Mab 07 PDF
Mab 07 PDF
This guide was developed by the Municipal Advisory Board (MAB) and published with the help of the
members of the Plastics Pipe Institute, Inc. (PPI).
This publication is intended as a guide for engineers, users, contractors, code officials, and other
interested parties for use in the design, construction and installation of high-density polyethylene (HDPE)
pressure water piping systems. The local utility or engineer may need to modify this guide to adapt the
document to local conditions, operations, and practices.
This guide has been prepared by MAB members and associates as a service to the water industry. The
information in this document is offered in good faith and believed to be accurate at the time of its
preparation, but is offered “as is” without express or implied warranties, including WARRANTIES OF
MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. Any reference to a specific
manufacturer’s product is merely illustrative, and not intended as an endorsement of that product.
Reference to or testing of a proprietary product should not be construed as an endorsement by the MAB
or PPI, which do not endorse the proprietary products or processes of any manufacturer. Users are
advised to consult the manufacturer for more detailed information about the specific manufacturer’s
products. The information in this document is offered for consideration by industry members in fulfilling
their own compliance responsibilities. MAB and the PPI assume no responsibility for compliance with
applicable laws and regulations.
The MAB serves as an independent, non-commercial adviser to the Municipal & Industrial (M & I) Division
of the PPI. Once adopted, MAB will consider revising this guide from time to time, in response to
comments and suggestions from the users. Please send suggestions of improvements to Camille
George Rubeiz, PE, F. ASCE, at [email protected].
ACKNOWLEDGEMENT
The Municipal Advisory Board would like to thank Dr. Larry Slavin of Outside Plant Consulting Services,
Inc. for developing and updating this guide that was previously published as PPI TR-46 (2009).
-2-
HDPE MUNICIPAL ADVISORY BOARD MEMBERS
UTILITIES
Marisa Boyce, PE EBMUD, CA
David Freireich, PE City of Round Rock, TX
Todd Jorgenson City of Austin, MN
Robert Justus City of Palo Alto, CA
Holly Link Colorado Springs Utilities, CO
Nelson Perez-Jacome City of Miami Beach, FL
Gordon Mahan San Antonio Water System, TX
Ryan McKaskle, PE City of Tulsa, OK
Eric Shaffer, PE City of Duluth, MN Standards Chair
Jessie Stein, PE Arlington Water Utilities, TX
Matthew Wirtz, PE City of Ft Wayne, IN
UNIVERSITIES
Dr. Alan Atalah, PE Bowling Green State University, OH
Dr. Tom Iseley, PE Purdue University, IN
Dr. Mark Knight, PEng CATT, University of Waterloo, ON
Dr. Mo Najafi, PE CUIRE, University of Texas at Arlington, TX R&D Chair
CONTRACTORS
Todd Grafenauer Murphy Pipelines, WI
David Mancini David Mancini & Sons, FL
Kevin Miller Miller Pipeline Co., IN Education Chair
CONSULTANTS
Luis Aguiar Miami–Dade Water & Sewer (past), Hazen & Sawyer, FL MAB Co-Chair
Alan Ambler, PE City of Casselberry, FL (past), AM Trenchless, FL
Joe Castronovo, PE AECOM (ret.), ASCE UESI, GA
John Fishburne, PE Charlotte Water (past), Freese & Nichols, NC
Steven Kramer, PE COWI North America, Inc., NJ
Ernest Lever Infrastructure Sector, Gas Technology Institute, IL
Greg Scoby, PE City of Palo Alto (past), Crossbore Consultants, CA Utility Chair
Dave Stewart City of Lago Vista (past), Stewart HDPE Consulting, TX
PPI Camille Rubeiz, PE Municipal & Industrial Division (M&I), TX MAB Co-Chair
FORMER MEMBERS:
Dr. Sam Ariaratnam, PE Arizona State University, AZ
Mike Heitmann Garney Construction, MO
Milton Keys Indy Water/Veolia, IN
Matthew Klein Veolia/ Citizens Energy, IN
Ed Lambing, PE San Jose Water Co., CA
Jonathan Leung, PE Los Angeles Dept. of Water and Power, CA
George McGuire Ditch Witch, OK
Dr. Ken Oliphant, PEng JANA, ON
Rafael Ortega, PE LAN, TX
Collins Orton TT Technologies, CA
Fred Ostler, PE Joint Powers Water Board, WY
Chad Owens, PE City Utilities, MO
Dr. Larry Slavin OPCS, NJ
Dan Smolik Garney Construction, FL
Serge Terentieff, PE EBMUD, CA
-3-
MAB Guidelines for
Use of Mini-Horizontal Directional Drilling for Placement of
HDPE (PE4710) Pipe for Municipal Applications
Table of Contents
1. Scope ................................................................................................................................. 6
2. Referenced Standards and Specifications .......................................................................... 7
3. Terminology ...................................................................................................................... 7
4. Preliminary Site Investigation ......................................................................................... 12
4.1 General Considerations ............................................................................................ 12
4.2 Existing Belowground Utilities ................................................................................ 13
4.3 Surface Investigation ................................................................................................ 13
4.4 Subsurface Investigation .......................................................................................... 14
4.5 Non-HDD Situations ................................................................................................ 16
5. Safety and Environmental Considerations ...................................................................... 16
5.1 General Considerations ............................................................................................ 16
5.2 Safety Training ......................................................................................................... 17
5.3 Work Clothing .......................................................................................................... 17
5.4 Machine Safety......................................................................................................... 17
5.5 Electrical Strike ........................................................................................................ 18
5.6 Natural Gas Line Strike ............................................................................................ 19
5.7 Damage to Existing Utilities .................................................................................... 19
5.8 Environmental .......................................................................................................... 19
5.9 Proficiency ............................................................................................................... 20
6. Regulations and Damage Prevention .............................................................................. 21
6.1 General Considerations ............................................................................................ 21
6.2 Locating and Marking .............................................................................................. 22
6.3 Tolerance Zone ......................................................................................................... 23
6.4 Subsurface Utility Engineering ................................................................................ 24
7. Pipe Design and Selection Considerations ...................................................................... 24
7.1 Objectives ................................................................................................................. 25
7.2 Minimum Wall Thickness Based upon Depth ......................................................... 26
7.3 Minimum Wall Thickness Based upon Pulling Load .............................................. 26
7.4 Results ...................................................................................................................... 31
7.5 Comments................................................................................................................. 32
8. Bore Path Planning and Drill Rig Setup .......................................................................... 32
8.1 General Considerations ............................................................................................ 33
8.2 Steering & Drill Rod Constraints ............................................................................. 34
8.3 Product Pipe Constraints .......................................................................................... 35
8.4 Bore Path Profile (Vertical Plane)............................................................................ 35
8.5 Bore Route (Horizontal Plane) ................................................................................. 44
-4-
9. Implementation ................................................................................................................ 47
9.1 Drill Rig Positioning ................................................................................................ 47
9.2 Pilot Bore.................................................................................................................. 47
9.3 Drilling Fluid Usage ................................................................................................. 48
9.4 Tracking and Steering .............................................................................................. 49
9.5 Records ..................................................................................................................... 50
9.6 Reaming ................................................................................................................... 51
9.7 Connecting the Product Pipe .................................................................................... 52
9.8 Handling the Pipe ..................................................................................................... 53
9.9 Potential Causes of Failure or Problems .................................................................. 54
9.10 Containment of Inadvertent Drilling Fluid Returns ................................................ 54
10. Completion ...................................................................................................................... 54
10.1 Inspection ................................................................................................................ 54
10.2 Pipe Testing ............................................................................................................. 55
10.3 Site Cleanup ............................................................................................................ 55
10.4 Certified Record (“As-Built”) Drawings................................................................. 55
APPENDICES ........................................................................................................................ 56
A. Drill Rod Bending or Steering Capability ...................................................................... 56
B. Maximum Allowable Depth (Pipe Collapse/Buckling) – Theoretical Development ..... 58
C. Pulling Tension Prediction – Theoretical Development................................................. 62
D. Examples of Load Prediction and Pipe Selection ........................................................... 66
E. Drill Rod Characteristics and Implications – Theoretical Development ......................... 70
F. Example of Drill Rig Setup and Bore Path Geometry..................................................... 73
REFERENCES ....................................................................................................................... 75
-5-
1. Scope
1.1 These guidelines describe the design, selection considerations, and installation
procedures for the placement of polyethylene (PE) pipe belowground using mini-horizontal
directional drilling (mini-HDD) equipment. The primary focus of this document is on pipe
constructed of high density polyethylene (HDPE) with a material designation code of
PE4710, for municipal applications, including potable water and sewers. For convenience,
the term “HDPE” is used as a generic term to refer to the PE4710 material. Related properties
for this material are provided in the “Plastics Pipe Institute Handbook of Polyethylene Pipe”.(1) 1
The pipe may be supplied in continuous lengths on a reel or discrete segments assembled
together, typically by fusion, in the required length.
1.2 Horizontal directional drilling (HDD) represents a form of trenchless technology. The
equipment and procedures are intended to minimize above and below ground surface damage,
restoration requirements, and disruption to traffic, with little or no interruption of existing
services. Mini-horizontal directional drilling (mini-HDD), also know as “guided boring”, is
typically used for the relatively shorter distances, shallower depths, and smaller diameter pipes
associated with local distribution lines, in comparison to maxi-horizontal directional drilling
(maxi-HDD), typically used for longer distances, greater depths, and larger diameter pipes, such
as major river crossings. ASTM F1962 provides detailed information and guidelines for the
placement of polyethylene pipe using maxi-HDD technology.
1.3 In contrast to ASTM F1962, from which the present guidelines are partially derived (see
Section 7 and Appendices B and C), the present document is intended to provide useful
information for the less sophisticated, and less well-controlled, mini-HDD technologies and
installations, as reflected in the planning and design practices. Thus, mini-HDD warrants more
simplified analysis, and correspondingly more conservative assumptions, than used in ASTM
F1962. The objective is to provide an outline and brief description of proper procedures to be
followed for mini-HDD operations, with reference to existing industry standards and guides that
provide greater detail, as appropriate. However, it is also the intention of this document to
provide useful details for specific aspects that may not be conveniently available in other
sources. Examples of the latter include drill rig setup information, such as setback distances, as
a function of drill rod characteristics and rig setup parameters, as well as a simple methodology
for selecting the strength (wall thickness) of HDPE pipe as a function of route geometry.
1.4 For convenience, the dimensions and other quantities are provided in the customary inch-
foot-pound units.
1The boldface numbers in parentheses refer to the list of references at the end of this document.
-6-
2. Referenced Standards and Specifications
ASCE 108, ASCE Manuals and Reports on Engineering Practice No. 108, Pipeline Design
for Installation by Horizontal Directional Drilling
ASTM F714, Specification for Polyethylene (PE) Plastic Pipe (SDR-PR) Based on Outside
Diameter
ASTM F1055, Standard Specification for Electrofusion Type Polyethylene Fittings for
Outside Diameter Controlled Polyethylene and Crosslinked Polyethylene (PEX) Pipe and
Tubing
ASTM F1962, Standard Guide for Use of Maxi-Horizontal Directional Drilling for
Placement of Polyethylene Pipe or Conduit Under Obstacles, Including River Crossings
ASTM F2620, Standard Practice for Heat Fusion Joining of Polyethylene Pipe and Fittings
ASTM F3190, Standard Practice for Heat Fusion Equipment (HFE) Operator Qualification
on Polyethylene (PE) and Polyamide (PA) Pipe and Fittings
AWWA C901, Polyethylene (PE) Pressure Pipe and Tubing, 3/4 in. (19 mm) through 3 in.
(76 mm), for Water Service
AWWA C906, Polyethylene (PE) Pressure Pipe And Fittings, 4 in. through 65 in. (100 mm
through 1,650 mm), for Waterworks
CI/ASCE 38, Standard Guidelines for the Collection and Depiction of Existing Subsurface
Utility Data, American Society of Civil Engineers
MAB-01, Generic Electrofusion Procedure for Field Joining of 12 Inch and Smaller
Polyethylene (PE) Pipe
MAB-02, Generic Electrofusion Procedure for Field Joining of 14 Inch to 30 Inch
Polyethylene (PE) Pipe
OPSS 450, Ontario Provincial Standard Specification Construction Specification for
Pipeline and Utility Installation in Soil by Horizontal Directional Drilling
OSHA 3075, Controlling Electrical Hazards
TIA/EIA-590A, Standard for Physical Location and Protection of BelowGround Fiber
Optic Cable Plant
3. Terminology
3.1 “Horizontal Directional Drilling” (HDD) is a technique for installing product pipes,
including utility lines, below ground using a surface-mounted drill rig that launches and places a
drill string at a shallow angle to the surface and has tracking and steering capabilities.
3.1.1. The drill string creates an initial (pilot) bore hole, of several inches diameter, in an
essentially horizontal path or shallow arc which may be enlarged during a secondary operation,
or sequence of such operations, through use of a reamer. The product pipe or utility line is
typically installed during the final reaming operation, or, if necessary, as a separate, last step in
the process. The predetermined path of the bore is maintained by tracking the path of the pilot
-7-
bore using a manually operated overhead receiver or a remote (wireline or wireless) tracking
system, and performing steering and path corrections by controlling the orientation of the drill
head. The drill head has a directional bias, such as a slanted face or mud motor on a slightly bent
portion (“bent sub”) at the leading drill rod. Turns and corrections are accomplished by pushing
the drill string forward with the drill head oriented in the direction desired. Continuous rotation
of the drill string allows the drill head to bore a straight path. Soil penetration is accomplished
using high pressure, low volume fluid jets and/or mechanical cutting. The drilling fluid volume
is controlled to avoid or minimize the creation of voids during the initial boring and back-
reaming operations. The drilling fluid serves several purposes, including stabilization of the bore
hole, removal of cuttings, lubrication for the drill string and product pipe, and cooling the drill
head and transmitter electronics. Typically, the resultant slurry created by the combination of the
drilling fluid and soil cuttings gradually solidifies into a solid mass encapsulating the product
pipe.
3.1.2 “Mini-Horizontal Directional Drilling” (mini-HDD) is a class of HDD typically
employed for boring segments less than 600 feet in length, at depths up to 15 feet, and placing
pipes up to 12 inches diameter. The equipment is characterized by a thrust or pullback capability
of up to 20,000 lbs, with a torque less than 950 ft-lbs. Mini-HDD machines weigh less than 9
tons.(2)
3.1.2.1 Mini-HDD equipment is typically used for installing pipes for water, sewer and gas
lines, as well as for ducts and conduits for local distribution utility cables (electric power,
communications), beneath local streets, private property, and along right-of-ways. Smaller mini-
HDD machines, sometimes referred to as “micro-HDD” equipment, or possibly even pit
launched, are appropriate for installing pipes for service lines or laterals to homes or businesses.
Improved technology and greater experience gained by contractors (excavators) have also
allowed mini-HDD equipment to place lines on an accurate grade, including gravity sewer
lines(3), possibly combined with the use of a “pilot tube”(2). The creation of the pilot bore hole
and the reaming operations are generally accomplished by fluid jet cutting and/or the cutting
torque provided by rotating the drill string. The locating and tracking systems may utilize a
manually operated overhead (walkover) receiver to follow the progress of the initial pilot bore,
or possibly a remote tracking/steering system. Figures 1 and 2 illustrate typical mini-HDD
equipment and pilot boring and back-reaming operations, including product pipe or utility line
placement.
-8-
Figure 1 Typical Mini-HDD Equipment and Pilot Boring Process
(Source: Outside Plant Consulting Services, Inc.)
-9-
Figure 2 Typical Mini-HDD Back-Reaming and Pipe Pullback Process
(Source: Outside Plant Consulting Services, Inc.)
3.2 “Dimension Ratio” (DR) is the ratio of pipe outer diameter to minimum wall thickness.
Higher DR values therefore correspond to thinner, weaker pipes and lower values to thicker,
stronger structures.
3.2.1 “Standard Dimension Ratio” (SDR) refers to specific values of dimension ratio.
3.2.2 The Iron Pipe Size (IPS) system is based on specified outer diameters and SDR values,
such as provided in ASTM F714, AWWA C901, or AWWA C906.
3.2.3 The Ductile Iron Pipe Size (DIPS) system is based on specified outer diameters and
SDR values, such as provided in ASTM F714 or AWWA C906.
3.3 The degree of bending to which a drill rod, or product pipe, may be subject, without
damage or degradation, is a function of the size and material of the item. There are several
alternative measures of the degree of allowable curvature as presently used in the industry; see
Figure 3.
3.3.1 “Radius of Curvature”, or “Bend Radius”, is the distance from the center of the
circular path or configuration, in a plane, to the perimeter.
3.3.2 “90° Bend Radius is the distance along a 90° portion (quadrant) of the perimeter of the
circular path.
3.3.3 “Degrees per Rod” is the angular change along a single rod length.
3.3.4 The various measures for quantifying the allowable curvature are related by the
following formulae:
90° Bend Radius (ft) = 90 x Rod Length (ft) / Angular Change (deg/rod) (1a)
Radius of Curvature (ft) = 90° Bend Radius (ft) / 1.57 (1b)
- 10 -
Radius of Curvature (ft) = 57.3 x Rod Length (ft) / Angular Change (deg/rod) (1c)
Figure 4 illustrates the above relationships. See Appendix A for examples quantifying the
bending capability of typical drilling rods, using the various terms. There is significant
quantitative difference between the 90° Bend Radius and Radius of Curvature. The latter
(Radius of Curvature) is approximately 2/3 of the 90° Bend Radius. For convenience, except
where otherwise indicated, the Radius of Curvature (Bend Radius) measure will be used in the
present document.
- 11 -
Figure 4 Allowable Curvature Relationships
(Source: Outside Plant Consulting Services, Inc.)
- 12 -
construction. Ideally, the owner would conduct as much of the preliminary investigation as
possible to allow a meaningful and equitable bidding process. The contractors would conduct
additional investigations to assist them in the bidding process, as well as to provide guidance for
the actual construction, following awarding of contracts. For projects of very limited duration,
the contractor may perform only a brief study, to verify the general feasibility and determine the
equipment and resources required to successfully complete the task.
4.1.3 The presence of special obstacles or situations must be considered. For example, the
presence of pollutants or contaminants in the construction area must be identified, including
corresponding arrangements for spoil disposal.
- 13 -
4.3.3 The ability for the tracking and monitoring system to function properly may be
hampered by the local conditions, along the path to be bored. Conventional walkover receivers
require direct overhead access, while more sophistical systems may allow remote tracking.
Potential sources of interference to the electronic locators of mini-HDD tracking systems include
overhead structures or wire lines, as well as steel-reinforced concrete sidewalks, driveways, and
roads.
4.3.3 The use of drilling fluids requires that a source of water, preferably potable, be
available for mixing. Although drilling fluids are not considered hazardous materials, excess
fluid and associated spoils must be disposed of properly. The location of an appropriate disposal
area, consistent with local regulations, should be identified in advance of the construction, as part
of the preliminary or planning phase.
4.3.4 Although noise levels associated with mini-HDD equipment are generally not
excessive, there may be restrictions on work hours in areas near residential buildings, hospitals,
or other institutions.
- 14 -
previous local projects involving trenchless methods, requiring boring of any type, would be
most relevant.
4.4.4 Soil Investigation Tests – If warranted by the scope of the project, existing subsurface
information may be supplemented by local soil tests, at strategic locations and relevant depths, to
verify the conditions. Possible characteristics to be evaluated include standard classification of
soils, standard penetration test values, rock type and strength and (Mohs) hardness.(ASCE 108)
ASTM F1962 provides reference ASTM test methods for soil evaluation studies, as appropriate.
Additional information is available elsewhere.(4)
4.4.5 For some mini-HDD applications, such as large scale upgrades of distribution
facilities in established areas, random blockages due to man-made debris would not be evident
based upon soil testing at a limited number of locations. Depending upon the depths of interest,
object dimensions, and soil conditions, existing technology (e.g., ground penetrating radar) may
be capable of electronically scanning the subsurface to detect obstacles of various sizes. Such
technologies are continuing to evolve and their practicality, including economic feasibility, will
depend upon the local conditions and concerns.(CI/ASCE 38)
4.4.6 Suitability of Soil Conditions -- Table 1 indicates the suitability of horizontal
directional drilling as a function of the general characteristics of the soil conditions in the area
and depths of interest.
Table 1 Applicability of Mini-HDD (or Midi-HDD) for Various Soil Conditions (2)
Soil Conditions Applicability
Mini-HDD Midi-HDD
Soft to very soft clays, silts, and organic deposits Yes Yes
4.4.6.1 The indications of applicability in Table 1 assume that the contractor and crew is
trained and experienced in the use of mini-HDD equipment and technology, employs appropriate
equipment for the specific soil condition (drill head, reamers, ...), and has a working knowledge
- 15 -
of drilling fluids. The proper use of drilling fluids is a critical aspect of HDD operations, the
importance of which is often underestimated. Preferably, contractors have successfully
completed industry training courses or seminars specifically addressing mini-HDD methods (see
Section 5.9), and have a minimum of one year field experience, and completed 30,000 ft of
construction in related projects.
4.4.6.2 “Marginal” conditions will generally result in a lower success rate, but which may
be positively impacted by greater contractor experience and training, and the use of consulting
services by industry suppliers. Some applications may not be economically feasible for
directional drilling using present technology; see Section 4.5.
- 17 -
connections and damaged hoses. The hoses and connectors must be properly maintained to
minimize the risk of leaks and the system pressure should be relieved before disconnecting any
hydraulic lines. Suspected leaks must not be checked using exposed parts of the body.
5.4.2 Drilling Fluid – Similar precautions as above (Section 5.4.1) apply to drilling fluid
used to for soil cutting and reaming. The drilling fluid supplements the mechanical cutting
provided by the drill head or reamer and, depending upon the equipment design and operation,
may also reach several thousand psi within the drill rod assembly, and may lead to leaks at
vulnerable connections and damaged hoses. Drilling fluid hoses and connectors must be
properly maintained to minimize the risk of leaks and, before inserting or removing individual
drill rods from the drill string, the drilling fluid pressure at the rig must be relieved to avoid high
velocity fluid squirting from the joint. The reduced drilling fluid pressure level must be verified
by the corresponding pressure gauge to verify the pressure has been relieved before
disconnecting any rods. As above, suspected leaks must not be checked using exposed parts
of the body.
5.4.2.1 Due to the possibility of soil clogging the drilling fluid ports of the drill head or
reamer, the attempt to relieve pressure at the rig may not result in an immediate loss of pressure
within the drill string. In such cases, special care is required when disconnecting the rod.
Clogged drill components should be cleared prior to continuing the operation, possibly requiring
the drill string to be retracted or exposed.
5.4.2.2 The exit point for the pilot bore represents a potentially hazardous location, from
which a safe distance must be maintained by all personnel. The drilling fluid pressure should be
relieved as soon as the drill head emerges at the far end, as well as when the reamer emerges
from the entry point at the rig end.
- 18 -
5.5.2 A successfully completed pilot bore does not ensure that a utility line may not be
damaged during the subsequent reaming or pullback operation, as the bore hole is enlarged. In
the event of an electrical strike during the latter operation, exposure to hazardous voltage may
exist at both ends of the bore. For example, if several pre-reaming operations are performed,
steel (conductive) drill rods are inserted at the bore exit point to maintain the path as the rods are
removed at the bore entry. In such cases, grid mats, ground rods, and an electrical bonding
system must be used at the bore hole exit, as well as in the vicinity of the drill rig. In comparison
to metallic product pipe, the non-conducting nature of plastic pipe essentially eliminates or
greatly reduces corresponding risks at the bore exit point (pipe entry) during final pullback of the
product pipe.
5.5.3 Specific emergency steps following an electrical strike are provided within industry
guidelines, and include precautions regarding equipment and worker movement. The facility
operator must be contacted immediately and a call to 911 should be made for emergency
response.(5)
5.8 Environmental
Drilling fluid serves many useful functions, including aiding soil penetration, removal of spoils,
bore hole stabilization, lubrication for the drill rods and product pipe, and cooling of the drill
head and transmitter electronics. Typical drilling fluid components are not hazardous materials,
with the waste material usually considered as excavation spoils, not requiring special disposal
procedures. The volume of spoils to be removed from the site may be significantly reduced by
means of drilling fluid recirculating systems. The most common additive is bentonite, a
naturally occurring type of clay. If clay represents a large component of the native soil in the
construction site, a polymer additive may be more appropriate. The bentonite or polymer
- 19 -
material used should be National Sanitation Foundation certified. The additive materials should
be chemically inert, biodegradable, and non-toxic, and petroleum-based or detergent additives
should not be used.(OPSS 450)
5.8.1 Contaminated Area – Although the bentonite-water, or commonly used polymer-
water, slurry, is not inherently a hazardous material, special disposal may be required when
drilling in an area known to be contain toxic pollutants. In such cases, disposal must be in
accordance with local laws and regulations, and it may be necessary to de-water the spoils,
transport the solids to an appropriate disposal site, and treat the water to meet disposal
requirements. It may be also necessary to add grouting to the drilling fluid to ensure proper
sealing of the bore hole to eliminate a possible passage for contaminants. Special drilling fluid
pumps may then be required.
5.8.2 Collection Pits – In order to maintain a neat, orderly work site, occasional small pits
must be available for collecting the excess drilling fluid or slurry exiting from the bore hole. A
clean work site will help ensure the installation of a clean product pipe, reducing the need to later
flush out mud or debris from within the pipe. Excessive drilling fluid and mud in the area may
impair the connections and associated grounding characteristics of the equipotential grid mat
system. Pits may already be present or required such as for utility access or connections at the
ends or along the bore (Section 8.4), thereby serving as convenient receptacles. If not otherwise
present, small pits should be provided at the ends, and possible intermediate points to serve this
function. The pits should be emptied as necessary.
5.9 Proficiency
It is required that employees operating mechanized equipment, including mini-HDD machinery,
be qualified for their tasks, and that their employer (contractor) ensure that the operators and
other workers in the vicinity have demonstrated proficiency in their duties, particularly safety
issues. Primary personnel must have proper training, including classroom and field experience.
Industry based HDD training and/or certification courses are available from equipment
manufacturers, as well as professional organizations. 2
5.9.1 Submissions – The contractor should submit the following information to the owner or
its representative (OPSS 450):
• Work plan outlining the procedure and schedule to be used to execute the work
• List of personnel, including backup personnel, and their qualifications and
experience
• Traffic control plan
• Drilling fluid management plan including potential environmental impacts and
emergency procedures and associated contingency plans
• Safety plan including the company safety manual and emergency procedures.
2 HDD training and/or certification courses are available from various sources, including the Center for
Underground Infrastructure Research and Education at the University of Texas at Arlington, the Centre for
Advancement of Trenchless Technologies at the University of Waterloo, Bowling Green State University, the
Trenchless Center at Louisiana Tech University, and the North American Society for Trenchless Technology.
- 20 -
6. Regulations and Damage Prevention
In order to help avoid the potential hazards described above, proper procedures must be adopted
to reduce the likelihood of damaging existing utilities. Section 6 discusses such practices,
including “call-before-you dig” (811); locating and marking existing utilities, as well as
exposing, when appropriate; avoiding mechanized digging within the required tolerance zone;
and the use of Subsurface Utility Engineering.
- 21 -
obvious indication that this has occurred. At some time in the future, a cleaning operation of the
lateral may then result in damage to the gas line, with potential hazardous consequences. It is
critical to avoid or prevent the occurrence of such cross-bore events.
- 22 -
6.2.4 APWA Uniform Color Code – The paths of existing belowground facilities should be
marked, using paint, flags or equivalent, or flags, based upon the Uniform Color Code developed
by the Utility Location and Coordination Council (ULCC) of the American Public Works
Association (APWA):
White proposed construction path
Red electric power
Orange communications
Yellow gas, oil, steam, petroleum
Green sewer, drain
Blue potable water
Purple reclaimed water, irrigation, slurry
Fluorescent pink temporary survey marking
- 23 -
6.4 Subsurface Utility Engineering
Subsurface Utility Engineering (SUE) refers to an engineering process for obtaining reliable
information regarding belowground utility lines, including types and specific (lateral and depth)
locations. The general principles and techniques of SUE are provided in CI/ASCE 38, which
defines four general levels of quality based upon the amount and detail of information obtained
for characterizing the existing facilities. Quality Level D is the lowest level, corresponding to
the least detailed and/or least reliable information, with Quality Level A the highest level,
corresponding to the most detailed and/or most reliable information. Although the higher quality
levels are more costly to achieve, such information is required for some stages of the mini-HDD
construction process.
6.4.1 Quality Level D – The minimum level of information is based upon existing utility
records. Such information is primarily useful for the purposes of project planning and route
selection only.
6.4.2 Quality Level C – In addition to the information from Quality Level D, this level
includes information obtained from a field visit and a survey of above-ground facilities, such as
manholes, valve boxes, posts, etc., and correlation of this information with existing utility
records. As a result, the presence of additional belowground utilities, or erroneously recorded
location information of utility lines, may be determined. Although such information may be
adequate for areas with minimal belowground facilities, or where possible repair is not a major
issue, this quality level would typically not be sufficient for proceeding with construction in
established areas.
6.4.3 Quality Level B – In addition to the information from Quality Level C, the use of
surface locators for identifying and marking the existing utility lines, as previously described in
Section 6.2, results in more useful, reliable information.
6.4.4 Quality Level A – In addition to the information from Quality Level B, the highest
quality level includes the use of non-aggressive digging equipment at critical points to expose the
utility to determine the precise horizontal and vertical position of underground utilities, as well
as the type, size, condition, material, and other characteristics. Mini-HDD operations include
such locating procedures at crossings and other critical locations, as described above (Section
6.2.3).
- 24 -
complexity of the HDD process and the sensitivity of the predictions to the model and assumed
parametric values, do not necessarily provide equivalent results.(9, 10)
7.1 Objectives
The pipe selection process for HDPE pipe is equivalent to determining the minimum wall
thickness, or maximum DR value, that is sufficient to withstand the long-term operational loads
as well as the stresses due to the installation process. Similar to its decision to select HDPE pipe
based upon its various advantageous properties, including its compatibility with HDD and other
pulling processes, it may be assumed that the owner of the facility will specify a pipe diameter
and minimum wall thickness consistent with the long term operation of the facility, based upon
independent technical analysis provided by its own staff and/or with industry support. This
includes the ability to satisfy internal fluid flow requirements and withstand internal pressure for
pressurized lines in combination with external pressures due to soil and surface loads (e.g.,
traffic) at various depths and conditions. Such design considerations are addressed in various
sources, including “The Plastics Pipe Institute Handbook of Polyethylene Pipe”.(1) These
operational design loads may be assumed to be essentially independent of the installation
method. In contrast, the HDD process imposes its unique installation loads due to the tensile
forces imposed on the pulling end of the pipe, and the temporary hydrostatic pressure associated
with the drilling fluid/slurry at the installed depths. (There is an additional limitation that
recommends a minimum depth of cover during the mini-HDD installation, based upon avoiding
possible negative effects at the ground surface, such as surface heaving or drilling fluid leakage,
as described in Section 8.1.3.) The appropriate pipe minimum wall thickness will be the
greater of the values necessary to safely withstand (a) the various long-term operational
(including soil and surface) loads and (b) the short-term installation (and pre-operational)
loads associated with the mini-HDD operation. The present guidelines primarily focus on the
latter issues.
ASTM F1962 provides a methodology for selecting HDPE wall thickness for pipe installed by
maxi-HDD, including for river crossings, in order to withstand the installation process. Such
operations are typically major events, requiring extensive preliminary investigations and
engineering planning, analysis and support, including the use of software tools, as available. For
these applications, it is necessary and desirable to perform as accurate engineering analyses as
possible, consistent with the present capabilities, in an attempt to reduce the likelihood of
significantly over- or under-designing the pipe, either of which may lead to serious economic
consequences. Such considerations do not generally arise in mini-HDD applications, which are
often part of a large-scale upgrade of facilities in a community or geographic area. Mini-HDD
operations typically comprise short, shallow installations and detailed calculations of pipe
stresses and loads due to the installation forces are generally not necessary or practical. Thus,
the relatively complicated, extensive analyses, such as provided in ASTM F1962, are not
appropriate for the present purposes. However, if the pulling distances are relatively long, or the
pipe relatively deep, or a thin-walled product is being considered, it is advisable to perform a
limited, approximate analysis to provide confidence in a successful installation. The present pipe
selection guidelines, derived from those in ASTM F1962, therefore provide a simplified
methodology for selecting or verifying the minimum wall thickness consistent with withstanding
the installation loads in mini-HDD applications, based upon reasonable assumptions and
approximations.(11)
- 25 -
7.2 Minimum Wall Thickness Based upon Depth
During the back-reaming and pullback operations (Figure 2), the mini-HDD drilling fluid creates
a relatively dense slurry that applies hydrostatic pressure symmetrically around the pipe
circumference. Under sufficient hydrostatic pressure, in combination with local drilling fluid
pressure, the pipe may deform and collapse. Appendix B provides the collapse strength of
HDPE (PE4710) pipe for various wall thicknesses (DR) values, under idealized conditions, and
also describes the basis for estimating the corresponding allowable (reduced) mini-HDD depths
for practical applications. The criteria are based upon a consideration of the installation phase as
well as the post-installation (but pre-operational) phase, and incorporate reductions consistent
with various degradations described in ASTM F1962, as well as a “safety” (i.e., uncertainty)
factor of approximately 2-to-1 to account for deviations from the simplified model.
The information in Appendix B indicates that essentially all the commonly used wall
thicknesses, with the possible exception of DR 17 pipe, would be sufficiently strong for
depths considerably greater than 15 ft, , the typical limit for mini-HDD installations. DR 17
pipe should generally be limited to less than 10 ft depth, although 15 ft may also be acceptable in
some cases (see Section B.3.6.). For depths significantly greater than 15 ft, the adequacy of the
product for the application should be verified using the information in Appendix B. In general,
the use of very thin-walled product pipe (e.g., > DR 17) is not recommended for typical mini-
HDD installations.
As discussed in Section 7.1, the pipe should be independently analyzed by the owner, or its
engineering consultant, to verify sufficient strength during the operational phase for withstanding
long-term soil and surface loads (e.g., for relatively shallow buried pipe), such as may be
imposed for conventional installations, using accepted industry practices.
The allowable depths as determined in Appendix B, and indicated above, assume an empty pipe
during the installation and pre-operational phase, in the absence of possible subsequent internal
fluids or pressure, which would offset the effects of the external pressure due to drilling
fluid/slurry. Although some HDD installations, such as more complex maxi-HDD installations,
or possibly some midi-HDD applications, may deliberately allow the pipe to be temporarily
filled with water or drilling fluid in order to reduce pull loads due to buoyancy effects, as well as
the net effective hydrostatic pressure, during installation, such practices are not typically
employed in mini-HDD operations; see Appendix B. For water applications, however, the
beneficial effects, will be present during the later operational phase, and may be reflected in the
design considerations by the facility owner.
- 26 -
Table 2 Safe Pull Tension (lbs), HDPE (PE4710) Pipe, 1 hour*
IPS
Nominal Pipe Diameter to Thickness Ratio (DR)
Size 7 9 11 13.5 17
- 27 -
12-in. 93,838 75,689 63,335 52,562 42,428
* PE4710 with minimum tensile yield strength 3500 psi x 0.4 factor =
1400 psi at 80oF
7.3.2 Peak Tension – Appendix C provides details regarding the technical basis and
development for the following equations and simplified methodology, including Equation 2
which provides an estimate of the peak force applied to the pipe as it is pulled throughout the
bore hole:
Tension (lbs) = [Bore Length (ft) x Buoyant Weight (lbs/ft) x (1/3)] x (1.6)n (2)
The buoyant weight may be conveniently (approximately) determined as
Buoyant Weight (lbs/ft) = ½ [Pipe Outer Diameter (in.)]2 – Pipe Weight (lbs/ft) (3)
and n is equal to the number (or fraction) of 90° route bends due to cumulative route curvature,
or
n = n1 + n2 (4)
The quantity n1 is the effective number of deliberate/planned 90° route bends, and n2 is the
cumulative curvature (90° route bends) due to the unplanned undulations. For example, as
illustrated in Figure 6, if a deliberate horizontal (planar) bend of 45° to the right, in order to
avoid an obstacle or follow a utility right-of-way, is followed by another 45° horizontal bend to
the left, each 45° bend is equal to half of a 90° bend, corresponding to a total of ½ + ½ = 1 full
90° bend; i.e. n1 = 1. The quantity n2 is described in Section 7.3.2.1.
The pipe weight (lbs per foot) in Equation 3 is available from the manufacturer (based upon the
diameter and DR rating), or may be determined by weighing a sample length. Alternatively,
Figure 7 may be used to determine the approximate buoyant weight for use in Equation 2,
recognizing that, for a given pipe size (nominal diameter), the actual buoyant will be somewhat
larger for the lower DR (thicker wall, heavier) pipes than the larger DR (thinner wall, lighter)
pipes
Figure 7 shows slightly greater buoyant weights for the DIPS system than the IPS system, due to
the somewhat larger outer diameters, for the same nominal pipe size. This results in
- 28 -
correspondingly greater predicted tensions, which are offset by the similarly larger safe pull
tensions in Table 3, allowing the same potential placement distances (see Figure 9). 3
3 For a given DR value, the buoyant weight, predicted pull tension (Equation 2), and strength of the pipe are both
proportional to the square of the outer diameter, allowing the same maximum placement distances,, for a specified
route geometry.
- 29 -
when applying the above procedures to mini- (or midi-) HDD equipment employing different
diameter (larger or smaller) rods, the following value of n2 should be used
n2 = [Bore Length (ft) / 500 ft] x [2-in / Rod Diameter (in.)] (6)
For example, a 4-inch diameter drill rod would correspond to one 90° bend every 1,000 ft. The
results of Equation 6 are illustrated in Figure 8.
Although, in principle, this same rule, for estimating unplanned path curvature, may be
extrapolated to maxi-HDD, using corresponding large diameter drill rods, it is considered
excessively conservative for such well-planned, well-controlled installations, as discussed below.
7.3.3 Pipe Selection – The estimated tension as calculated from Equation 2 must be
compared to the safe pulling load of Table 2 or Table 3, for which it is required that the former
not exceed the latter; i.e.,
Tension (Equation 2) ≤ Safe Pull Tension (Table 2 or Table 3) (7)
Appendix D provides examples of its application.
The use of Equation 7 provides a reasonable estimate of practical placement distances using
mini-HDD, and is analogous to the procedure incorporated in ASTM F1962 for maxi-HDD
installations. The present mini-HDD calculations, however, will generally result in considerably
shorter possible placement distances than that corresponding to application of the methodology
and equations provided in ASTM F1962, which may also include the use of anti-buoyancy
techniques to reduce buoyant weight to significantly reduce required pull loads. The shorter
placement distances for mini-HDD are also due to the increased drag (“capstan effect”)
generated by the additional route curvature characteristic of mini-HDD installations, especially
- 30 -
that due to path corrections 4 (Equations 5 and IMPORTANT NOTE
6), which are more likely and of greater The indicated mini-HDD allowable bore
magnitude and significance than that lengths in Figure 9 are significantly
encountered in typically well-controlled maxi- lower than that achievable with typical
HDD installations. (See IMPORTANT NOTE.) maxi-HDD operations. The estimated
mini-HDD pull loads assume (1) the
In general, therefore, the preceding formulas absence of water ballast within the
and methodology are recommended for pipe, which otherwise greatly reduces
estimating pull loads for mini-HDD the buoyant weight and associated
installations. Other methods for frictional drag, and (2) the presence of
determining pulling loads, including additional route curvatures due to path
software tools (e.g. Boreaid, corrections characteristic of typical
www.boreaid.com, www.ppiboreaid.com), mini-HDD operations. The latter
are typically based on well-controlled maxi- phenomenon, for example, would
HDD installations and not representative of significantly reduce practical placement
actual mini-HDD applications with respect to distances for pipes of any material.
anticipated pull loads. Thus, the implementation of anti-
buoyancy measures and/or avoidance
7.4 Results of unnecessary path curvatures, such
As discussed above, Equation 7 may be used to as representative of well-planned and
predict the pulling load as a fraction of the safe executed maxi-HDD installations,
pull tension, as a function of route length, for correspond to practical placement
various route geometries and applications. distances several times that shown in
Figure 9 illustrates the results for a nominally Figure 9. ASTM F1962 may be used to
straight bore (i.e., n1 = 0), for various HDPE determine such practical placement
(PE4710) pipe strengths (DR values), distances.
independent of diameter, for typical 2-inch drill
rods. For example, based upon pull load only, the DR 11 pipe may be installed in a segment
length of 1,000 ft, well beyond the nominal upper limit of mini-HDD capability, without
anticipated problems. Based upon the allowable depth information in Appendix B, the same pipe
may be installed as deep as 55 ft, again well beyond the capability of mini-HDD equipment.
These results indicate that DR 11 HDPE pipe should have adequate physical strength for
essentially all practical mini-HDD applications. DR 11 pipe should also be readily capable of
withstanding reasonable field handling, which is not directly considered by the analyses.
Maximum recommended lengths would be reduced for routes with additional planned bends (n1
> 0); see Appendix D.
Furthermore, based on Figure 9, all the DR values indicated would be acceptable for the nominal
limit (600 ft) of mini-HDD, and beyond, assuming the corresponding depth limits are satisfied
(Appendix B).
4 Due to the quantitative significance of the unplanned path curvatures due to path corrections – and the wide
variability of such effects – in some cases it may be considered desirable to apply a load factor of > 1.0, or possibly
< 1.0, to the tension predicted by Equation 2, depending on the experience and judgment of the contractor,; see
Appendix C.4 and Appendix D.
- 31 -
Figure 9 Predicted Mini-HDD Pull Load vs. Safe Pull Tension, HDPE (PE4710) Pipe
Nominally Straight Path, 2-inch Drill Rods
(Source: Outside Plant Consulting Services, Inc.)
7.5 Comments
A determination that the selected pipe (DR) meets the design criteria as described in Section 7
should not be misconstrued to encourage or allow reduced care or skill in the recommended
industry practices, such as summarized in other sections of this guide. The selection procedures
are based upon the assumption that proper drilling procedures are followed. For example, a
prematurely collapsed bore hole may impose pipe loads significantly greater than those assumed
in the present analyses, leading to an unsuccessful installation. Conversely, the determination
that a particular pipe size and strength does not meet the present design criteria for a desired bore
route does not necessarily indicate that the installation will fail. The methodology is based upon
a degree of inherent conservatism (see Appendix C) such that it would be expected that, in many
cases, individual selected pipes falling short of the criteria would nonetheless be successfully
installed by the mini-HDD process, albeit in the absence of the greater assurance provided by the
present design practices.
- 32 -
information, which is dependent upon the equipment parameters (e.g., allowable drill rod
curvature). The information provided supports the design of the bore path in both the vertical
and horizontal planes. Commercially available software tools may also be used to help perform
these functions.(13)
The information provided in this section comprises elements of the design (e.g., planning bore
path trajectory) and actual construction or implementation operations, both of which are typically
performed by the contractor for mini-HDD installations. For more complex HDD operations,
such as maxi-HDD installations, these functions would typically be performed separately, by
different individuals or organizations, including engineers, and utilizing software tools such as
Boreaid®.(8)
- 33 -
Figure 10 shows recommended depth of cover for conditions compatible with the nominal 10-to-
1 ratio for a compaction process, as well as a 5-to-1 ratio for a mini-HDD spoils removal
process, at a minimum of 36 inches, as a function of final bore hole diameter. It is noted that the
final bore hole size for mini-HDD operations is nominally recommended to be at least 50%
greater than the pipe outer diameter(s). Such recommendations for depth of cover are recognized
as only a guide, since the tendency for subsequent ground movement, as well as penetration of
drilling fluid to the surface, and other possible effects, are dependent upon local soil
characteristics and construction variables.(4, 15) However, if a lower depth of cover than that
indicated in Figure 10 is necessary, it is recommended that the final bore hole size be gradually
enlarged using several (one or more) pre-reaming passes, prior to the final pullback of the pipe,
accompanied by careful monitoring of the drilling fluid pressure; see Section 9.3.1.
- 34 -
8.3 Product Pipe Constraints
The allowable radius of curvature (bend radius) of the product pipe will be provided by the pipe
manufacturer. For pipe constructed from plastic or other very flexible material, the bend radius
limitation of the drill rods is generally sufficiently large to be compatible with that of the product
pipe. In particular, HDPE pipe is sufficiently flexible such that the corresponding bends and
path curvatures imposed on the pipe during an HDD installation will not be significant.
8.4.1 Angle Measurement – In HDD operations, the angle of the drill rig (entry angle)
relative to the surface, as well as the local angles established at the drill head during the pilot
boring process, determine the path of the bore hole. The angles may be in a vertical plane
(elevation), such as the drill rod entry angle, or in a horizontal plane (azimuth), during turns, or a
combination of both directions. The angle may be commonly measured in degrees or, for
- 35 -
elevation angle, in percent grade (vertical rise or drop per unit horizontal distance, times 100).
The angle in degrees is approximately equal to half the percent grade, as illustrated in Figure
12. Typical drill racks allow an entry angle in the range of 5° – 25° (10% – 45% grade).
8.4.2 Setback Distance – In order to achieve a specified depth at a particular point towards
the beginning of a pilot bore operation, the front of the drill rig must be located an appropriate
distance rearward from the point of interest. This setback distance depends not only upon the
depth at the point of interest, but also on the desired orientation (percent grade) of the bore at that
point. In Figure 11, point 1 is directly along the entry path of the drill rod, at which the resulting
bore path is inclined at the entry angle, and for which the setback distance corresponding to
reaching the depth d1 is designated as S1. S1 represents the minimal setback distance for
achieving a specified depth, independent of the orientation of the bore path, beyond which the
trajectory may become level.
Knowledge of such minimum setback requirements is important with respect to determining the
location and position of the drill rig, consistent with available space or feasible or convenient
setup locations.
8.4.2.1 Setback Distance to Level Trajectory – Beyond point 1, the drill rods are steered
such that the bore path trajectory becomes level at point 2, correspond to a depth d2 and setback
distance S2. The distance S2 is significantly greater than the corresponding to S1, assuming the
same depth of interest. The greater distance is required to allow the drill rods to establish an
upward curvature consistent with achieving a horizontal orientation. In this case, it is also
assumed that the bore is initiated along a straight path, at the entry angle, without any curvature
or steering for a distance equal to one full drill rod length (e.g., 10 ft, for typical mini-HDD
equipment) in the ground.(16) This is a recommended practice to avoid bearing loads at the
front of the drill rig. The upward desired curvature is introduced during the placement of
subsequent drill rods.
- 36 -
8.4.2.2 Minimum Depth for Level Trajectory – Due to the recommendation that the first
drill rod be placed in the ground without any curvature or steering, and the subsequent path
curvature consistent with the bending capability of the rod, there is a minimum depth at which
the trajectory will become level, depending upon the entry angle and rod characteristics. This
depth is designated as (d2)min.
8.4.3 Setback Guidelines – The above setback distances S1 and S2, as a function of depth,
d1 or d2, respectively, are shown in Figures 13, 14 and 15 for several drill rods, including
lengths of 6 ft, 10 ft and 15 ft, with corresponding allowable radii of curvature of 60 ft, 100 ft
and 150 ft. These figures also indicate the minimum depth (d2)min, and corresponding minimum
setback distance S2, at which the trajectory may become level. Thus, for the typical 10 ft drill
rods of Figure 14 and an entry angle of 15°, a depth d1 of 72 inches will be achieved at a setback
distance S1 of 22 ft based upon an inclined (non-level) trajectory. In comparison, a setback
distance S2 of 36 ft is required to reach the same depth (72 inches) at a level trajectory. Figure
14 also indicates that this particular drill rod (10 ft length and 100 ft allowable radius of
curvature) and entry angle are not consistent with achieving a level trajectory at depths shallower
than 72 inches. If it is necessary to be at a shallower depth, a lower entry angle and/or sharper
bend radius would be required. If necessary, the trajectory could exceed the desired depth at the
- 37 -
beginning of the bore, and rise to the proper depth further along the path, at a correspondingly
greater setback distance.
Appendix E provides additional information on setback distances, including formulae that may
be used to generate additional setback guidelines for drill rods with differing characteristic than
those considered in Figures 13 – 15. Appendix F provides examples of their application.
- 38 -
Figure 15 Drill Rig Setback Distance
Drill Rods: 15 ft Long, 150 ft Radius of Curvature
(Source: Outside Plant Consulting Services, Inc.)
8.4.4 Depth/Setback Implications – If the determined setback distances or drill rod angle
consistent with the project maximum depth specifications are not practical, consideration should
be given to receiving approval from the owner allowing increased depths in the vicinity of the
entry point, with a gradual transition to the preferred depth along the balance of the route. If
necessary, smaller diameter, more flexible, drill rods (e.g., Figure 13) may be considered if
consistent with anticipated thrust and torque loads. Smaller bend radii than that recommended
by the rod manufacturer may be considered by the contractor if it is recognized that reduced
service life may result for the drill rods. If the steering conditions in the soil preclude a
sufficiently sharp upward turn, mechanical assistance may be provided at the entry pit to apply
an upward bending moment on the rod.
8.4.5 Distance to Rise to Surface from Level Trajectory – Figures 16 – 18 show the
horizontal distances required for the head of the drill string to reach the surface from a point 3,
on a level trajectory, from its present depth d3, as indicated in Figure 11. The minimum distance
to reach the surface, designated S3, corresponds to that of steering upward at the minimum
allowable radius of curvature of the drill rod. Alternatively, if it is desired to exit the ground at a
specific angle, a greater horizontal distance will generally be required. For example, it may be
desired to exist at a relatively low angle to facilitate the subsequent pipe entry into the bore path,
which will require a greater horizontal rise distance, designated S5, than for a larger angle.
- 39 -
Knowledge of such distances is important with respect to determining the location for feeding of
the product pipe into the bore path during the pullback phase. Such locations must be
compatible with available space at the far end of the bore path.
Assuming the typical drill rod of Figure 17 (100 ft allowable radius of curvature 5), the shortest
rise distance, S3, from a level trajectory at 100 inches depth, d3, is approximately 40 ft, in
comparison to approximately 100 ft (S5) for an desired exit angle of only 5°; see Figure 11. The
maximum possible exit angle is limited by the depth. For this drill rod, relatively high exit
angles (e.g., greater than 20°), are not possible at depths less than approximately 72 inches.
Figure 19 illustrates exit angles for a rise at the indicated constant curvature.
5 The rod length is not a factor for the distance to rise to surface.
- 40 -
Figure 17 Distance to Rise to Surface
Drill Rods: 100 ft Radius of Curvature
(Source: Outside Plant Consulting Services, Inc.)
- 41 -
Figure 18 Distance to Rise to Surface
Drill Rods: 150 ft Radius of Curvature
(Source: Outside Plant Consulting Services, Inc.)
- 42 -
Figure 19 Exit Angle for Rise at Constant Curvature
(Source: Outside Plant Consulting Services, Inc.)
8.4.6 Distance to Exit at Specified Grade – Considering a drill head oriented at an upward
grade, Figure 20 shows the horizontal distance, S4, required for the head of the drill string to
reach the surface from a point 4, on an inclined path, from its present depth d4; see Figure 11.
The information may also be used to determine the horizontal distance corresponding to a
specified rise distance from any point on an inclined path. The present d4 and elevation angle is
available from the drill head locating system. The vertical rise results in Figure 20 directly
correspond to the local percent grade (fraction of horizontal distance) of the trajectory.
- 43 -
Figure 20 Horizontal Distance to Rise Vertical Distance or to Surface
Appendix E provides additional details and formulae that may be used to generate guidelines for
cases not explicitly considered in Figures 16 – 20. Appendix F provides examples in their
application.
- 44 -
exit points. The string may also provide a reference for verifying the proper depth during the
actual operation in the presence of minor surface depressions or irregularities (compared to
depth), and serves as a basis from which to interpret the guidelines of Section 8.4, which assume
a uniform level surface grade. In general, the bore should attempt to follow a path at the nominal
specified depth below the average surface profile. For large surface depressions or mounds (e.g.,
of height greater than the depth of interest and extending over a long expanse, on the order of the
drill rod bend radius or greater), including peaks and valleys, the bore should attempt to follow a
path at the specified depth below the local average surface grade.
8.5.2 Path Curvature – Although the presence of obstacles or ROW geometry may impose
deliberate path curvature (Figure 6), the bore plan should attempt to minimize such deliberate
bends and curves, whether left/right or up/down. Such trajectories are difficult to follow and
may lead to over-steering and excessive bends, resulting in increased stresses in the drill rods and
greater required pulling forces during the installation of the pipe; see Section 7.3. The average
radius of curvature, or 90° bend radius (see Section 3.3), of a path segment may be estimated
based upon the distance along the path segment and the angular change, as follows:
Radius of Curvature (ft) = 57.3 x Distance (ft) / Angle (deg) (8a)
90° Bend Radius (ft) = 90 x Distance (ft) / Angle (deg)
(8b)
- 45 -
Thus, a change of 20° along a 100 ft path segment corresponds to a path radius of curvature of
287 ft and a path 90° bend radius of 450 ft. Figure 21 illustrates the radius of curvature
corresponding to the angular change and distance along the path. The 90° bend radius, defined
as the distance for accomplishing a 90° angle, is equal to the radius of curvature multiplied by
1.57; see Section 3.3.4, Equation 1b. For example, the 90° bend radius corresponding to a 200 ft
radius of curvature is equal to 200 ft x 1.57 = 314 ft, which is seen to agree with the distance
traversed for a 90° bend, as indicated in Figure 21.
8.5.3 Proposed Bore Path – While more convenient methods and tools are now available for
preparing a bore plan(13), it is instructive to consider the conventional manual procedure, such
as illustrated in Figure 22. This figure shows a sample bore plan, comprising a straight path in
the planar view, which may be used as the basis of subsequent as-built drawings, illustrated in
Figure 24.(16) Although not explicitly shown in the sample, reference points should be
included.
8.5.4 Accuracy and Tolerance – Section 6.3 (Figure 5) discusses the tolerance zone, with
respect to existing facilities, which must be avoided by any part of the drill or reamer. To help
maintain the required separation, it is recommended that the proposed bore path, including the
outer edge of the cutter/reamer, be an additional 18 inches laterally offset from the outer edges of
the tolerance zone, corresponding to a total 36-inch initially planned separation. For the case of
the bore path crossing an exposed utility, adequate physical separation may be visually verified
as the drill head or reamer passes above or beneath the existing line. In the rare event in which it
is not feasible to expose an existing utility at a crossing, the position of the line must be
- 46 -
otherwise accurately established or verified and the proposed bore path must provide a
minimum of 24-inches separation, or greater if required by State or local regulations,
between the outer edge of the cutter/reamer and the closest portion of the utility, whose depth has
been determined as well as reasonably possible during the identification and location process
(Sections 6.2 and 6.4). The owner may place additional restrictions on the allowed deviation
from the proposed bore, in both vertical and horizontal directions. (See Section 9.5.1.) Soil
conditions, including cobbles and other encountered obstacles, as well as attempts to conform to
relatively sharp bends, may result in unintentional bore path deviations. More frequent
verification of the position of the drill head during the pilot bore phase will help detect potential
discrepancies as soon as possible, and facilitate path corrections; see Section 9.4.3.
9. Implementation
Section 9 discusses the overall sequence of operations, and appropriate procedures, during the
actual pipe installation. These operations include drill rig positioning, pilot boring, tracking,
steering, reaming and pullback. It is beyond the scope of these guidelines to provide detailed
operational procedures for the various mini-HDD and auxiliary equipment. It is therefore
assumed that the contractor has provided evidence of proficiency (see Section 5.9).
- 47 -
9.3 Drilling Fluid Usage
Drilling fluids are used to remove cuttings and spoils and help support and stabilize the bore
hole, as well as to provide possible cutting assistance during the boring or back-reaming
operations. The fluids provide lubrication during the various phases of the HDD process (pilot
boring, reaming, pullback), to reduce the required torque and thrust or pullback loads imposed on
the equipment. Reduced friction is an important factor in minimizing the required tensile forces
applied to the product pipe (Appendix C). The drilling fluid also cools the drill head to avoid
premature damage to the cutters and/or failure of the internal transmitter. The volume of fluid
required depends upon the size of the pilot bore and especially that of the subsequent expanded
hole (Section 9.6), and on the role of the fluid in accomplishing the ground penetration. If mud
motors are required, such as for rocky conditions, considerably greater volumes of drilling fluid
will be required, for which the use of drilling fluid recirculating systems is recommended. An
important element in the proficiency of the crew is an adequate understanding of the proper use
of drilling fluids, and the appropriate types for various ground conditions.(4, 17)
9.3.1 Drilling Fluid Pressure – A possible problem in HDD operations is the appearance of
drilling fluid at undesired surface locations, or possible heaving, sometimes as a result of
excessive drilling fluid pressures. Excessive applied drilling fluid pressures may also contribute
to premature pipe collapse (Appendix B). Figure 23 may serve as a guide for the upper limit on
the total pressure to be maintained within the bore hole, including that due to the weight of the
drilling fluid/slurry and the incremental pressure applied at the drill head or back-reamer
(Section B.3.4). Additional information and recommendations may be obtained from other
industry sources.(3)
- 48 -
9.3.2 Inadvertent Fluid at Surface – Due to the combination of drilling fluid pressure and
possible local fissures in the soil, it is possible that fluid may penetrate to the surface at an
intermediate point along the bore path. In such cases, the material should be promptly
remediated or removed. In order to avoid uncontrolled surface penetration in sensitive areas,
several deliberately placed vertical holes from the surface to the bore hole can serve as a vent to
locally relieve the fluid pressure. Such procedures may be appropriate at the edges of paved
areas including driveways. Any vented fluid should be cleaned immediately after completion of
the installation of the pipe, and the vent holes re-filled. See Section 9.10 for additional
information.
9.3.2.1 High Risk Situations(19) – Extra caution should be employed in situations with a
high risk of inadvertent returns:
• Fractured rock (pre-existing flow paths or presence of joints)
• Coarse grained permeable soils (gravel, cobble and boulders)
• Considerable elevation differences between the entry side and pipe side
• Areas where HDD vertical depth of cover is insufficient
• Artificial features (existing exploratory bore holes).
- 49 -
9.4.4 Steering – In areas with cobbles or other obstacles that may divert the drill head, and
when not using remote or target steering, measurements should be made whenever contact with
such obstacles is suspected. Such incidents can lead to significant departures from the intended
path, possibly towards adjacent facilities, which may require immediate correction. If not
acceptable to gradually steer back to the desired path, it may be possible to retract the rod
somewhat and attempt to pursue a path closer to that intended.
9.5 Records
9.5.1 Pilot Bore Position – Figure 24 shows the actual “as-built” path of the pilot bore based
upon the tracking information, corresponding to the original bore plan of Figure 22.(16) The
deviations from the intended path in both the horizontal and vertical directions are provided.
This information, and/or related drawings and supplemental information, may be used to provide
a record of the installation, to be submitted to the owner; see Section 10.4. The drawings should
reference permanent existing structures or features (e.g., curbing), and preferably indicate the
relationship to existing utilities, especially at crossings of such lines. Unforeseen obstacles
encountered during the drilling process should also be indicated. Similar to the availability of
more convenient (less manual) methods and tools available for preparing the original bore plan
(Section 8.5.3), software tools are also available for facilitating the preparation of the
information or drawings, including the ability to “Log-While-Drilling”.(13, 20)
9.5.2 Other Information – Figure 24 also includes information related to the actual boring
operation such as steering commands (drill head orientation). Additional information related to
the boring or reaming operation, such as type and size (diameter) drill head, reamer and/or
compactor; drilling fluid type and volume; duration of pilot bore and/or back-reaming operation,
may be useful for subsequent operations in the project area (see Section 4.4.3). In general, a
daily log book, or equivalent, should be maintained by the contractor to provide a permanent
record of the operation, including the above information.(4)
9.5.3 Product Pipe Position – The recorded path information is based upon the tracking
information obtained during the pilot bore operation, and assumes that the reamer closely follows
the original path. In practice, however, it is not uncommon for the reamer to deviate somewhat
from the pilot bore path, due to various effects, including a tendency for the reamer to cut
corners as it is pulled around curves and bends. Although such discrepancies may be significant
in cases of very close proximity to other utilities, it is not generally considered to be a major
issue, similar to the tendency of the installed product pipe to float above (or sit below) the
centerline of the final bore hole corresponding to the difference in their diameters.
- 50 -
Figure 24 Final “As-Built” Pilot Bore Path
(Source: Ditch Witch®)
9.6 Reaming
9.6.1 Final Hole Diameter – With the exception of very small diameter pipes, such as 1- to
1½-inch HDPE duct, most mini-HDD operations require the expansion of the initial pilot bore
hole, as illustrated in Figure 2. The increased size is necessary to accommodate the relatively
large diameter of the pipe, including pulling grips, as well as to facilitate spoils removal and
avoid unnecessarily large pullback forces on the pipe. A final hole diameter at least 50% greater
than the outer diameter of the pipe (or pipe bundle) is recommended. The back-reaming and
pullback operation typically requires greater time, machine load, and drilling fluid volume than
the initial pilot bore due to the creation of the larger hole. The soil conditions will determine the
appropriate type of reamer.
9.6.2 Pre-Reaming – In some cases, the mini-HDD operation requires more than the two
stages illustrated in Figures 1 and 2. A simultaneous back-reaming/pullback operation is
adequate for product pipes up to approximately 4-inch nominal size. For larger sizes, however, a
pre-reaming operation(s) is recommended, allowing relatively large holes to be created in stages.
Although time-consuming, this procedure reduces the required torque and thrust loads at the
mini-HDD equipment, and reduces the likelihood of subsurface voids, surface heaving or
settlement, and undesirable drilling fluid appearance at the surface. The hole diameter should be
expanded in increments of 6 inches or less during a single pass. In order to maintain the original
path during the pre-reaming operation, drill rods must be available at the pilot bore exit and
connected to a swivel at the rear of the reamer and pulled into the hole. Due to potential hazards
associated with expanding the hole in the presence of existing electrical facilities lines, it is
important to closely adhere to the electrical safety aspects discussed in Section 5.5.2 to avoid
electrical shock at the bore exit end where the rods are added, as well as at the drill rig.
- 51 -
9.7 Connecting the Product Pipe
9.7.1 Assembly – A major advantage of polyethylene pipe is its availability in continuous
lengths on a reel, or in a coil, for a wide range of diameters (possibly 6-inches or greater). For
HDPE products not available in continuous lengths, discrete lengths of HDPE pipe may be
readily fused in the field, without an appreciable loss in the tensile capability required for HDD
pulling operations. 6 In the latter case, the pipe should be assembled prior to the pullback
operation to maintain continuity during the pipe placement process and avoid unnecessary
delays. Significant interruptions may lead to increased drag and resulting pulling forces,
including eventual loss of integrity and collapse of the bore hole, preventing further movement
of the pipe.
9.7.2 Gripping – Appropriate gripping hardware and utilization should be compatible with
the inherent safe pulling load (Section 7.3.1) of the product during the pullback operation and
also ensure that debris or slurry does not enter the pipe. Improper gripping may result in
slippage or premature pipe rupture at the grip connection. One option is to use a pulling head
that is fused to the product pipe; see also Section 9.7.4. Although some, more sophisticated,
HDD operations, including maxi-HDD, may deliberately allow drilling fluid to enter the cavity
to minimize or eliminate buoyancy effects, which tend to increase pulling loads (Section 7), as
well as to offset the effects of external pressure, typical mini-HDD installations do not employ
this procedure.
9.7.2.1 Hardware – A relatively convenient gripping method, appropriate for a relatively
wide range of pipe sizes, utilizes a wire mesh grip that squeezes the outer surface of the pipe as
tension is applied, and is properly used in combination with an internal dowel inserted into the
pipe to prevent crushing as well as the entry of debris or slurry. (If the dowel or equivalent is not
employed, the exposed end of the duct must be taped closed.) The wire mesh grip should be
initially taped to the pipe outer surface to prevent initial loosening until tension is applied.
Although convenient to use, such grips may not be fully compatible with the safe pulling load of
the pipe. Another type of gripping hardware utilizes a tapered threaded shaft, in the appropriate
size range, that engages the interior surface of the pipe. A particularly effective hardware design
grips both the interior and exterior surfaces of the pipe. Using any hardware type, several pipes
in a bundle may be pulled simultaneously. A separate grip should be used for each pipe, and the
position of the grips should be staggered, to avoid a large bulge.
9.7.3 Swivel – In order to prevent the transmission of torsional loads to the pipe(s) due to the
rotating drill rods or back-reamer, a swivel should be mounted behind the rods or reamer, to
which the pulling line(s) and gripping hardware are connected; see Figure 2. The swivel must be
appropriate for drilling operations, compatible for use in soil and slurry. For non-breakaway
type swivels (Section 9.7.4.2 discusses breakaway swivels), the load rating should be at least as
large as the total safe pulling loads of the bundle of pipes to be installed, but not excessively
greater. Inefficiencies in overly large swivels may impose significant torque on small pipes.
9.7.4 Breakaway Link or Thinner-Walled Pipe Connection – Section 7 provides a
methodology for selecting the pipe strength (wall thickness, DR) for a mini-HDD operation,
providing confidence that the product pipe will safely withstand the installation stresses.
Nonetheless, for some applications it may be desirable to ensure that the integrity of the product
pipe has not been compromised by excessive tensile loads, especially when using product pipe
6 See ASTM F1055, ASTM F2620, ASTM F3190, MAB-01 and MAB-02.
- 52 -
thinner than DR 11. In general, attempting to monitor the pulling load on the pipe by observing
the hydraulic pressure at the control panel, which reflects the pulling load imposed on the drill
rig, is not appropriate. Such loads are not necessarily experienced by the pipe, but include the
pullback force necessary to ream or compact the hole, or pull the drill rods through the path. A
commonly used procedure would be to install a breakaway link between the main swivel and the
grip at the pipe, to ensure that the allowable tensile strength is not exceeded. The rating of the
breakaway link should be compatible (i.e., slightly lower than) with the safe pulling load of the
product pipe. Alternatively, it is possible to fuse a short segment of thinner-walled pipe to the
product pipe, to serve as a “weak link”. In the event of a broken or ruptured link, due to
excessive pull load, the pipe should attempted to be withdrawn from the pipe entry end. The
likely reason for failure should be determined and, assuming the predicted pull load is verified to
be acceptable (Section 7), the installation repeated. If necessary, a new bore path may have to be
created.
9.7.4.1 Multiple Pipes – When installing a bundle of pipes, the pull loads may not be equally
or proportionally distributed among the individual units, and an individual pipe may experience
excessive stress. Thus, it is preferable to use an individual breakaway link connected to each
pipe, rather than a single link rated at the cumulative strength of the bundle.
9.7.4.2 Breakaway Swivel – When pulling a single pipe, if a breakaway swivel is used as the
breakaway link, and is not specifically designed for direct exposure to soil, the use of such a
breakaway swivel does not reduce the need for the main swivel described in Section 9.7.3.
When pulling multiple pipes in a bundle and individual breakaway swivels are used for each pipe
(Section 9.7.4.1), a separate main swivel behind the reamer is again required to prevent twisting
of the bundle itself.
10. Completion
Following installation of the pipe, it is necessary to confirm the viability of the new facility, as
well as to provide a permanent record of the actual placement location. Section 10 addresses
these practices and also indicates the need for final site cleanup.
10.1 Inspection
It is assumed that the owner, or its representative, of the pipeline facility being installed, has had
an inspector on-site, or has regularly visited the area, to verify the progress of the operation and
that the construction is consistent with recommend practices, such as those provided herein or
7 “Hydrolock” occurs when the pressure acting on the leading end of the reamer, during the pullback process,
exceeds the pullback capability of the drill rig.
- 54 -
available from the industry.(4, 5) 8 It is essential that pipeline facility being installed be visibly
inspected prior to filling the various pits that may be present. In particular, the route should be
inspected at openings or pits provided for access, as well as any areas where existing utilities
have been exposed, such as at crossings with the new pipe. The depth of the pipe may be
conveniently verified at such locations.
8 HDD training and/or certification courses are available from various sources, including the Center for
Underground Infrastructure Research and Education at the University of Texas at Arlington, the Centre for
Advancement of Trenchless Technologies at the University of Waterloo, Bowling Green State University, the
Trenchless Center at Louisiana Tech University, and the North American Society for Trenchless Technology.
9 A new document, Standard Guideline for Recording and Exchanging Utility Infrastructure Data is under
preparation by the ASCE to provide a common means for communicating the positional accuracy of utility assets.
- 55 -
APPENDICES
These values describing the bending -- or maximum steering -- characteristics of the postulated 2
ft x 10 ft drill rod are representative of the capability of typical mini-HDD machines; see Section
A.2. These limitations apply to bends in a horizontal (plan) or vertical (profile) plane, as well as
an inclined plane or three-dimensional path.
- 57 -
B. Maximum Allowable Depth (Pipe Collapse/Buckling) – Theoretical Development
The following methodology, for application to mini-HDD installations, is based upon
techniques similar to that provided in “Simplified Methodology for Selecting Polyethylene
Pipe for Mini (or Midi) – HDD Applications”, by Slavin(11), which are derived from the
procedures provided in ASTM F1962.
- 58 -
Table B.1 Ideal Critical Pressure (Water Head, ft) for
Unconstrained HDPE (PE4710) Pipe (73°F)
- 59 -
which the drilling fluid is assumed to apply hydrostatic pressure on the pipe, subsequent to
which it is assumed to thicken and set sufficiently to provide adequate lateral support for the
pipe.(23, 24) For this post-installation phase, the tension reduction factor, fR , is equal to 1.0,
in the absence of significant tensile load, and there is no hydrokinetic pressure increment.
The effect of possible initial elevated material temperatures, due to conditions at the surface
prior to installation, is ignored, assuming the pipe adjusts to local belowground temperatures
during the installation process.
B.3.2 Ovality Factor– Based upon the ovality reduction factor provided in ASTMF
1962, and consistent with the present simplified approach, it is reasonable to assume a
maximum overall value of fo of approximately 0.65 to account for ring deformation due to
initial ovality plus that induced during installation (e.g., buoyancy or longitudinal bending,
aggravated by tension-induced wall bearing pressure), or possibly due to some degree of soil-
induced loads. This corresponds to an ovality of approximately 5%, a reasonable ring
deflection limit.(1)
B.3.3 Tension Reduction Factor – ASTM F1962 provides the tensile stress reduction
factor fR as a function of the average stress on the pipe cross-section. For stress levels
corresponding to that of the safe pulling load (Table 2 or Table 3), fR is equal to 0.65.
However, for tensile loads that are significantly less than the safe load, as would be typically
experienced, fR would be closer to the 1.0 level. For the present purposes, the likelihood of
experiencing a tensile load equal to the predicted value (i.e., equal to the safe pull tension),
based on placement at the somewhat conservatively determined maximum recommended
length, simultaneously with placement at the maximum recommended depth, is assumed to
be low.
B.3.4 Hydrokinetic Pressure – ASTM F1962 assumes the incremental hydrokinetic
pressure applied at the drill head or back-reamer to be as much as 10 psi (equivalent to 23 ft
of water head). However, the actual value should also be limited to that which would avoid
heaving or fluid leakage at the surface due to the total pressure, including that due to the
hydrostatic pressure head. In general, the lower the mud slurry density, the greater the
allowable hydrokinetic fluid pressure that may be applied. Thus, although a specific gravity
of 1.5 is conservatively assumed for the mud slurry for the purposes of these guidelines,
lower values are recommended in practice.(4) Figure 23 shows recommended total pressure
based upon the simplified assumption that the pressure due to the drilling fluid/slurry may be
as high as the overburden pressure due to the soil(OPSS 450), with an assumed density of
110 lbs/ft3, but also no greater than 10 psi above that due to the hydrostatic pressure of the
drilling fluid/slurry. Excessive pressures may also contribute to premature pipe collapse.
B.3.5 Maximum Allowable Depth – Both the 1 hour installation and the 1,000 hour
post-installation strengths should be considered relative to the applied loads, as described
above. Based upon the above discussions, and considering the various factors and their
applicability, the 1,000 hour installation conditions are assumed to be the more restrictive.
Thus, these values, as reduced by the slurry density (1.5) and ovality factor (0.65), plus a
suggested “safety” (i.e., uncertainty) factor of 2-to-1, to account for deviations from the
above assumptions, provide the allowable maximum depths based upon the short-term
(installation and pre-operational) considerations. These factors correspond to a net
reduction of 4.6 for the values indicated in Table B.1, and result in estimated allowable
depths ranging from greater than 250 ft. for thick-walled DR 7 to slightly less than 15 ft for
- 60 -
relatively thin-walled DR 17, with significantly greater (20%) average values due to the
oversize effect of actual manufactured product.
B.3.6 PPI Boreaid (www.ppiboreaid.com) – The Plastics Pipe Institute BoreAid™
software tool is intended to apply to maxi-HDD applications, and allows a more precise
determination of the maximum allowable depth, considering both short-term (e.g.,
installation) or long-term loads, and, based on the specific application (pressurized vs non-
pressurized) and soil characteristics. A consideration of a variety of possible combinations
indicates that the allowable depths, as estimated by the above simplified procedure, are
remarkably consistent with that of Boreaid, as applied to analogous maxi-HDD installations,
with the exception of DR 17 pipe, which appears to be limited to lesser depths, due to
collapse during initial installation. The DR 17 pipe may be conservatively placed at less than
10 ft, although a greater depth, such as 15 ft, may be justified for installation tensions less
than the maximum allowable, (e.g., a relatively short bore), and in consideration of the 20%
additional margin described above.
- 61 -
C. Pulling Tension Prediction – Theoretical Development
The following methodology, for application to mini-HDD installations, is based upon the
techniques provided in “Simplified Methodology for Selecting Polyethylene Pipe for Mini
(or Midi) – HDD Applications”(11), which are derived from the procedures provided in
ASTM F1962.
- 62 -
where wa and wb are the empty (above ground) and buoyant weights of the pipe, respectively,
and νa and νb. are the corresponding coefficients of friction; the angles α and β are expressed in
radians 10. For HDD installations for which the buoyant forces dominate – i.e., in the absence of
anti-buoyancy techniques, such as filling the product pipe with water or drilling fluid to serve as
ballast-- the peak required tension will tend to occur towards the end of the installation. Thus, as
described below, for the present purposes, an estimate of TD is sufficient for determining the
appropriate pipe strength.
C.2.1 Coulomb Friction Model – Equations C-1 are based upon conventional Coulomb
friction. In this mathematical model, drag forces on the pipe are proportional to the local normal
bearing pressure applied at the pipe surface, with the proportionality constant designated as the
“coefficient of friction”. Bearing pressures are due to the combination of several effects,
including the dead (empty) weight of the pipe where above ground, the buoyant weight of the
submerged pipe (possibly reduced by anti-buoyancy measures), or bending forces associated
with pulling a stiff pipe around a curved surface. For the case of HDPE pipe, of low bending
stiffness relative to that of the steel drill rods that created the gradually curved bore hole path, the
corresponding bearing and drag forces are not significant.
C.2.2 Capstan Effect – There is, however, another important source of bearing pressure
acting at bends that is independent of the pipe stiffness, or weight or buoyant forces, and is due
to the local tension tending to pull the pipe against the inner surface of the curved path. This
phenomenon is referred to as the “capstan effect” (i.e., the operating principle of the “capstan
winch”) and is the basis of the exponential terms in Equations C-1. Such effects are independent
of the direction of curvature, or the sharpness of the bend (radius of curvature) and accumulate
exponentially along the path. The capstan effect results in a local amplification factor at each
discrete bend of finite angle, or, for a gradual bend, an amplification effect distributed along the
path, with magnitude dependent upon the total cumulative traversed angle. For an idealized
weightless, perfectly flexible pipe:
F2 = F1 · eν θ (C-2)
F1 represents the axial tension at the entry point of a bend of magnitude θ (radians), ν is the local
coefficient of friction between the product pipe and bore hole wall surface, and F2 is the required
axial tension at the exit point of the bend. In practice, the effect of the actual weight, or possible
stiffness, of the pipe, is reflected in the preceding tension, F1. Due to the exponential
compounding character of the tension increase, discrete route bends or gradual accumulating
curvature, may represent the dominant source of drag, essentially controlling practical placement
distances.
10 The angle in radians is equal to the angle in degrees x (π / 180). For relatively small angles, such as typical HDD
bore entry or exit, the angle in radians is approximately equal to the percent grade divided by 100.
- 63 -
C.3.1 Simplifying Assumptions –Equations C-1 may be simplified for the present case of
interest -- i.e., typical mini-HDD installations of HDPE pipe – based upon the following
assumptions:
• No anti-buoyancy techniques employed
• Coefficients of friction, νa and νb , equal to 0.5 and 0.3 respectively
• Pipe entry angle, α, and exit angle, β, equal to 20°
• Depth of crossing, H, small compared to overall bore length, Lbore
• Peak pull force, TD , occurs at the end of the installation .
These assumptions are reasonable and/or conservative, and result in a simplification of Equation
C-1d:
TD ≈ Lbore · wb · (1/3) (C-3)
Although it is possible, under appropriate conditions and actual installations, that the pull force
may achieve its maximum level prior to point D, based upon the above assumptions, the
predicted tension at point D would be the maximum, or reasonably close in magnitude to a
previously occurring (predicted) maximum value.
C.3.2 Additional Path Curvature – Equations C-1 and C-2 account for the capstan effect
due to the deliberate route bends illustrated in Figure C.1 for a well controlled maxi-HDD
installation. However, mini-HDD installations tend to be accompanied by additional path
curvature due to possible planned course deviations to avoid previously identified obstacles, as
well as inevitable unplanned path corrections, depending upon the operator skill and soil
conditions. The above estimate of TD by Equation C-3 must therefore be modified to account for
a corresponding increase in the required pull force. These effects may be conservatively
included in the analysis by applying the exponential term in Equation C-2 to Equation C-3, such
that
TD1 = TD · eνb θ (C-4)
where TD1 represents the net final tension, and the angle θ is equal to the total additional route
curvature. The angle θ is conveniently expressed as an equivalent number of 90° route bends, n,
or fraction thereof, where each 90° route bend is equal to (π/2) radians; thus,
θ = n · (π/2) (C-5)
Using the previously assumed value of νb of 0.3, combining Equations C-3, C-4 and C-5 yields
TD1 ≈ [Lbore · wb · (1/3)] · (1.6)n (C-6)
which corresponds to Equation 2 (Section 7.3.2).
C.3.2.1 Effective Number of Route Bends – The total number of effective 90° route bends
may be expressed as
n = n1 + n2 (C-7)
where n1 is the number of deliberate/planned 90° route bends, and n2 is the cumulative effective
number of 90° bends due to the unplanned undulations. See Section 7.3.2 and Figure 6 for a
further description of the interpretation and determination of the effective number of route bends.
- 64 -
C.3.2.2 Unplanned Route Curvature – It is noted that the cumulative effective number of
90° bends due to the unplanned undulations, n2 , is difficult to predict since this will obviously
vary among installations due to soil conditions, expertise of the crew, … The final effective
curvature experienced by the product pipe during the pullback operation may also be impacted
by the reaming process, which may tend to straighten the path somewhat, and by the amount of
clearance between the product pipe and bore hole diameter, with greater clearances reducing the
imposed pipe curvature. The suggested values provided by Equations 5 and 6 are intended to
represent the general magnitude of the unplanned curvature experienced by the product pipe, as
based upon limited experiences, including analyses of sample as-built data provided in mini-
HDD equipment operator manuals.(16, 25) These levels are not necessarily intended to be
conservative for such mini-HDD applications, and significant variability may be anticipated.
C.3.2.3 Drill Rod Size – The linear dependence of the unplanned route curvature, n2 , on
rod diameter, as indicated in Equation 6, is consistent with maintaining an equivalent stress level
in the steel rod, and corresponds to approximately one-third that typically allowed by bending
specifications provided by drill rod manufacturers, as illustrated in Appendix A. Although, in
principle, this same rule may be extrapolated to maxi-HDD, using corresponding large diameter
drill rods, it is considered excessively conservative for such well-planned, well-controlled
installations.
C.3.3 Buoyant Weight – In order to apply Equation C-6 (or Equation 2, Section 7.3.2), it is
necessary to determine the buoyant weight, wb , of the portion of the HDPE pipe submerged in
the drilling fluid, along route segments L2, L3, and L4 (Figure C.1). ASTM F1962 provides
general formulae for calculating the buoyant weight of the pipe under various conditions,
including empty, filled with water, and filled with drilling fluid. For the present mini-HDD case
of interest, for which the pipe is assumed to be empty, and, as suggested in ASTM F1962, the
specific gravity of the drilling fluid (mud), γb, is conservatively assumed equal to 1.5, the
formula for calculating the buoyant weight reduces to Equation 3, Section 7.3.2.
C.4 Application
The guidelines for maxi-HDD provided in ASTM F1962 require that the predicted peak tensile
stress be no greater than the corresponding safe pull stress, without the imposition of any
additional explicit design/safety factor. However, the corresponding determination of the peak
tensile stress includes that due to the average tensile load applied across the pipe cross-sectional
area, as predicted by Equations C-1, plus the bending stresses at path bends, as well as the stress
increment due to hydrokinetic pressure from the drilling fluid flow along the length of the pipe.
In comparison, the simplified methodology as provided in the present mini-HDD guide does not
account for the latter two effects. For this reason, and the acknowledged lower degree of control
in mini-HDD operations, including anticipated wide variability in unplanned path curvature
(Appendix C.3.2.2), as well as the various simplifications used to arrive at above Equation C-6
(or Equation 2), an additional load factor (> 1.0) may be applied to the tension term on the left
side of Equation 2 or Equation C-6 for those applications in which a more conservative design
may be desired. This would effectively reduce the recommended maximum placement
distances; see Appendix D.
- 65 -
D. Examples of Load Prediction and Pipe Selection
- 66 -
impact of the unplanned curvature effect, reflected in the n2 (or n) term. Ignoring this term (i.e.,
assuming n2 = 0) would result in a predicted tension of less than 2,607 lbs -- underestimating the
measured load by 25%. The results are illustrated in Figure D.1 (Case 1).
D.1.2 Cases 2, 3, 4 – Another source provides data obtained during a series of three
experimental installations, using and reusing the same 590 ft long nominally straight bore hole
path, pre-reamed as necessary to approximately 50% greater than the outer diameter of the
pipe.(26) Two of the installations placed a 6-inch DR 11 (IPS) MDPE 12 pipe (Case 2 and Case
3) and the third placed an 8-inch DR 17 (IPS) HDPE pipe (Case 4). The installations were
accomplished using drill rods assumed to be of approximately 2-in. diameter. The recorded peak
pull loads were 5,620 lbs., 3,372 lbs., and 5,845 lbs., in the sequence described, and in general
were experienced prior to the end of the operations. These loads compare to predicted levels of
5,924, 5924, and 10,580 lbs., using the present methodology in a manner similar to that of Case
1. The results for the three sets of data are also illustrated in Figure D.1.
D.1.3 Discussion – The results demonstrate that the proposed simplified model is able to
predict the general magnitude of the experienced peak tensile load during a mini (or midi) - HDD
operation, within a factor of two or better, based upon the limited sample size. In general, the
degree of agreement is excellent, depending upon whether the additional tensile load due to
unplanned bore path curvature (n2) is included in the estimate. In some cases (Case 1 and Case
2), such considerations result in outstanding agreement, while in other cases (Case 3 and Case 4)
the agreement is excellent without considering the additional tension due to this effect. A
12 The methodology (Equation 2) for estimating the pull load does not depend upon the type of PE pipe.
- 67 -
possible explanation for the latter is the repeated use of the same bore hole, for the purposes of
the three field experiments, with subsequent reaming/pullback operations resulting in a
somewhat straighter path than that corresponding to the estimated magnitude of unplanned
curvature, more likely to be present in practical applications.
In spite if the demonstrated good-to-excellent agreement in the sample cases above, a wide
variability must be anticipated when considering mini-HDD installations in general, due to the
complexity of the soil-pipe interaction, variable soil conditions, operator skill, ... Such factors,
for example, will impact the degree of unplanned path curvatures, demonstrated to be of
importance in some cases, but only roughly estimated by Equations 5 and 6. The possible use of
a load or safety factor (> 1.0) applied to the tension, as discussed in Appendix C.4, attempts to
account for the wide variability associated with such effects in mini-HDD (and some midi-HDD)
installations; see design example of Appendix D.2.
13 These distances exceed the nominal limits for typical mini-HDD installations, but are used to illustrate the
proposed design procedure.
- 68 -
Thus, Equation 2 predicts a peak pull load of
Tension (lbs) = [Bore Length x Buoyant Weight x (1/3)] x (1.6)n
= [700 ft x 9.0 lbs/ft x (1/3)] x (1.6)2.4
= 6,488 lbs
Equation 7 then requires that this predicted installation load, approximately 6,500 lbs, be no
greater than the relevant safe pull tension (nominal 4-inch pipe, DR 11) indicated in Table 3 for
HDPE pipe, which corresponds to 8,375 lbs. The DR 11 pipe therefore has an apparent safety
factor equal to 8,375 lbs / 6,500 lbs, or 1.3. Table 3 also indicates that a DR 13.5 pipe should
have adequate tensile strength, but with a lower safety factor (< 1.1). Considering the potential
issues discussed above (Appendix C.4 and D.1.3), the responsible engineer may decide to select
the thicker wall DR 11 product.
Whereas the present example specifically considers a 4-inch DIPS pipe, for a given DR value,
the predicted pull load and the safe pull tension are both proportional to the square of the outer
diameter. The conclusions are therefore independent of the pipe diameter, including for IPS
designated pipes. It is noted that the use of the DR 11 pipe in a nominally straight route of more
than 1,000 ft-- significantly beyond the generally accepted limit for mini-HDD applications -- is
also predicted to be acceptable based on estimated pull loads (see Section 7.4 and Figure 9).
D.2.2 Collapse Strength – Regarding the potential vulnerability to collapse during the
installation or post-installation (but pre-operational) phase, while it is subject to the hydrostatic
pressure due to the drilling fluid/slurry, prior to its assumed “solidification”, Appendix B
indicates that DR 11 HDPE pipe may be placed at a depth of 58 ft (= 265 ft / 4.6), independent of
pipe diameter. Thus, the relatively high 30 ft proposed installation depth is well within the
capability of the DR 11 wall thickness. The allowable depth of a DR 13.5 pipe (= 135 ft / 4.6),
or slightly less than 30 ft, would be marginal, suggesting the need for the DR 11 product.
D.2.3 Discussion – The relatively difficult, aggressive mini-HDD installation of the design
example demonstrates that a DR 11 HDPE pipe represents a reliable selection for essentially all
mini-HDD (as well as many midi-HDD) applications. Thinner walled pipe (higher DR rating)
may also be a reasonable selection in many cases, but should be verified by specific calculations
for the route of interest. It is emphasized, however, that the present methodology for pipe DR
selection does not ensure that a weaker, thinner-walled pipe would not be successful in practice
in individual installations, but, as in most design procedures, the methodology provides
reasonable or conservative estimates of the capability of the pipe to withstand the application,
and serves as a warning that a weaker product may be marginal or inadequate.
- 69 -
E. Drill Rod Characteristics and Implications – Theoretical Development
The physical characteristics of the drill rods, in combination with the geometry associated with
the drill rig entry and desired bore path exit angle, provide restrictions on the bore path
configuration and mini-HDD operation. These include required minimum setback distances as
well as horizontal distances required to rise to the surface.
14 The bore path entry angle β corresponds to the pipe exit angle, as illustrated in Figure C.1.
- 70 -
the recommendation that the first rod be placed in the ground in a straight configuration, there is
a minimum depth at which the trajectory may be able to become level. The minimum possible
depth for d2 may be calculated by:
(d2)min = l sinβ + Rrod · (1 – cosβ)
≈ l β + Rrod · β2/ 2 (E-3)
This value is explicitly indicated in Figures 13 – 15, for various drill rods, for the case of a 15°
(27% grade) bore entry angle.
These values are shown as the dotted lines (S3) in Figures 16 – 18. The resulting bore exit angle
α 15will be determined by the depth d3, as given by:
α = arccos [1 – d3/Rrod]
≈ 2 ⋅ d3 / R rod (E-5)
Corresponding exit angles based upon this equation are provided in Figure 19.
E.2.2 Exit at Specified Angle – The distance S3 is shorter than that corresponding to the
distance S5 indicated in Figure 11. The latter distance corresponds to a path that rises from the
depth d3 partially on an arc and then (from point 4) continues along a straight path at a specified
bore exit angle (grade) α:
S5 = Rrod · sinα + [d3 – Rrod (1 – cosα)] / tanα
≈ Rrod · α + [2·d3 – Rrod · α2)] / 2 α (E-5)
These values are also shown in Figures 16 – 18, as a function of the specified exit angle, for
which the maximum possible exit angle is limited by the depth d3, consistent with Figure 19.
E.2.3 Horizontal Rise Distance along Fixed Grade – For a drill head oriented at an upward
angle α, the horizontal distance S4 to rise to the surface from a point 4 (Figure 11) from a depth
d4 is
S4 = d4 / tanα
15 The bore path exit angle α corresponds to the pipe entry angle, as illustrated in Figure C.1.
- 71 -
≈ d4 / α (E-6)
Analogous to Equation E-1, this formula corresponds to a rise at a constant grade, and is shown
in Figures 20, for various angles.
Appendix F provides examples in the application of the above equations, as reflected in Figures
13 – 20.
- 72 -
F. Example of Drill Rig Setup and Bore Path Geometry
F.1.1 Required Setback Distance – The utility specified depth of cover is consistent with that
recommended in Section 8.1.3. This may be verified by considering a final bore hole diameter
of approximately 50% greater than the pipe outer diameter, or approximately 10 inches (6.625 x
1.50), and comparing the specified 60 inches to the minimum cover of 50 inches indicated in
Figure 10.
Considering the shallowest entry angle (10°) indicated in Figure 15, the minimum depth (d2)min
required to achieve a level trajectory is approximately equal to the 60 inches desired 16.
However, the corresponding setback distance S2 of approximately 40 ft exceeds the available
space of 35 ft. Increasing the entry angle in an attempt more rapidly reach the desired depth is
not a solution since the minimum depth to achieve a level trajectory, at greater entry angles, will
now be greater than that desired. Unnecessarily deep placement is undesirable with respect to
possible future repair and maintenance activities.
One possible solution is to use a smaller HDD rig, utilizing drill rods of 10 ft length and 100 ft
allowable radius of curvature (Figure 14), for which the setback distance S2 at low entry angle
(10°) is approximately equal to the 35 ft available. The shorter drill rig also increases the
available setback distance by approximately 5 ft.
Another alternative would be to gain permission for the pipe to be somewhat shallower than the
desired 60 inches towards the entry point of the path, with the desired (level trajectory) depth
achieved slightly further along the route. Thus, for the original 15 ft drill rods, Figure 15
indicates that the available 35 ft space is approximately 5 ft less than the approximately 40 ft
necessary to achieve the level trajectory, and that a slightly shallower (non-level trajectory) depth
will be experienced for this short segment.
16 For the present purposes, the difference between the centerline of the bore path, as indicated in Figure 13, and the
reduced depth of cover corresponding to the pipe protruding above the centerline, is ignored.
- 73 -
Still another alternative is for the utility to agree that the objective depth may be exceeded
towards the beginning of the bore, beyond which the path may be adjusted to gradually rise to
the desired 60 inch depth. In this case, the 60 inch depth may be achieved along a path at the
entry grade after a setback distance S1 of only 30 ft (Figure 13).
F.1.2 Required Horizontal Distance to Rise – Figure 17 (and Figure 19) indicates that
steering the 150 ft radius of curvature drill rods such that they rise from the 60 inch level depth at
their maximum recommended bending capability, will result in an exit angle of 15°. Based upon
the information in Figure 18, this rise to the surface may be accomplished within a horizontal
distance S3 approximately equal to the 40 ft available space. Such a large exit angle is, however,
significantly greater than that originally specified (5°). In order to exit at the desired 5° angle, an
available distance S5 of more than 60 ft would be required (Figure 18). In this case, the use of a
smaller drill rig, with more flexible rods, would provide only a minor reduction in the required
horizontal rise distance S5 (Figures 16 and 17), and not represent a practical solution.
As a result of the above considerations, additional discussions with the utility may be warranted,
in order to obtain a better understanding of the space restriction at the pipe entry (bore exit) end
of the installation. It is possible that the utility had originally specified a low bore exit angle, as
well as reserved additional space at that end, in order to accommodate relatively rigid (non
polyethylene) pipe products. In such cases, significant longitudinal space is required to facilitate
assembly, layout and/or feeding of the pipe product into the completed bore hole. The use of
HDPE may therefore alleviate the problem, due to its possible availability in continuous lengths,
or convenient fusing into required lengths, greater physical flexibility and easier handling. For
example, the relatively large (15°) bore exit angle, achievable within the originally specified 40
ft, should not be an issue with an HDPE product.
- 74 -
REFERENCES
(1) The Plastics Pipe Institute, “The Plastics Pipe Institute Handbook of Polyethylene Pipe”,
Second Edition, 2008, including errata.
(2) Najafi, M., "Trenchless Technology, Pipeline and Utility Design, Construction, and
Renewal", McGraw-Hill, 2005.
(3) The Charles Machine Works, Inc., Ditch Witch® Equipment Solutions, HDD Gravity
Sewer Installations, https://www.ditchwitch.com/.
(4) North American Society for Trenchless Technology, Horizontal Directional Drilling
(HDD) Good Practices Guidelines - 2017 (4th Edition).
(5) Common Ground Alliance, Best Practices, The Definitive Guide for ", Underground Safety
& Damage Prevention”, Version 17.0, 2020.
(6) Svetlik, H., “Polyethylene Pipe Design for Directional Drillings and River-Crossings”, NO-
DIG 1995.
(7) Petroff, L.J., “Directional Drilling Design with ASTM F1962: A Decade of Success”,
ASCE International Pipelines Conference 2010.
(8) Vermeer Corporation, “BoreAid”.
(9) Kirby, M.J., Kramer, S.R., Pittard, G.T and Mamoun, M., “Design Guidelines and
Procedures for Guided Horizontal Drilling”, NO-DIG 2006.
(10) Huey, D.P, Hair, J.D., and McLeod, K.B., “Installation Loading and Stress Analysis
Involved with Pipelines Installed by Horizontal Directional Drilling”, NO-DIG 2006.
(11) Slavin, L.M., “Simplified Methodology for Selecting Polyethylene Pipe for Mini (or Midi)
– HDD Applications”, ASCE International Pipelines Conference 2007.
(12) Petroff, L., “Designing Polyethylene Water Pipe for Directional Drilling Applications
Using ASTM F1962”, NO-DIG 2006.
(13) Vermeer Corporation, “BoreAssist”.
(14) British Telecom, “Direct In Ground Manual, Moling Handbook”, 1988.
(15) Leuke, J.S., Ariaratnam, S.T., Colwell, D.A.F., “Towards the Development of Horizontal
Directional Drilling Depth of Cover Guidelines”, NO-DIG 2001.
(16) The Charles Machine Works, Inc. “Ditch Witch® Model 4/40 Jet Trac® Boring System
Operator’s Manual”, 1993.
(17) Najafi, M., "Trenchless Technology Piping", McGraw-Hill, 2010.
(18) Finnsson, S., “TensiTrak™ – A Tension Load and Drilling Fluid Pressure-Monitoring
Device for Horizontal Directional Drilling Installations”, NO-DIG 2004.
(19) Canadian Association of Petroleum Producers, “Guideline -- Planning Horizontal
Directional Drilling for Pipeline Construction”, CAPP Publication 2004-0022, September
2004.
- 75 -
(20) Digital Control Incorporated, “Digitrak Falcon® F5 Directional Drilling Guidance System,
Operator’s Manual”, 2017.
(21) Finnsson, Siggi, “HDD Pulls Off Bank Job in California”, Trenchless Technology, May
2020.
(22) Trenchless Technology, https://trenchlesstechnology.com/drill-master-you-might-not-be-
stuck-after-all-you-might-be-the-latest-victim-of-hydrolock/
(23) Ariaratnam, S.T., “Evaluation of the Annular Space Region in Horizontal Directional
Drilling Installations”, Arizona State University, 2001.
(24) Duyvestyn, G., Knight, M., Polak, M.A., “Excavation and Analysis of Two HDPE Pipes
Installed Using HDD Construction Techniques”, NO-DIG 2000.
(25) The Charles Machine Works, Inc., “Ditch Witch® Model 8/60 Jet Trac® Boring System
Operator’s Manual”, 1993.
(26) Knight, M.A., Duyvestyn, G.M., and Polak, M.A., “Horizontal Directional Drilling
Installation Loads on Polyethylene Pipes”, NO-DIG 2002.
- 76 -