SPECIFICATIONS
DC SUPPLY
CONTINUOUS VOLTAGE RATING
AUTO MAINS FAILURE CONTROL MODULE 8 V to 35 V Continuous
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing
supply was at least 10 V before dropout and
supply recovers to 5 V. This is achieved
without the need for internal batteries.
LEDs and backlight will not be maintained
during cranking.
MAINS (UTILITY)
VOLTAGE RANGE
15 V to 415 V AC (Ph to N)
26 V to 719 V AC (Ph to Ph)
KEY FEATURES • 3 engine maintenance alarms KEY BENEFITS
• Load unbalanced alarm • Engine speed protection • Automatically transfers between FREQUENCY RANGE
• Configurable for use as an auto • Engine hours counter mains (utility) and generator 3.5 Hz to 75 Hz
start and AMF control module • Engine pre-heat • Hours counter provides accurate OUTPUTS
• J1939-75 support and CAN alarm • Engine run-time scheduler information for monitoring and OUTPUT A (FUEL)
ignore functon • Engine idle control for starting & maintenance periods 10 A short term, 5 A continuous,
• Alternator frequency & CAN speed stopping • User-friendly set-up and button at supply voltage
sensing in one variant • Tier 4 engine instrumentation layout for ease of use OUTPUT B (START)
• Largest back-lit icon display in its screens • Multiple parameters are monitored 10 A short term, 5 A continuous,
class • Battery voltage monitoring simultaneously which are clearly at supply voltage
• Heated display option • Start on low battery voltage displayed on the large back-lit AUXILIARY OUTPUTS C, D, E & F
• Real time clock provides accurate • Configurable remote start input icon display. 2 A DC at supply voltage
event logging • 1 alternative configuration • The module can be configured to
• Comprehensive warning, electrical GENERATOR
• Fully configurable via the fascia or suit a wide range of applications
VOLTAGE RANGE
PC using USB communication trip or shutdown protection upon • Uses DSE Configuration 15 V to 415 V AC (Ph to N)
• Extremely efficient power save fault condition Suite PC Software for simplified 26 V to 719 V AC (Ph to Ph)
mode • LCD alarm indication configuration
FREQUENCY RANGE
• 3 phase generator sensing • Event log (50) • Compatible with a wide range of 3.5 Hz to 75 Hz
• 3 phase mains (utility) sensing • Fuel solenoid pulling circuit CAN engines including Tier 4
• Compatible with 600 V ph to ph • On-screen line diagram on/off • Licence-free PC software DIMENSIONS
OVERALL
nominal systems functionality • IP65 rating (with optional gasket) 140 mm x 113 mm x 43 mm
• Generator/load power monitoring • Configurable CAN instrumentation offers increased resistance to water 5.5’’ x 4.4” x 1.7”
(kW, kV A, kV Ar, pf) (10) ingress
• Accumulated power monitoring • Water in fuel digital input PANEL CUT-OUT
118 mm x 92 mm
(kW h, kVA h, kVAr h) • Tank bund alarm digital input 4.6’’ x 3.6”
• Generator overload protection (kW) • Generator at rest output
• Generator/load current monitoring • ECU periodic wake-up for MAXIMUM PANEL THICKNESS
8 mm
and protection information retrieval 0.3”
• Fuel and start outputs (configurable • Back-light power-save mode
when using CAN) • Adjustable delay crank timer STORAGE TEMPERATURE RANGE
• 4 configurable DC outputs • Pre/post heat functionality -40 °C to +85 °C
-40 °F to +185 °F
• 3 configurable analogue/digital • Overload protection
inputs • Mains/generator A/C system OPERATING TEMPERATURE RANGE
• 4 configurable digital inputs selection -30 °C to +70 °C
-22 °F to +158 °F
• Configurable staged loading • Output timer for external audible
outputs alarm