The Haze Front Access - AGM range covers Ah capacities from 30Ah to 180Ah (C10) with
dimensions suitable for racking systems for maximum space utilisation.
Specially designed racks and cabinets are available with cables and connectors to suit.
AGM is especially suited for premium sites with low to medium outage rates and climate
controlled environments, for more extreme temperature variations and increased cyclic
demands please consult the Haze Front Access - GEL range.
Haze facilities are fully accredited to ISO 14001 and the management system fully
accredited to ISO 9001.

A SSURE Specifications
Y D

ISO
IT

Nominal Voltage 12 Volts


QUAL

FIR

Design Life 12 Years


Operating Temperature -20 °C to 50 °C

9001
M

Grid alloy Calcium / Tin lead alloy

UKAS Plates
Separator
Flat Pasted
AGM - Absorbant Glass Mat

SGS
QUALITY
MANAGEMENT Active material Very high purity lead
Case and cover ABS (VO on request)
005
Charge Voltage Float 2.27 - 2.30 VPC @20 °C
Cycling 2.4 @20 °C
Max. 2.45 VPC. Max ripple
0.05C (A)
Electrolyte Sulphuric acid Analytical
grade purity
Venting Valve EPDM Rubber 1.5 to 2 psi
(10.5 - 14 KPa) release
pressure. Resealing at 1 psi (7
Features - Designed to meet the future needs of the KPa)
Tele-communications industry for - mobile, wired, Terminal Epoxy sealed by extended
access, transmission, switching, integrated power mechanical paths
applications etc. Torque setting The recommended torque
Resulting in the following benefits to the customer: value is 5-7 Nm
Connectors Supplied as standard (4 hr
- Compactness rate)
- ETSI / 19” / 23” Integration
- Modularity
- Rackable Standard component
- Long life
- Use under extreme conditions
- High power volume ratio
- Maintenance free utilising VRLA technology
- Low Installation costs
- Front Connections and terminal access
- Long Design Life - 12 years
- Rope handles on 100Ah upwards
- Central gassing system and hinged front covers on
all models
- Integral flame arrestor
- Low Internal resistance
- Recyclable lead and plastics
- Designed to meet BELLCORE recommendations
- Low self discharge rates
o
End of Discharge Voltage = 1.85 DISCHARGE CURRENT in A 20 - 25 C
Model 15' 20' 25' 30' 35' 40' 45' 1 hr 90' 2 hr 3 hr 4 hr 5 hr 6 hr 7 hr 8 hr 10 hr 12 hr 20 hr 24 hr
HZB12-30FA 52.5 43.6 37.2 32.8 28.9 26.0 23.5 18.5 13.2 10.5 7.66 6.17 5.14 4.41 3.88 3.44 2.83 2.41 1.51 1.29
HZB12-40FA 71.1 59.4 49.3 42.9 37.7 34.0 30.8 24.1 17.5 13.9 10.0 7.99 6.73 5.76 5.09 4.49 3.68 3.10 1.91 1.60
HZB12-55FA 99.5 80.4 67.4 59.1 52.2 47.5 43.5 34.8 25.0 20.0 14.5 11.4 9.5 8.11 7.14 6.32 5.21 4.42 2.75 2.31
HZB12-80FA 140 120 105 93.6 83.8 76.5 70.0 56.0 40.3 31.8 22.6 17.7 14.6 12.5 11.0 9.73 8.01 6.82 4.34 3.68
HZB12-95FA 159 137 120 107 96.7 88.8 81.8 65.4 47.3 37.6 27.3 21.6 17.9 15.3 13.4 11.8 9.61 8.12 5.09 4.32
HZB12-95FA-2 146 127 108 95.7 84.9 76.9 70.5 56.1 40.3 31.6 22.6 17.8 14.8 12.5 10.9 9.66 7.95 6.77 4.24 3.58
HZB12-100FA 129 118 108 100 93.2 87.8 82.5 68.7 50.2 39.5 28.1 22.1 18.3 15.5 13.6 11.9 9.78 8.28 5.16 4.35
HZB12-125FA 187 160 141 126 113 103 94.3 76.8 57.4 46.8 35.0 28.5 24.3 21.2 18.9 16.9 14.2 12.2 7.83 6.63
HZB12-150FA 200 180 166 155 144 133 123 101 73.2 57.7 41.5 32.7 27.0 23.2 20.2 17.9 14.7 12.5 7.82 6.68
HZB12-180FA 296 255 224 198 178 162 149 119 87.0 69.1 50.6 40.1 33.2 28.2 24.6 21.8 17.9 15.2 9.46 7.99

o
End of Discharge Voltage = 1.80 DISCHARGE CURRENT in A 20 - 25 C
Model 15' 20' 25' 30' 35' 40' 45' 1 hr 90' 2 hr 3 hr 4 hr 5 hr 6 hr 7 hr 8 hr 10 hr 12 hr 20 hr 24 hr
HZB12-30FA 56.1 46.5 39.7 35.1 30.9 27.8 25.1 19.7 14.1 11.2 8.18 6.59 5.49 4.71 4.15 3.68 3.02 2.57 1.61 1.37
HZB12-40FA 76.0 63.5 52.6 45.8 40.3 36.3 32.9 25.8 18.7 14.8 10.7 8.54 7.19 6.15 5.43 4.80 3.93 3.32 2.04 1.71
HZB12-55FA 106 85.8 72.0 63.1 55.8 50.7 46.5 37.1 26.7 21.4 15.5 12.2 10.1 8.67 7.63 6.75 5.56 4.72 2.94 2.47
HZB12-80FA 152 129 111 98.2 87.1 79.1 72.1 57.6 41.3 32.5 23.0 18.0 14.9 12.7 11.1 9.8 8.09 6.89 4.39 3.71
HZB12-95FA 170 147 128 115 103 94.8 87.4 69.9 50.6 40.2 29.2 23.1 19.1 16.3 14.3 12.6 10.3 8.67 5.44 4.61
HZB12-95FA-2 156 135 115 102 90.7 82.2 75.3 60.0 43.0 33.8 24.2 19.1 15.8 13.4 11.7 10.3 8.49 7.23 4.53 3.83
HZB12-100FA 138 126 115 107 100 93.8 88.1 73.4 53.6 42.2 30.0 23.6 19.5 16.6 14.5 12.8 10.4 8.84 5.51 4.65
HZB12-125FA 216 183 159 141 127 115 105 84.8 62.5 50.3 37.0 29.8 25.2 22.0 19.4 17.4 14.7 12.6 8.00 6.78
HZB12-150FA 214 193 178 165 154 142 132 108 78.2 61.6 44.3 34.9 28.8 24.8 21.6 19.1 15.7 13.3 8.35 7.14
HZB12-180FA 316 273 239 211 190 173 159 127 92.9 73.9 54.0 42.8 35.4 30.1 26.3 23.2 19.1 16.2 10.1 8.53

End of Discharge Voltage = 1.75 DISCHARGE CURRENT in A 20 - 25 oC


Model 15' 20' 25' 30' 35' 40' 45' 1 hr 90' 2 hr 3 hr 4 hr 5 hr 6 hr 7 hr 8 hr 10 hr 12 hr 20 hr 24 hr
HZB12-30FA 59.6 49.5 42.3 37.3 32.8 29.5 26.8 21.0 15.0 12.0 8.61 6.87 5.73 4.91 4.33 3.84 3.15 2.68 1.68 1.43
HZB12-40FA 80.8 67.5 56.0 48.8 42.9 38.6 35.0 27.4 19.9 15.8 11.4 9.08 7.65 6.54 5.78 5.10 4.19 3.53 2.17 1.82
HZB12-55FA 113 91.3 76.6 67.1 59.3 53.9 49.5 39.5 28.4 22.7 16.5 13.0 10.8 9.22 8.12 7.19 5.91 5.02 3.12 2.63
HZB12-80FA 159 133 114 100 89.1 80.7 73.6 58.4 41.7 32.8 23.2 18.2 15.0 12.8 11.2 9.93 8.18 6.96 4.43 3.76
HZB12-95FA 181 156 136 122 110 101 93.0 74.3 53.8 42.8 31.0 24.6 20.4 17.3 15.2 13.4 10.9 9.23 5.79 4.91
HZB12-95FA-2 166 144 122 109 96.4 87.4 80.2 63.8 45.8 36.0 25.7 20.3 16.8 14.2 12.4 11.0 9.04 7.69 4.82 4.07
HZB12-100FA 147 134 122 114 106 99.7 93.7 78.1 57.0 44.9 31.9 25.1 20.7 17.7 15.4 13.6 11.1 9.41 5.86 4.95
HZB12-125FA 234 197 170 150 135 123 112 88.7 64.7 51.8 37.9 30.5 25.6 22.3 19.7 17.7 14.9 12.7 8.06 6.84
HZB12-150FA 227 205 189 176 163 151 140 114 83.1 65.6 47.1 37.1 30.7 26.4 23.0 20.3 16.7 14.2 8.88 7.60
HZB12-180FA 337 290 254 225 202 184 169 135 98.9 78.6 57.5 45.5 37.7 32.1 28.0 24.7 20.4 17.3 10.8 9.08

End of Discharge Voltage = 1.70 DISCHARGE CURRENT in A 20 - 25 oC


Model 15' 20' 25' 30' 35' 40' 45' 1 hr 90' 2 hr 3 hr 4 hr 5 hr 6 hr 7 hr 8 hr 10 hr 12 hr 20 hr 24 hr
HZB12-30FA 61.0 50.6 43.2 38.1 33.6 30.2 27.3 21.5 15.3 12.2 8.89 7.16 5.97 5.12 4.51 4.00 3.28 2.80 1.75 1.49
HZB12-40FA 82.6 69.0 57.2 49.8 43.8 39.5 35.7 28.0 20.3 16.1 11.6 9.28 7.81 6.68 5.91 5.21 4.28 3.61 2.21 1.86
HZB12-55FA 116 93.3 78.2 68.6 60.6 55.1 50.6 40.4 29.1 23.2 16.8 13.3 11.0 9.42 8.29 7.34 6.04 5.13 3.19 2.68
HZB12-80FA 164 137 116 102 89.8 81.6 74.4 58.9 41.9 32.9 23.4 18.3 15.1 12.9 11.3 10.0 8.22 6.99 4.46 3.79
HZB12-95FA 185 160 139 125 112 103 95.0 76.0 55.0 43.7 31.7 25.1 20.8 17.7 15.5 13.7 11.2 9.43 5.91 5.02
HZB12-95FA-2 170 147 125 111 99 89.3 81.9 65.2 46.8 36.7 26.3 20.7 17.1 14.6 12.7 11.2 9.23 7.86 4.92 4.16
HZB12-100FA 150 137 125 116 108 102 95.8 79.8 58.3 45.9 32.6 25.6 21.2 18.1 15.8 13.9 11.4 9.62 5.99 5.06
HZB12-125FA 244 204 176 154 138 126 115 91.4 66.1 52.8 38.7 31.0 26.0 22.5 20.0 17.9 15.0 12.8 8.14 6.90
HZB12-150FA 232 210 193 180 167 155 143 117 85.0 67.0 48.2 37.9 31.3 26.9 23.5 20.8 17.1 14.5 9.08 7.76
HZB12-180FA 342 294 258 228 206 187 172 137 100 79.8 58.3 46.2 38.3 32.6 28.4 25.1 20.7 17.5 10.9 9.22
o
End of Discharge Voltage = 1.65 DISCHARGE CURRENT in A 20 - 25 C
Model 15' 20' 25' 30' 35' 40' 45' 1 hr 90' 2 hr 3 hr 4 hr 5 hr 6 hr 7 hr 8 hr 10 hr 12 hr 20 hr 24 hr
HZB12-30FA 61.7 51.2 43.7 38.6 34.0 30.6 27.7 21.7 15.5 12.4 9.00 7.25 - - - - - - - -
HZB12-40FA 83.6 69.9 57.9 50.5 44.4 40.0 36.2 28.4 20.6 16.3 11.8 9.40 - - - - - - - -
HZB12-55FA 117 94.5 79.2 69.5 61.4 55.8 51.2 40.9 29.4 23.5 17.1 13.5 - - - - - - - -
HZB12-80FA 168 139 117 102 90.8 82.2 75.1 59.2 42.3 33.2 23.5 18.4 - - - - - - - -
HZB12-95FA 187 162 141 126 114 104 96.2 76.9 55.7 44.2 32.1 25.4 - - - - - - - -
HZB12-95FA-2 172 149 127 113 100 90.5 83.0 66.0 47.4 37.2 26.6 21.0 - - - - - - - -
HZB12-100FA 152 139 127 118 110 103 97.0 80.9 59.0 46.4 33.0 25.9 - - - - - - - -
HZB12-125FA 249 207 178 156 140 127 117 93.1 67.5 53.6 39.1 31.4 - - - - - - - -
HZB12-150FA 235 212 196 182 169 157 145 118 86.1 67.9 48.8 38.4 - - - - - - - -
HZB12-180FA 347 299 262 232 209 190 174 139 102 81.1 59.3 47.0 - - - - - - - -

End of Discharge Voltage = 1.60 DISCHARGE CURRENT in A 20 - 25 oC


Model 15' 20' 25' 30' 35' 40' 45' 1 hr 90' 2 hr 3 hr 4 hr 5 hr 6 hr 7 hr 8 hr 10 hr 12 hr 20 hr 24 hr
HZB12-30FA 62.3 51.7 44.2 39.0 34.3 30.9 28.0 21.9 15.7 12.5 9.09 7.32 - - - - - - - -
HZB12-40FA 84.4 70.5 58.5 51.0 44.8 40.3 36.5 28.6 20.8 16.5 11.9 9.49 - - - - - - - -
HZB12-55FA 118 95.4 80.0 70.2 62.0 56.4 51.7 41.3 29.7 23.7 17.2 13.6 - - - - - - - -
HZB12-80FA 172 141 119 103 91.6 82.7 75.5 59.6 42.5 33.3 23.6 18.4 - - - - - - - -
HZB12-95FA 189 163 142 128 115 105 97.1 77.7 56.2 44.7 32.4 25.7 - - - - - - - -
HZB12-95FA-2 173 150 128 114 101 91.3 83.8 66.7 47.9 37.6 26.9 21.2 - - - - - - - -
HZB12-100FA 153 141 128 119 111 104 98.0 81.6 59.6 46.9 33.4 26.2 - - - - - - - -
HZB12-125FA 252 209 179 157 141 128 117 94.1 68.1 54.0 39.4 31.5 - - - - - - - -
HZB12-150FA 238 214 198 184 171 158 147 120 86.9 68.5 49.2 38.8 - - - - - - - -
HZB12-180FA 350 302 264 234 211 192 176 140 103 81.7 59.8 47.3 - - - - - - - -

Front Access AGM Construction - The AGM Technology - AGM technology has a number of advantages
positive and negative grids are cast from a over the equivalent Gel battery range, the main advantages for the
calcium/tin lead alloy to reduce grid growth Telecommunication applications are as follows:
and corrosion.
! Increased capacity over shorter discharge times.
! Lower initial cost.
! Ideal for starting and stationary applications.
! More suitable for UPS stand-by where power outages are
The active material is manufactured from a
uncommon.
high purity lead (99.9999%) to minimize the
! Smaller size battery can be used for higher rate discharges.
impurities, which would cause corrosion and
self-discharge. Haze only employ “S wrapping” in our AGM construction to further
reduce the possibility of short circuits due to mossing. Closely
controlled plate density and thickness results in excellent consistent
performance when placed in a string (series connection)
The separator is mat of random woven glass Batteries are manufactured under a quality system designed to meet
fibres, they are completely acid resistant and act and exceed ISO 9002.
as a sponge soaking up and immobilizing the
acid whilst keeping the acid available when it is
needed during periods of battery discharge. “S
Wrapping” is employed to reduce the risk of
short circuit due to mossing or debris at the Central Gassing - Haze
bottom of the cell. produce all models with an
integral central gassing
system. This system is a
useful feature when
The purpose of the separator is to maintain a batteries are installed in an
constant distance between the positive and IP66 cabinet. Sealed
negative plates, totally eliminating the enclosures prevent any
possibility of short circuits whilst allowing the escaping gas from exiting,
active materials to fully react with the central gassing however
electrolyte. The separator also has an open allows a tube carrying the
construction, which offers little resistance to the emissions to pass through
flow of the electrolyte during filling. a seal to atmosphere.
End of Discharge Voltage = 1.85 DISCHARGE IN WATTS PER CELL 20 - 25 oC
Model 15' 20' 25' 30' 35' 40' 45' 1 hr 90' 2 hr 3 hr 4 hr 5 hr 6 hr 7 hr 8 hr 10 hr 12 hr 20 hr 24 hr
HZB12-30FA 107 88.7 76.0 66.2 58.1 52.8 48.2 38.3 27.8 22.0 15.6 12.2 10.03 8.55 7.44 6.57 5.45 4.64 2.97 2.52
HZB12-40FA 120 100 88.1 79.3 71.8 65.8 60.5 49.0 35.5 28.0 19.9 15.7 13.1 11.3 9.92 8.83 7.30 6.19 3.89 3.29
HZB12-55FA 177 156 137 123 110 99.5 90.9 72.2 52.0 40.8 28.9 22.6 18.7 16.0 14.0 12.4 10.1 8.59 5.37 4.54
HZB12-80FA 242 213 189 170 155 142 131 106 77.0 60.5 43.1 33.9 27.9 23.8 20.7 18.4 15.2 13.0 8.34 7.09
HZB12-95FA 304 259 229 205 185 170 157 125 92.6 73.6 53.0 42.3 35.5 30.5 26.9 24.0 19.8 16.8 10.3 8.68
HZB12-95FA-2 276 236 207 184 166 152 140 113 81.9 64.6 45.8 36.2 30.1 25.9 22.6 20.0 16.3 13.8 8.4 7.02
HZB12-100FA 263 239 219 205 191 178 164 131 93.6 75.0 54.3 43.0 35.9 30.7 26.8 23.7 19.4 16.3 10.0 8.43
HZB12-125FA 365 318 277 247 225 208 194 162 123 100 74.7 59.6 51.8 42.0 38.8 34.4 28.6 24.5 15.9 13.5
HZB12-150FA 391 356 334 308 290 270 251 208 149 119 85.6 67.3 55.4 47.1 40.8 36.0 29.4 24.8 15.2 12.9
HZB12-180FA 545 477 418 367 328 301 279 227 167 133 95.7 76.0 63.4 54.3 47.4 41.8 34.2 28.9 18.0 15.2

End of Discharge Voltage = 1.80 DISCHARGE IN WATTS PER CELL 20 - 25 oC


Model 15' 20' 25' 30' 35' 40' 45' 1 hr 90' 2 hr 3 hr 4 hr 5 hr 6 hr 7 hr 8 hr 10 hr 12 hr 20 hr 24 hr
HZB12-30FA 114 94.8 81.2 70.7 62.1 56.4 51.5 40.9 29.7 23.5 16.6 13.0 10.7 9.13 7.95 7.02 5.82 4.96 3.18 2.69
HZB12-40FA 129 107 94.1 84.7 76.7 70.3 64.6 52.3 37.9 29.9 21.3 16.8 14.0 12.0 10.6 9.44 7.79 6.61 4.15 3.52
HZB12-55FA 190 166 147 131 117 106 97.1 77.1 55.5 43.6 30.8 24.1 20.0 17.0 14.9 13.2 10.8 9.18 5.73 4.85
HZB12-80FA 260 225 198 177 160 147 136 109 79.0 62.0 44.1 34.5 28.4 24.3 21.2 18.7 15.5 13.2 8.45 7.17
HZB12-95FA 325 277 245 219 197 181 167 134 99.0 78.6 56.7 45.2 37.9 32.6 28.7 25.6 21.1 17.9 11.0 9.27
HZB12-95FA-2 295 252 221 197 177 163 149 121 87.5 69.0 48.9 38.7 32.2 27.6 24.2 21.4 17.4 14.7 8.93 7.50
HZB12-100FA 281 255 234 219 204 190 175 140 100 80.1 58.0 45.9 38.3 32.8 28.7 25.3 20.7 17.4 10.7 9.00
HZB12-125FA 396 345 298 264 239 221 205 170 128 104 76.8 61.1 53.2 42.8 39.5 35.1 29.2 25.0 16.1 13.8
HZB12-150FA 418 381 357 329 310 288 269 222 160 127 91.4 71.9 59.2 50.3 43.6 38.5 31.4 26.5 16.3 13.7
HZB12-180FA 589 515 447 392 351 322 298 243 178 142 102 81.2 67.7 58.0 50.6 44.7 36.5 30.8 19.2 16.2

End of Discharge Voltage = 1.75 DISCHARGE IN WATTS PER CELL 20 - 25 oC


Model 15' 20' 25' 30' 35' 40' 45' 1 hr 90' 2 hr 3 hr 4 hr 5 hr 6 hr 7 hr 8 hr 10 hr 12 hr 20 hr 24 hr
HZB12-30FA 121 101 86.4 75.2 66.1 60.0 54.8 43.5 31.6 25.0 17.7 13.9 11.4 9.72 8.46 7.47 6.19 5.27 3.38 2.86
HZB12-40FA 137 114 100 90.1 81.5 74.8 68.7 55.7 40.4 31.8 22.6 17.9 14.9 12.8 11.3 10.0 8.29 7.03 4.42 3.74
HZB12-55FA 202 177 156 140 125 113 103 82.0 59.1 46.4 32.8 25.7 21.2 18.1 15.9 14.1 11.5 9.77 6.10 5.16
HZB12-80FA 271 232 203 182 164 150 138 111 80.0 62.8 44.5 34.9 28.7 24.4 21.3 18.9 15.6 13.3 8.49 7.21
HZB12-95FA 346 295 260 233 210 193 178 142 105 83.6 60.3 48.1 40.3 34.6 30.6 27.2 22.5 19.0 11.8 9.86
HZB12-95FA-2 314 268 236 210 189 173 159 129 93.1 73.4 52.1 41.2 34.2 29.4 25.7 22.8 18.6 15.6 9.5 7.98
HZB12-100FA 299 271 249 233 217 202 186 149 106 85.3 61.7 48.8 40.8 34.9 30.5 26.9 22.0 18.6 11.4 9.58
HZB12-125FA 423 359 309 274 247 227 209 173 130 105 77.5 61.8 53.7 43.4 40.1 35.6 29.6 25.3 16.3 13.9
HZB12-150FA 444 405 380 350 330 307 286 236 170 135 97.3 76.5 63.0 53.5 46.4 40.9 33.4 28.2 17.3 14.6
HZB12-180FA 620 542 475 417 373 342 317 258 190 151 109 86.4 72.0 61.7 53.8 47.5 38.9 32.8 20.5 17.2

o
End of Discharge Voltage = 1.70 DISCHARGE IN WATTS PER CELL 20 - 25 C
Model 15' 20' 25' 30' 35' 40' 45' 1 hr 90' 2 hr 3 hr 4 hr 5 hr 6 hr 7 hr 8 hr 10 hr 12 hr 20 hr 24 hr
HZB12-30FA 124 103 88.3 76.9 67.5 61.3 56.0 44.5 32.3 25.6 18.1 14.2 11.7 9.93 8.64 7.63 6.33 5.39 3.45 2.92
HZB12-40FA 140 116 102 92.1 83.3 76.4 70.2 56.9 41.2 32.5 23.1 18.2 15.2 13.1 11.5 10.3 8.47 7.19 4.51 3.82
HZB12-55FA 206 181 159 143 127 116 106 83.8 60.4 47.4 33.5 26.2 21.7 18.5 16.2 14.4 11.8 9.98 6.24 5.28
HZB12-80FA 278 236 206 184 166 151 139 112 80.7 63.4 44.8 35.1 28.9 24.6 21.5 19.0 15.7 13.4 8.55 7.28
HZB12-95FA 353 301 266 238 214 197 182 146 108 85.5 61.6 49.2 41.2 35.4 31.2 27.8 23.0 19.5 12.0 10.08
HZB12-95FA-2 320 274 241 214 193 177 162 131 95.1 75.0 53.2 42.1 35.0 30.0 26.3 23.3 19.0 16.0 9.71 8.15
HZB12-100FA 305 277 255 238 222 206 190 152 109 87.1 63.0 49.9 41.7 35.7 31.2 27.5 22.5 19.0 11.6 9.79
HZB12-125FA 435 365 314 277 250 228 211 175 131 106 78.1 62.3 54.1 43.6 40.4 35.8 29.8 25.5 16.4 13.9
HZB12-150FA 454 414 388 358 337 314 292 241 173 138 99.4 78.2 64.4 54.7 47.4 41.8 34.2 28.8 17.7 14.9
HZB12-180FA 633 554 486 426 381 350 324 264 194 155 111 88.3 73.6 63.0 55.0 48.6 39.7 33.5 20.9 17.6
End of Discharge Voltage = 1.65 DISCHARGE IN WATTS PER CELL 20 - 25 oC
Model 15' 20' 25' 30' 35' 40' 45' 1 hr 90' 2 hr 3 hr 4 hr 5 hr 6 hr 7 hr 8 hr 10 hr 12 hr 20 hr 24 hr
HZB12-30FA 126 104 89.4 77.8 68.4 62.1 56.7 45.0 32.7 25.9 18.3 14.4 - - - - - - - -
HZB12-40FA 142 118 104 93.3 84.4 77.4 71.1 57.6 41.8 32.9 23.4 18.5 - - - - - - - -
HZB12-55FA 209 183 161 145 129 117 107 84.9 61.1 48.0 34.0 26.6 - - - - - - - -
HZB12-80FA 284 240 209 186 167 153 140 113 81.4 63.8 45.2 35.3 - - - - - - - -
HZB12-95FA 358 305 269 241 217 200 184 147 109 86.5 62.4 49.8 - - - - - - - -
HZB12-95FA-2 325 278 244 217 195 179 164 133 96.3 76.0 53.9 42.6 - - - - - - - -
HZB12-100FA 309 281 258 241 225 209 193 154 110 88.2 63.8 50.5 - - - - - - - -
HZB12-125FA 443 368 316 279 251 230 213 176 131 106 78.1 62.6 - - - - - - - -
HZB12-150FA 460 419 393 362 341 318 296 244 176 140 101 79.2 - - - - - - - -
HZB12-180FA 641 561 492 431 386 354 328 267 196 157 113 89.4 - - - - - - - -

End of Discharge Voltage = 1.60 DISCHARGE IN WATTS PER CELL 20 - 25 oC


Model 15' 20' 25' 30' 35' 40' 45' 1 hr 90' 2 hr 3 hr 4 hr 5 hr 6 hr 7 hr 8 hr 10 hr 12 hr 20 hr 24 hr
HZB12-30FA 127 105 90.3 78.6 69.0 62.7 57.3 45.5 33.0 26.1 18.5 14.5 - - - - - - - -
HZB12-40FA 143 119 105 94.2 85.2 78.2 71.8 58.2 42.2 33.2 23.7 18.7 - - - - - - - -
HZB12-55FA 211 185 163 146 130 118 108 85.7 61.7 48.5 34.3 26.8 - - - - - - - -
HZB12-80FA 289 242 210 187 169 154 141 114 81.8 64.0 45.4 35.5 - - - - - - - -
HZB12-95FA 361 308 272 244 219 202 186 149 110 87.4 63.0 50.3 - - - - - - - -
HZB12-95FA-2 328 280 246 219 197 181 166 134 97.3 76.7 54.4 43.0 - - - - - - - -
HZB12-100FA 312 284 260 243 227 211 194 155 111 89.1 64.4 51.0 - - - - - - - -
HZB12-125FA 448 369 317 280 252 232 214 177 132 106 78.5 63.0 - - - - - - - -
HZB12-150FA 464 423 397 366 345 321 299 246 177 141 102 79.9 - - - - - - - -
HZB12-180FA 648 566 497 435 390 358 331 270 198 158 114 90.2 - - - - - - - -

Self-discharge C haracte ristics


100

80
Applications
Residual Capacity %

60 § Float service
§ Uninterruptible Power Supplies
40 § Medical
50 C
§ Telecommunications
40 C
20 30 C § Switch Gear
20 C § Photovoltaic
0 § Solar
0 5 10 15 § Wind
Storage Time (Months)
§ Control Systems
§ Cellular Radio Stations
§ Cathodic Protection
§ Navigation Aids
§ Marine equipment
§ Electric Power Systems
End of Discharge Voltage = 1.85 DISCHARGE CAPACITY Ah 20 - 25 oC
Model 15' 20' 25' 30' 35' 40' 45' 1 hr 90' 2 hr 3 hr 4 hr 5 hr 6 hr 7 hr 8 hr 10 hr 12 hr 20 hr 24 hr
HZB12-30FA 13.1 14.5 15.7 16.4 16.9 17.3 17.7 18.5 19.8 21.0 23.0 24.7 25.7 26.5 27.2 27.7 28.3 28.9 30.2 30.9
HZB12-40FA 17.8 19.8 20.8 21.5 22.1 22.6 23.1 24.1 26.2 27.7 30.0 32.0 33.6 34.6 35.6 36.1 36.8 37.3 38.1 38.4
HZB12-55FA 24.9 26.8 28.4 29.5 30.6 31.6 32.7 34.8 37.5 40.0 43.5 45.8 47.3 48.8 50.0 50.8 52.1 53.0 55.0 55.4
HZB12-80FA 35.0 40.1 43.7 46.8 49.1 51.0 52.5 56.0 60.5 63.6 67.8 70.6 73.1 75.0 76.8 78.2 80.1 81.8 86.9 88.2
HZB12-95FA 39.7 45.8 50.5 53.7 56.7 59.2 61.3 65.4 71.0 75.2 81.9 86.5 89.5 91.9 93.5 94.6 96.1 97.4 102 104
HZB12-95FA-2 36.5 42.2 45.4 47.9 49.7 51.3 52.9 56.1 60.4 63.3 67.9 71.4 73.8 75.5 76.5 77.6 79.5 81.2 84.8 86.0
HZB12-100FA 32.3 39.3 44.9 50.0 54.6 58.5 61.9 68.7 75.3 79.0 84.3 88.2 91.3 93.3 94.9 96.0 97.8 99.4 103 105
HZB12-125FA 47.7 54.5 59.8 64.3 67.2 69.8 72.2 78.3 87.9 95.4 107 116 124 130 135 139 145 150 160 162
HZB12-150FA 50.0 60.2 69.3 77.4 84.3 88.7 92.6 101 110 115 124 131 135 139 142 144 147 150 156 160
HZB12-180FA 74.1 85.1 93.1 98.9 104 108 112 119 131 138 152 160 166 169 172 175 179 183 189 192

End of Discharge Voltage = 1.80 DISCHARGE CAPACITY Ah 20 - 25 oC


Model 15' 20' 25' 30' 35' 40' 45' 1 hr 90' 2 hr 3 hr 4 hr 5 hr 6 hr 7 hr 8 hr 10 hr 12 hr 20 hr 24 hr
HZB12-30FA 14.0 15.5 16.8 17.5 18.1 18.5 18.9 19.7 21.2 22.5 24.5 26.3 27.5 28.3 29.0 29.6 30.2 30.9 32.3 33.0
HZB12-40FA 19.0 21.2 22.2 22.9 23.6 24.2 24.6 25.8 28.0 29.6 32.1 34.1 35.9 37.0 38.0 38.6 39.3 39.8 40.7 41.1
HZB12-55FA 26.6 28.6 30.4 31.6 32.7 33.8 34.9 37.1 40.1 42.7 46.5 48.9 50.5 52.2 53.4 54.3 55.6 56.7 58.7 59.2
HZB12-80FA 38.1 42.9 46.3 49.1 51.0 52.7 54.1 57.6 61.9 64.9 69.0 71.8 74.3 76.3 77.9 79.1 80.9 82.7 87.8 89.0
HZB12-95FA 42.4 48.9 53.9 57.4 60.5 63.2 65.5 69.9 75.9 80.4 87.5 92.4 95.7 98.1 99.8 101 103 104 109 111
HZB12-95FA-2 39.0 45.1 48.5 51.1 53.1 54.8 56.5 60.0 64.6 67.6 72.5 76.3 78.9 80.6 81.7 82.9 84.9 86.8 90.6 91.9
HZB12-100FA 34.5 42.0 47.9 53.4 58.3 62.5 66.1 73.4 80.4 84.4 90.0 94.2 97.5 99.7 101 103 104 106 110 112
HZB12-125FA 55.1 62.1 67.5 71.8 75.8 78.4 80.7 86.6 95.6 103 113 122 129 135 139 143 150 154 163 166
HZB12-150FA 53.4 64.3 74.0 82.7 90.0 94.8 98.9 108 117 123 133 140 144 149 151 154 157 160 167 171
HZB12-180FA 79.1 90.9 99.5 106 111 116 119 127 139 148 162 171 177 181 184 187 191 195 202 205

End of Discharge Voltage = 1.75 DISCHARGE CAPACITY Ah 20 - 25 oC


Model 15' 20' 25' 30' 35' 40' 45' 1 hr 90' 2 hr 3 hr 4 hr 5 hr 6 hr 7 hr 8 hr 10 hr 12 hr 20 hr 24 hr
HZB12-30FA 14.9 16.5 17.8 18.7 19.2 19.7 20.1 21.0 22.5 23.9 25.8 27.5 28.6 29.6 30.3 30.8 31.5 32.2 33.7 34.4
HZB12-40FA 20.2 22.5 23.6 24.4 25.1 25.7 26.2 27.4 29.8 31.5 34.1 36.3 38.2 39.4 40.5 41.0 41.9 42.3 43.3 43.7
HZB12-55FA 28.3 30.4 32.3 33.6 34.8 35.9 37.1 39.5 42.6 45.4 49.5 52.0 53.8 55.5 56.8 57.8 59.1 60.3 62.5 63.0
HZB12-80FA 39.8 44.4 47.6 50.2 52.2 53.8 55.2 58.4 62.6 65.5 69.7 72.6 75.0 77.0 78.6 79.9 81.8 83.5 88.6 90.2
HZB12-95FA 45.2 52.0 57.4 61.1 64.4 67.3 69.7 74.3 80.7 85.5 93.1 98.3 102 104 106 108 109 111 116 118
HZB12-95FA-2 41.5 47.9 51.6 54.4 56.5 58.3 60.1 63.8 68.7 71.9 77.2 81.1 83.9 85.7 86.9 88.2 90.4 92.3 96.3 97.7
HZB12-100FA 36.7 44.6 51.0 56.8 62.0 66.5 70.3 78.1 85.6 89.7 95.8 100 104 106 108 109 111 113 117 119
HZB12-125FA 59.8 67.0 72.3 76.4 80.1 83.5 85.7 90.5 99.1 106 116 124 131 137 141 145 152 156 165 168
HZB12-150FA 56.8 68.4 78.8 88.0 95.8 101 105 114 125 131 141 149 153 158 161 163 167 170 178 182
HZB12-180FA 84.2 96.7 106 112 118 123 127 135 148 157 172 182 189 192 196 199 204 207 215 218

End of Discharge Voltage = 1.70 DISCHARGE CAPACITY Ah 20 - 25 oC


Model 15' 20' 25' 30' 35' 40' 45' 1 hr 90' 2 hr 3 hr 4 hr 5 hr 6 hr 7 hr 8 hr 10 hr 12 hr 20 hr 24 hr
HZB12-30FA 15.2 16.9 18.2 19.1 19.7 20.1 20.5 21.5 23.0 24.4 26.7 28.6 29.9 30.8 31.6 32.1 32.8 33.5 35.1 35.8
HZB12-40FA 20.6 23.0 24.1 24.9 25.7 26.3 26.8 28.0 30.4 32.2 34.9 37.1 39.1 40.2 41.4 41.9 42.8 43.3 44.3 44.7
HZB12-55FA 28.9 31.1 33.0 34.3 35.5 36.7 37.9 40.4 43.6 46.4 50.5 53.1 54.9 56.7 58.1 59.0 60.4 61.6 63.9 64.4
HZB12-80FA 41.1 45.5 48.3 50.8 52.6 54.4 55.8 58.9 62.9 65.8 70.1 73.1 75.4 77.5 79.0 80.2 82.2 83.9 89.1 90.9
HZB12-95FA 46.2 53.2 58.7 62.4 65.8 68.7 71.2 76.0 82.5 87.4 95.2 100 104 107 109 110 112 113 118 120
HZB12-95FA-2 42.4 49.0 52.8 55.6 57.8 59.6 61.4 65.2 70.2 73.5 78.9 82.9 85.7 87.6 88.9 90.2 92.3 94.3 98 100
HZB12-100FA 37.5 45.6 52.1 58.1 63.4 68.0 71.9 79.8 87.4 91.7 97.9 102 106 108 110 111 114 115 120 121
HZB12-125FA 62.3 69.4 74.7 78.7 82.3 85.6 88.1 93.3 101 108 119 127 132 138 143 147 153 157 166 169
HZB12-150FA 58.1 69.9 80.5 89.9 97.9 103 107 117 127 134 144 152 157 162 164 167 171 174 182 186
HZB12-180FA 85.4 98.2 107 114 120 125 129 137 151 160 175 185 191 195 199 202 207 211 218 221
o
End of Discharge Voltage = 1.65 DISCHARGE CAPACITY Ah 20 - 25 C
Model 15' 20' 25' 30' 35' 40' 45' 1 hr 90' 2 hr 3 hr 4 hr 5 hr 6 hr 7 hr 8 hr 10 hr 12 hr 20 hr 24 hr
HZB12-30FA 15.4 17.1 18.5 19.3 19.9 20.4 20.8 21.7 23.3 24.8 27.0 29.0 - - - - - - - -
HZB12-40FA 20.9 23.3 24.4 25.2 26.0 26.6 27.1 28.4 30.8 32.6 35.3 37.6 - - - - - - - -
HZB12-55FA 29.3 31.5 33.4 34.7 36.0 37.2 38.4 40.9 44.1 47.0 51.2 53.8 - - - - - - - -
HZB12-80FA 41.9 46.3 48.9 51.2 53.2 54.8 56.3 59.2 63.4 66.3 70.4 73.4 - - - - - - - -
HZB12-95FA 46.7 53.8 59.4 63.2 66.7 69.6 72.2 76.9 83.5 88.5 96.4 102 - - - - - - - -
HZB12-95FA-2 42.9 49.6 53.4 56.3 58.5 60.3 62.2 66.0 71.1 74.4 79.9 84.0 - - - - - - - -
HZB12-100FA 37.9 46.2 52.8 58.8 64.2 68.8 72.8 80.9 88.6 92.9 99.1 104 - - - - - - - -
HZB12-125FA 63.4 70.5 75.6 79.6 83.2 86.4 89.3 95.0 103 109 120 128 - - - - - - - -
HZB12-150FA 58.8 70.7 81.5 91.1 99.1 104 109 118 129 136 146 154 - - - - - - - -
HZB12-180FA 86.8 100 109 116 122 127 131 139 153 162 178 188 - - - - - - - -

o
End of Discharge Voltage = 1.60 DISCHARGE CAPACITY Ah 20 - 25 C
Model 15' 20' 25' 30' 35' 40' 45' 1 hr 90' 2 hr 3 hr 4 hr 5 hr 6 hr 7 hr 8 hr 10 hr 12 hr 20 hr 24 hr
HZB12-30FA 15.6 17.2 18.6 19.5 20.1 20.6 21.0 21.9 23.5 25.0 27.3 29.3 - - - - - - - -
HZB12-40FA 21.1 23.5 24.7 25.5 26.3 26.9 27.4 28.6 31.1 32.9 35.7 38.0 - - - - - - - -
HZB12-55FA 29.5 31.8 33.8 35.1 36.3 37.6 38.8 41.3 44.6 47.5 51.7 54.3 - - - - - - - -
HZB12-80FA 42.9 47.0 49.6 51.7 53.7 55.1 56.6 59.6 63.8 66.6 70.7 73.8 - - - - - - - -
HZB12-95FA 47.2 54.4 60.0 63.8 67.3 70.3 72.9 77.7 84.3 89.3 97.3 103 - - - - - - - -
HZB12-95FA-2 43.4 50.1 54.0 56.8 59.1 60.9 62.8 66.7 71.8 75.2 80.6 84.8 - - - - - - - -
HZB12-100FA 38.3 46.6 53.3 59.4 64.8 69.5 73.5 81.6 89.4 93.8 100 105 - - - - - - - -
HZB12-125FA 64.3 71.1 76.2 80.2 83.7 86.9 89.8 96.0 104 110 121 129 - - - - - - - -
HZB12-150FA 59.4 71.4 82.3 91.9 100 105 110 120 130 137 148 155 - - - - - - - -
HZB12-180FA 87.5 101 110 117 123 128 132 140 154 163 179 189 - - - - - - - -

GAS RECOMBINATION - The gasses generated during normal operation of


the battery are internally recombined. In fact more than 99% of the gas
achieves recombination.

SAFETY RELEASE VALVE- The battery will operate above atmospheric pressure under
normal operating conditions, however the maximum pressure is governed by the safety
release valve. Open is activated by pressures in excess of approx. 2 psi (14 Kpa), resealing
at approx 1.2 psi (8.4 Kpa).

TERMINAL CONSTRUCTION - The contact


quality between the insert terminal and the lead
post is of vital importance during short duration
/ high Amp discharges. Elevated terminal
temperatures are the result of poor contact, A SSURE
D
TY
eventually causing seal degradation and
ISO
LI

FIR
QUA

electrolyte leaks. Haze design and assembly


M

technique for terminal casting ensures trouble 9001 UKAS


free operation for the design life of the battery.
SGS
QUALITY
MANAGEMENT
005

Capacity temperature correction Factor to be applied to Data at 20 Degrees C


-30 °C -20 °C -10 °C 0 °C 5 °C 10 °C 15 °C 20-25 °C 30 °C 35 °C 40 °C 50 °C
Discharge Time
5 minutes to 59
24% 36% 45% 68% 77% 83% 92% 100% 105% 107% 108% 110%
minutes

1 Hour to 100 Hours 28% 41% 58% 73% 79% 86% 94% 100% 104% 106% 107% 108%
Dimensions (Inches) & approx w eight Internal M a xi m u m
Battery Mod el Qty Per Dimensions (mm) & approx weight (kg) (Lbs) Terminal Resistance Charge
Box Length W i d th Height W e i gh t Length W i d th Height W e i gh t Layout mOhms Current
HZB12-30FA 1 225 99 225 10.1 8.86 3.90 8.86 22.3 M5 5 7.5
HZB12-40FA 1 225 99 225 13.1 8.86 3.90 8.86 29.0 M5 5 10
HZB12-55FA 1 277 105 223 17.9 10.91 4.13 8.78 39.6 M6 4.3 15
HZB12-80FA 1 563 114 182 26.8 22.17 4.49 7.17 59.2 M6 3.6 20
HZB12-95FA 1 507 109 227 32.5 19.96 4.29 8.94 71.8 M6 4.1 25
HZB12-95FA-2 1 395 105 257 27.5 15.55 4.13 10.12 60.8 M6 3.8 25
HZB12-100FA 1 395 110 285 32.6 15.55 4.33 11.22 72.0 M6 3.6 30
HZB12-125FA 1 417 172 240 46.0 16.42 6.77 9.45 101.7 M6 2.9 35
HZB12-150FA 1 550 109 286 48.5 21.65 4.29 11.26 107.2 M6 3.1 40
HZB12-180FA 1 560 125 320 57.9 22.05 4.92 12.60 128.0 M8 2.9 45

The graph shows extrapolated Design


Life condition for Haze batteries at
different ambient temperatures. Clearly 100
higher ambient temperatures will Temperature Vs
reduce service life. 75%
Life
Characteristics
33%
% Design

Physical Information
7%

3%

Temper ature Shelf Life 20 30 40 50 60


o o o o Temperature C
0 C - 20 C (32 F - 68 F) 12 Months
21 oC - 30 oC (69 oF - 86 oF) 9 Months
31 oC - 40 oC (87 oF - 104 oF) 5 Months
41 oC - 50 oC (105 oF - 1122 oF) 2.5 Months

CHARGING CHARACTERISTICS
Floating - The optimum float voltage for a battery is
temperature dependant, at 15 - 24oC the recommended
value is 2.27 - 2.30V. It is recommended that battery
installation sites are temperature controlled, however float
Recommended voltage can be increased or decreased to compensate for
Operating Applied Float Voltage temperature variations. Adjustment is calculated at +/- 3
Temperature VPC mV per degree C.
0-9 2.33 - 2.35
The most suitable charging method for battery life and
10-14 2.30 - 2.33 performance is the constant voltage method with a limited
initial current, usually limited to a maximum of C20/4.
15-19 2.27 - 2.30
20-24 2.27 - 2.30
25-29 2.25 - 2.27
30-34 2.23 - 2.25
35-40 2.21 - 2.23
414
458
99 6
110 6

225

395
12-30&40 Front Access
Battery Height: 225mm
438

105 6

12-100 Front Access


Battery Height: 285mm
277

706
172 6

12-50&55 Front Access


Battery Height: 223mm
474

114 6

417
563

454 12-125 Front Access


Battery Height: 240mm
109 6
535

515

12-70&80 Front Access


Battery Height: 182mm
454
Battery Drawings

550

109 6
146 221.5

450

12-150 Front Access


507

300mm Deep ETSI tray


Battery Height: 285mm

518

125 6
482.5

465
12-90&95 Front Access
Battery Height: 227mm
438

105 6
560

117.8 221.5

450
395

300mm deep 19 inch tray


12-170&180 Front Access
Battery Height: 320mm

12-95-2 Front Access


Battery Height: 257mm
528 465

508 347
5 6

5 6

25
25
278 x 2

340.2 x 2
1150

1370
278

340.2
100

100
Front View Side View
Front View Side View
16 x 12V50FA&55FA Rack
508 437 16 x 12V100FA Rack
5 6 524 620

5 6
25

25
312 x 2

339.2 x 2
1280

1365.6

339.2
312

100
100

Front View Side View


Front View Side View 16 x 12V150FA Rack
588 600

16 x 12V95FA-2 Rack 5 6

As can be seen from the rack diagrams, the Haze Front


Access range are compatible with ETSI and standard 19”
25

and 23” rack configurations, only the HZB12 125FA can


Typical Rack Layouts
not be used in the standard ETSI and 19” formats.
300mm or 600mm deep trays can be utilised.

Other racking configurations can be tailored to meet the


373 x 2

customers needs for a new installation or indeed to


1500

replace an existing arrangement utilising the same


footprint.

The Front Access design allows racking clearances to be


reduced whilst still allowing easy access for intercell
connection and terminal inspectio, all resulting in time and
373

cost savings.

With reduced space requirements the designer has the


100

option of smaller cabinets or more power from the same


foot print. Front View Side View
16 x 12V170FA&180FA Rack
Haze Battery Company Ltd

Product Range

4, 6 & 12 Volt AGM 1.3 to 230AH


6 & 12 Volt Gel 7.5 to 230AH
12 Volt Front Access AGM
12 Volt Front Access Gel
2 Volt AGM & Gel 50 to 3850AH
EV Gel
EV AGM
Marine Gel
Solar
OPzV
OPzS

Website: www.hazebattery.com
E mail [email protected]

061112

EMC
Germany
tested
AD
LE

RUBBISH BIN
RE
TU
RN

R
RECYCLE
Pb
Haze Battery Company keenly encourages
environmental awareness; PLEASE follow
guidelines for the recycling /disposal of lead.

You might also like