2016-06-16 Selectivity Tables PDF

Download as pdf or txt
Download as pdf or txt
You are on page 1of 31

Table of contents

3VA Selectivity tables

1 3WL air circuit breaker - 3VA molded case circuit breaker


→ 1.1 3WL1 - 3VA1
→ 1.2 3WL1 - 3VA2
2 3VA molded case circuit breakers - 3VA molded case circuit breakers
→ 2.1 3VA2 - 3VA1
→ 2.2 3VA2 - 3VA2
3 3VA molded case circuit breakers - 3RV motor starter protector
→ 3.1 3VA1 - 3RV
→ 3.2 3VA2 - 3RV
4 3VA molded case circuit breakers - miniature circuit breaker
→ 4.1 3VA1 - 5SL
→ 4.2 3VA1 - 5SY
→ 4.3 3VA2 - 5SL
→ 4.4 3VA2 - 5SP4
→ 4.5 3VA2 - 5SY
5 3VA molded case circuit breakers - LV HRC fuse
→ 5.1 3VA1 - 3NA
→ 5.2 3VA2 - 3NA
6 3VL molded case circuit breakers - 3VA molded case circuit breakers
→ 6.1 3VL - 3VA1
→ 6.2 3VL - 3VA2
7 3NA LV HRC fuse - 3VA molded case circuit breakers
→ 7.1 3NA - 3VA1
→ 7.2 3NA - 3VA2

Selektivitätstabellen_en_06_2016.xlsxIntroduction 1 von 31 Druckdatum:08.06.2016


SIEMENS AG Upstream 3WL1 air circuit breaker *)
Limit current with selectivity Is [kA]
for 230 / 415 V AC Line protection
acc. to IEC 60947-2
Trip Unit ETU15B ETU25B / ETU27B ETU45B / ETU76B

Edition 05/2016 Icu [kA] 55 / 66 / 80 / 85 / 100 / 130 / 150


1000
250
1250 1600
315
1600 2000
400
2500 2000 2500
Trip Unit

Icu [kA]
500
Size

In [A] 630 800 1000 1250 1600 2000 3200 250 315 400 500 630 800 2500 3200
630
4000 3200 4000
800
4000 5000
1000
5000 6300
1250
6300
16
20
9.4 T T T T T T 9.3 T T T T T T T T
25
32
16 (B)

40
50
63 8.6 13 T T T T T 8.5 13 T T T T T T T
80
100
16
20
9.4 20 T T T T T 9.3 19 T T T T T T T
25
32
TM210

25 (N)
100 A

40
50
63 8.6 13 T T T T T 8.5 13 T T T T T T T
80
100
16
20
9.4 20 T T T T T 9.3 19 T T T T T T T
25
32
36 (S)

40
50
63 8.6 13 25 T T T T 8.5 13 25 T T T T T T
80
100
16
20
9.4 20 T T T T T 9.3 19 T T T T T T T
25
32
40
25 (N)

50
63 8.6 13 T T T T T 8.5 13 T T T T T T T
Line protection
Downstream 3VA1 molded case circuit breaker

80
100
125
7.2 12 19 T T T T 7.1 12 19 T T T T T T
160
16
20
TM210 / TM220 / TM240

9.4 20 T T T T T 9.3 19 T T T T T T T
25
32
40
36 (S)
160 A

50
63 8.6 13 25 T T T T 8.5 13 25 T T T T T T
80
100
125
7.2 12 19 T T T T 7.1 12 19 T T T T T T
160
16
20
9.4 20 44 T T T T 9.3 19 44 T T T T T T
25
55 (M) / 70 (H)

32
40
50
63 8.6 13 25 42 T T T 8.5 13 25 42 T T T T T
80
100
125
7.2 12 19 40 70 T T 7.1 12 19 40 70 T T T T
160
160
70 (H) 25 (N) / 36 (S) / 55 (M)

5.3 7.9 16 20 24 T T 5.3 7.6 16 20 24 T T T T


200
TM240

250 5.3 7.9 16 20 24 T T 7.6 16 20 24 T T T T


250 A

160
5.3 7.9 16 20 24 55 T 5.3 7.6 16 20 24 55 T T T
200
250 5.3 7.9 16 20 24 55 T 7.6 16 20 24 55 T T T
32 9.4 20 44 T T T T 9.3 19 44 T T T T T T
55 (M) / 70 (H)

40
TM120M

50
160 A
Starter protection

63 8.6 14 24 42 T T T 8.5 13 24 42 T T T T T
80
100
125 7.2 14 19 40 T T T 7.1 14 19 40 T T T T T
160
70 (H) 55 (M)

5.3 7.9 16 20 24 T T 5.3 7.6 16 20 24 T T T T


TM120M

200
250 A

160
5.3 7.9 16 20 24 55 T 5.3 7.6 16 20 24 55 T T T
200

*) The limit currents with selectivity for the upstream circuit breakers apply to the maximum value Iimax for adjustable trip units.

Selektivitätstabellen_en_06_2016.xlsx1.1) 3WL1 - 3VA1 2 von 31 Druckdatum: 08.06.2016


SIEMENS AG Upstream 3WL1 air circuit breaker *)
Limit current with selectivity Is [kA]
for 230 / 415 V AC Line Protection
acc. to IEC 60947-2
Trip Unit ETU15B ETU25B / ETU27B ETU45B / ETU76B

Edition 05/2016 Icu [kA] 55 / 66 / 80 / 85 / 100 / 130 / 150 55 / 66 / 80 / 85 / 100 / 130 / 150 55 / 66 / 80 / 85 / 100 / 130 / 150
250
1600 1600
315
2000 2000
400
2500 2500
Trip Unit

Icu [kA]

500
In [A]
Size

630 800 1000 1250 1600 2000 2500 3200 4000 250 315 400 500 630 800 1000 1250 3200 3200
630
4000 4000
800
5000 5000
1000
6300 6300
1250
55 (M) / 85 (H) / 110(C) 55 (M) / 85 (H) / 110(C) 55 (M) / 85 (H) / 110(C) 55 (M) / 85 (H) / 110(C) 55 (M) / 85 (H) / 110(C)

25
40
100 A

8.5 11 17 32 90 T T T T 8.4 11 17 32 87 T T T T T T
63
100
ETU320 / ETU330 / ETU340 / ETU350 / ETU550 / ETU560 / ETU850 / ETU860

25
40
160 A

63 6.6 10 13 21 42 85 T T T 6.5 10 13 21 40 85 T T T T T
Downstream 3VA2 molded case circuit breaker

100
160
Line protection

160
250 A

4.7 6.6 11 17 29 55 T T T 4.6 6.4 11 17 28 55 T T T T T


250

250
400 A

5 6.9 9.6 15 26 47 T T 5.5 6.9 9.6 15 26 47 T T T T


400

400
630 A

500 8.7 9.8 22 33 67 T 13 22 33 62 T T T


630

*) The limit currents with selectivity for the upstream circuit breakers apply to the maximum value I imax for adjustable trip units.

Selektivitätstabellen_en_06_2016.xlsx 1.2) 3WL1 - 3VA2 3 von 31 Druckdatum: 08.06.2016


SIEMENS AG Upstream 3VA2 molded case circuit breaker *)
Limit current with selectivity Is [kA]
for 230 / 415 V AC Line protection
acc. to IEC 60947-2
Trip Unit ETU320 / ETU330 / ETU340 / ETU350 / ETU550 / ETU560 / ETU850 / ETU860

Edition 05/2016 Size 160 A 250 A 400 A 630 A

Icu [kA] 55 (M) / 85 (H) / 110 (C)


Trip Unit

Icu [kA]
Size
In [A] 100 160 160 250 250 400 400 500 630

16 36 36 36 36 T T T T T
20 36 36 36 36 T T T T T
16 (B) / 25 (N) / 36 (S)

25 36 36 36 36 T T T T T
32 36 36 36 36 T T T T T
100 A

40 2.9 4.4 36 36 T T T T T
50 2.9 4.4 36 36 T T T T T
63 2.9 4.4 36 36 T T T T T
80 4.4 36 36 T T T T T
100 4.4 36 36 T T T T T
16
36 36 36 36 T T T T T
25 (N) / 36 (S) / 55 (M) / 70 (H)

20 36 36 36 36 T T T T T
25 36 36 36 36 T T T T T
TM210 / TM220 / TM240

32 36 36 36 36 T T T T T
Downstream 3VA1 molded case circuit breaker

Line protection

40 2.9 4.4 36 36 T T T T T
160 A

50 2.9 4.4 36 36 T T T T T
63 2.9 4.4 36 36 T T T T T
80 4.4 36 36 T T T T T
100 4.4 36 36 T T T T T
125 36 T T T T T
160 36 T T T T T
25 (N) / 36 (S) / 55 (M) / 70 (H)

160 13 12 T T T
250 A

200 12 T T T

250 12 T T T

32 T T T T T T T
40 T T T T T T T
55 (M) / 70 (H)

50 T T T T T T T
Starter protection

160 A

63 T T T T T T T
TM120M

80 T T T T T T T
100 T T T T T T T
125 T T T T T T T
160 13 12 T T T
55 (M)
70 (H)
250 A

200 12 T T T

*) The limit currents with selectivity for the upstream circuit breakers apply to the
maximum value Iimax for adjustable trip units.

Selektivitätstabellen_en_06_2016.xlsx2.1) 3VA2 - 3VA1 4 von 31 Druckdatum: 08.06.2016


SIEMENS AG Upstream 3VA2 molded case circuit breaker *)
Limit current with selectivity Is [kA]
for 230 / 415 V AC Line protection
acc. to IEC 60947-2
Trip Unit ETU320 / ETU330 / ETU350 / ETU550 / ETU560 / ETU850 / ETU860 ETU340

Edition 05/2016 Size 250 A 400 A 630 A 250 A 400 A 630 A

Icu [kA] 55 (M) / 85 (H) / 110 (C)


Trip Unit

Icu [kA]
Size
In [A] 160 250 250 400 400 500 630 160 250 250 400 500 630

25 55 55 T T T T T 55 55 T T T T
55 (M) / 85 (H) / 110 (C)
ETU320 / ETU330 / ETU350 / ETU550 / ETU560 / ETU850 / ETU860

40 55 55 T T T T T 55 55 T T T T
100 A

63 55 55 T T T T T 55 55 T T T T

100 55 55 T T T T T 55 55 T T T T

25 5.7 6 T T T T T 5.7 6 T T T T
55 (M) / 85 (H) / 110 (C)

40 5.7 6 T T T T T 5.7 6 T T T T
160 A

63 5.7 6 T T T T T 5.7 6 T T T T

100 5.7 6 T T T T T 5.7 6 T T T T

160 6 T T T T T 6 T T T T
55 (M) / 85 (H) / 110 (C) 55 (M) / 85 (H) / 110 (C)
Downstream 3VA2 molded case circuit breaker

160 3.2 T T T T T 3.2 T T T T


250 A

250 T T T T T T
Line protection

25 55 55 T T T T T 55 55 T T T T

40 55 55 T T T T T 55 55 T T T T
100 A

63 55 55 T T T T T 55 55 T T T T

100 55 55 T T T T T 55 55 T T T T

25 5.7 6 T T T T T 5.7 6 T T T T
55 (M) / 85 (H) / 110 (C)

40 5.7 6 T T T T T 5.7 6 T T T T
ETU340

160 A

63 5.7 6 T T T T T 5.7 6 T T T T

100 5.7 6 T T T T T 5.7 6 T T T T

160 6 T T T T T 6 T T T T
55 (M) / 85 (H) / 110 (C)

160 3.2 T T T T T 3.2 T T T T


250 A

250 T T T T T T

Selektivitätstabellen_en_06_2016.xlsx2.2) 3VA2 - 3VA2 5 von 31 Druckdatum: 08.06.2016


SIEMENS AG Upstream 3VA2 molded case circuit breaker *)
Limit current with selectivity Is [kA]
for 230 / 415 V AC Line protection
acc. to IEC 60947-2
Trip Unit ETU320 / ETU330 / ETU350 / ETU550 / ETU560 / ETU850 / ETU860 ETU340

Edition 05/2016 Size 250 A 400 A 630 A 250 A 400 A 630 A

Icu [kA] 55 (M) / 85 (H) / 110 (C)


Trip Unit

Icu [kA]
Size
In [A] 160 250 250 400 400 500 630 160 250 250 400 500 630

25 5.7 6 T T T T T 5.7 6 T T T T
55 (M) / 110 (C)

40 5.7 6 T T T T T 5.7 6 T T T T
160 A

63 5.7 6 T T T T T 5.7 6 T T T T
ETU350M

100 5.7 6 T T T T T 5.7 6 T T T T


55 (M)
250 A

110 110 (C) 55 (M) 110

160 3.8 4.8 T T T 4.7 T T T


(C)

250 T T T T T T
400 A

250 87 87 87 87 87 87
Motor protection

55 (M)
630 A

400
(C)
Downstream 3VA2 molded case circuit breaker

25 5.7 6 T T T T T 5.7 6 T T T T
55 (M) / 110 (C)

40 5.7 6 T T T T T 5.7 6 T T T T
160 A

63 5.7 6 T T T T T 5.7 6 T T T T
ETU860M

100 5.7 6 T T T T T 5.7 6 T T T T


55 (M)
250 A

110 110 (C) 55 (M) 110

160 3.8 4.8 T T T 4.7 T T T


(C)

250 T T T T T T
400 A

250 87 87 87 87 87 87
55 (M)
630 A

400
(C)

25 5.7 6 T T T T T 5.7 6 T T T T

40 5.7 6 T T T T T 5.7 6 T T T T
160 A
Starter protection

63 5.7 6 T T T T T 5.7 6 T T T T
ETU310M

110 (C)

100 5.7 6 T T T T T 5.7 6 T T T T


630 A 400 A 250 A

160 3.8 4.8 T T T 4.7 T T T

250 87 87 87 87 87 87

400

*) The limit currents with selectivity for the upstream circuit breakers apply to the maximum value I imax for adjustable trip units.

Selektivitätstabellen_en_06_2016.xlsx2.2) 3VA2 - 3VA2 6 von 31 Druckdatum: 08.06.2016


SIEMENS AG Upstream 3VA1 molded case circuit breaker *)
Limit current with selectivity Is [kA]
for 230 / 415 V AC Line protection
acc. to IEC 60947-2
Trip Unit TM210 / TM220 TM240

Edition 05/2016 Size 100 A 160 A 250 A

Icu [kA] 16 (B) / 25 (N) / 36 (S) 25 (N) / 36 (S) / 55 (M) / 70 (H) 25 (N) / 36 (S) / 55 (M) / 70 (H)
16 16
Trip Unit

Icu [kA]
20 20
Size

In [A] 40 50 63 80 100 40 50 63 80 100 125 160 160 200 250


25 25
32 32
1 T T T T T T T T T T T T T T T T T
1.25 T T T T T T T T T T T T T T T T T
1.6 T T T T T T T T T T T T T T T T T
2 T T T T T T T T T T T T T
100

2.5 T T T T T T T T T
3.2 T T T T T T T
S00

4 T T T T T
5 T T T T
6.3 T T T
8 T T T
10 T T T
53

12 T T T
1 T T T T T T T T T T T T T T T T T
1.25 T T T T T T T T T T T T T T T T T
1.6 T T T T T T T T T T T T T T T T T
2 T T T T T T T T T T T T T T T T T
Downstream 3RV1 motor starter protector

2.5 25 T T T T T 25 T T T T T T T T T T
3.2 16 22 T T 16 22 T T T T T T T
100

4 T T T T T T T T T
5 16 16 T T T T T
S0

6.3 22 43 T T T
8 17 20 T T T
TMTU

10 T T T
12.5 T T T
16 T T T
20 T T T
50

22 T T T
25 T T T
16 T T T
20 T T T
25 T T T
32 T T T
S2

50

40 T T T
45 T T T
50 T T T
16 T T T
20 T T T
25 T T T
32 T T T
50 / 100

40 6.4 7.3 11
S3

50 5.8 6.6 11
63 4.7 5.6 6.8
75 5.2 6.4
90 5.4
100 5.1
0.16 T T T T T T T T T T T T T T T T T
0.2 T T T T T T T T T T T T T T T T T
0.25 T T T T T T T T T T T T T T T T T
0.32 T T T T T T T T T T T T T T T T T
0.4 T T T T T T T T T T T T T T T T T
0.5 T T T T T T T T T T T T T T T T T
0.63 T T T T T T T T T T T T T T T T T
0.8 T T T T T T T T T T T T T T T T T
1 T T T T T T T T T T T T T T T T T
1.25 T T T T T T T T T T T T T T T T T
100
S00

1.6 T T T T T T T T T T T T T T T T T
2 T T T T T T T T T T T T T T T T T
2.5 T T T T T T T T T T T T T T T T T
3.2 T T T T T T T T T T T T T T T
4 T T T T T T T T T T T
Downstream 3RV2 motor starter protector

5 T T T T T T T T T
6.3 T T T T T
8 T T T T T
10 11 T T T
12.5 T T T
16 T T T
55
TMTU

0.63 T T T T T T T T T T T T T T T T T
0.8 T T T T T T T T T T T T T T T T T
1 T T T T T T T T T T T T T T T T T
1.25 T T T T T T T T T T T T T T T T T
1.6 T T T T T T T T T T T T T T T T T
2 T T T T T T T T T T T T T T T T T
2.5 T T T T T T T T T T T T T T T T T
100

3.2 T T T T T T T T T T T T T T T
4 T T T T T T T T T T T
5 T T T T T T T T T
6.3 T T T T T
S0

8 T T T T T
10 11 T T T
12.5 T T T
16 T T T
20 T T T
22 T T T
55

25 T T T
28 T T T
32 T T T
36 T T T
20

40 T T T

*) The limit currents with selectivity for the upstream circuit breakers apply to the maximum value I imax for adjustable trip units.

Selektivitätstabellen_en_06_2016.xlsx3.1) 3VA1 - 3RV 7 von 31 Druckdatum: 08.06.2016


SIEMENS AG Upstream 3VA2 molded case circuit breaker *)
Limit current with selectivity Is [kA]
for 230 / 415 V AC Line protection
acc. to IEC 60947-2
Trip Unit ETU320 / ETU330 / ETU340 / ETU350 / ETU550 / ETU560 / ETU850 / ETU860

Edition 05/2016 Size 100 A 160 A 250 A 400 A 630 A

Icu [kA] 55 (M) / 85 (H) / 110 (C)


Trip Unit

Icu [kA]
Size

In [A] 25 40 63 100 25 40 63 100 160 160 250 250 400 400 500 630

1 T T T T T T T T T T T T T T T T
1.25 T T T T T T T T T T T T T T T T
1.6 T T T T T T T T T T T T T T T T
2 T T T T T T T T T T T T T T T T
100

2.5 1.4 T T T T T T T T T T T T T T T
3.2 T T T T T T T T T T T T T T T T
S00

4 0.9 T T T 2.8 T T T T T T T T T T T
5 1.1 T T T 2.1 T T T T T T T T T T T
6.3 0.7 10 T T 1.8 9.6 T T T T T T T T T T
8 0.7 1.3 T T 1.3 3.1 T T T T T T T T T T
10 0.6 3.1 4.3 T 1.1 3.3 11 T T T T T T T T T
53

12 1 12 T 1.7 9.8 T T T T T T T T T
1 T T T T T T T T T T T T T T T T
1.25 T T T T T T T T T T T T T T T T
1.6 T T T T T T T T T T T T T T T T
2 T T T T T T T T T T T T T T T T
Downstream 3RV1 motor starter protector

2.5 T T T T T T T T T T T T T T T T
3.2 T T T T T T T T T T T T T T T T
100

4 T T T T T T T T T T T T T T T T
5 T T T T T T T T T T T T T T T T
S0

6.3 T T T T T T T T T T T T T T T T
8 T T T T T T T T T T T T T T T T
TMTU

10 6.6 T T T 6.9 T T T T T T T T T T T
12.5 T T T T T T T T T T T T T T
16 T T T T T T T T T T T T T T
20 T T T T T T T T T T T T
50

22 T T T T T T T T T T T T
25 25 25 T T T T T T T T T T
16 T T T T T T T T T T T T T T
20 T T T T T T T T T T T T
25 25 25 T T T T T T T T T T
32 25 25 25 T T T T T T T
S2

50

40 25 25 25 T T T T T T T
45 25 T T T T T T T
50 25 25 25 T T T T T
16 T T T T T T T T T T T T T T
20 T T T T T T T T T T T T
25 25 25 50 50 50 T T T T T T T
32 25 25 25 T T T T T T T
50 /100

40 2.4 2.7 25 T T T T T T T
S3

50 25 25 25 T T T T T
63 25 25 25 T T T T T
75 25 T T T T T
90 25 T T T T T
100 25 T T T T T
0.16 T T T T T T T T T T T T T T T T
0.2 T T T T T T T T T T T T T T T T
0.25 T T T T T T T T T T T T T T T T
0.32 T T T T T T T T T T T T T T T T
0.4 T T T T T T T T T T T T T T T T
0.5 T T T T T T T T T T T T T T T T
0.63 T T T T T T T T T T T T T T T T
0.8 T T T T T T T T T T T T T T T T
1 T T T T T T T T T T T T T T T T
1.25 T T T T T T T T T T T T T T T T
100
S00

1.6 T T T T T T T T T T T T T T T T
2 T T T T T T T T T T T T T T T T
2.5 T T T T T T T T T T T T T T T T
3.2 T T T T T T T T T T T T T T T T
4 T T T T T T T T T T T T T T T T
Downstream 3RV2 motor starter protector

5 T T T T T T T T T T T T T T T T
6.3 T T T T T T T T T T T T T T T T
8 T T T T T T T T T T T T T T T T
10 T T T T T T T T T T T T T T T T
12.5 T T T T T T T T T T T T T T
16 T T T T T T T T T T T T T T
55
TMTU

0.63 T T T T T T T T T T T T T T T T
0.8 T T T T T T T T T T T T T T T T
1 T T T T T T T T T T T T T T T T
1.25 T T T T T T T T T T T T T T T T
1.6 T T T T T T T T T T T T T T T T
2 T T T T T T T T T T T T T T T T
2.5 T T T T T T T T T T T T T T T T
100

3.2 T T T T T T T T T T T T T T T T
4 T T T T T T T T T T T T T T T T
5 T T T T T T T T T T T T T T T T
6.3 T T T T T T T T T T T T T T T T
S0

8 T T T T T T T T T T T T T T T T
10 T T T T T T T T T T T T T T T T
12.5 T T T T T T T T T T T T T T
16 T T T T T T T T T T T T T T
20 T T T T T T T T T T T T
22 T T T T T T T T T T T T
55

25 T T T T T T T T T T T T
28 T T T T T T T T T T
32 T T T T T T T T T T
36 T T T T T T T T T T
20

40 T T T T T T T T T T

Selektivitätstabellen_en_06_2016.xlsx3.2) 3VA2 - 3RV 8 von 32 Druckdatum: 08.06.2016


SIEMENS AG Upstream 3VA2 molded case circuit breaker *)
Limit current with selectivity Is [kA]
for 230 / 415 V AC Line protection
acc. to IEC 60947-2
Trip Unit ETU320 / ETU330 / ETU340 / ETU350 / ETU550 / ETU560 / ETU850 / ETU860

Edition 05/2016 Size 100 A 160 A 250 A 400 A 630 A

Icu [kA] 55 (M) / 85 (H) / 110 (C)


Trip Unit

Icu [kA]
Size

In [A] 25 40 63 100 25 40 63 100 160 160 250 250 400 400 500 630

*) The limit currents with selectivity for the upstream circuit breakers apply to the maximum value imax for adjustable trip units.

Selektivitätstabellen_en_06_2016.xlsx3.2) 3VA2 - 3RV 9 von 32 Druckdatum: 08.06.2016


SIEMENS AG Upstream 3VA1 molded case circuit breaker *)
Limit current with selectivity Is [kA]
for 230 / 415 V AC Line protection
acc. to IEC 60947-2
Trip Unit TM210 / TM220 / TM240

Edition 05/2016 Size 100 A 160 A 250 A

Icu [kA] 16 (B) / 25 (N) / 36 (S) 25 (N) / 36 (S) / 55 (M) / 70 (H) 25 (N) / 36 (S) / 55 (M) / 70 (H)
Characteristic

Icn [kA]

In [A] 16 20 25 32 40 50 63 80 100 16 20 25 32 40 50 63 80 100 125 160 160 200 250

6 0.5 0.5 0.5 0.5 0.7 0.9 1.1 1.8 2.2 0.5 0.5 0.5 0.5 0.7 0.9 1.1 1.8 2.2 T T T T T
10 0.4 0.4 0.4 0.4 0.6 0.9 1 1.6 2 0.4 0.4 0.4 0.4 0.6 0.9 1 1.6 2 3.7 T T T T
13 0.4 0.4 0.4 0.6 0.8 1 1.5 2 0.4 0.4 0.4 0.6 0.8 1 1.5 2 3.6 T T T T
16 0.4 0.4 0.5 0.7 0.9 1.3 1.6 0.4 0.4 0.5 0.7 0.9 1.3 1.6 3 3.7 T T T
20 0.4 0.5 0.7 0.9 1.3 1.6 0.4 0.5 0.7 0.9 1.3 1.6 3 3.6 T T T
4.5
B

25 0.5 0.7 0.9 1.3 1.6 0.5 0.7 0.9 1.3 1.6 2.9 3.5 T T T
32 0.7 0.9 1.3 1.5 0.7 0.9 1.3 1.5 2.5 3 T T T
Downstream 5SL3 miniature circuit breaker

40 0.9 1.3 1.6 0.9 1.3 1.6 2.9 3.4 T T T


50 1.2 1.4 1.2 1.4 2.5 3 T T T
63 1.3 1.3 2.4 2.9 T T T
0.3 T T T T T T T T T T T T T T T T T T T T T T T
0.5 T T T T T T T T T T T T T T T T T T T T T T T
Line protection

1 2.1 2.1 2.1 2.1 T T T T T 2.1 2.1 2.1 2.1 T T T T T T T T T T


1.6 0.9 0.9 0.9 0.9 1.4 2.2 2.9 T T 0.9 0.9 0.9 0.9 1.4 2.2 2.9 T T T T T T T
2 0.7 0.7 0.7 0.7 1 1.5 1.8 3.1 3.6 0.7 0.7 0.7 0.7 1 1.5 1.8 3.1 3.6 T T T T T
3 0.7 0.7 0.7 0.7 0.9 1.2 1.5 2.6 3.1 0.7 0.7 0.7 0.7 0.9 1.2 1.5 2.6 3.1 T T T T T
4 0.7 0.7 0.7 0.7 0.9 1.2 1.4 2.5 2.9 0.7 0.7 0.7 0.7 0.9 1.2 1.4 2.5 2.9 T T T T T
6 0.5 0.5 0.5 0.5 0.7 0.9 1.1 1.8 2.2 0.5 0.5 0.5 0.5 0.7 0.9 1.1 1.8 2.2 T T T T T
8 0.5 0.5 0.5 0.5 0.7 0.9 1.1 1.7 2.1 0.5 0.5 0.5 0.5 0.7 0.9 1.1 1.7 2.1 4 T T T T
4.5
C

10 0.4 0.4 0.4 0.4 0.6 0.9 1 1.6 2 0.4 0.4 0.4 0.4 0.6 0.9 1 1.6 2 3.7 T T T T
13 0.4 0.4 0.4 0.6 0.8 1 1.5 2 0.4 0.4 0.4 0.6 0.8 1 1.5 2 3.6 T T T T
16 0.4 0.4 0.5 0.7 0.9 1.3 1.6 0.4 0.4 0.5 0.7 0.9 1.3 1.6 3 3.7 T T T
20 0.4 0.5 0.7 0.9 1.3 1.6 0.4 0.5 0.7 0.9 1.3 1.6 3 3.6 T T T
25 0.5 0.7 0.9 1.3 1.6 0.5 0.7 0.9 1.3 1.6 2.9 3.5 T T T
32 0.7 0.9 1.3 1.5 0.7 0.9 1.3 1.5 2.5 3 T T T
40 0.9 1.3 1.6 0.9 1.3 1.6 2.9 3.4 T T T
50 1.2 1.4 1.2 1.4 2.5 3 T T T
63 1.3 1.3 2.4 2.9 T T T
1 T T T T T T T T T T T T T T T T T T T T T T T
2 5.5 5.5 5.5 5.5 T T T T T 5.5 5.5 5.5 5.5 T T T T T T T T T T
3 1.1 1.1 1.1 1.1 2.3 4.5 T T T 1.1 1.1 1.1 1.1 2.3 4.5 T T T T T T T T
4 0.8 0.8 0.8 0.8 1.1 1.7 2.2 5 6.5 0.8 0.8 0.8 0.8 1.1 1.7 2.2 5 6.5 T T T T T
6 0.7 0.7 0.7 0.7 0.9 1.4 1.7 3.2 4.2 0.7 0.7 0.7 0.7 0.9 1.4 1.7 3.2 4.2 T T T T T
8 0.7 0.7 0.7 0.7 0.9 1.2 1.5 2.7 3.3 0.7 0.7 0.7 0.7 0.9 1.2 1.5 2.7 3.3 8.9 T T T T
10 0.6 0.6 0.6 0.6 0.8 1.1 1.4 2.3 2.7 0.6 0.6 0.6 0.6 0.8 1.1 1.4 2.3 2.7 6.6 9.3 T T T
13 0.5 0.5 0.5 0.7 1 1.3 2.1 2.5 0.5 0.5 0.5 0.7 1 1.3 2.1 2.5 5.2 6.8 T T T
10
B

16 0.5 0.5 0.7 0.9 1.1 1.9 2.2 0.5 0.5 0.7 0.9 1.1 1.9 2.2 4.2 5.4 T T T
20 0.4 0.6 0.8 1 1.6 2 0.4 0.6 0.8 1 1.6 2 4 5.2 T T T
25 0.6 0.8 1 1.6 2 0.6 0.8 1 1.6 2 3.6 4.6 T T T
32 0.7 0.9 1.4 1.7 0.7 0.9 1.4 1.7 3.1 3.9 T T T
40 0.8 1.4 1.7 0.8 1.4 1.7 3.2 4 T T T
50 1.2 1.5 1.2 1.5 2.6 3.1 T T T
63 1.4 1.4 2.5 3 T T T
0.3 T T T T T T T T T T T T T T T T T T T T T T T
0.5 T T T T T T T T T T T T T T T T T T T T T T T
1 T T T T T T T T T T T T T T T T T T T T T T T
1.6 1.7 1.7 1.7 1.7 3.6 T T T T 1.7 1.7 1.7 1.7 3.6 T T T T T T T T T
Downstream 5SL4 miniature circuit breaker

2 0.9 0.9 0.9 0.9 1.5 2.3 3.3 8.6 T 0.9 0.9 0.9 0.9 1.5 2.3 3.3 8.6 T T T T T T
3 0.8 0.8 0.8 0.8 1.1 1.5 2 4.5 6 0.8 0.8 0.8 0.8 1.1 1.5 2 4.5 6 T T T T T
4 0.7 0.7 0.7 0.7 0.9 1.4 1.8 3.4 4.2 0.7 0.7 0.7 0.7 0.9 1.4 1.8 3.4 4.2 T T T T T
6 0.6 0.6 0.6 0.6 0.8 1.1 1.4 2.4 2.9 0.6 0.6 0.6 0.6 0.8 1.1 1.4 2.4 2.9 7.2 T T T T
8 0.4 0.4 0.4 0.4 0.6 0.8 1 1.6 2 0.4 0.4 0.4 0.4 0.6 0.8 1 1.6 2 4.7 6.1 T T T
Line protection

10
C

10 0.4 0.4 0.4 0.4 0.6 0.8 1 1.6 2 0.4 0.4 0.4 0.4 0.6 0.8 1 1.6 2 4.7 6.1 T T T
13 0.4 0.4 0.4 0.6 0.8 1 1.6 2 0.4 0.4 0.4 0.6 0.8 1 1.6 2 3.6 4.5 T T T
16 0.4 0.4 0.6 0.8 1 1.6 2 0.4 0.4 0.6 0.8 1 1.6 2 3.6 4.5 T T T
20 0.5 0.7 0.9 1.4 1.7 0.5 0.7 0.9 1.4 1.7 3.1 4 T T T
25 0.5 0.7 0.9 1.4 1.7 0.5 0.7 0.9 1.4 1.7 3.1 4 T T T
32 0.7 0.8 1.2 1.5 0.7 0.8 1.2 1.5 2.9 3.5 T T T
40 0.8 1.2 1.5 0.8 1.2 1.5 2.8 3.6 T T T
50 1.1 1.4 1.1 1.4 2.8 3.3 T T T
63 1.4 1.4 2.8 3.3 T T T
0.3 T T T T T T T T T T T T T T T T T T T T T T T
0.5 T T T T T T T T T T T T T T T T T T T T T T T
1 2.5 2.5 2.5 2.5 T T T T T 2.5 2.5 2.5 2.5 T T T T T T T T T T
1.6 1.1 1.1 1.1 1.1 1.7 2.6 3.8 T T 1.1 1.1 1.1 1.1 1.7 2.6 3.8 T T T T T T T
2 0.8 0.8 0.8 0.8 1.3 1.9 2.6 6.3 7.6 0.8 0.8 0.8 0.8 1.3 1.9 2.6 6.3 7.6 T T T T T
3 0.7 0.7 0.7 0.7 1 1.4 1.8 3.3 4.4 0.7 0.7 0.7 0.7 1 1.4 1.8 3.3 4.4 T T T T T
4 0.6 0.6 0.6 0.6 0.8 1.1 1.5 2.7 3.3 0.6 0.6 0.6 0.6 0.8 1.1 1.5 2.7 3.3 7.8 T T T T
6 0.5 0.5 0.5 0.5 0.7 1 1.2 2.2 2.7 0.5 0.5 0.5 0.5 0.7 1 1.2 2.2 2.7 6.2 8.6 T T T
8 0.5 0.7 0.8 1.3 1.7 0.5 0.7 0.8 1.3 1.7 3.3 4.6 T T T
10
D

10 0.5 0.7 0.8 1.3 1.7 0.5 0.7 0.8 1.3 1.7 3.3 4.6 T T T
13 0.5 0.7 0.8 1.3 1.7 0.5 0.7 0.8 1.3 1.7 3.2 3.9 T T T
16 0.5 0.7 0.8 1.3 1.7 0.5 0.7 0.8 1.3 1.7 3.2 3.9 T T T
20 0.5 0.6 0.8 1.2 1.5 0.5 0.6 0.8 1.2 1.5 2.9 3.7 T T T
25 0.5 0.6 0.8 1.2 1.5 0.5 0.6 0.8 1.2 1.5 2.9 3.7 T T T
32 0.6 0.8 1.3 1.6 0.6 0.8 1.3 1.6 3 3.8 T T T
40 1.1 1.4 1.4 2.7 3.2 T T T
50 2.2 2.7 T T T
63 2.2 2.7 T T T

Selektivitätstabellen_en_06_2016.xlsx4.1) 3VA1 - 5SL 10 von 31 Druckdatum: 08.06.2016


SIEMENS AG Upstream 3VA1 molded case circuit breaker *)
Limit current with selectivity Is [kA]
for 230 / 415 V AC Line protection
acc. to IEC 60947-2
Trip Unit TM210 / TM220 / TM240

Edition 05/2016 Size 100 A 160 A 250 A

Icu [kA] 16 (B) / 25 (N) / 36 (S) 25 (N) / 36 (S) / 55 (M) / 70 (H) 25 (N) / 36 (S) / 55 (M) / 70 (H)
Characteristic

Icn [kA]
In [A] 16 20 25 32 40 50 63 80 100 16 20 25 32 40 50 63 80 100 125 160 160 200 250

2 2.2 2.2 2.2 2.2 T T T T T 2.2 2.2 2.2 2.2 T T T T T T T T T T


4 0.6 0.6 0.6 0.6 0.8 1.1 1.4 3.3 4.2 0.6 0.6 0.6 0.6 0.8 1.1 1.4 3.3 4.2 T T T T T
6 0.5 0.5 0.5 0.5 0.7 0.9 1.1 1.8 2.2 0.5 0.5 0.5 0.5 0.7 0.9 1.1 1.8 2.2 4.5 T T T T
10 0.4 0.4 0.4 0.4 0.6 0.9 1 1.6 2 0.4 0.4 0.4 0.4 0.6 0.9 1 1.6 2 3.7 4.7 T T T
13 0.4 0.4 0.4 0.6 0.8 1 1.5 2 0.4 0.4 0.4 0.6 0.8 1 1.5 2 3.6 4.7 T T T
16 0.4 0.4 0.5 0.7 0.9 1.3 1.6 0.4 0.4 0.5 0.7 0.9 1.3 1.6 3 3.7 T T T
B

20 0.4 0.5 0.7 0.9 1.3 1.6 0.4 0.5 0.7 0.9 1.3 1.6 3 3.6 T T T
25 0.5 0.7 0.9 1.3 1.6 0.5 0.7 0.9 1.3 1.6 2.9 3.5 T T T
Downstream 5SL6 miniature circuit breaker

32 0.7 0.9 1.3 1.5 0.7 0.9 1.3 1.5 2.5 3 T T T


40 0.9 1.3 1.6 0.9 1.3 1.6 2.9 3.4 T T T
50 1.2 1.4 1.2 1.4 2.5 3 T T T
63 1.3 2.4 2.9 T T T
0.3 T T T T T T T T T T T T T T T T T T T T T T T
Line protection

0.5 T T T T T T T T T T T T T T T T T T T T T T T
1 2.1 2.1 2.1 2.1 5.2 T T T T 2.1 2.1 2.1 2.1 5.2 T T T T T T T T T
1.6 0.9 0.9 0.9 0.9 1.4 2.2 2.9 T T 0.9 0.9 0.9 0.9 1.4 2.2 2.9 T T T T T T T
2 0.7 0.7 0.7 0.7 1 1.5 1.8 3.1 3.6 0.7 0.7 0.7 0.7 1 1.5 1.8 3.1 3.6 T T T T T
3 0.7 0.7 0.7 0.7 0.9 1.2 1.5 2.6 3.1 0.7 0.7 0.7 0.7 0.9 1.2 1.5 2.6 3.1 T T T T T
4 0.7 0.7 0.7 0.7 0.9 1.2 1.4 2.5 2.9 0.7 0.7 0.7 0.7 0.9 1.2 1.4 2.5 2.9 T T T T T
6 0.7 0.7 0.7 0.7 0.9 1.2 1.4 2.5 2.9 0.7 0.7 0.7 0.7 0.9 1.2 1.4 2.5 2.9 T T T T T
8 0.5 0.5 0.5 0.5 0.7 0.9 1.1 1.7 2.1 0.5 0.5 0.5 0.5 0.7 0.9 1.1 1.7 2.1 4 5 T T T
10 0.4 0.4 0.4 0.4 0.6 0.9 1 1.6 2 0.4 0.4 0.4 0.4 0.6 0.9 1 1.6 2 3.7 4.7 T T T
C

13 0.4 0.4 0.4 0.6 0.8 1 1.5 2 0.4 0.4 0.4 0.6 0.8 1 1.5 2 3.6 4.7 T T T
16 0.4 0.4 0.5 0.7 0.9 1.3 1.6 0.4 0.4 0.5 0.7 0.9 1.3 1.6 3 3.7 T T T
20 0.4 0.5 0.7 0.9 1.3 1.6 0.4 0.5 0.7 0.9 1.3 1.6 3 3.6 T T T
25 0.5 0.7 0.9 1.3 1.6 0.5 0.7 0.9 1.3 1.6 2.9 3.5 T T T
32 0.7 0.9 1.3 1.5 0.7 0.9 1.3 1.5 2.5 3 T T T
40 0.9 1.3 1.6 0.9 1.3 1.6 2.9 3.4 T T T
50 1.2 1.4 1.2 1.4 2.5 3 T T T
63 1.3 2.4 2.9 T T T

Selektivitätstabellen_en_06_2016.xlsx4.1) 3VA1 - 5SL 11 von 31 Druckdatum: 08.06.2016


SIEMENS AG Upstream 3VA1 molded case circuit breaker *)
Limit current with selectivity Is [kA]
for 230 / 415 V AC Line protection
acc. to IEC 60947-2
Trip Unit TM210 / TM220 / TM240

Edition 05/2016 Size 100 A 160 A 250 A

Icu [kA] 16 (B) / 25 (N) / 36 (S) 25 (N) / 36 (S) / 55 (M) / 70 (H) 25 (N) / 36 (S) / 55 (M) / 70 (H)
Characteristic

Icn [kA]

Icu [kA]
In [A] 16 20 25 32 40 50 63 80 100 16 20 25 32 40 50 63 80 100 125 160 160 200 250

1 16 16 16 16 16 16 16 15 16 16 16 16 16 16 16 16 15 16 35 35 35 35 35
1.6 16 16 16 16 16 16 16 15 16 16 16 16 16 16 16 16 15 16 35 35 35 35 35
2 16 16 16 16 16 16 16 15 16 16 16 16 16 16 16 16 15 16 35 35 35 35 35
35

3 1.4 1.4 1.4 1.4 2.3 3.8 5.9 16 16 1.4 1.4 1.4 1.4 2.3 3.8 5.9 16 16 35 35 35 35 35
4 1 1 1 1 1.7 2.5 3.3 8.6 16 1 1 1 1 1.7 2.5 3.3 8.6 16 16 16 35 35 35
6 0.8 0.8 0.8 0.8 1.2 1.8 2.3 4 5.3 0.8 0.8 0.8 0.8 1.2 1.8 2.3 4 5.3 16 16 35 35 35
8 0.8 0.8 0.8 0.8 1.2 1.7 2 3.1 4.1 0.8 0.8 0.8 0.8 1.2 1.7 2 3.1 4.1 14 16 20 20 20
10 0.7 0.7 0.7 0.7 0.9 1.4 1.7 2.7 3.2 0.7 0.7 0.7 0.7 0.9 1.4 1.7 2.7 3.2 6.9 9.4 20 20 20
10
A

13 0.6 0.6 0.6 0.9 1.2 1.5 2.4 2.8 0.6 0.6 0.6 0.9 1.2 1.5 2.4 2.8 5.6 7 20 20 20
16 0.6 0.6 0.9 1.2 1.5 2.3 2.7 0.6 0.6 0.9 1.2 1.5 2.3 2.7 5.2 6.3 20 20 20
20

20 0.6 0.8 1.1 1.3 2 2.4 0.6 0.8 1.1 1.3 2 2.4 4.5 5.5 20 20 20
25 0.8 1.1 1.3 2.1 2.4 0.8 1.1 1.3 2.1 2.4 4.5 5.6 20 20 20
32 0.9 1.1 1.7 2 0.9 1.1 1.7 2 3.5 4.3 20 20 20
40 1.1 1.8 2.1 1.1 1.8 2.1 3.6 4.3 15 15 15
50 1.6 1.9 1.6 1.9 3.1 3.8 15 15 15
15

63 1.7 1.7 2.9 3.6 12 14 15


6 0.8 0.8 0.8 0.8 1 1.5 1.9 3.1 4.2 0.8 0.8 0.8 0.8 1 1.5 1.9 3.1 4.2 10 16 T T T
35

10 0.6 0.6 0.6 0.6 0.9 1.2 1.5 2.3 2.6 0.6 0.6 0.6 0.6 0.9 1.2 1.5 2.3 2.6 5.3 6.7 T T T
13 0.6 0.6 0.6 0.8 1.1 1.3 2.1 2.5 0.6 0.6 0.6 0.8 1.1 1.3 2.1 2.5 4.5 5.5 T T T
16 0.5 0.5 0.8 1 1.3 2 2.3 0.5 0.5 0.8 1 1.3 2 2.3 4.3 5.4 T T T
20

20 0.5 0.7 1 1.2 1.8 2.2 0.5 0.7 1 1.2 1.8 2.2 3.8 4.8 T T T
10
B

25 0.6 0.9 1.1 1.7 2 0.6 0.9 1.1 1.7 2 3.5 4.4 T T T
32 0.9 1 1.6 1.9 0.9 1 1.6 1.9 3.4 4.1 T T T
40 1 1.5 1.8 1 1.5 1.8 3.1 3.9 T T T
50 1.4 1.7 1.4 1.7 2.8 3.4 13 T T
15

63 1.6 1.6 2.7 3.3 12 T T

Selektivitätstabellen_en_06_2016.xlsx4.2) 3VA1 - 5SY 12 von 31 Druckdatum: 08.06.2016


SIEMENS AG Upstream 3VA1 molded case circuit breaker *)
Limit current with selectivity Is [kA]
for 230 / 415 V AC Line protection
acc. to IEC 60947-2
Trip Unit TM210 / TM220 / TM240

Edition 05/2016 Size 100 A 160 A 250 A

Characteristic Icu [kA] 16 (B) / 25 (N) / 36 (S) 25 (N) / 36 (S) / 55 (M) / 70 (H) 25 (N) / 36 (S) / 55 (M) / 70 (H)

Icn [kA]

Icu [kA]
In [A] 16 20 25 32 40 50 63 80 100 16 20 25 32 40 50 63 80 100 125 160 160 200 250

0.3 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 35 35 35 35 35
0.5 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 35 35 35 35 35
1 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 35 35 35 35 35
Downstream 5SY4 miniature circuit breaker

1.6 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 35 35 35 35 35
2 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 35 35 35 35 35
2.5 0.9 0.9 0.9 0.9 1.3 1.9 2.4 4.4 6.3 0.9 0.9 0.9 0.9 1.3 1.9 2.4 4.4 6.3 35 35 35 35 35
35

3 0.9 0.9 0.9 0.9 1.3 1.9 2.4 4.4 6.3 0.9 0.9 0.9 0.9 1.3 1.9 2.4 4.4 6.3 35 35 35 35 35
3.5 0.7 0.7 0.7 0.7 0.9 1.2 1.5 2.6 3.1 0.7 0.7 0.7 0.7 0.9 1.2 1.5 2.6 3.1 10 14 35 35 35
Line protection

4 0.7 0.7 0.7 0.7 0.9 1.2 1.5 2.6 3.1 0.7 0.7 0.7 0.7 0.9 1.2 1.5 2.6 3.1 10 14 35 35 35
5 0.7 0.7 0.7 0.7 0.9 1.2 1.5 2.6 3.1 0.7 0.7 0.7 0.7 0.9 1.2 1.5 2.6 3.1 10 14 35 35 35
6 0.7 0.7 0.7 0.7 0.9 1.2 1.5 2.6 3.1 0.7 0.7 0.7 0.7 0.9 1.2 1.5 2.6 3.1 10 14 35 35 35
8 0.6 0.6 0.6 0.6 0.8 1 1.2 2.1 2.6 0.6 0.6 0.6 0.6 0.8 1 1.2 2.1 2.6 5.3 6.5 20 20 20
10 0.6 0.6 0.6 0.6 0.8 1 1.2 2.1 2.6 0.6 0.6 0.6 0.6 0.8 1 1.2 2.1 2.6 5.3 6.5 20 20 20
13 0.5 0.5 0.5 0.7 0.9 1.1 1.8 2.3 0.5 0.5 0.5 0.7 0.9 1.1 1.8 2.3 4.3 5.4 20 20 20
10
C

15 0.5 0.5 0.7 0.9 1.1 1.8 2.3 0.5 0.5 0.7 0.9 1.1 1.8 2.3 4.3 5.4 20 20 20
16 0.5 0.5 0.7 0.9 1.1 1.8 2.3 0.5 0.5 0.7 0.9 1.1 1.8 2.3 4.3 5.4 20 20 20
20

20 0.4 0.6 0.8 0.9 1.5 1.9 0.4 0.6 0.8 0.9 1.5 1.9 3.5 4.4 20 20 20
25 0.6 0.8 0.9 1.5 1.9 0.6 0.8 0.9 1.5 1.9 3.5 4.4 20 20 20
30 0.8 0.9 1.5 1.9 0.8 0.9 1.5 1.9 3.4 4.1 20 20 20
32 0.8 0.9 1.5 1.9 0.8 0.9 1.5 1.9 3.4 4.1 20 20 20
35 0.9 1.4 1.7 0.9 1.4 1.7 3.1 3.7 15 15 15
40 0.9 1.4 1.7 0.9 1.4 1.7 3.1 3.7 15 15 15
45 1.3 1.6 1.3 1.6 2.9 3.5 12 14 15
50 1.3 1.6 1.3 1.6 2.9 3.5 12 14 15
15

60 1.4 1.4 2.7 3.3 12 14 15


63 1.4 1.4 2.7 3.3 12 14 15
80
0.3 1 1 1 1 1.5 2.2 2.7 5.1 6.9 1 1 1 1 1.5 2.2 2.7 5.1 6.9 16 16 16 16 16
0.5 1 1 1 1 1.5 2.2 2.7 5.1 6.9 1 1 1 1 1.5 2.2 2.7 5.1 6.9 16 16 16 16 16
1 1 1 1 1 1.5 2.2 2.7 5.1 6.9 1 1 1 1 1.5 2.2 2.7 5.1 6.9 16 16 16 16 16
1.6 1 1 1 1 1.5 2.2 2.7 5.1 6.9 1 1 1 1 1.5 2.2 2.7 5.1 6.9 16 16 16 16 16
35

2 1 1 1 1 1.5 2.2 2.7 5.1 6.9 1 1 1 1 1.5 2.2 2.7 5.1 6.9 16 16 16 16 16
3 0.8 0.8 0.8 0.8 1.2 1.7 2.1 3.4 4.6 0.8 0.8 0.8 0.8 1.2 1.7 2.1 3.4 4.6 16 16 16 16 16
4 0.7 0.7 0.7 0.7 1 1.4 1.7 2.7 3.2 0.7 0.7 0.7 0.7 1 1.4 1.7 2.7 3.2 7.1 9.8 16 16 16
6 0.6 0.6 0.6 0.6 0.8 1.2 1.5 2.3 2.7 0.6 0.6 0.6 0.6 0.8 1.2 1.5 2.3 2.7 5.6 7.6 16 16 16
8 0.5 0.5 0.5 0.5 0.7 0.9 1.2 1.9 2.3 0.5 0.5 0.5 0.5 0.7 0.9 1.2 1.9 2.3 4.4 5.4 16 16 16
10
D

10 0.5 0.5 0.5 0.5 0.7 0.9 1.1 1.8 2.2 0.5 0.5 0.5 0.5 0.7 0.9 1.1 1.8 2.2 4 4.9 16 16 16
13 0.4 0.4 0.4 0.6 0.9 1.1 1.8 2.2 0.4 0.4 0.4 0.6 0.9 1.1 1.8 2.2 4.1 5.1 16 16 16
16 0.6 0.8 1 1.7 2.1 0.6 0.8 1 1.7 2.1 3.7 4.5 16 16 16
20

20 0.5 0.7 1 1.6 1.9 0.5 0.7 1 1.6 1.9 3.1 3.8 16 16 16
25 0.5 0.7 0.9 1.5 1.8 0.5 0.7 0.9 1.5 1.8 3 3.9 14 16 16
32 1.2 1.5 1.2 1.5 2.5 3 12 14 16
40 1.1 1.4 1.1 1.4 2.4 2.9 9.6 12 14
50 1.2 1.2 2.1 2.7 9.1 11 14
15

63 1.1 1.1 1.9 2.5 8.8 10 13

Selektivitätstabellen_en_06_2016.xlsx4.2) 3VA1 - 5SY 13 von 31 Druckdatum: 08.06.2016


SIEMENS AG Upstream 3VA1 molded case circuit breaker *)
Limit current with selectivity Is [kA]
for 230 / 415 V AC Line protection
acc. to IEC 60947-2
Trip Unit TM210 / TM220 / TM240

Edition 05/2016 Size 100 A 160 A 250 A

Characteristic Icu [kA] 16 (B) / 25 (N) / 36 (S) 25 (N) / 36 (S) / 55 (M) / 70 (H) 25 (N) / 36 (S) / 55 (M) / 70 (H)

Icn [kA]

Icu [kA]
In [A] 16 20 25 32 40 50 63 80 100 16 20 25 32 40 50 63 80 100 125 160 160 200 250

2 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 T T T T T
4 0.7 0.7 0.7 0.7 0.9 1.2 1.5 2.6 3.1 0.7 0.7 0.7 0.7 0.9 1.2 1.5 2.6 3.1 10 14 T T T
30

6 0.8 0.8 0.8 0.8 1 1.5 1.9 3.1 4.2 0.8 0.8 0.8 0.8 1 1.5 1.9 3.1 4.2 10 16 T T T
10 0.6 0.6 0.6 0.6 0.9 1.2 1.5 2.3 2.6 0.6 0.6 0.6 0.6 0.9 1.2 1.5 2.3 2.6 5.3 6.7 T T T
13 0.6 0.6 0.6 0.8 1.1 1.3 2.1 2.5 0.6 0.6 0.6 0.8 1.1 1.3 2.1 2.5 4.5 5.5 T T T
16 0.5 0.5 0.8 1 1.3 2 2.3 0.5 0.5 0.8 1 1.3 2 2.3 4.3 5.4 T T T
15
B

20 0.5 0.7 1 1.2 1.8 2.2 0.5 0.7 1 1.2 1.8 2.2 3.8 4.8 T T T
25 0.6 0.9 1.1 1.7 2 0.6 0.9 1.1 1.7 2 3.5 4.4 T T T
32 0.9 1 1.6 1.9 0.9 1 1.6 1.9 3.4 4.1 T T T
40 1 1.5 1.8 1 1.5 1.8 3.1 3.9 T T T
50 1.4 1.7 1.4 1.7 2.8 3.4 T T T
10

63 1.6 1.6 2.7 3.3 T T T


0,3 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 T T T T T
0,5 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 T T T T T
1 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 T T T T T
1.6 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 T T T T T
2 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 T T T T T
30

3 0.9 0.9 0.9 0.9 1.3 1.9 2.4 4.4 6.3 0.9 0.9 0.9 0.9 1.3 1.9 2.4 4.4 6.3 T T T T T
4 0.7 0.7 0.7 0.7 0.9 1.2 1.5 2.6 3.1 0.7 0.7 0.7 0.7 0.9 1.2 1.5 2.6 3.1 10 14 T T T
Downstream 5SY6 miniature circuit breaker

5 0.7 0.7 0.7 0.7 0.9 1.2 1.5 2.6 3.1 0.7 0.7 0.7 0.7 0.9 1.2 1.5 2.6 3.1 10 14 T T T
6 0.7 0.7 0.7 0.7 0.9 1.2 1.5 2.6 3.1 0.7 0.7 0.7 0.7 0.9 1.2 1.5 2.6 3.1 10 14 T T T
8 0.6 0.6 0.6 0.6 0.8 1 1.2 2.1 2.6 0.6 0.6 0.6 0.6 0.8 1 1.2 2.1 2.6 5.3 6.5 T T T
10 0.6 0.6 0.6 0.6 0.8 1 1.2 2.1 2.6 0.6 0.6 0.6 0.6 0.8 1 1.2 2.1 2.6 5.3 6.5 T T T
C

13 0.5 0.5 0.5 0.7 0.9 1.1 1.8 2.3 0.5 0.5 0.5 0.7 0.9 1.1 1.8 2.3 4.3 5.4 T T T
Line protection

15 0.5 0.5 0.7 0.9 1.1 1.8 2.3 0.5 0.5 0.7 0.9 1.1 1.8 2.3 4.3 5.4 T T T
16 0.5 0.5 0.7 0.9 1.1 1.8 2.3 0.5 0.5 0.7 0.9 1.1 1.8 2.3 4.3 5.4 T T T
15

20 0.4 0.6 0.8 0.9 1.5 1.9 0.4 0.6 0.8 0.9 1.5 1.9 3.5 4.4 T T T
25 0.6 0.8 0.9 1.5 1.9 0.6 0.8 0.9 1.5 1.9 3.5 4.4 T T T
30 0.8 0.9 1.5 1.9 0.8 0.9 1.5 1.9 3.4 4.1 T T T
32 0.8 0.9 1.5 1.9 0.8 0.9 1.5 1.9 3.4 4.1 T T T
40 0.9 1.4 1.7 0.9 1.4 1.7 3.1 3.7 T T T
50 1.3 1.6 1.3 1.6 2.9 3.5 T T T
10

63 1.4 1.4 2.7 3.3 T T T

Selektivitätstabellen_en_06_2016.xlsx4.2) 3VA1 - 5SY 14 von 31 Druckdatum: 08.06.2016


SIEMENS AG Upstream 3VA1 molded case circuit breaker *)
Limit current with selectivity Is [kA]
for 230 / 415 V AC Line protection
acc. to IEC 60947-2
Trip Unit TM210 / TM220 / TM240

Edition 05/2016 Size 100 A 160 A 250 A

Characteristic Icu [kA] 16 (B) / 25 (N) / 36 (S) 25 (N) / 36 (S) / 55 (M) / 70 (H) 25 (N) / 36 (S) / 55 (M) / 70 (H)

Icn [kA]

Icu [kA]
In [A] 16 20 25 32 40 50 63 80 100 16 20 25 32 40 50 63 80 100 125 160 160 200 250

0.3 1 1 1 1 1.5 2.2 2.7 5.1 6.9 1 1 1 1 1.5 2.2 2.7 5.1 6.9 16 16 16 16 16
0.5 1 1 1 1 1.5 2.2 2.7 5.1 6.9 1 1 1 1 1.5 2.2 2.7 5.1 6.9 16 16 16 16 16
1 1 1 1 1 1.5 2.2 2.7 5.1 6.9 1 1 1 1 1.5 2.2 2.7 5.1 6.9 16 16 16 16 16
1.6 1 1 1 1 1.5 2.2 2.7 5.1 6.9 1 1 1 1 1.5 2.2 2.7 5.1 6.9 16 16 16 16 16
30

2 1 1 1 1 1.5 2.2 2.7 5.1 6.9 1 1 1 1 1.5 2.2 2.7 5.1 6.9 16 16 16 16 16
3 0.8 0.8 0.8 0.8 1.2 1.7 2.1 3.4 4.6 0.8 0.8 0.8 0.8 1.2 1.7 2.1 3.4 4.6 16 16 16 16 16
4 0.7 0.7 0.7 0.7 1 1.4 1.7 2.7 3.2 0.7 0.7 0.7 0.7 1 1.4 1.7 2.7 3.2 7.1 9.8 16 16 16
6 0.6 0.6 0.6 0.6 0.8 1.2 1.5 2.3 2.7 0.6 0.6 0.6 0.6 0.8 1.2 1.5 2.3 2.7 5.6 7.6 16 16 16
8 0.5 0.5 0.5 0.5 0.7 0.9 1.2 1.9 2.3 0.5 0.5 0.5 0.5 0.7 0.9 1.2 1.9 2.3 4.4 5.4 T T T
D

10 0.5 0.5 0.5 0.5 0.7 0.9 1.1 1.8 2.2 0.5 0.5 0.5 0.5 0.7 0.9 1.1 1.8 2.2 4 4.9 T T T
13 0.4 0.4 0.4 0.6 0.9 1.1 1.8 2.2 0.4 0.4 0.4 0.6 0.9 1.1 1.8 2.2 4.1 5.1 T T T
16 0.6 0.8 1 1.7 2.1 0.6 0.8 1 1.7 2.1 3.7 4.5 T T T
15

20 0.5 0.7 1 1.6 1.9 0.5 0.7 1 1.6 1.9 3.1 3.8 T T T
25 0.5 0.7 0.9 1.5 1.8 0.5 0.7 0.9 1.5 1.8 3 3.9 14 T T
32 1.2 1.5 1.2 1.5 2.5 3 12 14 T
40 1.1 1.4 1.1 1.4 2.4 2.9 T T T
50 1.2 1.2 2.1 2.7 9.1 T T
10

63 1.1 1.1 1.9 2.5 8.8 T T


6 0.8 0.8 0.8 0.8 1 1.5 1.9 3.1 4.2 0.8 0.8 0.8 0.8 1 1.5 1.9 3.1 4.2 10 T T T T
30 40

10 0.6 0.6 0.6 0.6 0.9 1.2 1.5 2.3 2.6 0.6 0.6 0.6 0.6 0.9 1.2 1.5 2.3 2.6 5.3 6.7 T T T
13 0.6 0.6 0.6 0.8 1.1 1.3 2.1 2.5 0.6 0.6 0.6 0.8 1.1 1.3 2.1 2.5 4.5 5.5 T T T
16 0.5 0.5 0.8 1 1.3 2 2.3 0.5 0.5 0.8 1 1.3 2 2.3 4.3 5.4 T T T
20 0.5 0.7 1 1.2 1.8 2.2 0.5 0.7 1 1.2 1.8 2.2 3.8 4.8 T T T
25
15
B

25 0.6 0.9 1.1 1.7 2 0.6 0.9 1.1 1.7 2 3.5 4.4 T T T
32 0.9 1 1.6 1.9 0.9 1 1.6 1.9 3.4 4.1 T T T
40 1 1.5 1.8 1 1.5 1.8 3.1 3.9 17 T T
50 1.4 1.7 1.4 1.7 2.9 3.5 13 T T
20

63 1.6 1.6 2.7 3.2 12 T T

Selektivitätstabellen_en_06_2016.xlsx4.2) 3VA1 - 5SY 15 von 31 Druckdatum: 08.06.2016


SIEMENS AG Upstream 3VA1 molded case circuit breaker *)
Limit current with selectivity Is [kA]
for 230 / 415 V AC Line protection
acc. to IEC 60947-2
Trip Unit TM210 / TM220 / TM240

Edition 05/2016 Size 100 A 160 A 250 A

Characteristic Icu [kA] 16 (B) / 25 (N) / 36 (S) 25 (N) / 36 (S) / 55 (M) / 70 (H) 25 (N) / 36 (S) / 55 (M) / 70 (H)

Icn [kA]

Icu [kA]
In [A] 16 20 25 32 40 50 63 80 100 16 20 25 32 40 50 63 80 100 125 160 160 200 250

0.3 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 50 50 50 50 50
0.5 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 50 50 50 50 50
1 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 50 50 50 50 50
50

1.6 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 50 50 50 50 50
2 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 50 50 50 50 50
3 0.9 0.9 0.9 0.9 1.3 1.9 2.4 4.4 6.3 0.9 0.9 0.9 0.9 1.3 1.9 2.4 4.4 6.3 40 40 40 40 40
Downstream 5SY7 miniature circuit breaker

4 0.7 0.7 0.7 0.7 0.9 1.2 1.5 2.6 3.1 0.7 0.7 0.7 0.7 0.9 1.2 1.5 2.6 3.1 10 14 40 40 40
40

6 0.7 0.7 0.7 0.7 0.9 1.2 1.5 2.6 3.1 0.7 0.7 0.7 0.7 0.9 1.2 1.5 2.6 3.1 10 14 40 40 40
8 0.6 0.6 0.6 0.6 0.8 1 1.2 2.1 2.6 0.6 0.6 0.6 0.6 0.8 1 1.2 2.1 2.6 5.3 6.5 30 30 30
15

30
C

10 0.6 0.6 0.6 0.6 0.8 1 1.2 2.1 2.6 0.6 0.6 0.6 0.6 0.8 1 1.2 2.1 2.6 5.3 6.5 30 30 30
13 0.5 0.5 0.5 0.7 0.9 1.1 1.8 2.3 0.5 0.5 0.5 0.7 0.9 1.1 1.8 2.3 4.3 5.4 25 25 25
Line protection

16 0.5 0.5 0.7 0.9 1.1 1.8 2.3 0.5 0.5 0.7 0.9 1.1 1.8 2.3 4.3 5.4 25 25 25
20 0.4 0.6 0.8 0.9 1.5 1.9 0.4 0.6 0.8 0.9 1.5 1.9 3.5 4.4 25 25 25
25

25 0.6 0.8 0.9 1.5 1.9 0.6 0.8 0.9 1.5 1.9 3.5 4.4 25 25 25
32 0.8 0.9 1.5 1.9 0.8 0.9 1.5 1.9 3.4 4.1 25 25 25
40 0.9 1.4 1.7 0.9 1.4 1.7 3.1 3.7 17 20 20
50 1.3 1.6 1.3 1.6 2.9 3.5 13 20 20
20

63 1.4 1.4 2.7 3.2 12 14 20


0.3 1 1 1 1 1.5 2.2 2.7 5.1 6.9 1 1 1 1 1.5 2.2 2.7 5.1 6.9 16 16 16 16 16
0.5 1 1 1 1 1.5 2.2 2.7 5.1 6.9 1 1 1 1 1.5 2.2 2.7 5.1 6.9 16 16 16 16 16
1 1 1 1 1 1.5 2.2 2.7 5.1 6.9 1 1 1 1 1.5 2.2 2.7 5.1 6.9 16 16 16 16 16
50

1.6 1 1 1 1 1.5 2.2 2.7 5.1 6.9 1 1 1 1 1.5 2.2 2.7 5.1 6.9 16 16 16 16 16
2 1 1 1 1 1.5 2.2 2.7 5.1 6.9 1 1 1 1 1.5 2.2 2.7 5.1 6.9 16 16 16 16 16
3 0.8 0.8 0.8 0.8 1.2 1.7 2.1 3.4 4.6 0.8 0.8 0.8 0.8 1.2 1.7 2.1 3.4 4.6 16 16 16 16 16
4 0.7 0.7 0.7 0.7 1 1.4 1.7 2.7 3.2 0.7 0.7 0.7 0.7 1 1.4 1.7 2.7 3.2 7.1 9.8 16 16 16
40

6 0.6 0.6 0.6 0.6 0.8 1.2 1.5 2.3 2.7 0.6 0.6 0.6 0.6 0.8 1.2 1.5 2.3 2.7 5.6 7.6 16 16 16
8 0.5 0.5 0.5 0.5 0.7 0.9 1.2 1.9 2.3 0.5 0.5 0.5 0.5 0.7 0.9 1.2 1.9 2.3 4.4 5.4 16 16 16
30
15
D

10 0.5 0.5 0.5 0.5 0.7 0.9 1.1 1.8 2.2 0.5 0.5 0.5 0.5 0.7 0.9 1.1 1.8 2.2 4 4.9 16 16 16
13 0.4 0.4 0.4 0.6 0.9 1.1 1.8 2.2 0.4 0.4 0.4 0.6 0.9 1.1 1.8 2.2 4.1 5.1 16 16 16
16 0.6 0.8 1 1.7 2.1 0.6 0.8 1 1.7 2.1 3.7 4.5 16 16 16
20 0.5 0.7 1 1.6 1.9 0.5 0.7 1 1.6 1.9 3.1 3.8 16 16 16
25

25 0.5 0.7 0.9 1.5 1.8 0.5 0.7 0.9 1.5 1.8 3 3.9 14 16 16
32 1.2 1.5 1.2 1.5 2.5 3 12 14 16
40 1.1 1.4 1.1 1.4 2.4 2.9 9.6 12 14
15 20

50 1.2 1.2 2.1 2.7 9.1 11 14


63 1.1 1.1 1.9 2.5 8.8 10 13

Selektivitätstabellen_en_06_2016.xlsx4.2) 3VA1 - 5SY 16 von 31 Druckdatum: 08.06.2016


SIEMENS AG Upstream 3VA1 molded case circuit breaker *)
Limit current with selectivity Is [kA]
for 230 / 415 V AC Line protection
acc. to IEC 60947-2
Trip Unit TM210 / TM220 / TM240

Edition 05/2016 Size 100 A 160 A 250 A

Characteristic Icu [kA] 16 (B) / 25 (N) / 36 (S) 25 (N) / 36 (S) / 55 (M) / 70 (H) 25 (N) / 36 (S) / 55 (M) / 70 (H)

Icn [kA]

Icu [kA]
In [A] 16 20 25 32 40 50 63 80 100 16 20 25 32 40 50 63 80 100 125 160 160 200 250

0.3 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 50 50 50 50 50
0.5 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 50 50 50 50 50
1 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 50 50 50 50 50
70

1.6 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 50 50 50 50 50
2 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 50 50 50 50 50
3 0.9 0.9 0.9 0.9 1.3 1.9 2.4 4.4 6.3 0.9 0.9 0.9 0.9 1.3 1.9 2.4 4.4 6.3 40 40 40 40 40
4 0.7 0.7 0.7 0.7 1 1.5 1.8 3 3.9 0.7 0.7 0.7 0.7 1 1.5 1.8 3 3.9 10 14 40 40 40
50

6 0.7 0.7 0.7 0.7 0.9 1.3 1.6 2.6 3.1 0.7 0.7 0.7 0.7 0.9 1.3 1.6 2.6 3.1 10 14 40 40 40
8 0.6 0.6 0.6 0.6 0.8 1.1 1.4 2.1 2.6 0.6 0.6 0.6 0.6 0.8 1.1 1.4 2.1 2.6 5.3 6.5 40 40 40
k.A.

40
C

10 0.6 0.6 0.6 0.6 0.8 1 1.3 2.1 2.6 0.6 0.6 0.6 0.6 0.8 1 1.3 2.1 2.6 5.3 6.5 40 40 40
13 0.5 0.5 0.5 0.7 0.9 1.2 1.8 2.3 0.5 0.5 0.5 0.7 0.9 1.2 1.8 2.3 4.3 5.4 30 30 30
Downstream 5SY8 miniature circuit breaker

16 0.5 0.5 0.7 0.9 1.2 1.9 2.3 0.5 0.5 0.7 0.9 1.2 1.9 2.3 4.3 5.4 30 30 30
20 0.4 0.6 0.8 1 1.6 1.9 0.4 0.6 0.8 1 1.6 1.9 3.5 4.4 30 30 30
30

25 0.6 0.8 1 1.6 1.9 0.6 0.8 1 1.6 1.9 3.5 4.4 30 30 30
32 0.8 1 1.6 1.9 0.8 1 1.6 1.9 3.4 4.1 30 30 30
40 0.9 1.5 1.7 0.9 1.5 1.7 3.1 3.7 25 25 25
Line protection

50 1.4 1.6 1.4 1.6 2.9 3.5 13 25 25


25

63 1.5 1.5 2.7 3.2 12 14 20


0.3 1 1 1 1 1.5 2.2 2.7 5.1 6.9 1 1 1 1 1.5 2.2 2.7 5.1 6.9 16 16 40 40 40
0.5 1 1 1 1 1.5 2.2 2.7 5.1 6.9 1 1 1 1 1.5 2.2 2.7 5.1 6.9 16 16 40 40 40
1 1 1 1 1 1.5 2.2 2.7 5.1 6.9 1 1 1 1 1.5 2.2 2.7 5.1 6.9 16 16 40 40 40
70

1.6 1 1 1 1 1.5 2.2 2.7 5.1 6.9 1 1 1 1 1.5 2.2 2.7 5.1 6.9 16 16 40 40 40
2 1 1 1 1 1.5 2.2 2.7 5.1 6.9 1 1 1 1 1.5 2.2 2.7 5.1 6.9 16 16 40 40 40
3 0.8 0.8 0.8 0.8 1.2 1.7 2.1 3.4 4.6 0.8 0.8 0.8 0.8 1.2 1.7 2.1 3.4 4.6 16 16 40 40 40
4 0.7 0.7 0.7 0.7 1 1.4 1.7 2.7 3.2 0.7 0.7 0.7 0.7 1 1.4 1.7 2.7 3.2 7.1 9.8 40 40 40
50

6 0.6 0.6 0.6 0.6 0.8 1.2 1.5 2.3 2.7 0.6 0.6 0.6 0.6 0.8 1.2 1.5 2.3 2.7 5.6 7.6 40 40 40
8 0.5 0.5 0.5 0.5 0.7 0.9 1.2 1.9 2.3 0.5 0.5 0.5 0.5 0.7 0.9 1.2 1.9 2.3 4.4 5.4 T T T
k.A.

40
D

10 0.5 0.5 0.5 0.5 0.7 0.9 1.1 1.8 2.2 0.5 0.5 0.5 0.5 0.7 0.9 1.1 1.8 2.2 4 4.9 T T T
13 0.4 0.4 0.4 0.6 0.9 1.1 1.8 2.2 0.4 0.4 0.4 0.6 0.9 1.1 1.8 2.2 4.1 5.1 T T T
16 0.6 0.8 1 1.7 2.1 0.6 0.8 1 1.7 2.1 3.7 4.5 T T T
20 0.5 0.7 1 1.6 1.9 0.5 0.7 1 1.6 1.9 3.1 3.8 T T T
30

25 0.5 0.7 0.9 1.5 1.8 0.5 0.7 0.9 1.5 1.8 3 3.9 14 T T
32 1.2 1.5 1.2 1.5 2.5 3 12 14 25
40 1.1 1.4 1.1 1.4 2.4 2.9 9.6 12 14
20 25

50 1.2 1.2 2.1 2.7 9.1 11 14


63 1.1 1.1 1.9 2.5 8.8 10 13

Angaben zur totalen Selektivität, gekennzeichnet mit "T", beziehen sich auf das Ausschaltvermögen I cu der Geräte.

Selektivitätstabellen_en_06_2016.xlsx4.2) 3VA1 - 5SY 17 von 31 Druckdatum: 08.06.2016


SIEMENS AG Upstream 3VA2 molded case circuit breaker *)
Limit current with selectivity Is [kA]
for 230 / 415 V AC Line protection
acc. to IEC 60947-2
Trip Unit ETU320 / ETU330 / ETU340 / ETU350 / ETU550 / ETU560 / ETU850 / ETU860

Edition 05/2016 Size 100 A 160 A 250 A 400 A 630 A

Icu [kA] 55 (M) / 85 (H) / 110 (C)


Characteristic

Icn [kA]
In [A] 25 40 63 100 25 40 63 100 160 160 250 250 400 400 630

6 T T T T T T T T T T T T T T T
10 3.7 T T T 4 T T T T T T T T T T
13 3.7 T T T 4 T T T T T T T T T T
16 2.8 T T T 3.2 T T T T T T T T T T
20 T T T T T T T T T T T T T
4.5
B

25 T T T T T T T T T T T T T
32 T T T T T T T T T T T
40 T T T T T T T T T T T
Downstream 5SL3 miniature circuit breaker

50 T T T T T T T T T
63 T T T T T T T T T
0.3 T T T T T T T T T T T T T T T
0.5 T T T T T T T T T T T T T T T
Line protection

1 T T T T T T T T T T T T T T T
1.6 T T T T T T T T T T T T T T T
2 T T T T T T T T T T T T T T T
3 T T T T T T T T T T T T T T T
4 T T T T T T T T T T T T T T T
6 T T T T T T T T T T T T T T T
8 4 T T T T T T T T T T T T T T
4.5
C

10 3.7 T T T 4 T T T T T T T T T T
13 3.7 T T T 4 T T T T T T T T T T
16 2.8 T T T 3.2 T T T T T T T T T T
20 T T T T T T T T T T T T T
25 T T T T T T T T T T T T T
32 T T T T T T T T T T T
40 T T T T T T T T T T T
50 T T T T T T T T T
63 T T T T T T T T T
1 T T T T T T T T T T T T T T T
2 T T T T T T T T T T T T T T T
3 T T T T T T T T T T T T T T T
4 T T T T T T T T T T T T T T T
6 T T T T T T T T T T T T T T T
8 T T T T T T T T T T T T T T T
10 T T T T T T T T T T T T T T T
13 5.5 T T T 5.9 T T T T T T T T T T
10
B

16 4.4 T T T 4.9 T T T T T T T T T T
20 T 8 8 T T T T T T T T T T
25 T 8 8 T T T T T T T T T T
32 8 8 T T T T T T T T T
40 8 8 T T T T T T T T T
50 8 T T T T T T T T
63 8 T T T T T T T T
0.3 T T T T T T T T T T T T T T T
0.5 T T T T T T T T T T T T T T T
1 T T T T T T T T T T T T T T T
Downstream 5SL4 miniature circuit breaker

1.6 T T T T T T T T T T T T T T T
2 T T T T T T T T T T T T T T T
3 T T T T T T T T T T T T T T T
4 T T T T T T T T T T T T T T T
6 T T T T T T T T T T T T T T T
8 5.1 T T T 5.6 T T T T T T T T T T
Line protection

10
C

10 5.1 T T T 5.6 T T T T T T T T T T
13 3.7 T T T 4 T T T T T T T T T T
16 3.7 T T T 4 T T T T T T T T T T
20 T 8 8 7.3 T T T T T T T T T
25 T 8 8 7.3 T T T T T T T T T
32 8 8 T T T T T T T T T
40 8 8 T T T T T T T T T
50 8 T T T T T T T T
63 8 T T T T T T T T
0.3 T T T T T T T T T T T T T T T
0.5 T T T T T T T T T T T T T T T
1 T T T T T T T T T T T T T T T
1.6 T T T T T T T T T T T T T T T
2 T T T T T T T T T T T T T T T
3 T T T T T T T T T T T T T T T
4 T T T T T T T T T T T T T T T
6 6.7 T T T 7.1 T T T T T T T T T T
8 3.3 T T T 3.9 T T T T T T T T T T
10
D

10 3.3 T T T 3.9 T T T T T T T T T T
13 3.2 T T T 3.6 T T T T T T T T T T
16 3.2 T T T 3.6 T T T T T T T T T T

Selektivitätstabellen_en_06_2016.xlsx4.3) 3VA2 - 5SL 18 von 32 Druckdatum: 08.06.2016


SIEMENS AG Upstream 3VA2 molded case circuit breaker *)
Limit current with selectivity Is [kA]
for 230 / 415 V AC Line protection
acc. to IEC 60947-2
Trip Unit ETU320 / ETU330 / ETU340 / ETU350 / ETU550 / ETU560 / ETU850 / ETU860

Edition 05/2016 Size 100 A 160 A 250 A 400 A 630 A

Icu [kA] 55 (M) / 85 (H) / 110 (C)


Characteristic

Icn [kA]
In [A] 25 40 63 100 25 40 63 100 160 160 250 250 400 400 630

20 T 8 8 T T T T T T T T T T
25 T 8 8 T T T T T T T T T T
32 8 8 T T T T T T T T T
40 8 8 T T T T T T T T T
50 8 T T T T T T T T
63 8 T T T T T T T T

Selektivitätstabellen_en_06_2016.xlsx4.3) 3VA2 - 5SL 19 von 32 Druckdatum: 08.06.2016


SIEMENS AG Upstream 3VA2 molded case circuit breaker *)
Limit current with selectivity Is [kA]
for 230 / 415 V AC Line protection
acc. to IEC 60947-2
Trip Unit ETU320 / ETU330 / ETU340 / ETU350 / ETU550 / ETU560 / ETU850 / ETU860

Edition 05/2016 Size 100 A 160 A 250 A 400 A 630 A

Icu [kA] 55 (M) / 85 (H) / 110 (C)


Characteristic

Icn [kA]
In [A] 25 40 63 100 25 40 63 100 160 160 250 250 400 400 630

2 T T T T T T T T T T T T T T T
4 T T T T T T T T T T T T T T T
6 4.6 T T T 5 T T T T T T T T T T
10 3.7 T T T 4 T T T T T T T T T T
13 3.7 T T T 4 T T T T T T T T T T
16 2.8 T T T 3.2 T T T T T T T T T T
B

20 T T T T T T T T T T T T T
25 5.3 T T 5.4 T T T T T T T T T
Downstream 5SL6 miniature circuit breaker

32 T T T T T T T T T T T
40 T T T T T T T T T T T
50 T T T T T T T T T
63 T T T T T T T T T
0.5 T T T T T T T T T T T T T T T
Line protection

1 T T T T T T T T T T T T T T T
1.6 T T T T T T T T T T T T T T T
2 4.4 T T T 4.6 T T T T T T T T T T
3 4 T T T 4.3 T T T T T T T T T T
4 3.9 T T T 4.1 T T T T T T T T T T
6 3.9 T T T 4.1 T T T T T T T T T T
8 3.8 T T T 4.4 T T T T T T T T T T
10 3.7 T T T 4 T T T T T T T T T T
C

13 3.7 T T T 4 T T T T T T T T T T
16 2.8 T T T 3.2 T T T T T T T T T T
20 T T T T T T T T T T T T T
25 5.3 T T 5.4 T T T T T T T T T
32 T T T T T T T T T T T
40 T T T T T T T T T T T
50 T T T T T T T T T
63 T T T T T T T T T

*) The limit currents with selectivity for the upstream circuit breakers apply to the maximum value I imax for adjustable trip units.

Selektivitätstabellen_en_06_2016.xlsx4.3) 3VA2 - 5SL 20 von 32 Druckdatum: 08.06.2016


SIEMENS AG Upstream 3VA2 molded case circuit breaker *)
Limit current with selectivity Is [kA] Line protection
for 230 / 415 V AC Trip Unit ETU320 / ETU330 / ETU350 / ETU550 / ETU560 / ETU850 / ETU860 ETU340
acc. to IEC 60947-2 Size 100 A 160 A 250 A 400 A 630 A 160 A 250 A 400 A 630 A
36 (B) / 55 (M) /
36 (S) / 55 (M) / 55 (M) / 85 (H) /
Edition 05/2016 Icu [kA] 85 (H) / 110 (C) / 150 (L) 36 (S) / 55 (M) / 85 (H) / 110 (C) / 150 (L) 150 (L) 55 (M) / 85 (H) / 110 (C) / 150 (L)
85 (H) / 110 (C) 110 (C)
150 (L)
Characteristic 25 25 25 25 25

Icn [kA]

Icu [kA]
40 40 40 40 40
In [A] 160 160 160 250 250 400 400 630 160 250 400 500 630
63 63 63 63 63
100 100 100 100 100
80 T 2.3 T T T T T T T T T T T
miniature circuit breaker

100 T 2.2 T T T T T T T T T T T
10
Downstream 5SP4

B
Line protection

125 T T T T T T T T T T T
80 T 2.3 T T T T T T T T T T T
10

100 T 2.2 T T T T T T T T T T T
10
C

125 T T T T T T T T T T T
80 T 2.2 T T T T T T T T T T T
10
D

100 T 2.2 T T T T T T T T T T T

Selektivitätstabellen_en_06_2016.xlsx 4.4) 3VA2 - 5SP4 21 von 31 Druckdatum:08.06.2016


SIEMENS AG Upstream 3VA2 molded case circuit breaker *)
Limit current with selectivity Is [kA]
for 230 / 415 V AC Line protection
acc. to IEC 60947-2
Trip Unit ETU320 / ETU330 / ETU350 / ETU550 / ETU560 / ETU850 / ETU860 ETU340

Edition 05/2016 Size 100 A 160 A 250 A 400 A 630 A 160 A 250 A 400 A 630 A
36 (B) / 55 (M) /
Icu [kA] 36 (S) / 55 (M) / 85 (H) / 110 (C) 150 (L) 36 (S) / 55 (M) / 85 (H) / 110 (C) / 150 (L) 55 (M) / 85 (H) / 110 (C) 150 (L) 55 (M) / 85 (H) / 110 (C) / 150 (L)
85 (H) / 110 (C) / 150 (L)

Characteristic

Icn [kA]

Icu [kA]
In [A] 25 40 63 100 25 40 63 100 160 25 40 63 100 160 160 250 250 400 400 630 25 40 63 100 25 40 63 100 160 250 400 500 630

1 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35
1.6 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35
35 2 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35
3 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35
4 16 35 35 35 16 35 35 35 35 16 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35
6 16 35 35 35 16 35 35 35 35 16 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35
8 16 20 20 20 16 20 20 20 20 16 20 20 20 20 20 20 20 20 20 20 20 20 20 20 6.8 20 20 20 20 20 20 20 20
10 9.4 20 20 20 12 20 20 20 20 5.5 20 20 20 20 20 20 20 20 20 20 20 20 20 20 6.8 20 20 20 20 20 20 20 20
10
A

13 6.2 16 20 20 6.8 20 20 20 20 4.7 14 20 20 20 20 20 20 20 20 20 7.1 20 20 20 5.4 20 20 20 20 20 20 20 20


16 5.4 16 20 20 5.7 20 20 20 20 4.3 13 20 20 20 20 20 20 20 20 20 7.1 20 20 20 5.4 20 20 20 20 20 20 20 20
20

20 16 19 20 16 20 20 20 13 20 20 20 20 20 20 20 20 20 17 20 20 11 20 20 20 20 20 20 20
25 14 19 20 15 20 20 20 10 20 20 20 20 20 20 20 20 20 17 20 20 11 20 20 20 20 20 20 20
32 19 20 20 20 20 18 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20
40 8 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
50 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
15

63 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
6 16 35 35 35 16 35 35 35 35 8.1 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35
35

10 5.7 20 20 20 6.4 20 20 20 20 4.5 20 20 20 20 20 20 20 20 20 20 20 20 20 20 6.8 20 20 20 20 20 20 20 20


13 4.5 16 20 20 5 20 20 20 20 3.7 9.6 20 20 20 20 20 20 20 20 20 7.1 20 20 20 5.4 20 20 20 20 20 20 20 20
16 3.7 14 20 20 5 20 20 20 20 3.7 9.6 20 20 20 20 20 20 20 20 20 7.1 20 20 20 5.4 20 20 20 20 20 20 20 20
20

20 7.7 19 20 10 20 20 20 6.3 19 20 20 20 20 20 20 20 20 17 20 20 11 20 20 20 20 20 20 20
10
B

25 7.6 19 20 10 20 20 20 6.3 19 20 20 20 20 20 20 20 20 17 20 20 11 20 20 20 20 20 20 20
32 18 20 20 20 20 18 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20
40 8 15 15 15 15 7 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
50 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
15

63 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
0.3 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35
0.5 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35
1 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35
Downstream 5SY4 miniature circuit breaker

1.6 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35
2 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35
2.5 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35
35

3 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35
3.5 5.6 35 35 35 9.8 35 35 35 35 5.6 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35
Line protection

4 5.6 35 35 35 9.8 35 35 35 35 5.6 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35


5 5.6 35 35 35 9.8 35 35 35 35 5.6 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35
6 5.6 35 35 35 9.8 35 35 35 35 5.6 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35
8 4.5 20 20 20 6.4 20 20 20 20 4.5 20 20 20 20 20 20 20 20 20 20 20 20 20 20 6.8 20 20 20 20 20 20 20 20
10 4.5 20 20 20 6.4 20 20 20 20 4.5 20 20 20 20 20 20 20 20 20 20 20 20 20 20 6.8 20 20 20 20 20 20 20 20
13 3.7 9.6 20 20 5 20 20 20 20 3.7 9.6 20 20 20 20 20 20 20 20 20 7.1 20 20 20 5.4 20 20 20 20 20 20 20 20
10
C

15 3.7 9.6 20 20 5 20 20 20 20 3.7 9.6 20 20 20 20 20 20 20 20 20 7.1 20 20 20 5.4 20 20 20 20 20 20 20 20


16 3.7 9.6 20 20 5 20 20 20 20 3.7 9.6 20 20 20 20 20 20 20 20 20 7.1 20 20 20 5.4 20 20 20 20 20 20 20 20
20

20 6.3 19 20 10 20 20 20 6.3 19 20 20 20 20 20 20 20 20 17 20 20 11 20 20 20 20 20 20 20
25 6.3 19 20 10 20 20 20 6.3 19 20 20 20 20 20 20 20 20 17 20 20 11 20 20 20 20 20 20 20
30 18 20 20 20 20 18 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20
32 18 20 20 20 20 18 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20
35 7 15 15 15 15 7 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
40 7 15 15 15 15 7 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
45 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
50 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
15

60 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
63 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
80

Selektivitätstabellen_en_06_2016.xlsx4.5) 3VA2 - 5SY 22 von 31 Druckdatum: 08.06.2016


SIEMENS AG Upstream 3VA2 molded case circuit breaker *)
Limit current with selectivity Is [kA]
for 230 / 415 V AC Line protection
acc. to IEC 60947-2
Trip Unit ETU320 / ETU330 / ETU350 / ETU550 / ETU560 / ETU850 / ETU860 ETU340

Edition 05/2016 Size 100 A 160 A 250 A 400 A 630 A 160 A 250 A 400 A 630 A
36 (B) / 55 (M) /
Icu [kA] 36 (S) / 55 (M) / 85 (H) / 110 (C) 150 (L) 36 (S) / 55 (M) / 85 (H) / 110 (C) / 150 (L) 55 (M) / 85 (H) / 110 (C) 150 (L) 55 (M) / 85 (H) / 110 (C) / 150 (L)
85 (H) / 110 (C) / 150 (L)

Characteristic

Icn [kA]

Icu [kA]
In [A] 25 40 63 100 25 40 63 100 160 25 40 63 100 160 160 250 250 400 400 630 25 40 63 100 25 40 63 100 160 250 400 500 630

0.3 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
0.5 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
1 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
1.6 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
35

2 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
3 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
4 8.7 16 16 16 9.7 16 16 16 16 5.4 16 16 16 16 16 16 16 16 16 16 9.7 16 16 16 5.4 16 16 16 16 16 16 16 16
6 5.9 16 16 16 7.1 16 16 16 16 4.5 16 16 16 16 16 16 16 16 16 16 7.1 16 16 16 4.5 16 16 16 16 16 16 16 16
8 4.6 16 16 16 4.9 16 16 16 16 3.5 9.5 16 16 16 16 16 16 16 16 16 4.9 16 16 16 3.5 9.5 16 16 16 16 16 16 16
10
D

10 4.4 16 16 16 4.5 16 16 16 16 3.2 9.5 16 16 16 16 16 16 16 16 16 4.5 16 16 16 3.2 9.5 16 16 16 16 16 16 16


13 4.2 16 16 16 4.3 16 16 16 16 3.2 9.5 16 16 16 16 16 16 16 16 16 4.3 16 16 16 3.2 9.5 16 16 16 16 16 16 16
16 3.7 11 16 16 4 11 16 16 16 3 6.2 16 16 16 16 16 16 16 16 16 4 11 16 16 3 6.2 16 16 16 16 16 16 16
20

20 5.2 8 8 3.2 5.2 16 16 16 3.6 4.9 16 16 16 16 16 16 16 16 3.2 5.2 16 16 3.6 4.9 16 16 16 16 16 16


25 4.2 8 8 4.6 16 16 16 3.6 4.6 16 16 16 16 16 16 16 16 4.6 16 16 3.6 4.6 16 16 16 16 16 16
32 8 8 4.2 15 16 16 4.3 16 16 16 16 16 16 16 16 4.2 15 16 4.3 16 16 16 16 16 16
40 8 8 9 15 15 3.6 5.5 15 15 15 15 15 15 15 9 15 3.6 5.5 15 15 15 15 15
50 8 15 15 5.5 15 15 15 15 15 15 15 15 5.5 15 15 15 15 15
15

63 8 15 5.5 15 15 15 15 15 15 15 5.5 15 15 15 15 15
2 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35
4 16 35 35 35 16 35 35 35 35 16 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35
30

6 16 35 35 35 16 35 35 35 35 8.1 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35
10 5.7 20 20 20 6.4 20 20 20 20 4.5 20 20 20 20 20 20 20 20 20 20 20 20 20 20 6.8 20 20 20 20 20 20 20 20
13 4.5 16 20 20 5 20 20 20 20 3.7 9.6 20 20 20 20 20 20 20 20 20 7.1 20 20 20 5.4 20 20 20 20 20 20 20 20
16 3.7 14 20 20 5 20 20 21 20 3.7 9.6 20 20 20 20 20 20 20 20 20 7.1 20 20 20 5.4 20 20 20 20 20 20 20 20
15
B

20 7.7 19 20 10 20 20 20 6.3 19 20 20 20 20 20 20 20 20 17 20 20 11 20 20 20 20 20 20 20
25 7.6 19 20 10 20 20 20 6.3 19 20 20 20 20 20 20 20 20 17 20 20 11 20 20 20 20 20 20 20
32 18 20 20 20 20 18 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20
40 8 15 15 15 15 7 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
50 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
10

63 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
0.3 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35
0.5 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35
1 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35
1.6 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35
35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35
stream 5SY6 miniature circuit breaker (except 5SY60)

2
30

3 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35
4 5.6 35 35 35 9.8 35 35 35 35 5.6 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35
5 5.6 35 35 35 9.8 35 35 35 35 5.6 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35
6 5.6 35 35 35 9.8 35 35 35 35 5.6 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35
8 4.5 20 20 20 6.4 20 20 20 20 4.5 20 20 20 20 20 20 20 20 20 20 20 20 20 20 6.8 20 20 20 20 20 20 20 20
10 4.5 20 20 20 6.4 20 20 20 20 4.5 20 20 20 20 20 20 20 20 20 20 20 20 20 20 6.8 20 20 20 20 20 20 20 20
C

13 3.7 9.6 20 20 5 20 20 20 20 3.7 9.6 20 20 20 20 20 20 20 20 20 7.1 20 20 20 5.4 20 20 20 20 20 20 20 20


Line protection

15 3.7 9.6 20 20 5 20 20 20 20 3.7 9.6 20 20 20 20 20 20 20 20 20 7.1 20 20 20 5.4 20 20 20 20 20 20 20 20


16 3.7 9.6 20 20 5 20 20 20 20 3.7 9.6 20 20 20 20 20 20 20 20 20 7.1 20 20 20 5.4 20 20 20 20 20 20 20 20
15

20 6.3 20 20 10 20 20 20 6.3 20 20 20 20 20 20 20 20 20 20 20 20 11 20 20 20 20 20 20 20
25 6.3 20 20 10 20 20 20 6.3 20 20 20 20 20 20 20 20 20 20 20 20 11 20 20 20 20 20 20 20
30 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20
32 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20
40 7 15 15 15 15 7 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
50 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
10

63 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15

Selektivitätstabellen_en_06_2016.xlsx4.5) 3VA2 - 5SY 23 von 31 Druckdatum: 08.06.2016


SIEMENS AG Upstream 3VA2 molded case circuit breaker *)
Limit current with selectivity Is [kA]
for 230 / 415 V AC Line protection
acc. to IEC 60947-2
Trip Unit ETU320 / ETU330 / ETU350 / ETU550 / ETU560 / ETU850 / ETU860 ETU340

Edition 05/2016 Size 100 A 160 A 250 A 400 A 630 A 160 A 250 A 400 A 630 A
36 (B) / 55 (M) /
Icu [kA] 36 (S) / 55 (M) / 85 (H) / 110 (C) 150 (L) 36 (S) / 55 (M) / 85 (H) / 110 (C) / 150 (L) 55 (M) / 85 (H) / 110 (C) 150 (L) 55 (M) / 85 (H) / 110 (C) / 150 (L)
85 (H) / 110 (C) / 150 (L)

Characteristic

Icn [kA]

Icu [kA]
In [A] 25 40 63 100 25 40 63 100 160 25 40 63 100 160 160 250 250 400 400 630 25 40 63 100 25 40 63 100 160 250 400 500 630
Downs

0.3 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
0.5 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
1 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
1.6 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
30

2 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
3 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
4 8.7 16 16 16 9.7 16 16 16 16 5.4 16 16 16 16 16 16 16 16 16 16 9.7 16 16 16 5.4 16 16 16 16 16 16 16 16
6 5.9 16 16 16 7.1 16 16 16 16 4.5 16 16 16 16 16 16 16 16 16 16 7.1 16 16 16 4.5 16 16 16 16 16 16 16 16
8 4.6 16 16 16 4.9 16 16 16 16 3.5 9.5 16 16 16 16 16 16 16 16 16 4.9 16 16 16 3.5 9.5 16 16 16 16 16 16 16
D

10 4.4 16 16 16 4.5 16 16 16 16 3.2 9.5 16 16 16 16 16 16 16 16 16 4.5 16 16 16 3.2 9.5 16 16 16 16 16 16 16


13 4.2 16 16 16 4.3 16 16 16 16 3.2 9.5 16 16 16 16 16 16 16 16 16 4.3 16 16 16 3.2 9.5 16 16 16 16 16 16 16
16 3.7 11 16 16 4 11 16 16 16 3 6.2 16 16 16 16 16 16 16 16 16 4 11 16 16 3 6.2 16 16 16 16 16 16 16
15

20 5.2 8 8 3.2 5.2 16 16 16 3.6 4.9 16 16 16 16 16 16 16 16 3.2 5.2 16 16 3.6 4.9 16 16 16 16 16 16


25 4.8 8 8 4.6 16 16 16 3.6 4.6 16 16 16 16 16 16 16 16 4.6 16 16 3.6 4.6 16 16 16 16 16 16
32 8 8 15 16 16 4.3 16 16 16 16 16 16 16 16 15 16 4.3 16 16 16 16 16 16
40 8 8 9 15 15 3.6 5.5 15 15 15 15 15 15 15 9 15 3.6 5.5 15 15 15 15 15
50 8 15 15 5.5 15 15 15 15 15 15 15 15 5.5 15 15 15 15 15
10

63 8 15 5.5 15 15 15 15 15 15 15 5.5 15 15 15 15 15
6 16 40 40 40 16 40 40 40 40 8.1 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40
30 40

10 5.7 30 30 30 6.4 30 30 30 30 4.5 30 30 30 30 30 30 30 30 30 30 24 30 30 30 6.8 30 30 30 30 30 30 30 30


13 4.5 16 25 25 5 25 25 25 25 3.7 9.6 25 25 25 25 25 25 25 25 25 7.1 25 25 25 5.4 25 25 25 25 25 25 25 25
16 3.7 14 25 25 5 25 25 25 25 3.7 9.6 25 25 25 25 25 25 25 25 25 7.1 25 25 25 5.4 25 25 25 25 25 25 25 25
20 7.7 19 25 3.6 10 25 25 25 6.3 19 25 25 25 25 25 25 25 25 17 25 25 11 25 25 25 25 25 25 25
25
15
B

25 7.6 19 25 10 25 25 25 6.3 19 25 25 25 25 25 25 25 25 17 25 25 11 25 25 25 25 25 25 25
32 18 25 10 25 25 25 18 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25
40 8 20 20 20 20 7 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20
15 20

50 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20
63 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20
0.3 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
0.5 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
1 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
50

1.6 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
2 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
3 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40
nstream 5SY7 miniature circuit breaker

4 5.6 40 40 40 9.8 40 40 40 40 5.6 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40


40

6 5.6 40 40 40 9.8 40 40 40 40 5.6 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40


8 4.5 30 30 30 6.4 30 30 30 30 4.5 30 30 30 30 30 30 30 30 30 30 24 30 30 30 6.8 30 30 30 30 30 30 30 30
15

30
C

10 4.5 30 30 30 6.4 30 30 30 30 4.5 30 30 30 30 30 30 30 30 30 30 24 30 30 30 6.8 30 30 30 30 30 30 30 30


13 3.7 9.6 25 25 5 25 25 25 25 3.7 9.6 25 25 25 25 25 25 25 25 25 7.1 25 25 25 5.4 25 25 25 25 25 25 25 25
Line protection

16 3.7 9.6 25 25 5 25 25 25 25 3.7 9.6 25 25 25 25 25 25 25 25 25 7.1 25 25 25 5.4 25 25 25 25 25 25 25 25


20 6.3 19 25 10 25 25 25 6.3 19 25 25 25 25 25 25 25 25 17 25 25 11 25 25 25 25 25 25 25
25

25 6.3 19 25 10 25 25 25 6.3 19 25 25 25 25 25 25 25 25 17 25 25 11 25 25 25 25 25 25 25
32 18 25 25 25 25 18 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25
40 7 20 20 20 20 7 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20
50 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20
20

63 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20

Selektivitätstabellen_en_06_2016.xlsx4.5) 3VA2 - 5SY 24 von 31 Druckdatum: 08.06.2016


SIEMENS AG Upstream 3VA2 molded case circuit breaker *)
Limit current with selectivity Is [kA]
for 230 / 415 V AC Line protection
acc. to IEC 60947-2
Trip Unit ETU320 / ETU330 / ETU350 / ETU550 / ETU560 / ETU850 / ETU860 ETU340

Edition 05/2016 Size 100 A 160 A 250 A 400 A 630 A 160 A 250 A 400 A 630 A
36 (B) / 55 (M) /
Icu [kA] 36 (S) / 55 (M) / 85 (H) / 110 (C) 150 (L) 36 (S) / 55 (M) / 85 (H) / 110 (C) / 150 (L) 55 (M) / 85 (H) / 110 (C) 150 (L) 55 (M) / 85 (H) / 110 (C) / 150 (L)
85 (H) / 110 (C) / 150 (L)

Characteristic

Icn [kA]

Icu [kA]
In [A] 25 40 63 100 25 40 63 100 160 25 40 63 100 160 160 250 250 400 400 630 25 40 63 100 25 40 63 100 160 250 400 500 630

16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
Down

0.3
0.5 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
1 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
50
1.6 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
2 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
3 16 16 16 16 16 16 16 16 16 15 16 16 16 16 16 16 16 16 16 16 16 16 16 16 15 16 16 16 16 16 16 16 16
4 8.7 16 16 16 9.7 16 16 16 16 5.4 16 16 16 16 16 16 16 16 16 16 9.7 16 16 16 5.4 16 16 16 16 16 16 16 16
40

6 5.9 16 16 16 7.1 16 16 16 16 4.5 16 16 16 16 16 16 16 16 16 16 7.1 16 16 16 4.5 16 16 16 16 16 16 16 16


8 4.6 16 16 16 4.9 16 16 16 16 3.5 9.5 16 16 16 16 16 16 16 16 16 4.9 16 16 16 3.5 9.5 16 16 16 16 16 16 16
30
15
D

10 4.2 16 16 16 4.5 16 16 16 16 3.2 9.5 16 16 16 16 16 16 16 16 16 4.5 16 16 16 3.2 9.5 16 16 16 16 16 16 16


13 4 16 16 16 4.3 16 16 16 16 3.2 9.5 16 16 16 16 16 16 16 16 16 4.3 16 16 16 3.2 9.5 16 16 16 16 16 16 16
16 3.7 11 16 16 4 11 16 16 16 3 6.2 16 16 16 16 16 16 16 16 16 4 11 16 16 3 6.2 16 16 16 16 16 16 16
20 5.2 8 8 5.2 16 16 16 5.8 4.9 16 16 16 16 16 16 16 16 5.2 16 16 5.8 4.9 16 16 16 16 16 16
25

25 4.6 8 8 4.8 16 16 16 5.5 4.6 16 16 16 16 16 16 16 16 4.8 16 16 5.5 4.6 16 16 16 16 16 16


32 8 8 16 16 16 4.3 16 16 16 16 16 16 16 16 T 16 4.3 16 16 16 16 16 16
40 8 8 9 16 16 3.6 5.5 16 16 16 16 16 16 16 9 16 3.6 5.5 16 16 16 16 16
15 20

50 8 15 15 5.5 T 15 15 15 15 15 15 15 5.5 15 15 15 15 15
63 8 15 15 5.5 T 15 15 15 15 15 15 15 5.5 15 15 15 15 15
0.3 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
0.5 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
1 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
70

1.6 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
2 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
3 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40
4 14 40 40 40 15 40 40 40 40 7.7 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40
50

6 5.6 40 40 40 9.8 40 40 40 40 5.6 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40


8 4.9 40 40 40 6.4 40 40 40 40 4.5 40 40 40 40 40 40 40 40 40 40 24 40 40 40 6.8 40 40 40 40 40 40 40 40
k.A.

40
C

10 4.7 40 40 40 6.4 40 40 40 40 4.5 30 40 40 40 40 40 40 40 40 40 24 40 40 40 6.8 30 40 40 40 40 40 40 40


13 3.9 14 30 30 5 25 30 30 30 3.7 9.6 30 30 30 30 30 30 30 30 30 7.1 25 30 30 5.4 25 30 30 30 30 30 30 30
16 3.7 10 30 30 5 25 30 30 30 3.7 9.6 30 30 30 30 30 30 30 30 30 7.1 25 30 30 5.4 25 30 30 30 30 30 30 30
Downstream 5SY8 miniature circuit breaker

20 6.3 19 8 10 30 30 30 6.3 19 30 30 30 30 30 30 30 30 17 30 30 11 25 30 30 30 30 30 30
30

25 6.3 19 8 10 30 30 30 6.3 19 30 30 30 30 30 30 30 30 17 30 30 11 25 30 30 30 30 30 30
32 18 8 30 30 30 18 30 30 30 30 30 30 30 30 30 30 25 30 30 30 30 30 30
40 8 8 25 25 25 7 25 25 25 25 25 25 25 25 25 25 20 25 25 25 25 25 25
Line protection

50 8 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25
25

63 8 20 20 20 20 20 20 25 25 25 25 20 20 20 25 25 25 25
0.3 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40
0.5 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40
1 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40
70

1.6 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40
2 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40
3 40 40 40 40 40 40 40 40 40 15 40 40 40 40 40 40 40 40 40 40 40 40 40 40 15 40 40 40 40 40 40 40 40
4 8.7 40 40 40 9.7 40 40 40 40 5.4 40 40 40 40 40 40 40 40 40 40 9.7 40 40 40 5.4 40 40 40 40 40 40 40 40
50

6 5.9 40 40 40 7.1 40 40 40 40 4.5 40 40 40 40 40 40 40 40 40 40 7.1 40 40 40 4.5 40 40 40 40 40 40 40 40


8 4.6 40 40 40 4.9 40 40 40 40 3.5 9.5 40 40 40 40 40 40 40 40 40 4.9 40 40 40 3.5 9.5 40 40 40 40 40 40 40
k.A.

40
D

10 4.2 40 40 40 4.5 40 40 40 40 3.2 9.5 40 40 40 40 40 40 40 40 40 4.5 40 40 40 3.2 9.5 40 40 40 40 40 40 40


13 4 28 30 30 4.3 30 30 30 30 3.2 9.5 30 30 30 30 30 30 30 30 30 4.3 30 30 30 3.2 9.5 30 30 30 30 30 30 30
16 3.7 11 30 30 4 11 30 30 30 3 6.2 30 30 30 30 30 30 30 30 30 4 11 30 30 3 6.2 30 30 30 30 30 30 30
20 5.2 8 8 5.2 30 30 30 5.8 4.9 30 30 30 30 30 30 30 30 5.2 30 30 5.8 4.9 30 30 30 30 30 30
30

25 4.6 8 8 4.8 25 25 25 5.5 4.6 30 30 25 25 30 30 30 30 4.8 25 25 5.5 4.6 30 25 30 30 30 30


32 8 8 20 25 25 4.3 25 25 25 25 30 30 30 30 20 25 4.3 25 25 30 30 30 30
40 8 8 9 20 20 3.6 5.5 20 20 20 25 25 25 25 9 20 3.6 5.5 20 25 25 25 25
20 25

50 8 15 15 5.5 15 15 15 15 15 15 15 15 5.5 15 15 15 15 15
63 8 15 15 5.5 15 15 15 15 15 15 15 15 5.5 15 15 15 15 15

Angaben zur totalen Selektivität, gekennzeichnet mit "T", beziehen sich auf das Ausschaltvermögen Icu der Geräte.
*) The limit currents with selectivity for the upstream circuit breakers apply to the maximum value I imax for adjustable trip units.

Selektivitätstabellen_en_06_2016.xlsx4.5) 3VA2 - 5SY 25 von 31 Druckdatum: 08.06.2016


SIEMENS AG Upstream 3VA1 molded case circuit breaker *)
Limit current with selectivity Is [kA]
Line protection
for 230 / 415 V AC
acc. to IEC 60947-2 Trip Unit TM210 / TM220 / TM240
Size 100 A 160 A 250 A
Edition 05/2016
Icu [kA] 16 (B) / 25 (N) / 36 (S) 25 (N) / 36 (S) / 55 (M) / 70 (H) 25 (N) / 36 (S) / 55 (M) / 70 (H)
25 25

Icu [kA]

Un [V]

Size
fuse
In [A] 16 20 32 50 63 80 100 16 20 32 50 63 80 100 125 160 160 200 250
40 40
2
4
T T T T T T T T T T T T T T T T T T T
6
10
16 T T T T T T T T T T T T T T T T T
20 T T T T T T T T T T T T T T T
25 T T T T T T T T T T T T T
32 T T T T T T T T T T T
000

35
T T T T T T T T T
40
50
T T T T T
63
80
T T T
100
125 6.3 9 T
160 3.5
35 T T T T T T T T T
50
T T T T T
63
00

80
100 T T T
Downstream 3NA LV HRC fuse

125
6
T T T T T T T T T T T T T T T T T T T
10
400 / 500 / 690
Line protection

16 T T T T T T T T T T T T T T T T T
Type gG

20 T T T T T T T T T T T T T T T
120

25 T T T T T T T T T T T T T
32 T T T T T T T T T
35 T T T T T T T T T
0

40 T T T T T T T
50
T T T T T
63
80
100 T T T
125
16 T T T T T T T T T T T T T T T T T
20 T T T T T T T T T T T T T T T
25 T T T T T T T T T T T T T
35 T T T T T T T T T
40 T T T T T T T T T
1

50
T T T T T
63
80
100 T T T
125

Selektivitätstabellen_en_06_2016.xlsx5.1) 3VA1 - 3NA 26 von 31 Druckdatum: 08.06.2016


SIEMENS AG Upstream 3VA1 molded case circuit breaker *)
Limit current with selectivity Is [kA]
Line protection
for 230 / 415 V AC
acc. to IEC 60947-2 Trip Unit TM210 / TM220 / TM240
Size 100 A 160 A 250 A
Edition 05/2016
Icu [kA] 16 (B) / 25 (N) / 36 (S) 25 (N) / 36 (S) / 55 (M) / 70 (H) 25 (N) / 36 (S) / 55 (M) / 70 (H)
25 25

Icu [kA]

Un [V]

Size
fuse
In [A] 16 20 32 50 63 80 100 16 20 32 50 63 80 100 125 160 160 200 250
40 40
35 T T T T T T T T T
50 T T T T T
63 T T T T
80

2
100 T T T
125
160 T
D01 / D02 / D03
5SE2 (Neozed)

Line protection

35
Downstream

Type gG

40
fuse

400

T T T
50

50
63

*) The limit currents with selectivity for the upstream circuit breakers apply to the maximum value I imax for adjustable trip units.

Selektivitätstabellen_en_06_2016.xlsx5.1) 3VA1 - 3NA 27 von 31 Druckdatum: 08.06.2016


SIEMENS AG Upstream 3VA2 molded case circuit breaker *)
Limit current with selectivity Is [kA] Line protection
for 230 / 415 V AC Trip Unit ETU320 / ETU330 / ETU340 / ETU350 / ETU550 / ETU560 / ETU850 / ETU860
acc. to IEC 60947-2 Size 100 A 160 A 250 A 400 A 630 A
55 (M) 55 (M) 55 (M)
55 (M)
Edition 05/2016 Icu [kA] 85 (H) 150 (L) 85 (H) 150 (L) 110 (C) 150 (L) 85 (H) 150 (L) 55 (M) 85 (H) 110 (C)
85 (H)
110 (C) 110 (C) 110 (C)
25
25 25

Un [V] fuse
40 400 400 400
Icu [kA] 40 40 160 160 250 250

Size
In [A] 63 25 40 63 100 160 160 250 500 500 500
63 63 250 250 400 400
100 630 630 630
100 100
160
2, 4, 6, 10, 16, 20, 25, 32, 35, 40, 50, 63, 80 T T T T T T T T T T T T T T T T T
100 T T T T T T T T T T

000
125 T T T 2.7 5.3 T T T T T
160 2.3 T
35, 50, 63, 80 T T T T T T T T T T T T T T T
100, 125 T T T T T T T T T T
00

160 T 85 T T T T T
Downstream 3NA LV HRC fuse

6, 10, 16, 20, 25, 32, 35, 40, 50, 63, 80 T T T T T T T T T T T T T T T T T


100, 125 T T T T T T T T T T
0

160 T 85 T T T T T
400 / 500 / 690
Line protection

16, 20, 25, 35, 40, 50, 63, 80 T T T T T T T T T T T T T T T T T


Type gG

100, 125 T T T T T T T T T T
120

160, 200 T 85 T T T T T
224, 250 T T T T
35, 50, 63, 80 T T T T T T T T T T T T T T T
100, 125 T T T T T T T T T T
160, 200 T 85 T T T T T
2

224, 250 T T T T
300, 315, 355, 400 T T T
200 T 85 T T T T T
224, 250 T T T T
3

300, 315, 355, 400, 425 T T T


500 T 59 59
500 33 33 33
4a

35
Downstream 5SE2

D01 / D02 / D03


Line protection
(Neozed) fuse

40 T T T T T T T
Type gG

50
400
50

63 2.3 2.3 T T T T

s
*) The limit currents with selectivity for the upstream circuit breakers apply to the maximum value I imax for adjustable trip units.

Selektivitätstabellen_en_06_2016.xlsx5.2) 3VA2 - 3NA 28 von 31 Druckdatum: 08.06.2016


SIEMENS AG Upstream 3VL molded case circuit breaker *)
Limit current with selectivity Is [kA]
for 230 / 415 V AC 3VL1 3VL3 3VL4 3VL5 3VL6 3VL7 3VL8
acc. to IEC 60947-2
Line protection

Edition 05/2016 Trip Unit TM TM ETU TM ETU TM ETU ETU ETU ETU

Icu [kA] 55 / 70 55 / 70 / 100 55 / 70 / 100 55 / 70 / 100 55 / 70 / 100 55 / 70 / 100 55 / 70 / 100 55 / 70 / 100 55 / 70 / 100 55 70 100
Trip Unit

Icu [kA]
Size

In [A] 160 200 250 200 250 200 250 315 400 315 400 315 400 500 630 630 800 1000 1250 1600

16
20
2.8 4.1 7.9 2.8 3.9 7.2 8.1 8.7 T 8.3 8.3 T T T T T T T T T T T
25
32
16 (B) 40
50
63 3.1 4.6 3.7 4.5 6.1 6.8 12 7 7 12 T T T T T T T T T T
80
100
16
20
2.8 4.1 7.9 2.8 3.9 7.2 8.1 8.7 T 8.3 8.3 T T T T T T T T T T T
25
32
100 A

25 (N) 40
50
63 3.1 4.6 3.7 4.5 6.1 6.8 12 7 7 12 T T T 17 T T T T T T
80
100
16
20
2.8 4.1 7.9 2.8 3.9 7.2 8.1 8.7 T 8.3 8.3 T T T T 27 T T T T T T
25
32
40
TM210 / TM220

36 (S)
50
Downstream 3VA1 molded case circuit breaker

63 3.1 4.6 3.7 4.5 6.1 6.8 12 7 7 12 T T T 17 31 T T T T T


Line protection

80
100
16
20
2.8 4.1 7.9 2.8 3.9 7.2 8.1 8.7 T 8.3 8.3 T T T T T T T T T T T
25
32
40
25 (N) 50
63 3.1 4.6 3.7 4.5 6.1 6.8 12 7 7 12 T T T 17 T T T T T T
80
100
125
4.4 2.8 4.3 5.6 6 8.9 6.2 6.2 6.9 15 19 T 16 T T T T T T
160 A

160
16
20
2.8 4.1 7.9 2.8 3.9 7.2 8.1 8.7 T 8.3 8.3 T T T T 27 T T T T T T
25
32
36 (S) 40
55 (M) 50
70 (H) 63 3.1 4.6 3.7 4.5 6.1 6.8 12 7 7 12 T T T 17 31 T T T T T
80
100
125
4.4 2.8 4.3 5.6 6 8.9 6.2 6.2 6.9 15 19 T 16 26 T T T T T
160
25 (N)
160
TM240

36 (S)
250 A

200 19 31 31 T 65 65
55 (M)
250
70 (H)
32 T T T T T T
40
Starter protection

50
55 (M)
160 A

63 31 T T T T T
TM120M

70 (H)
80
100
125 26 T T T T T
55 (M) 160
250 A

19 31 31 T 65 65
70 (H) 200

*) The limit currents with selectivity for the upstream circuit breakers apply to the maximum value I imax for adjustable trip units.

Selektivitätstabellen_en_06_2016.xlsx6.1) 3VL - 3VA1 29 von 31 Druckdatum: 08.06.2016


SIEMENS AG Upstream 3VL molded case circuit breaker *)
Limit current with selectivity Is [kA]
for 230 / 415 V AC 3VL3 3VL4 3VL5 3VL6 3VL7 3VL8
acc. to IEC 60947-2
Anlagenschutz

Edition 05/2016 Trip Unit ETU TM ETU TM ETU ETU ETU ETU
Icu [kA] 55 / 70 / 100 55 / 70 / 100 55 / 70 / 100 55 / 70 / 100 55 / 70 / 100 55 / 70 / 100 55 / 70 / 100 55 / 70 / 100
Trip Unit

Icu [kA]
Size

In [A] 250 250 315 400 315 400 315 400 500 630 630 800 1000, 1250 1600

25
55 (M)
40
85 (H) 4.2 4.8 10 7.4 7.4 3.4 6.7 8.3 13 13 22 T T
ETU320 / ETU330 / ETU340 / ETU350 / ETU550 / ETU560 / ETU850 / ETU860

63
110 (C)
100 A 100
25
40
150 (L) 13 36 78
63
100
25
55 (M) 40
85 (H) 63 3.5 4 5.3 5.1 5.1 3.2 4.5 5.3 11 11 16 55 T
110 (C) 100
160 A 160
Line protection

25
40
Downstream 3VA2 molded case circuit breaker

150 (L) 63 13 36 78
100
160
55 (M)
85 (H) 160
250 A 2.7 3.2 4 3.5 4.4 4 5 6.9 7.7 13 36 78
110 (C) 250
150 (L)
55 (M)
250
85 (H) 5.4 6 7.8 18 33
400
400 A 110 (C)
250
150 (L) 7.8 18 33
400
55 (M) 400
630 A 85 (H) 500 7.4 16 27
110 (C) 630
25
Motor protection

40
160 A 16 55 T
ETU350M /
ETU860M

63
55 (M)
100
110 (H)
250 A 160 13 36 78
400 A 250 7.8 18 33
630 A 400 7.4 16 27
25
Starter protection

40
160 A 16 55 T
ETU310M

63
110 (H) 100
250 A 160 13 36 78
400 A 250 7.8 18 33
630 A 400 7.4 16 27

*) The limit currents with selectivity for the upstream circuit breakers apply to the maximum value I imax for adjustable trip units.

Selektivitätstabellen_en_06_2016.xlsx6.2) 3VL - 3VA2 30 von 31 Druckdatum: 08.06.2016


SIEMENS AG Upstream 3NA LV HRC fuse *)
Limit current with selectivity Is [kA]
for 230 / 415 V AC Line protection
acc. to IEC 60947-2
Type gG

Edition 05/2016 Icu [kA] 120

Un fuse [V] 400 / 500 / 690

Size 000 00 0 1 2 3 4 4a
Trip Unit

Icu [kA]
Size

In [A] 160 125 160 125 160 125 160 200 224 250 125 160 200 224 250 300 315 355 400 200 224 250 300 315 355 400 425 500 630 630 800 1000 1250 500 630 800 1000 1250

16
16 (B) / 25 (N) / 36 (S)

20
3.8 2.4 3.7 2.4 3.8 2.4 3.8 7.9 9.1 35 2.4 3.8 7.9 9.1 T T T T T 7.5 8.9 T T T T T T T T T T T T T T T T T
25
32
100 A

40
50
63 3.1 3 3.1 3.1 5.4 7.2 11 3.1 5.4 7.2 11 T T T T 5 6.9 11 T T T T T T T T T T T T T T T T
80
TM210 / TM220

100
16
25 (N) / 36 (S) / 55 (M) / 70 (H)

20
3.8 2.4 3.7 2.4 3.8 2.4 3.8 7.9 9.1 36 2.4 3.8 7.9 9.1 36 T T T T 7.5 8.9 43 T T T T T T T T T T T T T T T T
25
Downstream 3VA1 molded case circuit breaker

Line protection

32
40
160 A

50
63 3.1 3 3.1 3.1 5.4 7.2 11 3.1 5.4 7.2 11 36 41 T T 5 6.9 11 36 41 T T T T T T T T T T T T T T
80
100
125
5.4 6.2 7.4 5.4 6.2 7.4 16 17 56 T 5 6.1 7.6 16 17 56 T T T T T T T T T T T T T
160
25 (N) / 36 (S) / 55 (M) / 70

160
TM240

250 A

200 4.7 4.9 6.6 9.5 4.7 4.9 6.6 9.5 19 28 T T T T T 19 T T T T


(H)

250

32 3.8 2.4 3.8 2.4 3.8 2.4 3.8 7.9 9.1 35 2.4 3.8 7.9 9.1 35 T T T T 7.5 8.9 43 T T T T T T T T T T T T T T T T
40
Starter protection

50
55 (M) / 70 (H)
160 A / 250 A

63 3.1 3.1 3.1 3.1 5.4 7.2 11 3.1 5.4 7.2 11 33 41 T T 4.9 6.9 11 33 41 T T T T T T T T T T T T T T
TM120M

80
100
125 5.4 6.2 7.4 5.4 6.2 7.4 16 17 56 T 5 6.1 7.6 16 17 56 T T T T T T T T T T T T T
160
4.7 4.9 6.6 9.5 4.7 4.9 6.6 9.5 19 28 T T T T T 19 T T T T
200
*) The limit currents with selectivity for the upstream circuit breakers apply to the maximum value I imax for adjustable trip units.

Selektivitätstabellen_en_06_2016.xlsx7.1) 3NA - 3VA1 31 von 31 Druckdatum: 08.06.2016