PROFiTEST0100S-II

3-348-888-03
Test Instrument for DIN VDE 0100 2/3.99

Testing of Residual-Current Protective Devices (RCCBs)


• Measurement of contact voltage without tripping the RCCB
Contact voltage with reference to nominal residual current
is measured with 1/3 of nominal residual current.
• Trip test with nominal residual current, measurement of time to trip K EMA
EUR

Special Testing for Systems and RCCBs


• Testing of systems and RCCBs
with rising residual current and display of tripping current,
as well as contact voltage at the moment tripping occurs
• Testing of RCCBs (10 and 30 mA) with 5 • I∆N
• Testing of RCCBs
which are suitable for pulsating DC fault current,
testing is conducted with positive or negative half-waves
• Testing of RCCBs with adjustable residual current
for the determination of contact voltage and tripping current

Testing of Special RCCBs


• Selective S , SRCDs, PRCDs (Schukomat, Sidos etc.), type G

Testing of RCD Protection in IT Systems

Large Voltage and Frequency Range Low-Resistance Measurements


An extended-range measuring system allows for use of the test Bonding conductor resistance and protective conductor resis-
instrument for all AC and three-phase systems with voltages tance can be measured with a measuring current of
ranging from 65 to 500 V, and frequencies from 15.4 to 420 Hz. ≥ 200 mA DC, automatic measuring voltage polarity reversal and
selectable conduction direction. Violation of an (adjustable) limit
Loop and System Impedance Measurement value is signaled with an LED.
Measurement of loop and system impedance can be performed
within a range of 65 to 550 V. Conversion to short-circuit current Standing-Surface Insulation Measurement
is based upon respective line voltage, as long as the measured Measurement of standing-surface insulation is performed with
line voltage is within the prescribed range. Short-circuit current is actual line frequency and line voltage.
calculated from actual line voltage and measured impedance for
line voltages outside of this range. Universal Connector System
The PROFiTESTDC-II accessory device allows for the suppres- The interchangeable plug inserts and the plug-on 2-pole adapter
sion of RCCB tripping during measurement of loop impedance. (can be expanded to a 3-pole adapter for phase sequence mea-
surements) allow for use of the test instrument all over the world.
Insulation Resistance Measurement
with Nominal Voltage and Variable or Rising Test Voltage
Insulation resistance is usually measured with the nominal volt- Special Features
ages 500 V, 250 V or 100 V. For measurements at sensitive com-
ponents, as well as within systems with voltage limiting devices, • Display of allowable fuse types for electrical systems
22 different test voltages ranging from 20 to 500 V can be • Start-up testing for energy consumption meters
selected, which deviate from, and are generally lower than nomi- • Calculation of cable lengths for common copper
nal voltage. Measurements can be performed with continuously
conductor cross-sections
rising voltage for the detection of weak points in insulation, as well
as for the determination of response voltages for voltage limiting • Measurement of biasing, leakage and circulating current
devices. up to 1 A, as well as working current to 150 A with
Voltage at the device under test, any detected response or break- the Clip 0100S accessory clip-on current sensor
down voltage, as well as insulation resistance appear at the
• Phase sequence measurement
instrument’s display, and an LED indicates violation of an (adjust-
able) limit value. (phase sequence, highest line-to-line voltage)

GOSSEN-METRAWATT GMBH
PROFiTEST0100S-II
Test Instrument for DIN VDE 0100
Display Standard Equipment
The LCD field consists of a backlit dot matrix at which menus,
possible settings, measurement results, tables, tips and error 1 PROFiTEST0100S-II test instrument
messages, as well as wiring diagrams are displayed. 1 insert for earthing contact plug (PRO-Schuko)
1 two-pole measuring adapter
Selectable Language 1 cable for expansion to three-pole adapter
An appropriate language can be selected for the country in which 2 alligator clips
the test instrument is used. 1 carrying strap
Several instrument versions are available which include various
language combinations. 1 set batteries
1 operating instructions
Operation
The instrument is very easy to operate with its rotary function
selector switch and 5 keys. Two of the keys located at the instru-
ment have the same functions as the keys at the test plug, which Applicable Regulations and Standards
allows for convenient measuring at difficult to access locations.
Wiring diagrams and online help can be displayed at the LCD for IEC 61010-1/EN 61010-1/ Safety requirements for electrical equipment
all basic functions and sub-functions. VDE 0411-1 for measurement, control and laboratory use
IEC 61557/ EN 61557/ Part 1: General requirements
Phase Tester VDE 0413 Part 2: Insulation resistance measuring instruments
Protective conductor potential is tested by contacting the contact Part 3: Loop resistance measuring instruments
surface with the contact finger. If a potential difference of greater Part 4: Instruments for the measurement or resistance
than 100 V is detected between the contact surface and the pro- at earth conductors, protective conductors
and bonding conductors
tective contact at the earthing contact plug, the PE signal lamp Part 5: Earth resistance measuring instruments
lights up. Part 6: Instruments for testing for correct functioning
of residual-current protective devices (RCDs)
Signal Lamps and the effectiveness of protective measures in
Faults within the system are recognized automatically by the TT and TN systems
Part 7: Phase sequence indicators
instrument, and are indicated by means of four lamps.
DIN 43751 Part 1, 2 Digital measuring instruments
Battery or Rechargeable Battery Test and Self-Test VDE 0106 Part 1 Protection against electrical shock, classifications
for electrical and electronic equipment
The battery test is performed under load. The results are dis-
played both numerically and with a symbol. Test patterns can be EN 60529 Test instruments and test procedures
VDE 0470 Part 1 – Protection provided by enclosures (IP code)
queried one after the other during the self-test, and LEDs and
relays can be tested as well. The instrument is shut down auto- EN 50081-1 Electromagnetic Compatibility (EMC)
matically if the batteries are depleted. The instrument includes an Generic standard for interference emission
integrated charge control circuit for reliable charging of NiMH or EN 50082-1 Electromagnetic Compatibility (EMC)
NiCd batteries. Generic standard for interference immunity

Data Interface
Data are transmitted to the PROFiTESTPSI-E/TE accessory
module (optional) via the integrated IRDA interface, which pro-
vides for three advantages:
Nominal Ranges of Use
• Immediate print-out of all measurement data to Voltage UN 120 V (108 ... 132 V)
recording chart paper 230 V (196 ... 253 V)
• Storage of all data to memory for later processing 400 V (340 ... 440 V)
Frequency fN 16 2/3 Hz (15.4 ... 18 Hz)
• Transmission of stored data to a PC for archiving, or for the 50 Hz (49.5 ... 50.5 Hz)
preparation of reports 60 Hz (59.4 ... 60.6 Hz)
200 Hz (190 ... 210 Hz)
Software Updates 400 Hz (380 ... 420 Hz)
The test instrument will always be up to date, because its soft- Overall Voltage Range 65 ... 550 V
ware can be updated via the IRDA interface. Software updates Overall Frequency
can be performed within the framework of instrument Range 15.4 ... 420 Hz
re-calibration by our service department, or by the user. Waveshape sine
Temperature Range 0 °C ... + 40 °C
Battery Voltage 6 ... 10 V
Line Impedance Angle corresponds to cosϕ = 1 ... 0.95
Probe Resistance < 50 kΩ

2 GOSSEN-METRAWATT GMBH
PROFiTEST0100S-II
Test Instrument for DIN VDE 0100

Characteristic Values
Input Connections
Func- Measured Measuring Range Reso- Nominal Range
Impedance / Nominal Values Operating Error Intrinsic Error Plug 2-Pole 3-Pole
tion Quantity (Display Range IK) lution of Use Probe Clip
Test Current Insert 2) Adapter Adapter
0 ... 99.9 V 0.1 V ±(1% rdg.+5D)
108 ... 253 V
100 ... 500 V 1V ±(1% rdg.+1D)
UL-PE terminal L-N-PE ±(2% rdg.+1D)
0 ... 99.9 V 0.1 V ±(1% rdg.+5D)
500 kΩ 108 ... 500 V
100 ... 500 V 1V ±(1% rdg.+1D)

15.0 ... 99.9 Hz 0.1 Hz
f terminal L-PE 15.4 ... 420 Hz ±(0.2% rdg.+1D) ±(0.1% rdg.+1D) ●
100 ... 1000 Hz 1 Hz 500 kΩ
UL–PE 0 ... 99.9 V 0.1 V
U3~ 108 ... 500 V ±(3% rdg.+1D) ±(2% rdg.+1D) ●
100 ... 500(850)1) V 1V
0 ... 99.9 V 0.1 V probe-PE
USONDE 0 ... 253 V ±(3% rdg.+5D) ±(2% rdg.+4D) ●
100 ... 253 V 1V 1MΩ
IL 0 ... 1 A 0.1 mA 5 mA ... 1.0 A ±(5% rdg.+5D) ±(3% rdg.+3D) ●
0 ... 99.9 A 0.1 A
IAMP. 10 A ... 150 A ±(10% rdg.+5D) ±(5% rdg.+3D) ●
100 ... 199 A 1A
0 ... 99.9 V 0.1 V ±(1% rdg.+5D)
UL-N 108 ... 253 V ±(2% rdg.+1D)
100 ... 300 V 1V ±(1% rdg.+1D)
UL–N 330 kΩ ●
15.0 ... 99.9 Hz 0.1 Hz ±(0.1%
f 15.4 ... 420 Hz ±(0.2% rdg.+1D)
100 ... 1000 Hz 1 Hz rdg.+1D)
+1% rdg.–1D ...
UI∆N 0 ... 70.0 V 0.1 V 0.3 · I∆N 5 ... 70 V +10% rdg.+1D
+9% rdg.+1D
RE / I∆N = 10 mA 10 Ω ... 6.51 kΩ 10 Ω
3 Ω ... 999 Ω 3Ω
RE / I∆N = 30 mA
1 kΩ ... 2.17 kΩ 10 Ω UN = 120/230 V
RE / I∆N = 100 mA 1Ω ... 651 Ω 1Ω
calculated value
0.3 Ω ... 99.9 Ω 0.3 Ω fN = 50/60 Hz
RE / I∆N = 300 mA
100 Ω ... 217 Ω 1Ω
UL = 25/50 V
0.2 Ω ... 9.99 Ω 0.2 Ω
RE / I∆N = 500 mA
100 Ω ... 130 Ω 1Ω

I∆N I∆N = 10/30/ ● ● as
I∆ / I∆N = 10 mA 3.0 ... 13.0 mA 3.0 ... 13.0 mA 3.0 ... 13.0 mA 100/300/500
0.1 mA desired
I∆ / I∆N = 30 mA 9.0 ... 39.0 mA 9.0 ... 39.0 mA 9.0 ... 39.0 mA mA
±(3.5%
I∆ / I∆N = 100 mA 30 ... 130 mA 1 mA 30 ... 130 mA 30 ... 130 mA ±(5% rdg.+1D)
rdg.+2D)
I∆ / I∆N = 300 mA 90 ... 390 mA 1 mA 90 ... 390 mA 90 ... 390 mA UN3) = 400 V
I∆ / I∆N = 500 mA 150 ... 650 mA 1 mA 150 ... 650 mA 150 ... 650 mA
UI∆ / UL = 25 V 0 ... 25.0 V 0 ... 25.0 V +1% rdg.–1D ...
0.1 V same as I∆ +10% rdg.+1D
UI∆ / UL = 50 V 0 ... 50.0 V 0 ... 50.0 V +9% rdg.+1 D
tA / I∆N 0 ... 1000 ms 1 ms 1.05 · I∆N 0 ... 1000 ms
±4 ms ±3 ms
tA / 5 · I∆N 0 ... 40 ms 1 ms 5 · I∆N 0 ... 40 ms I∆N = 10/30 mA
0.15 ... 0.5 Ω ±(10% rdg.+8D) ±5 D
ZSchl (full-waves)
0.5 ... 1.0 Ω UN = 120/230 V ±(10% rdg.+5D) ±(4% rdg.+3D)
ZI
0.01 ... 9.99 Ω 10 mΩ 0.83 ... 4.0 A 1.0 ... 10 Ω ±(5% rdg.+3D) ±(3% rdg.+3D)
ZSchl
ZSchl 0.25 ... 1.0 Ω UN2)= 400 V/ ±(20% rdg.+5D) ±(6% rdg.+5D)
● ●
(+/– half-waves) 1.0 ... 10 Ω 500 V at ZSchl ±(10% rdg.+3D) ±(4% rdg.+3D) ZSchl
ZI
0 A ... 999 A 1A 120 (108 ... 132) V
IK 1.00 kA ... 9.99 kA 10 A — 230 (196 ... 253) V fN = 50/60 Hz — —
10.0 kA ... 50.0 kA4) 100 A 400 (340 ... 440) V
0 ... 10 Ω 10 mΩ 0.83 ... 3.4 A 0.15 Ω ... 0.5 Ω ±(10% rdg.+5D) ±5 D
0 ... 10 Ω 10 mΩ 0.83 ... 3.4 A 0.5 Ω ... 1.0 Ω ±(10% rdg.+5D) ±(4% rdg.+3D)
RE
0 ... 10 Ω 10 mΩ 0.83 ... 3.4 A 1.0 Ω ...10 Ω UN = 120/230 V ±(5% rdg.+3D) ±(3% rdg.+3D)
(RESchl without
0 ... 100 Ω 10 mΩ 400 mA 10 Ω ...100 Ω UN = 400 V ±(10% rdg.+3D) ±(3% rdg.+3D)
probe)
0 ... 1 kΩ 1Ω 40 mA 100 Ω ...1 kΩ fN = 50/60 Hz ±(10% rdg.+3D) ±(3% rdg.+3D)
RE 1 kΩ ... 10 kΩ 1Ω 4 mA 1 kΩ ...10 kΩ ±(10% rdg.+3D) ±(3% rdg.+3D) ● ● ●
UE 0 ... 253 V 1V — calculated value
10 kΩ ... 200 kΩ ±(10% rdg.+3D) ±(5% rdg.+3D)
ZST
0 ... 1 MΩ 1 kΩ 2.3 mA at 230 V 200 kΩ ... 1 MΩ U0 = UL-N ±(20% rdg.+3D) ±(10% rdg.+3D)
RST 10 kΩ ... 200 kΩ ±(30% rdg.+3D) ±(20% rdg.+3D)
0.01 ... 9.99 MΩ 10 kΩ UN = 100 V
10.0 ... 99.9 MΩ 100 kΩ IN = 1 mA
0.01 ... 9.99 MΩ 10 kΩ
UN = 250 V
10.0 ... 99.9 MΩ 100 kΩ
RISO, RE ISO IK = 1.5 mA 50 kΩ ... 100 MΩ IN = 1 mA ±(5% rdg.+1D) ±(3% rdg.+1D)
100 ... 200 MΩ 1 MΩ
RISO ● ●
0.01 ... 9.99 MΩ 10 kΩ
UN = 500 V
10.0 ... 99.9 MΩ 100 kΩ
IN = 1 mA
100 ... 300 MΩ 1 MΩ
±(1.5%
U 25 ... 600 V– 1V 500 kΩ 25 ... 600 V ±(3% rdg.+1D)
rdg.+1D)
0.01 Ω ... 9.99 Ω 10 mΩ
RLO RLO Im ≥ 200 mA 0.5 Ω ... 6 Ω U0 = 4.5 V ±(4% rdg.+3D) ±(2% rdg.+2D) ●
10.0 Ω ... 99.9 Ω 100 mΩ
1) Only for systems with overvoltage category II, fouling factor 2, max. 5 min 3) 500 mA RCCB, max. UN = 230 V
2) U > 253 V with 2-pole adapter only 4) 100 UN · 1/Ω

GOSSEN-METRAWATT GMBH 3
PROFiTEST0100S-II
Test Instrument for DIN VDE 0100

Reference Conditions Electrical Safety


Line Voltage 230 V ± 0.1% Protection Class II per IEC 61010-1/EN 61010-1/
Line Frequency 50 Hz ± 0.1% VDE 0411-1
Meas. Qty. Frequency 45 Hz ... 65 Hz Nominal Voltage 230/400 V (300/500 V)
Meas. Qty. Waveshape sine (deviation between RMS and Test Voltage 3.7 kV 50 Hz
rectified value ≤ 0.1%) Overvoltage Category III
Line Impedance Angle cos ϕ = 1 Contamination Factor 2
Probe Resistance ≤ 10 Ω Interference Emission EN 50081-1
Battery Voltage 8 V ± 0.5 V Interference Immunity EN 50082-1
Ambient Temperature + 23 °C ± 2 K Fuses
Relative Humidity 45% ... 55% Terminals L and N 1 ea. fuse link
Finger Contact potential difference test at earth potential M 3.15/500G 6.3 mm x 32 mm
(safety fuse: FF 3.15/500G)
Standing-Surface
Insulation purely ohmic

Power Supply Ambient Conditions


Batteries 6 ea. 1.5 V mignon cells (alkaline Operating Temperature –10 ... + 50° C
manganese per IEC-LR6 or ANSI-AA or Storage Temperature –20 ... + 60° C (without batteries)
JIS-AM3) or 6 rechargeable NiMH Relative Humidity max. 75%, no condensation
batteries Climatic Category 3z/-20/50/60/75%
Number of Measurements (with one set of batteries) Elevation max. 2000 m above sea level
– for RISO 1 measurement – 25 s pause
1500 measurements
– for RLO automatic polarity reversal
(1 measuring cycle) – 25 s pause:
1500 measurements Mechanical Design
Battery Test battery voltage displayed numerically
and as symbol Display multiple display with dot matrix
6.0 ... 10.0 V 64 x 128 pixels
Battery Saving Circuit Display illumination can be deactivated. Protection housing: IP 40
The instrument switches itself off 15 ... test probe: IP 40 per
90 seconds after last key operation. DIN VDE 0470 part 1/EN 60529
ON-time can be selected by the user. Dimensions 240 mm x 340 mm x 62 mm
Safety Shut-Down The instrument is switched off, or can- Weight approx. 2.5 kg with batteries
not be switched on, if the supply volt-
age drops to below a given level.
Charging Socket Rechargeable batteries can be directly
charged within the instrument by con-
necting the Z501D charger to the Data Interface
charging socket.
Type infrared interface (SIR/IrDa)
bidirectional, half-duplex
Format 9600 baud,
Overload Capacity 1 start bit, 1 stop bit, 8 data bits,
no parity, no handshake
Riso 600 V continuous
Range max. 30 cm
UL-PE, UL-N 600 V continuous recommended distance: < 10 cm
Fi, RE, RF 440 V continuous
Zschl, Zi 550 V (limits the number of measure-
ments and pause duration, a thermal
protector switches the instrument off if
overload should occur.)
RLO Electronic protection prevents the
instrument from being switched on if
interference voltage is present.
Fine-Wire Fuse
Protection 3.15 A 10 s,
> 5 A − fuse blows

4 GOSSEN-METRAWATT GMBH
PROFiTEST0100S-II
Test Instrument for DIN VDE 0100

Accessories for the PROFiTEST0100S-II PROFiTESTDC-II


Applications
PROFiTESTPSI-E and PSI-TE •Trip test for AC-DC sensitive
RCCBS
The PROFiTESTPSI-E module (Printer Storage Interface) reads
– for measuring tripping current
data out from the PROFiTEST0100S-II test instrument and is a
– for measuring time to trip
printer, a memory and an interface all in one. It is attached to the
– for the testing of undelayed
test instrument and secured by means of two snap hooks.
and delayed S RCCBs
Values measured with the PROFiTEST0100S-II are transmitted
and stored to the PSI module via infrared light. •Loop resistance measurement
with the PROFiTEST0100S-II by
Up to 4400 value from 200 circuits can be stored to the memory suppressing tripping of RCCBs which
at the PSI module. In order to be able to assign measurement val- are sensitive to pulsating current
ues to buildings (construction sites, floors etc.) and circuits in an
unambiguous fashion, identification numbers can be entered with
the keys at the PSI module.
The measurement values from all of the stored circuits can be dis-
played at the instrument in tabular form, and can be printed out
with a time and date stamp to a recording chart by pressing a key. Tripping Test Operating Mode for AC-DC Sensitive RCCBs
The measurement value table can, for example, be directly with Rising DC Residual Current and Measurement of Tripping Current
attached to an approval report. In selector switch position IF , a slowly rising direct current flows
The PSI module via N and PE. The measurement value for current is continuously
is equipped with displayed. When the RCCB is tripped, the last measured current
an RS232 inter- value appears. Measurement is performed for delayed RCCBs
face, via which (type S ) with a greatly reduced rate of rise.
stored data can
be transmitted at IF /mA Tripping
a later point in A steeper slope for the residual
time to a PC, 600 current curve as of 100 mA
allows for faster overall
fully indepen- testing.
dently of the test 500

instrument,
400
where they can be processed with PC.doc(-win) and PC.base-
m(+204) 300 A lesser slope for the residual current
software. curve between 0 and 100 mA results
For further information please request our data sheet: 200 in improved resolution.
PROFiTESTPSI-E/TE.
100 Start
Modules Comparison, PSI versus PSI-T
Feature PROFiTESTPSI-E PROFiTESTPSI-TE 0.4 0.8 1.0 1.6 2.0 2.4 2.8 3.2 3.6 4.0 4.4 4.8 t/s
Entry of buildings 3 place numeric 6 place alphanumeric
Entry of distribution cabinets — 3 place alphanumeric Tripping Test Operating Mode for AC-DC Sensitive RCCBs
Entry of RCD identification — 2 place alphanumeric with Constant DC Residual Current and Measurement of Tripping Current
Entry of circuits 3 place numeric 3 place alphanumeric In the selector switch position for the respective nominal residual
Number of measurement values 1 2 current, twice the nominal current flows via N and PE. Time
per circuit for insulation required until RCCB tripping occurs is measured and displayed.
resistance measurement
Entry of faults none 3 selectable possibilities Loop Impedance Measurement Operating Mode with the
Entry of number of existing none 3 place numeric PROFiTEST0100S-II by means of Suppressing RCCB Tripping
circuits The PROFiTESTDC-II allows for the measurement of loop
Report generating software PC.doc(-win) PC.base-m(+204) impedance in TN systems with RCCBs which are sensitive to pul-
and PC.base-m as of version 4.0 sating current (10/30/100/300/500 mA nominal residual current).
IF /mA The instrument gen-
erates a DC residual
current which satu-
DA-II rates the RCCB’s
Printer adapter for the connection of a printer with Centronics magnetic circuit. A
interface to the PROFiTESTPSI-E/TE for immediate printing of
t measuring current is
measured and stored values to a predefined report in A4 format. t1 t2 t3 superimposed by the
PROFiTEST0100S-
Measure
II which demon-
Operation strates half-waves
RCCB non-functional! only of like polarity.
Start The RCCB can no
longer detect the
measuring current and is not tripped during testing.

GOSSEN-METRAWATT GMBH 5
PROFiTEST0100S-II
Test Instrument for DIN VDE 0100
PROFiKALIBRATOR 1 3-Phase Current Adapters
The PROFiKALIBRATOR 1 is a calibration adapter for test instru- The A3-16, A3-32 and
ments in accordance with DIN VDE 0100. It is used in combina- A3-63 three-phase
tion with a test standard and a multimeter (e.g. METRAHit 28S) current adapters are
for the testing of protective device test instruments such as the used for the convenient
PROFiTEST0100S/S-II, M5010, M5011 and M5012. connection of test
The various functional values which must be determined in instruments to 5-pole
accordance with DIN VDE 0100, part 610, are first compared CEE outlets. The three
with the test standard and then with the measurement values different versions have
from the device under test. The measurement values from the test different sized plugs
standard serve as reference values. which correspond to
5-pole CEE outlets with
current ratings of 16 A,
32 A and 63 A. Phase
sequence is indicated
with lamps.
Testing for the effectiveness of protective devices is accomplished
via five 4 mm, contact protected jacks.

Variable Plug Set


Three contact protected,
ISO Calibrator 1 self-retaining test probes
Calibration adapter for quick and for connection to mea-
efficient testing of the accuracy of surement cables with
test instruments for insulation 4 mm banana plugs, or
resistance and low-value with contact protected
resistors. plugs for connection to
sockets with openings
ranging from 3.5 to
12 mm, e.g. CEE or Per-
PC.doc ilex outlets etc.
PC.doc DOS software allows for the preparation of test reports in The test probes also fit
compliance with ZVEH, and in accordance with DIN VDE 0100. into, for example, the
square PE jack at Perilex
Measurement values outlets. Maximum allow-
stored to the PSI mod- able operating voltage: 600 V per IEC 61010.
ule are entered directly
to a predefined report Floor Probe
format. The 1081 floor probe
Reports can also be allows for the measure-
archived at a PC. ment of resistance at insu-
lating floor coverings in
accordance with
DIN VDE 0100, part 610
and EN 1081.
PC.base-m+204
Reports in accordance with DIN VDE 0100 can also be prepared
with the help of PC.base-m+204 MS WINDOWS software.
The predefined report
format can be individu-
alized with the
integrated forms
generator.

KS24 Cable Set


The KS 24 cable set con-
sists of a 4 m extension
cable with permanently
attached test probe at one
end, and a contact pro-
tected jack at the other
end, as well as two alligator
clips which can be plugged
onto the test probe.

6 GOSSEN-METRAWATT GMBH
PROFiTEST0100S-II
Test Instrument for DIN VDE 0100
Drum with TR50 Order Information
Measurement Cable
50 m measurement cable Designation Type Article Number
wound onto a metal drum. Basic Instruments
Connection to one end of the Universal, protective device test
cable is accomplished with a instrument for DIN VDE 0100
jack which is integrated into per DIN VDE 0413,
the drum. The other end is parts 1+3+4+6+7+9 PROFi TEST 0100S-II M 520A
equipped with a banana plug. Same as PROFi TEST0100S-II with
The drum axle with handle languages English, Danish, Swedish,
can be removed for space Finnish and German, no plug insert, PROFi TEST 0100
saving storage. with English operating instructions S-UK-II M 520B
Cable resistance can be com- Same as PROFi TEST0100S-II with
pensated for in selector switch position RLO. Iberian languages (Castilian, Cata-
lan, Galician, Basque, Portuguese, PROFi TEST 0100
English) S-E-II M 520C
Various Accessories
Same as PROFi TEST0100S-II with
Clockwise: Slavic languages (Czech, Slovenian, PROFi TEST 0100
TR25 reel, Hungarian and German) S-Ost-II M 520D
SP350 earth drill,
Telearm 1
telescoping rod, Test Instrument Sets
PRO-UNI and Test set in K100 carrying case:
PRO-RLO plug PROFiTEST 0100S-II,
inserts PROFiTESTPSI-E, PC.doc, SP350,
Telearm 1, PS-10P, A3-16 and TR25 PGS110 M509H
Test set in F100 carrying pouch:
PROFiTEST0100S-II,
PROFiTESTPSI-E and PC.doc PGS113 M509J
Same as PGS113 with
PROFi TESTPSI-TE instead of
PROFi TESTPSI-E and with
PC.doc-win instead of
PC.doc PGS115 M509K
Test set in K100 carrying case:
F100 Carrying Pouch PROFi TEST0100S-II,
PROFi TESTPSI-E, PC.base-m,
The test instrument, SP350, Telearm 1, PS-10P, PRO-
the PSI module, plug RLO, variable plug set and TR25 PGS210 M509L
inserts, measuring
Same as PGS210 with
adapter, replacement PROFi TESTPSI-TE instead of
batteries, recording PROFiTESTPSI-E and with
chart paper etc., can PC.base-m+204 instead of
all be conveniently PC.base-m PGS211 M509M
stored and trans-
ported with the F100
Expansions
carrying pouch.
Printer, memory, RS232
as expansion module for
PROFiTEST0100S-II including
2 rolls of recording chart, 1 ink rib-
bon, batteries, operating instructions PROFi TEST PSI-E D) M522A
Same as PROFiTESTPSI-E,
series T, but with expanded data
K100 Carrying Case entry and report generating PROFi TEST PSI-TE D) M522B
As compared with the Printer adapter for the connection
F100 carrying pouch, of a printer with Centronics interface
the K100 carrying to the PROFiTESTPSI-E/TE DA-II Z745M
case has additional Test instrument, as described
room for three differ- on page 5, including connector
ent three-phase cable and operating instructions PROFi TEST DC-II D) M523A
current adapters, reel Differential current monitor DI-Mon 1 M662B
with measurement
IR interface for connection to the
cable, telescoping RS232 port at a PC for the transmis-
rod, earth drills and sion of data between the PC and the
1081 probe. PROFiTEST0100S-II,
e.g. for software updates
to the instrument or display
of measurement values at the PC IrDa 0100S Z501C

GOSSEN-METRAWATT GMBH 7
PROFiTEST0100S-II
Test Instrument for DIN VDE 0100

Designation Type Article Number Designation Type Article Number


Plug Inserts and Adapters Calibration Adapters
Measuring adapter for three-phase Comparator for calibration
current and poly-phase systems PRO-A3 1) GTZ 3214 000 R0001 of the PROFiTEST0100S/S-II PROFi KALIBRATOR 1 M661A
Schuko or equivalent PRO-Schuko GTZ 3228 000 R0001 Calibration adapter for testing
For Switzerland per SEV PRO-CH GTZ 3225 000 R0001 the accuracy of instruments for the
measurement of insulation resis-
For GB per BS PRO-GB GTZ 3226 000 R0001 tance and low-value resistors ISO-Kalibrator 1 M662A
For GB ring measurement PRO-GB/ring GTZ 3226 000 R0002
For Italy per IMQ PRO-I GTZ 3227 000 R0001 Software
For Denmark PRO-DK GTZ 3219 000 R0001 Report generating software
For South Africa PRO-RSA Z501A (DOS software on floppy disc
With 3 connector cables with interface cable for RS232) PC.doc GTZ 3252 000 R0001
for any standards PRO-UNI GTZ 3214 000 R0003 Windows software for the generation
With 10 m cable of reports and lists. Data import from
for PE measurements etc. PRO-RLO GTZ 3214 000 R0002 test instrument or PSI module PC.doc-win Z710F
5-pole three-phase current adapter Basic software in German for the
for 16 A CEE outlets A3-16 GTZ 3602 000 R0001 electrical trade, for the generation of
reports and lists per VDE 0100
5-pole three-phase current adapter (WINDOWS software on floppy disc
for 32 A CEE outlets A3-32 GTZ 3603 000 R0001 with interface cable for RS232) PC.base-m Z712B
5-pole three-phase current adapter Basic software in German for the
for 63 A CEE outlets A3-63 GTZ 3604 000 R0001 electrical trade, for the generation of
Variable plug set Z500A Z500A reports per EN 60204/
Adapter for PROFi TESTDC-II DIN VDE 0113, 0100, 0701/0702
in systems without earthing (WINDOWS software on floppy disc
contact outlets 3pol.-Adapter Z523A with interface cable for RS232) PC.base-m+204 M712C
Adapter for protective conductor Software update
and insulation testing with the for PROFiTEST0100S-II on floppy
PROFiTEST0100S-II Adapter 701 Z501F disc (one-time update only,
not a subscription) SW-Update AF Z520A

Accessories
Consumable Materials
4 m extension cable KS24 GTZ 3201 000 R0001
Package of 10 rolls of recording
Telescoping rod for PE measurement Telearm 1 GTZ 3232 000 R0001 chart for the PSI module PS-10P GTZ 3229 000 R0001
Reel with 25 m measurement cable TR25 Reel GTZ 3303 000 R0001 Package of 10 ink ribbon cartridges
Drum with 50 m measurement cable TR50 Drum GTY 1040 014 E34 for the PSI module Z3210 GTZ 3210 000 R0001
35 cm earth drill D)
Data sheet available
for earth measurement SP350 Earth Drill GTZ 3304 000 R0001 1) Included with the PROFiTEST0100S-II
Triang. probe for floor measurement
per EN 1081 and DIN VDE 0100 1081 Probe GTZ 3196 000 R0001 For further information concerning accessories,
6 special NiM rechargeable mignon see our Measuring Instruments and Testers catalog.
batteries with holder (1300 mAh) Akku-Set 0100S Z501B
Charger for recharging 0100S bat-
tery set in the PROFiTEST0100S-II NA 0100S Z501D
Clip-on current sensor for leakage
current, adjustable: 1 mA … 15 A,
3% and 1 A … 150 A, 2% CLIP 0100S Z501E
Carrying pouch F100 GTZ 3314 000 R0001
Carrying case K100 GTZ 3318 000 R0001

Printed in Germany • Subject to change without notice

GOSSEN-METRAWATT GMBH
Thomas-Mann-Str. 16-20
90471 Nuremberg, Germany
Phone +49 911 8602-0
Fax +49 911 8602-669
e-mail: [email protected]
http://www.gmc-instruments.com

You might also like