RSAD00700 - ACDB-4nos

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

TUBE LIGHT

+ DLS

PR OJ EC T N AM E : YA D AD R I T PS
RA T IN G : 10k VA ,1PH 230 V THERMOSTAT
SYS TE M : AC D B GF 0 1-16

PV C C H AN N EL
P N

MCB01
ON L1 L2 L3

PV C C H AN N EL
L01
L4 L5 L6

MCB1
MCB2

MCB3
MCB4
MCB5
MCB6
ON OFF TRIP
PV C C H AN N EL
L02 L03 L04 L7 L8 L9

MCB10
MCB11
MCB12
MCB7

MCB8
MCB9
VAF L10 L11 L12

PV C C H AN N EL
PV C C H AN N EL

MCB13

MCB14
MCB15
MCB16
L13 L14 L15

PV C C H AN N EL
L16

PV C C H AN N EL

PV C C H AN N EL
CT

PV C C H AN N EL

R6

PV C C H AN N EL

TE R M IN AL S

PV C C H AN N EL
32A TP
MCCB
INCOMER SPACE
HEA TER

PV C C H AN N EL

FRONT VIEW SIDE VIEW TENTATIVE INTERNAL


LAYOUT

BOTTOM VIEW
MCB 01

INCOMMING

2A SP
MCB

32A TP I>
MCCB I>>

VIF

RS 485

6A SP
MCB

Cu. BUSBAR COMMON BUS 240V~

10A DP 6A DP MCB
MCB

GLASS GLASS
FUSE FUSE

OUTGOING OUTGOING
6 NOS 10 NOS
BILL OF MATERIAL
S.NO DESCRIPTION MAKE QTY
A INCOMER
1 32A TP MCCB 30KA L&T 1
2 SPEADER FOR MCCB L&T 1
3 EXTENDED ROTARY HANDEL L&T 1
4 AUX CONTACT FOR TRIP INDICATION L&T 1
5 VAF+PF METER WITH RS485 L&T 1
6 32/5A 5VA CT'S AMOL/EQ 1
7 RED INDICATION LAMP 230VAC - ON & INCOMER 2
8 GREEN INDICATION LAMP 230VAC - OFF TEKNIC 1
9 AMBER INDICATION LAMP 230VAC - TRIP 1
10 2A SP MCB 10KA C CURVE L&T 1
B OUTGOING
1 10A DP MCB 10KA C CURVE L&T 6
2 6A DP MCB 10KA C CURVE L&T 10
C OTHER
1 RED INDICATION LAMP 230VAC - ON TEKNIC 16
2 2A GLASS FUSE WITH FUSE CONNECTOR CONNECTWELL 16
3 POWER TERMINALS SCREW TYPE 10 SQ. MM. CONNECTWELL 32
4 SPACE HEATER WITH THERMOSTAT STD 1
5 TUBE LIGHT WITH DLS STD 1
6 6A SP MCB 10KA C CURVE L&T 1