 15 Sense
.01uF
4 4 16 Shld
Ch. 8
+ Current
Source
23 23 34 +Input
RTD_08
- 22 22 35 -Input
3 3 17 NC
2 2 18 NC
1 1 19 NC
21 21 36 NC
20 20 37
Ground to DIN Rail
J1 Outer Shell 38
Woodward 247
MicroNet TMR Manual 26167V1
This MUX, under control of the microprocessor, selects the channel to be read.
The analog output of this MUX is converted to a digital value by the A/D
converter, and passed to the microcontroller. The microcontroller uses a lookup
table to linearize the RTD reading and stores the result in the Dual-Port RAM.
The CPU can then access the values stored in Dual-Port RAM through the VME
interface and bus. See Figure 8-67 for module block diagram.
During initialization, which occurs after every reset, the CPU turns the FAULT
LEDs on. The CPU then tests each I/O module using diagnostic routines built
into software. If the diagnostic test is not passed, the LED remains on. If the test
is successful, the LED goes off.
During initialization of the module, the module's micro-controller turns the LED off
after power-on self tests have passed and the CPU has initialized the module.
The CPU also tells this module in which rate group each channel is to run, as
well as special information. At run time, the CPU then periodically broadcasts a
"key" to all I/O cards, telling them which rate groups are to be updated at that
time. Through this initialization/key broadcast system, each I/O module handles
its own rate-group scheduling with minimal CPU intervention.
This module also has on-card on-line fault detection and automatic
calibration/compensation. Each input channel has its own precision voltage
reference. Once per minute, while not reading inputs, the on-board
microcontroller reads this reference. The microcontroller then uses this data read
from the voltage reference for both fault detection and automatic temperature
compensation/calibration.
248 Woodward
Manual 26167V1 MicroNet TMR
Limits have been set for the expected readings when the on-board
microcontroller reads each voltage reference. If the reading obtained is outside
these limits, the system determines that the input channel, A/D converter, or the
channel's precision-voltage reference is not functioning properly. If this happens,
the micro-controller flags that channel as having a fault condition. The CPU will
then take whatever action the application engineer has provided for in the
application program.
The readings from the precision-voltage reference are also used for on-line
temperature compensation and automatic calibration for the module. The
readings of the precision-voltage reference, obtained from the A/D converter, are
used by the microcontroller to determine software scaling- and offset-constants
for each channel. These scaling-and offset-constants are respectively multiplied
by and added to each channel reading to provide corrected channel readings.
The module therefore includes no potentiometers and needs no calibration.
Each I/O module has a fuse on it; this fuse is visible and can be changed through
a cutout in the plastic cover of the module. If this fuse is blown, replace it with a
fuse of the same type and size.
Troubleshooting Guide
If an RTD input is not functioning properly, verify the following:
1. Check that the cable is shielded and the shield is properly grounded per
the Shields and Grounding section in Chapter 14.
2. Measure the input voltage on the terminal block (Sense to – input). It
should be in the range generated by a 4 mA current source across the
RTD.
3. Verify that there are no or minimal AC components to the Analog Input
signal. AC components can be caused by improper shielding.
4. Check for proper connection of the sense line.
5. Check the software configuration to ensure that the input is configured
properly. Ensure that the proper RTD is selected.
6. If replacing the module does not fix the problem, replace the FTM. See
the instructions in Chapter 15 for replacing the FTM. The FTM contains
only traces and a few discrete components, so failure is extremely
unlikely.
Woodward 249
MicroNet TMR Manual 26167V1
8.25.2—Specification
Number of Channels: 8 semi-isolated, RTD channels
Input Type: 3 wire
(Must conform to (Deutsche Institut for Normung) DIN standard for 100 ohm
European curve (Alpha = .00385) or American curve 100 ohm curve (Alpha =
.00392))
250 Woodward
Manual 26167V1 MicroNet TMR
Temperature ranges
Standard module: –40 to +450 °C (100 ohm platinum, American,
European)
High Temp Module: –40 to +645 °C (100 ohm platinum, European)
–40 to +450 °C (100 ohm platinum, American)
Excitation: 2 mA
Module interface: VMEbus
Output: Linearized temperatures in °C
Resolution: 14 bit converter
Accuracy: 0.5% of full scale over the entire temperature
range
Temperature Coefficient: 12 ppm/degree C
Isolation: 1500 Vac continuous (input channels to
control common, not channel to channel)
Input Impedance: 2.2 MΩ
CMRR: -90 db
Status Indication: RED LED - channel fault or board fault
8.25.3—Installation
See 8 Ch RTD Input (10 ohm) Module.
8.25.4—FTM Reference
See Chapter 12 for complete field wiring information for the 8 Ch RTD Input (100
ohm) FTM. See Appendix A for part number Cross Reference for modules,
FTMs, and cables.
8.25.5—Troubleshooting
See 8 Ch RTD Input (10 ohm) Module.
Woodward 251
MicroNet TMR Manual 26167V1
8.26.1—Module Description
The eight channels of this module are semi-isolated. The channels are isolated
from the control common but not from each other. Each channel receives a
signal from an RTD. This signal must be from a 200 Platinum RTD (European
or American curve).
8.26.2—Specification
Number of Channels: 8 semi-isolated, RTD channels
Input Type: 3 wire
(Must conform to (Deutsche Institut for Normung) DIN standard for 200 ohm
European curve (Alpha = .00385) or American curve 200 ohm curve (Alpha =
.00392))
252 Woodward
Manual 26167V1 MicroNet TMR
Temperature ranges –40 to +450 °C (200 ohm platinum, American,
European)
Excitation: 1 mA
Module interface: VMEbus
Output: Linearized temperatures in °C
Resolution: 14 bit converter
Accuracy: 0.5% of full scale over the entire temperature
range
Temperature Coefficient: 12 ppm/degree C
Isolation: 1500 Vac continuous(input channels to control
common, not channel to channel)
Input Impedance: 2.2 MΩ
CMRR: -90 db
Status Indication: RED LED - channel fault or board fault
8.26.3—Installation
See 8 Ch RTD Input (10 ohm) Module.
8.26.4—FTM Reference
See Chapter 12 for complete field wiring information for the 8 Ch RTD Input (200
ohm) FTM. See Appendix A for part number Cross Reference for modules,
FTMs, and cables.
8.26.5—Troubleshooting
See 8 Ch RTD Input (10 ohm) Module.
Woodward 253
MicroNet TMR Manual 26167V1
8.27.2—Specification
Number of Channels: 8 semi-isolated, RTD channels
Input Type: 3 wire
(Must conform to (Deutsche Institut for Normung) DIN standard for 500 ohm
European curve (Alpha = .00385) or American curve 500 ohm curve (Alpha =
.00392))
254 Woodward
Manual 26167V1 MicroNet TMR
Temperature ranges –40 to +450 °C (500 ohm platinum, American,
European)
Excitation: 400 μA
Module interface: VMEbus
Output: Linearized temperatures in °C
Resolution: 14 bit converter
Accuracy: 0.5% of full scale over the `entire temperature
range
Temperature Coefficient: 12 ppm/degree C
Isolation: 1500 Vac continuous(input channels to control
common, not channel to channel)
Input Impedance: 2.2 MΩ
CMRR: -90 db
Status Indication: RED LED - channel fault or board fault
8.27.3—Installation
See 8 Ch RTD Input (10 ohm) Module.
8.27.4—FTM Reference
See Chapter 12 for complete field wiring information for the 8 Ch RTD Input (500
ohm) FTM. See Appendix A for part number Cross Reference for modules,
FTMs, and cables.
8.27.5—Troubleshooting
See 8 Ch RTD Input (10 ohm) Module.
Woodward 255
MicroNet TMR Manual 26167V1
8.28.1—Module Description
This module has four speed inputs that can be configured as either transformer
isolated MPU inputs or non-isolated proximity inputs. The configuration of MPU
and proximity inputs is dependent on the part number.
256 Woodward
Manual 26167V1 MicroNet TMR
8.28.2—Specification
Number Channels: 4
Input Type: MPU/Proximity Detector (factory selected by
part number)
Input Frequency Range: MPU: 50 Hz to 25 KHz
Prox: 0.04 Hz to 2 KHz
Input Amplitude: MPU: 1 Vrms min, 25 Vrms max, Freq > 20 Hz
Prox: 10 mA
Input Impedance: MPU: 2000 Ω
Prox: 2000 Ω
Isolation Voltage: MPU: 500 Vrms
Prox: None
Resolution: 16 bits
0.0015% of range per LSB
Speed Accuracy (max): 0.01% over temperature range
Temperature drift: 1 ppm/C
Derivative Accuracy (max): 0.10% of range (p-p)
Speed Filter: 5-10,000 ms (2 real poles)
Derivative Filter: 5-10,000 ms (1 pole + speed filter)
Acceleration Limit: 1-10,000 percent/second
Operating Temperature : –15 to +55 °C
8.28.3—Installation
The modules slide into card guides in the control's chassis and plug into the
motherboard. The modules are held in place by two screws, one at the top and
one at the bottom of the front panel. Also at the top and bottom of the module are
two handles which, when toggled (pushed outward), move the modules out just
far enough for the boards to disengage the motherboard connectors.
J1
P1
P2
J1
Woodward 257
MicroNet TMR Manual 26167V1
Any of the module’s four speed channels accept passive magnetic pickup units
(MPUs) or proximity probes. The number of MPU and proximity inputs per
module is determined by the position of jumpers internal to the module. These
jumpers are factor set. The part number of the module will determine the ratio of
MPU to Proximity inputs. Each speed input channel can only accept one MPU or
one proximity probe. See Appendix A for desired part number of modules.
A proximity probe may be used to sense very low speeds. With a proximity
probe, speed can be sensed down to 0.5 Hz. When interfacing to open collector
type proximity probes, a pull-up resistor is required between the supplied
proximity probe voltage and the proximity probe input to the FTM. See Figure
7-62 for MPU and proximity probe wiring examples.
8.28.4—FTM Reference
See Chapter 12 for complete field wiring information for the 4 Ch MPU/Proximity
FTM. See Appendix A for part number Cross Reference for modules, FTMs, and
cables.
8.28.5—Troubleshooting
Speed ranges are selected from the GAP and the signal is pre-scaled
accordingly. The pre-scaled signal then goes to a counter where the period of the
signal is measured. The Digital Signal Processor samples the counter's values
every 100 microseconds and performs a divide to generate a digital speed signal.
Once every rate time (5-200 ms typically), the latest speed and derivative
information is moved to the Dual-Port RAM for access by the CPU module.
During initialization, which occurs after every reset, the CPU turns the FAULT
LEDs on. The CPU then tests each I/O module using diagnostic routines built
into software. If the diagnostic test is not passed, the LED remains on. If the test
is successful, the LED goes off.
During initialization of the module, the module's micro-controller turns the LED off
after power-on self tests have passed and the CPU has initialized the module.
258 Woodward
Manual 26167V1 MicroNet TMR
MicroNet Module CABLE FTM
+24VDC
+5VDC
J2 J1 TB1
19 19 1 NC
.01uF
MPU_01 18 18 2
JPR 3
+
37 37 20
JPR 1
MPU #1
36 36 21 -
17 17 3 +24V
.01uF
16 16 4 Shld
MPU/PROX_02 Ch. 2
35 35 22 +Input
34 34 23 -Input
15 15 5 +24V
.01uF
14 14 6 Shld
MPU/PROX_03 Ch. 3
+24VDC 33 33 24 +Input
+5VDC
32 32 25 -Input
13 13 7 +24VDC
.01uF
JPR 23
PROX_04 12 12 8
+
31 31 26
PROX #4
30 30 27 -
JPR 21
11 11 9 NC
.01uF
10 10 10 NC
29 29 28 NC
28 28 29 NC
9 9 11 NC
.01uF
8 8 12 NC
27 27 30 NC
26 26 31 NC
7 7 13 NC
.01uF
6 6 14 NC
25 25 32 NC
24 24 33 NC
5 5 15 NC
.01uF
4 4 16 NC
23 23 34 NC
22 22 35 NC
3 3 17 NC
2 2 18 NC
1 1 19 NC
21 21 36 NC
20 20 37
Ground to DIN Rail
J1 Outer Shell 38
Woodward 259
MicroNet TMR Manual 26167V1
The CPU also tells this module in which rate group each channel is to run, as
well as special information. At run time, the CPU then periodically broadcasts a
"key" to all I/O cards, telling them which rate groups are to be updated at that
time. Through this initialization/key broadcast system, each I/O module handles
its own rate-group scheduling with minimal CPU intervention.
Each I/O module has a fuse on it; this fuse is visible and can be changed through
a cutout in the plastic cover of the module. If this fuse is blown, replace it with a
fuse of the same type and size.
Troubleshooting Guide
MPUs. If a magnetic pickup input is not functioning properly, verify the following:
1. Check that the cable is shielded and the shield is properly grounded per
the Shields and Grounding section in Chapter 14.
2. Measure the input voltage on the terminal block. It should be in the range
of 1-25 VRMS.
3. Verify that the signal waveform is clean and void of double zero
crossings.
4. Verify that no ground connection exists and that the resulting 60 Hz
signal is absent.
5. Measure the frequency. It should be in the range of 50 Hz - 25 kHz.
6. Check the wiring. Look for a loose connection at the terminal blocks and
disconnected or misconnected cables.
7. Check the software configuration to ensure that the input is configured
properly.
8. If the readings are incorrect on several channels of the module, replace
the Speed module.
9. If replacing the module does not fix the problem, replace the FTM. See
instructions for replacing the FTM in Chapter 15. The FTM does not
contain any active components on the MPU inputs, so replacing it should
be the last option.
260 Woodward
Manual 26167V1 MicroNet TMR
Proximity Probes
If a proximity probe input is not functioning properly, verify the following:
1. Check that the cable is shielded and the shield is properly grounded per
the Shields and Grounding section in Chapter 14.
2. Measure the input voltage on the terminal block. It should be in the range
of 3.5 - 24 Vpeak.
3. Verify that the signal waveform is clean and void of double zero
crossings.
4. Verify that no ground connection exists and that the resulting 60 Hz
signal is absent.
5. Measure the frequency. It should be in the range of 0.5 Hz to 25 kHz.
6. Check the wiring. Look for a loose connection at the terminal blocks,
disconnected or misconnected cables.
7. Check the software configuration to ensure that the input is configured
properly.
8. If the readings are incorrect on several channels of the Speed module,
replace the Speed module.
9. If replacing the module does not fix the problem, replace the FTM. See
instructions for replacing the FTM in Chapter 15.
Woodward 261
We appreciate your comments about the content of our publications.
Send comments to: [email protected]
2010/5/Colorado