MASS FLOW 1179bman PDF
MASS FLOW 1179bman PDF
MASS FLOW 1179bman PDF
Swagelok® , VCR®, and VCO® are registered trademarks of Swagelok Marketing Company, Solon, OH
Kalrez® and Viton® are registered trademarks of DuPont Dow Elastomers Inc., Wilmington, DE
NUPRO® is a registered trademark of Crawford Fitting Company, Solon, OH
Kel-F® is a registered trademark of 3M, Minneapolis, MN
1179B/1479B/2179B/179B Table of Contents
Table of Contents
iii
Table of Contents 1179B/1479B/2179B/179B
Chapter 4: Installation...................................................................................................................... 29
General Requirements ........................................................................................................ 29
Environmental......................................................................................................... 29
Location and Orientation ........................................................................................ 30
Protection against Dust and Water ........................................................................ 31
Use of a Positive Shutoff Valve, e.g. Type 2179B ................................................. 31
Leak Integrity .......................................................................................................... 31
Pressure Drop Test ................................................................................................ 31
Dimensions.......................................................................................................................... 32
Type 179, 1179 and 1479, Analog and Profibus Units .......................................... 32
Mounting Holes on 179, 1179, 1479 Analog and Profibus Units ........................... 33
Type 2179B, Analog and Profibus Units ................................................................ 34
Mounting Holes ...................................................................................................... 35
Electrical Connections and Cables ..................................................................................... 36
Cables and Controllers by MKS ............................................................................. 36
Power Supply / Readout Units of other Manufacturers.......................................... 36
Non MKS Cables .................................................................................................... 37
Finishing the Installation...................................................................................................... 37
iv
1179B/1479B/2179B/179B Table of Contents
v
Table of Contents 1179B/1479B/2179B/179B
vi
1179B/1479B/2179B/179B Table of Contents
vii
Table of Contents 1179B/1479B/2179B/179B
List of Figures
List of Tables
viii
1179B/1479B/2179B/179B Mass Flow Controller Safety Information
Definitions of WARNING, CAUTION, and NOTE messages used throughout the manual.
9
Mass Flow Controller Safety Information 1179B/1479B/2179B/179B
The following table describes symbols that may be found on the unit.
|
Protective earth
On (Supply) Off (Supply) Earth (ground) (ground)
IEC 417, No.5007 IEC 417, No.5008 IEC 417, No.5017 IEC 417, No.5019
Caution, refer to
accompanying Caution, risk of
documents electric shock Caution, hot surface
ISO 3864, No.B.3.1 ISO 3864, No.B.3.6 IEC 417, No.5041
10
1179B/1479B/2179B/179B Mass Flow Controller Safety Information
The following general safety precautions must be observed during all phases of operation of
this instrument. Failure to comply with these precautions or with specific warnings elsewhere in
this manual violates safety standards of intended use of the instrument and may impair the
protection provided by the equipment. MKS Instruments, Inc. assumes no liability for the
customer’s failure to comply with these requirements.
11
Mass Flow Controller Safety Information 1179B/1479B/2179B/179B
12
1179B/1479B/2179B/179B Chapter 1: General Information
Introduction
The digital mass flow controllers of the 1179B series accurately measure and control the mass flow
rate of gases. The type 179B of this series is a mass flow meter for mass flow measurement only
and is completely metal sealed.
Based upon an patented * MKS measurement technique, these instruments use a laminar flow
device whose precise indication of mass flow is achieved through the use of a laminar bypass
element in parallel with a sensor tube. The 1179, 1479 and 2179 digital controllers use a PID
algorithm which compares the flow signal with an external setpoint command, thus creating a
control signal which is applied to a solenoid driven control valve to set the desired flow rate. The
controllers also feature in the analog mode the ability to accept TTL level commands to remotely
open and close the control valve. The control valve is located at the outlet of the meter section,
also inside the metal instrument housing. The metal cover plus the RF bypass capacitors virtually
eliminate RFI and EMI interference.
The flow signal as derived from the sensor and also an analog setpoint signal are digitalized.
Therefore linearization, flow control and handling of all other signals and commands is operated by
the microcomputer, in both digital and analog versions of the B series. This provides best accuracy
and optimizes the controller’s response and stability.
The 1179,1479 controller and 179 meter have a three-inch footprint. The type 2179 has a positive
shutoff valve, pneumatically driven and close coupled to the controller outlet.
Overview of Versions
*
US Patent No 5461913
13
Chapter 1: General Information 1179B/1479B/2179B/179B
Options
Special versions
There are many variations of the above listed versions and options possible, for example
• with filter mounted at inlet
• with all metal valve plug
• low pressure drop versions for low inlet pressure or small differential pressure applications,
e.g. combination with vaporizers or use with air sampling pumps etc.
• combinations (Gas Sticks) with filters, pneumatic shutoff valves at inlet and/or outlet, purge
fitting, mini-pressure transducers etc.
The control valve of all mass flow controllers is a normally closed (NC) valve.
Profibus Version
The particular features of units with Profibus interface, setup and control are described in
Chapter 6, Operation.
Note: All Profibus versions can also be operated in analog manner, e.g. for diagnosis purposes.
The analog interface and Profibus interface connector are described in Chapter 3 Overview.
The mechanical features and installation are the same as for the analog version.
Non-Compatibility
Profibus versions 179A, 1179A, 1479A and 2179A measure temperature in K, whereas the B-
series described in this manual measure temperature in °C.
14
1179B/1479B/2179B/179B Chapter 1: General Information
Reliability
To help provide excellent reliability, the design contains a low mechanical and electronic
components count and has successfully passed the following tests:
• STRIFE, including temperature cycling, humidity and vibration (sine and random tests)
and with an overall metal braided shielded cable, properly grounded at both ends:
• CE Compliance - The instrument complies to EN 61326-2-3 with the requirements for
industrial applications with continuous not monitored operation. Braided shielded cables
must be used. The PROFIBUS cable must be qualified.
Contents
This manual provides instructions on setup, installation, operation and service of:
• Mass flow controller 1179B / analog version
• Mass flow controller 1179B / Profibus version
• Mass flow controller 1479B / Profibus version only *
• Mass flow controller 2179B / analog version
• Mass flow controller 2179B / Profibus version
• Mass flow meter 179B / analog version
• Mass flow meter 179B / Profibus version
Conventions
If not explicitly expressed differently at the respective place in this handbook all data are
referenced to:
a) Temperature in °C
b) Gas type is nitrogen N2
c) Pressure
in mbar or bar with index (a) relates to absolute pressure and whereas index (g) stands for
gage pressure, related to atmosphere.
Example: 1,7 bar (g) = 1,7 bar overpressure versus atmosphere (gage pressure).
0,5 bar (a) = 500 mbar absolute pressure.
d) Flow rates
are given in sccm ** or slm *** related to nitrogen or dry air.
*
for analog version order type 1479A
**
1 sccm = 1 standard cm3 / min ; Standard conditions: 1013,25 mbar and 0 °C
***
1 slm = 1 standard liter / min = 1000 sccm
15
Chapter 1: General Information 1179B/1479B/2179B/179B
16
1179B/1479B/2179B/179B Chapter 2: Shipment
Chapter 2: Shipment
General
Unpacking
MKS has carefully packed each unit so that it will reach you in perfect operating order. Upon
receiving the unit, however, you should check for defects, cracks, broken connectors, damaged
cables etc., to be certain that damage has not occurred during shipment.
Note Do not discard any packing materials until you have completed your
inspection and are sure the unit arrived safely.
If you find any damage, please notify your carrier and MKS immediately. If it is necessary to return
the unit to MKS, obtain an ERA Number (Equipment Return Authorization Number) from the MKS
Service Center before shipping. Please refer to the inside of the back cover of this manual for a list
of MKS Calibration and Service Centers.
Unpacking Checklist
Analog Units
Mass flow controller 1179B (type 1479B, 2179B or mass flow monitor 179B respectively)
Accessory kit ZB-30 consisting of
• Mating connector D-type; 15 pin female
• 2 mounting screws #8-32 UNF (MKS part no. 160-3973)
Manual (this book)
Calibration sheet
17
Chapter 2: Shipment 1179B/1479B/2179B/179B
Profibus Units
Mass flow controller 1179B ( type 1479B, 2179B or mass flow monitor 179B respectively)
Accessory kit ZB-27 consisting of
• Mating connector D-type; 9 pin female
• Mating connector D-type; 9 pin male
• 2 mounting screws #8-32 UNF (MKS part no. 160-3973)
GSD file (3,5” disc)
Manual (this book)
Calibration sheet
Note: The mounting screws are not needed for units with mounting plates.
Optional Accessories:
Control units, power supplies, readout units
Cable
Water&Dust protection cap type WPC 63 for use in humid or dusty environments
Profibus Support Kit for units with Profibus only
Ordering Code. 1179-PB-SUPPORT
Consisting of:
1 Disc 3,5“
1 RS 232 cable
1 converter RS232/RS485
1 instructions
etc.
18
1179B/1479B/2179B/179B Chapter 2: Shipment
Label
The label shows the following information: See figure 1 as an example:
Across the housing and the meter/controller body there is an extra label to avoid access to the
inside by unauthorized people. Broken or removed label means lost of any warranty.
19
Chapter 2: Shipment 1179B/1479B/2179B/179B
20
1179B/1479B/2179B/179B Chapter 3: Connectors and Control Elements
Analog Units
Status LED
(STS)
Zero
Reset
21
Chapter 3: Connectors and Control Elements 1179B/1479B/2179B/179B
ZERO
RESET
Potentiometer ZERO
Use this 25 turn potentiometer to adjust the signal output to zero.
Refer to Chapter 5, Operation (Analog Units), section Zero Adjust.
RESET Switch
After pressing the RESET key the unit performs a self check cycle and a reset. The same
procedure is done after power on. During the cycle the two colour LED, labeled STS, changes its
colour a few times between red and green.
Finally the LED changes to green, indicating that self test cycle and reset have been completed
successfully.
22
1179B/1479B/2179B/179B Chapter 3: Connectors and Control Elements
Electrical Connector
1 Reserved Reserved
2 Flow Signal Flow Signal Referenced to pin 11 and
(0 to +5 V) (0 to +5 V) 12
3 Valve Close1 Valve Close1 Connect to pin 5 to
1 1 activate
4 Valve Open Valve Open
5 ± 15 V Supply Common Signal Common
6 - 15 V Supply + 24 V Supply Common
7 + 15 V Supply +24 V
8 Setpoint Input1 Setpoint Input1 Referenced to pin 11 and
(0 to +5 V) (0 to +5 V) 12
9 NC NC
10 NC NC
11 Signal Common Signal Common
12 Signal Common Signal Common
13 NC NC
14 NC NC
15 Chassis Ground Chassis Ground Shield, Case
For use with control units from MKS Instruments (PR 4000, 647 etc.) we recommend to use the
standard cables of the manufacturer.
____________________
1
Not applicable with mass flow meter 179B
23
Chapter 3: Connectors and Control Elements 1179B/1479B/2179B/179B
Profibus Units
Reset
24
1179B/1479B/2179B/179B Chapter 3: Connectors and Control Elements
Address
Switches
RESET
RESET Switch
After pressing the RESET key the unit performs a self check cycle and a reset. The same
procedure is done after power on. During the cycle the two colour LED, labeled STS, changes its
colour a few times between red and green.
Finally the LED changes to green, indicating that self test cycle and reset have been completed
successfully.
25
Chapter 3: Connectors and Control Elements 1179B/1479B/2179B/179B
Electrical Connectors
For the use of the Profibus version in analog mode is a +/- 15 VDC power supply required. For the
use in digital mode a +/- 15 VDC or a 24 VDC power supply is sufficient.
This connector does not provide a particular pin for connection to the case. Connect the cable
shield to the connector housing for grounding.
_______________
1
To close the valve connect pin 1 to pin 5 (-15 V);
To open the valve apply + 5 V to pin 1 (referenced to pin 7 or 8).
2
Not applicable with mass flow meter 179B
3
To close the valve connect pin 1 to pin 4;
To open the valve apply + 5 V to pin 1 (referenced to pin 7 or 8).
26
1179B/1479B/2179B/179B Chapter 3: Connectors and Control Elements
1 NC
2 NC
3 RXD / TXD – P Bus positive
4 CNTR – P Control for Repeater, positive
5 DGND Digital Ground
6 VP Power Supply ( 5V )
7 NC
8 RXD / TXP – N Bus negative
9 NC
27
Chapter 3: Connectors and Control Elements 1179B/1479B/2179B/179B
28
1179B/1479B/2179B/179B Chapter 4: Installation
Chapter 4: Installation
General Requirements
Environmental
Follow the guidelines below when installing and using your mass flow controller.
1. Maintain the normal operating temperature between 0° - 50°C (32° and 122°F).
4. Allow minimum 15 minutes for warm-up time for analog units as well as for units with
Profibus.
6. The use of a filter upstream of the mass flow controller is recommended, if enough
pressure is available.
Refer also to Appendix A, Product Specifications for other possible precautions and restrictions.
1
For the use of the Profibus version in analog mode is a +/- 15 VDC power supply required. For
the use in digital mode a +/- 15 VDC or a 24 VDC power supply is sufficient.
29
Chapter 4: Installation 1179B/1479B/2179B/179B
1. Set the controller into position where it will be connected to a gas supply.
Placement of flow components in an orientation other than that in which they were
calibrated (typically horizontal) may cause a small zero shift. The zero offset can be
removed according to the instructions in Chapter 5, Zero Adjust if an analog unit is used or
in Chapter 6, Zeroing the Flow Controller if a Profibus unit is used.
2. Install the flow controller in the gas stream such that the flow will be in the direction of the
arrow on the side of the controller.
Take into consideration the specified leak through the closed control valve in case of a
mass flow controller. The specified value refers to new and unused units but may change
during operation by age, cycles, temperature and gas. To achieve best possible leak
tightness we strongly recommend the use of positive shut off valves. An optimum solution
is the type 2179, which employs a pneumatically driven shut off valve, close coupled to the
flow controller’s outlet to minimize dead volume.
3. The normal position is horizontal, the electrical connector pointing upwards or vertical with
flow direction either upwards or downwards.
It is possible to mount the units the way that the connector points downwards but control
performance and valve leak can be affected. This applies especially to units with higher
flow ranges. Therefore the ‘ceiling mount attitude’ should be avoided.
4. Allow adequate clearance for the tubing. Take into account when designing the plumbing
that a unit may be removed later, e.g. for service or maintenance.
To de-install units with metal ferrule compression fittings (for example Swagelok) the tubing
must be moved away some millimeters in axial direction whereas VCR fittings allow the
instrument to be removed sidewards also out from complexive and stiff plumbing systems.
5. Allow adequate clearance for the cable connector (two cable connectors in case of Profibus
version).
Straight, shielded connectors need about 75 mm clearance.
Right-angle connectors require about 50 mm space.
6. Position the unit to provide access to the zero potentiometer, in case of Profibus units
access to the dip switch bank and the RESET button:
Potentiometer or DIP-Switch / Button are located at the inlet side of the housing.
Make sure that the status LED is visible when installing units with Profibus.
30
1179B/1479B/2179B/179B Chapter 4: Installation
Leak Integrity
We recommend to check tightness of all ports and connections of the plumbing with a helium leak
detector.
31
Chapter 4: Installation 1179B/1479B/2179B/179B
Dimensions
139,5
12,7
76,2
Fittings (compatible) L
4 VCR 123,9
4 VCO 115,8
8 VCR 133,7
¼“ Swagelok* 112,7
6 mm Swagelok* 112,7
DN 16 KF 124,5
*) without nuts and ferrules
32
1179B/1479B/2179B/179B Chapter 4: Installation
ZERO
RESET
36.8
19,1
69,8 8,8
3,2
33
Chapter 4: Installation 1179B/1479B/2179B/179B
139,5
85,9
15,8
3,1
34
1179B/1479B/2179B/179B Chapter 4: Installation
160,7
141,7
4,7
28,5
4x∅6
L
Fittings (compatible) L
4 VCR 170,4
4 VCO 162,3
¼“ Swagelok* 159,2
6 mm Swagelok* 159,2
*) without nuts and ferrules
Mounting Holes
160,7
9,7 141,7
28,5 38,1
4x∅6
35
Chapter 4: Installation 1179B/1479B/2179B/179B
The units comply with the European standards and thus they are labelled with the CE-mark. To
fulfill the above listed guidelines it is mandatory to use the appropriate interconnection cables.
36
1179B/1479B/2179B/179B Chapter 4: Installation
Requirements
Should you choose to manufacture your own cables, follow the guidelines listed below:
1. The cable must have a braided shield, covering all wires. Neither aluminium foil nor
spiral shielding will be as effective: using either may nullify regulatory compliance.
2. The connectors must have a metal case which has direct contact to the cable’s shield on
the whole circumference of the cable.
3. With very few exceptions, the connector(s) must make good contact (typical 0,01Ω or less)
to the device’s case (ground). The case also must be properly grounded.
4. When selecting the cable, consider:
a) The voltage ratings.
b) The cumulative I2R heating of all the conductors (keep them safely cool).
c) The IR drop of the conductors, so that adequate power or signal voltage gets to the
device.
d) The capacitance and inductance of cables which are handling fast signals
e) If there are specific requirements when supply units etc of other manufacturers are
used
37
Chapter 4: Installation 1179B/1479B/2179B/179B
38
1179B/1479B/2179B/179B Chapter 5: Operation (Analog Units)
1. After you have successfully checked all mechanical and electrical connections and when
you are certain that there is no gas leakage, then power can be applied to the mass flow
controller or to the flow meter respectively.
The first start up should be done preferably using non-critical gas. This could be for
example nitrogen or dry air (if there are no reactive residuals in the plumbing system) or
any inert gas.
Note Do not use dangerous gases for the first start up. Use a non-critical gas,
for example the gas which serves for purging.
Note If the instrument is being used to control dangerous gases, be sure that
the system is fully warmed up before applying gases to the system. You
may choose to install a positive shutoff valve to prevent inadvertent gas
flow during the warm-up period.
Once the instrument is completely warmed up, you can proceed to zero the unit as
required.
39
Chapter 5: Operation (Analog Units) 1179B/1479B/2179B/179B
Zero Adjust
1. If no gas is flowing and the mass flow controller has stabilized (ref. to Appendix A,
Specifications, Warm Up) the flow output signal should be zeroed by means of the
potentiometer ZERO which is located at the gas inlet side of the unit.
Note Zeroing should be done only on units that are installed in final position.
2. When using a control unit by MKS then you should use the zeroing means there. If the
control unit does not provide enough compensation range then the potentiometer ZERO at
the mass flow unit must be used.
Note If a pressure difference exists at the mass flow control unit then a small
flow might be generated even if the integrated control valve is closed.
This is more likely with special units for low inlet pressures .
Do not adjust the flow signal then to zero value because it is a real flow
but use a positive shutoff valve to definitely stop the flow. Finally with
flow completely stopped you should adjust the flow signal to zero.
3. Periodically check the zero adjustment of the unit, e.g. on maintenance intervals. The zero
adjustment is affected by thermal effects and especially by contamination.
Beside of the need for measurements of highest accuracy the zero signal is very important
for diagnosing the flow sensor and the control valve.
40
1179B/1479B/2179B/179B Chapter 5: Operation (Analog Units)
The valve override feature enables the control valve to be fully opened (purged) or closed
independent of the set point command signal:
To open the valve, apply a TTL low to pin 4 or connect pin 4 to pin 5 (analog ground).
To close the valve, apply a TTL low to pin 3 or connect pin 3 to pin 5 (analog ground).
Priority of Commands
The 1179 flow controller executes commands based on a hierarchical command structure. The
highest priority command is Valve Open, followed by Valve Close, and finally the Set Point Control.
Therefore, if the flow controller is operating under Set Point Control, you can send a Valve Open
command to force the valve to the full open position.
Note When both the Valve Close and Valve Open pins are pulled down, the
Valve Open command takes precedence and the valve is moved to the
open position.
41
Chapter 5: Operation (Analog Units) 1179B/1479B/2179B/179B
42
1179B/1479B/2179B/179B Chapter 6: Operation (Profibus Unit)
Functions
Beside the normal flow control mode the units equipped with Profibus provide a number of helpful
functions and useful information.
Overview
• Valve Override
• Auto Zero
• Totalizer, gas counter
• Gas Correction
• 15 Calibration Tables, 15 points each
• 4 Limit Alarms
• Run Hours Counter
• Remaining Time to Calibration Observation (Calibration Cycle Count Down)
• Temperature Measurement
• Valve Drive Level
• Status LED
• Signal Filter (flow signal)
• User Span setting
• User Zero setting
• User Tag
Report Functions:
Calibration Date, Type, Model, Manufacturer, Serial No., Firmware/Hardware Revision, Product
Code, Date of Factory Calibration, Full Scale Range, Engineering Unit, Standard Temperature
Standard Pressure, Valve Type, Valve Power Off Mode.
43
Chapter 6: Operation (Profibus Unit) 1179B/1479B/2179B/179B
Valve Override
By means of an analog override signal applied to the respective pins at the connector ANALOG the
control valve can be driven completely open or closed, independent of the setpoint command
signal ( only in analog mode ). Refer to figure 9 and its explanations for the detailed description.
In Profibus mode the override however is only possible via the bus:
Set the parameter VALVE_OVERRIDE to NORMAL to allow the mass flow controller
establishing a flow in accordance to the setpoint command FLOW_SETPOINT.
Set the parameter VALVE_OVERRIDE to FLOW_OFF to completely close the control valve.
Set the parameter VALVE_OVERRIDE to PURGE to completely open the control valve. This
command may be used to purge or vent the instrument or the system.
Auto Zero
If VALVE_OVERRIDE is equal to FLOW_OFF and THERMAL_MASS_FLOW_RATE is smaller
than 5 % of full scale, the flag AUTOZERO (0 to 1 transition) will take the actual sensor signal as
zero and will subtract this value from all future measurements (refer also to USER_ZERO).
Alarm Limits
LOW_TRIP_POINT and HIGH_TRIP_POINT define the limits for LOW_LIMIT_ALARM and
HIGH_LIMIT_ALARM flags. Consider that there is a 0.5% hysteresis for each limit switch. The
hysteresis of 0.5% is divided in a slope 2.5% above and an other slope 2.5% below the defined
limit.
Temperature Measurement
The internal temperature of the device is measured in °C and given as INTERNAL_TEMP.
44
1179B/1479B/2179B/179B Chapter 6: Operation (Profibus Unit)
User Zero
The parameter USER_ZERO may be set to the flow sensors offset. (See also AUTO ZERO)
Filter
The filter is a single-pole low pass filter. The parameter that the user can adjust is the settling time
of the filter (FILTER_SETTLING). E.g. if a step input (magnitude 100) is applied to the filter with a
settling time of 100 second, the response out of the filter will be within 2% of the final value (98%)
in 100 second. The default value is 0 seconds (no filtering).
Gas Tables
Gas tables may be switched off by setting the default table to 15 (i.e. no table is used) and by
selecting the default table. Or by programming a 0 for POINT_NUM (ref. to Calibration Table at
the end of this chapter; function (y=x)) and selecting it. Or by selecting a table with no (zero) points.
A backup of the Gas Tables is generated on Factory Setup. This backup is used for reset the
tables.
45
Chapter 6: Operation (Profibus Unit) 1179B/1479B/2179B/179B
1. After you have successfully checked all mechanical and electrical connections and when
you are certain that there is no gas leakage, then power can be applied to the mass flow
controller or to the flow meter respectively.
The first start up should be done preferably using non-critical gas. This could be for
example nitrogen or dry air (if there are no reactive residuals in the plumbing system) or
any inert gas.
Note Do not use dangerous gases for the first start up. Use a non-critical gas,
for example the gas which serves for purging.
Note If the instrument is being used to control dangerous gases, be sure that
the system is fully warmed up before applying gases to the system. You
may choose to install a positive shutoff valve to prevent inadvertent gas
flow during the warm-up period.
Once the instrument is completely warmed up, you can proceed to zero the unit as
required.
46
1179B/1479B/2179B/179B Chapter 6: Operation (Profibus Unit)
Zero Offset
The Profibus version provides different modes for zero setting. If the mode switch A/B on the inlet
side of the unit is set to mode B then parameter USER_ZERO in the PROFIBUS Setup is used. If
set to mode A then 5 different options are provided, depending on the configuration of the address
switches. Refer to Zero Modes in this chapter.
1. If no gas is flowing and the mass flow controller has stabilized (ref. to Appendix A,
Specifications, Warm Up) the flow output signal should be zeroed by means of the
respective command.
Note Zeroing should be done only on units that are installed in their final
position.
2. The command for zero setting also sets the analog flow output signal to zero (pin 2 on the
connector ANALOG).
Note If a pressure difference exists at the mass flow control unit then a small
flow might be generated even if the integrated control valve is closed.
This is more likely with special units for low inlet pressures .
Do not adjust the flow signal then to zero value because it is a real flow
but use a positive shutoff valve to definitely stop the flow. Finally with
flow completely stopped you should adjust the flow signal to zero.
3. Periodically check the zero adjustment of the unit, e.g. on maintenance intervals. The zero
adjustment is affected by thermal effects and especially by contamination.
Beside of the need for measurements of highest accuracy the zero signal is very important
for diagnosing the flow sensor and the control valve.
47
Chapter 6: Operation (Profibus Unit) 1179B/1479B/2179B/179B
A two-colour LED, marked STS, between the D-connectors, reports basic status information of the
device. It is also used for setup and display of the PROFIBUS address.
This switch map serves for manually switching from analog mode to Profibus mode and there to
select the device’s address. In analog mode a mass flow controller needs an analog setpoint
signal!
If you are not familiar with the binary code refer to Appendix D how to convert decimal numbers.
Note: After changing any settings the unit must be restarted to store the new configuration.
Switch Assignment
Mode B
If the mode switch sets B mode, the device operates as PROFIBUS device. In that case the
address switches define the device PROFIBUS address. If the address switches are all down (127)
the internal programmed (via PROFIBUS) address is used. All other address switch settings define
the PROFIBUS address by hardware.
48
1179B/1479B/2179B/179B Chapter 6: Operation (Profibus Unit)
Setting an Address
Example for address 5 in Profibus mode:
ADDRESS B
0 1 2 3 4 5 6 A
Switch position =
Mode A
If the mode switch sets A mode, the device operates as an analog device. PROFIBUS may be
used for monitoring and the bus address will be used, which was set previously in bus mode. The
address switches in analog mode define the analog zeroing mode.
Example for setting analog mode and zero mode 3:
ADDRESS B
0 1 2 3 4 5 6 A
Switch position =
Zero Modes
49
Chapter 6: Operation (Profibus Unit) 1179B/1479B/2179B/179B
PROFIBUS Protocol
On diagnose data, the PROFIBUS protocol provides 6 bytes of PROFIBUS specific diagnosis
information, which comes ahead of the application specific diagnosis data. After this data there is a
length byte for the application specific diagnosis data. The total memory requirements are 6 + 1 +
‘length of the diagnosis data’.
If the communication of the bus is interrupted a set point from the bus will be set to zero, as soon
as the controller has recognized it. In the analog mode, the controller will not react to this event. Of
course in any case, all readings from the device are not longer valid, but the PROFIBUS master
will mark the device as not available.
Data Interface
The 1179 with PROFIBUS have a small data interface with a basic function set and a full data
interface with the full function set of the device. The selection between small and full functionality is
made at setup time with the type of configuration data, which is loaded down, to the device.
• Small / Full Parameter selects the internal function set and is declared by the GSD file
parameters:
• Small / Full Receive Data, is selected by the MODULE definition in the GSD file. E.g.:
The data interfaces are documented as data structures with consecutive fields. There is a table
entry for each field, with name, address (add), type information and a comment for explanation.
The address field (Add.) defines the byte and bit address (ByteOffset:BitOffset). For the memory
layout the Motorola Format is used. The following types are used:
50
1179B/1479B/2179B/179B Chapter 6: Operation (Profibus Unit)
Send Data
Name: SET_MFC
Type: Cyclic Write (small & full)
Size: 6
Description: Analog Output Transducer Block, Small & Full Setup
Parameters:
If the device is in the analog mode (i.e. set point is taken from the analog interface) some functions
are not active:
1. VALVE_OVERRIDE is not active
2. EN_GAS_CORRECTION is not active
3. SELECT_GAS_TABLE is not active and the default table will be used
51
Chapter 6: Operation (Profibus Unit) 1179B/1479B/2179B/179B
Parameters:
52
1179B/1479B/2179B/179B Chapter 6: Operation (Profibus Unit)
Parameters:
53
Chapter 6: Operation (Profibus Unit) 1179B/1479B/2179B/179B
Small Setup
Name: SMALL_SETUP
Type: Initial Write (small)
Size: 19
Parameters:
54
1179B/1479B/2179B/179B Chapter 6: Operation (Profibus Unit)
Full Setup
Name: FULL_SETUP
Type: Initial Write (full)
Size: 80
Parameters:
55
Chapter 6: Operation (Profibus Unit) 1179B/1479B/2179B/179B
56
1179B/1479B/2179B/179B Chapter 6: Operation (Profibus Unit)
Small Diagnostics
Name: SMALL_DIAG
Type: Diagnose (small)
Size: 22
Parameters:
57
Chapter 6: Operation (Profibus Unit) 1179B/1479B/2179B/179B
Full Diagnostics
Name: FULL_DIAG
Type: Diagnose (full)
Size: 217
Parameters:
58
1179B/1479B/2179B/179B Chapter 6: Operation (Profibus Unit)
59
Chapter 6: Operation (Profibus Unit) 1179B/1479B/2179B/179B
Calibration Table
Name: CAL_TABLE
Type: Initial Write, Diagnosis (full)
Size: 140
Parameters:
If a table is loaded, which is not strict monotonous, the table will be disabled (POINT_NUM = 0). If
a table, with a not valid index, is loaded, no tables will be affected. In both case the error flag for
the table will be set.
The calibration tables convert the measured value (SENSOR_VALS) to the true physical value
(FLOW_VALS). If the actual measured value is between two SENSOR_VALS, the flow will be
calculated by linear interpolation. If the measured value is outside of the table definitions, the first
(last) straight line will be continued.
The GAS_CODE may be any definition for gases. It is not evaluated. The GAS_NAME may be any
16 character string. It is also not evaluated.
The calibration tables stored from the factory may be recalled by an GAS_CODE of 255. In this
case the TABLE_FLAG in the full diagnostic is reset.
60
1179B/1479B/2179B/179B Chapter 6: Operation (Profibus Unit)
PROFIBUS Setup
Note:
At the time of release of this instruction manual the standard GSD file was mks 1179.gsd
(June 2002)
61
Chapter 6: Operation (Profibus Unit) 1179B/1479B/2179B/179B
62
1179B/1479B/2179B/179B Chapter 7: Theory of Operation
The design of the 1179B flow controller incorporates an advanced flow sensor, a new control valve
and an optimized bypass. The latest generation two-element sensing circuit provides accurate,
repeatable performance even in low flow ranges (< 10 sccm). Low temperature effect from ambient
temperature change and a low attitude sensitivity effect are also ensured. The newly optimized
sensor/bypass arrangement minimizes the flow splitting error for gases with different densities,
which dramatically improves measurement accuracy when gases other than the calibration gas are
used.
The surface mount digital, processor controlled electronic circuitry allows optimum adjustment of
the sensing and signal conditioning circuitry and provides tuned flow control for fast response to
any set point in common with excellent stability.
Electronic Board
Valve Housing
with Solenoid
Sensor
Seal Cones
O-Ring
The flow controller type 1179B measures and controls the gas flow rate accordingly to a given
setpoint signal, which may be an analog signal or a digital command when using the Profibus
version. The control range is from 2 % to 100% of full scale. The accuracy of the flow
measurement is ± (0,5 % of reading + 0,2 % of F.S.) for both the analog units and Profibus
versions.
63
Chapter 7: Theory of Operation 1179B/1479B/2179B/179B
Flow Path
Upon entering the flow controller, the gas stream passes first through the metering section of the
instrument for its mass flow to be measured. The gas moves on through the control valve for its
rate of flow to be regulated according to the given set point, and then exits the instrument at the
established rate of flow.
The metering section consists of one of the following:
The geometry of the sensor tube, in conjunction with the specified full scale flow rate, ensures fully
developed laminar flow in the sensing region. The bypass elements, in those instruments
containing them, are specifically matched to the characteristics of the sensor tube to achieve a
laminar flow splitting ratio which remains constant throughout each range.
Measurement Technique
The flow measurement is based on differential heat transfer between temperature sensing heater
elements which are attached symmetrically to the sensor tube. This senses the thermal mass
movement which is converted to mass flow via the specific heat, Cp, of the gas. The resulting
signal is then amplified, digitalized and linearized. The corrected digital signal is then transferred to
the control section (controllers only) and also converted into a 0 – 5 V analog signal.
Analog versions of the units described herein provide just the analog flow signal, Profibus versions
provide both the digital information and the analog signal.
The measurement principle of keeping temperatures constant results in much shorter response
time than conventional principles.
Control Circuitry
In the digital control section the flow rate is compared to the setpoint value and a control signal
(digital) is generated.
The digital control signal is then conditioned by a PID-algorithm, optimized for fastest controlling
and finally fed into the control circuitry which steers the solenoid control valve. The digital control
reduces overshoots to a minimum and for completely regulating the flow until the difference from
the setpoint is zero. Typical settle time is 0,8 s, for faster tuning contact MKS.
The control valve is closed when no power is applied (Normally Closed, N.O.). Controlling flow is
done by levitating the valve plug from the valve orifice. The plug is mounted at the front end of the
solenoid armature.
64
1179B/1479B/2179B/179B Chapter 7: Theory of Operation
Control Valve
The control valve is a specially designed solenoid driven valve. The armature is suspended by two
radial springs. This design provides frictionless movement and thus precise control. Mounted at the
front end of the cylindrical armature is the valve plug which incorporates the seal disc of Viton or
Kel-F or Teflon (ref. to Appendix A, Specifications). By preload force of the two above mentioned
springs the seal disc is pressed against the valve orifice, closing it’s flow channel. Therefore the
valve is closed when not activated. It is a „Normally Closed“ (N.C.) valve.
The inside diameter of the orifice determines the conductance. Each flow controller incorporates a
valve orifice with a conductance in accordance to the full scale range. The valve orifice in standard
units is sized that with a pressure difference between inlet and outlet fitting of typical 0,7 bar to 2,75
bar the specified full scale flow rate will be achieved. (related to air or nitrogen). For more
information refer to Appendix A, Specifications.
For special applications with low pressure conditions, e.g. vaporizer sources, configurations can be
provided. In this case the valve will have an orifice with higher conductance (=larger diameter of
the flow channel). Mass flow controllers for applications where only 200 mbar (or less) are
available have been realized.
At high line pressures in combination with high flow rates it may be necessary to have an orifice
with smaller conductance installed.
The mass flow monitor 179B has no valve!
65
Chapter 7: Theory of Operation 1179B/1479B/2179B/179B
66
1179B/1479B/2179B/179B Chapter 8: Gas Correction Factor (GCF)
A Gas Correction Factor (GCF) is used to indicate the ratio of flow rates of different gases which
will produce the same output signal from a mass flow meter / controller. The GCF is a function of
specific heat, density, and the molecular structure of the gases. Nitrogen (N2) is normally used as
the baseline gas (GCF = 1) since flow meters and controllers are usually calibrated with nitrogen.
GCF (N2) = 1
Appendix C lists the gas correction factors for many commonly used pure gases. If the gas you
are using is not listed in there, you must calculate its GCF. The equations for calculating gas
correction factors are described below.
0,3106 ∗ s
GCFx =
ρ x ∗ cpx
where:
67
Chapter 8: Gas Correction Factor (GCF) 1179B/1479B/2179B/179B
where:
Note 1. When using the GCF, the accuracy of the flow reading may vary by
± 5%, however, the repeatability will remain ± 0,2% of FS.
2. The linearity and accuracy may be improved by calibrating the unit
with the process gas or using a gas with equivalent properties
(surrogate gas). Contact MKS for more information.
3. All MKS readouts have gas correction adjustment controls to
provide direct readout.
68
1179B/1479B/2179B/179B Chapter 8: Gas Correction Factor (GCF)
Example
Calculate the GCF for a gas mixture of argon (gas 1) flowing at 150 sccm and nitrogen (gas 2)
flowing at 50 sccm, where:
s1 = 1.030 s2 = 1.000
(0 .3 1 0 6 ) [(0 .7 7 2 5 ) + (0 .2 5 )]
=
(0 .1 6 6 3 ) + (0 .0 7 7 7 )
(0 .3 1 0 6 ) (1 .0 2 2 5 )
=
0 .2 4 4
0 .3 1 7 6
=
0 .2 4 4
GCFM = 1 .3 0 2
Tx
GCFX = GCF x
TN
where:
Tx = actual reference temperature in Kelvin K
69
Chapter 8: Gas Correction Factor (GCF) 1179B/1479B/2179B/179B
If a direct reading of output is desirable, and the readout equipment has no GCF potentiometer, a
proper input divider may be constructed.
Example: Using a mass flow controller, full scale range 500 sccm N2, full scale signal is 5 VDC
and a process gas CCl4 . A flow rate of 100 sccm CCl4 shall be converted into 1 VDC.
As the gas correction factor of CCl4 is 0,31 the flow signal must be divided 3.22 to 1.00
volts.
Note All MKS readouts have gas correction adjustment controls to provide
direct readout. The analog setpoint output signal is generated
accordingly.
70
1179B/1479B/2179B/179B Chapter 9: MFC Sizing Guidelines
General
To select the correct MFC for an application, you must determine the:
The flow controller range depends on the desired flow rate and the gas correction factor for the gas
to be used. MKS states the flow controller ranges based on flow rate of nitrogen; the flow rate for
other gases may vary.
The proper valve configuration depends upon the flow range, inlet pressure, differential pressure
across the unit, and density of the gas. Proper valve configurations have been established for all
standard flow ranges flowing nitrogen under standard operating pressures. These configurations
are suitable for virtually all gases and pressure conditions.
71
Chapter 9: MFC Sizing Guidelines 1179B/1479B/2179B/179B
The Type 1179 controller is available in ranges of 10, 20, 50, 100, 200, 500, 1000, 2000, 5000,
10000 and 20000 sccm (N2 equivalent). To select the appropriate range, you must determine the
flow rate of nitrogen that is equivalent to the flow rate of the desired gas. Calculate the ratio of the
GCF of nitrogen (1.00) to the GCF of the desired gas (refer to Appendix C as shown in the
following example.
Example:
You need a flow rate of 250 sccm of argon (Ar). What range flow controller should you use?
(1.00) =
(x )
(1.39) (250 sccm Ar )
A flow rate of 250 sccm of argon will produce a flow rate equivalent to 180 sccm of N 2. This falls
within the range of a 200 sccm flow controller.
When calculating equivalent N2 flows using gas correction factors, be sure to use a flow controller
with a sufficient flow rate range. For example, if the calculated equivalent N2 flow in the example
shown above is 205 sccm, use a 500 sccm flow controller. The 500 sccm instrument can then be
calibrated such that 205 sccm N2 = full scale.
Note When using a gas with a density higher than nitrogen, be sure that the
control valve full scale range can accommodate the desired flow rate.
Please call the MKS Applications group if you have any questions.
72
1179B/1479B/2179B/179B Chapter 10: Maintenance
General
After proper installation and correct setup there is typically only the need for occasionally checking
and - if necessary - readjusting the zero flow signal. In general no further maintenance is required.
How often the calibration and the valve should be checked depends on physical influences, e.g.
temperature, vibrations, dust etc., is also related to the required accuracy and last not least on how
the process gas affects the wetted parts inside the unit.
If a controller fails to operate properly upon receipt, check for shipping damage, and check the
power/signal cable for correct continuity. Any damage should be reported to the carrier and MKS
Instruments immediately.
Zero Adjustment
To achieve optimum accuracy and reliability you should periodically check the zero readout and - if
necessary - readjusting it. For adjusting zero refer to the instructions in Chapter 5; Chapter 6,
Operation of Analog/Profibus Units. How often the zero readout should be checked and corrected
depends on the required accuracy and reproducibility the process is asking for.
73
Chapter 10: Maintenance 1179B/1479B/2179B/179B
Customer Support
Standard maintenance and repair services are available at all of our regional MKS Calibration and
Service Centers, listed at the end of this manual. In addition, MKS accepts the instruments of other
manufacturers for recalibration using the Primary and Transfer Standard calibration equipment
located at all of our regional service centers. Should any difficulties arise in the use of your type
1179 instrument, or to obtain information about companion products MKS offers, contact any
authorized MKS Calibration and Service Center. If it is necessary to return the instrument to MKS,
the MKS Calibration and Service Center will inform you about any formal requirements.
You will find a list of MKS Calibration and Service Centers and a form for Declaration of
Contamination at the end of this handbook.
74
1179B/1479B/2179B/179B Chapter 10: Maintenance
Troubleshooting
75
Chapter 10: Maintenance 1179B/1479B/2179B/179B
Table 3: Troubleshooting
76
1179B/1479B/2179B/179B Chapter 11: Type 179B, 1179B, 1479B, 2179B (Comparison)
Type 179B
The type 179B is the standard mass flow meter and provides the base for the mass flow controllers
type 1179, 1479 and 2179. The imprint on the aluminium housing is MASS-FLO METER. The flow
path is completely metal sealed. Therefore the meter is inherently an all metal sealed unit.
Type 1179B
The Type 1179B is the standard version of the MKS Mass-Flo® Controller series. Compared to the
flow monitor type 179B it employs an integrated control valve, solenoid driven, and a digital control
electronics. There is just one O-ring seal in the valve body, all other process gas wetted surfaces
are metal sealed or even welded.
The control valve is normally closed, e.g. when no power or a zero setpoint signal is applied. The
sealing material of the valve plug is typically Viton, Kel-F or Teflon which provides a closed
conductance which is sufficiently small for many application. Nevertheless it must be pointed out
that for reliable and completely closing a positive shut off valve is strongly recommended.
Type 1479B
The Type 1479B is the completely metal sealed type 1179B, meaning that also the one O-ring seal
is replaced by a metal C-seal. The valve plug seal disc is Kel-F or Teflon, depending of the range.
Type 2179B
The Type 2179B consists of a mass flow controller 1179B with a positive shut off valve closely
welded to the outlet. This is the recommended configuration for closing flow at minimum leak rate
with minimized dead volume between shutoff valve and control valve. The welded connection
prevents an additional connection by fittings with potential leak.
The shutoff valve is an all metal sealed diaphragm valve (material: 316L VAR SST and Elgiloy)
with a PCTFE valve seat.
The complete stick is mounted on a common base plate.
77
Chapter 11: Type 179B, 1179B, 1479B, 2179B (Comparison) 1179B/1479B/2179B/179B
Note Throughout this handbook all three types of mass flow controllers,
namely 1179B, 1479B and 2179B will be expressed by type 1179B in
common. The types 1479B and 2179B will only be mentioned by their
specific name where it is necessary to avoid confusion.
78
1179B/1479B/2179B/179B Appendix A: Product Specifications
Specifications
Accuracy1
Analog and Profibus version: 0,5 % of reading plus 0,2 % of full scale
Control Range (MFC only) 2,0 % to 100% of full scale
2
Controller Settling Time typically < 0,8 seconds (to within 2 % of set
point);
faster settling time on request
3
Full Scale Ranges (nitrogen equivalent) 10, 20, 50, 100, 200, 500, 1000, 2000, 5000,
10.000, 20.000 sccm
Maximum Inlet Pressure 150 psig
4
Operational Differential Pressure (MFC only)
≤ 5000 sccm 0,7 bar (g) to 2,8 bar (g)
10.000 to 20.000 sccm 1 bar (g) to 2,8 bar (g)
Pressure Coefficient 0.02 % of reading/psi
Repeatability (MFC only) ± 0,2 % of full scale
Resolution (measurement) 0,1 % of full scale
Temperature Coefficients
Zero <0.04 % of full scale /°C (400 ppm)
Span <0,08 % of reading /°C (800 ppm)
Warm Up Time 15 minutes
________________________________
1
Includes non-linearity, hysteresis and non-repeatability.
2
Controller settling time per SEMI E17-91, specified for flows starting from 0 to 10% (or greater) of full scale.
3 3
sccm = std. cm / min ; standard (std.) condition: 1013,25 mbar and 0 °C.
4
Referenced to an MFC outlet pressure at atmosphere.
79
Appendix A: Product Specifications 1179B/1479B/2179B/179B
Environmental Specifications
Electrical Specifications
Connectors
Analog Version: Sub D 15-poles, pin
Profibus Version: Sub D 9-poles, pin (Analog Interface)
Sub D 9-poles, socket (Profibus Interface)
Input Voltage/Current Required 20,5 to 31,5 VDC 2
Maximum at Start Up (first 5 seconds)5 @ 200 mA
Typical at Steady State @ 100 mA
Output Impedance <1Ω
Output Signal/Minimum Load 0 to + 5 VDC into > 10 kΩ
Set Point Command Signal (not for type 179B) 0 to + 5 VDC from < 20 kΩ
________________________________
5
Add 100 mA to start up current if the valve is energized.
2
For the use of the Profibus version in analog mode is a +/- 15 VDC power supply required. For
the use in digital mode a +/- 15 VDC or a 24 VDC power supply is sufficient.
80
1179B/1479B/2179B/179B Appendix A: Product Specifications
Physical Specifications
81
Appendix A: Product Specifications 1179B/1479B/2179B/179B
82
1179B/1479B/2179B/179B Appendix B: Model Codes
Model Code
##### XXX Y Z C A E
83
Appendix B: Model Codes 1179B/1479B/2179B/179B
Fittings (Y)
There are different fittings available, designated by a single letter code.
84
1179B/1479B/2179B/179B Appendix B: Model Codes
Valve (Z)
Two valve configurations are available, designated by a single number code.
Connector (C)
The electrical connector of the analog version is designated by a letter, the connectors of the
Profibus unit by a number.
Seals (A)
The seal material is indicated by a single letter code.
85
Appendix B: Model Codes 1179B/1479B/2179B/179B
Appendix (F)
With Profibus units the type code ends with two to four digit code which includes the revision code.
Example:
........26C1
Special versions end with a four digit code, consisting of a leading S followed by a three digit
number. Example:
.........S211
179B 52C D 3 B M
1179BX 12C R 1 B V
86
1179B/1479B/2179B/179B Appendix C: Gas Correction Factors
87
Appendix C: Gas Correction Factors 1179B/1479B/2179B/179B
88
1179B/1479B/2179B/179B Appendix C: Gas Correction Factors
89
Appendix C: Gas Correction Factors 1179B/1479B/2179B/179B
90
1179B/1479B/2179B/179B Appendix D: Binary Code
The following table shows how to convert numbers from decimal code into binary code:
91
Appendix D: Binary Code 1179B/1479B/2179B/179B
92
1179B/1479B/2179B/179B MKS Worldwide Calibration & Service Centers
93
Next page: Declaration of Contamination.