Masibus 5002U-P - R1F - 0616 - Digital Process Controller

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

5002U-P

Digital Process
Controller
Advanced. Precise. Compact

Features
Masibus 5002U-P is much more than a controller capable for complex Universal Input selection
and demanding process control applications. It has accessibility of Premium ON/OFF or Proportional controller
both hardware and software features in compact size making it a Transmitter Power Supply
highly configurable product, offering many features found in costly Fast Loop response time of 250mSec
programmable controllers. Up to 4 Independent programmable relay output
22 Alarm types
5002U-P accepts all analog process inputs like Thermocouple, RTD, High Accuracy of 0.1% FS
Current and Voltage.
Retransmission output (Optional)
5002U-P offers field configurable Control outputs comprising of RS485 port with Modbus RTU protocol (Optional)
ON-OFF or Proportional. It has total 4 Relay o/p providing a Input Scalability for Linear input type
combination of alarm/control output based on application Output Scalability for all input type
requirement. A comprehensive controlling can be implemented using Square Root Extraction for Linear input type
four relays with any of required control algorithm like On-off or Settable Digital Filter 0-60 Sec
Proportional control. Password Protected menu to avoid unauthorized acces
Unique one shot Calibration method
Using RS485 interface desired parameters configuration and status
can be communicated to SCADA/PLC/DCS applications. Using analog
retransmission output important process values can be retransmitted
as any standard current or voltage signal. Applications
It has Fail-safe Design protecting the process in case of system Heat treatment furnaces
malfunctioning Reheat furnaces
Ceramic Kilns
Glass Industry
Flow/ Pressure control
Distillation and Reactor control in Chemical plants
Water and waste water control

www,masibus.com [email protected]
TECHNICAL SPECIFICATIONS
Input Transmitter Power Supply 24V DC (±1V) @30 mA
Input 1: PV Input Power Supply
Thermocouple ( E, J, K, T, B, R, S, N,C,G) Standard 85-265V AC/110-300V DC
Input Type
RTD (Pt 100), Current, Voltage Optional 18-36V DC
Input Range Refer Table-1 Power consumption <12 VA
TC (E,J,K,T,C,J,N,C,G), RTD: ± 0.1% of F.S ± 1 °C
Isolation (Withstanding voltage)
TC (B,R,S): ± 0.2% of F.S ± 1 °C Betn primary terminals* and secondary terminals**: At least 1500V AC for 1 minute
Accuracy Betn primary terminals* and grounding terminal: At least 1500 V AC for 1 minute
Current, Voltage: ± 0.1% of F.S ± 1 Count
Betn grounding terminal and secondary terminals**: At least 1500 V AC for 1 minute
ADC Resolution 17 bits Betn secondary terminals**: At least 500 V AC for 1 minute
Display Resolution 0.1°C / 1 Count * Primary terminals indicate power terminals and relay output terminals.
** Secondary terminals indicate analog I/O signal and Communication O/P.
Sampling Rate 250 msec Insulation resistance: 50MΩ or more at 500 V DC between power terminals and
CJC Error ±2.0 °C Max grounding terminal
Sensor Burnout current 0.25uA Physical
RTD excitation current 1mA Max Dimension (in mm) 96(H) x 96(W) x 110(D)
NMRR > 40dB Panel cut out (in mm) 92.5(H) x 92.5(W)
CMRR > 120dB Weight (gms) 500 (Approx)
Temp-co < 100ppm/°C Enclosure Material Molded ABS
Input Impedance > 1MΩ Enclosure Protection IP20
Max Voltage 20VDC Terminal Cable Size 2.5mm²
Display & Keys Accessories Two mounting clamps, 100 Ohms Ext. Resistor
Process Value 0.56" Four-digit 7 segment Red LED Environmental
Set Value 0.4" Four-digit 7 segment Green LED Operating temperature 0 to 55 °C
Four Red LED's for Relays, alarm, set point Storage temperature 0 to 80 °C
Status Indication
selection, Green LEDs for Communication Humidity 20 to 95% RH non-condensing
Keys Menu, Escape, Shift, Increment, ACK Table 1: Display Range
Output
Input Type Ranges
Control Output (Field Programmable)
E -200 to 1000 °C
Output type ON/OFF or Proportional
J -200 to 1200 °C
Proportional band 0.1 to 999.9
K -200 to 1370 °C
Cycle time 1 to 250Sec
T -200 to 400 °C
MR(Manual Reset) -50% to 50%
B 450 to 1800 °C
Hysteresis 1 to 250 (on/off mode) Thermocouples
R 0 to 1750 °C
Relay/Alarm Output
S 0 to 1750 °C
Relays 4 (Configurable for control/Alarm)
N -200 to 1300 °C
1 Change over (C, NO, NC), 5A @
Type & Rating C 0 to 2310 °C
230V AC / 30V DC
G 0 to 2310 °C
Mode Proportional* or ON/OFF control (field selectable)
RTD Pt-100 -199.9 to 850.0 °C
Note: *proportional control settable for relay No.1 only.
-10 to 20mV
Retransmission Output (Optional)
0 to 75mV
Number of output 1
0 to 100mV
0/4-20mA @ 500 ohm Max
Output Signal 0.4 to 2V, 0 to 2V
0/ 1-5VDC, 0-10 V DC @ 3 K ohms min
Linear 4 to 20mA, 0 to 20mA -1999 to 9999
Output accuracy ±0.25% of span (Ext.100 Ω)
Communication Output (Optional) 0 to 5 V
Interface RS485 (2 Wire) 1 to 5 V
Protocol Modbus-RTU 0 to 10 V
Baud rate (bps) 9600, 19200
Ordering Code
Model Inputs Power Supply Retransmission O/P Communication o/p
5002U-P X X X X
1 E U1 85-265VAC / 125-300 VDC N None N None
2 J U2 18-36VDC 1 4-20 mA Y RS 485
3 K 2 0-20 mA
4 T 3 1-5V
5 B 4 0-5V
6 R 5 0-10V
7 S
8 N
P C
Q G
9 Pt-100
A -10 to 20 mV
B 0 to 75mV
C 0 to 100 mV
D 0.4 to 2V
E 0 to 2V
F 0 to 5V
G 1 to 5V
+: Consult Factory
H 0 to 10 V
S Special+
Head Office: Masibus Automation And Instrumentation Pvt. Ltd.
B-30, GIDC Electronics Estate, Sector-25, Gandhinagar-382044, Gujarat, India. All specifications are subject to change without notice
Tel: +91 79 23287275-77, Fax: +91 79 23287281. due to continuous improvements.
E-mail: [email protected], Web: www.masibus.com Doc. Ref. 5002U-P-R1F-0616