sd500sdm Datasheet PDF
sd500sdm Datasheet PDF
sd500sdm Datasheet PDF
Model SD500-SDM
Two-Wire Smoke Module
The SD500-SDM allows you to assign an address to a loop of conventional detection devices. These
devices can be dry contacts such as pull stations and heat detectors, or 2-wire smoke detectors. This
means you can retrofit an existing building and utilize existing conventional devices. The SD500-SDM
uses a 24VDC auxiliary power input to power the conventional loop, and is connected to the SLC loop
via two wires. The conventional loop can be configured as Class A or Class B giving you the flexibility
to handle any job.
Feature
• Converts a conventional two-wire
loop to an SLC loop
• Fully supervised
• Compatible with Class B and
Class A loops
• Listed for use with all major two-
wire detectors
• UL Listed
Specifications
Operating Voltage:
SLC: 32 VDC
Aux Power: 24 VDC
Aux Power Current:
Standby: 20 mA
Alarm: 106 mA
SLC Current:
Standby/Alarm: .55 mA
Max. SLC Loop
Resistance: 50W Model SD500-SDM
Max. 2-Wire Conventional
Smoke Loop Resistance: 50W
Dimensions:
Height: 4-7/8” (12.38 cm)
Width: 4-7/8” (12.38 cm)
Depth: 7/8” (2.22 cm)
Operating Temperature: 32ºF to 120ºF
(0ºC to 49ºC)
Humidity: 10 to 85% RH
Indoor Use Only
INTELLIKNIGHT ACCESSORY
Model SD500-SDM
Two-Wire Smoke Module
Engineering Specifications
The contractor shall furnish and install where indicated on the plans, two-wire smoke
modules, Silent Knight SD500-SDM. The modules shall be UL listed compatible with Silent
Knight's Intelliknight 5820XL fire panel.
Dimensions