Profitest100s II
Profitest100s II
Profitest100s II
3-348-888-03
Test Instrument for DIN VDE 0100 2/3.99
GOSSEN-METRAWATT GMBH
PROFiTEST0100S-II
Test Instrument for DIN VDE 0100
Display Standard Equipment
The LCD field consists of a backlit dot matrix at which menus,
possible settings, measurement results, tables, tips and error 1 PROFiTEST0100S-II test instrument
messages, as well as wiring diagrams are displayed. 1 insert for earthing contact plug (PRO-Schuko)
1 two-pole measuring adapter
Selectable Language 1 cable for expansion to three-pole adapter
An appropriate language can be selected for the country in which 2 alligator clips
the test instrument is used. 1 carrying strap
Several instrument versions are available which include various
language combinations. 1 set batteries
1 operating instructions
Operation
The instrument is very easy to operate with its rotary function
selector switch and 5 keys. Two of the keys located at the instru-
ment have the same functions as the keys at the test plug, which Applicable Regulations and Standards
allows for convenient measuring at difficult to access locations.
Wiring diagrams and online help can be displayed at the LCD for IEC 61010-1/EN 61010-1/ Safety requirements for electrical equipment
all basic functions and sub-functions. VDE 0411-1 for measurement, control and laboratory use
IEC 61557/ EN 61557/ Part 1: General requirements
Phase Tester VDE 0413 Part 2: Insulation resistance measuring instruments
Protective conductor potential is tested by contacting the contact Part 3: Loop resistance measuring instruments
surface with the contact finger. If a potential difference of greater Part 4: Instruments for the measurement or resistance
than 100 V is detected between the contact surface and the pro- at earth conductors, protective conductors
and bonding conductors
tective contact at the earthing contact plug, the PE signal lamp Part 5: Earth resistance measuring instruments
lights up. Part 6: Instruments for testing for correct functioning
of residual-current protective devices (RCDs)
Signal Lamps and the effectiveness of protective measures in
Faults within the system are recognized automatically by the TT and TN systems
Part 7: Phase sequence indicators
instrument, and are indicated by means of four lamps.
DIN 43751 Part 1, 2 Digital measuring instruments
Battery or Rechargeable Battery Test and Self-Test VDE 0106 Part 1 Protection against electrical shock, classifications
for electrical and electronic equipment
The battery test is performed under load. The results are dis-
played both numerically and with a symbol. Test patterns can be EN 60529 Test instruments and test procedures
VDE 0470 Part 1 – Protection provided by enclosures (IP code)
queried one after the other during the self-test, and LEDs and
relays can be tested as well. The instrument is shut down auto- EN 50081-1 Electromagnetic Compatibility (EMC)
matically if the batteries are depleted. The instrument includes an Generic standard for interference emission
integrated charge control circuit for reliable charging of NiMH or EN 50082-1 Electromagnetic Compatibility (EMC)
NiCd batteries. Generic standard for interference immunity
Data Interface
Data are transmitted to the PROFiTESTPSI-E/TE accessory
module (optional) via the integrated IRDA interface, which pro-
vides for three advantages:
Nominal Ranges of Use
• Immediate print-out of all measurement data to Voltage UN 120 V (108 ... 132 V)
recording chart paper 230 V (196 ... 253 V)
• Storage of all data to memory for later processing 400 V (340 ... 440 V)
Frequency fN 16 2/3 Hz (15.4 ... 18 Hz)
• Transmission of stored data to a PC for archiving, or for the 50 Hz (49.5 ... 50.5 Hz)
preparation of reports 60 Hz (59.4 ... 60.6 Hz)
200 Hz (190 ... 210 Hz)
Software Updates 400 Hz (380 ... 420 Hz)
The test instrument will always be up to date, because its soft- Overall Voltage Range 65 ... 550 V
ware can be updated via the IRDA interface. Software updates Overall Frequency
can be performed within the framework of instrument Range 15.4 ... 420 Hz
re-calibration by our service department, or by the user. Waveshape sine
Temperature Range 0 °C ... + 40 °C
Battery Voltage 6 ... 10 V
Line Impedance Angle corresponds to cosϕ = 1 ... 0.95
Probe Resistance < 50 kΩ
2 GOSSEN-METRAWATT GMBH
PROFiTEST0100S-II
Test Instrument for DIN VDE 0100
Characteristic Values
Input Connections
Func- Measured Measuring Range Reso- Nominal Range
Impedance / Nominal Values Operating Error Intrinsic Error Plug 2-Pole 3-Pole
tion Quantity (Display Range IK) lution of Use Probe Clip
Test Current Insert 2) Adapter Adapter
0 ... 99.9 V 0.1 V ±(1% rdg.+5D)
108 ... 253 V
100 ... 500 V 1V ±(1% rdg.+1D)
UL-PE terminal L-N-PE ±(2% rdg.+1D)
0 ... 99.9 V 0.1 V ±(1% rdg.+5D)
500 kΩ 108 ... 500 V
100 ... 500 V 1V ±(1% rdg.+1D)
●
15.0 ... 99.9 Hz 0.1 Hz
f terminal L-PE 15.4 ... 420 Hz ±(0.2% rdg.+1D) ±(0.1% rdg.+1D) ●
100 ... 1000 Hz 1 Hz 500 kΩ
UL–PE 0 ... 99.9 V 0.1 V
U3~ 108 ... 500 V ±(3% rdg.+1D) ±(2% rdg.+1D) ●
100 ... 500(850)1) V 1V
0 ... 99.9 V 0.1 V probe-PE
USONDE 0 ... 253 V ±(3% rdg.+5D) ±(2% rdg.+4D) ●
100 ... 253 V 1V 1MΩ
IL 0 ... 1 A 0.1 mA 5 mA ... 1.0 A ±(5% rdg.+5D) ±(3% rdg.+3D) ●
0 ... 99.9 A 0.1 A
IAMP. 10 A ... 150 A ±(10% rdg.+5D) ±(5% rdg.+3D) ●
100 ... 199 A 1A
0 ... 99.9 V 0.1 V ±(1% rdg.+5D)
UL-N 108 ... 253 V ±(2% rdg.+1D)
100 ... 300 V 1V ±(1% rdg.+1D)
UL–N 330 kΩ ●
15.0 ... 99.9 Hz 0.1 Hz ±(0.1%
f 15.4 ... 420 Hz ±(0.2% rdg.+1D)
100 ... 1000 Hz 1 Hz rdg.+1D)
+1% rdg.–1D ...
UI∆N 0 ... 70.0 V 0.1 V 0.3 · I∆N 5 ... 70 V +10% rdg.+1D
+9% rdg.+1D
RE / I∆N = 10 mA 10 Ω ... 6.51 kΩ 10 Ω
3 Ω ... 999 Ω 3Ω
RE / I∆N = 30 mA
1 kΩ ... 2.17 kΩ 10 Ω UN = 120/230 V
RE / I∆N = 100 mA 1Ω ... 651 Ω 1Ω
calculated value
0.3 Ω ... 99.9 Ω 0.3 Ω fN = 50/60 Hz
RE / I∆N = 300 mA
100 Ω ... 217 Ω 1Ω
UL = 25/50 V
0.2 Ω ... 9.99 Ω 0.2 Ω
RE / I∆N = 500 mA
100 Ω ... 130 Ω 1Ω
●
I∆N I∆N = 10/30/ ● ● as
I∆ / I∆N = 10 mA 3.0 ... 13.0 mA 3.0 ... 13.0 mA 3.0 ... 13.0 mA 100/300/500
0.1 mA desired
I∆ / I∆N = 30 mA 9.0 ... 39.0 mA 9.0 ... 39.0 mA 9.0 ... 39.0 mA mA
±(3.5%
I∆ / I∆N = 100 mA 30 ... 130 mA 1 mA 30 ... 130 mA 30 ... 130 mA ±(5% rdg.+1D)
rdg.+2D)
I∆ / I∆N = 300 mA 90 ... 390 mA 1 mA 90 ... 390 mA 90 ... 390 mA UN3) = 400 V
I∆ / I∆N = 500 mA 150 ... 650 mA 1 mA 150 ... 650 mA 150 ... 650 mA
UI∆ / UL = 25 V 0 ... 25.0 V 0 ... 25.0 V +1% rdg.–1D ...
0.1 V same as I∆ +10% rdg.+1D
UI∆ / UL = 50 V 0 ... 50.0 V 0 ... 50.0 V +9% rdg.+1 D
tA / I∆N 0 ... 1000 ms 1 ms 1.05 · I∆N 0 ... 1000 ms
±4 ms ±3 ms
tA / 5 · I∆N 0 ... 40 ms 1 ms 5 · I∆N 0 ... 40 ms I∆N = 10/30 mA
0.15 ... 0.5 Ω ±(10% rdg.+8D) ±5 D
ZSchl (full-waves)
0.5 ... 1.0 Ω UN = 120/230 V ±(10% rdg.+5D) ±(4% rdg.+3D)
ZI
0.01 ... 9.99 Ω 10 mΩ 0.83 ... 4.0 A 1.0 ... 10 Ω ±(5% rdg.+3D) ±(3% rdg.+3D)
ZSchl
ZSchl 0.25 ... 1.0 Ω UN2)= 400 V/ ±(20% rdg.+5D) ±(6% rdg.+5D)
● ●
(+/– half-waves) 1.0 ... 10 Ω 500 V at ZSchl ±(10% rdg.+3D) ±(4% rdg.+3D) ZSchl
ZI
0 A ... 999 A 1A 120 (108 ... 132) V
IK 1.00 kA ... 9.99 kA 10 A — 230 (196 ... 253) V fN = 50/60 Hz — —
10.0 kA ... 50.0 kA4) 100 A 400 (340 ... 440) V
0 ... 10 Ω 10 mΩ 0.83 ... 3.4 A 0.15 Ω ... 0.5 Ω ±(10% rdg.+5D) ±5 D
0 ... 10 Ω 10 mΩ 0.83 ... 3.4 A 0.5 Ω ... 1.0 Ω ±(10% rdg.+5D) ±(4% rdg.+3D)
RE
0 ... 10 Ω 10 mΩ 0.83 ... 3.4 A 1.0 Ω ...10 Ω UN = 120/230 V ±(5% rdg.+3D) ±(3% rdg.+3D)
(RESchl without
0 ... 100 Ω 10 mΩ 400 mA 10 Ω ...100 Ω UN = 400 V ±(10% rdg.+3D) ±(3% rdg.+3D)
probe)
0 ... 1 kΩ 1Ω 40 mA 100 Ω ...1 kΩ fN = 50/60 Hz ±(10% rdg.+3D) ±(3% rdg.+3D)
RE 1 kΩ ... 10 kΩ 1Ω 4 mA 1 kΩ ...10 kΩ ±(10% rdg.+3D) ±(3% rdg.+3D) ● ● ●
UE 0 ... 253 V 1V — calculated value
10 kΩ ... 200 kΩ ±(10% rdg.+3D) ±(5% rdg.+3D)
ZST
0 ... 1 MΩ 1 kΩ 2.3 mA at 230 V 200 kΩ ... 1 MΩ U0 = UL-N ±(20% rdg.+3D) ±(10% rdg.+3D)
RST 10 kΩ ... 200 kΩ ±(30% rdg.+3D) ±(20% rdg.+3D)
0.01 ... 9.99 MΩ 10 kΩ UN = 100 V
10.0 ... 99.9 MΩ 100 kΩ IN = 1 mA
0.01 ... 9.99 MΩ 10 kΩ
UN = 250 V
10.0 ... 99.9 MΩ 100 kΩ
RISO, RE ISO IK = 1.5 mA 50 kΩ ... 100 MΩ IN = 1 mA ±(5% rdg.+1D) ±(3% rdg.+1D)
100 ... 200 MΩ 1 MΩ
RISO ● ●
0.01 ... 9.99 MΩ 10 kΩ
UN = 500 V
10.0 ... 99.9 MΩ 100 kΩ
IN = 1 mA
100 ... 300 MΩ 1 MΩ
±(1.5%
U 25 ... 600 V– 1V 500 kΩ 25 ... 600 V ±(3% rdg.+1D)
rdg.+1D)
0.01 Ω ... 9.99 Ω 10 mΩ
RLO RLO Im ≥ 200 mA 0.5 Ω ... 6 Ω U0 = 4.5 V ±(4% rdg.+3D) ±(2% rdg.+2D) ●
10.0 Ω ... 99.9 Ω 100 mΩ
1) Only for systems with overvoltage category II, fouling factor 2, max. 5 min 3) 500 mA RCCB, max. UN = 230 V
2) U > 253 V with 2-pole adapter only 4) 100 UN · 1/Ω
GOSSEN-METRAWATT GMBH 3
PROFiTEST0100S-II
Test Instrument for DIN VDE 0100
4 GOSSEN-METRAWATT GMBH
PROFiTEST0100S-II
Test Instrument for DIN VDE 0100
instrument,
400
where they can be processed with PC.doc(-win) and PC.base-
m(+204) 300 A lesser slope for the residual current
software. curve between 0 and 100 mA results
For further information please request our data sheet: 200 in improved resolution.
PROFiTESTPSI-E/TE.
100 Start
Modules Comparison, PSI versus PSI-T
Feature PROFiTESTPSI-E PROFiTESTPSI-TE 0.4 0.8 1.0 1.6 2.0 2.4 2.8 3.2 3.6 4.0 4.4 4.8 t/s
Entry of buildings 3 place numeric 6 place alphanumeric
Entry of distribution cabinets — 3 place alphanumeric Tripping Test Operating Mode for AC-DC Sensitive RCCBs
Entry of RCD identification — 2 place alphanumeric with Constant DC Residual Current and Measurement of Tripping Current
Entry of circuits 3 place numeric 3 place alphanumeric In the selector switch position for the respective nominal residual
Number of measurement values 1 2 current, twice the nominal current flows via N and PE. Time
per circuit for insulation required until RCCB tripping occurs is measured and displayed.
resistance measurement
Entry of faults none 3 selectable possibilities Loop Impedance Measurement Operating Mode with the
Entry of number of existing none 3 place numeric PROFiTEST0100S-II by means of Suppressing RCCB Tripping
circuits The PROFiTESTDC-II allows for the measurement of loop
Report generating software PC.doc(-win) PC.base-m(+204) impedance in TN systems with RCCBs which are sensitive to pul-
and PC.base-m as of version 4.0 sating current (10/30/100/300/500 mA nominal residual current).
IF /mA The instrument gen-
erates a DC residual
current which satu-
DA-II rates the RCCB’s
Printer adapter for the connection of a printer with Centronics magnetic circuit. A
interface to the PROFiTESTPSI-E/TE for immediate printing of
t measuring current is
measured and stored values to a predefined report in A4 format. t1 t2 t3 superimposed by the
PROFiTEST0100S-
Measure
II which demon-
Operation strates half-waves
RCCB non-functional! only of like polarity.
Start The RCCB can no
longer detect the
measuring current and is not tripped during testing.
GOSSEN-METRAWATT GMBH 5
PROFiTEST0100S-II
Test Instrument for DIN VDE 0100
PROFiKALIBRATOR 1 3-Phase Current Adapters
The PROFiKALIBRATOR 1 is a calibration adapter for test instru- The A3-16, A3-32 and
ments in accordance with DIN VDE 0100. It is used in combina- A3-63 three-phase
tion with a test standard and a multimeter (e.g. METRAHit 28S) current adapters are
for the testing of protective device test instruments such as the used for the convenient
PROFiTEST0100S/S-II, M5010, M5011 and M5012. connection of test
The various functional values which must be determined in instruments to 5-pole
accordance with DIN VDE 0100, part 610, are first compared CEE outlets. The three
with the test standard and then with the measurement values different versions have
from the device under test. The measurement values from the test different sized plugs
standard serve as reference values. which correspond to
5-pole CEE outlets with
current ratings of 16 A,
32 A and 63 A. Phase
sequence is indicated
with lamps.
Testing for the effectiveness of protective devices is accomplished
via five 4 mm, contact protected jacks.
6 GOSSEN-METRAWATT GMBH
PROFiTEST0100S-II
Test Instrument for DIN VDE 0100
Drum with TR50 Order Information
Measurement Cable
50 m measurement cable Designation Type Article Number
wound onto a metal drum. Basic Instruments
Connection to one end of the Universal, protective device test
cable is accomplished with a instrument for DIN VDE 0100
jack which is integrated into per DIN VDE 0413,
the drum. The other end is parts 1+3+4+6+7+9 PROFi TEST 0100S-II M 520A
equipped with a banana plug. Same as PROFi TEST0100S-II with
The drum axle with handle languages English, Danish, Swedish,
can be removed for space Finnish and German, no plug insert, PROFi TEST 0100
saving storage. with English operating instructions S-UK-II M 520B
Cable resistance can be com- Same as PROFi TEST0100S-II with
pensated for in selector switch position RLO. Iberian languages (Castilian, Cata-
lan, Galician, Basque, Portuguese, PROFi TEST 0100
English) S-E-II M 520C
Various Accessories
Same as PROFi TEST0100S-II with
Clockwise: Slavic languages (Czech, Slovenian, PROFi TEST 0100
TR25 reel, Hungarian and German) S-Ost-II M 520D
SP350 earth drill,
Telearm 1
telescoping rod, Test Instrument Sets
PRO-UNI and Test set in K100 carrying case:
PRO-RLO plug PROFiTEST 0100S-II,
inserts PROFiTESTPSI-E, PC.doc, SP350,
Telearm 1, PS-10P, A3-16 and TR25 PGS110 M509H
Test set in F100 carrying pouch:
PROFiTEST0100S-II,
PROFiTESTPSI-E and PC.doc PGS113 M509J
Same as PGS113 with
PROFi TESTPSI-TE instead of
PROFi TESTPSI-E and with
PC.doc-win instead of
PC.doc PGS115 M509K
Test set in K100 carrying case:
F100 Carrying Pouch PROFi TEST0100S-II,
PROFi TESTPSI-E, PC.base-m,
The test instrument, SP350, Telearm 1, PS-10P, PRO-
the PSI module, plug RLO, variable plug set and TR25 PGS210 M509L
inserts, measuring
Same as PGS210 with
adapter, replacement PROFi TESTPSI-TE instead of
batteries, recording PROFiTESTPSI-E and with
chart paper etc., can PC.base-m+204 instead of
all be conveniently PC.base-m PGS211 M509M
stored and trans-
ported with the F100
Expansions
carrying pouch.
Printer, memory, RS232
as expansion module for
PROFiTEST0100S-II including
2 rolls of recording chart, 1 ink rib-
bon, batteries, operating instructions PROFi TEST PSI-E D) M522A
Same as PROFiTESTPSI-E,
series T, but with expanded data
K100 Carrying Case entry and report generating PROFi TEST PSI-TE D) M522B
As compared with the Printer adapter for the connection
F100 carrying pouch, of a printer with Centronics interface
the K100 carrying to the PROFiTESTPSI-E/TE DA-II Z745M
case has additional Test instrument, as described
room for three differ- on page 5, including connector
ent three-phase cable and operating instructions PROFi TEST DC-II D) M523A
current adapters, reel Differential current monitor DI-Mon 1 M662B
with measurement
IR interface for connection to the
cable, telescoping RS232 port at a PC for the transmis-
rod, earth drills and sion of data between the PC and the
1081 probe. PROFiTEST0100S-II,
e.g. for software updates
to the instrument or display
of measurement values at the PC IrDa 0100S Z501C
GOSSEN-METRAWATT GMBH 7
PROFiTEST0100S-II
Test Instrument for DIN VDE 0100
Accessories
Consumable Materials
4 m extension cable KS24 GTZ 3201 000 R0001
Package of 10 rolls of recording
Telescoping rod for PE measurement Telearm 1 GTZ 3232 000 R0001 chart for the PSI module PS-10P GTZ 3229 000 R0001
Reel with 25 m measurement cable TR25 Reel GTZ 3303 000 R0001 Package of 10 ink ribbon cartridges
Drum with 50 m measurement cable TR50 Drum GTY 1040 014 E34 for the PSI module Z3210 GTZ 3210 000 R0001
35 cm earth drill D)
Data sheet available
for earth measurement SP350 Earth Drill GTZ 3304 000 R0001 1) Included with the PROFiTEST0100S-II
Triang. probe for floor measurement
per EN 1081 and DIN VDE 0100 1081 Probe GTZ 3196 000 R0001 For further information concerning accessories,
6 special NiM rechargeable mignon see our Measuring Instruments and Testers catalog.
batteries with holder (1300 mAh) Akku-Set 0100S Z501B
Charger for recharging 0100S bat-
tery set in the PROFiTEST0100S-II NA 0100S Z501D
Clip-on current sensor for leakage
current, adjustable: 1 mA … 15 A,
3% and 1 A … 150 A, 2% CLIP 0100S Z501E
Carrying pouch F100 GTZ 3314 000 R0001
Carrying case K100 GTZ 3318 000 R0001
GOSSEN-METRAWATT GMBH
Thomas-Mann-Str. 16-20
90471 Nuremberg, Germany
Phone +49 911 8602-0
Fax +49 911 8602-669
e-mail: [email protected]