Catalogo Siemens
Catalogo Siemens
Catalogo Siemens
Catalog Edition
LV 10 10/2022
Low-Voltage Power
Distribution and Electrical
Installation Technology
Protection, Switching, Measuring and Monitoring
Devices, Switchboards and Distribution Systems
siemens.com/lowvoltage
© Siemens 2022
With SIRIUS, SENTRON, SIVACON and ALPHA, we offer an innovative portfolio for standard-compliant
and demand-oriented applications.
Efficient engineering tools and innovative cloud-based solutions can be flexibly tailored to individual
requirements.
Catalog LV 10 · 10/2022 The products and systems described in this catalog are manufactured/
distributed under application of a certified quality management system
You will find the latest edition and all future editions in accordance with EN ISO 9001 (for the Certified Registration Nos., see
in the Siemens Industry Online Support at www.siemens.com/system-certificates/ep).
www.siemens.com/lowvoltage/catalogs The certificate is recognized by all IQNet countries.
Refer to the Industry Mall for current prices Technical specifications
www.siemens.com/lowvoltage/mall The technical specifications are for general information purposes only.
Always heed the operating instructions and notices on individual products
during assembly, operation and maintenance.
All illustrations are not binding.
© Siemens 2022
© Siemens 2022
SENTRON · SIVACON · ALPHA
1
Protecting Air Circuit Breakers 1/1
2
Molded Case Circuit Breakers 2/1
3
Miniature Circuit Breakers 3/1
4
Residual Current Protective Devices/Arc Fault Detection Devices (AFDDs) 4/1
5
Switching Devices 5/1
6
Overvoltage Protection Devices 6/1
7
Fuse Systems 7/1
8
Protecting, Switching and Isolating Switch Disconnectors 8/1
9
Switching and Isolating Transfer Switching Equipment and Load Transfer Switches 9/1
10
Measuring and Monitoring Measuring Devices, Power Monitoring and Digitalization Solutions 10/1
11
Monitoring Devices 11/1
12
Distribution Transformers, Power Supply Units and Socket Outlets 12/1
13
Busbar Systems 13/1
14
Terminal Blocks 14/1
15
Power Distribution Boards, Motor Control Centers and Distribution Boards 15/1
16
Busbar Trunking Systems 16/1
17
System Cubicles, System Lighting and System Air-Conditioning 17/1
A
Appendix A/1
© Siemens 2022
Introduction | Sustainability@SI
Sustainability@SI
Smart infrastructure is sustainable infrastructure.
Siemens as a company takes an all-round view of environmental, social and governance criteria (ESG) with its DEGREE rulebook
(decarbonization, ethics, governance, resource efficiency, equity and employability). Not only are we committed to reducing the
carbon footprint in our own plants to net zero by 2030, but also to helping our customers achieve their decarbonization and sustaina-
bility objectives. The main areas in which smart infrastructure contributes to the DEGREE rulebook are decarbonization, resource
efficiency and employability.
Mission & strategy Technology with a purpose Our contribution Facts about sustainability
As a focused technology We develop technologies that Siemens makes a difference For almost 175 years, Siemens
company, Siemens is commit- interconnect the real world every single day by providing has been driven by the desire
ted to tackling the world's and the digital world and innovative solutions for to improve the lives of people
most profound challenges by enable our customers to make challenges in environmental around the world with our
leveraging the synergies of positive changes to their protection, decarbonization, technologies.
digitalization and sustainability. industries, which form the health and safety. Innovative
backbone of our economy: solutions that have a clear
industry, infrastructure, purpose: to make the world
transportation and healthcare. more sustainable, more
integrative and a better place
to live.
New products
I
SENTRON COM – Version 1.1
• Stability and system improvements
• Additional signals for devices
− Restart
I201_20406
− Manual tripping
− Confirmation of tripping
− Deactivation of an alarm, etc.
• 5SL6 COM miniature circuit breakers & AFDD/LS 5SV6 COM
− Additional information about the switching state
• 5ST3 COM auxiliary switches and fault signal contacts
− Additional device information about the mounted device (name, type)
• 7KN Powercenter 1000
I201_20406
− Additional temperature measurement and Bluetooth improvements
• Update function of the entire system via SENTRON powerconfig software
See chapter 10
Page 10/20
I
Introduction | Products and their applications in infrastructure Products and their applications in industry | Introduction
7KM PAC3200T
Climate
Page 10/26 SIVACON 8PS Page 16/4
7KM PAC3220 SIMATIC
Page 10/26 Energy Suite
TIA Portal
7KM PAC3220
Page 10/24
Page 10/26
SIVACON 8MF1
Shop (external) Parking Page 17/6 ALPHA distribution
board Page 15/160
Manufacturing Mounting
7KN 7KN
5SG7 MINIZED D02 3VA2 POC3000 5TT4 POC1000 SEM3
Page 7/13 Page 2/12 Page 10/18 Page 5/20 Page 10/20 Page 10/32
7KN POC3000
Page 10/18 7KN
3WL10 POC1000 3VA2
5SG7 MINIZED D02 Page 1/118 Page 10/20 Page 2/12
Page 7/13
COM800
Page 2/58
7KM PAC3120
3NJ4 Page 10/26
3NA COM
Overview of products
Page 8/100
Page 7/50
7KM PAC3220
Page 10/26
3NA COM
3WA
Page 7/50
I201_20178a
I201_20177
I/8 Siemens LV 10 · 10/2022 Siemens LV 10 · 10/2022 I/9 find an overview of the diverse
portfolio of catalog LV 10.
Introduction | Overview of protection, switching, measuring and monitoring tasks Overview of protection, switching, measuring and monitoring tasks | Introduction
Switching function
Current limitation
Starter protection
Isolating function
Personnel safety/
Motor protection
Line protection
Preventive fire
Measurement
(Short-circuit)
protection GF
protection LT
Ground-fault
fault current
Overvoltage
Short-circuit
Short-circuit
protection,
protection,
delayed ST
protection
protection
protection
protection
Generator
Overload
function
Protection, switching,
Fuse switch disconnectors 3NP 0 … 630 A 8/82 With suitable With suitable ■ With suitable With suitable With suitable
Switch disconnector with fuse 3NJ 0 … 630 A 8/134 fuse links fuse links ■ fuse links fuse links fuse links
3KF 0 … 630 A 8/118 ■
measuring and
Transfer switching equipment 3KC 16 … 3200 A 9/4 ■ ■
PAC measuring devices 7KM/ Any 10/26 ■
7KT
Motor starter protectors 3RV – Catalog IC 10 ■ ■ ■ ■ ■
monitoring tasks
Contactor 3RT – Catalog IC 10 ■
1)
Only applies to 3NW8
2)
Only applies to the communication-capable COM products
I
Miniature Circuit Breakers | Devices for all applications System overview | Miniature Circuit Breakers
Miniature circuit breakers Miniature circuit breakers Device protection switches Miniature circuit breakers for basic applications
for basic applications for advanced applications for advanced applications
Ideal for standard applications Ideal for industrial applications Ideal for devices in industry
The 5SL miniature circuit breakers are For circuits with motors or large lamps, Device protection switches from
the new standard with B and C tripping semiconductors or strong pulse- Siemens offer optimum protection for
characteristics for applications up to generating equipment such as transfor- all applications in AC and DC control 5SY6 5SY4 5SP4 5SP5 new 5SY5 5SY7 5SY8 5SJ4..HG.. 5SL6 COM
63 A. They can be used as main control mers and solenoid valves – the 5SY and circuits in industrial applications and
switches to disconnect or isolate 5SP devices are optimized for industrial plant engineering. Device protection switches for advanced applications
equipment. applications and are proven in use.
Thermomagnetic 5SY17 device
The 5SL devices are mainly installed in The 5SY devices offer you top quality protection switches are used to protect
meter panels and small distribution and functionality for installation in solenoid valves, servo motors, signal
boards to protect circuits for lamps, complex buildings and industry. With a lamps or even PLC inputs. Everywhere
cookers and even machines, for rated breaking capacity of up to 25 kA, where loads have to be precisely
example, in residential or commercial they are able to handle the most protected from overloads and short-
5SY17 5SK9
buildings. challenging requirements at a rated circuits.
current of 0.3 to 80 A.
Electronic 5SK9 device protection Electrical accessories
Special features switches are optimally suited to
• Dual-chamber terminals protecting, for example, relays,
• Simple to detach without tools using programmable controllers, motors,
sliding catches sensors, actuators and valves. A current
• Separate switching position indication analysis in conjunction with fast tripping
• A wide range of accessories in the event of a fault avoid the danger
• 5SL60 available as communication- of overloading the switched-mode
Auxiliary switches Fault signal Auxiliary switches and fault signal Shunt trips Undervoltage Remote control mechanisms 5SM6 arc fault
capable miniature circuit breaker power supply. (AS) contacts (FC) contacts (AS+FC)/(AS+FC) COM (ST) releases (UR) (RC mech.) detection units
System overview
Mechanical accessories
5SL6 COM miniature circuit breakers and 5ST3 COM auxiliary switches/fault signal
contacts with communication and measuring functions
Miniature Circuit Breakers | Quick selection guide Quick selection guide | Miniature Circuit Breakers
5SL6 COM 5SY6 5SY4 5SP4 5SP5 new 5SY5 5SY7 5SY8 5SJ4..HG..
Standards
Standards IEC/EN 60898-1 IEC/EN 60898-1 IEC/EN 60898-1 IEC/EN 60898-1 IEC/EN 60947-2 IEC/EN 60898-2 IEC/EN 60898-1 IEC/EN 60947-2 IEC/EN 60947-2
IEC/EN 60947-2 IEC/EN 60947-2 UL 1077 UL 1077 IEC/EN 60947-2 UL 1077 UL 489
3 UL 1077 UL 1077 UL 1077 3
Basic data
Breaking capacity Icn For AC (230/400 V) acc. to IEC/EN 60898-1 AC kA 6 6 10 10 – 10 15 25 –
Acc. to UL1077 and CSA C22.2 No.235 – Supplementary Supplementary Supplementary protector, – Supplementary protector, Supplementary protector, Supplementary protector, –
protector, OC, protector, OC, OC, FW 0, OL 0, TC 3 at OC, FW 0, OL 0, TC 3 at OC, FW 0, OL 0, TC 3 at OC, FW 0, OL 0, TC 3 at
FW 0, OL 0, TC 3 at FW 0, OL 0, TC 3 at 50°C 50°C 50°C 50°C
50 °C 50 °C
SC – U2: see Certificate U2: see Certificate U2: see Certificate of – U2: see Certificate of U2: see Certificate of U2: see Certificate of –
of Compliance of Compliance Compliance Compliance Compliance Compliance
Rated breaking capacity Icu In 0.3 … 2 A kA – 30 | 30 35 | 35 –|– –|– –|– 50 | 50 70 | 70 10
acc. to IEC/EN 60947-2 at Ue 230 V | at Ue 400 V In 3 … 6 A kA – 30 | 30 35 | 35 –|– –|– –|– 40 | 40 50 | 50 10
(1P, 1P+N) | (2P, 3P, 4P, 3P+N) In 8 … 10 A kA – 15 | 15 20 | 20 –|– –|– –|– 30 | 30 40 | 40 10
In 13 … 32 A kA – 15 | 15 20 | 20 –|– –|– –|– 25 | 25 30 | 30 10
In 35 … 40 A kA – 10 | 10 15 | 15 –|– –|– –|– 20 | 20 25 | 25 10
In 50 … 63 A kA – 10 | 10 15 | 15 –|– –|– –|– 15 | 15 20 | 20 10
In 80 … 125 A kA – –|– 10 | 10 10 | 10 –|– –|– –|– –|– –
Rated current A 2 … 32 0.3 … 63 0.3 … 80 80 … 125 80 … 125 0.3 … 63 0.3 … 63 0.3 … 63 0.3 … 63
Number of poles 1P+N 1P | 2P | 3P | 4P | 1P | 2P | 3P | 4P | 1P | 2P | 3P | 4P 1P | 2P 1P | 2P | 4P 1P | 2P | 3P | 4P | 1P+N | 1P | 2P | 3P | 4P | 1P+N | 1P | 2P | 3P
1P+N | 3P+N 1P+N | 3P+N 3P+N 3P+N
Tripping characteristic B|C B|C A|B|C|D B|C|D – B|C B|C|D C|D B|C|D
Approvals
General product approvals VDE, RED VDE, IMQ, CCC, VDE, IMQ, CCC, VDE, CCC, – VDE, CCC, VDE, IMQ, CCC, VDE, CCC,
Marine classifications – DNV-GL, LR, BV, DNV-GL, LR, BV, LR – ABS DNV-GL, LR, BV, RINA, ABS ABS –
RINA, ABS RINA, ABS
Operational voltage
I
Miniature Circuit Breakers | Basic units Basic units | Miniature Circuit Breakers
1P 1P+N 2P 3P 3P+N 4P
230/400 V AC 230 V AC 400 V AC 400 V AC 400 V AC 400 V AC
Mounting 1 MW 2 MW 2 MW 3 MW 4 MW 4 MW
width
1 1 N 1 3 1 3 5 1 3 5 N 1 3 5 7
2 2 N 2 4 2 4 6 2 4 6 N 2 4 6 8
3 Rated Characteristic Characteristic Characteristic Characteristic Characteristic Characteristic 3
current In A B C D A B C D A B C D A B C D A B C D A B C D
0.3 A – – 5SY4114-7 5SY4114-8 – – 5SY4514-7 5SY4514-8 – – 5SY4214-7 5SY4214-8 – – 5SY4314-7 5SY4314-8 – – 5SY4614-7 5SY4614-8 – – 5SY4414-7 5SY4414-8
0.5 A 5SY4105-5 – 5SY4105-7 5SY4105-8 – – 5SY4505-7 5SY4505-8 5SY4205-5 – 5SY4205-7 5SY4205-8 5SY4305-5 – 5SY4305-7 5SY4305-8 – – 5SY4605-7 5SY4605-8 – – 5SY4405-7 5SY4405-8
1A 5SY4101-5 5SY4101-6 5SY4101-7 5SY4101-8 5SY4501-5 – 5SY4501-7 5SY4501-8 5SY4201-5 5SY4201-6 5SY4201-7 5SY4201-8 5SY4301-5 5SY4301-6 5SY4301-7 5SY4301-8 5SY4601-5 – 5SY4601-7 5SY4601-8 5SY4401-5 – 5SY4401-7 5SY4401-8
1.6 A 5SY4115-5 5SY4115-6 5SY4115-7 5SY4115-8 5SY4515-5 5SY4515-6 5SY4515-7 5SY4515-8 5SY4215-5 5SY4215-6 5SY4215-7 5SY4215-8 5SY4315-5 5SY4315-6 5SY4315-7 5SY4315-8 5SY4615-5 – 5SY4615-7 5SY4615-8 5SY4415-5 – 5SY4415-7 5SY4415-8
2A 5SY4102-5 5SY4102-6 5SY4102-7 5SY4102-8 5SY4502-5 – 5SY4502-7 5SY4502-8 5SY4202-5 5SY4202-6 5SY4202-7 5SY4202-8 5SY4302-5 5SY4302-6 5SY4302-7 5SY4302-8 5SY4602-5 – 5SY4602-7 5SY4602-8 5SY4402-5 – 5SY4402-7 5SY4402-8
3A 5SY4103-5 5SY4103-6 5SY4103-7 5SY4103-8 5SY4503-5 – 5SY4503-7 5SY4503-8 5SY4203-5 5SY4203-6 5SY4203-7 5SY4203-8 5SY4303-5 5SY4303-6 5SY4303-7 5SY4303-8 5SY4603-5 – 5SY4603-7 5SY4603-8 5SY4403-5 – 5SY4403-7 5SY4403-8
4A 5SY4104-5 5SY4104-6 5SY4104-7 5SY4104-8 5SY4504-5 5SY4504-6 5SY4504-7 5SY4504-8 5SY4204-5 5SY4204-6 5SY4204-7 5SY4204-8 5SY4304-5 5SY4304-6 5SY4304-7 5SY4304-8 5SY4604-5 – 5SY4604-7 5SY4604-8 5SY4404-5 – 5SY4404-7 5SY4404-8
5A – – 5SY4111-7 – – – – – – – 5SY4211-7 – – – 5SY4311-7 – – – – – – – – –
6A 5SY4106-5 5SY4106-6 5SY4106-7 5SY4106-8 5SY4506-5 5SY4506-6 5SY4506-7 5SY4506-8 5SY4206-5 5SY4206-6 5SY4206-7 5SY4206-8 5SY4306-5 5SY4306-6 5SY4306-7 5SY4306-8 5SY4606-5 5SY4606-6 5SY4606-7 5SY4606-8 5SY4406-5 5SY4406-6 5SY4406-7 5SY4406-8
8A 5SY4108-5 5SY4108-6 5SY4108-7 5SY4108-8 5SY4508-5 – 5SY4508-7 5SY4508-8 5SY4208-5 5SY4208-6 5SY4208-7 5SY4208-8 5SY4308-5 5SY4308-6 5SY4308-7 5SY4308-8 5SY4608-5 – 5SY4608-7 5SY4608-8 5SY4408-5 – 5SY4408-7 5SY4408-8
10 A 5SY4110-5 5SY4110-6 5SY4110-7 5SY4110-8 5SY4510-5 5SY4510-6 5SY4510-7 5SY4510-8 5SY4210-5 5SY4210-6 5SY4210-7 5SY4210-8 5SY4310-5 5SY4310-6 5SY4310-7 5SY4310-8 5SY4610-5 5SY4610-6 5SY4610-7 5SY4610-8 5SY4410-5 5SY4410-6 5SY4410-7 5SY4410-8
13 A 5SY4113-5 5SY4113-6 5SY4113-7 5SY4113-8 5SY4513-5 5SY4513-6 5SY4513-7 5SY4513-8 5SY4213-5 5SY4213-6 5SY4213-7 5SY4213-8 5SY4313-5 5SY4313-6 5SY4313-7 5SY4313-8 5SY4613-5 5SY4613-6 5SY4613-7 5SY4613-8 5SY4413-5 5SY4413-6 5SY4413-7 5SY4413-8
15 A – – 5SY4118-7 – – – – – – – 5SY4218-7 – – – 5SY4318-7 – – – – – – – – –
16 A 5SY4116-5 5SY4116-6 5SY4116-7 5SY4116-8 5SY4516-5 5SY4516-6 5SY4516-7 5SY4516-8 5SY4216-5 5SY4216-6 5SY4216-7 5SY4216-8 5SY4316-5 5SY4316-6 5SY4316-7 5SY4316-8 5SY4616-5 5SY4616-6 5SY4616-7 5SY4616-8 5SY4416-5 5SY4416-6 5SY4416-7 5SY4416-8
20 A 5SY4120-5 5SY4120-6 5SY4120-7 5SY4120-8 5SY4520-5 5SY4520-6 5SY4520-7 5SY4520-8 5SY4220-5 5SY4220-6 5SY4220-7 5SY4220-8 5SY4320-5 5SY4320-6 5SY4320-7 5SY4320-8 5SY4620-5 5SY4620-6 5SY4620-7 5SY4620-8 5SY4420-5 5SY4420-6 5SY4420-7 5SY4420-8
25 A 5SY4125-5 5SY4125-6 5SY4125-7 5SY4125-8 5SY4525-5 5SY4525-6 5SY4525-7 5SY4525-8 5SY4225-5 5SY4225-6 5SY4225-7 5SY4225-8 5SY4325-5 5SY4325-6 5SY4325-7 5SY4325-8 5SY4625-5 5SY4625-6 5SY4625-7 5SY4625-8 5SY4425-5 5SY4425-6 5SY4425-7 5SY4425-8
30 A – – 5SY4130-7 – – – – – – – 5SY4230-7 – – – 5SY4330-7 – – – – – – – – –
32 A 5SY4132-5 5SY4132-6 5SY4132-7 5SY4132-8 5SY4532-5 5SY4532-6 5SY4532-7 5SY4532-8 5SY4232-5 5SY4232-6 5SY4232-7 5SY4232-8 5SY4332-5 5SY4332-6 5SY4332-7 5SY4332-8 5SY4632-5 5SY4632-6 5SY4632-7 5SY4632-8 5SY4432-5 5SY4432-6 5SY4432-7 5SY4432-8
35 A – – 5SY4135-7 – – – – – – – 5SY4235-7 – – – 5SY4335-7 – – – – – – – – –
40 A 5SY4140-5 5SY4140-6 5SY4140-7 5SY4140-8 5SY4540-5 5SY4540-6 5SY4540-7 5SY4540-8 5SY4240-5 5SY4240-6 5SY4240-7 5SY4240-8 5SY4340-5 5SY4340-6 5SY4340-7 5SY4340-8 5SY4640-5 5SY4640-6 5SY4640-7 5SY4640-8 5SY4440-5 5SY4440-6 5SY4440-7 5SY4440-8
45 A – – 5SY4145-7 – – – – – – – 5SY4245-7 – – – 5SY4345-7 – – – – – – – – –
50 A 5SY4150-5 5SY4150-6 5SY4150-7 5SY4150-8 5SY4550-5 5SY4550-6 5SY4550-7 5SY4550-8 5SY4250-5 5SY4250-6 5SY4250-7 5SY4250-8 5SY4350-5 5SY4350-6 5SY4350-7 5SY4350-8 5SY4650-5 5SY4650-6 5SY4650-7 5SY4650-8 5SY4450-5 5SY4450-6 5SY4450-7 5SY4450-8
60 A – – 5SY4160-7 – – – – – – – 5SY4260-7 – – – 5SY4360-7 – – – – – – – – –
63 A 5SY4163-5 5SY4163-6 5SY4163-7 5SY4163-8 5SY4563-5 5SY4563-6 5SY4563-7 5SY4563-8 5SY4263-5 5SY4263-6 5SY4263-7 5SY4263-8 5SY4363-5 5SY4363-6 5SY4363-7 5SY4363-8 5SY4663-5 5SY4663-6 5SY4663-7 5SY4663-8 5SY4463-5 5SY4463-6 5SY4463-7 5SY4463-8
80 A – 5SY4180-6 5SY4180-7 – – – 5SY4580-7 – – 5SY4280-6 5SY4280-7 – – 5SY4380-6 5SY4380-7 – – – 5SY4680-7 – – 5SY4480-6 5SY4480-7 –
Product page
Auxiliary switches (AS) Article No. Arc fault detection units (AFDD) Article No.
1 NO + 1 NC Standard 5ST3010 For basic units 1P+N In up to 16 A 5SM6021-2
optional optional For low power 5ST3013 (2 MW) In up to 40 A 5SM6024-2
18 mm
36 mm
18 mm
18 mm
18 mm
9 mm
9 mm
9 mm
9 mm
9 mm
9 mm
and and or or or or
For low power (with diode) 5ST3013-0XX01 Undervoltage releases (UR) Article No.
27 – 36 mm
18 mm
18 mm
9 mm
9 mm
9 mm
9 mm
9 mm
9 mm
and and or or or or
Auxiliary switches and fault signal contacts (AS+FC) Article No. Power 12 ... 30 V AC, 12 ... 48 V DC 5ST3055
1 CO (AS) + 1 CO (FC) 5ST3062 177 … 270 V AC 5ST3056
5SY4
basic unit
RC mech.
and
AS
FC
AS
FC + FC
AS ST
UR
ST AS
UR + FC
ST AS
UR + FC + FC
AS
5ST3 COM (AS+FC)
Shunt trips (ST)
110 … 415 V AC, 110 … 220 V DC
5ST3062-0MC
Article No.
5ST3030
Power with ARD
Quick selection guide, page 3/8 Quick selection guide, page 3/8
3/26 Siemens LV 10 · 10/2022 Siemens LV 10 · 10/2022 3/27
same page.
Air Circuit Breakers | 3WA11 – 3WA13 3WA11 – 3WA13 | Air Circuit Breakers
The structure shown below is intended as an overview of each position and its meaning.
For a complete and valid configuration of your air circuit breaker, please use our online configurator at
www.siemens.com/lowvoltage/3wa-configurator
1 1
5 6 7 8 9 10 11 12 13 14 15 16 5 6 7 8 9 10 11 12 13 14 15 16
3WA1 – – 3WA1 – –
Circuit breaker and Connection
SZ 1
SZ 2
SZ 3
Configurable products
Non-automatic circuit breakers, ready4COM feature C A
conveniently configurable
PMF-II Basic Power Voltage tap on top
voltage tap in the circuit Monitoring Voltage tap on bottom F
breaker, VTM680 voltage PMF-III Advanced Voltage tap on top N
tap module and Power Monitoring Voltage tap on bottom G
ready4COM
Quick selection guide, pages 1/4 and 1/8 Quick selection guide, pages 1/4 and 1/8
1/32 Siemens LV 10 · 10/2022 Siemens LV 10 · 10/2022 1/33
valid configuration.
3VA9157-0EK11 I201_20435
I201_20436
or by entering this web address incl. article number Industry image database:
www.siemens.com/product?Article No. www.siemens.com/lowvoltage/picturedb
Elevator
7KM PAC3200T
Climate
Page 10/26
7KM PAC3220
Page 10/26
Photovoltaic
5SL 5SV1
Page 3/6 Page 4/50
7KN 7KN
5SG7 MINIZED D02 3VA2 POC3000 5TT4 POC1000 SEM3
Page 7/13 Page 2/12 Page 10/18 Page 5/20 Page 10/20 Page 10/32
7KM PAC3120
3NJ4 Page 10/26
3NA COM
Page 8/100
Page 7/50
3WA
Page 1/28
ALPHA 3200
Page 15/14
I201_20177
5SY4 5SV1
5SV3 5SV1 5ST3 5SM6 5SV6 5SL6 7KN ALPHA Page 3/26 Page 4/50
Page 4/26 Page COM Page COM COM POC1000 SIMBOX XL
4/50 Page 3/52 4/52 Page Page Page Page
4/54 3/40 10/20 15/202
3VA 5SY17
Page 2/6 3NP1 Page 3/44
SIMATIC PCS7
Page 8/82
Page 10/25
7KM PAC2200
3VA2 Page 10/26
Page 2/12
RCD 3VA
Page 2/54 Page 2/6
7KN POC3000
3LD Page 10/18
5SV3
SIMATIC ET200SP Page 8/6
Page 4/26
Catalog ST70 5SU1
Page 4/38
7KM PAC3220
Page 10/26
SINAMICS G120
Catalog D31.1 5SV1
5SV3, type B Page 4/50
Page 4/26
SIMOCODE pro 5SY 5SD74,
Catalog IC10 Page 3/8 type 2
Page 6/14 5SY 5SD74, type 2
Page 3/8 Page 6/14
SIVACON 8MF1
Page 17/6 ALPHA distribution
board Page 15/156
Manufacturing Mounting
7KN POC3000
Page 10/18 7KN
3WL10 POC1000 3VA2
5SG7 MINIZED D02 Page 1/118 Page 10/20 Page 2/12
Page 7/13
COM800
Page 2/58
7KM PAC3220
Page 10/26
3NA COM
Page 7/50
3WA 3NJ6
Page 1/28 Page 8/134
7KM PAC4200 3NJ4
Page 10/26 Page 8/102
SIVACON S8
Page 15/12
I201_20178a
I $MPVECBTFE
BOBMZTJT
Elevator
or
7KM PAC3200T
Climate 7KM
Page 10/26
PAC3220
Page 10/26
Photovoltaic
$POEJUJPO
SIVACON 8PS NPOJUPSJOH
7KT PAC1200
1SFEJDUJWF
5SV3 5SV1 5ST3 5SV6 5SL6 7KN ALPHA Page 10/31 SENTRON SENTRON NBJOUFOBODF
COM COM COM POC1000 SIMBOX powermanager powerconfig
Page Page Page Page Page 10/14 Page 10/12
XL
3/52 4/54 3/40 10/20
5SL 5SV1
1PXFSNPOJUPSJOH
0OQSFNJTFT
5TT4
SEM3 Page 10/32
3NJ4 4UBOEBMPOF
7KM PAC3120
Page 10/26
7KN
POC1000
Page 10/20
3WA
3NJ6
Page 1/28
%FDFOUSBMJ[FEWJTVBMJ[BUJPO
7KM PAC4200 COM800 3KC
Page 10/26 Page 2/58 Page 9/8 PGNFBTVSFEWBMVFT
ALPHA 3200 3NA COM TUBUFTBOEBMBSNTWJB
I201_20179a
*OEVTUSJBM&UIFSOFU
QPXFSMJOF
Industrial Ethernet
3VA-line
powerline
&ORXGEDVHG
DQDO\VLV
Climate I
7KM PAC3200T
Page 10/26 3VA
SIVACON 8PS
7KM PAC3220 SIMATIC Energy
Page 10/26 Suite TIA Portal
Page 10/24
3RZHUPRQLWRULQJ
7KM
RCD
7KN PAC2200
3VA 3VA2
POC3000 Page 10/26
Page 2/12
SIMATIC ET200SP
Catalog ST70
2QSUHPLVHV 3LD 5SV3
7KM PAC3220
SINAMICS G120 Page 10/26
Catalog D31.1 5SU1
7KM PAC3220
Page 10/26
3NJ4
'HFHQWUDOL]HGYLVXDOL]DWLRQ
3WA
RIPHDVXUHGYDOXHV Page 1/28 7KM PAC4200
VWDWHVDQGDODUPVYLD 3NJ6
Page 10/26
I201_20180b
,QGXVWULDO(WKHUQHW
9$OLQH
SRZHUOLQH
Industrial Ethernet
3VA-line
powerline
Digitalization
Protection, switching and measuring devices in power distribution systems can display important information on local
visualization via integrated communication, e.g. in Powercenter, or transmit it to energy data management systems (EDMS),
e.g. SENTRON powermanager, as well as to cloud systems and applications.
• Diagnostics management
• Fault management – Email alarm
• Maintenance management – predictive maintenance
• Cost center management
7. Cybersecurity
• Protection from unauthorized access and manipulation to switchgear and controlgear assemblies and devices
ensures integrity, availability and confidentiality.
I
6LHPHQV$SSV
&XVWRPHU$SSV
UG3DUW\$SSV
DQDO\VLVV\VWHPV
&ORXGEDVHG
3RZHUPRQLWRULQJ
&RQGLWLRQ
3UHGLFWLYH
6(17521
PRQLWRULQJ
PDLQWHQDQFH
SRZHUPLQG
KWWSVVLHPHQVPLQGVSKHUHLR
2QSUHPLVHV
Ã6(17521SRZHUPDQDJHU ,QWHJUDWHG:HE,QWHUIDFH
Ã6(17521SRZHUFRQILJ
3ODWIRUP
&RQQHFWLYL\
.13RZHUFHQWHU
0RGEXV578 0RGEXV7&3
'LIIHUHQWFRPPXQLFDWLRQRSWLRQVGHSHQGLQJRQWKHGHYLFH
'HYLFHVVHQVRUV
3URWHFWLRQDQGVZLWFKLQJ 0HDVXULQJGHYLFHV
GHYLFHV
(QHUJ\PHDVXUHPHQW (QHUJ\PHDVXUHPHQWWRDFFXUDF\0,'
6WDWXVLQIRUPDWLRQ 2XWSXWPHDVXUHPHQWWRDFFXUDF\7+'
5HPRWHFRQWURO 3RZHU4XDOLW\WRDFFXUDF\+DUPRQLFV
,BD
6(17521FRPSRQHQWVLQ6,9$&21$/3+$GLVWULEXWLRQV\VWHPV
1)
Modbus TCP
Starter protection
Isolating function
Motor protection
Line protection
protection
Generator
Device class Type Rated current Page
Air circuit breakers 3WA/ 630 … 6300 A 1/28 ■ ■ ■ ■
3WL
Molded case circuit breakers 3VA 16 … 1600 A 2/6 ■ ■ ■ ■ ■
Miniature circuit breakers 5SY/ 0 … 80 A 3/6 ■
(automatic circuit breakers) 5SL
RCCB 5SV3/ 16 … 125 A 4/6 ■ ■
5SM3
RCBOs 5SU1/ 0 … 40 A 4/10 ■ ■
5SV1
AFD units 5SM6 0 … 40 A 4/12
AFDD/MCBs 5SV6 0 … 40 A 4/12 ■ ■
On/Off switches 5TL1 32 … 125 A 5/14
Overvoltage protection 5SD7 – 6/6 ■
devices
Fuses NEOZED, DIAZED, 5SE, 5SA, – 7/30 ■ ■ 1) ■
Cylindrical fuses 5SB, 3NW6,
3NW8
Photovoltaic fuses – – 7/79 ■
LV HRC fuses 3NA/ – 7/36 ■ ■ ■
3ND
SITOR semiconductor fuses – – 7/54 ■ ■ ■
Switch disconnectors 3LD 16 … 250 A 8/6 ■
3KD 16 … 1600 A 8/8 ■
Fuse switch disconnectors 3NP 0 … 630 A 8/82 With suitable With suitable ■
Switch disconnector with fuse 3NJ 0 … 630 A 8/134 fuse links fuse links ■
3KF 0 … 630 A 8/118 ■
Transfer switching equipment 3KC 16 … 3200 A 9/4 ■
PAC measuring devices 7KM/ Any 10/26
7KT
Motor starter protectors 3RV – Catalog IC 10 ■ ■
Contactor 3RT – Catalog IC 10 ■
1)
Only applies to 3NW8
2)
Only applies to the communication-capable COM products
■
■
■
■
■
■
■
■
■
(Short-circuit)
fuse links
With suitable
Overload
■
■
■
■
■
■
■
■
■
■
protection LT
fuse links
With suitable
Short-circuit
■
■
protection,
delayed ST
Short-circuit
■
■
■
■
■
■
■
■
■
■
protection,
fuse links
With suitable
instantaneous INST
Ground-fault
■
■
protection GF
Measurement
■
■
■
■ 2)
■ 2)
■ 2)
© Siemens 2022
function
Personnel safety/
■/■
■/■
■/■
fault current
protection
Overvoltage
■
protection
Preventive fire
■
■
■
■
protection
Siemens LV 10 · 10/2022
■ Switching function
I/15
Overview of protection, switching, measuring and monitoring tasks | Introduction
I
© Siemens 2022
Introduction | Overview of protection, switching, measuring and monitoring tasks
I201_20328
I201_20327
The trip units for line protection are designed to provide The setting values of the trip units are matched to protecting
overload and short-circuit protection for: generators.
• Cables
• Leads
• Non-motor loads
I201_20330
I201_20329
The overload and short-circuit releases are designed for Starter combinations consist of:
optimal protection and direct starting of three-phase AC
Molded case circuit breaker + contactor + overload relay.
squirrel-cage motors.
The molded case circuit breaker handles short-circuit protec-
The molded case circuit breakers for motor protection have
tion and the isolating function. The task of the contactor is the
phase-failure sensitivity and a thermal image that protects the
operational switching of the feeder. The overload relay
motor against overheating.
handles overload protection that can be specially matched to
The adjustable time lag class enables users to adjust the the motor.
overload release to the startup conditions of the motor to be
The molded case circuit breaker for the starter combination is
protected.
therefore equipped with an adjustable and instantaneous
short-circuit release.
+ or
I201_20406
I201_20406
Current limitation means that the peak value of the prospecti- In the selection of transfer switch equipment, the following
ve peak short-circuit current is limited to a smaller let-through functions are distinguished (See chapter 9):
current.
• Transfer control
• Current-limiting devices include molded case circuit • Load transfer
breakers (MCCBs), motor starter protectors (MSPs),
The following possibilities for transfer switching are available:
miniature circuit breakers (MCBs) and fuses
• MTSE = manual transfer switch equipment
• RTSE = remote transfer switch equipment
• ATSE = automatic transfer switch equipment
G G
,
Non-
Priority
I201_20422
priority
load
load
Tripping characteristics
The protective function of protection and switching devices in low-voltage power distribution systems is determined by the correct
I selection of the respective tripping characteristic (fuses, miniature circuit breakers) or TMTU/ETU trip units (air circuit breakers,
molded case circuit breakers).
All current-limiting protection devices, such as MCCBs, MSPs, MCBs and fuses, can be described in terms of three characteristic curves:
• Tripping curve (time/current)
• Let-through current curve
• Let-through energy curve
In the following, the functions of the tripping curves are presented as an example.
The time-current characteristic curve of fuses denotes the The characteristic curve is chosen based on the application
virtual melting time as a function of the overload or short- and is classified, for example, as tripping characteristic A, B, C
circuit current. or D.
Different characteristics must be considered in dimensioning Tripping curve = tripping characteristics according to
depending on the protection requirement and operational IEC/EN 60898-1
class (e.g. gG, gR, aR, etc.).
See Configuration Manual – Miniature circuit breakers
See Configuration Manual – Fuse systems www.siemens.com/lowvoltage/manuals (45302792)
www.siemens.com/lowvoltage/manuals (45314810)
10 4 1.13 1.45
I201_06044b
120
6 I201_13653
4 60
vs[s]
40
Tripping time
2
20
Minutes
10 3 250 A
200 A 10
6 160 A
4 6
125 A 4
100 A
2 80 A 2
102 63 A 1
50 A
6 40
4 20
2 10
101 6
4
6
4 2
1
2
Seconds
0.6
100 0.4
6 0.2
4
0.1
2 0.06
10-1 0.04
6 0.02
4 0.01
1 1.5 2 3 4 5 6 8 10 15 20 30
2
Multiple of rated current
10 -2
6
4
2
10 -3
10 1 2 4 6 8 10 2 2 4 6 8 10 3 2 4 6 8 10 4
rms [A]
ATFM ATAM
(Adjustable Thermal Fixed Magnetic) (Adjustable Thermal Adjustable Magnetic)
r r
Adjustable thermal overload trip unit, permanently set Adjustable thermal overload trip unit, adjustable magnetic trip
magnetic trip unit with short-circuit protection unit with short-circuit protection
Tripping characteristics
Molded case circuit breakers (MCCBs)/air circuit breakers (ACBs) with ETU
Selection of the electronic trip unit determines the protective function in power distribution.
I Electronic trip units offer the most extensive and variable protection settings of all protection and switching devices for
low-voltage power distribution.
• See Equipment Manual – 3VA molded case circuit breakers with IEC certificate www.siemens.com/lowvoltage/manuals (90318775)
• See Equipment Manual – 3WA air circuit breakers www.siemens.com/lowvoltage/manuals (109763061)
The graphs below show an overview of the time-current characteristic curve.
LT
Overload
Overload protection LT protection LT
IN
LT
Ir
t in s
1.000
Neutral conductor overload
tr ST
delayed ST
N protection
Short-circuit protection,
N
100
Short-circuit protection,
ST delayed ST
Short-circuit protection,
10 INST
instantaneous INST
Ig Short-circuit protection,
Isd INST instantaneous INST
1
Neutral conductor overload
N protection N Ground-fault protection GF
0,1
GF
tg
tsd Ground-fault protection
Ii GF
GF
0,01
I201_20325
0,5 1 5 10 50 100
I in kA
The ID letter for overload protection is LT (stands for "Long- The ID letter for neutral conductor overload protection is N.
time delay"). The trip unit is inverse-time delayed and exhibits The letters IN refer to the current setting value for the
the following characteristics depending on the trip unit type: overload protection; the associated tripping time is identical
• Bimetal characteristic with thermal-magnetic trip units to tr.
• I2t characteristics for molded case circuit breakers MCCBs
The short-circuit protection of the circuit breaker also protects
and I2t and I4t characteristics for ACBs
the neutral conductor.
• Depending on the electronic trip units, only I2t characteristic
or I2t and I4t characteristic Possible reasons for implementing overload protection in the
neutral conductor include:
The letters Ir refer to the current setting value; the associated
tripping time is identical to tr. • The neutral conductor has a smaller cross-section than the
phase conductors.
• Higher harmonic components in the system can be
IN Ir expected.
1.000 • A large number of loads, or predominantly 1-phase loads,
t in s
tr are connected.
100
10
0,1
I201_20326
0,01
0,5 1 5 10 50 100
I in kA
1.000 t in s 1.000
t in s
100 100
10 10
I sd
1 1
0,1 0,1
t sd Ii
I201_20511
I201_20331
0,01 0,01
0,5 1 5 10 50 100
0,5 1 5 10 50 100
I in kA
I in kA
Ground-fault protection GF
1.000
t in s
100
10
Ig
1
0,1 tg
I201_20320
0,01
0,5 1 5 10 50 100
I in kA
Overvoltage protection refers to the protection of electrical Arc fault detection devices evaluate occurring faults in the
and electronic devices against excessively high electrical current and voltage wave using an electronic switch and
voltages. Overvoltage can be caused by switching operations shutting off the current when it recognizes a contact fault.
or electrostatic discharging (ESD). This prevents overheating at poor contact points which can
prevent fires.
Z UV Terminal
HAK
equipment
230/400V 10000
1000
S S S N
P P P 100
t in s
D D D
10
I201_20525
1 100
0,1 10
0,01
B C D
1
0,001
I201_20331
0,1 1 10 100
Personnel safety/fault current protection I in kA
N
PE
N
PE
N
PE
humidity, gases can damage or age the insulation
RA RA RA • Damage caused by rodents
• Loose contact, e.g. caused by too low torque
• Conductor damaged by claw fixing
PE conductor Conductors
Damaged
interrupted interchanged
insulation
and insulation
failure in the
equipment
I201_06156a
4*."3*4
4*."3*4 4QFDJ DPO 1BSUT
CVTCBSQMBO DBUJPO HVSBUJPO MJTU
F1MBO
4$' 84 $"%
I201_19849b
4*."3*4 4*."3*4 $"Y%PXOMPBE BMMQPMF $POOFDUJWJUZ 8FC QPXFSNBOBHFS
EFTJHO QSPKFDU .BOBHFS DJSDVJU TFSWFS
EJBHSBN
*OUFMMJHFOU
EBUBNBOBHFNFOU
4JFNFOT "TTFNCMZ %PDVNFO "TTFNCMZ
*OEVTUSZ.BMM ESBXJOH UBUJPO
$VTUPNJ[FEBTTFNCMZ
.BOVGBDUVSJOHQSPDFTT
BWBJMBCMFGPS"-1)"&DP
4*7"$0/4
Highlights
• Thorough support of the engineering process with
interlinked software tools
• Provision of extensive CAx data for systems and
components
• Reduction of cost and time aspects during planning
Distribution systems
For industrial plants or in infrastructure
I SIVACON S8 power distribution boards and SIVACON 8PS busbar trunking systems
motor control centers
• Reliable, economical, flexible and communication-capable • For economic and reliable power supply
• For all applications in infrastructure and process industry • Space-saving and simple to install
• Low fire load, good electromagnetic compatibility
ALPHA 3200 power distribution boards ALPHA 3200 Eco power distribution boards
(DIN technology) (DIN technology)
• Safe investment, enhances productivity and performance • Saves resources: lower use of copper with centrally
• Optimized for applications in modern building infra positioned busbar
structures • Practical: optimized performance – from the transformer
• Integrated system for all SENTRON components connection via the busbar to the outgoing feeders
• Modular: a high packing density in a compact space due to
flexible use of ALPHA assembly kits
• Innovative: 3D processor generates a digital twin of the
configured system at the press of a button
Information + ordering
1
All the important things at a glance Everything you need for your order
For information about air circuit breakers, please visit Refer to the Industry Mall for an overview of your
our websites products
www.siemens.com/3WA • Air circuit breakers sie.ag/2lXiZjB
www.siemens.com/3WL
Direct forwarding to the individual products in the
Industry Mall by clicking on the article number in the
catalog or entering this web address incl. article
Your product in detail number www.siemens.com/product?Article No.
The Siemens Industry Online Support (SIOS) provides Order supports are available in Siemens Industry Online
comprehensive information Support (SIOS) at
www.siemens.com/lowvoltage/product-support www.siemens.com/lowvoltage/product-support
• Quick Selection Guide • Order Support
− 3WA air circuit breakers (109781967) − 3WA air circuit breakers – Made for makers.
− 3WL air circuit breakers (109751638) Simply reliable. (109800074)
• Brochure
− 3WA air circuit breakers (109800077)
• Technical Basic Information Configurators
− 3WL air circuit breakers (109767789)
The relevant tender specifications can be found at The configurator reduces the time and effort required in
www.siemens.com/lowvoltage/tenderspecifications the planning and ordering process, and allows for individ
ual adaptations. Configure your air circuit breaker at
Use our conversion tool for quick and easy conversion to www.siemens.com/lowvoltage/3wa-configurator
Siemens products www.siemens.com/conversion-tool www.siemens.com/lowvoltage/3wl-configurator
www.siemens.com/lowvoltage/3wl10-configurator
The following are additionally available for your
Siemens YouTube channel configured air circuit breaker:
• 3D views
• 3WA air circuit breaker – Teaserfilm • CAD data
bit.ly/3p14AOZ • Unit wiring diagrams
• 3WA air circuit breaker – Highlightfilm • Dimension drawings
bit.ly/2Y0iWD2
• 3WL air circuit breakers (general)
bit.ly/2ZH1rXH
Commissioning + operation
The combined commissioning and service tool SENTRON Manuals are available for downloading in Siemens
powerconfig for communication-capable measuring Industry Online Support (SIOS) at
devices, circuit protection devices and circuit breakers. www.siemens.com/lowvoltage/manuals
• Equipment Manual
Free download SENTRON powerconfig − 3WA air circuit breakers (109763061)
www.siemens.com/powerconfig − 3VA27 molded case circuit breakers &
3WL10 air circuit breakers (109753821)
Free download SENTRON powerconfig mobile via • System Manual
App Store and Play Store − 3WA air circuit breaker communication (109792368)
− 3WL/3VL circuit breakers with communications
capability – Modbus (39850157)
− 3WL/3VL PROFIBUS circuit breakers with
Your product in detail communications capability – PROFIBUS (12560390)
• Configuration Manual
− 3WL1 air circuit breakers (35681108)
The Siemens Industry Online Support (SIOS) provides − Low-voltage protection devices selectivity tables
detailed technical information (109748621)
www.siemens.com/lowvoltage/product-support • Communication Manual
− 3WL air circuit breakers via COM35 – PROFINET IO,
• Operating instructions Modbus TCP (109757987)
• Characteristic curves − 3WL10 air circuit breakers & 3VA27 molded case
• Certificates circuit breakers (109760220)
Comprehensive mobile support via the Siemens Industry
Online Support app available for download from the
App Store and Play Store Face-to-face or online training
You will find further information at
www.siemens.com/support-app
Our training courses can be found at
Provision of 3D data (step and u3d data formats) www.siemens.com/sitrain-lowvoltage
• Siemens Industry Mall • 3WA air circuit breakers (WT-LV3WA)
www.siemens.com/lowvoltage/mall • 3WL10 air circuit breaker, size 0 (WT-LVA3WL0)
• 3WL air circuit breakers, sizes 1-3 (WT-LVA3WL)
• Image database • Protection systems in low-voltage power distribution
www.siemens.com/lowvoltage/picturedb (WT-LVAPS)
Engineering data for CAD or CAE systems are available in • LV-3WA Basic (LV-3WA_BA)
the CAx Download Manager at • LV-3WA Advanced (LV-3WA_AD)
www.siemens.com/cax • Maintenance and operation of 3WA circuit breakers
(LV-3WAMAIN)
• Maintenance and operation of 3WL circuit breakers
(LV-3WLMAIN)
• Certification: Maintenance and operation of 3WL and
3WA circuit breakers (LV-CBCERT)
• 3WL and 3WA air circuit breakers protection technology and
communication (LV-COPR)
• Project planning and selection of SENTRON circuit breakers
(LV-CBPROJ)
Video tutorial on the 3WL air circuit breaker
www.lowvoltage.siemens.com/wcms/3wl-tutorial
3WA11 3WA12
Basic data
Rated operational voltage Ue V ≤1000 ≤1150
Rated current In A 630 … 2500 2000 … 4000
Size 1 2
Type of mounting Withdrawable Fixed-mounted Withdrawable Fixed-mounted
Number of poles 3/4-pole 3/4-pole 3/4-pole 3/4-pole
Dimensions
Width (3-pole | 4-pole) mm 320 | 410 320 | 410 460 | 590 460 | 590
Height (for breaking capacity N, S, M, H and D | C and E) mm 468 | 518 437 | 462 468 | 518 437 | 462
Depth mm 471 357 471 357
Approvals
General product approvals VDE, EAC, CCC, CE, C-Tick VDE, EAC, CCC, CE, C-Tick
Marine/shipbuilding ABS, DNV, GL, LRS, BV, PRS, CCS, ABS, DNV, GL, LRS, BV, PRS, CCS, RMRS
RMRS
Breaking capacity N S M E S M H C E
Rated short-circuit breaking capacity
Icu | Ics at Ue up to 415/440 V AC kA 55 | 55 66 | 66 85 | 85 – | – 66 | 66 85 | 85 100 | 100 130 | 130 – | –
Icu | Ics at Ue up to 500 V AC kA 55 | 55 66 | 66 85 | 85 – | – 66 | 66 85 | 85 100 | 100 130 | 130 – | –
Icu | Ics at Ue up to 690 V AC kA 42 | 42 50 | 50 66 | 66 85 | 85 50 | 50 66 | 66 85 | 85 100 | 100 85 | 85
Icu | Ics at Ue up to 1000 V AC kA – | – – | – – | – 50 | 50 – | – – | – – | – – | – 85 | 85
Icu | Ics at Ue up to 1150 V AC kA – | – – | – – | – – | – – | – – | – – | – – | – 50 | 50
Rated short-circuit making capacity Icm
Icm at Ue up to 415 V AC kA 121 145 187 – 145 187 220 286 –
Icm at Ue up to 690 V AC kA 88 105 145 187 105 145 187 220 187
AC DC
1
3WA13 3WA12
≤1150 ≤1000 (≤1500 for 4-pole, Breaking capacity E)
4000 … 6300 1000 … 4000
3 2
Withdrawable Fixed-mounted Withdrawable Fixed-mounted
3/4-pole 3/4-pole 3/4-pole 3/4-pole
VDE, EAC, CCC, CE, C-Tick VDE, EAC, CCC, CE, C-Tick
ABS, DNV, GL, LRS, BV, PRS, CCS, RMRS ABS, DNV, GL, LRS, BV, PRS, CCS, RMRS
H C E D E
3WA11 3WA12
Breaking capacity N S M E S M H C E
Rated short-time withstand current Icw 1)
Icw at Ue up to 500 V AC 0.5 s kA 55 66 85 – 66 85 100 100 –
1s kA 50 66 85 – 66 85 85 100 –
2s kA 35 2)/45 3) 45 70 – 66 66 4)/85 5) 66 4)/85 5) 85 –
3s kA 30 2)/35 3) 35 60 – 55 4)/66 5) 55 4)/75 5) 55 4)/75 5) 75 –
Icw at Ue up to 690 V AC 0.5 s kA 42 50 66 85 50 66 85 100 85
1s kA 42 50 66 85 50 66 85 100 85
2s kA 35 2)/42 3) 45 66 70 50 66 66 4)/85 5) 85 66 4)/85 5)
3s kA 30 2)/35 3) 35 60 60 50 55 4)/66 5) 55 4)/75 5) 75 55 4)/75 5)
Icw at Ue up to 1000 V AC 0.5 s kA – – – 50 – – – – 85
1s kA – – – 50 – – – – 85
2s kA – – – 50 – – – – 66 4)/85 5)
3s kA – – – 50 – – – – 55 4)/75 5)
Icw at Ue up to 1150 V AC 0.5 s kA – – – – – – – – 50
1s kA – – – – – – – – 50
2s kA – – – – – – – – 50
3s kA – – – – – – – – 50
Icw at Ue up to 220 V DC 1s kA – – – – – – – – –
Icw at Ue up to 300 V DC 1s kA – – – – – – – – –
Icw at Ue up to 600 V DC 1s kA – – – – – – – – –
Icw at Ue up to 1000 V DC 1s kA – – – – – – – – –
Icw at Ue up to 1500 V DC 1s kA – – – – – – – – –
Rated conditional short-circuit current Icc of the non-automatic air circuit breakers
Up to 500 V AC kA 55 66 85 – 66 85 100 100 –
Up to 690 V AC kA 42 50 66 85 50 66 85 100 85
Up to 1000 V AC kA – – – 50 – – – – 85
Up to 1150 V AC kA – – – – – – – – 50
Up to 220 V DC kA – – – – – – – – –
Up to 300 V DC kA – – – – – – – – –
Up to 600 V DC kA – – – – – – – – –
Up to 1000 V DC kA – – – – – – – – –
Up to 1500 V DC kA – – – – – – – – –
IT network capability
1-pole short-circuit breaking capacity IIT ≤500 V kA 50 50 50 – 50 50 50 50 –
acc. to IEC60947-2 Annex H ≤690 V kA – – – 50 – – – – 50
1000 V kA – – – – – – – – –
At rated operational voltage Ue ≥690 V, the Icwvalue of the
1)
Size 1 with In max ≤1250 A
2)
In max ≤ 2500 A
4)
circuit breaker corresponds to the Icuor Icsvalue Size 1 with In max ≥1600 A
3)
In max ≥3200 A
5)
AC DC
1
3WA13 3WA12
H C E D E
50 50 – – –
– – 50 – –
– – – – –
I201_20310
Degree of protection IP20 without control cabinet door, IP41 with door sealing frame,
IP55 with cover
Voltage
Rated operational voltage Ue at 1000 V version V AC ≤1000
50/60 Hz
Rated insulation voltage Ui V AC 1000
Rated impulse withstand Main conducting paths kV 12
voltage Uimp Auxiliary circuits kV 4
Control circuits kV 2.5
Permissible load
Permissible load for withdrawable versions
For all connection types Up to 55 °C (Cu bare) A 630 800 1000 1250 1600 2000 –
(except rear vertical main Up to 60 °C (Cu bare) A 630 800 1000 1250 1600 1930 –
connections) Up to 70 °C (Cu bare) A 630 800 1000 1210 1490 1780 –
With rear vertical connections Up to 55 °C (Cu bare) A 630 800 1000 1250 1600 2000 2500
Up to 60 °C (Cu bare) A 630 800 1000 1250 1600 2000 2370
Up to 70 °C (Cu bare) A 630 800 1000 1250 1545 1855 2060
Permissible load for fixed-mounted versions
For all connection types Up to 55 °C (Cu bare) A 630 800 1000 1250 1600 2000 –
(except rear vertical main Up to 60 °C (Cu bare) A 630 800 1000 1250 1600 2000 –
connections) Up to 70 °C (Cu bare) A 630 800 1000 1250 1600 2000 –
With rear vertical connections Up to 55 °C (Cu bare) A 630 800 1000 1250 1600 2000 2500
Up to 60 °C (Cu bare) A 630 800 1000 1250 1600 2000 2500
Up to 70 °C (Cu bare) A 630 800 1000 1250 1600 2000 2500
Power loss at In
With 3-phase symmetrical load Fixed-mounted W 30 45 70 105 135 240 360
with maximum rated current, Withdrawable versions W 55 85 130 205 310 440 600
complete device (3/4p)
3WA12 3WA13
1
Yes Yes
B B
–40 … +70 –40 … +70
–40 … +80 –40 … +80
[∆ h max 0.04 in]
∆ h max 1mm
≤ 30° ≤ 30° ≤ 30° ≤ 30° ≤ 30° ≤ 30° ≤ 30° ≤ 30°
I201_20310
I201_20310
IP20 without control cabinet door, IP41 with door sealing frame, IP20 without control cabinet door, IP41 with door sealing frame,
IP55 with cover IP55 with cover
≤1150 ≤1150
≤1150 ≤1150
12 12
4 4
2.5 2.5
3WA12 3WA13
1
35 35
34 34
100 100
73 73
≤80 ≤80
50 50
– –
– –
– –
– –
10000 –
20000 –
7500 7500 4000 2000 –
20000 –
10000 –
20000 –
7500 7500 4000 2000 –
20000 –
10000 5000
20000 10000
7500 7500 4000 2000 1000
1000 1000
500 500
20000 10000
10000 7500
20000 15000
7500 7500 4000 2000 2000
20000 20000 20000 20000 15000
5000 5000
10000 10000
5000 5000 4000 1000 1000
10000 10000 10000 10000 10000
45 –
60 –
3WA12 3WA13
1
2× 0.5 … 2.5 mm2 (AWG 20 … 14) 2× 0.5 … 2.5 mm2 (AWG 20 … 14)
2× 0.5 … 2.5 mm2 (AWG 20 … 14) 2× 0.5 … 2.5 mm2 (AWG 20 … 14)
2× 0.5 … 1.5 mm2 (AWG 20 … 16) 2× 0.5 … 1.5 mm2 (AWG 20 … 16)
10 … 12 mm (0.39 … 0.47 inch) 10 … 12 mm (0.39 … 0.47 inch)
2× 0.5 … 2.5 mm2 (AWG 20 … 14) 2× 0.5 … 2.5 mm2 (AWG 20 … 14)
1× 0.5 … 1.5 mm2 (AWG 20 … 16) 1× 0.5 … 1.5 mm2 (AWG 20 … 16)
1× 0.5 … 1.5 mm2 (AWG 20 … 16) 1× 0.5 … 1.5 mm2 (AWG 20 … 16)
7 … 8 mm (0.28 … 0.31 inch) 7 … 8 mm (0.28 … 0.31 inch)
43 45 50 52 79 80 111
47 48 54 53 84 86 86
33 34 41 40 70 87 86
54 56 63 64 100 102 144
57 60 67 88 107 108 108
40 42 50 71 71 89 110
3WA12
1
Rated current In 1000 A 2000 A 4000 A
General data
Isolating function acc. to EN 60947-2 Yes
Utilization category B
Permissible ambient temperature During operation (in operation °C –40 … +70
with LCD max. 55 °C)
Storage °C –40 … +80
Mounting position
I201_20310
Degree of protection IP20 without control cabinet door, IP41 with door sealing frame,
IP55 with cover
Voltage
Rated operational voltage Ue Breaking capacity D | E V DC 600 | 1000 (3-pole); 1500 (4-pole)
Rated insulation voltage Ui Breaking capacity D | E V DC 600 | 1000 (3-pole); 1500 (4-pole)
Rated impulse withstand voltage Main conducting paths kV 12
Uimp Auxiliary circuits kV 4
Control circuits kV 2.5
Permissible load
Permissible load for withdrawable versions
For all connection types (except rear Up to 40 °C (Cu bare) A 1000 2000 4000
vertical main connections) Up to 55 °C (Cu bare) A 1000 2000 3640
Up to 60 °C (Cu bare) A 1000 2000 3500
Up to 70 °C (Cu bare) A 1000 1950 3250
With rear vertical connections Up to 40 °C (Cu bare) A 1000 2000 4000
Up to 55 °C (Cu bare) A 1000 2000 4000
Up to 60 °C (Cu bare) A 1000 2000 3640
Up to 70 °C (Cu bare) A 1000 2000 3400
Permissible load for fixed-mounted versions
For all connection types (except rear Up to 40 °C (Cu bare) A 1000 2000 4000
vertical main connections) Up to 55 °C (Cu bare) A 1000 2000 4000
Up to 60 °C (Cu bare) A 1000 2000 4000
Up to 70 °C (Cu bare) A 1000 2000 3900
With rear vertical connections Up to 40 °C (Cu bare) A 1000 2000 4000
Up to 55 °C (Cu bare) A 1000 2000 4000
Up to 60 °C (Cu bare) A 1000 2000 4000
Up to 70 °C (Cu bare) A 1000 2000 4000
Power loss at In
With 3-phase symmetrical load, Withdrawable versions W 280 770 1640
complete device (3/4p) Fixed-mounted W 140 390 820
Switching times
Make time ms 35 35 35
Opening time ms 34 34 34
Electrical make time (through closing coil) ms 100 100 100
Electrical opening time (through shunt trip) ms 73 73 73
Electrical opening time (instantaneous undervoltage release) ms ≤80 ≤80 ≤80
3WA12
1
Rated current In 1000 A 2000 A 4000 A
Service life/endurance
Breaking capacity D, 3/4-pole
Mechanical Without maintenance Operating cycles 10000 10000 10000
With maintenance 1) Operating cycles 20000 20000 20000
Electrical Without maintenance 600 V Operating cycles 6000 6000 4000
With maintenance 1) Operating cycles 20000 20000 20000
Breaking capacity E, 3/4-pole
Mechanical Without maintenance Operating cycles 10000 10000 10000
With maintenance 1) Operating cycles 20000 20000 20000
Electrical Without maintenance 1000 V Operating cycles 1000 1000 1000
With maintenance 1) Operating cycles 20000 20000 20000
Breaking capacity E, 4-pole
Electrical Without maintenance 1500 V 2) Operating cycles 1000 1000 1000
With maintenance 1) Operating cycles 20000 20000 20000
Switching frequency
Breaking capacity D
Electrical 3/4-pole 1/h 60/60 60/60 60/60
Breaking capacity E
Electrical 3/4-pole 1/h 20/20 20/20 20/20
Connection
Minimum main conductor cross-sections
Copper bars, bare Unit, mm2 1× 50 x 10 2× 50 x 10 3 x 100 x 10 on the
infeed and outgoing
side; 6 x 250 x 500 x 5
for jumpers
Copper bars, painted black Unit, mm2 1× 50 x 10 2× 50 x 10 3 x 100 x 10 on the
infeed and outgoing
side; 6 x 250 x 500 x 5
for jumpers
Auxiliary conductor (Cu) max. number of auxiliary conductors × cross-section (solid/stranded)
Standard connection = push-in Without end sleeve 2× 0.5 … 2.5 mm2 (AWG 20 … 14)
With end sleeve acc. to DIN 46228 Part 2 2× 0.5 … 2.5 mm2 (AWG 20 … 14)
With twin end sleeve 2× 0.5 … 1.5 mm2 (AWG 20 … 16)
Stripped length 10 … 12 mm (0.39 … 0.47 inch)
Optional connection with screw Without end sleeve 2× 0.5 … 2.5 mm2 (AWG 20 … 14)
connection With end sleeve acc. to DIN 46228 Part 2 1× 0.5 … 1.5 mm2 (AWG 20 … 16)
With twin end sleeve 1× 0.5 … 1.5 mm2 (AWG 20 … 16)
Stripped length 7 … 8 mm (0.28 … 0.31 inch)
Position signaling switch
Spring-loaded terminals for standard Without end sleeve 0.08 ... 2.5 mm² (AWG 20 ... 12)
signaling contacts With end sleeve acc. to DIN 46228 Part 2 0.25 … 1.5 mm²
Stripped length 5 … 6 mm (0.2 … 0.24 inch)
Push-in connection for Without end sleeve 0.14 ... 1.5 mm² (AWG 20 ... 16)
communication signaling contacts With end sleeve acc. to DIN 46228 Part 2 0.25 ... 1.5 mm² (AWG 20 ... 16)
Stripped length 9 mm (0.35 inch)
Weights
3-pole Fixed-mounted circuit breaker kg 56 56 64
Withdrawable circuit breaker kg 60 60 68
without guide frame
Guide frames kg 31 31 45
4-pole Fixed-mounted circuit breaker kg 67 67 77
Withdrawable circuit breaker kg 72 72 82
without guide frame
Guide frames kg 37 37 54
Maintenance means: Replacing main contact elements and arc chutes
1) 2)
1500 V DC applications only possible with 4-pole circuit breakers and breaking capacity E.
(see operating instructions: www.siemens.com/lowvoltage/manuals).
The connection to the non-automatic circuit breakers is not dependent on direction and polarity; the circuit diagrams can be
adapted accordingly. If the parallel or series connections are made directly to the connection bars, for thermal reasons the
continuous load on the non-automatic circuit breakers must only be 80% of the permissible operational current. If the parallel or
1 series connection is made at a distance of 1 m from the connection bars, the non-automatic circuit breaker can be used at full
operational current load.
I201_20253
I201_20252
I201_20251
Load Load
I201_20263
I201_20255
I201_20254
I201_20253
Load
Rated operational voltage up to 1000 V
Load
I201_20264
I201_20260
I201_20258
I201_20256
Load Load
Rated operational voltage up to 1500 V
Load Load
I201_20265
I201_20259
I201_20258
Note:
DC 2-pole (all-pole) disconnection; grounded system
The grounded conductor must always be assigned to the individual switching pole of the non-automatic air circuit breaker, so that in the event of a ground fault
there are always 2 conducting paths in series in a circuit with 3-pole circuit breakers, and 3 conducting paths in series in a circuit with 4-pole circuit breakers.
The jumpers between the switching poles must be short-circuit and ground-fault proof.
1)
Available in Q1/2023
ETU300 LSIG
Protective function Setting range
G: Ground-fault protection GF
Tripping Switched on
Method of ground fault detection Residual Detection of ground-fault current via summation current
formation in all phases and the N conductor
Characteristic GF curve With LSIG option plug I 0t
Current setting Ig With LSIG option plug 0,2 × In (min. 100 A, max. 1200 A)
Tripping time tg 0.2 s
1)
Available in Q1/2023
2)
The setting value is limited as a function of the breaking capacity at rated operational voltage Ue.
– Not available
◾ Available, feature of the application package
◽ Can be retrofitted
Connection
Main circuit connection
3WA11 – 3WA13
Fixed-mounted Withdrawable
1
I201_20299
I201_20298
Rear horizontal Rear horizontal
I201_20297
I201_20323
Rear vertical Rear vertical
I201_20308
I201_20307
I201_20304
I201_20305
Horizontal on top, Vertical on top, Horizontal on top, Vertical on top,
vertical at the bottom horizontal at the bottom vertical at the bottom horizontal at the bottom
I201_20301
I201_20301
Front connection with double hole Front connection with double hole
I201_20309
Flange
I201_20302
I201_20303
I201_20296
with 4 blocks
− Non-automatic circuit breakers with ETU600 LSI or LSIG with
4 blocks
Screwless connection (push in) Screw connection (optional)
− Non-automatic circuit breaker with ETU600 LSIG-HiZ with 5
blocks
For dimension drawings, see Equipment Manual – 3WA air circuit
breakers www.siemens.com/lowvoltage/manuals (109763061)
Communication
MindSphere Application
SENTRON powermind
SENTRON
1
powerconfig
SENTRON SENTRON mobile
powermanager1) SIMATIC S7 powerconfig1)
Power monitoring
PAC3220
Commissioning/ PAC4200
7KN parameterization
1)
Powercenter 3000
PROFIBUS/
Modbus RTU
I201_19702b
PROFINET/
Modbus TCP 7KN COM100/ DSP800
Powercenter 1000 2) COM800 with max. with COM15,
2 x COM150 COM16
with COM040,
COM042 with max. with COM35
3VA-line 2 x COM190
with COM041,
with COM060 COM043
...
5SV6 COM 5SL6 COM 5ST3 COM 3NA COM 3VA 3VA 3VA27 3WL10 3WA 3WL11 - 3WL13
AFDD MCB AS+FC max. 24 max. 8
1) Direct connection to Modbus TCP; Modbus RTU via gateway; PROFINET and PROFIBUS are not supported.
2) Direct connection to Modbus TCP; PROFINET is not supported.
The 3WA can be equipped with up to two PROFINET IO/Modbus TCP COM190 communications modules or Modbus RTU COM150 and
up to five IOM230 digital input/output modules.
For the optional communications interface with the COM190 or COM150 communications module, a circuit breaker with the
"ready4COM" feature must be selected as the circuit breaker/non-automatic air circuit breaker. The first COM190 or COM150
communications module must be selected via a Z option. If you want to use a further COM190 or COM150 communications module,
this must be ordered separately as an accessory. Both COM190 or COM150 communications modules can be run in parallel.
The first IOM230 digital input/output module can be selected via a Z option.
The up to four further digital input/output modules must be ordered separately as accessories.
You will find further information on the COM190 in the Equipment Manual – 3WA air circuit breakers
www.siemens.com/lowvoltage/manuals (109763061)
For a complete and valid configuration of your air circuit breaker, please use our online configurator at
www.siemens.com/lowvoltage/3wa-configurator
1
Circuit breakers and
non-automatic circuit breakers
Sizes 1 to 3
ETU300 1) ETU600
Note: You will find a detailed range of accessories in the Accessories and spare parts section.
1)
Available in Q1/2023
1
Auxiliary release
Communications module Digital input/output module Zone-selective Sealable and lockable cover Current sensors
interlocking module
Trip alarm switch Motor disconnect Local electric close Emergency OPEN
switch button
Other accessories
Door sealing frame Arc chute cover Automatic reset of the reclosing lockout
Note: You will find a detailed range of accessories in the Accessories section.
Graphical display
• Integration of the legend as a color system
− Orange: still to be selected
1 − Petrol: already selected
− Gray: preselected (default)
• Graphical highlighting of the individual configuration steps: "What you see is what you get"
Direct conversion of a 3WL article number to a 3WA article number in the configurator
The structure shown below is intended as an overview of each position and its meaning.
For a complete and valid configuration of your air circuit breaker, please use our online configurator at
www.siemens.com/lowvoltage/3wa-configurator
1
5 6 7 8 9 10 11 12 13 14 15 16
3WA1 – –
Circuit breakers and
non-automatic circuit breakers
Size (SZ) 1 1
2 2
3 3
SZ 1
SZ 2
SZ 3
Short-circuit N ■ – – 55/42 kA 2
breaking capacity S ■ ■ – 66/50 kA 3
Icu at 500/690 V M ■ ■ – 85/66 kA 4
H – ■ ■ 100/85 kA 5
C – ■ – 130/100 kA 6
– – ■ 3-pole: 150/150 kA 6
4-pole: 130/130 kA
1
5 6 7 8 9 10 11 12 13 14 15 16
3WA1 – –
Connection
SZ 1
SZ 2
SZ 3
Type of mounting Fixed-mounted ◾ ◾ 1) ◾ Vertical 1
◾ ◾ 3) ◾ 4) Horizontal 2
◾ 2) ◾ 5) ◾ 6) Front 3
◾ ◾ 3) ◾ 4) Vertical on top/horizontal at the bottom 5
◾ ◾ 3) ◾ 4) Horizontal on top/vertical at the bottom 6
Withdrawable ◾ ◾ ◾ Without guide frame 0
◾ ◾ 1) ◾ Vertical 1
◾ 2) ◾ 3) ◾ 4) Horizontal 2
◾ 2) ◾ 5) ◾ 6) Front 3
◾ 2) ◾ 5) ◾ 6) Flange 4
◾ 2) ◾ 3) ◾ 4) Vertical on top/horizontal at the bottom 5
◾ 2) ◾ 3) ◾ 4) Horizontal on top/vertical at the bottom 6
◾ 2) ◾ 5) ◾ 6) Flange on top/horizontal at the bottom 7
◾ 2) ◾ 5) ◾ 6) Horizontal on top/flange at the bottom 8
1)
The 4000 A vertical connections for the 3WA1 have different dimensions from the 3WL1.
Dimensionally compatible connections can be ordered with the additional Z option D01.
2)
Not available for 2500 A
3)
Not available for 4000 A
4)
Not available for 6300 A
5)
Not available for 4000 A and for breaking capacity C
6)
Not available for 5000 A and 6300 A and for breaking capacity C
The structure shown below is intended as an overview of each position and its meaning.
For a complete and valid configuration of your air circuit breaker, please use our online configurator at
www.siemens.com/lowvoltage/3wa-configurator
1
5 6 7 8 9 10 11 12 13 14 15 16
3WA1 – –
Operating mechanisms, auxiliary switches and auxiliary releases
Operating Manual recharging of the Without spring charging 2 NO, 2 NC 0
mechanism and stored energy mechanism motor 4 NO, 4 NC 1
auxiliary switch
Recharging of the stored 24 ... 30 V DC 2 NO, 2 NC 2
energy mechanism by 4 NO, 4 NC 5
spring charging motor
48 ... 60 V DC 4 NO, 4 NC 6
(M)
110 ... 127 V AC/ 2 NO, 2 NC 3
110 ... 125 V DC 4 NO, 4 NC 7
208 ... 240 V AC/ 2 NO, 2 NC 4
220 ... 250 V DC 4 NO, 4 NC 8
Closing coil and Without closing coil Without remote trip alarm A
remote trip alarm reset coil
reset coil 1)2) With closing coil Without remote trip alarm 24 ... 30 V DC B
(CC/CC-COM) 3) reset coil 48 ... 60 V DC C
for uninterrupted duty,
110 ... 127 V AC/110 ... 125 V DC D
100% OP
208 ... 240 V AC/220 ... 250 V DC E
With remote trip alarm reset 24 ... 30 V DC F
coil (RR) 48 ... 60 V DC G
for momentary duty 1% OP
110 ... 127 V AC/110 ... 125 V DC H
208 ... 240 V AC/220 ... 250 V DC J
With closing coil (CC) Without remote trip alarm 24 ... 30 V DC K
for momentary duty, reset coil 48 ... 60 V DC L
5% OP
110 ... 127 V AC/110 ... 125 V DC M
208 ... 240 V AC/220 ... 250 V DC N
With remote trip alarm reset 24 ... 30 V DC P
coil (RR) 48 ... 60 V DC Q
for momentary duty 1% OP
110 ... 127 V AC/110 ... 125 V DC R
208 ... 240 V AC/220 ... 250 V DC S
1
5 6 7 8 9 10 11 12 13 14 15 16
3WA1 – –
Auxiliary releases
1st auxiliary release Without 1st auxiliary release 0
With shunt trip (ST/ST-COM) 1), 24 ... 30 V DC 1
uninterrupted duty 100% OP 48 ... 60 V DC 2
110 ... 127 V AC/110 ... 125 V DC 3
208 ... 240 V AC/220 ... 250 V DC 4
With shunt trip (ST), 24 ... 30 V DC 5
momentary duty 5% OP 48 ... 60 V DC 6
110 ... 127 V AC/110 ... 125 V DC 7
208 ... 240 V AC/220 ... 250 V DC 8
1)
If the ready4COM feature is provided, the communication-capable closing coils (CC-COM) and/or shunt trips (ST-COM) are installed at the factory.
1
5 6 7 8 9 10 11 12 13 14 15 16
3WA1 – –
Connection SZ 1
SZ 2
SZ 3
Type of mounting Fixed-mounted ■ ■ 3) ■ Vertical 1
■ ■ 2) ■ 4) Horizontal 2
■ 1) ■ 2) ■ 5) Front double hole 3
■ 1) ■ 2) ■ 4) Vertical on top/horizontal at the bottom 5
■ 1) ■ 2) ■ 4) Horizontal on top/vertical at the bottom 6
Withdrawable ■ ■ ■ Without guide frame 0
■ ■ 3) ■ Vertical 1
■ 1) ■ 2) ■ 4) Horizontal 2
■ 1) ■ 2) ■ 5) Front double hole 3
■ 1) ■ 2) ■ 5) Flange 4
■ 1) ■ 2) ■ 4) Vertical on top/horizontal at the bottom 5
■ 1) ■ 2) ■ 4) Horizontal on top/vertical at the bottom 6
■ 1) ■ 2) ■ 5) Flange on top/horizontal at the bottom 7
■ 1) ■ 2) ■ 5) Horizontal on top/flange at the bottom 8
1)
Only ≤2000 A is available for size 1
2)
Only ≤3200 A is available for size 2
3)
Vertical connection for 3WA size 2 for 4000 A has different dimensions than for the 3WL.
With Z option D01, vertical connection can be changed to the connection compatible with 3WL.
4)
Only ≤5000 A is available for size 3
5)
Only for 4000 A is available for size 3
Closing coil and Without closing coil Without remote trip alarm reset coil A
remote trip alarm With closing coil Without remote trip alarm 24 ... 30 V DC B
reset coil 1) (CC/CC-COM) 2) reset coil 48 ... 60 V DC C
for uninterrupted duty,
110 ... 127 V AC/110 ... 125 V DC D
100% OP
208 ... 240 V AC/220 ... 250 V DC E
With remote trip alarm reset 24 ... 30 V DC F
coil (RR) 48 ... 60 V DC G
for momentary duty 1% OP
110 ... 127 V AC/110 ... 125 V DC H
208 ... 240 V AC/220 ... 250 V DC J
With closing coil (CC) Without remote trip alarm 24 ... 30 V DC K
for momentary duty, reset coil 48 ... 60 V DC L
5% OP
110 ... 127 V AC/110 ... 125 V DC M
208 ... 240 V AC/220 ... 250 V DC N
With remote trip alarm reset 24 ... 30 V DC P
coil (RR) 48 ... 60 V DC Q
for momentary duty 1% OP
110 ... 127 V AC/110 ... 125 V DC R
208 ... 240 V AC/220 ... 250 V DC S
1
5 6 7 8 9 10 11 12 13 14 15 16
3WA1 – –
Auxiliary releases
1st auxiliary release Without 1st auxiliary release 0
With shunt trip 24 ... 30 V DC 1
(ST/ST-COM) 1), 48 ... 60 V DC 2
uninterrupted duty 100% OP
110 ... 127 V AC/110 ... 125 V DC 3
208 ... 240 V AC/220 ... 250 V DC 4
With shunt trip (ST), 24 ... 30 V DC 5
momentary duty 5% OP 48 ... 60 V DC 6
110 ... 127 V AC/110 ... 125 V DC 7
208 ... 240 V AC/220 ... 250 V DC 8
1)
If the ready4COM feature is provided, the communication-capable closing coils (CC-COM) and/or shunt trips (ST-COM) are installed at the factory.
The structure shown below is intended as an overview of each position and its meaning.
For a complete and valid configuration of your air circuit breaker, please use our online configurator at
www.siemens.com/lowvoltage/3wa-configurator
1
5 6 7 8 9 10 11 12 13 14 15 16
3WA1 – –
Non-automatic circuit breakers
Size (SZ) 2 2
SZ 2
Number of poles 1)
Fixed-mounted 3-pole 0
4-pole 1
Withdrawable Without position signaling 3-pole 3
switch 4-pole 4
With position signaling switch 1) 3-pole 6
4-pole 7
Connection
SZ 2
1
5 6 7 8 9 10 11 12 13 14 15 16
3WA1 – –
Operating mechanisms, auxiliary switches and auxiliary releases
Operating Manual recharging of the Without spring charging 2 NO, 2 NC 0
mechanism and stored energy mechanism motor 4 NO, 4 NC 1
auxiliary switch Recharging of the stored 24 ... 30 V DC 2 NO, 2 NC 2
energy mechanism by 4 NO, 4 NC 5
spring charging motor 48 ... 60 V DC 4 NO, 4 NC 6
(M)
110 ... 127 V AC/ 2 NO, 2 NC 3
110 ... 125 V DC 4 NO, 4 NC 7
208 ... 240 V AC/ 2 NO, 2 NC 4
220 ... 250 V DC 4 NO, 4 NC 8
Accessory options
For a complete and valid configuration of your air circuit breaker, please use our online configurator at
www.siemens.com/lowvoltage/3wa-configurator
1 To specify the options, add "-Z" to the complete article number and Order code
indicate the appropriate order code(s).
3WA....-.....-.... -Z
Option plug for electronic trip unit
• To reduce the rated current of the circuit breaker
• Only one module is possible per circuit breaker. As standard, the electronic trip unit is equipped with an option plug which is equal to the
maximum rated breaker current ( In max ). The rated current of the selected option plug must be less than In max .
SZ 1
SZ 2
SZ 3
Rated current In
Option plug 250 A ■ ■ – B02
315 A ■ ■ – B03
400 A ■ ■ – B04
500 A ■ ■ – B05
630 A ■ ■ – B06
800 A ■ ■ ■ B08
1000 A ■ ■ ■ B10
1250 A ■ ■ ■ B12
1600 A ■ ■ ■ B16
2000 A ■ ■ ■ B20
2500 A – ■ ■ B25
3200 A – ■ ■ B32
4000 A – – ■ B40
5000 A – – ■ B50
Module with 2 inputs and 3 outputs A module including adapter for mounting on the secondary disconnect terminal system of the F23
circuit breaker, connecting cables and CubicleBUS2 terminating resistor; five modules can be
operated at the same time. Further modules must be ordered separately as 3WA9111-0EC11,
which includes the adapter for mounting on the secondary disconnect terminal system of the
circuit breaker and the adapter for external mounting on a DIN rail.
Zone-selective interlocking with ETU600 A module, circuit breaker internal. A module including adapter for mounting on the secondary F20
disconnect terminal system of the circuit breaker, connecting cables and CubicleBUS2 terminating
resistor
• The precondition for connection is a circuit breaker or non-automatic circuit breaker with the "ready4COM" feature
Modbus RTU A module with terminal connection and optional internal terminating resistor, circuit breaker F15
internal. A module including adapter for mounting on the secondary disconnect terminal system
of the circuit breaker, connecting cables and CubicleBUS2 terminating resistor; two communi
cations modules can be run at the same time. The second communications module must be
ordered separately as 3WA9111-0EC15.
Automatic reset
• Only possible for circuit breakers with an electronic trip unit
Automatic reset Automatic reset of the reclosing lockout after ETU tripping; this option is not required when K01
ordering a circuit breaker with a remote trip alarm reset coil RR.
1)
When ordering this option for a circuit breaker or a non-automatic air circuit breaker of the installation type "withdrawable version without guide frame",
this must be used as the order option for the guide frame.
2)
For connecting the Ethernet cable, connectors angled 90° to the right are recommended, e.g. PROFINET connector 6GK1901-1BB20-2AA0.
3)
Available in Q1/2023
To specify the options, add "-Z" to the complete article number and
1
Order code
indicate the appropriate order code(s).
3WA....-.....-.... -Z
Tinned version of the main circuit connections on the guide frame
• Only for withdrawable circuit breakers with horizontal connection or flange connection
• Cannot be ordered for circuit breakers without a guide frame
• The normal delivery time increases to 15 work days
Tinned connections Sizes 1, 2, 3 D08
Circuit breakers In this version of the circuit breaker, Bluetooth is not provided. Neither can Bluetooth be retrofitted D80
without Bluetooth function by replacing the electronic trip unit.
Signaling switches
Trip alarm switch 2nd trip alarm switch (S25) 1 NO K06
1st trip alarm switch included as standard for circuit breakers.
Can only be used with circuit breakers with an electronic trip unit
without ready4COM.
Local electric close on operator panel This prevents unauthorized electrical closing from With sealing cap C11
(S10) the operator panel. Mechanical closing and remote With CES lock C12
closing remain possible. Only possible in
combination with a closing coil (CC)
Motor disconnect switch on operator This prevents automatic charging of the stored C24
panel (S12) energy mechanism by the spring charging motor
Cardboard packaging with water-repellent coating on corrugated cardboard (moisture protection) P61
Arc chute cover mounted on the guide Not available for: R10
frame − Fixed-mounted
− Breaking capacity C, E and D
− 4000 A size 2
Sealable and lockable covers For electronic trip unit F40
Internal current sensors (without energy core) for applications with frequency converters
• Used in converter applications with high harmonic components; can only be used for circuit breakers with an electronic trip unit
− External 24 V DC supply required
− Undervoltage release required
− Additionally contains a relay for monitoring the 24 V DC and warning labels
− If option Z=K60 is provided, an optional measurement function PMF-I to PMF-III according to IEC 61557-12 is not technically
feasible.
Internal current sensors Sizes 2, 3 K60
1)
Available in Q1/2023
Accessory options
For a complete and valid configuration of your air circuit breaker, please use our online configurator at
www.siemens.com/lowvoltage/3wa-configurator
1 To specify the options, add "-Z" to the complete article number and Order code
indicate the appropriate order code(s).
3WA....-.....-.... -Z
Mechanical interlocks
• Interlocking module with Bowden cable 2 m
Mechanical interlocks For fixed-mounted breakers S55
For withdrawable circuit breakers with guide frame R55
For guide frames (ordered separately) R56
For withdrawable circuit breakers (ordered separately) R57
Locking mechanisms
• R30 and R50 not possible in combination with order code "R81", "R85" or "R86".
• R30 and R50 only possible on complete order for a circuit breaker with a guide frame or when ordering the guide frame separately
• R40 can only be ordered with the circuit breaker
For fixed-mounted circuit breakers To prevent opening of the control cabinet door in ON position S30
For withdrawable circuit breakers To prevent opening of the control cabinet door in connected position R30
To prevent activation when the control cabinet door is open 3) R40
To prevent movement when the control cabinet door is open 4) R50
Accessory options
Further technical specifications
1 30 V DC
48 V DC
60 V DC
110 … 127 V AC/110 … 125 V DC
208 … 240 V AC/220 … 250 V DC
380 … 415 V AC
Primary operating range
Operating limits Operate voltage <70% Us
Pick-up voltage 85 … 110% Us
Integrated freewheeling diode Yes
Operation
Closing power AC/DC 50 VA/50 W
Continuous power AC/DC 5 VA/5 W
Break time
Us = 0 with UVR instantaneous ≤80 ms
Us = 0 with UVR short-time delayed ≤200 ms
Us = 0 with UVR-t delayed 0.2 … 3.2 s
With UVR-t by disconnection at terminals X5.13 and X5.14 (EMERGENCY-STOP circuit) ≤100 ms
Fuse protection of the control circuit
Smallest permissible DIAZED fuse, gL, slow-response 24 V, 30 V, 48 V, 60 V DC 2A
110 … 127 V AC/110 … 125 V DC 1A
208 … 240 V AC/220 … 250 V DC
380 … 415 V AC
Automatic circuit breaker with C characteristic 24 V, 30 V, 48 V, 60 V DC 2A
110 … 127 V AC/110 … 125 V DC 1A
208 … 240 V AC/220 … 250 V DC
380 … 415 V AC
Remote reset magnet for mechanical tripped indicator (F7) 3WA11 – 3WA13
Rated operational voltage
Rated control supply voltage Us 24 … 30 V DC
48 … 60 V DC 1
110 … 125 V DC/110 … 127 V AC
220 … 250 V DC/208 … 240 V AC
Primary operating range
Primary operating range (acc. to IEC 60947-2) 85 … 110% Us
Extended operating range for battery operation 70 … 126% Us
Integrated freewheeling diode Yes
Operation
Power consumption AC/DC 60 VA/60 W
Minimum command time at 1 × Us 60 ms
Fuse protection of the control circuit
Smallest permissible DIAZED fuse, gL 24 … 60 V DC 2 A TDz (slow)
100 V AC/> 100 V DC 1 A TDz (slow)
Automatic circuit breaker with C characteristic 24 … 60 V DC 2A
100 V AC/> 100 V DC 1A
Type NO or NC
Contact reliability From 1 mA at 5 V DC
Rated insulation voltage Ui 500 V DC/500 V AC 50/60 Hz
Rated impulse withstand voltage Uimp 4 kV
Fuse protection of the control circuit
Largest permissible DIAZED fuse (operational class gL) 8 A TDz (slow)
Automatic circuit breaker with C characteristic 8A
Breaking capacity
Rated operational current Ie DC12 24 V 10 A
30 V 4A
48 V 2,5 A
60 V 1A
110 V 0.4 A
220/240 V 0.2 A
DC13 24 V 3A
30 V 2.5 A
48 V 1A
60 V 0.4 A
110 V 0.2 A
220/240 V 0.1 A
AC12 ≤ 440 V 10 A
AC13 < 220 V 8A
220 … 240 V 4A
320 … 440 V 3A
Accessory options
Further technical specifications
Ready-to-close signaling switches (S20) (acc. to DIN VDE 0630) 3WA11 – 3WA13
Type NO contact
The structure shown below is intended as an overview of each position and its meaning.
For a complete and valid configuration of your guide frame, please use our online configurator at
www.siemens.com/lowvoltage/3wa-configurator
5 6 7 8 9 10 11 12 13 14 15 16
1
3WA8 – A A
–
Guide frames
Size 1 1
2 2
3 3
SZ 1
SZ 2
SZ 3
Short-circuit At N ■ – – 55/42 kA 2
breaking 500/690 V S ■ ■ – 66/50 kA 3
capacity Icu M ■ ■ – 85/66 kA 4
(Generate the selection H – ■ ■ 100/85 kA 5
of positions 6, 7 and 8
according to the list
C – ■ – 130/100 kA 6
below) – – ■ 3-pole: 150/150 kA 6
4-pole: 130/130 kA
At E ■ – – 80/50 kA/– 8
690/1000/1150 V – ■ – 85/85/50 kA 8
– – ■ 3-pole: 8
150/125/70 kA
4-pole:
130/125/70 kA
Main connection ■ ■ 5)
■ Vertical 1
■ 1) ■ 2) ■ 3) Horizontal 2
■ 1) ■ 2) ■ 4) Front double hole 3
■ 1) ■ 2) ■ 4) Flange 4
■ 1) ■ 2) ■ 3) Vertical on top/horizontal at the bottom 5
■ 1) ■ 2) ■ 3) Horizontal on top/vertical at the bottom 6
■ 1) ■ 2) ■ 4) Flange on top/horizontal at the bottom 7
■ 1) ■ 2) ■ 4) Horizontal on top/flange at the bottom 8
1)
Only ≤2000 A is available for size 1 Vertical connection for 3WA size 2 for 4000 A has different dimensions than for the 3WL. With Z option D01,
5)
2)
Only ≤3200 A is available for size 2 vertical connection can be changed to the connection compatible with 3WL.
3)
Only ≤5000 A is available for size 3
4)
Only for 4000 A is available for size 3
The following combinations of positions 6, 7 and 8 of the article number are technically feasible
Size Breaking capacity at In max 630 A 800 A 1000 A 1250 A 1600 A 2000 A 2500 A 3200 A 4000 A 5000 A 6300 A
Representation 6, 7, 8
1 N 10-2 10-2 10-2 16-2 16-2 20-3 25-3 – – – –
S 10-3 10-3 10-3 16-3 16-3 20-3 25-3 – – – –
M 20-4 20-4 20-4 20-4 20-4 20-4 25-4 – – – –
E 20-8 20-8 20-8 20-8 20-8 20-8 25-8 – – – –
2 S – – – – – 20-5 25-5 32-5 40-5 – –
M – – – – – 20-5 25-5 32-5 40-5 – –
H – – – – – 20-5 25-5 32-5 40-5 – –
E – – – – – 20-8 25-8 32-8 40-8 – –
C – – – – – 32-6 32-6 32-6 – – –
3 H – – – – – – – – 40-5 50-5 63-5
E – – – – – – – – 50-8 50-8 63-8
C – – – – – – – – 50-8 50-8 63-8
The structure shown below is intended as an overview of each position and its meaning.
For a complete and valid configuration of your guide frame, please use our online configurator at
www.siemens.com/lowvoltage/3wa-configurator
1 5 6 7 8 9 10 11 12 13 14 15 16
3WA8 – – 1 1
The structure shown below is intended as an overview of each position and its meaning.
For a complete and valid configuration of your guide frame, please use our online configurator at
www.siemens.com/lowvoltage/3wa-configurator
5 6 7 8 9 10 11 12 13 14 15 16
1
3WA8 – A U
– 1 1
Guide frames
Size (SZ) 2 2
Option plug
Basic configuration Rated current In SZ 1 SZ 2 SZ 3 Article No.
Protective function LSI: LT, ST, INST 3WA9111-0EB ..
Protective function LSIG: LT, ST, INST, GF 3WA9111-0EX ..
(ground-fault protection GFx with extended setting range)
250 A ■ ■ – 02
315 A ■ ■ – 03
400 A ■ ■ – 04
500 A ■ ■ – 05
630 A ■ ■ – 06
800 A ■ ■ ■ 08
1000 A ■ ■ ■ 10
1250 A ■ ■ ■ 12
1600 A ■ ■ ■ 16
2000 A ■ ■ ■ 20
2500 A ■ ■ ■ 25
3200 A – ■ ■ 32
4000 A – ■ ■ 40
5000 A – – ■ 50
6300 A – – ■ 63
Function packages for ETU600
Protective and alarm functions Article No.
Ground fault alarm (GF alarm) 3WA9111-0ES01
Directional short-time-delayed short-circuit protection (dST) and reverse power protection (RP) 3WA9111-0ES05
(requires an optional voltage tap module)
Enhanced protective functions (EPF) Article No.
Full package with unbalance, voltage, active power, frequency, THD and phase sequence detection 3WA9111-0ES11
Phase unbalance current and phase unbalance voltage 3WA9111-0ES12
Undervoltage and overvoltage 3WA9111-0ES13
Active power import and active power export 3WA9111-0ES14
Underfrequency and overfrequency 3WA9111-0ES15
Total harmonic distortion for current and voltage 3WA9111-0ES16
Phase sequence detection 3WA9111-0ES17
Functional expansions Article No.
Second protection parameter set 3WA9111-0ES21
Waveform memory 1) 3WA9111-0ES24 new
Extended measurement function Article No.
Upgrade to measurement function PMF-II Basic Power Monitoring 3WA9111-0ES52
(metering values, see catalog page 1/25)
Upgrade to measurement function PMF-III Advanced Power Monitoring 3WA9111-0ES53
(metering values, see catalog page 1/25)
BSS200 breaker status sensor for ETU600 new 1)
Version Article No.
• Gathers information about the statuses of the circuit breaker via signaling switches and 3WA9111-0EC40
transmits it to the CubicleBUS2
• Controls the communication-capable CC-COM closing coil and the ST-COM shunt trip in a
circuit breaker with the ready4COM feature
• The BSS200 breaker status sensor is fitted in every circuit breaker with ETU600
of the ready4COM application package and with the PMF-I to PMF-III measurement functions
1)
Available in Q1/2023
Locking mechanisms to prevent movement when the control cabinet door is open
• Mounted on guide frame
• Note: Not possible in combination with "Locking mechanisms to prevent movement of the
withdrawable circuit breakers in the disconnected position" (order codes "R81", "R82", "R85" or "R86").
Version Article No.
Spare part for option R50 3WA9111-0BB15
Mechanical interlocks
• With Bowden cable 2000 mm (one required for each circuit breaker)
Type Circuit breaker and guide frame when Spare part for Article No.
ordered separately
Fixed-mounted circuit breaker – Option S55 3WA9111-0BB21
Module for withdrawable circuit – Option R55 3WA9111-0BB22
breakers with guide frame
Module for guide frame ✓ Option R56 3WA9111-0BB23
Module for withdrawable circuit ✓ Option R57 3WA9111-0BB24
breaker
Adapter for size 3 withdrawable ✓ – 3WA9111-0BB25
circuit breaker
Coupling on the circuit breaker for mutual interlocking with Bowden cable
• Can be used in all circuit breakers
Article No.
3WA9111-0BB31
Auxiliary releases
Closing coil (CC)/shunt trip (ST)
• Suitable for uninterrupted duty
Version Voltage Article No.
100% OP 24 … 30 V DC 3WA9111-0AD02
Switching time ≦80 ms 48 … 60 V DC 3WA9111-0AD04
110 ... 125 V DC/110 ... 127 V AC 3WA9111-0AD05
220 ... 250 V DC/208 ... 240 V AC 3WA9111-0AD06
Closing coil (CC-COM)/shunt trip (ST-COM)
• Suitable for uninterrupted duty
Version Voltage Article No.
For circuit breakers and 24 … 30 V DC 3WA9111-0AD32
non-automatic circuit breakers 48 … 60 V DC 3WA9111-0AD34
with the "ready4com" feature
110 ... 125 V DC/110 ... 127 V AC 3WA9111-0AD35
100% OP
Switching time ≦80 ms 220 ... 250 V DC/208 ... 240 V AC 3WA9111-0AD36
Switching time via COM ≦120 ms
Auxiliary release
Closing coils (CC)
• For momentary duty, with cut-off switch S15 (NC)
1 Version Voltage Article No.
5% OP 24 … 30 V DC 3WA9111-0AD12
Switching time 50 ms 48 … 60 V DC 3WA9111-0AD14
110 ... 125 V DC/110 ... 127 V AC 3WA9111-0AD15
220 ... 250 V DC/208 ... 240 V AC 3WA9111-0AD16
Shunt trips (ST)
• For momentary duty, with cut-off switch S14 (NO)
Version Voltage Article No.
5% OP 24 … 30 V DC 3WA9111-0AD22
Switching time 50 ms 48 … 60 V DC 3WA9111-0AD24
110 ... 125 V DC/110 ... 127 V AC 3WA9111-0AD25
220 ... 250 V DC/208 ... 240 V AC 3WA9111-0AD26
Capacitor trip device
• For shunt trips
• Storage time 5 min
• Also suitable for 3VL, 3VA, 3WL and 3WN circuit breakers
• Note: Rated control supply voltage must match the rated control supply voltage of the shunt trips.
Rated control supply voltage/rated operational voltage Article No.
50/60 Hz AC DC
220 … 240 V 220 … 250 V 3WA9111-0AD81
Undervoltage release (UVR)
Version Voltage Article No.
Instantaneous ≤0.08 s (UVR) and 24 V DC 3WA9111-0AE02
short-time delayed ≤0.2 s 30 V DC 3WL9111-0AE02-0AA0
48 V DC 3WA9111-0AE04
60 V DC 3WL9111-0AE07-0AA0
110 ... 125 V DC/110 ... 127 V AC 3WA9111-0AE05
220 ... 250 V DC/208 ... 240 V AC 3WA9111-0AE06
380 … 415 V AC 3WA9111-0AE07
Delayed (UVR-t), 48 V DC 3WA9111-0AE13
adjustable delay 0.2 … 3.2 s 60 V DC 3WA9111-0AE14
110 ... 125 V DC/110 ... 127 V AC 3WA9111-0AE15
220 ... 250 V DC/208 ... 240 V AC 3WA9111-0AE16
380 … 415 V AC 3WA9111-0AE17
Operating mechanism
Spring charging motor to charge the stored energy mechanism
Voltage Article No.
24 … 30 V DC 3WA9111-0AF02
48 … 60 V DC 3WA9111-0AF04
110 ... 125 V DC/110 ... 127 V AC 3WA9111-0AF05
220 ... 250 V DC/208 ... 240 V AC 3WA9111-0AF06
Auxiliary contacts
Auxiliary switches (AUX)
Contacts Article No.
2 NO + 2 NC 3WA9111-0AG01
2 NO 3WA9111-0AG02
1 NO + 1 NC 3WA9111-0AG03
Grounding connection
Grounding connection between the guide frame and the circuit breaker
• Up to 30 kA or 60 kA ground-fault current
1 • 2 modules must be used for up to 60 kA ground-fault current
Contact module Size Number of poles Article No.
For guide frames 1, 2 1) 3WA9111-0BG01
3 3WA9111-0BG02
For withdrawable circuit breakers 1 3-pole 3WA9111-0BG11
4-pole 3WA9111-0BG21
2 3-pole 1) 3WA9111-0BG12
4-pole 1) 3WA9111-0BG22
3 3-pole 2) 3WA9111-0BG13
4-pole 2) 3WA9111-0BG23
1)
Cannot be used for size 2 with breaking capacity C and size 2, 4000 A.
2)
Not for breaking capacity E
Support bracket
Support bracket
• For mounting fixed-mounted circuit breakers on vertical plane
• Only for sizes 1 and 2 (1 set = 2 units)
Article No.
3WA9111-0BB50
Adapters
Version Article No.
For mounting the modules of the CubicleBUS2 on the secondary disconnect terminal system of the 3WA9111-0EC60
circuit breaker
For mounting the modules of the CubicleBUS2 on DIN rail 3WA9111-0EC61
1)
For connecting the Ethernet cable, connectors angled 90° to the right are recommended, e.g. PROFINET connector 6GK1901-1BB20-2AA0.
2)
Available in Q1/2023
Connecting flange
Size Breaking capacity | Rated current In Article No.
1 N, S | ≤ 1000 A AC 3WA9111-0AW11
N, S | 1250 … 2000 A AC; M, E | ≤ 2000 A AC 3WA9111-0AW12
2 S, M, H, E | 2000 A AC; D, E | ≤ 2000 A DC 3WA9111-0AW21
S, M, H, E | 2500 A AC 3WA9111-0AW22
S, M, H, E | 3200 A AC; D, E | 4000 A DC 3WA9111-0AW23
3 H | 4000 A AC 3WA9111-0AW31
1)
When using front-accessible main connections (withdrawable circuit breakers) supports are required
2)
Not for circuit breakers with very high breaking capacity C
Conversion kit
Conversion kit for converting fixed-mounted circuit breakers into withdrawable circuit breakers
• Guide frames and sliding contact modules must be ordered separately
• Conversion from fixed-mounted to withdrawable circuit breakers is not possible for 3WA circuit
breakers with breaking capacity C and breaking capacity E 1
Number of poles Size Article No.
3-pole 1 3WA9111-0BC11
2 3WA9111-0BC12
3 3WA9111-0BC13
4-pole 1 3WA9111-0BC14
2 3WA9111-0BC15
3 3WA9111-0BC16
3WL10 3WL11
Basic data
Rated operational voltage Ue V ≤690 ≤1000
Rated current In A 630 … 1250 630 … 2000
Size 0 1
Type of mounting Withdrawable Fixed-mounted Withdrawable Fixed-mounted
Number of poles 3/4-pole 3/4-pole 3/4-pole 3/4-pole
Dimensions
Width (3-pole | 4-pole) mm 278 | 348 210 | 280 320 | 410 320 | 410
Height (standard | A05, A15, A16, DC greater than 600 V) mm 363.5 296 468 | 518 462
Depth mm 271 183 471 357
Approvals
General product approvals VDE, EAC, CCC, CE, C-Tick VDE, EAC, CCC, CE, C-Tick
Marine/shipbuilding RMRS ABS, DNV, LR, BV, GL, PRS, RMRS
Breaking capacity B N S N S H
Rated short-circuit breaking capacity
Rated operational voltage Ue up to 415 V AC Icu | Ics kA 42 | 42 55 | 50 66 | 50 55 | 55 66 | 66 85 | 85
Rated operational voltage Ue up to 500 V AC Icu | Ics kA 42 | 42 50 | 50 50 | 50 55 | 55 66 | 66 85 | 85
Rated operational voltage Ue up to 690 V AC Icu | Ics kA – | – 42 | 42 50 | 50 42 | 42 50 | 50 66 | 66
Rated operational voltage Ue up to 690 V AC +20% 6), with Z option: A16 Icu | Ics kA – | – – | – – | – – | – – | – 50 | 50
Rated operational voltage Ue up to 1000 V AC, with Z option: A05 Icu | Ics kA – | – – | – – | – – | – – | – 50 | 50
Rated operational voltage Ue up to 1150 V AC, with Z option: A15 Icu | Ics kA – | – – | – – | – – | – – | – – | –
Rated short-time withstand current Icw 5)
Rated short-time withstand current Icw at Ue up to 500 V AC 0.5 s kA – – – 55 66 85
1s kA 42 42 50 50 66 85
2s kA – – – 35 1)/45 2) 45 70
3s kA 24 24 36 35 1)/45 2) 35 60
Rated short-time withstand current Icw at Ue up to 690 V AC 0.5 s kA – – – 42 50 66
1s kA 42 42 50 42 50 66
2s kA – – – 35 1)/42 2) 45 66
3s kA 24 24 36 30 1)/45 2) 35 60
Rated short-time withstand current Icw at DC 1s kA – – – – – –
Rated conditional short-circuit current Icc of the non-automatic air circuit breakers
Up to 500 V AC kA – 42 50 55 66 85
Up to 690 V AC kA – 42 50 42 50 66
Up to 1000 V/1150 V AC, with Z option: A05 kA – – – – – 50 /–
Up to 1000 V/1150 V AC, with Z option: A15 kA – – – – – –
Up to 220 V DC kA – – – – – –
Up to 300 V DC kA – – – – – –
Up to 600 V DC kA – – – – – –
Up to 1000 V DC kA – – – – – –
Rated short-circuit making capacity Icm
Icm at 415 V AC kA 88 121 145 121 145 187
Icm at 500 V AC kA 88 105 105 121 145 187
Icm at 690 V AC kA – 88 105 88 105 145
Icm at 1000 V AC kA – – – – – 105
Icm at 1150 V AC kA – – – – – –
1)
Size 1 with In max ≤1250 A 3)
Size 2 with In max ≤ 2500 A
2)
Size 1 with In max ≥1600 A 4)
Size 2 with In max ≥3200 A At rated operational voltage Ue ≥690 V, the Icw value of the circuit breaker corresponds to the Icu or Icsvalue
5)
AC DC
1
VDE, EAC, CCC, CE, C-Tick VDE, EAC, CCC, VDE, CE, C-Tick VDE, EAC, CCC, CE, C-Tick VDE, EAC, CCC, CE, C-Tick
ABS, DNV, LR, BV, GL, PRS, RMRS ABS, DNV, LR, BV, GL, PRS, RMRS ABS, DNV, LR, BV, GL, PRS, RMRS ABS, DNV, LR, BV, GL, PRS, RMRS
N S H C 7) H C 3p C 4p DC DC
I201_19679
NSE0_00061a NSE0_00062a
1600 A 2000 A 800 A 1000 A 1250 A 1600 A 2000 A 2500 A 3200 A 4000 A 4000 A 5000 A 6300 A
= 1 mm
= 1 mm
30° 30° 30° 30°
Dhmax.
Dhmax.
Dhmax.
30° 30° 30° 30°
NSE0_00927
NSE0_00927
NSE0_00927
NSE0_00061a NSE0_00062a NSE0_00061a NSE0_00062a
IP20 without cabinet IP20 without cabinet door, IP20 without cabinet door,
door, IP41 with door IP41 with door sealing frame, IP41 with door sealing frame,
sealing frame, IP55 with cover IP55 with cover
IP55 with cover
1600 2000 800 1000 1250 1600 2000 2500 3200 3950 4000 5000 5920
1600 1930 800 1000 1250 1600 2000 2500 3020 3810 4000 5000 5810
1490 8) 1780 8) 800 8) 1000 8) 1250 8) 1600 8) 2000 8) 2280 8) 2870 8) 3600 8) 4000 8) 5000 8) 5500 8)
35 35 35
38 34 34
80 100 100
73 73 73
≤80 ≤80 ≤80
50 50 50
15000 15000 10000 10000 10000 10000 10000 10000 10000 10000 – – –
25000 25000 17500 17500 17500 17500 17500 17500 17500 17500 – – –
– – – – – – – – – – – – –
10000 7500 7500 7500 7500 7500 7500 7500 4000 2000 – – –
25000 25000 17500 17500 17500 17500 17500 17500 17500 17500 – – –
10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 5000 5000 5000
15000 15000 15000 15000 15000 15000 15000 15000 15000 15000 10000 10000 10000
7500 7500 7500 7500 7500 7500 7500 7500 4000 2000 2000 2000 2000
1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
– – 500 500 500 500 500 500 500 500 500 500 500
15000 15000 15000 15000 15000 15000 15000 15000 15000 15000 10000 10000 10000
7)
Periodic greasing of breaker mechanism on the 3WL10 9)
Motorized operating mechanisms Uimp=1.2 kV
(see Manual), no spare part of components 10)
For 3WL size 2 4000 A and size 3 6300 A with rear vertical main
8)
Cu painted black connections.
1600 A 2000 A 800 A 1000 A 1250 A 1600 A 2000 A 2500 A 3200 A 4000 A 4000 A 5000 A 6300 A
10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 5000 5000 5000
15000 15000 15000 15000 15000 15000 15000 15000 15000 15000 10000 10000 10000
7500 7500 7500 7500 7500 7500 7500 7500 4000 2000 2000 2000 2000
1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
– – 500 500 500 500 500 500 500 500 500 500 500
10000 10000 15000 15000 15000 15000 15000 15000 15000 15000 10000 10000 10000
– – 5000 5000 5000 5000 5000 5000 5000 – 5000 5000 5000
– – 10000 10000 10000 10000 10000 10000 10000 – 10000 10000 10000
– – 5000 5000 5000 5000 5000 5000 4000 – 1000 1000 1000
– – 10000 10000 10000 10000 10000 10000 8000 – – – –
– 20/20 60/60 9) 60/60 9) 60/60 9) 60/60 9) 60/60 9) 60/60 9) 60/60 9) 60/60 9) 60/60 9) 60/60 9) 60/60 9)
– – 20/20 20/20 20/20 20/20 20/20 20/20 20/20 20/20 20/20 20/20 20/20
2× 50 × 10 3× 50 × 10 1× 50 × 10 1× 60 × 10 2× 40 × 10 2× 50 × 10 3× 50 × 10 2× 100 × 10 3× 100 × 10 4× 120 × 10 4× 100 × 10 6× 100 × 10 6× 120 × 10
2× 50 × 10 3× 50 × 10 1× 50 × 10 1× 60 × 10 2× 40 × 10 2× 50 × 10 3× 50 × 10 2× 100 × 10 3× 100 × 10 4× 100 × 10 4× 100 × 10 6× 100 × 10 6× 120 × 10
43 43 56 56 56 56 56 59 64 85 82 82 90
45 45 60 60 60 60 60 63 68 121 88 88 96
25 25 31 31 31 31 31 39 45 52 60 60 70
50 50 67 67 67 67 67 71 77 103 99 99 108
54 54 72 72 72 72 72 76 82 146 106 106 108
30 30 37 37 37 37 37 47 54 62 84 84 119
3WL11 3WL12
1
Rated current In 2000 A 1000 A 2000 A 4000 A
General data
Size 1 2
Isolating function acc. to EN 60947-2 Yes Yes
Utilization category B B
Permissible ambient temperature Operation °C –40 … +70 –40 … +70
Storage °C –40 … +80 –40 … +80
Mounting position 30° 30° 30° 30° 30° 30° 30° 30°
= 1 mm
= 1 mm
Dhmax.
Dhmax.
NSE0_00927
NSE0_00927
NSE0_00061a NSE0_00062a NSE0_00061a NSE0_00062a
Degree of protection IP20 without cabinet door, IP20 without cabinet door,
IP41 with door sealing frame, IP41 with door sealing frame,
IP55 with cover IP55 with cover
Voltage
Rated operational voltage Ue at 1000 V version V DC 1000 600/1000
50/60 Hz
Rated insulation voltage Ui V DC 1000 1000
Rated impulse withstand voltage Main conducting paths kV 12 12
Uimp Auxiliary circuits kV 4 4
Control circuits kV 2.5 2.5
Permissible load
At rear horizontal main connections Up to 40 °C (Cu black painted) A 2000 1000 2000 4000
Up to 55 °C (Cu black painted) A 1910 1000 2000 3640
Up to 60 °C (Cu black painted) A 1850 1000 2000 3500
Up to 70 °C (Cu black painted) A 1710 1000 1950 3250
Power loss at In
With symmetrical load Withdrawable circuit breaker W 150 280 770 1640
Switching times
Make time ms 35 35
Opening time ms 38 34
Electrical make time (through activation solenoid) 1) ms 100 100
Electrical opening time (through shunt trip) ms 73 73
Electrical opening time (instantaneous undervoltage release) ms ≤80 ≤80
Service life/endurance 3)
Mechanical Without maintenance Operating 10000 10000 10000 10000
cycles
With maintenance 2) Operating 15000 17500 17500 17500
cycles
Electrical Without maintenance Operating 1000 6000 6000 4000
cycles
Without maintenance 1000 V Operating 1000 1000 1000 1000
cycles
With maintenance 2) Operating 2000 17500 17500 17500
cycles
1)
Make time through activation solenoid for synchronization purposes 3)
Further technical specifications on request. 6)
At Ue = 600 V DC
(short-time excited) 50 ms. 4)
At Ue = 220 V DC 7)
At Ue = 1000 V DC
2)
Maintenance means: Replace main contact elements and arc chutes 5)
At Ue = 300 V DC
(see Operating Manual).
3WL11 3WL12
1
Rated current In 2000 A 1000 A 2000 A 4000 A
Short-circuit breaking capacity Icc
Up to 220 V DC kA 20 35
Up to 300 V DC kA 20 30
Up to 600 V DC kA 20 25
Up to 1000 V DC kA 20 20
Rated short-time withstand current Icw
0.5 s kA – –
1s kA 20 35 4)/30 5)/25 6)/20 7)
2s kA – –
3s kA – –
Switching frequency
690 V version 1/h – 60 60 60
1000 V version 1/h 20 20 20 20
Connection
Auxiliary conductor (Cu) max. number of auxiliary conductors × cross-section (solid/stranded)
Standard connection Without end sleeve 2× 0.5 … 2× 1.5 mm2 2× 0.5 … 2× 1.5 mm2
= strain-relief clamp (AWG 20 … 16); (AWG 20 … 16);
1× 2.5 mm2 (AWG 14) 1× 2.5 mm2 (AWG 14)
With end sleeve acc. to DIN 46228 Part 2 1× 0.5 … 1× 1.5 mm2 1× 0.5 … 1× 1.5 mm2
(AWG 20 … 16) (AWG 20 … 16)
With twin end sleeve 2× 0.5 … 2× 1.5 mm2 2× 0.5 … 2× 1.5 mm2
(AWG 20 … 16) (AWG 20 … 16)
Optional connection Without end sleeve 2× 0.5 … 2× 2.5 mm2 2× 0.5 … 2× 2.5 mm2
= tension spring (AWG 20 … 14) (AWG 20 … 14)
With end sleeve acc. to DIN 46228 Part 2 2× 0.5 … 2× 1.5 mm2 2× 0.5 … 2× 1.5 mm2
(AWG 20 … 16) (AWG 20 … 16)
Weights
3-pole Fixed-mounted circuit breaker kg 43 56 56 64
Withdrawable circuit breaker kg – 60 60 68
Guide frames kg – 31 31 45
4-pole Fixed-mounted circuit breaker kg 50 67 67 77
Withdrawable circuit breaker kg – 72 72 82
Guide frames kg – 37 37 54
The connection to the non-automatic circuit breakers is not dependent on direction and polarity; the circuit diagrams can be
adapted accordingly. If the parallel or series connections are made directly to the connection bars, for thermal reasons the
continuous load on the non-automatic circuit breakers must only be 80% of the permissible operational current. If the parallel or
1 series connection is made at a distance of 1 m from the connection bars, the non-automatic circuit breaker can be used at full
operational current load.
NSS0_00539
I201_20318
I201_20306
I201_20319
Grounded system 2) Grounded system 3)
Rated operational voltage up to 600 V
I201_20263
I201_20314
I201_20315
I201_20311
Grounded system Grounded system 2)
Rated operational voltage up to 1000 V 4)
I201_20264
NSS0_00595
I201_20316
I201_20317
Grounded system Grounded system Grounded system
Size 1
Required contact gaps at rated voltage 1) For 4-pole non-automatic circuit breakers
2-pole
Rated operational voltage up to 1000 V 4) Nicht geerdetes Netz Geerdetes Netz
+ (-) - (+) + (-) - (+)
Erdung
Last Last
pYWYZZ`^Y
3WL10
S Short-time-delayed short-circuit Setting range of operating value Isd = In × … – 1 | 1.5 | 2 | 2.5 | 3 | 4 | 1 | 1.5 | 2 | 2.5 | 3 | 4 | 6
protection (ST tripping) 6 | 8 | 10 | Default OFF | 8 | 10 | Default OFF
Setting range of the delay time tsd at I2t – 0.1 | 0.2 | 0.3 | 0.4 | 0.1 | 0.2 | 0.3 | 0.4 | 0.5
0.5 | (Ref. 10× In) | (Ref. 10× In)
Setting range of the delay time tsd (t = const.) – 0.08 | 0.15 | 0.22 | 0.3 0.08 | 0.15 | 0.22 | 0.3 |
| 0.4 s 0.4 s
ZSI function – – –
I Instantaneous short-circuit protection Setting range II = In × … OFF | 1.5 | 2 | 3 | 4 | 6 | OFF | 1.5 | 2 | 3 | 4 | 6 | OFF | 1.5 | 2 | 3 | 4 | 6 |
(INST tripping) 8 | 10 | 12 | 15 8 | 10 | 12 | 15 8 | 10 | 12 | 15
N Neutral conductor protection N conductor setting range IN = In × … OFF | 50% | 100% | OFF | 50% | 100% | OFF | 50% | 100% |
200% 200% 200%
G Ground-fault tripping (GF tripping) Tripping function can be switched on/off – – ■
Detection of ground-fault current Alarm function can be switched on/off – – Permanently
through summation current formation switched on
with internal or external neutral
Detection of ground-fault current through – – –
conductor transformer
external current transformer
Setting range of the operating current – – 0.1 | 0.2 | 0.3 | 0.4 | 0.5 |
Ig = In × … 0.6 | 0.7 | 0.8 | 1
ETU650 (LSI) ETU660 (LSIG) ETU15B (LI) ETU25B (LSI) ETU27B (LSIG) ETU45B (LSIG) ETU76B (LSIG)
0.4 … 1 | Default 1 0.4 … 1 | Default 1 0.5 | 0.55 | 0.6 | 0.65 | 0.4 | 0.45 | 0.5 | 0.55 | 0.4 | 0.45 | 0.5 | 0.55 | 0.4 | 0.45 | 0.5 | 0.55 | 0.4 … 1
(in steps of 0.001) (in steps of 0.001) 0.7 | 0.75 | 0.8 | 0.85 | 0.6 | 0.65 | 0.7 | 0.8 | 0.6 | 0.65 | 0.7 | 0.8 | 0.6 | 0.65 | 0.7 | 0.8 |
0.9 | 1 0.9 | 1 0.9 | 1 0.9 | 1
■ ■ – – – ■ ■
– Alternative Rc or G-ret – – – ■ ■
ground-fault
monitoring
– 0.1 … 1 | – – A 1) (100/400 A) | A 1) (100/400 A) | SZ 1, 2: 100 … 1200 A
(in steps of 0.001) B 1) (300/600 A); B 1) (300/600 A); SZ 3: 400 … 1200 A
Ig = In × … C 1) (600/800 A) | C 1) (600/800 A) |
D 1) (900/ 1000 A); D 1) (900/ 1000 A);
E 1) (1200/1200 A) E 1) (1200/1200 A)
– 50% … 90% × Ir | – – – A 1) (100/400 A); SZ 1, 2: 100 … 1200 A
(in steps of 1%) B 1) (300/600 A); SZ 3: 400 … 1200 A
PreAlarm C 1) (600/800 A);
D 1) (900/ 1000 A);
E 1) (1200/1200 A)
– 0.1 … 1 s | Default 0.1 s | – – 100 | 200 | 300 | 400 | 100 | 200 | 300 | 400 | 100 … 500 ms
(in steps of 0.05 s) 500 ms 500 ms
– t = const./I2t | – – – ■ ■
Default const.
– 0.1 … 1 s | – – – 100 | 200 | 300 | 400 | 100 … 500 ms
(in steps of 0.05 s) 500 ms
(Ref. 2× In)
3WL10
Increment size when settings are made for the ETU76B using the menu
From ... to Increment size
0…1 0.1
1 … 100 1
100 … 500 5
500 … 1000 10
1000 … 1600 50
1600 … 10000 100
10000 … max. 1000
ETU650 (LSI) ETU660 (LSIG) ETU15B (LI) ETU25B (LSI) ETU27B (LSIG) ETU45B (LSIG) ETU76B (LSIG)
■ ■ – – – – ■
Integrated Integrated – – – Optional Integrated
Optional Optional – – – Optional Optional
Basic/Advanced Basic/Advanced – – – Measurement Measurement
function Plus function Plus
■ ■ – – – ■ ■
■ ■ – – – ■ ■
IOM040/IOM300 IOM040/IOM300 – – – ■ ■
Connection
Main circuit connection
NSE0_00971b
NSE0_00968b
NSE0_00970b
NSE0_00969b
Direct
Extended
1-hole 2-hole 1-hole 2-hole
Extended
I201_20312
Broadened
Rear-mounted
NSE0_00973b
NSE0_00979a
NSE0_00972b
Vertical
NSE0_00967b
NSE0_00967b
Horizontal
Broadened
I201_20313
Cable
Cable terminals
Cable lug
NSE0_00975b
NSE0_00976b
For a complete and valid configuration of your air circuit breaker, please use our online configurator at
www.siemens.com/lowvoltage/3wl-configurator
1
Circuit breakers and
non-automatic circuit breakers
Sizes 1 to 3
ETU Accessories
NSE0_01027a
LI LSI LSING LSIN, LSING LSIN, LSING Communi Rating plugs Remote reset Breaker status Ground-fault
cations magnets sensors (BSS) modules
modules
Connection Accessories
Fixed-mounted, Main connection vertical, Auxiliary conductor plug-in system
withdrawable versions horizontal, front, flange
Note: You will find a detailed range of accessories in the Accessories and spare parts section.
1
Auxiliary switches NSE0_00996a
Accessories
Further accessories
NSE0_01022
NSE0_01018a
Door sealing frames Shutters EMERGENCY-OFF Operating cycles Support brackets Grounding connections
pushbuttons counters
Interlocking
NSE0_00987
Note: You will find a detailed range of accessories in the Accessories section.
Automatic generation of the 3D model, 2D dimension drawing and the internal circuit diagram
according to IEC
The structure shown below is intended as an overview of each position and its meaning.
For a complete and valid configuration of your air circuit breaker, please use our online configurator at
www.siemens.com/lowvoltage/3wl-configurator
1 5 6 7 8 9 10 11 12 13 14 15 16
3WL1 – –
Circuit breakers, non-automatic
circuit breakers and ETU
Size (SZ) 1 1
2 2
3 3
SZ 1
SZ 2
SZ 3
Short-circuit N ECO ■ – – 55 kA 2
breaking capacity – ■ – 66 kA 2
Icu at 500 V
S Standard ■ – – 66 kA 3
– ■ – 85 kA 3
H High ■ – – 85 kA 4
– ■ ■ 100 kA 4
C Very high – ■ ■8) 130 kA 5
– – ■9) 150 kA 5
Connection
SZ 1
SZ 2
SZ 3
5 6 7 8 9 10 11 12 13 14 15 16
1
3WL1 – –
Operating mechanisms and auxiliary releases
Stored energy Manual With mechanical operation 1
mechanism recharging of the With mechanical and electrical 110 V AC 50/60 Hz/110 V DC 2
stored energy operation, closing coil suitable for 230 V AC 50/60 Hz/220 V DC 3
mechanism uninterrupted duty, 100% OP
Motorized With mechanical and electrical 208 … 240 V AC 50/60 Hz/220 … 250 V DC 4
recharging operation, closing coil suitable for 110 … 127 V AC 50/60 Hz/110 … 125 V DC 5
uninterrupted duty, 100% OP
24 V DC 6
Auxiliary switches
1st auxiliary switch block 2 NO + 2 NC 2
The structure shown below is intended as an overview of each position and its meaning.
For a complete and valid configuration of your air circuit breaker, please use our online configurator at
www.siemens.com/lowvoltage/3wl-configurator
1 5 6 7 8 9 10 11 12 13 14 15 16
3WL1 – –
Non-automatic circuit breakers
and ETU
Size (SZ) 1 1
2 2
SZ 1
SZ 2
Short-circuit 1000 V DC 20 kA ■ – 8
breaking 600 V DC 25 kA – ■ 8
capacity Icc
Connection
SZ 1
SZ 2
5 6 7 8 9 10 11 12 13 14 15 16
1
3WL1 – –
Operating mechanisms and auxiliary releases
Stored energy Manual With mechanical operation 1
mechanism recharging of the With mechanical and electrical 110 V AC 50/60 Hz/110 V DC 2
stored energy operation, closing coil suitable for 230 V AC 50/60 Hz/220 V DC 3
mechanism uninterrupted duty, 100% OP
Motorized With mechanical and electrical 208 … 240 V AC 50/60 Hz/220 … 250 V DC 4
recharging operation, closing coil suitable for 110 … 127 V AC 50/60 Hz/110 … 125 V DC 5
uninterrupted duty, 100% OP
24 V DC 6
Auxiliary switches
1st auxiliary switch block 2 NO + 2 NC 2
Accessory options
For a complete and valid configuration of your air circuit breaker, please use our online configurator at
www.siemens.com/lowvoltage/3wl-configurator
1 To specify the options, add "-Z" to the complete article number and indicate the Order code
appropriate order code(s).
3WL....-.....-.... -Z
To specify the options, add "-Z" to the complete article number and indicate the
1
Order code
appropriate order code(s).
3WL....-.....-.... -Z
Communication 1)
Breaker status sensor (BSS) For determining the statuses ON/OFF/Tripped F01
PROFIBUS DP communication port 2) Including COM15 and breaker status sensor (BSS) F02
Modbus RTU communication port 2) Including COM16 and breaker status sensor (BSS) F12
PROFINET IO/Modbus TCP Including COM35 and breaker status sensor (BSS) F35
communication port 2)
EMC filter
• Common-mode interference suppressor filters (e.g. in converter applications)
• Insertion loss (asymmetric) in the range 40 kHz to 10 MHz >40 dB.
EMC filter F31
Accessory options
For a complete and valid configuration of your air circuit breaker, please use our online configurator at
www.siemens.com/lowvoltage/3wl-configurator
1 To specify the options, add "-Z" to the complete article number and indicate the Order code
appropriate order code(s).
3WL....-.....-.... -Z
Connection
Tinned version of the customer's connections on the guide frame
• Only for withdrawable circuit breakers with horizontal connection or flange connection
• The normal delivery time increases to 15 work days
Customer's connections 1) 2) Size 1 A08
Size 2 A08
Size 3 A08
Top: horizontal
5) 6)
Size 1 ≤1600 A P07
Bottom: accessible from front, Size 2 ≤3200 A P07
single hole
Size 3 ≤4000 A P07
1)
Front connections are tinned as standard. 3)
Not for 3WL1 size 1 with high breaking capacity H and 5)
Not for size 2, 3 circuit breakers with very high breaking capacity C.
2)
The permissible temperature rise limits according circuit breakers with very high breaking capacity C. 6)
Not for 3WL1 size 1 with high breaking capacity H
to IEC 60947-2 are 5 K lower for a tin surface than 4) Not for size 3 with very high breaking capacity C.
for a silver surface.
To specify the options, add "-Z" to the complete article number and indicate the
1
Order code
appropriate order code(s).
3WL....-.....-.... -Z
Connection
Connection technology for main connections (withdrawable versions)
Top: vertical Size 1 ≤2000 A P18
Bottom: horizontal Size 2 ≤3200 A P18
Size 3 ≤5000 A P18
Connection technology for auxiliary conductors (for fixed-mounted and withdrawable versions)
Connection technology for Fixed-mounted N61
screwless terminals (tension spring) Withdrawable P61
Accessory options
For a complete and valid configuration of your air circuit breaker, please use our online configurator at
www.siemens.com/lowvoltage/3wl-configurator
1 To specify the options, add "-Z" to the complete article number and indicate the Order code
appropriate order code(s).
3WL....-.....-.... -Z
Further accessories
Pushbuttons/disconnect switches/closing lockouts
EMERGENCY-OFF pushbuttons Mushroom pushbutton instead of the mechanical S24
OFF pushbutton
Local electric close on operator panel 1) This prevents unauthorized electrical closing from With sealing cap C11
(S10) the operator panel. Mechanical closing and remote With CES lock C12
closing remain possible. Possible only for circuit
breakers with closing coil (CC)
Motor disconnect switch on operator panel 4) This prevents automatic charging of the stored S25
(S12) energy mechanism by motorized operating
mechanism
Shutters
Shutter: 2-part, lockable, with padlocks 5) 3-pole/4-pole R21
1)
Not possible with "communications interface" 3)
Only possible with option "K07". 5)
Padlock not included in the scope of supply.
option, order code "F02", "F12" or "F35". 4)
Only for breakers with motorized operating mechanism,
Not available for non-automatic air circuit
2)
not possible with order codes "C11", "C12".
breakers.
To specify the options, add "-Z" to the complete article number and indicate the
1
Order code
appropriate order code(s).
3WL....-.....-.... -Z
Further accessories
Instrument transformers (without energy transformers), for powering the ETU
• Used in converter applications with high harmonic components; can only be used with ETU45B or ETU76B
− External 24 V DC supply required
− Undervoltage release required
• Comprises:
− 3 (3-pole) or 4 (4-pole) transformers
− 24 V DC relay
− Warning signs
− Manual
Transformer 3-pole/4-pole Sizes 2, 3 K60
Interlocking
Mechanical interlocking mechanism
• Interlocking module with Bowden cable 2 m
Mechanical interlocks For fixed-mounted breakers S55
For withdrawable circuit breakers with guide frame R55
For guide frames (ordered separately) R56
For withdrawable circuit breakers (ordered separately) R57
Accessory options
For a complete and valid configuration of your air circuit breaker, please use our online configurator at
www.siemens.com/lowvoltage/3wl-configurator
1 To specify the options, add "-Z" to the complete article number and indicate the Order code
appropriate order code(s).
3WL....-.....-.... -Z
Interlocking
Locking provisions (for withdrawable version)
• The disconnector unit fulfills the requirements for main circuit breakers acc. to EN 60204-1, consisting of a lock in the guide frame,
active in the connected position, function is retained when circuit breaker is replaced.
• Not possible in combination with order code "R81", "R85" or "R86".
Locking provisions Against unauthorized closing Made by CES R61
from the operator panel Made by RONIS R68
Made by PROFALUX R60
Locking mechanisms
• Not possible in combination with order code "R81", "R85" or "R86".
For fixed-mounted circuit breakers To prevent opening of the cabinet door in ON position S30
For withdrawable circuit breakers To prevent opening of the cabinet door in connected position R30
To prevent activation when the cabinet door is open 1) 3) R40
To prevent movement when the cabinet door is open 2) R50
Seals
Door sealing frame for degree of protection IP41 T40
Accessory options
Further technical specifications
Remote trip alarm reset coil for mechanical tripped indicator (F7) 3WL11 – 3WL13
Primary operating range
Primary operating range 0.85 … 1.1 × Us
Extended operating range for battery operation At 24 … 30 V DC, 48 … 60 V DC, 0.7 … 1.26 × Us
110 … 125 V DC, 220 … 250 V DC 1
Operation
Power consumption AC/DC 60 VA/60 W
Min. command duration at Us for the remote trip alarm reset coil 60 ms
Short-circuit protection
Smallest permissible DIAZED fuse (operational class gL)/ 2 A TDz (slow-response)/2 A at Us = 24 … 60 V DC,
miniature circuit breaker with C characteristic 1 A TDz (slow-response)/1 A at > 100 V DC and 100 V AC
Contact position-driven auxiliary switches (S1, S2, S3, S4, S7, S8) 3WL11 – 3WL13
Rated operational voltage
Rated insulation voltage Ui AC/DC 500 V
Rated operational voltage Ue AC/DC 500 V
Rated impulse withstand voltage Uimp 4 kV
Contact reliability From 1 mA at 5 V DC
Breaking capacity
Alternating current 50/60 Hz Rated operational voltage Ue 24 … 230 V 380 V, 400 V
Rated operational current Ie/AC-12 10 A 10 A
Rated operational current Ie/AC-15 4A 3A
Direct current Rated operational voltage Ue 24 V 48 V 110 V 220 V
Rated operational current Ie/DC-12 10 A 8A 3.5 A 1A
Rated operational current Ie/DC-13 8A 4A 1.2 A 0.4 A
Short-circuit protection
Largest permissible DIAZED fuse (operational class gL) 10 A TDz, 10 A Dz
Largest permissible miniature circuit breaker with C characteristic 10 A
Ready-to-close signaling switches (S20) (acc. to DIN VDE 0630) 3WL11 – 3WL13
Breaking capacity
Alternating current 50/60 Hz Rated operational voltage Ue 250 V
Rated operational current Ie 8A
Direct current Rated operational voltage Ue 125 V 250 V
Rated operational current Ie 0.4 A 0.2 A
Contact reliability From 1 mA at 5 V DC
Short-circuit protection
Largest permissible DIAZED fuse (operational class gL) 2 A Dz (quick-response)
Accessory options
Further technical specifications
The structure shown below is intended as an overview of each position and its meaning.
For a complete and valid configuration of your guide frame, please use our online configurator at
www.siemens.com/lowvoltage/3wl-configurator
5 6 7 8 9 10 11 12 13 14 15 16 1
3WL9 2 1
– – 1
Size (SZ) 1 1
2 2
3 SZ 1 3
SZ 2
Short-circuit N, 55 kA ■ – – N
breaking capacity S, 66 kA ■ – – S
Icu at 500 V
H, 85 kA ■5) – – H
N, S and H ≤100 kA – ■ ■ H
C 130 kA – ■ – C
C 150 kA – – ■ C
1)
Not available for rated circuit breaker current 2000 A and breaking capacity H 5)
For size 1 with breaking capacity H, please select the max. rated current In 2000 A
2)
Not available for rated circuit breaker current 4000 A of the guide frame
3)
Not available for rated circuit breaker current 5000 A + 6300 A + breaking capacity C 6)
Not available for breaking capacity C
4)
Not available for rated circuit breaker current 6300 A 7)
For all rated circuit breaker currents up to 3200 A with breaking capacity C
Options
5 6 7 8 9 10 11 12 13 14 15 16
3WL9 2 1
– – 1
Shutters Without A
With shutter, 2-part, lockable B
8)
Can only be selected if the number of auxiliary supply connectors is zero.
The structure shown below is intended as an overview of each position and its meaning.
For a complete and valid configuration of your guide frame, please use our online configurator at
www.siemens.com/lowvoltage/3wl-configurator
1 5 6 7 8 9 10 11 12 13 14 15 16
3WL9 2 1 2
– – 0 1
Options
5 6 7 8 9 10 11 12 13 14 15 16
3WL9 2 1 2
– – 0 1
Shutters Without A
With shutter, 2-part, lockable B
2)
Can only be selected if the number of auxiliary supply connectors is zero.
of the circuit breaker must not be exceeded. The following applies: In ≤ In max
Size Rated current In Article No.
1, 2 250 A 3WL9111-0AA51-0AA0
315 A 3WL9111-0AA52-0AA0
400 A 3WL9111-0AA53-0AA0
500 A 3WL9111-0AA54-0AA0
630 A 3WL9111-0AA55-0AA0
800 A 3WL9111-0AA56-0AA0
1000 A 3WL9111-0AA57-0AA0
1, 2, 3 1250 A 3WL9111-0AA58-0AA0
1600 A 3WL9111-0AA61-0AA0
2000 A 3WL9111-0AA62-0AA0
2, 3 2500 A 3WL9111-0AA63-0AA0
3200 A 3WL9111-0AA64-0AA0
4000 A 3WL9111-0AA65-0AA0
3 5000 A 3WL9111-0AA66-0AA0
6300 A 3WL9111-0AA67-0AA0
Ground-fault modules
• Alarm and tripping
• For direct metering of the ground-fault current, e.g. in the neutral point of the transformer,
a 1200 A/1 A current transformer, class 1, is required. The internal load of the 3WL circuit breaker
NSE0_01027a
is 0.11 . If the ground-fault current is to be determined using the vectorial sum of the phases,
a transformer must be installed in the neutral conductor.
Type Accessory for Article No.
GFM AT 45B ETU45B 3WL9111-0AT53-0AA0
GFM AT 55B – 76B ETU76B 3WL9111-0AT56-0AA0
Display
Accessory for Version Article No.
NSE0_01609
2 3WL9111-0AA22-0AA0
3 3WL9111-0AA23-0AA0
✓ 1 3WL9111-0AA31-0AA0
NSE0_00991a
2 3WL9111-0AA32-0AA0
3 3WL9111-0AA33-0AA0
ETU25B
ETU15B to ETU45B 3WL9111-0AT45-0AA0
ETU76 3WL9111-0AT46-0AA0
breaker is replaced
• Spare part for option R60, R61, R68
Type Scope of supply Article No.
Made by CES Locks, cylinders and keys included 3WL9111-0BA51-0AA0
Made by IKON Locks, cylinders and keys included 3WL9111-0BA53-0AA0
Made by KIRK-Key 1) Without locks, cylinders or keys 3WL9111-0BA57-0AA0
Made by RONIS Locks, cylinders and keys included 3WL9111-0BA58-0AA0
Made by PROFALUX Locks, cylinders and keys included 3WL9111-0BA50-0AA0
Locking provisions for charging handle with padlock
Version Scope of supply Article No.
Spare part for option S33 Without padlock 3WL9111-0BA71-0AA0
NSE0_00984
• Defeatable
• Note: Not possible in combination with "Locking mechanism to prevent movement of the
withdrawable circuit breakers in disconnected position" (order codes "R81", "R85" or "R86").
Version Article No.
Spare part for option S30 3WL9111-0BB12-0AA0
1)
Locks, cylinders and keys must be ordered from the manufacturer.
Article No.
3WL9112-8AH47-0AA0
Bowden cable
Length Article No.
2000 mm 3WL9111-0BB45-0AA0
3000 mm 3WL9111-0BB46-0AA0
4500 mm 3WL9111-0BB47-0AA0
Test devices
Manual tester, Release 2 for electronic trip units ETU15B to ETU76B
• For testing the electronic trip unit functions of all 3WL ETUs (Release 1 and Release 2)
Article No.
3WL9111-0AT32-0AA0
Spare part for options R15 and 1st block (3 CO) 3WL9111-0AH11-0AA0
R16 2nd block (6 CO) 3WL9111-0AH12-0AA0
Article No.
NSE0_00978
3WA9111-0AB01
Coding kits 3
Article No.
NSE0_00977a
3WA9111-0AB08
Auxiliary release
Closing coils/shunt trips
Version Voltage Article No.
100% OP 24 … 30 V DC 3WA9111-0AD02 1
NSE0_01000
48 … 60 V DC 3WA9111-0AD04
110 ... 125 V DC/110 ... 127 V AC 3WA9111-0AD05
220 ... 250 V DC/208 ... 240 V AC 3WA9111-0AD06
30 V DC 3WL9111-0AE02-0AA0
48 V DC 3WA9111-0AE04
60 V DC 3WL9111-0AE07-0AA0
110 ... 125 V DC/110 ... 127 V AC 3WA9111-0AE05
220 ... 250 V DC/208 ... 240 V AC 3WA9111-0AE06
380 … 415 V AC 3WA9111-0AE07
Delayed 48 V DC 3WA9111-0AE13
NSE0_01002
110 ... 125 V DC/110 ... 127 V AC 3WA9111-0AE15
220 ... 250 V DC/208 ... 240 V AC 3WA9111-0AE16
380 … 415 V AC 3WA9111-0AE17
Operating mechanism
Motorized operating mechanisms
• Auxiliary supply connector X5 required for circuit breakers or guide frames.
If this is not already available, please order additionally
Voltage Article No.
24 … 30 V DC 3WA9111-0AF02
NSE0_01003a
48 … 60 V DC 3WA9111-0AF04
110 ... 125 V DC/110 ... 127 V AC 3WA9111-0AF05
220 ... 250 V DC/208 ... 240 V AC 3WA9111-0AF06
Auxiliary contacts
Auxiliary switch blocks
Contacts Article No.
NSE0_01004
Arc chute
Arc chute
Voltage Size Breaking capacity Article No.
690 V 1 N, S, H 3WL9111-0AS01-0AA0
2 N, S, H 3WL9111-0AS02-0AA0
NSE0_01007
C 3WL9111-0AS10-0AA0
3 H, C 3WL9111-0AS03-0AA0
1000 V/1150 V 2 H, C 3WL9111-0AS05-0AA0
3 H, C 3WL9111-0AS06-0AA0
Arc chute covers
• Parts kit for guide frame
• Spare part for option R10
• Not available for:
− 1000 V version (order code "A05"),
− 1150 V version (order code "A15")
− DC version
− 4000 A size 2
− Circuit breakers with very high breaking capacity C.
Number of poles Size Article No.
3-pole 1 3WL9111-0AS32-0AA0
2 3WL9111-0AS36-0AA0
NSE0_01008
3 3WL9111-0AS38-0AA0
4-pole 1 3WL9111-0AS42-0AA0
2 3WL9111-0AS44-0AA0
3 3WL9111-0AS46-0AA0
1
NSE0_01009
Grounding connections
Grounding connection between the guide frame and the withdrawable circuit breaker
• Up to 30 kA or 60 kA ground-fault current
• 2 modules must be used for up to 60 kA ground-fault current
Contact module Size Number of poles Article No.
For guide frames 1, 2 1) 3WL9111-0BA01-0AA0
3 3WL9111-0BA02-0AA0
For withdrawable circuit breakers 1 3-pole 3WL9111-0BA05-0AA0
4-pole 3WL9111-0BA08-0AA0
2 3-pole 1) 3WL9111-0BA06-0AA0
4-pole 1) 3WL9111-0BA04-0AA0
3 3-pole 3WL9111-0BA07-0AA0
4-pole 3WL9111-0BA10-0AA0
1)
Cannot be used for size 2 with very high breaking capacity C and size 2, 4000 A.
Support bracket
Support bracket
• For mounting fixed-mounted circuit breakers on vertical plane
NSE0_01022
Digital output module with rotary coding switch, relay outputs 3WL9111-0AT26-0AA0
Digital output module, configurable, relay outputs 3WL9111-0AT20-0AA0
Digital input module 3WL9111-0AT27-0AA0
Analog output module 3WL9111-0AT23-0AA0
ZSI module 3WL9111-0AT21-0AA0
Preassembled cables for the CubicleBUS
For connection to 3WL Length Article No.
With COM15/COM16/COM35 0.5 m 3WL9111-0BC04-0AA0
1m 3WL9111-0BC02-0AA0
2m 3WL9111-0BC03-0AA0
Without COM15/COM16/COM35 2 m 3WL9111-0BC05-0AA0
Voltage transformers
• Required for 3WL circuit breakers with measurement function Plus, if no direct voltage tap is available.
• 380 ... 690 V/100 V, class 0.5
Number of poles Measurement function Article No.
3-pole With measurement function Plus 3WL9111-0BB68-0AA0
Interfaces
Interface to the IEC 61850
• The SICAM A8000 smart data concentrator connects the circuit breakers from the SENTRON portfolio
via the Modbus TCP/IP protocol and transmits data via communication protocols (e.g.: IEC61850,
IEC60870-5-104, IEC60870-5-101, Modbus and DNP) to higher-level systems.
1
Type Operational voltage Article No.
SICAM CP-8021 1) – 6MF2802-1AA00
SICAM CP-8050 2) – 6MF2805-0AA00
1)
Dimensioned for device quantities of max. 1× 3WL and 1× 3VA
2)
Dimensioned for device quantities of max. 3× 3WL and 8× 3VA
You will find further information at:
www.siemens.com/sicam-a8000
For the SICAM CP-8021 and SICAM CP-8050, predefined modules were created to reduce commissioning work to a minimum.
The modules can be downloaded from SIOS free of charge www.siemens.com/lowvoltage/product-support (109779191)
&UIFSOFU*&$
356
4*$".
"
&UIFSOFU.PECVT5$1
I201_19878a
$0.
$0.
7"MJOF
7" 7"
8-
Storage devices
Capacitor trip device
• For shunt trips
1 •
•
Storage time 5 min
Also suitable for 3VL, 3VA and 3WN circuit breakers
• Note: Rated control supply voltage must match the rated control supply voltage of the shunt trips.
Rated control supply voltage/rated operational voltage Article No.
50/60 Hz AC DC
220 … 240 V 220 … 250 V 3WL9111-0BA14-0AA0
Spare parts
Measurement function Plus for retrofitting
• As spare part or for retrofitting the measurement function Plus with an external voltage transformer
− For ETU45B or ETU76B Release 2
− Voltage transformer required
− Voltage converter required
− A measuring accuracy of 3% is achieved if retrofitted.
Article No.
3WL9111-0AT05-0AA0
Voltage converter
Version Article No.
As spare part or for retrofitting the measurement function Plus 3WL9111-0AT06-0AA0
Components for conversion of an existing internal voltage tap 2)
• Conversion requires 3 components for 3-pole 3WL
• Conversion requires 4 components for 4-pole 3WL
• Conversion of a measurement function (Z option A05) is not possible.
Conversion of internal voltage tap Size Article No.
to main contact
From bottom to top 1 3WL9111-0AT71-0AA0
2 3WL9111-0AT72-0AA0
3 3WL9111-0AT73-0AA0
From top to bottom 1 3WL9111-0AT74-0AA0
2 3WL9111-0AT75-0AA0
3 3WL9111-0AT76-0AA0
Transformers (without iron core), Rogowski coil only (instrument transformer for the protective function)
• Used in converter applications with high harmonic components;
can only be used with ETU45B or ETU76B
− External 24 V DC supply required
− Undervoltage release required (e.g. 3WL9111-0AE01-0AA0)
• As retrofit kit or as spare part. With new circuit breakers, please use the Z option K60
• Scope of supply:
− Transformer
− Warning signs
− Manual
Number of poles Size Article No.
3-pole 1 3WL9111-0AA42-0AA0
2 3WL9111-0AA43-0AA0
3 3WL9111-0AA44-0AA0
4-pole 1 3WL9111-0AA45-0AA0
2 3WL9111-0AA46-0AA0
3 3WL9111-0AA47-0AA0
2 4) ≤2000 A 3WL9111-0AL11-0AA0
≤2500 A 3WL9111-0AL12-0AA0
≤3200 A 3WL9111-0AL13-0AA0
3 ≤4000 A 3WL9111-0AL14-0AA0
Front-accessible main connections according to DIN 43673, double hole at bottom
Size Rated current In Article No.
1 ≤1000 A 1) 3WL9111-0AL57-0AA0
1250 … 2000 A 5) 3WL9111-0AL58-0AA0
NSE0_01011
2 4) ≤2000 A 3WL9111-0AL61-0AA0
≤2500 A 3WL9111-0AL62-0AA0
≤3200 A 3WL9111-0AL63-0AA0
3 ≤4000 A 3WL9111-0AL64-0AA0
Rear vertical main connections
Size Rated current In Article No.
1 2) ≤2000 A 3WL9111-0AM01-0AA0
2 3) ≤3200 A 3WL9111-0AM02-0AA0
3 ≤6300 A 3WL9111-0AM03-0AA0
NSE0_01012
1)
Not for 3WL1 size 1 with high breaking capacity H
2)
In the case of vertical connection size 1 with breaking capacity N and S, up to 1000 A one 3WL9111-0AM01-0AA0 vertical connection is required,
up to 2000 A or with breaking capacity H two 3WL9111-0AM01-0AA0 vertical connections are required.
3)
In the case of vertical connection size 2, up to 2500 A one 3WL9111–0AM02–0AA0 vertical connection is required,
up to 3200 A two 3WL9111-0AM02-0AA0 vertical connections are required.
4)
Not for circuit breakers with very high breaking capacity C.
5)
Can be used for size 1 with H breaking capacity of 630 A … 2000 A.
2 3) ≤2000 A 3WL9111-0AN03-0AA0
≤2500 A 3WL9111-0AN04-0AA0
≤3200 A 3WL9111-0AN05-0AA0
3 ≤4000 A 3WL9111-0AN06-0AA0
Front-accessible main connections according to DIN 43673, double hole at top or at bottom 1)
Size Rated current In Article No.
1 ≤1000 A 2) 3WL9111-0AN07-0AA0
1250 … 2000 A 5) 3WL9111-0AN08-0AA0
NSE0_01014
2 3) ≤2000 A 3WL9111-0AN11-0AA0
≤2500 A 3WL9111-0AN12-0AA0
≤3200 A 3WL9111-0AN13-0AA0
3 ≤4000 A 3WL9111-0AN14-0AA0
Supports for front and DIN connection bars
Number of poles Size Article No.
3-pole for 3 bars 1 3WL9111-0AN41-0AA0
2 3WL9111-0AN42-0AA0
NSE0_01017
3 3WL9111-0AN43-0AA0
4-pole for 4 bars 1 3WL9111-0AN44-0AA0
2 3WL9111-0AN45-0AA0
3 3WL9111-0AN46-0AA0
Rear vertical main connections
Size Rated current In Connection pieces Article No.
NSE0_01015
1 ≤1000 A 2) 3WL9111-0AN15-0AA0
1250 … 2000 A 5) 3WL9111-0AN16-0AA0
2 ≤2000 A 3) 3WL9111-0AN17-0AA0
≤2500 A 3) 3WL9111-0AN18-0AA0
≤3200 A 3) 3WL9111-0AN21-0AA0
1600 … 3200 A 4) 3WL9111-0AN38-0AA0
3 ≤5000 A 3WL9111-0AN22-0AA0
≤6300 A 3 pieces for 3-pole switches 3WL9111-0AN23-0AA0
≤6300 A, top 4 pieces for 4-pole switches 3WL9111-0AN20-0AA0
≤6300 A, bottom 4 pieces for 4-pole switches 3WL9111-0AN10-0AA0
Rear horizontal main connections
Size Rated current In Article No.
1 ≤1000 A 2) 3WL9111-0AN32-0AA0
1250 … 2000 A 5) 3WL9111-0AN33-0AA0
2 ≤2000 A 3) 3WL9111-0AN34-0AA0
≤2500 A 3) 3WL9111-0AN35-0AA0
≤3200 A and 4000 A DC 3) 3WL9111-0AN36-0AA0
1600 … 3200 A 4) 3WL9111-0AN47-0AA0
3 ≤5000 A 3WL9111-0AN37-0AA0
Connecting flange
Size Rated current In Article No.
1 ≤1000 A 2) 3WL9111-0AN24-0AA0
1250 … 2000 A 5) 3WL9111-0AN25-0AA0
NSE0_01016
2 3) ≤2000 A 3WL9111-0AN26-0AA0
≤2500 A 3WL9111-0AN27-0AA0
≤3200 A 3WL9111-0AN28-0AA0
3 ≤4000 A 3WL9111-0AN31-0AA0
1)
When using front-accessible main connections (withdrawable circuit breakers) supports are required.
2)
Not for 3WL1 size 1 with high breaking capacity H
3)
Not for circuit breakers with very high breaking capacity C.
4)
Only for circuit breakers with very high breaking capacity C.
5)
Can be used for size 1 with H breaking capacity of 630 A … 2000 A.
Conversion kit
Conversion kit for converting fixed-mounted circuit breakers into withdrawable circuit breakers
• Guide frames and sliding contact modules must be ordered separately
• Conversion from fixed-mounted to withdrawable circuit breakers is not possible for 3WL1 circuit
breakers with very high breaking capacity C and for circuit breakers with Z options A05, A15 or A16 1
Number of poles Size Article No.
3-pole 1 3WL9111-0BC11-0AA0
2 3WL9111-0BC12-0AA0
3 3WL9111-0BC13-0AA0
4-pole 1 3WL9111-0BC14-0AA0
2 3WL9111-0BC15-0AA0
3 3WL9111-0BC16-0AA0
1)
Not for circuit breakers with very high breaking capacity C.
2)
Replacement of the main contact elements for 3WL1 circuit breakers with very high breaking capacity C is only possible at the factory.
3)
Please specify the circuit breaker ID No. in plain text when ordering.
4)
Not for size 1 circuit breakers with breaking capacity H and circuit breakers with In = 2000A.
For a complete and valid configuration of your air circuit breaker, please use our online configurator at
www.siemens.com/lowvoltage/3wl10-configurator
1
Circuit breakers and
non-automatic circuit breakers
Size 0
Electronic trip units ETU Electronic trip units ETU Communi Rating plugs Breaker Measurement External ground
(LI, LSI, LSIG) (LSI, LSIG) cation and Connect function (Basic/ fault transformers
I/O modules modules Advanced)
Fixed-mounted, Rear vertical/horizontal Front connections Front connections, Terminals for Cu/Al
withdrawable connections extended cable connection
versions
Motor Accessories
Note: You will find a detailed range of accessories in the Accessories and spare parts section.
1
Auxiliary releases/closing coils
Interlocking
Interlocking sets Locking provisions Locking mechanisms Door sealing frames Protective covers
Note: You will find a detailed range of accessories in the Accessories section.
Product list stores multiple configurations and can transfer them collectively to the shopping cart
Responsive Design
www.siemens.com/lowvoltage/3wl10-configurator
The structure shown below is intended as an overview of each position and its meaning.
For a complete and valid configuration of your air circuit breaker, please use our online configurator at
www.siemens.com/lowvoltage/3wl10-configurator
1 6 7 8 9 10 11 12 13 14 15 16
3WL10 – –
Connection 3)
Type of mounting Withdrawable Without frame 0
Rear vertical connection 1
Rear horizontal connection 2
Adapter for cable lug connection (rear) 4
Front-accessible, extended main connection 5
Fixed-mounted Rear vertical connection 1
versions Rear horizontal connection 2
Front main connection 3
Circular conductor terminals (front) 4
Front-accessible, extended main connection 5
3)
Broadened connections available as accessories.
6 7 8 9 10 11 12 13 14 15 16 1
3WL10 – –
Motor
Operating Manual operating mechanism 0
mechanisms Spring charging motor 24 ... 30 V AC/DC 1
48 ... 60 V AC/DC 2
110 V AC/DC 3
230 V AC/DC 4
Accessory options
For a complete and valid configuration of your air circuit breaker, please use our online configurator at
www.siemens.com/lowvoltage/3wl10-configurator
1 To specify the options, add "-Z" to the complete article number and Order code
indicate the appropriate order code(s).
3WL....-.....-.... -Z
Accessories for basic configuration
Mounting options for fixed-mounted versions
• In the basic configuration, the fixed-mounted circuit breaker is mounted onto the rear panel. Floor mounting is possible as an option.
The device must additionally be modified if it is to be extended to include functionalities such as external auxiliary switches or mechanical
interlocking mechanism.1)
Mounting options for Floor mounting Mounting support standard A07
fixed-mounted versions 1) Mounting support extended 2) S56
Rear panel mounting onto mounting plate Side wall extended 2) S57
Communications modules
• No more than two different communications modules can be used at the same time.
• When using an IOM040 digital I/O module (Z option K56), only 1 communications module can be used.
Communications modules COM040 PROFIBUS F02
COM041 PROFINET F03
COM043 Modbus TCP F11
COM042 Modbus RTU F12
To specify the options, add "-Z" to the complete article number and indicate the
1
Order code
appropriate order code(s).
3WL....-.....-.... -Z
Accessories for the motor
Mechanical operating cycles counter, 5-digit C01
Locking provisions Against unauthorized closing Cylinder lock, made by RONIS S08
in the operator panel (safe OFF) For no more than 3 padlocks, plastic 4 mm S22
For no more than 1 padlock, metal 7 mm S23
For no more than 2 padlocks, metal 8 mm S07
Interlocking sets For mechanical Open and/or Close For no more than 3 padlocks, plastic 4 mm S42
on the operator panel For no more than 1 padlock, metal 7 mm S43
For no more than 2 padlocks, metal 8 mm S44
Guide frames
To specify the options, add "-Z" to the complete article number and Order code
indicate the appropriate order code(s).
3VW8....-.....-.... -Z
Locking, blocking and interlocking
Locking provisions To prevent movement of the Cylinder lock, made by RONIS R78
withdrawable circuit breaker
For no more than 3 padlocks, 8 mm R65
Locking mechanisms To prevent movement to disconnected position (only in combination with R78 or R65) R79
Auxiliary/signaling switches
Position signaling switch PSS for For 24 V DC digital signals, 2 CO | 2 CO | 2 CO (connected | test | disconnected position) K55
guide frame for minimum currents
Auxiliary and signaling switches for currents >100 mA and up to 400 V AC are installed as standard.
For currents <100 mA for PLC connections, these auxiliary and signaling switches can be modified.
The auxiliary/signaling switches for 24 V DC digital signals are designed for
• a minimum load above 1 mA at 5 V DC, and
• a maximum breaking capacity of 100 mA at 24 V DC.
Remote reset magnets RR for the circuit breakers including tripped signaling
• Remote reset magnet (RR) for resetting the circuit breaker after tripping as a result of overcurrent conditions
Accessory for Voltage Article No.
ETU320, ETU350, ETU360, 24 V DC 3VW9011-0AK03
ETU650, ETU660 110 V AC/DC 3VW9011-0AK05
250 V AC/DC 3VW9011-0AK06
Rating plugs
• Only one module is possible per circuit breaker.
Accessory for Version Rated current In Article No.
Broadened main connections, Front main connections, top 3-pole/3 units 3VW9011-0AL73
including insulation plate and Front main connections, 3-pole/3 units 3VW9011-0AL75
extended phase barriers bottom
Front main connections, top, 4-pole/4 units 3VW9011-0AL74
bottom
Withdrawable Front-accessible main connections Flange of the guide frame 3-pole/3 units 3VW9011-0AN01
4-pole/4 units 3VW9011-0AN02
1)
For connecting Al cables up to 1000 A
Mounting support extended • Fixation for external auxiliary switches AUX 15 CO (3VW9011-0AG15) 3VW9011-0BB52
(circuit breaker feet), • Locking mechanism for control cabinet door, direct (for 3VW9011-0BB10)
including mechanical • Locking mechanism for control cabinet door, Bowden cable
transmission of switch (for 3VW9011-0BB16)
position on circuit breaker • Mechanical interlock for 3WL/3VA (for 3VW9011-0BB21)
side panel (= Z option S56)
Extension kits for modification of the side wall of the fixed-mounted circuit breaker
• For fixed-mounted versions
• Rear wall fixing on mounting plate
• For modification for mechanical transmission of switch position on circuit breaker side panel (= Z option S57)
Version Use Article No.
Extension kit for side wall • Fixation for external auxiliary switches AUX 15 CO (3VW9011-0AG15) 3VW9011-0BB53
• Locking mechanism for control cabinet door, direct (for 3VW9011-0BB10)
• Locking mechanism for control cabinet door, Bowden cable
(for 3VW9011-0BB16)
• Mechanical interlock for 3WL/3VA (for 3VW9011-0BB21)
Motor
Spring charging motor (MO)
Description Voltage Article No.
1 For automatic charging of the 24 ... 30 V AC/DC 3VW9011-0AF01
stored energy mechanism 48 ... 60 V AC/DC 3VW9011-0AF02
100 ... 130 V AC/DC 3VW9011-0AF03
220 ... 250 V AC/DC 3VW9011-0AF04
Interlocking
Locking provision to prevent movement of the withdrawable circuit breaker
Version Article No.
1 RONIS cylinder lock (spare part for R78) 3VW9011-0BA80
Padlock 8 mm (spare part for R65), for no more than 3 padlocks 3VW9011-0BA87
Locking mechanisms to prevent movement of the withdrawable circuit breakers in disconnected position
• Only possible as a supplement in conjunction with R78 (3VW9011-0BA80) and/or R65 (3VW9011-0BA87)
Description Article No.
Locking mechanism (spare part for R79) 3VW9011-0BA84
Interlocking
Locking mechanisms for control cabinet door
• To prevent opening of the control cabinet door in ON position
• It additionally prevents the circuit breaker from being closed when the control cabinet door is open. 1
Mounting Version Article No.
Fixed-mounted onto side panel or floor Direct fixed interlocking 3VW9011-0BB10
Locking with Bowden cable 3VW9011-0BB16
Withdrawable Direct fixed interlocking 3VW9011-0BB14
Locking with Bowden cable 3VW9011-0BB18
Molded case circuit breakers and switch disconnectors for all applications 2/4
3VA10 – 3VA26 2/20
Communication 2/56
3VA27 2/66
3VL 2/85
Information + ordering
All the important things at a glance Everything you need for your order
2
For information about molded case circuit breakers, Refer to the Industry Mall for an overview of your
please visit our website www.siemens.com/3VA products
• Molded case circuit breakers sie.ag/2mmLcAk
Direct forwarding to the individual products in the
Your product in detail
Industry Mall by clicking on the article number in the
catalog or entering this web address incl. article n
umber
The Siemens Industry Online Support (SIOS) provides www.siemens.com/product?Article No.
comprehensive information
Order supports are available in Siemens Industry Online
www.siemens.com/lowvoltage/product-support
Support (SIOS) at
• Quick Selection Guide www.siemens.com/lowvoltage/product-support
− 3VA molded case circuit breaker (109757591)
• Order Support
• Technical Basic Information
− 3VA molded case circuit breakers – One system.
− 3VA molded case circuit breakers (109766672)
Global use (109765994)
The relevant tender specifications can be found at
www.siemens.com/lowvoltage/tenderspecifications
Use our conversion tool for quick and easy conversion to Configurators
Siemens products www.siemens.com/conversion-tool
The configurator reduces the time and effort required in
the planning and ordering process, and allows for individ
Siemens YouTube channel ual adaptations. Configure your 3VA molded case circuit
breaker at
www.siemens.com/lowvoltage/3va-configurator
• 3VA molded case circuit breakers (general)
www.siemens.com/lowvoltage/3va27-configurator
bit.ly/2xNxlFA
The following are additionally available for your 3VA
molded case circuit breaker:
• 3D views
• CAD data
• Unit wiring diagrams
• Dimension drawings
Commissioning + operation
The combined commissioning and service tool SENTRON Manuals are available for downloading in Siemens
powerconfig for communication-capable measuring Industry Online Support (SIOS) at
devices, circuit protection devices and circuit breakers. www.siemens.com/lowvoltage/manuals
Free download SENTRON powerconfig • Configuration Manual
www.siemens.com/powerconfig − 3VA selectivity (109743975)
Free download SENTRON powerconfig mobile via • Communication Manual
App Store and Play Store − 3VA molded case circuit breakers with IEC and UL
certification (98746267)
− 3WL10 air circuit breakers & 3VA27 molded case
circuit breakers (109760220)
Your product in detail
• Equipment Manual
− 3VA molded case circuit breakers with IEC certificate
The Siemens Industry Online Support (SIOS) provides (90318775)
detailed technical information − 3VA27 molded case circuit breakers & 3WL10 air
www.siemens.com/lowvoltage/product-support circuit breakers (109753821)
• Operating instructions
• Characteristic curves
• Certificates Face-to-face or online training
Comprehensive mobile support via the Siemens Industry
Online Support app available for download from the Our training courses can be found at
App Store and Play Store www.siemens.com/sitrain-lowvoltage
You will find further information at • 3VA molded case circuit breaker (WT-LVA3VA)
www.siemens.com/support-app
• Protection systems in low-voltage power distribution
Provision of 3D data (step and u3d data formats) (WT-LVAPS)
• Project planning and selection of SENTRON circuit
• Siemens Industry Mall
breakers (LV-CBPROJ)
www.siemens.com/lowvoltage/mall
• Image database
www.siemens.com/lowvoltage/picturedb
Engineering data for CAD or CAE systems are available in
the CAx Download Manager at
www.siemens.com/cax
Accessories
Size 100 A 160 A 250 A 400 A 630 A 1000 A
Accessories
Auxiliary switches and signaling switches ■ ■ ■ ■ ■ ■
Auxiliary releases ■ ■ ■ ■ ■ ■
Connection technology ■ ■ ■ ■ ■ ■
Plug-in version – ■ ■ ■ ■ ■
Withdrawable version – – ■ ■ ■ –
Front mounted rotary operator ■ ■ ■ ■ ■ ■
Door mounted rotary operator ■ ■ ■ ■ ■ ■
Side wall mounted rotary operator ■ ■ ■ ■ ■ –
MO310 motor operator (mounted onto the side) – ■ – – –
MO320 motor operator (mounted onto the front) – ■ ■ ■ ■ –
Motor operator with SEO520 stored energy mechanism – – – – – –
Motor operator (MO), integrable – – – – – –
Locking, blocking and interlocking ■ ■ ■ ■ ■ ■
Residual current device (mounted onto the side) – ■ ■ – – –
Residual current device (mounted underneath) – ■ ■ – – –
Communications interface – – – – – –
EFB300 – – – – – –
Testing and commissioning devices – – – – – –
Cover frame ■ ■ ■ ■ ■ ■
DIN-rail adapter ■ ■ – – – –
Busbar adapter ■ ■ ■ ■ ■ –
– – – – – – – ■
– – – – – – – –
– – – – – – – –
■ ■ ■ ■ ■ ■ ■ ■
■ ■ ■ ■ ■ ■ ■ ■
■ ■ ■ ■ ■ ■ ■ ■
■ ■ ■ ■ ■ ■ ■ ■
– ■ ■ ■ ■ ■ – ■
– ■ ■ ■ ■ ■ – ■
– ■ ■ ■ ■ ■ – ■
– ■ ■ ■ ■ ■ – ■
■ ■ ■ ■ ■ ■ ■ ■
■ ■ ■ ■ ■ ■ ■ ■
■ ■ ■ ■ ■ ■ ■ ■
■ ■ ■ ■ ■ ■ ■ –
■ ■ ■ ■ ■ – – ■
■ ■ ■ ■ ■ ■ ■ ■
■ ■ ■ ■ ■ ■ ■ ■
■ ■ ■ ■ ■ – – –
– – – – – – – –
■ ■ ■ ■ ■ – – –
■ ■ ■ – – – – –
– – – – – – – ■
■ ■ ■ ■ ■ ■ ■ ■
– – – – – – – –
■ ■ ■ ■ ■ – – –
■ ■ ■ ■ ■ ■ ■ ■
■ ■ ■ ■ ■ ■ ■ ■
■ ■ ■ ■ ■ ■ ■ ■
■ ■ ■ ■ ■ ■ ■ ■
– – – – – – – –
■ ■ ■ ■ ■ – – –
D mm 88 88 88
1)
For detailed data on DC breaking capacity, number of switching poles and circuit diagrams, see FAQ www.siemens.com/lowvoltage/product-support (109779932)
2)
For In = 630 A/800 A
3)
In 125 A, 160 A: Icu/Ics = 36 kA/36 kA
76.2 (3P) | 101.6 (4P) 105 (3P) | 140 (4P) 138 (3P) | 184 (4P) 138 (3P) | 184 (4P) 210 (3P) | 280 (4P)
130 158 248 248 320
70 70 110 110 120
88 88 137 137 253
■ – – – –
■ – – – –
■ ■ ■ ■ ■
■ ■ ■ ■ ■
85 110 150 200 – 85 110 150 200 – 85 110 200 85 110 200 100 150 200
55 85 110 150 200 55 85 110 150 200 55 85 110 55 85 110 55 85 110
55 85 110 – – 55 85 110 – – 55 85 110 55 85 110 55 85 100
36 55 85 – – 36 55 85 – – 36 55 85 36 55 85 36 55 85
5 5 5 25 85 6 6 6 25 85 25 35 35 25 35 35 25 36 50
– – – – – – – – – – – – – – – – – – –
– – – – – – – – – – – – – – – – – – –
– – – – – – – – – – – – – – – – – – –
– – – – – – – – – – – – – – – – – – –
85 110 150 200 – 85 110 150 200 – 85 110 150 85 110 150 100 150 200
55 85 110 150 200 55 85 110 150 200 55 85 85 55 85 85 55 85 110
55 85 110 – – 55 85 110 – – 55 70 70 55 70 70 55 85 100
36 55 65 – – 36 55 85 1) – – 36 55 65 36 55 65 36 55 63
5 5 5 18 65 6 6 6 18 65 19 19 19 19 19 19 25 36 36
– – – – – – – – – – – – – – – – – – –
– – – – – – – – – – – – – – – – – – –
– – – – – – – – – – – – – – – – – – –
– – – – – – – – – – – – – – – – – – –
138 (3P) | 184 (4P) 138 (3P) | 184 (4P) 210 (3P) | 280 (4P) 210 (3P) | 280 (4P) 210 (3P) | 280 (4P)
248 248 320 320 291
110 110 120 120 171 (handle operating
mechanism) |
183 (stored energy
operating mechanism)
137 137 253 253 225
Trip units
ETU310M I – ■ ■
ETU350M LSI – ■ ■
ETU550M LSI – ■ ■
ETU860M LSIG – ■ ■
ETU320 LI – – –
ETU350 LSI – – –
ETU360 LSIG – – –
ETU650 LSIG – – –
ETU660 LSIG – – –
■ ■ ■ ■ ■
■ ■ ■ ■ –
■ ■ ■ ■ –
■ ■ ■ ■ ■
■ ■ ■ ■ –
■ ■ ■ ■ –
– – – – ■
– – – – ■
– – – – ■
■ ■ – – –
■ ■ ■ – –
■ ■ ■ – –
■ ■ ■ – –
– – – – ■
– – – – ■
– – – – ■
– – – – ■
– – – – ■
Trip units
Protection system for 3VA molded case circuit breakers up to 1000 A
Trip units Thermal-magnetic Electronic Electronic with display Electronic with display and
measurement function
I201_18484
I201_18828
I201_19035
I201_19701
I r /A Ii /A /A /s /s N=X r
OFF
– EFB300 external function box EFB300 external function box for EFB300 external function box for
for connection to the ETU connection to the ETU connection to the ETU
Communications
module
2
1-pole and 2-pole breakers – ■ – –
3-pole breaker ■ ■ ■ ■
4-pole breaker – ■ ■ ■
Available protection parameters
Ir adjustable – – ■ ■
Ii adjustable ■ – – ■
Ir fixed – ■ – –
Ii fixed – ■ ■ –
IN 1) – ■ ■ ■
1)
3VA10 only without N protection
3VA11, 3VA12, 3VA13, 3VA14 without, 50% or 100% N protection
50% N protection from In ≥100 A
Available for:
- Circuit breakers with ETU (4-pole)
- Circuit breakers with ETU5/ETU8 3-pole with external neutral conductor transformer or 4-pole
Product list stores multiple configurations and can transfer them collectively to the shopping cart
Responsive Design
www.siemens.com/lowvoltage/3va-configurator and
www.siemens.com/lowvoltage/3va27-configurator
Automatic generation of the 3D model, the 2D dimension drawing and the internal circuit
diagram according to IEC
System overview
For a complete and valid configuration of your molded case circuit breaker, please use our online
configurator at www.siemens.com/lowvoltage/3va-configurator
I r /A Ii /A /A /s /s N=X r
OFF
Thermal-magnetic trip Electronic trip unit Electronic trip unit (ETU) 24 V module Communica- Data External Test device
unit (TMTU) (ETU) with display, and tions module concentrator display
optionally with measure-
ment function
Fixed-mounted Withdrawable unit, Plug-in unit, Auxiliary Door Position Cylinder lock Crank
complete kit complete kit circuit feedthrough signaling adapter
connector switch
Bus Bus Circular Box Nut keeper kits, Insulation accessories
connectors connectors conductor terminals right-angled
broadened terminals
Note:
You will find a detailed range of accessories in the Accessories and spare parts section.
Shunt trip Universal Undervoltage Auxiliary Tripped Leading changeover Electrical alarm Short circuit alarm switch
release release switch signaling switch switch LCS switches EAS SAS
Mountable accessories
Sliding bar interlock Interlocking with rod Handle interlocking module with Bowden cable
Note:
You will find a detailed range of accessories in the Accessories and spare parts section.
The structure shown below is intended as an overview of each position and its meaning.
For a complete and valid configuration of your molded case circuit breaker, please use our online
configurator at www.siemens.com/lowvoltage/3va-configurator
4 5 6 7 8 9 10 11 12
3VA – – 0AA0
2
Trip units Thermal-magnetic 1
Electronic 2
3VA10
3VA11
3VA12
3VA13
3VA14
3VA15
3VA20
3VA21
3VA22
3VA23
3VA24
3VA25
3VA26
Size (SZ) 100 A ■ – – – – – ■ – – – – – – 0
160 A – ■ – – – – – ■ – – – – – 1
250 A – – ■ – – – – – ■ – – – – 2
400 A – – – ■ – – – – – ■ – – – 3
630 A – – – – ■ – – – – – ■ – – 4
1000 A – – – – – ■ – – – – – ■ – 5
1250 A – – – – – – – – – – – – ■ 6
4 5 6 7 8 9 10 11 12
3VA – – 0AA0
2
3VA10
3VA11
3VA12
3VA13
3VA14
3VA15
3VA20
3VA21
3VA22
3VA23
3VA24
3VA25
3VA26
Short-circuit Without overload
– ■ – ■ – ■ – – – – – – – 1
breaking protection
capacity Without short-circuit
– ■ ■ ■ ■ – – – – – – – – 1
Icu = Ics at 415 V protection
16 kA ■ – – – – – – – – – – – – 2
25 kA ■ ■ – – – – – – – – – – – 3
36 kA ■ ■ ■ ■ ■ – – – – – – – – 4
55 kA – ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ 5
70 kA – ■ ■ ■ ■ ■ – – – – – – – 6
85 kA – – – – – – ■ ■ ■ ■ ■ ■ ■ 6
110 kA – – – ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ 7
150 kA – – – – – – ■ ■ ■ ■ ■ – – 8
200 kA 1) – – – – – – – ■ ■ ■ ■ – – 0
1)
Available for 3 and 8-series ETUs
Protective No protection A
function Line protection Without neutral conductor protection E
thermal-mag 50% neutral conductor protection F
netic, neutral 100% neutral conductor protection G
conductor
protection
The structure shown below is intended as an overview of each position and its meaning.
For a complete and valid configuration of your molded case circuit breaker, please use our online
configurator at www.siemens.com/lowvoltage/3va-configurator
4 5 6 7 8 9 10 11 12
3VA – – 0AA0
2
Trip units Thermal-magnetic 1
Electronic 2
3VA11
3VA12
3VA13
3VA14
3VA15
3VA21
3VA22
3VA23
3VA24
3VA25
Size (SZ) 160 A ■ – – – – ■ – – – – 1
250 A – ■ – – – – ■ – – – 2
400 A – – ■ – – – – ■ – – 3
630 A – – – ■ – – – – ■ – 4
1000 A – – – – ■ – – – – ■ 5
Short-circuit 55 kA ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ 5
breaking 70 kA ■ ■ ■ ■ ■ – – – – – 6
capacity 110 kA – – ■ ■ ■ ■ ■ ■ ■ ■ 7
Icu = Ics at 415 V
200 kA – – – – – ■ ■ ■ ■ – 0
4 5 6 7 8 9 10 11 12
3VA – – 0AA0
2
3VA11
3VA12
3VA13
3VA14
3VA15
3VA21
3VA22
3VA23
3VA24
3VA25
Protective Starter protection ■ – – – – – – – – – TM110M FM M G
function ■ ■ ■ ■ ■ – – – – – TM120M AM M H
thermal-
magnetic
Internal accessories
Auxiliary switches and alarm switches
For a complete and valid configuration of your molded case circuit breaker, please use our online
configurator at www.siemens.com/lowvoltage/3va-configurator
3VA20
3VA21
2 3VA22
3VA23
3VA12 3VA24
3VA13 3VA25
3VA10 3VA11 3VA14 3VA15 3VA26
Auxiliary switches AUX
• Used to signal the position of the main contacts of
the molded case circuit breaker
• The contacts of the auxiliary switch and the molded
case circuit breaker close in unison
Type Width Ie Ue AC/DC Version
HQ 7 mm 6A 240 V/250 V Standard 3VA9988-0AA12
(1 slot) <1 A 24 V/24 V Electronic- 3VA9988-0AA13
compatible
HP 14 mm 10 A 600 V/250 V Standard – 3VA9988-0AA11
(2 slots)
Leading changeover switches LCS
• Used for load shedding, for example
• Signal the opening of the main contacts with a lead
time of 20 ms in advance of molded case circuit
breaker trips
Type Width Ie Ue AC/DC Version
HQ 7 mm 6A 240 V/250 V Standard – 3VA9988-0AA22
(1 slot) <1 A 24 V/24 V Electronic- – 3VA9988-0AA23
compatible
HP 14 mm 10 A 600 V/250 V Standard – 3VA9988-0AA21
(2 slots)
Trip alarm switches TAS
• Signal every circuit breaker tripping operation
• Are actuated whenever the molded case circuit
breaker switches to the TRIP position
Type Width Ie Ue AC/DC Version
HQ 7 mm 6A 240 V/250 V Standard 3VA9988-0AB12
(1 slot) <1 A 24 V/24 V Electronic- 3VA9988-0AB13
compatible
HP 14 mm 10 A 600 V/250 V Standard – 3VA9988-0AB11
(2 slots)
Short circuit alarm switches SAS
• Signal tripping operations only if they have been
initiated by a short circuit
• The tripping operation must be reset by deliberate
acknowledgement of the fault before the molded
case circuit breaker can be switched to ON again
Type Width Ie Ue AC/DC Version
HQ 7 mm 6A 240 V/250 V Standard 3VA9988-0AB32 3VA9988-0AB32 3VA9988-0AB34 – –
(1 slot) <1 A 24 V/24 V Electronic- 3VA9988-0AB33 3VA9988-0AB33 3VA9988-0AB35 – –
compatible
Electrical alarm switches EAS
• Are actuated as soon as the main contacts of the
molded case circuit breaker open in the event that
the breaker is tripped by the ETU
Type Width Ie Ue AC/DC Version
HQ 7 mm 6A 240 V/250 V Standard – – – – 3VA9988-0AB22
(1 slot) <1 A 24 V/24 V Electronic- – – – – 3VA9988-0AB23
compatible
Auxiliary releases
For a complete and valid configuration of your molded case circuit breaker, please use our online
configurator at www.siemens.com/lowvoltage/3va-configurator
3VA10
3VA11 3VA20 2
3VA12 3VA21
3VA13 3VA22
3VA14 3VA23 3VA25
3VA15 3VA24 3VA26
Shunt trips left STL
• Used for remote-controlled tripping of the molded case circuit breaker
• Have particularly low power consumption
• Especially suitable for electrical interlocking in the EI variant 1)
Version Ue 50/60 Hz AC Ue DC
Standard – 12 V 3VA9988-0BL10
24 V 24 … 30 V 3VA9988-0BL30
48 … 60 V 48 … 60 V 3VA9988-0BL31
110 … 127 V 110 … 127 V 3VA9988-0BL32
208 … 277 V 220 … 250 V 3VA9988-0BL33
380 … 600 V – 3VA9988-0BL20
Electrical (EI) – 24 V 3VA9988-0BM10
Shunt trips flexible STF
• Used for remote-controlled tripping of the molded case circuit breaker
• Flexible installation
Ue 50/60 Hz AC Ue DC
24 V – – 3VA9988-0BA20 –
48 … 60 V – – 3VA9988-0BA21 –
110 … 127 V – – 3VA9988-0BA22 –
208 … 277 V – – 3VA9988-0BA23 –
380 … 500 V – – 3VA9988-0BA24 –
600 V – – 3VA9988-0BA25 –
Universal releases UNI
• Combination of shunt trip and undervoltage release
Ue 50/60 Hz AC Ue DC
– 12 V 3VA9908-0BD11
24 V 3VA9908-0BD12
48 V 3VA9908-0BD13
Undervoltage releases UVR
• Trip the molded case circuit breaker in the event that the rated
operational voltage of a monitored circuit drops below a minimum
permissible limit or fails altogether
Ue 50/60 Hz AC Ue DC
– 12 V 3VA9908-0BB10
24 V 3VA9908-0BB11
48 V 3VA9908-0BB12
60 V 3VA9908-0BB13
125 … 127 V 3VA9908-0BB14
220 … 230 V 3VA9908-0BB15
250 V 3VA9908-0BB16
24 V – 3VA9908-0BB20
48 V – 3VA9908-0BB21
60 V – 3VA9908-0BB22
110 V – 3VA9908-0BB23
120 … 127 V – 3VA9908-0BB24
208 … 230 V – 3VA9908-0BB25
380 … 400 V – 3VA9908-0BB26
440 … 480 V – 3VA9908-0BB27
Time-delay devices for undervoltage releases
Ue 50/60 Hz AC Ue DC
110 V 110 V 3VA9988-0BF21
230 V 230 V 3VA9988-0BF22
– 24 V 3VA9988-0BF23
1)
In combination with TAS and AUX. For circuit diagrams, see the operating instructions
Manual operators
For a complete and valid configuration of your molded case circuit breaker, please use our online
configurator at www.siemens.com/lowvoltage/3va-configurator
3VA13
3VA20 3VA14 3VA15
2 3VA10 3VA21 3VA23 3VA25
3VA11 3VA12 3VA22 3VA24 3VA26
Front mounted rotary operators
• Handle
• For IEC
• Degree of protection IP30
• For 3-pole and 4-pole breakers
Version Illumination Door
kit interlock
Standard (gray) Without Without 3VA9157-0EK11 3VA9257-0EK11 3VA9267-0EK11 3VA9467-0EK11 3VA9687-0EK11
With 3VA9157-0EK21 3VA9257-0EK21 3VA9267-0EK21 3VA9467-0EK21 3VA9687-0EK21
With Without 3VA9157-0EK13 3VA9257-0EK13 3VA9267-0EK13 3VA9467-0EK13 –
With 3VA9157-0EK23 3VA9257-0EK23 3VA9267-0EK23 3VA9467-0EK23 –
EMERGENCY-OFF Without Without 3VA9157-0EK15 3VA9257-0EK15 3VA9267-0EK15 3VA9467-0EK15 3VA9687-0EK15
(red/yellow) With 3VA9157-0EK25 3VA9257-0EK25 3VA9267-0EK25 3VA9467-0EK25 3VA9687-0EK25
With Without 3VA9157-0EK17 3VA9257-0EK17 3VA9267-0EK17 3VA9467-0EK17 –
With 3VA9157-0EK27 3VA9257-0EK27 3VA9267-0EK27 3VA9467-0EK27 –
Door mounted rotary operators with tolerance compensation
• Shaft 300 mm
(325 mm for 3VA15/3VA25/3VA26)
• With mounting tolerance compensation
• Handle with masking plate 75 × 75 mm
(100 × 100 mm for 3VA15/3VA25/3VA26)
• Degree of protection IP65
• For 3-pole and 4-pole breakers
Version Illumination Door
kit interlock
Standard (gray) Without With 3VA9157-0FK21 3VA9257-0FK21 3VA9267-0FK21 3VA9467-0FK21 3VA9687-0FK21
With With 3VA9157-0FK23 3VA9257-0FK23 3VA9267-0FK23 3VA9467-0FK23 3VA9687-0FK23
3VA13
3VA20 3VA14 3VA15
3VA10 3VA21 3VA23 3VA25 2
3VA11 3VA12 3VA22 3VA24 3VA26
Side wall mounted rotary operators
• Rotary operator with shaft 300 mm
• Handle with masking plate 75 × 75 mm
• Degree of protection IP65
• For 3-pole and 4-pole breakers
Version Mounting Illumination
bracket kit
Standard Without Without 3VA9157-0PK11 3VA9257-0PK11 3VA9267-0PK11 3VA9467-0PK11 –
(gray) With 3VA9157-0PK13 3VA9257-0PK13 3VA9267-0PK13 3VA9467-0PK13 –
EMERGENCY-OFF Without Without 3VA9157-0PK15 3VA9257-0PK15 3VA9267-0PK15 3VA9467-0PK15 –
(red/yellow) With 3VA9157-0PK17 3VA9257-0PK17 3VA9267-0PK17 3VA9467-0PK17 –
Side wall mounted rotary operators with mounting bracket
• Rotary operator with short shaft and mounting
bracket for mounting directly on the side wall
• Handle with masking plate 75 × 75 mm
• Degree of protection IP65
• For 3-pole and 4-pole breakers
Version Mounting Illumination
bracket kit
Standard With Without 3VA9157-0PK51 3VA9257-0PK51 3VA9267-0PK51 – –
(gray) With 3VA9157-0PK53 3VA9257-0PK53 3VA9267-0PK53 – –
EMERGENCY-OFF With Without 3VA9157-0PK55 3VA9257-0PK55 3VA9267-0PK55 – –
(red/yellow) With 3VA9157-0PK57 3VA9257-0PK57 3VA9267-0PK57 – –
Extended DIN rail for N/PE terminals
Version Rated current
For mounting ≤250 A 3VA9987-0GL30 3VA9987-0GL30 3VA9987-0GL30 – –
bracket
Manual operators
For a complete and valid configuration of your molded case circuit breaker, please use our online
configurator at www.siemens.com/lowvoltage/3va-configurator
3VA13
3VA20 3VA14 3VA15
2 3VA10 3VA21 3VA23 3VA25
3VA11 3VA12 3VA22 3VA24 3VA26
Supplementary handles for door mounted rotary operators
• For operation when control cabinet door is open
Version
Standard 3VA9287-0GC01 3VA9287-0GC01 3VA9487-0GC01 3VA9487-0GC11 3VA9687-0GC01
(gray)
EMERGENCY-OFF 3VA9287-0GC05 3VA9287-0GC05 3VA9487-0GC05 3VA9487-0GC15 3VA9687-0GC05
(red/yellow)
Handles
• With masking plate
Version Tolerance compensation
Standard With 8UD1721-0AB21 8UD1731-0AB21 8UD1741-0AB21
(gray) Without 8UD1721-0AB11 8UD1731-0AB11 8UD1741-0AB11
EMERGENCY-OFF With 8UD1721-0AB25 8UD1731-0AB25 8UD1741-0AB25
(red/yellow) Without 8UD1721-0AB15 8UD1731-0AB15 8UD1741-0AB15
Handle lever extensions
• Note: The handle lever extension is already
included in the scope of supply of the
breakers.
– – – 3VA9487-0SC10 3VA9987-0SC10
Shafts
Type Length
8 × 8 mm 300 mm 8UD1900-2WA00 –
600 mm 8UD1900-2WB00 –
12 × 12 mm 300 mm – – – – 8UD1900-4WA00
600 mm – – – – 8UD1900-4WB00
Adapters for shafts
Type Use
8 × 8 mm With door mounted rotary 8UD1900-2DA00 –
operator and side wall
mounted rotary operator
Door couplings
Type
8 × 8 mm 8UD1900-2HA00 –
12 × 12 mm – – – – 8UD1900-4HA00
3VA13
3VA20 3VA14 3VA15
3VA10 3VA21 3VA23 3VA25 2
3VA11 3VA12 3VA22 3VA24 3VA26
Mounting tolerance compensations
Type
8 × 8 mm 8UD1900-2GA00 –
12 × 12 mm – – – – 8UD1900-4GA00
Manual operators
For a complete and valid configuration of your molded case circuit breaker, please use our online
configurator at www.siemens.com/lowvoltage/3va-configurator
3VA20
3VA21
2 3VA10 3VA22
3VA11 3VA13 3VA23 3VA25
3VA12 3VA14 3VA15 3VA24 3VA26
Labeling plates for manual operators
3VA9087-0SX10
Motor operators
For a complete and valid configuration of your molded case circuit breaker, please use our online
configurator at www.siemens.com/lowvoltage/3va-configurator
2
Side mounted motor operators without stored energy mechanisms (MO310)
• Cover size 45 mm
Addressable via Isolating features in Make time, typically Break time, typically Rated
control signals accordance with For 3VA1 For 3VA2 For 3VA1 For 3VA2 operational
IEC/EN 60947-1 power
■ ■ <300 ms – <300 ms – 250 W,
max. 500 W
(60 ms)
3VA20
3VA21 3VA13 3VA23
3VA10 3VA11 3VA12 3VA22 3VA14 3VA24 2
– – – 3VA9267-0HC00 – –
– – – 3VA9267-0HC05 – –
1)
For 3VA13 and 3VA14 (IEC) with product version < *E04* and for 3VA23 and 3VA24 (IEC) with product version < *E06*, the service life (mechanical operating cycles) of the molded
case circuit breaker is reduced when the SEO520 is used. For newer product versions, this is not the case. We recommend upgrading the circuit breaker to a higher product version,
if necessary.
Reset mode
All motor operators have the following reset modes:
Reset mode 1: Automatic reset
Reset mode 2: Reset via OFF-signal
The motor operator with SEO520 stored energy operator additionally has:
Reset mode 3: Reset via OFF-signal with additional acknowledge signal
Connection technology
1 For mounting onto the circuit breaker
I201_20321
1 1
2 For mounting on plug-in and withdrawable
2 2 units
For a complete and valid configuration of your molded case circuit breaker, please use our online
configurator at www.siemens.com/lowvoltage/3va-configurator
2
Box terminals
Connection options Scope of supply Cable cross-section,
copper stranded
➀ ➁ 3 single terminals 1.5 … 70 mm²
6 … 120 mm²
25 … 185 mm²
50 … 185 mm²
35 … 300 mm²
➀ ➁ 4 single terminals 1.5 … 70 mm²
6 … 120 mm²
25 … 185 mm²
50 … 185 mm²
35 … 300 mm²
Nut keeper kits
Connection options Scope of supply Max. tap width Max. tap thickness
➀ ➁ 3 terminals 17 mm 6.5 mm
25 mm 8 mm
35 mm 10 mm
Nut keeper kit for 3-pole 50 mm 25 mm
breakers, 1 terminal cover
➀ ➁ 4 terminals 17 mm 6.5 mm
25 mm 8 mm
35 mm 10 mm
Nut keeper kit for 4-pole 50 mm 28 mm
breakers, 1 terminal cover
Circular conductor terminals, 1 cable
Connection options Scope of supply Cable cross-section Copper/aluminum stranded
Cu Al
➀ ➁ 3 single terminals 1.5 … 10 mm² ■ –
1.5 … 50 mm² ■ –
10 … 95 mm² ■ ■
16 … 185 mm² ■ ■ 4)
35 … 185 mm² ■ ■
50 … 300 mm² ■ ■ 3)
➀ ➁ 4 single terminals 1.5 … 10 mm² ■ –
1.5 … 50 mm² ■ –
10 … 95 mm² ■ ■
16 … 185 mm² ■ ■ 4)
35 … 185 mm² ■ ■
50 … 300 mm² ■ ■ 3)
1)
Maximum current-carrying capacity of cable connection 400 A
Flexible copper bar: No restrictions
2)
Maximum current-carrying capacity of cable connection 400 A
3)
Al cable only tested according to UL486 A/B
4)
Use antioxidants
3VA13
3VA14
3VA10 3VA20 3VA23 3VA15
2
3VA11 3VA12 3VA21 3VA22 3VA24 3VA25
3VA9153-0JA11 – – – – –
– 3VA9253-0JA11 3VA9163-0JA12 3VA9163-0JA12 – –
– – 3VA9263-0JA12 3VA9263-0JA12 – –
– 3VA9253-0JA12 – – – –
– – – – 3VA9483-0JA13 1) –
3VA9154-0JA11 – – – – –
– 3VA9254-0JA11 3VA9164-0JA12 3VA9164-0JA12 – –
– – 3VA9264-0JA12 3VA9264-0JA12 – –
– 3VA9254-0JA12 – – – –
– – – – 3VA9484-0JA13 1) –
3VA9113-0QA00 – – – – –
– 3VA9213-0QA00 3VA9203-0QA00 3VA9203-0QA00 – –
– – – – 3VA9403-0QA00 –
– – – – – 3VA9603-0QA00
3VA9114-0QA00 – – – – –
– 3VA9214-0QA00 3VA9204-0QA00 3VA9204-0QA00 – –
– – – – 3VA9404-0QA00 –
– – – – – 3VA9604-0QA00
3VA9113-0JB10 – – – – –
– – 3VA9103-0JB11 3VA9103-0JB11 – –
3VA9113-0JB11 – – – – –
– – 3VA9263-0JB12 3VA9263-0JB12 – –
– 3VA9253-0JB12 – – – –
– – – – 3VA9383-0JB13 2) –
3VA9114-0JB10 – – – – –
– – 3VA9104-0JB11 3VA9104-0JB11 – –
3VA9114-0JB11 – – – – –
– – 3VA9264-0JB12 3VA9264-0JB12 – –
– 3VA9254-0JB12 – – – –
– – – – 3VA9384-0JB13 2) –
Connection technology
1 For mounting onto the circuit breaker
I201_20321
1 1
2 For mounting on plug-in and withdrawable
2 2 units
For a complete and valid configuration of your molded case circuit breaker, please use our online
configurator at www.siemens.com/lowvoltage/3va-configurator
2
Circular conductor terminals with control wire taps, 1 cable 2)
Connection options Scope of supply Cable cross-section Copper/aluminum stranded
Cu Al
➀ ➁ 3 single terminals 1.5 … 10 mm² ■ –
1.5 … 50 mm² ■ –
10 … 95 mm² ■ ■
16 … 185 mm² ■ ■ 4)
50 … 185 mm² ■ ■
50 … 300 mm² ■ ■ 3)
➀ ➁ 4 single terminals 1.5 … 10 mm² ■ –
1.5 … 50 mm² ■ –
10 … 95 mm² ■ ■
16 … 185 mm² ■ ■ 4)
50 … 185 mm² ■ ■
50 … 300 mm² ■ ■ 3)
Circular conductor terminals, 2 cables
Connection options Scope of supply Cable cross-section Copper/aluminum stranded 3) Control wire tap
Cu Al
➀ ➁ 3 single terminals, 120 … 300 mm² ■ ■ No
1 short terminal cover Yes 2)
1)
Maximum current-carrying capacity of copper cables 380 A 2)
Maximum current-carrying capacity 15 A 3)
Al cable only tested according to UL 486 A/B
Maximum current-carrying capacity of aluminum cables 310 A Maximum cable connection up to 2.5 mm2 4)
Use antioxidants
3VA13
3VA14
3VA10 3VA20 3VA23 3VA15
2
3VA11 3VA12 3VA21 3VA22 3VA24 3VA25
3VA9113-0JG10 – – – – –
– – 3VA9103-0JG11 3VA9103-0JG11 – –
3VA9113-0JG11 – – – – –
– – 3VA9263-0JG12 3VA9263-0JG12 – –
– 3VA9253-0JG12 – – – –
– – – – 3VA9383-0JG13 1) –
3VA9114-0JG10 – – – – –
– – 3VA9104-0JG11 3VA9104-0JG11 – –
3VA9114-0JG11 – – – – –
– – 3VA9264-0JG12 3VA9264-0JG12 – –
– 3VA9254-0JG12 – – – –
– – – – 3VA9384-0JG13 1) –
– – – – – 3VA9503-0JB23
– – – – – 3VA9503-0JG23
– – – – – 3VA9504-0JB23
– – – – – 3VA9504-0JG23
– – – – – 3VA9503-0JB32
– – – – – 3VA9503-0JG32
– – – – – 3VA9504-0JB32
– – – – – 3VA9504-0JG32
Connection technology
1 For mounting onto the circuit breaker
I201_20321
1 1
2 For mounting on plug-in and withdrawable
2 2 units
For a complete and valid configuration of your molded case circuit breaker, please use our online
configurator at www.siemens.com/lowvoltage/3va-configurator
Note:
All bus connectors, bus connectors broadened and rear connections are Cu/Sn 6 r plated according to ISO 2093.
2
Front bus connectors
Number of poles Connection options Scope of supply Max. tap width Max. tap thickness
1P ➀ – 1 terminal 22 mm 8 mm
3P – ➁ 3 terminals 6 × 50 mm 8 mm
4P ➀ ➁ 4 terminals, 22 mm 8 mm
3 phase barriers 32 mm 10 mm
40 mm 12.5 mm
50 mm 28 mm
4P ➀ ➁ 4 terminals, 20 mm 6 mm
3 phase barriers 25 mm 7 mm
40 mm 8 mm
– ➁ 3 terminals, 80 mm 15 mm
2 Phase barriers
4P ➀ ➁ 4 terminals, 30 mm 8 mm
3 phase barriers 35 mm 10 mm
60 mm 12.5 mm
80 mm 10 mm
3VA13
3VA20 3VA14
3VA10 3VA21 3VA23 3VA15 2
3VA11 3VA12 3VA22 3VA24 3VA25 3VA26
3VA9151-0QB00 – – – – –
– – – – 3VA9603-0QB01 –
3VA9153-0QB00 – – – – –
– 3VA9253-0QB00 3VA9263-0QB00 – – –
– – – 3VA9483-0QB00 – –
– – – – 3VA9603-0QB00 –
3VA9154-0QB00 – – – – –
– 3VA9254-0QB00 3VA9264-0QB00 – – –
– – – 3VA9484-0QB00 – –
– – – – 3VA9604-0QB00 –
3VA9153-0QD00 – – – – –
– 3VA9253-0QD00 3VA9263-0QD00 – – –
– – – 3VA9483-0QD00 – –
3VA9154-0QD00 – – – – –
– 3VA9254-0QD00 3VA9264-0QD00 – – –
– – – 3VA9484-0QD00 – –
3VA9153-0QC00 – – – – –
– 3VA9253-0QC00 3VA9263-0QC00 – – –
– – – 3VA9483-0QC00 – –
– – – – 3VA9603-0QC00 –
– – – – 3VA9603-0QC01 3VA9603-0QC01
3VA9154-0QC00 – – – – –
– 3VA9254-0QC00 3VA9264-0QC00 – – –
– – – 3VA9484-0QC00 – –
– – – – 3VA9604-0QC00 –
Connection technology
1 For mounting onto the circuit breaker
I201_20321
1 1
2 For mounting on plug-in and withdrawable
2 2 units
For a complete and valid configuration of your molded case circuit breaker, please use our online
configurator at www.siemens.com/lowvoltage/3va-configurator
Note:
All bus connectors, bus connectors broadened and rear connections are Cu/Sn 6 r plated according to ISO 2093.
2
Nut keeper kits, right-angled 1)
Number of poles Connection options Scope of supply Max. tap width Max. tap thickness
3P ➀ ➁ 3 terminals, 22 mm 8 mm
2 phase barriers 32 mm 10 mm
40 mm 12.5 mm
4P ➀ ➁ 4 terminals, 22 mm 8 mm
3 phase barriers 32 mm 10 mm
40 mm 12.5 mm
1)
Can only be connected to breaker side N, 1, 3, 5
3VA13
3VA20 3VA14
3VA10 3VA21 3VA23 3VA15 2
3VA11 3VA12 3VA22 3VA24 3VA25
3VA9113-0QG00 – – – –
– 3VA9213-0QG00 3VA9223-0QG00 – –
– – – 3VA9403-0QG00 –
3VA9114-0QG00 – – – –
– 3VA9214-0QG00 3VA9224-0QG00 – –
– – – 3VA9404-0QG00 –
– – – – 3VA9603-0QE01
3VA9114-0QE00 3VA9214-0QE00 3VA9204-0QE00 3VA9404-0QE00 –
Connection technology
1 For mounting onto the circuit breaker
I201_20321
1 1
2 For mounting on plug-in and withdrawable
2 2 units
For a complete and valid configuration of your molded case circuit breaker, please use our online
configurator at www.siemens.com/lowvoltage/3va-configurator
2
Circular conductor terminals, 2P
Connection options Scope of supply Number of cables Cable cross-section Cu/Al stranded Control wire tap
Cu Al
➀ – 2 single terminals, 1 25 … 150 mm² ■ ■ 3) Yes 1)
1 extended terminal cover, No
1 insulation plate 6 1.5 … 35 mm² ■ – No
3VA13
3VA20 3VA14
3VA10 3VA21 3VA23 3VA15
2
3VA11 3VA12 3VA22 3VA24 3VA25
3VA9112-0JC12 – – – –
3VA9112-0JJ12 – – – –
3VA9112-0JF60 – – – –
3VA9113-0JC12 – – – –
3VA9113-0JJ12 – – – –
– 3VA9213-0JC13 3VA9223-0JC13 – –
– 3VA9213-0JJ13 3VA9223-0JJ13 – –
– 3VA9213-0JC22 3VA9223-0JC22 – –
– 3VA9213-0JJ22 3VA9223-0JJ22 – –
– – – 3VA9403-0JC23 –
– – – 3VA9403-0JJ23 –
– – – – 3VA9603-0JC43
– – – – 3VA9603-0JJ43
– – – – 3VA9603-0JC44
– – – – 3VA9603-0JJ44
3VA9113-0JF60 3VA9213-0JF60 3VA9223-0JF60 3VA9303-0JF60 –
3VA9153-0JC12 – – – –
– 3VA9253-0JC13 3VA9263-0JC13 – –
– 3VA9253-0JC22 3VA9263-0JC22 – –
– – – 3VA9483-0JC23 –
– – – – 3VA9603-0JJ25
– – – – 3VA9603-0JJ35
– – – – 3VA9603-0JJ45
3VA9153-0JF60 3VA9253-0JF60 3VA9263-0JF60 3VA9383-0JF60 –
3VA9114-0JC12 – – – –
3VA9114-0JJ12 – – – –
– 3VA9214-0JC13 3VA9224-0JC13 – –
– 3VA9214-0JJ13 3VA9224-0JJ13 – –
– 3VA9214-0JC22 3VA9224-0JC22 – –
– 3VA9214-0JJ22 3VA9224-0JJ22 – –
– – – 3VA9404-0JC23 –
– – – 3VA9404-0JJ23 –
– – – – 3VA9604-0JC43
– – – – 3VA9604-0JJ43
– – – – 3VA9604-0JC44
– – – – 3VA9604-0JJ44
3VA9114-0JF60 3VA9214-0JF60 3VA9224-0JF60 3VA9304-0JF60 –
3VA9154-0JC12 – – – –
– 3VA9254-0JC13 3VA9264-0JC13 – –
– 3VA9254-0JC22 3VA9264-0JC22 – –
– – – 3VA9484-0JC23 –
3VA9154-0JF60 3VA9254-0JF60 3VA9264-0JF60 3VA9384-0JF60 –
Connection technology
1 For mounting onto the circuit breaker
I201_20321
1 1
2 For mounting on plug-in and withdrawable
2 2 units
For a complete and valid configuration of your molded case circuit breaker, please use our online
configurator at www.siemens.com/lowvoltage/3va-configurator
2 3VA10 3VA11
Terminal covers specially for fixed-mounted units
Version Number of poles Mounting location
Short 1P ➀ – – 3VA9111-0WD10
2P ➀ – – 3VA9111-0WD20
3P ➀ – 3VA9111-0WD30 3VA9111-0WD30
4P ➀ – 3VA9111-0WD40 3VA9111-0WD40
Intermediate 3P ➀ – – –
4P ➀ – – –
Extended 1) 2P ➀ – – 3VA9111-0WF20
3P ➀ – 3VA9111-0WF30 3VA9111-0WF30
4P ➀ – 3VA9111-0WF40 3VA9111-0WF40
4P ➀ – 3VA9111-0WG40 3VA9111-0WG40
Extended 1) 3P – ➁ – 3VA9153-0KB04
– ➁ – 3VA9154-0KB04
Broadened 1) 3P – ➁ – 3VA9153-0KB05
4P – ➁ – 3VA9154-0KB05
1)
Including insulating plate
2)
Suitable for circular conductor terminals 2/4 cables
3VA13
3VA20 3VA14
3VA21 3VA23 3VA15
3VA12 3VA22 3VA24 3VA25 2
– – – –
– – – –
3VA9211-0WD30 3VA9221-0WD30 3VA9481-0WD30 3VA9601-0WD30
3VA9211-0WD40 3VA9221-0WD40 3VA9481-0WD40 3VA9601-0WD40
– – – 3VA9601-0WE30 2)
– – – 3VA9601-0WE40 2)
– – – –
3VA9211-0WF30 3VA9221-0WF30 3VA9481-0WF30 3VA9601-0WF30
3VA9211-0WF40 3VA9221-0WF40 3VA9481-0WF40 3VA9601-0WF40
Connection technology
1 For mounting onto the circuit breaker
I201_20321
1 1
2 For mounting on plug-in and withdrawable
2 2 units
For a complete and valid configuration of your molded case circuit breaker, please use our online
configurator at www.siemens.com/lowvoltage/3va-configurator
2
3VA10 3VA11
Insulating plates
Version Number of poles Mounting location
Standard 2P ➀ – – 3VA9111-0WJ20
3P ➀ – 3VA9111-0WJ30 3VA9111-0WJ30
4P ➀ – 3VA9111-0WJ40 3VA9111-0WJ40
Broadened 3P ➀ – 3VA9111-0WK30 3VA9111-0WK30
4P ➀ – 3VA9111-0WK40 3VA9111-0WK40
Phase barriers
Mounting location Scope of supply
➀ ➁ 2 phase barriers 3VA9152-0WA00
– ➁ 2 phase barriers –
DC insulation plates for 3VA1 for fixed-mounted molded case circuit breakers
Number of poles
3P 3VA9113-0SG10
4P 3VA9114-0SG10
Side plates for 3VA1 for fixed-mounted molded case circuit breakers
Number of poles Mounting
2P On 2-pole molded case circuit breakers – 3VA9112-0SG20
3VA13
3VA20 3VA14
3VA21 3VA23 3VA15 2
3VA12 3VA22 3VA24 3VA25 3VA26
– – – – –
3VA9211-0WJ30 3VA9221-0WJ30 3VA9481-0WJ30 – –
3VA9211-0WJ40 3VA9221-0WJ40 3VA9481-0WJ40 – –
3VA9211-0WK30 3VA9221-0WK30 3VA9481-0WK30 – –
3VA9211-0WK40 3VA9221-0WK40 3VA9481-0WK40 – –
– – – 3VA9603-0WH05 –
– – – – –
– – – – –
– – – – –
For a complete and valid configuration of your molded case circuit breaker, please use our online
configurator at www.siemens.com/lowvoltage/3va-configurator
3VA13
3VA20 3VA14 3VA15
3VA21 3VA23 3VA25
3VA11 3VA12 3VA22 3VA24 3VA26
Withdrawable units, complete kits
• Scope of supply:
− Withdrawable socket
− Withdrawable unit, conversion kit
− Mounting screw kit
• Note: The crank for the withdrawable
unit must be ordered separately.
Number of poles
3P – 3VA9213-0KD00 3VA9123-0KD00 3VA9323-0KD00 –
4P – 3VA9214-0KD00 3VA9124-0KD00 3VA9324-0KD00 –
Withdrawable units, conversion kits
• Scope of supply:
− Screw-fastened terminal covers for
molded case circuit breakers
− Side panels
− Plug-in contacts
− Cable cages
− Autotrip plunger
• Note: The crank for the withdrawable
unit must be ordered separately.
Number of poles
3P – 3VA9213-0KD10 3VA9123-0KD10 3VA9323-0KD10 –
4P – 3VA9214-0KD10 3VA9124-0KD10 3VA9324-0KD10 –
3VA13
3VA20 3VA14 3VA15
3VA21 3VA23 3VA25
3VA11 3VA12 3VA22 3VA24 3VA26
Plug-in units, complete kits
• Scope of supply:
− Plug-in socket
− Plug-in unit, conversion kit
2
− Mounting screw kit
• Note on 3VA9603-0KP00:
− The circuit breaker must be
equipped with additional threaded
holes for installing the compo-
nents of the plug-in unit. When
ordering the circuit breaker,
specify "with plug-in" accordingly.
− An undervoltage release (UVR)
(article number 3VA9908-0BB..) is
required in the circuit breaker in
order to provide the protection trip
specified in the standard for
unplugging the circuit breaker
under load. The required UVR
voltage version must be ordered in
addition.
Number of poles
3P 3VA9113-0KP00 3VA9213-0KP00 3VA9123-0KP00 3VA9323-0KP00 3VA9603-0KP00
4P 3VA9114-0KP00 3VA9214-0KP00 3VA9124-0KP00 3VA9324-0KP00 –
Plug-in units, conversion kits
• Scope of supply:
− Screw-fastened terminal covers for
molded case circuit breakers
− Plug-in contacts
− Cable cages
− Autotrip plunger
Number of poles
3P 3VA9113-0KP10 3VA9213-0KP10 3VA9123-0KP10 3VA9323-0KP10 –
4P 3VA9114-0KP10 3VA9214-0KP10 3VA9124-0KP10 3VA9324-0KP10 –
Plug-in units, conversion kits with blade contacts
• Scope of supply:
− 6× blade contacts
− Guide frame for circuit breaker
− 2× cover for blade contacts
− Position signaling switch
− Connecting cable for auxiliary
circuits
• Note: The circuit breaker must be
equipped with additional threaded
holes for installing the components
of the plug-in unit. When ordering
the circuit breaker, specify "with
plug-in" accordingly.
Number of poles
3P – – – – 3VA9603-0KP10
For a complete and valid configuration of your molded case circuit breaker, please use our online
configurator at www.siemens.com/lowvoltage/3va-configurator
3VA13
3VA20 3VA14 3VA15
2 3VA11 3VA12
3VA21
3VA22
3VA23
3VA24
3VA25
3VA26
Cable cages for plug-in/withdrawable units (spare part)
• For routing of the required cables
from the internal accessories on the
back of the circuit breaker
Number of poles
3P/4P 3VA9157-0KB02 3VA9257-0KB02 3VA9167-0KB02 3VA9367-0KB02 –
Door feedthroughs
3VA13
3VA20 3VA14 3VA15
3VA21 3VA23 3VA25
Accessories 3VA11 3VA12 3VA22 3VA24 3VA26
Communications interface for withdrawable unit
Scope of supply
Set of cables with three special position 3VA9987-0KC00 3VA9987-0KC00 3VA9987-0KC00 3VA9987-0KC00 –
2
signaling switches,
3VA9987-0KC10 connecting cables
2 Residual current devices (RCD) for switch disconnectors and molded case circuit breakers
• Mounted onto the side (left)
Number Type Sensitivity 3) Rated Limit value of Rated Fault Pre-alarm Trip alarm
of poles residual non-tripping operational current
response time voltage Ue frequency
current IΔn Δt NC NC
COM TRIP COM
NO
COM NO
COM
3-pole RCD510 Type A 0.03 ... 5 A 0…3s 127 ... 480 V AC 50/60 Hz 1 – – ■ ■ –
4-pole RCD310 Type A 0.03 ... 5 A Instantaneous 127 ... 480 V AC 50/60 Hz 1 – – ■ ■ –
RCD510 Type A 0.03 ... 5 A 0…3s 127 ... 480 V AC 50/60 Hz 1 – – ■ ■ –
1)
3-pole version in 4-pole enclosure
2)
With energy infeed from below, the required auxiliary switch (AUX) must be ordered separately
3)
Type A: pulse current sensitive, type B/B+: universal current sensitive
4)
Sensitivity selectable for type B/B+
5)
I Δn = 30A: type AC
6)
If the molded case circuit breaker has no box terminals as connections, a set of box terminals must be ordered additionally for the taps below the thermal-magnetic trip units.
7)
1 set of box terminals is included in scope of supply of the RCD510 (3VA921.-0RS20).
Modular residual current devices type A/B (according to IEC 60947-2 Annex M),
see monitoring devices, from page 11/1 onwards
3VA10
3VA13
3VA14
3VA15
3VA20 3VA25
3VA11 3VA12 3VA21 3VA22 3VA23 3VA24 3VA26
2
Monitoring Remote Commu-
mode (trip- test/ nication-
ping can be remote capable
disabled as reset
an option)
■ – – 3VA9113-0RS20 6) 3VA9213-0RS20 7) – – – – –
■ – – 3VA9114-0RS10 6) – – – – – –
■ – – 3VA9114-0RS20 6) 3VA9214-0RS20 7) – – – – –
3VA9988-0BR10 3VA9988-0BR10 – – – – –
Communication
2 Average value over the three phase currents ILAVG= (I1 + I2 + I3)/3 A – ■ – □ ■
Asymmetry of the phase currents Inba % – ■ – □ ■
THD of the 3 phases THDI1, THDI2, THDI3 % – ■ – □ ■
Voltage
Phase voltages incl. average value U12, U23, U31, Uphavg V – ■ □ □ ■
Voltages to N conductor incl. average value U1N, U2N, U3N, UNavg V – ■ – □ ■
Voltage unbalance % – ■ – □ ■
THD phase/phase and phase/N THDI1, THDI2, THDI3 % – ■ – □ ■
Power
Active power, total and per phase P1, P2, P3, Ptot kW – ■ □ (Ptot) □ ■
Apparent power, total and per phase S1, S2, S3, Stot kVA – ■ – □ ■
Reactive power, total and per phase Q1, Q2, Q3, Qtot kVAr – ■ □ □ ■
Power factor of the fundamental PF1, PF2, PF3, PFavg – ■ □ (PFavg) □ ■
Energy
Active energy, infeed and feedback Ep kWh – ■ □ □ ■
Reactive energy, infeed and feedback Eq kVArh – ■ – □ ■
Apparent energy Es kVAh – ■ – □ ■
Frequency
Present frequency f Hz – ■ □ □ ■
Min/max pointer function
Min./max. current, voltage, power With time stamp – – – – – ■
Condition Monitoring 2)
Operating cycles counter CLOSE-OPEN cycle ■ ■ – – ■
Operating hours h ■ ■ – – ■
Trip counter Differentiated by trip ■ ■ – – ■
causes
Health indicator 3) Incl. contact state % ■ ■ ■ – ■
Remaining life time 3) Time ■ ■ – – ■
1)
Depending on ETU version
2)
Only available with continuous external power supply and COM060 and COM800/100 communication interfaces
3)
Firmware 4.4 or higher of ETU, COM060, COM800/100 required
3VA23
3VA20 3VA24
3VA21 3VA25
3VA22 3VA26
COM060 communications modules
• For mounting in the right-hand accessories compartment of the 3VA2
molded case circuit breaker (including ETU power supply)
• Including a T-Connector
Use
Communication to the COM800/COM100 data concentrator via 3VA line 3VA9187-0TB10 3VA9387-0TB10
24 V modules
• 24 V DC
• For mounting in the right-hand accessories compartment of the 3VA2
Use
Optional energy supply for the ETU, also includes continuous operation 3VA9187-0TB50 3VA9387-0TB50
of the ETU display and the measurement function of the ETU 8-series
PROFIBUS
I201_18907
Ethernet (Modbus TCP)
SIMATIC S7
PROFINET
3VA-line
T-Connector T-Connector
COM800 DSP800
breaker data server display
Communication
Data concentrator
COM800 data concentrators
Version Article No.
Central communications module for connection of up to eight 3VA2 molded case circuit breakers via the 3VA 3VA9987-0TA10
line, Ethernet 10/100 Mbps interface module socket for inserting an optional PROFIBUS DP or PROFINET
module, 2 terminating resistors
2
COM100 data concentrators
Version Article No.
Central communications module for connection of a 3VA2 molded case circuit breaker via the 3VA line, 3VA9987-0TA20
Ethernet 10/100 Mbps interface module socket for inserting an optional PROFIBUS DP or PROFINET module,
2 terminating resistors
1)
Dimensioned for device quantities of 8× 3VA and 1× 3W
&UIFSOFU*&$
356
4*$".
"
&UIFSOFU.PECVT5$1
I201_19878a
$0.
$0.
7"MJOF
7" 7"
8-
Communication
Display
DSP800 displays
Use Article No.
For displaying the status and measured values of up to eight devices 3VA9987-0TD10
• 3VA2 via COM800/100
• 3VA27
• 3WL10
• 3WL11-13
• PAC3200T
Test devices
TD300 test devices
Use Connection Article No.
For activation of the ETU and initiation On the front interface of the ETU 3VA9987-0MA10
of a test tripping operation
Connecting cables for connecting TD500 to 3VA2 molded case circuit breakers (spare part)
Article No.
3VA9987-0MY10
1)
A country-specific radio license is required to operate the Bluetooth interface.
Before activating the Bluetooth function, ensure that the license is available:
www.siemens.com/lowvoltage/certificates
3VA20
3VA21
3VA11 3VA12 3VA22
Locking
• The locking provisions make it possible to lock the 3VA molded case circuit breakers
2 in either the OFF or the ON operating position.
Version
Adapter kit for mounting the cylinder lock (type RONIS) in the accessories compartment 3VA9157-0LF10 3VA9257-0LF10 3VA9167-0LF10
of the molded case circuit breaker
Interlocking
• Using interlocking technology, it is possible to mutually interlock two or more
molded case circuit breakers.
• The interlock system is designed to ensure that no more than one molded case
circuit breaker can be operated at a time.
• The following methods of interlocking can be used on 3VA molded case
circuit breakers:
− Front interlock
− Rear interlock
Version
Mounting frame for rear interlock with rod Mounting rails 3VA9088-0VK10
Can be used with breaker 3VA15 from “E02” and 3VA25 from “E05” (Line protection CB with TMTU, 3-Series ETU and 5-Series ETU)
3VA13
3VA14 3VA15
3VA23 3VA25
3VA24 3VA26
Locking
2
Use in Locking in Locking in Front Rear Interlocked
OFF position ON position mounting mounting breakers
3VA9980-0VL10 Breakers, motor ■ ■ ■ – –
3VA9980-0VL30 operators, manual
operators, withdrawable
3VA9980-0VL40
technology
Interlocking
3VA9980-0VC10
3VA9980-0VC20
3VA9980-0VC30
3VA9468-0VK20 –
3VA10
3VA11 3VA12
Cover frames for door cut-outs for molded case circuit breakers
Number of poles Door cut-out with trip unit
2 3P No 3VA9053-0SB10 3VA9253-0SB10
Yes 3VA9053-0SB20 3VA9253-0SB20
4P No 3VA9054-0SB10 3VA9254-0SB10
Yes 3VA9054-0SB20 3VA9254-0SB20
Cover frames for RCD320, RCD520 and RCD820 residual current devices
Number of poles
3P 3VA9053-0SB10 3VA9253-0SB10
4P 3VA9054-0SB10 3VA9254-0SB10
3VA9053-0SB10 3VA9253-0SB10
– 3VA9253-0SB20
3VA9087-0SX10
3VA13
3VA20 3VA14 3VA15
3VA21 3VA23 3VA25
3VA22 3VA24 3VA26
3VA9257-0SB30 3VA9377-0SB30 –
3VA9167-0SB30 3VA9377-0SB30 –
3VA9253-0SB10 3VA9303-0SB40 –
3VA9254-0SB10 3VA9304-0SB40 –
3VA9253-0SB20 3VA9353-0SB20 –
3VA9087-0SX10
– – –
– – –
– – –
– – –
– – –
– – –
– – –
3VA9126-0SS10 – –
3VA9124-0SS10 – –
– 3VA9328-0SS10 3VA9517-0SS10
– – 3VA9603-0SS10
3VA9124-0SS10 3VA9328-0SS10 –
System overview
For a complete and valid configuration of your molded case circuit breaker, please use our online
configurator at www.siemens.com/lowvoltage/3va27-configurator
Electronic trip unit (ETU) Communications Rating plugs Breaker Connect Test devices and
module module breaker data
adapters
Rear vertical/ Rear Front Front Cable lug Phase barriers Terminal cover
horizontal broadened extended broadened
Motors Accessories
Note:
You will find a detailed range of accessories in the Accessories and spare parts section.
Auxiliary switches
2
Trip alarm switch Ready-to-close Auxiliary switch Trip alarm switch Trip alarm switch
signaling switch (RTC) ON/OFF (AUX) (S24) (TAS)
Other accessories
Interlocking sets Locking provision Locking mechanism Door sealing frame Protective cover Mechanical Manual operator
interlock
Note:
You will find a detailed range of accessories in the Accessories and spare parts section.
The structure shown below is intended as an overview of each position and its meaning.
For a complete and valid configuration of your molded case circuit breaker, please use our online
configurator at www.siemens.com/lowvoltage/3va27-configurator
6 7 8 9 10 11 12 13 14 15 16
3VA27 – –
2
Molded case circuit breakers and ETUs
Max. rated current 800 A 8 0
In max 1000 A 1 0
1250 A 1 2
1600 A 1 6
Connections
Type of mounting Withdrawable Withdrawable circuit breaker without guide frame 0
(guide frame must be ordered separately)
Fixed-mounted breaker/ Rear vertical connection 1
withdrawable breaker Rear horizontal connection 2
Front main connection 3
Front-accessible, extended main connection 5
Front-accessible, broadened main connection 6
Rear broadened bus connectors 7
6 7 8 9 10 11 12 13 14 15 16
3VA27 – –
2
Alarm switch combinations
Alarm switches Without 0
With trip alarm switch TAS
1
and trip alarm switch S25
With two leading changeover switches S26 2
With trip alarm switch TAS
and trip alarm switch S25 3
and two leading changeover switches S26
The structure shown below is intended as an overview of each position and its meaning.
For a complete and valid configuration of your molded case circuit breaker, please use our online
configurator at www.siemens.com/lowvoltage/3va27-configurator
6 7 8 9 10 11 12 13 14 15 16
3VA27 – –
2
Molded case circuit breakers and ETUs
Max. rated current 800 A 8 0
In max 1000 A 1 0
1250 A 1 2
1600 A 1 6
Connections
Type of mounting Withdrawable Withdrawable circuit breaker without guide frame 0
(guide frame must be ordered separately)
Fixed-mounted breaker/ Rear vertical connection 1
withdrawable breaker Rear horizontal connection 2
Front main connection 3
Front-accessible, extended main connection 5
Front-accessible, broadened main connection 6
Rear broadened bus connectors 7
Motor
Operating Manual operator 0
mechanisms Spring charging motor 24 ... 30 V AC/DC 1
48 ... 60 V AC/DC 2
110 V AC/DC 3
230 V AC/DC 4
6 7 8 9 10 11 12 13 14 15 16
3VA27 – –
2
Auxiliary releases, closing coils, remote reset magnets
Closing coil (CC), Without A
remote reset magnet (RR) Closing coil (CC) 24 V AC/DC B
30 V AC/DC C
48 V AC/DC D
60 V AC/DC E
110 ... 120 V AC/DC F
120 ... 127 V AC/DC G
220 ... 240 V AC/DC H
240 ... 250 V AC/DC J
Closing coil (CC) and 24 V AC/DC K
additional remote reset magnet (RR) 110 V AC/DC L
220 V AC/DC M
Accessory options
For a complete and valid configuration of your molded case circuit breaker, please use our online
configurator at www.siemens.com/lowvoltage/3va27-configurator
To specify the options, add „-Z“ to the complete article number and Order code
indicate the appropriate order code(s).
2 3VA27..-.....-.... -Z
Accessories for basic configuration
Mounting options for fixed-mounted circuit breakers
• In the basic configuration, the fixed-mounted circuit breaker is mounted onto the rear panel. Floor mounting is possible as an option. The
device must additionally be modified if it is to be extended to include functionalities such as external auxiliary switches or mechanical
interlocking mechanism.1)
Mounting options for Floor mounting Mounting support standard A07
fixed-mounted circuit Mounting support extended 2) S56
breakers1)
Rear panel mounting onto mounting plate Side wall extended 2) S57
Communications modules
• Up to 2 different communication modules can be used at the same time.
• When using an IOM040 digital I/O module (Z option K56), only 1 communication module can be used.
Communications modules COM040 PROFIBUS F02
COM041 PROFINET F03
COM043 Modbus TCP F11
COM042 Modbus RTU F12
To specify the options, add „-Z“ to the complete article number and indicate the Order code
appropriate order code(s).
3VA27..-.....-.... -Z 2
Accessories for motors
Mechanical operating cycles counter, 5-digit – C01
Locking provision Against unauthorized closing Cylinder lock, made by RONIS – S08
in the operator panel (safe OFF) For no more than 3 padlocks, plastic 4 mm – S22
For no more than 1 padlock, metal 7 mm – S23
For no more than 2 padlocks, metal 8 mm – S07
Interlocking set For mechanical ON and/or OFF on For no more than 3 padlocks, plastic 4 mm – S42
the operator panel For no more than 1 padlock, metal 7 mm – S43
For no more than 2 padlocks, metal 8 mm – S44
Guide frames
3VA27
Guide frames for ordering separately without circuit breakers
• Guide frames without breakers up to 1600 A
• Note: All CB bus modules for communication COM04x/IOM300/Breaker Connect module, as well as COMPSS
signaling switches are configured without frames in the withdrawable circuit breaker and defined there by
means of Z options, and are included with the breaker. PSS Standard is always included in the frame and
can be changed to an electronics-capable signal by means of a Z option.
2 Number of poles Connection type Article No.
3-pole Rear vertical 3VW8116-7AA01
Rear horizontal 3VW8116-7AB01
Front straight bus connectors extended 3VW8116-7AE01
Broadened bus connectors 3VW8116-7AF01
Rear broadened bus connectors 3VW8116-7AG01
4-pole Rear vertical 3VW8116-7BA01
Rear horizontal 3VW8116-7BB01
Front straight bus connectors extended 3VW8116-7BE01
Broadened bus connectors 3VW8116-7BF01
Rear broadened bus connectors 3VW8116-7BG01
To specify the options, add „-Z“ to the complete article number and Order code
indicate the appropriate order code(s).
3VW8....-.....-.... -Z
Locking mechanism To prevent movement to disconnected position (only in combination with R78 or R65) R79
Auxiliary/signaling switches
Position signaling switch PSS For 24 V DC digital signals, 2 CO | 2 CO | 2 CO (connected | test | disconnected position) K55
for guide frame for minimum currents
Auxiliary and signaling switches for currents >100 mA and up to 400 V AC are installed as standard.
For currents <100 mA for PLC connections, these auxiliary and signaling switches can be modified.
The auxiliary/signaling switches for 24 V DC digital signals are designed for
• a minimum load above 1 mA at 5 V DC, and
• a maximum breaking capacity of 100 mA at 24 V DC.
3VA27
Electronic trip units (ETU)
Version With communications/ Type Protective Article No.
measurement function, function
enhanced protective functions
With rotary switches No ETU320 LIN 3VW9011-5AA00
ETU350 LSIN 3VW9012-5AA00 2
ETU360 LSING 3VW9012-7AA00
Remote reset magnets RR for the circuit breakers including tripped signaling
• Remote reset magnet (RR) for resetting the circuit breaker after tripping as a result of overcurrent conditions
Accessory for Voltage Article No.
ETU320, ETU350, ETU360, 24 V DC – 3VW9011-0AK03
ETU650, ETU660 110 V AC/DC – 3VW9011-0AK05
250 V AC/DC – 3VW9011-0AK06
3VA27
Rating plugs
• Only one module is possible per circuit breaker.
Accessory for Version Rated current In Article No.
ETU320, ETU350, Rating plugs for setting (< In max) 400 A 3VW9011-0AA53
ETU360, ETU650, the rated current In 630 A 3VW9011-0AA55
2 ETU660
800 A 3VW9011-0AA56
1000 A 3VW9011-0AA57
1250 A 3VW9011-0AA58
1600 A 3VW9011-0AA61
ETU 6-series Rating plug without overload protection (L = OFF) 400 A 3VW9011-0LF53
and for setting (< In max) the rated current In 630 A 3VW9011-0LF55
800 A 3VW9011-0LF56
1000 A 3VW9011-0LF57
1250 A 3VW9011-0LF58
1600 A 3VW9011-0LF61
ETU660 Rating plug Rc for ETU660 for enabling of the residual 400 A 3VW9011-0RC53
current protective function and setting (< In max) of the 630 A 3VW9011-0RC55
rated current In. A residual current function is only
possible with the MF advanced measurement function. 800 A 3VW9011-0RC56
1250 A 3VW9011-0RC58
CB bus modules - communications modules
• Contains the communications module
• Up to 2 different communications modules can be used at the same time.
• When using a digital I/O module IOM040 (Z option K56), only 1 communications module can be used.
• Can only be used with ETU of the 6-series and require a Breaker Connect module for connection to the circuit
breaker. This can also be configured directly on the device by means of a Z option if the communications
interface to the ETU 6-series is selected.
Communications Protocol Article No.
module
COM040 PROFIBUS 3VW9011-0AT15
COM041 PROFINET 3VW9011-0AT14
COM043 Modbus TCP 3VW9011-0AT16
COM042 Modbus RTU 3VW9011-0AT17
CB bus modules - I/O modules external IOM300
• For snapping onto DIN rail
Accessory for Maximum switching current per contact Inputs Outputs Article No.
ETU 6-series • 2 A at ≤ 30 V DC 11 10 3VW9011-0AT20
• 0.8 A at 50 V DC
• 0.2 A at 150 V DC
• 4 A at 250 V AC
CB bus modules - I/O modules internal IOM040
• When using a digital I/O module IOM040, only 1 communication module can be used.
Accessory for Maximum switching current per contact Inputs Outputs Article No.
ETU 6-series • 2 A at ≤ 30 V DC 2 2 3VW9011-0AT30
• 0.8 A at 50 V DC
• 0.2 A at 150 V DC
• 4 A at 250 V AC
3VA27
Actuator modules COM ACT
• For switching the circuit breaker on/off remotely via communication.
• Actuation of the closing coil (CC) and the 1st shunt trip (ST).
• Can only be used in combination with a communications module, spring charging motor,
closing coil and 1st shunt trip.
• Automatically included if the communications interface of the ETU 6-series is selected in the basic circuit
breaker configuration. 2
Accessory for Article No.
ETU 6-series – 3VW9011-0AT10
Breaker Connect modules
• For external power supply for the electronics components
Voltage Article No.
110 ... 240 V AC/DC 3VW9011-0AT06
24 ... 48 V DC 3VW9011-0AT07
3VA27
Front main connections acc. to IEC 60947-2
• Acc. to IEC 60947-2 for 3VA27 up to 1600 A (depending on application conditions)
• To be ordered separately for top and bottom
Mounting Version Mounting onto Number of poles/quantity Article No.
Fixed-mounted Front main connections – 3-pole/3 units 3VW9011-0AL01
2 4-pole/4 units 3VW9011-0AL02
Extended main terminals, Front main 3-pole/3 units 3VW9011-0AL77
including insulation plate connections 4-pole/4 units 3VW9011-0AL78
and phase barriers, standard
1)
For connecting Al cables up to 1000 A
For molded case circuit breakers with stored energy mechanism
For molded case circuit breakers with handle operating mechanism
3VA27
Auxiliary supply connectors in push-in version
• Control wire tap in push-in version for upgrading fixed-mounted circuit breakers and guide frames.
• The device is always fitted at the factory with the exact number of control wire taps required.
Version Article No.
Push-in 3VW9011-0AB11
2
Terminal covers for fixed-mounted circuit breakers
• Finger-proof for front main connections for fixed-mounted versions
• Necessary isolation measures are always supplied with the corresponding connection technology and
do not need to be ordered separately.
Version Number of poles/quantity Article No.
Standard 3-pole/2 units 3VW9723-0WD30
4-pole/2 units 3VW9724-0WD40
Mounting support extended • Fixation for external auxiliary switches AUX 15 CO 3VW9011-0BB52
(circuit breaker feet) (3VW9011-0AG15)
including mechanical • Locking mechanism for control cabinet door, direct
transmission of switch (for 3VW9011-0BB10)
position on circuit breaker • Locking mechanism for control cabinet door, Bowden cable
side panel (for 3VW9011-0BB16),
(= Z option S56) • Mechanical interlock to 3WA/3WL/3VA
(for 3VW9011-0BB21)
Extension kits for modification of the side wall of the fixed-mounted circuit breakers
• For fixed-mounted versions only
• Rear fixation on mounting plate
• For modification for mechanical transmission of switch position on circuit breaker side panel (= Z option S57)
Version Use Article No.
Extension kit for side wall • Fixation for external auxiliary switches AUX 15 CO 3VW9011-0BB53
(3VW9011-0AG15)
• Locking mechanism for control cabinet door, direct
(for 3VW9011-0BB10)
• Locking mechanism for control cabinet door, Bowden cable
(for 3VW9011-0BB16),
• Mechanical interlock to 3WA/3WL/3VA
(for 3VW9011-0BB21)
3VA27
Spring charging motor (MO)
Description Voltage Article No.
For automatic charging of the stored energy mechanism 24 ... 30 V AC/DC – 3VW9011-0AF01
48 ... 60 V AC/DC – 3VW9011-0AF02
100 ... 130 V AC/DC – 3VW9011-0AF03
2 220 ... 250 V AC/DC – 3VW9011-0AF04
Mechanical operating cycles counter MOC
Description Version Article No.
Only possible in combination with a spring charging 5 digits – 3VW9011-0AH07
motor.
3VA27
Closing coils CC/shunt trips ST
• Note:
− For molded case circuit breakers with handle operating mechanism, the products can only be used as
closing shunt trips ST.
− For molded case circuit breakers with stored energy mechanism, the products can be used as closing coils
CC and shunt trips ST.
Voltage Article No. 2
24 V AC/DC 3VW9011-0AD01
30 V AC/DC 3VW9011-0AD02
48 V AC/DC 3VW9011-0AD03
60 V AC/DC 3VW9011-0AD04
110 ... 120 V AC/DC 3VW9011-0AD05
120 ... 127 V AC/DC 3VW9011-0AD06
220 ... 240 V AC/DC 3VW9011-0AD07
240 ... 250 V AC/DC 3VW9011-0AD08
380 ... 400 V AC 3VW9011-0AD17
415 ... 440 V AC 3VW9011-0AD18
TD320 function test units for closing coils/shunt trips
• The TD320 test unit allows the operational availability and functions of the closing coils and shunt trips with
a rated operational voltage between 24 V and 250 V (AC and DC) to be tested.
• The operational availability test is performed cyclically at intervals of 30 seconds.
• The unit has visual indicators in the form of LEDs on the front in order to display the following states:
− LED POWER ON LIT: Correct function of the YO/YC test device
− LED DEACTIVATION LIT: Power supply failure, wire break
− LED SHORT-CIRCUIT LIT: Winding short-circuit
− LED DEACTIVATION and SHORT-CIRCUIT FLASHING: Incorrect power supply
− LED DEACTIVATION and SHORT-CIRCUIT OFF: Closing coil/shunt trips OK
Description Article No.
For all closing coils/shunt trips – 3VW9011-0AT31
Auxiliary/signaling switches
• The auxiliary/signaling switches for 24 V DC digital signals are designed for
− a minimum load above 1 mA at 5 V DC, and
− a maximum breaking capacity of 100 mA at 24 V DC
• For external auxiliary switches ON/OFF AUX 15 CO, a 3VW9011-0AG1x fixation must be ordered in addition,
and for fixed-mounted circuit breakers a 3VW9011-0BB5x side wall modification
Description Contacts Article No.
Ready-to-close signal RTC 1 CO standard – 3VW9011-0AH01
1 CO digital – 3VW9011-0AH02
Auxiliary switch ON/OFF AUX 4 CO standard 3VW9011-0AG01
4 CO digital 3VW9011-0AG02
2 CO standard + 2 CO digital 3VW9011-0AG03
External auxiliary switch ON/OFF AUX 15 CO standard 3VW9011-0AG05
15 CO digital 3VW9011-0AG06
Trip alarm switch S24 1 CO standard 3VW9011-0AH14
1 CO digital 3VW9011-0AH15
Spring charge signaling switch S21 1 CO standard – 3VW9011-0AH10
1 CO digital – 3VW9011-0AH08
Position signaling switches PSS 2 CO | 2 CO | 2 CO 3VW9011-0AH11
(only with withdrawable versions) (connected | test | disconnected position) standard
2 CO | 2 CO | 2 CO 3VW9011-0AH12
(connected | test | disconnected position) digital
3VA27
Auxiliary/signaling switches for handle operating mechanism
• Auxiliary and signaling switches are each offered in two versions:
− Standard version for currents >100 mA and up to 400/250 V AC,
minimum load above 100 mA at 24 V DC, and maximum breaking capacity 5 A at 250 V AC
− Digital version for currents <100 mA for PLC connections,
minimum load above 1 mA at 5 V DC, and maximum breaking capacity 100 mA at 24 V DC
2 • For external auxiliary switches ON/OFF AUX 15 CO, a 3VW9011-0AG1x fixation must be ordered in addition,
and for fixed-mounted circuit breakers a 3VW9011-0BB5x side wall modification.
Description Contacts Article No.
Trip alarm switch TAS signals the trip position 1 CO standard – 3VW9727-0AB11
irrespective of the tripping reason 1 CO digital – 3VW9727-0AB13
Trip alarm switch via auxiliary release S25 signals 1 CO standard – 3VW9727-0AB41
tripping operations via auxiliary releases (UVR, ST) in 1 CO digital – 3VW9727-0AB43
UVR/ST2 pocket
Leading changeover switch S26 (2 units) 1 NO standard, 250 V AC – 3VW9727-0AA21
Fixation for external auxiliary switches AUX 15 CO
• External auxiliary switches ON/OFF AUX 15 CO must be ordered separately.
Version Article No.
For fixed-mounted circuit breakers with rear panel or floor mounting 3VW9011-0AG15
(in combination with Z option S56 or S57)
For guide frames 3VW9011-0AG17
3VA27
Locking provision to prevent movement of the withdrawable circuit breaker
Version Article No.
RONIS cylinder lock (spare part for R78) 3VW9011-0BA80
Padlock 8 mm (spare part for R65), for no more than 3 padlocks 3VW9011-0BA87
2
Locking mechanisms to prevent movement of the withdrawable circuit breakers in disconnected position
• Only possible as a supplement in conjunction with R78 (3VW9011-0BA80) and/or R65 (3VW9011-0BA87).
Description Article No.
Locking mechanism (spare part for R79) 3VW9011-0BA84
Locking provision in OFF position for handle operating mechanism without rotary operators
• Against unauthorized closing in the operator panel in the case of
molded case circuit breakers without rotary operator
Description Article No.
For padlocks – 3VW9727-0LB10
Interlocking sets for mechanical Open and/or Close on the operator panels
Description Version Article No.
Padlock 4 mm (spare part for S42) Plastic for no more than 3 locks – 3VW9011-0BA22
Padlock 7 mm (spare part for S43) Metal for no more than 1 lock – 3VW9011-0BA23
Padlock 8 mm (spare part for S44) Metal for no more than 2 locks – 3VW9011-0BA24
3VA27
Protective covers for mechanical ON/OFF
• Mechanical ON/OFF to protect against unintentional actuation on the operator panel.
• Not lockable.
Description Article No.
Not lockable (spare part for S41) – 3VW9011-0BA21
2 Mechanical interlock
• Mechanical interlock with Bowden cable 2 m
• For fixed-mounted versions, an additional support 3VW9011-0BB52 (option S56) or extension kit
3VW9011-0BB53 (option S57) must be ordered
Mounting Mounting Article No.
Fixed-mounted Rear panel or floor mounting 3VW9011-0BB21
Withdrawable Mounting onto guide frame 3VW9011-0BB22
Product Discontinuation
The 3VL molded case circuit breaker up to 1600 A IEC can only be
ordered as a spare part since 10/2020, and will be removed from
the order portfolio from 10/2025 onwards.
Documents available for downloading:
You can find comprehensive information on the
3VL molded case circuit breaker in the catalog extract.
3VL molded case circuit breakers
www.siemens.com/lowvoltage/catalogs (109769073)
Information + ordering
All the important things at a glance Everything you need for your order
For information about miniature circuit breakers, Refer to the Industry Mall for an overview of your
3 please visit our websites products
www.siemens.com/mcb
• SENTRON miniature circuit breakers sie.ag/2kTFXI5
www.siemens.com/protection-concept
Direct forwarding to the individual products in the
Industry Mall by clicking on the article number in the
catalog or entering this web address incl. article n
umber
Your product in detail www.siemens.com/product?Article No.
Commissioning + operation
The Siemens Industry Online Support (SIOS) provides Manuals are available for downloading in Siemens
detailed technical information Industry Online Support (SIOS) at
www.siemens.com/lowvoltage/product-support www.siemens.com/lowvoltage/manuals
• Operating instructions • Configuration Manual
• Characteristic curves − Miniature circuit breakers (45302792)
• Certificates • Installation Manual
Comprehensive mobile support via the Siemens Industry − SENTRON circuit protection devices with communi
Online Support app available for download from the cation and measuring function (109791805)
App Store and Play Store • System Manual
You will find further information at − SENTRON circuit protection devices with communi
www.siemens.com/support-app cation and measuring function (109791806)
Miniature circuit breakers Miniature circuit breakers Circuit breakers for equipment
for basic applications for advanced applications for advanced applications
Ideal for standard applications Ideal for industrial applications Ideal for devices in industry
The 5SL miniature circuit breakers are For circuits with motors or large lamps, Circuit breakers for equipment from
the new standard with B and C tripping semiconductors or strong pulse Siemens offer optimum protection for
characteristics for applications up to generating equipment such as transfor- all applications in AC and DC control
63 A. They can be used as main control mers and solenoid valves – the 5SY and circuits in industrial applications and
switches to disconnect or isolate 5SP devices are optimized for industrial plant engineering.
equipment. applications and are proven in use.
Thermomagnetic 5SY17 circuit breakers
The 5SL devices are mainly installed in The 5SY devices offer you top quality for equipment are used to protect
meter panels and small distribution and functionality for installation in solenoid valves, servo motors, signal
boards to protect circuits for lamps, complex buildings and industry. With a lamps or even PLC inputs. Everywhere
cookers and even machines, for rated breaking capacity of up to 25 kA, where loads have to be precisely
example, in residential or commercial they are able to handle the most protected from overloads and short-
buildings. challenging requirements at a rated circuits.
current of 0.3 to 80 A.
Electronic 5SK9 circuit breakers for
Special features equipment are optimally suited to
• Dual-chamber terminals protecting, for example, relays,
• Simple to detach without tools using programmable controllers, motors,
sliding catches sensors, actuators and valves. A current
• Separate switching position indication analysis in conjunction with fast tripping
• A wide range of accessories in the event of a fault avoid the danger
• 5SL60 available as communication- of overloading the switched-mode
capable miniature circuit breaker power supply.
5SL6 COM miniature circuit breakers and 5ST3 COM auxiliary switches/fault signal
contacts with communication and measuring functions
The new communication-capable protective devices and auxiliary components record measured values and status information and
transmit this data wirelessly to higher-level systems.
• Recording of energy and active power, current, voltage, line
frequency and temperature
• Integrated status acquisition, operating hours counter and trip
counter
• Higher system availability through early response to warning
messages
• Convenient integration into new and existing systems thanks to
compact mounting widths of 1 MW
• Fast parameterization and commissioning with the SENTRON
5SL6 COM 5ST3 COM 7KN POC1000 powerconfig mobile app or the SENTRON powerconfig software
see page 3/40 see page 3/52 see page 10/20 • Wireless transmission of measurement data from up to
24 communication-capable devices to the 7KN Powercenter 1000
data transceiver
System overview
Basic units and accessories
5SY6 5SY4 5SP4 5SP5 new 5SY5 5SY7 5SY8 5SJ4..HG.. 5SL6 COM
5SY17 5SK9
Electrical accessories
Auxiliary switches Fault signal Auxiliary switches and fault signal Shunt trips Undervoltage Remote control mechanisms 5SM6 arc fault
(AS) contacts (FC) contacts (AS+FC)/(AS+FC) COM (ST) releases (UR) (RC mech.) detection units
Mechanical accessories
Rotary operating Spacers Terminal covers Wall enclosures Molded-plastic Holders for front Intermediate
mechanisms enclosures panel installation frames
Compact busbars Standard busbars Terminals Touch protection End caps Series connectors Distribution
blocks
Note:
You will find a detailed range of accessories with the basic units and in the Accessories section.
5SL3 5SL6
Standards
3 Standards
Basic data
IEC/EN 60898-1 IEC/EN 60898-1
VDE, CEBEC, IMQ VDE VDE, IMQ, NF, CCC VDE, IMQ, NF, CCC VDE
– – – DNV-GL –
–25 … +55 3) –25 … +45 2) –25 … +60 4) –25 … +60 4) –25 … +55
–40 … +75 4) –40 … +75 4) –40 … +75 –40 … +75 –40 … +70
– – – – –
– – – – –
– – – – –
– – – – –
See page 3/16 See page 3/18 See page 3/20 See page 3/22 See page 3/42
U2: see Certificate of – U2: see Certificate of U2: see Certificate of U2: see Certificate of –
Compliance Compliance Compliance Compliance
–|– –|– –|– 50 | 50 70 | 70 10
–|– –|– –|– 40 | 40 50 | 50 10
–|– –|– –|– 30 | 30 40 | 40 10
–|– –|– –|– 25 | 25 30 | 30 10
–|– –|– –|– 20 | 20 25 | 25 10
–|– –|– –|– 15 | 15 20 | 20 10
10 | 10 –|– –|– –|– –|– –
80 … 125 80 … 125 0.3 … 63 0.3 … 63 0.3 … 63 0.3 … 63
1P | 2P | 3P | 4P 1P | 2P 1P | 2P | 4P 1P | 2P | 3P | 4P | 1P+N | 1P | 2P | 3P | 4P | 1P+N | 1P | 2P | 3P
3P+N 3P+N
B|C|D – B|C B|C|D C|D B|C|D
– – ■ ■ ■ ■
10 … 50 10 … 50 0.75 … 35 0.75 … 35 0.75 … 35 0.75 … 25 (16) 6)
10 … 35 10 … 35 0.75 … 25 0.75 … 25 0.75 … 25 0.75 … 25 (10)
AWG 3 … 1 AWG 3 … 1 AWG 18 … 4 AWG 18 … 4 AWG 18 … 4 AWG 18 … 4 (5)
2.5 … 3.5 max. 2.5 … 3.5 max. 2.5 … 3.5 max. 2.5 … 3.5 max. 2.5 … 3.5 max. 2.5 … 3.5 max.
22 … 31 22 … 31 22 … 26 22 … 26 22 … 26 22 … 26
–25 … +55 4) –25 … +55 4) –40 … +70 3) –40 … +70 3) –25 … +55 4) –25 … +55 4)
–40 … +75 3) –40 … +75 3) –40 … +75 3) –40 … +75 3) –40 … +75 3) –40 … +75 3)
– – ■ ■ – ■
■ – ■ ■ ■ ■
– – ■ ■ – –
■ – ■ ■ – –
3/III 3/III 3/III 4) 3/III 3/III 3/III
– – – – – –
See page 3/28 See page 3/30 See page 3/32 See page 3/34 See page 3/36 See page 3/38
The device properties specified, for example, in the product standards, such as service
7) 8)
Please note the country-specific radio licenses of the products in SIOS
life, breaking capacity and surface temperature, cannot be guaranteed at the specified www.siemens.com/lowvoltage/certificates (109801197)
ambient temperatures that lie outside the specified product standards.
5SY17
Standards
Standards IEC/EN 60934
UL 1077
3
Basic data
Breaking capacity Icn At rated voltage kA 3
Rated current A 0.5 … 16
Number of poles 1P+AS
DC tripping Magnetic F1 (2.5 … 4 × In) | F2 (4 … 7 × In)
Thermal 1.05 × holding current | 1.35 × tripping current | TC3 1.35 × In
Electronic –
Service life/endurance Actuations 6000
Approvals
General product approvals CCC,
Operational voltage
Min. AC Acc. to EN 60934 V 12 2)
Acc. to UL 1077, CSA C22.2 No.235 V 12 2)
Max. AC Acc. to EN 60934 V 250
Acc. to UL 1077, CSA C22.2 No.235 V 277
Min. DC per phase pole V 12 2)
Max. DC per phase pole V 72
Rated voltage Acc. to IEC/EN 60934 V 230
Acc. to UL 1077 V 277
Rated impulse voltage Uimp kV 4
Rated frequency fn Hz 50/60
Auxiliary switch
MIn. operational voltage (AC) V 12
Max. operational voltage (AC) V 250
MIn. operational voltage (DC) V 12
Max. operational voltage (DC) V 60
Utilization category AC-12 6A at 230 V AC
Utilization category AC-14 6A at 230 V AC
Utilization category DC-13 1A at 60 V DC
Connection
Dual-chamber terminal –
Conductor cross-section 1 wire Solid/stranded mm2 0.75 … 16
Finely stranded with end sleeve mm2 0.75 … 10
Finely stranded with insulated end sleeve mm2 0.75 … 10
Finely stranded without end sleeve mm2 0.75 … 16
Conductor cross-section AWG –
2-wire (same cross-section) Solid/stranded mm2 0.75 … 4
Finely stranded with end sleeve mm2 0.75 … 2.5
Finely stranded with insulated end sleeve mm2 0.75 … 1.5
Finely stranded without end sleeve mm2 0.75 … 4
Terminal tightening torque Nm 2.0 … 2.5 max.
lb-in 17.7 ... 22.1
Ambient conditions
Ambient temperature °C –25 … +60 3)
Storage temperature °C –40 … +70
Shock acc. to IEC 60068-2-27 150 m/s2 at 11 ms half-sine –
Resistance to vibrations acc. to IEC 60068-2-6: 5 ... 25 Hz (±1mm) and at 25 ... 150 Hz (50 m/s2) –
Resistant to shock and vibrations acc. to EN 61373 and EN 50155 "1B" (railway engineering) ■
Fire behavior of materials acc. to EN 45545-2 (fire protection on railway vehicles) ■
Degree of pollution for overvoltage category Acc. to IEC 2/III
Further information
See page 3/44
1)
Max. 95% humidity 2)
At a minimum current of 100 mA
5SK9
EN 61000-6-2, EN 61000-6-3, EN 60068-2-78,
EN 50178, EN 60068-2-6, EN 60068-2-27,
UL 508, UL 2367 3
–
1…8
1P+AS
–
–
Overload 1.2 × In/1s | Short-circuit 2 × In/<10 ms
–
–
–
–
–
–
30
–
–
0.5
–
–
–
–
–
–
–
–
–
0.2 … 4
0.2 … 2.5
0.2 … 2.5
–
AWG 24 ... 12
–
–
–
–
–
–
–25 … +60 1)
–40 … +70
–
–
–
–
–
1P 1P+N 2P 3P
230/400 V AC 230 V AC 400 V AC 400 V AC
Mounting width 1 MW 2 MW 2 MW 3 MW
1 1 N 1 3 1 3 5
2 2 N 2 4 2 4 6
3 Rated current In Characteristic Characteristic Characteristic Characteristic
B C B C B C B C
0.3 A – 5SL3114-7 – 5SL3514-7 – 5SL3214-7 – –
0.5 A – 5SL3105-7 – 5SL3505-7 – 5SL3205-7 – –
1A – 5SL3101-7 – 5SL3501-7 – 5SL3201-7 – 5SL3301-7
1.6 A – 5SL3115-7 – 5SL3515-7 – 5SL3215-7 – –
2A – 5SL3102-7 – 5SL3502-7 – 5SL3202-7 – 5SL3302-7
3A – 5SL3103-7 – 5SL3503-7 – 5SL3203-7 – 5SL3303-7
4A – 5SL3104-7 – 5SL3504-7 – 5SL3204-7 – 5SL3304-7
6A 5SL3106-6 5SL3106-7 5SL3506-6 5SL3506-7 5SL3206-6 5SL3206-7 5SL3306-6 5SL3306-7
8A – 5SL3108-7 – 5SL3508-7 – 5SL3208-7 – –
10 A 5SL3110-6 5SL3110-7 5SL3510-6 5SL3510-7 5SL3210-6 5SL3210-7 5SL3310-6 5SL3310-7
13 A 5SL3113-6 5SL3113-7 5SL3513-6 5SL3513-7 5SL3213-6 5SL3213-7 – –
16 A 5SL3116-6 5SL3116-7 5SL3516-6 5SL3516-7 5SL3216-6 5SL3216-7 5SL3316-6 5SL3316-7
20 A 5SL3120-6 5SL3120-7 5SL3520-6 5SL3520-7 5SL3220-6 5SL3220-7 5SL3320-6 5SL3320-7
25 A 5SL3125-6 5SL3125-7 5SL3525-6 5SL3525-7 5SL3225-6 5SL3225-7 5SL3325-6 5SL3325-7
32 A 5SL3132-6 5SL3132-7 5SL3532-6 5SL3532-7 5SL3232-6 5SL3232-7 5SL3332-6 5SL3332-7
40 A 5SL3140-6 5SL3140-7 5SL3540-6 5SL3540-7 5SL3240-6 5SL3240-7 5SL3340-6 5SL3340-7
50 A 5SL3150-6 5SL3150-7 5SL3550-6 5SL3550-7 5SL3250-6 5SL3250-7 5SL3350-6 5SL3350-7
63 A 5SL3163-6 5SL3163-7 5SL3563-6 5SL3563-7 5SL3263-6 5SL3263-7 5SL3363-6 5SL3363-7
Mounting concept
18 – 72 mm
optional
9 mm
9 mm
9 mm
or
and
5SL3 AS AS AS
basic unit FC FC + FC
I201_20333
AS + FC AS + FC AS + FC
3P+N 4P
400 V AC 400 V AC
4 MW 4 MW
1 3 5 N 1 3 5 7
2 4 6 N 2 4 6 8
Characteristic Characteristic 3
B C B C
– – – –
– – – –
– 5SL3601-7 – 5SL3401-7
– – – –
– 5SL3602-7 – 5SL3402-7
– 5SL3603-7 – 5SL3403-7
– 5SL3604-7 – 5SL3404-7
5SL3606-6 5SL3606-7 – 5SL3406-7
– 5SL3608-7 – –
5SL3610-6 5SL3610-7 – 5SL3410-7
5SL3613-6 5SL3613-7 – 5SL3413-7
5SL3616-6 5SL3616-7 – 5SL3416-7
5SL3620-6 5SL3620-7 – 5SL3420-7
5SL3625-6 5SL3625-7 – 5SL3425-7
5SL3632-6 5SL3632-7 – 5SL3432-7
5SL3640-6 5SL3640-7 – 5SL3440-7
5SL3650-6 5SL3650-7 – 5SL3450-7
5SL3663-6 5SL3663-7 – 5SL3463-7
Accessories
Auxiliary switches (AS) Article No. Fault signal contacts (FC) Article No.
1 NO + 1 NC Standard 5ST3010 1 NO + 1 NC 5ST3020
For low power 5ST3013 2 NO 5ST3021
For low power (with diode) 5ST3013-0XX01 2 NC 5ST3022
2 NO Standard 5ST3011 Auxiliary switches and fault signal contacts (AS+FC) Article No.
For low power 5ST3014 1 CO (AS) + 1 CO (FC) 5ST3062
2 NC Standard 5ST3012 5ST3 COM (AS+FC) 5ST3062-0MC
For low power 5ST3015
1 CO Standard 5ST3016
1P 1P+N 2P 3P
230/400 V AC 230 V AC 400 V AC 400 V AC
Mounting width 1 MW 2 MW 2 MW 3 MW
1 1 N 1 3 1 3 5
2 2 N 2 4 2 4 6
3 Rated current In Characteristic Characteristic Characteristic Characteristic
B C B C B C B C
0.3 A – 5SL6114-7 – 5SL6514-7 – 5SL6214-7 – 5SL6314-7
0.5 A – 5SL6105-7 – 5SL6505-7 – 5SL6205-7 – 5SL6305-7
1A – 5SL6101-7 – 5SL6501-7 – 5SL6201-7 – 5SL6301-7
1.6 A – 5SL6115-7 – 5SL6515-7 – 5SL6215-7 – 5SL6315-7
2A 5SL6102-6 5SL6102-7 – 5SL6502-7 – 5SL6202-7 – 5SL6302-7
3A – 5SL6103-7 – 5SL6503-7 – 5SL6203-7 – 5SL6303-7
4A 5SL6104-6 5SL6104-7 – 5SL6504-7 – 5SL6204-7 – 5SL6304-7
6A 5SL6106-6 5SL6106-7 5SL6506-6 5SL6506-7 5SL6206-6 5SL6206-7 5SL6306-6 5SL6306-7
8A – 5SL6108-7 – 5SL6508-7 – 5SL6208-7 – 5SL6308-7
10 A 5SL6110-6 5SL6110-7 5SL6510-6 5SL6510-7 5SL6210-6 5SL6210-7 5SL6310-6 5SL6310-7
13 A 5SL6113-6 5SL6113-7 5SL6513-6 5SL6513-7 5SL6213-6 5SL6213-7 5SL6313-6 5SL6313-7
16 A 5SL6116-6 5SL6116-7 5SL6516-6 5SL6516-7 5SL6216-6 5SL6216-7 5SL6316-6 5SL6316-7
20 A 5SL6120-6 5SL6120-7 5SL6520-6 5SL6520-7 5SL6220-6 5SL6220-7 5SL6320-6 5SL6320-7
25 A 5SL6125-6 5SL6125-7 5SL6525-6 5SL6525-7 5SL6225-6 5SL6225-7 5SL6325-6 5SL6325-7
32 A 5SL6132-6 5SL6132-7 5SL6532-6 5SL6532-7 5SL6232-6 5SL6232-7 5SL6332-6 5SL6332-7
40 A 5SL6140-6 5SL6140-7 5SL6540-6 5SL6540-7 5SL6240-6 5SL6240-7 5SL6340-6 5SL6340-7
50 A 5SL6150-6 5SL6150-7 5SL6550-6 5SL6550-7 5SL6250-6 5SL6250-7 5SL6350-6 5SL6350-7
63 A 5SL6163-6 5SL6163-7 5SL6563-6 5SL6563-7 5SL6263-6 5SL6263-7 5SL6363-6 5SL6363-7
Mounting concept
18 – 72 mm
27 – 36 mm
optional optional
9 mm
9 mm
9 mm
or
and and
5SL6 RC mech. AS AS AS
basic unit and FC FC + FC
G_I201_20334
AS + FC AS + FC AS + FC
Adapter
3P+N 4P
400 V AC 400 V AC
4 MW 4 MW
1 3 5 N 1 3 5 7
2 4 6 N 2 4 6 8
Characteristic Characteristic 3
B C B C
– 5SL6614-7 – 5SL6414-7
– 5SL6605-7 – 5SL6405-7
– 5SL6601-7 – 5SL6401-7
– 5SL6615-7 – 5SL6415-7
– 5SL6602-7 – 5SL6402-7
– 5SL6603-7 – 5SL6403-7
– 5SL6604-7 – 5SL6404-7
5SL6606-6 5SL6606-7 5SL6406-6 5SL6406-7
– 5SL6608-7 – 5SL6408-7
5SL6610-6 5SL6610-7 5SL6410-6 5SL6410-7
5SL6613-6 5SL6613-7 5SL6413-6 5SL6413-7
5SL6616-6 5SL6616-7 5SL6416-6 5SL6416-7
5SL6620-6 5SL6620-7 5SL6420-6 5SL6420-7
5SL6625-6 5SL6625-7 5SL6425-6 5SL6425-7
5SL6632-6 5SL6632-7 5SL6432-6 5SL6432-7
5SL6640-6 5SL6640-7 5SL6440-6 5SL6440-7
5SL6650-6 5SL6650-7 5SL6450-6 5SL6450-7
5SL6663-6 5SL6663-7 5SL6463-6 5SL6463-7
Accessories
Auxiliary switches (AS) Article No. Auxiliary switches and fault signal contacts (AS+FC) Article No.
1 NO + 1 NC Standard 5ST3010 1 CO (AS) + 1 CO (FC) 5ST3062
For low power 5ST3013 5ST3 COM (AS+FC) 5ST3062-0MC
For low power (with diode) 5ST3013-0XX01 Remote control mechanisms (RC mech.) Article No.
2 NO Standard 5ST3011 Basic 12 ... 30 V AC, 12 ... 48 V DC 5ST3053
For low power 5ST3014 177 … 270 V AC 5ST3054
2 NC Standard 5ST3012 Power 12 ... 30 V AC, 12 ... 48 V DC 5ST3055
For low power 5ST3015 177 … 270 V AC 5ST3056
1 CO Standard 5ST3016 Power with ARD 12 ... 30 V AC, 12 ... 48 V DC 5ST3057
Fault signal contacts (FC) Article No. 177 … 270 V AC 5ST3058
1 NO + 1 NC 5ST3020 Power with extended 12 ... 30 V AC, 12 ... 48 V DC 5ST3070
2 NO 5ST3021 function 170 … 277 V AC, 77 … 286 V DC 5ST3071
2 NC 5ST3022 Adapters for remote control mechanisms (RC mech.) Article No.
1 … 2 MW 5ST3820-6
3 … 4 MW 5ST3820-7
1P 1P+N 2P
230/400 V AC 230 V AC 400 V AC
Mounting width 1 MW 2 MW 2 MW
1 1 N 1 3
2 2 N 2 4
3 Rated Characteristic Characteristic Characteristic
current In B C D B C D B C D
0.3 A – 5SL4114-7 5SL4114-8 – 5SL4514-7 5SL4514-8 – 5SL4214-7 5SL4214-8
0.5 A – 5SL4105-7 5SL4105-8 – 5SL4505-7 5SL4505-8 – 5SL4205-7 5SL4205-8
1A 5SL4101-6 5SL4101-7 5SL4101-8 5SL4501-6 5SL4501-7 5SL4501-8 5SL4201-6 5SL4201-7 5SL4201-8
1.6 A – 5SL4115-7 5SL4115-8 – 5SL4515-7 5SL4515-8 – 5SL4215-7 5SL4215-8
2A 5SL4102-6 5SL4102-7 5SL4102-8 5SL4502-6 5SL4502-7 5SL4502-8 5SL4202-6 5SL4202-7 5SL4202-8
3A 5SL4103-6 5SL4103-7 5SL4103-8 5SL4503-6 5SL4503-7 5SL4503-8 5SL4203-6 5SL4203-7 5SL4203-8
4A 5SL4104-6 5SL4104-7 5SL4104-8 5SL4504-6 5SL4504-7 5SL4504-8 5SL4204-6 5SL4204-7 5SL4204-8
6A 5SL4106-6 5SL4106-7 5SL4106-8 5SL4506-6 5SL4506-7 5SL4506-8 5SL4206-6 5SL4206-7 5SL4206-8
8A 5SL4108-6 5SL4108-7 5SL4108-8 5SL4508-6 5SL4508-7 5SL4508-8 5SL4208-6 5SL4208-7 5SL4208-8
10 A 5SL4110-6 5SL4110-7 5SL4110-8 5SL4510-6 5SL4510-7 5SL4510-8 5SL4210-6 5SL4210-7 5SL4210-8
13 A 5SL4113-6 5SL4113-7 5SL4113-8 5SL4513-6 5SL4513-7 5SL4513-8 5SL4213-6 5SL4213-7 5SL4213-8
16 A 5SL4116-6 5SL4116-7 5SL4116-8 5SL4516-6 5SL4516-7 5SL4516-8 5SL4216-6 5SL4216-7 5SL4216-8
20 A 5SL4120-6 5SL4120-7 5SL4120-8 5SL4520-6 5SL4520-7 5SL4520-8 5SL4220-6 5SL4220-7 5SL4220-8
25 A 5SL4125-6 5SL4125-7 5SL4125-8 5SL4525-6 5SL4525-7 5SL4525-8 5SL4225-6 5SL4225-7 5SL4225-8
32 A 5SL4132-6 5SL4132-7 5SL4132-8 5SL4532-6 5SL4532-7 5SL4532-8 5SL4232-6 5SL4232-7 5SL4232-8
40 A 5SL4140-6 5SL4140-7 5SL4140-8 5SL4540-6 5SL4540-7 5SL4540-8 5SL4240-6 5SL4240-7 5SL4240-8
50 A 5SL4150-6 5SL4150-7 5SL4150-8 5SL4550-6 5SL4550-7 5SL4550-8 5SL4250-6 5SL4250-7 5SL4250-8
63 A 5SL4163-6 5SL4163-7 5SL4163-8 5SL4563-6 5SL4563-7 5SL4563-8 5SL4263-6 5SL4263-7 5SL4263-8
Mounting concept
optional optional
18 mm
36 mm
18 mm
18 mm
18 mm
9 mm
9 mm
9 mm
9 mm
9 mm
or or or or 9 mm
and and
5SM6 5SL4 AS AS AS ST ST AS ST AS AS
AFDD basic unit FC FC + FC UR UR + FC UR + FC + FC
G_I201_20335
(1P+N) up to AS + FC AS + FC AS + FC AS + FC AS + FC AS + FC
max. 40 A
18 – 72 mm
27 – 36 mm
optional optional
18 mm
18 mm
18 mm
9 mm
9 mm
9 mm
9 mm
9 mm
9 mm
or or or or
and and
5SL4 RC mech. AS AS AS ST ST AS ST AS AS
basic unit and FC FC + FC UR UR + FC UR + FC + FC
G_I201_20336
AS + FC AS + FC AS + FC AS + FC AS + FC AS + FC
Adapter
AFDD Arc fault detection units See page 3/57 AS+FC Auxiliary switches and UR Undervoltage releases See page 3/55
AS Auxiliary switches See page 3/48 fault signal contacts See page 3/51 RC mech. Remote control mechanisms See page 3/56
FC Fault signal contacts See page 3/50 ST Shunt trips See page 3/54
3P 3P+N 4P
400 V AC 400 V AC 400 V AC
3 MW 4 MW 4 MW
1 3 5 1 3 5 N 1 3 5 7
2 4 6 2 4 6 N 2 4 6 8
Characteristic Characteristic Characteristic 3
B C D B C D B C D
– 5SL4314-7 5SL4314-8 – 5SL4614-7 5SL4614-8 – 5SL4414-7 5SL4414-8
– 5SL4305-7 5SL4305-8 – 5SL4605-7 5SL4605-8 – 5SL4405-7 5SL4405-8
5SL4301-6 5SL4301-7 5SL4301-8 5SL4601-6 5SL4601-7 5SL4601-8 5SL4401-6 5SL4401-7 5SL4401-8
– 5SL4315-7 5SL4315-8 – 5SL4615-7 5SL4615-8 – 5SL4415-7 5SL4415-8
5SL4302-6 5SL4302-7 5SL4302-8 5SL4602-6 5SL4602-7 5SL4602-8 5SL4402-6 5SL4402-7 5SL4402-8
5SL4303-6 5SL4303-7 5SL4303-8 5SL4603-6 5SL4603-7 5SL4603-8 5SL4403-6 5SL4403-7 5SL4403-8
5SL4304-6 5SL4304-7 5SL4304-8 5SL4604-6 5SL4604-7 5SL4604-8 5SL4404-6 5SL4404-7 5SL4404-8
5SL4306-6 5SL4306-7 5SL4306-8 5SL4606-6 5SL4606-7 5SL4606-8 5SL4406-6 5SL4406-7 5SL4406-8
5SL4308-6 5SL4308-7 5SL4308-8 5SL4608-6 5SL4608-7 5SL4608-8 5SL4408-6 5SL4408-7 5SL4408-8
5SL4310-6 5SL4310-7 5SL4310-8 5SL4610-6 5SL4610-7 5SL4610-8 5SL4410-6 5SL4410-7 5SL4410-8
5SL4313-6 5SL4313-7 5SL4313-8 5SL4613-6 5SL4613-7 5SL4613-8 5SL4413-6 5SL4413-7 5SL4413-8
5SL4316-6 5SL4316-7 5SL4316-8 5SL4616-6 5SL4616-7 5SL4616-8 5SL4416-6 5SL4416-7 5SL4416-8
5SL4320-6 5SL4320-7 5SL4320-8 5SL4620-6 5SL4620-7 5SL4620-8 5SL4420-6 5SL4420-7 5SL4420-8
5SL4325-6 5SL4325-7 5SL4325-8 5SL4625-6 5SL4625-7 5SL4625-8 5SL4425-6 5SL4425-7 5SL4425-8
5SL4332-6 5SL4332-7 5SL4332-8 5SL4632-6 5SL4632-7 5SL4632-8 5SL4432-6 5SL4432-7 5SL4432-8
5SL4340-6 5SL4340-7 5SL4340-8 5SL4640-6 5SL4640-7 5SL4640-8 5SL4440-6 5SL4440-7 5SL4440-8
5SL4350-6 5SL4350-7 5SL4350-8 5SL4650-6 5SL4650-7 5SL4650-8 5SL4450-6 5SL4450-7 5SL4450-8
5SL4363-6 5SL4363-7 5SL4363-8 5SL4663-6 5SL4663-7 5SL4663-8 5SL4463-6 5SL4463-7 5SL4463-8
Accessories
Auxiliary switches (AS) Article No. Undervoltage releases (UR) Article No.
1 NO + 1 NC Standard 5ST3010 With integrated 230 V AC 5ST3040
For low power 5ST3013 auxiliary switch 110 V DC 5ST3041
For low power (with diode) 5ST3013-0XX01 24 V DC 5ST3042
2 NO Standard 5ST3011 Without integrated 230 V AC 5ST3043
For low power 5ST3014 auxiliary switch 110 V DC 5ST3044
2 NC Standard 5ST3012 24 V DC 5ST3045
For low power 5ST3015 Remote control mechanisms (RC mech.) Article No.
1 CO Standard 5ST3016 Basic 12 ... 30 V AC, 12 ... 48 V DC 5ST3053
Fault signal contacts (FC) Article No. 177 … 270 V AC 5ST3054
1 NO + 1 NC 5ST3020 Power 12 ... 30 V AC, 12 ... 48 V DC 5ST3055
2 NO 5ST3021 177 … 270 V AC 5ST3056
2 NC 5ST3022 Power with ARD 12 ... 30 V AC, 12 ... 48 V DC 5ST3057
Auxiliary switches and fault signal contacts (AS+FC) Article No. 177 … 270 V AC 5ST3058
1 CO (AS) + 1 CO (FC) 5ST3062 Power with extended 12 ... 30 V AC, 12 ... 48 V DC 5ST3070
5ST3 COM (AS+FC) 5ST3062-0MC function 170 … 277 V AC, 77 … 286 V DC 5ST3071
Shunt trips (ST) Article No. Adapters for remote control mechanisms (RC mech.) Article No.
110 … 415 V AC, 110 … 220 V DC 5ST3030 1 … 2 MW 5ST3820-6
24 ... 48 V AC/DC 5ST3031 3 … 4 MW 5ST3820-7
12 V DC 5ST3031-0XX01 Arc fault detection units (AFDD) Article No.
For basic units 1P+N (2 MW), In up to 16 A 5SM6021-2
not in combination with RC mech. I up to 40 A 5SM6024-2
n
1P 1P+N 2P 3P
230/400 V AC 230/400 V AC 230/400 V AC 230/400 V AC
Mounting width 1 MW 2 MW 2 MW 3 MW
1 1 N 1 3 1 3 5
2 2 N 2 4 2 4 6
3 Rated current In Characteristic Characteristic Characteristic Characteristic
B C B C B C B C
10 A 5SJ6110-6KS 5SJ6110-7KS 5SJ6510-6KS 5SJ6510-7KS 5SJ6210-6KS 5SJ6210-7KS 5SJ6310-6KS 5SJ6310-7KS
13 A 5SJ6113-6KS 5SJ6113-7KS 5SJ6513-6KS 5SJ6513-7KS 5SJ6213-6KS 5SJ6213-7KS 5SJ6313-6KS 5SJ6313-7KS
16 A 5SJ6116-6KS 5SJ6116-7KS 5SJ6516-6KS 5SJ6516-7KS 5SJ6216-6KS 5SJ6216-7KS 5SJ6316-6KS 5SJ6316-7KS
20 A 5SJ6120-6KS 5SJ6120-7KS 5SJ6520-6KS 5SJ6520-7KS 5SJ6220-6KS 5SJ6220-7KS 5SJ6320-6KS 5SJ6320-7KS
I201_20441
2 N N 2
3 Rated current In Characteristic Characteristic
C C
2A 5SL3002-7 5SL3002-7KL
4A 5SL3004-7 5SL3004-7KL
6A 5SL3006-7 5SL3006-7KL
8A 5SL3008-7 5SL3008-7KL
10 A 5SL3010-7 5SL3010-7KL
13 A 5SL3013-7 5SL3013-7KL
16 A 5SL3016-7 5SL3016-7KL
20 A 5SL3020-7 5SL3020-7KL
25 A 5SL3025-7 5SL3025-7KL
32 A 5SL3032-7 5SL3032-7KL
40 A 5SL3040-7 5SL3040-7KL
Mounting concept
18 mm
optional
9 mm
9 mm
9 mm
and or
5SL30 AS AS AS
G_I201_20337
basic unit FC FC + FC
AS + FC AS + FC AS + FC
Accessories
Auxiliary switches (AS) Article No. Fault signal contacts (FC) Article No.
1 NO + 1 NC Standard 5ST3010 1 NO + 1 NC 5ST3020
For low power 5ST3013 2 NO 5ST3021
For low power (with diode) 5ST3013-0XX01 2 NC 5ST3022
2 NO Standard 5ST3011 Auxiliary switches and fault signal contacts (AS+FC) Article No.
For low power 5ST3014 1 CO (AS) + 1 CO (FC) 5ST3062
2 NC Standard 5ST3012 5ST3 COM (AS+FC) 5ST3062-0MC
For low power 5ST3015
1 CO Standard 5ST3016
I201_20441
2 N N 2
3 Rated current In Characteristic Characteristic
B C C
2A – 5SL6002-7 5SL6002-7KL
4A – 5SL6004-7 5SL6004-7KL
6A 5SL6006-6 5SL6006-7 5SL6006-7KL
8A – 5SL6008-7 5SL6008-7KL
10 A 5SL6010-6 5SL6010-7 5SL6010-7KL
13 A 5SL6013-6 5SL6013-7 5SL6013-7KL
16 A 5SL6016-6 5SL6016-7 5SL6016-7KL
20 A 5SL6020-6 5SL6020-7 5SL6020-7KL
25 A 5SL6025-6 5SL6025-7 5SL6025-7KL
32 A 5SL6032-6 5SL6032-7 5SL6032-7KL
40 A 5SL6040-6 5SL6040-7 5SL6040-7KL
Mounting concept
18 mm
18 mm
optional optional
9 mm
9 mm
9 mm
and and or
AFDD 5SL60 AS AS AS
basic unit FC FC + FC
G_I201_20338
optional optional
18 mm
9 mm
9 mm
9 mm
and and or
5SL60 RC mech. AS AS AS
basic unit and FC FC + FC
AS + FC AS + FC AS + FC
G_I201_20339
Adapter
Accessories
Auxiliary switches (AS) Article No. Remote control mechanisms (RC mech.) Article No.
1 NO + 1 NC Standard 5ST3010 Basic 12 ... 30 V AC, 12 ... 48 V DC 5ST3053
For low power 5ST3013 177 … 270 V AC 5ST3054
For low power (with diode) 5ST3013-0XX01 Power 12 ... 30 V AC, 12 ... 48 V DC 5ST3055
2 NO Standard 5ST3011 177 … 270 V AC 5ST3056
For low power 5ST3014 Power with ARD 12 ... 30 V AC, 12 ... 48 V DC 5ST3057
2 NC Standard 5ST3012 177 … 270 V AC 5ST3058
For low power 5ST3015 Power with extended 12 ... 30 V AC, 12 ... 48 V DC 5ST3070
1 CO Standard 5ST3016 function 170 … 277 V AC, 77 … 286 V DC 5ST3071
Fault signal contacts (FC) Article No. Adapters for remote control mechanisms (RC mech.) Article No.
1 NO + 1 NC 5ST3020 1 MW 5ST3820-6
2 NO 5ST3021 Arc fault detection units (AFDD) Article No.
2 NC 5ST3022 For basic units 1P + N In up to 16 A 5SM6011-2
Auxiliary switches and fault signal contacts (AS+FC) Article No. (1 MW), not for KL types I up to 40 A 5SM6014-2
n
1 CO (AS) + 1 CO (FC) 5ST3062
5ST3 COM (AS+FC) 5ST3062-0MC
1P 1P+N 2P 3P
230/400 V AC 230 V AC 400 V AC 400 V AC
Mounting width 1 MW 2 MW 2 MW 3 MW
1 1 N 1 3 1 3 5
2 2 N 2 4 2 4 6
3 Rated current In Characteristic Characteristic Characteristic Characteristic
B C B C B C B C
0.3 A – 5SY6114-7 – 5SY6514-7 – 5SY6214-7 – 5SY6314-7
0.5 A – 5SY6105-7 – 5SY6505-7 – 5SY6205-7 – 5SY6305-7
1A – 5SY6101-7 – 5SY6501-7 – 5SY6201-7 – 5SY6301-7
1.6 A – 5SY6115-7 – 5SY6515-7 – 5SY6215-7 – 5SY6315-7
2A 5SY6102-6 5SY6102-7 – 5SY6502-7 – 5SY6202-7 – 5SY6302-7
3A – 5SY6103-7 – 5SY6503-7 – 5SY6203-7 – 5SY6303-7
4A 5SY6104-6 5SY6104-7 – 5SY6504-7 – 5SY6204-7 – 5SY6304-7
5A – 5SY6111-7 – – – 5SY6211-7 – 5SY6311-7
6A 5SY6106-6 5SY6106-7 5SY6506-6 5SY6506-7 5SY6206-6 5SY6206-7 5SY6306-6 5SY6306-7
8A – 5SY6108-7 – 5SY6508-7 – 5SY6208-7 – 5SY6308-7
10 A 5SY6110-6 5SY6110-7 5SY6510-6 5SY6510-7 5SY6210-6 5SY6210-7 5SY6310-6 5SY6310-7
13 A 5SY6113-6 5SY6113-7 5SY6513-6 5SY6513-7 5SY6213-6 5SY6213-7 5SY6313-6 5SY6313-7
15 A – 5SY6118-7 – – – 5SY6218-7 – 5SY6318-7
16 A 5SY6116-6 5SY6116-7 5SY6516-6 5SY6516-7 5SY6216-6 5SY6216-7 5SY6316-6 5SY6316-7
20 A 5SY6120-6 5SY6120-7 5SY6520-6 5SY6520-7 5SY6220-6 5SY6220-7 5SY6320-6 5SY6320-7
25 A 5SY6125-6 5SY6125-7 5SY6525-6 5SY6525-7 5SY6225-6 5SY6225-7 5SY6325-6 5SY6325-7
30 A – 5SY6130-7 – – – 5SY6230-7 – 5SY6330-7
32 A 5SY6132-6 5SY6132-7 5SY6532-6 5SY6532-7 5SY6232-6 5SY6232-7 5SY6332-6 5SY6332-7
40 A 5SY6140-6 5SY6140-7 5SY6540-6 5SY6540-7 5SY6240-6 5SY6240-7 5SY6340-6 5SY6340-7
50 A 5SY6150-6 5SY6150-7 5SY6550-6 5SY6550-7 5SY6250-6 5SY6250-7 5SY6350-6 5SY6350-7
63 A 5SY6163-6 5SY6163-7 5SY6563-6 5SY6563-7 5SY6263-6 5SY6263-7 5SY6363-6 5SY6363-7
Mounting concept
optional optional
18 mm
36 mm
18 mm
18 mm
18 mm
9 mm
9 mm
9 mm
9 mm
9 mm
9 mm
and and or or or or
AFDD 5SY6 AS AS AS ST ST AS ST AS AS
basic unit FC FC + FC UR UR + FC UR + FC + FC
G_I201_20340
(1P+N) AS + FC AS + FC AS + FC AS + FC AS + FC AS + FC
up to
max. 40 A
18 – 72 mm
27 – 36 mm
optional optional
18 mm
18 mm
18 mm
9 mm
9 mm
9 mm
9 mm
9 mm
9 mm
and and or or or or
5SY6 RC mech. AS AS AS ST ST AS ST AS AS
basic unit and FC FC + FC UR UR + FC UR + FC + FC
AS + FC AS + FC AS + FC AS + FC AS + FC AS + FC
G_I201_20341
Adapter
AFDD Arc fault detection units See page 3/57 AS+FC Auxiliary switches and UR Undervoltage releases See page 3/55
AS Auxiliary switches See page 3/48 fault signal contacts See page 3/51 RC mech. Remote control mechanisms See page 3/56
FC Fault signal contacts See page 3/50 ST Shunt trips See page 3/54
3P+N 4P
400 V AC 400 V AC
4 MW 4 MW
1 3 5 N 1 3 5 7
2 4 6 N 2 4 6 8
Characteristic Characteristic 3
B C B C
– 5SY6614-7 – 5SY6414-7
– 5SY6605-7 – 5SY6405-7
– 5SY6601-7 – 5SY6401-7
– 5SY6615-7 – 5SY6415-7
– 5SY6602-7 – 5SY6402-7
– 5SY6603-7 – 5SY6403-7
– 5SY6604-7 – 5SY6404-7
– – – –
5SY6606-6 5SY6606-7 5SY6406-6 5SY6406-7
– 5SY6608-7 – 5SY6408-7
5SY6610-6 5SY6610-7 5SY6410-6 5SY6410-7
5SY6613-6 5SY6613-7 5SY6413-6 5SY6413-7
– – – –
5SY6616-6 5SY6616-7 5SY6416-6 5SY6416-7
5SY6620-6 5SY6620-7 5SY6420-6 5SY6420-7
5SY6625-6 5SY6625-7 5SY6425-6 5SY6425-7
– – – –
5SY6632-6 5SY6632-7 5SY6432-6 5SY6432-7
5SY6640-6 5SY6640-7 5SY6440-6 5SY6440-7
5SY6650-6 5SY6650-7 5SY6450-6 5SY6450-7
5SY6663-6 5SY6663-7 5SY6463-6 5SY6463-7
Accessories
Auxiliary switches (AS) Article No. Undervoltage releases (UR) Article No.
1 NO + 1 NC Standard 5ST3010 With integrated 230 V AC 5ST3040
For low power 5ST3013 auxiliary switch 110 V DC 5ST3041
For low power (with diode) 5ST3013-0XX01 24 V DC 5ST3042
2 NO Standard 5ST3011 Without integrated 230 V AC 5ST3043
For low power 5ST3014 auxiliary switch 110 V DC 5ST3044
2 NC Standard 5ST3012 24 V DC 5ST3045
For low power 5ST3015 Remote control mechanisms (RC mech.) Article No.
1 CO Standard 5ST3016 Basic 12 ... 30 V AC, 12 ... 48 V DC 5ST3053
Fault signal contacts (FC) Article No. 177 … 270 V AC 5ST3054
1 NO + 1 NC 5ST3020 Power 12 ... 30 V AC, 12 ... 48 V DC 5ST3055
2 NO 5ST3021 177 … 270 V AC 5ST3056
2 NC 5ST3022 Power with ARD 12 ... 30 V AC, 12 ... 48 V DC 5ST3057
Auxiliary switches and fault signal contacts (AS+FC) Article No. 177 … 270 V AC 5ST3058
1 CO (AS) + 1 CO (FC) 5ST3062 Power with extended 12 ... 30 V AC, 12 ... 48 V DC 5ST3070
5ST3 COM (AS+FC) 5ST3062-0MC function 170 … 277 V AC, 77 … 286 V DC 5ST3071
Shunt trips (ST) Article No. Adapters for remote control mechanisms (RC mech.) Article No.
110 … 415 V AC, 110 … 220 V DC 5ST3030 1 … 2 MW 5ST3820-1
24 ... 48 V AC/DC 5ST3031 3 … 4 MW 5ST3820-2
12 V DC 5ST3031-0XX01 Arc fault detection units (AFDD) Article No.
For basic units 1P+N (2 MW), In up to 16 A 5SM6021-2
not in combination with RC mech. I up to 40 A 5SM6024-2
n
1P 1P+N 2P
230/400 V AC 230 V AC 400 V AC
Mounting 1 MW 2 MW 2 MW
width
1 1 N 1 3
2 2 N 2 4
3 Rated Characteristic Characteristic Characteristic
current In A B C D A B C D A B C D
0.3 A – – 5SY4114-7 5SY4114-8 – – 5SY4514-7 5SY4514-8 – – 5SY4214-7 5SY4214-8
0.5 A 5SY4105-5 – 5SY4105-7 5SY4105-8 – – 5SY4505-7 5SY4505-8 5SY4205-5 – 5SY4205-7 5SY4205-8
1A 5SY4101-5 5SY4101-6 5SY4101-7 5SY4101-8 5SY4501-5 – 5SY4501-7 5SY4501-8 5SY4201-5 5SY4201-6 5SY4201-7 5SY4201-8
1.6 A 5SY4115-5 5SY4115-6 5SY4115-7 5SY4115-8 5SY4515-5 5SY4515-6 5SY4515-7 5SY4515-8 5SY4215-5 5SY4215-6 5SY4215-7 5SY4215-8
2A 5SY4102-5 5SY4102-6 5SY4102-7 5SY4102-8 5SY4502-5 – 5SY4502-7 5SY4502-8 5SY4202-5 5SY4202-6 5SY4202-7 5SY4202-8
3A 5SY4103-5 5SY4103-6 5SY4103-7 5SY4103-8 5SY4503-5 – 5SY4503-7 5SY4503-8 5SY4203-5 5SY4203-6 5SY4203-7 5SY4203-8
4A 5SY4104-5 5SY4104-6 5SY4104-7 5SY4104-8 5SY4504-5 5SY4504-6 5SY4504-7 5SY4504-8 5SY4204-5 5SY4204-6 5SY4204-7 5SY4204-8
5A – – 5SY4111-7 – – – – – – – 5SY4211-7 –
6A 5SY4106-5 5SY4106-6 5SY4106-7 5SY4106-8 5SY4506-5 5SY4506-6 5SY4506-7 5SY4506-8 5SY4206-5 5SY4206-6 5SY4206-7 5SY4206-8
8A 5SY4108-5 5SY4108-6 5SY4108-7 5SY4108-8 5SY4508-5 – 5SY4508-7 5SY4508-8 5SY4208-5 5SY4208-6 5SY4208-7 5SY4208-8
10 A 5SY4110-5 5SY4110-6 5SY4110-7 5SY4110-8 5SY4510-5 5SY4510-6 5SY4510-7 5SY4510-8 5SY4210-5 5SY4210-6 5SY4210-7 5SY4210-8
13 A 5SY4113-5 5SY4113-6 5SY4113-7 5SY4113-8 5SY4513-5 5SY4513-6 5SY4513-7 5SY4513-8 5SY4213-5 5SY4213-6 5SY4213-7 5SY4213-8
15 A – – 5SY4118-7 – – – – – – – 5SY4218-7 –
16 A 5SY4116-5 5SY4116-6 5SY4116-7 5SY4116-8 5SY4516-5 5SY4516-6 5SY4516-7 5SY4516-8 5SY4216-5 5SY4216-6 5SY4216-7 5SY4216-8
20 A 5SY4120-5 5SY4120-6 5SY4120-7 5SY4120-8 5SY4520-5 5SY4520-6 5SY4520-7 5SY4520-8 5SY4220-5 5SY4220-6 5SY4220-7 5SY4220-8
25 A 5SY4125-5 5SY4125-6 5SY4125-7 5SY4125-8 5SY4525-5 5SY4525-6 5SY4525-7 5SY4525-8 5SY4225-5 5SY4225-6 5SY4225-7 5SY4225-8
30 A – – 5SY4130-7 – – – – – – – 5SY4230-7 –
32 A 5SY4132-5 5SY4132-6 5SY4132-7 5SY4132-8 5SY4532-5 5SY4532-6 5SY4532-7 5SY4532-8 5SY4232-5 5SY4232-6 5SY4232-7 5SY4232-8
35 A – – 5SY4135-7 – – – – – – – 5SY4235-7 –
40 A 5SY4140-5 5SY4140-6 5SY4140-7 5SY4140-8 5SY4540-5 5SY4540-6 5SY4540-7 5SY4540-8 5SY4240-5 5SY4240-6 5SY4240-7 5SY4240-8
45 A – – 5SY4145-7 – – – – – – – 5SY4245-7 –
50 A 5SY4150-5 5SY4150-6 5SY4150-7 5SY4150-8 5SY4550-5 5SY4550-6 5SY4550-7 5SY4550-8 5SY4250-5 5SY4250-6 5SY4250-7 5SY4250-8
60 A – – 5SY4160-7 – – – – – – – 5SY4260-7 –
63 A 5SY4163-5 5SY4163-6 5SY4163-7 5SY4163-8 5SY4563-5 5SY4563-6 5SY4563-7 5SY4563-8 5SY4263-5 5SY4263-6 5SY4263-7 5SY4263-8
80 A – 5SY4180-6 5SY4180-7 – – – 5SY4580-7 – – 5SY4280-6 5SY4280-7 –
Mounting concept
optional optional
18 mm
36 mm
18 mm
18 mm
18 mm
9 mm
9 mm
9 mm
9 mm
9 mm
9 mm
and and or or or or
G_I201_20342
AFDD 5SY4 AS AS AS ST ST AS ST AS AS
basic unit (1P+N) FC FC + FC UR UR + FC UR + FC + FC
up to max. 40 A AS + FC AS + FC AS + FC AS + FC AS + FC AS + FC
18 – 72 mm
27 – 36 mm
optional optional
18 mm
18 mm
18 mm
9 mm
9 mm
9 mm
9 mm
9 mm
9 mm
and and or or or or
5SY4 RC mech. AS AS AS ST ST AS ST AS AS
basic unit and FC FC + FC UR UR + FC UR + FC + FC
G_I201_20343
AS + FC AS + FC AS + FC AS + FC AS + FC AS + FC
Adapter
3P 3P+N 4P
400 V AC 400 V AC 400 V AC
3 MW 4 MW 4 MW
1 3 5 1 3 5 N 1 3 5 7
2 4 6 2 4 6 N 2 4 6 8
Characteristic Characteristic Characteristic 3
A B C D A B C D A B C D
– – 5SY4314-7 5SY4314-8 – – 5SY4614-7 5SY4614-8 – – 5SY4414-7 5SY4414-8
5SY4305-5 – 5SY4305-7 5SY4305-8 – – 5SY4605-7 5SY4605-8 – – 5SY4405-7 5SY4405-8
5SY4301-5 5SY4301-6 5SY4301-7 5SY4301-8 5SY4601-5 – 5SY4601-7 5SY4601-8 5SY4401-5 – 5SY4401-7 5SY4401-8
5SY4315-5 5SY4315-6 5SY4315-7 5SY4315-8 5SY4615-5 – 5SY4615-7 5SY4615-8 5SY4415-5 – 5SY4415-7 5SY4415-8
5SY4302-5 5SY4302-6 5SY4302-7 5SY4302-8 5SY4602-5 – 5SY4602-7 5SY4602-8 5SY4402-5 – 5SY4402-7 5SY4402-8
5SY4303-5 5SY4303-6 5SY4303-7 5SY4303-8 5SY4603-5 – 5SY4603-7 5SY4603-8 5SY4403-5 – 5SY4403-7 5SY4403-8
5SY4304-5 5SY4304-6 5SY4304-7 5SY4304-8 5SY4604-5 – 5SY4604-7 5SY4604-8 5SY4404-5 – 5SY4404-7 5SY4404-8
– – 5SY4311-7 – – – – – – – – –
5SY4306-5 5SY4306-6 5SY4306-7 5SY4306-8 5SY4606-5 5SY4606-6 5SY4606-7 5SY4606-8 5SY4406-5 5SY4406-6 5SY4406-7 5SY4406-8
5SY4308-5 5SY4308-6 5SY4308-7 5SY4308-8 5SY4608-5 – 5SY4608-7 5SY4608-8 5SY4408-5 – 5SY4408-7 5SY4408-8
5SY4310-5 5SY4310-6 5SY4310-7 5SY4310-8 5SY4610-5 5SY4610-6 5SY4610-7 5SY4610-8 5SY4410-5 5SY4410-6 5SY4410-7 5SY4410-8
5SY4313-5 5SY4313-6 5SY4313-7 5SY4313-8 5SY4613-5 5SY4613-6 5SY4613-7 5SY4613-8 5SY4413-5 5SY4413-6 5SY4413-7 5SY4413-8
– – 5SY4318-7 – – – – – – – – –
5SY4316-5 5SY4316-6 5SY4316-7 5SY4316-8 5SY4616-5 5SY4616-6 5SY4616-7 5SY4616-8 5SY4416-5 5SY4416-6 5SY4416-7 5SY4416-8
5SY4320-5 5SY4320-6 5SY4320-7 5SY4320-8 5SY4620-5 5SY4620-6 5SY4620-7 5SY4620-8 5SY4420-5 5SY4420-6 5SY4420-7 5SY4420-8
5SY4325-5 5SY4325-6 5SY4325-7 5SY4325-8 5SY4625-5 5SY4625-6 5SY4625-7 5SY4625-8 5SY4425-5 5SY4425-6 5SY4425-7 5SY4425-8
– – 5SY4330-7 – – – – – – – – –
5SY4332-5 5SY4332-6 5SY4332-7 5SY4332-8 5SY4632-5 5SY4632-6 5SY4632-7 5SY4632-8 5SY4432-5 5SY4432-6 5SY4432-7 5SY4432-8
– – 5SY4335-7 – – – – – – – – –
5SY4340-5 5SY4340-6 5SY4340-7 5SY4340-8 5SY4640-5 5SY4640-6 5SY4640-7 5SY4640-8 5SY4440-5 5SY4440-6 5SY4440-7 5SY4440-8
– – 5SY4345-7 – – – – – – – – –
5SY4350-5 5SY4350-6 5SY4350-7 5SY4350-8 5SY4650-5 5SY4650-6 5SY4650-7 5SY4650-8 5SY4450-5 5SY4450-6 5SY4450-7 5SY4450-8
– – 5SY4360-7 – – – – – – – – –
5SY4363-5 5SY4363-6 5SY4363-7 5SY4363-8 5SY4663-5 5SY4663-6 5SY4663-7 5SY4663-8 5SY4463-5 5SY4463-6 5SY4463-7 5SY4463-8
– 5SY4380-6 5SY4380-7 – – – 5SY4680-7 – – 5SY4480-6 5SY4480-7 –
Accessories
Auxiliary switches (AS) Article No. Arc fault detection units (AFDD) Article No.
1 NO + 1 NC Standard 5ST3010 For basic units 1P+N In up to 16 A 5SM6021-2
For low power 5ST3013 (2 MW) In up to 40 A 5SM6024-2
For low power (with diode) 5ST3013-0XX01 Undervoltage releases (UR) Article No.
2 NO Standard 5ST3011 With integrated 230 V AC 5ST3040
For low power 5ST3014 auxiliary switch 110 V DC 5ST3041
2 NC Standard 5ST3012 24 V DC 5ST3042
For low power 5ST3015 Without integrated 230 V AC 5ST3043
1 CO Standard 5ST3016 auxiliary switch 110 V DC 5ST3044
Fault signal contacts (FC) Article No. 24 V DC 5ST3045
1 NO + 1 NC 5ST3020 Remote control mechanisms (RC mech.) Article No.
2 NO 5ST3021 Basic 12 ... 30 V AC, 12 ... 48 V DC 5ST3053
2 NC 5ST3022 177 … 270 V AC 5ST3054
Auxiliary switches and fault signal contacts (AS+FC) Article No. Power 12 ... 30 V AC, 12 ... 48 V DC 5ST3055
1 CO (AS) + 1 CO (FC) 5ST3062 177 … 270 V AC 5ST3056
5ST3 COM (AS+FC) 5ST3062-0MC Power with ARD 12 ... 30 V AC, 12 ... 48 V DC 5ST3057
Shunt trips (ST) Article No. 177 … 270 V AC 5ST3058
110 … 415 V AC, 110 … 220 V DC 5ST3030 Power with extended 12 ... 30 V AC, 12 ... 48 V DC 5ST3070
24 … 48 V AC/DC 5ST3031 function 170 … 277 V AC, 77 … 286 V DC 5ST3071
12 V DC 5ST3031-0XX01 Adapters for remote control mechanisms (RC mech.) Article No.
1 … 2 MW 5ST3820-1
3 … 4 MW 5ST3820-2
1P 2P
230/400 V AC 400 V AC
Mounting width 1.5 MW 3 MW
1 1 3
2 2 4
3 Rated current In Characteristic Characteristic
B C D B C D
80 A 5SP4180-6 5SP4180-7 5SP4180-8 5SP4280-6 5SP4280-7 5SP4280-8
100 A 5SP4191-6 5SP4191-7 5SP4191-8 5SP4291-6 5SP4291-7 5SP4291-8
125 A 5SP4192-6 5SP4192-7 – 5SP4292-6 5SP4292-7 –
Mounting concept
27 – 108 mm
optional optional
36 mm
18 mm
18 mm
18 mm
9 mm
9 mm
9 mm
9 mm
9 mm
9 mm
and and or or or or
5SP4 RC mech. AS AS AS ST ST AS ST AS AS
basic unit and FC FC + FC UR UR + FC UR + FC + FC
AS + FC AS + FC AS + FC AS + FC AS + FC AS + FC
G_I201_20344
Adapter
3P 4P
400 V AC 400 V AC
4.5 MW 6 MW
1 3 5 1 3 5 7
2 4 6 2 4 6 8
Characteristic Characteristic 3
B C D B C D
5SP4380-6 5SP4380-7 5SP4380-8 5SP4480-6 5SP4480-7 5SP4480-8
5SP4391-6 5SP4391-7 5SP4391-8 5SP4491-6 5SP4491-7 5SP4491-8
5SP4392-6 5SP4392-7 – 5SP4492-6 5SP4492-7 –
Accessories
Auxiliary switches (AS) Article No. Undervoltage releases (UR) Article No.
1 NO + 1 NC Standard 5ST3010 With integrated 230 V AC 5ST3040
For low power 5ST3013 auxiliary switch 110 V DC 5ST3041
For low power (with diode) 5ST3013-0XX01 24 V DC 5ST3042
2 NO Standard 5ST3011 Without integrated 230 V AC 5ST3043
For low power 5ST3014 auxiliary switch 110 V DC 5ST3044
2 NC Standard 5ST3012 24 V DC 5ST3045
For low power 5ST3015 Remote control mechanisms (RC mech.) Article No.
1 CO Standard 5ST3016 Power 12 ... 30 V AC, 12 ... 48 V DC 5ST3055
Fault signal contacts (FC) Article No. 177 … 270 V AC 5ST3056
1 NO + 1 NC 5ST3020 Power with ARD 12 ... 30 V AC, 12 ... 48 V DC 5ST3057
2 NO 5ST3021 177 … 270 V AC 5ST3058
2 NC 5ST3022 Power with extended 12 ... 30 V AC, 12 ... 48 V DC 5ST3070
Auxiliary switches and fault signal contacts (AS+FC) Article No. function
1 CO (AS) + 1 CO (FC) 5ST3062 Adapters for remote control mechanisms (RC mech.) Article No.
5ST3 COM (AS+FC) 5ST3062-0MC 1.5 MW 5ST3820-1
Shunt trips (ST) Article No. 3 … 6 MW 5ST3820-2
110 … 415 V AC, 110 … 220 V DC 5ST3030
24 ... 48 V AC/DC 5ST3031
12 V DC 5ST3031-0XX01
1P 2P
220 V DC 440 V DC
Mounting width 1.5 MW 3 MW
1 1 3
2 2 4
3 Rated current In
80 A 5SP5180-7CC 5SP5280-7CC
100 A 5SP5191-7CC 5SP5291-7CC
125 A 5SP5192-7CC 5SP5292-7CC
Mounting concept
27 – 108 mm
optional optional
36 mm
18 mm
18 mm
18 mm
9 mm
9 mm
9 mm
9 mm
9 mm
9 mm
or or or or
and and
5SP5 RC mech. AS AS AS ST ST AS ST AS AS
basic unit and FC FC + FC UR UR + FC UR + FC + FC
AS + FC AS + FC AS + FC AS + FC AS + FC AS + FC
I201_20345
Adapter
Accessories
Auxiliary switches (AS) Article No. Undervoltage releases (UR) Article No.
1 NO + 1 NC Standard 5ST3010 With integrated 230 V AC 5ST3040
For low power 5ST3013 auxiliary switch 110 V DC 5ST3041
For low power (with diode) 5ST3013-0XX01 24 V DC 5ST3042
2 NO Standard 5ST3011 Without integrated 230 V AC 5ST3043
For low power 5ST3014 auxiliary switch 110 V DC 5ST3044
2 NC Standard 5ST3012 24 V DC 5ST3045
For low power 5ST3015 Remote control mechanisms (RC mech.) Article No.
1 CO Standard 5ST3016 Power 12 ... 30 V AC, 12 ... 48 V DC 5ST3055
Fault signal contacts (FC) Article No. 177 … 270 V AC 5ST3056
1 NO + 1 NC 5ST3020 Power with ARD 12 ... 30 V AC, 12 ... 48 V DC 5ST3057
2 NO 5ST3021 177 … 270 V AC 5ST3058
2 NC 5ST3022 Power with extended 12 ... 30 V AC, 12 ... 48 V DC 5ST3070
Auxiliary switches and fault signal contacts (AS+FC) Article No. function
1 CO (AS) + 1 CO (FC) 5ST3062 Adapters for remote control mechanisms (RC mech.) Article No.
5ST3 COM (AS+FC) 5ST3062-0MC 1.5 MW 5ST3820-1
Shunt trips (ST) Article No. 3 … 6 MW 5ST3820-2
110 … 415 V AC, 110 … 220 V DC 5ST3030
24 ... 48 V AC/DC 5ST3031
12 V DC 5ST3031-0XX01
1P 2P 4P
230/400 V AC, 220 V DC 400 V AC, 440 V DC 400 V AC, 880 V DC
Mounting width 1 MW 2 MW 4 MW
1 1 3 1 3 5 7
2 2 4 2 4 6 8
3 Rated current In Characteristic Characteristic Characteristic
B C B C B C
0.3 A – 5SY5114-7 – 5SY5214-7 – 5SY5414-7
0.5 A – 5SY5105-7 – 5SY5205-7 – 5SY5405-7
1A – 5SY5101-7 – 5SY5201-7 – 5SY5401-7
1.6 A – 5SY5115-7 – 5SY5215-7 – 5SY5415-7
2A 5SY5102-6 5SY5102-7 5SY5202-6 5SY5202-7 – 5SY5402-7
3A – 5SY5103-7 – 5SY5203-7 – 5SY5403-7
4A 5SY5104-6 5SY5104-7 5SY5204-6 5SY5204-7 – 5SY5404-7
6A 5SY5106-6 5SY5106-7 5SY5206-6 5SY5206-7 5SY5406-6 5SY5406-7
8A 5SY5108-6 5SY5108-7 5SY5208-6 5SY5208-7 – 5SY5408-7
10 A 5SY5110-6 5SY5110-7 5SY5210-6 5SY5210-7 5SY5410-6 5SY5410-7
13 A 5SY5113-6 5SY5113-7 5SY5213-6 5SY5213-7 5SY5413-6 5SY5413-7
16 A 5SY5116-6 5SY5116-7 5SY5216-6 5SY5216-7 5SY5416-6 5SY5416-7
20 A 5SY5120-6 5SY5120-7 5SY5220-6 5SY5220-7 5SY5420-6 5SY5420-7
25 A 5SY5125-6 5SY5125-7 5SY5225-6 5SY5225-7 5SY5425-6 5SY5425-7
32 A 5SY5132-6 5SY5132-7 5SY5232-6 5SY5232-7 5SY5432-6 5SY5432-7
40 A 5SY5140-6 5SY5140-7 5SY5240-6 5SY5240-7 5SY5440-6 5SY5440-7
50 A 5SY5150-6 5SY5150-7 5SY5250-6 5SY5250-7 5SY5450-6 5SY5450-7
63 A 5SY5163-6 5SY5163-7 5SY5263-6 5SY5263-7 5SY5463-6 5SY5463-7
Mounting concept
18 – 72 mm
27 – 36 mm
optional optional
18 mm
18 mm
18 mm
9 mm
9 mm
9 mm
9 mm
9 mm
9 mm
and and or or or or
5SY5 RC mech. AS AS AS ST ST AS ST AS AS
basic unit and FC FC + FC UR UR + FC UR + FC + FC
AS + FC AS + FC AS + FC AS + FC AS + FC AS + FC
G_I201_20346
Adapter
Accessories
Auxiliary switches (AS) Article No. Undervoltage releases (UR) Article No.
1 NO + 1 NC Standard 5ST3010 With integrated 230 V AC 5ST3040
For low power 5ST3013 auxiliary switch 110 V DC 5ST3041
For low power (with diode) 5ST3013-0XX01 24 V DC 5ST3042
2 NO Standard 5ST3011 Without integrated 230 V AC 5ST3043
For low power 5ST3014 auxiliary switch 110 V DC 5ST3044
2 NC Standard 5ST3012 24 V DC 5ST3045
For low power 5ST3015 Remote control mechanisms (RC mech.) Article No.
1 CO Standard 5ST3016 Basic 12 ... 30 V AC, 12 ... 48 V DC 5ST3053
Fault signal contacts (FC) Article No. 177 … 270 V AC 5ST3054
1 NO + 1 NC 5ST3020 Power 12 ... 30 V AC, 12 ... 48 V DC 5ST3055
2 NO 5ST3021 177 … 270 V AC 5ST3056
2 NC 5ST3022 Power with ARD 12 ... 30 V AC, 12 ... 48 V DC 5ST3057
Auxiliary switches and fault signal contacts (AS+FC) Article No. 177 … 270 V AC 5ST3058
1 CO (AS) + 1 CO (FC) 5ST3062 Power with extended 12 ... 30 V AC, 12 ... 48 V DC 5ST3070
5ST3 COM (AS+FC) 5ST3062-0MC function 170 … 277 V AC, 77 … 286 V DC 5ST3071
Shunt trips (ST) Article No. Adapters for remote control mechanisms (RC mech.) Article No.
110 … 415 V AC, 110 … 220 V DC 5ST3030 1 … 2 MW 5ST3820-1
24 ... 48 V AC/DC 5ST3031 4 MW 5ST3820-2
12 V DC 5ST3031-0XX01
1P 1P+N 2P
230/400 V AC 230 V AC 400 V AC
Mounting width 1 MW 2 MW 2 MW
1 1 N 1 3
2 2 N 2 4
3 Rated Main MCB, line Characteristic Characteristic Characteristic
current In side of meter B C D B C D B C D
0.3 A – – 5SY7114-7 5SY7114-8 – 5SY7514-7 5SY7514-8 – 5SY7214-7 5SY7214-8
0.5 A – – 5SY7105-7 5SY7105-8 – 5SY7505-7 5SY7505-8 – 5SY7205-7 5SY7205-8
1A – – 5SY7101-7 5SY7101-8 – 5SY7501-7 5SY7501-8 – 5SY7201-7 5SY7201-8
1.6 A – – 5SY7115-7 5SY7115-8 – 5SY7515-7 5SY7515-8 – 5SY7215-7 5SY7215-8
2A – – 5SY7102-7 5SY7102-8 – 5SY7502-7 5SY7502-8 – 5SY7202-7 5SY7202-8
3A – – 5SY7103-7 5SY7103-8 – 5SY7503-7 5SY7503-8 – 5SY7203-7 5SY7203-8
4A – – 5SY7104-7 5SY7104-8 – 5SY7504-7 5SY7504-8 – 5SY7204-7 5SY7204-8
6A – 5SY7106-6 5SY7106-7 5SY7106-8 5SY7506-6 5SY7506-7 5SY7506-8 5SY7206-6 5SY7206-7 5SY7206-8
■ 5SY7106-6KK13 – – – – – – – –
8A – – 5SY7108-7 5SY7108-8 – 5SY7508-7 5SY7508-8 – 5SY7208-7 5SY7208-8
10 A – 5SY7110-6 5SY7110-7 5SY7110-8 5SY7510-6 5SY7510-7 5SY7510-8 5SY7210-6 5SY7210-7 5SY7210-8
■ 5SY7110-6KK13 – – – – – – – –
13 A – 5SY7113-6 5SY7113-7 5SY7113-8 5SY7513-6 5SY7513-7 5SY7513-8 5SY7213-6 5SY7213-7 5SY7213-8
16 A – 5SY7116-6 5SY7116-7 5SY7116-8 5SY7516-6 5SY7516-7 5SY7516-8 5SY7216-6 5SY7216-7 5SY7216-8
20 A – 5SY7120-6 5SY7120-7 5SY7120-8 5SY7520-6 5SY7520-7 5SY7520-8 5SY7220-6 5SY7220-7 5SY7220-8
25 A – 5SY7125-6 5SY7125-7 5SY7125-8 5SY7525-6 5SY7525-7 5SY7525-8 5SY7225-6 5SY7225-7 5SY7225-8
32 A – 5SY7132-6 5SY7132-7 5SY7132-8 5SY7532-6 5SY7532-7 5SY7532-8 5SY7232-6 5SY7232-7 5SY7232-8
40 A – 5SY7140-6 5SY7140-7 5SY7140-8 5SY7540-6 5SY7540-7 5SY7540-8 5SY7240-6 5SY7240-7 5SY7240-8
50 A – 5SY7150-6 5SY7150-7 5SY7150-8 5SY7550-6 5SY7550-7 5SY7550-8 5SY7250-6 5SY7250-7 5SY7250-8
63 A – 5SY7163-6 5SY7163-7 5SY7163-8 5SY7563-6 5SY7563-7 5SY7563-8 5SY7263-6 5SY7263-7 5SY7263-8
Mounting concept
optional optional
18 mm
36 mm
18 mm
18 mm
18 mm
9 mm
9 mm
9 mm
9 mm
9 mm
9 mm
and and or or or or
G_I201_20347
AFDD 5SY7 AS AS AS ST ST AS ST AS AS
basic unit (1P+N) FC FC + FC UR UR + FC UR + FC + FC
up to max. 40 A AS + FC AS + FC AS + FC AS + FC AS + FC AS + FC
18 – 72 mm
27 – 36 mm
optional optional
18 mm
18 mm
18 mm
9 mm
9 mm
9 mm
9 mm
9 mm
9 mm
and and or or or or
5SY7 RC-Mech. AS AS AS ST ST AS ST AS AS
basic unit und FC FC + FC UR UR + FC UR + FC + FC
G_I201_20348
AS + FC AS + FC AS + FC AS + FC AS + FC AS + FC
Adapter
AFDD Arc fault detection units See page 3/57 AS+FC Auxiliary switches and UR Undervoltage releases See page 3/55
AS Auxiliary switches See page 3/48 fault signal contacts See page 3/51 RC mech. Remote control mechanisms See page 3/56
FC Fault signal contacts See page 3/50 ST Shunt trips See page 3/54
3P 3P+N 4P
400 V AC 400 V AC 400 V AC
3 MW 4 MW 4 MW
1 3 5 1 3 5 N 1 3 5 7
2 4 6 2 4 6 N 2 4 6 8
Characteristic Characteristic Characteristic 3
B C D B C D B C D
– 5SY7314-7 5SY7314-8 – 5SY7614-7 5SY7614-8 – 5SY7414-7 5SY7414-8
– 5SY7305-7 5SY7305-8 – 5SY7605-7 5SY7605-8 – 5SY7405-7 5SY7405-8
– 5SY7301-7 5SY7301-8 – 5SY7601-7 5SY7601-8 – 5SY7401-7 5SY7401-8
– 5SY7315-7 5SY7315-8 – 5SY7615-7 5SY7615-8 – 5SY7415-7 5SY7415-8
– 5SY7302-7 5SY7302-8 – 5SY7602-7 5SY7602-8 – 5SY7402-7 5SY7402-8
– 5SY7303-7 5SY7303-8 – 5SY7603-7 5SY7603-8 – 5SY7403-7 5SY7403-8
– 5SY7304-7 5SY7304-8 – 5SY7604-7 5SY7604-8 – 5SY7404-7 5SY7404-8
5SY7306-6 5SY7306-7 5SY7306-8 5SY7606-6 5SY7606-7 5SY7606-8 5SY7406-6 5SY7406-7 5SY7406-8
– – – – – – – – –
– 5SY7308-7 5SY7308-8 – 5SY7608-7 5SY7608-8 – 5SY7408-7 5SY7408-8
5SY7310-6 5SY7310-7 5SY7310-8 5SY7610-6 5SY7610-7 5SY7610-8 5SY7410-6 5SY7410-7 5SY7410-8
– – – – – – – – –
5SY7313-6 5SY7313-7 5SY7313-8 5SY7613-6 5SY7613-7 5SY7613-8 5SY7413-6 5SY7413-7 5SY7413-8
5SY7316-6 5SY7316-7 5SY7316-8 5SY7616-6 5SY7616-7 5SY7616-8 5SY7416-6 5SY7416-7 5SY7416-8
5SY7320-6 5SY7320-7 5SY7320-8 5SY7620-6 5SY7620-7 5SY7620-8 5SY7420-6 5SY7420-7 5SY7420-8
5SY7325-6 5SY7325-7 5SY7325-8 5SY7625-6 5SY7625-7 5SY7625-8 5SY7425-6 5SY7425-7 5SY7425-8
5SY7332-6 5SY7332-7 5SY7332-8 5SY7632-6 5SY7632-7 5SY7632-8 5SY7432-6 5SY7432-7 5SY7432-8
5SY7340-6 5SY7340-7 5SY7340-8 5SY7640-6 5SY7640-7 5SY7640-8 5SY7440-6 5SY7440-7 5SY7440-8
5SY7350-6 5SY7350-7 5SY7350-8 5SY7650-6 5SY7650-7 5SY7650-8 5SY7450-6 5SY7450-7 5SY7450-8
5SY7363-6 5SY7363-7 5SY7363-8 5SY7663-6 5SY7663-7 5SY7663-8 5SY7463-6 5SY7463-7 5SY7463-8
Accessories
Auxiliary switches (AS) Article No. Undervoltage releases (UR) Article No.
1 NO + 1 NC Standard 5ST3010 With integrated 230 V AC 5ST3040
For low power 5ST3013 auxiliary switch 110 V DC 5ST3041
For low power (with diode) 5ST3013-0XX01 24 V DC 5ST3042
2 NO Standard 5ST3011 Without integrated 230 V AC 5ST3043
For low power 5ST3014 auxiliary switch 110 V DC 5ST3044
2 NC Standard 5ST3012 24 V DC 5ST3045
For low power 5ST3015 Remote control mechanisms (RC mech.) Article No.
1 CO Standard 5ST3016 Basic 12 ... 30 V AC, 12 ... 48 V DC 5ST3053
Fault signal contacts (FC) Article No. 177 … 270 V AC 5ST3054
1 NO + 1 NC 5ST3020 Power 12 ... 30 V AC, 12 ... 48 V DC 5ST3055
2 NO 5ST3021 177 … 270 V AC 5ST3056
2 NC 5ST3022 Power with ARD 12 ... 30 V AC, 12 ... 48 V DC 5ST3057
Auxiliary switches and fault signal contacts (AS+FC) Article No. 177 … 270 V AC 5ST3058
1 CO (AS) + 1 CO (FC) 5ST3062 Power with extended 12 ... 30 V AC, 12 ... 48 V DC 5ST3070
5ST3 COM (AS+FC) 5ST3062-0MC function 170 … 277 V AC, 77 … 286 V DC 5ST3071
Shunt trips (ST) Article No. Adapters for remote control mechanisms (RC mech.) Article No.
110 … 415 V AC, 110 … 220 V DC 5ST3030 1 … 2 MW 5ST3820-1
24 … 48 V AC/DC 5ST3031 3 … 4 MW 5ST3820-2
12 V DC 5ST3031-0XX01 Arc fault detection units (AFDD) Article No.
For basic units 1P+N In up to 16 A 5SM6021-2
(2 MW) I up to 40 A 5SM6024-2
n
1P 1P+N 2P 3P
230/400 V AC 230 V AC 400 V AC 400 V AC
Mounting width 1 MW 2 MW 2 MW 3 MW
1 1 N 1 3 1 3 5
2 N 2 4 6
3 2 2 4
Rated current In Characteristic Characteristic Characteristic Characteristic
C D C D C D C D
0.3 A 5SY8114-7 5SY8114-8 5SY8514-7 5SY8514-8 5SY8214-7 5SY8214-8 5SY8314-7 5SY8314-8
0.5 A 5SY8105-7 5SY8105-8 5SY8505-7 5SY8505-8 5SY8205-7 5SY8205-8 5SY8305-7 5SY8305-8
1A 5SY8101-7 5SY8101-8 5SY8501-7 5SY8501-8 5SY8201-7 5SY8201-8 5SY8301-7 5SY8301-8
1.6 A 5SY8115-7 5SY8115-8 5SY8515-7 5SY8515-8 5SY8215-7 5SY8215-8 5SY8315-7 5SY8315-8
2A 5SY8102-7 5SY8102-8 5SY8502-7 5SY8502-8 5SY8202-7 5SY8202-8 5SY8302-7 5SY8302-8
3A 5SY8103-7 5SY8103-8 5SY8503-7 5SY8503-8 5SY8203-7 5SY8203-8 5SY8303-7 5SY8303-8
4A 5SY8104-7 5SY8104-8 5SY8504-7 5SY8504-8 5SY8204-7 5SY8204-8 5SY8304-7 5SY8304-8
6A 5SY8106-7 5SY8106-8 5SY8506-7 5SY8506-8 5SY8206-7 5SY8206-8 5SY8306-7 5SY8306-8
8A 5SY8108-7 5SY8108-8 5SY8508-7 5SY8508-8 5SY8208-7 5SY8208-8 5SY8308-7 5SY8308-8
10 A 5SY8110-7 5SY8110-8 5SY8510-7 5SY8510-8 5SY8210-7 5SY8210-8 5SY8310-7 5SY8310-8
12.5 A – – – – – – – –
13 A 5SY8113-7 5SY8113-8 5SY8513-7 5SY8513-8 5SY8213-7 5SY8213-8 5SY8313-7 5SY8313-8
16 A 5SY8116-7 5SY8116-8 5SY8516-7 5SY8516-8 5SY8216-7 5SY8216-8 5SY8316-7 5SY8316-8
20 A 5SY8120-7 5SY8120-8 5SY8520-7 5SY8520-8 5SY8220-7 5SY8220-8 5SY8320-7 5SY8320-8
25 A 5SY8125-7 5SY8125-8 5SY8525-7 5SY8525-8 5SY8225-7 5SY8225-8 5SY8325-7 5SY8325-8
32 A 5SY8132-7 5SY8132-8 5SY8532-7 5SY8532-8 5SY8232-7 5SY8232-8 5SY8332-7 5SY8332-8
40 A 5SY8140-7 5SY8140-8 5SY8540-7 5SY8540-8 5SY8240-7 5SY8240-8 5SY8340-7 5SY8340-8
50 A 5SY8150-7 5SY8150-8 5SY8550-7 5SY8550-8 5SY8250-7 5SY8250-8 5SY8350-7 5SY8350-8
63 A 5SY8163-7 5SY8163-8 5SY8563-7 5SY8563-8 5SY8263-7 5SY8263-8 5SY8363-7 5SY8363-8
Mounting concept
optional
36 mm
18 mm
18 mm
18 mm
9 mm
9 mm
9 mm
9 mm
9 mm
9 mm
and or or or or
G_I201_20349
5SY8 AS AS AS ST ST AS ST AS AS
basic unit FC FC + FC UR UR + FC UR + FC + FC
(1P+N) AS + FC AS + FC AS + FC AS + FC AS + FC AS + FC
18 – 72 mm
27 – 36 mm
optional optional
18 mm
18 mm
18 mm
9 mm
9 mm
9 mm
9 mm
9 mm
9 mm
and and or or or or
5SY8 RC mech. AS AS AS ST ST AS ST AS AS
basic unit and FC FC + FC UR UR + FC UR + FC + FC
G_I201_20350
AS + FC AS + FC AS + FC AS + FC AS + FC AS + FC
Adapter
AFDD Arc fault detection units See page 3/57 AS+FC Auxiliary switches and UR Undervoltage releases See page 3/55
AS Auxiliary switches See page 3/48 fault signal contacts See page 3/51 RC mech. Remote control mechanisms See page 3/56
FC Fault signal contacts See page 3/50 ST Shunt trips See page 3/54
3P+N 4P
400 V AC 400 V AC
4 MW 4 MW
1 3 5 N 1 3 5 7
2 4 6 N 2 4 6 8 3
Characteristic Characteristic
C D C D
5SY8614-7 5SY8614-8 5SY8414-7 5SY8414-8
5SY8605-7 5SY8605-8 5SY8405-7 5SY8405-8
5SY8601-7 5SY8601-8 5SY8401-7 5SY8401-8
5SY8615-7 5SY8615-8 5SY8415-7 5SY8415-8
5SY8602-7 5SY8602-8 5SY8402-7 5SY8402-8
5SY8603-7 5SY8603-8 5SY8403-7 5SY8403-8
5SY8604-7 5SY8604-8 5SY8404-7 5SY8404-8
5SY8606-7 5SY8606-8 5SY8406-7 5SY8406-8
5SY8608-7 5SY8608-8 5SY8408-7 5SY8408-8
5SY8610-7 5SY8610-8 5SY8410-7 5SY8410-8
– – – –
5SY8613-7 5SY8613-8 5SY8413-7 5SY8413-8
5SY8616-7 5SY8616-8 5SY8416-7 5SY8416-8
5SY8620-7 5SY8620-8 5SY8420-7 5SY8420-8
5SY8625-7 5SY8625-8 5SY8425-7 5SY8425-8
5SY8632-7 5SY8632-8 5SY8432-7 5SY8432-8
5SY8640-7 5SY8640-8 5SY8440-7 5SY8440-8
5SY8650-7 5SY8650-8 5SY8450-7 5SY8450-8
5SY8663-7 5SY8663-8 5SY8463-7 5SY8463-8
Accessories
Auxiliary switches (AS) Article No. Undervoltage releases (UR) Article No.
1 NO + 1 NC Standard 5ST3010 With integrated 230 V AC 5ST3040
For low power 5ST3013 auxiliary switch 110 V DC 5ST3041
For low power (with diode) 5ST3013-0XX01 24 V DC 5ST3042
2 NO Standard 5ST3011 Without integrated 230 V AC 5ST3043
For low power 5ST3014 auxiliary switch 110 V DC 5ST3044
2 NC Standard 5ST3012 24 V DC 5ST3045
For low power 5ST3015 Remote control mechanisms (RC mech.) Article No.
1 CO Standard 5ST3016 Basic 12 ... 30 V AC, 12 ... 48 V DC 5ST3053
Fault signal contacts (FC) Article No. 177 … 270 V AC 5ST3054
1 NO + 1 NC 5ST3020 Power 12 ... 30 V AC, 12 ... 48 V DC 5ST3055
2 NO 5ST3021 177 … 270 V AC 5ST3056
2 NC 5ST3022 Power with ARD 12 ... 30 V AC, 12 ... 48 V DC 5ST3057
Auxiliary switches and fault signal contacts (AS+FC) Article No. 177 … 270 V AC 5ST3058
1 CO (AS) + 1 CO (FC) 5ST3062 Power with extended 12 ... 30 V AC, 12 ... 48 V DC 5ST3070
5ST3 COM (AS+FC) 5ST3062-0MC function 170 … 277 V AC, 77 … 286 V DC 5ST3071
Shunt trips (ST) Article No. Adapters for remote control mechanisms (RC mech.) Article No.
110 … 415 V AC, 110 … 220 V DC 5ST3030 1 … 2 MW 5ST3820-1
24 … 48 V AC/DC 5ST3031 3 … 4 MW 5ST3820-2
12 V DC 5ST3031-0XX01
2 2
3 Rated current In Characteristic Characteristic
B C D C C D D
0.3 A – 5SJ4114-7HG40 5SJ4114-8HG40 5SJ4114-7HG41 5SJ4114-7HG42 5SJ4114-8HG41 5SJ4114-8HG42
0.5 A – 5SJ4105-7HG40 5SJ4105-8HG40 5SJ4105-7HG41 5SJ4105-7HG42 5SJ4105-8HG41 5SJ4105-8HG42
1A – 5SJ4101-7HG40 5SJ4101-8HG40 5SJ4101-7HG41 5SJ4101-7HG42 5SJ4101-8HG41 5SJ4101-8HG42
1.6 A – 5SJ4115-7HG40 5SJ4115-8HG40 5SJ4115-7HG41 5SJ4115-7HG42 5SJ4115-8HG41 5SJ4115-8HG42
2A – 5SJ4102-7HG40 5SJ4102-8HG40 5SJ4102-7HG41 5SJ4102-7HG42 5SJ4102-8HG41 5SJ4102-8HG42
3A – 5SJ4103-7HG40 5SJ4103-8HG40 5SJ4103-7HG41 5SJ4103-7HG42 5SJ4103-8HG41 5SJ4103-8HG42
4A – 5SJ4104-7HG40 5SJ4104-8HG40 5SJ4104-7HG41 5SJ4104-7HG42 5SJ4104-8HG41 5SJ4104-8HG42
5A – 5SJ4111-7HG40 5SJ4111-8HG40 5SJ4111-7HG41 5SJ4111-7HG42 5SJ4111-8HG41 5SJ4111-8HG42
6A 5SJ4106-6HG40 5SJ4106-7HG40 5SJ4106-8HG40 5SJ4106-7HG41 5SJ4106-7HG42 5SJ4106-8HG41 5SJ4106-8HG42
8A – 5SJ4108-7HG40 5SJ4108-8HG40 5SJ4108-7HG41 5SJ4108-7HG42 5SJ4108-8HG41 5SJ4108-8HG42
10 A 5SJ4110-6HG40 5SJ4110-7HG40 5SJ4110-8HG40 5SJ4110-7HG41 5SJ4110-7HG42 5SJ4110-8HG41 5SJ4110-8HG42
13 A 5SJ4113-6HG40 5SJ4113-7HG40 5SJ4113-8HG40 5SJ4113-7HG41 5SJ4113-7HG42 5SJ4113-8HG41 5SJ4113-8HG42
15 A 5SJ4118-6HG40 5SJ4118-7HG40 5SJ4118-8HG40 5SJ4118-7HG41 5SJ4118-7HG42 5SJ4118-8HG41 5SJ4118-8HG42
16 A 5SJ4116-6HG40 5SJ4116-7HG40 5SJ4116-8HG40 5SJ4116-7HG41 5SJ4116-7HG42 5SJ4116-8HG41 5SJ4116-8HG42
20 A 5SJ4120-6HG40 5SJ4120-7HG40 5SJ4120-8HG40 5SJ4120-7HG41 5SJ4120-7HG42 5SJ4120-8HG41 5SJ4120-8HG42
25 A 5SJ4125-6HG40 5SJ4125-7HG40 5SJ4125-8HG40 5SJ4125-7HG41 5SJ4125-7HG42 5SJ4125-8HG41 5SJ4125-8HG42
30 A 5SJ4130-6HG40 5SJ4130-7HG40 5SJ4130-8HG40 5SJ4130-7HG41 5SJ4130-7HG42 5SJ4130-8HG41 5SJ4130-8HG42
32 A 5SJ4132-6HG40 5SJ4132-7HG40 5SJ4132-8HG40 5SJ4132-7HG41 5SJ4132-7HG42 5SJ4132-8HG41 5SJ4132-8HG42
35 A 5SJ4135-6HG40 5SJ4135-7HG40 5SJ4135-8HG40 5SJ4135-7HG41 5SJ4135-7HG42 5SJ4135-8HG41 –
40 A 5SJ4140-6HG40 5SJ4140-7HG40 5SJ4140-8HG40 5SJ4140-7HG41 5SJ4140-7HG42 5SJ4140-8HG41 –
45 A 5SJ4145-6HG40 5SJ4145-7HG40 5SJ4145-8HG40 5SJ4145-7HG41 – 5SJ4145-8HG41 –
50 A 5SJ4150-6HG40 5SJ4150-7HG40 5SJ4150-8HG40 5SJ4150-7HG41 – 5SJ4150-8HG41 –
60 A 5SJ4160-6HG40 5SJ4160-7HG40 5SJ4160-8HG40 5SJ4160-7HG41 – 5SJ4160-8HG41 –
63 A 5SJ4163-6HG40 5SJ4163-7HG40 5SJ4163-8HG40 5SJ4163-7HG41 – 5SJ4163-8HG41 –
Mounting concept
18 – 54 mm
optional
18 mm
18 mm
18 mm
9 mm
9 mm
9 mm
9 mm
9 mm
9 mm
and or or or or
G_I201_20351
5SJ4..HG.. AS AS AS ST ST AS ST AS AS
+ + + +
basic unit FC FC FC FC FC FC
2P 3P
240 V AC 480Y/277 V AC 240 V AC 480Y/277 V AC 240 V AC 480Y/277 V AC 240 V AC 480Y/277 V AC
2 MW 3 MW
1 3 1 3 5
2 4 2 4 6
Characteristic Characteristic 3
C C D D C C D D
5SJ4214-7HG41 5SJ4214-7HG42 5SJ4214-8HG41 5SJ4214-8HG42 5SJ4314-7HG41 5SJ4314-7HG42 5SJ4314-8HG41 5SJ4314-8HG42
5SJ4205-7HG41 5SJ4205-7HG42 5SJ4205-8HG41 5SJ4205-8HG42 5SJ4305-7HG41 5SJ4305-7HG42 5SJ4305-8HG41 5SJ4305-8HG42
5SJ4201-7HG41 5SJ4201-7HG42 5SJ4201-8HG41 5SJ4201-8HG42 5SJ4301-7HG41 5SJ4301-7HG42 5SJ4301-8HG41 5SJ4301-8HG42
5SJ4215-7HG41 5SJ4215-7HG42 5SJ4215-8HG41 5SJ4215-8HG42 5SJ4315-7HG41 5SJ4315-7HG42 5SJ4315-8HG41 5SJ4315-8HG42
5SJ4202-7HG41 5SJ4202-7HG42 5SJ4202-8HG41 5SJ4202-8HG42 5SJ4302-7HG41 5SJ4302-7HG42 5SJ4302-8HG41 5SJ4302-8HG42
5SJ4203-7HG41 5SJ4203-7HG42 5SJ4203-8HG41 5SJ4203-8HG42 5SJ4303-7HG41 5SJ4303-7HG42 5SJ4303-8HG41 5SJ4303-8HG42
5SJ4204-7HG41 5SJ4204-7HG42 5SJ4204-8HG41 5SJ4204-8HG42 5SJ4304-7HG41 5SJ4304-7HG42 5SJ4304-8HG41 5SJ4304-8HG42
5SJ4211-7HG41 5SJ4211-7HG42 5SJ4211-8HG41 5SJ4211-8HG42 5SJ4311-7HG41 5SJ4311-7HG42 5SJ4311-8HG41 5SJ4311-8HG42
5SJ4206-7HG41 5SJ4206-7HG42 5SJ4206-8HG41 5SJ4206-8HG42 5SJ4306-7HG41 5SJ4306-7HG42 5SJ4306-8HG41 5SJ4306-8HG42
5SJ4208-7HG41 5SJ4208-7HG42 5SJ4208-8HG41 5SJ4208-8HG42 5SJ4308-7HG41 5SJ4308-7HG42 5SJ4308-8HG41 5SJ4308-8HG42
5SJ4210-7HG41 5SJ4210-7HG42 5SJ4210-8HG41 5SJ4210-8HG42 5SJ4310-7HG41 5SJ4310-7HG42 5SJ4310-8HG41 5SJ4310-8HG42
5SJ4213-7HG41 5SJ4213-7HG42 5SJ4213-8HG41 5SJ4213-8HG42 5SJ4313-7HG41 5SJ4313-7HG42 5SJ4313-8HG41 5SJ4313-8HG42
5SJ4218-7HG41 5SJ4218-7HG42 5SJ4218-8HG41 5SJ4218-8HG42 5SJ4318-7HG41 5SJ4318-7HG42 5SJ4318-8HG41 5SJ4318-8HG42
5SJ4216-7HG41 5SJ4216-7HG42 5SJ4216-8HG41 5SJ4216-8HG42 5SJ4316-7HG41 5SJ4316-7HG42 5SJ4316-8HG41 5SJ4316-8HG42
5SJ4220-7HG41 5SJ4220-7HG42 5SJ4220-8HG41 5SJ4220-8HG42 5SJ4320-7HG41 5SJ4320-7HG42 5SJ4320-8HG41 5SJ4320-8HG42
5SJ4225-7HG41 5SJ4225-7HG42 5SJ4225-8HG41 5SJ4225-8HG42 5SJ4325-7HG41 5SJ4325-7HG42 5SJ4325-8HG41 5SJ4325-8HG42
5SJ4230-7HG41 5SJ4230-7HG42 5SJ4230-8HG41 5SJ4230-8HG42 5SJ4330-7HG41 5SJ4330-7HG42 5SJ4330-8HG41 5SJ4330-8HG42
5SJ4232-7HG41 5SJ4232-7HG42 5SJ4232-8HG41 5SJ4232-8HG42 5SJ4332-7HG41 5SJ4332-7HG42 5SJ4332-8HG41 5SJ4332-8HG42
5SJ4235-7HG41 5SJ4235-7HG42 5SJ4235-8HG41 – 5SJ4335-7HG41 5SJ4335-7HG42 5SJ4335-8HG41 –
5SJ4240-7HG41 5SJ4240-7HG42 5SJ4240-8HG41 – 5SJ4340-7HG41 5SJ4340-7HG42 5SJ4340-8HG41 –
5SJ4245-7HG41 – 5SJ4245-8HG41 – 5SJ4345-7HG41 – 5SJ4345-8HG41 –
5SJ4250-7HG41 – 5SJ4250-8HG41 – 5SJ4350-7HG41 – 5SJ4350-8HG41 –
5SJ4260-7HG41 – 5SJ4260-8HG41 – 5SJ4360-7HG41 – 5SJ4360-8HG41 –
5SJ4263-7HG41 – 5SJ4263-8HG41 – 5SJ4363-7HG41 – 5SJ4363-8HG41 –
Accessories
Auxiliary switches (AS) acc. to UL 489 Article No.
1 NO + 1 NC 5ST3010-0HG
2 NO 5ST3011-0HG
2 NC 5ST3012-0HG
Fault signal contacts (FC) acc. to UL 489 Article No.
1 NO + 1 NC 5ST3020-0HG
2 NO 5ST3021-0HG
2 NC 5ST3022-0HG
Shunt trips (ST) acc. to UL 489 Article No.
110 … 415 V AC, 110 … 220 V DC 5ST3030-0HG
24 ... 48 V AC/DC 5ST3031-0HG
18 mm
18 mm
9 mm
9 mm
9 mm
and and or
1 N
3
2 N AFDD 5SL60 AS AS AS
basic unit FC FC + FC
G_I201_20352
Rated Characteristic (not for KL types) AS + FC AS + FC AS + FC
current In B C
2A 5SL6002-6MC 5SL6002-7MC
4A 5SL6004-6MC 5SL6004-7MC
6A 5SL6006-6MC 5SL6006-7MC
8A – 5SL6008-7MC
27 – 36 mm
optional optional
18 mm
9 mm
9 mm
9 mm
10 A 5SL6010-6MC 5SL6010-7MC and and or
13 A 5SL6013-6MC 5SL6013-7MC
16 A 5SL6016-6MC 5SL6016-7MC
20 A 5SL6020-6MC 5SL6020-7MC
5SL60 RC mech. AS AS AS
25 A 5SL6025-6MC 5SL6025-7MC basic unit and FC FC + FC
AS + FC AS + FC AS + FC
G_I201_20353
32 A 5SL6032-6MC 5SL6032-7MC
Adapter
Accessories
Auxiliary switches (AS) Article No. Remote control mechanisms (RC mech.) Article No.
1 NO + 1 NC Standard 5ST3010 Basic 12 ... 30 V AC, 12 ... 48 V DC 5ST3053
For low power 5ST3013 177 … 270 V AC 5ST3054
For low power (with diode) 5ST3013-0XX01 Power 12 ... 30 V AC, 12 ... 48 V DC 5ST3055
2 NO Standard 5ST3011 177 … 270 V AC 5ST3056
For low power 5ST3014 Power with ARD 12 ... 30 V AC, 12 ... 48 V DC 5ST3057
2 NC Standard 5ST3012 177 … 270 V AC 5ST3058
For low power 5ST3015 Power with extended 12 ... 30 V AC, 12 ... 48 V DC 5ST3070
1 CO Standard 5ST3016 function 170 … 277 V AC, 77 … 286 V DC 5ST3071
Fault signal contacts (FC) Article No. Adapters for remote control mechanisms (RC mech.) Article No.
1 NO + 1 NC 5ST3020 1 MW 5ST3820-6
2 NO 5ST3021 Arc fault detection units (AFDD) Article No.
2 NC 5ST3022 For basic units 1P + N In up to 16 A 5SM6011-2
Auxiliary switches and fault signal contacts (AS+FC) Article No. (1 MW), not for KL types I up to 40 A 5SM6014-2
n
1 CO (AS) + 1 CO (FC) 5ST3062
5ST3 COM (AS+FC) 5ST3062-0MC
7KN1110-0MC00
7KN Powercenter 1000
See page 10/20
You will find further information at
www.siemens.com/lowvoltage/manuals
Installation Manual – SENTRON
... ... ... ... circuit protection devices with
communication and measuring
function (109791805)
5SL6 COM 5ST3 COM 5SV6 COM 3NA COM
MCB AS+FC AFDD Fuse System Manual – SENTRON circuit
max. 24 protection devices with communi
Wireless Protocol
cation and measuring function
(109791806)
S S S S
3 2 2 4 6
Rated current In Characteristic Characteristic
E E
L1 L2 L3 L1 + L2 + L3
16 A 5SP3716-2KK01 5SP3716-2KK02 5SP3716-2KK03 5SP3716-2 5SP3816-2
20 A 5SP3720-2KK01 5SP3720-2KK02 5SP3720-2KK03 5SP3720-2 5SP3820-2
25 A 5SP3725-2KK01 5SP3725-2KK02 5SP3725-2KK03 5SP3725-2 5SP3825-2
35 A 5SP3735-2KK01 5SP3735-2KK02 5SP3735-2KK03 5SP3735-2 5SP3835-2
40 A 5SP3740-2KK01 5SP3740-2KK02 5SP3740-2KK03 5SP3740-2 5SP3840-2
50 A 5SP3750-2KK01 5SP3750-2KK02 5SP3750-2KK03 5SP3750-2 5SP3850-2
63 A 5SP3763-2KK01 5SP3763-2KK02 5SP3763-2KK03 5SP3763-2 5SP3863-2
S S S S S S S S S S S S S
2 2 4 6 2 4 2 2 2 2 4 6 8 3
Rated current In Characteristic Characteristic Characteristic Characteristic Characteristic
E E E E E
16 A 5SP3716-3 5SP3816-3 5SP3216-3 5SP3316-3 5SP3416-3
20 A 5SP3720-3 5SP3820-3 5SP3220-3 5SP3320-3 5SP3420-3
25 A 5SP3725-3 5SP3825-3 5SP3225-3 5SP3325-3 5SP3425-3
35 A 5SP3735-3 5SP3835-3 5SP3235-3 5SP3335-3 5SP3435-3
40 A 5SP3740-3 5SP3840-3 5SP3240-3 5SP3340-3 5SP3440-3
50 A 5SP3750-3 5SP3850-3 5SP3250-3 5SP3350-3 5SP3450-3
63 A 5SP3763-3 5SP3863-3 5SP3263-3 5SP3363-3 5SP3463-3
1P+AS
230 V AC/12 … 72 V DC
Mounting width 1 MW (18 mm)
1 13
I201_20322
2 14
Mounting concept
27 – 36 mm
optional optional
18 mm
9 mm
9 mm
9 mm
and and or
5SY17 RC mech. AS AS AS
basic unit and FC FC + FC
AS + FC AS + FC AS + FC
G_I201_20354
Adapter
Accessories
Auxiliary switches (AS) Article No. Auxiliary switches and fault signal contacts (AS+FC) Article No.
1 NO + 1 NC Standard 5ST3010 1 CO (AS) + 1 CO (FC) 5ST3062
For low power 5ST3013 5ST3 COM (AS+FC) 5ST3062-0MC
For low power (with diode) 5ST3013-0XX01 Remote control mechanisms (RC mech.) Article No.
2 NO Standard 5ST3011 Basic 12 ... 30 V AC, 12 ... 48 V DC 5ST3053
For low power 5ST3014 177 … 270 V AC 5ST3054
2 NC Standard 5ST3012 Power 12 ... 30 V AC, 12 ... 48 V DC 5ST3055
For low power 5ST3015 177 … 270 V AC 5ST3056
1 CO Standard 5ST3016 Power with ARD 12 ... 30 V AC, 12 ... 48 V DC 5ST3057
Fault signal contacts (FC) Article No. 177 … 270 V AC 5ST3058
1 NO + 1 NC 5ST3020 Power with extended 12 ... 30 V AC, 12 ... 48 V DC 5ST3070
2 NO 5ST3021 function 170 … 277 V AC, 77 … 286 V DC 5ST3071
2 NC 5ST3022 Adapters for remote control mechanisms (RC mech.) Article No.
1 MW 5ST3820-6
1P+AS
24 V DC
Mounting width 6.2 mm
1 13
I201_20322
2 14
Rated current In 3
1A 5SK9101-1
2A 5SK9102-1
3A 5SK9103-1
4A 5SK9104-1
6A 5SK9106-1
8A 5SK9108-1
Specific accessories
Connecting combs
Type Number of poles Max. load current Imax Article No.
For parallel infeed 2-pole 24 A 8WH9020-6BC10
32 A 8WH9020-6CC10
5-pole 24 A 8WH9020-6BF10
32 A 8WH9020-6CF10
For remote signal – group signal 2-pole 32 A 8WH9020-6CC10
Reducing combs for terminal blocks of 10 mm2
Type Number of poles Max. load current Imax Article No.
For bypassing the power supply 2-pole 40 A 8WH9020-0AC10
5SL60/
5SL3 5SL6 5SL4 5SJ6...-.KS 5SL30 5SY
5SL6 COM
Auxiliary switches (AS) Article No.
1 NO + 1 NC Standard 5ST3010 ■ ■ ■ – ■ ■ ■
3 For low power 5ST3013 ■ ■ ■ – ■ ■ ■
For low power (with diode) 5ST3013-0XX01 ■ ■ ■ – ■ ■ ■
2 NO Standard 5ST3011 ■ ■ ■ – ■ ■ ■
For low power 5ST3014 ■ ■ ■ – ■ ■ ■
2 NC Standard 5ST3012 ■ ■ ■ – ■ ■ ■
For low power 5ST3015 ■ ■ ■ – ■ ■ ■
1 CO Standard 5ST3016 ■ ■ ■ – ■ ■ ■
5ST1010-0FP – – – – – – –
Fault signal contacts (FC) Article No.
1 NO + 1 NC 5ST3020 ■ ■ ■ – ■ ■ ■
2 NO 5ST3021 ■ ■ ■ – ■ ■ ■
2 NC 5ST3022 ■ ■ ■ – ■ ■ ■
■ ...-0HG ■ ■ ■ ■ ■ ■ – ■ □ ■ ■ ■
■ – ■ ■ ■ ■ ■ ■ – ■ □ ■ ■ ■ 3
■ – ■ ■ ■ ■ ■ ■ – ■ □ ■ ■ ■
■ ...-0HG ■ ■ ■ ■ ■ ■ – ■ □ ■ ■ ■
■ – ■ ■ ■ ■ ■ ■ – ■ □ ■ ■ ■
■ ...-0HG ■ ■ ■ ■ ■ ■ – ■ □ ■ ■ ■
■ – ■ ■ ■ ■ ■ ■ – ■ □ ■ ■ ■
■ – ■ ■ ■ ■ ■ ■ – ■ □ ■ ■ ■
– – – – – – – – ■ – – – – –
■ ...-0HG ■ ■ ■ ■ ■ ■ – ■ □ ■ – –
■ ...-0HG ■ ■ ■ ■ ■ ■ – ■ □ ■ – –
■ ...-0HG ■ ■ ■ ■ ■ ■ – ■ □ ■ – –
■ – ■ ■ ■ ■ ■ ■ – ■ □ ■ – –
■ – ■ ■ ■ ■ ■ ■ – ■ □ ■ – –
■ ...-0HG – ■ ■ ■ ■ ■ – – □ – – –
■ ...-0HG – ■ ■ ■ ■ ■ – – □ – – –
■ – – ■ ■ ■ ■ ■ – – □ – – –
■ – – ■ ■ ■ ■ ■ – – □ – – –
■ – – ■ ■ ■ ■ ■ – – □ – – –
■ – – ■ ■ ■ ■ ■ – – □ – – –
■ – – ■ ■ ■ ■ ■ – – □ – – –
■ – – ■ ■ ■ ■ ■ – – □ – – –
■ – – ■ ■ ■ ■ ■ – – □ – – –
– – ■ – – – ■ – – ■ – – – ■
– – ■ – – – ■ – – ■ – – – ■
■ – ■ ■ ■ – ■ – – ■ – – – ■
■ – ■ ■ ■ – ■ – – ■ – – – ■
■ – ■ ■ ■ – ■ – – ■ – – – ■
■ – ■ ■ ■ – ■ – – ■ – – – ■
■ – ■ ■ ■ – ■ – – ■ – – – –
– – ■ ■ – – ■ – – ■ – – – –
– – – – – – ■ – – – – – – –
– – – – – – – – – ■ – – – –
– – – – – – ■ – – – – – – –
– – – – – – – – – ■ – – – –
■ ■ ■ ■ ■ ■ ■ ■ ■ ■ □ ■ □ ■
■ ■ ■ ■ ■ ■ ■ ■ ■ ■ □ ■ □ ■
– – ■ ■ – – – – – ■ ■ ■ – –
– – – ■ – – – – – ■ ■ ■ – –
From page 3/12 From From page 4/18 From page 4/52 From page 5/6
page
3/44
Electrical accessories
Auxiliary switches (AS)
• Signals the contact position of the mounted device
• Version for the switching of small currents and voltages
according to EN 61131-2 for control of programmable control
systems (PLCs)
• Test button enables the testing of control circuits without the
need to switch the mounted device
For combining with basic units Contacts Version Mounting Article No.
Miniature Circuit RCCBs RCBOs Arc fault ON/OFF width
3 circuit
breakers
breakers for
equipment
detection
devices
switches (1 MW =
18 mm)
Auxiliary switches (AS)
5SL, 5SY, 5SY17 5SV 5SU1 1), 5SV6 5TL1, 5TE8 1 NO + 1 NC Standard 0.5 MW 5ST3010
5SP4, 5SP5 5SV1 For low power 0.5 MW 5ST3013
For low power 0.5 MW 5ST3013-0XX01
(with diode)
2 NO Standard 0.5 MW 5ST3011
For low power 0.5 MW 5ST3014
2 NC Standard 0.5 MW 5ST3012
For low power 0.5 MW 5ST3015
1 CO Standard 0.5 MW 5ST3016
Auxiliary switches (AS) with TEST button
5SL, 5SY, 5SY17 5SV 5SU1 1), 5SV6 5TL1, 5TE8 1 NO + 1 NC Standard 0.5 MW 5ST3010-2
5SP4, 5SP5 5SV1 For low power 0.5 MW 5ST3013-2
2 NO Standard 0.5 MW 5ST3011-2
For low power 0.5 MW 5ST3014-2
2 NC Standard 0.5 MW 5ST3012-2
For low power 0.5 MW 5ST3015-2
Auxiliary switches (AS) acc. to UL 489
5SJ4...-.HG – – – – 1 NO + 1 NC Standard 0.5 MW 5ST3010-0HG
2 NO Standard 0.5 MW 5ST3011-0HG
2 NC Standard 0.5 MW 5ST3012-0HG
1)
5ST3805-1 handle coupler required
5ST3010, 5ST3013,
5ST3011, 5ST3010-0HG, 5ST3010-2, 5ST3014, 5ST3013-2,
5ST3012, 5ST3011-0HG, 5ST3011-2, 5ST3015, 5ST3014-2,
Further technical specifications 5ST3016 5ST3012-0HG 5ST3012-2 5ST3013-0XX01 1) 5ST3015-2
Standards
Standards IEC/EN IEC/EN 62019, – IEC/EN 62019, IEC/EN 60947-5-1
IEC/EN 60947-5-1
UL, CSA UL 1077, UL 489, – UL 1077, –
CSA C22.2 No. 235 CSA 22.2 No. 5-02 CSA C22.2 No. 235
Contacts
Minimum contact load 50 mA, 24 V 1 mA, 5 V DC 5 mA, 5 V DC 3
Maximum contact load – 100 mA, 30 V DC 50 mA, 30 V DC
Contact load acc. to IEC/EN 62019/ 230 V AC, AC-12 –
IEC/EN 60947-5-1 230 V AC, AC-13 6 A/6 A –
400 V AC, AC-13 2 A/2 A –
230 V AC, AC-14 6 A/6 A –
400 V AC, AC-14 2 A/2 A –
24 V DC, DC-13 6 A/3 A –
30 V DC, DC-14 – 0.1 A
60 V DC, DC-13 3 A/1.5 A –
110 V DC, DC-13 1 A/0.75 A –
220 V DC, DC-12 –
220 V DC, DC-13 1 A/0.5 A –
Contact load acc. to UL 120 V AC – 6A –
125 V AC 3A –
240 V AC 4A –
277 V AC – 3A –
480 V AC 1.5 A –
60 V DC – 3A –
125 V DC 1.1 A 1A –
250 V DC 0.55 A –
Service life, on average, with rated load Actuations 20000 12000 20000
Safety
Short-circuit protection 5SY… 6A miniature circuit breaker or gG 6 A fuse
Connections
Conductor cross-sections 0.5 … 2.5 mm2 (AWG 22 … 14)
Terminals Max. tightening torque 0.5 Nm (4.5 lb-in)
Ambient conditions
Permissible ambient temperature –40 ... +70 °C
Permissible storage temperature –40 ... +75 °C
Resistance to climate Acc. to IEC 60068-2-30 28 cycles
Mounting position Any
Shock at 11 ms half-sine Acc. to IEC 60068-2-27 150 m/s2
Resistance to vibrations at 5 ... 150 Hz Acc. to IEC 60068-2-6 50 m/s2
1)
No approvals
Electrical accessories
Fault signal contacts (FC)
• Signals automatic tripping of the circuit protection device in the event
of a fault, such as an overload or a short circuit
• If the fault signal contact is activated, the contact position does not change
if the mounted circuit protection device is tripped manually
• Version with TEST and RESET buttons enables the testing of control circuits
without operation of the circuit protection device
• Red RESET button in the operating handle indicates automatic tripping
of the mounted circuit protection device
3 For combining with basic units Contacts Mounting width Article No.
Miniature circuit Circuit breakers for RCCBs RCBOs Arc fault (1 MW = 18 mm)
breakers equipment detection devices
Fault signal contacts (FC)
5SL, 5SY, 5SP4, 5SY17 5SV 5SU1 1), 5SV1 5SV6 1 NO + 1 NC 0.5 MW 5ST3020
5SP5 2 NO 0.5 MW 5ST3021
2 NC 0.5 MW 5ST3022
Fault signal contacts (FC) with TEST and RESET button
5SL, 5SY, 5SP4, 5SY17 5SV 5SU1 1), 5SV1 5SV6 1 NO + 1 NC 0.5 MW 5ST3020-2
5SP5 2 NO 0.5 MW 5ST3021-2
2 NC 0.5 MW 5ST3022-2
Fault signal contacts (FC) acc. to UL 489
5SJ4...-.HG – – – – 1 NO + 1 NC 0.5 MW 5ST3020-0HG
2 NO 0.5 MW 5ST3021-0HG
2 NC 0.5 MW 5ST3022-0HG
1)
5ST3805-1 handle coupler required
For combining with basic units Contacts Mounting width Article No.
Miniature circuit Circuit breakers for RCCBs RCBOs Arc fault (1 MW = 18 mm)
breakers equipment detection devices 3
Auxiliary switches and fault signal contacts (AS+FC)
5SL, 5SY, 5SP4, 5SY17 5SV 5SU1 1), 5SV1 5SV6 1 CO (AS) + 1 CO (FC) 0.5 MW 5ST3062
5SP5
1)
5ST3805-1 handle coupler required
Electrical accessories
5ST3 COM auxiliary switches and fault signal contacts (AS+FC)
with communication and measuring function
• Reports the switching state of the mounted standard circuit protection device
(ON, tripped, manual OFF, tripped with locked handle)
• Measures the temperature of the device and counts operating cycles, trips and operating hours
• Communication via radio to 7KN Powercenter 1000 data transceiver
• Plug-in terminals for 24 V DC power supply incl. daisy chain function
• Low space requirements of 0.5 MW (9 mm)
Note:
Please note the country-specific radio licenses of the products in SIOS
www.siemens.com/lowvoltage/certificates (109801197)
SENTRON SENTRON
• Wireless radio transmission of 3
powerconfig powerconfig mobile measured values and data to the
or other 7KN Powercenter 1000 data
Software transceiver
Solutions
• Commissioning, parameter assign-
Modbus TCP ment, firmware updates and
further processing of the data via
the 7KN Powercenter 1000 data
transceiver
7KN1110-0MC00
7KN Powercenter 1000
See page 10/20
You will find further information at
www.siemens.com/lowvoltage/manuals
Installation Manual – SENTRON
... ... ... ... circuit protection devices with
communication and measuring
function (109791805)
5SL6 COM 5ST3 COM 5SV6 COM 3NA COM
MCB AS+FC AFDD Fuse System Manual – SENTRON circuit
max. 24 protection devices with communi
Wireless Protocol
cation and measuring function
(109791806)
Electrical accessories
Shunt trips (ST)
• For remote-controlled tripping of the mounted device
For combining with basic units Rated operational voltage Ue Mounting width Article No.
Miniature circuit breakers RCCBs RCBOs (1 MW = 18 mm)
Shunt trips (ST)
5SL4, 5SY, 5SP 5SV 5SU1 1) 110 … 415 V AC, 110 … 220 V DC 1 MW 5ST3030
24 ... 48 V AC/DC 1 MW 5ST3031
12 V DC 1 MW 5ST3031-0XX01
Shunt trips (ST) acc. to UL 489
3 5SJ4...-.HG – – 110 … 415 V AC, 110 … 220 V DC 1 MW 5ST3030-0HG
24 ... 60 V AC/DC 1 MW 5ST3031-0HG
1)
5ST3805-1 handle coupler required
For combining with basic units Rated operational voltage Ue Mounting width Article No. 3
Miniature circuit breakers RCCBs RCBOs (1 MW = 18 mm)
With integrated auxiliary switch
5SL4, 5SY, 5SP4, 5SP5 5SV 5SU1 1) 230 V AC 1 MW 5ST3040
110 V DC 1 MW 5ST3041
24 V DC 1 MW 5ST3042
Without integrated auxiliary switch
5SL4, 5SY, 5SP4, 5SP5 5SV 5SU1 1) 230 V AC 1 MW 5ST3043
110 V DC 1 MW 5ST3044
24 V DC 1 MW 5ST3045
1)
5ST3805-1 handle coupler required
Electrical accessories
5ST3 remote control mechanisms (RC mech.)
• For locations that are spread out over a wide area or not permanently attended
• Permits direct and immediate access to the installation even if it is remote or in a location
that is hard to access
• Permits fast reconnection after a fault
• Version with ARD with automatic restart
• Versions with ARD and Power with integrated auxiliary switches and fault signal contacts
Type of remote Display Ambient Vibration and shock Rated operational voltage Ue Mounting width Article No.
control mechanism temperature requirements (1 MW = 18 mm)
3 Basic – –25 °C … +45 °C – 12 ... 30 V AC, 12 ... 48 V DC 1.5 MW 5ST3053
177 … 270 V AC 2 MW 5ST3054
Power LED –25 °C … +45 °C – 12 ... 30 V AC, 12 ... 48 V DC 2 MW 5ST3055
177 … 270 V AC 2 MW 5ST3056
Power with ARD LED –25 °C … +45 °C – 12 ... 30 V AC, 12 ... 48 V DC 2 MW 5ST3057
177 … 270 V AC 2 MW 5ST3058
Power with extended LED –40 °C … +70 °C Acc. to EN 61373/ 12 ... 30 V AC, 12 ... 48 V DC 2 MW 5ST3070
function EN 50155 "1B" 170 ... 277 V AC, 77 ... 286 V DC 2 MW 5ST3071
Further technical specifications 5ST3053 5ST3054 5ST3055 5ST3056 5ST3057 5ST3058 5ST3070 5ST3071
Standards
Standards EN 50557 (VDE 0640-20)
Supply
Rated frequency fn 50 ... 60 Hz
Rated power dissipation in standby ≤1 VA
Contacts
Service life, on average, Actuations 10000
with rated load
Number of remote switching 2
operations per minute
Number of automatic reclose attempts – 3 –
Cable length in the control circuit ≤1500 m ≤1500 m (DC)/
≤200 m (AC)
Sliding selector with locking device – ■
Integrated auxiliary switches – 1CO;
2 A; 250 V
Integrated fault signal contacts – 1CO;
2 A; 250 V
Connections
Conductor cross-sections 0.5 … 1.5 mm2 (AWG 14 … 30)
Terminal tightening torque 0.2 … 0.25 Nm (2.0 lb-in)
Ambient conditions
Permissible storage temperature –40 … +55 °C –40 … +70 °C
Degree of protection IP20
Degree of pollution for overvoltage category 3/II
For combining with basic units Rated current In Mounting width Article No.
Width of basic unit Miniature circuit breakers RCBOs (1 MW = 18 mm)
1 MW 5SL60 1P + N (no KL types) 5SV1 Up to 16 A 1 MW 5SM6011-2
Up to 40 A 1 MW 5SM6014-2 3
2 MW 5SY , 5SL4 (1P+N devices only,
1)
5SU1.5 Up to 16 A 1 MW 5SM6021-2
not compact) Up to 40 A 1 MW 5SM6024-2
1)
Not suitable for use with 5SY5, 5SY8
Mechanical accessories
Terminal cover
• For miniature circuit breakers, but not for 5SL60..
• For additional covering of the screw openings per pole
3 • Lockable
• In the case of 5SY, also prevents removal of device from the DIN rail
Article No.
5ST3800
Handle locking devices
• To prevent undesired mechanical ON/OFF switching
• Sealable and lockable
For miniature circuit breakers For padlocks with Article No.
5SP4, 5SP5, 5SY Max. 3 mm shackle 5ST3801
Padlocks
• For 5ST3801 and 5ST3806 handle locking devices and remote control mechanisms
5ST3054 … 58, 5ST3070
Article No.
5ST3802
Locking devices
• Comprising 5ST3801 or 5ST3806 handle locking device and 5ST3802 padlock
For miniature circuit breakers Comprising Article No.
5SP4, 5SP5, 5SY 5ST3801 handle locking device, 5ST3803
5ST3802 padlock
5SL, 5SV, 5TL1 5ST3806 handle locking device, 5ST3807
5ST3802 padlock
Spacers
• Can be placed on either side of the DIN rail. Two spacers allow for convenient cable routing
Mounting width Article No.
0.5 MW 5TG8240
Device labels
• For adhesive attachment
• For modular installation devices, e.g. 5SY, 5SL, 5TL1
Types Article No.
15 x 6 mm, white (WIN 098) 8WH8210-0AA35
15 x 6 mm, yellow (WIN 099) 8WH8210-0AA36
Covers
• Can be assembled as mini distribution board
• Suitable for all devices
• Cover parts prepared for rail mounting of conventional label caps
Comprising Article No.
End plate 5ST2134
Angled profile 5ST2135
Flat profile as alternative 5ST2136
Holders for front panel installation
• Universal use for devices from 1 to 6 MW
Cutout height Cutout width Article No.
45+0.5 mm 23, 41, 59, 77, 95 or 113 mm 7LF9006
Intermediate frames
• For 70 mm devices in 55 mm ALPHA SIMBOX small distribution boards
Types Article No.
1-tier 8GB4561
2-tier 8GB4562
3-tier 8GB4563
4-tier 8GB4564
Standard busbars
General information
Infeed
At the start or end of the busbar Along the busbar or midpoint infeed
3 2 1 1 2 3
3
I201_13755
S I201_13754a
S1 S2
L1 L1
14
3,4
3,4
L1 L2/N L1 L2/N
19
6,6 7,3
∅ 10 mm2 ∅ 16 mm2
3-phase Article No. Article No.
1 1 1 1 For 2 MCBs 3P 6 MW 102 mm 5ST3613 5ST3643
For 3 MCBs 3P 9 MW 157.5 mm 5ST3614 5ST3644
L3L1 L2 L3 For 4 MCBs 3P 12 MW 210 mm 5ST3615 5ST3645
15,2
L1 L2
19
L1 L2 L3L1 N L2 L3 N
19
11,8 13,3
∅ 10 mm2 ∅ 16 mm2
1 1 11 11 11 1 1 For 6 MCBs 1P+N 12 MW 210 mm 5ST3623 5ST3653
For 7 MCBs 1P+N 14 MW 248 mm 5ST3623-4 –
15,2
L1 N L2L1 N N L3L2 N N L3 N
19
11,8 13,3
∅ 10 mm2 ∅ 16 mm2
Standard busbars
Fixed lengths, cannot be cut
For MCBs equipped with auxiliary switch (AS) or fault signal contact (FC)
Pin spacing in MW Application No. of MW Length Conductor cross-section
(1 MW = 18 mm) 10 mm2 16 mm2
1-phase Article No. Article No.
1,5 For 2 MCBs 1P 2 MW 40 mm 5ST3603 5ST3633
9 mm
L1 AS L1
14
FC
3
3,4
L1 AS L1
14
FC
3,4
FC
For 5 MCBs 10 MW 210 mm – 5ST3642
7,3
(2P/1P+N)
3-phase Article No. Article No.
1 1 1
1,5 1 1,5 For 2 MCBs 3P 6 MW 115 mm 5ST3616 5ST3646
For 4 MCBs 3P 12 MW 237 mm 5ST3617 5ST3647
9 mm
9 mm
AS
L3L1 AS L2L1 L3 FC L1
15,2
L1 L2
19
FC
9,2 10,3
∅ 10 mm2 ∅ 16 mm2
1,5 1,5 1,5 1,5 1,5 1,5 For 6 MCBs 1P 9 MW 156 mm/ 5ST3618 5ST3648
158 mm
9 mm
9 mm
9 mm
9 mm
9 mm
9 mm
19
FC FC FC FC FC
9,2 10,3
∅ 10 mm2 ∅ 16 mm2
Accessories
Terminals for 5ST36 and 5ST37 Article No. Terminals for infeed at side Article No.
For conductors Cable entry on the left 5ST3768-4 For conductors Short 5ST3768
6 … 25 mm2 Cable entry in the center 5ST3768-3 6 … 25 mm2
Cable entry on the right 5ST3768-5 Short, IP20 5ST3771-2
For conductors Cable entry on the left 5ST3760-4 Touch protection Article No.
6 … 50 mm2 Cable entry in the center 5ST3760-3 For free connections, yellow (RAL 1004) 5× 1 pin 5ST3655
Cable entry on the right 5ST3760-5
72 mm
N right
15,2
L1 L2 L3L1 NL2 L1L3 L2N L3L1 L1L2 L2L3 L3L1 L1L2 L2L3 L1 L2
19
3
9,2 10,3
∅ 10 mm2 ∅ 16 mm2
1 1 2 1 1 1 1 1 1 1 1 1 For 10 MCBs 1P 14 MW 249 mm 5ST3624-4 –
with 1 RCCB 3P+N
72 mm
15,2
L1 L2 L3 N L1 L2 L3 L1 L2 L3 L1 L2 L3 L1
MCBs 1P
8,6
15,2
L1 L2 L3 N L1 L2 L3 L1 L2 L3
3 MCBs 1P
8,6
N L1 N
L2 L1
L3 L2
L1 L3
L2 L1
L3 L2
L1 L3
L2 L1
L3 L2
L1 L3
L2 L1 L2
15,2
19
9,2 10,3
∅ 10 mm2 ∅ 16 mm2
4-phase/3-phase + N Article No. Article No.
1 1 1 1 1 1 1 1 1 1 1 1 1 For 1 RCCB 3P+N, 14 MW 248 mm 5ST3724-4 –
1 MCB 3P+N and
6 MCBs 1P
pYWXYWX[_
15,2
L1 L2 L3 N L1 L2 L3 N L1 L2 L3 L1 L2 L3
10,7
15,2
L1 L2 L3 N L1 L2 L3 N L1 N L2 N L3 N
10,7
15,2
L1 L2 L3 N L1 L2 L3 L1 N L2 N L3 N
10,7
15,2
L1 L2 L3 N L1 N L2 N L3 N L1 N L2 N
10,7
Standard busbars
Can be cut
For miniature circuit breakers (MCBs)
Pin spacing in MW (1 MW = 18 mm) Application No. of Length End caps Color Conductor cross-section
MW included 10 mm2 16 mm2
1-phase, straight Article No. Article No.
1 For MCBs 1P+N 12 MW 216 mm ■ Gray 5ST3762 –
compact Blue 5ST3687-0 –
L1 L1 56 MW 1016 mm – Gray 5ST3764 –
10
5,6
18
18
20
L1
L1 N
N L2 L1 N N
N N L1 L3 L2 N N L3
L2 N N L3 N N L1 L3
L2 L1 N N N
N L1
L1
19,7 21,4
∅ 10 mm2 ∅ 16 mm2
Accessories
Terminals for 5ST36 and 5ST37 Article No. End caps Article No.
For conductors Cable entry on the left 5ST3768-4 For 1-phase busbars (MCB 1P+N compact) Gray 5ST3766
6 … 25 mm2 Cable entry in the center 5ST3768-3 Blue 5ST3767
Cable entry on the right 5ST3768-5 White 5ST3748
For conductors Cable entry on the left 5ST3760-4 For 2-phase busbars 5ST3750
6 … 50 mm2 Cable entry in the center 5ST3760-3 Touch protection Article No.
Cable entry on the right 5ST3760-5 For free connections, yellow (RAL 1004) 5× 1 pin 5ST3655
Terminals for Infeed at side Article No.
For conductors Short 5ST3768
6 … 25 mm2 Short, IP20 5ST3771-2
For MCBs equipped with auxiliary switch (AS) or fault signal contact (FC)
Pin spacing in MW Application No. of Length End caps Conductor cross-section
(1 MW = 18 mm) MW included 10 mm2 16 mm2
1-phase, angled 90° Article No. Article No.
1,5 For MCBs 1P 12 MW 214 mm ■ 5ST3732 5ST3702
56 MW 1016 mm – 5ST3733 5ST3703
9 mm
3,5
L1 AS L1 13
FC
L1 L2/N AS L1
15
FC
18
L1 L2 L3 AS L1
15
FC
18
9 mm
L1 AS L2 AS L3 AS L1
15
FC FC FC
18
9 mm
L1 N AS L2 N AS L3 N
17
FC FC
20
For MCBs equipped with undervoltage release (UR) or shunt trips (ST)
Pin spacing in MW Application No. of Length End caps Conductor cross-section
(1 MW = 18 mm) MW included
10 mm2 16 mm2
2-phase Article No. Article No.
2 2 For MCBs 1P 56 MW 1016 mm – 5ST3735-2 –
with UR/ ST
18 mm
18 mm
L1 UR L2 UR L1
17
ST ST
14
Standard busbars
Can be cut
For MCBs with line-side RCCB or RCCBs equipped with AS/FC devices
Pin spacing in MW Application No. of Length End caps Conductor cross-section
(1 MW = 18 mm) MW included 10 mm2 16 mm2
4-phase/3-phase + N Article No. Article No.
1 1,5 1 1,5 1 For RCCB / MCBs 56 MW 1016 mm – 5ST3746-2 –
9 mm
9 mm
L1 N AS L2 N AS L3 N
17
FC FC
3 1 1 1 1 1
20
L1 L2 L3 N L2 N L3 N
22,1
Accessories
Terminals for 5ST36 and 5ST37 Article No. End caps Article No.
For conductors Cable entry on the left 5ST3768-4 For 3-phase busbars 5ST3750
6 … 25 mm2 Cable entry in the center 5ST3768-3 For 4-phase busbars 5ST3718
Cable entry on the right 5ST3768-5 Touch protection Article No.
For conductors Cable entry on the left 5ST3760-4 For free connections, yellow (RAL 1004) 5× 1 pin 5ST3655
6 … 50 mm2 Cable entry in the center 5ST3760-3
Cable entry on the right 5ST3760-5
L1 L1 15
L1 L1 15
L1 L2
23
21
21
L1 L2 L3
23
21
21
Standard busbars
5ST37 acc. to UL 508, can be cut
For MCBs equipped with auxiliary switch (AS) or fault signal contact (FC)
Pin spacing in MW Application No. of MW Length Conductor cross-section
(1 MW = 18 mm) 18 mm2 25 mm2
1-phase Article No. Article No.
1,5 For MCBs 1P 56 MW 1000 mm 5ST3703-0HG –
9 mm
L1 AS L1 15
FC
L1 L2 AS L1
23
FC
21
L1 L2 L3 AS L1
23
FC
21
9 mm
L1 AS L2 AS L3 AS L1
23
FC FC FC
21
Accessories
Terminals according to UL 508 Article No. Touch protection according to UL 508 Article No.
For infeed at the device 6 … 35 mm2 5ST3770-0HG For open terminals, yellow 5× 1 pin 5ST3655-0HG
For infeed at the busbar 2.5 … 50 mm2 5ST3770-1HG
End caps according to UL 508 Article No.
For 1-phase busbars 5ST3748-0HG
For 2 and 3-phase busbars 5ST3750-0HG
1)
All unassigned pins of the busbars that cannot be cut must be covered with 5ST3666-1HG touch protection covers.
1 19,3
1 19,3
1 1 19,3
Standard busbars
5ST3.. acc. to UL 489 specially for 5SJ4... -.HG..
Can be cut, for MCBs equipped with auxiliary switch (AS) or fault signal contact (FC)
Pin spacing in MW Application No. of MW Length Conductor cross-section
(1 MW = 18 mm) 18 mm2
1-phase Article No.
L1 AS L1 For MCBs 1P 56 MW 1016 mm 5ST3703-3HG
FC
9 mm
19,3
1,5
19,3
1 1,5
19,3
1 1 1,5
9 mm
19,3
1,5 1,5 1,5
Accessories
Terminals according to UL 489 Article No. Touch protection according to UL 489 Article No.
For infeed at the 5SJ4... -.HG.. miniature 2.5 … 35 mm2 5ST3666-0HG For open terminals, yellow For 5ST37..-.HG busbars that 5ST3666-1HG
circuit breaker 6 … 35 mm2 5ST3770-3HG 3× 1 pin cannot be cut
For infeed at the busbar 2.5 … 50 mm2 5ST3666-2HG For 5ST37..-3HG busbars that 5ST3655-3HG
can be cut
End caps according to UL 489 Article No.
For 1, 2 and 3-phase busbars 5ST3750-3HG
Compact busbars
General information
Infeed
At the start or end of the busbar Along the busbar or midpoint infeed
3 2 1 1 2 3
3
I201_13755
S I201_13754a
S1 S2
Compact busbars
5ST36, fixed lengths, cannot be cut
Pin spacing in MW Application No. of Length End caps Conductor cross-
(1 MW = 18 mm) MW included section
10 mm2
2-phase/1-phase + N, for infeed via RCCB Article No.
1 2 2 For 1× RCCB 1P+N and 5× compact devices 12 MW 216 mm ■ 5ST3685-0
equipped with 5SM6 arc fault detection unit
AFDD
AFDD
13,7
L1 N L1 N L1 N
42,4
L1 N L1 N L1 N
42,4
+ AS + AS + AS
42,4
AFDD
AFDD
13,7
L1 N L1 N
42,4
L1 N L2 N L3 N L1 N
42,4 14 MW 254 mm ■ 5ST3673-4
AFDD
AFDD
13,7
L1 N L2 N L3 N
42,4
N L1 N L1 N L1 N
L1 devices
42,4
L1 N L1 N L1 N
13
40,8
AFDD
AFDD
40,8
9 mm
9 mm
with auxiliary
switch
L1 N AS L1 N AS L1 N AS
13
40,8
AFDD
AFDD
9 mm
9 mm
40,8 switch
1 2,5 For 2 MW units 54 MW 956 mm – 5ST3786-0
(MCBs or RCBOs)
AFDD
AFDD
9 mm
with mounted
5SM6 arc fault
N AS N
L1 L1 detection unit and
13
FC
40,8 auxiliary switch
Accessories
Terminals for infeed at side Article No. Touch protection Article No.
For conductors 6 … 25 mm2 Short, IP20 5ST3771-2 For free connections, For pins L1, N 5ST3655
End caps Article No. yellow (RAL 1004) For pins L2, L3 5ST3655-0HG
2 and 4-phase compact busbars 5ST3788-0
Compact busbars
5ST37, can be cut
Pin spacing in MW Application No. of Length End Conductor
(1 MW = 18 mm) MW caps cross-section
included 10 mm2
4-phase/3-phase + N, for infeed via RCCB Article No.
1 1 1 1 1 1 1 1 For 1× RCCB 3P+N 10 MW 181 mm ■ 5ST3783-1
and 6× compact
devices
pYWXYWX\\
13,7
L1 L2 L3 N L1 N L2 N L3 N L1 N L2 N L3 N For 1× RCCB 3P+N 12 MW 216 mm ■ 5ST3783-0
42,4 and 8× compact
devices
devices
1 1 1 1 1 1 1 1 For 1× RCCB 3P+N 10 MW 181 mm ■ 5ST3783-1KL
(RCCB N left only)
and 6× compact
pYWXYWX\]
N L1 L2 L3 L1 N L2 N L3 N L1 N L2 N L3 N 13,7 devices
42,4 For 1× RCCB 3P+N 12 MW 216 mm ■ 5ST3783-0KL
(RCCB N left only)
and 8× compact
devices
1 1 1 1 1 1 1 1 1 1 1 1 For 1× RCCB 14 MW 253 mm ■ 5ST3785-4
3P+N,
1× MCBs 3P and
pYWXYWX\X
13,7
L1 L2 L3 N L1 L2 L3 L1 N L2 N L3 N L1 N L2 N L3 N L1 N 7× compact
42,4 devices
1 1 1 1 1 1 1 1 1 1 1 1 1 For 1× RCCB 24 MW 430 mm ■ 5ST3790-1
3P+N,
2× MCBs 3P+N
pYWXYWX\Z
13,7
40,8 devices
1 1 1 1 1 1 1 1 1 1 1 For 1× RCCB 12 MW 217 mm ■ 5ST3795-0
3P+N,
1x MCBs 3P+N
pYWXYWX\Y
13,7
L1 L2 L3 N L1 L2 L3 N L1 N L2 N L3 N L1 N and 4× compact
42,4 devices
1 1 1 1 1 1 1 1 1 1 1 For 1× RCCB 14 MW 253 mm ■ 5ST3795-4
3P+N,
1× MCBs 3P+N
pYWXYWX\W
13,7
N L1 N L2 N L3 N L1 N L2 N L3 N
L1 L2 L3 N L1 L2 L3 and 6× compact
42,4 devices
L1 N L2 N L3 N L1 N
13
40,8
AFDD
AFDD
40,8
9 mm
9 mm
with auxiliary
switch
L1 N AS L2 N AS L3 N AS L1
13
40,8
Accessories
Terminals for infeed at side Article No. Touch protection Article No.
For conductors 6 … 25 mm2 Short, IP20 5ST3771-2 For free connections, For pins L1, N 5ST3655
End caps Article No. yellow (RAL 1004) For pins L2, L3 5ST3655-0HG
2 and 4-phase compact busbars 5ST3788-0
Terminals
For conductors Version Cable entry Infeed Article No.
6 … 25 mm2 Short – Lateral 5ST3768
Short, IP20 – Lateral 5ST3771-2
5ST36 5ST37 5ST37 (acc. to UL 508) 5ST3.. (acc. to UL 489) 5ST3 compact
■ ■
■ ■ ■
■
■ 3
■
■
■
■
■
■
Touch protection
Version Scope of supply Version Article No.
For free connections, 5× 1 pin – 5ST3655
yellow (RAL 1004) 5ST3655-0HG
3× 1 pin – 5ST3666-1HG
– 5ST3655-3HG
For conductors 10 mm2 20× 5ST3613 + 10× 5ST3614 + 50× 5ST3615 + 50× 5ST3655 – 5ST3656
For conductors 16 mm2 20× 5ST3643 + 10× 5ST3644 + 50× 5ST3645 + 50× 5ST3655 For 5ST337..-3HG 5ST3657
3 End caps
Version Color Article No.
For 1-phase busbars Gray 5ST3748
For 2 and 3-phase busbars Gray 5ST3750
For 4-phase busbars Gray 5ST3718
For 1, 2 and 3-phase busbars Gray 5ST3750-3HG
– Gray 5ST3766
Blue 5ST3767
5ST36 5ST37 5ST37 (acc. to UL 508) 5ST3.. (acc. to UL 489) 5ST3 compact
■ ■
■ ■
■
■
■
■
3
■
■
■
■
■
■
■
■
Series connectors
Conductor cross-section Length of cable Color Number of phases Article No.
10 mm2 125 mm N conductor blue 1 5ST3781-0
Cable black 1 5ST3791-0
3 5ST3793-0
150 mm N conductor blue 1 5ST3781-1
Cable black 1 5ST3791-1
3 5ST3793-1
3
16 mm2 125 mm N conductor blue 1 5ST3782-0
Cable black 1 5ST3792-0
3 5ST3794-0
150 mm N conductor blue 1 5ST3782-1
Cable black 1 5ST3792-1
3 5ST3794-1
200 mm N conductor blue 1 5ST3781-2
Cable black 1 5ST3791-2
3 5ST3793-2
3× cables black and 3 + N 5ST3793-3
1× N conductor blue
5ST36 5ST37 5ST37 (acc. to UL 508) 5ST3.. (acc. to UL 489) 5ST3 compact
■
■
■
■
■
■
3
■
■
■
■
■
■
■
■
■
■
SIKclip busbar
Length Article No.
12 MW 5ST2520
24 MW 5ST2521
36 MW 5ST2522
Connecting cables with plug
Length Conductor cross-section Color Article No.
120 mm 6 mm2 Black 5ST2523
Blue 5ST2524
10 mm2 Black 5ST2525 3
Blue 5ST2526
200 mm 6 mm2 Black 5ST2527
Blue 5ST2528
10 mm2 Black 5ST2530
Blue 5ST2531
Crimp connector
• For connection to cables 4/6 mm2
Article No.
5ST2532
Mounting brackets
• For mounting on the rear of the DIN rail (pair)
Article No.
5ST2533
RCCBs 4/6
RC units 4/8
RCBOs 4/10
Accessories 4/56
Information + ordering
All the important things at a glance Everything you need for your order
For information about residual current protective Refer to the Industry Mall for an overview of your
devices/arc fault detection devices, please visit our products
websites
• SENTRON residual current protective devices
www.siemens.com/rccb
4 www.siemens.com/protection-concept
sie.ag/2m55Y7j
Direct forwarding to the individual products in the
Industry Mall by clicking on the article number in the
catalog or entering this web address incl. article n
umber
Your product in detail www.siemens.com/product?Article No.
Commissioning + operation
The Siemens Industry Online Support (SIOS) provides Manuals are available for downloading in Siemens
detailed technical information Industry Online Support (SIOS) at
www.siemens.com/lowvoltage/product-support www.siemens.com/lowvoltage/manuals
• Operating instructions • Configuration Manual
• Characteristic curves − Residual current protective devices/arc fault detection
• Certificates devices (45303255)
Comprehensive mobile support via the Siemens Industry • Installation Manual
Online Support app available for download from the − SENTRON circuit protection devices with
App Store and Play Store communication and measuring function
You will find further information at (109791805)
www.siemens.com/support-app • System Manual
− SENTRON circuit protection devices with
Provision of 3D data (step and u3d data formats) communication and measuring function
• Siemens Industry Mall (109791806)
www.siemens.com/lowvoltage/mall
• Image database
www.siemens.com/lowvoltage/picturedb Face-to-face or online training
Engineering data for CAD or CAE systems are available in
the CAx Download Manager at Our training courses can be found at
www.siemens.com/cax www.siemens.com/sitrain-lowvoltage
• 5SM6/5SV6 arc fault detection devices (WT-LVBAFDD)
• SENTRON circuit protection devices with measuring and
communication function (WT-LVBCOM)
• Basic principles of electrical engineering (WT-LVBGET)
• Protection concept (WT-LVBPC)
System overview
Basic units and accessories
Basic units
5SV3 RCCBs 5SM3 RCCBs 5SM2 RC units 5SU1 RCBOs 5SV1 RCBOs 5SM6 arc fault detection units and
5SV6 AFDD/MCB and
5SV6 COM AFDD/MCB
4 Electrical accessories
Auxiliary switches (AS) Fault signal contacts Auxiliary switches and Shunt trips (ST) Undervoltage releases Remote control
(FC) fault signal contacts (UR) mechanisms
(AS+FC)/(AS+FC) COM (RC mech.)
Mechanical accessories
Locking devices Handle couplers Touch protection Wall enclosures Molded-plastic Terminal covers
enclosures
Note:
You will find a detailed range of accessories with the basic units and in the Accessories section.
Introduction
Residual current protective devices
Equipment, Design
power, RCCBs
ambient RCBOs
conditions RC units
Number of pole
1P+N
2P
3P
3P+N
4P 4
Rated current In
0.3 … 125 A
I201_20542
I201_20537
I201_20540
I201_20539
I201_20538
I201_20541
I201_20545
6 mA 10 mA
I201_20544
Type ACAC ■ – – – – – –
Selection criteria
I201_20548
Type A A ■ ■ ■ ■ – – –
I201_20546
Type F F ■ ■ ■ ■ ■ ■ –
I201_20547
Type B B ■ ■ ■ ■ ■ ■ ■
Type B+ ■ ■ ■ ■ ■ ■ ■
Version
SIGRES With active condensation protection for use in severe ambient conditions
500 V With their creepage distances and clearances designed for power grids up to 500 V
alternating voltage
50 … 400 Hz Meet the triggering conditions up to 400 Hz due to low decrease in sensitivity with
increasing frequency
conditions B
according to C
VDE 0100-410 D
RCCBs
5SV
Types Instantaneous SIGRES, Short-time delayed [G]
instantaneous
Type AC ■ – –
Type A ■ ■ ■
4 Type F
Type B/B+
–
–
–
–
–
–
Peak withstand current 8/20 μs
Type A kA >1 >3
Type F kA – – >3
Type B/B+ kA – – –
Minimum operational voltage for operation of test equipment
30-mA devices V AC 195
Non-30-mA devices V AC 100
24 V devices V AC 20
Terminal conductor cross-sections
1 conductor Solid/stranded mm2 0.75 … 35
Finely stranded with end sleeve mm2 0.75 … 25
Finely stranded without end sleeve mm2 1 … 35
2 conductors, same cross-section, Solid/stranded mm2 0.75 … 10
same conductor type Finely stranded with end sleeve mm2 0.75 … 4
Finely stranded without end sleeve mm2 1…4
1 conductor + busbar Solid/stranded mm2 10 … 25
(pin thickness 1.5 mm) Finely stranded with non-insulated end sleeve mm2 6 … 25
Finely stranded with insulated end sleeve mm2 6 … 16
Terminal tightening torque Nm 2.5… 3.5
Poles
Number of poles 1P+N | 3P+N
Rated voltage Un V AC 24 … 125 | 230 | 400 | 500
Operating frequency Hz 50 | 50 … 400 | 50/60
Standards
IEC/EN 61008 (VDE 0664-10), IEC/EN 61008-2-1 (VDE 0664-11),
IEC/EN 61543 (VDE 0664-30), IEC/EN 62423 (VDE 0664-40),
ÖVE EN 61008,ÖVE/ÖNORM E 8601
Rated residual current I∆n mA 10, 30, 100, 300, 500, 1000
Rated current In A 16 … 80
Rated breaking capacity Icn kA –
Connection N right | N left
Service life Average number of operating cycles >10000
Test button test cycles Half-yearly 1) | SIGRES annually 2)
Degree of protection Acc. to EN 60529 (VDE 0470-1) IP20, if the distribution board is installed,
with connected conductors
Touch protection Acc. to EN 50274 (VDE 0660-514) Finger and back-of-hand safe
Temperature Storage temperature °C -40 … +75 °C
Ambient temperature °C -25 … +45, marked with -25
Resistance to climate Acc. to IEC 60068-2-30 28 cycles (55 °C; 95% rel. humidity)
CFC and silicone-free ■
Mains connection Top | bottom | SIGRES on top only
Overvoltage category | Degree of pollution III | 2
Further information
See page 4/14
1)
Extension to annual test interval under certain conditions
2)
Extension to four-yearly test interval under certain conditions
– – – – – ■ ■
■ ■ ■ – – ■ ■
■
–
■
–
–
–
–
■
–
■
–
–
–
–
4
195 70 195
100 70 195
20 – –
IEC/EN 61008 (VDE 0664-10), IEC/EN 61008-2-1 IEC/EN 62423 (VDE 0664-40), IEC/EN 61008-1 (VDE 0664-10),
(VDE 0664-11), IEC/EN 61543 (VDE 0664-30), IEC/EN 61543 (VDE 0664-30), IEC/EN 61008-2-1 (VDE 0664-11),
IEC/EN 62423 (VDE 0664-40), DIN VDE 0664-400 (Type B+ only) IEC/EN 61543 (VDE 0664-30),
ÖVE EN 61008,ÖVE/ÖNORM E 8601 IEC/EN 62423 (VDE 0664-40)
10, 30, 100, 300, 500, 1000 30, 300, 500 30, 100, 300, 500
16 … 80 16 … 80 100 … 125
– – –
N right | N left N right N right
>10000 >10000 >10000
Half-yearly 1) | SIGRES annually 2) Annually 2) Half-yearly
IP20, if the distribution board is installed, IP20, if the distribution board is installed, IP20, if the distribution board is installed,
with connected conductors with connected conductors with connected conductors
Finger and back-of-hand safe Finger and back-of-hand safe Finger and back-of-hand safe
-40 … +75 °C -40 … +75 °C -40 … +75 °C
-25 … +45, marked with -25
-25 … +45, marked with -25
-25 … +45, marked with -25
28 cycles (55 °C; 95% rel. humidity) 28 cycles (55 °C; 95% rel. humidity) 28 cycles (55 °C; 95% rel. humidity)
■ ■ ■
Top | bottom | SIGRES on top only Top | bottom | SIGRES on top only Top | bottom
III | 2 III | 2 III | 2
RC units
Rated residual current I∆n mA 10, 30, 100, 300, 500, 1000
Rated current In A 0.3 … 63
Service life Average number of operating cycles >10000
Test button test cycles Half-yearly 1)
Degree of protection Acc. to EN 60529 (VDE 0470-1) IP20, if the distribution board is installed, with connected conductors
Touch protection Acc. to EN 50274 (VDE 0660-514) Finger and back-of-hand safe
Temperature Storage temperature °C -40 … +75 °C
Ambient temperature °C -25 … +45, marked with -25
Resistance to climate Acc. to IEC 60068-2-30 28 cycles (55 °C; 95% rel. humidity)
CFC and silicone-free ■
Mains connection Top | bottom
Overvoltage category | Degree of pollution III | 2
Further information
See page 4/32
1)
Extension to annual test interval under certain conditions
2)
Extension to four-yearly test interval under certain conditions
195 195
100 100
1.0 … 25 6.0 … 50
2.5 … 3.0 2.5 … 3.0
2P | 3P | 4P 4P 2P | 4P
230 | 400 230 | 400
50 | 50/60 50 | 50/60
IEC/EN 61009-1 (VDE 0664-20), IEC/EN 61009-2-1 (VDE 0664-21), IEC/EN 61009-1 (VDE 0664-20), IEC/EN 61009-2-1 (VDE 0664-21),
IEC/EN 61543 (VDE 0664-30), IEC/EN 62423 (VDE 0664-40) IEC/EN 61543 (VDE 0664-30), IEC/EN 62423 (VDE 0664-40)
28 cycles (55 °C; 95% rel. humidity) 28 cycles (55 °C; 95% rel. humidity)
■ ■
Top | bottom Top | bottom
III | 2 III | 2
RCBOs
5SU1 (up to 40 A)
Short-time delayed/
Types Instantaneous Selective [S]
Super resistant
Type AC ■ ■ –
Type A ■ ■ ■
4 Type B – – –
Type B+ – – –
Type F – ■ –
Peak withstand current 8/20 μs
Type A kA >1 >3 >5
Type F kA – >3 –
Minimum voltage for operation of the test equipment
30-mA devices V AC 195
Non-30-mA devices V AC 100
Terminal conductor cross-sections
1 conductor at front + busbar at rear Solid/stranded mm2 0.75 … 35
Finely stranded with end sleeve mm2 0.75 … 25
Finely stranded without end sleeve mm2 1 … 25
2 conductors at rear Solid/stranded mm2 0.75 … 6
Finely stranded with non-insulated end sleeve mm2 0.75 … 4
Finely stranded with insulated end sleeve mm2 0.75 … 4
Finely stranded without end sleeve mm2 1…4
Terminal tightening torque Nm 2.5 … 3.0
Poles
Number of poles 1P+N | 2P
Rated voltage Un V AC 110 | 230
Operating frequency Hz 50 | 50/60
Standards
IEC/EN 61009-1 (VDE 0664-20),
IEC/EN 61009-2-1 (VDE 0664-21),
IEC/EN 61543 (VDE 0664-30),
IEC/EN 62423 (VDE 0664-40)
Resistance to climate Acc. to IEC 60068-2-30 28 cycles (55 °C; 95% rel. humidity)
CFC and silicone-free ■
Mains connection Top | bottom
Energy limitation class 3
Overvoltage category | Degree of pollution III | 2
Further information
See page 4/42
1)
Extension to annual test interval under certain conditions
0.75 … 16 1 … 35 25 … 50 20 … 50
0.75 … 10 1 … 35 25 … 35 25 … 35
0.75 … 16 – – –
0.75 … 4 – – –
0.75 … 2.5 – – –
0.75 … 1.5 – – –
0.75 … 4 – – –
1.2 … 2.0 2.0 3.0 … 3.5 3.0 … 3.5
1P+N 2P | 3P | 4P 2P | 4P 4P
230 230 V | 400 V 230 | 400 400 | 430
50 | 50/60 50 | 50/60 50 | 50/60 50/60
IEC/EN 61009-1 (VDE 0664-20), IEC/EN 61009-1 (VDE 0664-20), IEC/EN 61009-1 (VDE 0664-20), IEC/EN 61009-1 (VDE 0664-20),
IEC/EN 61009-2-1 (VDE 0664-21), IEC/EN 61009-2-1 (VDE 0664-21) IEC/EN 61009-2-1 (VDE 0664-21), IEC/EN 61009-2-1 (VDE 0664-21),
IEC/EN 61543 (VDE 0664-30), IEC/EN 61543 (VDE 0664-30), IEC/EN 61543 (VDE 0664-30),
IEC/EN 62423 (VDE 0664-40) IEC/EN 62423 (VDE 0664-40) IEC/EN 62423 (VDE 0664-40)
28 cycles (55 °C; 95% rel. humidity) 28 cycles (55 °C; 95% rel. humidity) 28 cycles (55 °C; 95% rel. humidity) 28 cycles (55 °C; 95% rel. humidity)
■ – ■ ■
Top | bottom Top | bottom Top | bottom Top | bottom
3 3|1 3 3
III | 2 III | 3 III | 2 III | 2
See page 4/50 See page 4/44 See page 4/42 See page 4/49
Resistance to climate Acc. to IEC 60068-2-30 28 cycles (55 °C; 28 cycles (55 °C; 28 cycles (55 °C;
95% rel. humidity) 95% rel. humidity) 95% rel. humidity)
CFC and silicone-free ■ ■ ■
Mains connection Bottom Top | bottom Bottom
Overvoltage category | Degree of pollution III | 2 III | 2 III | 2
Tripping in the event of overvoltage V >275 >285 >285
Additional functions
Communication and measuring function – ■ –
Further information
See page 4/52 See page 4/53 See page 4/53
and page 4/54
5SV RCCBs
Type A, 1P + N (2 MW)
Instantaneous Instantaneous
(only available in Belgium) 2)
24 … 125 V AC 230 V AC 230 V AC
N connection Right Right Left Right
Thermal overload protection according to OVE E 8101 possible up to rated current of the RCCB (40 A, 63 A).
1)
These products cannot be used in France according to NF C 15-100. Product complies with the specifications of the Belgian market only.
2)
(Simultaneous tripping of the 3 poles and the N conductor.) Available for the export market only.
Mounting concept
optional optional
36 mm
36 mm
18 mm
18 mm
18 mm
9 mm
9 mm
9 mm
9 mm
9 mm
9 mm
or or or or
and and
Adapters
SIGRES, instantaneous Short-time delayed [G] Super resistant [K] Selective [S]
4
– – – – –
– – – – –
5SV3311-6KK12 – – – –
– – – – –
5SV3312-6KK12 – 5SV3312-6KK01 – –
– – – – –
5SV3314-6KK12 – 5SV3314-6KK01 – –
– – – – –
– 5SV3314-6LA01 – – –
5SV3316-6KK12 – 5SV3316-6KK01 – –
– – 5SV3317-6KK01 – –
– – – – –
– – – – –
– – – 5SV3416-8 –
– – – – –
– – 5SV3612-6KK01 5SV3612-8 –
– – 5SV3614-6KK01 5SV3614-8 5SV3614-8KL
– – 5SV3616-6KK01 5SV3616-8 5SV3616-8KL
– – 5SV3617-6KK01 5SV3617-8 –
Accessories
Auxiliary switches (AS) Article No. Shunt trips (ST) Article No.
1 NO + 1 NC Standard 5ST3010 110 … 415 V AC, 110 … 220 V DC 5ST3030
For low power 5ST3013 24 … 48 V AC/DC 5ST3031
For low power (with diode) 5ST3013-0XX01 12 V DC 5ST3031-0XX01
2 NO Standard 5ST3011 Undervoltage releases (UR) Article No.
For low power 5ST3014 With integrated 230 V AC 5ST3040
2 NC Standard 5ST3012 auxiliary switch 110 V DC 5ST3041
For low power 5ST3015 24 V DC 5ST3042
1 CO Standard 5ST3016 Without integrated 230 V AC 5ST3043
Fault signal contacts (FC) Article No. auxiliary switch 110 V DC 5ST3044
1 NO + 1 NC 5ST3020 24 V DC 5ST3045
2 NO 5ST3021 Remote control mechanisms (RC mech.) Article No.
2 NC 5ST3022 Power 12 … 30 V AC, 12 … 48 V DC 5ST3055
Auxiliary switches and fault signal contacts (AS+FC) Article No. 177 … 270 V AC 5ST3056
1 CO (AS) + 1 CO (FC) 5ST3062 Power with ARD 12 … 30 V AC, 12 … 48 V DC 5ST3057
5ST3 COM (AS+FC) 5ST3062-0MC 177 … 270 V AC 5ST3058
Power with extended 12 … 30 V AC, 12 … 48 V DC 5ST3070
function 170 ... 277 V AC, 77 ... 286 V DC 5ST3071
Adapters for remote control mechanisms (RC mech.) Article No.
2 MW 5ST3820-6
5SV RCCBs
Type F, 1P + N (2 MW)
Super resistant [K] Selective [S]
230 V AC 230 V AC
N connection Right Right
IΔn In
Type F
4 30 mA 25 A
40 A
5SV3312-3
5SV3314-3
–
–
63 A 5SV3316-3 –
80 A 5SV3317-3 –
300 mA 25 A 5SV3612-3 –
40 A 5SV3614-3 5SV3614-7
63 A 5SV3616-3 –
80 A 5SV3617-3 5SV3617-7
Mounting concept
optional optional
36 mm
36 mm
18 mm
18 mm
18 mm
9 mm
9 mm
9 mm
9 mm
9 mm
9 mm
or or or or
and and
Adapters
Accessories
Auxiliary switches (AS) Article No. Shunt trips (ST) Article No.
1 NO + 1 NC Standard 5ST3010 110 … 415 V AC, 110 … 220 V DC 5ST3030
For low power 5ST3013 24 … 48 V AC/DC 5ST3031
For low power (with diode) 5ST3013-0XX01 12 V DC 5ST3031-0XX01
2 NO Standard 5ST3011 Undervoltage releases (UR) Article No.
For low power 5ST3014 With integrated 230 V AC 5ST3040
2 NC Standard 5ST3012 auxiliary switch 110 V DC 5ST3041
For low power 5ST3015 24 V DC 5ST3042
1 CO Standard 5ST3016 Without integrated 230 V AC 5ST3043
Fault signal contacts (FC) Article No. auxiliary switch 110 V DC 5ST3044
1 NO + 1 NC 5ST3020 24 V DC 5ST3045
2 NO 5ST3021 Remote control mechanisms (RC mech.) Article No.
2 NC 5ST3022 Power 12 … 30 V AC, 12 … 48 V DC 5ST3055
Auxiliary switches and fault signal contacts (AS+FC) Article No. 177 … 270 V AC 5ST3056
1 CO (AS) + 1 CO (FC) 5ST3062 Power with ARD 12 … 30 V AC, 12 … 48 V DC 5ST3057
5ST3 COM (AS+FC) 5ST3062-0MC 177 … 270 V AC 5ST3058
Power with extended 12 … 30 V AC, 12 … 48 V DC 5ST3070
function 170 ... 277 V AC, 77 ... 286 V DC 5ST3071
Adapters for remote control mechanisms (RC mech.) Article No.
2 MW 5ST3820-6
5SV RCCBs
Type AC, 1P + N (2 MW)
Instantaneous
230 V AC 24 … 125 V AC
N connection Right Left Right
4 10 mA 16 A
25 A
–
–
5SV4111-0
5SV4112-0
5SV4111-0KL
–
–
–
30 mA 16 A – 5SV4311-0 5SV4311-0KL 5SV4311-0KK13
25 A – 5SV4312-0 5SV4312-0KL 5SV4312-0KK13
■ 5SV4312-0GV01 – –
40 A – 5SV4314-0 5SV4314-0KL 5SV4314-0KK13
■ 5SV4314-0GV01 5SV4314-0GV02 –
63 A – 5SV4316-0 5SV4316-0KL 5SV4316-0KK13
80 A – 5SV4317-0 5SV4317-0KL –
100 mA 25 A – 5SV4412-0 – –
40 A – 5SV4414-0 5SV4414-0KL –
63 A – 5SV4416-0 5SV4416-0KL –
80 A – 5SV4417-0 – –
300 mA 25 A – 5SV4612-0 5SV4612-0KL –
40 A – 5SV4614-0 5SV4614-0KL –
63 A – 5SV4616-0 5SV4616-0KL –
80 A – 5SV4617-0 5SV4617-0KL –
Mounting concept
optional optional
36 mm
36 mm
18 mm
18 mm
18 mm
9 mm
9 mm
9 mm
9 mm
9 mm
9 mm
or or or or
and and
Adapters
Accessories
Auxiliary switches (AS) Article No. Shunt trips (ST) Article No.
1 NO + 1 NC Standard 5ST3010 110 … 415 V AC, 110 … 220 V DC 5ST3030
For low power 5ST3013 24 … 48 V AC/DC 5ST3031
For low power (with diode) 5ST3013-0XX01 12 V DC 5ST3031-0XX01
2 NO Standard 5ST3011 Undervoltage releases (UR) Article No.
For low power 5ST3014 With integrated 230 V AC 5ST3040
2 NC Standard 5ST3012 auxiliary switch 110 V DC 5ST3041
For low power 5ST3015 24 V DC 5ST3042
1 CO Standard 5ST3016 Without integrated 230 V AC 5ST3043
Fault signal contacts (FC) Article No. auxiliary switch 110 V DC 5ST3044
1 NO + 1 NC 5ST3020 24 V DC 5ST3045
2 NO 5ST3021 Remote control mechanisms (RC mech.) Article No.
2 NC 5ST3022 Power 12 … 30 V AC, 12 … 48 V DC 5ST3055
Auxiliary switches and fault signal contacts (AS+FC) Article No. 177 … 270 V AC 5ST3056
1 CO (AS) + 1 CO (FC) 5ST3062 Power with ARD 12 … 30 V AC, 12 … 48 V DC 5ST3057
5ST3 COM (AS+FC) 5ST3062-0MC 177 … 270 V AC 5ST3058
Power with extended 12 … 30 V AC, 12 … 48 V DC 5ST3070
function 170 ... 277 V AC, 77 ... 286 V DC 5ST3071
Adapters for remote control mechanisms (RC mech.) Article No.
2 MW 5ST3820-6
5SV RCCBs
Type A, 3P + N (4 MW)
Instantaneous
Thermal overload protection according to OVE E 8101 possible up to rated current of the RCCB (40 A, 63 A).
1)
These products cannot be used in France according to NF C 15-100. Product complies with the specifications of the Belgian market only.
2)
(Simultaneous tripping of the 3 poles and the N conductor.) Available for the export market only.
Mounting concept
optional optional
72 mm
36 mm
18 mm
18 mm
18 mm
9 mm
9 mm
9 mm
9 mm
9 mm
9 mm
or or or or
and and
Adapters
AS Auxiliary switch See page 4/58 ST Shunt trips See page 4/64
FC Fault signal contact See page 4/60 UR Undervoltage release See page 4/65
AS+FC Auxiliary switch and fault signal contact See page 4/61 RC mech. Remote control mechanism See page 4/66
Instantaneous SIGRES, Short-time delayed [G] Super resistant [K] Selective [S] SIGRES, selective
(only available in Belgium) 2) instantaneous [S]
400 V AC 400 V AC 400 V AC 400 V AC 400 V AC 400 V AC
Right Right Right Right Right Left Right
Accessories
Auxiliary switches (AS) Article No. Shunt trips (ST) Article No.
1 NO + 1 NC Standard 5ST3010 110 … 415 V AC, 110 … 220 V DC 5ST3030
For low power 5ST3013 24 … 48 V AC/DC 5ST3031
For low power (with diode) 5ST3013-0XX01 12 V DC 5ST3031-0XX01
2 NO Standard 5ST3011 Undervoltage releases (UR) Article No.
For low power 5ST3014 With integrated 230 V AC 5ST3040
2 NC Standard 5ST3012 auxiliary switch 110 V DC 5ST3041
For low power 5ST3015 24 V DC 5ST3042
1 CO Standard 5ST3016 Without integrated 230 V AC 5ST3043
Fault signal contacts (FC) Article No. auxiliary switch 110 V DC 5ST3044
1 NO + 1 NC 5ST3020 24 V DC 5ST3045
2 NO 5ST3021 Remote control mechanisms (RC mech.) Article No.
2 NC 5ST3022 Power 12 … 30 V AC, 12 … 48 V DC 5ST3055
Auxiliary switches and fault signal contacts (AS+FC) Article No. 177 … 270 V AC 5ST3056
1 CO (AS) + 1 CO (FC) 5ST3062 Power with ARD 12 … 30 V AC, 12 … 48 V DC 5ST3057
5ST3 COM (AS+FC) 5ST3062-0MC 177 … 270 V AC 5ST3058
Power with extended 12 … 30 V AC, 12 … 48 V DC 5ST3070
function 170 ... 277 V AC, 77 ... 286 V DC 5ST3071
Adapters for remote control mechanisms (RC mech.) Article No.
4 MW 5ST3820-7
5SV RCCBs
Type F, 3P + N (4 MW)
Super resistant [K] Selective [S]
400 V AC 400 V AC
N connection Right Right
IΔn In
Type F
4 30 mA 25 A
40 A
5SV3342-3
5SV3344-3
–
–
63 A 5SV3346-3 –
80 A 5SV3347-3 –
300 mA 25 A 5SV3642-3 –
40 A 5SV3644-3 5SV3644-7
63 A 5SV3646-3 –
80 A 5SV3647-3 5SV3647-7
Mounting concept
optional optional
72 mm
36 mm
18 mm
18 mm
18 mm
9 mm
9 mm
9 mm
9 mm
9 mm
9 mm
or or or or
and and
Adapters
Accessories
Auxiliary switches (AS) Article No. Shunt trips (ST) Article No.
1 NO + 1 NC Standard 5ST3010 110 … 415 V AC, 110 … 220 V DC 5ST3030
For low power 5ST3013 24 … 48 V AC/DC 5ST3031
For low power (with diode) 5ST3013-0XX01 12 V DC 5ST3031-0XX01
2 NO Standard 5ST3011 Undervoltage releases (UR) Article No.
For low power 5ST3014 With integrated 230 V AC 5ST3040
2 NC Standard 5ST3012 auxiliary switch 110 V DC 5ST3041
For low power 5ST3015 24 V DC 5ST3042
1 CO Standard 5ST3016 Without integrated 230 V AC 5ST3043
Fault signal contacts (FC) Article No. auxiliary switch 110 V DC 5ST3044
1 NO + 1 NC 5ST3020 24 V DC 5ST3045
2 NO 5ST3021 Remote control mechanisms (RC mech.) Article No.
2 NC 5ST3022 Power 12 … 30 V AC, 12 … 48 V DC 5ST3055
Auxiliary switches and fault signal contacts (AS+FC) Article No. 177 … 270 V AC 5ST3056
1 CO (AS) + 1 CO (FC) 5ST3062 Power with ARD 12 … 30 V AC, 12 … 48 V DC 5ST3057
5ST3 COM (AS+FC) 5ST3062-0MC 177 … 270 V AC 5ST3058
Power with extended 12 … 30 V AC, 12 … 48 V DC 5ST3070
function 170 ... 277 V AC, 77 ... 286 V DC 5ST3071
Adapters for remote control mechanisms (RC mech.) Article No.
4 MW 5ST3820-7
5SV RCCBs
Type AC, 3P + N (4 MW)
Instantaneous
400 V AC
N connection Right Left
Mounting concept
optional optional
72 mm
36 mm
18 mm
18 mm
18 mm
9 mm
9 mm
9 mm
9 mm
9 mm
9 mm
or or or or
and and
Adapters
Accessories
Auxiliary switches (AS) Article No. Shunt trips (ST) Article No.
1 NO + 1 NC Standard 5ST3010 110 … 415 V AC, 110 … 220 V DC 5ST3030
For low power 5ST3013 24 … 48 V AC/DC 5ST3031
For low power (with diode) 5ST3013-0XX01 12 V DC 5ST3031-0XX01
2 NO Standard 5ST3011 Undervoltage releases (UR) Article No.
For low power 5ST3014 With integrated 230 V AC 5ST3040
2 NC Standard 5ST3012 auxiliary switch 110 V DC 5ST3041
For low power 5ST3015 24 V DC 5ST3042
1 CO Standard 5ST3016 Without integrated 230 V AC 5ST3043
Fault signal contacts (FC) Article No. auxiliary switch 110 V DC 5ST3044
1 NO + 1 NC 5ST3020 24 V DC 5ST3045
2 NO 5ST3021 Remote control mechanisms (RC mech.) Article No.
2 NC 5ST3022 Power 12 … 30 V AC, 12 … 48 V DC 5ST3055
Auxiliary switches and fault signal contacts (AS+FC) Article No. 177 … 270 V AC 5ST3056
1 CO (AS) + 1 CO (FC) 5ST3062 Power with ARD 12 … 30 V AC, 12 … 48 V DC 5ST3057
5ST3 COM (AS+FC) 5ST3062-0MC 177 … 270 V AC 5ST3058
Power with extended 12 … 30 V AC, 12 … 48 V DC 5ST3070
function 170 ... 277 V AC, 77 ... 286 V DC 5ST3071
Adapters for remote control mechanisms (RC mech.) Article No.
4 MW 5ST3820-7
4 30 mA 16 A
25 A
–
–
5SV3321-4
5SV3322-4
40 A – 5SV3324-4
■ 5SV3324-4GV01
63 A – 5SV3326-4
300 mA 16 A – 5SV3621-4
25 A – 5SV3622-4
40 A – 5SV3624-4
63 A – 5SV3626-4
Mounting concept
optional optional
72 mm
36 mm
18 mm
18 mm
18 mm
9 mm
9 mm
9 mm
9 mm
9 mm
9 mm
or or or or
and and
Adapters
Accessories
Auxiliary switches (AS) Article No. Shunt trips (ST) Article No.
1 NO + 1 NC Standard 5ST3010 110 … 415 V AC, 110 … 220 V DC 5ST3030
For low power 5ST3013 24 … 48 V AC/DC 5ST3031
For low power (with diode) 5ST3013-0XX01 12 V DC 5ST3031-0XX01
2 NO Standard 5ST3011 Undervoltage releases (UR) Article No.
For low power 5ST3014 With integrated 230 V AC 5ST3040
2 NC Standard 5ST3012 auxiliary switch 110 V DC 5ST3041
For low power 5ST3015 24 V DC 5ST3042
1 CO Standard 5ST3016 Without integrated 230 V AC 5ST3043
Fault signal contacts (FC) Article No. auxiliary switch 110 V DC 5ST3044
1 NO + 1 NC 5ST3020 24 V DC 5ST3045
2 NO 5ST3021 Remote control mechanisms (RC mech.) Article No.
2 NC 5ST3022 Power 12 … 30 V AC, 12 … 48 V DC 5ST3055
Auxiliary switches and fault signal contacts (AS+FC) Article No. 177 … 270 V AC 5ST3056
1 CO (AS) + 1 CO (FC) 5ST3062 Power with ARD 12 … 30 V AC, 12 … 48 V DC 5ST3057
5ST3 COM (AS+FC) 5ST3062-0MC 177 … 270 V AC 5ST3058
Power with extended 12 … 30 V AC, 12 … 48 V DC 5ST3070
function 170 ... 277 V AC, 77 ... 286 V DC 5ST3071
Adapters for remote control mechanisms (RC mech.) Article No.
4 MW 5ST3820-7
4 30 mA 25 A –
■
5SV3342-4
5SV3342-4GV01
–
–
40 A – 5SV3344-4 –
■ 5SV3344-4GV01 –
63 A – 5SV3346-4 –
■ 5SV3346-4GV01 –
80 A – 5SV3347-4 –
300 mA 25 A – 5SV3642-4 –
■ 5SV3642-4GV01 –
40 A – 5SV3644-4 –
■ 5SV3644-4GV01 –
63 A – 5SV3646-4 5SV3646-5
■ 5SV3646-4GV01 –
80 A – 5SV3647-4 5SV3647-5
500 mA 25 A – 5SV3742-4 –
40 A – 5SV3744-4 –
63 A – 5SV3746-4 5SV3746-5
80 A – 5SV3747-4 5SV3747-5
Type B+
30 mA 25 A – 5SV3342-4KK14 –
40 A – 5SV3344-4KK14 –
63 A – 5SV3346-4KK14 –
80 A – 5SV3347-4KK14 –
300 mA 25 A – 5SV3642-4KK14 –
40 A – 5SV3644-4KK14 –
63 A – 5SV3646-4KK14 5SV3646-5KK14
80 A – 5SV3647-4KK14 5SV3647-5KK14
Mounting concept
optional optional
72 mm
36 mm
18 mm
18 mm
18 mm
9 mm
9 mm
9 mm
9 mm
9 mm
9 mm
or or or or
and and
Adapters
Accessories
Auxiliary switches (AS) Article No. Shunt trips (ST) Article No.
1 NO + 1 NC Standard 5ST3010 110 … 415 V AC, 110 … 220 V DC 5ST3030
For low power 5ST3013 24 … 48 V AC/DC 5ST3031
For low power (with diode) 5ST3013-0XX01 12 V DC 5ST3031-0XX01
2 NO Standard 5ST3011 Undervoltage releases (UR) Article No.
For low power 5ST3014 With integrated 230 V AC 5ST3040
2 NC Standard 5ST3012 auxiliary switch 110 V DC 5ST3041
For low power 5ST3015 24 V DC 5ST3042
1 CO Standard 5ST3016 Without integrated 230 V AC 5ST3043
Fault signal contacts (FC) Article No. auxiliary switch 110 V DC 5ST3044
1 NO + 1 NC 5ST3020 24 V DC 5ST3045
2 NO 5ST3021 Remote control mechanisms (RC mech.) Article No.
2 NC 5ST3022 Power 12 … 30 V AC, 12 … 48 V DC 5ST3055
Auxiliary switches and fault signal contacts (AS+FC) Article No. 177 … 270 V AC 5ST3056
1 CO (AS) + 1 CO (FC) 5ST3062 Power with ARD 12 … 30 V AC, 12 … 48 V DC 5ST3057
5ST3 COM (AS+FC) 5ST3062-0MC 177 … 270 V AC 5ST3058
Power with extended 12 … 30 V AC, 12 … 48 V DC 5ST3070
function 170 ... 277 V AC, 77 ... 286 V DC 5ST3071
Adapters for remote control mechanisms (RC mech.) Article No.
4 MW 5ST3820-7
5SM3 RCCBs
Type A and AC, 1P + N (2 MW), high-current
Instantaneous
230 V AC
N connection Right
IΔn In
Type A
4 30 mA 100 A
125 A
5SM3318-6KK
5SM3315-6KK
100 mA 100 A 5SM3418-6KK
125 A 5SM3415-6KK
300 mA 100 A 5SM3618-6KK
125 A 5SM3615-6KK
Type AC
30 mA 100 A 5SM3318-0KK
125 A 5SM3315-0KK
100 mA 100 A 5SM3418-0KK
125 A 5SM3415-0KK
300 mA 100 A 5SM3618-0KK
125 A 5SM3615-0KK
IΔn In
Type A
30 mA 100 A
125 A
5SM3348-6
5SM3345-6
–
–
4
100 mA 100 A 5SM3448-6 –
125 A 5SM3445-6 –
300 mA 100 A 5SM3648-6 5SM3648-8
125 A 5SM3645-6 5SM3645-8
500 mA 100 A 5SM3748-6 –
125 A 5SM3745-6 5SM3745-8
Type AC
30 mA 100 A 5SM3348-0 –
125 A 5SM3345-0 –
100 mA 100 A 5SM3448-0 –
125 A 5SM3445-0 –
300 mA 100 A 5SM3648-0 5SM3648-2
125 A 5SM3645-0 –
500 mA 100 A 5SM3748-0 –
125 A 5SM3745-0 –
Accessories
Auxiliary switches (AS) Article No.
1 NO + 1 NC Standard 5SW3330
5SM2 RC units
Type A, F and AC, 2-pole
For 5SY miniature circuit breakers 1)
230 V AC
Version Instantaneous Super resistant [K] Selective [S]
Mounting width 2 MW 2 MW 2 MW
IΔn In
4 Type A
10 mA 0.3 … 16 A 5SM2121-6 – –
30 mA 0.3 … 40 A 5SM2322-6 5SM2322-6KK01 –
0.3 … 63 A 5SM2325-6 5SM2325-6KK01 –
80 … 100 A – – –
100 mA 0.3 … 63 A 5SM2425-6 – –
300 mA 0.3 … 40 A 5SM2622-6 – 5SM2622-8
0.3 … 63 A 5SM2625-6 – 5SM2625-8
80 … 100 A – – –
500 mA 0.3 … 63 A 5SM2725-6 – –
1000 mA 0.3 … 40 A – – 5SM2822-8
0.3 … 63 A – – 5SM2825-8
80 … 100 A – – –
Type F
30 mA 0.3 … 40 A – 5SM2322-3 –
0.3 … 63 A – 5SM2325-3 –
Type AC
10 mA 0.3 … 40 A 5SM2121-0 – –
30 mA 0.3 … 40 A 5SM2322-0 – –
0.3 … 63 A 5SM2325-0 – –
80 … 100 A – – –
300 mA 0.3 … 40 A 5SM2622-0 – 5SM2622-2
0.3 … 63 A 5SM2625-0 – 5SM2625-2
80 … 100 A – – –
500 mA 0.3 … 63 A 5SM2725-0 – –
1000 mA 0.3 … 63 A 5SM2825-0 – –
1)
Not suitable for use with 5SY5 and type A + type F not suitable for use with 5SY8
Mounting concept
optional
63 mm
54 mm
18 mm
18 mm
18 mm
9 mm
9 mm
9 mm
9 mm
9 mm
9 mm
or or or or
and
FC FC + FC UR UR + FC UR + FC + FC
AS + FC AS + FC AS + FC AS + FC AS + FC AS + FC
optional optional
36 mm
36 mm
36 mm
18 mm
18 mm
18 mm
9 mm
9 mm
9 mm
9 mm
9 mm
9 mm
or or or or
and and
Adapters
MCB Miniature circuit breaker See page 3/1 AS+FC Auxiliary switch and UR Undervoltage release See page 4/65
AS Auxiliary switch See page 4/58 fault signal contact See page 4/61 RC mech. Remote control mechanism See page 4/66
FC Fault signal contact See page 4/60 ST Shunt trips See page 4/64
For 5SL4 miniature circuit breakers For 5SP4 miniature circuit breakers (B and C characteristics)
230 V AC 230 V AC
Instantaneous Selective [S] Instantaneous Selective [S]
2 MW 2 MW 3.5 MW 3.5 MW
– – – –
4
5SM2323-6 – – –
5SM2326-6 – – –
– – 5SM2327-6 –
– – – –
5SM2623-6 5SM2623-8 – –
5SM2626-6 5SM2626-8 – –
– – 5SM2627-6 5SM2627-8
– – – –
– – – –
– – – –
– – – 5SM2827-8
– – – –
– – – –
– – – –
5SM2323-0 – – –
5SM2326-0 – – –
– – – –
5SM2623-0 5SM2623-2 5SM2327-0 –
5SM2626-0 5SM2626-2 5SM2627-0 –
– – – –
– – – –
– – – –
Accessories
Auxiliary switches (AS) Article No. Undervoltage releases (UR) Article No.
1 NO + 1 NC Standard 5ST3010 With integrated 230 V AC 5ST3040
For low power 5ST3013 auxiliary switch 110 V DC 5ST3041
For low power (with diode) 5ST3013-0XX01 24 V DC 5ST3042
2 NO Standard 5ST3011 Without integrated 230 V AC 5ST3043
For low power 5ST3014 auxiliary switch 110 V DC 5ST3044
2 NC Standard 5ST3012 24 V DC 5ST3045
For low power 5ST3015 Remote control mechanisms (RC mech.) Article No.
1 CO Standard 5ST3016 Power 12 … 30 V AC, 12 … 48 V DC 5ST3055
Fault signal contacts (FC) Article No. 177 … 270 V AC 5ST3056
1 NO + 1 NC 5ST3020 Power with ARD 12 … 30 V AC, 12 … 48 V DC 5ST3057
2 NO 5ST3021 177 … 270 V AC 5ST3058
2 NC 5ST3022 Power with extended 12 … 30 V AC, 12 … 48 V DC 5ST3070
Auxiliary switches and fault signal contacts (AS+FC) Article No. function
1 CO (AS) + 1 CO (FC) 5ST3062 Adapters for remote control mechanisms (RC mech.) Article No.
5ST3 COM (AS+FC) 5ST3062-0MC 5SM2 with 5SY (2P) 5ST3820-3 +
5ST3820-1
Shunt trips (ST) Article No.
5SM2 with 5SL (2P) 5ST3820-3 +
110 … 415 V AC, 110 … 220 V DC 5ST3030
5ST3820-6
24 … 48 V AC/DC 5ST3031
12 V DC 5ST3031-0XX01
5SM2 RC units
Type A and AC, 3-pole
For 5SY miniature circuit breakers 1) For 5SL4 miniature circuit breakers
400 V AC 400 V AC
Version Instantaneous Super resistant [K] Selective [S] Instantaneous Selective [S]
Mounting width 3 MW 3 MW 3 MW 3 MW 3 MW
IΔn In
4 Type A
30 mA 0.3 … 40 A 5SM2332-6 5SM2332-6KK01 – 5SM2333-6 –
0.3 … 63 A 5SM2335-6 5SM2335-6KK01 – 5SM2336-6 –
100 mA 0.3 … 63 A 5SM2435-6 – – – –
300 mA 0.3 … 40 A 5SM2632-6 – – 5SM2633-6 –
0.3 … 63 A 5SM2635-6 – 5SM2635-8 5SM2636-6 5SM2636-8
500 mA 0.3 … 63 A 5SM2735-6 – 5SM2735-8 – –
1000 mA 0.3 … 40 A – – 5SM2832-8 – –
0.3 … 63 A – – 5SM2835-8 – –
Type AC
30 mA 0.3 … 40 A 5SM2332-0 – – 5SM2333-0 –
0.3 … 63 A 5SM2335-0 – – 5SM2336-0 –
300 mA 0.3 … 40 A 5SM2632-0 – – 5SM2633-0 –
0.3 … 63 A 5SM2635-0 – – 5SM2636-0 –
500 mA 0.3 … 63 A 5SM2735-0 – – – –
1)
Not suitable for use with 5SY5 and type A not suitable for use with 5SY8
Mounting concept
optional optional
54 mm
54 mm
36 mm
18 mm
18 mm
18 mm
9 mm
9 mm
9 mm
9 mm
9 mm
9 mm
or or or or
and and
Adapters
MCB Miniature circuit breaker See page 3/1 ST Shunt trips See page 4/64
AS Auxiliary switch See page 4/58 UR Undervoltage release See page 4/65
FC Fault signal contact See page 4/60 RC mech. Remote control mechanism See page 4/66
AS+FC Auxiliary switch and fault signal contact See page 4/61
Accessories
Auxiliary switches (AS) Article No. Undervoltage releases (UR) Article No.
1 NO + 1 NC Standard 5ST3010 With integrated 230 V AC 5ST3040
For low power 5ST3013 auxiliary switch 110 V DC 5ST3041
For low power (with diode) 5ST3013-0XX01 24 V DC 5ST3042
2 NO Standard 5ST3011 Without integrated 230 V AC 5ST3043
For low power 5ST3014 auxiliary switch 110 V DC 5ST3044
2 NC Standard 5ST3012 24 V DC 5ST3045
For low power 5ST3015 Remote control mechanisms (RC mech.) Article No.
1 CO Standard 5ST3016 Power 12 … 30 V AC, 12 … 48 V DC 5ST3055
Fault signal contacts (FC) Article No. 177 … 270 V AC 5ST3056
1 NO + 1 NC 5ST3020 Power with ARD 12 … 30 V AC, 12 … 48 V DC 5ST3057
2 NO 5ST3021 177 … 270 V AC 5ST3058
2 NC 5ST3022 Power with extended 12 … 30 V AC, 12 … 48 V DC 5ST3070
Auxiliary switches and fault signal contacts (AS+FC) Article No. function
1 CO (AS) + 1 CO (FC) 5ST3062 Adapters for remote control mechanisms (RC mech.) Article No.
5ST3 COM (AS+FC) 5ST3062-0MC 5SM2 with 5SY (2P) 5ST3820-3 +
5ST3820-1
Shunt trips (ST) Article No.
5SM2 with 5SL (2P) 5ST3820-3 +
110 … 415 V AC, 110 … 220 V DC 5ST3030
5ST3820-6
24 … 48 V AC/DC 5ST3031
12 V DC 5ST3031-0XX01
5SM2 RC units
Type A and AC, 4-pole
For 5SY miniature circuit breakers 1)
400 V AC
Version Instantaneous Super resistant [K] Selective [S] SIGRES, instantaneous new
Mounting width 3 MW 3 MW 3 MW 3 MW
IΔn In
4 Type A
30 mA 0.3 … 40 A 5SM2342-6 5SM2342-6KK01 – –
0.3 … 63 A 5SM2345-6 5SM2345-6KK01 – 5SM2345-6KK12
80 … 100 A – – – –
100 mA 0.3 … 63 A 5SM2445-6 – – –
300 mA 0.3 … 40 A 5SM2642-6 – – –
0.3 … 63 A 5SM2645-6 – 5SM2645-8 5SM2645-6KK12
80 … 100 A – – – –
500 mA 0.3 … 63 A 5SM2745-6 – 5SM2845-8 –
1000 mA 0.3 … 40 A – – 5SM2842-8 –
0.3 … 63 A – – 5SM2845-8 –
80 … 100 A – – – –
Type AC
30 mA 0.3 … 40 A 5SM2342-0 – – –
0.3 … 63 A 5SM2345-0 – – –
80 … 100 A – – – –
300 mA 0.3 … 40 A 5SM2642-0 – – –
0.3 … 63 A 5SM2645-0 – 5SM2645-2 –
80 … 100 A – – – –
500 mA 0.3 … 63 A 5SM2745-0 – – –
1000 mA 0.3 … 63 A – – 5SM2845-2 –
1)
Not suitable for use with 5SY5 and type A not suitable for use with 5SY8
Mounting concept
108 mm
optional
90 mm
18 mm
18 mm
18 mm
9 mm
9 mm
9 mm
9 mm
9 mm
9 mm
or or or or
and
AS + FC AS + FC AS + FC AS + FC AS + FC AS + FC
optional optional
54 mm
72 mm
36 mm
18 mm
18 mm
18 mm
9 mm
9 mm
9 mm
9 mm
9 mm
9 mm
or or or or
and and
Adapters
MCB Miniature circuit breaker See page 3/1 AS+FC Auxiliary switch and UR Undervoltage release See page 4/65
AS Auxiliary switch See page 4/58 fault signal contact See page 4/61 RC mech. Remote control mechanism See page 4/66
FC Fault signal contact See page 4/60 ST Shunt trips See page 4/64
For 5SL4 miniature circuit breakers For 5SP4 miniature circuit breakers (B and C characteristics)
400 V AC 400 V AC
Instantaneous Selective [S] Instantaneous Selective [S]
3 MW 3 MW 5 MW 5 MW
5SM2343-6 – – –
4
5SM2346-6 – – –
– – 5SM2347-6 –
– – – –
5SM2643-6 – – –
5SM2646-6 5SM2646-8 – –
– – 5SM2647-6 5SM2647-8
– – – –
– – – –
– – – –
– – – 5SM2847-8
5SM2343-0 – – –
5SM2346-0 – – –
– – 5SM2347-0 –
5SM2643-0 – – –
5SM2646-0 5SM2646-2 – –
– – 5SM2647-0 –
– – – –
– – – –
Accessories
Auxiliary switches (AS) Article No. Undervoltage releases (UR) Article No.
1 NO + 1 NC Standard 5ST3010 With integrated 230 V AC 5ST3040
For low power 5ST3013 auxiliary switch 110 V DC 5ST3041
For low power (with diode) 5ST3013-0XX01 24 V DC 5ST3042
2 NO Standard 5ST3011 Without integrated 230 V AC 5ST3043
For low power 5ST3014 auxiliary switch 110 V DC 5ST3044
2 NC Standard 5ST3012 24 V DC 5ST3045
For low power 5ST3015 Remote control mechanisms (RC mech.) Article No.
1 CO Standard 5ST3016 Power 12 … 30 V AC, 12 … 48 V DC 5ST3055
Fault signal contacts (FC) Article No. 177 … 270 V AC 5ST3056
1 NO + 1 NC 5ST3020 Power with ARD 12 … 30 V AC, 12 … 48 V DC 5ST3057
2 NO 5ST3021 177 … 270 V AC 5ST3058
2 NC 5ST3022 Power with extended 12 … 30 V AC, 12 … 48 V DC 5ST3070
Auxiliary switches and fault signal contacts (AS+FC) Article No. function
1 CO (AS) + 1 CO (FC) 5ST3062 Adapters for remote control mechanisms (RC mech.) Article No.
5ST3 COM (AS+FC) 5ST3062-0MC 5SM2 with 5SY (4P) 5ST3820-3 +
5ST3820-2
Shunt trips (ST) Article No.
5SM2 with 5SL (4P) 5ST3820-3 +
110 … 415 V AC, 110 … 220 V DC 5ST3030
5ST3820-7
24 … 48 V AC/DC 5ST3031
12 V DC 5ST3031-0XX01
5SU1 RCBOs
Type A, 1P + N
Instantaneous
230 V AC
Mounting width 2 MW 2 MW 2 MW
Short-circuit breaking capacity 4.5 kA 4.5 kA 6 kA
N connection Right Left Right
Mounting concept
27 – 36 mm
optional optional
optional
18 mm
36 mm
18 mm
18 mm
18 mm
9 mm
9 mm
9 mm
9 mm
9 mm
9 mm
Adapters Handle coupler Handle coupler Handle coupler Handle coupler Handle coupler
1)
Handle couplers are required for direct attachment of the components to the 5SU1. No handle coupler is required for attaching the components to the RC mech.
AFDD Arc fault detection unit See page 4/52 ST Shunt trips See page 4/64
AS Auxiliary switch See page 4/58 UR Undervoltage release See page 4/65
FC Fault signal contact See page 4/60 RC mech. Remote control mechanism See page 4/66
AS+FC Auxiliary switch and fault signal contact See page 4/61
Characteristic
B C
Characteristic
B C
4
5SU1154-6KK06 5SU1154-7KK06 – –
5SU1154-6KK10 5SU1154-7KK10 – –
5SU1154-6KK13 5SU1154-7KK13 – –
5SU1154-6KK16 5SU1154-7KK16 – –
5SU1354-6KK06 5SU1354-7KK06 – –
5SU1354-6GV06 5SU1354-7GV06 – –
– 5SU1354-7KK08 – –
5SU1354-6KK10 5SU1354-7KK10 5SU1354-6LB10 5SU1354-7LB10
5SU1354-6GV10 5SU1354-7GV10 – –
5SU1354-6KK13 5SU1354-7KK13 5SU1354-6LB13 5SU1354-7LB13
5SU1354-6KK16 5SU1354-7KK16 5SU1354-6LB16 5SU1354-7LB16
5SU1354-6GV16 5SU1354-7GV16 – –
5SU1354-6KK20 5SU1354-7KK20 5SU1354-6LB20 5SU1354-7LB20
5SU1354-6KK25 5SU1354-7KK25 5SU1354-6LB25 5SU1354-7LB25
5SU1354-6KK32 5SU1354-7KK32 5SU1354-6LB32 5SU1354-7LB32
5SU1354-6KK40 5SU1354-7KK40 5SU1354-6LB40 5SU1354-7LB40
5SU1654-6KK06 5SU1654-7KK06 – –
5SU1654-6KK10 5SU1654-7KK10 – –
5SU1654-6KK13 5SU1654-7KK13 – –
5SU1654-6KK16 5SU1654-7KK16 – –
5SU1654-6KK20 5SU1654-7KK20 – –
5SU1654-6KK25 5SU1654-7KK25 – –
5SU1654-6KK32 5SU1654-7KK32 – –
5SU1654-6KK40 5SU1654-7KK40 – –
Accessories
Auxiliary switches (AS) Article No. Undervoltage releases (UR) Article No.
1 NO + 1 NC Standard 5ST3010 With integrated 230 V AC 5ST3040
For low power 5ST3013 auxiliary switch 110 V DC 5ST3041
For low power (with diode) 5ST3013-0XX01 24 V DC 5ST3042
2 NO Standard 5ST3011 Without integrated 230 V AC 5ST3043
For low power 5ST3014 auxiliary switch 110 V DC 5ST3044
2 NC Standard 5ST3012 24 V DC 5ST3045
For low power 5ST3015 Handle couplers for AS, FC, AS+FC, ST and UR Article No.
1 CO Standard 5ST3016 1 set = 5 units 5ST3805-1
Fault signal contacts (FC) Article No. Remote control mechanisms (RC mech.) Article No.
1 NO + 1 NC 5ST3020 Basic 12 … 30 V AC, 12 … 48 V DC 5ST3053
2 NO 5ST3021 177 … 270 V AC 5ST3054
2 NC 5ST3022 Power 12 … 30 V AC, 12 … 48 V DC 5ST3055
Auxiliary switches and fault signal contacts (AS+FC) Article No. 177 … 270 V AC 5ST3056
1 CO (AS) + 1 CO (FC) 5ST3062 Power with ARD 12 … 30 V AC, 12 … 48 V DC 5ST3057
5ST3 COM (AS+FC) 5ST3062-0MC 177 … 270 V AC 5ST3058
Shunt trips (ST) Article No. Power with extended 12 … 30 V AC, 12 … 48 V DC 5ST3070
110 … 415 V AC, 110 … 220 V DC 5ST3030 function 170 ... 277 V AC, 77 ... 286 V DC 5ST3071
24 … 48 V AC/DC 5ST3031 Adapters for remote control mechanisms (RC mech.) Article No.
12 V DC 5ST3031-0XX01 2 MW 5ST3820-5
Arc fault detection units (AFDD) Article No.
For 5SU1 basic units In up to 16 A 5SM6021-2
In up to 40 A 5SM6024-2
5SU1 RCBOs
Type F, 1P + N
Super resistant [K]
230 V AC
Mounting width 2 MW
Short-circuit breaking capacity 10 kA
N connection Right
4 IΔn In Characteristic
B C
Type F
30 mA 6A 5SU1354-3KK06 5SU1354-4KK06
10 A 5SU1354-3KK10 5SU1354-4KK10
13 A 5SU1354-3KK13 5SU1354-4KK13
16 A 5SU1354-3KK16 5SU1354-4KK16
20 A 5SU1354-3KK20 5SU1354-4KK20
25 A 5SU1354-3KK25 5SU1354-4KK25
32 A 5SU1354-3KK32 5SU1354-4KK32
40 A 5SU1354-3KK40 5SU1354-4KK40
Mounting concept
27 – 36 mm
optional optional
optional
18 mm
36 mm
18 mm
18 mm
18 mm
9 mm
9 mm
9 mm
9 mm
9 mm
9 mm
Adapters Handle coupler Handle coupler Handle coupler Handle coupler Handle coupler
1)
Handle couplers are required for direct attachment of the components to the 5SU1. No handle coupler is required for attaching the components to the RC mech.
AFDD Arc fault detection unit See page 4/52 ST Shunt trips See page 4/64
AS Auxiliary switch See page 4/58 UR Undervoltage release See page 4/65
FC Fault signal contact See page 4/60 RC mech. Remote control mechanism See page 4/66
AS+FC Auxiliary switch and fault signal contact See page 4/61
Accessories
Auxiliary switches (AS) Article No. Undervoltage releases (UR) Article No.
1 NO + 1 NC Standard 5ST3010 With integrated 230 V AC 5ST3040
For low power 5ST3013 auxiliary switch 110 V DC 5ST3041
For low power (with diode) 5ST3013-0XX01 24 V DC 5ST3042
2 NO Standard 5ST3011 Without integrated 230 V AC 5ST3043
For low power 5ST3014 auxiliary switch 110 V DC 5ST3044
2 NC Standard 5ST3012 24 V DC 5ST3045
For low power 5ST3015 Handle couplers for AS, FC, AS+FC, ST and UR Article No.
1 CO Standard 5ST3016 1 set = 5 units 5ST3805-1
Fault signal contacts (FC) Article No. Remote control mechanisms (RC mech.) Article No.
1 NO + 1 NC 5ST3020 Basic 12 … 30 V AC, 12 … 48 V DC 5ST3053
2 NO 5ST3021 177 … 270 V AC 5ST3054
2 NC 5ST3022 Power 12 … 30 V AC, 12 … 48 V DC 5ST3055
Auxiliary switches and fault signal contacts (AS+FC) Article No. 177 … 270 V AC 5ST3056
1 CO (AS) + 1 CO (FC) 5ST3062 Power with ARD 12 … 30 V AC, 12 … 48 V DC 5ST3057
5ST3 COM (AS+FC) 5ST3062-0MC 177 … 270 V AC 5ST3058
Shunt trips (ST) Article No. Power with extended 12 … 30 V AC, 12 … 48 V DC 5ST3070
110 … 415 V AC, 110 … 220 V DC 5ST3030 function AC 170 ... 277 V, DC 77 ... 286 V 5ST3071
24 … 48 V AC/DC 5ST3031 Adapters for remote control mechanisms (RC mech.) Article No.
12 V DC 5ST3031-0XX01 2 MW 5ST3820-5
Arc fault detection units (AFDD) Article No.
For 5SU1 basic units In up to 16 A 5SM6021-2
In up to 40 A 5SM6024-2
5SU1 RCBOs
Type AC, 1P + N
Instantaneous
230 V AC
Mounting width 2 MW 2 MW 2 MW
Short-circuit breaking capacity 4.5 kA 4.5 kA 6 kA
N connection Right Left Right
Mounting concept
27 – 36 mm
optional optional
optional
18 mm
36 mm
18 mm
18 mm
18 mm
9 mm
9 mm
9 mm
9 mm
9 mm
9 mm
Adapters Handle coupler Handle coupler Handle coupler Handle coupler Handle coupler
1)
Handle couplers are required for direct attachment of the components to the 5SU1. No handle coupler is required for attaching the components to the RC mech.
AFDD Arc fault detection unit See page 4/52 ST Shunt trips See page 4/64
AS Auxiliary switch See page 4/58 UR Undervoltage release See page 4/65
FC Fault signal contact See page 4/60 RC mech. Remote control mechanism See page 4/66
AS+FC Auxiliary switch and fault signal contact See page 4/61
Characteristic Characteristic
B C B C
4
5SU1354-0KK06 5SU1354-1KK06 – –
– 5SU1354-1KK08 – –
5SU1354-0KK10 5SU1354-1KK10 5SU1354-0LB10 5SU1354-1LB10
– – – –
5SU1354-0KK13 5SU1354-1KK13 5SU1354-0LB13 5SU1354-1LB13
5SU1354-0KK16 5SU1354-1KK16 5SU1354-0LB16 5SU1354-1LB16
– – – –
5SU1354-0KK20 5SU1354-1KK20 5SU1354-0LB20 5SU1354-1LB20
5SU1354-0KK25 5SU1354-1KK25 5SU1354-0LB25 5SU1354-1LB25
5SU1354-0KK32 5SU1354-1KK32 5SU1354-0LB32 5SU1354-1LB32
5SU1354-0KK40 5SU1354-1KK40 5SU1354-0LB40 5SU1354-1LB40
– 5SU1454-1KK06 – –
– 5SU1454-1KK10 – –
– 5SU1454-1KK13 – –
– 5SU1454-1KK16 – –
– 5SU1454-1KK20 – –
– 5SU1454-1KK25 – –
– 5SU1454-1KK32 – –
– 5SU1454-1KK40 – –
5SU1654-0KK06 5SU1654-1KK06 – –
5SU1654-0KK10 5SU1654-1KK10 – –
5SU1654-0KK13 5SU1654-1KK13 – –
5SU1654-0KK16 5SU1654-1KK16 – –
– – – –
5SU1654-0KK20 5SU1654-1KK20 – –
5SU1654-0KK25 5SU1654-1KK25 – –
5SU1654-0KK32 5SU1654-1KK32 – –
5SU1654-0KK40 5SU1654-1KK40 – –
Accessories
Auxiliary switches (AS) Article No. Undervoltage releases (UR) Article No.
1 NO + 1 NC Standard 5ST3010 With integrated 230 V AC 5ST3040
For low power 5ST3013 auxiliary switch 110 V DC 5ST3041
For low power (with diode) 5ST3013-0XX01 24 V DC 5ST3042
2 NO Standard 5ST3011 Without integrated 230 V AC 5ST3043
For low power 5ST3014 auxiliary switch 110 V DC 5ST3044
2 NC Standard 5ST3012 24 V DC 5ST3045
For low power 5ST3015 Handle couplers for AS, FC, AS+FC, ST and UR Article No.
1 CO Standard 5ST3016 1 set = 5 units 5ST3805-1
Fault signal contacts (FC) Article No. Remote control mechanisms (RC mech.) Article No.
1 NO + 1 NC 5ST3020 Basic 12 … 30 V AC, 12 … 48 V DC 5ST3053
2 NO 5ST3021 177 … 270 V AC 5ST3054
2 NC 5ST3022 Power 12 … 30 V AC, 12 … 48 V DC 5ST3055
Auxiliary switches and fault signal contacts (AS+FC) Article No. 177 … 270 V AC 5ST3056
1 CO (AS) + 1 CO (FC) 5ST3062 Power with ARD 12 … 30 V AC, 12 … 48 V DC 5ST3057
5ST3 COM (AS+FC) 5ST3062-0MC 177 … 270 V AC 5ST3058
Shunt trips (ST) Article No. Power with extended 12 … 30 V AC, 12 … 48 V DC 5ST3070
110 … 415 V AC, 110 … 220 V DC 5ST3030 function 170 ... 277 V AC, 77 ... 286 V DC 5ST3071
24 … 48 V AC/DC 5ST3031 Adapters for remote control mechanisms (RC mech.) Article No.
12 V DC 5ST3031-0XX01 2 MW 5ST3820-5
Arc fault detection units (AFDD) Article No.
For 5SU1 basic units In up to 16 A 5SM6021-2
In up to 40 A 5SM6024-2
5SU1 RCBOs
Type A, 2/3/4-pole with residual current tripped indication
2-pole
Instantaneous
230 V AC
Short-circuit breaking capacity 6 kA 10 kA
Mounting concept
36 – 72 mm
9 mm
9 mm
9 mm
or
I201_20475
AS AS AS 5SU1
basic unit
Accessories
Auxiliary switches (AS) Article No.
1 CO Standard 5ST1010-0FP
5SU1 RCBOs
Type A and AC, 2-pole
Instantaneous
110 V AC 230 V AC
Mounting width 3 MW 3 MW
Short-circuit breaking capacity 10 kA 10 kA
Mounting concept
27 – 36 mm
optional optional
optional
18 mm
54 mm
18 mm
18 mm
18 mm
9 mm
9 mm
9 mm
9 mm
9 mm
9 mm
and if not and if not or or or or
RC mech. AFDD and
Adapters Handle coupler Handle coupler Handle coupler Handle coupler Handle coupler
1)
Handle couplers are required for direct attachment of the components to the 5SU1. No handle coupler is required for attaching the components to the RC mech.
117 mm
optional
18 mm
18 mm
18 mm
9 mm
9 mm
9 mm
9 mm
9 mm
9 mm
or or or or
and
basic unit AS AS AS ST ST AS ST AS AS
I201_20477
AFDD Arc fault detection unit See page 4/52 AS+FC Auxiliary switch and UR Undervoltage release See page 4/65
AS Auxiliary switch See page 4/58 fault signal contact See page 4/61 RC mech. Remote control mechanism See page 4/66
FC Fault signal contact See page 4/60 ST Shunt trips See page 4/64
Selective [S]
230 V AC
6.5 MW 6.5 MW
10 kA 10 kA
Characteristic Characteristic
C B C B C
4
5SU1324-7FA06 – – – –
5SU1324-7FA10 – – – –
5SU1324-7FA13 – – – –
5SU1324-7FA16 – – – –
5SU1324-7FA20 – – – –
5SU1324-7FA25 – – – –
5SU1324-7FA32 – – – –
5SU1324-7FA40 – – – –
– 5SU1324-6KK82 5SU1324-7KK82 – –
– 5SU1624-6KK82 5SU1624-7KK82 5SU1624-6WK82 5SU1624-7WK82
– 5SU1324-0KK82 5SU1324-1KK82 – –
– 5SU1624-0KK82 5SU1624-1KK82 – –
Accessories
Auxiliary switches (AS) Article No. Undervoltage releases (UR) Article No.
1 NO + 1 NC Standard 5ST3010 With integrated 230 V AC 5ST3040
For low power 5ST3013 auxiliary switch 110 V DC 5ST3041
For low power (with diode) 5ST3013-0XX01 24 V DC 5ST3042
2 NO Standard 5ST3011 Without integrated 230 V AC 5ST3043
For low power 5ST3014 auxiliary switch 110 V DC 5ST3044
2 NC Standard 5ST3012 24 V DC 5ST3045
For low power 5ST3015 Handle couplers for AS, FC, AS+FC, ST and UR Article No.
1 CO Standard 5ST3016 1 set = 5 units 5ST3805-1
Fault signal contacts (FC) Article No. Remote control mechanisms (RC mech.) Article No.
1 NO + 1 NC 5ST3020 Basic 12 … 30 V AC, 12 … 48 V DC 5ST3053
2 NO 5ST3021 177 … 270 V AC 5ST3054
2 NC 5ST3022 Power 12 … 30 V AC, 12 … 48 V DC 5ST3055
Auxiliary switches and fault signal contacts (AS+FC) Article No. 177 … 270 V AC 5ST3056
1 CO (AS) + 1 CO (FC) 5ST3062 Power with ARD 12 … 30 V AC, 12 … 48 V DC 5ST3057
5ST3 COM (AS+FC) 5ST3062-0MC 177 … 270 V AC 5ST3058
Shunt trips (ST) Article No. Power with extended 12 … 30 V AC, 12 … 48 V DC 5ST3070
110 … 415 V AC, 110 … 220 V DC 5ST3030 function 170 ... 277 V AC, 77 ... 286 V DC 5ST3071
24 … 48 V AC/DC 5ST3031 Adapters for remote control mechanisms (RC mech.) Article No.
12 V DC 5ST3031-0XX01 2 MW 5ST3820-5
Arc fault detection units (AFDD) Article No.
For 5SU1 basic units In up to 16 A 5SM6021-2
(3 MW) In up to 40 A 5SM6024-2
5SU1 RCBOs
Type A and AC, 4-pole
Instantaneous Selective [S]
400 V AC 400 V AC
Mounting width 11 MW 11 MW
Short-circuit breaking capacity 10 kA 10 kA
Mounting concept
198 mm
optional
18 mm
18 mm
18 mm
9 mm
9 mm
9 mm
9 mm
9 mm
9 mm
or or or or
and
FC FC + FC UR UR + FC UR + FC + FC
AS + FC AS + FC AS + FC AS + FC AS + FC AS + FC
AS Auxiliary switch See page 4/58 ST 5 Shunt trips See page 4/64
FC Fault signal contact See page 4/60 UR5 Undervoltage release See page 4/65
AS+FC Auxiliary switch and fault signal contact See page 4/61
Accessories
Auxiliary switches (AS) Article No. Auxiliary switches and fault signal contacts (AS+FC) Article No.
1 NO + 1 NC Standard 5ST3010 1 CO (AS) + 1 CO (FC) 5ST3062
For low power 5ST3013 5ST3 COM (AS+FC) 5ST3062-0MC
For low power (with diode) 5ST3013-0XX01 Shunt trips (ST) Article No.
2 NO Standard 5ST3011 110 … 415 V AC, 110 … 220 V DC 5ST3030
For low power 5ST3014 24 … 48 V AC/DC 5ST3031
2 NC Standard 5ST3012 12 V DC 5ST3031-0XX01
For low power 5ST3015 Undervoltage releases (UR) Article No.
1 CO Standard 5ST3016 With integrated 230 V AC 5ST3040
Fault signal contacts (FC) Article No. auxiliary switch 110 V DC 5ST3041
1 NO + 1 NC 5ST3020 24 V DC 5ST3042
2 NO 5ST3021 Without integrated 230 V AC 5ST3043
2 NC 5ST3022 auxiliary switch 110 V DC 5ST3044
24 V DC 5ST3045
5SV1 RCBOs
Type A, 1P + N
Instantaneous Short-time delayed [G],
Super resistant [K]
230 V AC 230 V AC
Mounting width 1 MW 1 MW 1 MW
Short-circuit breaking capacity 4.5 kA 6 kA 6 kA
N connection Right Right Right
Mounting concept
27 – 36 mm
18 mm
9 mm
9 mm
9 mm
Adapters
AFDD Arc fault detection units See page 4/52 AS+FC Auxiliary switch and fault signal contact See page 4/61
AS Auxiliary switch See page 4/58 RC mech. Remote control mechanism See page 4/66
FC Fault signal contact See page 4/60
Accessories
Auxiliary switches (AS) Article No. Remote control mechanisms (RC mech.) Article No.
1 NO + 1 NC Standard 5ST3010 Basic 12 … 30 V AC, 12 … 48 V DC 5ST3053
For low power 5ST3013 177 … 270 V AC 5ST3054
For low power (with diode) 5ST3013-0XX01 Power 12 … 30 V AC, 12 … 48 V DC 5ST3055
2 NO Standard 5ST3011 177 … 270 V AC 5ST3056
For low power 5ST3014 Power with ARD 12 … 30 V AC, 12 … 48 V DC 5ST3057
2 NC Standard 5ST3012 177 … 270 V AC 5ST3058
For low power 5ST3015 Power with extended 12 … 30 V AC, 12 … 48 V DC 5ST3070
1 CO Standard 5ST3016 function 170 ... 277 V AC, 77 ... 286 V DC 5ST3071
Fault signal contacts (FC) Article No. Adapters for remote control mechanisms (RC mech.) Article No.
1 NO + 1 NC 5ST3020 1 MW 5ST3820-6
2 NO 5ST3021 Arc fault detection units (AFDD) Article No.
2 NC 5ST3022 For 5SV1 basic units In up to 16 A 5SM6011-2
Auxiliary switches and fault signal contacts (AS+FC) Article No.
1 CO (AS) + 1 CO (FC) 5ST3062
5ST3 COM (AS+FC) 5ST3062-0MC
9 mm
9 mm
9 mm
and or
and For low power (with diode) 5ST3013-0XX01
2 NO Standard 5ST3011
For low power 5ST3014
5SM6 5SY, 5SL, AS AS AS 2 NC Standard 5ST3012
5SV1, 5SU1 FC FC + FC
For low power 5ST3015
I201_20480
AS + FC AS + FC AS + FC
1 CO Standard 5ST3016
Fault signal contacts (FC) Article No.
AS Auxiliary switch See page 4/58 1 NO + 1 NC 5ST3020
FC Fault signal contact See page 4/60 2 NO 5ST3021
AS+FC Auxiliary switch and fault signal contact See page 4/61 2 NC 5ST3022
The mounting concept shown is only one example of how Auxiliary switches and fault signal contacts (AS+FC) Article No.
devices and accessories can be combined. 1 CO (AS) + 1 CO (FC) 5ST3062
5ST3 COM (AS+FC) 5ST3062-0MC
5SV6 AFDD/MCB
optional
9 mm
9 mm
9 mm
or
and
For low power (with diode) 5ST3013-0XX01
2 NO Standard 5ST3011
For low power 5ST3014
5SV6 AS AS AS 2 NC Standard 5ST3012
FC FC + FC
For low power 5ST3015
I201_20481
AS + FC AS + FC AS + FC
1 CO Standard 5ST3016
Fault signal contacts (FC) Article No.
AS Auxiliary switch See page 4/58 1 NO + 1 NC 5ST3020
FC Fault signal contact See page 4/60 2 NO 5ST3021
AS+FC Auxiliary switch and fault signal contact See page 4/61 2 NC 5ST3022
Auxiliary switches and fault signal contacts (AS+FC) Article No.
1 CO (AS) + 1 CO (FC) 5ST3062
5ST3 COM (AS+FC) 5ST3062-0MC
Mounting width 1 MW
4 6A
10 A
5SV6016-6MC06
5SV6016-6MC10
5SV6016-7MC06
5SV6016-7MC10
13 A 5SV6016-6MC13 5SV6016-7MC13
16 A 5SV6016-6MC16 5SV6016-7MC16
20 A 5SV6016-6MC20 5SV6016-7MC20
25 A 5SV6016-6MC25 5SV6016-7MC25
32 A 5SV6016-6MC32 5SV6016-7MC32
Note:
Please note the country-specific radio licenses of the products in SIOS
www.siemens.com/lowvoltage/certificates (109801197)
optional
9 mm
9 mm
9 mm
or
and For low power (with diode) 5ST3013-0XX01
2 NO Standard 5ST3011
For low power 5ST3014
5SV6 AS AS AS 2 NC Standard 5ST3012
FC FC + FC
For low power 5ST3015
I201_20481
AS + FC AS + FC AS + FC
1 CO Standard 5ST3016
Fault signal contacts (FC) Article No.
AS Auxiliary switch See page 4/58 1 NO + 1 NC 5ST3020
FC Fault signal contact See page 4/60 2 NO 5ST3021
AS+FC Auxiliary switch and fault signal contact See page 4/61 2 NC 5ST3022
Auxiliary switches and fault signal contacts (AS+FC) Article No.
1 CO (AS) + 1 CO (FC) 5ST3062
5ST3 COM (AS+FC) 5ST3062-0MC
7KN1110-0MC00
7KN Powercenter 1000
See page 10/20
You will find further information at
www.siemens.com/lowvoltage/manuals
Installation Manual – SENTRON
... ... ... ... circuit protection devices with
communication and measuring
function (109791805)
5SL6 COM 5ST3 COM 5SV6 COM 3NA COM
MCB AS+FC AFDD Fuse System Manual – SENTRON circuit
max. 24 protection devices with communica-
Wireless Protocol
tion and measuring function
(109791806)
– – – – – – □ – – – □ – – – – –
– ■ – – – – – – – □ – – – – – –
– – – – – – □ – – – □ – – – – –
– ■ – – – – – – – □ – – – – – –
4
– ■ □ ■ ■ ■ ■ – ■ ■ ■ ■ ...-0HG ■ ■ ■
– ■ □ ■ ■ ■ ■ – ■ ■ ■ ■ – ■ ■ ■
– ■ □ ■ ■ ■ ■ – ■ ■ ■ ■ – ■ ■ ■
– ■ □ ■ ■ ■ ■ – ■ ■ ■ ■ ...-0HG ■ ■ ■
– ■ □ ■ ■ ■ ■ – ■ ■ ■ ■ – ■ ■ ■
– ■ □ ■ ■ ■ ■ – ■ ■ ■ ■ ...-0HG ■ ■ ■
– ■ □ ■ ■ ■ ■ – ■ ■ ■ ■ – ■ ■ ■
– ■ □ ■ ■ ■ ■ – ■ ■ ■ ■ – ■ ■ ■
■ – – – – – – – – – – – – – – –
– ■ □ ■ ■ ■ ■ – ■ ■ ■ ■ ...-0HG ■ – –
– ■ □ ■ ■ ■ ■ – ■ ■ ■ ■ ...-0HG ■ – –
– ■ □ ■ ■ ■ ■ – ■ ■ ■ ■ ...-0HG ■ – –
– ■ □ ■ ■ ■ ■ – ■ ■ ■ ■ – ■ – –
– ■ □ ■ ■ ■ ■ – ■ ■ ■ ■ – ■ – –
– – □ – – – ■ – – – ■ ■ ...-0HG – – –
– – □ – – – ■ – – – ■ ■ ...-0HG – – –
– – □ – – – ■ – – – ■ ■ – – – –
– – □ – – – ■ – – – ■ ■ – – – –
– – □ – – – ■ – – – ■ ■ – – – –
– – □ – – – ■ – – – ■ ■ – – – –
– – □ – – – ■ – – – ■ ■ – – – –
– – □ – – – ■ – – – ■ ■ – – – –
– – □ – – – ■ – – – ■ ■ – – – –
– ■ – – – ■ ■ – – ■ ■ – – ■ – ■
– ■ – – – ■ ■ – – ■ ■ – – ■ – ■
– ■ – – – ■ ■ – – ■ ■ ■ – ■ – ■
– ■ – – – ■ ■ – – ■ ■ ■ – ■ – ■
– ■ – – – ■ ■ – – ■ ■ ■ – ■ – ■
– ■ – – – ■ ■ – – ■ ■ ■ – ■ – ■
– ■ – – – ■ ■ – – ■ ■ ■ – ■ – –
– ■ – – – ■ ■ – – ■ ■ – – ■ – –
■ ■ □ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ □ ■
■ ■ □ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ □ ■
– ■ ■ ■ □ □ □ – ■ ■ – – – ■ – –
– ■ ■ ■ □ □ □ – ■ ■ – – – – – –
From page 4/52 From page 3/12 From From
page page 5/6
3/42
Electrical accessories
Auxiliary switches (AS)
• Signals the contact position of the mounted device
• Version for the switching of small currents and voltages
according to EN 61131-2 for control of programmable control
systems (PLCs)
• Test button enables the testing of control circuits without the
need to switch the mounted device
For combining with basic units Contacts Version Mounting width Article No.
Miniature Circuit RCCBs RCBOs Arc fault ON/OFF (1 MW = 18 mm)
circuit breakers for detection switches
breakers equipment devices
Auxiliary switches (AS)
4 – – 5SM3 (3P+N, – – – 1 NO + 1 NC Standard 0.5 MW 5SW3330
100/125 A)
5SL, 5SY, 5SY17 5SV 5SU1 1), 5SV6 5TL1, 5TE8 1 NO + 1 NC Standard 0.5 MW 5ST3010
5SP4, 5SP5 5SV1 For low power 0.5 MW 5ST3013
For low power 0.5 MW 5ST3013-0XX01
(with diode)
2 NO Standard 0.5 MW 5ST3011
For low power 0.5 MW 5ST3014
2 NC Standard 0.5 MW 5ST3012
For low power 0.5 MW 5ST3015
1 CO Standard 0.5 MW 5ST3016
– – – 5SU1... – – 1 CO Standard 0.5 MW 5ST1010-0FP
FP/FR
Auxiliary switches (AS) with TEST button
5SL, 5SY, 5SY17 5SV 5SU1 1), 5SV6 5TL1, 5TE8 1 NO + 1 NC Standard 0.5 MW 5ST3010-2
5SP4, 5SP5 5SV1 For low power 0.5 MW 5ST3013-2
2 NO Standard 0.5 MW 5ST3011-2
For low power 0.5 MW 5ST3014-2
2 NC Standard 0.5 MW 5ST3012-2
For low power 0.5 MW 5ST3015-2
1)
5ST3805-1 handle coupler required
5ST3010, 5ST3013,
5ST3011, 5ST3010-2, 5ST3014, 5ST3013-2,
5ST3012, 5ST3011-2, 5ST3015, 5ST3014-2,
Further technical specifications 5ST3016 5ST3012-2 5ST3013-0XX011) 5ST3015-2 5SW3330 5ST1010-0FP
Standards
Standards IEC/EN IEC/EN 62019, IEC/EN 60947-5-1 IEC/EN 62019
UL, CSA UL 1077, – UL 1077, –
CSA C22.2 CSA C22.2 No. 235
No. 235
Contacts
Minimum contact load 50 mA, 1 mA, 5 mA, 50 mA, 5 mA,
24 V 5 V DC 5 V DC 24 V 24 V DC
Maximum contact load – 100 mA, 50 mA, –
30 V DC 30 V DC 4
Contact load acc. to IEC/EN 62019 and 230 V AC, AC-12 – 5/– 6 A/–
IEC/EN 60947-5-1 230 V AC, AC-13 6 A/6 A –
400 V AC, AC-13 2 A/2 A –
230 V AC, AC-14 6 A/6 A –
400 V AC, AC-14 2 A/2 A –
24 V DC, DC-13 6 A/3 A –
30 V DC, DC-14 – 0.1 A –
60 V DC, DC-13 3 A/1.5 A –
110 V DC, DC-13 1 A/0.75 A –
220 V DC, DC-12 – 0.5/– 1 A/–
220 V DC, DC-13 1 A/0.5 A –
Contact load acc. to UL 120 V AC –
125 V AC 3A –
240 V AC 4A –
277 V AC –
480 V AC –
60 V DC –
125 V DC 1.1 A –
250 V DC 0.55 A –
Service life, on average, with rated load Actuations 20000 – 8000
Safety
Short-circuit protection Miniature circuit breakers 5SY... 6 A or gG 6 A fuse B6 or C6 or gL/gG 6 A fuse
Connections
Conductor cross-sections 0.5 ... 2.5 mm2 (AWG 22 … 14) 0.75 ... 2.5 mm2
Terminals Max. tightening 0.5 Nm (4.5 lb-in) – 0.6 Nm
torque
Ambient conditions
Permissible ambient temperature –40 … +70 °C –25 … +60 °C
Permissible storage temperature –40 ... +75 °C –40 … +70 °C
Resistance to climate Acc. to IEC 28 cycles
60068-2-30
Mounting position Any
Shock at 11 ms half-sine Acc. to IEC 150 m/s2 –
60068-2-27
Resistance to vibrations at 10 … 150 Hz Acc. to IEC 50 m/s2 –
60068-2-6
1)
No approvals
Electrical accessories
Fault signal contacts (FC)
• Signals automatic tripping of the circuit protection device in the event of a fault,
such as an overload or a short circuit
• If the fault signal contact is activated, the contact position does not change if
the mounted circuit protection device is tripped manually
• Version with TEST and RESET buttons enables the testing of control circuits
without operation of the circuit protection device
• Red RESET button in the operating handle indicates automatic tripping of the
mounted circuit protection device
For combining with basic units Contacts Mounting width Article No.
Miniature circuit Circuit breakers for RCCBs RCBOs Arc fault (1 MW = 18 mm)
4 breakers
Fault signal contacts (FC)
equipment detection devices
5SL, 5SY, 5SP4, 5SY17 5SV 5SU1 1), 5SV1 5SV6 1 NO + 1 NC 0.5 MW 5ST3020
5SP5 2 NO 0.5 MW 5ST3021
2 NC 0.5 MW 5ST3022
Fault signal contacts (FC) with TEST and RESET buttons
5SL, 5SY, 5SP4, 5SY17 5SV 5SU1 1), 5SV1 5SV6 1 NO + 1 NC 0.5 MW 5ST3020-2
5SP5 2 NO 0.5 MW 5ST3021-2
2 NC 0.5 MW 5ST3022-2
1)
5ST3805-1 handle coupler required
5ST3020, 5ST3020-2,
5ST3021, 5ST3021-2,
Further technical specifications 5ST3022 5ST3022-2
Standards
Standards IEC/EN IEC/EN 62019, IEC/EN 60947-5-1
UL, CSA UL 1077, CSA C22.2 No. 235 –
Contacts
Minimum contact load 50 mA, 24 V
Contact load acc. to IEC/EN 62019/IEC/EN 60947-5-1 230 V AC, AC-13 6 A/6 A
400 V AC, AC-13 6 A/6 A
230 V AC, AC-14 2 A/2A
400 V AC, AC-14 2 A/2A
24 V DC, DC-13 6 A/3 A
60 V DC, DC-13 3 A/1.5 A
110 V DC, DC-13 1 A/0.75 A
220 V DC, DC-13 1 A/0.5 A
Contact load acc. to UL 120 V AC –
125 V AC 3A –
240 V AC 4A –
277 V AC –
480 V AC 1.5 A –
60 V DC –
125 V DC 1.1 A –
250 V DC 0.55 A –
Service life, on average, with rated load Actuations 20000
Safety
Short-circuit protection Miniature circuit breaker or gG 6 A fuse
Connections
Conductor cross-sections 0.5 ... 2.5 mm2 (AWG 22 … 14)
Terminals Max. tightening torque 0.5 Nm (4.5 lb-in)
Ambient conditions
Permissible ambient temperature –25 … +55 °C
Permissible storage temperature –40 ... +75 °C
Resistance to climate Acc. to IEC 60068-2-30 28 cycles
Mounting position Any
Shock at 11 ms half-sine Acc. to IEC 60068-2-27 150 m/s2
Resistance to vibration at 10 … 150 Hz Acc. to IEC 60068-2-6 50 m/s2
For combining with basic units Contacts Mounting width Article No.
Miniature circuit Circuit breakers for RCCBs RCBOs Arc fault detection (1 MW = 18 mm)
breakers equipment devices
Auxiliary switches and fault signal contacts (AS+FC)
5SL, 5SY, 5SP4, 5SY17 5SV 5SU1 1), 5SV1 5SV6 1 CO (AS) + 1 CO (FC) 0.5 MW 5ST3062
5SP5 4
1)
5ST3805-1 handle coupler required
Electrical accessories
5ST3 COM auxiliary switches and fault signal contacts (AS+FC)
with communication and measuring function
• Reports the switching state of the mounted standard circuit protection device (ON, tripped, manual
OFF, tripped with locked handle)
• Measures the temperature of the device and counts operating cycles, trips and operating hours
• Communication via radio to 7KN Powercenter 1000 data transceiver
• Plug-in terminals for 24 V DC power supply incl. daisy chain function
• Low space requirements of 0.5 MW (9 mm)
1)
5ST3805-1 handle coupler required
Note:
Please note the country-specific radio licenses of the products in SIOS
www.siemens.com/lowvoltage/certificates (109801197)
7KN1110-0MC00
7KN Powercenter 1000
See page 10/20
You will find further information at
www.siemens.com/lowvoltage/manuals
Installation Manual – SENTRON
... ... ... ... circuit protection devices with
communication and measuring
function (109791805)
5SL6 COM 5ST3 COM 5SV6 COM 3NA COM
MCB AS+FC AFDD Fuse System Manual – SENTRON circuit
max. 24 protection devices with communica-
Wireless Protocol
tion and measuring function
(109791806)
Electrical accessories
Shunt trips (ST)
• For remote-controlled tripping of the mounted device
For combining with basic units Rated operational Mounting width Article No.
Miniature circuit breakers RCCBs RCBOs voltage Ue (1 MW = 18 mm)
Shunt trips (ST)
5SL4, 5SY, 5SP4, 5SP5 5SV 5SU1 1) 110 … 415 V AC, 110 … 220 V DC 1 MW 5ST3030
24 ... 48 V AC/DC 1 MW 5ST3031
12 V DC 1 MW 5ST3031-0XX01
1)
5ST3805-1 handle coupler required
For combining with basic units Rated operational Mounting width Article No.
Miniature circuit breakers RCCBs RCBOs voltage Ue (1 MW = 18 mm)
4
With integrated auxiliary switch
5SL4, 5SY, 5SP4, 5SP5 5SV 5SU1 1)
230 V AC 1 MW 5ST3040
110 V DC 1 MW 5ST3041
24 V DC 1 MW 5ST3042
Without integrated auxiliary switch
5SL4, 5SY, 5SP4, 5SP5 5SV 5SU1 1) 230 V AC 1 MW 5ST3043
110 V DC 1 MW 5ST3044
24 V DC 1 MW 5ST3045
1)
5ST3805-1 handle coupler required
Electrical accessories
5ST3 remote control mechanisms (RC mech.)
• For locations that are spread out over a wide area or not permanently attended
• Permits direct and immediate access to the installation even if it is remote or
in a location that is hard to access
• Permits fast reconnection after a fault
• Version with ARD with automatic restart
• Versions with ARD and Power with integrated auxiliary switches and fault signal contacts
Type of remote control Display Ambient Vibration and shock Rated operational Mounting width Article No.
mechanism temperature requirements voltage Ue (1 MW = 18 mm)
Basic – –25 °C … +45 °C – 12 … 30 V AC, 12 … 48 V DC 1.5 MW 5ST3053
177 … 270 V AC 2 MW 5ST3054
Power LED –25 °C … +45 °C – 12 … 30 V AC, 12 … 48 V DC 2 MW 5ST3055
4 177 … 270 V AC 2 MW 5ST3056
Power with ARD LED –25 °C … +45 °C – 12 … 30 V AC, 12 … 48 V DC 2 MW 5ST3057
177 … 270 V AC 2 MW 5ST3058
Power with extended LED –40 °C … +70 °C Acc. to EN 61373/ 12 … 30 V AC, 12 … 48 V DC 2 MW 5ST3070
function EN 50155 "1B" 170 ... 277 V AC, 77 ... 286 V DC 2 MW 5ST3071
Further technical specifications 5ST3053 5ST3054 5ST3055 5ST3056 5ST3057 5ST3058 5ST3070 5ST3071
Standards
Standards EN 50557 (VDE 0640-20)
Supply
Rated frequency fn 50 ... 60 Hz
Rated power dissipation on standby ≤1 VA
Contacts
Service life, on average, Actuations 10000
with rated load
Number of remote switching operations per 2
minute
Number of automatic reclose attempts – 3 –
Cable length in the control circuit ≤1500 m ≤1500 m (DC)/
≤200 m (AC)
Sliding selector with locking device – ■
Integrated auxiliary switches – 1CO; 2 A; 250 V
Integrated fault signal contacts – 1CO; 2 A; 250 V
Connections
Conductor cross-sections 0.5 ... 1.5 mm2 (AWG 14 … 30)
Terminal tightening torque 0.2 … 0.25 Nm (2.0 lb-in)
Ambient conditions
Permissible storage temperature –40 … +55 °C –40 … +70 °C
Degree of protection IP20
Degree of pollution for overvoltage category 3/II
Mechanical accessories
Locking device
• For 5SV RCCBs, 5SV1 RCBOs, 5SV6 AFDD/MCB
Comprising Article No.
5ST3806 handle locking device and 5ST3802 padlock 5ST3807
Padlock
• For 5ST3801-1 and 5ST3806 handle locking devices and 5ST3054 … 58, 5ST3070 remote control mechanisms
Article No.
5ST3802
Device labels
• For adhesive attachment
• For modular installation devices, e.g. 5SY, 5SL, 5TL1
Types Article No.
15 mm x 6 mm, white (WIN 098) 8WH8210-0AA35
15 mm x 6 mm, yellow (WIN 099) 8WH8210-0AA36
Standard busbars
General information
Infeed
At the start or end of the busbar Along the busbar or midpoint infeed
3 2 1 1 2 3
I201_13755
S I201_13754a
S1 S2
4
S
L1 L2/N L1 L2/N
19
6,6 7,3
∅ 10 mm2 ∅ 16 mm2
3-phase, for MCBs with RCCB Article No. Article No.
1 1 12 1 1 21 11 11 11 11 11 1 1 For 8 MCBs 1P 12 MW 210 mm 5ST3624 5ST3654
with 1 RCCB 3P+N,
72 mm
72 mm
N right
4
15,2
L1 L2 L3L1 NL2 L1L3 L2N L3L1 L1L2 L2L3 L3L1 L1L2 L2L3 L1 L2
19
9,2 10,3
∅ 10 mm2 ∅ 16 mm2
1 1 2 1 1 1 1 1 1 1 1 1 For 10 MCBs 1P 14 MW 249 mm 5ST3624-4 –
with 1 RCCB 3P+N
72 mm
15,2
L1 L2 L3 N L1 L2 L3 L1 L2 L3 L1 L2 L3 L1
7 MCBs 1P
8,6
1 RCCB 3P+N,
1 MCB 3P and
pYWXYWX[^
15,2
L1 L2 L3 N L1 L2 L3 L1 L2 L3
3 MCBs 1P
8,6
1 1 11 11 11 11 11 11 11 11 1 1 For 8 MCBs 1P with 11 MW 192 mm 5ST3667 5ST3668
1 RCCB 3P+N, N left
72 mm
72 mm
N L1 N
L2 L1
L3 L2
L1 L3
L2 L1
L3 L2
L1 L3
L2 L1
L3 L2
L1 L3
L2 L1 L2
15,2
19
9,2 10,3
∅ 10 mm2 ∅ 16 mm2
4-phase/3-phase + N Article No. Article No.
1 1 11 11 11 1 1 For 6× 2MW devices 12 MW 215 mm 5ST3623 5ST3653
(1P+N)
15,2
L1 N L2L1 N N L3L2 N N L3 N
19
11,8 13,3
∅ 10 mm2 ∅ 16 mm2
4-phase/3-phase + N, for MCBs with RCCB Article No. Article No.
1 1 1 1 1 1 1 1 1 1 1 1 1 For 1 RCCB 3P+N, 14 MW 248 mm 5ST3724-4 –
1 MCB 3P+N and
6 MCBs 1P
pYWXYWX[_
15,2
L1 L2 L3 N L1 L2 L3 N L1 L2 L3 L1 L2 L3
10,7
1 1 1 1 1 1 1 1 1 1 1 1 1 For 1 RCCB 3P+N, 14 MW 248 mm 5ST3725-4 –
1 MCB 3P+N and
3 MCBs 1P+N
pYWXYWX[\
15,2
L1 L2 L3 N L1 L2 L3 N L1 N L2 N L3 N
10,7
15,2
L1 L2 L3 N L1 L2 L3 L1 N L2 N L3 N
10,7
1 1 1 1 1 1 1 1 1 1 1 1 1 For 1 RCCB 3P+N 14 MW 248 mm 5ST3625-4 –
and 5 MCBs 1P+N
pYWXYWX[]
15,2
L1 L2 L3 N L1 N L2 N L3 N L1 N L2 N
10,7
Standard busbars
Can be cut
Pin spacing in MW Application No. of MW Length End caps Conductor cross-section
(1 MW = 18 mm) included 10 mm2 16 mm2
2-phase/1-phase + N Article No. Article No.
1 For 2 MW units 12 MW 214 mm ■ 5ST3734 5ST3704
(2P/1+N) 56 MW 1016 mm – 5ST3735 5ST3705
L1 L2/N
15
18
17,3
17,3
L2 L1 N N L2 N N L3 N N L1 L3 N L1
4
L1
L1 N
N N N L1 L3 L2 N N L3 L2 L1 N N N L1
19,7 21,4
∅ 10 mm2 ∅ 16 mm2
1 1 1 1 1 1 For 6 MCBs 16 MW 292 mm ■ 5ST3770-4 5ST3770-5
1P+N
with 1 RCCB
18,3
L1 L2 L3 N L2 N L3 N
3P+N,
22,1 N right
L1 L2 L3
9,2
Can be cut, for devices with add-on 5SM6 arc fault detection units
Pin spacing in MW Application No. of MW Length End caps Color Conductor
(1 MW = 18 mm) included cross-section
10 mm2
1-phase, straight Article No.
2 2 For 5SM601. 56 MW 1000 mm – Gray 5ST3764-1
Blue 5ST3765-2
10
5,6
5,6
L1 N L1 N L1 N
14,5
L1 L2 L3
14,5
L1 N L2 N L3 N
19,8
Standard busbars
5ST36 and 5ST37
Can be cut, for devices with add-on 5SM6 arc fault detection units and infeed via RCCB
Pin spacing in MW Application No. of MW Length End caps Color Conductor
(1 MW = 18 mm) included cross-section
16 mm2
2-phase/1-phase + N Article No.
1 2 2 For RCCB 2P N-right and 12 MW 214 mm ■ Gray 5ST3772
5 AFDD (5SM601.) +
compact device
N L1 N L1 N
18,3
L1
18
Accessories
Terminals for infeed at side Article No.
For conductors Short 5ST3768
6 … 25 mm2 Short, IP20 5ST3771-2
Long 5ST3771-1
End caps Article No.
For 1-phase busbars Gray 5ST3766
Blue 5ST3767
For 2 and 3-phase busbars 5ST3750
For 4-phase busbars 5ST3718
Touch protection Article No.
For free connections, yellow (RAL 1004) 5× 1 pin 5ST3655
Compact busbars
General information
Infeed
At the start or end of the busbar Along the busbar or midpoint infeed
3 2 1 1 2 3
I201_13755
S I201_13754a
S1 S2
4
S
Compact busbars
5ST36, fixed lengths, cannot be cut
Pin spacing in MW Application No. of MW Length End caps Conductor
(1 MW = 18 mm) included cross-section
10 mm2
2-phase/1-phase + N, for infeed via RCCB Article No.
1 2 2 For 1 x RCCB 1P+N and 5 x compact 12 MW 216 mm ■ 5ST3685-0
devices equipped with 5SM6 arc fault
AFDD
AFDD
detection unit
13,7
L1 N L1 N L1 N
42,4
4 9 MW
12 MW
166 mm
218 mm
■
■
5ST3674-7
5ST3674-0
13,7
L1 N L1 N L1 N
42,4
AFDD
AFDD
13,7
L1 N L1 N
42,4
L1 N L2 N L3 N L1 N
42,4 14 MW 254 mm ■ 5ST3673-4
AFDD
AFDD
13,7
L1 N L2 N L3 N
42,4
N L1 N L1 N L1 N
L1 devices
42,4 4
2-phase/1-phase + N Article No.
1 1 For compact 60 MW 1060 mm – 5ST3774-0
devices
L1 N L1 N L1 N
13
40,8
AFDD
AFDD
40,8
9 mm
9 mm
with auxiliary
switch
L1 N AS L1 N AS L1 N AS
13
40,8
AFDD
AFDD
9 mm
9 mm
40,8 switch
1 2,5 For 2 MW units 54 MW 956 mm – 5ST3786-0
(MCBs or RCBOs)
AFDD
AFDD
9 mm
with mounted
5SM6 arc fault
N AS N
L1 L1 detection unit and
13
FC
40,8 auxiliary switch
Compact busbars
5ST37, can be cut
Pin spacing in MW Application No. of Length End caps Conductor
(1 MW = 18 mm) MW included cross-section
10 mm2
4-phase/3-phase + N, for infeed via RCCB Article No.
1 1 1 1 1 1 1 1 For 1× RCCB 3P+N 10 MW 181 mm ■ 5ST3783-1
and 6× compact
devices
pYWXYWX\\
13,7
L1 L2 L3 N L1 N L2 N L3 N L1 N L2 N L3 N For 1× RCCB 3P+N 12 MW 216 mm ■ 5ST3783-0
42,4 and 8× compact
devices
For 1× RCCB 3P+N 14 MW 251 mm ■ 5ST3783-4
and 10× compact
devices
4 1 1 1 1 1 1 1 1 For 1× RCCB 3P+N 10 MW 181 mm ■ 5ST3783-1KL
(RCCB N left only)
and 6× compact
pYWXYWX\]
13,7
N L1 L2 L3 L1 N L2 N L3 N L1 N L2 N L3 N devices
42,4 For 1× RCCB 3P+N 12 MW 216 mm ■ 5ST3783-0KL
(RCCB N left only)
and 8× compact
devices
1 1 1 1 1 1 1 1 1 1 1 1 For 1× RCCB 14 MW 253 mm ■ 5ST3785-4
3P+N,
1× MCB 3P and
pYWXYWX\X
13,7
L1 L2 L3 N L1 L2 L3 L1 N L2 N L3 N L1 N L2 N L3 N L1 N 7× compact
42,4 devices
1 1 1 1 1 1 1 1 1 1 1 1 1 For 1× RCCB 24 MW 430 mm ■ 5ST3790-1
3P+N,
2× MCBs 3P+N
pYWXYWX\Z
13,7
40,8 devices
1 1 1 1 1 1 1 1 1 1 1 For 1× RCCB 12 MW 217 mm ■ 5ST3795-0
3P+N,
1x MCB 3P+N and
pYWXYWX\Y
13,7
L1 L2 L3 N L1 L2 L3 N L1 N L2 N L3 N L1 N 4× compact
42,4 devices
1 1 1 1 1 1 1 1 1 1 1 For 1× RCCB 14 MW 253 mm ■ 5ST3795-4
3P+N,
1× MCB 3P+N and
pYWXYWX\W
13,7
N L1 N L2 N L3 N L1 N L2 N L3 N
L1 L2 L3 N L1 L2 L3 6× compact
42,4 devices
L1 N L2 N L3 N L1 N
13
40,8
AFDD
AFDD
40,8
9 mm
9 mm
with auxiliary
switch
L1 N AS L2 N AS L3 N AS L1
13
40,8
Accessories for 5ST3 compact busbars, versions that can and cannot be cut
Touch protection for 5ST3
Version Color Article No.
For free connections, for pins L1, N Yellow (RAL1004) 5ST3655
For pins L2, L3 Yellow (RAL1004) 5ST3655-0HG
End caps for 5ST3
Version Color Article No.
For 2-phase and 4-phase busbars Gray 5ST3788-0
Electrical switching –
on the safe side
Control and automatic functions always employ
electrical switching.
Switching Devices
Timers 5/36
Information + ordering
All the important things at a glance Everything you need for your order
For information about switching devices, please visit our Refer to the Industry Mall for an overview of your
website www.siemens.com/switching-devices products
• Switching devices sie.ag/2m4eG5M
Direct forwarding to the individual products in the
Your product in detail Industry Mall by clicking on the article number in the
catalog or entering this web address incl. article n
umber
5 The relevant tender specifications can be found at www.siemens.com/product?Article No.
www.siemens.com/lowvoltage/tenderspecifications
Use our conversion tool for quick and easy conversion to
Siemens products www.siemens.com/conversion-tool
Commissioning + operation
The Siemens Industry Online Support (SIOS) provides Manuals are available for downloading in Siemens
detailed technical information Industry Online Support (SIOS) at
www.siemens.com/lowvoltage/product-support www.siemens.com/lowvoltage/manuals
• Operating instructions • Configuration Manual
• Certificates − Switching devices (45315361)
Comprehensive mobile support via the Siemens Industry
Online Support app available for download from the
App Store and Play Store Face-to-face or online training
You will find further information at
www.siemens.com/support-app Our training courses can be found at
Provision of 3D data (step and u3d data formats) www.siemens.com/sitrain-lowvoltage
• Siemens Industry Mall • Basic principles of electrical engineering (WT-LVBGET)
www.siemens.com/lowvoltage/mall
• Image database
www.siemens.com/lowvoltage/picturedb
Engineering data for CAD or CAE systems are available in
the CAx Download Manager at
www.siemens.com/cax
System overview
Basic units and accessories
Accessories
Auxiliary switches Shunt trips Undervoltage Remote control Handle locking LEDs Caps/covers Connectors
(AS) (ST) releases (UR) mechanisms devices
(RC mech.)
Timers
7LF4 digital 7LF5 mechanical 7LF6 timers for 5TT3 timers for
time switches time switches buildings industrial applications
Accessories
Holders
Note:
You will find a detailed range of accessories with the basic units.
Accessories
Handle locking device
• To prevent undesired mechanical On/Off switching
• Sealable
• For padlock with max. 3 mm shackle
Article No.
5ST3801
Spacer
• Contour for modular devices with a mounting depth of 70 mm
• Can be snapped onto either side of the busbar for convenient cable routing
• Spacer is recommended for better heat dissipation
Article No.
5TG8240
5TE48 pushbuttons
With/without LED
Pushbuttons without Pushbuttons with Control pushbuttons with
maintained-contact function maintained-contact function maintained-contact function or
momentary-contact function
Without LED Without LED With LED
Rated operational current Ie per conducting path 20 A 20 A 20 A
Rigid/flexible conductor cross-section 1 … 6 mm2 1 … 6 mm2 1 … 6 mm2
Max. cable length Standard Standard Standard
1× red 5TE4822 – –
230 V AC White
Red
5TG8058-0
5TG8058-1
5
1× blue 5TE4822-1 – –
Yellow 5TG8058-2
– – 1× green, 1× red 5TE4840
Green 5TG8058-3
– – –
– – – Blue 5TG8058-4
– – – Cap sets
– 1× green, 1× red 5TE4830 1× green, 1× red 5TE4841 • For manual changing of colored caps
with or without lamps
– – –
• 1 set = 5 units
– – –
Color Article No.
– 1× green, 1× red 5TE4831 –
Red, transparent 5TG8061
– – –
– – –
– – – Green, transparent 5TG8062
– – –
– – –
– – – Yellow, transparent 5TG8063
Ue AC Mounting width
230 V 1 MW 1× red 5TE5800 1× red 5TE5804
1× green, 1× red 5TE5801 –
5 3× green 5TE5802 –
1× red, 1× yellow, 1× green 5TE5803 –
12 … 60 V 1 MW 1× red 5TE5810 –
1× green 5TE5810-1 –
1× green, 1× red 5TE5811 –
3× green 5TE5812 –
1× red, 1× yellow, 1× green 5TE5812-1 –
Accessories
LEDs for manual spare part
Ie Ue Color Article No.
0.4 A 12 ... 60 V AC/DC White 5TG8056-0
Red 5TG8056-1
Yellow 5TG8056-2
Green 5TG8056-3
Blue 5TG8056-4
115 V AC/DC White 5TG8057-0
Red 5TG8057-1
Yellow 5TG8057-2
Green 5TG8057-3
Blue 5TG8057-4
230 V AC White
Red
5TG8058-0
5TG8058-1
5
Yellow 5TG8058-2
Green 5TG8058-3
Blue 5TG8058-4
Cap sets
• For manual changing of colored caps
• 1 set = 5 units
Color Article No.
Red, transparent 5TG8061
Accessories
Auxiliary switches (AS)
• For right-hand-side retrofitting with factory-fitted brackets
Contacts Type Article No.
1 NO + 1 NC Standard 5ST3010
For low power 5ST3013
For low power (with diode) 5ST3013-0XX01
2 NO Standard 5ST3011
For low power 5ST3014
2 NC Standard 5ST3012
For low power 5ST3015
1 CO Standard 5ST3016
Handle locking device
• To prevent undesired mechanical On/Off switching
• Sealable 5
• For padlock with max. 3 mm shackle
Article No.
5ST3801
Terminal cover
• For covering screw openings
• Sealable
Article No.
5ST3800
Spacer
• Contour for modular devices with a mounting depth of 70 mm
• Can be snapped onto either side of the busbar for convenient cable routing
• Spacer is recommended for better heat dissipation
Article No.
5TG8240
Contacts Rated operational Mounting Gray handle Gray handle Gray handle Red handle Gray handle Gray handle
voltage Ue AC width
1 NO 230 V 1 MW 5TL1132-0 5TL1140-0 5TL1163-0 5TL1163-1 5TL1180-0 5TL1191-0
5 2 NO 400 V 2 MW 5TL1232-0 5TL1240-0 5TL1263-0 5TL1263-1 5TL1280-0 5TL1291-0
3 NO 400 V 3 MW 5TL1332-0 5TL1340-0 5TL1363-0 5TL1363-1 5TL1380-0 5TL1391-0
4 NO 400 V 4 MW 5TL1432-0 5TL1440-0 5TL1463-0 – 5TL1480-0 5TL1491-0
3 NO + N 400 V 4 MW 5TL1632-0 5TL1640-0 5TL1663-0 5TL1663-1 5TL1680-0 5TL1691-0
Accessories
125 A
Auxiliary switches (AS)
2.5 ... 50 mm2
• For right-hand-side retrofitting with factory-fitted brackets
2.5 ... 50 mm 2
Contacts Type Article No.
1 NO + 1 NC Standard 5ST3010
For low power 5ST3013
For low power (with diode) 5ST3013-0XX01
2 NO Standard 5ST3011
For low power 5ST3014
2 NC Standard 5ST3012
For low power 5ST3015
Red handle Gray handle
1 CO Standard 5ST3016
Remote control mechanisms (RC mech.)
5TL1191-1 5TL1192-0
5TL1291-1 5TL1292-0
Type
Basic
Ue
12 … 30 V AC, 12 … 48 V DC
Article No.
5ST3053
5
5TL1391-1 5TL1392-0
177 … 270 V AC 5ST3054
– 5TL1492-0
Power 12 … 30 V AC, 12 … 48 V DC 5ST3055
5TL1691-1 5TL1692-0
177 … 270 V AC 5ST3056
Power with ARD 12 … 30 V AC, 12 … 48 V DC 5ST3057
177 … 270 V AC 5ST3058
Adapters for remote control mechanisms (RC mech.)
Mounting width Article No.
1–2 MW 5ST3820-6
3–4 MW 5ST3820-7
Handle locking device
• To prevent undesired mechanical On/Off switching
• Sealable
• For padlock with max. 3 mm shackle
Article No.
5ST3806
Terminal cover
• For covering screw openings
• Sealable
Article No.
5ST3800
Spacer
• Contour for modular devices with a mounting depth of 70 mm
• Can be snapped onto either side of the busbar for convenient cable
routing
• Spacer is recommended for better heat dissipation
Article No.
5TG8240
Phase connectors
• For easy wiring in various circuit versions and bus mountings
• As a support terminal for conductors from 2.5 to 50 mm2
Number of poles Ie Ue AC Mounting width Article No.
1-pole 125 A 230 V 1 MW 5TL1192-4
N conductor connectors
• For easy wiring in various circuit versions and bus mountings
• As a support terminal for N conductors from 2.5 to 50 mm2
with blue color marking
Number of poles Ie Ue AC Mounting width Article No.
1-pole 125 A 230 V 1 MW 5TL1192-3
5TE DC isolator
Can be used as switch disconnectors according to EN 60947-3
Rated operational current Ie
63 A
Rigid conductor cross-section 0.75 ... 35 mm2
Flexible conductor cross-section, with end sleeve 0.75 ... 25 mm2
Contacts Max. operational voltage Umax Mounting width Auxiliary switches can be retrofitted
DC
4 NO 1000 V 4 MW 5TE2515-1
5
Accessories
Auxiliary switches (AS)
• For right-hand-side retrofitting with factory-fitted brackets
Contacts Type Article No.
1 NO + 1 NC Standard 5ST3010
For low power 5ST3013
For low power (with diode) 5ST3013-0XX01
2 NO Standard 5ST3011
For low power 5ST3014
2 NC Standard 5ST3012
For low power 5ST3015
1 CO Standard 5ST3016
Shunt trips (ST)
Rated operational voltage Ue Article No.
110 … 415 V AC, 110 … 220 V DC 5ST3030 5
24 ... 48 V AC/DC 5ST3031
12 V AC/DC 5ST3031-0XX01
5TE busbars
For modular installation devices
1-phase busbar
• For all 5TE8 switches, 20 A and 32 A
• For the cutting of unused terminal lugs and to ensure insulation clearances if one device terminal
is to be supplied separately despite being mounted on the bus
• Infeed to unit terminal with conductor cross-section of 6 mm2 up to 32 A
• Can be mounted from either top or bottom, in the front or rear terminal area
• An end cap is not required on 1-phase busbars
Length Division Article No.
210 mm 12 MW version with 1 MW modular clearance 5TE9100
2-phase busbar
• For all 5TE8 switches, 20 A and 32 A
• Infeed to unit terminal with conductor cross-section of 6 mm2 up to 32 A
• Can be mounted from either top or bottom, in the front and/or rear terminal area,
thus allowing realization of a 4-wire connection using 2 2-phase busbars
• Both copper conductors of the 2-phase busbar are insulated together
Length Division Article No.
5 220 mm 12 MW version each with 1 MW modular clearance, phases offset by 0.5 MW 5TE9101
End caps for 2-phase busbars
• End caps for 5TE9101 2-phase busbars to maintain insulation clearances when the bar is being cut
• 1 set = 10 units
Article No.
5TE9102
Contacts Ue Uc AC Uc DC Mounting width Auxiliary switches can be retrofitted
1 MW 2 MW
1 NO 250 V 230 V – ■ – 5TT4101-0
5 115 V – ■ – 5TT4101-1
24 V – ■ – 5TT4101-2
12 V – ■ – 5TT4101-3
8V – ■ – 5TT4101-4
– 110 V ■ – 5TT4111-1
24 V ■ – 5TT4111-2
12 V ■ – 5TT4111-3
1 NO + 1 NC 250 V 230 V – ■ – 5TT4105-0
115 V – ■ – 5TT4105-1
24 V – ■ – 5TT4105-2
12 V – ■ – 5TT4105-3
8V – ■ – 5TT4105-4
– 110 V ■ – 5TT4115-1
24 V ■ – 5TT4115-2
12 V ■ – 5TT4115-3
2 NO 400 V 230 V – ■ – 5TT4102-0
115 V – ■ – 5TT4102-1
24 V – ■ – 5TT4102-2
12 V – ■ – 5TT4102-3
8V – ■ – 5TT4102-4
– 110 V ■ – 5TT4112-1
24 V ■ – 5TT4112-2
12 V ■ – 5TT4112-3
3 NO 400 V 230 V – – ■ 5TT4103-0
24 V – – ■ 5TT4103-2
4 NO 400 V 230 V – – ■ 5TT4104-0
24 V – – ■ 5TT4104-2
– 110 V – ■ 5TT4114-1
24 V – ■ 5TT4114-2
Accessories
Auxiliary switches
• One device per remote control switch can be retrofitted
Contacts Type Ie Ue Mounting width Article No.
1 CO Standard 5A 250 V AC 0.5 MW 5TT4900
For low power 0.1 A 30 V AC/DC 0.5 MW 5TT4901
Compensator
• For increasing the glow lamp load by 20 mA
Ue Mounting width Article No.
250 V AC 1 MW 5TT4920
Contacts Ue Uc AC Mounting width Auxiliary switches cannot be retrofitted Auxiliary switches cannot be retrofitted
1 NO 250 V 230 V 1.5 MW 5TT4121-0 5TT4151-0
24 V 1.5 MW 5TT4121-2 5TT4151-2
2 NO 400 V 230 V 1.5 MW 5TT4122-0 5TT4152-0
5 24 V 1.5 MW 5TT4122-2 5TT4152-2
3 NO 400 V 230 V 2.5 MW 5TT4123-0 –
1 NO + 1 NC 250 V 115 V 1.5 MW 5TT4125-0 –
Contacts Ue Uc AC Mounting width Auxiliary switches cannot be retrofitted Auxiliary switches cannot be retrofitted
2 NO 250 V 230 V 1 MW 5TT4132-0 5TT4142-0
24 V 1 MW – 5TT4142-2
12 V 1 MW 5TT4132-3 5TT4142-3
5TT412 5TT413
Further technical specifications 5TT415 5TT414
Standards
Standards EN 60669-1 (VDE 0632-1)/EN 60669-1/A1/A2
EN 60669-2-2 (VDE 0632-2-2)/EN 60669-2-2
Approvals VDE
Supply
Rated operational current Ie At p.f. = 0.6 ... 1 (AC-15) 16 A
Primary operating range 0.8 ... 1.1 × Uc
Rated frequency fc 50 Hz
Rated power dissipation Pv Magnet coil, only pulse 4.5 W/7 VA
Per pole, max. 1.2 W
Contacts
Contact gap >1.2 mm
Minimum contact load 10 V; 100 mA 5
Electrical endurance at Ie/Ue, p.f. = 0.6, Operating cycles 50000
incandescent lamp load 600 W
Incandescent lamp load At AC-5b (230 V) 1200 W
(switching of incandescent lamps for 15000 switching cycles)
Glow lamp load at 230 V 5 mA
With 1 5TT4920 compensator 25 mA
With 2 5TT4920 compensators 45 mA
Minimum pulse duration 50 ms
Safety
Different phases between magnet coil and contact Permissible
Clearances Between magnet coil and contact >6 mm
Creepage distances Between magnet coil and contact >6 mm
Rated impulse voltage Uimp 4 kV
Function
Manual operation Yes
Switching position indication Yes –
Connections
Terminals ± Screw (Pozidriv) PZ1
Max. tightening torque 0.8 ... 1 Nm
Ambient conditions
Permissible ambient temperature –10 … +40 °C
Resistance to climate at 95% relative humidity Acc. to DIN 50015 35 °C
Degree of protection Acc. to EN 60529 IP20, with connected conductors
Accessories
Auxiliary switches
• One device per remote control switch can be retrofitted
Contacts Type Ie Ue Mounting width Article No.
1 CO Standard 5A 250 V AC 0.5 MW 5TT4900
For low power 0.1 A 30 V AC/DC 0.5 MW 5TT4901
Compensator
• For increasing the glow lamp load by 20 mA
Ue Mounting width Article No.
250 V AC 1 MW 5TT4920
Contacts Ue Uc AC Uc DC Mounting
width
Accessories
Auxiliary switch
Contacts Ue Ie Mounting width Article No.
1 NO + 1 NC 250 V AC 16 A 0.5 MW 5TT4930
5 1 CO Standard
For low power
5A
0.1 A
250 V AC
30 V AC/DC
0.5 MW
0.5 MW
5TT4900
5TT4901
–
–
Auxiliary switches, central with diode for central function (no auxiliary switch)
250 V AC 0.5 MW – 5TT4931
Auxiliary switches, group with several diodes for group function (no auxiliary switch)
250 V AC 0.5 MW – 5TT4932
Accessories
Compensator
• For increasing the glow lamp load by 20 mA
Ue Mounting width Article No.
250 V AC 1 MW 5TT4920
5 24 V
12 V
–
–
1 MW
1 MW
5TT4201-2
5TT4201-3
8V – 1 MW 5TT4201-4
2 NO 400 V 230 V – 1 MW 5TT4202-0
115 V – 1 MW 5TT4202-1
24 V – 1 MW 5TT4202-2
12 V – 1 MW 5TT4202-3
8V – 1 MW 5TT4202-4
4 NO 400 V 230 V – 1 MW 5TT4204-0
115 V – 1 MW 5TT4204-1
24 V – 1 MW 5TT4204-2
12 V – 1 MW 5TT4204-3
8V – 1 MW 5TT4204-4
1 NO + 1 NC 400 V 230 V – 1 MW 5TT4205-0
115 V – 1 MW 5TT4205-1
24 V – 1 MW 5TT4205-2
12 V – 1 MW 5TT4205-3
8V – 1 MW 5TT4205-4
1 CO 250 V 230 V – 1 MW 5TT4206-0
115 V – 1 MW 5TT4206-1
24 V – 1 MW 5TT4206-2
12 V – 1 MW 5TT4206-3
8V – 1 MW 5TT4206-4
2 CO 400 V 230 V – 1 MW 5TT4207-0
115 V – 1 MW 5TT4207-1
24 V – 1 MW 5TT4207-2
12 V – 1 MW 5TT4207-3
8V – 1 MW 5TT4207-4
– 110 V 1 MW 5TT4217-1
30 V 1 MW 5TT4217-6
24 V 1 MW 5TT4217-2
12 V 1 MW 5TT4217-3
Further technical specifications 5TT4201-. 5TT4202-. 5TT4204-. 5TT4205-. 5TT4206-. 5TT4207-. 5TT4217-.
Standards
Standards EN 60947-5-1, EN 60669-2-2
Approvals VDE, CCC
Supply
Rated operational current Ie At p.f. = 0.6 ... 1 16 A
Primary operating range 0.8 ... 1.1 × Uc
Rated frequency fc 50 Hz
Rated power dissipation Pv Magnet coil 2.4 W 4.8 W 2.4 W 1.7 W
3.0 VA 6.0 VA 3.0 VA 1.7 VA
Per pole, max. 1.0 W
Contacts
Contact gap >1.2 mm
Minimum contact load 10 V AC; 100 mA
Electrical endurance at Ie/Ue, Operating cycles 50000 5
p.f. = 0.6,
incandescent lamp load 600 W
Safety
Different phases between magnet coil and contact Permissible
Safe separation >6 mm
Rated impulse voltage Uimp 4 kV
Function
Manual operation Yes
Connections
Terminals ± Screw (Pozidriv) PZ1
Max. tightening 0.8 ... 1 Nm
torque
Ambient conditions
Permissible ambient temperature –10 … +40 °C
Resistance to climate at 95% Acc. to DIN 50015 35 °C
relative humidity
Degree of protection Acc. to EN 60529 IP20, with connected conductors
Accessories
Spacer
• Contour for modular devices with a mounting depth of 70 mm
• Can be snapped onto either side of the busbar for convenient cable routing
• Spacer is recommended for better heat dissipation
Article No.
5TG8240
Contacts Ue Uc AC Uc DC Mounting width
5 Insta contactors with manual switch
2 NO 230 V 230 V 220 V 1 MW 5TT5000-0 – – –
24 V 24 V 1 MW 5TT5000-2 – – –
4 NO 400 V 230 V 220 V 2 MW – 5TT5030-0 – –
3 MW – – 5TT5040-0 5TT5050-0
115 V 110 V 2 MW – 5TT5030-1 – –
24 V 24 V 2 MW – 5TT5030-2 – –
3 MW – – 5TT5040-2 5TT5050-2
2 NC 230 V 230 V 220 V 1 MW 5TT5002-0 – – –
24 V 24 V 1 MW 5TT5002-2 – – –
4 NC 400 V 230 V 220 V 2 MW – 5TT5033-0 – –
3 MW – – 5TT5043-0 –
24 V 24 V 2 MW – 5TT5033-2 – –
3 MW – – 5TT5043-2 –
1 NO + 1 NC 230 V 230 V 220 V 1 MW 5TT5001-0 – – –
24 V 24 V 1 MW 5TT5001-2 – – –
2 NO + 2 NC 400 V 230 V 220 V 2 MW – 5TT5032-0 – –
3 MW – – 5TT5042-0 5TT5052-0
24 V 24 V 2 MW – 5TT5032-2 – –
3 MW – – 5TT5042-2 5TT5052-2
3 NO + 1 NC 400 V 230 V 220 V 2 MW – 5TT5031-0 – –
3 MW – – 5TT5041-0 5TT5051-0
24 V 24 V 2 MW – 5TT5031-2 – –
3 MW – – 5TT5041-2 5TT5051-2
Insta contactors with O/I/Automatic
2 NO 230 V 230 V 220 V 1 MW 5TT5000-6 – – –
24 V 24 V 1 MW 5TT5000-8 – – –
4 NO 400 V 230 V 220 V 2 MW – 5TT5030-6 – –
24 V 24 V 2 MW – 5TT5030-8 – –
1 NO + 1 NC 230 V 230 V 220 V 1 MW 5TT5001-6 – – –
24 V 24 V 1 MW 5TT5001-8 – – –
3 NO + 1 NC 400 V 230 V 220 V 2 MW – 5TT5031-6 – –
24 V 24 V 2 MW – 5TT5031-8 – –
Note:
Provision must be made for spacers to ensure heat dissipation.
See Configuration Manual – Switching devices www.siemens.com/lowvoltage/manuals (45315361).
Accessories
Spacer
• Contour for modular devices with a mounting depth of 70 mm
• Can be snapped onto either side of the busbar for convenient cable routing
• Spacer is recommended for better heat dissipation
Article No.
5TG8240
Accessories
Auxiliary switches Sealable terminal covers
• For right-hand-side retrofitting For Insta contactor Mounting width Article No.
• Max. one auxiliary switch per Insta contactor 20 A 1 MW 5TT5910-5
Contacts Mounting width Article No. 25 A 2 MW 5TT5910-6
2 NO 0.5 MW 5TT5910-0 40 A and 63 A 3 MW 5TT5910-7
1 NO + 1 NC 0.5 MW 5TT5910-1
Contacts Ue Uc AC Mounting
width
Insta contactors without manual switch
5 2 NO 230 V 230 V 1 MW 5TT5800-0 5TT5810-0 5TT5860-0 – –
new new
24 V 1 MW 5TT5800-2 – – – –
4 NO 400 V 230 V Standard 2 MW – 5TT5830-0 – – –
3 MW – – – 5TT5840-0 5TT5850-0
Capacitive loads 2 MW – 5TT5820-0 – – –
up to 150 µF
115 V 2 MW – 5TT5830-1 – – –
24 V 2 MW – 5TT5830-2 – – –
3 MW – – – 5TT5840-2 5TT5850-2
2 NC 230 V 230 V 1 MW 5TT5802-0 – – – –
24 V 1 MW 5TT5802-2 – – – –
4 NC 400 V 230 V 2 MW – 5TT5833-0 – – –
3 MW – – – 5TT5843-0 5TT5853-0
24 V 2 MW – 5TT5833-2 – – –
3 MW – – – 5TT5843-2 5TT5853-2
1 NO + 1 NC 230 V 230 V 1 MW 5TT5801-0 – – – –
24 V 1 MW 5TT5801-2 – – – –
2 NO + 2 NC 400 V 230 V 2 MW – 5TT5832-0 – – –
3 MW – – – 5TT5842-0 5TT5852-0
24 V 2 MW – 5TT5832-2 – – –
3 MW – – – 5TT5842-2 5TT5852-2
3 NO + 1 NC 400 V 230 V 2 MW – 5TT5831-0 – – –
3 MW – – – 5TT5841-0 5TT5851-0
115 V 2 MW – 5TT5831-1 – – –
24 V 2 MW – 5TT5831-2 – – –
3 MW – – – 5TT5841-2 5TT5851-2
Insta contactors with manual switch O/I/Automatic
2 NO 230 V 230 V 1 MW 5TT5800-6 – – – –
24 V 1 MW 5TT5800-8 – – – –
4 NO 400 V 230 V 2 MW – 5TT5830-6 – – –
3 MW – – – 5TT5840-6 5TT5850-6
24 V 2 MW – 5TT5830-8 – – –
3 MW – – – 5TT5840-8 –
1 NO + 1 NC 230 V 230 V 1 MW 5TT5801-6 – – – –
24 V 1 MW 5TT5801-8 – – – –
3 NO + 1 NC 400 V 230 V 2 MW – 5TT5831-6 – – –
3 MW – – – 5TT5841-6 –
24 V 2 MW – 5TT5831-8 – – –
3 MW – – – 5TT5841-8 –
Note:
Provision must be made for spacers to ensure heat dissipation.
See Configuration Manual – Switching devices www.siemens.com/lowvoltage/manuals (45315361).
5TT582.
Further technical specifications 5TT580. 5TT581. 5TT583. 5TT584. 5TT585. 5TT586.
Standards
Standards IEC 60947-4-1, IEC 60947-5-1, IEC 61095;
EN 60947-4-1, EN 60947-5-1, EN 61095, VDE 0660
Supply
Number of poles 2 4 2
Rated operational current Ie 20 A 25 A 40 A 63 A 32 A
Primary operating range 0.85 ... 1.1 × Uc
Rated frequency fc at AC 50/60 Hz
Rated power dissipation Pv Pick-up power (without 6 VA/3.8 W 12 VA /10 W 10 VA/5 W 15.4 VA/4.6 W 12 VA /10 W
manual switch or manual
switch in "I" position)
Pick-up power (with manual 12 VA/10 W – 33 VA/25 W 62 VA/50 W –
switch in "AUTO" position)
Holding power 2.8 VA/1.2 W 5.5 VA/1.6 W 7.7 VA/3 W 2.8 VA/1.2 W
Per contact AC-1/AC-7a 1.7 VA 2.0 VA 2.2 VA 4 VA 8 VA 2.5 VA 5
Contacts
Contact gap Minimum 3.6 mm 3.4 mm 3.6 mm
Minimum switching capacity (= minimum contact load) ≥17 V; 50 mA
Electrical endurance at Ie and load AC-1/AC-7a operating cycles 200000 100000 150000
AC-3/AC-7b operating cycles 300000 500000 150000 300000
Mechanical service life Operating cycles 3 million
Switching of resistive loads AC-1/AC-7a 1-phase (230 V) (NO contacts) 4 kW 5.4 kW 8.7 kW 13.3 kW 5.9 kW
for rated operational power Ps 3-phase (400 V) (NO contacts) – 16 kW 26 kW 40 kW –
Switching of 3-phase asynchronous motors 1-phase (230 V) (NO contacts) 1.3 kW 1) 1.3 kW 3.7 kW 5 kW 1.3 kW
AC-3/AC-7b for rated operational power Ps 3-phase (400 V) (NO contacts) – 4 kW 11 kW 15 kW –
Maximum switching frequency at load 600 h-1
Safety
Rated insulation voltage Ui 440 V 500 V 440 V
Rated impulse voltage Uimp 4 kV
Short-circuit protection, Back-up fuse characteristic 20 A 25 A 63 A 80 A 32 A
according to coordination type 1 gL/gG
Overload withstand capability at 10 s Per conducting path 72 A 68 A 176 A 240 A 72 A
(NO contacts only)
Function
Switching times Closing (NO contacts) 15 … 25 ms 10 … 20 ms 15 … 20 ms 15 … 25 ms
Opening (NO contacts) 20 ms 10 … 30 ms 20 ms 10 ms 10 … 30 ms
Closing (NC contacts) 20 … 30 ms – 20 … 30 ms 5 … 10 ms –
Opening (NC contacts) 10 ms – 10 ms 10 … 15 ms –
Connections
Coil connection terminals ± Screw (Pozidriv) PZ1
Main connection terminals ± Screw (Pozidriv) PZ1 PZ2 PZ1
Coil connection conductor cross-section Rigid 1.0 ... 2.5 mm2
Flexible, with end sleeve 1.0 ... 2.5 mm2
Main connection conductor cross-section Rigid 1.0 ... 10 mm2 1 … 25 mm2 1.0 ... 10 mm2
Flexible, with end sleeve 1.0 ... 6 mm2 1 … 16 mm2 1.0 ... 6 mm2
Tightening torque Coil connection 0.6 Nm
Main connection 1.2 Nm 3.5 Nm 1.2 Nm
Ambient conditions
Permissible ambient temperature For operation/for storage –5 … +55 °C/–30 … +80 °C
Degree of protection Acc. to EN 60529 IP20, with connected conductors
1)
For NO contacts only.
Accessories
Auxiliary switches Spacer
• For right-hand-side retrofitting • Contour for modular devices with a
• Max. one auxiliary switch per Insta contactor mounting depth of 70 mm
Contacts Mounting width Article No. • Can be snapped onto either side of the
busbar for convenient cable routing
2 NO 0.5 MW 5TT5910-0
• Spacer is recommended for better heat
1 NO + 1 NC 0.5 MW 5TT5910-1 dissipation
Sealable terminal covers Article No.
For Insta contactor Mounting width Article No. 5TG8240
20 A 1 MW 5TT5910-5
25 A 2 MW 5TT5910-6
40 A and 63 A 3 MW 5TT5910-7
5
Further technical specifications 5TT5910
Standards
Standards IEC 60947-5-1
Approvals CCC
Supply
Number of poles 2
Rated operational current Ie 230 V 6A
400 V 4A
Rated frequency fc at AC 50/60 Hz
Contacts
Contact gap Minimum 4 mm
Minimum switching capacity (= minimum contact load) ≥12 V; 5 mA
Mechanical service life Operating cycles 3 million
Maximum switching frequency at load 600 h-1
Safety
Rated insulation voltage Ui 500 V
Rated impulse voltage Uimp 4 kV
Short-circuit protection, Back-up fuse characteristic gL/gG 6A
according to coordination type 1
Connections
Terminals ± Screw (Pozidriv) PZ1
Conductor cross-section Rigid 1 ... 2.5 mm2
Flexible, with end sleeve 1 ... 2.5 mm2
Tightening torque 0.8 Nm
Ambient conditions
Permissible ambient temperature For operation/for storage –5 … +55 °C/–30 … +80 °C
Degree of protection Acc. to EN 60529 IP20, with connected conductors
5
Further technical specifications 5TT3440
Standards
Standards EN 60947-4-2 (VDE 0660-117)
Supply
Line/motor voltage 400 V AC
Primary operating range 0.8 ... 1.1 × Uc
Rated frequency fc at AC 50/60 Hz
Rated power 3.5 VA
Rated power dissipation Pv Coil/drive 3.5 VA
at rated operational current Per contact 4.6 VA
Rated output of motor at 400 V Max. 5500 VA
Min. 300 VA
Startup voltage 30 … 70%
Starting ramp 0.1 ... 10 s
Safety
Quick-acting semiconductor fuse 35 A
Function
Switching frequency 3× IN, TAN = 10 s, νu = 20% Operating cycles (up to 3 kW) 36 h-1
Operating cycles (from 3 … 5.5 kW) 20 h-1
Recovery time 100 ms
Connections
Conductor cross-section Rigid Max. 2× 2.5 mm2
Flexible, with end sleeve Min. 1× 0.5 mm2
Ambient conditions
Permissible ambient temperature –20 … +60 °C
Resistance to climate Acc. to EN 60068-1 20/60/4
1)
A program consists of an ON time, an OFF time and assigned ON and OFF days or day blocks.
Top
1)
A program consists of an ON time, an OFF time and assigned ON and OFF days or day blocks.
2)
The combination of line voltage (230 V) and SELV is not permissible in conjunction with a 2-channel time switch.
This requirement is, however, admissible in the case of 1-channel time switch.
1)
A program consists of an ON time, an OFF time and assigned ON and OFF days or day blocks.
2)
The combination of line voltage (230 V) and SELV is not permissible in conjunction with a 2-channel time switch.
This requirement is, however, admissible in the case of 1-channel time switch.
Astro
1)
A program consists of an ON time, an OFF time and assigned ON and OFF days or day blocks.
2)
The combination of line voltage (230 V) and SELV is not permissible in conjunction with a 2-channel time switch.
This requirement is, however, admissible in the case of 1-channel time switch.
Contacts
At p.f. = 0.6 4A
5
Minimum contact load 4 V/1 mA
Electrical operating cycles At p.f. = 1 100000
Mechanical operating cycles 20 million
Incandescent lamp load 5A
Fluorescent lamp load Parallel p.f. correction 70 µF 60 VA
Uncorrected 1400 VA
Safety
Different phases between operating Permissible
mechanism and contact
Electrical isolation, creepage Operating mechanism 8 mm
distances and clearances Contact 6 mm
Rated impulse voltage Uimp 4 kV
Electrostatic discharge Acc. to IEC 61000-4-2 >8.0 kV
EMC: Burst Acc. to IEC 61000-4-4 >4.4 kV
EMC: Surge Acc. to IEC 61000-4-5 >2.0 kV
Overvoltage category Acc. to EN 61010-1 III
Function
Switching accuracy ±5 min ±30 min ±5 min
Clock errors System-synchronized
Make and break cycles 15 min 120 min 10 min
Minimum switching sequences 30 min 240 min 30 min
Connections
Terminals ± Screw (Pozidriv) PZ1
Conductor cross-sections of main Rigid 1.5 ... 4 mm²
conducting path Flexible, with end sleeve Max. 2.5 mm²
Flexible, without end sleeve Max. 4 mm²
Ambient conditions
Permissible ambient temperature For operation/for storage –10 … +55 °C/–10 … +60 °C
Resistance to climate Acc. to EN 60068-1 10/055/21
Degree of protection Acc. to EN 60529 IP20, with connected conductors
Protection class Acc. to EN 61140 II
Accessories
Holders for front panel installation
• Universal application for devices from 1 MW ... 6 MW
• Cutout dimensions:
− Height 45+0.5 mm
− Width 23 mm, 41 mm, 59 mm, 77 mm, 95 mm or 113 mm
Article No.
7LF9006
Accessories
Holders for front panel installation
• Universal application for devices from 1 MW ... 6 MW
• Cutout dimensions:
− Height 45+0.5 mm
− Width 23 mm, 41 mm, 59 mm, 77 mm, 95 mm or 113 mm
Article No.
7LF9006
5
Contacts Mounting width
1 CO 1 MW 5TT3185 5TT3181
6/6
6/8
6
6/10
Information + ordering
All the important things at a glance Everything you need for your order
For information about overvoltage protection devices, Refer to the Industry Mall for an overview of your
please visit our website products
www.siemens.com/overvoltage-protection
• SENTRON overvoltage protection devices
sie.ag/2kTfytV
Direct forwarding to the individual products in the
Your product in detail Industry Mall by clicking on the article number in the
catalog or entering this web address incl. article number
The Siemens Industry Online Support (SIOS) provides www.siemens.com/product?Article No.
6 comprehensive information
www.siemens.com/lowvoltage/product-support
• Technology Primer
− Overvoltage protection devices (109756965)
The relevant tender specifications can be found at
www.siemens.com/lowvoltage/tenderspecifications
Use our conversion tool for quick and easy conversion to
Siemens products www.siemens.com/conversion-tool
Commissioning + operation
The Siemens Industry Online Support (SIOS) provides Manuals are available for downloading in Siemens
detailed technical information Industry Online Support (SIOS) at
www.siemens.com/lowvoltage/product-support www.siemens.com/lowvoltage/manuals
• Operating instructions • Configuration Manual
• Certificates − Overvoltage protection devices (45315289)
Comprehensive mobile support via the Siemens Industry
Online Support app available for download from the
App Store and Play Store Face-to-face or online training
You will find further information at
www.siemens.com/support-app Our training courses can be found at
www.siemens.com/sitrain-lowvoltage
Provision of 3D data (step and u3d data formats)
• Siemens Industry Mall • Basic principles of electrical engineering (WT-LVBGET)
www.siemens.com/lowvoltage/mall • Protection concept (WT-LVBPC)
• Image database
www.siemens.com/lowvoltage/picturedb
System overview
Basic units
5SD74 lightning arresters, 5SD74 combination surge 5SD74 surge arresters, 5SD74 combination
type 1 arresters, type 1 + type 2 type 1 + type 2 + type 3 surge arresters,
for 40 mm busbar system type 1/type 2
Note:
You will find a detailed range of accessories with the basic units.
Z UV Terminal
HAK
equipment
230/400V
S S S
6
P P P
D D D
I201_20525
HAK: Main terminal box Z/HV: In or close to the central meter system/main distribution board UV: Subdistribution board
Installation location 1 must be as close as possible to the supply point for the electrical system, so that the downstream installations are protected.
The SPDs at installation locations 2 and 3 shall not be used without SPDs at installation location 1, and they must be coordinated with these SPDs
(i.e. SPDs all from the same manufacturer).
For TN-C systems and IT For TN-C systems For TN-S and TT systems
networks
Protection paths L-PE L-PEN L-N, L-PE and N-PE L-N, L-PE and N-PE
Rated voltage Un 690 V AC 240/415 V AC 240 V AC 240/415 V AC
Maximum continuous voltage Uc 800 V AC 350 V AC 350 V AC 350 V AC
Circuit Mounting
width
With remote signaling
1+0 –1) 5SD7411-2 – – –
1+1 4 MW – – 5SD7412-1 –
6 3+0
3+1
6 MW
8 MW
–
–
5SD7413-1
–
–
–
–
5SD7414-1
1)
No modular installation device.
Accessories
Spare part plugs
Protection paths Basic units Article No.
N-PE 5SD7412-1 and 5SD7414-1 5SD7418-0
Circuit Mounting
width
With remote signaling
1+1 4 MW – 5SD7442-1 –
3+0 6 MW 5SD7443-1 – –
3+1 8 MW – – 5SD7444-1
6
Further technical specifications 5SD7442-1 5SD7443-1 5SD7444-1
Standards
Standards IEC 61643-11;
EN 61643-11
Approvals KEMA, UL/cUL
Voltage
Protection level Up L-N and L-PEN ≤1.50 kV
L-PE ≤2.20 kV – ≤2.20 kV
N-PE ≤1.50 kV – ≤1.50 kV
Current
Lightning impulse current Iimp L-N and L-PEN 25 kA
(10/350 µs) N-PE 100 kA – 100 kA
Rated discharge surge current In L-N and L-PEN 25 kA
(8/20 µs) N-PE 100 kA – 100 kA
Follow current discharge capacity Ifi L-N and L-PEN 25 kA
(AC) N-PE 100 A – 100 A
Function
Response time tA L-N and L-PEN ≤25 ns
L-N and N-PE ≤100 ns – ≤100 ns
Connections
Conductor cross-section Finely stranded 2.5 … 25 mm2
Solid 2.5 … 35 mm2
Protection devices
Max. back-up fuse acc. to IEC 61643-1 For stub wiring (gL/gG) 315 A
For V wiring (gL/gG) 125 A
Short-circuit strength With max. back-up fuse 25 kA
Ambient conditions
Degree of protection IP20, with connected conductors
Temperature range –40 … +80 °C
Display
Visual function/fault indication Yes
Accessories
Spare part plugs
Protection paths Type Basic units Article No.
N-PE – 5SD7442-1 and 5SD7444-1 5SD7418-0
– – – –
5SD7444-8KK21 – 5SD7444-8KK11 –
– – – –
– 5SD7444-8KK22 – 5SD7444-8KK12 6
12.5 kA 7.5 kA
20/80 kA
100 A RMS
6 3+1
Without remote signaling
4 MW – – – 5SD7414-3 –
1)
No modular installation device.
5SD7413-2 5SD7414-2
Further technical specifications 5SD7411-2 5SD7412-2 5SD7413-3 5SD7414-3 5SD7483-6
Standards
Standards IEC 61643-11 EN 50539
Approvals – KEMA
Voltage
Protection level Up L-N and L-PEN ≤4.50 kV ≤1.20 kV ≤3.50 kV
L-PE – ≤2.0 kV –
N-PE – ≤1.70 kV – ≤1.70 kV –
Current
Lightning impulse current Iimp L-N and L-PEN 35 kA 12.5 kA ≤5 kA
(10/350 µs) N-PE – 50 kA – 50 kA –
Rated discharge surge current In L-N and L-PEN 35 kA 12.5 kA 15 kA
(8/20 µs) N-PE – 50 kA –
Max. discharge surge current Imax. (8/20 L-N 100 kA 12.5 kA 50 kA 40 kA
µs) N-PE – 50 kA – 50 kA –
Function
Response time tA L-N and L-PEN <100 ns ≤25 ns
L-N and N-PE – ≤100 ns – ≤100 ns ≤25 ns
Connections
Conductor cross-section Finely stranded 16 … 50 mm2 1.5 … 25 mm2
Solid 16 … 50 mm 2
1.5 … 35 mm2
Protection devices
Max. back-up fuse acc. to IEC 61643-1 For stub wiring (gL/gG) 400 A 160 A –
For V wiring (gL/gG) 125 A 80 A –
Short-circuit strength With max. back-up fuse 50 kA 25 kA –
Ambient conditions
Degree of protection IP20, with connected conductors
Temperature range –40 … +80 °C
Accessories
Spare part plugs
Protection paths Type Basic units Article No.
N-PE – 5SD7412-2, 5SD7412-3, 5SD7414-2 and 5SD7414-3 5SD7418-2
L-N and L-PEN 1 5SD7412-2, 5SD7412-3, 5SD7413-2, 5SD7413-3, 5SD7414-2 and 5SD7418-3
5SD7414-3
Circuit Mounting
width
With remote signaling
1+0 1 MW – 5SD7461-1 – – – – –
6 2 MW – – 5SD7481-1 – – – –
3+0 3 MW – – – 5SD7463-1 5SD7473-1 5SD7483-5 –
3+1 4 MW – – – – – – 5SD7464-1
Without remote signaling
1+0 1 MW 5SD7481-0 5SD7461-0 – – – – –
3+0 3 MW – – – 5SD7463-0 – – –
3+1 4 MW – – – – – – 5SD7464-0
Accessories
Spare part plugs
Protection paths Basic units Article No.
N-PE 5SD7481-0, 5SD7464-0 and 5SD7464-1 5SD7488-0
L-N and L-PEN 5SD7461-0, 5SD7461-1, 5SD7463-0, 5SD7463-1, 5SD7464-0 and 5SD7464-1 5SD7468-1
5SD7481-1 5SD7488-4
5SD7422-0 5SD7424-0
Further technical specifications 5SD7422-1 5SD7424-1
Standards
Standards IEC 61643-11,
EN 61643-11
Approvals KEMA/UL/cUL
Voltage
Protection level Up L-N and L-PEN ≤1.50 kV
L-PE ≤1.90 kV
N-PE ≤1.50 kV
Current
Rated discharge surge current In (8/20 µs) L-N and L-PEN 20 kA
N-PE 20 kA
Max. discharge surge current Imax. (8/20 µs) L-N 40 kA
N-PE 40 kA
Function
Response time tA L-N and L-PEN ≤25 ns
L-N and N-PE ≤100 ns
Connections
Conductor cross-section Finely stranded 2.5 … 16 mm2
Solid 2.5 … 25 mm2
Protection devices
Max. back-up fuse acc. to IEC 61643-1 For stub wiring (gL/gG) 315 A
For V wiring (gL/gG) 63 A
Short-circuit strength With max. back-up fuse 25 kA
Ambient conditions
Degree of protection IP20, with connected conductors
Temperature range –40 … +80 °C
Accessories
Spare part plugs
Protection paths Basic units Article No.
N-PE 5SD7422-0, 5SD7422-1, 5SD7424-0 and 5SD7424-1 5SD7428-0
Fuse Systems
Information + ordering
All the important things at a glance Everything you need for your order
For information about fuse systems, please visit Refer to the Industry Mall for an overview of your
our website www.siemens.com/fuses products
• Fuse systems sie.ag/2kW3pnU
Direct forwarding to the individual products in the
Your product in detail
Industry Mall by clicking on the article number in the
catalog or entering this web address incl. article n
umber
The Siemens Industry Online Support (SIOS) provides www.siemens.com/product?Article No.
comprehensive information
www.siemens.com/lowvoltage/product-support
• Technology Primer Configurators
− Fuse systems (109482303)
7
The relevant tender specifications can be found at The configurator reduces the time and effort required in
www.siemens.com/lowvoltage/tenderspecifications the planning and ordering process, and allows for indivi-
dual adaptations. Configure your SITOR semiconductor
Use our conversion tool for quick and easy conversion to
fuse at
Siemens products www.siemens.com/conversion-tool
www.siemens.com/lowvoltage/sitor-configurator
Commissioning + operation
The Siemens Industry Online Support (SIOS) provides Manuals are available for downloading in Siemens
detailed technical information Industry Online Support (SIOS) at
www.siemens.com/lowvoltage/product-support www.siemens.com/lowvoltage/manuals
• Operating instructions • Configuration Manual
• Characteristic curves − Fuse systems (45314810)
• Certificates • Planning Manual
Comprehensive mobile support via the Siemens Industry − Planning with SIVACON 8PS (109478425)
Online Support app available for download from the • Installation Manual
App Store and Play Store − SENTRON circuit protection devices with communi
You will find further information at cation and measuring function (109791805)
www.siemens.com/support-app • System Manual
− SENTRON circuit protection devices with communi
Provision of 3D data (step and u3d data formats) cation and measuring function (109791806)
• Siemens Industry Mall
www.siemens.com/lowvoltage/mall
• Image database
Face-to-face or online training
www.siemens.com/lowvoltage/picturedb
Engineering data for CAD or CAE systems are available in Our training courses can be found at
the CAx Download Manager at www.siemens.com/sitrain-lowvoltage
www.siemens.com/cax
• SENTRON circuit protection devices with measuring
and communication function (WT-LVBCOM)
System overview
Fuse holders and bases
MINIZED NEOZED DIAZED Bus-mounting bases Photovoltaic
for busbars cumulative fuses
Class CC Class J
Covers Screw caps Adapter sleeves Isolating blades LV HRC signal detectors
Can be cut Terminals Touch protection End caps
Note:
You will find a detailed range of accessories with the basic units.
Fuse links
I201_20406
NEOZED DIAZED LV HRC LV HRC Cylindrical SILIZED Photovoltaic Photovoltaic
(3NA COM) fuses cumulative fuses cylindrical fuses
SITOR semiconductor fuses
(LV HRC design)
SITOR semiconductor fuses
(cylindrical fuse design) 7
UL fuse links
Class CC
Note:
You will find a detailed range of accessories with the basic units.
Fuse links
For protection and switching tasks System overview, see page 8/94, 8/126
Floor DIN rail Busbar Type Stan- Further
mounting dard information
Fuse switch disconnectors ■ ■ ■ 3NP1 IEC/UL See page 8/94 – –
■ – ■ 3NP5 IEC/UL See page 8/96 – –
– ■ ■ 5SG76 IEC See page 8/112 ■ –
– – ■ 3NJ4 IEC See page 8/100 – –
Switch disconnector with fuse ■ ■ – 3KF LV HRC IEC See page 8/126 – –
■ ■ – 3KF SITOR IEC/UL See page 8/128 – –
– – ■ 3NJ63 IEC See page 8/134 – –
– ■ ■ 5SG71 IEC See page 8/142 ■ –
I201_20406
■ ■ ■ – – – ■
■ – ■ – – – ■
– – – ■ ■ – –
– – – – – ■ – 7
– – – ■ ■ – –
3NA, 3ND 3NA COM 3NW6, 3NW8 3NE, 3NC 3NC10 3NE…, 3NW… 3NW1, 3NW2, 3NW3
See page 7/36 See page 7/50 See page 7/52 See page 7/54 See page 7/71 See page 7/79, See page 7/80
7/78
– – – – – – –
– – – – – – –
■ ■ – ■ – – –
– – – – – ■ –
– – ■ – – – ■
– – – – ■ – –
– – – – – ■ –
■ ■ – ■ – – –
■ ■ – ■ – – –
– – – – – – –
■ ■ – – – – –
■ ■ – (■) – – –
– – – ■ – – –
■ ■ – – – – –
– – – – – – –
MINIZED MINIZED fuse NEOZED fuse bases NEOZED NEOZED DIAZED fuse
switch discon- switch discon- comfort fuse bases bases
nectors with nectors bases
fuses
Basic data
Size/for fuses of size D02 D01 D01 D02 D03 D01, D02 D01, D02 NDz, DII, DIII
Approvals – – – – – –
Certifications – – – – – –
Technical specifications AC
Rated voltage Un V AC 230/400, 230/400, 400 400 400 – – 500, 690, 750
240/415 240/415
Rated insulation voltage V AC 500 690 – – – – – –
Short-circuit strength kA AC 50 50 50 50 50 50 50 50
Rated current In A 63 16 16 63 100 16/63 16/63 2 ... 100
Rated impulse withstand voltage kV AC 6 6 – – – – – –
Utilization category Acc. to VDE 0638 A AC-22 AC-22 – – – – – –
Acc. to EN 60947-3 A AC-22B, AC-22A – – – – – –
AC-23B (35A)
Technical specifications DC
Rated voltage Un V DC 65 (1P), 48 (1P), 250 250 250 – – 500, 600, 750
130 (2P) 110 (2P)
Un acc. to UL V DC – – – – – – – –
Short-circuit strength kA DC – – 8 8 8 8 8 –
Utilization category Acc. to EN 60947-3 A DC-22B – – – – – – –
IEC
Cylindrical fuse LV HRC fuse bases Photovoltaic cumulative NEOZED NEOZED DIAZED
holders fuse bases bus-mounting bus-mounting bus-mounting bases
bases for 8US bases for 8US for 8US 60 mm busbar
60 mm compact 60 mm busbar systems
busbar systems systems
Any Any Any From the busbar From the busbar From the busbar
7
IEC 60269-1, -2, -3; IEC 60269-1, -2; EN 60269-1; IEC 60269, IEC 60269-2, IEC 60269-3, IEC 60269-3, IEC 60269-3, IEC 60269-3,
NF C 60-200, DIN VDE 0636-2, UL 4248-1 IEC 60947 DIN VDE 0636-3 DIN VDE DIN VDE DIN VDE
NF C 63-210, -211; (only downstream from the 0636-3 0636-3 0636-3
NBN C 63269-2-1; branch protection)
CEI 32-4, -12; UL 4248-1
UL File number E171267 KEMA; UL file number E171267-IZLT2 – – – – – – – – – –
– – – – – – – – – – – – –
400 690 690 1) 690 1) 690 1) 690 1) 690 1) 690 – – – – – – 400 400 500 690
– – – – – – – – – – – – – – – – – –
20 100 – – – – – – – – – – – – – – – –
20 100 160 160 250 400 630 1250 160 250 400 630 250 400 63 63 25 63
– – – – – – – – – – – – – – – – – –
– – – – – – – – – – – – – – – – – –
AC-20B – – – – – – – – – – – – – – – –
(switching without load)
– – 250 440 440 440 440 440 1000 1000 1000 1000 1500 1500 250 250 – 600
– – – – – – – – – – – – – – – – – –
– – 25 25 25 25 25 25 – – – – – – 8 8 8 8
DC-20B – – – – – – DC-20B (switching without load) – – – –
(switching without load)
– – – – – – – – – – – – – – – – –
– – – – – – – – – – – – – – – – –
See page 7/24 See page 7/22 See page 7/27 See page 7/20
Certifications – u, s u, s u, s –
Technical specifications AC
Rated voltage Un V AC 690 1) 690 1) 690 1) 690 1) 690 1) 690 690 690 1500
Un acc. to UL V AC 690 690 1000 1000 1000 600 600 600 –
Un acc. to CSA V AC 600 600 600 600 600 – – – –
Rated insulation voltage V AC – – – – – – – – –
Short-circuit strength kA AC – – – – – 50 50 50 30
(100 at 400 V) (100 at 500 V)
Rated current In A 160 160 250 400 630 32 50 100 63
In acc. to UL A 160 160 250 – 500 30 50 80 –
In acc. to CSA A 160 160 250 – 850 30 40 80 –
Rated impulse withstand voltage kV AC – – – – – 6 6 6 –
Max. power dissipation of fuse links W 12 25 32 45 60 3 (6 mm²), 5 (10 mm²), 9.5 (35 mm²), 15
(conductor cross-section used) 4.3 (10 mm²) 6.5 (25 mm²) 11 (50 mm²) (1 … 50 mm²)
Pollution degree – – – – – 2 2 2 –
Further information
See page 7/22 See page 7/72
1)
Extended rated voltage up to 1000 V
2)
Types with UL approval and types with CSA approval may differ
IEC/UL UL
10 × 38 mm 14 × 51 mm 10 x 38 mm 10 x 85 mm – –
IEC 60269-1, -2, -3; IEC 60269, IEC 60269, UL 4248-1; UL 4248-1 Ed.1, UL 4248-8 Ed.1
NF C 60-200, IEC 60269-2, IEC 60269-2, CSA C22.2
NF C 63-210, -211; IEC 60947, IEC 60947, 7
NBN C 63269-2-1; UL 4248-1, -18 UL 4248-1, -18
CEI 32-4, -12; UL 4248-1
UL File number E171267 U (File number U (E355487) UL 4248-1; UL File number E171267;
E469670, CCC) UL File number E171267; CSA File number 233322;
(types without CSA C22.2 Class number 6225-01
signal detector)
U, s U – – – u, s u, s UUS
C C UUS u, s
Busbar device: CUUS
690 690 – – – – – – – –
600 700 – – 600 600 600 600 600 600
– – – – – – – – – –
– – – – – – – – – –
100 100 – – 200 200 200 200 200 200
See page 7/24 See page 7/26 See page 7/29 See page 7/28
Size In
D01 2…6A 5SG7611-0KK06 – – 5SG7631-0KK06 –
10 A 5SG7611-0KK10 – – 5SG7631-0KK10 –
16 A 5SG7611-0KK16 5SG7651-0KK16 5SG7621-0KK16 5SG7631-0KK16 5SG7661-0KK16
Note:
NEOZED adapter sleeves are not required for these devices
Accessories
7
Electronic fuse monitor
• For all low-voltage fuse systems
• For monitoring all types and versions of melting fuses that cannot be equipped with a fault signal contact
• Can be used in asymmetric systems afflicted with harmonics and regenerative feedback motors
• Signal also for disconnected loads
Ue AC In Uc Article No.
230 V 4A 3 AC 380 … 415 V 5TT3170
Size In
D02 25 A – – – 5SG7133-8BA25 1) –
35 A – – – 5SG7133-8BA35 1) –
50 A – – 5SG7133-8BA50 1) –
63 A 5SG7113 5SG7153 5SG7123 5SG7133 5SG7163
1)
Versions for Austria only, with permanently fitted adapter sleeves and incl. fuse link
Note:
NEOZED adapter sleeves are required for these devices, see page 7/16
Use fuse links from 35 A with silver-plated contact caps, see page 7/32
Accessories
7
Reducers
Use Article No.
For D01 fuse links in MINIZED switch disconnectors with fuses D02 5SH5527
5ST3 COM auxiliary switches and fault signal contacts (AS+FC) with communication and measuring function
• Wireless information about manual ON/OFF, temperature, operating cycles, operating hours, warnings
Article No.
5ST3062-0MC
For flat copper In Un Standard Without LED signal detector With LED
profiles IEC UL 508 IEC AC IEC DC UL 508 signal detector
Box terminals
5 mm and 10 mm 63 A 1) – 400 V AC – – IEC 5SG7234-1 – 5SG7234-2
63 A 2) – 400 V AC 110 V DC – IEC – 5SG7230 –
1)
In the case of permanent load over 35 A, we recommend the use of lateral module 5SH5533. Please observe EN 60439-1, Table 1.
2)
In the case of permanent load over 35 A, we recommend the use of lateral module 5SH5526. Please observe EN 60439-1, Table 1.
7
Suitable accessories
Auxiliary switches
• For signaling the switching state for bus-mounting switch disconnectors
Contacts Mounting width Article No. Article No. Article No.
1 CO 0.5 MW – 5SH5525 –
Lateral modules
• For greater heat dissipation for loads from 35 A
Mounting width Article No. Article No. Article No.
0.5 MW 5SH5533 5SH5526 5SH5533
Reducers
Use Article No. Article No. Article No.
For NEOZED D01 fuse links in bus-mounting switch disconnectors 5SH5527 5SH5527 5SH5527
Number of poles 1P 3P 1P 3P 1P 3P
Size In
D01 16 A 5SG1301 5SG5301 5SG1302 5SG5302 5SG1302-1 5SG5302-1
D02 63 A 5SG1701 5SG5701 5SG1702 5SG5702 5SG1702-1 5SG5702-1
D03 100 A – – – – – –
Accessories
NEOZED screw caps
7 Material
Molded plastic
Version
With inspection hole
Fuse size
D01
Article No.
5SH4116
D02 5SH4163
5SG1553 5SG5553 – – – –
– – 5SG1653 5SG5653 5SG1693 5SG5693
– – – – 5SG1812 –
NEOZED covers
Fuse size
D03
Article No.
5SH5233
7
Number of poles 1P 3P 1P
Size In Un AC/DC
DII 25 A 500 V/500 V 5SF1060 5SF5068 5SF1005
DIII 63 A 500 V/500 V 5SF1260 1) 5SF5268 1) –
750 V/750 V – – –
1)
Can also be used for 690 V AC/600 V DC.
7 Accessories
DIAZED screw caps
Material Version Fuse size Rated voltage AC/DC Article No.
Molded plastic With inspection hole NDz 500 V/500 V 5SH1112
DII 500 V/500 V 5SH1221
DIII 500 V/500 V 5SH1231
Ceramic Without inspection hole DII 500 V/500 V 5SH112
DIII 500 V/500 V 5SH113
– –
5SF1205 1) –
– 5SF4230
7
DIAZED reduction sleeves for screw caps
Use Article No.
For DII fuse links in DIII base 5SH302
Bus-mounting bases
For 8US busbar systems
60 mm compact 60 mm busbar systems
busbar systems
NEOZED design NEOZED design DIAZED design
Number of poles 3P 3P 3P
Size In Mounting Un AC/DC With touch protec- Standard With touch protec- Standard With touch protec-
width tion cover tion cover tion cover
D02 63 A 1.5 MW – – 5SG6202 5SG6206 – –
2 MW – 5SG6208 – 5SG6207 – –
DII 25 A – 500 V/500 V – – – 5SF6015 5SF6020
DIII 63 A – 500 V/500 V 1) – – – 5SF6215 5SF6220
1)
Can also be used for 690 V AC/ 600 V DC.
Note:
7 NEOZED adapter sleeves and DIAZED screw adapters as well as the respective screw caps are required, see page 7/16 and 7/18
Accessories
Covers for bus-mounting base standard version for 60 mm busbar systems
Design Fuse size Version Mounting width (1 MW = 18 mm) Article No.
NEOZED D02 Standard 1.5 MW 5SH5241
Extra wide 2 MW 5SH5242
Ceramic
Number of poles 1P
Size In Flat terminals Plug-in terminal Saddle-type terminal Double busbar terminal
000/00 160 A 3NH3030 3NH3031 3NH3032 –
0 1) 160 A 3NH3120 – – –
1 250 A 3NH3230 – – 3NH3220
2 400 A 3NH3330 – – 3NH3320
3 630 A 3NH3430 – – 3NH3420
4 1250 A 3NH3530 – – –
4a 1250 A – – – –
1)
No longer to be used for new installations!
7
Accessories
LV HRC protective covers for LV HRC fuse bases
• As touch protection for contact pieces
Size Article No.
000/00 3NX3105
0 3NX3114
1 3NX3106
2 3NX3107
3 3NX3108
LV HRC partitions for LV HRC fuse bases
• As intermediate phase and end barrier
Size Type Article No.
000/00 3NH30/3NH40 3NX2023
0 3NH31 3NX2030
1 3NH32 3NX2024
2 3NH33 3NX2025
3 3NH34 3NX2026
LV HRC protective covers
Size Number of poles Article No.
000/00 1P and 3P 3NX3115
Grip lug cover for plugging into the LV HRC protective cover
Size Use Article No.
000/00 When using fuse links with non-insulated grip lugs 3NX3116
7
Blanking covers for LV HRC fuse bases (instead of LV HRC fuse link)
• Red color
• With inscription "Isolating point"
• Observe width 60 mm of the blank insert when using for size 1
Size Article No.
000/00 3NX1003
1, 2, 3 3NX1004
Fuse pullers for LV HRC fuse links
Size Version Article No.
000 ... 3 Without sleeve 3NX1013
Isolating blades for LV HRC fuse bases and fuse switch disconnectors
Version Contacts Size Article No.
With insulated grip lugs Silver-plated 000/00 3NG1002
0 3NG1102
1 3NG1202
2 3NG1302
3 3NG1402
With non-insulated Tin-coated 4 3NG1503
grip lugs Nickel-plated 4a 3NG1505
For fuses of size In Standard Standard Standard Standard Compact Bus-mounting Standard
fuse holders
Without LED signal detector
8 × 32 mm 20 A 3NW7313 3NW7353 3NW7323 3NW7333 – – 3NW7363
10 × 38 mm 30 A – – – – – 3NW7431 –
32 A 3NW7013 3NW7053 3NW7023 3NW7033 3NW7033-1 – 3NW7063
14 × 51 mm 50 A 3NW7111 3NW7151 3NW7121 3NW7131 – – 3NW7161
22 × 58 mm 100 A 3NW7211 3NW7251 3NW7221 3NW7231 – – 3NW7261
7 With LED signal detector
8 × 32 mm 20 A 3NW7314 3NW7354 3NW7324 3NW7334 – – 3NW7364
10 × 38 mm 32 A 3NW7014 3NW7054 3NW7024 3NW7034 3NW7034-1 – 3NW7064
14 × 51 mm 50 A 3NW7112 3NW7152 3NW7122 3NW7132 – – 3NW7162
22 × 58 mm 100 A 3NW7212 3NW7252 3NW7222 3NW7232 – – 3NW7262
Note:
Semiconductor fuses heat up substantially more than standard fuses of operational classes gG and aM.
We therefore recommend only using SITOR cylindrical fuses in the intended SITOR fuse holders and complying with the maximum permissible current-carrying
capacity.
Accessories
Auxiliary switches for cylindrical fuse holders, standard
• For retrofitting using the factory-fitted brackets
Display Fuse link size Article No.
Disconnection of fuse link, for striker fuse links only 14 × 51 mm 3NW7901
22 × 58 mm 3NW7902
Switching state of fuse holder 8 × 32 mm and 10 × 38 mm 3NW7903
For fuses of size Un AC/DC With signaling switch
10 × 38 mm 600 V/– – – – –
690 V/800 V 3NC1091 – 3NC1092 3NC1093
14 × 51 mm 690 V/800 V 3NC1491 3NC1491-5 3NC1492 3NC1493
22 × 58 mm 690 V/800 V 3NC2291 3NC2291-5 3NC2292 3NC2293
22 × 127 mm 1500 V/1000 V 3NC2391-0MK – 3NC2392-0MK 3NC2393-0MK
Note:
Please comply with the maximum permissible current-carrying capacity.
Accessories
Fuse tongs
For fuses of size Article No.
10 × 38 mm 3NC1000
14 × 51 mm
22 × 58 mm
With flat terminals, With swiveling mecha- With swiveling mechanism and
ceramic nism microswitch for tripped signaling
Size In Un DC
1 250 A 1000 V 3NH3230 – 3NH7262-4KK01
1L 250 A 1000 V – 3NH7260-4 –
2L 400 A 1000 V – 3NH7360-4 3NH7360-4KK01
3L 630 A 1000 V/1500 V – 3NH7460-4 –
1XL 250 A 1500 V – 3NH7261-4 –
2XL 400 A 1500 V – 3NH7361-4 –
Accessories
Terminal covers for PV fuse bases with swiveling mechanism
Fuse link size Article No. 7
1, 1L, 1XL 3NX3121
2L, 2XL 3NX3122
3L 3NX3123
For mounting on DIN mounting rail For screwing Bus-mounting fuse holders
onto mounting for 8US 60 mm busbar systems
plate
Number of poles 1P 2P 3P 3P 3P 3P 3P
For fuses In Un
of size
21 × 57 mm 30 A 600 V 3NW7511-3HG 3NW7521-3HG 3NW7531-3HG – – – –
27 × 60 mm 60 A 600 V 3NW7511-5HG 3NW7521-5HG 3NW7531-5HG – – – –
28 × 118 mm 100 A 600 V – – – 3NW7531-6HG 3NW7431-6HG – –
41 × 146 mm 200 A 600 V – – – 3NW7531-7HG – 3NW7431-7HG –
54 × 181 mm 400 A 600 V – – – 3NW7531-8HG – – 3NW7431-8HG
In Un Signal detector
without with
30 A 600 V 3NW7513-0HG 3NW7523-0HG 3NW7533-0HG 3NW7533-1HG 3NW7534-1HG 3NW7431-0HG
Accessories for standard Class CC fuse holders, see Busbar systems, from page 13/1 onwards
Accessories
Auxiliary switches for cylindrical fuse holders, compact 7
In/AC-12 Un Contacts Article No.
5A Max. 250 V 1 NO + 1 NC 3NW7903-1
IEC
I201_20406
NEOZED fuse DIAZED fuse SILIZED fuse LV HRC fuse links 3NA COM
links links links LV HRC fuse
links 1)
Basic data
Design NEOZED DIAZED NEOZED, DIAZED LV HRC LV HRC
Size/for fuses of size D01, D02, D03 NDz, DII, DIII D01, D02, DII, DIII, 000/00, 0, 1, 2
DIV 2, 3, 4, 4a
Technical specifications AC
Rated voltage AC V 400 500 … 750 400 … 500 400 … 690 400
600 (CSA)
Rated breaking capacity AC kA 50 50 50 120 100
Technical specifications DC
Rated voltage DC V 250 500 … 750 250 … 500 250 … 440 –
Rated breaking capacity DC kA 8 8 8 25 –
Further information
See page 7/32 See page 7/33 See page 7/34 See page 7/36 See page 7/50
1)
With current measuring function and wireless communication
IEC IEC/UL UL
Cylindrical fuse links Photovoltaic Photovoltaic SITOR LV HRC SITOR cylindrical Class CC fuse links
cylindrical fuse links cumulative fuse links semiconductor fuse semiconductor fuse
links links
See page 7/52 See page 7/78 See page 7/79 See page 7/54 See page 7/71 See page 7/80
In Identification Un AC/DC
color
2A Pink 500 V/500 V 5SB211 – – – 5SA211
690 V/600 V – 5SD8002 – – –
750 V/750 V – – 5SD601 – –
4A Brown 500 V/500 V 5SB221 – – – 5SA221
690 V/600 V – 5SD8004 – – –
750 V/750 V – – 5SD602 – –
6A Green 500 V/500 V 5SB231 – – – 5SA231
690 V/600 V – 5SD8006 – – –
750 V/750 V – – 5SD603 – –
10 A Red 500 V/500 V 5SB251 – – – 5SA251 7
690 V/600 V – 5SD8010 – – –
750 V/750 V – – 5SD604 – –
16 A Gray 500 V/440 V 5SB2611 – – – 5SA2611
690 V/600 V – 5SD8016 – – –
750 V/750 V – – 5SD605 – –
20 A Blue 500 V/440 V 5SB2711 – – – 5SA2711
690 V/600 V – 5SD8020 – – –
750 V/750 V – – 5SD606 – –
25 A Yellow 500 V/440 V 5SB2811 – – – 5SA2811
690 V/600 V – 5SD8025 – – –
750 V/750 V – – 5SD607 – –
32 A Violet 500 V/440 V – 5SB4011 – – –
35 A Black 500 V/440 V – 5SB4111 – – –
690 V/600 V – 5SD8035 – – –
750 V/750 V – – 5SD608 – –
50 A White 500 V/440 V – 5SB4211 – – –
690 V/600 V – 5SD8050 – – –
750 V/750 V – – 5SD610 – –
63 A Copper 500 V/440 V – 5SB4311 – – –
690 V/600 V – 5SD8063 – – –
750 V/750 V – – 5SD611 – –
80 A Silver 500 V/400 V – – – 5SC211 –
100 A Red 500 V/400 V – – – 5SC221 –
1)
For 2 … 25 A use screw adaptor DII
In Un AC/DC
Insulated grip lugs
2A 500 V/250 V 3NA6802 – –
690 V 1)/250 V 3NA6802-6 – –
4A 500 V/250 V 3NA6804 – –
690 V 1)/250 V 3NA6804-6 – –
6A 500 V/250 V 3NA6801 – –
690 V 1)/250 V 3NA6801-6 – –
10 A 400 V/– 3NA6803-4 – –
500 V/250 V 3NA6803 – –
690 V 1)/250 V 3NA6803-6 – –
– – –
– – –
– – –
– – –
– – –
– – –
– – –
– – –
– – –
– – –
7
– – –
– – –
– – –
– – –
– – –
– – –
– – –
– – –
– – –
– – –
– – –
– – –
– – –
– – –
– – –
– – –
– – –
– 3NA6214 –
– – –
– – –
– – –
– – –
– 3NA6220-4 –
– – –
– – –
– 3NA6220 –
– – –
In Un AC/DC
Insulated grip lugs
63 A 400 V/– 3NA6822-4 – 3NA6122-4
500 V/250 V 3NA6822 – –
690 V 1)/250 V – 3NA6822-6 –
500 V/440 V – – 3NA6122
690 V 1)/440 V – – 3NA6122-6
80 A 400 V/– 3NA6824-4 3NA6824-4KK 3NA6124-4
500 V/250 V 3NA6824 3NA6824-7 –
690 V 1)/250 V – 3NA6824-6 –
500 V/440 V – – 3NA6124
– 3NA6222-4 –
– – –
– – –
– 3NA6222 –
– – –
– 3NA6224-4 –
– – –
– – –
– 3NA6224 –
– 3NA6224-6 –
7
– 3NA6230-4 –
– – –
– – –
– 3NA6230 –
– 3NA6230-6 –
– 3NA6232-4 –
– – –
– 3NA6232 –
– 3NA6232-6 –
– 3NA6236-4 –
– – –
– 3NA6236 –
– 3NA6236-6 –
3NA6140-4 3NA6240-4 –
3NA6140 3NA6240 –
3NA6140-6 3NA6240-6 –
3NA6142-4 3NA6242-4 –
3NA6142 3NA6242 –
– – 3NA6242-6
3NA6144-4 3NA6244-4 –
3NA6144 3NA6244 –
– – 3NA6244-6
– – 3NA6250-4
– – 3NA6250
– – 3NA6250-6
– – 3NA6252-4
– – 3NA6252
– – 3NA6252-6
– – 3NA6254-4
– – 3NA6254
– – 3NA6260-4
– – –
In Un AC/DC
Non-insulated grip lugs
2A 500 V/250 V 3NA7802 – –
690 V 1)/250 V 3NA7802-6 – –
4A 500 V/250 V 3NA7804 – –
690 V 1)/250 V 3NA7804-6 – –
6A 500 V/250 V 3NA7801 – –
690 V 1)/250 V 3NA7801-6 – –
10 A 500 V/250 V 3NA7803 – –
690 V 1)/250 V 3NA7803-6 – –
16 A 500 V/250 V 3NA7805 – –
– – –
– – –
– – –
– – –
– – –
– – –
– – –
– – –
– – –
– – –
7
– – –
– – –
– – –
– – –
– – –
– – –
– – –
– – –
– – –
– – –
– – –
– 3NA7214 –
– – –
– – –
– – –
– – –
– – –
– 3NA7220 –
– – –
– – –
– – –
– 3NA7222 –
– – –
– – –
– – –
– 3NA7224 –
– 3NA7224-6 –
– – –
– – –
– 3NA7230 –
– 3NA7230-6 –
– – –
– 3NA7232 –
– 3NA7232-6 –
In Un AC/DC
Non-insulated grip lugs
160 A 500 V/250 V – 3NA7836 –
500 V/440 V – – 3NA7136
690 V 1)/440 V – – 3NA7136-6
200 A 500 V/440 V – – –
690 V 1)/440 V – – –
224 A 500 V/440 V – – –
690 V 1)/440 V – – –
250 A 500 V/440 V – – –
690 V 1)/440 V – – –
– – –
– 3NA7236 –
– 3NA7236-6 –
3NA7140 3NA7240 –
3NA7140-6 3NA7240-6 –
3NA7142 3NA7242 –
– – 3NA7242-6
3NA7144 3NA7244 –
– – 3NA7244-6
– – 3NA7250-6
7
– – 3NA7252
– – 3NA7252-6
– – –
– – 3NA7260
In Un AC/DC
Non-insulated grip lugs
2A 500 V/250 V 3NA3802 – – – –
690 V 1)/250 V 3NA3802-6 – – – –
4A 500 V/250 V 3NA3804 – – – –
690 V 1)/250 V 3NA3804-6 – – – –
6A 500 V/250 V 3NA3801 – – – –
690 V 1)/250 V 3NA3801-6 – – – –
500 V/440 V – – 3NA3001 – –
10 A 500 V/250 V 3NA3803 – – – –
– – – – – –
– – – – – –
– – – – – –
– – – – – –
– – – – – –
– – – – – –
– – – – – –
– – – – – –
– – – – – –
7
– – – – – –
– – – – – –
– – – – – –
– – – – – –
– – – – – –
– – – – – –
– – – – – –
– – – – – –
– – – – – –
– – – – – –
– – – – – –
– – – – – –
– – – – – –
– – – – – –
– – – – – –
3NA3214 – – – – –
– – – – – –
– – – – – –
– – – – – –
– – – – – –
– – – – – –
3NA3220 – – – – –
– – – – – –
– – – – – –
– – – – – –
– – – – – –
– – – – – –
– – – – – –
– – – – – –
3NA3224 – – – – –
3NA3224-6 – – – – –
– – – – – –
– – – – – –
3NA3230 – – – – –
– – – – – –
In Un AC/DC
Non-insulated grip lugs
125 A 400 V/250 V 3NA3832-8 – – – –
500 V/250 V – 3NA3832 – – –
500 V/440 V – – 3NA3032 3NA3132 –
690 V 1)/440 V – – – 3NA3132-6 –
160 A 400 V/250 V 3NA3836-8 – – – –
500 V/250 V – 3NA3836 – – –
500 V/440 V – – 3NA3036 3NA3136 –
690 V 1)/440 V – – – 3NA3136-6 –
– – – – – –
– – – – – –
3NA3232 – – – – –
3NA3232-6 – – – – –
– – – – – –
– – – – – –
3NA3236 – – – – –
3NA3236-6 – – – – –
3NA3240 – 3NA3340 – – –
7
3NA3240-6 – – – – –
3NA3242 – 3NA3342 – – –
– 3NA3242-6 – – – –
3NA3244 – 3NA3344 – – –
– 3NA3244-6 3NA3344-6 – – –
– 3NA3250 3NA3350 – – –
– 3NA3250-6 – – – –
– 3NA3252 3NA3352 – – –
– 3NA3252-6 3NA3352-6 – – –
– 3NA3254 3NA3354 – – –
– – – 3NA3354-6 – –
– 3NA3260 3NA3360 – – –
– – – 3NA3360-6 – –
– – – 3NA3362 – –
– – – 3NA3362-6 – –
– – – 3NA3365 – 3NA3665
– – – 3NA3365-6 – –
– – – 3NA3372 3NA3472 3NA3672
– – – – 3NA3475 3NA3675
– – – – 3NA3480 3NA3680
– – – – 3NA3482 3NA3682
In Un AC
Non-insulated grip lugs
6A 500 V 3ND1801 – – – – – – –
10 A 500 V 3ND1803 – – – – – – –
16 A 500 V 3ND1805 – – – – – – –
20 A 500 V 3ND1807 – – – – – – –
25 A 500 V 3ND1810 – – – – – – –
32 A 500 V 3ND1812 – – – – – – –
35 A 500 V 3ND1814 – – – – – – –
40 A 500 V 3ND1817 – – – – – – –
50 A 500 V 3ND1820 – – – – – – –
7 63 A 500 V 3ND1822 – – – – – – –
690 V – – 3ND2122 – – – – –
80 A 500 V 3ND1824 – – – – – – –
690 V – – 3ND2124 – – – – –
100 A 500 V 3ND1830-8 3ND1830 – – – – – –
690 V – – 3ND2130 – – – – –
125 A 500 V – 3ND1832 – – – – – –
690 V – – – 3ND2132 3ND2232 – – –
160 A 500 V – 3ND1836 – – – – – –
690 V – – – 3ND2136 3ND2236 – – –
200 A 690 V – – – 3ND2140 3ND2240 – – –
250 A 690 V – – – 3ND2144 3ND2244 – – –
315 A 690 V – – – – – 3ND2252 3ND2352 –
355 A 690 V – – – – – 3ND2254 3ND2354 –
400 A 690 V – – – – – 3ND2260 3ND2360 –
500 A 690 V – – – – – – – 3ND1365
630 A 690 V – – – – – – – 3ND1372
I201_20406 I201_20406
In Un AC
80 A 400 V – 3NA3224-4KK03 – 3NA3224-4KK04
100 A 400 V 3NA3230-4KK01 3NA3230-4KK03 3NA3230-4KK02 3NA3230-4KK04
125 A 400 V 3NA3232-4KK01 3NA3232-4KK03 3NA3232-4KK02 3NA3232-4KK04
160 A 400 V 3NA3236-4KK01 3NA3236-4KK03 3NA3236-4KK02 3NA3236-4KK04
200 A 400 V 3NA3240-4KK01 3NA3240-4KK03 3NA3240-4KK02 3NA3240-4KK04
224 A 400 V 3NA3242-4KK01 – 3NA3242-4KK02 –
7 250 A 400 V 3NA3244-4KK01 3NA3244-4KK03 3NA3244-4KK02 3NA3244-4KK04
315 A 400 V 3NA3252-4KK01 – 3NA3252-4KK02 –
1)
Electronic module is mounted by simple insertion 2)
For spare part purposes (electronic module can be reused after the fuse has been replaced!)
7KN1110-0MC00
In Un AC
0.5 A 500 V – 3NW6000-1 – –
1A 500 V – 3NW6011-1 – –
2A 400 V 3NW6302-1 – – –
500 V – 3NW6002-1 – –
4A 400 V 3NW6304-1 – – –
500 V – 3NW6004-1 – –
690 V – – 3NW6104-1 –
6A 400 V 3NW6301-1 – – –
500 V – 3NW6001-1 – –
690 V – – 3NW6101-1 –
8A 500 V – 3NW6008-1 – –
7 10 A
690 V
400 V
–
3NW6303-1
–
–
3NW6108-1
–
–
–
500 V – 3NW6003-1 – –
690 V – – 3NW6103-1 –
12 A 500 V – 3NW6006-1 – –
690 V – – 3NW6106-1 –
16 A 400 V 3NW6305-1 – – –
500 V – 3NW6005-1 – –
690 V – – 3NW6105-1 3NW6205-1
20 A 400 V 3NW6307-1 – – –
500 V – 3NW6007-1 – –
690 V – – 3NW6107-1 3NW6207-1
25 A 500 V – 3NW6010-1 – –
690 V – – 3NW6110-1 3NW6210-1
32 A 400 V – 3NW6012-1 – –
690 V – – 3NW6112-1 3NW6212-1
40 A 500 V – – 3NW6117-1 –
690 V – – – 3NW6217-1
50 A 500 V – – 3NW6120-1 –
690 V – – – 3NW6220-1
63 A 500 V – – – 3NW6222-1
80 A 500 V – – – 3NW6224-1
100 A 500 V – – – 3NW6230-1
Operational class aM
Size 10 × 38 mm Size 14 × 51 mm Size 22 × 58 mm
In Un AC
0.5 A 500 V 3NW8000-1 – –
1A 500 V 3NW8011-1 – –
2A 500 V 3NW8002-1 – –
690 V – 3NW8102-1 –
4A 500 V 3NW8004-1 – –
690 V – 3NW8104-1 –
6A 500 V 3NW8001-1 – –
690 V – 3NW8101-1 –
8A 500 V 3NW8008-1 – –
690 V – 3NW8108-1 –
10 A 500 V 3NW8003-1 – –
12 A
690 V
500 V
–
3NW8006-1
3NW8103-1
–
–
–
7
690 V – 3NW8106-1 –
16 A 500 V 3NW8005-1 3NW8105-1 –
690 V – – 3NW8205-1
20 A 400 V 3NW8007-1 – –
500 V – 3NW8107-1 –
690 V – – 3NW8207-1
25 A 400 V 3NW8010-1 – –
500 V – 3NW8110-1 –
690 V – – 3NW8210-1
32 A 400 V 3NW8012-1 – –
500 V – 3NW8112-1 –
690 V – – 3NW8212-1
40 A 500 V – 3NW8117-1 –
690 V – – 3NW8217-1
50 A 400 V – 3NW8120-1 –
690 V – – 3NW8220-1
63 A 500 V – – 3NW8222-1
80 A 500 V – – 3NW8224-1
100 A 500 V – – 3NW8230-1
7
80 A 18000 A2s 8W 1.00 690 V 1) 3NE1820-0 – – – –
100 A 33000 A2s 10 W 1.00 690 V 1) – 3NE1021-0 – – –
125 A 63000 A2s 11 W 1.00 690 V 1) – 3NE1022-0 – – –
160 A 60000 A2s 24 W 1.00 690 V 1) – – 3NE1224-0 – –
200 A 100000 A2s 27 W 1.00 690 V 1) – – 3NE1225-0 – –
250 A 200000 A2s 30 W 1.00 690 V 1) – – 3NE1227-0 – –
315 A 310000 A2s 38 W 1.00 690 V 1) – – 3NE1230-0 – –
350 A 430000 A2s 42 W 1.00 690 V 1) – – – 3NE1331-0 –
400 A 590000 A2s 45 W 1.00 690 V 1) – – – 3NE1332-0 –
450 A 750000 A2s 53 W 1.00 690 V 1) – – – 3NE1333-0 –
500 A 950000 A2s 56 W 1.00 690 V 1) – – – 3NE1334-0 –
560 A 1700000 A2s 50 W 1.00 690 V 1) – – – – 3NE1435-0
630 A 2350000 A2s 55 W 1.00 690 V 1) – – – – 3NE1436-0
710 A 3400000 A2s 58 W 1.00 690 V 1) – – – – 3NE1437-0
800 A 5000000 A2s 58 W 1.00 690 V 1) – – – – 3NE1438-0
Further information
Installation in 3NH LV HRC fuse bases ■ ■ ■ ■ ■
Installation in 3NP and 3KF fuse switching devices ■ ■ ■ ■ ■
1)
For the max. DC voltage, see the Configuration Manual "Fuse systems", chapter "Configuration", "Use with direct current"
1)
For the max. DC voltage, see the Configuration Manual "Fuse systems", chapter "Configuration", "Use with direct current"
– – – – –
– – – – –
– – – – –
– – – – –
– – – – –
– – – – –
3NE4101 – – – –
– – – – – 7
– – – – –
– – – – –
3NE4102 – – – –
– – – – –
3NE4117 – – – –
– – – – –
– – – – –
– – – – –
– – – – –
– – – – –
– – – – –
– 3NE1224-2 – – –
– 3NE1225-2 – – –
– 3NE1227-2 – – –
– 3NE1230-2 – – –
– – 3NE1331-2 – –
– – 3NE1332-2 – –
– – 3NE1333-2 – –
– – 3NE1334-2 – –
– – – – 3NE1435-2
– – – – 3NE1436-2
– – – – 3NE1447-2
– – – – 3NE1437-2
– – – 3NE1437-1 –
– – – – 3NE1438-2
– – – 3NE1438-1 –
– – – – 3NE1448-2
■ ■ ■ ■ ■
■ ■ ■ ■ ■
See page 7/61 – – – –
1)
For the max. DC voltage, see the Configuration Manual "Fuse systems", chapter "Configuration", "Use with direct current" 2)
Minimum clearance 90 mm
– – – – – – –
– 3NE5302-0MK06 – – – – –
– – – – – – –
– 3NE5317-0MK06 – – – – –
– – – – – – –
– 3NE5318-0MK06 – – – – –
– – – – – – – 7
– – – 3NC8423-3C – – –
– – 3NC2423-3C – – – –
– – – – – – –
– – – 3NC8425-3C – – –
– – – – – – –
– – 3NC2425-3C – – – –
– – – 3NC8427-3C – – –
– – – – – – –
– – 3NC2427-3C – – – –
– – 3NC2428-3C – – – –
– – – – – – –
– – – 3NC8431-3C – – –
3NE1331-3 – – – – – –
– – 3NC2431-3C – – – –
3NE1332-3 – – – – – –
3NE1333-3 – – – – – –
3NE1334-3 – – – – – –
– – – 3NC8434-3C – – –
– – – – 3NE1435-3 – –
– – – – 3NE1436-3 – –
– – – – 3NE1447-3 – –
– – – – 3NE1437-3 – –
– – – – 3NE1438-3 – –
– – – – 3NE1448-3 – –
– – – – – 3NB3350-1KK26 –
– – – – – 3NB3351-1KK26 –
– – – – – 3NB3352-1KK26 –
– – – – – 3NB3354-1KK26 –
– – – – – 3NB3355-1KK26 –
– – – – – 3NB3357-1KK26 –
– – – – – – 3NB3358-1KK27
– – – – – 3NB3358-1KK26 –
– – – – – – 3NB3362-1KK27
■ ■ ■ ■ ■ ■ ■
3NH5463 3NH5473 3NH5463 3NH5463 3NH5463 – –
■ ■ ■ ■ ■ – –
■ ■ ■ ■ ■ – –
– – See page 7/62 See page 7/62 See page 7/62 – –
1)
For the max. DC voltage, see the Configuration Manual "Fuse systems", chapter "Configuration", "Use with direct current"
Size 2
M10, 110 mm M10, 170 mm M10, 190 mm M12, 260 mm
– 3NE5320-0MK06 – –
– – – –
– – – –
– 3NE5321-0MK06 – –
– – – –
– – – –
– 3NE5322-0MK06 – –
– – – –
– – – –
–
–
3NE5324-0MK06
–
–
–
–
–
7
– – – –
– 3NE5325-0MK06 – –
3NE4327-0B – – –
– – – –
– – – –
– 3NE5327-0MK06 – –
3NE4330-0B – – –
– – – –
– – – 3NE9330-0MK07
– – – –
– 3NE5330-0MK06 – –
– – – –
– – – –
– – – –
3NE3332-0B – – –
– – – –
– – – –
– 3NE5332-0MK06 – –
3NE4333-0B – – –
3NE3333 – – –
– – – –
– – – –
3NE4334-0B – – –
3NE3334-0B – – –
– – – –
– – – –
– 3NE5334-0MK06 – –
– – – –
– – – –
3NE3335 – – –
3NE3336 – – –
– – – –
– – – –
– 3NE5336-0MK06 3NE5336-0MK66 –
3NE4337 – – –
3NE3337-8 – – –
3NE3338-8 – – –
3NE3340-8 – – –
■ ■ ■ ■
3NH5463 3NH5473 3NH5473 –
■ – – –
■ – – –
– See page 7/50 – –
– – – – –
– – – – 3NE9622-1C
– – – – –
– – – – –
– – – – –
– – – – –
– – – – –
– – – – –
– – – – –
– 3NC3430-1U – – –
– – – – –
– – – – – 7
– – – – –
– – – – –
– – – – –
– 3NC3432-1U – – –
– – – – 3NE9632-1C
– – – – –
– – – – –
– – – – –
– – – 3NE5433-1C –
– – – 3NE7633-1U –
– – – – –
– 3NC3434-1U – – –
– – – – 3NE9634-1C
– – – 3NE7648-1U –
– – – – –
3NC3236-1U – – – –
– 3NC3336-1U – – –
– – – – –
– 3NC3436-1U – – –
– – – 3NE7636-1U –
– – – – 3NE9636-1C
3NC3237-1U – – – –
– 3NC3337-1U – – –
– – 3NE3637-1C – –
– – – 3NE7637-1U –
3NC3238-1U – – – –
– 3NC3338-1U – – –
– 3NC3438-1U – – –
3NC3240-1U – – – –
– 3NC3340-1U – – –
– – – – –
3NC3241-1U – – – –
– 3NC3341-1U – – –
3NC3242-1U – – – –
– 3NC3342-1U – – –
3NC3243-1U – – – –
– 3NC3343-1U – – –
3NC3244-1U – – – –
3NC3245-1U – – – –
■ ■ ■ ■ ■
– 3NH5463 – – –
– ■ – – –
– ■ – – –
– – – – –
1)
For the max. DC voltage, see the Configuration Manual "Fuse systems", chapter "Configuration", "Use with direct current"
M12, 73 mm M12, 73 mm
– 3NC3430-6U
– 3NC3432-6U
– –
– 3NC3434-6U
– –
3NC3336-6U –
– 3NC3436-6U
– –
7
3NC3337-6U –
– –
3NC3338-6U –
– 3NC3438-6U
– –
3NC3340-6U –
– –
3NC3341-6U –
– –
3NC3342-6U –
– –
3NC3343-6U –
– –
– –
■ ■
– – – 3NE4121-5
– – – 3NE4146-5
– – 3NE3525-5 –
3NC7327-2 – – –
– 3NE4327-6B – –
– 3NE4330-6B – –
3NC7331-2 – – –
– – – –
3NC7331-2 – – –
– 3NE4333-6B – –
– – 3NE3535-5 –
– 3NE4334-6B – –
– – – –
– – – –
– 3NE4337-6 – –
– – – –
– – – –
– – – –
– – – –
■ ■ ■ ■
1)
I2t at UVSI 1400 V is 240000 A2s
2)
I2t at Un 1250 V is reduced by the factor k = 0.79.
– –
– –
– –
3NC1810-0MK –
– –
– –
– –
– – 7
3NC1816-0MK –
– –
3NC1820-0MK –
– –
– –
– 3NC2625-0MK
– –
3NC1825-0MK –
– –
– –
– 3NC2632-0MK
3NC1832-0MK –
– –
– –
– 3NC2640-0MK
– –
3NC1840-0MK –
– –
– –
– –
– 3NC2650-0MK
3NC1850-0MK –
– –
– 3NC2663-0MK
– –
– –
– –
■ ■
– –
3NH5723 3NH5023
– –
– –
– – – –
– – – –
– – – –
– – – –
– – – –
– – – –
– – – –
– – – –
– – – –
– – – –
– – – –
– – – –
– – – – 7
– – – –
– – – –
– – – –
– – – –
– – – –
3NC2220 – – –
– – – –
– 3NC2220-5 – –
– – – –
3NC2225 – – –
– – – –
– 3NC2225-5 – –
– – – –
– – – –
– – – –
3NC2232 – – –
– – – –
– 3NC2232-5 – –
– – – –
3NC2240 – – –
– – – –
– 3NC2240-5 – –
– – – ■
3NC229. 3NC229.-5 3NC23 –
– – – 3NH5023
– – See page 7/72 –
– – See page 7/71 –
3NC2250 – – –
– 3NC2250-5 – –
– – – –
– – 3NC2350-0MK –
– – – –
3NC2263 – – –
– 3NC2263-5 – –
– – – 3NC2680-0MK
3NC2280 – – –
– 3NC2280-5 – –
– – – 3NC2600-0MK
3NC2200 – – – 7
– 3NC2200-5 – –
– – – 3NC2611-0MK
3NC2211-0MK – – –
– – – ■
3NC229. 3NC229.-5 3NC23 –
– – – 3NH5023
– – See page 7/72 –
– – See page 7/71 –
7 16 A
3.3 W
3.2 W
1.4 W
1.3 W
1500 V
1000 V
–
3NW6005-4
3NW6606-4
–
3.7 W 1.6 W 1500 V – 3NW6605-4
20 A 3.4 W 1.4 W 1000 V 3NW6007-4 –
4.0 W 1.7 W 1200 V – 3NW6607-4
Further information
Installation in fuse holders 3NW70..-4 3NW76..-4
1)
Tested in fuse holders 3NW7013-4 and 3NW7613-4.
In DC Power loss Un DC
Pv
63 A 19 W 1000 V 3NE1218-4 – – – – –
20 W 1500 V – – – – 3NE1218-5E –
80 A 20 W 1000 V 3NE1220-4 – – – – –
25 W 1500 V – – – – 3NE1220-5E –
100 A 24 W 1000 V 3NE1221-4 – – – – –
30 W 1500 V – – – – 3NE1221-5E –
125 A 26 W 1000 V 3NE1222-4 – – – – –
29 W 1500 V – – – – 3NE1222-5E –
160 A 32 W 1000 V 3NE1224-4 – – – – –
34 W 1500 V – – – – 3NE1224-5E –
200 A 41 W 1500 V – – – – 3NE1225-5E –
51 W 1000 V – 3NE1225-4D – – – – 7
250 A 53 W 1500 V – – – – – 3NE1327-5E
54 W 1000 V – 3NE1227-4D – – – –
315 A 63 W 1500 V – – – – – 3NE1330-5E
73 W 1000 V – – 3NE1330-4D – – –
400 A 82 W 1000 V – – 3NE1332-4D – – –
500 A 100 W 1000 V – – – 3NE1434-4E – –
630 A 110 W 1000 V – – – 3NE1436-4E – –
In In 1)
0.6 A 6/10 A 3NW1006-0HG – –
0.8 A 8/10 A 3NW1008-0HG – –
1A – 3NW1010-0HG 3NW3010-0HG 3NW2010-0HG
1.5 A 1.5 A 3NW1015-0HG – –
2A – 3NW1020-0HG 3NW3020-0HG 3NW2020-0HG
2.5 A – 3NW1025-0HG – –
3A – 3NW1030-0HG 3NW3030-0HG 3NW2030-0HG
4A – 3NW1040-0HG 3NW3040-0HG 3NW2040-0HG
5A – 3NW1050-0HG 3NW3050-0HG 3NW2050-0HG
6A – 3NW1060-0HG 3NW3060-0HG 3NW2060-0HG
7.5 A – 3NW1075-0HG – –
7 8A – 3NW1080-0HG 3NW3080-0HG 3NW2080-0HG
10 A – 3NW1100-0HG 3NW3100-0HG 3NW2100-0HG
12 A – – 3NW3120-0HG 3NW2120-0HG
15 A – 3NW1150-0HG 3NW3150-0HG 3NW2150-0HG
20 A – 3NW1200-0HG 3NW3200-0HG 3NW2200-0HG
25 A – 3NW1250-0HG 3NW3250-0HG 3NW2250-0HG
30 A – 3NW1300-0HG 3NW3300-0HG 3NW2300-0HG
Further information
Installation in fuse holders 3NW75.3-0HG, 3NW753.-1HG, 3NW75.3-0HG, 3NW753.-1HG, 3NW75.3-0HG, 3NW753.-1HG,
3NW7431-0HG 3NW7431-0HG 3NW7431-0HG
1)
American English wording
Busbars
According to IEC, can be cut
Pin spacing 1 MW
Pin spacing in MW Application Length Version Conductor
(1 MW = 18 mm) cross-section
1-phase, angled Article No.
1 For cylindrical fuse holders 8 × 32 mm and 10 × 38 mm 214 mm With end caps 16 mm2 5ST3700
For SITOR cylindrical fuse holders 10 × 38 mm 1016 mm Without end caps 16 mm2 5ST3701
I201_20423
L1 L1
L1 L2
L1 L2 L3
7
Fork spacing 1 MW
Fork spacing in MW Application Length Version Conductor
(1 MW = 18 mm) cross-section
1-phase Article No.
1 For MINIZED D01 fuse switch disconnectors 1000 mm Without end caps 16 mm2 5ST2190
1 1
I201_20183
L1 L1
10
L1 L1 L1
5,6
L1 L2 L1
L1 L2 L3
5SG1302, 5SG1702
For NEOZED D01/D02 fuse bases made of ceramic with saddle terminals
L1 L1 For cylindrical fuse holders 14 × 51 mm, 3NW7111
For SITOR cylindrical fuse holders 14 × 51 mm, 3NC1491
5SG5302, 5SG5702
L1 L2 L3 For NEOZED D01/D02 fuse bases made of ceramic with saddle terminals
For cylindrical fuse holders 14 × 51 mm, 3NW7131
For SITOR cylindrical fuse holders 14 × 51 mm, 3NC1493 7
L1 L2 L3
Busbars
According to UL 508, can be cut
Pin spacing 1 MW
Pin spacing in MW Application Length Version Conductor
(1 MW = 18 mm) cross-section
1-phase Article No.
1 For Class CC fuse holders 10 × 38 mm (3NC1091, 3NW7513-0HG) 1000 mm Without end caps 18 mm2 5ST3701-0HG
I201_20423
L1 L1
2-phase Article No.
1 For Class CC fuse holders 10 × 38 mm (3NC1092, 3NW7523-0HG) 1000 mm Without end caps 18 mm2 5ST3705-0HG
I201_20420
L1 L2
L1 L2 L3
L1 L1
2-phase
1,5 For fuse holders 14 × 51 mm (3NC1492, 3NW7121) 1000 mm Without end caps 25 mm2 5ST3705-2HG
I201_20434
L1 L2
L1 L2 L3
Busbars
Accessories
For busbars according to IEC
Terminals
• For NEOZED D01/D02 fuse bases made of ceramic
• For DIAZED DII/DIII fuse bases made of ceramic
Terminal version Conductor cross-section Article No.
Terminal version S 2 … 25 mm2 5SH5327
Touch protection
• For free connections, yellow (RAL 1004) 5 × 1 pin
Article No.
5ST3655
End caps
7 Version For busbar type Article No.
For 1-phase busbars 5ST2190 5ST2196
5ST37 and 5SH55 5ST3748
End-to-end safety
for user and systems
Switch Disconnectors
Information + ordering
All the important things at a glance Everything you need for your order
For information about switch disconnectors, Refer to the Industry Mall for an overview of your
please visit our website products
www.siemens.com/switching-devices
• Switch disconnectors sie.ag/36HDiZp
Direct forwarding to the individual products in the
Industry Mall by clicking on the article number in the
Your product in detail catalog or entering this web address incl. article number
www.siemens.com/product?Article No.
The Siemens Industry Online Support (SIOS) provides
comprehensive information You will find order support for the electrical wholesale
www.siemens.com/lowvoltage/product-support trade carrying fast-selling items in the Siemens Industry
Online Support (SIOS) at
• Technical Basic Information
www.siemens.com/lowvoltage/product-support
− Switch disconnectors and transfer switching
equipment (109763354) • Order Support
8 The relevant tender specifications can be found at − 3KD switch disconnectors – End-to-end safety
www.siemens.com/lowvoltage/tenderspecifications for user and systems (109750228)
− 3LD2 main control and EMERGENCY-STOP-switching
Use our conversion tool for quick and easy conversion to equipment – End-to-end safety for user and systems
Siemens products www.siemens.com/conversion-tool
(109755626)
− 3NP1 fuse switch disconnectors – End-to-end safety
for user and systems (109755624)
Configurators − 3KF switch disconnectors with fuses – End-to-end
safety for user and systems (109750229)
The configurator reduces the time and effort required − 3NJ63 switch disconnectors with fuses – End-to-end
in the planning and ordering process, and allows for safety for user and systems (109755619)
individual adaptations.
Configure your switch disconnector at
www.siemens.com/lowvoltage/3nj63-configurator
www.siemens.com/lowvoltage/3ld-configurator
www.siemens.com/lowvoltage/3kd-configurator,
your switch disconnector with fuses at
www.siemens.com/lowvoltage/3kf-configurator
and your 3NP1 fuse switch disconnector at
www.siemens.com/lowvoltage/3np1-configurator
Choose the right SITOR semiconductor fuse for
your application
www.siemens.com/lowvoltage/sitor-configurator
Commissioning + operation
The Siemens Industry Online Support (SIOS) provides Manuals are available for downloading in Siemens
detailed technical information Industry Online Support (SIOS) at
www.siemens.com/lowvoltage/product-support www.siemens.com/lowvoltage/manuals
• Operating instructions • Configuration Manual
• Certificates − Switch disconnectors (109769744)
− Fuse systems (45314810)
Comprehensive mobile support via the Siemens Industry
− Transfer switching equipment and load transfer
Online Support app available for download from the
App Store and Play Store switches (109769745)
You will find further information at − 8US busbar systems (109769746)
www.siemens.com/support-app • System Manual
− SENTRON 3NJ62 in-line plug-in switch disconnectors
Provision of 3D data (step and u3d data formats) with fuses (31753460)
• Siemens Industry Mall − SENTRON 3NP1 fuse switch disconnector (33515690)
www.siemens.com/lowvoltage/mall • Equipment Manual
• Image database − 3KD switch disconnector (109758120)
www.siemens.com/lowvoltage/picturedb
Engineering data for CAD or CAE systems are available in
the CAx Download Manager at
www.siemens.com/cax
Functional switching 1)
Suitable fuses
– – – – –
mounting Mounting on a ■ ■ ■ ■ ■
DIN rail (up to 125 A) (up to 63 A) (up to 250 A) (up to 160 A)
Front mounting ■ ■ ■ – –
Mounting on busbar – – – – ■
systems
(spacing of the busbars)
Draw-out technology – – – – ■
Number of 1-pole – – – – –
poles 2-pole – – – – –
3-pole ■ ■ ■ ■ ■
4-pole ■ ■ ■ ■ ■
6-pole – ■ – ■ –
Functional Occasional
Occasional switching 2) switching 1) switching 2)
IEC LV HRC,
optimized for
IEC NH IEC NH IEC NH NEOZED IEC NH IEC NH NEOZED
semiconductor
protection
■ ■ – – ■ ■ – –
■ – – ■ ■ ■ – –
– – – – – – – –
40/60 mm 40/60 mm 60/100/185 mm – – – 185 mm 60 mm
– – – – – – ■ –
■ ■ ■ ■ ■ ■ ■ ■
– – – – ■ ■ – –
– – – – – – ■ –
■ – – ■ – – – ■
■ – – ■ – – ■ ■
■ ■ ■ ■ ■ ■ ■ ■
■ – – ■ ■ ■ ■ ■
– – – – – – – –
■ ■ ■ ■ ■ ■ ■ ■
– – ■ – – – – –
3LD3 3LD2
8
At AC-21A | AC-21B at 690 V A 16 25 32 40 63 16 25 32
At AC-22A | AC-22B at 400 V A 16 20 22 36 43 16 25 32
At AC-22A | AC-22B at 690 V A 9 11 13 17 22 16 25 32
At AC-22A | AC-22B at 1000 V A – – – – – – – –
At AC-23A | AC-23B at 400 V A 16 20 22 36 43 16 20 22
At AC-23A | AC-23B at 690 V A 9 11 13 17 22 9 11 13
At DC-20A | DC-20B at 1000 V A – – – – – – – –
At DC-21A | DC-21B at 110 V A – – – – – – – –
At DC-21A | DC-21B at 220 V A – – – – – – – –
At DC-21A | DC-21B at 440 V A – – – – – – – –
At DC-22A | DC-22B at 220 V A – – – – – – – –
At DC-22A | DC-22B at 440 V A – – – – – – – –
At DC-23A | DC-23B at 220 V A – – – – – – – –
At DC-23A | DC-23B at 440 V A – – – – – – – –
Motor switching capacity At AC-23A | AC-23B at 400 V kW 7.5 9.5 11.5 18.5 22 7.5 9.5 11.5
At AC-23A | AC-23B at 690 V kW 7.5 9 11.5 15 18.5 7.5 9.5 11.5
At AC-3 | at 400 V kW 5.5 7.5 9.5 11.5 18.5 5.5 7.5 9.5
At AC-3 | at 690 V kW 5.5 7.5 9.5 11.5 15 5.5 7.5 9.5
Rated short-time withstand current At 690 V AC (t = 1 s) kA 0.5 0.5 0.5 1 1 0.34 0.64 0.64
Icw At 1000 V AC (t=1 s) kA – – – – – – – –
Rated conditional short-circuit At 400/415 V AC kA 10 10 10 10 10 50 50 50
current with upstream fuse At 690 V AC kA 6 6 6 6 6 50 50 50
Degree of protection
Maximum achievable IP degree of protection IP65 IP65
(with a rotary operating mechanism)
General technical specifications acc. to UL
General technical specifications
Certification according to UL standard UL 508 UL 508
In acc. to UL 508/UL60947-4-1 | UL489 A 16 | – 25 | – 32 | – 40 | – 63 | – 16 | – 25 | – 32 | –
Ue acc. to UL 508/UL60947-4-1 | UL489 V AC 600 | – 600 | –
Operating and short-circuit behavior
Operational power, 3-phase At 480 V hp 7.5 10 20 20 25 7.5 10 20
At 600 V hp 10 15 20 20 30 10 15 20
Short circuit current rating (SCCR) At 480 V | at 600 V kA 5 | 5 5 | 5 5 | 5 5 | 5
Upstream fuse according to UL RK5 RK5
Further information
See page 8/12 See page 8/22
3LD2 3LD5 UL
3LD25 3LD27 3LD28 3LD23 3LD24 3LD50 3LD52 3LD54 3LD56 3LD58
– –
– –
– – – – – – – – – –
63 100 125 160 250 32 63 100 125 160
8
63 100 125 160 250 32 63 100 125 160
63 100 125 140 230 32 63 100 125 160
63 100 125 140 230 32 63 100 125 160
– – – – – – – – – –
43 70 80 132 224 32 63 100 125 160
22 34 39 47 58 22 39 39 47 58
– – – – – – – – – –
– – – – – – – – – –
– – – – – – – – – –
– – – – – – – – – –
– – – – – – – – – –
– – – – – – – – – –
– – – – – – – – – –
– – – – – – – – – –
22 37 45 75 132 15 30 45 55 75
18.5 30 37 45 55 18.5 37 37 45 55
18.5 30 37 50 110 15 30 45 55 75
15 22 30 37 45 – – 30 37 45
1.26 2 2 4 4 1.26 2 4 4 4
– – – – – – – – – –
50 50 25 50 50 50 50 50 50 50
50 50 25 50 50 50 50 50 50 30
IP65 IP65
UL 508 UL60947-4-1/UL489
63 | – 100 | – 125 | – 160 | – 250 | – 30 | 30 60 | 60 100 | 100 125 | 125 150 | 150
600 | – 480 | 480
40 60 75 75 100 20 30 60 75 100
50 75 100 50 75 – – – – –
5 | 5 10 | 10 10 | 10 10 | 10 10 | 10 50 | – 65 | – 65 | – 65 | – 50 | –
RK5 J | CC J J J J
3KD
Type 3KD 3KD 3KD 3KD 3KD 3KD 3KD 3KD 3KD 3KD 3KD
01..–.K 02..–.K 03..–.K 03..–.L 04..–.L 05..–.L 06..–.L 16 22 26 28‥–M.
General technical specifications acc. to IEC 60947-3
General technical specifications
Rated uninterrupted current Iu A 16 32 63 63 80 100 125 16 32 63 80
Rated operational voltage Ue At 50/60 Hz AC V 690 690 415 690 690 690 690 1000 1000 1000 1000
At DC – 2 conducting paths V – – – – – – – 220 220 220 220
in series
At DC – 3 conducting paths V – – – – – – – 440 440 440 440
in series
At DC – 4 conducting paths V – – – – – – – – – – –
in series
Operating and short-circuit behavior
Rated operational current Ie 1) At AC-20A | AC-20B at 1000 V A – – – – – – – 16 32 63 80
At AC-21A | AC-21B at 400 V A 16 32 63 63 80 100 125 16 32 63 80
8 At AC-21A | AC-21B at 690 V A 16 32 – 63 80 100 125 16 32 63 80
At AC-22A | AC-22B at 400 V A 16 32 63 63 80 100 125 16 32 63 80
At AC-22A | AC-22B at 690 V A 16 32 – 63 80 100 125 16 32 63 80
At AC-22A | AC-22B at 1000 V A – – – – – – – 16 32 63 80
At AC-23A | AC-23B at 400 V A 16 32 63 63 75 80 90 16 32 63 80
At AC-23A | AC-23B at 690 V A 14 17 – 22 30 35 39 16 32 63 80
At DC-20A | DC-20B at 1000 V A – – – – – – – 16 32 63 80
At DC-21A | DC-21B at 110 V A – – – – – – – 16 32 63 80
At DC-21A | DC-21B at 220 V A – – – – – – – 16 32 63 80
At DC-21A | DC-21B at 440 V A – – – – – – – 16 32 63 80
At DC-22A | DC-22B at 220 V A – – – – – – – 16 32 63 80
At DC-22A | DC-22B at 440 V A – – – – – – – 16 32 63 80
At DC-23A | DC-23B at 220 V A – – – – – – – 16 32 63 80
At DC-23A | DC-23B at 440 V A – – – – – – – 16 32 63 80
Motor switching capacity At AC-23A | AC-23B at 400 V kW 7.5 15 30 30 37 45 45 7.5 15 30 45
At AC-23A | AC-23B at 690 V kW 11 15 – 18.5 22 30 30 11 30 55 75
At AC-3 | at 400 V kW – – – – – – – – – – –
At AC-3 | at 690 V kW – – – – – – – – – – –
Rated short-time withstand current At 690 V AC (t = 1 s) kA 1.26 1.26 1.26 1) 2.5 2.5 2.5 2.5 3 3 3 3
Icw At 1000 V AC (t=1 s) kA – – – – – – – 3 3 3 3
Rated conditional short-circuit At 400/415 V AC kA 50 50 50 50 50 50 50 100 100 100 100
current with upstream fuse At 690 V AC kA 50 50 – 50 50 50 20 100 100 100 100
Degree of protection
Maximum achievable IP degree of protection IP65
(with a rotary operating mechanism)
General technical specifications acc. to UL
General technical specifications
Certification according to UL standard –
In acc. to UL 508/UL60947-4-1 | UL489 A –
Ue acc. to UL 508/UL60947-4-1 | UL489 AC V –
Operating and short-circuit behavior
Operational power, 3-phase At 480 V hp –
At 600 V hp –
Short circuit current rating (SCCR) At 480 V | at 600 V kA –
Fuse type –
Further information
See page 8/64
1)
Applies to 415 V AC
3KD
3KD 3KD 3KD 3KD 3KD 3KD 3KD 3KD 3KD 3KD 3KD 3KD 3KD 3KD 3KD 3KD 3KD 3KD 3KD 3KD
28‥–N 30‥–M. 30‥–N. 32 34 36..–.N 36..–.P 38..–N. 38..–P. 40 42 44..–P. 44..–Q. 46 48 50..–Q. 50..–R. 52 54 56
80 100 100 125 160 200 200 250 250 315 400 500 500 630 800 1000 1000 1250 1600 2000
1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
220 220 220 220 220 220 220 220 220 220 220 220 220 220 220 220 220 220 220 220
440 440 440 440 440 440 440 440 440 440 440 440 440 440 440 440 440 440 440 440
– – – – – – – – – – – – – – – – – – – –
80 100 100 125 160 200 200 250 250 315 400 500 500 630 800 1000 1000 1250 1600 2000
80 100 100 125 160 200 200 250 250 315 400 500 500 630 800 1000 1000 1250 1600 2000
80 100 100 125 160 200 200 200 250 315 400 400 500 630 800 1000 1000 1250 1600 2000 8
80 100 100 125 160 200 200 250 250 315 400 500 500 630 800 1000 1000 1250 1600 2000
80 100 100 125 160 160 200 200 250 315 400 400 500 630 800 1000 1000 1250 1600 2000
80 80 100 125 160 160 200 200 250 315 400 400 500 630 800 800 1000 1250 1600 1600
80 80 100 125 160 160 200 160 250 315 400 400 500 630 800 1000 1000 1250 1600 2000
80 80 100 125 160 160 200 160 250 315 400 400 500 630 800 1000 1000 1250 1600 2000
80 100 100 125 160 200 200 250 250 315 400 500 500 630 800 1000 1000 1250 1600 2000
80 80 100 125 160 160 200 160 250 315 400 400 500 630 800 800 1000 1250 1600 1600
80 80 100 125 160 160 200 160 250 315 400 400 500 630 800 800 1000 1250 1600 1600
80 80 100 125 160 160 200 160 250 315 400 400 500 630 800 800 1000 1250 1600 1600
80 80 100 125 160 160 200 160 250 315 400 400 500 630 800 800 – – – –
80 80 100 125 160 160 200 160 250 315 400 400 500 630 800 800 – – – –
80 80 100 125 160 160 200 160 250 315 400 400 500 630 800 800 – – – –
80 80 100 125 160 160 200 160 250 315 400 400 500 630 800 800 – – – –
45 45 55 55 90 90 110 90 132 160 200 200 250 355 400 560 560 710 900 1000
75 75 90 110 110 110 185 110 250 315 315 315 500 630 800 1000 1000 1000 1000 1000
– – – – – – – – – – – – – – – – – – – –
– – – – – – – – – – – – – – – – – – – –
4 3 4 4 4 4 13 4 13 13 13 13 30 30 30 30 55 55 55 55
4 3 4 4 4 4 13 4 13 13 13 13 30 30 30 30 55 55 55 55
100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 80 80 80
80 100 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 100 100 65
IP65
–
–
–
–
–
–
–
3KD
Type 3KD 3KD 3KD 3KD 3KD 3KD 3KD 3KD 3KD
16 22 26 28 30 32 34 36 38
General technical specifications acc. to IEC 60947-3
General technical specifications
Rated uninterrupted current Iu A 16 32 63 80 100 125 160 200 250
Rated operational voltage Ue At DC - V 1200 1200 1200 1200 1200 1200 1200 1200 1200
at degree of pollution 2
At DC - V 1000 1000 1000 10001) 10001) 10001) 10001) 1200 1200
at degree of pollution 3
Operating and short-circuit behavior
Rated operational current Ie At DC-21A at 1200 V A 16 32 63 80 100 125 160 – –
At DC-21B at 1200 V A 16 32 63 80 100 125 160 200 250
Rated short-time withstand current At DC 1200 V (t = 1 s) kA 3 3 3 4 4 4 4 10 10
Icw
Degree of protection
8 Maximum achievable IP degree of protection IP20
(with a rotary operating mechanism)
General technical specifications acc. to UL
General technical specifications
Certification according to UL standard –
In acc. to UL 508/UL60947-4-1 | UL489 A –
Ue acc. to UL 508/UL60947-4-1 | UL489 AC V –
Operating and short-circuit behavior
Operational power, 3-phase At 480 V hp –
At 600 V hp –
Short circuit current rating (SCCR) At 480 V | at 600 V kA –
Fuse type –
Further information
See page 8/64
1)
Valid for version with box terminal, version with flat terminal max. 1200 V
3KD
– – – – – – – –
315 400 500 630 800 800 1250 1600
10 10 20 20 20 20 20 20
IP20 8
–
–
–
–
–
–
–
3P knob-operated 3P basic switches without 3P + N knob-operated 3P + N basic switches without
mechanisms knob-operated mechanism mechanisms knob-operated mechanism
Operating mechanisms
Rotary operating mechanisms for Knob-operated mechanisms for Door-coupling rotary Door-coupling knob-
front or floor mounting (center hole) front or floor mounting (center hole) operating mechanisms operated mechanisms
Further accessories
4 4 4 4 4 4 4
optional optional
3-pole
2 1 or 1 or 2 or 3 3 or 2 or 1 or 1
1 22
and and
4 4 4 4 4 4 4
optional and
5 or 6 or 7 or 8
Legend
1 N switching contact 1) 4 Terminal cover 7 Door-coupling rotary operating mechanism,
center-hole mounting
2 N/PE terminal 5 Rotary operating mechanism, center-hole mounting
3 Auxiliary switch 6 Knob-operated mechanism, center-hole mounting 8 Door-coupling knob-operated mechanism,
I201_20482
center-hole mounting
1)
N switching contact 1 must first be installed on the basic unit 8
The switches for front mounting are mounted on the inside of covers, The switches for floor mounting are snapped onto 35 mm DIN rails
side panels or, if applicable, control cabinet doors (depending on the according to EN 60715 or screw-mounted on mounting panels. The
applicable standard and switching function). The switches are mounted actuators are connected to the lower section of the switch through a
via the 22.5 mm diameter center hole. door coupling, which can be released in the 0 position,
and a 300 mm long switch shaft. When the control cabinet door is open,
the switch can be protected against inadvertent operation by removing
the switch shaft from the lower section of the switch. The overall depth
can be adapted to individual requirements by adjusting the switch shaft
length.
The switches for distribution board mounting are suited for operation For the basic switch variant without knob-operated mechanism,
in distribution boards and for switching inside control cabinets or the appropriate door-coupling rotary operating mechanism can be
distributors. They have cap and mounting dimensions acc. to DIN 43880 ordered separately.
and can be fitted under the same cover together with miniature circuit
breakers. The selector switches can be locked in their OFF position
with no more than one padlock with a shackle thickness of 4 to 6 mm.
Operating mechanisms, black
Number of poles 3P
I201_20448
I201_20450
Uninterrupted current Iu Operational power P Operational power P Without 1 NO + 1 NC
At AC-21A, 380 … 440 V At AC-23A, 380 … 440 V At AC-3, 380 … 440 V auxiliary switch
Rotary operating mechanisms
16 A 7.5 kW 5.5 kW 3LD3054-0TK51 3LD3054-1TK51
25 A 9 kW 7.5 kW 3LD3154-0TK51 3LD3154-1TK51
32 A 11.5 kW 9.5 kW 3LD3254-0TK51 3LD3254-1TK51
40 A 18.5 kW 11.5 kW 3LD3354-0TK51 3LD3354-1TK51
63 A 22 kW 18.5 kW 3LD3454-0TK51 3LD3454-1TK51
Knob-operated mechanisms
Scope of supply:
• Including terminal covers for the infeed side
Knob-operated mechanisms
Version Color Article No.
Lockable in 0 position with Black 3LD9343-6C ■ ■ ■ ■ ■
max. 2 padlocks Red/yellow 3LD9343-7C ■ ■ ■ ■ ■
Operating mechanisms, red/yellow
3P+N 3P 3P+N
I201_20448
I201_20450
I201_20451
I201_20451
I201_20453
I201_20453
Without 1 NO + 1 NC Without 1 NO + 1 NC Without 1 NO + 1 NC
auxiliary switch auxiliary switch auxiliary switch
Inscription labels
• Pack of 10 units
Inscription Article No.
German/English (Hauptschalter/Main Switch) 3LD9346-1A ■ ■ ■ ■ ■
French/Spanish (Interrupteur Principal/Interruptor Principal) 3LD9346-2A ■ ■ ■ ■ ■
Without inscription 3LD9346-3A ■ ■ ■ ■ ■
Operating mechanisms, black
Number of poles 3P
I201_20448
I201_20450
Uninterrupted current Iu Operational power P Operational power P Without 1 NO + 1 NC
At AC-21A, 380 … 440 V At AC-23A, 380 … 440 V At AC-3, 380 … 440 V auxiliary switch
Rotary operating mechanisms
16 A 7.5 kW 5.5 kW 3LD3048-0TK51 3LD3048-1TK51
25 A 9 kW 7.5 kW 3LD3148-0TK51 3LD3148-1TK51
32 A 11.5 kW 9.5 kW 3LD3248-0TK51 3LD3248-1TK51
40 A 18.5 kW 11.5 kW 3LD3348-0TK51 3LD3348-1TK51
63 A 22 kW 18.5 kW 3LD3448-0TK51 3LD3448-1TK51
Knob-operated mechanisms
Scope of supply:
• Including terminal covers for the infeed side
Mounting:
• Using screws- or snap-on mounting on 35 mm mounting rails
Knob-operated mechanisms
Version Color Article No.
• Lockable in 0 position with Black 3LD9343-4C ■ ■ ■ ■ ■
max. 2 padlocks Red/yellow 3LD9343-5C ■ ■ ■ ■ ■
• Incl. funnel
Switch shafts
Cross-section Length Article No.
6 × 6 mm 600 mm 3LD9345-1C ■ ■ ■ ■ ■
Operating mechanisms, red/yellow
3P+N 3P 3P+N
I201_20448
I201_20450
I201_20451
I201_20451
I201_20453
I201_20453
Without 1 NO + 1 NC Without 1 NO + 1 NC Without 1 NO + 1 NC
auxiliary switch auxiliary switch auxiliary switch
Terminal covers
• Pack of 4 units
Version Article No.
For N switching contacts, N terminals or PE terminals 3LD9341-2A ■ ■ ■ ■ ■
Inscription labels
• Pack of 10 units
Inscription Article No.
German/English (Hauptschalter/Main Switch) 3LD9346-1A ■ ■ ■ ■ ■
French/Spanish (Interrupteur Principal/Interruptor Principal) 3LD9346-2A ■ ■ ■ ■ ■
Without inscription 3LD9346-3A ■ ■ ■ ■ ■
Operating mechanisms, black
Number of poles 3P
I201_20448
I201_20450
Uninterrupted current Iu Operational power P Operational power P Without 1 NO + 1 NC
At AC-21A, 380 … 440 V At AC-23A, 380 … 440 V At AC-3, 380 … 440 V auxiliary switch
Basic switch with masking plate and selector knob, DIN rail mounting
16 A 7.5 kW 5.5 kW 3LD3030-0TK11 3LD3030-1TK11
25 A 9 kW 7.5 kW 3LD3130-0TK11 3LD3130-1TK11
32 A 11.5 kW 9.5 kW 3LD3230-0TK11 3LD3230-1TK11
40 A 18.5 kW 11.5 kW 3LD3330-0TK11 3LD3330-1TK11
63 A 22 kW 18.5 kW 3LD3430-0TK11 3LD3430-1TK11
Basic switches without knob-operated mechanism
8 16 A
25 A
7.5 kW
9 kW
5.5 kW
7.5 kW
3LD3010-0TK05
3LD3110-0TK05
3LD3010-1TK05
3LD3110-1TK05
32 A 11.5 kW 9.5 kW 3LD3210-0TK05 3LD3210-1TK05
40 A 18.5 kW 11.5 kW 3LD3310-0TK05 3LD3310-1TK05
63 A 22 kW 18.5 kW 3LD3410-0TK05 3LD3410-1TK05
Scope of supply:
• Basic switches without direct operating mechanism, incl. terminal covers for the infeed side
Mounting:
• Using screws or snap-on mounting on 35 mm mounting rails
Accessories for switches for installation in distribution boards 3LD30 3LD31 3LD32 3LD33 3LD34
(16 A) (25 A) (32 A) (40 A) (63 A)
and basic switches without knob-operated mechanism
Additional poles
Type Contacts Article No.
N switching contact (4th contact Leading switch-on, 3LD9340-0C ■ ■ ■ ■ ■
element) lagging switch-off
N terminal Through-type 3LD9340-2C ■ ■ ■ ■ ■
PE terminal Through-type 3LD9340-3C ■ ■ ■ ■ ■
Auxiliary switches
Contacts Article No.
1 NO + 1 NC 3LD9340-6C ■ ■ ■ ■ ■
Terminal covers
• Pack of 4 units
Version Article No.
For N switching contacts, N terminals or PE terminals 3LD9341-2A ■ ■ ■ ■ ■
Switch shafts
Cross-section Length Article No.
6 × 6 mm 600 mm 3LD9345-1C ■ ■ ■ ■ ■
Operating mechanisms, red/yellow
3P+N 3P 3P+N
I201_20448
I201_20450
I201_20451
I201_20451
I201_20453
I201_20453
Without 1 NO + 1 NC Without 1 NO + 1 NC Without 1 NO + 1 NC
auxiliary switch auxiliary switch auxiliary switch
3LD3010-0TL05
3LD3110-0TL05
3LD3010-1TL05
3LD3110-1TL05
–
–
–
–
–
–
–
–
8
3LD3210-0TL05 3LD3210-1TL05 – – – –
3LD3310-0TL05 3LD3310-1TL05 – – – –
3LD3410-0TL05 3LD3410-1TL05 – – – –
Knob-operated mechanisms
Version Color Article No.
• Lockable in 0 position with Black 3LD9343-4C ■ ■ ■ ■ ■
max. 2 padlocks Red/yellow 3LD9343-5C ■ ■ ■ ■ ■
• Incl. funnel
Switch shafts
Cross-section Length Article No.
6 × 6 mm 600 mm 3LD9345-1C ■ ■ ■ ■ ■
Inscription labels
• Pack of 10 units
Inscription Article No.
German/English (Hauptschalter/Main Switch) 3LD9346-1A ■ ■ ■ ■ ■
French/Spanish (Interrupteur Principal/Interruptor Principal) 3LD9346-2A ■ ■ ■ ■ ■
Without inscription 3LD9346-3A ■ ■ ■ ■ ■
Knob-operated mechanisms
• Lockable in 0 position with max. 2 padlocks
Version Color Article No.
For front mounting, without funnel Black 3LD9343-6C ■ ■ ■ ■ ■
Red/yellow 3LD9343-7C ■ ■ ■ ■ ■
Terminal covers
• For front mounting, floor mounting, installation in distribution boards
and basic switches without knob-operated mechanism
• Pack of 4 units
Number of poles Article No.
1-pole 3LD9341-2A ■ ■ ■ ■ ■
3-pole 3LD9341-0A ■ ■ ■ ■ ■
Switch shafts
Cross-section Length Article No.
6 × 6 mm 600 mm 3LD9345-1C ■ ■ ■ ■ ■
Inscription labels
• Pack of 10 units
• Not for installation in distribution boards
Inscription Article No.
German/English (Hauptschalter/Main Switch) 3LD9346-1A ■ ■ ■ ■ ■
French/Spanish (Interrupteur Principal/Interruptor Principal) 3LD9346-2A ■ ■ ■ ■ ■
Without inscription 3LD9346-3A ■ ■ ■ ■ ■
3P rotary operating 3P knob-operated 3P knob-operated 3P + N rotary ope- 3P + N knob-ope- 3P + N knob-operated 6P rotary operating
mechanisms mechanisms mechanisms rating mechanisms rated mechanisms mechanisms mechanisms
(3LD23/3LD24) (3LD23/3LD24)
3P rotary operating 3P knob-operated 3P knob-operated 3P + N rotary ope- 3P + N knob-ope- 3P+N knob-operated 6P rotary operating
mechanisms mechanisms mechanisms, rating mechanisms rated mechanisms mechanisms, mechanisms
(3LD23/3LD24) defeatable (3LD23/3LD24) defeatable
N switching contacts N/PE terminals (through-type) Auxiliary switches (standard version) Auxiliary switch for mounting on the front
Operating mechanisms
Rotary operating mechanisms for Knob-operated mechanisms Switch shafts Coupling pieces Assembly tools for
4-hole and center-hole mounting (3LD23/3LD24) without ON-lock center-hole mounting
Further accessories
Terminal covers, 1-pole Terminal covers, 3 and 4-pole Inscription labels (with and without inscription)
Note:
You will find a detailed range of accessories with the basic units.
4 4 4 4 4 4 4
3-pole
optional optional
3 2 or 3 or 2 or 1 1 or 2 or 3
1 or 2
1 3
2
and and
4 4 4 4 4 4 4
and
6 or 7 or 8 or 9
Legend
1 Auxiliary switch 3 N/PE terminal 5 Auxiliary switch for mounting on the front 2) 7 Rotary operating mechanism,
four-hole mounting
2 N switching contact 1) 4 Terminal cover 6 Rotary operating mechanism, center-hole
8 Knob-operated mechanism,
mounting
four-hole mounting
I201_20483
1)
N switching contact 2 must first be installed on the basic unit 9 Switch shaft (300 or 600 mm)
Can only be used with four-hole front mounting and floor mounting
8
2)
The switches for front mounting are mounted on the inside of covers, The switches for floor mounting up to 125 A (3LD28) are snapped
side panels or, if applicable, control cabinet doors (depending on the onto 35 mm DIN rails according to EN 60715 or screw-mounted on
applicable standard and switching function). In addition to the 4-hole mounting panels. The switches for 160 and 250 A (3LD23/3LD24) are
fastening of the handle, up to 63 A (3LD25) fastening with the 22.5 mm exclusively screwed onto mounting panels. The actuators are connected
diameter center hole can also be chosen. to the lower section of the switch through a door coupling, which can be
released in the 0 position, and a 300 mm long switch shaft. When the
control cabinet door is open, the switch can be protected against
inadvertent operation by removing the switch shaft from the lower
section of the switch. The overall depth can be adapted to individual
requirements by adjusting the switch shaft length.
The switches for distribution board mounting are suited for operation The DC isolators in the enclosure are suitable for disconnecting loads of
in distribution boards and for switching inside control cabinets or up to 800 V DC due to their 8-pole design. To provide additional safety,
distributors. Up to 125 A (3LD28), they have cap and mounting the isolators can be locked in the 0 position.
dimensions according to DIN 43880 and can be fitted under the same
cover together with miniature circuit breakers.
Operating mechanisms, black
Number of poles 3P
I201_20448
I201_20450
Uninterrupted current Iu Operational power P Operational power P Without 1 NO + 1 NC
At AC-21A, 380 … 440 V At AC-23A, 380 … 440 V At AC-3A, 380 … 440 V auxiliary switch (standard version)
Rotary operating mechanism, four-hole mounting
16 A 7.5 kW 5.5 kW 3LD2003-0TK51 3LD2003-1TP51
25 A 9.5 kW 7.5 kW 3LD2103-0TK51 3LD2103-1TP51
32 A 11.5 kW 9.5 kW 3LD2203-0TK51 3LD2203-1TP51
63 A 22 kW 18.5 kW 3LD2504-0TK51 3LD2504-1TP51
100 A 37 kW 30 kW 3LD2704-0TK51 3LD2704-1TP51
125 A 45 kW 37 kW 3LD2804-0TK51 3LD2804-1TP51
160 A 75 kW 50 kW 3LD2305-0TK11 3LD2305-0TK11 + 3LD9200-5B
8 250 A 132 kW 110 kW 3LD2405-0TK11 3LD2405-0TK11 + 3LD9200-5B
Rotary operating mechanism, center-hole mounting Ø 22.5 mm
16 A 7.5 kW 5.5 kW 3LD2054-0TK51 3LD2054-1TP51
25 A 9.5 kW 7.5 kW 3LD2154-0TK51 3LD2154-1TP51
32 A 11.5 kW 9.5 kW 3LD2254-0TK51 3LD2254-0TK51 + 3LD9200-5B
63 A 22 kW 18.5 kW 3LD2555-0TK51 3LD2555-0TK51 + 3LD9200-5B
Knob-operated mechanism, four-hole mounting
16 A 7.5 kW 5.5 kW 3LD2022-0TK11 3LD2022-0TK11 + 3LD9200-5B
25 A 9.5 kW 7.5 kW 3LD2122-0TK11 3LD2122-0TK11 + 3LD9200-5B
32 A 11.5 kW 9.5 kW 3LD2222-0TK11 3LD2222-0TK11 + 3LD9200-5B
Knob-operated mechanism, center-hole mounting Ø 22.5 mm
16 A 7.5 kW 5.5 kW 3LD2050-0TK11 3LD2050-0TK11 + 3LD9200-5B
25 A 9.5 kW 7.5 kW 3LD2150-0TK11 3LD2150-0TK11 + 3LD9200-5B
32 A 11.5 kW 9.5 kW 3LD2250-0TK11 3LD2250-0TK11 + 3LD9200-5B
Scope of supply:
• Including terminal covers for the infeed side
3P+N 6P
I201_20455
I201_20454
I201_20451
I201_20453
Without 1 NO + 1 NC Without 1 NO + 1 NC
auxiliary switch (standard version) auxiliary switch (standard version)
3LD2003-1TL51 3LD2003-2EP51 – –
3LD2103-1TL51 3LD2103-2EP51 3LD2103-3VK51 3LD2103-4VP51
3LD2203-1TL51 3LD2203-1TL51 + 3LD9200-5B 3LD2203-3VK51 3LD2203-3VK51 + 3LD9200-5B
3LD2504-1TL51 3LD2504-1TP51 + 3LD9250-0BA 3LD2504-3VK51 3LD2504-3VK51 + 3LD9200-5B
3LD2704-0TK51 + 3LD9280-0B 3LD2704-0TK51 + 3LD9280-0B + 3LD9200-5B – –
3LD2804-0TK51 + 3LD9280-0B 3LD2804-0TK51 + 3LD9280-0B + 3LD9200-5B – –
3LD2305-1TL11 3LD2305-1TL11 + 3LD9200-5B 3LD2305-3VK11 3LD2305-3VK11 + 3LD9200-5B
3LD2405-1TL11 3LD2405-1TL11 + 3LD9200-5B 3LD2405-3VK11 3LD2405-3VK11 + 3LD9200-5B 8
3LD2054-1TL51 3LD2054-2EP51 – –
3LD2154-1TL51 3LD2154-2EP51 – –
3LD2254-1TL51 3LD2254-1TL51 + 3LD9200-5B – –
3LD2555-0TK51 + 3LD9250-0BA 3LD2555-0TK51 + 3LD9250-0BA + 3LD9200-5B – –
Operating mechanisms, red/yellow
Number of poles 3P
I201_20448
I201_20450
Uninterrupted current Iu Operational power P Operational power P Without 1 NO + 1 NC
At AC-21A, 380 … 440 V At AC-23A, 380 … 440 V At AC-3A, 380 … 440 V auxiliary switch (standard version)
Rotary operating mechanism, four-hole mounting
16 A 7.5 kW 5.5 kW 3LD2003-0TK53 3LD2003-1TP53
25 A 9.5 kW 7.5 kW 3LD2103-0TK53 3LD2103-1TP53
32 A 11.5 kW 9.5 kW 3LD2203-0TK53 3LD2203-1TP53
63 A 22 kW 18.5 kW 3LD2504-0TK53 3LD2504-1TP53
100 A 37 kW 30 kW 3LD2704-0TK53 3LD2704-1TP53
125 A 45 kW 37 kW 3LD2804-0TK53 3LD2804-1TP53
160 A 75 kW 50 kW 3LD2305-0TK13 3LD2305-0TK13 + 3LD9200-5B
8 250 A 132 kW 110 kW 3LD2405-0TK13 3LD2405-0TK13 + 3LD9200-5B
Rotary operating mechanism, center-hole mounting Ø 22.5 mm
16 A 7.5 kW 5.5 kW 3LD2054-0TK53 3LD2054-1TP53
25 A 9.5 kW 7.5 kW 3LD2154-0TK53 3LD2154-1TP53
32 A 11.5 kW 9.5 kW 3LD2254-0TK53 3LD2254-0TK53 + 3LD9200-5B
63 A 22 kW 18.5 kW 3LD2555-0TK53 3LD2555-0TK53 + 3LD9200-5B
Knob-operated mechanism, four-hole mounting
16 A 7.5 kW 5.5 kW 3LD2022-0TK13 3LD2022-0TK13 + 3LD9200-5B
25 A 9.5 kW 7.5 kW 3LD2122-0TK13 3LD2122-0TK13 + 3LD9200-5B
32 A 11.5 kW 9.5 kW 3LD2222-0TK13 3LD2222-0TK13 + 3LD9200-5B
Knob-operated mechanism, center-hole mounting Ø 22.5 mm
16 A 7.5 kW 5.5 kW 3LD2050-0TK13 3LD2050-0TK13 + 3LD9200-5B
25 A 9.5 kW 7.5 kW 3LD2150-0TK13 3LD2150-0TK13 + 3LD9200-5B
32 A 11.5 kW 9.5 kW 3LD2250-0TK13 3LD2250-0TK13 + 3LD9200-5B
Scope of supply:
• Including terminal covers for the infeed side
3P+N 6P
I201_20455
I201_20454
I201_20451
I201_20453
Without 1 NO + 1 NC Without 1 NO + 1 NC
auxiliary switch (standard version) auxiliary switch (standard version)
3LD2003-1TL53 3LD2003-2EP53 – –
3LD2103-1TL53 3LD2103-2EP53 3LD2103-3VK53 3LD2103-4VP53
3LD2203-1TL53 3LD2203-1TL53 + 3LD9200-5B 3LD2203-3VK53 3LD2203-3VK53 + 3LD9200-5B
3LD2504-1TL53 3LD2504-1TP53 + 3LD9250-0BA 3LD2504-3VK53 3LD2504-3VK53 + 3LD9200-5B
3LD2704-0TK53 + 3LD9280-0B 3LD2704-0TK53 + 3LD9280-0B + 3LD9200-5B – –
3LD2804-0TK53 + 3LD9280-0B 3LD2804-0TK53 + 3LD9280-0B + 3LD9200-5B – –
3LD2305-1TL13 3LD2305-1TL13 + 3LD9200-5B 3LD2305-3VK13 3LD2305-3VK13 + 3LD9200-5B
3LD2405-1TL13 3LD2405-1TL13 + 3LD9200-5B 3LD2405-3VK13 3LD2405-3VK13 + 3LD9200-5B 8
3LD2054-1TL53 3LD2054-2EP53 – –
3LD2154-1TL53 3LD2154-2EP53 – –
3LD2254-1TL53 3LD2254-1TL53 + 3LD9200-5B – –
3LD2555-0TK53 + 3LD9250-0BA 3LD2555-0TK53 + 3LD9250-0BA + 3LD9200-5B – –
Knob-operated mechanisms
• Lockable in 0 position
with up to 3 padlocks
Version Mounting Article No.
For main control Four-hole mounting 3LD9243-1B ■ ■
switches
For EMERGENCY-STOP Four-hole mounting 3LD9243-3B ■ ■
switches
4-pole 3LD9201-1A ■
Inscription labels
• Pack of 10 units
Inscription Article No.
German/English (Hauptschalter/Main Switch) 3LD9286-1A ■ ■ ■ ■ ■ ■
Assembly tools
Without inscription 3LD9286-4A ■ ■ ■ ■ ■ ■
8
• For center-hole mounting with nut
• Pack of 5 units
Version Article No.
For main control switches and 3LD9256-0A ■ ■ ■ ■
EMERGENCY-STOP switches
Operating mechanisms, black
Number of poles 3P
I201_20448
I201_20450
Uninterrupted current Iu Operational power P Operational power P Without 1 NO + 1 NC
At AC-21A, 380 … 440 V At AC-23A, 380 … 440 V At AC-3A, 380 … 440 V auxiliary switch (standard version)
Door-coupling rotary operating mechanism, four-hole mounting
16 A 7.5 kW 5.5 kW 3LD2013-0TK51 3LD2013-0TK51 + 3LD9200-5C
25 A 9.5 kW 7.5 kW 3LD2113-0TK51 3LD2113-0TK51 + 3LD9200-5C
32 A 11.5 kW 9.5 kW 3LD2213-0TK51 3LD2213-0TK51 + 3LD9200-5C
63 A 22 kW 18.5 kW 3LD2514-0TK51 3LD2514-0TK51 + 3LD9200-5C
100 A 37 kW 30 kW 3LD2714-0TK51 3LD2714-0TK51 + 3LD9200-5C
8 125 A 45 kW 37 kW 3LD2814-0TK51 3LD2814-0TK51 + 3LD9200-5C
160 A 75 kW 50 kW 3LD2318-0TK11 3LD2318-0TK11 + 3LD9200-5C
250 A 132 kW 110 kW 3LD2418-0TK11 3LD2418-0TK11 + 3LD9200-5C
Door-coupling rotary operating mechanism, center-hole mounting Ø 22.5 mm
16 A 7.5 kW 5.5 kW 3LD2044-0TK51 3LD2044-0TK51 + 3LD9200-5C
25 A 9.5 kW 7.5 kW 3LD2144-0TK51 3LD2144-0TK51 + 3LD9200-5C
32 A 11.5 kW 9.5 kW 3LD2244-0TK51 3LD2244-0TK51 + 3LD9200-5C
63 A 22 kW 18.5 kW 3LD2545-0TK51 3LD2545-0TK51 + 3LD9200-5C
Defeatable door-coupling knob-operated mechanism, four-hole mounting
16 A 7.5 kW 5.5 kW 3LD2017-0TK11 3LD2017-0TK11 + 3LD9200-5C
32 A 11.5 kW 9.5 kW 3LD2217-0TK11 3LD2217-0TK11 + 3LD9200-5C
63 A 22 kW 18.5 kW 3LD2517-0TK11 3LD2517-0TK11 + 3LD9200-5C
Scope of supply:
• Including terminal covers for the infeed side
• Up to 125 A with integrated tolerance compensation
Mounting:
• Up to 125 A using screws or snap-on mounting on 35 mm mounting rails
3P+N 6P
I201_20455
I201_20454
I201_20451
I201_20453
Without 1 NO + 1 NC Without 1 NO + 1 NC
auxiliary switch (standard version) auxiliary switch (standard version)
Operating mechanisms, red/yellow
Number of poles 3P
I201_20448
I201_20450
Uninterrupted current Iu Operational power P Operational power P Without 1 NO + 1 NC
At AC-21A, 380 … 440 V At AC-23A, 380 … 440 V At AC-3A, 380 … 440 V auxiliary switch (standard version)
Door-coupling rotary operating mechanism, four-hole mounting
16 A 7.5 kW 5.5 kW 3LD2013-0TK53 3LD2013-0TK53 + 3LD9200-5C
25 A 9.5 kW 7.5 kW 3LD2113-0TK53 3LD2113-0TK53 + 3LD9200-5C
32 A 11.5 kW 9.5 kW 3LD2213-0TK53 3LD2213-0TK53 + 3LD9200-5C
63 A 22 kW 18.5 kW 3LD2514-0TK53 3LD2514-0TK53 + 3LD9200-5C
100 A 37 kW 30 kW 3LD2714-0TK53 3LD2714-0TK53 + 3LD9200-5C
8 125 A 45 kW 37 kW 3LD2814-0TK53 3LD2814-0TK53 + 3LD9200-5C
160 A 75 kW 50 kW 3LD2318-0TK13 3LD2318-0TK13 + 3LD9200-5C
250 A 132 kW 110 kW 3LD2418-0TK13 3LD2418-0TK13 + 3LD9200-5C
Door-coupling rotary operating mechanism, center-hole mounting Ø 22.5 mm
16 A 7.5 kW 5.5 kW 3LD2044-0TK53 3LD2044-0TK53 + 3LD9200-5C
25 A 9.5 kW 7.5 kW 3LD2144-0TK53 3LD2144-0TK53 + 3LD9200-5C
32 A 11.5 kW 9.5 kW 3LD2244-0TK53 3LD2244-0TK53 + 3LD9200-5C
63 A 22 kW 18.5 kW 3LD2545-0TK53 3LD2545-0TK53 + 3LD9200-5C
Defeatable door-coupling knob-operated mechanism, four-hole mounting
16 A 7.5 kW 5.5 kW 3LD2017-0TK13 3LD2017-0TK13 + 3LD9200-5C
32 A 11.5 kW 9.5 kW 3LD2217-0TK13 3LD2217-0TK13 + 3LD9200-5C
63 A 22 kW 18.5 kW 3LD2517-0TK13 3LD2517-1TL13 + 3LD9200-5C
Scope of supply:
• Including terminal covers for the infeed side
• Up to 125 A with integrated tolerance compensation
Mounting:
• Up to 125 A using screws or snap-on mounting on 35 mm mounting rails
3P+N 6P
I201_20455
I201_20454
I201_20451
I201_20453
Without 1 NO + 1 NC Without 1 NO + 1 NC
auxiliary switch (standard version) auxiliary switch (standard version)
Knob-operated mechanisms
• Lockable in 0 position
with up to 3 padlocks
Version Mounting Article No.
For main control Four-hole mounting 3LD9243-1B ■ ■
switches
For EMERGENCY-STOP Four-hole mounting 3LD9243-3B ■ ■
switches
8UC7.. door-coupling rotary operating mechanisms
• To achieve defeatability from
3LD27 (100 A) to 3LD24 (250 A)
Type Version Article No.
8UC71 Standard 8UC7110-1BB ■ ■
EMERGENCY-STOP 8UC7120-3BB ■ ■
8UC72 Standard 8UC7210-1BB ■ ■
EMERGENCY-STOP 8UC7220-3BB ■ ■
Terminal covers
• Pack of 4 units
Number of poles Article No.
1-pole 3LD9201-2A ■ 8
3LD9221-2A ■ ■
3LD9251-2A ■
3LD9281-2A ■ ■
3LD9241-2A ■ ■
3-pole 3LD9221-0A ■ ■
3LD9251-0A ■
4-pole 3LD9201-1A ■
Inscription labels
• Pack of 10 units
• Cannot be used with defeatable 3LD2.17
door-coupling rotary operating
mechanisms
Inscription Article No.
German/English (Hauptschalter/Main Switch) 3LD9286-1A ■ ■ ■ ■ ■ ■
Without inscription 3LD9286-4A ■ ■ ■ ■ ■ ■
Assembly tools
• For center-hole mounting with nut
• Pack of 5 units
Version Article No.
For main control switches and EMERGENCY- 3LD9256-0A ■ ■ ■ ■
STOP switches
I201_20448
I201_20450
Uninterrupted current Iu Operational power P Operational power P Without 1 NO + 1 NC
At AC-21A, 380 … 440 V At AC-23A, 380 … 440 V At AC-3A, 380 … 440 V auxiliary switch (standard version)
Knob-operated mechanisms with masking plate
16 A 7.5 kW 5.5 kW 3LD2030-0TK11 3LD2030-0TK11 + 3LD9200-5C
25 A 9.5 kW 7.5 kW 3LD2130-0TK11 3LD2130-0TK11 + 3LD9200-5C
32 A 11.5 kW 9.5 kW 3LD2230-0TK11 3LD2230-0TK11 + 3LD9200-5C
63 A 22 kW 18.5 kW 3LD2530-0TK11 3LD2530-0TK11 + 3LD9200-5C
100 A 37 kW 30 kW 3LD2730-0TK11 3LD2730-0TK11 + 3LD9200-5C
125 A 45 kW 37 kW 3LD2830-0TK11 3LD2830-0TK11 + 3LD9200-5C
8 160 A
250 A
75 kW
132 kW
50 kW
110 kW
3LD2330-0TK11
3LD2430-0TK11
3LD2330-0TK11 + 3LD9200-5C
3LD2430-0TK11 + 3LD9200-5C
Scope of supply:
• 3LD23/3LD24 including terminal covers for the infeed side
Mounting:
• Up to 125 A using screws or snap-on mounting on 35 mm mounting rails
• Up to 125 A cap and mounting dimensions acc. to DIN 43880
3P+N
I201_20453
I201_20451
Without 1 NO + 1 NC
auxiliary switch (standard version)
4-pole 3LD9201-1A ■
I201_20448
I201_20450
Uninterrupted current Iu Operational power P Operational power P Without 1 NO + 1 NC
At AC-21A, 380 … 440 V At AC-23A, 380 … 440 V At AC-3A, 380 … 440 V auxiliary switch (standard version)
Knob-operated mechanisms with masking plate
16 A 7.5 kW 5.5 kW 3LD2030-0TK13 3LD2030-0TK13 + 3LD9200-5C
25 A 9.5 kW 7.5 kW 3LD2130-0TK13 3LD2130-0TK13 + 3LD9200-5C
32 A 11.5 kW 9.5 kW 3LD2230-0TK13 3LD2230-0TK13 + 3LD9200-5C
63 A 22 kW 18.5 kW 3LD2530-0TK13 3LD2530-0TK13 + 3LD9200-5C
100 A 37 kW 30 kW 3LD2730-0TK13 3LD2730-0TK13 + 3LD9200-5C
125 A 45 kW 37 kW 3LD2830-0TK13 3LD2830-0TK13 + 3LD9200-5C
8 160 A
250 A
75 kW
132 kW
50 kW
110 kW
3LD2330-0TK13
3LD2430-0TK13
3LD2330-0TK13 + 3LD9200-5C
3LD2430-0TK13 + 3LD9200-5C
Scope of supply:
• 3LD23/3LD24 including terminal covers for the infeed side
Mounting:
• Up to 125 A using screws or snap-on mounting on 35 mm mounting rails
• Up to 125 A cap and mounting dimensions acc. to DIN 43880
3P+N
I201_20451
I201_20453
Without 1 NO + 1 NC
auxiliary switch (standard version)
4-pole 3LD9201-1A ■
I201_20530
Mains voltage Rated operational current Ie Rated operational current Ie Without
At DC-21A, 800 V DC At DC-22A, 800 V DC auxiliary switch
Knob-operated mechanisms
800 V DC 32 A 16 A 3LD2230-8VQ11-0AF6
N/PE terminals
Version Contacts Article No.
For front mounting Through-type 3LD9200-2B ■
3LD9220-2B ■ ■
3LD9250-2BA ■
3LD9280-2B ■ ■
3LD9240-2B ■ ■
For floor mounting, Through-type 3LD9200-2C ■
installation in 3LD9220-2C ■ ■
distribution boards
3LD9250-2CA ■
8
3LD9280-2C ■ ■
3LD9240-2C ■ ■
Auxiliary switches (standard version)
• For mounting on the left and/or right
• Lagging switch-on,
leading switch-off
Version Contacts Article No.
For front mounting 1 NO + 1 NC, standard 3LD9200-5B ■ ■ ■ ■ ■ ■ ■ ■
1 NO + 1 NC, 3LD9200-5BF ■ ■ ■ ■ ■ ■ ■ ■
gold-plated
Knob-operated mechanisms
• Lockable in 0 position with up to 3 padlocks
• Including seal
Switch Mounting Article No.
For main control Four-hole mounting 3LD9243-1B ■ ■
switches
For EMERGENCY-STOP Four-hole mounting 3LD9243-3B ■ ■
switches
Supplementary handles for door-coupling rotary operating mechanism
8 • For requirements according to UL508A/NFPA79
• Can be locked with up to 1 padlocks in
0 position
• Can only be switched on by deliberate action
Inscription Color Article No.
O-I Gray 3LD9287-1C ■ ■ ■ ■ ■ ■
3LD9247-1C ■ ■
Red/yellow 3LD9287-3C ■ ■ ■ ■ ■ ■
3LD9247-3C ■ ■
Switch shafts
Version Cross-section Length Article No.
For floor mounting 6 × 6 mm 300 mm 3LD9205-0C ■ ■ ■ ■ ■ ■
600 mm 3LD9205-2C ■ ■ ■ ■ ■ ■
8 × 8 mm 300 mm 3LD9245-0C ■ ■
600 mm 3LD9245-2C ■ ■
Coupling pieces
• Without ON-lock
Version Article No.
For floor mounting 3LD9242-4F ■ ■
4-pole 3LD9201-1A ■
Inscription labels
• Pack of 10 units
Inscription Article No.
German/English (Hauptschalter/Main Switch) 3LD9286-1A ■ ■ ■ ■ ■ ■
Without inscription 3LD9286-4A ■ ■ ■ ■ ■ ■
Assembly tools
• For center-hole mounting with nut
• Pack of 5 units
8
Switch Article No.
For main control switches and EMERGENCY-STOP 3LD9256-0A ■ ■ ■ ■
switches
3P 3P/6P 3P/6P
molded-plastic enclosures molded-plastic enclosures molded-plastic enclosures
8 DC isolators in enclosure
Operating mechanisms
Further accessories
Note:
You will find a detailed range of accessories with the basic units.
optional optional
3-pole
3 2 or 3 or 2 or 1 1 or 2 or 3 or 2 3
and and
and
as spare part
ಮ
5
Legend
1 Auxiliary switch 3 N/PE terminal 5 Rotary operating mechanism, center-hole mounting
2 N switching contact 1) 4 Auxiliary switch for mounting on the front
I201_20484
1)
N switching contact 2 must first be installed on the basic unit
Note: Depending on the enclosure size, not all accessories can be used in combination
8
Mounting types
For surface mounting of individual main control and EMERGENCY-STOP The DC isolators in the enclosure are suitable for disconnecting loads of up
switches, molded plastic-enclosed switches with degree of protection to 800 V DC due to their 8-pole design. To provide additional safety, the
IP65 are used. The molded-plastic enclosures each contain an N and/or a isolators can be locked in the 0 position.
PE terminal. As the switches can be locked in the 0 position, they can
also be used as maintenance and repair switches.
I201_20448
I201_20450
I201_20451
Uninterrupted Operational Operational Without auxiliary switch 1 NO + 1 NC Without auxiliary switch
current Iu power P power P (standard version)
At AC-21A, At AC-23A, At AC-3A,
380 … 440 V 380 … 440 V 380 … 440 V
Rotary operating mechanisms Base Base Base
with masking plate terminal terminal terminal
16 A 7.5 kW 5.5 kW PE+N 3LD2064-0TB51 N 3LD2064-1GP51 PE 3LD2064-1TC51
25 A 9.5 kW 7.5 kW PE+N 3LD2164-0TB51 N 3LD2164-1GP51 PE 3LD2164-1TC51
32 A 11.5 kW 9.5 kW PE+N 3LD2264-0TB51 N 3LD2264-1GP51 PE 3LD2264-1TC51
63 A 22 kW 18.5 kW PE+N 3LD2565-0TB51 N 3LD2565-1GP51 PE 3LD2565-1TC51
8 100 A 37 kW 30 kW PE+N 3LD2766-0TB51 N 3LD2766-1GP51 PE+N 3LD2766-0TB51 + 3LD9280-0C
125 A 45 kW 37 kW PE+N 3LD2866-0TB51 N 3LD2866-1GP51 PE+N 3LD2866-0TB51 + 3LD9280-0C
N/PE terminals
Contacts Article No.
Through-type 3LD9200-2C ■
3LD9220-2C ■ ■
3LD9250-2CA ■
3LD9280-2C ■ ■
Auxiliary switches (standard version)
• For mounting on the left and/or right
• Lagging switch-on, leading switch-off
Contacts Contact surface Article No.
1 NO + 1 NC Standard 3LD9200-5C ■ ■ ■ ■ ■ ■
Gold-plated 3LD9200-5CF ■ ■ ■ ■ ■ ■
2 NO Standard 3LD9200-6C ■ ■ ■ ■ ■ ■
Auxiliary switches for mounting on the front
• Mounted on the front of the switch shaft
• For long leading times (20 … 150 ms)
Contacts Contact surface Article No.
1 NO + 1 NC Standard 3LD9280-5D ■ ■ ■ ■ ■ ■
Gold-plated 3LD9280-5DF ■ ■ ■ ■ ■ ■
Rotary operating mechanisms
• Lockable in 0 position with up to 3 padlocks
Article No.
3LD9224-1G ■ ■ ■
3LD9284-1G ■ ■ ■
t
6P
I201_20454
I201_20455
I201_20453
I201_20448
I201_20450
I201_20451
Uninterrupted Operational Operational Without auxiliary switch 1 NO + 1 NC Without auxiliary switch
current Iu power P power P (standard version)
At AC-21A, At AC-23A, At AC-3A,
380 … 440 V 380 … 440 V 380 … 440 V
Rotary operating mechanisms Base Base Base
with masking plate terminal terminal terminal
16 A 7.5 kW 5.5 kW PE+N 3LD2064-0TB53 N 3LD2064-1GP53 PE 3LD2064-1TC53
25 A 9.5 kW 7.5 kW PE+N 3LD2164-0TB53 N 3LD2164-1GP53 PE 3LD2164-1TC53
32 A 11.5 kW 9.5 kW PE+N 3LD2264-0TB53 N 3LD2264-1GP53 PE 3LD2264-1TC53
63 A 22 kW 18.5 kW PE+N 3LD2565-0TB53 N 3LD2565-1GP53 PE 3LD2565-1TC53
8 100 A 37 kW 30 kW PE+N 3LD2766-0TB53 N 3LD2766-1GP53 PE+N 3LD2766-0TB53 + 3LD9280-0C
125 A 45 kW 37 kW PE+N 3LD2866-0TB53 N 3LD2866-1GP53 PE+N 3LD2866-0TB53 + 3LD9280-0C
N/PE terminals
Contacts Article No.
Through-type 3LD9200-2C ■
3LD9220-2C ■ ■
3LD9250-2CA ■
3LD9280-2C ■ ■
Auxiliary switches (standard version)
• For mounting on the left and/or right
• Lagging switch-on, leading switch-off
Contacts Contact surface Article No.
1 NO + 1 NC Standard 3LD9200-5C ■ ■ ■ ■ ■ ■
Gold-plated 3LD9200-5CF ■ ■ ■ ■ ■ ■
2 NO Standard 3LD9200-6C ■ ■ ■ ■ ■ ■
Auxiliary switches for mounting on the front
• Mounted on the front of the switch shaft
• For long leading times (20 … 150 ms)
Contacts Contact surface Article No.
1 NO + 1 NC Standard 3LD9280-5D ■ ■ ■ ■ ■ ■
Gold-plated 3LD9280-5DF ■ ■ ■ ■ ■ ■
Rotary operating mechanisms
• Lockable in 0 position with up to 3 padlocks
Article No.
3LD9224-3G ■ ■ ■
3LD9284-3G ■ ■ ■
t
6P
I201_20454
I201_20455
I201_20453
I201_20530
I201_20530
Mains voltage Rated operational Rated operational Without
current Ie current Ie auxiliary switch
At DC-21A, 800 V DC At DC-22A, 800 V DC
Rotary operating mechanisms
800 V DC 32 A 16 A 3LD2265-8VQ51-0AF6 3LD2265-8VQ53-0AF6
3LD2 maintenance and repair switches with EMC shield plate, 25 … 50 kArms
I201_20455
I201_20450
Uninterrupted Operational power P Uninterrupted Operational power 1 NO + 1 NC 1 NO + 1 NC
current Iu At AC-20, 0 … 550 Hz, current lu AC-23A, 50/60 Hz, (Auxiliary switch for (Auxiliary switch for
At AC-20, 0 … 550 Hz, 380 … 440 V At AC-21, 50/60 Hz, 380 … A440 V mounting on the front) mounting on the front)
380 … 440 V 380 … 440 V
Knob-operated mechanisms with masking plate Base Base
terminal terminal
10.2 A 4 kW 16 A 7.5 kW PE 3LD2084-2GP21 2× PE –
13.2 A 5.5 kW 25 A 9 kW PE 3LD2184-2GP21 2× PE 3LD2185-5VD21
18 A 7.5 kW 32 A 11.5 kW PE 3LD2284-2GP21 2× PE 3LD2285-5VD21
38 A 18.5 kW 63 A 22 kW PE 3LD2585-2GP21 2× PE 3LD2586-5VD21
75 A
90 A
37 kW
45 kW
100 A
125 A
37 kW
45 kW
PE
PE
3LD2786-2GP21 2× PE
3LD2886-2GP21 2× PE
–
–
8
Scope of supply:
• Incl. shield clamps or hose clips for contacting the cable shield
• The PE terminal as a through-type terminal is insulated from the cable shield
M20
M25 M25 M40/32 M40/32 M50/63 M50/63
N/PE terminals
Contacts Article No.
Through-type 3LD9200-2C ■
3LD9220-2C ■ ■
3LD9250-2CA ■
3LD9280-2C ■ ■
Auxiliary switches (standard version)
• For mounting on the left and/or right
• Lagging switch-on, leading switch-off
Contacts Contact surface Article No.
1 NO + 1 NC Standard 3LD9200-5C ■ ■ ■ ■ ■ ■
Gold-plated 3LD9200-5CF ■ ■ ■ ■ ■ ■
2 NO Standard 3LD9200-6C ■ ■ ■ ■ ■ ■
Auxiliary switches for mounting on the front
• Mounted on the front of the switch shaft
• For long leading times (20 … 150 ms)
8 Contacts Contact surface Article No.
1 NO + 1 NC Standard 3LD9280-5D ■ ■ ■ ■ ■ ■
Gold-plated 3LD9280-5DF ■ ■ ■ ■ ■ ■
Rotary operating mechanisms
• Lockable in 0 position with up to 3 padlocks
Version Article No.
Main control switches 3LD9224-1G ■ ■ ■
3LD9284-1G ■ ■ ■
t
EMERGENCY-STOP switches 3LD9224-3G ■ ■ ■
3LD9284-3G ■ ■ ■
Terminal blocks
Version Article No.
Through-type terminal with screw connection 8WH1000-0AF00 ■ ■ ■ ■ ■ ■
Shield terminals
Terminal area Article No.
3 …12 mm 3LD9228-1G ■ ■ ■ ■ ■ ■
N/PE terminals
Contacts Article No.
Through-type 3LD9200-2C ■
3LD9220-2C ■ ■
3LD9250-2CA ■
3LD9280-2C ■ ■
Auxiliary switches (standard version)
• For mounting on the left and/or right
• Lagging switch-on, leading switch-off
Contacts Contact surface Article No.
1 NO + 1 NC Standard 3LD9200-5C ■ ■ ■ ■ ■ ■
Gold-plated 3LD9200-5CF ■ ■ ■ ■ ■ ■
2 NO Standard 3LD9200-6C ■ ■ ■ ■ ■ ■
Auxiliary switches for mounting on the front
• Mounted on the front of the switch shaft
• For long leading times (20 … 150 ms) 8
Contacts Contact surface Article No.
1 NO + 1 NC Standard 3LD9280-5D ■ ■ ■ ■ ■ ■
Gold-plated 3LD9280-5DF ■ ■ ■ ■ ■ ■
Shield terminals
Terminal area Article No.
3 …12 mm 3LD9228-1G ■ ■ ■ ■ ■ ■
N switching contact N/PE terminals (through-type) Auxiliary switches (standard version) Auxiliary switch for mounting on the front
Operating mechanisms
Rotary operating mechanisms for four-hole mounting Coupling heads with and without Supplementary handles Switch shafts
tolerance compensation for UL508A/NFPA79
Further accessories
Note:
You will find a detailed range of accessories with the basic units.
4 4 4 4 4 4 4
3-pole
optional optional
3 2 or 3 or 2 or 1 1 or 2 or 3 or 2 3
and and
4 4 4 4 4 4 4
and
5 or 6 or 7
Legend
1 Auxiliary switch 3 N/PE terminal 5 Rotary operating mechanism, four-hole mounting 7 Switch shaft (300 or 600 mm)
2 N switching contact 1)
4 Terminal cover 6 Knob-operated mechanism, four-hole mounting
I201_20485
1)
N switching contact 2 must first be installed on the basic unit
8
The certification according to UL489 makes the 3LD5 UL ideal for use as a main control switch for machinery and plants for export to the NAFTA states. The
variety of accessories makes it especially suitable as a main disconnect switch for industrial machinery. The switch is also certified according to UL508 and
can also be used as a manual motor controller.
Mounting types
The switches for front mounting are mounted on the inside of covers, side The switches for floor mounting with direct operating mechanism up to
panels or, if applicable, control cabinet doors (depending on the 60 A are snapped onto 35 mm DIN rails according to EN 60715 or
applicable standard and switching function). Installation is achieved by screw-mounted on mounting panels. The switches for 100 … 160 A
4-hole mounting of the handle. This switch is especially suitable when (3LD54 … 3LD58) are exclusively screwed onto mounting panels.
door interlocking is not required or is implemented in a different way.
I201_20448
I201_20451
Uninterrupted current Iu General use acc. to Operational power P
At AC-21A, 380 … 440 V UL489/60947-4-1 At AC-23A, 380 … 440 V
Rotary operating mechanism, four-hole mounting
32 30 15 3LD5020-0TK11 3LD5020-0TL11
63 60 30 3LD5220-0TK11 3LD5220-0TL11
100 100 45 3LD5420-0TK11 3LD5420-0TL11
125 125 55 3LD5620-0TK11 3LD5620-0TL11
160 150 75 3LD5820-0TK11 3LD5820-0TL11
8 Scope of supply:
• Including terminal covers for the infeed side
N/PE terminals
Contacts Article No.
Through-type 3LD9250-2BA ■
3LD9280-2B ■
3LD9240-2B ■ ■ ■
I201_20451
3LD5020-0TK13 3LD5020-0TL13
3LD5220-0TK13 3LD5220-0TL13
3LD5420-0TK13 3LD5420-0TL13
3LD5620-0TK13 3LD5620-0TL13
3LD5820-0TK13 3LD5820-0TL13
Knob-operated mechanisms
• Lockable in 0 position with up to 3 padlocks
Version Article No.
For main control switches 3LD9243-1B ■ ■ ■
For EMERGENCY-STOP switches 3LD9284-3B ■ ■ ■
Terminal covers
• Pack of 4 units
Number of poles Article No.
1-pole 3LD9251-2A ■
3LD9281-2A ■
3LD9241-2A ■ ■ ■
3-pole 3LD9251-0A ■
Inscription labels
• Pack of 10 units
Inscription Article No.
German/English (Hauptschalter/Main Switch) 3LD9286-1A ■ ■ ■ ■ ■
Without inscription 3LD9286-4A ■ ■ ■ ■ ■
I201_20448
I201_20451
Uninterrupted current Iu General use acc. to Operational power P
At AC-21A, 380 … 440 V UL489/508 At AC-23A, 380 … 440 V
Rotary operating mechanism, four-hole mounting
32 30 15 3LD5000-0TK11 3LD5000-0TL11
63 60 30 3LD5200-0TK11 3LD5200-0TL11
100 100 45 3LD5400-0TK11 3LD5400-0TL11
125 125 55 3LD5600-0TK11 3LD5600-0TL11
160 150 75 3LD5800-0TK11 3LD5800-0TL11
Scope of supply:
8 • Including terminal covers for the infeed side
Accessories for floor mounting with direct operating mechanisms 3LD50 3LD52 3LD54 3LD56 3LD58
N/PE terminals
Contacts Article No.
Through-type 3LD9250-2CA ■
3LD9280-2C ■
3LD9240-2C ■ ■ ■
Auxiliary switches
• For mounting on the left and/or right
• Lagging switch-on, leading switch-off
Contacts Contact surface Article No.
1 NO + 1 NC Standard 3LD9200-5C ■ ■ ■ ■ ■
Gold-plated 3LD9200-5CF ■ ■ ■ ■ ■
Terminal covers
• Pack of 4 units
Number of poles Article No.
1-pole 3LD9251-2A ■
3LD9281-2A ■
3LD9241-2A ■ ■ ■
3-pole 3LD9251-0A ■
I201_20451
3LD5000-0TK13 3LD5000-0TL13
3LD5200-0TK13 3LD5200-0TL13
3LD5400-0TK13 3LD5400-0TL13
3LD5600-0TK13 3LD5600-0TL13
3LD5800-0TK13 3LD5800-0TL13
I201_20448
I201_20451
Uninterrupted current Iu General use acc. to Operational power P
At AC-21A, 380 … 440 V UL489/508 At AC-23A, 380 … 440 V
Rotary operating mechanism, four-hole mounting
32 30 15 3LD5010-0TK11 3LD5010-0TL11
63 60 30 3LD5210-0TK11 3LD5210-0TL11
100 100 45 3LD5410-0TK11 3LD5410-0TL11
125 125 55 3LD5610-0TK11 3LD5610-0TL11
160 150 75 3LD5810-0TK11 3LD5810-0TL11
Scope of supply:
• Including terminal covers for the infeed side
8 • Defeatable door-coupling rotary operating mechanisms with shaft 300 mm
• Without tolerance compensation
N/PE terminals
Contacts Article No.
Through-type 3LD9250-2CA ■
3LD9280-2C ■
3LD9240-2C ■ ■ ■
I201_20451
3LD5010-0TK13 3LD5010-0TL13
3LD5210-0TK13 3LD5210-0TL13
3LD5410-0TK13 3LD5410-0TL13
3LD5610-0TK13 3LD5610-0TL13
3LD5810-0TK13 3LD5810-0TL13
3-pole 3LD9251-0A ■
Inscription labels
• Pack of 10 units
Inscription Article No.
German/English (Hauptschalter/Main Switch) 3LD9286-1A ■ ■ ■ ■ ■
Without inscription 3LD9286-4A ■ ■ ■ ■ ■
Switch shafts
Cross-section Length Article No.
6 × 6 mm 300 mm 3LD9205-0C ■ ■
600 mm 3LD9205-2C ■ ■
8 × 8 mm 300 mm 3LD9245-0C ■ ■ ■
600 mm 3LD9245-2C ■ ■ ■
8 3LD9240-2C ■ ■ ■
Terminal covers
• Pack of 4 units
Number of poles Article No.
1-pole 3LD9251-2A ■
3LD9281-2A ■
3LD9241-2A ■ ■ ■
3-pole 3LD9251-0A ■
Inscription labels
• Pack of 10 units
Inscription Article No.
German/English (Hauptschalter/Main Switch) 3LD9286-1A ■ ■ ■ ■ ■
Without inscription 3LD9286-4A ■ ■ ■ ■ ■
Switch shafts
Cross-section Length Article No.
6 × 6 mm 300 mm 3LD9205-0C ■ ■
600 mm 3LD9205-2C ■ ■
8 × 8 mm 300 mm 3LD9245-0C ■ ■ ■
600 mm 3LD9245-2C ■ ■ ■
Basic units
Front operating Front operating Lateral operating Lateral operating Front-mounted devices, Front operating
mechanisms, 3-pole mechanisms, 4-pole mechanisms, 3-pole mechanisms, 4-pole 6-pole for DC applications mechanisms, 3-pole
Operating mechanisms
Direct operating Door-coupling rotary Handles for door-coupling Further accessories for door-coupling
mechanisms operating mechanisms rotary operating mechanisms rotary operating mechanisms
Auxiliary Terminal Phase Blocking pin Mounting Accessories for
switches covers barriers test function elements DC applications
Note:
You will find a detailed range of accessories with the basic units.
I201_18836
All 3KD switch disconnectors are designed for floor mounting. Sizes 01 and 02 of the 3KD0 and sizes 1 and 2 of the 3KD can be
To ensure that the switch can be flexibly adapted to the relevant snapped onto a DIN rail (TH35 according to EN 60715) as an alternative
installation conditions, the mounting bracket can be rotated mounting method.
through 90° with size 3 or larger.
4 4 4 4 4 4 4
optional optional
3-pole
3 2 or 3 or 2 or 1 1 or 2 or 3
1 or 2
1 32
and and
4 4 4 4 4 4 4
and
8 Legend
1 Auxiliary switch 3 N/PE terminal 5 Door-coupling rotary operating mechanism
2 N switching contact 1) 4 Terminal cover
I201_20486
1)
N switching contact 2 must first be installed on the basic unit
Note: Design with door-coupling rotary operating mechanism for sizes 01 and 02 only possible for basic unit without operating mechanism
5 5
4a
or
2 or
1 or
5 Auxiliary switch
optional and optional and optional and optional and optional and 6 Phase barrier 3)
7 Terminal cover3)
5 6 or 7 6 or 7 6 or 7 5
8 Direct operating mechanism
optional and if 4 and optional and if 4a 9 Door-coupling rotary operating
mechanism
5 5
5
1)
Only for 3-pole 3K, max. 1× per switch
8 or 9 2)
Max. 1× for each side of the switch,
requires at least 1× auxiliary switch 5
I201_20487
3)
Only for size 2, flat terminals
5 5
3 or 4a
4a Auxiliary switch module for
33 or
4a
or
2 or
and and and and
6 Phase barrier 3)
2
7 Terminal cover3)
1 or
1 or
8 Direct operating mechanism
optional and optional and optional and optional and optional and 9 Door-coupling rotary operating
mechanism
5 6 or 7 6 or 7 6 or 7 5
5 5
5 8
1)
Only for 3-pole 3K, max. 1× per switch
8 or 9 2)
Max. 1× for each side of the switch,
requires at least 1× auxiliary switch 5
I201_20488
3)
Only for size 2, flat terminals
6 or 7 6 or 7 6 or 7
Legend
3
3
and and
3 4th contact element 1)
or
5 Auxiliary switch 2)
1
1
6 Phase barrier
5 1)
Only for 3-pole 3K, max. 1× per switch
ૣ
8 or
99 2)
Up to 4× auxiliary switches 5
I201_20489
optional
and if 4a Legend
1 Neutral conductor terminal
6 or 7 6 or 7 5
2 N/PE terminal
optional optional optional
and and and 3 4th contact element 1)
3 or 4a
standard version 2)
5 Auxiliary switch
4a
9 and
2 or
and and 7 Terminal cover 3)
9 Door-coupling rotary operating
1 or
mechanism
6 or 7 6 or 7 5 1)
Only for 3-pole 3K
2)
Max. 1× per switch,
8 optional
and if 4a
Requires at least 1× auxiliary switch /5
3)
Only for size 2, flat terminals
I201_20490
5
ૡ
6 or ૢ
7 6 or 7
optional optional
and and
Legend
3
and
2
and
3 4th contact element 1)
or
5 Auxiliary switch 2)
1
6 Phase barrier
optional optional 7 Terminal cover
and and
9 Door-coupling rotary operating mechanism
ૡ
6 or ૢ
7 6 or 7 1)
Only for 3-pole 3K
2)
Up to 4× auxiliary switches
optional
and
ૠ
I201_20491
ૠ
5
optional
and if 4a
ૠ
5 6 or 7 ૡ
6 or ૢ
7 Legend
optional optional optional 1 Neutral conductor terminal
and and and 2 N/PE terminal
or 4a
optional optional
9 5 Auxiliary switch
4a
and
or
and and
6 Phase barrier 3)
2
7 Terminal cover 3)
or
I201_20492
ૠ
5
ಯ
6 or ರ
7 ಯ
6 or ರ
7
optional optional
and and
3
Legend
2 or
optional
1 Neutral conductor terminal
and
and ಲ
9
2 N/PE terminal
1 or
6 Phase barrier
optional optional
and and 7 Terminal cover
9 Door-coupling rotary operating mechanism
ಯ
6 or ರ
7 ಯ
6 or ರ
7
1)
Only for 3-pole 3K
optional 2)
Up to 4× auxiliary switches 5
and
ಮ
I201_20493
Size Uninterrupted
current Iu
Box terminals
01 16 A 3KD0132-2KG20-3 3KD0142-2KG20-3 – –
32 A 3KD0232-2KG20-3 3KD0242-2KG20-3 – –
63 A 3KD0332-2KG20-3 – – –
02 63 A 3KD0332-2LG20-3 3KD0342-2LG20-3 – –
80 A 3KD0432-2LG20-3 3KD0442-2LG20-3 – –
8 100 A
125 A
3KD0532-2LG20-3
3KD0632-2LG20-3
3KD0542-2LG20-3
3KD0642-2LG20-3
–
–
–
–
1 16 A – – 3KD1632-2ME10-0 3KD1642-2ME10-0
32 A – – 3KD2232-2ME10-0 3KD2242-2ME10-0
63 A – – 3KD2632-2ME10-0 3KD2642-2ME10-0
80 A – – 3KD2832-2ME10-0 3KD2842-2ME10-0
100 A – – 3KD3032-2ME10-0 3KD3042-2ME10-0
2 80 A – – 3KD2832-2NE10-0 3KD2842-2NE10-0
100 A – – 3KD3032-2NE10-0 3KD3042-2NE10-0
125 A – – 3KD3232-2NE10-0 3KD3242-2NE10-0
160 A – – 3KD3432-2NE10-0 3KD3442-2NE10-0
Flat terminals
2 80 A – – 3KD2832-0NE10-0 3KD2842-0NE10-0
100 A – – 3KD3032-0NE10-0 3KD3042-0NE10-0
125 A – – 3KD3232-0NE10-0 3KD3242-0NE10-0
160 A – – 3KD3432-0NE10-0 3KD3442-0NE10-0
200 A – – 3KD3632-0NE10-0 3KD3642-0NE10-0
250 A – – 3KD3832-0NE10-0 3KD3842-0NE10-0
3 200 A – – 3KD3632-0PE10-0 3KD3642-0PE10-0
250 A – – 3KD3832-0PE10-0 3KD3842-0PE10-0
315 A – – 3KD4032-0PE10-0 3KD4042-0PE10-0
400 A – – 3KD4232-0PE10-0 3KD4242-0PE10-0
500 A – – 3KD4432-0PE10-0 3KD4442-0PE10-0
4 500 A – – 3KD4432-0QE10-0 3KD4442-0QE10-0
630 A – – 3KD4632-0QE10-0 3KD4642-0QE10-0
800 A – – 3KD4832-0QE10-0 3KD4842-0QE10-0
1000 A – – 3KD5032-0QE10-0 3KD5042-0QE10-0
5 1000 A – – 3KD5032-0RE10-0 3KD5042-0RE10-0
1250 A – – 3KD5232-0RE10-0 3KD5242-0RE10-0
1600 A – – 3KD5432-0RE10-0 3KD5442-0RE10-0
2000 A – – 3KD5632-0RE10-0 3KD5642-0RE10-0
Scope of supply:
• Incl. terminal covers on input and output side for 3KD0 sizes 01 and 02
• Incl. phase barriers on the input and output side for size 2 with flat terminals
• Terminal covers must be ordered separately for switch disconnectors with flat terminals and direct operating mechanisms
Mounting:
• The switch disconnectors are designed for floor mounting and the sizes 01, 02, 1 and 2 can optionally also be mounted on DIN rails
3KD0133-2KG20-3 3KD0143-2KG20-3
3KD0233-2KG20-3 3KD0243-2KG20-3
3KD0333-2KG20-3 –
3KD0333-2LG20-3 3KD0343-2LG20-3
3KD0433-2LG20-3 3KD0443-2LG20-3
3KD0533-2LG20-3
3KD0633-2LG20-3
3KD0543-2LG20-3
3KD0643-2LG20-3
8
– –
– –
– –
– –
– –
– –
– –
– –
– –
– –
– –
– –
– –
– –
– –
– –
– –
– –
– –
– –
– –
– –
– –
– –
– –
– –
– –
– –
Note:
• The complete units with a direct operating mechanism are not suitable for conversion to door-coupling rotary operating mechanisms;
the basic units are to be used for this purpose
• All basic units without handles are suitable for use with door-coupling rotary operating mechanisms, from size 1 to size 5 these can also be equipped with direct
operating mechanisms
• The switch disconnectors with lateral operating mechanism are suitable for door-coupling rotary operating mechanisms
• For 3KD switch disconnectors and lateral operating mechanism (left or right), only 8UD door-coupling rotary operating mechanisms
without the test function can be used
Size Uninterrupted
current Iu
Box terminals
01 16 A – – 3KD0130-2KG20-3 3KD0140-2KG20-3 –
32 A – – 3KD0230-2KG20-3 3KD0240-2KG20-3 –
63 A – – 3KD0330-2KG20-3 – –
02 63 A – – 3KD0330-2LG20-3 3KD0340-2LG20-3 –
80 A – – 3KD0430-2LG20-3 3KD0440-2LG20-3 –
8 100 A – – 3KD0530-2LG20-3 3KD0540-2LG20-3 –
125 A – – 3KD0630-2LG20-3 3KD0640-2LG20-3 –
1 16 A 3KD1630-2ME10-0 3KD1640-2ME10-0 – – 3KD1630-2ME20-0
32 A 3KD2230-2ME10-0 3KD2240-2ME10-0 – – 3KD2230-2ME20-0
63 A 3KD2630-2ME10-0 3KD2640-2ME10-0 – – 3KD2630-2ME20-0
80 A 3KD2830-2ME10-0 3KD2840-2ME10-0 – – 3KD2830-2ME20-0
100 A 3KD3030-2ME10-0 3KD3040-2ME10-0 – – 3KD3030-2ME20-0
2 80 A 3KD2830-2NE10-0 3KD2840-2NE10-0 – – 3KD2830-2NE20-0
100 A 3KD3030-2NE10-0 3KD3040-2NE10-0 – – 3KD3030-2NE20-0
125 A 3KD3230-2NE10-0 3KD3240-2NE10-0 – – 3KD3230-2NE20-0
160 A 3KD3430-2NE10-0 3KD3440-2NE10-0 – – 3KD3430-2NE20-0
Flat terminals
2 80 A 3KD2830-0NE10-0 3KD2840-0NE10-0 – – 3KD2830-0NE20-0
100 A 3KD3030-0NE10-0 3KD3040-0NE10-0 – – 3KD3030-0NE20-0
125 A 3KD3230-0NE10-0 3KD3240-0NE10-0 – – 3KD3230-0NE20-0
160 A 3KD3430-0NE10-0 3KD3440-0NE10-0 – – 3KD3430-0NE20-0
200 A 3KD3630-0NE10-0 3KD3640-0NE10-0 – – 3KD3630-0NE20-0
250 A 3KD3830-0NE10-0 3KD3840-0NE10-0 – – 3KD3830-0NE20-0
3 200 A 3KD3630-0PE10-0 3KD3640-0PE10-0 – – 3KD3630-0PE20-0
250 A 3KD3830-0PE10-0 3KD3840-0PE10-0 – – 3KD3830-0PE20-0
315 A 3KD4030-0PE10-0 3KD4040-0PE10-0 – – 3KD4030-0PE20-0
400 A 3KD4230-0PE10-0 3KD4240-0PE10-0 – – 3KD4230-0PE20-0
500 A 3KD4430-0PE10-0 3KD4440-0PE10-0 – – 3KD4430-0PE20-0
4 500 A 3KD4430-0QE10-0 3KD4440-0QE10-0 – – 3KD4430-0QE20-0
630 A 3KD4630-0QE10-0 3KD4640-0QE10-0 – – 3KD4630-0QE20-0
800 A 3KD4830-0QE10-0 3KD4840-0QE10-0 – – 3KD4830-0QE20-0
1000 A 3KD5030-0QE10-0 3KD5040-0QE10-0 – – 3KD5030-0QE20-0
5 1000 A 3KD5030-0RE10-0 3KD5040-0RE10-0 – – 3KD5030-0RE20-0
1250 A 3KD5230-0RE10-0 3KD5240-0RE10-0 – – 3KD5230-0RE20-0
1600 A 3KD5430-0RE10-0 3KD5440-0RE10-0 – – 3KD5430-0RE20-0
2000 A 3KD5630-0RE10-0 3KD5640-0RE10-0 – – 3KD5630-0RE20-0
Scope of supply:
• Incl. terminal covers on input and output side for 3KD0 sizes 01 and 02
• Incl. phase barriers on the input and output side for size 2 with flat terminals
• Terminal covers must be ordered separately for switch disconnectors with flat terminals and direct operating mechanisms
Mounting:
• The switch disconnectors are designed for floor mounting and the sizes 01, 02, 1 and 2 can optionally also be mounted on DIN rails
– – – – – –
– – – – – –
– – – – – –
– – – – – –
– – – – – –
– – – – – – 8
– – – – – –
3KD1640-2ME20-0 3KD1660-2ME20-0 3KD1634-2ME10-0 3KD1644-2ME10-0 3KD1634-2ME40-0 3KD1644-2ME40-0
3KD2240-2ME20-0 3KD2260-2ME20-0 3KD2234-2ME10-0 3KD2244-2ME10-0 3KD2234-2ME40-0 3KD2244-2ME40-0
3KD2640-2ME20-0 3KD2660-2ME20-0 3KD2634-2ME10-0 3KD2644-2ME10-0 3KD2634-2ME40-0 3KD2644-2ME40-0
3KD2840-2ME20-0 – 3KD2834-2ME10-0 3KD2844-2ME10-0 3KD2834-2ME40-0 3KD2844-2ME40-0
3KD3040-2ME20-0 – 3KD3034-2ME10-0 3KD3044-2ME10-0 3KD3034-2ME40-0 3KD3044-2ME40-0
3KD2840-2NE20-0 3KD2860-2NE20-0 3KD2834-2NE10-0 3KD2844-2NE10-0 3KD2834-2NE40-0 3KD2844-2NE40-0
3KD3040-2NE20-0 3KD3060-2NE20-0 3KD3034-2NE10-0 3KD3044-2NE10-0 3KD3034-2NE40-0 3KD3044-2NE40-0
3KD3240-2NE20-0 3KD3260-2NE20-0 3KD3234-2NE10-0 3KD3244-2NE10-0 3KD3234-2NE40-0 3KD3244-2NE40-0
3KD3440-2NE20-0 3KD3460-2NE20-0 3KD3434-2NE10-0 3KD3444-2NE10-0 3KD3434-2NE40-0 3KD3444-2NE40-0
Note:
• The complete units with a direct operating mechanism are not suitable for conversion to door-coupling rotary operating mechanisms;
the basic units are to be used for this purpose
• All basic units without handles are suitable for use with door-coupling rotary operating mechanisms, from size 1 to size 5 these can also be equipped with direct
operating mechanisms
• The switch disconnectors with lateral operating mechanism are suitable for door-coupling rotary operating mechanisms
• For 3KD switch disconnectors and lateral operating mechanism (left or right), only 8UD door-coupling rotary operating mechanisms
without the test function can be used
N N 3KD9025-2 ■
3KD9105-2 ■
3KD9205-2 ■
I201_20442
8
Red/yellow 3KD9101-8 ■
3KD9201-8 ■
Note:
• For 3KD switch disconnectors and lateral operating mechanism (left or right), only 8UD door-coupling rotary operating mechanisms
without the test function can be used
• The door-coupling rotary operating mechanisms of the 3KD90 type are mounted on the inside of the door by means of center-hole mounting
Accessories for door-coupling rotary operating mechanisms Size 01 Size 02 Size 1 Size 2 Size 3 Size 4 Size 5
Handles
• Supplied with a masking plate, but without an extension shaft
and without coupling driver
• Can be locked with up to max. 3 padlocks
Inscription Lighting Color Article No.
O – I Without Gray 8UD1771-2AD01 ■ ■ ■ ■
8UD1841-2AD01 ■
8UD1851-3AD01 ■
8UD1861-4AD01 ■
Red/yellow 8UD1771-2AD05 ■ ■ ■ ■
8UD1841-2AD05 ■
8UD1851-3AD05 ■
8UD1861-4AD05 ■
With Gray 8UD1771-2CD01 ■ ■
8UD1841-2CD01 ■
8UD1851-3CD01 ■
8UD1861-4CD01 ■
Red/yellow 8UD1771-2CD05 ■ ■
8UD1841-2CD05 ■
8UD1851-3CD05 ■
8UD1861-4CD05 ■
8 Test – O – I Without Gray 8UD1771-2AF01 ■ ■
8UD1841-2AF01 ■
8UD1851-3AF01 ■
8UD1861-4AF01 ■
Red/yellow 8UD1771-2AF05 ■ ■
8UD1841-2AF05 ■
8UD1851-3AF05 ■
8UD1861-4AF05 ■
With Gray 8UD1771-2CF01 ■ ■
8UD1841-2CF01 ■
8UD1851-3CF01 ■
8UD1861-4CF01 ■
Red/yellow 8UD1771-2CF05 ■ ■
8UD1841-2CF05 ■
8UD1851-3CF05 ■
8UD1861-4CF05 ■
Extension shafts
• A shaft jack is required for the 8UD1 handle when the
600 mm long shaft is used and for sizes 01, 02, 1 and 2
Length Article No.
300 mm 3KD9002-0 ■ ■
8UC6032 ■ ■ ■
8UC6033 ■
8UC6034 ■
600 mm 3KD9002-1 ■ ■
8UC6082 ■ ■ ■
8UC6083 ■
8UC6084 ■
Shaft jack for 8UD1 handle
Version Article No.
For shaft 600 mm 8UD1900-0FA00 ■ ■ ■ ■
Accessories for door-coupling rotary operating mechanisms Size 01 Size 02 Size 1 Size 2 Size 3 Size 4 Size 5
Coupling drivers
Version Article No.
With tolerance compensation 8UD1900-1GA00 ■ ■
8UD1900-2GA00 ■ ■
8UD1900-6GA00 ■
8UD1900-3GA00 ■
8UD1900-4GA00 ■
Without tolerance compensation 8UD1900-1HA00 ■ ■
8UD1900-2HA00 ■ ■
8UD1900-6HA00 ■
8UD1900-3HA00 ■
8UD1900-4HA00 ■
Adapters for shafts
Article No.
8UC6022 ■ ■ ■
8UC6023 ■
8UC6024 ■
Further accessories and spare parts Size 01 Size 02 Size 1 Size 2 Size 3 Size 4 Size 5
Further accessories and spare parts Size 01 Size 02 Size 1 Size 2 Size 3 Size 4 Size 5
Phase barriers
• For 3KD with flat terminals
• For 3KD size 2 with flat terminals, phase barriers are
already contained in the scope of supply
Version Scope of supply Article No.
For 3-pole devices 6 units 3KD9108-6 ■
3KD9308-6 ■
3KD9408-6 ■
3KD9508-6 ■
For 4-pole devices 8 units 3KD9108-8 ■
3KD9308-8 ■
3KD9408-8 ■
3KD9508-8 ■
Terminal covers
• For sizes 01 and 02, terminal covers are already part of the
scope of supply and must therefore only be used as spare parts
• For 3KD with flat terminals
• Not permissible for 2000 A devices
Version Scope of supply Type Article No.
For 1-pole devices 4 units 3KD9014-1B ■
3KD9024-1B ■
For 3-pole devices 4 units 3KD9014-3B ■
8 6 units Standard version 3KD9504-6 ■
3KD9204-6 ■
Short version 3KD9204-7 ■
8 units Standard version 3KD9304-6 ■
3KD9404-6 ■
Short version 3KD9304-7 ■
3KD9404-7 ■
For 4-pole devices 8 units Standard version 3KD9504-8 ■
3KD9204-8 ■
Short version 3KD9204-5 ■
10 units Standard version 3KD9304-8 ■
3KD9404-8 ■
Short version 3KD9304-5 ■
3KD9404-5 ■
Spare part for terminal covers
• Not permissible for 2000 A devices
Scope of supply Type Article No.
1 unit Standard version 3KD9504-1 ■
Short version 3KD9204-1 ■
3KD9304-1 ■
3KD9404-1 ■
Blocking pin test function
• Enables permanent deactivation of the test function for
auxiliary switches
• It is installed in the operating mechanism module of the
3KD switch disconnector
Scope of supply Article No.
10 units 3KF9112-1AA00 ■ ■
3KF9412-1AA00 ■ ■
3KF9512-1AA00 ■
Mounting brackets
• Spare part, included in the scope of supply of the 3KD
Scope of supply Article No.
4 units 3KD9120-1 ■ ■
3KF9212-0AA00 ■
3KF9412-0AA00 ■
3KF9512-0AA00 ■
Further accessories and spare parts Size 01 Size 02 Size 1 Size 2 Size 3 Size 4 Size 5
Slide for mounting on a DIN rail
• Spare part, included in the scope of supply of the 3KD
Scope of supply Article No.
5 units 3KF9112-0BA00 ■ ■
Accessories for DC applications Size 01 Size 02 Size 1 Size 2 Size 3 Size 4 Size 5
Connecting bridges
• Suitable for connecting 2 poles
• For 3KD switch disconnectors with 400 A, 800 A, 1250 A and
1600 A, two units are required.
Connection Article No.
Box terminals 3KD9118-1 ■
3KD9218-1 ■
3NP1
Further information
See page 8/94
The technical specifications apply to the standard types stated below.
For the complete specifications for all versions, see the Online Support
3NP1: 3-pole and 4-pole devices without fuse monitoring 3NJ4/5: Disconnectors for cable and line protection without fuse monitoring,
3NP5: Devices without fuse monitoring not for transformer protection
00 1 2 3 00 1 2 3 4a D01
6 17 17 17 – – – – – –
– – – – – 14.5 14.5 14.5 35 –
690 1) 690 1) 690 1) 690 1) 800 1000 1000 1000 1000 400
6 6 6 6 8 12 12 12 12 2.5
7.8 7.5 15 39 18 23 54 115 190 –
12 23 34 48 12 32 45 48 110 2.5
1600 1600 1600 1600 1400 1400 800 800 500 –
IP00/IP00 IP00/IP00 IP00/IP00 IP00/IP00 IP00/IP00 IP00/IP00 IP00/IP00 IP00/IP00 IP00/IP00 IP20/IP20
IP30/IP10 IP30/IP10 IP30/IP10 IP30/IP10 IP30/IP10 IP30/IP10 IP30/IP10 IP30/IP10 IP10/IP00 IP20/IP20
CCC
1)
Applies to degree of pollution 3 3)
Max. 9 W for operation up to 160 A
(for degree of pollution 2, use up to Ui 1000 V possible) 4)
3NP1 NH000 in narrow design only has IEC approval
2)
If optional infeed terminal is used max. 160 A
Basic units
1, 3, 4-pole for floor mounting 3 and 4-pole mounting on busbar systems
Connection parts
Terminals for retrofitting to 3NP1 Auxiliary conductor connections 3-phase busbars
Assembly kits
8
I201_19737
DIN-rail mounting Mechanical connection 1/4-pole busbar mounting Locking function Protection against power theft
I201_19726
Masking frames and supports Cable connection covers Reach-around protection for busbar
Further accessories
Auxiliary switches Isolating blades Fuse carriers with and without fuse monitoring
Note:
You will find a detailed range of accessories with the basic units.
General information
The new the 3NA COM LV HRC fuse links with communication and measuring function make your products
communication-capable.
Directly to 3NP1
Modular design configurator under:
sie.ag/3llXQZH
The fastest and simplest way to find the right switch combination is to use our 3NP1 configurator in the
Siemens Industry Mall.
3NP1 fuse switch disconnectors are available from the factory in 1, 3 and 4-pole device versions.
4-pole types are available in all common versions from the factory ready for installation (without fuse
monitoring, N-pole on the right-hand side).
All other conceivable device combinations, such as 2-pole 3NP1s, 4-pole with fuse monitoring or with a
neutral conductor on the left-hand side can simply be put together on site by combining two 3NP1s.
All that is needed for this in addition to the two 3NP1 basic units is the matching connection assembly kit
I201_19728
(see accessories).
All sizes of the 3NP1 fuse switch disconnec- The devices for floor mounting of sizes 000,
tors are available in floor mounting versions. 00 and 1 can also be mounted on a DIN rail
using accessories. For this purpose, the
The 3NP1 is mounted on a mounting panel assembly kit for mounting on a DIN rail is
with screws.
I201_19729
3-pole and 4-pole 3NP1 are available for 1-pole 3NP1 devices for wall mounting in
mounting on busbar systems. In the case of sizes 000 and 00 can be adapted to the 8US
4-pole devices, the infeed for the fourth pole 60 mm busbar system using the assembly kit
I201_19733
is supplied by the neutral conductor bar for 1-pole busbar mounting. Due to the
located above the 3 phases. modular design of the assembly kit, any
I201_19731
phase can be selected for the infeed.
The fuse monitoring is used to detect, indicate and signal that a fuse has tripped.
The fuse monitors are permanently installed on the handle of the 3NP1. They have floating contacts for
remote signaling of a tripped fuse and also indicate this locally.
Various versions of fuse monitors are available, which can be selected to suit the requirements of the
I201_19725
Common combinations of the 3NP1 basic unit and fuse monitoring are available from the factory ready for
installation. A fuse monitor can also be easily retrofitted by replacing the fuse carrier. (Fuse carriers for all fuse
monitoring versions are available as accessories.)
Note:
Fuses with insulated grip lugs cannot be used for 3NP1 with fuse monitoring.
3NP1 are available in versions with box terminals (all sizes) or flat terminals (sizes 00 and larger).
Various additional types of terminal are available as accessories for adaptation to the respective
wiring situation, e.g. prism, saddle or three-tier terminals.
1 2
I201_19734
3 4 5
Auxiliary switches enable remote querying of The assembly kit for protection from power 4-pole 3NP1s are used in 3-phase AC systems
the switch position of the 3NP1. Up to two theft seals the holes on the front of the 3NP1 with switched neutral conductors. They are
auxiliary switches can be installed. (for voltage testing) permanently, which supplied without an isolating blade for the N
reliably prevents unauthorized access to live pole. The switching instant is selected by
parts. choosing the appropriate isolating blade.
100
%
Power dissipation at partial load
80
The 3NP5 fuse switch disconnector is suitable for all fuses with LV HRC design in sizes 000 to 3 that comply
dissipated at rated current)
60
cable and line protection and motor protection.
40 Fuses for semiconductor protection (Siemens trademark SITOR) can also be used. However, some of these
fuses have substantially higher power losses than fuses according to IEC 60269-2. This means that the load
20
current has to be reduced until the value that is permissible in the fuse switch disconnector is not exceeded.
I201_12646
0 For use of SITOR semiconductor fuses, ready-made derating tables are available in the linked document.
0 20 40 60 80 100
Load current %
(as a % of rated current n )
For a complete and valid configuration of your fuse switch disconnectors, please use our online
configurator at www.siemens.com/lowvoltage/3np1-configurator
Flat terminals
NH00 NH1 NH2 NH3
Notes:
• On the 3NP1 with fuse monitoring, the permissible operational voltage is limited by the fuse monitoring
• Permissible operational voltage with fuse monitoring:
− MFM AC max. 690 V (L – L)/max. 440 V (L+ – L–)
− EFM10 230 … 690 V AC (L – L)
− EFM15 3-pole 190 … 690 V AC (L – L)
− EFM15 1-pole 24 … 240 V AC (L – N)/24 … 250 V DC (L+ – L–)
− EFM20 230 … 690 V AC (L – L)
• Additional variants are available as accessories:
− EFM15 with further operational voltage ranges
− EFM25 – DC version of the EFM20
• Devices for busbar mounting with reach-around protection
− For Siemens 8US, mounting is possible on the Wöhner Classic and Rittal RiLine systems without a floor pan
− For Rittal, mounting is possible on the RiLine60 system with a floor pan
Box terminals
NH000 narrow NH000 NH00 NH1 NH2 NH3
3NP1113-1BC20 1)
3NP1123-1JC20 3NP1133-1JC20 3NP1143-1JC20 3NP1153-1JC20 3NP1163-1JC20
– – 3NP1133-1JC21 3NP1143-1JC21 3NP1153-1JC21 3NP1163-1JC21
– 3NP1123-1JC22 3NP1133-1JC22 3NP1143-1JC22 3NP1153-1JC22 3NP1163-1JC22
– 3NP1123-1JC23 3NP1133-1JC23 3NP1143-1JC23 3NP1153-1JC23 3NP1163-1JC23
– 3NP1123-1BB20 3NP1133-1BB20 – – –
– – 3NP1133-1BB21 – – –
– 3NP1123-1BB22 3NP1133-1BB22 – – –
– 3NP1123-1BB23 3NP1133-1BB23 – – –
– 3NP1123-1JB20 3NP1133-1JB20 – – –
– – 3NP1133-1JB21 – – –
– 3NP1123-1JB22 3NP1133-1JB22 – – –
– 3NP1123-1JB23 3NP1133-1JB23 – – –
1)
The direction of the cable outlet for the load side cannot be changed on size NH000, narrow design
3NP1113-1BC20 → Cable outlet at the bottom
3NP1113-2BC20 → Cable outlet at the top
2)
If optional infeed terminal is used max. 160 A
8 70 … 150 mm2
120 … 240 mm2
3NP1941-1BB10 3NP1943-1BB10
3NP1951-1BB10 3NP1953-1BB10
■
■
150 … 300 mm2 3NP1961-1BB10 3NP1963-1BB10 ■
Double 2× 35 … 70 mm2 3NP1941-1BB20 3NP1943-1BB20 ■
2× 70 … 120 mm2 3NP1951-1BB20 3NP1953-1BB20 ■
2× 150 … 185 mm2 3NP1961-1BB20 3NP1963-1BB20 ■
Three-tier terminals
• Distributes one outgoing feeder directly to three
smaller loads
Type Conductor cross- Article No. Article No.
section
For 3NP1 3× 1.5 …16 mm2 3NP1931-1BE10 3NP1933-1BE10 ■
with flat terminals
For 3NP1 3× 1.5 …16 mm2 3NP1921-1BE20 3NP1923-1BE20 ■ ■
with box terminals
Connection module
• Used with a 3NP1 for busbar mounting if a
masking frame is to be supported on the 32 mm
cover plane (installation of the terminals under
the masking frame)
• For 3NP1 with flat terminals
Type Conductor cross- Article No. Article No.
section
Connection module 3× 6 … 70 mm2 3NP1931-1BC00 3NP1933-1BC00 ■
Infeed terminal
• Extends the conductor cross-section of a 000 with
box terminal to up to 95 mm²
Version Conductor cross- Article No. Article No.
section
Infeed terminal 16 … 95 mm2 3NP1921-1BD00 3NP1923-1BD00 ■
8 3NP1931-1EC00 ■
3NP1941-1EC00 ■ ■ ■
4-pole connection assembly kit for mounting on a 8US 60-mm busbar
• Connects a 3-pole 3NP1 for busbar mounting 60 mm 8US to a
1-pole 3NP1 for floor mounting
• The 1-pole 3NP1 switches the neutral conductor of a 3P+N system
in this combination
3NP1 connection Article No.
With flat terminals 3NP1934-1ED20 ■
With box terminals 3NP1924-1ED10 ■
3NP1934-1ED10 ■
With flat terminals or box terminals 3NP1944-1ED00 ■
3NP1954-1ED00 ■ ■
1-pole connection assembly kit for mounting on a 8US 60-mm busbar
• Permits adaptation of a 1-pole 3NP1 for floor mounting to a 3-pole
I201_199
46
busbar system
• The feeding busbar (L1, L2 or L3) can be chosen freely
• If two such 3NP1 are combined by mechanical connection using
the assembly kit, 2-pole 3NP1 for busbar mounting can also be
assembled
3NP1 connection Article No.
With box terminals 3NP1921-1EE10 ■
3NP1931-1EE10 ■
1)
Only for 3NP1 for mounting on busbar systems
2)
Only for 3NP1 with flat terminals
3)
Only for 3NP1 with flat terminals for floor mounting
3NP1940-1FB00 ■ ■ ■
Isolating blades
• Are used in a 3NP1 if only the isolating function of a 3NP1 is
required and not protection with fuses or in the neutral
conductor of a 4-pole 3NP1.
• The isolating blade, which is leading switch-on and lagging
switch-off, is used in the neutral conductor of a 4-pole 3NP1 if
shifting of the neutral point of the 3P+N system has to be
avoided during switching.
Version Article No.
Switching simultaneously with fuses 3NG1002 ■ ■ 8
3NG1202 ■
3NG1302 ■
3NG1402 ■
Leading switch-on, lagging switch-off 3NP1924-1MA20 ■
3NP1934-1MA20 ■
3NP1944-1MA20 ■
3NP1954-1MA20 ■
3NP1964-1MA20 ■
Basic units
Connection parts
Further accessories
Note:
You will find a detailed range of accessories with the basic units.
General information
The new the 3NA COM LV HRC fuse links with communication and measuring function make your products
communication-capable.
8
3NP50
3NP52
3NP54
The 3NP5 fuse switch disconnector is an extremely robust device for extreme operating conditions.
The fuse carrier has a pretensioned spring that prevents accidental, slow closure.
All 3NP5 are designed for mounting on a mounting plate. Size NH00 is also available in versions for 40 mm busbar systems.
All sizes can also be mounted using adapters on 60 mm busbar systems.
100
%
Power dissipation at partial load
80
dissipated at rated current)
(as a % of the power
60
40
20
I201_12646
0
0 20 40 60 80 100
Load current %
(as a % of rated current n )
The 3NP5 fuse switch disconnector is suitable for all fuses with LV HRC design in sizes 000 to 3 that comply with IEC 60269-2, including fuses for
cable and line protection and motor protection.
Fuses for semiconductor protection (Siemens trademark SITOR) can also be used. However, some of these fuses have substantially higher power losses
than fuses according to IEC 60269-2. This means that the load current has to be reduced until the value that is permissible in the fuse switch disconnector
is not exceeded.
For use of Siemens SITOR semiconductor fuses, ready-made derating tables are available in the linked document.
Flat terminals
NH00 NH1 NH2 NH3
Clamp terminals
Version Scope of supply Article No.
For retrofitting to 3NP5 with flat terminals 3 units 3NY1903 ■
3NY1907 ■
Busbar adapters
• For 60 mm busbar system
Version Article No.
For adaptation of a 3NP5, 8US1291-4SB00 ■
for floor mounting on a 60-mm busbar system 8US1210-4AG00 ■ ■ ■
Covers for cable lug connections
Version Scope of supply Article No.
Can be screwed onto the free end of the screw 6 units 3NY1241 ■
3NY1245 ■ ■
Covers for 3NP5, with auxiliary switch mounted
• With punched cutouts for auxiliary switches
Color Version Dimensions Article No.
Gray Flat 215 × 135 mm 3NY1115 ■
Black Flat, with additional bending edges 290 × 135 mm 3NY1116 ■
Arc chutes
• Spare part for arc chutes installed in the factory,
one unit per switch is required for NH00, three units for NH1 to NH3
Article No.
3NY4031 ■
3NY4011 ■
3NY4012 ■ ■
Assembly kits for flush mounting in front panel
Version Article No.
Assembly kit with cover and mounting accessories 3NY1208 ■
3NY1210 ■
3NY1211 ■
3NY1212 ■
Covers (spare part for assembly kit) 3NY1102 ■
3NY1103 ■
Fuse carriers
Version Article No.
Without fuse monitoring 3NY1074 ■
3NY1371 ■
3NY1372 ■
1-pole switchable
3-pole switchable
8 Accessories
Covers Adapters on Mounting and Busbar connection Fuses Current
busbar systems assembly elements assembly kits transformers
Note:
You will find a detailed range of accessories with the basic units.
General information
The new the 3NA COM LV HRC fuse links with communication and measuring function make your products
communication-capable.
100
8
%
Power dissipation at partial load
80
dissipated at rated current)
(as a % of the power
60
40
20
I201_12646
0
0 20 40 60 80 100
Load current %
(as a % of rated current n )
The 3NJ4 fuse switch disconnector is suitable for all fuses with LV HRC design in sizes 000 to 3 that comply with IEC 60269-2, including fuses for
cable and line protection.
1-pole switchable 3-pole switchable
Note:
• Fixing screws for mounting on busbars must be ordered separately.
10
8
11
185
1
185
2
8
3 4
1
4 6
7
7
14 12
13
2
15
16
1 Busbar support 7 Unequipped section cover, 50 mm 13 Switch disconnector, NH3, with EFM
2 Lateral masking frame support 8 Adapter, 185 mm to 185 mm 14 Assembly kit, 2 x 240 mm²
3 Switch disconnector, NH1 9 Cover, spacer 15 Busbar connection assembly kit, 4 x 185 mm²
4 Switch disconnector, NH2 10 Switch disconnector, NH00, 100 mm 16 Cover, NH1-3
5 Coupling of operating handle 11 Adapter, 100 mm to 185 mm
6 Switch disconnector, NH00, 185 mm 12 Blanking cover, 633 x 100 mm
Accessories
➒ Covers
• Additional touch protection when using cable lugs and as spacer
Size Busbar center-to-center spacing Version Article No.
NH00 100 mm Top and bottom 3NJ4912-1DA02
185 mm 100 mm for bottom 3NJ4912-1FA01
132 mm for top 3NJ4912-1FA00
⑯ NH1 … NH3 Connection for top and bottom 3NJ4912-1AA01
NH3 For double in-line disconnectors 3NJ4912-1EA00
Blanking covers
Version Length Width Busbar center-to-center spacing Article No.
For switchboard cutout 299 mm 50 mm 100 mm only 3NJ4912-2CA00
633 mm 50 mm 3NJ4912-2AA00
633 mm 100 mm 3NJ4912-2BA00
Fixing clips
Scope of supply Article No.
1 set = 4 units, including fixing accessories 3NJ4918-0AA00
Fixing screws
• For fitting 3NJ4103 switch disconnectors with integratable current transformers onto adapters
Scope of supply Article No.
1 set = 3 units 3NJ4918-0DC02
1)
Touch protection only suitable for 3NJ4103-3BF02
2)
Touch protection only suitable for 3NJ4101-3BF01 and 3NJ4103-3BF01
■ 1)
■ 2) ■ 2)
■ 2) ■ 2)
■ ■ ■ ■ ■
■ ■ ■ ■ ■
■
■ ■
■ ■ ■ ■ ■ ■ ■ ■ ■
■ ■ ■
■ ■ ■ ■ ■ ■ ■ ■ ■
■ ■ ■ ■ ■ ■ ■ ■ ■
■ ■ ■ ■ ■ ■ ■ ■ ■
■ ■ ■ ■ ■ ■ ■ ■ ■
■
■ ■
■
Accessories
➊ Busbar supports
• For screwing on the busbars
Version Article No.
For 100 and 185 mm busbar center-to-center spacing 3NJ5974-0AB
Grounding kits
Version Article No.
With connecting cable 25 mm2 3NJ4910-1AA00
Busbar terminals
• Not for devices with transformer installation
Version Article No.
For each fuse switch disconnector, 3 units are required 3NJ4911-3AA00
For more rapid mounting of the switch disconnectors onto the busbars (1 set = 3 units) 3NJ4911-3BA01
Saddle terminals
• 1 set = 3 units
Connection Article No.
Cu 1.5 … 70 mm2 3NJ4911-4AA00
8
Prism terminal assembly kits
• 1 set = 3 units
Connection Article No.
Al/Cu 10 … 70 mm2 3NJ4911-1AA00
Mounting hook
• 1 per in-line disconnector required
Article No.
3NJ4918-1AA00
Distance compensation
Version Article No.
For NH00 3NJ4915-1BA00
For fuse switch disconnectors, with integratable current transformers if no current transformer is built in 3NJ4915-2BA00
Terminal strips
Article No.
3NJ4915-1CA00
■ ■ ■ ■ ■ ■ ■ ■ ■
■ ■ ■ ■ ■ ■ ■
■ ■
■ ■ ■
■
8
■ ■
■ ■ ■
■ ■ ■ ■ ■ ■ ■ ■ ■
■ ■ ■
■
■ ■ ■
Accessories
Busbar connection assembly kits for NH2 and NH3
• With flat terminals
Screws Conductor cross-section Article No.
M12 2× 240 mm2 3NJ4911-5AA00
2× 300 mm2/3× 120 mm2 3NJ4911-5BA00
M16 1× 400 mm2 3NJ4911-5CA00
Busbar connection assembly kits for NH3
Version Conductor cross-section Article No.
For NH3 as double in-line disconnectors 3× 300 mm2/⑮ 4× 185 mm2 3NJ4911-6AA00
4× 240 mm2 3NJ4911-6BA00
■ ■ ■
■ ■ ■
■ ■ ■
■ ■
■ ■
■ ■
■ ■ ■ ■
8
■
■
■
■
■
■ ■ ■
■ ■ ■
■ ■ ■
■ ■ ■
■ ■ ■
■ ■ ■
■ ■ ■
■ ■ ■
■ ■ ■
■ ■ ■
■ ■ ■
■ ■ ■
■ ■ ■
■ ■ ■
■ ■ ■
Accessories
Current transformers .../5 A
Rated primary current Ipr Accuracy class Rated power Pn Article No.
100/5 A 0.5 1.0 VA 3NJ4915-1EB10
1 1.5 VA 3NJ4915-1EB20
150/5 A 0.5 1.5 VA 3NJ4915-1FB10
0.5 calibrated 1.5 VA 3NJ4915-1FB11
1 2.5 VA 3NJ4915-1FB20
75/5 A 1 1.5 VA 3NJ4915-2DB20
100/5 A 0.5 1.0 VA 3NJ4915-2EB10
1 2.0 VA 3NJ4915-2EB20
150/5 A 0.5 1.5 VA 3NJ4915-2FB10
1 2.5 VA 3NJ4915-2FB20
250/5 A 0.5 2.5 VA 3NJ4915-2GB10
0.5 calibrated 2.5 VA 3NJ4915-2GB11
1 3.75 VA 3NJ4915-2GB20
400/5 A 0.5 2.5 VA 3NJ4915-2HB10
0.5 calibrated 2.5 VA 3NJ4915-2HB11
1 5.0 VA 3NJ4915-2HB20
500/5 A 0.5 2.5 VA 3NJ4915-2JB10
1 5.0 VA 3NJ4915-2JB20
600/5 A 0.5 2.5 VA 3NJ4915-2KB10
8 0.5 calibrated 2.5 VA 3NJ4915-2KB11
1 5.0 VA 3NJ4915-2KB20
■
■
■
■
■
■ ■ ■
■ ■ ■
■ ■ ■
■ ■ ■
■ ■ ■
■ ■ ■
■ ■ ■
■ ■ ■
■ ■ ■
■ ■ ■
■ ■ ■
■ ■ ■
■ ■ ■
■ ■ ■
■ ■ ■ 8
■ ■ ■
1P 1P+N 2P 3P 3P+N
Number of poles 1P 1P+N 2P 3P 3P+N
I201_20443
I201_20444
I201_20445
I201_20447
I201_20446
Fuse size Rated current In Mounting width Mounting width Mounting width Mounting width Mounting width
1 MW 2 MW 2 MW 3 MW 4 MW
MINIZED fuse switch disconnectors
D01 6 A 1) 5SG7611-0KK06 – – 5SG7631-0KK06 –
10 A 5SG7611-0KK10 – – 5SG7631-0KK10 –
16 A 5SG7611-0KK16 5SG7651-0KK16 5SG7621-0KK16 5SG7631-0KK16 5SG7661-0KK16
1)
For 2 A, 4 A, 6 A fuses
Note: 8
No NEOZED adapter sleeves are required for this type series
3KF LV HRC
Size 1 1 1 2 2 3 4 5 5
General technical specifications acc. to IEC 60947-3
Basic data
Rated uninterrupted current Iu A 32 63 80 125 160 250 400 630 800
For fuse links acc. to IEC 60269-2 000 and 00 0 and 1 1 and 2 2 and 3
Rated operational voltage Ue At 50/60 Hz AC V AC 690
At DC - 2 conducting paths V DC 220
in series
At DC - 3 conducting paths V DC 440
in series
At DC V DC –
Operating and short-circuit behavior
Rated operational current Ie 1) At AC-21A | AC-21B at 400 V A 32 63 80 125 160 250 400 630 800
At AC-21A | AC-21B at 500 V A – – – – – – – – –
At AC-21A | AC-21B at 690 V A 32 63 80 125 160 250 400 630 800
At AC-22A | AC-22B at 400 V A 32 63 80 125 160 250 400 630 800
At AC-22A | AC-22B at 500 V A – – – – – – – – –
At AC-22A | AC-22B at 690 V A 32 63 80 125 160 250 400 630 800
8 At AC-23A | AC-23B at 400 V A 32 63 80 125 160 250 400 630 800
At AC-23A | AC-23B at 500 V A – – – – – – – – –
At AC-23A | AC-23B at 690 V A 32 63 80 125 160 250 400 630 800
At DC-21A | DC-21B at 48 V A – – – – – – – – –
At DC-21A | DC-21B at 65 V A – – – – – – – – –
At DC-21A | DC-21B at 110 V A – – – – – – – – –
At DC-21A | DC-21B at 130 V A – – – – – – – – –
At DC-21A | DC-21B at 220 V A 32 63 80 125 160 250 400 630 800
At DC-21A | DC-21B at 400 V A – – – – – – – – –
At DC-21A | DC-21B at 440 V A 32 63 80 125 160 250 400 630 800
At DC-22A | DC-22B at 48 V A – – – – – – – – –
At DC-22A | DC-22B at 65 V A – – – – – – – – –
At DC-22A | DC-22B at 110 V A – – – – – – – – –
At DC-22A | DC-22B at 130 V A – – – – – – – – –
At DC-22A | DC-22B at 220 V A 32 63 80 125 160 250 400 630 800
At DC-22A | DC-22B at 400 V A – – – – – – – – –
At DC-22A | DC-22B at 440 V A 32 63 80 125 160 250 400 630 800
At DC-23A | DC-23B at 48 V A – – – – – – – – –
At DC-23A | DC-23B at 110 V A – – – – – – – – –
At DC-23A | DC-23B at 220 V A 32 63 80 125 160 250 400 630 800
At DC-23A | DC-23B at 400 V A – – – – – – – – –
At DC-23A | DC-23B at 440 V A 32 63 80 125 160 250 400 630 800
Motor switching capacity 2) At AC-23A at 400 V kW 15 30 37 55 90 132 220 355 400
At AC-23A at 500 V kW 18.5 37 55 75 110 160 280 400 560
At AC-23A at 690 V kW 30 55 75 110 132 250 400 630 800
Rated conditional short-circuit current At 400/500 V AC kA 100 100 100 100 100 100 100 100 100
with upstream fuse 3) At 690 V AC kA 100 100 100 100 100 100 100 80 80
Let-through current Ic At 400/500 V AC kA 11.8 11.8 11.8 18 18 33.7 37.1 77.4 77.4
of usable fuses, max. 3) At 690 V AC kA 11.5 11.5 11.5 25.5 25.5 37.7 47 65 65
Let-through current I2t value At 400/500 V AC kA2s 34 34 34 223 223 1500 2150 10400 10400
of usable fuses, max. 3) At 690 V AC kA2s 55 55 55 360 360 940 2600 7000 7000
Maximum power loss of the usable fuses (per fuse) W 6.5 7.5 8.5 11 12 25.5 34 48 60
Degree of protection
Maximum IP degree of protection (with a rotary operating mechanism) IP65 IP65
Maximum IP degree of protection – –
1)
Values valid even at +10% line voltage tolerance 2)
Values are provided as a guide only and 3)
Valid for combination of 3KF and fuse type 3NA/3ND,
in case of AC may vary depending on the make of motor characteristic gG/aM
440 – – – – – – –
– – – – – 65 – –
IP65 IP41 – – –
– – IP20 – –
3KF LV HRC
Size 1 1 1 2 2 3 4 5 5
General technical specifications acc. to UL
Basic data
Certification according to UL standard – – – – – – – – –
In acc. to UL 508 A – – – – – – – – –
Ue acc. to UL 508 – – – – – – – – –
Operating and short-circuit behavior
Operational power, 3-phase At 240 V kA – – – – – – – – –
At 480 V kA – – – – – – – – –
At 600 V kA – – – – – – – – –
Short circuit current rating (SCCR) – – – – – – – – –
Fuse type – – – – – – – – –
Further information
8 See page 8/126
Technical specifications Configuration in SIMARIS
UL 508 – – – – – – – – – – –
32 56 56 125 125 500 320 530 530 – – – – – – – – – – –
600 – – – – – – – – – – –
Basic units
Front operating Front operating Lateral operating mecha- Lateral operating mecha- 3KF SITOR
mechanisms, 3-pole mechanisms, 4-pole nisms, 3-pole nisms, 4-pole
8 Additional poles
Operating mechanisms
Direct operating Door-coupling rotary opera- Handles for door-coupling Further accessories for door-coupling
mechanisms ting mechanisms rotary operating mechanisms rotary operating mechanisms
Auxiliary switches Fuse monitoring Terminal covers Mounting elements Fuse covers
Note:
You will find a detailed range of accessories with the basic units.
General information
The new the 3NA COM LV HRC fuse links with communication and measuring function make your products
communication-capable.
100
8
%
Power dissipation at partial load
80
dissipated at rated current)
The 3KF switch disconnector with fuses is suitable for all fuses with LV HRC design in sizes 000 to 3 that comply
with IEC 60269-2. These include fuses for cable and line protection and motor protection.
(as a % of the power
60
Fuses for semiconductor protection (Siemens trademark SITOR) can also be used. However, some of these fuses
40
have substantially higher power losses than fuses according to IEC 60269-2. This means that the load current
20
has to be reduced until the value that is permissible in the switch disconnector with fuses is not exceeded.
For use of Siemens semiconductor fuses (SITOR), ready-made derating tables are available in the
I201_12646
0 linked document.
0 20 40 60 80 100
Load current %
(as a % of rated current n )
I201_19581
All 3KF switch disconnectors with fuses Size 1 can be snapped onto a DIN rail (TH35 according to EN 60715)
are designed for floor mounting. as an alternative mounting method.
I201_19585
I201_19579
I201_19572
NN
/N
/N
The box terminals for size 1 (32 A … 80 A) Sizes 2 … 5 are available with flat terminals, Sizes 1 and 2 (32 A, 63 A and 125 A) are
are designed to allow the rapid connection for the connection of cable lugs or available with rear flat terminals, for the
of stripped conductors. busbar systems. connection of cable lugs or busbar systems.
Size 1 Sizes 2 … 5
I201_19571
I201_19568
1
1 Auxiliary switch,
2
2 leading
1 2 Auxiliary switch,
1 simultaneous
The auxiliary switches used for size 1 are microswitches For sizes 2 … 5, the auxiliary switches are directly attached to the
(changeover contacts), which can be snapped into an auxiliary switch operating mechanism module. The auxiliary switch with the leading
module. This auxiliary switch module is mounted on the side of the switching function is always installed in the right-hand mounting
switch disconnector with fuses in the same way as an additional pole. location. The other locations are provided for simultaneously switching
A maximum of two microswitches can be installed in each with the main contacts. Auxiliary switches with spring-type terminals
auxiliary switch module. from the 3SU1 program can also be used.
Size 1 Sizes 2 … 5
SITOR semiconductor fuse data Permissible load currents of fuse when installed in
3NE8021-1 100 690 aR 00 22 32.0 63.0 60.0 79.0 82.0 32.0 63.0 68.0 100.0 100.0
I201_20559
3NE8022-1 125 690 aR 00 28 32.0 63.0 70.0 90.0 92.5 32.0 63.0 75.0 125.0 125.0
3NE8024-1 160 690 aR 00 38 --- 63.0 80.0 100.8 104.0 32.0 63.0 80.0 125.0 140.0
3KF SITOR is a variation of the proven switch disconnector with Siemens provides you with pretested load currents of the
3KF LV HRC fuses and provides optimized heat dissipation and SITOR semiconductor fuses for installation in the 3KF SITOR.
permits the use of fuses with substantially higher power losses. The derating tables are provided both for IEC constraints and
All 3KF SITOR types are approved according to UL508. for UL constraints and are intended to help you with selection.
The permissible load faults for the 3KF LV HRC were calculated
from the test results of the 3KF SITOR.
8
ಮ
5 ಮ
5 ಮ
5 ಮ
5
3 or 4a
4
or
33
2 or
4a
4a
2 or
1 or
1 or
2 N/PE terminal
3 4th contact element 1)
and and if 4 and and if 4a and
4 Auxiliary switch module, leading, with
ಮ
5 ಮ
5
ಱ
8 ಮ
5 ಮ
5 test function 2)
4a Auxiliary switch module
for auxiliary switches 2)
or
5 Auxiliary switch
8 Direct operating mechanism
9 Door-coupling rotary operating
ಲ
9
mechanism
8
I201_20494
1)
Only for 3-pole 3K, max. 1×
2)
Max. 1×
5 5 5 5
3 or 4a
4a
2 or
2 or
1 or
2 N/PE terminal
3 4th contact element 1)
and and if 4a and and if 4a and
4a Auxiliary switch module
5 5 8 5 5 for auxiliary switches 2)
5 Auxiliary switch
or
8 Direct operating mechanism
9 Door-coupling rotary
operating mechanism
9 1)
Only for 3-pole 3K, max. 1×
2)
Max. 1×
I201_20595
6 or 7 6 or 7 6 or 7
and and and
3
3
or
or
optional optional
and
2
2
and
Legend
or
or
1 Neutral conductor terminal
1
1
2 N/PE terminal
3 4th contact element 1)
and and and 5 Auxiliary switch 2)
6 or 7 6 or 7 6 or 7 6 Phase barrier
and and 7 Terminal cover
8 Direct operating mechanism
5 8 9 Door-coupling rotary operating mechanism
or
1)
Only for 3-pole 3K, max. 1×
2)
Max. 4×
9 8
I201_20596
5 5
Legend
and if 4a and 1 Neutral conductor terminal
2 N/PE terminal
3 or 4a
3 4th contact element 1)
4a Auxiliary switch module for
optional optional auxiliary switches 2)
9
4a
and
2 or
and and 5 Auxiliary switch
9 Door-coupling rotary operating
mechanism
1 or
10 Lateral auxiliary switch module
I201_20497
10 5 5
6 or 7 6 or 7
and and
Legend
1 Neutral conductor terminal
3
2 N/PE terminal
2 or
6 Phase barrier
7 Terminal cover
9 Door-coupling rotary
and and
operating mechanism
6 or 7 6 or 7
1)
Only for 3-pole 3K, max. 1×
and
2)
Max. 4×
I201_20598
Legend
5 5
1 Neutral conductor terminal
and and if 4a 2 N/PE terminal
3 4th contact element 1)
3 or 4a
and
2 or
1)
Only for 3-pole 3K, max. 1×
2)
Max. 1×
and and if 4a and
I201_20499
5 5 10
6 or 7 6 or 7
and and
Legend
1 Neutral conductor terminal
2 N/PE terminal
3
optional
and 9 5 Auxiliary switch 2)
and
6 Phase barrier
1 or
7 Terminal cover
9 Door-coupling rotary
operating mechanism
and and
1)
Only for 3-pole 3K, max. 1×
6 or 7 6 or 7 2)
Max. 4×
and
I201_20500
Complete units with direct operating mechanisms Basic units without handle
Front operating mechanisms, Front operating mechanisms, Front operating mechanism,
left left center
Number of poles 3P 4P 3P 4P 3P
Size Uninterrupted
current Iu
Box terminals
1 32 A 3KF1303-2LB11 3KF1403-2LB11 3KF1303-0LB11 3KF1403-0LB11 3KF1303-0MB11
63 A 3KF1306-2LB11 3KF1406-2LB11 3KF1306-0LB11 3KF1406-0LB11 3KF1306-0MB11
80 A 3KF1308-2LB11 3KF1408-2LB11 3KF1308-0LB11 3KF1408-0LB11 3KF1308-0MB11
Flat terminals at rear
1 32 A – – – – 3KF1303-0MR11
8 2
63 A
125 A
–
–
–
–
–
–
–
–
3KF1306-0MR11
3KF2312-0MR11
Flat terminals
2 125 A 3KF2312-2LF11 3KF2412-2LF11 3KF2312-0LF11 3KF2412-0LF11 3KF2312-0MF11
160 A 3KF2316-2LF11 3KF2416-2LF11 3KF2316-0LF11 3KF2416-0LF11 3KF2316-0MF11
3 250 A 3KF3325-2LF11 3KF3425-2LF11 3KF3325-0LF11 3KF3425-0LF11 3KF3325-0MF11
4 400 A 3KF4340-2LF11 3KF4440-2LF11 3KF4340-0LF11 3KF4440-0LF11 3KF4340-0MF11
5 630 A 3KF5363-2LF11 3KF5463-2LF11 3KF5363-0LF11 3KF5463-0LF11 3KF5363-0MF11
800 A 3KF5380-2LF11 3KF5480-2LF11 3KF5380-0LF11 3KF5480-0LF11 3KF5380-0MF11
Note:
• NH00 and NH000: For 3KF sizes 1 and 2
• NH1 and NH0: For 3KF size 3
• NH2 and NH1: For 3KF size 4
• NH3 and NH2: For 3KF size 5
• For 3KF with lateral operating mechanism (left or right), only door-coupling rotary operating mechanisms without "Test" can be used.
• The complete units with a direct operating mechanism are not suitable for conversion to door-coupling rotary operating mechanisms;
the basic units are to be used for this purpose.
– – – – –
–
–
–
–
–
–
–
–
–
–
8
Note:
• Use of standard LV HRC fuses gG, gL, aM in 3KF SITOR is possible without restriction
Door-coupling rotary operating mechanisms, for 3KF LV HRC and 3KF SITOR
• Scope of supply:
− Handle with masking plate
− Coupling driver with tolerance compensation
− Shaft 300 mm
• Can be locked with up to max. 3 padlocks
Inscription Color Article No.
Test – O – I Gray 8UD1171-2AF21 ■
8UD1141-2AF21 ■
8UD1141-3AF21 ■
8UD1151-3AF21 ■
8UD1161-4AF21 ■
Red/yellow 8UD1171-2AF25 ■
8UD1141-2AF25 ■
8UD1141-3AF25 ■
8UD1151-3AF25 ■
8UD1161-4AF25 ■
Handles, for 3KF LV HRC and 3KF SITOR
• With masking plate
• Can be locked with up to max. 3 padlocks
Inscription Lighting Color Article No.
O – I Without Gray 8UD1771-2AD01 ■
8 8UD1841-2AD01 ■ ■
8UD1851-3AD01 ■
8UD1861-4AD01 ■
Red/yellow 8UD1771-2AD05 ■
8UD1841-2AD05 ■ ■
8UD1851-3AD05 ■
8UD1861-4AD05 ■
With Gray 8UD1771-2CD01 ■
8UD1841-2CD01 ■ ■
8UD1851-3CD01 ■
8UD1861-4CD01 ■
Red/yellow 8UD1771-2CD05 ■
8UD1841-2CD05 ■ ■
8UD1851-3CD05 ■
8UD1861-4CD05 ■
Test – O – I Without Gray 8UD1771-2AF01 ■
8UD1841-2AF01 ■ ■
8UD1851-3AF01 ■
8UD1861-4AF01 ■
Red/yellow 8UD1771-2AF05 ■
8UD1841-2AF05 ■ ■
8UD1851-3AF05 ■
8UD1861-4AF05 ■
With Gray 8UD1771-2CF01 ■
8UD1841-2CF01 ■ ■
8UD1851-3CF01 ■
8UD1861-4CF01 ■
Red/yellow 8UD1771-2CF05 ■
8UD1841-2CF05 ■ ■
8UD1851-3CF05 ■
8UD1861-4CF05 ■
Further accessories and spare parts Size 1 Size 2 Size 3 Size 4 Size 5
Further accessories and spare parts Size 1 Size 2 Size 3 Size 4 Size 5
Auxiliary switches, for 3KF LV HRC and 3KF SITOR
• Auxiliary switches for sizes 2 to 5 have a screw terminal and are
mounted on the 3KF operating mechanism module. Auxiliary
switches with spring-type terminals from the 3SU1 program can also
be used.
• All auxiliary switches for sizes 2 to 5 can be used as leading
auxiliary switches, depending on the mounting position of the
auxiliary switch (see operating instructions).
Type Contacts Contact surface Article No.
With connecting cables 1 CO Standard 3KD9103-1 ■
Solid-state compatible 3KD9103-3 ■
Without connecting cables 1 CO Standard 3KD9103-2 ■
Solid-state compatible 3KD9103-4 ■
1 NO Standard 3SU1400-1AA10-1BA0 ■ ■ ■ ■
Gold-plated 3SU1400-1AA10-1LA0 ■ ■ ■ ■
1 NC Standard 3SU1400-1AA10-1CA0 ■ ■ ■ ■
Gold-plated 3SU1400-1AA10-1MA0 ■ ■ ■ ■
1 NO + 1 NC Standard 3SU1400-1AA10-1FA0 ■ ■ ■ ■
Gold-plated 3SU1400-1AA10-1QA0 ■ ■ ■ ■
2 NO Standard 3SU1400-1AA10-1DA0 ■ ■ ■ ■
Gold-plated 3SU1400-1AA10-1NA0 ■ ■ ■ ■
2 NC Standard 3SU1400-1AA10-1EA0 ■ ■ ■ ■
Gold-plated 3SU1400-1AA10-1PA0 ■ ■ ■ ■
Electronic fuse monitoring, for 3KF LV HRC and 3KF SITOR
Version Article No.
8 For remote display of tripped fuses 3KF9010-1AA00 ■ ■ ■ ■ ■
Further accessories and spare parts Size 1 Size 2 Size 3 Size 4 Size 5
Blocking pin test function, for 3KF LV HRC and 3KF SITOR
• Enables permanent deactivation of the test function for
auxiliary switches
• It is installed in the operating mechanism module of the
3KF switch disconnector
Scope of supply Article No.
10 units 3KF9112-1AA00 ■
3KF9412-1AA00 ■ ■
3KF9512-1AA00 ■
Mounting brackets, for 3KF LV HRC
• The 3KF9112-0AB00 mounting bracket is needed if an
auxiliary switch module is mounted on a 3KF1 with rear terminals
Connection Article No.
Box terminals, flat terminals 3KF9112-0AA00 ■
3KF9212-0AA00 ■
Flat terminals at rear 3KF9212-0AB00 ■ ■
Mounting brackets, for 3KF SITOR
Connection Article No.
Box terminals, flat terminals 3KF9112-0AA10 ■
3KF9212-0AA10 ■
NH 000 NH 00 NH 1 NH 2 NH 3
LV HRC isolating blades, for 3KF LV HRC and 3KF SITOR
Version Article No.
With insulated grip lugs 3NG1002 ■ ■
3NG1202 ■
3NG1302 ■
3NG1402 ■
Fuse links
Accessories
Note:
8 You will find a detailed range of accessories with the basic units.
General information
The new the 3NA COM LV HRC fuse links with communication and measuring function make your products
communication-capable.
100
8
%
Power dissipation at partial load
80
dissipated at rated current)
(as a % of the power
60
40
20
I201_12646
0
0 20 40 60 80 100
Load current %
(as a % of rated current n )
The 3NJ63 switch disconnector with fuses is suitable for all fuses with LV HRC design in sizes 000 to 3 that comply with IEC 60269-2, including fuses for
cable and line protection.
For a complete and valid configuration of your switch disconnectors with fuses, please use our online
configurator at www.siemens.com/lowvoltage/3nj63-configurator
6 7 8 9 10 11 12 13 14 15 16
3NJ63 – A 0 –
8
Electronic fuse moni- Without A
toring ≤690 V AC Operate voltage <20 V EFM10 B
≤690 V AC Operate voltage <13 V EFM20 C
with line monitoring
≤440 V DC Operate voltage <20 V EFM25 E
1)
Only in AC-22B
6 7 8 9 10 11 12 13 14 15 16
3NJ63 – –
Terminals
Type Article No.
For 2/3-pole devices 3NJ6923-1BA00 ■
3NJ6933-1BA00 ■
3NJ6943-1CA00 ■ ■
For 4-pole devices 3NJ6924-1BA00 ■
3NJ6934-1BA00 ■
3NJ6944-1CA00 ■ ■
Terminal covers
Type Version Article No.
For 2/3-pole – 3NJ6923-1DA00 ■
devices 3NJ6933-1DA01 ■
3NJ6943-1DA00 ■ ■
As an internal terminal cover 3NJ6933-1DB00 ■
For 4-pole devices 3NJ6904-1DA00 ■ ■ ■ ■
Contact extensions
Number of poles Article No.
3-pole 3NJ6923-1EB00 ■
3NJ6933-1EB00 ■
3NJ6943-1EB00 ■ ■
8 4-pole 3NJ6924-1EB00 ■
3NJ6934-1EB00 ■
3NJ6944-1EB00 ■ ■
Electronic fuse monitoring and line monitoring devices
Type Version Article No.
EFM 10 With line monitoring for AC networks 3NJ6920-3FB00 ■
3NJ6930-3FB00 ■
3NJ6940-3FB00 ■ ■
EFM 20 With line monitoring for AC networks 3NJ6920-3FC00 ■
3NJ6930-3FC00 ■
3NJ6940-3FC00 ■ ■
EFM 25 With line monitoring for AC networks 3NJ6920-3FE00 ■
3NJ6930-3FE00 ■
3NJ6940-3FE00 ■ ■
Auxiliary switches
Contacts Version Article No.
1 NO With cover 3NJ6920-2BB00 ■
3NJ6930-2BB00 ■
3NJ6940-2BB00 ■ ■
Without cover 3NJ6900-2BC00 ■ ■ ■ ■
1 NC With cover 3NJ6920-2CB00 ■
3NJ6930-2CB00 ■
3NJ6940-2CB00 ■ ■
Without cover 3NJ6900-2CC00 ■ ■ ■ ■
Amperemeter
Type Version Rated current Ie Article No.
Moving-iron For measurements on transformer 50 A/1 A 3NJ6900-4HB11 ■ ■
measuring x/1 A with double overload 100 A/1 A 3NJ6900-4HD11 ■ ■
8 instruments 150 A/1 A 3NJ6900-4HE11 ■ ■
200 A/1 A 3NJ6900-4HF11 ■
250 A/1 A 3NJ6900-4HG11 ■
300 A/1 A 3NJ6900-4HH11 ■ ■
400 A/1 A 3NJ6900-4HJ11 ■ ■
500 A/1 A 3NJ6900-4HK11 ■ ■
600 A/1 A 3NJ6900-4HL11 ■ ■
For measurements on transformer 50 A/5 A 3NJ6900-4HB21 ■ ■
x/5 A with double overload 100 A/5 A 3NJ6900-4HD21 ■ ■
150 A/5 A 3NJ6900-4HE21 ■ ■
200 A/5 A 3NJ6900-4HF21 ■
250 A/5 A 3NJ6900-4HG21 ■
300 A/5 A 3NJ6900-4HH21 ■ ■
400 A/5 A 3NJ6900-4HJ21 ■ ■
500 A/5 A 3NJ6900-4HK21 ■ ■
600 A/5 A 3NJ6900-4HL21 ■ ■
Bi-metal For measurements on transformer 50 A/1 A 3NJ6900-4HB12 ■ ■
measuring x/1 A with 1.2-times overload 100 A/1 A 3NJ6900-4HD12 ■ ■
instruments 150 A/1 A 3NJ6900-4HE12 ■ ■
200 A/1 A 3NJ6900-4HF12
250 A/1 A 3NJ6900-4HG12
300 A/1 A 3NJ6900-4HH12 ■ ■
400 A/1 A 3NJ6900-4HJ12 ■ ■
500 A/1 A 3NJ6900-4HK12 ■ ■
600 A/1 A 3NJ6900-4HL12 ■ ■
For measurements on transformer 50 A/5 A 3NJ6900-4HB22 ■ ■
x/5 A with 1.2-times overload 100 A/5 A 3NJ6900-4HD22 ■ ■
150 A/5 A 3NJ6900-4HE22 ■ ■
200 A/5 A 3NJ6900-4HF22 ■
250 A/5 A 3NJ6900-4HG22 ■
300 A/5 A 3NJ6900-4HH22 ■ ■
400 A/5 A 3NJ6900-4HJ22 ■ ■
500 A/5 A 3NJ6900-4HK22 ■ ■
600 A/5 A 3NJ6900-4HL22 ■ ■
Multi-function plugs
Version Dimensions Article No.
With fixing 6 × 2.5 mm2 3NJ6920-3EB01 ■ ■
screws 8 × 2.5 mm2 3NJ6920-3ED01 ■ ■
3NJ6940-3EC00 ■ ■
Without fixing 8 × 2.5 mm2 3NJ6940-3ED00 ■ ■
screws 10 × 1.5 mm2 and 8 × 2.5 mm2 3NJ6920-3EE01 ■ ■
12 × 1.5 mm2 and 8 × 2.5 mm2 3NJ6940-3EF00 ■ ■
Front panels
Use Version Article No.
3NJ6303-..... With LV HRC fuse 3NJ6923-4BB00 ■
3NJ6313-..... With LV HRC fuse 3NJ6933-4BB00 ■
3NJ6323-..... With LV HRC fuse 3NJ6943-4BB00 ■ ■
3NJ6333-..... With LV HRC fuse 3NJ6953-4BB00 ■ ■
Busbar covers
Article No.
3NJ6916-4EA00 ■ ■ ■ ■
Blanking covers
Article No.
3NJ6900-4CB00 ■ ■ ■ ■
Connection modules 8
Article No.
3NJ6915-3BA00 ■ ■ ■ ■
Guide rails
Overall depth Article No.
200 mm 3NJ6900-4FB00 ■ ■ ■ ■
400 mm 3NJ6900-4FC00 ■ ■ ■ ■
LV HRC fuse puller tongs new
Version Article No.
For NH00 8PQ9400-1AA50 ■
For NH1, NH2, NH3 8PQ9400-1AA51 ■ ■ ■
Locking devices for padlocks
Article No.
3NJ6900-4LL ■ ■ ■ ■
1P 3P
Accessories
8
Auxiliary switches Lateral modules Reducers
Note:
You will find a detailed range of accessories with the basic units.
2 2 N 2 4 2 4 6 2 4 6 N
Fuse size Rated Mounting width Mounting width Mounting width Mounting Mounting Mounting
current In width width width
1.5 MW 3 MW 3 MW 1.5 MW 4.5 MW 6 MW
MINIZED switch disconnectors with fuses 1) 3)
D02 63 A 5SG7113 5SG7153 5SG7123 – 5SG7133 5SG7163
MINIZED switch disconnectors with fuses – version for Austria only 2) 3)
D02 25 A – – – – 5SG7133-8BA25 –
35 A – – – – 5SG7133-8BA35 –
50 A – – – – 5SG7133-8BA50 –
NEOZED bus-mounting switch disconnectors 8
D02 63 A – – – 5SG7230 4) – –
NEOZED bus-mounting switch disconnectors, without LED signal detector
D02 63 A – – – 5SG7234-1 5) – –
NEOZED bus-mounting switch disconnectors, with LED signal detector
D02 63 A – – – 5SG7234-2 5) – –
1)
Using withdrawable design with touch protection according to BGV A3, adapter sleeves not included in the scope of delivery
2)
With permanently fitted adapter sleeves, incl. fuse link
3)
Do not use fuse links with nickel-plated contact caps
4)
In the case of permanent load over 35 A, we recommend the use of 5SH5526 lateral modules. Please observe EN 60439-1, Table 1
5)
In the case of permanent load over 35 A, we recommend the use of 5SH5533 lateral modules. Please observe EN 60439-1, Table 1
Note:
NEOZED adapter sleeves are required for these devices
Accessories
Auxiliary switches
Version Type Mounting width Contacts Article No.
For MINIZED D02 switch disconnectors Standard 0.5 MW 1 NO + 1 NC 5ST3010
2 NO 5ST3011
2 NC 5ST3012
With test button 0.5 MW 1 NO + 1 NC 5ST3010-2
2 NO 5ST3011-2
2 NC 5ST3012-2
For NEOZED bus-mounting Standard 0.5 MW 1 CO 5SH5525
switch disconnectors
Lateral modules
Version Type Mounting width Article No.
For NEOZED bus-mounting 5SG7230 0.5 MW 5SH5526
switch disconnectors 5SG7234-1 and -2 0.5 MW 5SH5533
Reducers
Version Article No.
For D01 fuse links 5SH5527
Applications 9/6
Information + ordering
All the important things at a glance Everything you need for your order
For information about transfer switching equipment and Refer to the Industry Mall for an overview of your
load transfer switches, please visit our website products
www.siemens.com/switching-devices
• Transfer switching equipment and load transfer
Our white paper provides you with a good overview of switches sie.ag/2mmMw6g
the transfer switching equipment sie.ag/2XBonIi
Direct forwarding to the individual products in the
Industry Mall by clicking on the article number in the
catalog or entering this web address incl. article number
Your product in detail www.siemens.com/product?Article No.
The Siemens Industry Online Support (SIOS) provides Order supports are available in Siemens Industry Online
comprehensive information Support (SIOS) at
www.siemens.com/lowvoltage/product-support www.siemens.com/lowvoltage/product-support
• Technical Basic Information • Order Support
− Switch disconnectors and transfer switching − 3KC automatic transfer switching equipment (ATSE)
equipment (109763354) – End-to-end safety for user and systems
(109755620)
9 The relevant tender specifications can be found at
− 3KC remotely operated transfer switching equipment
www.siemens.com/lowvoltage/tenderspecifications
(RTSE) – End-to-end safety for user and systems
Use our conversion tool for quick and easy conversion to (109755627)
Siemens products www.siemens.com/conversion-tool − 3KC manual transfer switching equipment (MTSE)
– End-to-end safety for user and systems
(109750227)
Commissioning + operation
The Siemens Industry Online Support (SIOS) provides Manuals are available for downloading in Siemens
comprehensive information Industry Online Support (SIOS) at
www.siemens.com/lowvoltage/product-support www.siemens.com/lowvoltage/manuals
• Operating instructions • Configuration Manual
• Certificates − Transfer switching equipment and load transfer
Comprehensive mobile support via the Siemens Industry switches (109769745)
Online Support app available for download from the • Equipment Manual
App Store and Play Store − 3KC3 and 3KC6 transfer switching equipment
You will find further information at (109754954)
www.siemens.com/support-app − 3KC0 manual transfer switching equipment
(109763232)
Provision of 3D data (step and u3d data formats) − 3KC4 and 3KC8 transfer switching equipment
• Siemens Industry Mall (109738725)
www.siemens.com/lowvoltage/mall − 3KC ATC3100 transfer control device (100341671)
• Image database − 3KC ATC6300 transfer control device (109755149)
www.siemens.com/lowvoltage/picturedb − 3KC ATC6500 transfer control device (109758018)
Engineering data for CAD or CAE systems are available in
the CAx Download Manager at
www.siemens.com/cax
System overview
3KC3 (RTSE), 4-pole 3KC4 (RTSE), 3 and 4-pole 3KC6 (ATSE), 4-pole 3KC8 (ATSE), 3 and 4-pole
Bridging bars Auxiliary Terminal covers Autotransformers Dual power Power supply and voltage
switches supply sensing cables
Accessories, MTSE
Bridging bars 4th contact Auxiliary switches Direct operating Door-coupling Phase barriers Terminal covers
element mechanisms rotary operating
mechanisms
Note:
You will find a detailed range of accessories in the Accessories section.
Front mounting Floor mounting Molded-plastic 4th contact N/PE terminal Auxiliary Terminal covers
3LD2 3LD2 enclosures 3LD2 element switches
3KC ATC3100 3KC ATC6300 3KC ATC6500 Expansion modules Front interface Protective seal
Note:
You will find a detailed range of accessories in the Accessories section.
Applications
9 Further information From page 9/24 From page 9/17 From page 9/17 From page 9/17 From page 9/17
onwards onwards onwards onwards onwards
1)
Manual load transfer switch, not an MTSE
Transfer control G G
G G G G
Non-
Priority
I201_20422
I201_20395
I201_20517
priority
Load Load load
load
With circuit breakers
With switch disconnectors With circuit breakers
and automatic load shedding
Load transfer
I201_20518
Load 1 Load 2
With switch disconnectors
3LD2 3KC ATC3100 (+ 3VA/3WA/3WL) 3KC ATC6300 (+ 3VA/3WA/3WL) 3KC ATC6500 (+ 3VA/3WA/3WL)
■ – – –
– – – –
– ■ ■ ■
■ 1) – – –
– ■ ■ ■
– ■ ■ ■
– ■ ■ ■
– ■ ■ ■
– – ■ ■
25 … 250 A 3VA: 16 … 630 A, 3WA/3WL: 630 … 6300 A 3VA: 16 … 630 A, 3WA/3WL: 630 … 6300 A 3VA: 16 … 1600 A, 3WA/3WL: 630 … 6300 A
3 and 4 3 and 4 3 and 4 3 and 4
– – ■ ■
– – – ■
From page 9/30 From page 9/32 From page 9/32 From page 9/32
9
onwards onwards onwards onwards
3KC4.38 3KC4.42 3KC4.46 3KC4.48 3KC4.50 3KC4.52 3KC4.54 3KC4.56 3KC4.58 3KC4.60
3KC8.38 3KC8.42 3KC8.46 3KC8.48 3KC8.50 3KC8.52 3KC8.54 3KC8.56 3KC8.58 3KC8.60
250 A 400 A 630 A 800 A 1000 A 1250 A 1600 A 2000 A 2500 A 3200 A
Flat terminal
I – O – II
3 and 4
–
415
690
12
4
–/250 –/400 –/630 –/800 –/1000 –/1250 –/1600 –/2000 –/2500 –/3200
–/200 –/400 –/500 –/800 –/1000 –/1250 –/1250 –/2000 –/2000 –/2000
200 200 400 800 1000 1000 1000 1250 1250 1250
250 400 630 800 1000 1250 1600 –/2000 –/2500 –/3200 9
200 200 500 800 1000 1250 1600 –/2000 –/2000 –/2000
250 400 630 800 1000 1250 1600 –/2000 –/2500 –/3200
160 160 400 630 800 1000 1000 – – –
200 400 500/630 800 1000 1250 1250 –/1600 –/1600 –/1600
125 125 400 630 630 800 800 – – –
110 220 335 450 700 800 900 – – –
110 110 400 400 630 800 800 – – –
–
–
50 50 50 50 50 100 100 – – –
–
50 50 50 50 50 100 100 – – –
0.5 0.5 0.6 1.4 1.4 1.4 1.4 1.6 1.6 1.6
0.4 0.4 0.4 1.4 1.4 1.4 1.5 1.2 1.2 1.2
0.9/1.0 0.9/1.0 1.0/1.1 2.8/3.1 2.8/3.1 2.8/3.1 2.9/3.3 2.8/2.8 2.8/2.8 2.8/2.8
IP20
–
–
–
–
3KC0.36 3KC0.38 3KC0.40 3KC0.42 3KC0.44 3KC0.46 3KC0.48 3KC0.50 3KC0.52 3KC0.54 3LD21 3LD22 3LD25 3LD27 3LD23 3LD24
200 A 250 A 315 A 400 A 500 A 630 A 800 A 1000 A 1250 A 1600 A 25 A 32 A 63 A 100 A 160 A 250 A
Flat terminal Flat terminal Flat terminal Box terminal Box terminal
I – O – II I – O – II I – O – II I – O – II I – O – II
3 and 4 3 and 4 3 and 4 3 3 and 4
3 4 5 – –
– – – – –
– – – – –
– – – – –
From page 9/24 onwards From page 9/24 onwards From page 9/24 onwards From page 9/30 onwards
3)
Values in brackets apply to devices in molded-plastic enclosure.
2
2
optional and
4
4
3
optional
and and
66
1
5
optional
and and
4
4 33
optional and
22
Legend
1 Auxiliary switch 4 Control wire tap
I201_20552
1)
1× per change-over switch
optional and
4
4
3
optional
and and
optional optional
or
1
1
55
11
and and
optional
optional and
and
7
4
4
optional and
Legend
1 Auxiliary switch 4 Control wire tap 7 Sealable cover
2 Terminal cover 5 Autotransformer
I201_20553
2 or 3 or 4
optional and
8 optional
and 7
and
optional optional
6
and and
optional
and and
optional
8 and 7 1
optional and
2 or 3 or 4
Legend
1 Auxiliary switch 4 Terminal plate 7 Bridging bar
2 Phase barrier 5 Autotransformer 8 Copper bar connection kit 1) 9
I201_20554
3 Terminal cover 6 Dual power supply
1)
3× with 3-pole change-over switch, 4× with 4-pole change-over switch
optional
and
and
optional
8 and 7 1
optional and
2 or 3 or 4
Legend
1 Auxiliary switch 4 Terminal plate 7 Bridging bar 10 External display
2 Phase barrier 5 Autotransformer 8 Copper bar connection kit 1)
3 Terminal cover 6 Dual power supply 9 Power supply cable
I201_20555
1)
3× with 3-pole change-over switch, 4× with 4-pole change-over switch
4 or 5
optional and
8
and
Legend
3 Auxiliary switch 1)
4 Phase barrier
5 Side plate cover and terminal cover 2)
6 Direct operating mechanism
7 Door-coupling rotary operating mechanism
8 Bridging bar 3)
and
optional 1)
Up to 4 auxiliary switches
and 8 2)
Side plate cover must be ordered separately from
optional and the terminal cover
3
55
3)
3× with 3-pole change-over switch,
4 or
4× with 4-pole change-over switch
and
6 or 7
9
I201_20556
33 33 8 3
3 33
9
9
or
or
3
3 33 88 33 33
and
6
6 or 7
7
Legend
1)
Only for 3-pole 3K, max. 1× 2)
Max. 1× for each side of the switch, 3)
Only 1× per change-over switch
requires at least 1× auxiliary switch 3
or or optional optional
or or
2
3
3
2
and and
4 4 4 4 4 4 4
Legend
1 Auxiliary switch 3 N switching contact 1)
2 N/PE terminal 4 Terminal cover
I201_20558
1)
N switching 3 contact must first be installed on the basic unit
I201_19477
I201_19476
M M M
9 40 A
63 A
3KC3424-2AA22-0AA3
3KC3426-2AA22-0AA3
–
–
–
–
80 A 3KC3428-2AA22-0AA3 – –
100 A 3KC3430-2AA22-0AA3 – –
125 A 3KC3432-2AA22-0AA3 – –
160 A 3KC3434-2AA22-0AA3 – –
Flat terminal
250 A – 3KC4338-0CA21-0AA3 3KC4438-0CA21-0AA3
400 A – 3KC4342-0DA21-0AA3 3KC4442-0DA21-0AA3
630 A – 3KC4346-0EA21-0AA3 3KC4446-0EA21-0AA3
800 A – 3KC4348-0FA21-0AA3 3KC4448-0FA21-0AA3
1000 A – 3KC4350-0FA21-0AA3 3KC4450-0FA21-0AA3
1250 A – 3KC4352-0GA21-0AA3 3KC4452-0GA21-0AA3
1600 A – 3KC4354-0HA21-0AA3 3KC4454-0HA21-0AA3
2000 A – 3KC4356-0JA21-0AA3 3KC4456-0JA21-0AA3
2500 A – 3KC4358-0JA21-0AA3 3KC4458-0JA21-0AA3
3200 A – 3KC4360-0JA21-0AA3 3KC4460-0JA21-0AA3
I201_19478
I201_19479
I201_19475
M M M
Accessories
For remote transfer switching equipment (RTSE) and
automatic transfer switching equipment (ATSE)
RTSE ATSE
Bridging bar
• For load-side connection
• For 3KC4/3KC8 3-pole transfer switches 3 units,
for 3KC4/3KC8 4-pole transfer switches 4 units are required
Version Number of poles Scope of supply Article No.
For 40 ... 125 A 4-pole 1 unit 3KC9618-2 ■ ■
For 160 A 4-pole 1 unit 3KC9618-3 ■ ■
RTSE ATSE
Terminal covers
Version Number of poles Scope of supply Article No.
For 40 ... 160 A 4-pole 2 units (1 unit covers 4 poles) 3KC9604-2 ■ ■
For 250 ... 400 A 3-pole 3 units (1 unit covers 1 pole) 3KC9804-1 ■ ■
4-pole 4 units (1 unit covers 1 pole) 3KC9804-2 ■ ■
Sealable cover
Version Scope of supply Article No.
For 3KC6 (ATSE) 40 … 160 A Incl. bolt set and sealing ribbons 3KC9721-1 – ■
For 3KC8 (ATSE) 250 … 3200 A Incl. bolt set and sealing ribbons 3KC9821-0 – ■
Sealing ribbon
• Also as spare part for sealable cover
Version Scope of supply Article No.
For 40 ... 3200 A 10 units 3KC9621-2 – ■
Autotransformers
Version Technical specifications Article No.
For 40 ... 160 A 400 V/230 V AC; 400 VA 3KC9624-1 ■ ■
For 250 ... 3200 A, 3-pole 400 V/230 V AC; 200 VA 3KC9824-1 ■ ■
Accessories
For remote transfer switching equipment (RTSE) and
automatic transfer switching equipment (ATSE)
RTSE ATSE
Power supply and voltage sensing cables for ATSE
Application Infeed Switches Version Article No.
2-pole From below, with power supply 3-pole For 250 A 3KC9833-1 – ■
For 400 A 3KC9833-2 – ■
For 630 A 3KC9833-3 – ■
For 800 ... 1000 A 3KC9833-4 – ■
For 1250 A 3KC9833-5 – ■
For 1600 A 3KC9833-6 – ■
RTSE ATSE
Dual power supply
Version Technical specifications Article No.
For 3KC3 and 3KC4 (RTSE) 40 … 3200 A 240 V AC, 3 A 3KC9625-1 ■ –
External display
• For installing in the control cabinet door
Version Article No.
For 3KC8 (ATSE) 250 … 3200 A 3KC9823-0 – ■
Connection cable
• 3 m RJ45 cable for external display
Version Article No.
For 250 ... 3200 A 3KC9823-2 – ■
Phase barrier
• For 800 … 3200 A transfer switching equipment
included in the scope of supply of the basic unit
Version Number of poles Scope of supply Article No.
For 250 ... 400 A 3-pole 2 units 3KC9808-1 ■ ■
4-pole 3 units 3KC9808-6 ■ ■
For 630 A 3-pole 2 units 3KC9808-2 ■ ■ 9
4-pole 3 units 3KC9808-7 ■ ■
Cover frame for ATSE
• For a clean and safe door cut-out
• To enable access to the front of the 3KC8 transfer switching equipment
(electronic module and operation of the motorized operating mechanism)
Version Article No.
250 … 630 A 3KC9820-4 – ■
800 … 3200 A 3KC9820-5 – ■
Accessories
For remote transfer switching equipment (RTSE) and
automatic transfer switching equipment (ATSE)
RTSE ATSE
Copper bar connection kit
Version Designation Scope of supply Article No.
For 2000 … 2500A C-bracket, part A 1 unit 3KC9811-0 ■ ■
Terminal plates
• For protecting the front side at the upper and lower connecting terminals
9 Version Number of poles Article No.
For 250 ... 400 A 3-pole 3KC9827-1 ■ ■
4-pole 3KC9828-1 ■ ■
RTSE ATSE
Motorized operating mechanism as spare part
Version Article No.
For 250 ... 400 A 3KC9826-1 ■ ■
9 100 A
125 A
–
–
–
–
3KC0330-2NE00-0AA0
3KC0332-2NE00-0AA0
3KC0430-2NE00-0AA0
3KC0432-2NE00-0AA0
160 A – – 3KC0334-2NE00-0AA0 3KC0434-2NE00-0AA0
Flat terminal
200 A – – – –
250 A – – – –
315 A – – – –
400 A – – – –
500 A – – – –
630 A – – – –
800 A – – – –
1000 A – – – –
1250 A – – – –
1600 A – – – –
1)
An assembly kit is required for floor mounting
Flat terminal
Size 3 Size 4 Size 5
Basic unit without handle Basic unit without handle Basic unit without handle
Front operating mechanism Front operating mechanism Front operating mechanism
Floor mounting Floor mounting Floor mounting
Additionally required for connection side Additionally required for connection side Additionally required for connection side
– – – – – –
– – – – – –
– – – – – –
– – – – – –
–
–
–
–
–
–
–
–
–
–
–
–
9
– – – – – –
3KC0336-0PE00-0AA0 3KC0436-0PE00-0AA0 – – – –
3KC0338-0PE00-0AA0 3KC0438-0PE00-0AA0 – – – –
3KC0340-0PE00-0AA0 3KC0440-0PE00-0AA0 – – – –
3KC0342-0PE00-0AA0 3KC0442-0PE00-0AA0 – – – –
– – 3KC0344-0QE00-0AA0 3KC0444-0QE00-0AA0 – –
– – 3KC0346-0QE00-0AA0 3KC0446-0QE00-0AA0 – –
– – 3KC0348-0QE00-0AA0 3KC0448-0QE00-0AA0 – –
– – – – 3KC0350-0RE00-0AA0 3KC0450-0RE00-0AA0
– – – – 3KC0352-0RE00-0AA0 3KC0452-0RE00-0AA0
– – – – 3KC0354-0RE00-0AA0 3KC0454-0RE00-0AA0
Accessories
For manual transfer switching equipment (MTSE)
Size 1 Size 2 Size 3 Size 4 Size 5
Box terminal (4th contact element, switching pole)
I201_20442
Connection Article No.
3KD9105-2 ■
N N
3KD9205-2 ■
Red/yellow 3KC9301-2 ■
3KC9401-2 ■
3KC9501-2 ■
100 mm 8 × 8 mm 8UD1841-2AE01 ■
140 mm 10 × 10 mm 8UD1851-3AE01 ■
200 mm 12 × 12 mm 8UD1861-4AE01 ■
Red/yellow 55 mm 8 × 8 mm 8UD1731-2AE05 ■ ■
100 mm 8 × 8 mm 8UD1841-2AE05 ■
140 mm 10 × 10 mm 8UD1851-3AE05 ■
200 mm 12 × 12 mm 8UD1861-4AE05 ■
Accessories
For manual transfer switching equipment (MTSE)
Size 1 Size 2 Size 3 Size 4 Size 5
Extension shaft for door-coupling rotary operating mechanism, 8UD1 series
• A shaft jack is required for the 8UD1 handle when the 600 mm
long shaft is used and for sizes 1/2.
Length Cross-section Article No.
300 mm 8 × 8 mm 8UC6032 ■ ■ ■
10 × 10 mm 8UC6033 ■
12 × 12 mm 8UC6034 ■
600 mm 8 × 8 mm 8UC6082 ■ ■ ■
10 × 10 mm 8UC6083 ■
12 × 12 mm 8UC6084 ■
Shaft jack for 8UD1 handle for shaft, 600 mm
Shaft Article No.
8 × 8 mm 8UD1900-0FA00 ■ ■
Coupling drivers
Type Shaft Article No.
With tolerance 8 × 8 mm 8UD1900-2GA00 ■ ■
compensation
8 × 8 mm 8UD1900-6GA00 ■
10 × 10 mm 8UD1900-3GA00 ■
12 × 12 mm 8UD1900-4GA00 ■
9
Without tolerance 8 × 8 mm 8UD1900-2HA00 ■ ■
compensation
8 × 8 mm 8UD1900-6HA00 ■
10 × 10 mm 8UD1900-3HA00 ■
12 × 12 mm 8UD1900-4HA00 ■
1)
Can only be used as a spare part, as no additional poles can be installed in the enclosure.
– – 3LD2165-7UB01
– – 3LD2265-7UB01
– – 3LD2566-7UB01
– – 3LD2766-7UB01
3LD2318-7UK01 3LD2318-7UL01 –
3LD2418-7UK01 3LD2418-7UL01 –
Shaft coupling
• No ON-lock
Load transfer switch design Article No.
Floor mounting 3LD9242-4F ■ ■
G G G G
I201_20395
Load Non-
Priority
I201_20422
priority
load
load
Front interface
• For parameterization on the front using software
ATC6 front interface Features Article No.
USB • Mini-USB cable, 1.8 m 3KC9000-8TL73
Protective seal
• For front IP65 protection
Suitable for Version Article No.
3KC ATC6300 144 × 144 mm 3KC9000-8TL67
3KC ATC6500 240 × 180 mm 3KC9000-8TL68
Accessories 10/10
Information + ordering
All the important things at a glance Everything you need for your order
For information about measuring devices, power Refer to the Industry Mall for an overview of your
monitoring and digitalization solutions, please visit our products
websites • Measuring devices and power monitoring
www.siemens.com/powermonitoring sie.ag/2kTH9Lz
www.siemens.com/sentron-digital • Digitalization solutions sie.ag/2olIiNi
• Library for SIMATIC sie.ag/2kpbwcs
• SENTRON powermanager/SENTRON powerconfig
Your product in detail sie.ag/2kTJjuF
Direct forwarding to the individual products in the
The Siemens Industry Online Support (SIOS) provides Industry Mall by clicking on the article number in the
comprehensive information catalog or entering this web address incl. article n
umber
www.siemens.com/lowvoltage/product-support www.siemens.com/product?Article No.
• Brochure
− SENTRON portfolio for power monitoring
(109744725) Configurators
− SENTRON powermanager – update and benefit
(109805178) The configurator reduces the time and effort required
The relevant tender specifications can be found at in the planning and ordering process, and allows for
individual adaptations.
10 www.siemens.com/lowvoltage/tenderspecifications
Configure your 7KM PAC and 7KT PAC measuring device
at www.siemens.com/lowvoltage/pac-configurator
Siemens YouTube channel
Commissioning + operation
The Siemens Industry Online Support (SIOS) The combined commissioning and service tool SENTRON
provides detailed technical information powerconfig for communication-capable measuring
devices, circuit protection devices and circuit breakers.
www.siemens.com/lowvoltage/product-support
Free download SENTRON powerconfig
• Operating instructions www.siemens.com/powerconfig
• Certificates Free download SENTRON powerconfig mobile via
App Store and Play Store
Comprehensive mobile support via the Siemens Industry
Online Support app available for download from the
App Store and Play Store
You will find further information at
Manuals
www.siemens.com/support-app
Manuals are available for downloading in Siemens Industry
Provision of 3D data (step and u3d data formats) Online Support (SIOS) at
• Siemens Industry Mall www.siemens.com/lowvoltage/manuals
www.siemens.com/lowvoltage/mall • Configuration Manual
• Image database − Measuring devices and power monitoring (45315973)
www.siemens.com/lowvoltage/picturedb • Equipment Manual
− 7KT PAC1600 energy meter (109759827)
Engineering data for CAD or CAE systems are available in − 7KT PAC1600 multimeter (109760293)
the CAx Download Manager at − 7KM PAC2200 power monitoring device (109746835)
www.siemens.com/cax − 7KM PAC2200CLP power monitoring device
(109783220)
− 7KM PAC3200T power monitoring device
(109746833)
Face-to-face or online training − SENTRON PAC5100/5200 7KM5212/5412
(109477872)
− 7KM PAC3120 and 7KM PAC3220 (109767307)
Our training courses can be found at − 7KN POWERCENTER 3000 (109763838)
www.siemens.com/sitrain-lowvoltage • System Manual
− 7KT multichannel current measuring system
• Digitalization in power distribution boards (WT-LVDIGI) (109483442)
• SENTRON circuit protection devices with measuring and − SENTRON PAC4200 power monitoring device
communication function (WT-LVBCOM) (34261595)
− SENTRON circuit protection devices with communica-
• Power Monitoring with SENTRON (WT-LVAEM) tion and measuring function (109791806)
• Energy Management with SENTRON powermanager – • Communication Manual
User training (LV-PM) − SENTRON PAC5100/5200 7KM5212/5412 (109477870)
− 3VA molded case circuit breakers with IEC and UL
• SENTRON powermanager graphic module – certification (98746267)
User training (LV-PMG) • SEM3™
− Embedded Micro Metering Module™ (109748928)
• Quick Installation Guide
− 7KN POWERCENTER 3000 (109766001)
• Installation Manual
− SENTRON circuit protection devices with communica-
tion and measuring function (109791805)
Power monitoring
Software Local monitoring systems
Web Mobile App
I201_20440
I201_08932
SENTRON SENTRON 7KN Powercenter SENTRON SIMATIC SIMATIC
powerconfig powermanager 3) 3000 powermind TIA Portal TIA Portal
(MindSphere) integrated capable
■ – – – ■ –
■ ■ ■ ■ ■ ■
■ ■ ■ ■ ■ ■
– ■ – ■ ■ –
– ■ – – – –
– – – ■ – –
– ■ – – ■ ■
Free of charge License and trial license – Subscription – –
Windows X64 Windows X64 – Browser – –
– ■ (TÜV) ■ ■ – –
– ■ ■ ■ – –
– ■ ■ ■ – – 10
From page 10/12 From page 10/14 From page 10/18 From page 10/22
■ ■ 4) ■ ■ – –
■ ■ ■ ■ – ■ 5)
■ ■ ■ ■ – ■ 5)
■ ■ ■ ■ – –
■ ■ ■ ■ ■ ■
■ ■ ■ ■ ■ ■
■ ■ – – – –
■ ■ – – – –
■ ■ ■ – – –
– ■/■ 4) – – – –
■ ■ ■ ■ – ■
■ ■ ■ ■ ■ ■
■ ■ – – – ■
■ ■ ■ ■ ■ ■
■ ■ ■ ■ – –
■ ■ ■ ■ – –
Hardware components
Industry
7KM 7KM 7KT 7KT SEM3 3WA 3WL 3WL10/ 3VA ETU8
PAC4200 PAC5200 PAC1200 PAC1600 3VA27
– – ■ ■ – – – – –
■ ■ ■ ■ – ■ ■ ■ ■
– – ■ – ■ – – – –
■ ■ ■ ■ ■ – – – –
■ ■ ■ ■ ■ – – – –
– – ■ – ■ ■ ■ ■ ■
■ – – – – ■ ■ – –
■ ■ ■ ■ ■ ■ ■ ■ ■
■ ■ ■ ■ ■ ■ ■ ■ ■
■ ■ – – – ■ ■ – ■
2nd to 64th 2nd to 40th – – – 2nd to 31st 2nd to 29th – –
■ ■ – – – – – – –
■ – – – ■ ■ ■ ■ ■
– ■ – – – – – – –
■ – – ■ – ■ ■ – ■
■ ■ – ■ – – ■ ■ ■
■ ■ – – ■ – – – –
> 4000 events ■ – – ■ – ■ ■ ■
■ – – – – – – – –
– ■ – – – – – – –
– ■ – – – – – – –
See page 10/26 See page 10/26 See page 10/31 See page 10/30 See page 10/32 See page 1/4 See page 1/66 See page 1/66 See page 2/6
See page 2/6
Hardware components
I201_20406
I201_20406 I201_20406
I201_20406
I201_20406
■ ■
– –
– –
– –
■ –
– ■
■ –
■ ■
■ ■
■ –
■ –
■ –
■ –
■ ■
■ ■ 10
■ –
■ –
■ –
■ ■
■ – 1)
– –
Accessories
Communication modules
7KM PAC1020 – – – –
7KM PAC2200 – – – ■
7KM PAC3200T – – – ■
7KM PAC3120 – – – –
10 7KM PAC3220 ■ ■ ■ –
7KM PAC4200 ■ ■ ■ –
7KM PAC5200 – – – –
7KT PAC1200 – – – –
7KT PAC1600 – – – –
SEM3 – – – –
Circuit breakers
3WA/3WL – – – –
3WL10/3VA27 – – – –
3VA ETU5/8 ■ ■ ■ –
– – ■ ■ ■
– – ■ ■ ■
– – – – ■
– – ■ ■ ■
– – ■ ■ ■
■ ■ ■ ■ ■ 10
■ ■ ■ ■ ■
– – ■ ■ ■
– – – – –
– – ■ ■ ■
– – – – –
– – – – –
– – – – –
– – – – –
SENTRON powerconfig
Configuration software for commissioning and maintenance
SENTRON powerconfig is available free of charge at Free download SENTRON powerconfig mobile via:
www.siemens.com/powerconfig
You will find further information on the internet at
www.siemens.com/sentron
• Software tool for the efficient commissioning and diagnostics • Service functions:
of communication-capable SENTRON components − Detection of devices and acquisition of measured quantities
• Supports all electronic SENTRON devices, e.g. 3WA, 3WL, 3VA, and status information via different networks, e.g. via
7KN Powercenter 3000 and 7KN Powercenter 1000, Ethernet
with 5ST3 AS+FC COM, 5SL6 MCB COM, 5SV6 AFDD COM and − Device and status acquisition via local interfaces, such as
3NA Fuse COM Bluetooth and USB
• General range of functions: − Acquisition and archiving of historic records, such as load
− User-friendly parameter assignment even for complex profiles and events
devices such as the 3WA − Firmware updates
− Fast, optical detection of communication and measuring- − Switching of language packs for 7KM PAC measuring devices
capable circuit protection devices, such as • Cooperative interaction between powerconfig mobile and
7KN Powercenter 1000 powerconfig on the PC:
− Saving and printing of device settings − powerconfig mobile offers a high degree of mobile versatili-
− Monitoring, saving and printing of instantaneous measured ty, e.g. to scan codes on the circuit protection devices
quantities − powerconfig on the PC can be used for subsequent editing
− Execution of specific device functions, such as resetting of and archiving of the system configuration
devices and setting of energy meters
10
SENTRON
powerconfig
*splx
Modbus TCP
I201_20139
7KN Powercenter 1000
SENTRON
Powerconfig
mobile
10
Display of the circuit breaker status Display of the state of health of the 3VA
SENTRON powermanager
PC-based power monitoring software
SENTRON powermanager
SENTRON powermanager is based on the modern Desigo CC If you wish to migrate from classic powermanager (3.6) to the
platform with advanced graphical capabilities and a standard SQL current version, please get in touch with your local Siemens
database. The workflows for setting up the system, creating contact.
devices, graphically displaying the device data and processing it
The "Trial" license gives customers the opportunity to gain initial
in reports have been fundamentally revised.
experience with SENTRON powermanager during a 60-day test
You can find the latest download and change information in the phase. The application can still be used by purchasing a regular
SIOS portal at license.
www.siemens.com/lowvoltage/product-support (109771760)
You will find further information on the internet at
Updates and upgrades of version 4.x or higher are based on the www.siemens.com/powermanager
SUS/SUR principles.
You will find training courses on the internet at
You will find further information in the brochure – SENTRON
www.siemens.com/sitrain-lowvoltage
powermanager – update and benefit
www.siemens.com/lowvoltage/product-support (109805178)
10
SENTRON powermanager
PC-based power monitoring software
10
Health Dashboard
10
7KN Powercenter
Edge/IoT-based data acquisition and visualization for low-voltage power distribution
Internet
Cloud Mindsphere and other Clouds
(e. g. AWS, Azure, Alibaba Cloud, etc.)
Intranet
Facility Email Server for Integrated
Webinterface SCADA/Local
Notification monitoring system
Distribution
System
7KN Powercenter 3000
3WA/3WL 3VA 7KM 3NA COM 3VA 7KM 3NA COM 7KM 5SL6 5SV6 5ST3
PAC4200 PAC4200 PAC2200 COM COM COM
The following examples give an impression of the diverse functions of the 7KN Powercenter 3000. These are aimed at different
customer groups, such as energy managers and maintenance personnel, but also electricians. All information is available via a web
browser on a standard PC, but also on mobile devices, such as tablets and smartphones. The information is therefore also available
remotely within the company network.
Predefined dashboards
These are automatically selected according to the configuration of the 7KN Powercenter 3000 and show the most important data of
SENTRON protection, switching and measuring devices.
Data visualization based on the example of a measuring device Information on the status of protection and switching devices
• Key data points such as active energy or active power are displayed in the • Representation of the device status, e.g. open, closed, tripped and relevant
form of a curve (time range can be altered by scrolling).
• Further instantaneous values or device information are available in tabular
measured quantities, such as maximum phase current, total power ...
• Condition monitoring information is used to assess the state of health and
10
form. predict the remaining service life
7KN Powercenter
Wireless data acquisition and visualization in the final circuit
Mounting Power supply Devices that can be connected Interfaces Article No.
DIN-rail mounting 24 V DC SELV 24 circuit protection devices via 2× Ethernet 7KN1110-0MC00
radio link
Note:
Please note the country-specific radio licenses of the products in SIOS:
10 www.siemens.com/lowvoltage/certificates (109801197)
Bundle 4
I201_20406 9× 3NA COM LV HRC fuse links 7KN1110-0XC04
1× 7KN Powercenter 1000
I201_20406 1× 7KN Powercenter 3000
Bundle 5
I201_20406 9× 3NA COM LV HRC fuse links 7KN1110-0XC05
1× 7KN Powercenter 1000
I201_20406
www.siemens.com/lowvoltage/manuals
7KN Powercenter 1000
Installation Manual – SENTRON
circuit protection devices with
communication and measuring
function (109791805)
... ... ... ... System Manual – SENTRON circuit
protection devices with 10
communication and measuring
5SL6 COM 5ST3 COM 5SV6 COM 3NA COM function (109791806)
MCB AS+FC AFDD Fuse
max. 24
Wireless Protocol
SENTRON powermind
Cloud-based solution for data visualization and
analysis in power distribution systems
SENTRON powermind is aimed equally at energy managers, facility managers and/or operators. For energy managers, predefined,
automated representations and analyses of energy data are available, such as:
• Analysis of data in graphical form, e.g. lines, bars, heatmap, Sankey diagram (Can also be output as a report)
• Comparison of energy consumption on weekdays versus weekends with percentage day-by-day representation of the distribution
of energy consumption to identify unnecessary energy consumption
• Comparison of energy consumption and power import during a selected period as compared with a reference period to assess the
effectiveness of energy efficiency measures
• Day-by-day representation of the 15 min power demand, incl. min and max values to assess power peaks
SENTRON powermind offers operators and facility managers the following information and analyses:
• Status of the switching and protection devices, such as 3VA, 3WA and 3WL
• Display of the maximum current value of an individual phase in relation to In
• Condition monitoring information about the condition of the contact system of each circuit breaker and also as an overview of all
circuit breakers
• The following devices are supported:
PAC1020, PAC2200/PAC2200CLP, PAC3100/PAC3120, PAC3200/PAC3200T/PAC3220, PAC4200 measuring devices,
3VA, 3WA and 3WL circuit breakers
You will find further information on the MindSphere Store at
www.dex.siemens.com/mindsphere/applications
10 SENTRON powermind
3WA/3WL 3VA 7KM PAC4200 7KM PAC3220 7KM PAC3200T 7KM PAC2200 MODBUS
device
Modbus RTU
3WL COM16 7KM PAC3120 7KM PAC1020 7KT PAC1600 5SV6 COM 5SL6 COM 5ST3 COM
(AFDD) (MCB) (AUX COM)
A large number of devices transmit data via SENTRON Powercenter 3000 or SENTRON powermanager to SENTRON powermind
SENTRON powermind processes data from SENTRON Powercenter 3000. No complex configuration or parameterization is required, as
the necessary information is exchanged using files. This also prevents possible incorrect entries or write errors. An error-free connec-
tion can thus be easily established in just a few minutes.
The examples show some of the functions of SENTRON powermind, which are aimed at different customer groups, such as energy
managers and maintenance personnel, but also electricians. All information is available via a web browser on a standard PC, but also
on mobile devices, such as tablets and smartphones. The information is therefore available both on-site (locally) and off-site
(remotely).
Creating transparency
• Representation of the device status, e.g. open, closed, tripped and relevant
Overview of the circuit breaker status
• Overview of the state of the health of all circuit breakers in the switchboard
10
measured quantities, such as maximum phase current, total power … • Assignment to a maintenance cycle (< 1 year; between 1 and 3 years; > 3 years)
• Information about the state of health of the device to take action proactively • Display of circuit breakers in list form as well as link to the respective circuit breaker
dashboard
Creating transparency
• Representation of the power flow/power import in various parts of the power distribution system
• Comparison of the weekly energy consumption (percentage distribution of weekdays in comparison to weekend) to identify unusual energy consumption
patterns and to check energy-saving measures in the form of a bar chart or Sankey diagram
Energy management
• Comparison of the energy consumption of two periods, for example, to assess the effectiveness of energy saving measures
• Representation of the active power as mean and min/max values in a line diagram or heatmap
Operating and
monitoring level
Archive
PROFINET
10
SIMATIC PCS 7 / WinCC, Industrial Ethernet
Option powerrate and function block libraries
Processing level
SIMATIC S7, e.g. with Energy Suite
PROFINET /
PROFIBUS DP PROFIenergy
Industrial Ethernet
COM35
max. 8
3WL
Connec- Power supply Display Interface MID PTB- 7KM PAC1020 7KM PAC2200/PAC2200 CLP 7KM PAC3200T
tions A50.7
Transformer measurement
Screw Self-powered With M-Bus With Without – 7KM2200-2EA30-1GA1 –
terminals Without Without – 7KM2200-2EA30-1CA1 –
Modbus RTU With Without – 7KM2200-2EA30-1HA1 –
Without Without – 7KM2200-2EA30-1DA1 –
Modbus TCP With With – 7KM2200-2EA00-1JB1 –
Without – 7KM2200-2EA30-1JA1 –
Without Without – 7KM2200-2EA30-1EA1 –
AC/DC wide-range With Modbus RTU Without Without 7KM1020-0BA01-1DA0 – –
power supply unit Modbus TCP Without Without – – –
Without Modbus TCP Without Without – – 7KM3200-0CA01-1AA0
DC power supply With Modbus TCP Without Without – – –
10 unit with
extra-low voltage
Modbus RTU Without Without – – –
– – – –
– – – –
– – – –
– – – –
– – – –
– – – –
– – – –
7KM3120-0BA01-1DA0 – – –
– 7KM3220-0BA01-1DA0 7KM4212-0BA00-3AA0 7KM5412-6BA00-1EA2
– – – 7KM5412-6CA00-1EA8
– 7KM3220-1BA01-1EA0 7KM4211-1BA00-3AA0 –
7KM3120-1BA01-1EA0 – – –
10
– – 7KM4212-0BA00-2AA0 –
– – – –
– – – –
– – – –
– – – –
– – – –
– – – –
x/1 A or x/5 A
690/400 V 500/289 V 690/400 V
–
7KM9900-0XA00-0AA0
7KM PAC TMP mounting plate
• Adapter for mounting a measuring device on DIN rail
• Display faces backwards towards DIN rail
• Readout and evaluation of measurements solely via mains operation
7KM9900-0YA00-0AA0
Compact holder
• Device holder for 7KM PAC1020/3100/3120/3200/3220/4200
• 10 holders for 5 PAC devices
• For seamless side-by-side mounting of the devices (without spaces)
7KM9900-0GA00-0AA0
7KM PAC3100
7KM PAC3200
7KM PAC4200
10 Spare parts for 7KM PAC
• Spare parts comprising:
− Device holders for panel mounting (2X)
Note: can also be used for 7KM PAC3120/3220
− Screw terminal for connection of voltage inputs
− Screw terminal for connection of current inputs
− Terminal block inputs/outputs for 7KM PAC3100/4200
− Terminal block inputs/outputs for 7KM PAC3200
− RS485 terminal blocks for 7KM PAC3100
7KM9900-0SA00-0AA0
7KM PAC2200
7KM PAC2200 CLP
7KM PAC2200 MID 7KM PAC3200T
SENTRON PROFINET Proxy SPP2000 new
• Proxy for transition from Modbus TCP-capable measuring devices to PROFINET
IO. Connection of up to 8 devices from the PAC2200, PAC2200 CLP, PAC2200
MID and PAC3200T product ranges
• PROFINET Conformance Class C
• Two switched ports
• Integration in TIA by means of GSDML file
7KM9300-0PP20-0AA0
7KM9300-0AE02-0AA0
7KM9300-0AB01-0AA0
7KM9300-0AM00-0AA0 1)
7KM9200-0AB00-0AA0 –
10
7KM PAC I(N), I(Diff), analog expansion module
• To add the following functions to the measuring inputs:
− N conductor measurement
− Two analog inputs, also for measuring non-electrical quantities such as temperature,
water or air pressure
− Residual current measurement via type A or type B
summation current transformers
7KM9200-0AD00-0AA0 –
1)
Suitable for 7KM PAC4200 (especially for the Modbus TCP/RTU Gateway)
Residual-current transformers for 7KM PAC I(N), I(Diff), analog expansion module, from page 11/1 onwards
6 7KT1236
9 7KT1238
12 7KT1242
10
PAC1200 Bundles
10
Accessories
Metering modules
• For recording measured values
• Accuracy of 0.2% or 1% for the entire measurement including current transformer
• Simple setting of phase configuration by means of slide switch
• Connection of a current transformer for measuring a phase
• Metering module is plugged into meter rack
Measuring accuracy Article No.
0.2% US2:SEM3PHAMETER
1% US2:SEM3PLAMETER
Meter racks
Version Article No.
For 3 metering modules US2:SEM3RACK3
For 9 metering modules US2:SEM3RACK9
For 15 metering modules US2:SEM3RACK15
For 21 metering modules US2:SEM3RACK21
Connecting cables
• 600 V insulated special cable for connecting meter racks to the data manager
Length Article No.
0.3 m US2:SEM3CAB12INCH
0.6 m US2:SEM3CAB24INCH
0.9 m US2:SEM3CAB36INCH
Standard current transformers
• Standard power cable brown and yellow, 1.82 m long
• Can be extended up to 100 m while still maintaining accuracy
• Transformer configuration is carried out in the data manager
Output signal Transformer transmission ratio Article No.
100 mA 50 : 0.1 US2:SEM3SCCT50
125 : 0.1 US2:SEM3SCCT125 10
250 : 0.1 US2:SEM3SCCT250
400 : 0.1 US2:SEM3SCCT400
600 : 0.1 US2:SEM3SCCT600
800 : 0.1 US2:SEM3SCCT800
1200 : 0.1 US2:SEM3SCCT1200
Folding transformers
• Standard power cable brown and yellow, 1.82 m long
• Can be extended up to 100 m while still maintaining accuracy
• Transformer configuration is carried out in the data manager
Output signal Transformer transmission ratio Article No.
100 mA 50 : 0.1 7KT1280-5MA00
125 : 0.1 7KT1280-5MA01
250 : 0.1 7KT1280-5MA02
400 : 0.1 7KT1280-5MA03
600 : 0.1 7KT1280-5MA04
800 : 0.1 7KT1280-5MA05
1200 : 0.1 7KT1280-5MA06
1600 : 0.1 7KT1280-5MA07
2000 : 0.1 7KT1280-5MA08
DIN-rail adapters
• 5 adapters for snapping onto DIN rail
• 1 adapter each for data manager and for meter racks with 3, 9, 15 and 21 metering modules
• Adapters are screwed onto the data manager or the meter racks
Article No.
US2:SEM3DINKIT
10
Accessories
Metering module
• For recording measured values
• No configuration necessary for modules
• Connection of a temperature sensor
• Metering module is plugged into meter rack
Article No.
7KT1281-1AA00
Meter racks
Version Article No.
For 3 metering modules US2:SEM3RACK3
For 9 metering modules US2:SEM3RACK9
For 15 metering modules US2:SEM3RACK15
For 21 metering modules US2:SEM3RACK21
Connecting cables
• 600 V insulated special cable for connecting meter racks to the data manager
Length Article No.
0.3 m US2:SEM3CAB12INCH
0.6 m US2:SEM3CAB24INCH
0.9 m US2:SEM3CAB36INCH
Temperature sensors
• Standard connection cable, brown and yellow, 3 m long
• Can be extended up to 15 m while still maintaining accuracy
• Configuration is carried out in the data manager
Version Size Article No.
Sensors with ring cable lugs Sensor 1/4“ 7KT1281-2SA00
Sensor 5/16“
Sensor 3/8“
7KT1281-2SA01
7KT1281-2SA02
10
Sensor 1/2“ 7KT1281-2SA03
Cylindrical sensor 7KT1281-2CA00
10
Current transformers
For measurement purposes
4NC 1) 7KT 3NJ 1)
1-phase 3-phase 1-phase
Size Insulation level Rated primary Rated power Isr = 5 A Isr = 1 A Isr = 5 A Isr = 5 A Isr = 1 A
Um current Ipr Pn
Accuracy class 0.2s
1 720 V 150 A 1 VA 4NC5121-2FA21 – – – –
200 A 2.5 VA 4NC5122-2FC21 – – – –
250 A 2.5 VA 4NC5123-2FC21 – – – –
300 A 5 VA 4NC5124-2FE21 – – – –
400 A 5 VA 4NC5125-2FE21 – – – –
500 A 5 VA 4NC5126-2FE21 – – – –
5 720 V 600 A 5 VA 4NC5227-2FE21 – – – –
700 A 5 VA 4NC5228-2FE21 – – – –
800 A 5 VA 4NC5231-2FE21 – – – –
1000 A 5 VA 4NC5232-2FE21 – – – –
Accuracy class 0.5
1 720 V 100 A 1 VA 4NC5117-2DA21 4NC5117-0DA21 – – –
150 A 2.5 VA 4NC5121-2DC21 4NC5121-0DC21 – – –
200 A 5 VA 4NC5122-2DE21 4NC5122-0DE21 – – –
250 A 5 VA 4NC5123-2DE21 4NC5123-0DE21 – – –
2 720 V 200 A 5 VA 4NC5222-2DE21 4NC5222-0DE21 – – –
250 A 5 VA 4NC5223-2DE21 4NC5223-0DE21 – – –
10 300 A 5 VA 4NC5224-2DE21 4NC5224-0DE21 – – –
400 A 5 VA 4NC5225-2DE21 4NC5225-0DE21 – – –
3 720 V 400 A 5 VA 4NC5325-2DE21 4NC5325-0DE21 – – –
500 A 5 VA 4NC5326-2DE21 4NC5326-0DE21 – – –
600 A 5 VA 4NC5327-2DE21 4NC5327-0DE21 – – –
750 A 5 VA 4NC5330-2DE21 4NC5330-0DE21 – – –
800 A 5 VA 4NC5331-2DE21 – – – –
4 720 V 800 A 10 VA 4NC5431-2DH21 4NC5431-0DH21 – – –
1000 A 10 VA 4NC5432-2DH21 4NC5432-0DH21 – – –
1200 A 10 VA 4NC5433-2DH21 4NC5433-0DH21 – – –
1500 A 10 VA 4NC5435-2DH21 4NC5435-0DH21 – – –
1600 A 15 VA 4NC5436-2DK21 – – – –
2000 A 20 VA 4NC5438-2DL21 – – – –
2500 A 25 VA 4NC5440-2DM21 – – – –
3000 A 30 VA 4NC5441-2DN21 – – – –
Accuracy class 0.5 calibrated
– 720 V 100 A 1.5 VA – – – 3NJ6920-3BD23 3NJ6920-3BD13
150 A 2.5 VA – – – 3NJ6920-3BE23 3NJ6920-3BE13
300 A 5 VA – – – 3NJ6940-3BH23 3NJ6940-3BH13
400 A 5 VA – – – 3NJ6940-3BJ23 3NJ6940-3BJ13
500 A 5 VA – – – 3NJ6940-3BK23 3NJ6940-3BK13
600 A 5 VA – – – 3NJ6940-3BL23 3NJ6940-3BL23
1)
Overcurrent limiting factor FS5
Size Insulation level Rated primary Rated power Isr = 5 A Isr = 1 A Isr = 5 A Isr = 5 A Isr = 1 A
Um current Ipr Pn
Accuracy class 1.0
1 720 V 50 A 1.2 VA 4NC5112-2CB21 4NC5112-0CB21 – – –
60 A 1.2 VA 4NC5113-2CB21 4NC5113-0CB21 – – –
1.25 VA – – 7KT1200 – –
75 A 2.5 VA 4NC5115-2CC21 4NC5115-0CC21 – – –
100 A 2.5 VA 4NC5117-2CC21 4NC5117-0CC21 7KT1201 – –
150 A 2.5 VA 4NC5121-2CC21 4NC5121-0CC21 – – –
3.75 VA – – 7KT1202 – –
200 A 5 VA 4NC5122-2CE21 4NC5122-0CE21 – – –
250 A 5 VA 4NC5123-2CE21 4NC5123-0CE21 – – –
2 720 V 200 A 5 VA 4NC5222-2CE21 4NC5222-0CE21 – – –
250 A 5 VA 4NC5223-2CE21 4NC5223-0CE21 – – –
300 A 5 VA 4NC5224-2CE21 4NC5224-0CE21 – – –
400 A 5 VA 4NC5225-2CE21 4NC5225-0CE21 – – –
3 720 V 400 A 5 VA 4NC5325-2CE21 4NC5325-0CE21 – – –
500 A 5 VA 4NC5326-2CE21 4NC5326-0CE21 – – –
600 A 5 VA 4NC5327-2CE21 4NC5327-0CE21 – – –
750 A 5 VA 4NC5330-2CE21 4NC5330-0CE21 – – –
4 720 V 800 A 10 VA 4NC5431-2CH21 4NC5431-0CH21 – – – 10
1000 A 10 VA 4NC5432-2CH21 4NC5432-0CH21 – – –
1250 A 10 VA 4NC5434-2CH21 4NC5434-0CH21 – – –
1500 A 10 VA 4NC5435-2CH21 4NC5435-0CH21 – – –
2000 A 12.5 VA 4NC5438-2CJ21 4NC5438-0CJ21 – – –
2500 A 12.5 VA 4NC5440-2CJ21 4NC5440-0CJ21 – – –
3000 A 30 VA 4NC5441-2CN21 – – – –
Accessories
DIN-rail mounting
For transformer size Article No. Article No. Article No. Article No. Article No.
1 and 5 4NC5923-5LT21 4NC5923-5LT21 – – –
2 4NC5925-5LT21 4NC5925-5LT21 – – –
3 4NC5930-5LT21 4NC5930-5LT21 – – –
4 4NC5940-5LT21 4NC5940-5LT21 – – –
Well-monitored – well-protected
Monitoring devices perform numerous functions
to protect people and machinery: At dusk, they
switch on automatically, control the temperature
or signal the location where a fuse has tripped.
Monitoring Devices
Information + ordering
All the important things at a glance Everything you need for your order
For information about monitoring devices, Refer to the Industry Mall for an overview of your
please visit our website www.siemens.com/lowvoltage products
• Monitoring devices sie.ag/2m3no4A
Direct forwarding to the individual products in the
Your product in detail Industry Mall by clicking on the article number in the
catalog or entering this web address incl. article n
umber
The relevant tender specifications can be found at www.siemens.com/product?Article No.
www.siemens.com/lowvoltage/tenderspecifications
Use our conversion tool for quick and easy conversion to
Siemens products www.siemens.com/conversion-tool
11
Commissioning + operation
The Siemens Industry Online Support (SIOS) provides Manuals are available for downloading in Siemens
detailed technical information Industry Online Support (SIOS) at
www.siemens.com/lowvoltage/product-support www.siemens.com/lowvoltage/manuals
• Operating instructions • Configuration Manual
• Characteristic curves − Monitoring devices (45316099)
• Certificates
Comprehensive mobile support via the Siemens Industry
Online Support app available for download from the
App Store and Play Store
You will find further information at
www.siemens.com/support-app
System overview
5SV8 residual current monitor 5SV8 modular residual current device 5TT3 and 5TT6 relay 5TT3 monitors
Accessories
Summation current transformer Holders for DIN rails Magnetic field centering sleeves
11
Accessories
Immersion electrodes
Note:
You will find a detailed range of accessories with the basic units.
11
Rated operational Rated residual current IΔn Response time Δt 1 channel 4 channels
voltage Ue Type A Type AC
230 V AC 0.03 … 5 A >3 A 0.02 … 5 s 5SV8000-6KK – –
0.03 … 3 A 5 … 30 A 0.02 … 10 s, INS, SEL 1) – 5SV8001-6KK 5SV8200-6KK
1)
INS: Instantaneous,
SEL: Selective
Accessories
Summation current transformers
• Including holder for DIN rail or wall mounting
• Standard u
Mounting options Lowest measurable Rated Maximum Internal diameter Article No.
residual current IΔn min current In current 2) Imax
DIN rail 30 mA ≤40 A 240 A 20 mm 5SV8700-0KK
≤63 A 380 A 30 mm 5SV8701-0KK
1)
The holder for DIN rails is additionally required for mounting onto the DIN rail.
2)
Short-time starting current, up to 2 s
1)
INS: Instantaneous,
SEL: Selective
Accessories
Summation current transformers
• Including holder for wall mounting
• Standard u
Mounting options Lowest measurable Rated Maximum Internal diameter Article No.
residual current IΔn min current In current 2) Imax
Wall mounting, 30 mA ≤80 A 480 A 35 mm 5SV8702-0KK
DIN rail 1) 30 mA ≤200 A 1200 A 70 mm 5SV8703-0KK
Accessories
Summation current transformers
Lowest measurable Rated current In Maximum Internal diameter Version Article No.
residual current IΔn min current 1) Imax
10 mA ≤80 A 500 A 35 mm Standard 5SV8701-2KK
With shield 5SV8701-2KP
1)
Short-time starting current, up to 2 s
5
5SV8101-4KK/5SV8111-4KK
6 ➋ DIN rail
EN 60715 – TH35 – 7,5 35 – 15
➌ Summation current transformers
∅ 35 mm 5SV8701-2KK/5SV8701-2KP
∅ 60 mm 5SV8702-2KK/5SV8702-2KP
∅ 120 mm 5SV8703-2KK
∅ 210 mm 5SV8704-2KK
➍ Relay contacts
1 DC: AC: max. 230 V, 5A
2 3
5TT3400
5TT3401
5TT3402 5TT3404
Further technical specifications 5TT3403 5TT3405 5TT3406
Standards
Standards IEC 60255, DIN VDE 0435-110, DIN VDE 0435-303
Supply
Rated control circuit voltage Uc 230/400 V AC
Primary operating range (overload capability) 1.1 × Uc
11 Rated frequency 50/60 Hz
Contacts
μ contact AC-11 4A
Response values ON-switching 0.9/0.95 × Uc 4% hysteresis
OFF-switching 0.7/0.85 × Uc 0.7 … 0.95 × Uc
Minimum contact load 10 V/100 mA
Safety
Rated insulation voltage Ui Between coil/contact 4 kV
Electrical isolation, creepage distances Actuator/contact 3 mm 5.5 mm
and clearances
Rated impulse withstand voltage Uimp Actuator/contact >2.5 kV >4 kV
Functions
Phase asymmetry Setting accuracy – Approx. 5 … 10%
Repeat accuracy – 1
Phase failure detection At L1 or L2 or L3 100 ms
Functions Monitoring of 1/2 phases against N Yes –
Monitoring of 3 phases against N Yes
Asymmetry (failure) detection – Yes
Reverse (failure) detection – Yes
Phase failure detection Yes
N-conductor monitoring – Yes
Connection
Terminals ± Screw (Pozidriv) PZ 1
Conductor cross-sections Rigid Max. 2x 2.5 mm2
Flexible, with end sleeve Min. 1x 0.5 mm2
Ambient conditions
Permissible ambient temperature –20 … +60 °C
Resistance to climate Acc. to EN 60068-1 20/60/4
Rated operational voltage Rated operational current Switching Hysteresis Standard With TEST pushbutton
Ue Ie thresholds
Not adjustable
230 V AC 4A 0.85 × Uc 5% 5TT3414 5TT3415
5TT6113
5TT6111 5TT6114
Further technical specifications 5TT6112 5TT6115
Standards
Standards IEC 60255 IEC 60255
DIN VDE 0435-303
Supply
Rated control current Ic 1 … 10 A 0.1 … 1 A, 0.5 … 5 A,
1 … 10 A, 1.5 … 15 A
Rated control circuit voltage Uc 230 V AC
Primary operating range 0.9 … 1.1 × Uc
11 Overload capability Continuous 15 A 20 A
At 50 °C ambient temperature max. 3 s 20 A –
Independent of measuring range, max. 3 s – 30 A
Rated frequency 50/60 Hz
Contacts
μ contact (AC-15) NO 3A 5A
NC 1A
Response values ON-switching Infinitely variable
OFF-switching Permanent, 4% hysteresis
Switching delay tv 0.1 … 20 s,
continuously adjustable
Response time Non-adjustable Current corresponds to the See Siemens Service and
rated operational power of Support Portal, search term
the continuous-flow heater "Article No.", e.g. 5TT6113
Minimum contact load 10 V/100 mA
Safety
Rated insulation voltage Ui Between coil/contact 2.5 kV
Electrical isolation, creepage distances and Actuator/contact 3 mm
clearances
Rated impulse withstand voltage Uimp Actuator/contact >4 kV
Connection
Terminals ± Screw (Pozidriv) PZ 1
Conductor cross-sections Rigid Max. 2x 2.5 mm2
Flexible, with end sleeve Min. 1x 0.5 mm2
Ambient conditions
Permissible ambient temperature –20 … +60 °C
Resistance to climate Acc. to EN 60068-1 20/60/4
Rated operational Rated operational Contacts Rated control circuit With 3 green LEDs for 3 phases
voltage Ue current Ie voltage Uc
250 V AC 4A 1 CO 230/400 V 5TT3421
Rated operational Rated operational Contacts Rated control circuit With one green LED,
voltage Ue current Ie voltage Uc which lights up for right-rotating field
250 V AC 4A 1 CO 400 V 5TT3423
11 μ contact
Switching hysteresis At Rmeas 50 kΩ
2 CO
15% 10 … 15%
Measuring circuit
Measuring circuit For 3-phase and AC systems For direct voltage systems
Measurement voltage range Umeas 0 ... 500 V AC 12 ... 280 V DC
Measurement voltage Umeas Internal Approx. 15 V DC –
Primary operating range 0 … 1.1 × Umeas 0.9 … 1.1 × Umeas
Frequency range for Umeas 10 … 10000 Hz –
Alarm values Measuring shunt RAL 5 … 100 kΩ 5 … 200 kΩ
Setting of alarm value On absolute scale Infinitely variable Infinitely variable
Alternating current internal resistance Internal testing resistance >250 kΩ –
Direct current internal resistance Internal testing resistance >250 kΩ –
L+ and L- to PE – 75 kΩ each
Max. measurement current Imeas Short circuit <0.1 mA 0.2 ... 4 mA, depending on the voltage
Direct interference voltage Max. permissible 500 V DC –
Response delay ∞ to 0.9 × Rmeas <1.3 s 0.8 s
at RAL 50 kΩ and 1 μF Rmeas from ∞ to 0 Ω <0.7 s 0.4 s
Safety
Rated impulse withstand voltage Uimp Terminals A1 to A2 <4 kV
Terminals L to PE <4 kV
Terminals A1, A2 to L, PE <4 kV <3 kV
Terminals against contacts <6 kV
Degree of protection Terminals (according to EN 60529) IP20
Enclosure (according to EN 60529) IP40
Connection
Terminals ± Screw (Pozidriv) PZ 2
Conductor cross-sections Rigid Max. 2x 2.5 mm2
Flexible, with end sleeve Min. 1× 0.50 mm2
Ambient conditions
Permissible ambient temperature –20 … +60 °C
Resistance to climate Acc. to EN 60068-1 20/060/04
Mounting width 4 MW
Accessories
Immersion electrodes
• Made of stainless steel, with PG13 sealing cap
• Suitable for pure water in open containers
Temperature range Connection Article No.
0 … 60 °C Terminal connection 5TG8223
Accessories
Base load resistors for electronic devices
• With 15 cm connection wires, end sleeves and shrink sleeving
Article No.
5TG8222
Spare part
Light sensor
• Included in the 7LQ2300 package
• IP65 degree of protection
Temperature range Mounting Article No.
–20 … +70 °C Surface mounting 7LQ2920
11
Transformers 12/6
12
Information + ordering
All the important things at a glance Everything you need for your order
For information about transformers, power supply units Refer to the Industry Mall for an overview of your
and socket outlets, please visit our website products
www.siemens.com/lowvoltage
• Transformers, power supply units and socket outlets
sie.ag/2mmSHHu
Direct forwarding to the individual products in the
Your product in detail
Industry Mall by clicking on the article number in the
catalog or entering this web address incl. article n
umber
The relevant tender specifications can be found at www.siemens.com/product?Article No.
www.siemens.com/lowvoltage/tenderspecifications
Use our conversion tool for quick and easy conversion to
Siemens products www.siemens.com/conversion-tool
12
Commissioning + operation
The Siemens Industry Online Support (SIOS) provides Manuals are available for downloading in Siemens
detailed technical information Industry Online Support (SIOS) at
www.siemens.com/lowvoltage/product-support www.siemens.com/lowvoltage/manuals
• Operating instructions • Configuration Manual
• Certificates − Transformers, power supply units and socket outlets
(45315886)
Comprehensive mobile support via the Siemens Industry
Online Support app available for download from the
App Store and Play Store
You will find further information at
www.siemens.com/support-app
System overview
Transformers
Note:
You will find a detailed range of accessories with the basic units.
12
12
Bell transformers
Mounting width 2 MW 2 MW
1 7
1 7 230 V AC
230 V AC
50Hz 50Hz
I201_18469
I201_18470
8V
4 8 4 6 8
8V
12V
2 MW 2 MW
1 7 1 7
230 V AC 230 V AC
50Hz 50Hz
I201_18472
I201_18471
8V 12V 4V 8V
4 6 8 4 6 8
24V 12V
14 VA 18 VA
– –
– –
4AC3214-0 –
– 4AC3218-0
12
1 7 1 7
230 V AC 230 V AC
50Hz 50Hz
I201_18473
I201_18474
8V
4 8 4 6
8V 8
12V
5 MW 5 MW 5 MW
1 11 1 11 1 11
230 V AC 230 V AC 230 V AC
50Hz I201_18477 50Hz 50Hz
I201_18475
I201_18476
6 8 10 12 6 8 10 12 2 4 10 12 2 4 10 12 6 8 10 12 6 8 10 12 6 8 10 12 6 8 10 12
12V 24V 16V 32V 12V 24V 12V 24V
40 VA 40 VA 63 VA
– – –
– – –
4AC3740-1 – –
– 4AC3740-0 –
– – 4AC3763-0
12
A1 A2
US+ US-
12
Accessories
5TE6 hinged lids for socket outlets
Mounting width Article No. Article No.
2.5 MW 5TE9120 –
1)
The hinged lid can be retrofitted on all versions.
2)
In distribution boards with 55 mm mounting depth, the socket outlet can only be used without the hinged lid.
3)
In system components where equipment is still live even after the main switch has been disconnected, this must be indicated
according to EN 50110-1 (VDE 0105-1) and IEC/EN 60204-1/VDE 0113-1.
Yellow socket outlets are used for these applications.
12
5TE6800
5TE6801
Further technical specifications 5TE6810 5TE6802 5TE6803 5TE6804
Standards
Standards VDE 0620-1 CEI 23-50 CEE 7 standard sheet V UL 498
Approvals VDE 0620-1 – UL File No. E258598/
CSA C22.2 No. 182.3M
Connection
Terminals ± Screw (Pozidriv) PZ1
Terminal tightening torque Max. 0.8 ... 1 Nm
Stripped length 10 mm
Conductor cross-section Rigid 1.5 ... 6 mm2 (AWG 10 … 14)
Flexible, with end sleeve 0.5 ... 4 mm2 (AWG 14)
Ambient conditions
Permissible ambient temperature –10 … +55 °C
Degree of protection Acc. to EN 60529 IP20, with connected conductors
Mounting position Without hinged lid Any
With hinged lid Horizontally or vertically
– – – 5TE6804
5TE6810 5TE6803 – –
– – 5TE6802 –
12
Busbar Systems
Information + ordering
All the important things at a glance Everything you need for your order
For information about busbar systems, please visit our Refer to the Industry Mall for an overview of your
website www.siemens.com/lowvoltage products
• Busbar systems sie.ag/2lXoUFl
Direct forwarding to the individual products in the
Your product in detail Industry Mall by clicking on the article number in the
catalog or entering this web address incl. article number
The relevant tender specifications can be found at www.siemens.com/product?Article No.
www.siemens.com/lowvoltage/tenderspecifications
Use our conversion tool for quick and easy conversion to
Siemens products www.siemens.com/conversion-tool
13
Commissioning + operation
The Siemens Industry Online Support (SIOS) provides Manuals are available for downloading in Siemens
detailed technical information Industry Online Support (SIOS) at
www.siemens.com/lowvoltage/product-support www.siemens.com/lowvoltage/manuals
• Operating instructions • Configuration Manual
• Certificates − 8US busbar systems (109769746)
System overview
Busbar supports N/PE busbar supports Flat copper TT special Connection Cover Blanking covers
profiles profiles pieces profiles
Connection modules Terminals Covers
Bus-mounting Bus-mounting Bus-mounting switch Covers Auxiliary switches Lateral modules
fuse bases fuse holders disconnectors
13
Device adapters Device holders N/PE modules Lateral modules Vibration & shock kits
Note:
You will find a detailed range of accessories with the basic units.
40 mm 60 mm compact 60 mm 60 mm
busbar system busbar system busbar system busbar system
flat copper profile TT profile
Busbars
Busbar center-to-center spacing 40 mm 60 mm 60 mm 60 mm
Flat copper profiles 5 mm 12 × 5 mm 12 × 5 mm 12 × 5 mm –
15 × 5 mm 15 × 5 mm
20 × 5 mm
25 × 5 mm
30 × 5 mm
10 mm 12 × 10 mm 12 × 10 mm 20 × 10 mm –
15 × 10 mm 30 × 10 mm
TT special profile – – – 2400 × 30 × 40 mm
Rated values
Rated operational current IEC 200 … 360 A 200 … 360 A 200 … 900 A 1020 … 1600 A
Ie UL 508 – 300 A 630 A 1400 A
Rated operational voltage IEC 690 V AC 690 V AC 690 V AC 690 V AC
Ue UL 508 – 600 V AC 600 V AC 600 V AC
Standards
IEC ■ ■ ■ ■
UL 508 ■ ■ ■ ■
Connection modules and terminals for
Circular conductors IEC – Cu 1.5 … 150 mm2 Cu 1.5 … 300 mm2 Cu 16 … 300 mm2
Al 95 … 300 mm2
UL 508 – Cu AWG 2 … MCM 300 Cu AWG 16 … MCM 600 Cu AWG 4 … MCM 600
Al AWG 3
Laminated copper – Cu lam. Cu lam. Cu lam.
15 … 20 × 5 … 10 mm 3 × 20 × 1 …10 × 32 × 1 mm 2 × 40 × 10 mm
Cable lugs – – Max. 240 mm2 –
Built-in components for
NEOZED bus-mounting fuse bases – ■ ■ ■
DIAZED bus-mounting fuse bases – – ■ ■ 13
Bus-mounting fuse holders for – – ■ ■
cylindrical fuses 10 × 38 mm
Class CC bus-mounting fuse – – ■ ■
holders
Class J bus-mounting fuse holders – – ■ ■
NEOZED bus-mounting switch ■ ■
disconnectors
Device adapters for
Universal application 3P/5P – ■/■ ■/■ ■/■
Molded case circuit breakers – ■ ■ ■
Switch disconnectors – – ■ ■
Fuse switch disconnectors – – ■ ■
SIRIUS 3RM1 motor starters – ■ – –
SIRIUS load feeders – – ■ ■
3RM193 fuse module – ■ – –
5SY miniature circuit breakers – ■ – –
Further information
See page 13/6 See page 13/7 See page 13/12 See page 13/14
➊ Basic assemblies
For 40 mm 8US busbar system up to 400 A
I201_20501
➊ ➋ ➌ ➍
Busbar supports
No. of poles 3P 5P
Suitable accessories 3P 5P
Flat copper profile
Surface Length Size Article No. Article No.
Bare 2400 mm 12 × 5 mm 8WC5123 8WC5123
15 × 5 mm 8WC5121 –
Cover profiles for busbars
Material Length Size Article No. Article No.
Plastic profile 1000 mm 12 × 5 mm 8US1922-2CA00 8US1922-2CA00
13 15 × 5 mm 8US1922-2AA00 –
➊ Basic assemblies
For 8US compact busbar system up to 360 A (3P) or 200 A (5P)
I201_20502
➊ ➋ ➌ ➍
Busbar supports 1)
No. of poles 3P/5P
Flat copper profiles Rated operational Short-circuit current Standard Dimensions Min. order Connection
voltage Ue rating SCCR quantity
12 × 5 mm 12 × 10 mm IEC UL 508 3-pole 5-pole L1– L3 + N + PE/N
Interior mounting
■ ■ 690 V AC – 54 kA 32 kA IEC 12 × 160 × 45 mm 10 units 8US1923-5CA02
– 600 V AC 18 kA – UL 508 12 × 160 × 45 mm 10 units 8US1923-5CA02
1)
Including end cover
Suitable accessories
Flat copper profiles
Surface Length Size Article No.
Bare 2400 mm 12 × 5 mm 8WC5123
UL spacers for busbar supports
Dimensions Minimum order quantity Height Article No.
12 × 160 x 18 mm 10 units 18 mm 8US1922-1CA02
Stabilizing modules
• Only for 12 × 5 mm busbars 13
• For protecting the N and PE busbars against bending
Dimensions Minimum order quantity Article No.
2 × 160 × 47 mm 10 units 8US1928-5CA02
Cover profiles
Dimensions Minimum order quantity Article No.
700 × 160 × 63 mm 2 units 8US1922-2CB02
I201_20503
➊ ➋ ➌ ➍
Conductor Rated operational current Rated operational voltage Rated peak with- Standard Minimum Dimensions
cross-section Ie Ue stand current order quantity
IEC UL 508 IEC UL 508 IEC Ipk max
Spring terminal
1.5 … 16 mm2 63 A 48 A 690 V AC 600 V AC 10 kA IEC, UL 508 6 units 20 × 160 × 91 mm
Connecting terminal
6 … 50 mm2 175 A 175 A 690 V AC 600 V AC 40.5 kA IEC, UL 508 1 unit 54 × 160 × 115 mm
10 … 120 mm2 250 A 200 A 690 V AC 600 V AC 35.4 kA IEC, UL 508 1 unit 90 × 160 × 80 mm
– – 690 V AC 600 V AC 35.1 kA IEC, UL 508 1 unit 30 × 160 × 80 mm
35.4 kA IEC, UL 508 1 unit 30 × 160 × 80 mm
35 … 150 mm2 275 A 285 A 690 V AC 600 V AC 45.9 kA IEC, UL 508 1 unit 90 × 160 × 115 mm
➌ Built-in components
For 8US compact busbar systems up to 360 A (3P)
13
I201_20504
ಪ ಫ ಬ ಭ
Number of poles
Mounting width
Conductor cross-section For flat copper profiles Rated operational Rated operational voltage Ue Standard Minimum
current Ie order quantity
12 × 5 mm 12 × 10 mm IEC IEC
Box terminals
Rigid 1.5 … 10 mm2 ■ ■ 63 A 400 V AC IEC 6 units
Flexible 1.5 … 25 mm2
See NEOZED screw caps, NEOZED adapter sleeves and NEOZED fuse links, from page 7/1 onwards
Connection modules Connection modules Connection modules Connection modules
3P 3P N PE
8US1921-1BA02 – – –
8US1921-1CB02 – – –
– 8US1921-1CD02 – –
– – 8US1921-1CE02 –
– – – 8US1921-1CF02
8US1921-1CC02 – – –
13
5SG6208
➍ Device adapters
For 8US compact busbar system up to 360 A (3P) or 200 A (5P)
I201_20505
➊ ➋ ➌ ➍
Rated operational Rated operational voltage Standard For flat copper profiles Adapters Minimum
current Ie Ue order quantity
IEC UL 508 IEC UL 508 12 × 5 mm 12 × 10 mm Height Width Length
16 A – 690 V AC – IEC – – 160 mm 22.5 mm 122 mm 4 units –
200 mm 22.5 mm 122 mm 5 units –
25 A – 690 V AC – IEC ■ – 160 mm 22.5 mm 41.5 mm 5 units –
185 mm 22.5 mm 23.5 mm 5 units –
200 mm 22.5 mm 41.5 mm 5 units –
32 A – 690 V AC – IEC ■ – 160 mm 18 mm 73 mm 12 units –
25 A 690 V AC 600 V AC IEC, UL 508 ■ ■ 160 mm 45 mm 63 mm 4 units 8US1651-5DK02
63 A – 690 V AC – IEC ■ – 160 mm 18 mm 73 mm 12 units –
160 mm 18 mm 82 mm 12 units –
65 A 690 V AC 600 V AC IEC, UL 508 ■ ■ 160 mm 54 mm 63 mm 4 units 8US1661-5FK02
144 A – 690 V AC – IEC ■ ■ 160 mm 77 mm 35 mm 1 unit –
Suitable accessories
N modules
Rated voltage Ue Connecting terminal Dimensions Minimum order quantity Article No.
13 690 V AC 1.5 … 16 mm2 9 × 160 × 114 mm 12 units –
PE modules
Rated voltage Ue Connecting terminal Dimensions Minimum order quantity Article No.
690 V AC 1.5 … 16 mm2 9 × 160 × 114 mm 12 units –
Support modules
Dimensions Minimum order quantity Article No.
18 × 160 × 54 mm 6 units 8US1620-5AK02
Lateral modules
Dimensions Minimum order quantity Article No.
9 × 160 × 47 mm 12 units 8US1998-2BH02
With latching function Adapters, 1-pole With fuse module and With DIN Adapters, 1-pole
DIN mounting rail mounting rail
– – 8US1615-5CK10 – – –
– – 8US1215-5CS10 – – –
– – – 8US1616-0AK02 – –
– – – – 8US1716-0RK00 –
– – – 8US1216-0AS00 – –
– 8US1621-2NJ02 – – – –
– – – – – –
– 8US1621-2FK02 – – – –
– – – – – 8US1624-2FK02
– – – – – –
8US1613-4AU01 – – – – –
Article No. Article No. Article No. Article No. Article No. Article No.
– 8US1600-0RE02 8US1600-0RE02 8US1600-0RE02 8US1600-0RE02 8US1600-0RE02 13
Article No. Article No. Article No. Article No. Article No. Article No.
– 8US1600-0RF02 8US1600-0RF02 8US1600-0RF02 8US1600-0RF02 8US1600-0RF02
Article No. Article No. Article No. Article No. Article No. Article No.
8US1620-5AK02 8US1620-5AK02 8US1620-5AK02 8US1620-5AK02 8US1620-5AK02 8US1620-5AK02
Article No. Article No. Article No. Article No. Article No. Article No.
8US1998-2BH02 8US1998-2BH02 8US1998-2BH02 8US1998-2BH02 8US1998-2BH02 8US1998-2BH02
Article No. Article No. Article No. Article No. Article No. Article No.
– 8US1998-1AA02 8US1998-1AA02 8US1998-1AA02 8US1998-1AA02 8US1998-1AA02
➊ Basic assemblies
Up to 630 A
I201_20502
➊ ➋ ➌ ➍
Suitable accessories
Flat copper profile
Surface Length Size Rated operational Cross-section Standard Article No.
current
Bare 1100 mm 25 × 5 mm 400 A 125 mm2 EN 12167 8WC5031-1AA00
30 × 5 mm 447 A 150 mm2 EN 12167 8WC5033-1AA00
13 2400 mm 12 × 5 mm 200 A 60 mm2 EN 12167 8WC5123
15 × 5 mm 250 A 75 mm2 EN 12167 8WC5121
20 × 5 mm 320 A 100 mm2 EN 12167 8WC5126
25 × 5 mm 400 A 125 mm2 EN 12167 8WC5131
30 × 5 mm 447 A 150 mm2 EN 12167 8WC5133
20 × 10 mm 520 A 200 mm2 EN 12167 8WC5128
30 × 10 mm 630 A 300 mm2 EN 12167 8WC5134
Tin-coated 2000 mm 12 × 5 mm 200 A 60 mm2 EN 12167 8WC5051
15 × 5 mm 250 A 75 mm2 EN 12167 8WC5052
20 × 5 mm 320 A 100 mm2 EN 12167 8WC5053
25 × 5 mm 400 A 125 mm2 EN 12167 8WC5054
30 × 5 mm 447 A 150 mm2 EN 12167 8WC5055
20 × 10 mm 520 A 200 mm2 EN 12167 8WC5063
30 × 10 mm 630 A 300 mm2 EN 12167 8WC5065
End covers
• For covering free busbar ends
For connection For busbar support Standard Article No.
L1–L3 8US1923-2AA01, 8US1923-3AA01, 8US1923-3UA01 IEC, UL 508 8US1922-1AC00
L1–L3 + PE/N 8US1923-4AA00 IEC 8US1922-1AB00
Connection Connection Connection Connection
L1–L3 L1/L2/L3/PE/N L1–L3 + PE/N PE/N
8US1923-3AA01 – – –
8US1923-3UA01 – – –
– – 8US1923-4AA00 –
– – – 5SH3540
– – – 8US1923-1AA01
8US1923-2AA01 – – –
– 8US1923-5AA00 – –
Blanking covers
40 mm 14 mm 12, 15, 20, 25, 30 × 10 mm UL 508 8US1922-2BA00
13
Length Height Depth Standard Article No.
700 mm 195 mm 63 mm UL 508 8US1922-2EB00
Base plates
Version Length Width Standard Article No.
For 3-pole system 1100 mm 240 mm UL 508 8US1922-2UA01
➊ Basic assemblies
Up to 1600 A
I201_20502
➊ ➋ ➌ ➍
Busbar supports
No. of poles 3P
Copper profile Rated operational Rated operational voltage Short-circuit current Standard Connection
current Ie Ue rating SCCR
IEC UL 508 IEC UL 508 IEC UL 508 L1–L3
Interior mounting
TT special profile 1600 A 1400 A 690 V AC 600 V AC 90 kA 100 kA IEC, UL 508 8US1943-3AA00
Suitable accessories
TT special copper profile
Surface Length Rated operational Rated operational voltage Cross-section Article No.
current
Tin-coated 2400 mm 1600 A 690 V AC 720 mm2 8US1948-2AA00
Cover profile for TT special copper profile
Length Article No.
1000 mm 8US1922-2DA00
Blanking covers
Length Height Depth Standard Article No.
13 700 mm 195 mm 63 mm UL 508 8US1922-2EB00
Partitions, closed
• For additional lateral touch protection at the top/bottom
Length Depth Article No.
76
48
2400
NSB0_91362b
2400 mm 76 mm 8US1922-1JA00
13
I201_20503
➊ ➋ ➌ ➍
Conductor cross-section, Conductor cross-section, Rated operational Rated operational voltage Standard Length
circular conductor laminated copper current Ie Ue
IEC UL 508 IEC UL 508 IEC UL 508
With cover
Cu 1.5 … 16 mm2 Cu AWG 16 … 4 Cu lam. 8 × 6 × 0.5 mm 63 A 48 A 690 V AC 600 V AC IEC, UL 508 200 mm
Cu 6 … 50 mm2 Cu AWG 10 … 2 – 175 A 175 A 690 V AC 600 V AC IEC, UL 508 200 mm
Cu 25 … 120 mm2 Cu AWG 6 … MCM 250 – 250 A 250 A 690 V AC 600 V AC IEC, UL 508 200 mm
Cu 95 … 300 mm2 AWG 3/0 … MCM 600 – 500 A 420 A 690 V AC – IEC, UL 508 200 mm
Al 120 … 240 mm2
Without cover
Cu 95 … 300 mm2 AWG 3/0 … MCM 600 – 500 A 420 A 690 V AC 600 V AC IEC, UL 508 184 mm
– – Cu lam. 3 × 20 × 1 … 10 × 32 × 1 mm 550 A 420 A 690 V AC 600 V AC IEC, UL 508 184 mm
For 4th pole (PE/N) 2)
Cu 1.5 … 16 mm2 – – – – 690 V AC 600 V AC IEC, UL 508 242 mm
1)
Shown without cover
2)
For mounting on device adapter or device holder
Suitable accessories
13 Cover for connection module
Connection modules
For 5 mm and 10 mm flat copper profiles For 5 mm and 10 mm flat copper profiles For laminated copper
and TT special profile
Width Connection modules Connection modules Connection modules Connection modules Connection modules
3P 3P 3P PE/N 3P
20 mm 5SH3538 – – – –
54 mm – – 8US1921-1BA00 – –
81 mm – – 8US1921-1AA00 – –
135 mm – 5SH3535 1) – – –
153 mm – – – – 8US1941-2AA03
153 mm – – – – 8US1941-2AA04
18 mm – – – 8US1200-0AA00 –
13
Article No. Article No. Article No. Article No. Article No.
– – – – 8US1922-1GC00
I201_20503
➊ ➋ ➌ ➍
Conductor cross-section, Conductor cross-section, Rated operational Rated operational voltage Standard Minimum
circular conductor laminated copper current Ie Ue order quantity
IEC UL 508 IEC UL 508 IEC UL 508
Cu 1.5 … 16 mm2 AWG 16 .. 6 Cu lam. 8 × 6 × 0.5 mm 65 A 55 A 690 V AC 600 V AC IEC, UL 508 15 units
100 units
Cu 4 … 35 mm2 AWG 10 … 2 Cu lam. 3 × 9 × 0.8 mm, 115 A 115 A 690 V AC 600 V AC IEC, UL 508 15 units
Cu lam. 6 × 9 × 0.8 mm 50 units
Cu 16 … 70 mm2 AWG 4 … 2/0 Cu lam. 2 × 9 × 0.8 mm, 175 A 175 A 690 V AC 600 V AC IEC, UL 508 15 units
Cu lam. 6 × 9 × 0.8 mm, 50 units
Cu lam. 6 × 13 × 0.5 mm
Cu 16 … 120 mm2 AWG 4 … MCM 250 Cu lam. 4 × 15.5 × 0.8 mm, 250 A 255 A 690 V AC 600 V AC IEC, UL 508 15 units
Cu lam. 6 × 15.5 × 0.8 mm, 50 units
Cu lam. 10 × 15.5 × 0.5 mm
1)
Finely stranded, directly clamped or with end sleeve, solid and stranded circular conductor
Suitable accessories
Terminal covers for circular conductors
13 • Fixing to busbar
Length Width
200 mm 84 mm
Terminals 1)
For 12 × 5 mm, 15 × 5 mm, 20 × 5 mm, 25 × 5 mm and 30 × 5 mm For 12 × 10 mm, 15 × 10 mm, 20 × 10 mm, 25 × 10 mm and 30 × 10 mm
flat copper profiles flat copper profiles and TT special profile
8US1921-2AA01 – – – 8US1921-2BA01 – – –
8US1921-2AA00 – – – 8US1921-2BA00 – – –
– 8US1921-2AB01 – – – 8US1921-2BB01 – –
– 8US1921-2AB00 – – – 8US1921-2BB00 – –
– – 8US1921-2AD01 – – – 8US1921-2BD01 –
– – 8US1921-2AD00 – – – 8US1921-2BD00 –
– – – 8US1921-2AC01 – – – 8US1921-2BC01
– – – 8US1921-2AC00 – – – 8US1921-2BC00
13
Article No. Article No. Article No. Article No. Article No. Article No. Article No. Article No.
8US1922-1GA00 8US1922-1GA00 8US1922-1GA00 8US1922-1GA00 8US1922-1GA00 8US1922-1GA00 8US1922-1GA00 8US1922-1GA00
I201_20503
➊ ➋ ➌ ➍
Conductor cross-section, Conductor Conductor Rated operational Rated operational voltage Standard
circular conductor cross-section, cross-section, current Ie Ue
IEC UL 508 laminated copper cable lugs IEC UL 508 IEC UL 508
Cu 95 … 185 mm2 AWG 3/0 … MCM 350 – – 300 A 310 A 690 V AC 600 V AC IEC,
Al 95 … 185 mm2 UL 508
Cu 95 … 300 mm2 AWG 3/0 … MCM 600 – – 500 A 420 A 690 V AC 600 V AC IEC,
Al 120 … 140 mm2 UL 508
– – Cu lam. 3 × 20 × – 500 A 420 A 690 V AC 600 V AC IEC,
1 … 10 × 24 × 1 mm UL 508
Cu lam. 2 × 40 × 10 mm – 1250 A – 690 V AC – IEC
Suitable accessories
Terminal covers for circular conductors
• Fixing to busbar
13 Length Width
200 mm 270 mm
Terminals
For 20 × 5 mm, 25 × 5 mm and 30 × 5 mm For 20 × 10 mm, 25 × 10 mm and 30 × 10 mm For 40 × 25 mm and 30 × 10 mm
flat copper profiles flat copper profiles flat copper profiles
and TT special profile
Mounting
– 8US1941-2AA01 – – – –
– 8US1941-2AA02 – – – –
Article No. Article No. Article No. Article No. Article No. 13
8US1922-1GA02 – – – –
➌ Built-in components
Up to 630 A
I201_20504
ಪ ಫ ಬ ಭ
For flat copper Rated operational Rated operational voltage Ue Standard Standard With touch protection
profiles current Ie
IEC UL 508 IEC AC IEC DC UL
Box terminals
5 mm and 10 mm 25 A – 500 V AC – – IEC – – –
63 A – 400 V AC 250 V DC – IEC 5SG6202 5SG6206 5SG6207
690 V AC – – IEC – – –
– 30 A 690 V AC – 600 V AC IEC, U, s – – –
– – 600 V AC u, s – – –
100 A – – 600 V AC UUS
C – – –
200 A – – 600 V AC UUS
C – – –
400 A – – 600 V AC s, CUUS – – –
Further information
3NP1 fuse switch disconnectors See page 8/86 See page 8/86 See page 8/86
Note:
NEOZED adapter sleeves or DIAZED screw adapters are required for NEOZED and DIAZED bus-mounting fuse bases.
13
Suitable accessories
NEOZED covers for standard version
Size Version Mounting width Article No. Article No. Article No.
D02 Standard 1.5 MW 5SH5241 – –
5SF6015 5SF6020 – – – – –
– – – – – – –
5SF6215 5SF6220 – – – – –
– – 3NW7431 – – – –
– – – 3NW7431-0HG – – –
– – – – 3NW7431-6HG – –
– – – – – 3NW7431-7HG –
– – – – – – 3NW7431-8HG
See page 8/86 See page 8/86 See page 8/86 See page 8/86 See page 8/86 See page 8/86 See page 8/86
13
Article No. Article No. Article No. Article No. Article No. Article No. Article No.
– – – – – – –
– – – – – – –
– – – – – – –
Article No. Article No. Article No. Article No. Article No. Article No. Article No.
5SH2042 – – – – – –
5SH2242 – – – – – –
➌ Built-in components
Up to 630 A
I201_20504
ಪ ಫ ಬ ಭ
For flat copper Rated operational Rated operational voltage Ue Standard Without LED signal detector With LED
profiles current Ie signal detector
IEC UL 508 IEC AC IEC DC UL 508
Box terminals
5 mm, 10 mm 63 A – 400 V AC – – IEC 5SG7234-1 2) – 5SG7234-2 2)
110 V DC – IEC – 5SG7230 1) –
1)
From 35 A current load use 5SH5526 lateral module
2)
From 35 A current load use 5SH5533 lateral module
Note:
NEOZED adapter sleeves or DIAZED screw adapters are required for NEOZED and DIAZED bus-mounting fuse bases.
Suitable accessories
Auxiliary switches
• For signaling the switching state for bus-mounting switch disconnectors
Contacts Mounting width Article No. Article No. Article No.
1 CO 0.5 MW – 5SH5525 –
13
Lateral modules
• For greater heat dissipation for loads from 35 A
Mounting width Article No. Article No. Article No.
0.5 MW 5SH5533 5SH5526 5SH5533
Reducers
• For NEOZED D01 fuse links in bus-mounting switch disconnectors
Article No. Article No. Article No.
– 5SH5527 –
13
I201_20505
➊ ➋ ➌ ➍
Rated operational Rated operational voltage Ue Standard For copper Adapters Connecting cable
current Ie profiles
IEC UL 508 IEC UL 508 Width Height Cross-section Max. temperature Length
25 A 25 A 690 V AC 600 V AC IEC, UL 508 5 mm, 10 mm, 45 mm 200 mm AWG 12 150 °C 99 mm
TT profile 167 mm
260 mm AWG 12 150 °C 99 mm
167 mm
32 A 32 A 690 V AC 600 V AC IEC, UL 508 5 mm, 10 mm, 45 mm 200 mm AWG 10 105 °C 118 mm
TT profile 150 °C 99 mm
167 mm
260 mm AWG 10 150 °C 99 mm
167 mm
80 A 80 A 690 V AC 600 V AC IEC, UL 508 5 mm, 10 mm, 54 mm 200 mm AWG 4 150 °C 150 mm
TT profile 260 mm AWG 4 150 °C 150 mm
119 mm 260 mm AWG 4 150 °C 150 mm
100 A 100 A 690 V AC 600 V AC IEC, UL 508 5 mm, 10 mm, 72 mm 200 mm AWG 4 105 °C 210 mm
TT profile
– – – – – 5 mm, 10 mm, 45 mm 200 mm – – –
TT profile – – –
260 mm – – –
13
Accessories
Lateral modules
• For extending device adapters and device holders of the same length
Length Width
200 mm 9 mm
For lateral mounting on
device adapter
8US1251-5DS10 – – – – – – –
8US1251-5DS11 – – – – – – –
8US1251-5DT10 – – – – – – –
8US1251-5DT11 – – – – – – –
– 8US1211-1NS10 – – – – – –
– – 8US1251-5NS10 – – – – –
– – 8US1251-5NS11 – – – – –
– – 8US1251-5NT10 – – – – –
– – 8US1251-5NT11 – – – – –
– – – 8US1261-5MS13 – – – –
– – – 8US1261-6MT10 – – – –
– – – – – 8US1211-6MT10 – –
– – – – 8US1211-4TR00 – – –
– – – – – – – 8US1250-1AA10
– – – – – – 8US1250-5AS10 –
– – – – – – 8US1250-5AT10 –
13
Article No. Article No. Article No. Article No. Article No. Article No. Article No. Article No.
8US1998-2BJ10 8US1998-2BJ10 8US1998-2BJ10 8US1998-2BJ10 – – 8US1998-2BJ10 –
I201_20505
➊ ➋ ➌ ➍
Rated operational Rated operational voltage Ue Standard For copper profile Adapters Connecting cable
current Ie
IEC UL 508 IEC UL 508 Length Width
Screw terminals
80 A 80 A – 600 V AC UL 508 5 mm, 10 mm, TT profile 200 mm 81 mm AWG 4
125 A 125 A 690 V AC 600 V AC IEC, UL 508 5 mm, 10 mm, TT profile 200 mm 90 mm Cu laminated 6 × 9 × 0.8 mm
Busbar contact
144 A – 690 V AC – IEC 5 mm, 10 mm, TT profile 200 mm 76 mm –
160 A – 690 V AC – IEC 5 mm, 10 mm, TT profile 175 mm 108 mm –
250 A 250 A 690 V AC 600 V AC IEC, UL 508 5 mm, 10 mm, TT profile 190 mm 105 mm –
240 mm 105 mm –
630 A 630 A 690 V AC 600 V AC IEC, UL 508 5 mm, 10 mm, TT profile 320 mm 250 mm –
– 690 V AC – IEC 5 mm, 10 mm, TT profile 320 mm 184 mm –
320 mm 250 mm –
1)
Observe the short-circuit strength of the busbar system: Short-circuit strength > 50 kA on request.
2)
Usable only for 3VL circuit breakers with line-side box terminals.
3)
Only for 3VL 250 A circuit breakers, for screw fixing with metric thread, for flat terminals.
4)
Without connecting cables. The connecting cable between adapter and device should be manufactured in accordance with the rated operational current as a circular conductor,
e.g. H07V-R with cable lug, or as a flat conductor for an M10 pin connector.
5)
Without connecting cables. The connecting cable between adapter and device should be manufactured in accordance with the rated operational current as a circular conductor,
e.g. H07V-R, bared at both ends for tunnel terminals.
Device adapters
For molded case circuit breakers For switch For fuse switch
disconnectors disconnectors
3VA 3VL 1) 3KA and 3KL 3NP5
Device 3-pole 4-pole 3-pole 3-pole 3-pole
Size/type
I201_20505
➊ ➋ ➌ ➍
Rated operational Rated operational voltage Ue Standard For copper Adapters Connecting cable Device
current Ie profile
IEC UL 508 IEC UL 508 U, s Length Width Cross-section Max. temperature Size
Screw terminals
25 A 25 A 690 V AC 600 V AC – IEC, UL 508 5 mm, 10 mm, 200 mm 45 mm AWG 12 150 °C S00
TT profile S0
260 mm 45 mm AWG 12 150 °C S00
32 A 32 A 690 V AC 600 V AC – IEC, UL 508 5 mm, 10 mm, 200 mm 45 mm AWG 10 150 °C S0
TT profile 260 mm 45 mm AWG 10 150 °C S0
– – 690 V AC U, s 5 mm, 10 mm, 200 mm 45 mm AWG 10 105 °C S00/S0
TT profile
65 A 65 A 690 V AC 600 V AC – IEC, UL 508 5 mm, 10 mm, 260 mm 54 mm AWG 4 150 °C S2
TT profile 119 mm AWG 4 150 °C S2
80 A 80 A 690 V AC 600 V AC – IEC, UL 508 5 mm, 10 mm, 200 mm 54 mm AWG 4 150 °C S2
TT profile 215 mm 72 mm AWG 4 150 °C S3
Spring-loaded terminals
25 A 25 A 690 V AC 600 V AC – IEC, UL 508 5 mm, 10 mm, 200 mm 45 mm AWG 12 150 °C S00
TT profile 260 mm 45 mm AWG 12 150 °C S00
13 32 A 32 A 690 V AC 600 V AC – IEC, UL 508 5 mm, 10 mm, 200 mm 45 mm AWG 10 150 °C S0
TT profile 260 mm 45 mm AWG 10 150 °C S0
Suitable accessories
Vibration & shock kit S2
Use
For size 2 devices
Lateral modules
• For extending device adapters and device holders of the same length
Length Width
200 mm 9 mm
– 8US1261-6MT10 – – – –
– – 8US1211-6MT10 – – –
8US1261-5MS13 – – – – –
– – – 8US1211-4TR00 – –
8US1251-5DS11 – – – – –
8US1251-5DT11 8US1251-5DT11 8US1251-5DT11 + 8US1250-5AT10 – – –
8US1251-5NS11 – – – – – 13
8US1251-5NT11 8US1251-5NT11 8US1251-5NT11 + 8US1250-5AT10 – – –
Article No. Article No. Article No. Article No. Article No. Article No.
8US1998-1DA10 8US1998-1DA10 8US1998-1DA10 – – –
Article No. Article No. Article No. Article No. Article No. Article No.
8US1998-2BJ10 8US1998-2BJ10 8US1998-2BJ10 – 8US1998-2BJ10 8US1998-2BJ10
I201_20505
➊ ➋ ➌ ➍
54 mm 54 mm 8US1998-7CB54
72 mm 54 mm 8US1998-7CB72
Positioning pieces
• For pushing on
• Secures the adaptable devices on the adapter
For adapter width Article No.
45 mm 8US1998-1DA45
54 mm 8US1998-1DA54
Connecting element
13 • For connecting busbar adapters and device holders
Article No.
8US1998-1AA10
Spacers
• Fix the feeder to the busbar adapter
Article No.
8US1998-1BA10
Vibration & shock kit
Article No.
8US1998-1CA10
13
Terminal Blocks
Information + ordering
All the important things at a glance Everything you need for your order
For information about terminal blocks, please visit our Refer to the Industry Mall for an overview of your
website www.siemens.com/distribution-components products
• Terminal blocks sie.ag/2kW8ZXo
Direct forwarding to the individual products in the
Your product in detail Industry Mall by clicking on the article number in the
catalog or entering this web address incl. article n
umber
Use our conversion tool for quick and easy conversion to www.siemens.com/product?Article No.
Siemens products www.siemens.com/conversion-tool
14
Commissioning + operation
8WH6 8WH6
iPo plug-in terminals iPo installation
terminals
Through-type terminals Through-type terminals 2.5 … 150 mm2 See page 14/8 2.5 … 35 mm2 See page 14/18
Three-tier terminals – –
–
Infeed terminals 2.5 mm2 See page 14/16
Diode terminals – –
Shield terminals – –
1.5 … 35 mm2 See page 14/24 2.5 mm2 See page 14/36 1.5 … 2.5 mm2 See page 14/40 2.5 … 240 mm2 See page 14/44
1.5 … 4 mm2 See page 14/27 – 1.5 mm2 See page 14/40 2.5 … 4 mm2 See page 14/47
2.5 … 4 mm2 See page 14/30 – 1.5 … 2.5 mm2 See page 14/40 4 … 6 mm2 See page 14/48
– – – –
– – – –
– – – –
– – – –
– – – –
2.5 mm2 See page 14/34 – – 2.5 mm2 See page 14/55
Diameter
– – – See page 14/56
2 … 35 mm
From page 14/24 From page 14/36 From page 14/40 From page 14/44
8WA1 8WA2
screw terminals spring-loaded
terminals
Three-tier terminals – –
Shield terminals – –
14
Terminals Color
➊ Through-type terminals
2 Gray 8WH6000-0AF00 8WH6000-0AG00
Blue 8WH6000-0AF01 8WH6000-0AG01
3 Gray 8WH6003-0AF00 8WH6003-0AG00
Blue 8WH6003-0AF01 8WH6003-0AG01
4 Gray 8WH6004-0AF00 8WH6004-0AG00
Blue 8WH6004-0AF01 8WH6004-0AG01
➋ PE through-type terminals
2 Green-yellow 8WH6000-0CF07 8WH6000-0CG07
3 Green-yellow 8WH6003-0CF07 8WH6003-0CG07
4 Green-yellow 8WH6004-0CF07 8WH6004-0CG07
Specific accessories
Covers
14 Terminals Color Width Article No. Article No.
2 Gray 2.2 mm 8WH9000-1GA00 8WH9003-1GA00
3 Gray 2.2 mm 8WH9000-2GA00 8WH9003-2SA00
4 Gray 2.2 mm 8WH9000-4GA00 8WH9003-4SA00
Compartment partitions
Terminals Color Width Article No. Article No.
2 Gray 2.0 mm 8WH9070-0AA00 8WH9070-0AA00
3 Gray 2.0 mm 8WH9070-0GA00 8WH9070-0GA00
4 Gray 2.0 mm 8WH9070-0HA00 8WH9070-0HA00
Cover segments
Color Article No. Article No.
Gray 8WH9000-0GA00 –
Terminals Color
➊ Through-type terminals
2 Gray 8WH6000-0AN00 8WH6000-0AQ00 8WH6000-0AS00
Blue 8WH6000-0AN01 8WH6000-0AQ01 8WH6000-0AS01
➋ PE through-type terminals
2 Green-yellow 8WH6000-0CN07 8WH6000-0CQ07 –
Specific accessories
Connecting combs
Number of poles Article No. Article No. Article No.
2-pole 8WH9020-3AB00 8WH9020-3AD00 8WH9020-3AF00
3-pole 8WH9020-3AC00 8WH9020-3AE00 8WH9020-3AG00
14 Tap-off terminal
Number of poles Article No. Article No. Article No.
1-pole 8WH9120-0DA00 8WH9120-0DA00 8WH9120-0DA00
Test plugs
Surface Article No. Article No. Article No.
Metal 8WH9010-0NB00 8WH9010-0NB00 8WH9010-0NB00
Insulating sleeves for test plugs
Color Article No. Article No. Article No.
Red 8WH9010-0MB02 8WH9010-0MB02 8WH9010-0MB02
Warning covers new
Article No. Article No. Article No.
8WH9067-5CA06 8WH9068-5CA06 8WH9068-5CA06
Two-tier terminals
➀ Terminal size
2.5 mm2 4 mm2
Terminal width 5.2 mm 6.2 mm
Max. load current Imax 26 A 32 A
Max. operational voltage Umax 500 V 500 V
AWG 26 … 12 24 … 10
➁ Connection capacity, one rigid conductor 0.14 … 4 mm2 0.2 … 6 mm2
Connection capacity, one flexible conductor 0.14 … 2.5 mm2 0.2 … 4 mm2
with end sleeve
Standard IEC 60947-7-1, IEC 60947-7-2, IEC 60947-7-1, IEC 60947-7-2,
CUUS CUUS
Version Color
➊ Two-tier terminals
Without equipotential bonding Gray 8WH6020-0AF00 8WH6020-0AG00
Blue 8WH6020-0AF01 8WH6020-0AG01
With equipotential bonding Gray 8WH6025-0AF00 8WH6025-0AG00
➋ PE two-tier terminals 1)
Green-yellow 8WH6020-0CF07 8WH6020-0CG07
1)
Bridging the terminal is only possible in the top tier (in the center).
Specific accessories
Covers
Terminals Color Width Article No. Article No.
4 Gray 2.2 mm 8WH9000-4SE00 –
4 Gray 2.2 mm – 8WH9003-1VA00 14
Compartment partitions
Terminals Color Width Article No. Article No.
4 Gray 2 mm 8WH9070-0BA00 8WH9070-0BA00
Terminals Color
2 Gray 8WH6000-6CF00 8WH6000-6AG00
3 Gray 8WH6003-6CF00 –
4 Gray 8WH6004-6CF00 –
Specific accessories
Covers
Terminals Color Width Article No. Article No.
2 Gray 2.2 mm 8WH9000-3SC00 8WH9003-1GA00
3 Gray 2.2 mm 8WH9000-3SD00 –
4 Gray 2.2 mm 8WH9000-5GA00 –
Compartment partitions
Terminals Color Width Article No. Article No.
2 Gray 2.2 mm 8WH9070-0AA00 8WH9070-0AA00
3 Gray 2.2 mm 8WH9070-0GA00 –
Plug-in zone connectors
Types Color Imax Illuminated display Article No. Article No.
Isolating plugs Orange – – 8WH9040-0DB04 8WH9040-0DB04
1)
The G fuse holders must be selected according to the maximum power loss (heat dissipation) of the G fuse links.
Depending on the application and method of installation, the heat rise conditions in closed fuse holders must be tested.
Higher ambient temperatures represent an additional load for the fuse links.
A shift in rated current should therefore be taken into account in such applications.
Terminals Color
2 Gray 8WH6000-6AF00 8WH6000-6CG00
3 Gray 8WH6003-6AF00 –
4 Gray 8WH6004-6AF00 –
Specific accessories
Covers
Terminals Color Width Article No. Article No.
2 Gray 2.2 mm 8WH9000-3SC00 8WH9003-1GA00
3 Gray 2.2 mm 8WH9000-3SD00 –
4 Gray 2.2 mm 8WH9000-5GA00 –
Compartment partitions
Terminals Color Width Article No. Article No.
2 Gray 2 mm 8WH9070-0AA00 8WH9070-0AA00
LED Color
Fuse terminals for 5 × 20 mm G fuse links
➀ Without Black 8WH6000-1GG08
➁ 10 … 30 V AC/DC Black 8WH6000-1KG38
➁ 110 … 250 V AC/DC Black 8WH6000-1MG88
Specific accessories
Covers
Terminals Color Width Article No.
2 Gray 2.2 mm 8WH9003-1GA00
5 × 25 mm G fuse links
Types Breaking capacity Rated uninterrupted current Article No.
Quick Large 1A 8WA1822-7EF16
1.6 A 8WA1822-7EF18
2.5 A 8WA1822-7EF21
4A 8WA1822-7EF23
6.3 A 8WA1822-7EF25
Slow Small 1A 8WA1822-7EF76
1.6 A 8WA1822-7EF78
2.5 A 8WA1822-7EF81
14 4A 8WA1822-7EF83
6.3 A 8WA1822-7EF85
Isolating links, 5 × 20 mm
Size Article No.
5 × 20 mm 8WH9021-0CB12
Initiator/actuator terminals
➀ ➁ Terminal size
A A $ $ 1.5 mm2
Specific accessories
Covers
Version Width Color Article No. Article No.
For 3-wire 2.2 mm Gray 8WH9001-2VD00 –
For 4-wire 2.2 mm Gray – 8WH9001-4VE00
14
Conductors 1) Color
➀ 3-wire, L+, L– Orange 8WH6003-0DF04
➁ 4-wire, L+, L–, PE Orange 8WH6004-0HE04
1)
L+ = red, L– = blue, A (output) = petrol, L = petrol, PE (ground) = green/yellow
14
Specific accessories
Covers
Color Width Article No. Article No.
Gray 1.8 mm – –
2.2 mm 8WH9000-1WA00 8WH9003-7WA00
N conductor support brackets
• For holding the N busbar
Color Article No. Article No.
Blue 8WH9143-0AF01 8WH9143-0AF01
14 Connecting combs
Number of poles Article No. Article No.
2-pole – –
3-pole – –
10-pole – –
Compartment partitions
Color Article No. Article No.
Gray – –
Connecting terminals
Color Width Article No. Article No.
Blau 10.3 mm 8WH9126-0BA01 8WH9126-0BA01
iPo plug-in technology Screw terminals Screw terminals
Specific accessories
Covers
Color Width Article No. Article No.
Blue 2.2 mm 8WH9000-1SA00 8WH9003-1SA00
Gray 2.2 mm – –
Connecting terminals
Color Width Article No. Article No.
Blue 10.3 mm 8WH9126-0BA01 8WH9126-0BA01
– 8WH9005-3PB00 8WH9005-3PB00 –
Types Color
L Gray 8WH6001-4QF00
L/L Gray 8WH6001-4DF00
L/N Gray 8WH6001-4CF00
PE/L/L Gray 8WH6001-4HF00
PE/L/N Gray 8WH6001-4EF00
PE/L/NT Gray 8WH6001-4FF00
Specific accessories
Covers
Color Width Article No.
Gray 2.2 mm 8WH9000-3SA00
1)
Only copper busbars may be installed.
Types Color
➊ Through-type terminals with identical contour
PE/L/L Gray – – 8WH6001-4PF00
➋ Isolating terminals
PE/L/L isolation Gray 8WH6001-4MF00 – –
➌ Isolating blade terminals
PE/L/L isolating blade Gray – 8WH6001-4NF00 –
PE/L/N isolating blade Gray – 8WH6001-4GF00 –
Specific accessories
Covers for isolating terminal in the contour
Color Width Article No. Article No. Article No.
Gray 2.2 mm – 8WH9000-6SA00 8WH9000-6SA00
14
Terminals Color
➊ Through-type terminals
2 Gray 8WH2000-0AE00 8WH2000-0AF00
Blue 8WH2000-0AE01 8WH2000-0AF01
Orange 8WH2000-0AE04 8WH2000-0AF04
Red 8WH2000-0AE02 8WH2000-0AF02
Black 8WH2000-0AE08 8WH2000-0AF08
Green 8WH2000-0AE03 8WH2000-0AF03
White 8WH2000-0AE05 8WH2000-0AF05
Yellow 8WH2000-0AE06 8WH2000-0AF06
3 Gray 8WH2003-0AE00 8WH2003-0AF00
Blue 8WH2003-0AE01 8WH2003-0AF01
Orange 8WH2003-0AF04 8WH2003-0AF04
4 Gray 8WH2004-0AE00 8WH2004-0AF00
Blue 8WH2004-0AE01 8WH2004-0AF01
Orange 8WH2004-0AF04 8WH2004-0AF04
➋ PE through-type terminals
2 Green-yellow 8WH2000-0CE07 8WH2000-0CF07
3 Green-yellow 8WH2003-0CE07 8WH2003-0CF07
14 4 Green-yellow 8WH2004-0CE07 8WH2004-0CF07
Specific accessories
Covers
Color Width Terminals Article No. Article No.
Gray 2.2 mm 2 8WH9000-1GA00 8WH9000-1GA00
3 8WH9000-2GA00 8WH9000-2GA00
4 8WH9000-4GA00 8WH9000-4GA00
Compartment partitions
Color Terminals Article No. Article No.
Gray 2 8WH9070-0AA00 8WH9070-0AA00
3 8WH9070-0GA00 8WH9070-0GA00
4 8WH9070-0HA00 8WH9070-0HA00
Cover segments
• For covering multi-wire terminals when mounting
two-wire terminals side-by-side
Color Article No. Article No.
Gray 8WH9000-0GA00 8WH9000-0GA00
Warning covers for the operating shafts of 8WH2 through-type terminals
Article No. Article No.
8WH9061-5AA06 8WH9060-5AA06
Article No. Article No. Article No. Article No. Article No.
8WH9003-1GA00 8WH9004-1GA00 8WH9005-1GA00 8WH9006-1GA00 –
8WH9003-2GA00 8WH9004-2GA00 – – –
8WH9003-4GA00 – – – –
Article No. Article No. Article No. Article No. Article No.
8WH9070-0AA00 8WH9070-0DA00 – – –
8WH9070-0GA00 8WH9070-0DA00 – – –
8WH9070-0HA00 – – – –
Article No. Article No. Article No. Article No. Article No.
8WH9003-0GA00 – – – –
Article No. Article No. Article No. Article No. Article No.
8WH9063-5AA06 8WH9064-5AA06 8WH9065-5AA06 8WH9066-5AA06 8WH9067-5AA06
Specific accessories
Covers
Color Width Terminals Article No. Article No.
Gray 2.2 mm 3 8WH9000-2HA00 8WH9003-2HA00
14
See general accessories, from page 14/57 onwards
Two-tier terminals
➀ Terminal size
1.5 mm2 2.5 mm2 4 mm2
Terminal width 4.2 mm 5.2 mm 6.2 mm
Max. load current Imax 17.5 A 26 A 32 A
Max. operational voltage Umax 500 V 500 V 500 V
AWG 28 … 16 28 … 12 28 … 10
Connection capacity, rigid 0.08 … 1.5 mm2 0.08 … 4 mm2 0.08 … 6 mm2
➁
Connection capacity, 0.08 … 1.5 mm2 0.08 … 2.5 mm2 0.08 … 4 mm2
flexible with end sleeve
Standard IEC 60947-7-1, IEC 60947-7-1, IEC 60947-7-1,
IEC 60947-7-2, CUUS, s IEC 60947-7-2, CUUS IEC 60947-7-2, CUUS
Specific accessories
Covers
Width Terminals Color Article No. Article No. Article No.
2.2 mm 4 Gray 8WH9000-1VA00 8WH9000-1VA00 8WH9003-1VA00
6 Gray – 8WH9000-2VA00 –
Compartment partitions
Color Article No. Article No. Article No.
Gray 8WH9070-0BA00 8WH9070-0BA00 8WH9070-0BA00
Specific accessories
Covers
Width Color Article No.
14 2.2 mm Gray 8WH9000-1GD00
Label holder
Color Article No.
Gray 8WH9060-4BA00
Types Color
L/L/L/PE Gray 8WH2040-4LF00 8WH2040-4LG00
Specific accessories
Covers
Color Width Article No. Article No.
Gray 2.2 mm 8WH9000-1GE00 –
14
Terminals Color
2 Gray 8WH2000-6AF00 8WH2000-6AG00
3 Gray 8WH2003-6AF00 –
4 Gray 8WH2004-6AF00 –
Specific accessories
Covers
Width Color Terminals Article No. Article No.
2.2 mm Gray 2 8WH9000-2GA00 –
3 8WH9000-4GA00 –
4 8WH9000-5GA00 –
Compartment partitions
Color Terminals Article No. Article No.
Gray 2 8WH9070-0AA00 8WH9070-0AA00
3 8WH9070-0GA00 –
4 8WH9070-0HA00 –
Cover segments
• For covering multi-wire terminals when mounting
two-wire terminals side-by-side
Color Terminals Article No. Article No.
Gray 3/4 8WH9000-0GA00 –
1)
The G fuse holders must be selected according to the maximum power loss (heat dissipation) of the G fuse links.
Depending on the application and method of installation, the heat rise conditions in closed fuse holders must be tested.
Higher ambient temperatures represent an additional load for the fuse links.
A shift in rated current should therefore be taken into account in such applications.
Terminals Color
2 Gray 8WH2000-6CF00 – 8WH2000-6CG00
3 Gray – 8WH2003-6CF00 –
4 Gray – 8WH2004-6CF00 –
1)
On terminals with three and four clamping points, the total current through all connected conductors must not exceed the max. load current.
Specific accessories
Covers
Color Width Terminals Article No. Article No. Article No.
Gray 2.2 mm 2 8WH9000-2GA00 8WH9000-2GA00 –
3 8WH9000-4GA00 8WH9000-4GA00 –
4 8WH9000-5GA00 8WH9000-5GA00 –
Compartment partitions
Color Terminals Article No. Article No. Article No.
Gray 2 8WH9070-0AA00 8WH9070-0AA00 8WH9070-0AA00
3 8WH9070-0GA00 8WH9070-0GA00 –
4 8WH9070-0HA00 8WH9070-0HA00 –
Cover segments
Color Terminals Article No. Article No. Article No.
Gray 3/4 8WH9000-0GA00 8WH9000-0GA00 –
14
14
Specific accessories
Compartment partitions
Color Terminals Article No. Article No. Article No.
Gray 2 8WH9070-0AA00 8WH9070-0AA00 8WH9070-0AA00
14
Specific accessories
Covers
Color Width Terminals Article No.
Gray 2.2 mm 3 8WH9000-4GA00
Compartment partitions
Color Terminals Article No.
Gray 3 8WH9070-0GA00
Cover segments
• For covering multi-wire terminals when mounting two-wire terminals side-by-side
Color Terminals Article No.
Gray 3 8WH9000-0GA00
14
See general accessories, from page 14/57 onwards
Types Color
➊ With one diode
Let-through from top to bottom Gray 8WH2020-5AF00
Let-through from bottom left to bottom right Gray 8WH2020-5DF00
➋ With two diodes
Let-through from top to bottom left and Gray 8WH2020-5KF00
from bottom right to bottom left
➌ With illuminated display
15 … 30 V DC/2.5 … 7.5 A Gray 8WH2020-5JF30
Specific accessories
Covers
Width Color Article No.
2.2 mm Gray 8WH9000-1VA00
Compartment partitions
Color Article No.
Gray 8WH9070-0BA00
14
Specific accessories
Covers
Terminals Color Width Article No.
2 Gray 2.2 mm 8WH9000-1VA00
Compartment partitions
Terminals Color Article No.
2 Gray 8WH9070-0BA00
30
Maximum load current in A
25
2-pole
5-pole
20 10-pole
15-pole
15
10
5
I201_13471
0 20 40 60 80 100 120
Ambient temperature in °C
Specific accessories
Covers
Terminals Color Width Article No.
2 Gray 2.2 mm 8WH9000-1GA00
Compartment partitions
Terminals Color Article No.
4 Gray 8WH9070-0HA00
14
Version Color With slot for comb Without slot for comb
Plug
Left element Gray 8WH9040-1DB00 8WH9040-1AB00
Blue 8WH9040-1DB01 8WH9040-1AB01
Central element Gray 8WH9040-1EB00 8WH9040-1BB00
Blue 8WH9040-1EB01 8WH9040-1BB01
Right element Gray 8WH9040-1FB00 8WH9040-1CB00
Blue 8WH9040-1FB01 8WH9040-1CB01
PE plugs
Left element Green-yellow 8WH9040-1DB07 8WH9040-1AB07
Central element Green-yellow 8WH9040-1EB07 –
Right element Green-yellow 8WH9040-1FB07 8WH9040-1CB07
Specific accessories
14
Latches
Version Color Article No. Article No.
With strain relief Orange 8WH9050-2BA04 8WH9050-2BA04
Without strain relief Orange 8WH9050-2AA04 8WH9050-2AA04
Shielding
• For connection of shielded cables
Cable diameter Color Article No. Article No.
5 … 10 mm Black 8WH9120-0DB08 8WH9120-0DB08
2.5 mm²
2.5 mm²
2.5 mm²
2.5 mm²
2.5 mm²
2.5 mm²
2.5 mm²
2.5 mm²
and/ and/
or or and and or or
or or
I201_20506
without slot for without slot for without slot for without slot for without slot for without slot for without slot for without slot for
comb comb comb comb comb comb comb comb
Note:
The configuration concept shown is just one example of how combination plugs can be configured.
14
Terminals Color
➊ Through-type terminals
2 Gray 8WH3000-0AE00
Blue 8WH3000-0AE01
3 Gray 8WH3003-0AE00
Blue 8WH3003-0AE01
4 Gray 8WH3004-0AE00
Blue 8WH3004-0AE01
➋ PE through-type terminals
2 Green-yellow 8WH3000-0CE07
3 Green-yellow 8WH3003-0CE07
4 Green-yellow 8WH3004-0CE07
1)
On terminals with three and four clamping points, the total current through all connected conductors must not exceed the maximum load current.
Specific accessories
Covers
14 Terminals Color Width Article No.
2 Gray 2.2 mm 8WH9001-1AA00
3 Gray 2.2 mm 8WH9001-2AA00
4 Gray 2.2 mm 8WH9001-4AA00
Compartment partitions
Terminals Color Width Article No.
2 Gray 2 mm 8WH9070-0JA00
4 Gray 2 mm 8WH9070-0MA00
Cover segments
• For covering multi-wire terminals when mounting two-wire terminals side-by-side
Terminals Color Article No.
3 Gray –
Two-tier terminals
➀ Terminal size
1.5 mm2
Terminal width 5.2 mm
Max. load current Imax 17.5 A
➁ Max. operational voltage Umax 500 V
AWG 24 … 16
Connection capacity, rigid 0.25 … 1.5 mm2
Connection capacity, flexible with end sleeve 0.25 … 1.5 mm2
Standard CUUS
Version Color
➊ Two-tier terminals
Without equipotential bonding Gray 8WH3020-0AE00
Blue 8WH3020-0AE01
➋ PE two-tier terminals
Green-yellow 8WH3020-0CE07
Specific accessories
Covers
Width Color Article No.
2.2 mm Gray 8WH9001-1BA00
Compartment partitions
Color Article No.
Gray 8WH9070-0MA00
14
Terminals Color
2 Gray 8WH3000-6AE00
Specific accessories
Covers
Width Color Article No.
2.2 mm Gray 8WH9001-2AA00
14
Terminals Color
➊ Through-type terminals
2 Gray 8WH1000-0AF00 8WH1000-0AG00
Blue 8WH1000-0AF01 8WH1000-0AG01
Orange 8WH1000-0AF04 8WH1000-0AG04
Red 8WH1000-0AF02 8WH1000-0AG02
Black 8WH1000-0AF08 8WH1000-0AG08
Green 8WH1000-0AF03 –
Yellow 8WH1000-0AF06 –
➋ PE through-type terminals
2 Green-yellow 8WH1000-0CF07 8WH1000-0CG07
Specific accessories
Covers
14 Width
2.2 mm
Color
Gray
Article No.
8WH9000-1PA00
Article No.
8WH9000-1PA00
Compartment partitions
Width Color Article No. Article No.
2 mm Gray 8WH9070-6BA00 8WH9070-6BA00
Reducing combs
Version Color Article No. Article No.
From screw to screw Turquoise – –
From screw to spring Turquoise – –
Article No.
8WH9000-1PA00
Article No.
8WH9000-1PA00
Article No.
8WH9076-1PA00
Article No.
–
Article No.
–
14
Article No. Article No. Article No. Article No. Article No.
8WH9070-6BA00 8WH9070-6BA00 – – –
Article No. Article No. Article No. Article No. Article No.
8WH9002-8AC10 – 8WH9002-8EC10 8WH9002-8GC10 8WH9002-8GC10
– – 8WH9002-8FC10 8WH9002-8HC10 8WH9002-8HC10
Article No. Article No. Article No. Article No. Article No.
8WH9064-5BA06 8WH9065-5BA06 8WH9066-5BA06 8WH9067-5BA06 8WH9067-5BA06
Terminals Color
➊ Through-type terminals
2 Gray 8WH1000-0AN00 8WH1000-0AP00 8WH1000-0AQ00 8WH1000-0AS00 8WH1000-0AU00
Blue 8WH1000-0AN01 8WH1000-0AP01 8WH1000-0AQ01 8WH1000-0AS01 8WH1000-0AU01
➋ PE through-type terminals
2 Green-yellow 8WH1000-0CN07 8WH1000-0CP07 8WH1000-0CQ07 – –
Specific accessories
Tap-off terminal
• When wiring a tap-off with a
smaller cross-section, observe the
overload and short-circuit strength
specified in VDE 0100 Part 430
Imax Cross-section Article No. Article No. Article No. Article No. Article No.
57 A 10 mm2 8WH9120-0AA00 – 8WH9120-0BA00 8WH9120-0CA00 8WH9120-0CA00
Insertion profiles
Version Color
➊ Two-tier terminals
Without equipotential bonding Gray 8WH1020-0AF00 8WH1020-0AG00
Blue 8WH1020-0AF01 8WH1020-0AG01
With equipotential bonding Gray 8WH1025-0AF00 8WH1025-0AG00
➋ PE two-tier terminals
Green-yellow 8WH1020-0CF07 8WH1020-0CG07
Specific accessories
Covers
Width Color Article No. Article No.
2.2 mm Gray 8WH9000-1QA00 8WH9000-1QA00
14
Compartment partitions
Width Color Article No. Article No.
2 mm Gray 8WH9070-6FA00 8WH9070-6FA00
Spacer plates
• Compensates for tier offset if other terminals are mounted side by side
Width Color Article No. Article No.
2.5 mm Gray 8WH9160-0AA00 8WH9160-0AA00
Terminals Color
2 Gray 8WH1000-6AG00 8WH1000-6AH00
Specific accessories
Plug-in zone connectors
Types Color Imax Illuminated display Article No. Article No.
Isolating plugs Orange – – 8WH9040-0DB04 8WH9040-0DB04
1)
The G fuse holders must be selected according to the maximum power loss (heat dissipation) of the G fuse links.
Depending on the application and method of installation, the heat rise conditions in closed fuse holders must be tested.
Higher ambient temperatures represent an additional load for the fuse links.
A shift in rated current should therefore be taken into account in such applications.
Terminals Color
2 Gray 8WH1000-6CG00
Specific accessories
Warning covers for 8WH1
Image Color Article No.
Lightning symbol Yellow 8WH9063-5BA06
14
Version Color
➊ Isolating terminal
Isolating terminal in the upper tier Gray 8WH1020-6AG00 –
➋ Isolating blade
Isolating blade in the upper tier Gray – 8WH1020-6AC00
Specific accessories
Covers
Width Color Article No. Article No.
2.2 mm Gray 8WH9000-1QA00 8WH9000-1QA00
Compartment partitions
Width Color Article No. Article No.
2 mm Gray 8WH9070-6FA00 8WH9070-6FA00
14 Spacer plates
• Compensates for tier offset if other terminals are
mounted side by side
Width Color Article No. Article No.
2.5 mm Gray 8WH9160-0AA00 8WH9160-0AA00
Terminals Color
➊ Isolating terminals
2 recesses for screwing in the test sockets Gray 8WH1000-7AH00 –
➋ Through-type terminals with identical contour
2 recesses for screwing in the test sockets Gray – 8WH1000-7BH00
Specific accessories
Covers
Width Color Article No. Article No.
2.2 mm Gray 8WH9000-3UA00 8WH9000-3UA00
Disconnecting links
• For bridging two adjacent terminals
• Cannot be used with the bare 8WH9010-0MB12 test socket
Tightening torque Number of poles Color Article No. Article No.
0.6 … 0.8 Nm 2-pole Gray 8WH9021-0AC00 8WH9021-0AC00
LED Color
For 5 × 20 mm G fuse links
➀ Without Black 8WH1000-1GG08 –
➁ AC/DC with LED 10 … 30 V Black 8WH1000-1KG38 –
➁ AC/DC with LED 110 … 250 V Black 8WH1000-1MG88 –
For 6.3 × 32 mm G fuse links (inch fuses)
➀ Without Black – 8WH1000-1HH08
➁ AC/DC with LED 12 … 30 V Black – 8WH1000-1PH38
Specific accessories
Plug-in zone connectors
Version Color Imax Illuminated display Article No. Article No.
Fused connectors 1) Schwarz 6.3 A 12 … 30 V, 1 … 2.5 mA 8WH9040-3AB08 8WH9040-3AB08
Without 8WH9040-3DB08 8WH9040-3DB08
Reducing combs
• For connecting terminals from terminal size
6 mm2 to 2.5 mm2 or 4 mm2
14 Version Color Article No. Article No.
From screw to Turquoise – 8WH9002-8AC10
screw
1)
The G fuse holders must be selected according to the maximum power loss (heat dissipation) of the G fuse links.
Depending on the application and method of installation, the heat rise conditions in closed fuse holders must be tested.
Higher ambient temperatures represent an additional load for the fuse links.
A shift in rated current should therefore be taken into account in such applications.
Terminals Color
4 Gray 8WH1020-5LF00
1)
Supplied without components; the appropriate components (resistors, diodes, capacitors, ...) are to be soldered in by user
Specific accessories
Covers
Width Color Article No.
2.2 mm Gray 8WH9000-1QA00
Compartment partitions
Width Color Article No.
2 mm Gray 8WH9070-6FA00
Spacer plates
14
• Compensates for tier offset if other terminals are mounted side by side
Width Color Article No.
2.5 mm Gray 8WH9160-0AA00
Let-through Color
➀ From left to right Gray 8WH1000-6LG00
➁ From right to left Gray 8WH1000-6KG00
Specific accessories
Covers
Width Color Article No.
2.2 mm Gray 8WH9000-2PA00
14
Specific accessories
Covers
Width Color Article No.
14
2.2 mm Gray 8WH9000-1QA00
Compartment partitions
Width Color Article No.
2 mm Gray 8WH9070-6FA00
Spacer plates
• Compensates for tier offset if other terminals are mounted side by side
Width Color Article No.
2.5 mm Gray 8WH9160-0AA00
Version
For direct shield attachment on conductive mounting plate
For connecting cable shield and enclosure ground 8WH9130-0AA00 8WH9130-0BA00 8WH9130-0CA00 8WH9130-0DA00
For 10 × 3 mm busbars
For connecting cable shield and enclosure ground 8WH9130-0LA00 8WH9130-0MA00 8WH9130-0NA00 8WH9130-0PA00
Specific accessories
N conductor support brackets
Version Article No. Article No. Article No. Article No.
Made of molded plastic and 8WH9140-0DA00 8WH9140-0DA00 8WH9140-0DA00 8WH9140-0DA00
conductive connection with
retaining screw
For mounting rail with clearance 8WH9140-0BA00 8WH9140-0BA00 8WH9140-0BA00 –
of approx. 30 mm to the busbar
Blank labels
• Horizontal and vertical labeling
Version Terminal width Designation Color Article No.
Front 3.5 mm WIN 97 White 8WH8112-0AA05
4.2 mm WIN 97 White 8WH8112-1AA05
5.2 and 6.2 mm WIN 88 White 8WH8112-2AA05
8.2, 10.2, 12.2 and 16 mm WIN 40 White 8WH8112-4AA05
Flat 3.5 mm WIN 97 White 8WH8113-0AA05
4.2 mm WIN 180 White 8WH8113-1AA05
5.2 mm WIN 182 White 8WH8113-1AA05
6.2 mm WIN 184 White 8WH8113-1AA05
8.2 mm WIN 186 White 8WH8113-1AA05
10.2 mm WIN 188 White 8WH8113-1AA05
12.2 and 16 mm WIN 46Z White 8WH8113-6AA05
Snap-on device labels
• For identification of, e.g. circuit breakers, contactors and control systems
Version Designation Color Article No.
20 × 7 mm, snap-on hooks at side WIN 95 White 8WH8210-0AA55
20 × 7 mm, snap-on hooks at side WIN 95 Turquoise 8WH8210-0AA56
NSH0_00038
Flat
Text alignment Inscription Numbering Article No. Article No.
Vertical Consecutive numbering 1 … 10 (10×) 8WH8121-1AB05 8WH8121-2AB05
11 … 20 (10×) 8WH8121-1AB15 8WH8121-2AB15
21 … 30 (10×) 8WH8121-1AB25 8WH8121-2AB25
31 … 40 (10×) 8WH8121-1AB35 8WH8121-2AB35
41 … 50 (10×) 8WH8121-1AB45 8WH8121-2AB45
51 … 60 (10×) 8WH8121-1AB55 8WH8121-2AB55
14 61 … 70 (10×) – 8WH8121-2AB65
71 … 80 (10×) – 8WH8121-2AB75
81 … 90 (10×) – 8WH8121-2AB85
91 … 100 (10×) – 8WH8121-2AC05
Custom inscription – 8WH8121-1XA05-Z Y01 8WH8121-2XA05-Z Y01
Horizontal Consecutive numbering 1 … 10 (10×) 8WH8141-1AB05 8WH8141-2AB05
11 … 20 (10×) 8WH8141-1AB15 8WH8141-2AB15
21 … 30 (10×) 8WH8141-1AB25 8WH8141-2AB25
31 … 40 (10×) 8WH8141-1AB35 8WH8141-2AB35
41 … 50 (10×) 8WH8141-1AB45 8WH8141-2AB45
51 … 60 (10×) – 8WH8141-2AB55
61 … 70 (10×) – 8WH8141-2AB65
71 … 80 (10×) – 8WH8141-2AB75
81 … 90 (10×) – 8WH8141-2AB85
91 … 100 (10×) – 8WH8141-2AC05
Custom inscription – 8WH8141-1XA05-Z Y01 8WH8141-2XA05-Z Y01
Blank – – 8WH8111-1AA05 8WH8111-2AA05
Spacer plates
• For skipping single terminals for individual test plug assembly
• Not suitable for 8WH3 insulation displacement terminals
Terminal size Terminal width Color Article No.
2.5 mm2 5.2 mm Red 8WH9010-2BA02
Reducing combs
• For connecting two through-type terminals
• Cannot be used for 8WH1 through-type terminals and 8WH3 insulation displacement terminals
From terminal size To terminal size Color Article No.
2.5 mm2 or 4 mm2 1.5 mm2 Turquoise 8WH9020-0CC10
6 mm2 Turquoise 8WH9020-0FC10
10 mm2 Turquoise 8WH9020-0AC10
16 mm2 Turquoise 8WH9020-0BC10
35 mm2 Turquoise 8WH9020-0EC10
14 16 mm2 35 mm2 Turquoise 8WH9020-0DC10
Connecting combs
Terminal size Terminal width Max. load current Imax Used for 8WH3 Number of poles Article No.
1.5 mm2 4.2 mm 17.5 A Cannot be used 2-pole 8WH9020-6AC10
3-pole 8WH9020-6AD10
4-pole 8WH9020-6AE10
5-pole 8WH9020-6AF10
10-pole 8WH9020-6AL10
20-pole 8WH9020-6AS10
2.5 mm2 5.2 mm 24 A Can be used for 2-pole 8WH9020-6BC10
terminal size 3-pole 8WH9020-6BD10
1.5 mm2
4-pole 8WH9020-6BE10
5-pole 8WH9020-6BF10
10-pole 8WH9020-6BL10
20-pole 8WH9020-6BS10
50-pole 8WH9020-6BT10
4 mm2 6.2 mm 32 A Can be used for 2-pole 8WH9020-6CC10
terminal size 3-pole 8WH9020-6CD10
2.5 mm2
4-pole 8WH9020-6CE10
5-pole 8WH9020-6CF10
10-pole 8WH9020-6CL10
20-pole 8WH9020-6CS10
50-pole 8WH9020-6CT10
6 mm2 8.2 mm 41 A Cannot be used 2-pole 8WH9020-6DC10
3-pole 8WH9020-6DD10
4-pole 8WH9020-6DE10
5-pole 8WH9020-6DF10
10-pole 8WH9020-6DL10
10 mm2 10.2 mm 57 A Cannot be used 2-pole 8WH9020-6EC10
16 mm2 12.2 mm 76 A Cannot be used 2-pole 8WH9020-6FC10
35 mm2 16 mm 101 A Cannot be used 2-pole 8WH9020-6GC10
14
14
8WA1011-1DH11 8WA1204 8WA1205 8WA1206
8WA1011-1BH23 8WA1011-1BK11 8WA1011-1BM11 8WA1011-1BP11
– – – –
– – – –
– – – –
8WA1011-1BH24 – – –
– – – –
– – – –
8WA1011-1PH00 8WA1011-1PK00 8WA1011-1PM00 –
Disconnecting links
• The terminals must be fitted with end plates and must
be mounted with the end plates facing each other
In Article No. Article No.
Up to 32 A 8WA1865 8WA1865
Insulation plate
Article No. Article No.
8WA1825 8WA1825
Barriers
• Between terminals with terminal sizes 2.5 and
6 mm2 two 8WH1820 barriers are required
Width Article No. Article No.
14 2 mm 8WA1820 8WA1820
Connection bars
Version Article No. Article No.
For two terminals 8WA1895 8WA1850
For three terminals 8WA1896 8WA1851
For four terminals 8WA1897 8WA1852
For ten terminals 8WA1898 8WA1853
Terminals Surface
PE through-type terminals
2 Bare 8WA1010-1PH01 8WA1010-1PQ00
Specific accessories
Barriers
Article No. Article No.
8WA1821 –
14
Two-tier terminals
➀ Terminal size
4 mm2
➁ Terminal width 6.5 mm
Max. load current Imax 32 A
Rated insulation voltage Ui 690 V
AWG U 18 … 10
AWG s 18 … 10
Connection capacity, rigid 0.5 … 6 mm2
Connection capacity, flexible with end sleeve 0.75 … 4 mm2
Standard U, s
Version Color
➊ Two-tier terminals without equipotential bonding
2-pole with two electrically isolated connections Beige 8WA1011-2DG11
Blue 8WA1011-2BG11
➋ Two-tier terminals with equipotential bonding
1-pole Beige 8WA1011-6DG11
Blue 8WA1011-6BG11
Specific accessories
Covers
Version Article No.
With lightning symbol 8WA1811
Jumpers
Version Article No.
For upper tier of 2-pole terminals 8WA1822-7VG00
For lower tier of 1 and 2-pole terminals 8WA1822-7VG01
Disconnecting links
Article No.
8WA1865
14
End plates
Article No.
8WA1817
Insulation plate
Version Article No.
For upper and lower tier 8WA1825
Connection bars
Version Types Article No.
For upper tier of 2-pole terminals For two terminals 8WA1850
For three terminals 8WA1851
For four terminals 8WA1852
For ten terminals 8WA1853
For lower tier of 1 and 2-pole terminals For two terminals 8WA1835
For ten terminals 8WA1838
Barriers
Color Article No.
Gray 8WA1823
Types Color
➀ L, L Beige 8WA1011-3JF18
➁ PE, L, L Beige 8WA1011-3JF16
➁ PE, L, N Beige 8WA1011-3JF17
➂ PE, L, NT Beige 8WA1011-3JF20
Specific accessories
Covers
Version Article No.
For connection bars, transparent 8WA1822-7AX01
For connection bars, white 8WA1822-7AX03
Bare infeed terminals, for N busbars
Size Conductor cross-section Rated uninterrupted current Article No.
6 × 6 mm and 10 × 3 mm Up to 4 mm2 32 A 8WA2867
Up to 25 mm2 76 A 8WA2868
Up to 35 mm2 125 A 8WA2870
N busbars, 6 × 6 mm
Version Length Rated uninterrupted current Article No.
For four-field 1109 mm 125 A 8GF9324-2
Terminals Color
2 Blue 8WA1011-1NF01 8WA1011-1NG31 8WA1011-1NH01 8WA1604
Specific accessories
Infeed terminals, for N busbars
Size Rated uninter Article No. Article No. Article No. Article No.
rupted current
6 × 6 mm and 32 A 8WA2867 8WA2867 – –
10 × 3 mm 76 A 8WA2868 8WA2868 8WA2868 8WA2868
125 A 8WA2870 8WA2870 8WA2870 8WA2870
N busbars, 6 × 6 mm, for four-field
Length Rated uninter Article No. Article No. Article No. Article No.
rupted current
1109 mm 125 A 8GF9324-2 8GF9324-2 8GF9324-2 8GF9324-2
Label holder
Article No. Article No. Article No. Article No.
3TX4210-0J 3TX4210-0J 3TX4210-0J 3TX4210-0J
14
Specific accessories
Barriers
Color Article No.
Gray 8WA1820
14
Specific accessories
Covers, for connection bars
Types Article No.
Transparent 8WA1822-7AX01
White, facility for labeling 8WA1822-7AX03
Test sockets
Diameter Article No.
4 mm 8WA1822-7PH00
Disconnecting links
• Rated insulation voltage with disconnecting
link open according to DIN VDE 0110:
125 V size C or 250 V size B
Article No.
8WA1822-7VH01
Insulation plate
Article No.
14
8WA1825
Connecting comb
Number of poles Article No.
2-pole 8WA1822-7VH22
10-pole, can be shortened as required 8WA7163
Connection bars
Types Article No.
Two terminals 8WA1885
Three terminals 8WA1886
Four terminals 8WA1887
Ten terminals 8WA1888
Unmounted for ten terminals 8WA1822-7VH10
Barriers
Color Article No.
Gray 8WA1822-7TH00
Version Color
For 5 × 25 mm G fuse links
➀ Without LED Beige 8WA1011-1SF12
➁ With LED 24 V AC/DC Beige 8WA1011-1SF13
➁ With LED 230 V AC/DC Beige 8WA1011-1SF15
For 6.3 × 32 mm G fuse links (inch fuses)
➀ Without LED Beige 8WA1011-1SF30
➁ With LED 24 V AC/DC Beige 8WA1011-1SF31
➁ With LED 120 V AC/110 V DC Beige 8WA1011-1SF32
Specific accessories
5 × 25 mm G fuse links
Types Breaking capacity Rated uninterrupted current Article No.
Quick Large 1A 8WA1822-7EF16
1.6 A 8WA1822-7EF18
2.5 A 8WA1822-7EF21
4A 8WA1822-7EF23
14 6.3 A 8WA1822-7EF25
Slow Small 1A 8WA1822-7EF76
1.6 A 8WA1822-7EF78
2.5 A 8WA1822-7EF81
4A 8WA1822-7EF83
6.3 A 8WA1822-7EF85
Isolating links, 5 × 20 mm
Size Article No.
5 × 20 mm 8WH9021-0CB12
Terminals Color
Screw terminal at both ends for 2 conductors each Gray 8WA1011-1EE00
Specific accessories
Plugs for components
Version Article No.
With PCB and inscription label (20 × 9 mm) 8WA1822-7EE00
Diode terminals
Terminal size
2.5 mm2
Terminal width 6 mm
Max. load current Imax 1 A
Rated insulation voltage URRM 250 V
Peak blocking voltage 1000 V
Connection capacity, rigid 0.5 … 4 mm2 14
Connection capacity, flexible without end sleeve 0.5 … 2.5 mm2
Connection capacity, flexible with end sleeve 0.5 … 1.5 mm2
Tightening torque 0.5 Nm
Specific accessories
Barriers
Color Article No.
Gray 8WA1820
Specific accessories
End plates
Color Article No.
Gray 8WA1817
14
8WA1011-6EG20 – –
– – –
8WA1011-6EG23 – –
8WA1011-6EG24 – –
– 8WA1011-6EG25 –
– – 8WA1011-6EG44
L− L+ L− S
Terminal width 5 mm
Max. load current Imax 10 A
Max. operational voltage Umax 65 V
A A A A Current consumption with LED 4.8 mA
L− L+ L− S AWG U 22 … 16
AWG s 28 … 16
Connection capacity, rigid 0.08 … 1.5 mm2
Connection capacity, flexible with end sleeve 0.2 … 1.5 mm2
A A A A Standard U, s
L− L+ S L+ S
$ $
/ï / /
Specific accessories
Connection module
Version Width Height Color Article No.
For 8 initiator/actuator terminals 47 mm 65 mm Black 8WA2011-3KE50
14 and one infeed terminal
For 16 initiator/actuator terminals, one infeed 93 mm 65 mm Black 8WA2011-3KE51
terminal and space for one terminal for further
bridging for subsequent module
Specific accessories
Connection module
Version Width Height Color Article No.
For 8 initiator/actuator terminals 47 mm 65 mm Black 8WA2011-3KE50
and one infeed terminal
For 16 initiator/actuator terminals, one infeed 93 mm 65 mm Black 8WA2011-3KE51
terminal and space for one terminal for further
bridging for subsequent module
Blank labels
• For 8WA1 and 8WA2, individually removable
• Cannot be used for two-tier terminals (lower tier),
8WA1010-1PQ00 flat terminals and 8WA1808 end retainers
Version Designation Color Article No.
NSH0_00037
14
Vertical L1 8WA8348-2AC
L2 8WA8348-2AD
L3 8WA8348-2AE
N 8WA8348-1AR
MP 8WA8348-2AB
PE 8WA8348-2AH
L+ 8WA8348-2AF
L− 8WA8348-2AG
X 8WA8348-1AG
Y 8WA8348-1AH
Mounting accessories
End retainers, with screw fixing
• Suitable for 8WA1806 end labeling plate or 8WA8826-0A. terminal strip identification label
or 3TX4 210-0H device label or four 8WA88 labels
Mounting width Article No.
10 mm 8WA1808
45
20 22
Spacers
5,5 Version Drill hole Article No.
NSH0_00044
33 9
Mounting brackets
Version Article No.
M5 For mounting rails 8WA746
50
70
NSH0_00042a
14
6
25 50
Insulation carriers
Version Article No.
M4 For insulated mounting of mounting rails onto plates, frame profiles and DIN rails EN 50022-35 8WA1857
49
54
NSH0_00045
20 8
14
14
Information + ordering
All the important things at a glance Everything you need for your order
For information about power distribution boards, motor Refer to the Industry Mall for an overview of your
control centers and distributionboards, please visit our products
websites
• SIVACON S4 (NF)
www.siemens.com/sivacon-S8
sie.ag/2JUQwE4
www.siemens.com/distributionsystems
• Distribution boards sie.ag/2kURLd8
• SIMARIS planning tools sie.ag/2m3oFbS
Commissioning + operation
The SIMARIS planning tools effectively assist you The Siemens Industry Online Support (SIOS)
in your planning process. Project-specific IFC data provides detailed technical information
(Building Information Modeling) for cross-package www.siemens.com/lowvoltage/product-support
planning is also possible. • Operating instructions
www.siemens.com/simaris • Characteristic curves
• Certificates
Comprehensive mobile support via the Siemens Industry
SIMARIS configuration
Online Support app available for download from the
App Store and Play Store
The SIMARIS configuration software supports the engineer- You will find further information at
ing process of the SIVACON and ALPHA distribution sys- www.siemens.com/support-app
tems from planning right through to plant documentation.
www.siemens.com/simarisconfig Provision of 3D data (step and u3d data formats)
• Siemens Industry Mall
www.siemens.com/lowvoltage/mall
Manuals • Image database
www.siemens.com/lowvoltage/picturedb
Manuals are available for downloading in Siemens Engineering data for CAD or CAE systems are available in
Industry Online Support (SIOS) at the CAx Download Manager at
www.siemens.com/lowvoltage/manuals www.siemens.com/cax
• Planning Manual
− SIVACON S8 – Technical planning information
(107113936)
Face-to-face or online training
• Application Manual
− SIVACON S4 Power distribution boards up to 6300 A Our training courses can be found at
(25909512) www.siemens.com/sitrain-lowvoltage
• SIMARIS configuration (WT-LVASIMC)
• ALPHA 3200 low voltage switch boards –
technic and software (LV-ALPHAT)
• ALPHA 3200 low voltage switch boards –
mounting (LV-ALPHAPB)
Technical overview – Power distribution boards, motor control centers and distribution boards
Distribution systems
Power distribution
boards
SIVACON S4
Basic data
Rated current A 4000
6300 with license
Busbar position Top, rear (NF)
Overvoltage category III/IV
Rated impulse withstand voltage Uimp kV 12
Rated insulation voltage Ui V 1000
Rated operational voltage Ue V AC 690
Rated peak withstand current Ipk kA 220
Rated short-time current Icw (1 s) kA 100
Degree of protection according to IEC 60529/EN 60529 IP40 + IPX1/IP55
Form of internal separation 4b
Protection class I
Color RAL 7035 (light gray)
Dimensions
Height mm 2000
Base 100/200
Width mm 400 … 1200
Depth mm 400 … 1200
Standards and specifications
DIN EN 61439-1/-2
IEC IEC 61439-1/-2
VDE VDE 0660-600-1/-2
Operating personnel Ordinary person –
Electrically skilled person ■
Approvals VDE, EAC
15 Equipment
Tested for resistance to internal arcing acc. to EN 61439-2 Supplement 1 –
Active protection against internal arcing –
Reactive power compensation –
Other
Type of installation Wall/back to back
Pre-assembled solutions Without copper ■
With copper ■
Further information
See page 15/22
– – –
III III III
6 6 6
690 690 400
690 690 400
74 53 10
35 25 17
IP30/IP43/IP55 IP30/IP43/IP55 IP30/IP31D/IP43
1 1 1
I I I
RAL 7035 (light gray) RAL 7035 (light gray) RAL 7035 (light gray)
– – –
15
– – –
– – –
Distribution systems
Power distribution Power distribution
boards and motor boards
control centers
Basic data
Rated current A 7010 3200 3200
Busbar position Top, rear Rear Center
Overvoltage category IV III/IV III/IV
Rated impulse withstand voltage Uimp kV 12 1) 8 8
Rated insulation voltage Ui V 1000 1000 1000
Rated operational voltage Ue V AC 690 690 400
Rated peak withstand current Ipk kA 330 165 165
Rated short-time current Icw (1 s) kA 150 75 75
Degree of protection according to IEC 60529/EN 60529 IP30 … IP54 IP40 + IPX1/ IP54 IP30 + IPX1/IP54
Form of internal separation 4b 2b 1
Protection class I I I
Color RAL 7035 (light gray) RAL 7035 (light gray) RAL 7035 (light gray)
Dimensions
Height mm 2000/2200 2000 2000
Base 100/200 Base 100/200 Base 100/200
Width mm 200 … 1400 350 … 1400 350 … 1100
1)
Depending on the devices used
ALPHA 1250 ALPHA 630 ALPHA 400 ALPHA 160 ALPHA SIMBOX ALPHA SIMBOX
XL WP
– – – – – –
– – – – – –
– – – – – –
Surface mounting Surface mounting Surface mounting/ Surface mounting/ Flush mounting/ Surface mounting
flush mounting flush mounting hollow wall/
surface mounting
■ ■ ■ ■ – –
– – – – – –
See page 15/158 See page 15/162 See page 15/166 See page 15/170 See page 15/202 See page 15/205
Distribution systems
Applications
Power Center
Main distribution
boards
Subdistribution
boards
15
I201_20527
Loads
SIVACON S8
15
To specify the options, add "-Z" to the complete article number Order code
and indicate the appropriate order code(s).
8GK.....-.....-.... -Z
RAL 1003, signal yellow Semi-gloss C 2 7
15
15
SIVACON S8
Devices 3WA, 3WL and 3VA 3VA, 3RV, 3NP, 3K… and 5S… 3NJ6
SIVACON S4
15
In-line design, Reactive power Active protection against Universal mounting design/ Frequency converter
Fixed-mounted compensation internal arcing motor control center technology
3NJ4 Capacitor units, controllers Internal arcing protection system 3VA, 3RV, 3NP, 3K…, 3R…, 3UF, SINAMICS G120 (6SL)
3NJ6 and 3LD
Fixed-mounted Fixed-mounted Fixed-mounted Withdrawable Fixed-mounted (modules)
Fixed-mounted
with compartment doors
Plug-in
Outgoing cable feeders Central compensation Active protection against internal Outgoing cable feeders Motor feeders (MCC)
of reactive power arcing Motor feeders (MCC)
630 A Without inductor up to 600 kvar Short-circuit-proof up to 100 kA 630 A, 250 kW 132 kW
With inductor up to 500 kvar at 690 V
Front Front – Front or rear Front
15
Fixed-mounted Fixed-mounted
630 A –
Front Front
ALPHA 3200
15
Circuit breaker design Molded case circuit breaker design In-line design, fixed-mounted
15
Fixed-mounted Fixed-mounted
4*."3*4
4*."3*4 4QFDJ DPO 1BSUT
CVTCBSQMBO DBUJPO HVSBUJPO MJTU
F1MBO
4$' 84 $"%
I201_19849b
4*."3*4 4*."3*4 $"Y%PXOMPBE BMMQPMF $POOFDUJWJUZ 8FC QPXFSNBOBHFS
EFTJHO QSPKFDU .BOBHFS DJSDVJU TFSWFS
EJBHSBN
*OUFMMJHFOU
EBUBNBOBHFNFOU
4JFNFOT "TTFNCMZ %PDVNFO "TTFNCMZ
*OEVTUSZ.BMM ESBXJOH UBUJPO
$VTUPNJ[FEBTTFNCMZ
.BOVGBDUVSJOHQSPDFTT
BWBJMBCMFGPS"-1)"&DP
4*7"$0/4
15
SIMARIS design is a planning tool for quick, effective network SIMARIS project is a planning tool for fast calculation of
calculations and dimensioning of electrical power distribution space requirements and electrical power distribution system
systems for non-residential and industrial buildings. budgets for non-residential and industrial buildings, and
• Dimensioning of electrical networks on the basis of real for generating specifications automatically.
products according to acknowledged rules of technology • Import of projects created in SIMARIS design
and the applicable standards (VDE, IEC) • Export of 3D data in IFC 4.x format for BIM (Building
• Automatic selection of the appropriate components Information Modeling)
from the integrated product database SIMARIS project forms parts of SIMARIS Suite.
SIMARIS design forms parts of SIMARIS Suite. Free download of the SIMARIS Suite and further information at:
Free download of the SIMARIS Suite and further information at: www.siemens.com/simarisproject
www.siemens.com/simarisdesign
15
With the configuration software SIMARIS configuration, SIMARIS curves is a planning tool for visualizing and
the SIVACON S8, ALPHA 3200, SIVACON S4 and evaluating characteristic curves of Siemens low-voltage
ALPHA UNIVERSAL power distribution boards as well as the protection equipment and fuses (IEC) quickly and easily,
ALPHA distribution boards can be quickly and reliably including the possibility of simulating instrument settings.
configured. • Is available both as a PC version and also as an app for use
• Comprehensive documentation of the installation on a tablet PC or a smartphone
with design verification acc. to IEC 61439
SIMARIS curves forms parts of SIMARIS Suite.
• Configuration of the devices from the SENTRON portfolio
Free download of the SIMARIS Suite and further information at:
with the exact article numbers and integrated price
www.siemens.com/simariscurves
calculation feature
Free download and further information at:
www.siemens.com/simarisconfig
System overview
ALPHA 3200 Eco power distribution boards
Busbar systems
I201_20292
Section expansion
15
3WA, 3WL10 3WA 3VA 3NJ4 ALPHA 8GK Mounting plates
incoming feeder coupling panels molded case circuit outgoing feeder modular
panels breaker design panels installation system
Note:
You will find a detailed range of accessories under section expansions.
Note:
You will find a detailed range of accessories under section expansions.
15
Pre-assembled solutions
Deliveries are made to system partners in accordance with the configuration in SIMARIS configuration.
Version Type
Section extension stage 3 Mechanically pre-assembled without copper, 8LK3200-0TA30
in-house production of copper assemblies according to drawing
Section extension stage 4 Mechanically pre-assembled with copper 8LK3200-0TA40
Copper surcharge (calculated according to DEL quotation) + 8LK3200-0TA50
Spare parts 8LK3200-0TA10
Accessories
Circular conductors
Busbar thickness Ø Cable Scope of supply Article No.
5 mm 1,5 … 16 mm2 100 units 8US1921-2AA00
1,5 … 35 mm2 50 units 8US1921-2AB00
16 … 70 mm2 50 units 8US1921-2AC00
I201_20292
Cubicle keys
Version Scope of supply Article No.
3 mm double bit 10 units 8PQ9400-0BA12
Cable entries
• Ø Installation = 38 mm
Ø Cable Scope of supply Article No.
1× 12 … 29 mm 1 unit 8HP1805
15
Mounting accessories
Scope of supply Article No.
For ALPHA 8GK supports 1 unit 8GK9910-0KK27
System overview
SIVACON S4 power distribution boards
Busbar systems
I202_29630
I202_29634a
I201_19491
I201_20292
15 3WA 3WA
incoming feeder panels coupling panels
3VA
outgoing feeder
3NJ4
outgoing feeder
3NJ6
outgoing feeder
Cable section
Note:
You will find a detailed range of accessories under section expansions.
Internal separation
1 1 1 1
2 2 2 2
I202_29902
I202_29903
I202_29901
I202_29900
Note:
You will find a detailed range of accessories under section expansions.
15
Frame
For main busbar at top, at bottom and without
1 Gerüst
2 Bodenraumteilung
5 3 Trägerausbau außen
3 4 Trägerausbau innen
5 Feldteilung
I201_18881
1 2
➀ Frame
➁ Bottom plate partition crossbar
➂ Exterior intermediate upright
➃ Interior side upright
➄ Section division
Width Depth ➊ Frame ➋ Bottom plate ➌ Exterior ➍ Interior side upright ➎ Section division
partition crossbar intermediate upright
400 mm 400 mm 8PQ1204-4BA01 – – 8PQ3000-0BA65 –
600 mm 8PQ1204-6BA01 – – 8PQ3000-0BA01 –
800 mm 8PQ1204-8BA01 – – 8PQ3000-0BA02 –
600 mm 400 mm 8PQ1206-4BA01 – – 8PQ3000-0BA65 –
600 mm 8PQ1206-6BA01 – – 8PQ3000-0BA01 –
800 mm 8PQ1206-8BA01 – – 8PQ3000-0BA02 –
800 mm 400 mm 8PQ1208-4BA01 8PQ3000-1BA38 8PQ3000-1BA43 8PQ3000-0BA65 8PQ3000-1BA31
600 mm 8PQ1208-6BA01 8PQ3000-1BA40 8PQ3000-1BA43 8PQ3000-0BA01 8PQ3000-1BA32
800 mm 8PQ1208-8BA01 2× 8PQ3000-1BA38 8PQ3000-1BA43 8PQ3000-0BA02 8PQ3000-1BA34
1000 mm 400 mm 8PQ1201-4BA02 8PQ3000-1BA38 8PQ3000-1BA43 8PQ3000-0BA65 8PQ3000-1BA31
600 mm 8PQ1201-6BA02 8PQ3000-1BA40 8PQ3000-1BA43 8PQ3000-0BA01 8PQ3000-1BA32
15 800 mm 8PQ1201-8BA03 2× 8PQ3000-1BA38 8PQ3000-1BA43 8PQ3000-0BA02 8PQ3000-1BA34
1200 mm 400 mm 8PQ1202-4BA02 8PQ3000-1BA38 8PQ3000-1BA43 8PQ3000-0BA65 8PQ3000-1BA31
600 mm 8PQ1202-6BA02 8PQ3000-1BA40 8PQ3000-1BA43 8PQ3000-0BA01 8PQ3000-1BA32
800 mm 8PQ1202-8BA02 2× 8PQ3000-1BA38 8PQ3000-1BA43 8PQ3000-0BA02 8PQ3000-1BA34
1 Gerüst
5 5
2 Bodenraumteilung
3 Trägerausbau außen
3
4 Trägerausbau innen
5 Feldteilung
4 4
3
I201_18882
I202_29629
1 2 1 2
➀ Frame ➀ Frame
➁ Bottom plate partition crossbar ➁ Bottom plate partition crossbar
➂ Exterior intermediate upright ➂ Exterior intermediate upright
➃ Interior side upright ➃ Interior side upright
➄ Section division ➄ Section division
➍ Interior side upright ➎ Section division ➍ Interior side upright ➎ Section division
8PQ3000-0BA10 – – –
8PQ3000-3BA10 – 8PQ3000-0BA03 –
8PQ3000-3BA11 – 8PQ3000-0BA03 –
8PQ3000-0BA10 – – –
8PQ3000-3BA10 – 8PQ3000-0BA03 –
8PQ3000-3BA11 – 8PQ3000-0BA03 –
8PQ3000-0BA10 8PQ3000-0BA10 – –
8PQ3000-3BA10 8PQ3000-3BA47 8PQ3000-0BA03 8PQ3000-1BA36
8PQ3000-3BA11 8PQ3000-3BA48 8PQ3000-0BA03 8PQ3000-1BA37
8PQ3000-0BA10 8PQ3000-0BA10 – –
8PQ3000-3BA10 8PQ3000-3BA47 8PQ3000-0BA03 8PQ3000-1BA36
8PQ3000-3BA11 8PQ3000-3BA48 8PQ3000-0BA03 8PQ3000-1BA37 15
8PQ3000-0BA10 8PQ3000-0BA10 – –
8PQ3000-3BA10 8PQ3000-3BA47 8PQ3000-0BA03 8PQ3000-1BA36
8PQ3000-3BA11 8PQ3000-3BA48 8PQ3000-0BA03 8PQ3000-1BA37
Frame
For main busbar at rear
Single Duplex
In = 3200 A In = 6300 A
I201_20212
2
1
➀ Frame
➁ Bottom plate partition crossbar
➂ Exterior intermediate upright
➃ Interior side upright
➄ Section division
Frame
Accessories
Frame reinforcement
Use Scope of supply Article No.
Recommended from width 1000 mm 4 units 8PQ9400-0BA35
Crossbars
Version Width Crossbar length Scope of supply Article No.
– 400 mm 350 mm 2 units 8PQ3000-0BA12
600 mm 550 mm 2 units 8PQ3000-0BA71
800 mm 750 mm 2 units 8PQ3000-0BA72
1000 mm 950 mm 2 units 8PQ3000-0BA84
1200 mm 1150 mm 2 units 8PQ3000-0BA85
Without uprights 400 mm 300 mm 2 units 8PQ3000-0BA10
600 mm 500 mm 2 units 8PQ3000-1BA24
800 mm 700 mm 2 units 8PQ3000-1BA25
With uprights 600 mm 300 mm 2 units 8PQ3000-0BA10
800 mm 300 mm 2 units 8PQ3000-0BA10
Forming rows of frames
Version Scope of supply Article No.
Frame connection 6 units 8PQ1204-4BA05
Self-tapping screws
Type Version Scope of supply Article No.
Cylinder-head screws M6 × 10 mm 100 units 8PQ9500-0BA34
M6 × 16 mm 100 units 8PQ9500-0BA32
M6 × 20 mm 100 units 8PQ9500-0BA31
Countersunk screws M6 × 12 mm 100 units 8PQ9500-1BA07
15
15
Enclosure
Paneling sections, main busbar at top/at bottom
4
I201_18204
1 Sockel 4 Seitenwand
2 Bodenblech 5 Dachblech Position of main busbar At top
3 Rückwand 6 Türen / alternativ Gerüstverblendung At bottom
➊ Bases ➋ Bottom plates
Enclosure
Paneling sections, main busbar at top/at bottom
Accessories
Reinforcements for transport
Height Width/depth Article No.
100 mm 400 mm 8PQ1014-0BA02
600 mm 8PQ1016-0BA02
800 mm 8PQ1018-0BA02
1000 mm 8PQ1011-1BA01
1200 mm 8PQ1012-2BA01
15
15
Enclosure
Paneling sections, main busbar at rear
1 Sockel
5 2 Bodenblech
3 Seitenwände
4
4 Dachblech
3 5 IPX1 Dachblechaufsatz
I201_20208
Accessories
Base corner pieces for depths of 1000 mm and 1200 mm
Height Article No.
100 mm 8PQ1010-1BA01
200 mm 8PQ1020-1BA01
Enclosure
Paneling sections
1
2 I201_20273
Hinge Width IP40 IP55 IP55 glass doors IP40 IP55 IP55 glass doors
Left 200 mm – – – – – –
400 mm 8PQ2197-4BA08 8PQ2197-4BA05 – 8PQ2197-4BA06 8PQ2197-4BA03 –
600 mm 8PQ2197-6BA06 8PQ2197-6BA03 8PQ2197-6BA10 8PQ2197-6BA04 8PQ2197-6BA01 8PQ2197-6BA07
800 mm 8PQ2197-8BA06 8PQ2197-8BA03 8PQ2197-8BA10 8PQ2197-8BA04 8PQ2197-8BA01 8PQ2197-8BA07
1000 mm 8PQ2197-1BA06 8PQ2197-1BA03 8PQ2197-1BA10 8PQ2197-1BA07 8PQ2197-1BA04 8PQ2197-1BA11
Right 200 mm – – – – – –
400 mm 8PQ2197-4BA11 8PQ2197-4BA10 – 8PQ2197-4BA07 8PQ2197-4BA04 –
600 mm 8PQ2197-6BA13 8PQ2197-6BA12 8PQ2197-6BA14 8PQ2197-6BA05 8PQ2197-6BA02 8PQ2197-6BA08
800 mm 8PQ2197-8BA13 8PQ2197-8BA12 8PQ2197-8BA14 8PQ2197-8BA05 8PQ2197-8BA02 8PQ2197-8BA08
1000 mm 8PQ2197-1BA18 8PQ2197-1BA17 8PQ2197-1BA20 8PQ2197-1BA08 8PQ2197-1BA05 8PQ2197-1BA12
15 Lock systems
Locking rods
8PQ9400-0BA37 8PQ9400-0BA37 8PQ9400-0BA38
Bar guides
8PQ9400-0BA36 8PQ9400-0BA36 8PQ9400-0BA36
15
Door cutouts
15/37
I201_20266
Siemens LV 10 · 10/2022
© Siemens 2022
Power Distribution Boards, Motor Control Centers and Distribution Boards | SIVACON S4 power distribution boards
Enclosure
Paneling sections
Accessories
Cubicle keys
Version Scope of supply Article No.
3 mm double bit 10 units 8PQ9400-0BA12
Cubicle ID plate
Version Article No.
SIVACON designed by Siemens 8PQ9400-0BA06
Door hinges
Version Scope of supply Article No.
Hinges, incl. fixing accessories 2 units 8PQ9400-0BA55
15
15
Enclosure
Internal covers
2
I201_20274
1 Blendrahmen
2 Blenden
Position of main busbar At top
Without
➊ Cover frames
I201_20324
I201_20362
1600 mm
1800 mm
➋ Covers
Accessories
Covers, ventilated
Height Width Article No.
100 mm 600 mm 8PQ2010-6BA02
800 mm 8PQ2010-8BA02
Quick-release lock
Version Scope of supply Article No.
SIVACON – Blue green basic 20 units 8PQ9400-0BA54
15
Enclosure
Compartment doors
1 Device Device
➀ compartments Compartment doors Covers
compartments
2 Head compartments
2 3 Base compartments
15 800 mm 50 mm
100 mm
–
–
–
–
8PQ2005-8BA04
8PQ2010-8BA04
8PQ2005-8BA03
8PQ2010-8BA03
150 mm 8PQ2015-8BA05 8PQ2015-8BA07 – –
200 mm 8PQ2020-8BA07 8PQ2020-8BA08 – –
250 mm 8PQ2025-8BA04 8PQ2025-8BA05 – –
300 mm 8PQ2030-8BA05 8PQ2030-8BA06 – –
350 mm 8PQ2035-8BA06 8PQ2035-8BA07 – –
400 mm 8PQ2040-8BA12 8PQ2040-8BA13 – –
450 mm 8PQ2045-8BA03 8PQ2045-8BA04 – –
500 mm 8PQ2050-8BA03 8PQ2050-8BA04 – –
550 mm 8PQ2055-8BA03 8PQ2055-8BA06 – –
600 mm 8PQ2060-8BA04 8PQ2060-8BA05 – –
650 mm 8PQ2065-8BA03 8PQ2065-8BA04 – –
700 mm 8PQ2070-8BA01 8PQ2070-8BA02 – –
750 mm 8PQ2075-8BA01 8PQ2075-8BA02 – –
800 mm 8PQ2080-8BA03 8PQ2080-8BA04 – –
15
Enclosure
Compartment doors
Accessories
Door hinges
Version Scope of supply Article No.
Hinges, incl. fixing accessories 2 units 8PQ9400-0BA55
Locks
Version Article No.
Two-way interlocking mechanisms 8PQ9400-0BA40
Cubicle keys
Version Scope of supply Article No.
3 mm double bit 10 units 8PQ9400-0BA12
15
Busbar systems
Main busbars
1 Sammelschienenhalter
2 Versteifung
3 Stromausgleich
4 Abdeckung
6
5 Hauptsammelschiene
6 PE Schiene
I202_29634a
3
2 1 5
Accessories
Connecting lugs
Type Cross-section Article No.
➎ Main busbars 20 × 10 mm 8PQ4000-0BA53
30 × 10 mm 8PQ4000-0BA54
40 × 10 mm 8PQ4000-0BA56
50 × 10 mm 8PQ4000-0BA57
➏ PE bar 20 × 5 mm 8PQ4000-0BA52
30 × 5 mm
30 × 10 mm 15
40 × 5 mm 8PQ4000-0BA67
40 × 10 mm
50 × 10 mm
Protective cover
Type Article No.
• Main busbar at rear 8PQ4000-3BA35
• Mounting width 200 mm
Circular conductors
Busbar thickness Ø Cable Scope of supply Article No.
5 mm 1,5 … 16 mm2 100 units 8US1921-2AA00
1,5 … 35 mm2 50 units 8US1921-2AB00
16 … 70 mm2 50 units 8US1921-2AC00
I201_20292
Busbar systems
Vertical distribution busbars, cascaded, up to Icw = 65 kA
➊ Busbar supports ➋ Supports
Position 30 × 10 mm 40 × 10 mm
of main busbar
Top 8PQ4000-0BA32 8PQ4000-0BA63 –
Bottom 8PQ4000-0BA32 8PQ4000-0BA63 8PQ4000-1BA23
I202_29630
Accessories
Connection
Component Version Scope of supply Article No.
Busbar clamps M10 20 units 8PQ9400-0BA02
Connecting lugs
Cross-section Position of vertical Position of main Depth Article No.
distribution busbar busbar
30 × 10 mm Right Front 400 mm 8PQ4000-0BA45
600 mm 8PQ4000-0BA46
800 mm 8PQ4000-0BA46
Rear 800 mm 8PQ4000-0BA50
Left Front 400 mm 8PQ4000-0BA73
600 mm 8PQ4000-0BA72
800 mm 8PQ4000-0BA72
Rear 800 mm 8PQ4000-0BA70
40 × 10 mm Right Front 400 mm 8PQ4000-0BA47
600 mm 8PQ4000-0BA48
800 mm 8PQ4000-0BA48
15 Rear 800 mm 8PQ4000-0BA51
Left Front 400 mm 8PQ4000-0BA75
600 mm 8PQ4000-0BA48
800 mm 8PQ4000-0BA48
Rear 800 mm 8PQ4000-0BA71
Position Width
of main busbar
At top 200 mm 8PQ4000-2BA25 8PQ4000-0BA37 8PQ4000-0BA78
2 400 mm 8PQ4000-2BA26 8PQ4000-0BA37 8PQ4000-0BA61
At bottom 200 mm 8PQ4000-2BA25 8PQ4000-0BA37 –
400 mm 8PQ4000-2BA26 8PQ4000-0BA37 –
I201_18802
Accessories
Connecting lugs
Cross-section Position of main busbar Depth Article No.
20 × 10 mm At front 400 mm 8PQ4000-0BA38
30 × 10 mm 600 mm 8PQ4000-0BA40
800 mm 8PQ4000-0BA40
At rear 800 mm 8PQ4000-0BA43
15
Section expansion
3WA air circuit breakers, main busbar at top
1 Head compartment door
2 Compartment door
3 Base compartment door
4 Mounting plate
2 4
7
I201_20189
+ 3WA9111-0AP01 + 3WA9111-0AP03
Type of Size Width Depth IP40 IP55 IP40 IP55 IP55
mounting upgrade upgrade
Fixed- I 600 mm 400 mm 8PQ2067-6BA01 8PQ2067-6BA02 8PQ2055-6BA16 8PQ2055-6BA17 8PQ2055-6BA06
mounted 600 mm 8PQ2067-6BA01 8PQ2067-6BA02 8PQ2055-6BA16 8PQ2055-6BA17 8PQ2055-6BA06
800 mm 8PQ2067-6BA01 8PQ2067-6BA02 8PQ2055-6BA16 8PQ2055-6BA17 8PQ2055-6BA06
II 800 mm 600 mm 8PQ2067-8BA01 8PQ2067-8BA02 8PQ2055-8BA08 8PQ2055-8BA10 8PQ2055-8BA06
800 mm 8PQ2067-8BA01 8PQ2067-8BA02 8PQ2055-8BA08 8PQ2055-8BA10 8PQ2055-8BA06
III 1000 mm 800 mm 8PQ2067-1BA01 8PQ2067-1BA02 8PQ2055-1BA03 8PQ2055-1BA04 8PQ2055-1BA06
Withdraw I 600 mm 400 mm 8PQ2067-6BA01 8PQ2067-6BA02 8PQ2055-6BA16 8PQ2055-6BA17 8PQ2055-6BA06
able 600 mm 8PQ2067-6BA01 8PQ2067-6BA02 8PQ2055-6BA16 8PQ2055-6BA17 8PQ2055-6BA06
800 mm 8PQ2067-6BA01 8PQ2067-6BA02 8PQ2055-6BA16 8PQ2055-6BA17 8PQ2055-6BA06
II 800 mm 600 mm 8PQ2067-8BA01 8PQ2067-8BA02 8PQ2055-8BA08 8PQ2055-8BA10 8PQ2055-8BA06
15 800 mm 8PQ2067-8BA01 8PQ2067-8BA02 8PQ2055-8BA08 8PQ2055-8BA10 8PQ2055-8BA06
III 1000 mm 800 mm 8PQ2067-1BA01 8PQ2067-1BA02 8PQ2055-1BA03 8PQ2055-1BA04 8PQ2055-1BA06
➌ Base compartment doors ➍ Mounting ➎ Main busbar connection ➏ Separation 4b ➐ Cable Insulation
plates connection
Accessories
Compartment ID strip for plug-in plates, H = 17 mm
Width Scope of supply Article No.
600 mm 6 units 8PQ5000-3BA43
800 mm 6 units 8PQ5000-3BA46
1000 mm 6 units 8PQ5000-3BA47
Section expansion
3WA air circuit breakers, main busbar at bottom
4
2
6 5
I201_20188a
+ 3WA9111-0AP01 + 3WA9111-0AP03
Type of Size Width Depth IP40 IP55 IP40 IP55 IP55
mounting upgrade upgrade
Fixed- I 600 mm 400 mm 8PQ2067-6BA01 8PQ2067-6BA02 8PQ2055-6BA16 8PQ2055-6BA17 8PQ2055-6BA06
mounted 600 mm 8PQ2067-6BA01 8PQ2067-6BA02 8PQ2055-6BA16 8PQ2055-6BA17 8PQ2055-6BA06
800 mm 8PQ2067-6BA01 8PQ2067-6BA02 8PQ2055-6BA16 8PQ2055-6BA17 8PQ2055-6BA06
II 800 mm 600 mm 8PQ2067-8BA01 8PQ2067-8BA02 8PQ2055-8BA08 8PQ2055-8BA10 8PQ2055-8BA06
800 mm 8PQ2067-8BA01 8PQ2067-8BA02 8PQ2055-8BA08 8PQ2055-8BA10 8PQ2055-8BA06
Withdraw I 600 mm 400 mm 8PQ2067-6BA01 8PQ2067-6BA02 8PQ2055-6BA16 8PQ2055-6BA17 8PQ2055-6BA06
able 600 mm 8PQ2067-6BA01 8PQ2067-6BA02 8PQ2055-6BA16 8PQ2055-6BA17 8PQ2055-6BA06
800 mm 8PQ2067-6BA01 8PQ2067-6BA02 8PQ2055-6BA16 8PQ2055-6BA17 8PQ2055-6BA06
II 800 mm 600 mm 8PQ2067-8BA01 8PQ2067-8BA02 8PQ2055-8BA08 8PQ2055-8BA10 8PQ2055-8BA06
800 mm 8PQ2067-8BA01 8PQ2067-8BA02 8PQ2055-8BA08 8PQ2055-8BA10 8PQ2055-8BA06
15
➌ Base compartment doors ➍ Mounting ➎ Main busbar connection ➏ Separation 4b ➐ Cable Insulation
plates connection
Accessories
Compartment ID strip for plug-in plates, H = 17 mm
Width Scope of supply Article No.
600 mm 6 units 8PQ5000-3BA43
800 mm 6 units 8PQ5000-3BA46
Section expansion
3WA air circuit breakers, coupling
1 6
2 4
6 5
I201_19645a
+ 3WA9111-0AP01 + 3WA9111-0AP03
Type of Size Width Depth IP40 IP55 IP4X IP55 IP55
mounting upgrade upgrade
Fixed- I 600 mm 400 mm 8PQ2067-6BA01 8PQ2067-6BA02 8PQ2055-6BA16 8PQ2055-6BA17 8PQ2055-6BA06
mounted 600 mm 8PQ2067-6BA01 8PQ2067-6BA02 8PQ2055-6BA16 8PQ2055-6BA17 8PQ2055-6BA06
800 mm 8PQ2067-6BA01 8PQ2067-6BA02 8PQ2055-6BA16 8PQ2055-6BA17 8PQ2055-6BA06
II 800 mm 600 mm 8PQ2067-8BA01 8PQ2067-8BA02 8PQ2055-8BA08 8PQ2055-8BA10 8PQ2055-8BA06
800 mm 8PQ2067-8BA01 8PQ2067-8BA02 8PQ2055-8BA08 8PQ2055-8BA10 8PQ2055-8BA06
Withdraw I 600 mm 400 mm 8PQ2067-6BA01 8PQ2067-6BA02 8PQ2055-6BA16 8PQ2055-6BA17 8PQ2055-6BA06
able 600 mm 8PQ2067-6BA01 8PQ2067-6BA02 8PQ2055-6BA16 8PQ2055-6BA17 8PQ2055-6BA06
800 mm 8PQ2067-6BA01 8PQ2067-6BA02 8PQ2055-6BA16 8PQ2055-6BA17 8PQ2055-6BA06
II 800 mm 600 mm 8PQ2067-8BA01 8PQ2067-8BA02 8PQ2055-8BA08 8PQ2055-8BA10 8PQ2055-8BA06
800 mm 8PQ2067-8BA01 8PQ2067-8BA02 8PQ2055-8BA08 8PQ2055-8BA10 8PQ2055-8BA06
15
➌ Base compartment doors ➍ Mounting plates ➎ Main busbar connection ➏ Separation 4b ➐ Uprights
IP40 IP55
upgrade
8PQ2075-6BA01 8PQ2075-6BA03 8PQ6000-5BA26 2× 8PQ6000-6BA75 8PQ5000-5BA12 –
8PQ2075-6BA01 8PQ2075-6BA03 8PQ6000-5BA26 2× 8PQ6000-6BA75 8PQ5000-5BA13 2× 8PQ3000-3BA50
8PQ2075-6BA01 8PQ2075-6BA03 8PQ6000-5BA26 2× 8PQ6000-6BA75 8PQ5000-5BA14 2× 8PQ3000-3BA51
8PQ2075-8BA01 8PQ2075-8BA03 8PQ6000-5BA24 2× 8PQ6000-6BA76 8PQ5000-5BA15 2× 8PQ3000-3BA50
8PQ2075-8BA01 8PQ2075-8BA03 8PQ6000-5BA24 2× 8PQ6000-6BA76 8PQ5000-5BA16 2× 8PQ3000-3BA51
8PQ2075-6BA01 8PQ2075-6BA03 8PQ6000-5BA26 2× 8PQ6000-6BA75 8PQ5000-5BA12 –
8PQ2075-6BA01 8PQ2075-6BA03 8PQ6000-5BA26 2× 8PQ6000-6BA75 8PQ5000-5BA13 2× 8PQ3000-3BA50
8PQ2075-6BA01 8PQ2075-6BA03 8PQ6000-5BA26 2× 8PQ6000-6BA75 8PQ5000-5BA14 2× 8PQ3000-3BA51
8PQ2075-8BA01 8PQ2075-8BA03 8PQ6000-5BA24 2× 8PQ6000-6BA76 8PQ5000-5BA15 2× 8PQ3000-3BA50
8PQ2075-8BA01 8PQ2075-8BA03 8PQ6000-5BA24 2× 8PQ6000-6BA76 8PQ5000-5BA16 2× 8PQ3000-3BA51
15
Accessories
Compartment ID strip for plug-in plates, H = 17 mm
Width Scope of supply Article No.
600 mm 6 units 8PQ5000-3BA43
800 mm 6 units 8PQ5000-3BA46
Section expansion
3WA air circuit breakers, connection of section busbar systems
7
3
2
5
6
1
4
I201_20213
+ 3WA9111-0AP01 + 3WA9111-0AP03
Type of mounting Size Width Number of poles In IP40 IP55 IP55
upgrade
Fixed-mounted I 400 mm 3-pole 1600 A 8PQ6000-5BA25 8PQ2055-4BA12 – –
2000 A 8PQ6000-5BA25 8PQ2055-4BA12 – –
600 mm 4-pole 1600 A 8PQ6000-5BA26 8PQ2055-6BA16 8PQ2055-6BA17 + 8PQ2055-6BA06
2000 A 8PQ6000-5BA26 8PQ2055-6BA16 8PQ2055-6BA17 + 8PQ2055-6BA06
Withdrawable I 400 mm 3-pole 1600 A 8PQ6000-5BA25 8PQ2055-4BA12 –
2000 A 8PQ6000-5BA25 8PQ2055-4BA12 –
600 mm 4-pole 1600 A 8PQ6000-5BA26 8PQ2055-6BA16 8PQ2055-6BA17 + 8PQ2055-6BA06
2000 A 8PQ6000-5BA26 8PQ2055-6BA16 8PQ2055-6BA17 + 8PQ2055-6BA06
15
+ 3WA9111-0AP01
Type of mounting Size Width Number of poles In IP40
Fixed-mounted I 600 mm 3-pole 1600 A 8PQ6000-3BA31 8PQ2055-6BA05
2000 A 8PQ6000-3BA31 8PQ2055-6BA05
4-pole 1600 A 8PQ6000-3BA31 8PQ2055-6BA07
2000 A 8PQ6000-3BA31 8PQ2055-6BA07
800 mm 3/4-pole 1600 A 8PQ6000-3BA32 8PQ2055-8BA04
2000 A 8PQ6000-3BA32 8PQ2055-8BA04
Withdrawable I 600 mm 3-pole 1600 A 8PQ6000-3BA31 8PQ2055-6BA05
2000 A 8PQ6000-3BA31 8PQ2055-6BA05
4-pole 1600 A 8PQ6000-3BA31 8PQ2055-6BA07
2000 A 8PQ6000-3BA31 8PQ2055-6BA07
800 mm 3/4-pole 1600 A 8PQ6000-3BA32 8PQ2055-8BA04
2000 A 8PQ6000-3BA32 8PQ2055-8BA04
➌ Section busbars ➍ Cable connection ➎ Device compartment ➏ Cable connection ➐ Section busbars
➌ Section busbars ➍ Cable connection ➎ Device compartment ➏ Cable connection ➐ Section busbars
15
Section expansion
3WA air circuit breakers, fixed-mounted
1 Frame
2 Head compartment
3 Compartment door
1 4 Auxiliary device compartment
2 5 Mounting plate
7 6 Main busbar connectio
8 7 Cable connection
3
8 Separation
5 6 9 Base compartment cover
I201_20209
+ 3WA9111-0AP01 + 3WA9111-0AP03
Size In Width Depth Number At front At rear Covers IP40 IP55 IP55
of poles upgrade
I 2000 A 400 mm 800 mm 3- pole 8PQ1204-8BA01 – 8PQ2025-4BA03 8PQ2055-4BA12 – –
1000 mm 3- pole 8PQ1204-4BA01 + 8PQ1204-6BA01 8PQ2025-4BA03 8PQ2055-4BA12 – –
1200 mm 3- pole 8PQ1204-4BA01 + 8PQ1204-8BA01 8PQ2025-4BA03 8PQ2055-4BA12 – –
1200 mm 3- pole 8PQ1204-4BA01 + 8PQ1204-8BA01 8PQ2025-4BA03 8PQ2055-4BA12 – –
duplex
600 mm 800 mm 3/4-pole 8PQ1206-8BA01 – 8PQ2025-6BA25 8PQ2055-6BA16 8PQ2055-6BA17 + 8PQ2055-6BA06
1000 mm 3/4-pole 8PQ1206-4BA01 + 8PQ1206-6BA01 8PQ2025-6BA25 8PQ2055-6BA16 8PQ2055-6BA17 + 8PQ2055-6BA06
1200 mm 3/4-pole 8PQ1206-4BA01 + 8PQ1206-8BA01 8PQ2025-6BA25 8PQ2055-6BA16 8PQ2055-6BA17 + 8PQ2055-6BA06
15 1200 mm 3/4-pole 8PQ1206-4BA01 + 8PQ1206-8BA01 8PQ2025-6BA25 8PQ2055-6BA16 8PQ2055-6BA17 + 8PQ2055-6BA06
duplex
II 3200 A 800 mm 800 mm 3/4-pole 8PQ1208-8BA01 – 8PQ2025-8BA16 8PQ2055-8BA08 8PQ2055-8BA10 + 8PQ2055-8BA06
1000 mm 3/4-pole 8PQ1208-4BA01 + 8PQ1208-6BA01 8PQ2025-8BA16 8PQ2055-8BA08 8PQ2055-8BA10 + 8PQ2055-8BA06
1200 mm 3/4-pole 8PQ1208-4BA01 + 8PQ1208-8BA01 8PQ2025-8BA16 8PQ2055-8BA08 8PQ2055-8BA10 + 8PQ2055-8BA06
1200 mm 3/4-pole 8PQ1208-4BA01 + 8PQ1208-8BA01 8PQ2025-8BA16 8PQ2055-8BA08 8PQ2055-8BA10 + 8PQ2055-8BA06
duplex
III 4000 A 1000 mm 1200 mm 3/4-pole 8PQ1201-4BA02 + 8PQ1201-8BA03 8PQ2025-1BA01 8PQ2055-1BA03 8PQ2055-1BA04 + 8PQ2055-1BA06
III 5000 A 1000 mm 1200 mm 3/4-pole 8PQ1201-4BA02 + 8PQ1201-8BA03 8PQ2025-1BA01 8PQ2055-1BA03 8PQ2055-1BA04 + 8PQ2055-1BA06
Accessories
Frame reinforcement Compartment ID strip for plug-in plates, H = 17 mm
Size Depth Article No. Width Scope of Article No.
III 1200 mm 8PQ5000-5BA46 supply
400 mm 6 units 8PQ5000-3BA42
600 mm 6 units 8PQ5000-3BA43
800 mm 6 units 8PQ5000-3BA46
Barrier supports
1000 mm 6 units 8PQ5000-3BA47
Size Depth Scope of supply Article No.
I, II, III 1200 mm 1 set = 6 units 8PQ3000-3BA67
Section expansion
3WA air circuit breakers, withdrawable
1 Frame
2 Head compartment
3 Compartment door
1 4 Auxiliary device compartment
2 5 Mounting plate
7 6 Main busbar connectio
8 7 Cable connection
3
8 Separation
5 6 9 Base compartment cover
I201_20209
+ 3WA9111-0AP01 + 3WA9111-0AP03
Size In Width Depth Number At front At rear Covers IP40 IP55 IP55
of poles upgrade
I 2000 A 400 mm 800 mm 3-pole 8PQ1204-8BA01 – 8PQ2025-4BA03 8PQ2055-4BA12 – –
1000 mm 3-pole 8PQ1204-4BA01 + 8PQ1204-6BA01 8PQ2025-4BA03 8PQ2055-4BA12 – –
1200 mm 3-pole 8PQ1204-4BA01 + 8PQ1204-8BA01 8PQ2025-4BA03 8PQ2055-4BA12 – –
1200 mm 3-pole 8PQ1204-4BA01 + 8PQ1204-8BA01 8PQ2025-4BA03 8PQ2055-4BA12 – –
duplex
600 mm 800 mm 3/4-pole 8PQ1204-4BA05 – 8PQ2025-6BA25 8PQ2055-6BA16 8PQ2055-6BA17 + 8PQ2055-6BA06
1000 mm 3/4-pole 8PQ1206-4BA01 + 8PQ1206-6BA01 8PQ2025-6BA25 8PQ2055-6BA16 8PQ2055-6BA17 + 8PQ2055-6BA06
1200 mm 3/4-pole 8PQ1206-4BA01 + 8PQ1206-8BA01 8PQ2025-6BA25 8PQ2055-6BA16 8PQ2055-6BA17 + 8PQ2055-6BA06
1200 mm 3/4-pole 8PQ1206-4BA01 + 8PQ1206-8BA01 8PQ2025-6BA25 8PQ2055-6BA16 8PQ2055-6BA17 + 8PQ2055-6BA06
15
duplex
II 3200 A 800 mm 800 mm 3/4-pole 8PQ1204-4BA05 – 8PQ2025-8BA16 8PQ2055-8BA08 8PQ2055-8BA10 + 8PQ2055-8BA06
1000 mm 3/4-pole 8PQ1208-4BA01 + 8PQ1208-6BA01 8PQ2025-8BA16 8PQ2055-8BA08 8PQ2055-8BA10 + 8PQ2055-8BA06
1200 mm 3/4-pole 8PQ1208-4BA01 + 8PQ1208-8BA01 8PQ2025-8BA16 8PQ2055-8BA08 8PQ2055-8BA10 + 8PQ2055-8BA06
1200 mm 3/4-pole 8PQ1208-4BA01 + 8PQ1208-8BA01 8PQ2025-8BA16 8PQ2055-8BA08 8PQ2055-8BA10 + 8PQ2055-8BA06
duplex
III 4000 A 1000 mm 1200 mm 3/4-pole 8PQ1201-4BA02 + 8PQ1201-8BA03 8PQ2025-1BA01 8PQ2055-1BA03 8PQ2055-1BA04 + 8PQ2055-1BA06
III 5000 A 1000 mm 1200 mm 3/4-pole 8PQ1201-4BA02 + 8PQ1201-8BA03 8PQ2025-1BA01 8PQ2055-1BA03 8PQ2055-1BA04 + 8PQ2055-1BA06
III 6300 A 1000 mm 1200 mm 3/4-pole 8PQ1201-4BA02 + 8PQ1201-8BA03 8PQ2025-1BA01 8PQ2055-1BA03 8PQ2055-1BA04 + 8PQ2055-1BA06
Accessories
Frame reinforcement Compartment ID strip for plug-in plates, H = 17 mm
Size Depth Article No. Width Scope of Article No.
III 1200 mm 8PQ5000-5BA46 supply
400 mm 6 units 8PQ5000-3BA42
600 mm 6 units 8PQ5000-3BA43
800 mm 6 units 8PQ5000-3BA46
Barrier supports
1000 mm 6 units 8PQ5000-3BA47
Size Depth Scope of supply Article No.
I, II, III 1200 mm 1 set = 6 units 8PQ3000-3BA67
15
8PQ6001-0BA61
8PQ2035-8BA06 8PQ6000-5BA24 8PQ6001-0BA73 8PQ6001-0BA81 8PQ5000-3BA81 8PQ5000-5BA23 8PQ5000-5BA38 8PQ2000-8BA13 8PQ2000-8BA11
8PQ2035-8BA06 8PQ6000-5BA24 8PQ6001-0BA73 8PQ6001-0BA81 8PQ5000-3BA81 8PQ5000-5BA51 8PQ5000-5BA38 8PQ2000-8BA13 8PQ2000-8BA11
8PQ2035-8BA06 8PQ6000-5BA24 8PQ6001-0BA73 8PQ6001-0BA81 8PQ5000-3BA81 8PQ5000-5BA23 8PQ5000-5BA38 8PQ2000-8BA13 8PQ2000-8BA11
8PQ2035-8BA06 8PQ6000-5BA24 8PQ6001-0BA73 + 8PQ6001-0BA81 8PQ5000-3BA81 8PQ5000-5BA23 8PQ5000-5BA41 8PQ2000-8BA13 8PQ2000-8BA11
8PQ6001-0BA61
8PQ2035-1BA01 8PQ6000-8BA70 8PQ6001-0BA74 8PQ6001-0BA83 8PQ5000-1BA74 8PQ5000-5BA24 8PQ5000-5BA43 8PQ2000-1BA04 8PQ2000-1BA02
8PQ2035-1BA01 8PQ6000-8BA70 8PQ6001-0BA75 8PQ6001-0BA83 8PQ5000-1BA74 8PQ5000-5BA24 8PQ5000-5BA43 8PQ2000-1BA04 8PQ2000-1BA02
8PQ2035-1BA01 8PQ6000-8BA70 8PQ6001-0BA76 8PQ6001-0BA84 8PQ5000-1BA74 8PQ5000-5BA24 8PQ5000-5BA43 8PQ2000-1BA04 8PQ2000-1BA02
Section expansion
3WA air circuit breakers, couplings, fixed-mounted
3
7
5 6
I201_20210
+ 3WA9111-0AP01 + 3WA9111-0AP03
Size In Width Depth
Number At front At rear Covers IP40 IP55 IP55
of poles upgrade
I 2000 A 400 mm 800 mm 3-pole 8PQ1204-8BA01 – 8PQ2025-4BA03 8PQ2055-4BA12 – –
1000 mm 3-pole 8PQ1204-4BA01 + 8PQ1204-6BA01 8PQ2025-4BA03 8PQ2055-4BA12 – –
1200 mm 3-pole 8PQ1204-4BA01 + 8PQ1204-8BA01 8PQ2025-4BA03 8PQ2055-4BA12 – –
1200 mm 3-pole 8PQ1204-4BA01 + 8PQ1204-8BA01 8PQ2025-4BA03 8PQ2055-4BA12 – –
duplex
600 mm 800 mm 3-/4-pole 8PQ1206-8BA01 – 8PQ2025-6BA25 8PQ2055-6BA16 8PQ2055-6BA17 + 8PQ2055-6BA06
1000 mm 3-/4-pole 8PQ1206-4BA01 + 8PQ1206-6BA01 8PQ2025-6BA25 8PQ2055-6BA16 8PQ2055-6BA17 + 8PQ2055-6BA06
1200 mm 3-/4-pole 8PQ1206-4BA01 + 8PQ1206-8BA01 8PQ2025-6BA25 8PQ2055-6BA16 8PQ2055-6BA17 + 8PQ2055-6BA06
1200 mm 3-/4-pole 8PQ1206-4BA01 + 8PQ1206-8BA01 8PQ2025-6BA25 8PQ2055-6BA16 8PQ2055-6BA17 + 8PQ2055-6BA06
15 II 3200 A
duplex
800 mm 800 mm 3-/4-pole 8PQ1208-8BA01 – 8PQ2025-8BA16 8PQ2055-8BA08 8PQ2055-8BA10 + 8PQ2055-8BA06
1000 mm 3-/4-pole 8PQ1208-4BA01 + 8PQ1208-6BA01 8PQ2025-8BA16 8PQ2055-8BA08 8PQ2055-8BA10 + 8PQ2055-8BA06
1200 mm 3-/4-pole 8PQ1208-4BA01 + 8PQ1208-8BA01 8PQ2025-8BA16 8PQ2055-8BA08 8PQ2055-8BA10 + 8PQ2055-8BA06
1200 mm 3-/4-pole 8PQ1208-4BA01 + 8PQ1208-8BA01 8PQ2025-8BA16 8PQ2055-8BA08 8PQ2055-8BA10 + 8PQ2055-8BA06
duplex
III 4000 A 1000 mm 1200 mm 3-/4-pole 8PQ1201-4BA02 + 8PQ1201-8BA03 8PQ2025-1BA01 8PQ2055-1BA03 8PQ2055-1BA04 + 8PQ2055-1BA06
III 5000 A 1000 mm 1200 mm 3-/4-pole 8PQ1201-4BA02 + 8PQ1201-8BA03 8PQ2025-1BA01 8PQ2055-1BA03 8PQ2055-1BA04 + 8PQ2055-1BA06
Accessories
Frame reinforcement Compartment ID strip for plug-in plates, H = 17 mm
Size Depth Article No. Width Scope of Article No.
III 1200 mm 8PQ5000-5BA46 supply
400 mm 6 units 8PQ5000-3BA42
600 mm 6 units 8PQ5000-3BA43
800 mm 6 units 8PQ5000-3BA46
Barrier supports
1000 mm 6 units 8PQ5000-3BA47
Size Depth Scope of supply Article No.
I, II, III 1200 mm 1 set = 6 units 8PQ3000-3BA67
8PQ2035-8BA06 8PQ6000-5BA24
+
2×
8PQ6001-0BA62
8PQ6001-0BA72 8PQ5000-3BA81 8PQ5000-5BA27 8PQ5000-5BA40 8PQ2000-8BA13 8PQ2000-8BA11
15
8PQ2035-8BA06 8PQ6000-5BA24 2× 8PQ6001-0BA72 8PQ5000-3BA81 8PQ5000-5BA54 8PQ5000-5BA40 8PQ2000-8BA13 8PQ2000-8BA11
8PQ2035-8BA06 8PQ6000-5BA24 2× 8PQ6001-0BA72 8PQ5000-3BA81 8PQ5000-5BA27 8PQ5000-5BA40 8PQ2000-8BA13 8PQ2000-8BA11
8PQ2035-8BA06 8PQ6000-5BA24 2× 8PQ6001-0BA72 8PQ5000-3BA81 8PQ5000-5BA27 8PQ5000-5BA42 8PQ2000-8BA13 8PQ2000-8BA11
+ 8PQ6001-0BA64
8PQ2035-1BA01 8PQ6000-8BA70 2× 8PQ6001-0BA74 8PQ5000-1BA74 8PQ5000-5BA28 8PQ5000-5BA44 8PQ2000-1BA04 8PQ2000-1BA02
8PQ2035-1BA01 8PQ6000-8BA70 2× 8PQ6001-0BA75 8PQ5000-1BA74 8PQ5000-5BA28 8PQ5000-5BA44 8PQ2000-1BA04 8PQ2000-1BA02
Section expansion
3WA air circuit breakers, couplings, withdrawable
3
7
5 6
I201_20210
+ 3WA9111-0AP01 + 3WA9111-0AP03
Size In Width Depth
Number At front At rear Covers IP40 IP55 IP55
of poles upgrade
I 2000 A 400 mm 800 mm 3-pole 8PQ1204-8BA01 – 8PQ2025-4BA03 8PQ2055-4BA12 – –
1000 mm 3-pole 8PQ1204-4BA01 + 8PQ1204-6BA01 8PQ2025-4BA03 8PQ2055-4BA12 – –
1200 mm 3-pole 8PQ1204-4BA01 + 8PQ1204-8BA01 8PQ2025-4BA03 8PQ2055-4BA12 – –
1200 mm 3-pole 8PQ1204-4BA01 + 8PQ1204-8BA01 8PQ2025-4BA03 8PQ2055-4BA12 – –
duplex
600 mm 800 mm 3/4-pole 8PQ1206-8BA01 – 8PQ2025-6BA25 8PQ2055-6BA16 8PQ2055-6BA17 + 8PQ2055-6BA06
1000 mm 3/4-pole 8PQ1206-4BA01 + 8PQ1206-6BA01 8PQ2025-6BA25 8PQ2055-6BA16 8PQ2055-6BA17 + 8PQ2055-6BA06
1200 mm 3/4-pole 8PQ1206-4BA01 + 8PQ1206-8BA01 8PQ2025-6BA25 8PQ2055-6BA16 8PQ2055-6BA17 + 8PQ2055-6BA06
1200 mm 3/4-pole 8PQ1206-4BA01 + 8PQ1206-8BA01 8PQ2025-6BA25 8PQ2055-6BA16 8PQ2055-6BA17 + 8PQ2055-6BA06
15 II
duplex
3200 A 800 mm 800 mm 3/4-pole 8PQ1208-8BA01 – 8PQ2025-8BA16 8PQ2055-8BA08 8PQ2055-8BA10 + 8PQ2055-8BA06
1000 mm 3/4-pole 8PQ1208-4BA01 + 8PQ1208-6BA01 8PQ2025-8BA16 8PQ2055-8BA08 8PQ2055-8BA10 + 8PQ2055-8BA06
1200 mm 3/4-pole 8PQ1208-4BA01 + 8PQ1208-8BA01 8PQ2025-8BA16 8PQ2055-8BA08 8PQ2055-8BA10 + 8PQ2055-8BA06
1200 mm 3/4-pole 8PQ1208-4BA01 + 8PQ1208-8BA01 8PQ2025-8BA16 8PQ2055-8BA08 8PQ2055-8BA10 + 8PQ2055-8BA06
duplex
III 4000 A 1000 mm 1200 mm 3/4-pole 8PQ1201-4BA02 + 8PQ1201-8BA03 8PQ2025-1BA01 8PQ2055-1BA03 8PQ2055-1BA04 + 8PQ2055-1BA06
III 5000 A 1000 mm 1200 mm 3/4-pole 8PQ1201-4BA02 + 8PQ1201-8BA03 8PQ2025-1BA01 8PQ2055-1BA03 8PQ2055-1BA04 + 8PQ2055-1BA06
III 6300 A 1000 mm 1200 mm 3/4-pole 8PQ1201-4BA02 + 8PQ1201-8BA03 8PQ2025-1BA01 8PQ2055-1BA03 8PQ2055-1BA04 + 8PQ2055-1BA06
Accessories
Frame reinforcement Compartment ID strip for plug-in plates, H = 17 mm
Size Depth Article No. Width Scope of Article No.
III 1200 mm 8PQ5000-5BA46 supply
400 mm 6 units 8PQ5000-3BA42
600 mm 6 units 8PQ5000-3BA43
800 mm 6 units 8PQ5000-3BA46
Barrier supports
1000 mm 6 units 8PQ5000-3BA47
Size Depth Scope of supply Article No.
I, II, III 1200 mm 1 set = 6 units 8PQ3000-3BA67
8PQ2035-8BA06 8PQ6000-5BA24
+
2×
8PQ6001-0BA62
8PQ6001-0BA73 8PQ5000-3BA81 8PQ5000-5BA27 8PQ5000-5BA40 8PQ2000-8BA13 8PQ2000-8BA11 15
8PQ2035-8BA06 8PQ6000-5BA24 2× 8PQ6001-0BA73 8PQ5000-3BA81 8PQ5000-5BA54 8PQ5000-5BA40 8PQ2000-8BA13 8PQ2000-8BA11
8PQ2035-8BA06 8PQ6000-5BA24 2× 8PQ6001-0BA73 8PQ5000-3BA81 8PQ5000-5BA27 8PQ5000-5BA40 8PQ2000-8BA13 8PQ2000-8BA11
8PQ2035-8BA06 8PQ6000-5BA24 2× 8PQ6001-0BA73 8PQ5000-3BA81 8PQ5000-5BA27 8PQ5000-5BA42 8PQ2000-8BA13 8PQ2000-8BA11
+ 8PQ6001-0BA64
8PQ2035-1BA01 8PQ6000-8BA70 2× 8PQ6001-0BA74 8PQ5000-1BA74 8PQ5000-5BA28 8PQ5000-5BA44 8PQ2000-1BA04 8PQ2000-1BA02
8PQ2035-1BA01 8PQ6000-8BA70 2× 8PQ6001-0BA75 8PQ5000-1BA74 8PQ5000-5BA28 8PQ5000-5BA44 8PQ2000-1BA04 8PQ2000-1BA02
8PQ2035-1BA01 8PQ6000-8BA70 2× 8PQ6001-0BA76 8PQ5000-1BA74 8PQ5000-5BA28 8PQ5000-5BA44 8PQ2000-1BA04 8PQ2000-1BA02
Section expansion
3WA air circuit breakers, accessories
Busbar supports
Size Width Number of poles Scope of supply Article No.
I 600 mm 4-pole 4 units 8PQ6000-4BA35
800 mm 4-pole 4 units 8PQ6000-4BA37
II 600 mm 3-pole 4 units 8PQ6000-4BA36
800 mm 4-pole 4 units 8PQ6000-4BA38
III 1000 mm 4-pole 4 units 8PQ6000-4BA40
Busbar connections
Size Width Number of poles Scope of supply Article No.
For use with SIVACON I 600 mm 4-pole 1 unit 8PQ3000-1BA70
8PS 800 mm 4-pole 1 unit 8PQ3000-1BA71
II 600 mm 3-pole 1 unit 8PQ3000-1BA70
800 mm 4-pole 1 unit 8PQ3000-1BA71
III 1000 mm 4-pole 1 unit 8PQ3000-1BA72
Cable brackets
Size Width Scope of supply Article No.
I 400 mm 5 units 8PQ3000-0BA41
600 mm 5 units 8PQ3000-0BA42
800 mm 5 units 8PQ3000-0BA43
II 600 mm 5 units 8PQ3000-0BA42
800 mm 5 units 8PQ3000-0BA43
III 1000 mm 4 units 8PQ3000-3BA68
15
15
Section expansion
3VA molded case circuit breakers, 3-pole
1 Festeinbau ➊ Fixed-mounted version
2 Festeinbau mit RCD
3 Stecktechnik
– – ■ 8PQ6000-8BA07 8PQ2020-8BA20
3VA13 400 A 600 mm ■ ■ – 8PQ6000-8BA23 8PQ2020-6BA41
– – ■ 8PQ6000-8BA23 8PQ2020-6BA41
800 mm ■ ■ – 8PQ6000-8BA27 8PQ2025-8BA14
– – ■ 8PQ6000-8BA27 8PQ2025-8BA14
3VA14 630 A 600 mm ■ ■ – 8PQ6000-8BA23 8PQ2020-6BA41
– – ■ 8PQ6000-8BA23 8PQ2020-6BA41
800 mm ■ ■ – 8PQ6000-8BA27 8PQ2025-8BA14
– – ■ 8PQ6000-8BA27 8PQ2025-8BA14
3VA15 new 1000 A 800 mm ■ – – 8PQ6001-4BA22 8PQ2045-8BA22
3VA20 100 A 600 mm ■ ■ – 8PQ6000-8BA08 8PQ2020-6BA38
– – ■ 8PQ6000-8BA08 8PQ2020-6BA38
800 mm ■ ■ – 8PQ6000-8BA10 8PQ2020-8BA21
– – ■ 8PQ6000-8BA10 8PQ2020-8BA21
3VA21 160 A 600 mm ■ ■ – 8PQ6000-8BA08 8PQ2020-6BA38
– – ■ 8PQ6000-8BA08 8PQ2020-6BA38
800 mm ■ ■ – 8PQ6000-8BA10 8PQ2020-8BA21
– – ■ 8PQ6000-8BA10 8PQ2020-8BA21
3VA22 250 A 600 mm ■ ■ – 8PQ6000-8BA08 8PQ2020-6BA38
– – ■ 8PQ6000-8BA08 8PQ2020-6BA38
800 mm ■ ■ – 8PQ6000-8BA10 8PQ2020-8BA21
– – ■ 8PQ6000-8BA10 8PQ2020-8BA21
3VA23 400 A 600 mm ■ ■ – 8PQ6000-8BA23 8PQ2020-6BA41
– – ■ 8PQ6000-8BA23 8PQ2020-6BA41
800 mm ■ ■ – 8PQ6000-8BA27 8PQ2025-8BA14
15 – – ■ 8PQ6000-8BA27 8PQ2025-8BA14
3VA24 630 A 600 mm ■ ■ – 8PQ6000-8BA23 8PQ2020-6BA41
– – ■ 8PQ6000-8BA23 8PQ2020-6BA41
800 mm ■ ■ – 8PQ6000-8BA27 8PQ2025-8BA14
– – ■ 8PQ6000-8BA27 8PQ2025-8BA14
3VA25 new 1000 A 800 mm ■ – – 8PQ6001-4BA22 8PQ2045-8BA22
3VA26 new 1250 A 800 mm ■ – – 8PQ6001-4BA22 8PQ2045-8BA22
3VA27 new 1600 A 800 mm ■ – – 8PQ6001-4BA23 8PQ2045-8BA23
– – – – – –
– – – – – –
8PQ6000-8BA01 8PQ2015-6BA27 8PQ6000-8BA01 8PQ2015-6BA26 – –
8PQ6000-8BA01 8PQ2015-6BA27 8PQ6000-8BA01 8PQ2015-6BA26 – –
8PQ6000-8BA02 8PQ2015-8BA11 8PQ6000-8BA02 8PQ2015-8BA11 – –
8PQ6000-8BA02 8PQ2015-8BA11 8PQ6000-8BA02 8PQ2015-8BA11 – –
8PQ6000-8BA03 1) 8PQ2015-6BA30 8PQ6000-8BA04 8PQ2015-6BA28 8PQ6000-8BA04 8PQ2025-6BA21
8PQ6000-8BA03 8PQ2015-6BA30 8PQ6000-8BA04 8PQ2015-6BA28 – –
8PQ6000-8BA07 8PQ2020-8BA20 8PQ6000-8BA07 8PQ2020-8BA20 8PQ6000-8BA07 8PQ2025-8BA12
8PQ6000-8BA07 8PQ2020-8BA20 8PQ6000-8BA07 8PQ2020-8BA20 – –
– – – – – –
– – – – – –
– – 8PQ6001-1BA02 8PQ2025-8BA18 8PQ6001-1BA02 8PQ2030-8BA15
– – 8PQ6001-1BA02 8PQ2025-8BA18 – –
– – – – – –
– – – – – –
– – 8PQ6001-1BA02 8PQ2025-8BA18 8PQ6001-1BA02 8PQ2030-8BA15
– – 8PQ6001-1BA02 8PQ2025-8BA18 – –
– – – – – –
8PQ6000-8BA11 8PQ2020-6BA40 8PQ6000-8BA08 8PQ2020-6BA38 8PQ6000-8BA08 8PQ2025-6BA22
8PQ6000-8BA11 8PQ2020-6BA40 8PQ6000-8BA08 8PQ2020-6BA38 – –
8PQ6000-8BA10 8PQ2020-8BA21 8PQ6000-8BA10 8PQ2020-8BA21 8PQ6000-8BA10 8PQ2025-8BA13
8PQ6000-8BA10 8PQ2020-8BA21 8PQ6000-8BA10 8PQ2020-8BA21 – –
8PQ6000-8BA11 8PQ2020-6BA40 8PQ6000-8BA08 8PQ2020-6BA38 8PQ6000-8BA08 8PQ2025-6BA22
8PQ6000-8BA11 8PQ2020-6BA40 8PQ6000-8BA08 8PQ2020-6BA38 – –
8PQ6000-8BA10 8PQ2020-8BA21 8PQ6000-8BA10 8PQ2020-8BA21 8PQ6000-8BA10 8PQ2025-8BA13
8PQ6000-8BA10 8PQ2020-8BA21 8PQ6000-8BA10 8PQ2020-8BA21 – –
8PQ6000-8BA11 8PQ2020-6BA40 8PQ6000-8BA08 8PQ2020-6BA38 8PQ6000-8BA08 8PQ2025-6BA22
8PQ6000-8BA11 8PQ2020-6BA40 8PQ6000-8BA08 8PQ2020-6BA38 – –
8PQ6000-8BA10 8PQ2020-8BA21 8PQ6000-8BA10 8PQ2020-8BA21 8PQ6000-8BA10 8PQ2025-8BA13
8PQ6000-8BA10 8PQ2020-8BA21 8PQ6000-8BA10 8PQ2020-8BA21 – –
– – – – – –
– – – – – –
8PQ6000-8BA27 8PQ2025-8BA14 8PQ6001-1BA02 8PQ2025-8BA18 8PQ6001-1BA02 8PQ2035-8BA15
8PQ6000-8BA27 8PQ2025-8BA14 8PQ6001-1BA02 8PQ2025-8BA18 – – 15
– – – – – –
– – – – – –
8PQ6000-8BA27 8PQ2025-8BA14 8PQ6001-1BA02 8PQ2025-8BA18 8PQ6001-1BA02 8PQ2035-8BA15
8PQ6000-8BA27 8PQ2025-8BA14 8PQ6001-1BA02 8PQ2025-8BA18 – –
– – – – – –
– – – – – –
– – – – 8PQ6001-4BA25 8PQ2045-8BA24
1)
For applications >415 V, front mounted rotary operating mechanism or motorized operating mechanism required for compliance with creepage distances and clearances.
2)
Guide frame with direct operating mechanism only
Section expansion
3VA molded case circuit breakers, 4-pole
1 Festeinbau ➊ Fixed-mounted version
2 Festeinbau mit RCD
3 Stecktechnik
15 800 mm
–
■
–
■
■
–
8PQ6000-8BA25
8PQ6000-8BA27
8PQ2025-6BA23
8PQ2025-8BA14
– – ■ 8PQ6000-8BA27 8PQ2025-8BA14
3VA24 630 A 600 mm ■ ■ – 8PQ6000-8BA25 8PQ2025-6BA23
– – ■ 8PQ6000-8BA25 8PQ2025-6BA23
800 mm ■ ■ – 8PQ6000-8BA27 8PQ2025-8BA14
– – ■ 8PQ6000-8BA27 8PQ2025-8BA14
3VA25 new 1000 A 800 mm ■ – – 8PQ6001-4BA22 8PQ2045-8BA22
3VA26 new 1250 A 800 mm ■ – – 8PQ6001-4BA22 8PQ2045-8BA22
3VA27 new 1600 A 800 mm ■ – – 8PQ6001-4BA23 8PQ2045-8BA23
– – – – – –
– – – – – –
8PQ6000-8BA01 8PQ2015-6BA27 8PQ6000-8BA01 8PQ2015-6BA26 – –
8PQ6000-8BA01 8PQ2015-6BA27 8PQ6000-8BA01 8PQ2015-6BA26 – –
8PQ6000-8BA02 8PQ2015-8BA11 8PQ6000-8BA02 8PQ2015-8BA11 – –
8PQ6000-8BA02 8PQ2015-8BA11 8PQ6000-8BA02 8PQ2015-8BA11 – –
8PQ6000-8BA05 1) 8PQ2020-6BA37 8PQ6000-8BA06 8PQ2020-6BA36 8PQ6000-8BA06 8PQ2030-6BA25
8PQ6000-8BA05 1) 8PQ2020-6BA37 8PQ6000-8BA06 8PQ2020-6BA36 – –
8PQ6000-8BA07 8PQ2020-8BA20 8PQ6000-8BA07 8PQ2020-8BA20 8PQ6000-8BA07 8PQ2030-8BA12
8PQ6000-8BA07 8PQ2020-8BA20 8PQ6000-8BA07 8PQ2020-8BA20 – –
– – – – – –
– – – – – –
– – 8PQ6001-1BA02 8PQ2025-8BA18 8PQ6001-1BA02 8PQ2030-8BA15
– – 8PQ6001-1BA02 8PQ2025-8BA18 – –
– – – – – –
– – – – – –
– – 8PQ6001-1BA02 8PQ2025-8BA18 8PQ6001-1BA02 8PQ2030-8BA15
– – 8PQ6001-1BA02 8PQ2025-8BA18 – –
– – – – – –
8PQ6000-8BA11 8PQ2020-6BA40 8PQ6000-8BA08 8PQ2020-6BA38 8PQ6000-8BA08 8PQ2030-6BA26
8PQ6000-8BA11 8PQ2020-6BA40 8PQ6000-8BA08 8PQ2020-6BA38 – –
8PQ6000-8BA10 8PQ2020-8BA21 8PQ6000-8BA10 8PQ2020-8BA21 8PQ6000-8BA10 8PQ2030-8BA13
8PQ6000-8BA10 8PQ2020-8BA21 8PQ6000-8BA10 8PQ2020-8BA21 – –
8PQ6000-8BA11 8PQ2020-6BA40 8PQ6000-8BA08 8PQ2020-6BA38 8PQ6000-8BA08 8PQ2030-6BA26
8PQ6000-8BA11 8PQ2020-6BA40 8PQ6000-8BA08 8PQ2020-6BA38 – –
8PQ6000-8BA10 8PQ2020-8BA21 8PQ6000-8BA10 8PQ2020-8BA21 8PQ6000-8BA10 8PQ2030-8BA13
8PQ6000-8BA10 8PQ2020-8BA21 8PQ6000-8BA10 8PQ2020-8BA21 – –
8PQ6000-8BA11 8PQ2020-6BA40 8PQ6000-8BA08 8PQ2020-6BA38 8PQ6000-8BA08 8PQ2030-6BA26
8PQ6000-8BA11 8PQ2020-6BA40 8PQ6000-8BA08 8PQ2020-6BA38 – –
8PQ6000-8BA10 8PQ2020-8BA21 8PQ6000-8BA10 8PQ2020-8BA21 8PQ6000-8BA10 8PQ2030-8BA13
8PQ6000-8BA10 8PQ2020-8BA21 8PQ6000-8BA10 8PQ2020-8BA21 – –
– – – – – –
–
8PQ6000-8BA27
–
8PQ2025-8BA14
–
8PQ6001-1BA02
–
8PQ2025-8BA18
–
8PQ6001-1BA02
–
8PQ2035-8BA15
15
8PQ6000-8BA27 8PQ2025-8BA14 8PQ6001-1BA02 8PQ2025-8BA18 – –
– – – – – –
– – – – – –
8PQ6000-8BA27 8PQ2025-8BA14 8PQ6001-1BA02 8PQ2025-8BA18 8PQ6001-1BA02 8PQ2035-8BA15
8PQ6000-8BA27 8PQ2025-8BA14 8PQ6001-1BA02 8PQ2025-8BA18 – –
– – – – – –
– – – – – –
– – – – 8PQ6001-4BA25 8PQ2045-8BA24
1)
For applications >415 V, front mounted rotary operating mechanism or motorized operating mechanism required for compliance with creepage distances and clearances.
2)
Guide frame with direct operating mechanism only
Section expansion
3VA molded case circuit breakers, 3-pole
1 Festeinbau ➊ Fixed-mounted version
2 Festeinbau mit RCD
3 Stecktechnik
1
Type In Width Operating mechanism Device holders Covers
Direct Rotary Motorized
3VA10 100 A 600 mm ■ ■ – 8PQ6000-8BA33 8PQ2035-6BA26
2 800 mm ■ ■ – 8PQ6000-8BA47 8PQ2035-8BA16
3VA11 160 A 600 mm ■ ■ – 8PQ6000-8BA33 8PQ2035-6BA26
– – ■ 8PQ6000-8BA33 8PQ2035-6BA26
3 800 mm ■ ■ – 8PQ6000-8BA47 8PQ2035-8BA16
– – ■ 8PQ6000-8BA47 8PQ2035-8BA16
3VA12 250 A 600 mm ■ ■ – 8PQ6000-8BA35 8PQ2040-6BA26
– – ■ 8PQ6000-8BA35 8PQ2040-6BA26
I201_20284
– – – –
– – – –
8PQ6000-8BA33 8PQ2045-6BA08 8PQ6000-8BA33 8PQ2035-6BA26
8PQ6000-8BA33 8PQ2045-6BA08 8PQ6000-8BA33 8PQ2035-6BA26
8PQ6000-8BA47 8PQ2045-8BA08 8PQ6000-8BA47 8PQ2035-8BA16
8PQ6000-8BA47 8PQ2045-8BA08 8PQ6000-8BA47 8PQ2035-8BA16
8PQ6000-8BA35 8PQ2050-6BA10 8PQ6000-8BA36 8PQ2040-6BA26
8PQ6000-8BA35 8PQ2050-6BA10 8PQ6000-8BA36 8PQ2040-6BA26
8PQ6000-8BA43 8PQ2050-8BA12 8PQ6000-8BA44 8PQ2040-8BA23
8PQ6000-8BA43 8PQ2050-8BA12 8PQ6000-8BA44 8PQ2040-8BA23
– – 8PQ6000-8BA56 8PQ2055-6BA22
– – 8PQ6000-8BA56 8PQ2055-6BA22
– – 8PQ6000-8BA60 8PQ2055-8BA15
– – 8PQ6000-8BA60 8PQ2055-8BA15
– – 8PQ6000-8BA56 8PQ2055-6BA22
– – 8PQ6000-8BA56 8PQ2055-6BA22
– – 8PQ6000-8BA60 8PQ2055-8BA15
– – 8PQ6000-8BA60 8PQ2055-8BA15
8PQ6000-8BA37 8PQ2055-6BA20 8PQ6000-8BA38 8PQ2045-6BA11
8PQ6000-8BA37 8PQ2055-6BA21 8PQ6000-8BA38 8PQ2045-6BA13
8PQ6000-8BA50 8PQ2055-8BA11 8PQ6000-8BA51 8PQ2045-8BA11
8PQ6000-8BA50 8PQ2055-8BA13 8PQ6000-8BA51 8PQ2045-8BA15
8PQ6000-8BA37 8PQ2055-6BA20 8PQ6000-8BA38 8PQ2045-6BA11
8PQ6000-8BA37 8PQ2055-6BA21 8PQ6000-8BA38 8PQ2045-6BA13
8PQ6000-8BA50 8PQ2055-8BA11 8PQ6000-8BA51 8PQ2045-8BA11
8PQ6000-8BA50 8PQ2055-8BA13 8PQ6000-8BA51 8PQ2045-8BA15
8PQ6000-8BA37 8PQ2055-6BA20 8PQ6000-8BA38 8PQ2045-6BA11
8PQ6000-8BA37 8PQ2055-6BA21 8PQ6000-8BA38 8PQ2045-6BA13
8PQ6000-8BA50 8PQ2055-8BA11 8PQ6000-8BA51 8PQ2045-8BA11
8PQ6000-8BA50 8PQ2055-8BA13 8PQ6000-8BA51 8PQ2045-8BA15
8PQ6000-8BA55 8PQ2060-6BA25 8PQ6000-8BA56 8PQ2045-6BA12
8PQ6000-8BA55 8PQ2060-6BA25 8PQ6000-8BA56 8PQ2045-6BA12
8PQ6000-8BA58 8PQ2060-8BA07 8PQ6000-8BA60 8PQ2045-8BA13 15
8PQ6000-8BA58 8PQ2060-8BA07 8PQ6000-8BA60 8PQ2045-8BA13
8PQ6000-8BA55 8PQ2060-6BA25 8PQ6000-8BA56 8PQ2045-6BA12
8PQ6000-8BA55 8PQ2060-6BA25 8PQ6000-8BA56 8PQ2045-6BA12
8PQ6000-8BA58 8PQ2060-8BA07 8PQ6000-8BA60 8PQ2045-8BA13
8PQ6000-8BA58 8PQ2060-8BA07 8PQ6000-8BA60 8PQ2045-8BA13
Section expansion
3VA molded case circuit breakers, 4-pole
1 Festeinbau ➊ Fixed-mounted version
2 Festeinbau mit RCD
3 Stecktechnik
1
Type In Width Operating mechanism Device holders Covers
Direct Rotary Motorized
3VA10 100 A 600 mm ■ ■ – 8PQ6000-8BA34 8PQ2035-6BA27
2 800 mm ■ ■ – 8PQ6000-8BA48 8PQ2035-8BA17
3VA11 160 A 600 mm ■ ■ – 8PQ6000-8BA34 8PQ2035-6BA27
– – ■ 8PQ6000-8BA34 8PQ2035-6BA27
3 800 mm ■ ■ – 8PQ6000-8BA48 8PQ2035-8BA17
– – ■ 8PQ6000-8BA48 8PQ2035-8BA17
3VA12 250 A 600 mm ■ ■ – 8PQ6000-8BA35 8PQ2040-6BA26
– – ■ 8PQ6000-8BA35 8PQ2040-6BA26
I201_20284
– – – –
– – – –
8PQ6000-8BA34 8PQ2045-6BA10 8PQ6000-8BA34 8PQ2035-6BA27
8PQ6000-8BA34 8PQ2045-6BA10 8PQ6000-8BA34 8PQ2035-6BA27
8PQ6000-8BA48 8PQ2045-8BA10 8PQ6000-8BA48 8PQ2035-8BA17
8PQ6000-8BA48 8PQ2045-8BA10 8PQ6000-8BA48 8PQ2035-8BA17
8PQ6000-8BA35 8PQ2050-6BA10 8PQ6000-8BA36 8PQ2040-6BA26
8PQ6000-8BA35 8PQ2050-6BA10 8PQ6000-8BA36 8PQ2040-6BA26
8PQ6000-8BA45 8PQ2050-8BA13 8PQ6000-8BA46 8PQ2040-8BA24
8PQ6000-8BA45 8PQ2050-8BA13 8PQ6000-8BA46 8PQ2040-8BA24
– – 8PQ6000-8BA66 8PQ2055-6BA23
– – 8PQ6000-8BA66 8PQ2055-6BA23
– – 8PQ6000-8BA63 8PQ2055-8BA16
– – 8PQ6000-8BA63 8PQ2055-8BA16
– – 8PQ6000-8BA66 8PQ2055-6BA23
– – 8PQ6000-8BA66 8PQ2055-6BA23
– – 8PQ6000-8BA63 8PQ2055-8BA16
– – 8PQ6000-8BA63 8PQ2055-8BA16
8PQ6000-8BA37 8PQ2055-6BA20 8PQ6000-8BA38 8PQ2045-6BA11
8PQ6000-8BA37 8PQ2055-6BA21 8PQ6000-8BA38 8PQ2045-6BA13
8PQ6000-8BA52 8PQ2055-8BA12 8PQ6000-8BA53 8PQ2045-8BA12
8PQ6000-8BA52 8PQ2055-8BA14 8PQ6000-8BA53 8PQ2045-8BA16
8PQ6000-8BA37 8PQ2055-6BA20 8PQ6000-8BA38 8PQ2045-6BA11
8PQ6000-8BA37 8PQ2055-6BA21 8PQ6000-8BA38 8PQ2045-6BA13
8PQ6000-8BA52 8PQ2055-8BA12 8PQ6000-8BA53 8PQ2045-8BA12
8PQ6000-8BA52 8PQ2055-8BA14 8PQ6000-8BA53 8PQ2045-8BA16
8PQ6000-8BA37 8PQ2055-6BA20 8PQ6000-8BA38 8PQ2045-6BA11
8PQ6000-8BA37 8PQ2055-6BA21 8PQ6000-8BA38 8PQ2045-6BA13
8PQ6000-8BA52 8PQ2055-8BA12 8PQ6000-8BA53 8PQ2045-8BA12
8PQ6000-8BA52 8PQ2055-8BA14 8PQ6000-8BA53 8PQ2045-8BA16
8PQ6000-8BA65 8PQ2060-6BA26 8PQ6000-8BA66 8PQ2045-6BA14
8PQ6000-8BA65 8PQ2060-6BA26 8PQ6000-8BA66 8PQ2045-6BA14
8PQ6000-8BA62 8PQ2060-8BA08 8PQ6000-8BA63 8PQ2045-8BA14 15
8PQ6000-8BA62 8PQ2060-8BA08 8PQ6000-8BA63 8PQ2045-8BA14
8PQ6000-8BA65 8PQ2060-6BA26 8PQ6000-8BA66 8PQ2045-6BA14
8PQ6000-8BA65 8PQ2060-6BA26 8PQ6000-8BA66 8PQ2045-6BA14
8PQ6000-8BA62 8PQ2060-8BA08 8PQ6000-8BA63 8PQ2045-8BA14
8PQ6000-8BA62 8PQ2060-8BA08 8PQ6000-8BA63 8PQ2045-8BA14
Section expansion
3VA molded case circuit breakers, compartment door
➌ Plug-in version
– –
– –
8PQ6000-8BA01 8PQ2015-6BA31
8PQ6000-8BA02 8PQ2015-8BA12
8PQ6000-8BA04 8PQ2015-6BA34
8PQ6000-8BA07 8PQ2020-8BA22
– –
8PQ6001-1BA02 8PQ2025-8BA23
– –
8PQ6001-1BA02 8PQ2025-8BA23
– –
8PQ6000-8BA08 8PQ2020-6BA44
8PQ6000-8BA10 8PQ2020-8BA23
8PQ6000-8BA08 8PQ2020-6BA44
8PQ6000-8BA10 8PQ2020-8BA23
8PQ6000-8BA08 8PQ2020-6BA44
8PQ6000-8BA10 8PQ2020-8BA23
– –
8PQ6001-1BA02 8PQ2025-8BA23
– –
8PQ6001-1BA02 8PQ2025-8BA23
– –
– –
– –
➌ Plug-in version
– –
– –
8PQ6000-8BA01 8PQ2015-6BA31
8PQ6000-8BA02 8PQ2015-8BA12
8PQ6000-8BA06 8PQ2020-6BA42
8PQ6000-8BA07 8PQ2020-8BA22 15
– – Accessories
8PQ6001-1BA02 8PQ2025-8BA23 Compartment ID strip for plug-in plates, H = 17 mm
– – Width Scope of supply Article No.
8PQ6001-1BA02 8PQ2025-8BA23 600 mm 6 units 8PQ5000-3BA43
– – 800 mm 6 units 8PQ5000-3BA46
8PQ6000-8BA08 8PQ2020-6BA44
8PQ6000-8BA10 8PQ2020-8BA23
8PQ6000-8BA08 8PQ2020-6BA44
8PQ6000-8BA10 8PQ2020-8BA23
8PQ6000-8BA08 8PQ2020-6BA44
8PQ6000-8BA10 8PQ2020-8BA23
– –
8PQ6001-1BA02 8PQ2025-8BA23
– –
8PQ6001-1BA02 8PQ2025-8BA23
– –
– –
– –
Section expansion
3VA molded case circuit breakers, 8US multiple feeders new
6 1 Geräteträger
2 Blende
3 Sammelschienenhalter
3 5 4 4. Pol
5 Endabdeckung
6 8US Adapter
I201_20294
1 4
3-pole
4-pole
15
15
Section expansion
3VA molded case circuit breakers, DIN-rail mounting
3-pole
1 Hutschienenmontage
4-pole
Accessories
Cable duct fastening
Version Article No.
Mounting brackets 8PQ6000-0BA16
Blanking strips
Types Article No.
Length 1 m 8GK9910-0KK01
15
➊ DIN-rail mounting
8PQ6000-3BA36 8PQ2035-6BA28
8PQ6000-3BA37 8PQ2035-8BA18
8PQ6000-3BA36 8PQ2035-6BA28
8PQ6000-3BA37 8PQ2035-8BA18
➊ DIN-rail mounting
8PQ6000-3BA36 8PQ2035-6BA28
8PQ6000-3BA37 8PQ2035-8BA18
8PQ6000-3BA36 8PQ2035-6BA28
8PQ6000-3BA37 8PQ2035-8BA18
15
Section expansion
3VA molded case circuit breakers, internal separation – front connection
1 3-pole,
Cable width
connection 600 mm ➊ Cable connection
2 Separation, horizontal
3 Plug-in rail
4 Separation, rear
5 Increase in module height
4
1
3 Type In Height Operating mechanism
2
Direct Rotary Motorized
3VA10 100 A 150 mm Fixed-mounted ■ ■ – 8PQ5000-2BA28 + 8PQ5000-0BA05
3VA11 160 A 150 mm Fixed-mounted ■ ■ ■ 8PQ5000-2BA28 + 8PQ5000-0BA05
Plug-in ■ ■ ■ 8PQ5000-2BA28 + 8PQ5000-0BA05
3VA12 250 A 150 mm Fixed-mounted ■ ■ 8PQ6000-8BA12
– – ■ 8PQ6000-8BA13
I201_19489a
5
Plug-in ■ ■ – 8PQ6000-8BA13
– – ■ 8PQ6000-8BA12
250 mm Withdrawable ■ – ■ 8PQ6000-8BA12
3VA13 400 A 200 mm Fixed-mounted ■ ■ ■ 8PQ6000-8BA20
3VA14 630 A 200 mm Fixed-mounted ■ ■ ■ 8PQ6000-8BA20
3VA20 100 A 200 mm Fixed-mounted ■ ■ ■ 8PQ5000-2BA30 + 8PQ5000-0BA05
Plug-in ■ ■ ■ 8PQ5000-2BA30 + 8PQ5000-0BA05
250 mm Withdrawable ■ – ■ 8PQ5000-2BA30
3VA21 100 A 200 mm Fixed-mounted ■ ■ ■ 8PQ5000-2BA30 + 8PQ5000-0BA05
Plug-in ■ ■ ■ 8PQ5000-2BA30 + 8PQ5000-0BA05
250 mm Withdrawable ■ – ■ 8PQ5000-2BA30 + 8PQ5000-0BA05
3VA22 250 A 200 mm Fixed-mounted ■ ■ – 8PQ6000-8BA16
– – ■ 8PQ6000-8BA17
Plug-in ■ ■ – 8PQ6000-8BA17
– – ■ 8PQ6000-8BA16
250 mm Withdrawable ■ – ■ 8PQ6000-8BA16
3VA23 400 A 200 mm Fixed-mounted ■ ■ – 8PQ6000-8BA20
– – ■ 8PQ6000-8BA18
3VA24 630 A 200 mm Fixed-mounted ■ ■ ■ 8PQ6000-8BA20
– – – 8PQ6000-8BA18
15
15
Section expansion
3VA molded case circuit breakers, internal separation – front connection
1 3-pole,
Cable width
connection 800 mm ➊ Cable connection
2 Separation, horizontal
3 Plug-in rail
4 Separation, rear
5 Increase in module height
4
1 Type In Height Operating mechanism
3
2 Direct Rotary Motorized
3VA10 100 A 150 mm Fixed-mounted ■ ■ – 8PQ5000-2BA28 + 8PQ5000-0BA05
3VA11 160 A 150 mm Fixed-mounted ■ ■ ■ 8PQ5000-2BA28 + 8PQ5000-0BA05
Plug-in ■ ■ ■ 8PQ5000-2BA28 + 8PQ5000-0BA05
3VA12 250 A 200 mm Fixed-mounted ■ ■ ■ 8PQ5000-2BA30 + 8PQ5000-0BA05
Plug-in ■ ■ ■ 8PQ5000-2BA30 + 8PQ5000-0BA05
250 mm Withdrawable ■ – ■ 8PQ6000-8BA14
I201_19489a
5
3VA13 400 A 250 mm Fixed-mounted ■ ■ – 8PQ6000-8BA22
– – ■ 8PQ6000-8BA21
Plug-in ■ ■ ■ 8PQ6000-8BA21
300 mm Withdrawable ■ – – 8PQ6000-8BA22
3VA14 630 A 250 mm Fixed-mounted ■ ■ – 8PQ6000-8BA22
– – ■ 8PQ6000-8BA21
Plug-in ■ ■ ■ 8PQ6000-8BA21
300 mm Withdrawable ■ – – 8PQ6000-8BA22
3VA20 250 A 200 mm Fixed-mounted ■ ■ ■ 8PQ5000-2BA30 + 8PQ5000-0BA05
Plug-in ■ ■ ■ 8PQ5000-2BA30 + 8PQ5000-0BA05
250 mm Withdrawable ■ – ■ 8PQ5000-2BA30 + 8PQ5000-0BA05
3VA21 250 A 200 mm Fixed-mounted ■ ■ ■ 8PQ5000-2BA30 + 8PQ5000-0BA05
Plug-in ■ ■ ■ 8PQ5000-2BA30 + 8PQ5000-0BA05
250 mm Withdrawable ■ – ■ 8PQ5000-2BA30 + 8PQ5000-0BA05
3VA22 250 A 200 mm Fixed-mounted ■ ■ – 8PQ6000-8BA16
– – ■ 8PQ6000-8BA17
Plug-in ■ ■ ■ 8PQ6000-8BA17
250 mm Withdrawable ■ – ■ 8PQ6000-8BA16
3VA23 400 A 250 mm Fixed-mounted ■ ■ – 8PQ6000-8BA22
– – ■ 8PQ6000-8BA21
Plug-in ■ ■ ■ 8PQ6000-8BA21
300 mm Withdrawable ■ – – 8PQ6000-8BA22
3VA24 630 A 250 mm Fixed-mounted ■ ■ – 8PQ6000-8BA22
– – ■ 8PQ6000-8BA21
15 Plug-in ■ ■ ■ 8PQ6000-8BA21
300 mm Withdrawable ■ – – 8PQ6000-8BA22
Section expansion
3VA molded case circuit breakers, internal separation – front connection
1 4-pole,
Cable width
connection 600 mm ➊ Cable connection
2 Separation, horizontal
3 Plug-in rail
4 Separation, rear
5 Increase in module height
4
1 Type In Height Operating mechanism Terminals
3
2
Direct Rotary Motorized
3VA10 100 A 150 mm Fixed-mounted ■ ■ – 8PQ5000-2BA28 + 8PQ5000-0BA05
3VA11 160 A 150 mm Fixed-mounted ■ ■ ■ 8PQ5000-2BA28 + 8PQ5000-0BA05
Plug-in ■ ■ ■ 8PQ5000-2BA28 + 8PQ5000-0BA05
3VA12 250 A 200 mm Fixed-mounted ■ ■ – 8PQ6000-8BA14
– – ■ 8PQ6000-8BA15
I201_19489a
5
Plug-in ■ ■ – 8PQ6000-8BA15
– – ■ 8PQ6000-8BA14
300 mm Withdrawable ■ – ■ 8PQ6000-8BA14
3VA13 400 A 250 mm Fixed-mounted ■ ■ – 8PQ6000-8BA22
– – ■ 8PQ6000-8BA21
3VA14 630 A 250 mm Fixed-mounted ■ ■ – 8PQ6000-8BA22
– – ■ 8PQ6000-8BA21
3VA20 250 A 200 mm Fixed-mounted ■ ■ ■ 8PQ5000-2BA30 + 8PQ5000-0BA05
Plug-in ■ ■ – 8PQ5000-2BA30 + 8PQ5000-0BA05
– – ■ 8PQ5000-2BA30 + 8PQ5000-0BA05
300 mm Withdrawable ■ – ■ 8PQ5000-2BA30 + 8PQ5000-0BA05
3VA21 250 A 200 mm Fixed-mounted ■ ■ ■ 8PQ5000-2BA30 + 8PQ5000-0BA05
Plug-in ■ ■ – 8PQ5000-2BA30 + 8PQ5000-0BA05
– – ■ 8PQ5000-2BA30 + 8PQ5000-0BA05
300 mm Withdrawable ■ – ■ 8PQ5000-2BA30 + 8PQ5000-0BA05
3VA22 250 A 200 mm Fixed-mounted ■ ■ – 8PQ6000-8BA16
– – ■ 8PQ6000-8BA17
Plug-in ■ ■ – 8PQ6000-8BA17
– – ■ 8PQ6000-8BA17
300 mm Withdrawable ■ – ■ 8PQ6000-8BA17
3VA23 400 A 250 mm Fixed-mounted ■ ■ – 8PQ6000-8BA22
– – ■ 8PQ6000-8BA21
Plug-in ■ ■ ■ 8PQ6000-8BA21
3VA24 630 A 250 mm Fixed-mounted ■ ■ – 8PQ6000-8BA22
15 – – ■ 8PQ6000-8BA21
Section expansion
3VA molded case circuit breakers, internal separation – front connection
1 4-pole,
Cable width
connection 800 mm ➊ Cable connection
2 Separation, horizontal
3 Plug-in rail
4 Separation, rear
5 Increase in module height
4
1 Type In Height Operating mechanism Terminals
3
2
Direct Rotary Motorized
3VA10 100 A 150 mm Fixed-mounted ■ ■ – 8PQ5000-2BA28 + 8PQ5000-0BA05
3VA11 160 A 150 mm Fixed-mounted ■ ■ ■ 8PQ5000-2BA28 + 8PQ5000-0BA05
Plug-in ■ ■ ■ 8PQ5000-2BA28 + 8PQ5000-0BA05
3VA12 250 A 200 mm Fixed-mounted ■ ■ – 8PQ6000-8BA14
– – ■ 8PQ6000-8BA15
I201_19489a
5
Plug-in ■ ■ – 8PQ6000-8BA15
– – ■ 8PQ6000-8BA14
300 mm Withdrawable ■ – ■ 8PQ6000-8BA14
3VA13 400 A 250 mm Fixed-mounted ■ ■ – 8PQ6000-8BA22
– – ■ 8PQ6000-8BA21
Plug-in ■ ■ ■ 8PQ6000-8BA21
300 mm Withdrawable ■ – – 8PQ6000-8BA22
3VA14 630 A 250 mm Fixed-mounted ■ ■ – 8PQ6000-8BA22
– – ■ 8PQ6000-8BA21
Plug-in ■ ■ ■ 8PQ6000-8BA21
Withdrawable ■ – – 8PQ6000-8BA22
3VA20 250 A 200 mm Fixed-mounted ■ ■ ■ 8PQ5000-2BA30 + 8PQ5000-0BA05
Plug-in ■ ■ ■ 8PQ5000-2BA30 + 8PQ5000-0BA05
300 mm Withdrawable ■ – ■ 8PQ5000-2BA30 + 8PQ5000-0BA05
3VA21 250 A 200 mm Fixed-mounted ■ ■ ■ 8PQ5000-2BA30 + 8PQ5000-0BA05
Plug-in ■ ■ ■ 8PQ5000-2BA30 + 8PQ5000-0BA05
300 mm Withdrawable ■ – ■ 8PQ5000-2BA30 + 8PQ5000-0BA05
3VA22 250 A 200 mm Fixed-mounted ■ ■ – 8PQ6000-8BA16
– – ■ 8PQ6000-8BA17
Plug-in ■ ■ 8PQ6000-8BA17
– – ■ 8PQ6000-8BA16
300 mm Withdrawable ■ – ■ 8PQ6000-8BA16
3VA23 400 A 250 mm Fixed-mounted ■ ■ – 8PQ6000-8BA22
– – ■ 8PQ6000-8BA21
Section expansion
3VA molded case circuit breakers, internal separation – rear connection
Front of cubicle Front of cubicle
1 Cable connection
2 Separation, horizontal
3 Plug-in rail
4 Separation, rear
5 Increase in module height
4 7
3 9
1
2 5
6
8
I201_18607a
I201_18380a
I201_19489a
3-pole, width 600 mm 4 Vertical busbar connection ➊ Lateral ➋ Horizontal ➌ Increase in module height
5 Segment cover
6 Support plate
➍ Vertical busbar ➎ Segment covers ➏ Support plates ➐ Connection ➑ Cable entries ➎ Plug-in rails
connection compartments
1600 mm 1800 mm
Busbar system
Top Rear or without
8PQ5000-3BA52 8PQ5000-3BA63 8PQ5000-4BA73 8PQ6000-5BA13 8PQ5000-4BA80 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA52 8PQ5000-3BA63 8PQ5000-4BA73 8PQ6000-5BA13 8PQ5000-4BA80 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA52 8PQ5000-3BA63 8PQ5000-4BA73 8PQ6000-5BA13 8PQ5000-4BA80 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA52 8PQ5000-3BA63 8PQ5000-4BA73 8PQ6000-5BA15 8PQ5000-3BA71 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA52 8PQ5000-3BA63 8PQ5000-4BA73 8PQ6000-5BA15 8PQ5000-3BA71 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA54 8PQ5000-3BA63 8PQ5000-4BA73 8PQ6000-5BA15 8PQ5000-3BA71 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA53 8PQ5000-3BA63 8PQ5000-4BA74 8PQ6000-5BA18 8PQ5000-3BA73 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA53 8PQ5000-3BA63 8PQ5000-4BA74 8PQ6000-5BA18 8PQ5000-3BA73 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA53 8PQ5000-3BA63 8PQ5000-4BA74 8PQ6000-5BA14 8PQ5000-3BA72 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA53 8PQ5000-3BA63 8PQ5000-4BA74 8PQ6000-5BA14 8PQ5000-3BA72 8PQ3000-0BA82 8PQ3000-0BA83 15
8PQ5000-3BA54 8PQ5000-3BA63 8PQ5000-4BA74 8PQ6000-5BA14 8PQ5000-3BA72 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA53 8PQ5000-3BA63 8PQ5000-4BA74 8PQ6000-5BA14 8PQ5000-3BA72 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA53 8PQ5000-3BA63 8PQ5000-4BA74 8PQ6000-5BA14 8PQ5000-3BA72 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA54 8PQ5000-3BA63 8PQ5000-4BA74 8PQ6000-5BA14 8PQ5000-3BA72 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA53 8PQ5000-3BA63 8PQ5000-4BA74 8PQ6000-8BA30 8PQ5000-3BA72 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA53 8PQ5000-3BA63 8PQ5000-4BA74 8PQ6000-8BA30 8PQ5000-3BA72 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA54 8PQ5000-3BA63 8PQ5000-4BA74 8PQ6000-8BA30 8PQ5000-3BA72 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA53 8PQ5000-3BA63 8PQ5000-4BA74 8PQ6000-5BA18 8PQ5000-3BA73 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA53 8PQ5000-3BA63 8PQ5000-4BA74 8PQ6000-5BA18 8PQ5000-3BA73 8PQ3000-0BA82 8PQ3000-0BA83
Section expansion
3VA molded case circuit breakers, internal separation – rear connection
Front of cubicle Front of cubicle
1 Cable connection
2 Separation, horizontal
3 Plug-in rail
4 Separation, rear
5 Increase in module height
4 7
3 9
1
2 5
6
8
I201_18607a
I201_18380a
I201_19489a
4-pole, width 600 mm 4 Vertical busbar connection ➊ Lateral ➋ Horizontal ➌ Increase in module height
5 Segment cover
6 Support plate
➍ Vertical busbar ➎ Segment covers ➏ Support plates ➐ Connection ➑ Cable entries ➎ Plug-in rails
connection compartments
1600 mm 1800 mm
Busbar system
Top Rear or without
8PQ5000-3BA52 8PQ5000-3BA63 8PQ5000-4BA73 8PQ6000-5BA13 8PQ5000-4BA80 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA52 8PQ5000-3BA63 8PQ5000-4BA73 8PQ6000-5BA13 8PQ5000-4BA80 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA52 8PQ5000-3BA63 8PQ5000-4BA73 8PQ6000-5BA13 8PQ5000-4BA80 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA53 8PQ5000-3BA63 8PQ5000-4BA74 8PQ6000-5BA17 8PQ5000-3BA72 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA53 8PQ5000-3BA63 8PQ5000-4BA74 8PQ6000-5BA17 8PQ5000-3BA72 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA55 8PQ5000-3BA63 8PQ5000-4BA74 8PQ6000-5BA17 8PQ5000-3BA72 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA54 8PQ5000-3BA63 8PQ5000-4BA75 8PQ6000-5BA20 8PQ5000-3BA74 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA54 8PQ5000-3BA63 8PQ5000-4BA75 8PQ6000-5BA20 8PQ5000-3BA74 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA53 8PQ5000-3BA63 8PQ5000-4BA74 8PQ6000-5BA14 8PQ5000-3BA72 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA53 8PQ5000-3BA63 8PQ5000-4BA74 8PQ6000-5BA14 8PQ5000-3BA72 8PQ3000-0BA82 8PQ3000-0BA83 15
8PQ5000-3BA55 8PQ5000-3BA63 8PQ5000-4BA74 8PQ6000-5BA14 8PQ5000-3BA72 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA53 8PQ5000-3BA63 8PQ5000-4BA74 8PQ6000-5BA14 8PQ5000-3BA72 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA53 8PQ5000-3BA63 8PQ5000-4BA74 8PQ6000-5BA14 8PQ5000-3BA72 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA55 8PQ5000-3BA63 8PQ5000-4BA74 8PQ6000-5BA14 8PQ5000-3BA72 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA53 8PQ5000-3BA63 8PQ5000-4BA74 8PQ6000-5BA17 8PQ5000-3BA72 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA53 8PQ5000-3BA63 8PQ5000-4BA74 8PQ6000-5BA17 8PQ5000-3BA72 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA55 8PQ5000-3BA63 8PQ5000-4BA74 8PQ6000-5BA17 8PQ5000-3BA72 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA54 8PQ5000-3BA63 8PQ5000-4BA75 8PQ6000-5BA20 8PQ5000-3BA74 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA54 8PQ5000-3BA63 8PQ5000-4BA75 8PQ6000-5BA20 8PQ5000-3BA74 8PQ3000-0BA82 8PQ3000-0BA83
Section expansion
3VA molded case circuit breakers, internal separation – rear connection
Front of cubicle
1 Cable connection
2 Separation, horizontal
3 Plug-in rail
4 Separation, rear
5 Increase in module height
4
3
1
2 5
6
I201_18380a
I201_19489a
➌ Increase in module height ➍ Vertical busbar Distribution ➎ Segment covers ➏ Support plates
connection busbar
Section expansion
3VA molded case circuit breakers, internal separation – rear connection
Front of cubicle
7
9
8
I201_18607a
Busbar system
Top Rear or without
8PQ5000-4BA80 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-4BA80 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-4BA80 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA72 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA72 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA72 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA74 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA74 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA74 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA74 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA74 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA74 8PQ3000-0BA82 8PQ3000-0BA83 15
– 8PQ5000-5BA82 + 8PQ9400-0BA71 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA72 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA72 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA72 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA72 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA72 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA72 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA72 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA72 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA72 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA74 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA74 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA74 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA74 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA74 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA74 8PQ3000-0BA82 8PQ3000-0BA83
– 8PQ5000-5BA82 + 8PQ9400-0BA71 8PQ3000-0BA82 8PQ3000-0BA83
– 8PQ5000-5BA82 + 8PQ9400-0BA71 8PQ3000-0BA82 8PQ3000-0BA83
– 8PQ5000-5BA83 + 8PQ9400-0BA71 8PQ3000-0BA82 8PQ3000-0BA83
– 8PQ5000-5BA83 + 8PQ9400-0BA71 8PQ3000-0BA82 8PQ3000-0BA83
Section expansion
3VA molded case circuit breakers, internal separation – rear connection
Front of cubicle
1 Cable connection
2 Separation, horizontal
3 Plug-in rail
4 Separation, rear
5 Increase in module height
4
3
1
2 5
6
I201_18380a
I201_19489a
➌ Increase in module height ➍ Vertical busbar Distribution ➎ Segment covers ➏ Support plates
connection busbar
Section expansion
3VA molded case circuit breakers, internal separation – rear connection
Front of cubicle
7
9
8
I201_18607a
Busbar system
Top Rear or without
8PQ5000-4BA80 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-4BA80 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-4BA80 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA72 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA72 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA72 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA74 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA74 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA74 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA74 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA74 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA74 8PQ3000-0BA82 8PQ3000-0BA83 15
– 8PQ5000-BA82 + 8PQ9400-0BA71 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA72 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA72 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA72 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA72 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA72 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA72 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA72 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA72 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA72 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA74 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA74 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA74 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA74 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA74 8PQ3000-0BA82 8PQ3000-0BA83
8PQ5000-3BA74 8PQ3000-0BA82 8PQ3000-0BA83
– 8PQ5000-BA82 + 8PQ9400-0BA71 8PQ3000-0BA82 8PQ3000-0BA83
– 8PQ5000-BA82 + 8PQ9400-0BA71 8PQ3000-0BA82 8PQ3000-0BA83
– 8PQ5000-BA83 + 8PQ9400-0BA71 8PQ3000-0BA82 8PQ3000-0BA83
– 8PQ5000-BA83 + 8PQ9400-0BA71 8PQ3000-0BA82 8PQ3000-0BA83
Section expansion
3K switch disconnectors
1
I201_18392a
➊ Horizontal
3-pole 4-pole
Due to the size of its handle, the 3KA715 disconnector can be used only up to 1250 A/35 kA when installed horizontally.
1)
Due to the size of its handle, the 1250 A/50 kA 3KA715 disconnector requires an additional 200 mm cover.
➋ Vertical
3-pole 4-pole
Section expansion
3NP1 fuse switch disconnectors, 3-pole
1 Festeinbautechnik
waagerecht
2 Festeinbautechnik
senkrecht
3 Feldverschienung
4 Kabelanschluss
11
4
33
1
I201_18394b
15
➋ Vertical
15
Section expansion
3NJ4 fuse switch disconnectors, 3-pole
Accessories
15 Blanking covers
Size Width Article No.
NH00 50 mm 3NJ4912-2AA00
NH1 – NH3 100 mm 3NJ4912-2BA00
Form 3b horizontal
8PQ2080-6BA10 8PQ5000-1BA70 8PQ5000-2BA61 + 8PQ5000-2BA63
8PQ2080-8BA05 8PQ5000-1BA71 8PQ5000-2BA62 + 8PQ5000-2BA63
15
Section expansion
3NJ6 switch disconnectors with fuses, 3 and 4-pole
1 1 Gerüst
5 9
2 Trägerausbau außen
2 4 3 Bodenraumteilung
4 Trägerausbau
5 Kopfraumblende
6 6 Geräteträger 3NJ6
11 7 Unterteilung Verteilschiene
7
10 8 Sockelraumblende
9 Unterteilung Hauptsammelschiene
10 PE Hochführung
11 N/PEN Anbindung
I201_20250
3
8
Device compartment
➊ Frames ➋ Exterior ➌ Bottom plate ➍ Uprights ➎ Head com- ➏ 3NJ6 ➐ Cover
intermediate partition cross- partment device holder Distribution
uprights bars covers busbar
Width Depth
Device compartment 600 mm + cabling compartment 400 mm
1000 mm 400 mm 8PQ1201-4BA02 8PQ3000-1BA43 1× 8PQ3000-1BA38 8PQ3000-0BA65 8PQ2022-6BA01 8PQ3000-1BA48 + 6x 3NJ6916-4EA00
600 mm 8PQ1201-6BA02 8PQ3000-1BA43 1× 8PQ3000-1BA40 8PQ3000-0BA01 8PQ2022-6BA01 8PQ3000-1BA48 + 6x 3NJ6916-4EA00
800 mm 8PQ1201-8BA03 8PQ3000-1BA43 2x 8PQ3000-1BA38 8PQ3000-0BA02 8PQ2022-6BA01 8PQ3000-1BA48 + 6x 3NJ6916-4EA00
800 mm 8PQ1201-8BA03 8PQ3000-1BA43 2× 8PQ3000-1BA38 8PQ3000-0BA02 8PQ2022-6BA01 8PQ3000-1BA48 + 6x 3NJ6916-4EA00
duplex
Accessories
Device compartments
Height Article No.
200 mm 8PQ3000-1BA50
400 mm 8PQ3000-1BA51
Blanking covers
Height Article No.
50 mm 3NJ6900-4CB00
Section expansion
Modular installation devices
1 Einbausatz für Installations-
einbaugeräte
2 Blende Internal covers ➊ Device holders ➋ Covers
15
Width MW Tier spacing Height
600 mm 1× 24 200 mm 200 mm 1 × 8PQ6000-6BA52 8PQ2020-6BA28
800 mm 1× 35 200 mm 200 mm 1 × 8PQ6000-6BA53 8PQ2020-8BA14
Accessories
Cable duct fastening
Version Article No.
Mounting brackets 8PQ6000-0BA16
Blanking strips
Types Article No.
Length 1 m 8GK9910-0KK01
Section expansion
Cable section
➊ PE bars
Version Scope of supply Article No.
Busbar supports 5 units 8PQ4000-2BA23
1 3
➋ N/PEN connection
Version Article No.
Busbar supports and connection terminals 8PQ4000-2BA22
➌ Cable fixtures
Version Scope of supply Article No.
Holders 10 units 8PQ3000-0BA73
Section expansion
Corner sections
RGXWWG
6
W WG
R GX
2
I201_20137
At bottom
➎ Rear panels ➏ Top plates
Section expansion
Mounting plates
1 3 Mounting plate
4 Connecting panel
3
5 Uprights
2
4 1900 mm
1600 mm
5
I202_30327b
I202_30327
700 mm
Width Door Door Inner door struts Inner doors Inner door struts
with double-bit for profile
lock semicylinders
IP40 400 mm 8PQ2197-4BA08 8PQ2197-4BA06 8PQ2197-0BA10 – –
600 mm 8PQ2197-6BA06 8PQ2197-6BA04 8PQ2197-0BA10 8PQ2000-6BA05 2× 8PQ2080-0BA07
800 mm 8PQ2197-8BA06 8PQ2197-8BA04 8PQ2197-0BA10 8PQ2000-8BA05 2× 8PQ2080-0BA07
1000 mm 8PQ2197-1BA06 8PQ2197-1BA07 8PQ2197-0BA10 8PQ2000-1BA01 2× 8PQ2080-0BA07
1000 mm – Double doors 8PQ2197-1BA14 8PQ2197-1BA16 8PQ2197-0BA10 – –
1200 mm – Double doors 8PQ2197-2BA11 8PQ2197-2BA13 8PQ2197-0BA10 – –
IP55 400 mm 8PQ2197-4BA05 8PQ2197-4BA03 8PQ2197-0BA10 – –
600 mm 8PQ2197-6BA03 8PQ2197-6BA01 8PQ2197-0BA10 8PQ2000-6BA05 2× 8PQ2080-0BA07
15 800 mm 8PQ2197-8BA03 8PQ2197-8BA01 8PQ2197-0BA10 8PQ2000-8BA05 2× 8PQ2080-0BA07
1000 mm 8PQ2197-1BA03 8PQ2197-1BA04 8PQ2197-0BA10 8PQ2000-1BA01 2× 8PQ2080-0BA07
1000 mm – Double doors 8PQ2197-1BA13 8PQ2197-1BA15 8PQ2197-0BA10 – –
1200 mm – Double doors 8PQ2197-2BA10 8PQ2197-2BA12 8PQ2197-0BA10 – –
Height Width
400 mm 600 mm 800 mm
150 mm 8PQ3000-2BA60 8PQ3000-2BA62 8PQ3000-2BA64
200 mm 8PQ3000-2BA17 8PQ3000-1BA56 8PQ3000-1BA58
250 mm – 8PQ3000-3BA63 8PQ3000-3BA64
300 mm 8PQ3000-2BA66 8PQ3000-2BA51 8PQ3000-2BA53
400 mm 8PQ3000-2BA18 8PQ3000-1BA61 8PQ3000-1BA63
500 mm new – 8PQ3000-3BA76 8PQ3000-3BA77
550 mm 8PQ3000-3BA65 8PQ3000-3BA07 8PQ3000-3BA08
600 mm 8PQ3000-2BA21 8PQ3000-1BA65 8PQ3000-1BA67
700 mm new – 8PQ3000-3BA78 8PQ3000-3BA80
800 mm 8PQ3000-2BA23 8PQ3000-1BA26 8PQ3000-1BA28
At top
➌ Mounting plates ➎ Uprights ➌ Mounting plates ➎ Uprights
1900 mm 1650 mm
I201_20217
I201_20218
Mounting plates Connecting panels Depth Mounting plates Connecting panels Depth Depth
600 mm, 800 mm 600 mm 800 mm
Internal separation
Quick selection guide
Form 1 Form 2b
No internal separation Separation
+ Main busbar ➀
+ Vertical busbar ➁
1 1
2 2
I202_29900
I202_29901
11 11
22 22 22 22
15
I201_18216
I201_18218
Form 3b Form 4b
Separation Separation
+ Main busbar ➀ + Main busbar ➀
+ Vertical busbar ➁ + Vertical busbar ➁
+ Device compartments (functional units) ➂ + Device compartments (functional units) ➂
+ Connections ➃
1 1
2 2
I202_29903
I202_29902
11 11
22 22 22 22
3 3 4
3 3
4
15
3 3
4
I201_18220
I201_20282
Internal separation
Main busbar at top/at bottom, form 2b
3 3
2 2
I202_29633
1
Position At top
of main busbar
➊ Main busbars
At bottom
Depth
400 mm 600 mm 800 mm
– – –
8PQ3000-3BA14 8PQ3000-3BA23 8PQ3000-3BA32
8PQ3000-3BA15 8PQ3000-3BA24 8PQ3000-3BA33
8PQ3000-3BA16 8PQ3000-3BA25 8PQ3000-3BA34 15
8PQ3000-3BA18 8PQ3000-3BA27 8PQ3000-3BA36
8PQ3000-3BA20 8PQ3000-3BA28 8PQ3000-3BA37
Internal separation
Main busbar at top/at bottom, form 2b
1 Hauptsammelschiene
1
2 Feldsammelschiene
3 Berührungsschutzabdeckung
4 Trennwand Feld-Feld
3 3
2 4 2 4
I201_20286
1
Position At top
of main busbar Without
➋ Vertical busbar
15
Rear Depth
800 mm 400 mm 600 mm 800 mm
8PQ4000-0BA76 8PQ3000-2BA50 8PQ3000-0BA15 8PQ3000-0BA16 2× 8PQ3000-0BA15
8PQ4000-0BA76 8PQ3000-0BA51 8PQ3000-0BA15 8PQ3000-0BA16 2× 8PQ3000-0BA15
15
Internal separation
Main busbar at rear, form 2b
Position At top
of main busbar Center
➊ Main busbar
Position At top
of vertical busbar Center
15 ➋ Vertical busbar
At bottom
Depth Depth
1200 mm 1200 mm duplex 800 mm 1000 mm 1200 mm 1200 mm duplex
8PQ3000-3BA53 8PQ3000-3BA58 8PQ3000-3BA33 8PQ3000-3BA24 8PQ3000-3BA33 8PQ3000-3BA33
8PQ3000-3BA54 8PQ3000-3BA60 8PQ3000-3BA34 8PQ3000-3BA25 8PQ3000-3BA34 8PQ3000-3BA34
At bottom
Barrier supports
15
1 set = 6 units
Internal separation
Modular kits, form 3b
1
2
3
1600 mm
4
I201_18363c
Height Width
1600 mm 1800 mm 600 mm 800 mm
8PQ5000-2BA63 8PQ3000-0BA82 8PQ3000-0BA83 8PQ5000-2BA52 8PQ5000-2BA68
8PQ5000-2BA63 8PQ3000-0BA82 8PQ3000-0BA83 8PQ5000-4BA40 –
8PQ5000-2BA63 8PQ3000-0BA82 8PQ3000-0BA83 8PQ5000-4BA41 8PQ5000-4BA48
8PQ5000-2BA63 8PQ3000-0BA82 8PQ3000-0BA83 8PQ5000-4BA42 8PQ5000-4BA50
8PQ5000-2BA63 8PQ3000-0BA82 8PQ3000-0BA83 8PQ5000-4BA43 –
8PQ5000-2BA63 8PQ3000-0BA82 8PQ3000-0BA83 8PQ5000-4BA44 8PQ5000-4BA51
8PQ5000-2BA63 8PQ3000-0BA82 8PQ3000-0BA83 8PQ5000-4BA45 8PQ5000-4BA52
8PQ5000-2BA63 8PQ3000-0BA82 8PQ3000-0BA83 8PQ5000-4BA46 8PQ5000-4BA53
8PQ5000-2BA63 8PQ3000-0BA82 8PQ3000-0BA83 – –
8PQ5000-2BA63 8PQ3000-0BA82 8PQ3000-0BA83 8PQ5000-4BA47 – 15
8PQ5000-2BA63 8PQ3000-0BA82 8PQ3000-0BA83 – –
8PQ5000-2BA63 8PQ3000-0BA82 8PQ3000-0BA83 – –
8PQ5000-2BA63 8PQ3000-0BA82 8PQ3000-0BA83 – –
8PQ5000-2BA63 8PQ3000-0BA82 8PQ3000-0BA83 – –
Internal separation
Accessories
Connecting terminals
In Busbar Scope of supply Article No.
– – 4 units 8PQ5000-0BA05
Protective bellows
Version Scope of supply Article No.
For connecting terminal 4 units 8PQ9400-0BA71
Cable entries
Version Scope of supply Article No.
Ø cable = 14 … 38 mm 6 units 8PQ9400-0BA33
Ø installation = 46 mm
I201_20207
Ø 46
Other
Version Scope of supply Article No.
Screwdriver insert, Length 200 mm 2 units 8PQ9400-0BA10
Universal mounting brackets 10 units 8PQ9400-0BA01
15
System overview
Distribution boards, assembly kits and accessories
Assembly kits
15
For molded case For switch For fuse switch For modular For front cover
circuit breakers disconnectors disconnectors installation devices with cutout
Note:
You will find a detailed range of accessories with the basic units and in the Accessories section.
Busbars
Accessories
15
Bases Crossbars Partitions Front covers Locking systems
Note:
You will find a detailed range of accessories with the basic units and in the Accessories section.
Unequipped
Accessories distribution boards
Sheet-steel doors
Types Width Cubicle height Cubicle width Article No.
Standard – 1800 mm 300 mm 8GK9515-8KK11
600 mm 8GK9515-8KK21
900 mm 8GK9515-8KK31
2000 mm 300 mm 8GK9515-8KK12
600 mm 8GK9515-8KK22
900 mm 8GK9515-8KK32
For cabling compartment 250 mm 1800 mm 900 mm 8GK9515-8KK41
2000 mm 900 mm 8GK9515-8KK42
Transparent doors
Types Cubicle height Cubicle width Article No.
Standard 1800 mm 300 mm 8GK9505-8KK12
600 mm 8GK9505-8KK21
900 mm 8GK9505-8KK31
2000 mm 300 mm 8GK9505-8KK10
600 mm 8GK9505-8KK22
900 mm 8GK9505-8KK32
15 Giugiaro design 1800 mm 600 mm 8GK9507-8KK21
900 mm 8GK9507-8KK31
2000 mm 600 mm 8GK9507-8KK22
900 mm 8GK9507-8KK32
Double doors
Types Width Cubicle height Cubicle width Article No.
Made of sheet steel 600 + 250 mm 1800 mm 900 mm 8GK9515-8KK21 +
8GK9515-8KK41
2000 mm 900 mm 8GK9515-8KK22 +
8GK9515-8KK42
Unequipped
Accessories distribution boards
Vertical profile bars for cabling compartment/busbars
Cubicle height Cubicle width Article No.
1800 mm 300/600/900 mm 8GK9200-8KK00
2000 mm 300/600/900 mm 8GK9200-8KK01
Side panels
Color Cubicle height Cubicle width Article No.
RAL 7035 (pair) 1800 mm 300/600/900 mm 8GK9200-8KK04
2000 mm 300/600/900 mm 8GK9200-8KK05
Supports
Types Height Article No.
Mounting stays (pair) 1600 mm 8GK6850-0KK02
1800 mm 8GK6850-0KK03
2000 mm 8GK6850-0KK04
Rear universal supports 1800 mm 8GK6850-0KK05 15
2000 mm 8GK6850-0KK06
Crossbars
Types Article No.
Upper crossbar 8GK6850-0KK00
Lateral crossbar 8GK6850-0KK01
Adapter for installation of assembly kits in the cabling compartment, width 250 mm (2 units) 8GK9920-0KK01
Unequipped distri
Accessories Flat pack IP43 bution boards IP55
Sheet-steel doors
Types Cubicle height Cubicle width Article No. Article No.
Standard 400 mm 600 mm 8GK9515-3KK20 –
600 mm 600 mm 8GK9515-4KK20 8GK9515-4KK20
800 mm 600 mm 8GK9515-5KK20 8GK9515-5KK23
1000 mm 600 mm 8GK9515-6KK20 8GK9515-6KK23
900 mm 8GK9515-6KK30 8GK9515-6KK33
1200 mm 600 mm 8GK9515-7KK20 8GK9515-7KK23
900 mm 8GK9515-7KK30 8GK9515-7KK33
For cabling compartment 1000 mm 900 mm 8GK9515-6KK40 8GK9515-6KK43
1200 mm 900 mm 8GK9515-7KK40 8GK9515-7KK33
600 + 300 mm – 8GK9515-7KK43
Transparent doors
Unequipped distri
Accessories Flat pack IP43 bution boards IP55
Double doors
Types Width Cubicle height Cubicle width Article No. Article No.
Made of sheet steel 600 + 250 mm 1) 1000 mm 900 mm 8GK9515-6KK20 + 8GK9515-6KK23 +
8GK9515-6KK40 8GK9515-6KK43
1200 mm 900 mm 8GK9515-7KK20 + 8GK9515-7KK23 +
8GK9515-7KK40 8GK9515-7KK43
Bases
Color Height Cubicle height Cubicle width Article No. Article No.
Blue-green 100 mm 600/1200 mm 600 mm 8GK9906-0KK23 8GK9906-0KK23
1000/1200 mm 900 mm 8GK9906-0KK33 8GK9906-0KK33
Side panels
Color Cubicle height Cubicle width Article No. Article No.
Blue-green 600 mm 600 mm – 8GK9122-4KK01
800 mm 600 mm – 8GK9122-5KK01
1000 mm 600/900 mm – 8GK9122-6KK01
1200 mm 600/900 mm – 8GK9122-7KK01
1)
For distribution boards with a width of 900 mm with double door and vertical profile bar
Height Depth Width Protection class I Protection class I Protection class I Protection class I
Outside Inside Outside Outside Inside
1650 mm 1600 mm 250 mm 350 mm 300 mm 8GK2300-5KL13 8GK2325-5KK13 – –
650 mm 600 mm 8GK2300-5KL23 8GK2325-5KK23 – –
950 mm 900 mm 8GK2300-5KL43 8GK2325-5KK43 – –
1850 mm 1800 mm 250 mm 350 mm 300 mm 8GK2300-6KL13 8GK2325-6KK13 – –
650 mm 600 mm 8GK2300-6KL23 8GK2325-6KK23 8GK2348-7KL00 8GK2348-7KL01
950 mm 900 mm 8GK2300-6KL43 8GK2325-6KK43 – –
2050 mm 2000 mm 250 mm 350 mm 300 mm 8GK2300-7KL13 8GK2325-7KK13 – –
650 mm 600 mm 8GK2300-7KL23 8GK2325-7KK23 – –
950 mm 900 mm 8GK2300-7KL43 8GK2325-7KK43 – –
15
15
15 2000 mm 900 mm
8GK9515-8KK41
8GK9515-8KK22 +
8GK9515-8KK41
8GK9515-8KK22 +
8GK9515-8KK42 8GK9515-8KK42
Transparent door 600 + 250 mm 1600 mm 900 mm 8GK9505-8KK20 + 8GK9505-8KK20 +
+ sheet-steel door 8GK9515-8KK40 8GK9515-8KK40
1800 mm 900 mm 8GK9505-8KK21 + 8GK9505-8KK21 +
8GK9515-8KK41 8GK9515-8KK41
2000 mm 900 mm 8GK9505-8KK22 + 8GK9505-8KK22 +
8GK9515-8KK42 8GK9515-8KK42
Transparent door 600 + 250 mm 1600 mm 900 mm 8GK9507-8KK20 + 8GK9507-8KK20 +
in Giugiaro design 8GK9515-8KK40 8GK9515-8KK40
+ sheet-steel door 1800 mm 900 mm 8GK9507-8KK21 + 8GK9507-8KK21 +
8GK9515-8KK41 8GK9515-8KK41
2000 mm 900 mm 8GK9507-8KK22 + 8GK9507-8KK22 +
8GK9515-8KK42 8GK9515-8KK42
Vertical profile bars for cabling compartment
Cubicle height Cubicle width Article No. Article No.
1600 mm 900 mm 8GK9125-8KK11 8GK9125-8KK11
1800 mm 900 mm 8GK9125-8KK12 8GK9125-8KK12
2000 mm 900 mm 8GK9125-8KK13 8GK9125-8KK13
Unequipped
Accessories Flat pack distribution boards
Front covers for cabling compartment
Height Width Cubicle height Cubicle width Article No. Article No.
800 + 800 mm 250/300 mm 1600 mm 300 mm 8GK9607-5KK10 + 8GK9607-5KK10 +
8GK9607-5KK10 8GK9607-5KK10
900 mm 8GK9606-5KK10 + 8GK9606-5KK10 +
8GK9606-5KK10 8GK9606-5KK10
800 + 1000 mm 250/300 mm 1800 mm 300 mm 8GK9607-5KK10 + 8GK9607-5KK10 +
8GK9607-7KK10 8GK9607-7KK10
900 mm 8GK9606-5KK10 + 8GK9606-5KK10 +
8GK9606-7KK10 8GK9606-7KK10
1000 + 1000 mm 250/300 mm 2000 mm 300 mm 8GK9607-7KK10 + 8GK9607-7KK10 +
8GK9607-7KK10 8GK9607-7KK10
900 mm 8GK9606-7KK10 + 8GK9606-7KK10 +
8GK9606-7KK10 8GK9606-7KK10
Bases
Color Height Cubicle height Cubicle width Article No. Article No.
Blue-green 100 mm 1600/2000 mm 300 mm 8GK9906-0KK13 8GK9906-0KK13
1600/2000 mm 600 mm 8GK9906-0KK23 8GK9906-0KK23
1600/2000 mm 900 mm 8GK9906-0KK33 8GK9906-0KK33
Side panels
Color Cubicle height Cubicle width Article No. Article No.
RAL 7035 (pair) 1600 mm 300/600/900 mm 8GK9120-8KK00 8GK9122-8KK03
1800 mm 300/600/900 mm 8GK9120-8KK01 8GK9122-8KK04
2000 mm 300/600/900 mm 8GK9120-8KK02 8GK9122-8KK05
15
Height Depth Width Tiers Protection class I Protection class I Protection class I Protection class I
Outside Inside Outside Outside Inside (MW = 18 mm)
450 mm 400 mm 140 mm 660 mm 600 mm 48 (2× 24) 8GK2042-0KL21 8GK2042-0KM21 – –
650 mm 600 mm 140 mm 660 mm 600 mm 72 (3× 24) 8GK2042-1KL21 8GK2042-1KM21 – –
800 mm 850 mm 140 mm 660 mm 600 mm 96 (4× 24) 8GK2042-2KL21 8GK2042-2KM21 – –
1050 mm 1000 mm 140 mm 660 mm 600 mm 120 (5× 24) 8GK2042-3KL21 8GK2042-3KM21 – –
1250 mm 1200 mm 140 mm 660 mm 600 mm 144 (6× 24) 8GK2042-4KL21 8GK2042-4KM21 – –
508 mm 400 mm 140 mm 718 mm 600 mm 48 (2× 24) – – 8GK2043-0KL21 8GK2043-0KM21
708 mm 600 mm 140 mm 718 mm 600 mm 72 (3× 24) – – 8GK2043-1KL21 8GK2043-1KM21
908 mm 800 mm 140 mm 718 mm 600 mm 96 (4× 24) – – 8GK2043-2KL21 8GK2043-2KM21
1108 mm 1000 mm 140 mm 718 mm 600 mm 120 (5× 24) – – 8GK2043-3KL21 8GK2043-3KM21
1308 mm 1200 mm 140 mm 718 mm 600 mm 144 (6× 24) – – 8GK2043-4KL21 8GK2043-4KM21
Accessories
Front covers
• With quick-lock screws and integrated grounding connection
Type Height Width Article No.
Closed 50 mm 600 mm 8GK9620-1KK20
100 mm 600 mm 8GK9621-1KK20
150 mm 600 mm 8GK9622-1KK20
200 mm 600 mm 8GK9623-1KK20
400 mm 600 mm 8GK9622-2KK20
600 mm 600 mm 8GK9622-4KK20
800 mm 600 mm 8GK9622-5KK20
For modular installation 150 mm 600 mm 8GK9608-1KK22
devices 200 mm 600 mm 8GK9608-1KK20
300 mm 600 mm 8GK9608-2KK22
400 mm 600 mm 8GK9608-2KK20
15 450 mm 600 mm 8GK9608-3KK22
600 mm 600 mm 8GK9608-4KK20
DIN rails for modular installation devices
Width Article No.
600 mm 8GK9920-0KK11
Grounding bars, PE
Width Article No.
600 mm (20 × 5 mm2) 8GK9920-0KK10
Rotary handles
Version Color Article No.
Plastic Black 8GK9560-0KK04
Lockable Black 8GK9560-0KK13
15
Assembly kits
For 3VA molded case circuit breakers
Horizontal
15
Vertical
Assembly kits
For 3KA7 switch disconnectors
Vertical
1)
In order to use box width 250 mm in the ALPHA 630 UNIVERSAL as a switchgear compartment, the following bars are required:
8GF9655 (height 1000 mm),
8GF9656 (height 1200 mm),
8GF9650 (height 1600 mm),
8GF9658 (height 1800 mm),
8GF9654 (height 2000 mm).
In order to use box width 250 mm in the ALPHA 800 UNIVERSAL as a switchgear compartment, you must order side supports and, for each assembly kit,
a pair of crossbars 8GK9920-0KK01.
2)
In order to use cubicle width 300 mm in the ALPHA 630 UNIVERSAL as a switchgear compartment, you require the following inner supports:
8GK9126-8KK03 (height 1600 mm),
15
8GK9126-8KK04 (height 1800 mm),
8GK9126-8KK05 (height 2000 mm).
In order to use cubicle width 300 mm in the ALPHA 800 UNIVERSAL as a switchgear compartment, you must order the following side supports:
8GK6850-0KK02 (height 1600 mm),
8GK6850-0KK03 (height 1800 mm),
8GK6850-0KK04 (height 2000 mm).
Assembly kits
For modular installation devices
Accessories
DIN rails
Version Width No. of tiers Article No.
For mounting modular devices at 600 mm 1 8GF9670
various depths 900 mm 1 8GF9671
15
Accessories
DIN rails
Version Width No. of tiers Article No.
For mounting modular devices 600 mm 1 8GF9670
at various depths 900 mm 1 8GF9671
15
Busbars
For ALPHA 800/630 UNIVERSAL distribution boards
15
Version
Busbar supports With support plate 8GK9750-0KK02
Without support plate 8PQ4000-1BA12
Supplements If there is no support 8GK9750-0KK02 mounted onto the side of the cabling compartment,
you will need to order an upper crossbar 8GK6850-0KK00.
15
Busbars
Vertical
Busbar cross-section Width Number of Article No. Article No.
poles
15/20/30 × 5 mm 300 mm 4-pole 50 mm 8GF5768 8GF5768
30 × 10 mm 300 mm 4-pole 50 mm 8GF5770 8GF5770
Vertical, at rear
Busbar cross-section Width Number of Article No. Article No.
poles
15/20/30 × 5 mm 600 mm 4-pole 50 mm 8GF5764 8GF5764
900 mm 4-pole 50 mm 8GF5766 8GF5766
Horizontal, at front 1)
Horizontal, at top
Busbar cross-section Number of Article No. Article No.
poles
20/30 × 10 mm 600/900 mm 4-pole 50 mm – 8GK9750-0KK02
– 8PQ4000-1BA12
1)
Can be mounted directly on device holders with a clearance of 525 mm (width 600 mm) and 825 mm (width 900 mm).
15
Accessories
Non-transparent covers
Height Width Article No.
50 mm 600 mm 8GK9620-1KK20 ■ ■ ■
900 mm 8GK9620-1KK30 ■ ■ ■
100 mm 600 mm 8GK9621-1KK20 ■ ■ ■
900 mm 8GK9621-1KK30 ■ ■ ■
150 mm 600 mm 8GK9622-1KK20 ■ ■ ■
900 mm 8GK9622-1KK30 ■ ■ ■
200 mm 300 mm 8GK9607-1KK10 ■ ■ ■
600 mm 8GK9623-1KK20 ■ ■ ■
900 mm 8GK9623-1KK30 ■ ■ ■
400 mm 250 mm 8GK9606-2KK10 ■ ■ ■
300 mm 8GK9607-2KK10 ■ ■ ■
600 mm 8GK9622-2KK20 ■ ■ ■
900 mm 8GK9622-2KK30 ■ ■ ■
600 mm 250 mm 8GK9606-4KK10 ■ ■ ■
300 mm 8GK9607-4KK10 ■ ■ ■
600 mm 8GK9622-4KK20 ■ ■ ■
900 mm 8GK9622-4KK30 ■ ■ ■
800 mm 250 mm 8GK9606-5KK10 ■ ■ ■
300 mm 8GK9607-5KK10 ■ ■ ■
600 mm 8GK9622-5KK20 ■ ■ ■
900 mm 8GK9622-5KK30 ■ ■ ■
15 1000 mm 250 mm 8GK9606-7KK10 ■ ■ ■
300 mm 8GK9607-7KK10 ■ ■ ■
Deep-drawn covers 25 mm
Height Width Article No.
800 mm 600 mm 8GK9635-5KK20 ■ ■ ■
900 mm 8GK9635-5KK30 ■ ■ ■
1000 mm 600 mm 8GK9636-7KK20 ■ ■ ■
900 mm 8GK9636-7KK30 ■ ■ ■
Deep-drawn front covers 35 mm
Height Width Article No.
200 mm 600 mm 8GK9605-1KK20 ■ ■ ■
900 mm 8GK9605-1KK30 ■ ■ ■
400 mm 600 mm 8GK9605-2KK20 ■ ■ ■
900 mm 8GK9605-2KK30 ■ ■ ■
600 mm 600 mm 8GK9605-4KK20 ■ ■ ■
900 mm 8GK9605-4KK30 ■ ■ ■
15
Accessories
15
Partitions for ALPHA 630 UNIVERSAL
Mounting Height Width Article No.
Horizontal – 250 mm 8GK9525-0KK03 ■
300 mm 8GK9525-0KK13 ■
600 mm 8GK9525-0KK23 ■
900 mm 8GK9525-0KK33 ■
Transparent covers
Width Article No.
250 mm 8GK9527-0KK03 ■ ■ ■
300 mm 8GK9527-0KK00 ■ ■ ■
600 mm 8GK9527-0KK01 ■ ■ ■
900 mm 8GK9527-0KK02 ■ ■ ■
15
Accessories
Holders for terminal strips and locking systems 125 630 800
DIN rails for terminal blocks
Type Height Width Article No.
I201_11239
2
Horizontal – 600 mm 8GF9672 ■ ■ ■
900 mm 8GF9674 ■ ■ ■
1 Horizontal, recessed – 600 mm 8GF9673 ■ ■ ■
900 mm 8GF9675 ■ ■ ■
Vertical with 3 mounting rails 200 mm 600 mm 8GF7175 ■ ■ ■
400 mm 600 mm 8GF7176 ■ ■ ■
Vertical with 5 mounting rails – 900 mm 8GF7178 ■ ■ ■
400 mm 900 mm 8GF7180 ■ ■ ■
Holder for vertical terminal strips in side compartment L = 900 mm
• ALPHA 800 UNIVERSAL: Each holder must be mounted onto a lateral crossbar
Width Article No.
600/900 mm 8GF9683 ■ ■ ■
Mounting brackets
Version Width Article No.
M5 For angular mounting of the terminal blocks 600/900 mm 8WA746 ■ ■ ■
50
70
NSH0_00042a
14
6
25 50
15 600/900 mm 8GK9560-0KK06 ■ ■ ■
15
Hinges for front covers
Scope of supply Article No.
10 units 8GK9120-0KK11 ■ ■ ■
Accessories
Self-tapping screws M6 × 10
Scope of supply Article No.
10 units 8GF9662 ■ ■ ■
Captive nuts M6
Scope of supply Article No.
100 units 8GF9643 ■ ■ ■
Transport eyebolts
Scope of supply Article No.
4 units 8GF9660 ■ ■ ■
Siemens nameplate
Material Version Color Article No.
Aluminum Self-adhesive Petrol 8GD9084 ■ ■ ■
Sticker, foil Self-adhesive Petrol 8GF9661 ■ ■ ■
Circuit diagram pockets
Types Depth Article No.
DIN A3, made of sheet steel 10 mm 8GK9910-0KK22 ■ ■ ■
DIN A4, transparent sleeve, adhered all-over 10 mm 8GK9910-0KK23 ■ ■ ■
DIN A4, made of plastic 30 mm 8GD9132 ■ ■ ■
DIN A4, large pack, made of plastic 30 mm 8GK9910-1KK24 ■ ■ ■
Cover strips
Length Article No.
1m 8GK9910-0KK01 ■ ■ ■
15
System overview
Distribution boards, assembly kits and accessories
1
1
5
5 5
2 4
5
6 2
3
3 5 6
5
ALPHA 1250 ALPHA 630 ALPHA 630 ALPHA 400 ALPHA 160 ALPHA SIMBOX XL and WP
➋ Quick-assembly kits
15
➌ Assembly kits
For modular For terminal blocks For fuse switch For switch For molded case For busbar-adaptable units
installation devices disconnectors disconnectors circuit breakers
Note:
You will find a detailed range of accessories with the basic units and in the Accessories section.
1
5
5 2
6
5
2
3
4
5
6
➍ Busbars
➎ Mechanical accessories
15
Bases Stays Crossbars Partitions Front covers Locking systems
➏ Electrical accessories
N and PE terminals Terminals N/PE bars Flanges Cable entries Cable holders
Note:
You will find a detailed range of accessories with the basic units and in the Accessories section.
Height Depth Tiers Width Protection class I Protection class I Protection class I
Outside Inside Outside (MW = 18 mm) Outside Inside
1950 mm 1800 mm 400 mm max. 12 MW 300 mm 250 mm 8GK1423-8KK15 8GK1483-8KP15 8GK1483-8KN15
550 mm 500 mm 8GK1423-8KK25 8GK1483-8KP25 8GK1483-8KN25
800 mm 750 mm 8GK1423-8KK35 8GK1483-8KP35 8GK1483-8KN35
1050 mm 1000 mm 8GK1423-8KK45 8GK1483-8KP45 8GK1483-8KN45
1300 mm 1250 mm 8GK1423-8KK55 – –
Accessories
Spare part doors
Height Cubicle width Door version Door width Article No.
1950 mm 300 mm Complete 300 mm 8GK9513-8KK10
550 mm Complete 550 mm 8GK9513-8KK20
800 mm Left 525 mm 8GK9513-8KK30
Right 275 mm 8GK9513-8KK40
1050 mm Left 525 mm 8GK9513-8KK30
Right 525 mm 8GK9513-8KK50
1300 mm Left 775 mm 8GK9513-8KK60
Right 525 mm 8GK9513-8KK50
Side panels, modular distribution board
Depth Article No.
400 mm 8GK9520-0KK05
Busbar supports
• Busbar spacing 100/185 mm
Type Article No.
With matching support plate for mounting on the rear panel 8GK9720-0KK00
Without support plate for mounting on the busbar (no fixing to the cabinet enclosure) 8GK9720-0KK01
15
15
Accessories
Spare part doors
Height Cubicle width Door version Door width Article No.
1950 mm 300 mm Complete 300 mm 8GK9513-8KK10
550 mm Complete 550 mm 8GK9513-8KK20
800 mm Left 525 mm 8GK9513-8KK30
Right 275 mm 8GK9513-8KK40
1050 mm Left 525 mm 8GK9513-8KK30
15 Right 525 mm 8GK9513-8KK50
1300 mm Left 775 mm 8GK9513-8KK60
Right 525 mm 8GK9513-8KK50
Side panels, modular distribution board
Depth Article No.
250/320 mm 8GK9520-0KK03
Flat pack
With closed side panel With open side panel
IP55 IP55 IP43
Protection class I Protection class II Protection class I Protection class I Protection class II
– – – 8GK1302-8KK12 8GK1312-8KK12
– – – 8GK1302-8KK22 8GK1312-8KK22
– – – 8GK1302-8KK32 8GK1312-8KK32
– – – 8GK1302-8KK42 8GK1312-8KK42
– – – 8GK1302-8KK52 8GK1312-8KK52
8GK1323-8KN13 8GK1333-8KN13 8GK1323-8KP13 – –
8GK1323-8KN23 8GK1333-8KN23 8GK1323-8KP23 – –
8GK1323-8KN33 8GK1333-8KN33 8GK1323-8KP33 – –
8GK1323-8KN43 8GK1333-8KN43 8GK1323-8KP43 – –
8GK1323-8KN53 8GK1333-8KN53 8GK1323-8KP53 – –
8GK1323-8KN14 8GK1333-8KN14 8GK1323-8KP14 – –
8GK1323-8KN24 8GK1333-8KN24 8GK1323-8KP24 – –
8GK1323-8KN34 8GK1333-8KN34 8GK1323-8KP34 – –
8GK1323-8KN44 8GK1333-8KN44 8GK1323-8KP44 – –
8GK1323-8KN54 8GK1333-8KN54 8GK1323-8KP54 – –
15
1)
For flat pack distribution boards only
15
Protection class I Protection class II Protection class I Protection class II Protection class I
8GK1122-1KA12 – – – –
8GK1122-1KA22 – – – –
8GK1122-2KA12 8GK1132-2KA12 – – –
8GK1122-2KA22 8GK1132-2KA22 – – –
8GK1122-2KA32 8GK1132-2KA32 – – –
8GK1122-2KA42 8GK1132-2KA42 – – –
8GK1122-3KA12 8GK1132-3KA12 – – –
8GK1122-3KA22 8GK1132-3KA22 – – 8GK1121-3KK22
8GK1122-3KA32 8GK1132-3KA32 – – 8GK1121-3KK32
8GK1122-3KA42 8GK1132-3KA42 – – –
8GK1122-4KA12 8GK1132-4KA12 8GK1123-4KA12 8GK1133-4KA12 –
8GK1122-4KA22 8GK1132-4KA22 8GK1123-4KA22 8GK1133-4KA22 8GK1121-4KK22
8GK1122-4KA32 8GK1132-4KA32 8GK1123-4KA32 8GK1133-4KA32 8GK1121-4KK32
8GK1122-4KA42 8GK1132-4KA42 8GK1123-4KA42 8GK1133-4KA42 –
8GK1122-4KA52 8GK1132-4KA52 8GK1123-4KA52 8GK1133-4KA52 –
8GK1122-5KA12 8GK1132-5KA12 8GK1123-5KA12 8GK1133-5KA12 –
8GK1122-5KA22 8GK1132-5KA22 8GK1123-5KA22 8GK1133-5KA22 –
8GK1122-5KA32 8GK1132-5KA32 8GK1123-5KA32 8GK1133-5KA32 –
8GK1122-5KA42 8GK1132-5KA42 8GK1123-5KA42 8GK1133-5KA42 –
8GK1122-5KA52 8GK1132-5KA52 8GK1123-5KA52 8GK1133-5KA52 –
8GK1122-6KA12 8GK1132-6KA12 8GK1123-6KA12 8GK1133-6KA12 –
8GK1122-6KA22 8GK1132-6KA22 8GK1123-6KA22 8GK1133-6KA22 8GK1121-6KK22
8GK1122-6KA32 8GK1132-6KA32 8GK1123-6KA32 8GK1133-6KA32 8GK1121-6KK32
8GK1122-6KA42 8GK1132-6KA42 8GK1123-6KA42 8GK1133-6KA42 –
8GK1122-6KA52 8GK1132-6KA52 8GK1123-6KA52 8GK1133-6KA52 –
8GK1122-7KA12 8GK1132-7KA12 8GK1123-7KA12 8GK1133-7KA12 –
8GK1122-7KA22 8GK1132-7KA22 8GK1123-7KA22 8GK1133-7KA22 8GK1121-7KK22
8GK1122-7KA32 8GK1132-7KA32 8GK1123-7KA32 8GK1133-7KA32 8GK1121-7KK32
8GK1122-7KA42 8GK1132-7KA42 8GK1123-7KA42 8GK1133-7KA42 –
8GK1122-7KA52 8GK1132-7KA52 8GK1123-7KA52 8GK1133-7KA52 – 15
15
15
15
Height Depth Tiers/MW Width Protection class II
Outside Inside Outside (MW = 18 mm) Outside Inside
558 mm 450 mm 120 mm 3/36 358 mm 250 mm 8GK1031-1KK10
3/72 608 mm 500 mm 8GK1031-1KK20
708 mm 600 mm 120 mm 4/48 358 mm 250 mm 8GK1031-2KK10
4/96 608 mm 500 mm 8GK1031-2KK20
4/144 858 mm 750 mm 8GK1031-2KK30
858 mm 750 mm 120 mm 5/60 358 mm 250 mm 8GK1031-3KK10
5/120 608 mm 500 mm 8GK1031-3KK20
5/180 858 mm 750 mm 8GK1031-3KK30
5/240 1108 mm 1000 mm 8GK1031-3KK40
1008 mm 900 mm 120 mm 6/72 358 mm 250 mm 8GK1031-4KK10
6/144 608 mm 500 mm 8GK1031-4KK20
6/216 858 mm 750 mm 8GK1031-4KK30
6/288 1108 mm 1000 mm 8GK1031-4KK40
1158 mm 1050 mm 120 mm 7/84 358 mm 250 mm 8GK1031-5KK10
7/168 608 mm 500 mm 8GK1031-5KK20
7/252 858 mm 750 mm 8GK1031-5KK30
8GK1052-1KK11 8GK1062-1KK11 – –
8GK1052-1KK21 8GK1062-1KK21 – –
8GK1052-1KK31 8GK1062-1KK31 – –
8GK1052-2KK11 8GK1062-2KK11 – –
8GK1052-2KK21 8GK1062-2KK21 – 8GK1072-2KK21
8GK1052-2KK31 8GK1062-2KK31 – –
8GK1052-2KK41 8GK1062-2KK41 – –
8GK1052-3KK11 8GK1062-3KK11 8GK1082-3KK11 –
8GK1052-3KK21 8GK1062-3KK21 8GK1082-3KK21 –
8GK1052-3KK31 8GK1062-3KK31 8GK1082-3KK31 8GK1072-3KK31
8GK1052-3KK41 8GK1062-3KK41 8GK1082-3KK41 –
8GK1052-4KK11 8GK1062-4KK11 8GK1082-4KK11 –
8GK1052-4KK21 8GK1062-4KK21 8GK1082-4KK21 –
8GK1052-4KK31 8GK1062-4KK31 8GK1082-4KK31 –
8GK1052-4KK41 8GK1062-4KK41 8GK1082-4KK41 –
8GK1052-5KK11 8GK1062-5KK11 8GK1082-5KK11 –
8GK1052-5KK21 8GK1062-5KK21 8GK1082-5KK21 –
8GK1052-5KK31 8GK1062-5KK31 8GK1082-5KK31 –
8GK1052-5KK41 8GK1062-5KK41 8GK1082-5KK41 –
15
Protection class II Protection class II Protection class II Protection class II
8GK1051-1KK10 8GK1061-1KK10 – –
8GK1051-1KK20 8GK1061-1KK20 – –
8GK1051-2KK10 8GK1061-2KK10 – –
8GK1051-2KK20 8GK1061-2KK20 – –
8GK1051-2KK30 8GK1061-2KK30 – –
8GK1051-3KK10 8GK1061-3KK10 8GK1081-3KK10 –
8GK1051-3KK20 8GK1061-3KK20 8GK1081-3KK20 8GK1072-3KK20
8GK1051-3KK30 8GK1061-3KK30 8GK1081-3KK30 8GK1072-3KK30
8GK1051-3KK40 8GK1061-3KK40 8GK1081-3KK40 –
8GK1051-4KK10 8GK1061-4KK10 8GK1081-4KK10 –
8GK1051-4KK20 8GK1061-4KK20 8GK1081-4KK20 –
8GK1051-4KK30 8GK1061-4KK30 8GK1081-4KK30 8GK1072-4KK30
8GK1051-4KK40 8GK1061-4KK40 8GK1081-4KK40 –
8GK1051-5KK10 8GK1061-5KK10 8GK1081-5KK10 –
8GK1051-5KK20 8GK1061-5KK20 8GK1081-5KK20 –
8GK1051-5KK30 8GK1061-5KK30 8GK1081-5KK30 –
Assembly kits
For modular installation devices
ALPHA 1250/630/400 ALPHA 160
Tier spacing 125 mm 150 mm 125 mm 150 mm
15
Height Width Standard With inspection window With deep-drawn Standard
Outside Outside cover 40 mm
75 mm 250 mm 8GK4501-0KK12 – – –
500 mm 8GK4501-0KK22 – – –
150 mm 250 mm 8GK4501-1KK12 – – 8GK4501-1KK11
500 mm 8GK4501-1KK22 – – 8GK4501-1KK21
750 mm 8GK4501-1KK32 – – –
300 mm 250 mm 8GK4501-2KK12 8GK4500-2KK12 8GK4501-2KK13 8GK4501-2KK11
500 mm 8GK4501-2KK22 8GK4500-2KK22 8GK4501-2KK23 8GK4501-2KK21
750 mm 8GK4501-2KK32 – 8GK4501-2KK33 –
450 mm 250 mm 8GK4501-3KK12 8GK4500-3KK12 8GK4501-3KK13 8GK4501-3KK11
500 mm 8GK4501-3KK22 8GK4500-3KK22 8GK4501-3KK23 8GK4501-3KK21
750 mm 8GK4501-3KK32 – 8GK4501-3KK33 –
600 mm 250 mm 8GK4501-4KK12 8GK4500-4KK12 – 8GK4501-4KK11
500 mm 8GK4501-4KK22 8GK4500-4KK22 – 8GK4501-4KK21
750 mm 8GK4501-4KK32 – – –
750 mm 250 mm 8GK4501-5KK12 – – –
500 mm 8GK4501-5KK22 – – –
750 mm 8GK4501-5KK32 – – –
Assembly kits
For 3NP1 fuse switch disconnectors
ALPHA 1250/630/400
Accessories
Cover 3NP1123 … size 000
• Required for size 000 fuse switch disconnectors
Article No.
8GK9912-0KK00
Busbar supports
Busbar center-to-center spacing Number of poles Article No.
60 mm 1-pole 8GK9710-0KK00
2-pole 8GK9710-0KK01
3-pole 8GK9711-0KK03
4-pole 8GK9670-0KK00
40 mm 5-pole 8GK9650-0KK00
15
Accessories
Blanking covers
Switching device size Busbar center-to-center spacing Height Width Article No.
NH00 100 mm 299 mm 50 mm 3NJ4912-2CA00
NH1 – NH3 185 mm 699 mm 50 mm 3NJ4912-2AA00
100 mm 3NJ4912-2BA00
Assembly kits
For SR60 busbar-adaptable units
ALPHA 1250/630/400
Busbar center-to-center spacing 60 mm
Height Width
Outside Outside
300 mm 250 mm 8GK4801-2KK13
500 mm 8GK4801-2KK23
750 mm 8GK4801-2KK33
450 mm 250 mm 8GK4801-3KK13
500 mm 8GK4801-3KK23
750 mm 8GK4801-3KK33
Accessories
Supports for blanking covers
Article No.
8US1922-2EA00
Blanking covers
Article No.
8US1922-2EB00
Blanking covers
Width Article No.
195 mm 8GK9910-0KK08
15
Accessories
Blanking covers
Width Article No.
195 mm 8GK9910-0KK08
Holding plates
• For 4-pole busbar supports for mounting in section with height of 300 mm
Article No.
8GK9711-0KK07
15
Assembly kits
For 3KF switch disconnectors with fuses
ALPHA 1250/630/400
Operating mechanism Front operating Door-coupling rotary
mechanism, center operating mechanism
(mounted in the front
cover)
15 3
3 … 4
200 … 400 A
200 … 800 A
1
1
■
■
■
■
300 mm
450 mm
250 mm
500 mm
210 mm
≥250 mm
8GK4721-2KK10
–
–
8GK4720-3KK20
15
Assembly kits
For 3VL molded case circuit breakers
ALPHA 1250/630/400
15
– –
8GK4720-3KK10 8GK4722-3KK10
– –
8GK4721-3KK10 8GK4722-3KK10
8GK4721-3KK10 8GK4722-3KK10
– 8GK4722-4KK10
8GK4720-5KK10 –
– –
– –
– 8GK4723-4KK10
– 8GK4721-4KK20
– –
– –
– –
– –
15
Assembly kits
For 3VA molded case circuit breakers, 3-pole and 4-pole
ALPHA 1250/630/400
1)
For insulated connection only
2)
Distribution board depth at least 250 mm
3)
Distribution board depth at least 320 mm
4)
With side mounted motorized operating mechanism
– – – – –
– – – – –
– – – – –
8GK4734-2KK12 2) – – – –
– 8GK4731-3KK12 4) 8GK4731-3KK10 8GK4734-3KK12 2) –
– – – – –
– – – – –
– – – – –
8GK4734-2KK22 2) – – – –
– 8GK4731-3KK22 – 8GK4734-3KK22 2) –
– – – – –
– – – – –
– – – – –
8GK4735-3KK10 2) – – – –
– – – – 8GK4733-4KK10 2)
– 8GK4732-4KK10 – 8GK4736-4KK12 –
– – – – –
– – – – –
– – – – –
8GK4732-3KK20 2) – – – –
– – – – –
– – – – –
– 8GK4735-4KK12 – – –
– – – – –
– – – – –
– 8GK4735-4KK22 – 8GK4736-4KK22 3) –
– – – – –
– – – – –
– – – – –
8GK4734-4KK12 3) – – – –
8GK4734-4KK22 3) – – – – 15
– 8GK4731-4KK12 – – –
– 8GK4731-4KK22 – – –
Assembly kits
For meter mounting without top and bottom terminal compartment
ALPHA 630
Height Width
Outside Outside
450 mm 250 mm 8GE3713-4
Accessories
Supports for front cover
Article No.
8GS4018-8
15 DIN rails
Article No.
8GS4010-6
15
Quick-assembly kits
For modular installation devices and terminal blocks
ALPHA 1250/630/400
Tier spacing 125 mm
Height Width No. of tiers MW With N/PE bar With 2 N/PE bars
Outside Outside Terminals
For modular installation devices
450 mm 250 mm 3 – 36 – –
600 mm 250 mm 4 – 48 8GK4001-4KK11 –
500 mm 8 – 96 8GK4001-4KK22 –
750 mm