GEH-6721 Vol I PDF
GEH-6721 Vol I PDF
GEH-6721 Vol I PDF
GE Proprietary and Internal (Class II) – This document contains proprietary information of GE and is intended for internal use only. It may not be used,
shown, reproduced, or disclosed outside of GE without the express written consent of GE.
These instructions do not purport to cover all details or variations in equipment, nor to provide for every possible
contingency to be met during installation, operation, and maintenance. The information is supplied for informational
purposes only, and GE makes no warranty as to the accuracy of the information included herein. Changes, modifications,
and/or improvements to equipment and specifications are made periodically and these changes may or may not be reflected
herein. It is understood that GE may make changes, modifications, or improvements to the equipment referenced herein or to
the document itself at any time. This document is intended for trained personnel familiar with the GE products referenced
herein.
GE may have patents or pending patent applications covering subject matter in this document. The furnishing of this
document does not provide any license whatsoever to any of these patents.
GE provides the following document and the information included therein as is and without warranty of any kind, expressed
or implied, including but not limited to any implied statutory warranty of merchantability or fitness for particular purpose.
For further assistance or technical information, contact the nearest GE Sales or Service Office, or an authorized GE Sales
Representative.
Document Updates
Location Description
Chapter, Control System Overview Section I/O Types, correction to table, Turbine Specific I/O
Chapter, Networks Reorganized and reworded for clarity. Updated information on UDH devices and
third-party interfaces.
Chapter, Communication Protocols Reorganized and new sections: PROFIBUS, OPC, and CANopen
Chapter, Technical Regulations, Updates to the following sections: Safety Standards, Electrical, Elevation
Standards, and Environments New section: Conditions for Compliance
Deleted sections: Clearances, Printed Circuit Board Assemblies
Updated section, Temperature of Components: added DACA to restrictive table
Chapter, Installation Guidelines Updates to the sections: Power Requirements, Equipment Grounding, and Cable
Specifications, and the figure Circuit Diagram
Chapter, Software Tools Reorganized tools sections, and updated some descriptions
GE Proprietary and Internal (Class II) – This document contains proprietary information of GE and is intended for internal use only. It may not be
used, shown, reproduced, or disclosed outside of GE without the express written consent of GE.
Safety Symbol Legend
Warning
Attention
GEH-6800 Mark VIe Control Migration from Mark V Control & Mark V LM Control System Guide
GEI-100709 Mark VIe Control PPROS1B and PPRAS1x Functional Safety Instruction Guide
FE Functional Earth
FTD Flow Totalizer Display (OTEK)
KP Keyphasor*
2.1 Controllers
The Mark VIe controller can be a UCSx stand-alone module that mounts directly inside a
cabinet or a UCCx CompactPCI® (CPCI) 6U high single board computer that mounts in a
rack. The Mark VIe controller is loaded with software specific to its application, which
includes but is not limited to steam, gas, land-marine (LM), or BoP products. It can run
Relay Ladder Diagrams (RLD) or blocks. The IEEE® 1588 protocol is used through the
R, S, and T I/O networks (IONet) to synchronize the clock of the I/O modules and
controllers to within ±100 microseconds. Data is transferred to and from the control
system database in the controller over the I/O network(s). IONet data includes process
inputs/outputs to the I/O packs.
Refer to the section, Controller In a dual system, IONet data also includes:
Redundancy for more
information. • Internal state values and initialization information from the designated controller
• Status and synchronization information from both controllers
• Internal state values for voting and status and synchronization information from all
three controllers
• Initialization information from the designated controller
• Single module
• Built-in power supply
• No jumper settings required
• No battery
• No fan (UCSAH1A and UCSBH1A/UCSBH4A)
• Dual-redundant monitored fans with IS420UCSBH3A
• Smaller cabinet footprint
• Easy access to the UCSA’s CompactFlash® and the UCSB’s NAND flash
Refer to Chapter 5 Networks Two 10/100Base-TX Ethernet ports provide connectivity to the UDH and the CDH. Three
and Communications, the additional 10/100Base-TX Ethernet ports provide connectivity to the IONets.
section, Data Highways.
UCSx Controller Processors
Controller Processor
IS220UCSAH1A 667 MHz PowerQUICC II® Pro Freescale
IS420UCSBH1A 600 MHz EP80579 Intel ®
IS420UCSBH3A 1200 MHz EP80579 Intel
IS420UCSBH4A 1066 MHz EP80579 Intel
The I/O pack provides fault detection through a combination of special circuitry in the
data acquisition board and software running in the Central Processing Unit (CPU)
board. The fault status is transmitted to and used by the controllers. The I/O pack
transmits inputs and receives outputs on both network interfaces if connected.
Each I/O pack also sends an identification message (ID packet) to the main controller
when requested. The packet contains, the hardware catalog number of the I/O board,
the hardware revision, the board barcode serial number, the firmware catalog number,
and the firmware version. The I/O packs have a temperature sensor that is accurate to
within ±2°C (36 °F). Every I/O pack temperature is available in the database and can
be used to generate an alarm.
Input Output
Screws Screws
I/O Pack
Connector
I/O Pack
Connector
Vote /
I/O Pack Select
Connector
I/O Pack
Connector
S-type boards have Euro-style, box type terminal blocks. Some boards are available as
either removable or fixed terminal block versions. S-type board terminal blocks accept
one 2.05 mm (0.08 in) (#12AWG) wire or two 1.63 mm (0.06 in) (#14AWG) wires, each
with 300 V insulation per point. Screw spacing is 5.08 mm (0.2 in) minimum and
center-to-center.
PDIAH1A/1, 2, 3 TBCIH1C 24 discrete inputs (DI) (125 V dc, group isolated) Barrier Yes
PDIAH1B/1, 2, 3 sequence of events (SOE)
PDIOH1A/1 TDBSH2A 24 DI and 12 type C mechanical relays (24 V dc group Box Yes
PDIOH1B/1 isolated) SOE (Refer to Option Boards Note 1, 2, and 3),
SOE for relay outputs
PDIOH1A/1 TDBSH4A 24 DI and 12 type C mechanical relays (48 V dc group Box Yes
PDIOH1B/1 isolated) SOE (Refer to Option Boards Note 1, 2, and 3),
SOE for relay outputs
PDIOH1A/1 TDBSH6A 24 DI and 12 type C mechanical relays (125 V dc group Box Yes
PDIOH1B/1 isolated) SOE (Refer to Option Boards Note 1, 2, and 3),
SOE for relay outputs
PDIOH1A/3 TDBTH2A 24 DI and 12 type C mechanical relays (24 V dc group Box Yes
PDIOH1B/3 isolated) SOE (Refer to Option Boards Note 1), SOE for
relay outputs
PDIOH1A/3 TDBTH4A 24 DI and 12 type C mechanical relays (48 V dc group Box Yes
PDIOH1B/3 isolated) SOE (Refer to Option Boards Note 1), SOE for
relay outputs
PDIOH1A/3 TDBTH6A 24 DI and 12 type C mechanical relays (125 V dc group Box Yes
PDIOH1B/3 isolated) SOE (Refer to Option Boards Note 1), SOE for
relay outputs
PDOAH1A/1, 3 TRLYH1B 12 type C mechanical relays with 6 solenoids, coil Barrier Yes
PDOAH1B/1, 3 diagnostics (115/230 V ac, 24/48/125 V dc), SOE for relay
outputs
PDOAH1A/1, 3 TRLYH1C 12 type C mechanical relays with 6 solenoids, voltage Barrier Yes
PDOAH1B/1, 3 diagnostics (115/230 V ac, 125 V dc), SOE for relay
outputs
PDOAH1A/1, 3 TRLYH2C 12 type C mechanical relays with 6 solenoids, voltage Barrier Yes
PDOAH1B/1, 3 diagnostics (24 V dc), SOE for relay outputs
PDOAH1A/1, 3 TRLYH1D 6 type A mechanical relays for solenoids, solenoid Barrier Yes
PDOAH1B/1, 3 impedance diagnostics (24/125 V dc), SOE for relay
outputs
PDOAH1A/1 SRLYH2A 12 type C mechanical relays (115/230 V ac, 24/48/125 V Box yes
PDOAH1B/1 dc) (Refer to Option Boards Note1, 2, and 3), SOE for
relay outputs
PDOAH1A/1, 3 TRLYH1E 12 type A solid-state relays (115/230 V ac), voltage Barrier yes
PDOAH1B/1, 3 diagnostics, SOE for relay outputs
PDOAH1A/1, 3 TRLYH2E 12 type A solid-state relays (125 V dc), voltage Barrier yes
PDOAH1B/1, 3 diagnostics, SOE for relay outputs
PDOAH1A/1, 3 TRLYH3E 12 type A solid-state relays (24 V dc), voltage Barrier yes
PDOAH1B/1, 3 diagnostics, SOE for relay outputs
PDOAH1A/3 TRLYH1F 36 mechanical relays, 12 voted type A normally open Barrier yes
PDOAH1B/3 (NO) outputs (115 V ac, 24/48/125 V dc) (Refer to Option
Boards Note 4 and 5), SOE for relay outputs
PDOAH1A/3 TRLYH2F 36 mechanical relays, 12 voted type B normally closed Barrier yes
PDOAH1B/3 (NC) outputs (115 V ac, 24/48/125 V dc) (Refer to Option
Boards Note 4 and 5), SOE for relay outputs
Option Boards
WROGH1A Note 3: Add fuse power distribution in COM leg of all 12 relay circuits
WPDFH1A Note 4: Fuses for solenoid power in (+) and (-) legs
WPDFH2A Note 5: Fuses for field solenoid power in top side only for common neutral AC solenoids
PAICH2A/1, 3 TBAIH1C 10 AI (V/I inputs, group isolated) and 2 AO (0-20/0-200 Barrier Yes
PAICH2B/1, 3 mA outputs, group isolated)
PAICH1A/1 STAIH2A 10 AI (V/I inputs, group isolated) and 2 AO (0-20 mA Box Yes
PAICH1B/1 outputs, group isolated)
PAICH2A/1 STAIH2A 10 AI (V/I inputs, group isolated) and 2 AO (0-20/0-200 Box Yes
PAICH2B /1 mA outputs, group isolated)
PAICH1A/1 SAIIH2A 10 AI (V/I inputs, point isolated) and 2 AO (0-20 mA Box Yes
PAICH1B/1 outputs, group isolated)
PAICH2A/1 SAIIH2A 10 AI (V/I inputs, point isolated) and 2 AO (0-20/0-200 Box Yes
PAICH2B/1 mA outputs, group isolated)
PRTDH1A/1, 2 TRTDH1D 16 RTDs 3 wires /RTD (8 per I/O pack) Barrier Yes
PRTDH1B/1, 2
PRTDH1A/1, 2 TRTDH2D 16 RTDs 3 wires /RTD (8 per I/O pack) supports fast Barrier Yes
PRTDH1B/1, 2 scan rate
2.3.3.2 Fieldbus
Fieldbus I/O
I/O Pack/Qty Board Communications Types Type Removable
per Board
PSCHHIA/1, 2 SSCAH1A 6 serial Box No
SSCAH2A 6 serial Box Yes
PRTDH1A/1 SRTDH1A 8 RTDs 3 wires /RTD Box No
PRTDH1B/1
PRTDH1A/1 SRTDH2A 8 RTDs 3 wires /RTD Box Yes
PRTDH1B/1
PSCAH1A/1 SSCAH1A 6 MODBUS Master serial or 1 Modbus Ethernet Box No
PSCAH1B/1
PSCAH1A/1 SSCAH2A 6 MODBUS Master serial or 1 Modbus Ethernet Box Yes
PSCAH1B/1
PCNOH1A/1 CANopen Master Gateway n/a n/a
PCNOH1B/1
PPRFH1A/1 PROFIBUS - DP-V0, Class 1 Master Communications n/a n/a
SPIDG1A
PPRFH1B/1 PROFIBUS - DP-V1 Class 1 Master Communications
(PPRFH1B only)
PCLAH1A/1 SCLSH2A Core Analog I/O for aero-derivative turbines, simplex, TMR Box Yes
PCLAH1B/1 SCLTH2A Additional I/O with SCLT board for TMR applications
PCAAH1A/1 TCASH2A Core Analog I/O for heavy duty gas turbines, Simplex and Box Yes
PCAAH1B/1 TCATH2A TMR Additional I/O with TCAT board for TMR applications
PGENH1A/1, 3 TGNAH1A Power Load Unbalance: (3) 1-phase PTs, 3 V/I inputs ** **
PSVOH1A/1, 3 TSVCH1 Servos: 2 channels, 2-coil outputs, 8 LVDTs and excitation, 2 Barrier Yes
TSVCH2A pulse rate inputs (heavy duty & aero gas & steam)
PSVPH1A/1 SSVPH1A Steam servo applications: 2 channels, 2-coil outputs, 6 LVDTs Barrier Yes
SSVPH2A and 2 excitation, 1 pulse rate input for speed feedback Box Yes
Trip Protection: Primary and emergency trip protection is available in many combinations, which are too complex to describe
in this table. For descriptions of these combinations, refer to GEH-6721, Mark VIe Control, Volume II System Hardware
Guide.
** Analog inputs are box-type and removable. Current transformer (CT) inputs are barrier-type and not removable.
PMVE/1, 3 QTBA, TCQC, UCSA used as I/O pack controller to interface Box No – H1A,
TBQA, MVRA, with dedicated turbine I/O application boards. Yes - H2A,
TBQB, MVRB, UCSA has 6 communication ports No - G1A,
TBQC, MVRC, (1 –RS-232C, 2 –Ethernet, 3 –HSSL) No - G1B
TBQF, MVRF
TBQD,
TBQG,
CTBA,
TBCA,
TBCB
PMVD/1, 3 DTBA, TCRA 96 contact inputs, Box No – H1A,
DTBB, 60 relay contact outputs Yes – H2A,
DTBC, No –G1A,
DTBD No – G1B
PMVP/3 PTBAG1A Expansion 2 magnetic p.u. speed inputs, Barrier No
PTBAG2A board TCEB 8 flame detector pulse inputs,
and trip Trip solenoid interface relays,
boards Generator breaker synchronizing circuits
TCTE, E-Stop
TCTG,
TCTL,
TCTS,
RST
Control JPDP
System JPDS or JPDM Power
PPDA
Feedback 28 V Control Power
R S T JPDL
PS PS PS Pack
RST
Dc Power
JPDR Distribution Boards
JPDF do not conn ect
Ac Power
Selector Board Select1 of 2
simu lta neously.
Local Ac Power
Distribution Boards
Ac Input
JPDB Ac
115 / 230 V ac JPDA
Power
x2
Ac Input Ac
JPDA
Power
JPDD Dc
JPDF
125 V Battery Power
125 V dc
Dc
JPDD
Power
DACA
Ac to Dc
Converter Modules
PDM Basic Layout
• Simplex controller
• Dual controllers
• Triple redundant controllers (TMR)
Each I/O pack delivers an input packet at the beginning of the frame on its primary
network. The controller sees the inputs from the I/O modules, performs application code,
and then delivers an output packet(s) for all I/O modules. The following diagram displays
typical simplex controller architecture.
The dual control Mark VIe architecture reliability can be significantly better than the
single controller. All of the network and controller components are redundant and can be
repaired online. The I/O reliability can be mixed and matched meeting reliability needs
described in the I/O option sections below.
In a dual Mark VIe control system, both controllers receive inputs from the I/O modules
on both networks and transmit outputs on their respective IONet continuously. When a
controller or network component fails the system does not require fault detection nor
failover time to continue operating.
In a dual control system, the application software in each controller tries to produce the
same results. After many iterations of the application software, it is possible for the
internal data values to differ due to mathematical round off, and different past history
(power-up). To converge this data, the internal data (state) variables are taken from the
designated controller and transmitted to the non-designated controller for its use. This is
known as state exchange.
State variables are any internal variables not immediately derived from input or control
constants. Any variable that is used prior to being re-calculated is an internal state
variable.
A = B+C
C=3xD
Assume B and D are inputs and A and C are intermediate values. Since C is used prior to
being calculated, the value of C during the previous scan retains some state information.
Therefore, C is a state variable that must be updated in the non-designated controller if
both controllers are to remain synchronized.
In the Mark VIe controller, Boolean state variables are updated on every control frame.
The analog state variable updates are multiplexed. A subset of analog state variables is
updated every control frame. The controller rolls through each subset until all state
variables are transmitted.
In a TMR system, the level of In a TMR Mark VIe control system, all three controllers receive inputs from the I/O
I/O reliability can be varied to modules on all networks and transmit outputs on their respective IONet continuously. If a
meet specific application controller or network component fails, the system does not require fault detection or
requirements. Not all I/O has failover time to continue operating. All controllers transmit their copy of the state
to be dual or triple redundant. variables after the output packet has been transmitted. Each controller takes the three sets
of state variables and votes the data to get the values for the next run cycle.
The I/O pack delivers input data on both networks at the beginning of the frame and
receives output data from both controllers at the end of the frame.
• Redundant sensors
• Redundant data acquisition
• Redundant network
• Online repair
Each I/O pack delivers input data on a separate network at the beginning of the frame and
receives output data from separate controllers at the end of the frame.
Each I/O pack delivers input data on a separate network at the beginning of the frame.
The two I/O packs are both connected to both networks, but only communicates to the
controller and the gateway network. If a failure occurs on the active I/O pack, the backup
I/O pack becomes the active I/O pack, thus maintaining communication with the
connected devices.
For any of the above input configurations, multiple inputs can be used to provide
application redundancy. For example, three Simplex inputs can be used and selected in
application code to provide sensor redundancy.
The Mark VIe control provides configuration capability for input selection and voting
using a simple, highly reliable and efficient selection/voting/fault detection algorithm to
reduce application configuration effort. This maximizes the reliability options for a given
set of sensor inputs and provides output voting hardware compatibility. All applicable
subsets of reliability options are available on a per terminal board basis for any given
Mark VIe topology. For example, in a TMR controller, all simplex and dual option
capabilities are also provided.
While each IONet is associated with a specific controller that is responsible for
transmitting outputs, all controllers see all IONets. The result is that for a simplex input
the data is not only seen by the output owner of the IONet, it is seen in parallel by any
other controllers. The benefit of this is that loss of a controller associated with a simplex
input does NOT result in the loss of that data. The simplex data continues to arrive at
other controllers in the system.
TMR Fanned – Three I/O Packs with One IONet per I/O Pack
TMR Dedicated – Three simplex I/O modules with One IONet per I/O Pack
One sensor can be fanned to three I/O boards as above for medium-integrity applications.
This is used for sensors with medium-to-high reliability. Three such circuits are needed
for three sensors. Typical inputs are 0-20 mA inputs, contacts, thermocouples, and RTDs.
The following figure displays three sensors, each one fanned and then software
implemented fault tolerance (SIFT) voted. This provides a high reliability system for
current and contact inputs, and temperature sensors.
Three Sensors, Each One Fanned and Voted, for Medium-to-High Reliability Applications
Three Sensors with Dedicated Inputs, Software Voted for High Reliability Applications
The three voting controllers calculate TMR system outputs independently. Each controller
sends the output to its associated I/O hardware (for example, the R controller sends output
to the R I/O). The three independent outputs are then combined into a single output by a
voting mechanism. Different signal types require different methods of establishing the
voted value.
The signal outputs from the three controllers fall into three groups:
• Outputs are driven as single ended non-redundant outputs from individual I/O
networks
• Outputs exist on all three I/O networks and are merged into a single signal by the
output hardware
• Outputs exist on all three I/O networks and are output separately to the controlled
process. This process may contain external voting hardware.
For normal relay outputs, the three signals feed a voting relay driver, which operates a
single relay per signal. For critical protective signals, the three signals drive three
independent relays, with the relay contacts connected in the typical six-contact voting
configuration.
For servo outputs, the three independent current signals drive a three-coil servo actuator,
which adds them by magnetic flux summation, as displayed in the following figure.
Failure of a servo driver is sensed and a deactivating relay contact is closed to short the
servo coil.
MTBF roll up of the system components gives the equipment owner the knowledge
needed to determine how long the equipment can be expected to operate without failure
under given conditions. If it is essential that the equipment does not fail during operation,
the owner can use this data to schedule maintenance/replacement of the equipment prior
to failure. Alternately, redundant applications could be used preventing system problems
when a failure occurs.
MTBF data is also used to determine the weak links in a system. The system engineer
provides contingency options for those weak links to obtain higher reliability.
The engineer must be very aware of MTBF and MTBFO when designing a reliable
continuous system. To maximize the MTBFO, Mark VIe control systems undergo
evaluation of all system component MTBF values. The effects of failures and contingency
operation are then analyzed to maximizing MTBFO.
To continue operation after a critical system component has failed, a control must have
one or more backups in place (redundancy) to improve the MTBFO significantly above
that of a simplex control. The simplest method is adding a second component that takes
over the critical function when a fault is detected.
The redundancy in the system can be either active or standby. The Mark VIe control uses
active redundancy and has all components operating simultaneously. Standby redundancy
activates backup systems after a failure is detected.
Realizing the full benefits of redundancy, a system failure must be detectable for the
control to bypass it. In a dual control, gross failures are readily detectable while subtle
failures are more difficult to detect. TMR controls, using two out of three voting, are
always able to select a valid value when presented with any single failure.
Depending on the equipment, the time required to detect the fault and switch to the new
component may be hours/minutes/seconds/milliseconds. In the case of fuel-flow control
to a turbine, this is required to be done in milliseconds.
A TMR control normally configures the control for two out of three selection. This yields
high running and tripping reliability from the primary control. Additional dedicated
tripping controls can be used to achieve even higher tripping reliability, but they must also
be TMR to preserve running reliability.
Complex control systems have many potential failure points. This can be very costly and
time consuming to create foolproof fault detection. Failure to control the outputs of a
system is the most damaging. Fault detection must be determined as close to the output as
possible to achieve the highest level of reliability. With the Mark VIe control configured
using triple redundant controllers and I/O modules, a high level of detection and fault
masking is provided by voting the outputs of all three controllers and monitoring
discrepancies.
Option 2 - Continue running until the system is brought down in a controlled manner to
replace the failed component.
Option 1 is not recommended. A redundant system, where the MTTR is infinite can have
a lower total reliability than a simplex system.
Option 2 is a valid procedure for some processes needing predictable mission times.
Many controlled processes cannot be easily scheduled for a shut down.
Note As MTTR increases from the expected four hours to infinite, the system reliability
can decline from significantly greater down to less than a simplex system reliability.
Repair should be accomplished as soon as possible.
Option 3 is required to get the maximum benefit from redundant systems with long
mission times. In dual or triple redundant Mark VIe controller applications, the
controllers and redundant I/O packs can be replaced online.
For the purposes of deciding which controller is to be the designated controller, each
controller nominates itself on a weighting algorithm. The nominating values are voted
among the controllers and the majority value is used. If there is a tie, or no majority, the
priority is R, then S, and then T. If a designated controller is powered down and later
powered up, the designated controller will move and not come back if all controllers are
equal. This ensures that a toggling designated controller is not automatically reselected.
• Control state
• UDH connectivity
• IONet connectivity
• NVRAM health
For critical loops, the default action is the only acceptable choice. The other options are
provided for non-critical loops, where running liability may be enhanced by an alternate
output.
2.6.8 Voting
Voting in the Mark VIe control is separated into analog and logic voting. Additionally,
fault detection mechanisms directly choose owned inputs and designated states.
Selected signals from the controller database can be mapped into pages of peer outputs
that are broadcast periodically on the UDH I/O to peer controllers. For TMR systems, the
UDH communicator performs this action using the data from its internal database. In the
event of a redundant UDH network failure, the controller will request data over the
remaining network, the IONet.
Each PPRO independently determines when to trip, and the signals are passed to the
TREG terminal board. TREG operates in a similar way to TRPG, voting the three trip
signals in relay circuits and removing power from the trip solenoids. This system contains
no software voting, making the three PPRO modules completely independent. The only
link between PPRO and the other parts of the control system is the IONet cable, which
transmits status information.
Additional protection for simplex systems is provided by the protection module through
the Servo Terminal Board, TSVC. Plug J1 on TREG is wired to plug JD1 on TSVC, and
if this is energized, relay K1 disconnects the servo output current and applies a bias to
force the control valve closed.
Ethernet is used for all data highways and the I/O network. Fiber is just the transmission
medium. The protocol is the same as the copper paths.Each layer uses industry standard
components and protocols to simplify integration between different platforms and
improve overall reliability and maintenance. The layers are designated as the enterprise,
supervisory, unit control, and IONet, and are described in the following sections.
The Supervisory layer provides operator interface capabilities such as coordination of the
HMI viewer and server nodes, as well as other functions like data collection (Historian),
remote monitoring, and vibration analysis. This layer may be used as a single or dual
network configuration. A dual network provides redundant Ethernet switches and cables
to prevent complete network failure if a single component fails. The network is known as
the Plant Data Highway (PDH).
Other fieldbus based devices The Control layer provides continuous operation of the process equipment. The
may not be restricted to EGD controllers on this layer are highly coordinated to support continuous operation without
data transfers. interruption. The controllers operate at a fundamental rate called the frame rate, which
can be between 6-100 Hz. These controllers use EGD to exchange data between nodes.
Various levels of redundancy for the connected equipment are supported by the
supervisory and control layers. This network is known as the Unit Data Highway (UDH).
Speed 100 megabit per second or with 1000 megabit per second trunks interconnecting switches
Media and Distance Ethernet 100Base-TX is used for switch to controller/device connections. Cable is CAT 5e compliant.
Distance is up to 100 m (328 ft). * Fiber-optic connections, Ethernet 100FX, 1000SX, 1000 LX are
used for distances of 2 km (1.24 mi), 550 m (1804.46 ft), and 5 km (3.11 mi), respectively.
Protocols Ethernet-compatible protocol, typically TCP/IP-based. Use GSM or Modbus over Ethernet for external
communications.
Message Integrity 32-bit cyclic redundancy code (CRC) appended to each Ethernet packet plus additional checks in
protocol used.
External Interfaces Various third-party interfaces are available; GSM and Modbus are the most common.
* Fiber-optic cable provides the best signal quality, completely free of electromagnetic interference (EMI) and radio frequency
interference (RFI). Large point-to-point distances are possible, and since the cable does not carry electrical charges, ground
potential problems are eliminated.
Media and Distance Ethernet 100Base-TX for switch to controller/device connections. The cable is 22 to 26 AWG
unshielded twisted pair; category 5e EIA/TIA 568 A/B. Distance is up to 100 m. Ethernet
100Base-FX with fiber-optic cable optional for distances up to 2 km (1.24 mi).
Number of Nodes At least 25 nodes, given a 25 Hz data rate. For other configurations, contact the factory.
Type of Nodes Supported Controllers, PLCs, operator interfaces, and engineering workstations
Message Integrity 32-bit CRC appended to each Ethernet packet plus integrity checks built into UDP and EGD
Refer to the section, UDH The UDH is an Ethernet-based network that provides direct or broadcast peer-to-peer
Communicator. communications between controllers and an operator/maintenance interface. It uses
Ethernet Global Data (EGD), which is a message-based protocol for sharing information
with multiple nodes based on UDP/IP. UDH network hardware is similar to the PDH
hardware. The following figure displays redundant UDH networks with connections to
the controllers and HMI servers.
When a controller does not receive external EGD data from its UDH connection, it may
request the data be forwarded across the IONet from another UDH communicator. One or
more communicators supply the data and the requesting controller uses the last data set
received. Only the external EGD data used in sequencing by the controllers is forwarded
in this manner.
Simplex Dual The simplex controller connects to the second Ethernet ports of both the <R> and
<S> controllers of the dual system using a category 5 network cable through a
network switch.
Simplex TMR The simplex controller connects to the second Ethernet ports of <R>, <S>, and <T>
controllers of the TMR system using a category 5 network cable through a network
switch.
Dual Dual The <R> and <S> controllers of each system connect using a category 5 network
cable through a network switch.
Dual TMR The <R> and <S> controllers of the dual system connect to the <R>, <S>, and <T>
controllers of the TMR system using a category 5 network cable through a network
switch.
TMR TMR The <R>, <S>, and <T> controllers of each system connect using a category 5
network cable through a network switch.
With the TMR and TMR configuration, the customer does not have to use the
network if all EGD exchanges run at frame rate.
The LS2100e control contains a digital control that interfaces seamlessly with various
Mark control system devices, including the Human-machine Interface (HMI) and
Historian products. These devices communicate with each other over an Ethernet-based
data highway to form a fully integrated control system.
The HMI can be configured as a server or viewer, containing tools and utility programs. It
can be linked to one data highway, or redundant network interface boards can be used to
link the HMI to both data highways for greater reliability. The HMI can be cabinet,
control console, or table-mounted.
WorkstationST OPC servers collect data on the UDH and use the PDH to communicate
with HMI viewers. Multiple servers can be used to provide redundancy. Configuration
servers, Historian servers, and Alarm Servers are used for large system scaling.
Redundant data servers are optional, and if supplied, communication with the viewers
continues even if one server fails.
The I/O networks (IONet) are IEEE 802.3 100 Megabits full duplex Ethernet networks.
All traffic on each IONet is deterministic UDP/IP packets. TCP/IP is not used. Each
network (red, blue, black) is an independent IP subnet. The IONet is limited to Mark VIe
qualified control devices, I/O devices, Ethernet switches, and cables.
Refer to GEH-6753, The networks are fully switched full-duplex preventing collisions that can occur on
NetworkST 3.0 for Mark VIe non-switched Ethernet networks. The switches also provide data buffering and flow
Controls Application Guide for control during the critical input scan. The IEEE 1588 standard for precision clock
more information. synchronization protocol is used to synchronize frame and time, the controllers, and the
I/O modules. This synchronization provides a high level of traffic flow control on the
networks.
Network communication between the controller and IONet has tightly synchronized
UDP/IP Ethernet packets. The synchronization is achieved using the IEEE 1588 standard
for precision clock synchronization protocol and special hardware/software on the
controller and I/O packs. The Ethernet switches have been qualified for minimum latency
and maximum throughput.
BPPx
IONet Specifications
IONet is presently recommended to only pass through five switches in series when going
from I/O pack to main controller (refer to the following figure). Any configured IONet
port on a controller or I/O module is continuously sending data, providing immediate
detection of faulty network cables, switches, or board components. When a fault occurs, a
diagnostic alarm is generated in the controller or I/O module.
Note When a terminal board is replaced, the user must associate the new Host ID to the
configured device. The ToolboxST application presents a list of unrecognized devices that
have requested IP addresses to simplify this process.
IONets are class C networks. Each is an independent network with different subnet
addresses. The IONet IP host addresses for the controllers are fixed. The IP addresses of
the I/O packs are assigned by the ToolboxST application and the controller automatically
distributes the addresses to the I/O packs through a standard Dynamic Host Configuration
Protocol (DHCP) server in the controllers.
Type of controller processor • OPC UA direct from the Mark VIe controller
effects idle time.
• OPC UA, DA, AE from the WorkstationST server
• Serial Modbus® slave link from the WorkstationST server using the computer
RS-232C port
• Ethernet Modbus Slave direct from the Mark VIe controller to the third-party device
(Ethernet to serial converter device may be used)
• GSM from the WorkstationST server to the DCS.
GEDS Standard Messages (GSM) is a proprietary 100 mbps Ethernet link using TCP/IP.
It supports turbine control commands, Mark VIe control data and alarms, the alarm
silence function, logical events, and contact input sequence of events records with 1 ms
resolution. Ethernet GSM has the advantage of tighter system integration.
OPC UA
Modbus
GSM
WorkstationST Server
PDH
Ethernet
U CS BH1 A
Serial Modbus
UDH
Ethernet
OPC UA Ethernet
Modbus
CDH
Event Driven Messages are sent from the HMI to the DCS spontaneously when a system
alarm or system event occurs or clears, or a contact input (SOE) closes or opens. Each
logic point transmits with an individual time tag.
Periodic Data Messages are groups of data points, defined by the DCS and transmitted
with a group time tag. All of the 5000 data points in the Mark control are available for
transmission to the DCS at periodic rates down to 1-second. One or multiple data lists can
be defined by the DCS using controller names and point names.
Common Request Messages, including turbine control commands and alarm queue
commands, are sent from the DCS to the Mark VIe control system HMI. Turbine control
commands include momentary logical commands such as raise and lower, start and stop,
and analog setpoint target commands. Alarm queue commands consist of silence, plant
alarm horn, and reset commands as well as alarm dump requests causing the entire alarm
queue to be transmitted from the Mark VIe control system to the DCS.
For using OPC with the WorkstationST server, refer to the following documents.
This Modbus communication link would allow an operator at a remote location to make
an operator command by sending a logical command or an analog setpoint to the
controller. Logical commands are used to initiate automatic sequences in the controller.
Analog setpoints are used to set a target, such as turbine load, and initiate a ramp to the
target value at a ramp rate predetermined by the application software.
Each page is identified by the combination of a Producer ID and an Exchange ID. The
consumer recognizes the data and knows where to store it. EGD allows one controller
component, referred to as the producer of the data, to simultaneously send information at
a fixed periodic rate to any number of peer controller components, known as the
consumers. This network supports a large number of controller components capable of
both producing and consuming information.
The exchange contains a configuration signature, which displays the revision number of
the exchange configuration. If the consumer receives data with an unknown configuration
signature, it makes that data unhealthy.
If a transmission is interrupted, the receiver waits three periods for the EGD message,
after which it times out and the data is considered unhealthy. Data integrity is preserved
by the following:
Redundancy Pages may be broadcast onto multiple Ethernet subnets or may be received from multiple
Ethernet subnets, if the specified controller hardware supports multiple Ethernet ports.
Fault Tolerance In TMR configurations, a controller can forward EGD data across the IONet to another
controller that has been isolated from the Ethernet.
Sizes An exchange can be a maximum of 1400 B. Pages can contain multiple exchanges. The
number of exchanges within a page and the number of pages within an EGD node are limited
by each EGD device type. The Mark VIe controller does not limit the number of, exchanges, or
pages.
Message Integrity Ethernet supports a 32-bit CRC appended to each Ethernet packet.
Reception timeout is determined by EGD device type. The exchange times out after an
exchange update had not occurred within four times the exchange period, using Sequence ID.
Missing/out of order packet detection
UDP and IP header checksums
Configuration signature (data layout revision control)
Exchange size validation
Function Codes EGD allows each controller to send a block of information to, or receive a block from, other
controllers in the system. Integer, Floating Point, and Boolean data types are supported.
The Device Manager Gateway performs TCP exchanges in its configuration and device
communications. The EGD protocol also applies TCP for configuration messages and
exchanges. Class 1 exchanges are not synchronized by 1588 Synchronization and Class 2
exchanges occur between frames. Flow control is provided only between network
switches.
One controller in a TMR configuration is automatically selected to transmit the EGD data
onto the UDH. If the UDH fractures, causing the controllers to be isolated from each
other onto different physical network segments, multiple controllers are enabled for
transmission. These provide data to each of the segments. These features add a level of
Ethernet fault tolerance to the basic protocol.
NTP uses the Marzullo’s algorithm, and includes support for features such as leap
seconds. NTPV4 can usually maintain time to within 10 ms on the internet, and achieve
accuracies of 200 microseconds or better in local area networks. It provides Coordinated
Universal Time (UTC). No information about time zones or daylight saving time is
transmitted and must be obtained separately.
For modern Unix system, the NTP client is implemented as a daemon process that runs
continuously in user space (ntpd). Because of sensitivity to timing, however, it is
important to have the standard NTP clock phase-locked loop implementation in kernel
space. For QNX, in the Mark VIe controller, ntpd runs in kernel space.
A time/frequency processor board is placed in the HMI. This board acquires time from
the master time source with a high degree of accuracy. When the HMI receives the time
signal, it makes the time information available to the turbine and generator controls on the
network by way of NTP. The HMI server provides time-to-time slaves either by
broadcasting time, or by responding to NTP time queries, or both methods.
Local time is used for display of real time data by adding a local time correction to UTC.
A node’s internal time clock is normally UTC rather than local. This is done because
UTC time steadily increases at a constant rate while corrections are allowed to local time.
Historical data is stored with global time to minimize discontinuities.
Stratum 0 are devices such as atomic (cesium, rubidium) clocks, GPS clocks, or other
radio clocks. Stratum 0 devices are usually not attached to the network. Instead, they are
locally connected to computers (for example, through an RS-232 connection using a pulse
per second signal).
Stratum 1 are computers attached to Stratum 0 devices. Normally they act as servers
for timing requests from Stratum 2 servers through NTP. These computers are also
referred to as time servers.
Stratum 2 are computers that send NTP requests to Stratum 1 servers. Normally a
Stratum 2 computer will reference a number of Stratum 1 servers and use the NTP
algorithm to gather the best data sample, dropping any Stratum 1 servers that are wrong.
Stratum 2 computers are grouped with other Stratum 2 computers to provide more stable
and robust time for all devices in the peer group. Stratum 2 computers normally operate
as servers for Stratum 3 NTP requests.
Stratum 3 are computers that use exactly the same NTP functions of peering and data
sampling as Stratum 2, and can be used as servers for lower strata. NTP support up to 256
strata, depending on the version of NTP protocol in use.
The time of the request packet transmission is t0, the time of the packet reception is t1, the
time of the response packet transmission is t2, and the time of the response packet
reception is t3. The elapsed time on the client side between the emission of the request
packet and the reception of the response packet is t3 - t0. The time the server waited before
sending the answer is t2 - t1.
The NTP synchronization is correct when both the incoming and outgoing routes between
the client and the server have a symmetrical nominal delay. If the routes do not have a
common nominal delay, the synchronization has a systematic bias of half the difference
between the forward and backward travel time.
Servers provide time to clients. Clients send requests to the server and the server sends
back a time stamped response, along with information such as accuracy and stratum.
Clients get time responses from a NTP server or servers, and uses the information to
calibrate its clock. This consists of the client determining how far its clock is off and
adjusting its time to match that of the server. The maximum error is determined based on
the round-trip delay time for the packet to be received.
Peers are members of a group of NTP servers that are tightly coupled. In a group of
two peers, at any given time, the most accurate peer is acting as a server and the other
peers are acting as clients. The result is that peer groups will have closely synchronized
times without requiring a single server to be specified.
The NTP broadcast or multicast client listens for NTP packets on a broadcast or multicast
address. When the first packet is received, it attempts to quantify the delay to the server to
better quantify the correct time from later broadcasts. This is accomplished by a series of
brief interchanges where the client and server function as a regular (non-broadcast) NTP
client and server. Once these interchanges occur, the client has an idea of the network
delay and can estimate the time based only on broadcast packets. If this interchange is not
desirable, it can be disabled using NTP’s access control features. The -r option can be
used when xntpd is started to hardwire a delay if the interchange fails because of access
control issues or other problems.
To allow clocks to quickly achieve high accuracy, yet avoid overshooting the time with
large time adjustments, NTP uses a system where large adjustments occur quickly and
small adjustments occur over time. For small time differences (less than 128 ms), NTP
uses a gradual adjustment. This is called slewing. For larger time differences, the
adjustment is immediate. This is called stepping. If the accuracy of the clock becomes too
insufficient (off by more than 17 minutes), NTP aborts the NTP daemon, with the
assumption that something is wrong with either the server or client. To accurately
synchronize with a server, the client needs to avoid step adjustments.
Once down to the minimum sane servers, the system considers these to be the candidates
for selection as the One True Clock. NTP will then sync to this clock. By default the
minimum required number of good servers (minsane) is three, and the minimum required
numbers of candidates (minclock) is one. However, this has been known to have very
undesired consequences. The NTP Byzantine algorithm needs four sources so that, if one
of them turns falsetick, the remaining three truechimes can vote it out. The recommended
value for minsane is four and minclock is four, and two less than the total number of
servers.
The Mark VIe control’s NTP has a minsane of two and a minclock of one. The minimum
number of servers is three, and four servers would increase the chances of sane servers.
Also, the NTP client of the designated controller (dual or TMR system) drives the time
for the entire system. The non-designated controllers track the designated controller. It is
possible that the NTP status viewer connected to a non-designated controller will not
display the actual time in the devices. However, the time will be correct if that controller
becomes designated.
• Reduced wiring
• Multi-variables from a single multi-channel field instrument
• Simpler integration
• Easier maintenance
• Device diagnostics
Ultimately, FOUNDATION technology can be the key to greater flexibility and productivity.
This can be achieved by predictive maintenance scheduling and improved upkeep enabled
by the diagnostics, performance analysis data, and operational statistics available.
The ability to interchange a certified device from one manufacturer with a certified device
from another manufacturer (interoperability) is made possible by the fact that devices and
software are conforming to the same standard. PROFIBUS International tests and
registers the devices to ensure interoperability of registered instruments from multiple
vendors. This enables the end user to select the best instruments for the application
regardless of the host system supplier.
The PROFIBUS Master Gateway (PPRF) I/O module has been available for the Mark VIe
control system since 2008. The PPRF module has continued to increase in functionality
and internal component upgrades. The addition of PROFIBUS DPV1 messaging for
device management is available in ControlST* V04.06 or higher.
• Reduced wiring
• Multi-variables from a single multi-channel field instrument
• Simpler integration
• Easier maintenance
• Device diagnostics
Ultimately, PROFIBUS technology can be the key to greater flexibility and productivity.
This can be achieved by predictive maintenance scheduling and improved upkeep enabled
by the diagnostics, performance analysis data, and operational statistics available.
4.8 CANopen
Refer to GEH-6721_Vol_II, the Mark VIe control systems offer a wide range of native I/O types and I/O bus solutions for
chapter PCNO CANopen flexible integration of instrumentation. This includes a CANopen Master Gateway for
Master Gateway. Woodward GS6/16 fuel metering valves on gas turbines. The valve can be applied as a
single valve (single manifold base turbines) or in a multiple valve configuration (dry low
emission turbines). The CANopen Master Gateway (PCNO) complies with the EN
50325-4 standard for embedded control systems. It includes the application layer, and
communication, application, device, and interface profiles. The protocol specifications are
developed and maintained by the Controller Area Network (CAN) in Automation
standards organization comprising 500 companies.
CAN/CSA® 22.2 No. 61010-1-12 Safety Requirements for Electrical Equipment for Measurement, Control, and
Laboratory Use, Part 1: General Requirements
UL 61010-1 (3rd Edition) Safety Standard for Electrical and Electronic Test, Measuring, Controlling, and
Related Equipment – General Requirements
• Mark VIe control equipment must be mounted inside a grounded steel enclosure, with doors that require a tool or key to
open, and 0.86 mm minimum steel thickness. The enclosure must provide a minimum Intrusion Protection of IP 20 and
an internal micro-environment of not more than Pollution Degree 2.
• PE and FE connections must be clearly marked. Customer must connect PE/FE to suitable building ground system
through minimum 120 mm2 (4/0 AWG) gauge wire. Refer to the chapter Installation Guidelines, the section Grounding
for more information.
• Use only Mark VIe family of controllers, IO, switches, and power supplies.
• Customer power supply mains connection terminal boards must be clearly marked with L (Line) and N (Neutral) for each
AC supply feed connection and Hi (+) and Lo (-) for each DC supply feed connection.
• A Power Requirements nameplate with supply source designations, voltage, and rated current shall be located on the
front door of the cabinet with the customer supply mains connections. Refer to the chapter Installation Guidelines, the
section Power Requirements for details and nameplate examples.
• The customer shall provide an easily accessible external disconnect device for each of the mains supplies near the control
panel. The customer shall provide external 30 A two-pole circuit breaker protection for each 120 V ac and 125 V dc
mains and 15 A two-pole circuit breaker protection for each 240 V ac and 220 V dc mains. Circuit breaker can serve as
the Disconnect Device if mounted accessible to the control panel.
• Any accessory outlet / socket must be labeled near the outlet with the max rated current.
• All AC and DC power supply mains must connect thru a Mark VIe Overvoltage Transient Protection and EMI Filter
circuit. These OV and EMI filter circuits are built-in to the JPDB and JPDF Power Distribution Modules. If JPDB/JPDF
are not used to distribute AC and DC power supply mains to the Mark VIe control, then a separate GE Filter Module
246B8279Gx should be used to filter the mains. Refer to GEH-6721 Volume II, the chapter PDM Power Distribution
Modules for more information.
• Elevation shall not exceed 2000 m for compliance to 61010-1.
• Appropriate Warning nameplates shall be applied to the front door of each panel cabinet and shall include appropriate
warning symbols per IEC 61010-1 per Table 1. See examples below. Warning nameplates shall highlight the presence of
electrical circuits that must be disconnected before opening the enclosure for servicing, electrical shock or burn hazard,
Qualified Personnel Only, and include symbols 12 and 14 from IEC 61010-1 Table 1.
! WARNING ! DANGER
This e quipme nt ma y re ce ive e le ctrica l HIGH VOLTAGE
e ne rgy from more tha n one s ource . HAZARD OF ELECTRICAL
S HOCK OR BURN
Additiona l dis conne cts a re loca te d
336A3551P 1, Re v B
The Mark VIe control fulfils the requirements listed in the following table.
Code Description
EN 55011:2009 + A1:2010 ISM equipment - Electromagnetic disturbance characteristics
EN 61000-6-2: 2005 Generic Immunity Industrial Environment
IEC 61000-4-2 Electrostatic Discharge Susceptibility
IEC 61000-4-3 Radiated RF Immunity
IEC 61000-4-4 Electrical Fast Transient Susceptibility
IEC 61000-4-5 Surge Immunity
IEC 61000-4-6 Conducted RF Immunity
IEC 61000-4-11 Voltage Variation, Dips and Interruptions
Warning
The above meets IEC 60204-1 2005, and exceeds IEEE STD 141-1993, and ANSI
C84.1-1989.
Dc Supplies – Operating line variations of -30%, 10% or 140 V dc. This meets IEC
60204-1 2005.
Additional 2% of total rms voltages between live conductors for sum of 6th through 30th
harmonic
Less than 15% of maximum demand load current for harmonics less than 11
Less than 7% of maximum demand load current for harmonics between 11 and 17
Less than 6% of maximum demand load current for harmonics between 17 and 23
Less than 2.5% of maximum demand load current for harmonics between 23 and 35
5.3.3.5 Surge
Withstand 2 kV common mode, 1 kV differential mode
This meets IEC 61000-4-5 (ENV50142), and ANSI C62.41 (combination wave).
5.4.2 Enclosures
It is recommended that enclosures not be placed in direct sunlight, and locations near heat
generating equipment need to be evaluated. Since the internal temperature increases from
the bottom to the top of the enclosure, limiting the temperature at the top is a key design
objective.
For all types of enclosure systems, it is important to highlight the potential effect of
changes from the original design. GE designed enclosure systems are engineered to
maintain the Mark VIe system components within their specified temperature ratings.
Modifying the enclosure or adding additional equipment to the enclosure could
potentially compromise the thermal design.
While effective enclosure cooling can be accomplished in many ways, including active
cooling like air conditioners, thermoelectric coolers, or vortex coolers, most enclosures
are air cooled using one of the following cooling systems. The following are key points to
consider when selecting one of these systems and are not intended to take the place of
proper enclosure thermal analyses.
The equipment should be arranged by following normal wiring practices for separation
of high and low levels, but in a few cases, heat should be considered. Some components
dissipate more heat than others. If there is a significant temperature rise from the bottom
of the enclosure to the top, then electronics with significant heat dissipation should be
mounted lower in the enclosure.
Enclosure Example
For internal enclosure design considerations, most Mark VIe components have an
ambient temperature rating of -30 to 65°C (-22 to 149 °F). The following table lists only
the components with more restrictive ambient ratings.
Mark VIe Equipment with Restrictive Ambient Ratings
Equipment Operating Temperature
UCCA controller 0 to 60°C (32 to 140 °F)
UCCC controller 0 to 50°C (32 to 122 °F)
UCSA controller (also PMVE and PAMC) 0 to 65°C (32 to 149 °F)
UCSBH3A controller
PCNO, PPRF -20 to 55°C (-4 to 131 °F)
PFFA 0 to 55°C (32 to 131 °F)
DACA -30 to 60°C (-22 to 140 °F)
Interconnecting cables can be brought into the cabinet through removable access plates.
Convection cooling of the cabinet requires that conduits be sealed to the access plates. In
addition, air passing through the conduit must be within the acceptable temperature range
as listed previously.
5.4.6 Humidity
The ambient humidity range is 5 to 95% non-condensing. This exceeds EN50178.
†Elevation shall not exceed Equipment elevation is related to the equivalent ambient air pressure:
2000 m for compliance to
61010-1. • Normal operation: 0 to 1000 m (0 to 3280.8 ft) at 101.3 to 89.8 kPa
The extended operation and • Extended operation: 1000 to 3000 m† (3280.8 to 6561.7 ft) at 89.8 to 69.7 kPa
shipping specifications exceed • Shipping: 4600 m (15091.8 ft) at 57.2 kPa max
EN50178.
Note For extended altitude operation, the maximum ambient temperature rating of the
equipment should be reduced by 1°C (3.4 °F) for each additional 410 m (1345 ft) above
1000 m (3280.83 ft). Therefore, an I/O pack rated for 65°C (149 °F) at 1000 m (3280.8 ft)
will be rated for 62.6°C (144.7 °F) at 2000 m (6562 ft).
5.4.8 Contaminants
The control equipment withstands the following concentrations of corrosive gases at 50%
relative humidity and 40°C (104 °F):
This meets EN50178 Section Corrosive Gas Concentration
A.6.1.4 Table A.2 (m).
Sulfur dioxide (SO2) 30 ppb
5.4.9 Vibration
5.4.9.1 Seismic
Universal Building Code (UBC) - Seismic Code section 2312 Zone 4 (Optional)
Note For a list of UL Class 1, Division 2 and Class 1, Zone 2 capable modules, go to the
following internet address: http://www.ul.com.
Select the Certifications link, select the Online Certifications Directory link, type
E207685 into the basic search UL File Number field, and click Search.
General information, such as this document, provides product-specific guidelines for the
equipment. They are intended as supplements to the requisition-specific information.
Requisition documents, such as outline drawings and elementary diagrams provide data
specific to a custom application. Therefore, they reflect the customer’s specific
installation needs and should be used as the primary data source.
These services are not normally included as installation support or in basic startup and
commissioning services displayed below. GE presents installation support options to the
customer during the contract negotiation phase.
The cable and conduit schedule should define signal levels and classes of wiring (refer to
the section, Cable Separation and Routing). This information should be listed in a
separate column to help prevent installation errors.
The cable and conduit schedule should include the signal level definitions in the
instructions. This provides all level restriction and practice information needed before
installing cables.
The conduit and cable schedule should indicate shield terminal practice for each shielded
cable (refer to the section, Connecting the System).
Upon receipt, carefully examine the contents of each shipment and check them with the
packing list. Immediately report any shortage, damage, or visual indication of rough
handling to the carrier. Then notify both the transportation company and GE. Be sure to
include the serial number, part (model) number, GE requisition number, and case number
when identifying the missing or damaged part.
• Place the equipment under adequate cover with the following requirements:
− Keep the equipment clean and dry, protected from precipitation and flooding.
− Use only breathable (canvas type) covering material – do not use plastic.
• Unpack the equipment as described, and label it.
• Maintain the following environment in the storage enclosure:
− Recommended ambient storage temperature limits for the Mark VIe controller
are from -40 to 85°C (-40 to 185 °F).
− Surrounding air free of dust and corrosive elements, such as salt spray or
chemical and electrically conductive contaminants
− Ambient relative humidity from 5 to 95% with provisions to prevent
condensation
− No rodents, snakes, birds or insects
− No temperature variations that cause moisture condensation
Attention
Condensation occurs with temperature drops of 15°C (59 °F) at 50% humidity over a
four-hour period, and with smaller temperature variations at higher humidity.
If the storage room temperature varies in such a way, install a reliable heating system that
keeps the equipment temperature slightly above that of the ambient air. This can include
space heaters or cabinet space heaters (when supplied) inside each enclosure. A 100 W
lamp can sometimes serve as a substitute source of heat.
external, two-pole, thermal, magnetic circuit breaker before entering the control system
enclosure. The breaker should be supplied in accordance with required site codes. The
A
REV
circuit breaker must be included in the installation. If used as the panel disconnect, it must
SHEET
6
be suitably located and easily reachable. The circuit breaker must be marked as the
disconnecting device and suitably located near the equipment for servicing.
Mark VIe control panels / systems may use up to three mains supplies; two for redundant
control power (ac and / or dc) and one auxiliary ac supply for accessories such as panel
109T7428
lights and fans. The following are example mains power supply rating labels used on the
(100 [3.94]) (100
front cabinet door where the panel mains power is to be[3.94])
connected.
DWG NO.
A
SIZE
P0006
Referencing the designators from the rating label, AC1 and optional AC2 may be 120 V
P0002
ac or 240 V ac, 50/60 Hz. DC1 and optional DC2 are 220 V dc supplies that may be used
instead of AC1 and AC2. DC is an optional floating source 125 V dc supply, usually a
battery. AUXAC is used only to supply internal auxiliary appliances, such as fans,
heaters, lights, or socket outlets. The AC1, AC2, DC, DC1, or DC2 mains supplies may
feed one or more Switch Mode Power Supplies to provide 28 V dc control power, or 24 or
48 V dc wetting for contact I/O circuits.
Refer to GEH-6421, Mark VI AC1 and AC2 may also feed one or two optional DACA Line Rectified Power Supplies.
©COPYRIGHT 2013 GE GE CLASS II (INTERNAL CRITICAL)
2013 GE Control, Volume II System Each DACA
ENERGY (USA), is
LLCfactory-set
GEAND/OR
CLASS for eitherCRITICAL)
ITS AFFILIATES.
II (INTERNAL
All rights reserved. The information contained
120 or 240 V ac input, and provides a floating 107 V
A), LLC AND/OR ITS AFFILIATES. GENERAL ELECTRIC COMPANY
Guide, the chapter, Power
ved. The information contained dc output. The DACA
GENERAL
Technical Information belongsDC
herein is GE Energy C & PE COE Proprietary
thatELECTRIC output may be connected through an internal diode SALEM,
COMPANY
to the General with the
VA.
nergy C & PE COE Proprietary
mation that belongs to the General
Distribution Modules GE
(PDM). DC
Electric Company, GE Energy (USA),
optional 125 hasV dc
LLC
supply
and/or
SALEM, VA.
to provide GE OR’d
diode Energydc redundancy to feed Switch Mode
any, GE Energy (USA), LLC and/or
which has been provided solely for
Energy the express reason of restricted private use. All
their affiliates, which been provided solely for
4. Add 2.0 A rms † continuous for each 120 V ac external solenoid powered (inrush 10 A).
Note † These are external and do not create cabinet heat load.
• System Topology
• Cabinet Outline
• Cabinet Layout
• Circuit Diagram
In addition to the installation drawings, site personnel will need the I/O Assignments (I/O
Report).
• Equipment grounding protects personnel from risk of serious or fatal electrical shock,
burn, fire, and/or other damage to equipment caused by ground faults or lightning.
• Signal referencing helps protect equipment from the effects of internal and external
electrical noise, such as lightning or switching surges.
Installation practices must simultaneously comply with all codes in effect at the time and
place of installation, and with all practices that improve the immunity of the installation.
Code requirements for safety of personnel and equipment must take precedence in the
case of any conflict with noise control practices.
Note In addition to technical regulations, guidance from IEEE Std 142-2007 IEEE
Recommended Practice for Grounding of Industrial and Commercial Power Systems, and
IEEE Std 1100-2005 IEEE Recommended Practice for Powering and Grounding
Electronic Equipment are provided by the design and implementation of the system.
This section provides equipment grounding and bonding guidelines for control and I/O
cabinets. These guidelines also apply to motors, transformers, brakes, and reactors. Each
of these devices should have its own grounding conductor going directly to the building
ground grid.
• Ground each cabinet or cabinet lineup to the equipment ground at the source of
power feeding it.
− See NEC Article 250 for sizing and other requirements for the
equipment-grounding conductor.
− For dc circuits only, the NEC allows the equipment-grounding conductor to be
run separate from the circuit conductors.
• With certain restrictions, the NEC allows the metallic raceways or cable trays
containing the circuit conductors to serve as the equipment grounding conductor:
− This use requires that they form a continuous, low-impedance path capable of
conducting anticipated fault current.
− This use requires bonding across loose-fitting joints and discontinuities. See
NEC Article 250 for specific bonding requirements. This chapter includes
recommendations for high-frequency bonding methods.
− If metallic raceways or cable trays are not used as the primary equipment-
grounding conductor, they should be used as a supplementary equipment
grounding conductor. This enhances the safety of the installation and improves
the performance of the SRS.
• The equipment-grounding connection for the control cabinets is plated copper bus or
stub bus. This connection is bonded to the cabinet enclosure using bolting that keeps
the conducting path’s resistance at 1 ohm or less.
• There should be a bonding jumper across the ground bus or floor sill between all
shipping splits. The jumper may be a plated metal plate.
• The non-current carrying metal parts of the equipment covered by this section should
be bonded to the metallic support structure or building structure supporting this
equipment. The equipment mounting method may satisfy this requirement. If
supplementary bonding conductors are required, size them the same as
equipment-grounding conductors.
The guidelines below are for metal-framed buildings. For non-metal framed buildings,
consult the GE factory.
The ground electrode system should be composed of steel reinforcing bars in building
column piers bonded to the major building columns.
• A buried ground ring should encircle the building. This ring should be interconnected
with the bonding conductor running between the steel reinforcing bars and the
building columns.
• All underground, metal water piping should be bonded to the building system at the
point where the piping crosses the ground ring.
• NEC Article 250 requires that separately derived systems (transformers) be grounded
to the nearest effectively grounded metal building structural member.
• Braze or exothermically weld all electrical joints and connections to the building
structure, where practical. This type of connection keeps the required good electrical
and mechanical properties from deteriorating over time.
The goal of the SRS is to hold the electronics at or near case potential to prevent
unwanted signals from disturbing operation. The following conditions must all be met by
an SRS:
• Bonding connections to the SRS must be less than 1/20 wavelength of the highest
frequency to which the equipment is susceptible. This prevents standing waves. In
modern equipment using high-frequency digital electronics, frequencies as high as
500 MHz should be considered. This translates to about 30 mm (1 in).
• SRS must be a good high-frequency conductor. (Impedance at high frequencies
consists primarily of distributed inductance and capacitance.) Surface area is more
important than cross-sectional area because of skin effect. Conductivity is less
important (steel with large surface area is better than copper with less surface area).
• SRS must consist of multiple paths. This lowers the impedance and the probability of
wave reflections and resonance
In general, a good signal referencing system can be obtained with readily available
components in an industrial site. All of the items listed below can be included in an SRS:
In the control cabinet, the base is insulated from the chassis and bonded at one point. The
grounding recommendations, displayed in the following figure, call for the equipment
grounding conductor to be 120 mm2 (4/0 AWG) gauge wire, connected to the building
ground system. The Functional Earth (FE) is bonded at one point to the PE ground using
two 25 mm2 (6 AWG or larger) green/yellow bonding jumpers.
If acceptable by local codes, the bonding jumpers may be removed and a 4/0 AWG
identified insulated wire run from FE to the nearest accessible point on the building
ground system, or to another ground point as required by the local code.
For armored cables, the armor is an additional current carrying braid that surrounds the
internal conductors. This type cable can be used to carry control signals between
buildings. The armor carries secondary lightning-induced earth currents, bypassing the
control wiring, thus avoiding damage or disturbance to the control system. At the cable
ends and at any strategic places between, the armor is grounded to the building ground
through the structure of the building with a 360° mechanical and electrical fitting. The
armor is normally terminated at the entry point to a metal building or machine. Attention
to detail in installing armored cables can significantly reduce induced lightning surges in
control wiring.
Connected equipment - Cable tray installations for connected equipment should pay
special attention to good high-frequency bonding between the cable tray and the
equipment.
Cable spacing - Maintain cable spacing between signal levels in cable drops, as
recommended in the section, Cable Separation and Routing.
Conduit sleeves - Where conduit sleeves are used for bottom-entry cables, the sleeves
should be bonded to the floor decking and equipment enclosure with short bonding
jumpers.
Embedded conduits - Bond all embedded conduits to the enclosure with multiple
bonding jumper connections following the shortest possible path.
Galvanized steel sheet floor decking - Floor decking can serve as a high-frequency
signal reference plane for equipment located on upper floors. With typical building
construction, there will be a large number of structural connections between the floor
decking and building steel. If this is not the case, then an electrical bonding connection
must be added between the floor decking and building steel. The added connections need
to be as short as possible and of sufficient surface area to be low impedance at high
frequencies.
High-frequency bonding jumpers - Jumpers must be short, less than 500 mm (20 in)
and good high-frequency conductors. Thin, wide metal strips are best with length not
more than three times width for best performance. Jumpers can be copper, aluminum, or
steel. Steel has the advantage of not creating galvanic half-cells when bonded to other
steel parts.
Jumpers must make good electrical contact with both the enclosure and the signal
reference structure. Welding is best. If a mechanical connection is used, each end should
be fastened with two bolts or screws with star washers backed up by large diameter flat
washers.
Each enclosure must have two bonding jumpers of short, random lengths. Random
lengths are used so that parallel bonding paths are of different quarter wavelength
multiples. Do not fold bonding jumpers or make sharp bends.
Metallic cable tray - System must be installed per NEC Article 318 with signal level
spacing per the section, Cable Separation and Routing. This serves as a signal reference
structure between remotely connected pieces of equipment. The large surface area of
cable trays provides a low impedance path at high frequencies.
Metal framing channel - Metal framing channel cable support systems also serve as
parts of the SRS. Make certain that channels are well bonded to the equipment enclosure,
cable tray, and each other, with large surface area connections to provide low impedance
at high frequencies.
Power cables - Keep single-conductor power cables from the same circuit tightly bundled
together to minimize interference with nearby signal cables. Keep 3-phase ac cables in a
tight triangular configuration.
Woven wire mesh - Woven wire mesh can serve as a high-frequency signal reference
grid for enclosures located on floors not accessible from below. Each adjoining section of
mesh must be welded together at intervals not exceeding 500 mm (20 in) to create a
continuous reference grid. The woven wire mesh must be bonded at frequent intervals to
building structural members along the floor perimeter.
Conduit terminal at cable trays - To provide the best shielding, conduits containing
level L cables (see Leveling channels) should be terminated to the tray's side rails (steel
solid bottom) with two locknuts and a bushing. Conduit should be terminated to ladder
tray side rails with approved clamps.
Where it is not possible to connect conduit directly to tray (such as with large conduit
banks), conduit must be terminated with bonding bushings and bonded to tray with short
bonding jumpers.
Leveling channels - If the enclosure is mounted on leveling channels, bond the channels
to the woven wire mesh with solid-steel wire jumpers of approximately the same gauge as
the woven wire mesh. Bolt the enclosure to leveling channel, front and rear.
Signal and power levels - Refer to section, Cable Separation and Routing, for
guidelines.
Solid-bottom tray - Use steel solid bottom cable trays with steel covers for low-level
signals most susceptible to noise.
Note Electrical noise from cabling of various voltage levels can interfere with
microprocessor-based control systems, causing a malfunction. If a situation at the
installation site is not covered in this document, or if these guidelines cannot be met,
please contact GE before installing the cable.
The following are specific examples of level L signals used in the control cabling:
Signal input to analog and • All analog and digital signals including LVDTs, Servos, RTDs, Analog Inputs and
digital blocks or to Outputs, and Pyrometer signals
programmable logic control
• Thermocouples are in a special category (Level LS) because they generate millivolt
(PLC)-related devices should
signals with very low current.
be run as shielded twisted-pair
(for example, input from • Network communication bus signals: Ethernet, IONet, UDH, PDH, RS-232C, and
RTDs). RS-422
• Phone circuits
• Contact inputs
• Relay outputs
• Solenoid outputs
• Potential transformer (PT) and current transformer (CT) circuits
Note Flame detector (GM) type signals, 335 V dc, and Ultraviolet detectors are a special
category (Level HS). Special low capacitance twisted shielded pair wiring is required.
S Special handling of specified levels can require special spacing of conduit and trays.
Check dimension chart for levels. These wires include:
If there is no class code, there are no grouping restrictions within designated levels
Cables can be marked by any means that makes the level easy to recognize (for example,
coding or numbering). Conduit and trays should be marked at junction points or at
periodic intervals.
• All cables of like signal levels and power levels must be grouped together in like
cableways.
• In general, different levels must run in separate cableways, as defined in the different
levels. Intermixing cannot be allowed, except as noted by exception.
• Interconnecting wire runs should carry a level designation.
• If wires are the same level and same type signal, group those wires from one cabinet
to any one specific location together in multiconductor cables.
• When unlike signals must cross in trays or conduit, cross them in 90° angles at
maximum spacing. Where it is not possible to maintain spacing, place a grounded
steel barrier between unlike levels at the crossover point.
• When entering terminal equipment where it is difficult to maintain the specific
spacing guidelines displayed in the following tables, keep parallel runs to a
minimum, not to exceed 1.5 m (5 ft) in the overall run.
• Where the tables display tray or conduit spacing as 0, the levels can be run together.
Spacing for other levels must be based on the worst condition.
• Trays for all levels should be solidly grounded with good ground continuity. Conduit
should provide shielding.
The following general practices should be used for specific levels of cabling:
• When separate trays are impractical, levels L and M can be combined in a common
tray if a grounded steel barrier separates levels. This practice is not as effective as
tray separation, and may require some rerouting at system startup. If levels L and M
are run side-by-side, a 50 mm (1.97 in) minimum spacing is recommended.
• Locate levels L and M trays and conduit closest to the control panels.
• Trays containing level L and level M wiring should have solid galvanized steel
bottoms and sides and be covered to provide complete shielding. There must be
positive and continuous cover contact to side rails to avoid high-reluctance air gaps,
which impair shielding.
• Trays containing levels other than L and M wiring can have ventilation slots or
louvers.
• Trays and conduit containing levels L, M, and H(S) should not be routed parallel to
high power equipment enclosures of 100 kV and larger at a spacing of less than 1.5 m
(5 ft) for trays, and 750 mm (2.5 ft) for conduit.
• Level H and H(S) can be combined in the same tray or conduit but cannot be
combined in the same cable.
• Level H(S) is listed only for information since many customers want to isolate
unfused high voltage potential wires.
• Do not run levels H and H(S) in the same conduit as level P.
• Where practical for level P and/or P(S) wiring, route the complete power circuit
between equipment in the same tray or conduit. This minimizes the possibility of
power and control circuits encircling each other.
Trunnions entering floor mounted operator station cabinets should be kept as short as
possible when used as cableways. This helps minimize parallel runs of unlike levels to a
maximum of 1.5 m (5 ft) before entering the equipment. Where different signal/power
levels are running together for short distances, each level should be connected by cord
ties, barriers, or some logical method to prevent intermixing.
6.6.3.5 RF Interference
To prevent radio frequency (RF) interference, take care when routing power cables near
radio-controlled devices (for example, cranes) and audio/visual systems (public address
and closed-circuit television systems).
6.6.3.6 Suppression
Unless specifically noted otherwise, suppression (for example, a snubber) is required on
all inductive devices controlled by an output. This suppression minimizes noise and
prevents damage caused by electrical surges. Standard relay and solenoid output boards
have adequate suppression.
The main advantages of fiber-optic transmission in the power plant environment are:
• Fiber segments can be longer than copper because the signal attenuation per foot is
less.
• In high-lightning areas, copper cable can pick up currents, which can damage the
communications electronics. Since the glass fiber does not conduct electricity, the use
of fiber-optic segments avoids pickup and reduces lightning-caused outages.
• Grounding problems are avoided with optical cable. The ground potential can rise
when there is a ground fault on transmission lines, caused by currents coming back to
the generator neutral point, or lightning.
• Optical cable can be routed through a switchyard or other electrically noisy area and
not pick up any interference. This can shorten the required runs and simplify the
installation.
• Fiber-optic connections normally have higher signal levels and decreased chances of
packet discard from noise corruption. Typical differences in error rate is 10000 lower
for fiber-optic cables.
• The cost per connection for fiber may now be less than copper cables. Large,
multifiber trunk cables contain many fibers, so cost per foot for each connection may
actually cost less than multiple copper cables.
• Fiber-optic cable with proper jacket materials can be run direct buried in trays or in
conduit.
• High-quality fiber-cable is light, tough, and easily pulled. With careful installation, it
can last the life of the plant.
• The cost, especially for short runs, may be more for a fiber-optic link.
• Inexpensive fiber-optic cable can be broken during installation, and is more prone to
mechanical and performance degradation over time. The highest quality cable avoids
these problems.
6.7.1 Basics
Each fiber link consists of two fibers, one outgoing and the other incoming, to form a
duplex channel. A LED drives the outgoing fiber, and the incoming fiber illuminates a
phototransistor, which generates the incoming electrical signal. 1000SX and 1000LX use
laser diodes instead of LEDs.
Multi-mode fiber, with a graded index of refraction core and outer cladding, is
recommended for the optical links. The fiber is protected with buffering that is the
equivalent of insulation on metallic wires. Mechanical stress is bad for fibers so a strong
sheath is used, sometimes with pre-tensioned Kevlar® fibers to carry the stress of pulling
and vertical runs.
Never look directly into a fiber. Although most fiber links use
LEDs that cannot damage the eyes, some longer links use lasers,
which can cause permanent damage to the eyes.
Warning
Multi-mode fibers are rated for use at 850 nm and 1300 nm wavelengths. Cable
attenuation is between 3.0 and 3.3 dB/km at 850 nm. The core of the fiber is normally
62.5 µ in diameter, with a gradation of index of refraction. The higher index of refraction
is at the center, gradually shifting to a medium index at the circumference. The higher
index slows the light, therefore, a light ray entering the fiber at an angle curves back
toward the center, out toward the other side, and then back toward the center. This ray
travels further but goes faster because it spends most of its time closer to the
circumference where the index is less. The index is graded to keep the delays nearly
equal, thus preserving the shape of the light pulse as it passes through the fiber.
The inner core is protected with a low index of refraction cladding, which for the
recommended cable is 125 µ in diameter. 62.5/125 fiber-optic cable is the most common
type of cable and should be used.
The process of attaching the fiber connectors involves stripping the buffering from the
fiber, inserting the end through the connector, and casting it with an epoxy or other
plastic. This requires a special kit designed for that particular connector. After the epoxy
has hardened, the end of the fiber is cut off, ground, and polished. An experienced person
can complete the process in five minutes.
Installation of the fiber can decrease its performance compared to factory-new cable.
Installers may not make the connectors as well as experts can, resulting in more loss than
planned. The LED light source can get dimmer over time, the connections can get dirty,
the cable loss increases with aging, and the receiver can become less sensitive. For all
these reasons, there must be a margin between the available power budget and the link
loss budget, of a minimum of 3 dB. Having a 6 dB margin is more comfortable, helping
assure a fiber link that will last the life of the plant.
• Install the fiber-optic cable in accordance with all local safety codes. Polyurethane
and PVC are two possible options for cable materials that might NOT meet the local
safety codes.
• Select a cable strong enough for indoor and outdoor applications, including direct
burial.
• Adhere to the manufacturer's recommendations on the minimum bend radius and
maximum pulling force.
• Test the installed fiber to measure the losses. A substantial measured power margin is
the best proof of a high-quality installation. Use trained people for the installation. If
necessary, hire outside contractors with fiber LAN installation experience.
• The fiber switches and converters need reliable power, and should be placed in a
location that minimizes the amount of movement they must endure, yet keep them
accessible for maintenance.
The following figure displays the differences between multi-mode and single-mode cable
types with a typical 62.5/125 µm MMF segment.
In the SMF cable, the aperture is reduced to ~9 µm, comparable to the 1500 µm
wavelength of transmission. In this small aperture, there is little difference in the angle of
incidence of the light and as such, the light propagates with little dispersion. The
attenuation is the main property that degrades the signal and as such, much greater
distances are achievable. The main advantage of SMF cable over traditional MMF cable
in the power plant environment is that fiber-optic segments can now be longer than 2000
m (6561.68 ft) because the signal attenuation per foot is less.
GE ESWx Switch
In a typical SMF application, each 8624 switch is connected to its local network by
multi-mode fiber (could be copper 10/100Base-T/TX.) Each switch has a SMF interface
that is used to connect to the single-mode fiber link. The distance between the two
switches can then be up to 15 km (9.32 mi). The topology would be identical if AT-8724
switches are used, except that AT-A41/SC modules are used for the SMF interfaces.
Fiber-optic Cable:
Each of these cables are SMF 8.3/125 um Core/Cladding diameter with a numeric
aperture of 0.13.
Fiber-optic Connectors:
Note Wires with appropriate temperature ratings must be used, especially in applications
where the internal panel ambient temperature can exceed 60°C (140 °F).
It is standard practice to use shielded cable with control equipment. Shielding provides
the following benefits:
Note The specifications listed are for sensitive computer-based controls. Cabling for less
sensitive controls should be considered on an individual basis.
Never look directly into a fiber. Although most fiber links use
light-emitting diodes, which cannot damage the eyes, some
longer links use lasers, which can cause permanent eye damage.
Warning
The grounded shield bars provide an equipotential ground plane to which all cable shield
drain wires should be connected, with as short a pigtail as practical. The length should not
exceed 5 cm (2 in) to reduce the high-frequency impedance of the shield ground.
Reducing the length of the pigtail should take precedence over reducing the length of
exposed wire within the cabinet. Pigtails should not be connected except at the grounding
bars provided, to avoid loops and maintain a radial grounding system. Shields should be
insulated up to the pigtail. In most instances, shields should not be connected at the far
end of the cable, to avoid circulating power-frequency currents induced by pickup.
A small capacitor can be used to ground the far end of the shield, producing a hybrid
ground system, improving noise immunity. Shields must continue across junction boxes
between the control and the turbine, and should match up with the signal they are
shielding. Avoid hard grounding the shield at the junction boxes, but small capacitors to
ground at junction boxes may improve immunity.
If the connection within a building and the sites share a common ground, it is acceptable
to use 100Base-TX connections. If connecting between buildings, or there are differences
in ground potential within a building, or distances exceed 100 m (328 ft), then
100Base-FX fiber is required.
For equipment grounding Inspect the cabinet components for any damage possibly occurring during shipping.
instructions, refer to the Check for loose cables, wires, connections, or loose components, such as relays or
section, Grounding. retainer clips. Report all damage that occurred during shipping to GE Product Service.
The following steps should be completed to check the cabinet wiring and circuits.
Verifying that the 125 V dc is properly grounded. A qualified person using appropriate
safety procedures and equipment should make tests. Measure the current from first the
P125 V dc, and then the N125 V dc, using a 2000 Ω, 10 W resistor to the protective
conductor terminal of the Mark VIe control in series with a dc ammeter. The measured
current should be 1.7 to 2.0 mA, (the tolerance will depend on the test resistor and the
JPDF tolerances). If the measured current exceeds 2.0 mA, the system must be cleared of
the extra ground(s). A test current of about 65 mA, usually indicates one or more hard
grounds on the system, while currents in multiples of 1 mA usually indicate more than
one BJS jumper is installed.
Note At this point the system is ready for initial application of power.
Features include:
• Alarms
• Events
• Holds
• SOE
• Diagnostics
• WorkstationST Server
• Signal database
The WorkstationST server is the hub of the system, channeling data between the UDH
and the PDH, and providing data support and system management. The server also has
the responsibility for device communication for both internal and external data
interchanges.
The Signal database establishes signal management and definition for the control system,
provides a single repository for system alarm messages and definitions, and contains
signal relationships and correlation between the controllers and I/O. It is used for system
configuration, but not required for running.
• Dynamic graphics
• Alarm displays
• Process variable trending
• Point control panel right-click menu
• HMI access security
The graphic system performs key HMI functions and provides the operator with real time
process visualization and control using the following:
CimEdit is an object-oriented program that creates and maintains the users graphic
screen displays. Editing and animation tools, with the familiar Windows environment,
provide an intuitive, easy to use interface. Features include:
Alarm Viewer provides alarm management functions, such as sorting and filtering by
priority, by unit, by time, or by source device. Also supported are configurable alarm field
displays, and embedding dynamically updated objects into CimView screens.
Third-party interfaces allow Trending, based on ActiveX® technology, gives users data analysis capabilities. Trending
the HMI to exchange data with uses data collected by the HMI, or data from other third-party software packages or
DCS systems, PLCs, I/O interfaces. Trending includes multiple trending charts per graphic screen with unlimited
devices, and other computers. pens per chart, and the operator can resize or move trend windows to convenient locations
on the display.
Point control panel is a right-click menu, which is normally used during troubleshooting
to access variables for trends and watch windows.
Function Description
Data collection Data is collected over the UDH and Modbus.
Data storage Stored in the Exception database for SOE, events, and alarms
Data retrieval Data can be retrieved through a web browser or a standard trend
screen.
Data points that are configured for collection in the archives are sampled once per second
from the OPC® DA Server. Analog data that exceeds an exception Deadband and digital
data that changes state is sent to the archives. A third-party compression algorithm is used
to determine when to save a value. This allows the Historian to keep orders of magnitude
and more available data online than in conventional scanned systems.
7.6 uOSM
The Universal Onsite Monitor (uOSM) is a separate computer module that is the GE
Services portal to provide warranty and contractual service offerings. The uOSM has no
operator interface and does not expose its data directly to the end user. The uOSM
monitors turbine-operating data and periodically uploads the data to the GE Services
Operations Center for analysis. Fleet analysis data is collected to improve overall system
availability, performance, and individual event information for root cause analysis.
Balance of Plant (BOP) Plant equipment other than the turbine that needs to be
controlled.
baud A unit of data transmission. Baud rate is the number of bits per second
transmitted.
bit Binary Digit. The smallest unit of memory used to store only one piece of
information with two states, such as One/Zero or On/Off. Data requiring more than two
states, such as numerical values 000 to 999, requires multiple bits (see Word).
block Instruction blocks contain basic control functions, which are connected together
during configuration to form the required machine or process control. Blocks can perform
math computations, sequencing, or continuous control. The toolbox receives a description
of the blocks from the block libraries.
Boolean Digital statement that expresses a condition that is either True or False. In the
toolbox, it is a data type for logical signals.
byte A group of binary digits (bits); a measure of data flow when bytes per second.
Computer Operator Interface (COI) Interface that consists of a set of product and
application specific operator displays running on a small cabinet computer hosting
Embedded Windows NT®.
configure To select specific options, either by setting the location of hardware jumpers
or loading software parameters into memory.
data server A computer that gathers control data from input networks and makes the
data available to computers on output networks.
Ethernet Global Data (EGD) Control network and protocol for the controller.
Devices share data through EGD exchanges (pages).
fanned input An input to the terminal board that is connected to all three TMR I/O
boards.
firmware The set of executable software that is stored in memory chips that hold their
content without electrical power, such as EEPROM.
forcing Setting a live signal to a particular value, regardless of the value blockware or
I/O is writing to that signal.
frame rate Basic scheduling period of the controller encompassing one complete
input-compute-output cycle for the controller. It is the system-dependent scan rate.
function The highest level of the blockware hierarchy, and the entity that corresponds
to a single .tre file.
I/O device Input/output hardware device that allows the flow of data.
I/O drivers Interface the controller with input/output devices, such as sensors, solenoid
valves, and drives, using a choice of communication networks.
item A line of hierarchy of the outline view of the toolbox application, which can be
inserted, configured, and edited (such as Function or System Data).
LS2100 Static Starter control GE’s current state-of-the-art control for static starter
control systems, used to bring a gas turbine up to starting speed.
module A collection of tasks that have a defined scheduling period in the controller.
online Online mode provides full CPU communications, allowing data to be both read
and written. It is the state of the toolbox when it is communicating with the system for
which it holds the configuration. Online is also, a download mode where the device is not
stopped and then restarted.
period The time between execution scans for a Module or Task. Also a property of a
Module that is the base period of all of the Tasks in the Module.
pin Block, macro, or module parameter that creates a signal used to make
interconnections.
Plant Data Highway (PDH) Ethernet communication network between the HMI
Servers and the HMI Viewers and workstations.
Relay Ladder Diagram (RLD) A ladder diagram that represents a relay circuit.
Power is considered to flow from the left rail through contacts to the coil connected at the
right.
server A computer that gathers data over the Ethernet from plant devices, and makes
the data available to computer-based operator interfaces known as viewers.
simplex Operation that requires only one set of control and I/O, and generally uses
only one channel. The entire Mark VIe control system can operate in simplex mode.
simulation Running a system without all of the configured I/O devices by modeling
the behavior of the machine and the devices in software.
Software Implemented Fault Tolerance (SIFT) A technique for voting the three
incoming I/O data sets to find and inhibit errors. Note that control also uses output
hardware voting.
trend A time-based plot to show the history of values, similar to a recorder, available
with the ControlST Historian and the ToolboxST application.
Triple Module Redundancy (TMR) An operation that uses three identical sets of
control and I/O (channels R, S, and T) and votes the results.
Unit Data Highway (UDH) Connects the controllers, static starter control system,
excitation control system, PLCs, and other GE provided equipment to the HMI Servers.
Index Electrical 85
Electromagnetic Compatibility
Directive (EMC) 85
A Elevation 92
Environment 85
Acronyms and Abbreviations 9
Operating 91
Applications 7
Ethernet
Global Data (EGD) 72
C GSM 69
cable
fiber-optic 122–125, 135 F
Guidelines 123
Fiber-Optic Cables 122
Installation 125
Forcing 47
Instrument 134
Frequency Variations 86
Routing Guidelines 121
RS-232C 134
Separation and Routing 116 G
shielded 131–132 Grounding 107
SMF 135 Notes on 113
UTP 133 System 109
codes 83 Guidelines
Command Action 49 Cableway Spacing 118
Communication
Loss 45
Communications 60 H
RS-232C 134 Harmonic Distortion 86
Component Sources 130 Historian 143
configuration configuration 143
dual 74 Data collection 146
dual network 52 Human-machine Interface (HMI) 61
TMR 73
Contaminants 92
Control Data Highway (CDH) 58
I
controller I/O 62
overview 12 Pack 14
Controller Peer 47
UCCx 13 Wiring 136
ControlST Installation 95
Historian 143 Support Drawings 102
CPCI 11 IONet Components 127
D L
Data Highway Line Variations 86
Plant 54 Low Voltage Directive 85
Directive
Electromagnetic Compatibility 85 M
Disagreement Detector 47
Dual Controller 29 Median Value Analog 46
MTBF 41
O
overspeed protection 49
P
Power Requirements 100
Power Sources 26, 100
Processing
Input 34
Output 38
R
Rate of Response 47
redundancy
network 53
Redundancy Options 27
S
Safety Standards 83
Simplex Controller 28
standards 83
State Exchange 45
Storage 99
Supply Voltage 86
system
Considerations 124
T
Terminal Board 15
Turbine Protection 49
Two Out of Three Logic 46
U
UDH Communicator 56
V
Vibration 92
Voltage Unbalance 86
Voting 45