FA AGM Cat 061112 S
FA AGM Cat 061112 S
FA AGM Cat 061112 S
ACCESS
AGM
A SSURE Specifications
Y D
ISO
IT
FIR
9001
M
UKAS Plates
Separator
Flat Pasted
AGM - Absorbant Glass Mat
SGS
QUALITY
MANAGEMENT Active material Very high purity lead
Case and cover ABS (VO on request)
005
Charge Voltage Float 2.27 - 2.30 VPC @20 °C
Cycling 2.4 @20 °C
Max. 2.45 VPC. Max ripple
0.05C (A)
Electrolyte Sulphuric acid Analytical
grade purity
Venting Valve EPDM Rubber 1.5 to 2 psi
(10.5 - 14 KPa) release
pressure. Resealing at 1 psi (7
Features - Designed to meet the future needs of the KPa)
Tele-communications industry for - mobile, wired, Terminal Epoxy sealed by extended
access, transmission, switching, integrated power mechanical paths
applications etc. Torque setting The recommended torque
Resulting in the following benefits to the customer: value is 5-7 Nm
Connectors Supplied as standard (4 hr
- Compactness rate)
- ETSI / 19” / 23” Integration
- Modularity
- Rackable Standard component
- Long life
- Use under extreme conditions
- High power volume ratio
- Maintenance free utilising VRLA technology
- Low Installation costs
- Front Connections and terminal access
- Long Design Life - 12 years
- Rope handles on 100Ah upwards
- Central gassing system and hinged front covers on
all models
- Integral flame arrestor
- Low Internal resistance
- Recyclable lead and plastics
- Designed to meet BELLCORE recommendations
- Low self discharge rates
o
End of Discharge Voltage = 1.85 DISCHARGE CURRENT in A 20 - 25 C
Model 15' 20' 25' 30' 35' 40' 45' 1 hr 90' 2 hr 3 hr 4 hr 5 hr 6 hr 7 hr 8 hr 10 hr 12 hr 20 hr 24 hr
HZB12-30FA 52.5 43.6 37.2 32.8 28.9 26.0 23.5 18.5 13.2 10.5 7.66 6.17 5.14 4.41 3.88 3.44 2.83 2.41 1.51 1.29
HZB12-40FA 71.1 59.4 49.3 42.9 37.7 34.0 30.8 24.1 17.5 13.9 10.0 7.99 6.73 5.76 5.09 4.49 3.68 3.10 1.91 1.60
HZB12-55FA 99.5 80.4 67.4 59.1 52.2 47.5 43.5 34.8 25.0 20.0 14.5 11.4 9.5 8.11 7.14 6.32 5.21 4.42 2.75 2.31
HZB12-80FA 140 120 105 93.6 83.8 76.5 70.0 56.0 40.3 31.8 22.6 17.7 14.6 12.5 11.0 9.73 8.01 6.82 4.34 3.68
HZB12-95FA 159 137 120 107 96.7 88.8 81.8 65.4 47.3 37.6 27.3 21.6 17.9 15.3 13.4 11.8 9.61 8.12 5.09 4.32
HZB12-95FA-2 146 127 108 95.7 84.9 76.9 70.5 56.1 40.3 31.6 22.6 17.8 14.8 12.5 10.9 9.66 7.95 6.77 4.24 3.58
HZB12-100FA 129 118 108 100 93.2 87.8 82.5 68.7 50.2 39.5 28.1 22.1 18.3 15.5 13.6 11.9 9.78 8.28 5.16 4.35
HZB12-125FA 187 160 141 126 113 103 94.3 76.8 57.4 46.8 35.0 28.5 24.3 21.2 18.9 16.9 14.2 12.2 7.83 6.63
HZB12-150FA 200 180 166 155 144 133 123 101 73.2 57.7 41.5 32.7 27.0 23.2 20.2 17.9 14.7 12.5 7.82 6.68
HZB12-180FA 296 255 224 198 178 162 149 119 87.0 69.1 50.6 40.1 33.2 28.2 24.6 21.8 17.9 15.2 9.46 7.99
o
End of Discharge Voltage = 1.80 DISCHARGE CURRENT in A 20 - 25 C
Model 15' 20' 25' 30' 35' 40' 45' 1 hr 90' 2 hr 3 hr 4 hr 5 hr 6 hr 7 hr 8 hr 10 hr 12 hr 20 hr 24 hr
HZB12-30FA 56.1 46.5 39.7 35.1 30.9 27.8 25.1 19.7 14.1 11.2 8.18 6.59 5.49 4.71 4.15 3.68 3.02 2.57 1.61 1.37
HZB12-40FA 76.0 63.5 52.6 45.8 40.3 36.3 32.9 25.8 18.7 14.8 10.7 8.54 7.19 6.15 5.43 4.80 3.93 3.32 2.04 1.71
HZB12-55FA 106 85.8 72.0 63.1 55.8 50.7 46.5 37.1 26.7 21.4 15.5 12.2 10.1 8.67 7.63 6.75 5.56 4.72 2.94 2.47
HZB12-80FA 152 129 111 98.2 87.1 79.1 72.1 57.6 41.3 32.5 23.0 18.0 14.9 12.7 11.1 9.8 8.09 6.89 4.39 3.71
HZB12-95FA 170 147 128 115 103 94.8 87.4 69.9 50.6 40.2 29.2 23.1 19.1 16.3 14.3 12.6 10.3 8.67 5.44 4.61
HZB12-95FA-2 156 135 115 102 90.7 82.2 75.3 60.0 43.0 33.8 24.2 19.1 15.8 13.4 11.7 10.3 8.49 7.23 4.53 3.83
HZB12-100FA 138 126 115 107 100 93.8 88.1 73.4 53.6 42.2 30.0 23.6 19.5 16.6 14.5 12.8 10.4 8.84 5.51 4.65
HZB12-125FA 216 183 159 141 127 115 105 84.8 62.5 50.3 37.0 29.8 25.2 22.0 19.4 17.4 14.7 12.6 8.00 6.78
HZB12-150FA 214 193 178 165 154 142 132 108 78.2 61.6 44.3 34.9 28.8 24.8 21.6 19.1 15.7 13.3 8.35 7.14
HZB12-180FA 316 273 239 211 190 173 159 127 92.9 73.9 54.0 42.8 35.4 30.1 26.3 23.2 19.1 16.2 10.1 8.53
Front Access AGM Construction - The AGM Technology - AGM technology has a number of advantages
positive and negative grids are cast from a over the equivalent Gel battery range, the main advantages for the
calcium/tin lead alloy to reduce grid growth Telecommunication applications are as follows:
and corrosion.
! Increased capacity over shorter discharge times.
! Lower initial cost.
! Ideal for starting and stationary applications.
! More suitable for UPS stand-by where power outages are
The active material is manufactured from a
uncommon.
high purity lead (99.9999%) to minimize the
! Smaller size battery can be used for higher rate discharges.
impurities, which would cause corrosion and
self-discharge. Haze only employ “S wrapping” in our AGM construction to further
reduce the possibility of short circuits due to mossing. Closely
controlled plate density and thickness results in excellent consistent
performance when placed in a string (series connection)
The separator is mat of random woven glass Batteries are manufactured under a quality system designed to meet
fibres, they are completely acid resistant and act and exceed ISO 9002.
as a sponge soaking up and immobilizing the
acid whilst keeping the acid available when it is
needed during periods of battery discharge. “S
Wrapping” is employed to reduce the risk of
short circuit due to mossing or debris at the Central Gassing - Haze
bottom of the cell. produce all models with an
integral central gassing
system. This system is a
useful feature when
The purpose of the separator is to maintain a batteries are installed in an
constant distance between the positive and IP66 cabinet. Sealed
negative plates, totally eliminating the enclosures prevent any
possibility of short circuits whilst allowing the escaping gas from exiting,
active materials to fully react with the central gassing however
electrolyte. The separator also has an open allows a tube carrying the
construction, which offers little resistance to the emissions to pass through
flow of the electrolyte during filling. a seal to atmosphere.
End of Discharge Voltage = 1.85 DISCHARGE IN WATTS PER CELL 20 - 25 oC
Model 15' 20' 25' 30' 35' 40' 45' 1 hr 90' 2 hr 3 hr 4 hr 5 hr 6 hr 7 hr 8 hr 10 hr 12 hr 20 hr 24 hr
HZB12-30FA 107 88.7 76.0 66.2 58.1 52.8 48.2 38.3 27.8 22.0 15.6 12.2 10.03 8.55 7.44 6.57 5.45 4.64 2.97 2.52
HZB12-40FA 120 100 88.1 79.3 71.8 65.8 60.5 49.0 35.5 28.0 19.9 15.7 13.1 11.3 9.92 8.83 7.30 6.19 3.89 3.29
HZB12-55FA 177 156 137 123 110 99.5 90.9 72.2 52.0 40.8 28.9 22.6 18.7 16.0 14.0 12.4 10.1 8.59 5.37 4.54
HZB12-80FA 242 213 189 170 155 142 131 106 77.0 60.5 43.1 33.9 27.9 23.8 20.7 18.4 15.2 13.0 8.34 7.09
HZB12-95FA 304 259 229 205 185 170 157 125 92.6 73.6 53.0 42.3 35.5 30.5 26.9 24.0 19.8 16.8 10.3 8.68
HZB12-95FA-2 276 236 207 184 166 152 140 113 81.9 64.6 45.8 36.2 30.1 25.9 22.6 20.0 16.3 13.8 8.4 7.02
HZB12-100FA 263 239 219 205 191 178 164 131 93.6 75.0 54.3 43.0 35.9 30.7 26.8 23.7 19.4 16.3 10.0 8.43
HZB12-125FA 365 318 277 247 225 208 194 162 123 100 74.7 59.6 51.8 42.0 38.8 34.4 28.6 24.5 15.9 13.5
HZB12-150FA 391 356 334 308 290 270 251 208 149 119 85.6 67.3 55.4 47.1 40.8 36.0 29.4 24.8 15.2 12.9
HZB12-180FA 545 477 418 367 328 301 279 227 167 133 95.7 76.0 63.4 54.3 47.4 41.8 34.2 28.9 18.0 15.2
o
End of Discharge Voltage = 1.70 DISCHARGE IN WATTS PER CELL 20 - 25 C
Model 15' 20' 25' 30' 35' 40' 45' 1 hr 90' 2 hr 3 hr 4 hr 5 hr 6 hr 7 hr 8 hr 10 hr 12 hr 20 hr 24 hr
HZB12-30FA 124 103 88.3 76.9 67.5 61.3 56.0 44.5 32.3 25.6 18.1 14.2 11.7 9.93 8.64 7.63 6.33 5.39 3.45 2.92
HZB12-40FA 140 116 102 92.1 83.3 76.4 70.2 56.9 41.2 32.5 23.1 18.2 15.2 13.1 11.5 10.3 8.47 7.19 4.51 3.82
HZB12-55FA 206 181 159 143 127 116 106 83.8 60.4 47.4 33.5 26.2 21.7 18.5 16.2 14.4 11.8 9.98 6.24 5.28
HZB12-80FA 278 236 206 184 166 151 139 112 80.7 63.4 44.8 35.1 28.9 24.6 21.5 19.0 15.7 13.4 8.55 7.28
HZB12-95FA 353 301 266 238 214 197 182 146 108 85.5 61.6 49.2 41.2 35.4 31.2 27.8 23.0 19.5 12.0 10.08
HZB12-95FA-2 320 274 241 214 193 177 162 131 95.1 75.0 53.2 42.1 35.0 30.0 26.3 23.3 19.0 16.0 9.71 8.15
HZB12-100FA 305 277 255 238 222 206 190 152 109 87.1 63.0 49.9 41.7 35.7 31.2 27.5 22.5 19.0 11.6 9.79
HZB12-125FA 435 365 314 277 250 228 211 175 131 106 78.1 62.3 54.1 43.6 40.4 35.8 29.8 25.5 16.4 13.9
HZB12-150FA 454 414 388 358 337 314 292 241 173 138 99.4 78.2 64.4 54.7 47.4 41.8 34.2 28.8 17.7 14.9
HZB12-180FA 633 554 486 426 381 350 324 264 194 155 111 88.3 73.6 63.0 55.0 48.6 39.7 33.5 20.9 17.6
End of Discharge Voltage = 1.65 DISCHARGE IN WATTS PER CELL 20 - 25 oC
Model 15' 20' 25' 30' 35' 40' 45' 1 hr 90' 2 hr 3 hr 4 hr 5 hr 6 hr 7 hr 8 hr 10 hr 12 hr 20 hr 24 hr
HZB12-30FA 126 104 89.4 77.8 68.4 62.1 56.7 45.0 32.7 25.9 18.3 14.4 - - - - - - - -
HZB12-40FA 142 118 104 93.3 84.4 77.4 71.1 57.6 41.8 32.9 23.4 18.5 - - - - - - - -
HZB12-55FA 209 183 161 145 129 117 107 84.9 61.1 48.0 34.0 26.6 - - - - - - - -
HZB12-80FA 284 240 209 186 167 153 140 113 81.4 63.8 45.2 35.3 - - - - - - - -
HZB12-95FA 358 305 269 241 217 200 184 147 109 86.5 62.4 49.8 - - - - - - - -
HZB12-95FA-2 325 278 244 217 195 179 164 133 96.3 76.0 53.9 42.6 - - - - - - - -
HZB12-100FA 309 281 258 241 225 209 193 154 110 88.2 63.8 50.5 - - - - - - - -
HZB12-125FA 443 368 316 279 251 230 213 176 131 106 78.1 62.6 - - - - - - - -
HZB12-150FA 460 419 393 362 341 318 296 244 176 140 101 79.2 - - - - - - - -
HZB12-180FA 641 561 492 431 386 354 328 267 196 157 113 89.4 - - - - - - - -
80
Applications
Residual Capacity %
60 § Float service
§ Uninterruptible Power Supplies
40 § Medical
50 C
§ Telecommunications
40 C
20 30 C § Switch Gear
20 C § Photovoltaic
0 § Solar
0 5 10 15 § Wind
Storage Time (Months)
§ Control Systems
§ Cellular Radio Stations
§ Cathodic Protection
§ Navigation Aids
§ Marine equipment
§ Electric Power Systems
End of Discharge Voltage = 1.85 DISCHARGE CAPACITY Ah 20 - 25 oC
Model 15' 20' 25' 30' 35' 40' 45' 1 hr 90' 2 hr 3 hr 4 hr 5 hr 6 hr 7 hr 8 hr 10 hr 12 hr 20 hr 24 hr
HZB12-30FA 13.1 14.5 15.7 16.4 16.9 17.3 17.7 18.5 19.8 21.0 23.0 24.7 25.7 26.5 27.2 27.7 28.3 28.9 30.2 30.9
HZB12-40FA 17.8 19.8 20.8 21.5 22.1 22.6 23.1 24.1 26.2 27.7 30.0 32.0 33.6 34.6 35.6 36.1 36.8 37.3 38.1 38.4
HZB12-55FA 24.9 26.8 28.4 29.5 30.6 31.6 32.7 34.8 37.5 40.0 43.5 45.8 47.3 48.8 50.0 50.8 52.1 53.0 55.0 55.4
HZB12-80FA 35.0 40.1 43.7 46.8 49.1 51.0 52.5 56.0 60.5 63.6 67.8 70.6 73.1 75.0 76.8 78.2 80.1 81.8 86.9 88.2
HZB12-95FA 39.7 45.8 50.5 53.7 56.7 59.2 61.3 65.4 71.0 75.2 81.9 86.5 89.5 91.9 93.5 94.6 96.1 97.4 102 104
HZB12-95FA-2 36.5 42.2 45.4 47.9 49.7 51.3 52.9 56.1 60.4 63.3 67.9 71.4 73.8 75.5 76.5 77.6 79.5 81.2 84.8 86.0
HZB12-100FA 32.3 39.3 44.9 50.0 54.6 58.5 61.9 68.7 75.3 79.0 84.3 88.2 91.3 93.3 94.9 96.0 97.8 99.4 103 105
HZB12-125FA 47.7 54.5 59.8 64.3 67.2 69.8 72.2 78.3 87.9 95.4 107 116 124 130 135 139 145 150 160 162
HZB12-150FA 50.0 60.2 69.3 77.4 84.3 88.7 92.6 101 110 115 124 131 135 139 142 144 147 150 156 160
HZB12-180FA 74.1 85.1 93.1 98.9 104 108 112 119 131 138 152 160 166 169 172 175 179 183 189 192
o
End of Discharge Voltage = 1.60 DISCHARGE CAPACITY Ah 20 - 25 C
Model 15' 20' 25' 30' 35' 40' 45' 1 hr 90' 2 hr 3 hr 4 hr 5 hr 6 hr 7 hr 8 hr 10 hr 12 hr 20 hr 24 hr
HZB12-30FA 15.6 17.2 18.6 19.5 20.1 20.6 21.0 21.9 23.5 25.0 27.3 29.3 - - - - - - - -
HZB12-40FA 21.1 23.5 24.7 25.5 26.3 26.9 27.4 28.6 31.1 32.9 35.7 38.0 - - - - - - - -
HZB12-55FA 29.5 31.8 33.8 35.1 36.3 37.6 38.8 41.3 44.6 47.5 51.7 54.3 - - - - - - - -
HZB12-80FA 42.9 47.0 49.6 51.7 53.7 55.1 56.6 59.6 63.8 66.6 70.7 73.8 - - - - - - - -
HZB12-95FA 47.2 54.4 60.0 63.8 67.3 70.3 72.9 77.7 84.3 89.3 97.3 103 - - - - - - - -
HZB12-95FA-2 43.4 50.1 54.0 56.8 59.1 60.9 62.8 66.7 71.8 75.2 80.6 84.8 - - - - - - - -
HZB12-100FA 38.3 46.6 53.3 59.4 64.8 69.5 73.5 81.6 89.4 93.8 100 105 - - - - - - - -
HZB12-125FA 64.3 71.1 76.2 80.2 83.7 86.9 89.8 96.0 104 110 121 129 - - - - - - - -
HZB12-150FA 59.4 71.4 82.3 91.9 100 105 110 120 130 137 148 155 - - - - - - - -
HZB12-180FA 87.5 101 110 117 123 128 132 140 154 163 179 189 - - - - - - - -
SAFETY RELEASE VALVE- The battery will operate above atmospheric pressure under
normal operating conditions, however the maximum pressure is governed by the safety
release valve. Open is activated by pressures in excess of approx. 2 psi (14 Kpa), resealing
at approx 1.2 psi (8.4 Kpa).
FIR
QUA
1 Hour to 100 Hours 28% 41% 58% 73% 79% 86% 94% 100% 104% 106% 107% 108%
Dimensions (Inches) & approx w eight Internal M a xi m u m
Battery Mod el Qty Per Dimensions (mm) & approx weight (kg) (Lbs) Terminal Resistance Charge
Box Length W i d th Height W e i gh t Length W i d th Height W e i gh t Layout mOhms Current
HZB12-30FA 1 225 99 225 10.1 8.86 3.90 8.86 22.3 M5 5 7.5
HZB12-40FA 1 225 99 225 13.1 8.86 3.90 8.86 29.0 M5 5 10
HZB12-55FA 1 277 105 223 17.9 10.91 4.13 8.78 39.6 M6 4.3 15
HZB12-80FA 1 563 114 182 26.8 22.17 4.49 7.17 59.2 M6 3.6 20
HZB12-95FA 1 507 109 227 32.5 19.96 4.29 8.94 71.8 M6 4.1 25
HZB12-95FA-2 1 395 105 257 27.5 15.55 4.13 10.12 60.8 M6 3.8 25
HZB12-100FA 1 395 110 285 32.6 15.55 4.33 11.22 72.0 M6 3.6 30
HZB12-125FA 1 417 172 240 46.0 16.42 6.77 9.45 101.7 M6 2.9 35
HZB12-150FA 1 550 109 286 48.5 21.65 4.29 11.26 107.2 M6 3.1 40
HZB12-180FA 1 560 125 320 57.9 22.05 4.92 12.60 128.0 M8 2.9 45
Physical Information
7%
3%
CHARGING CHARACTERISTICS
Floating - The optimum float voltage for a battery is
temperature dependant, at 15 - 24oC the recommended
value is 2.27 - 2.30V. It is recommended that battery
installation sites are temperature controlled, however float
Recommended voltage can be increased or decreased to compensate for
Operating Applied Float Voltage temperature variations. Adjustment is calculated at +/- 3
Temperature VPC mV per degree C.
0-9 2.33 - 2.35
The most suitable charging method for battery life and
10-14 2.30 - 2.33 performance is the constant voltage method with a limited
initial current, usually limited to a maximum of C20/4.
15-19 2.27 - 2.30
20-24 2.27 - 2.30
25-29 2.25 - 2.27
30-34 2.23 - 2.25
35-40 2.21 - 2.23
414
458
99 6
110 6
225
395
12-30&40 Front Access
Battery Height: 225mm
438
105 6
706
172 6
114 6
417
563
515
550
109 6
146 221.5
450
518
125 6
482.5
465
12-90&95 Front Access
Battery Height: 227mm
438
105 6
560
117.8 221.5
450
395
508 347
5 6
5 6
25
25
278 x 2
340.2 x 2
1150
1370
278
340.2
100
100
Front View Side View
Front View Side View
16 x 12V50FA&55FA Rack
508 437 16 x 12V100FA Rack
5 6 524 620
5 6
25
25
312 x 2
339.2 x 2
1280
1365.6
339.2
312
100
100
16 x 12V95FA-2 Rack 5 6
cost savings.
Product Range
Website: www.hazebattery.com
E mail [email protected]
061112
EMC
Germany
tested
AD
LE
RUBBISH BIN
RE
TU
RN
R
RECYCLE
Pb
Haze Battery Company keenly encourages
environmental awareness; PLEASE follow
guidelines for the recycling /disposal of lead.