Aqua4Trans FM New
Aqua4Trans FM New
Aqua4Trans FM New
Demineralisers
Reverse osmosis
Concentration (regenerations)
Waste streams
Desalination
Industrial wastewater
Cooling water
RO plants
Specifications
Display Backlit display dot matrix (128 x 64 dot matrix liquid crystal display)
Programmable for multichannel display of measured value, temperature, units and error
messages
Keypad Tactical 4 keys for menu, up/down scroll, enter, menu interface
Input Analogue Sensors; pH, ORP, conductivity/ TDS, chlorine, turbidity, TSS, 4-20 mA
Output Dual current output per channel, 4-20 mA DC, galvanically isolated, max load 750Ω
Option of linear, bilinear and logarithmic
Maths functions % accepted : X/Y*100 [%]
% rejection : (1-X/Y)* 100 [%]
Difference : X-Y
Addition : X+Y
Comparator or ratio function : X/Y or Y/X
Note - X, Y : channel 1 or 2
Temperature -20 to 200 Deg C
Pt100, Pt1000, 2 wire
Temperature compensation, linear (ref. temp – 25 Deg.C) auto/manual
Modules Factory installed function cards can be reconfigured in the field
Parameters Card 1: communication RS 485 (MODBUS-RTU)
Card 2: pH, ORP, conductivity, TDS, Chlorine, Turbidity, TSS, 4-20 mA
Card 3: pH, ORP, conductivity, TDS, Chlorine, Turbidity, TSS, 4-20 mA
Card 4: Relay 6 nos. Rated 250 VAC 5A
Power 110 - 240 VAC, 50/60 Hz (UPS recommended), 40 watt
Electrical EMC : IEC 61326-1
Vibration : IEC 60068-2-6
Ingress Protection (IP) : IEC60529
Safety/LVD : IEC/EN 61010-1 CE Compliant*
Service test Current: test current can be specified for output 1 and 2
In-built power supervisory circuit for data integrity and memory
Display of last error that occurred
Sensor test, display of direct, raw sensor signal
Housing MOC polycarbonate, 10% glass filled
Colour RAL 9007
Panel, wall and 2” pipe mounting
Ingress protection IP66
Dimensions H 144mm X W 144mm X Depth 103mm
Cable Gland M20 X 6 nos
Weight 1 Kg
Environmental Ambient temperature: -20 to 60 DegC
Transport, storage temperature: -20 to 80 DegC
Relative humidity: 95% at temperature up to 55 DegC
pH / ORP Measurement
Measurement Range Unit Resolution Accuracy
pH 0 to 14 pH 0.01 ± 0.01 pH
ORP -2000 to +2000 mV 1 ± 1 mV
Temperature -20 to 200 Deg C ºC 0.1 ±0.5% of full scale
Conductivity Measurement
Measurement Range Unit Resolution Accuracy
Cell K: 0.01 0 µS/cm to 20 µS/cm µS/cm, ms/cm 0.01 µS/cm ±0.5% of FS
Cell K: 0.01 0 µS/cm to 200 µS/cm µS/cm, ms/cm 0.1 µS/cm ±0.5% of FS
Cell K: 0.1 0 µS/cm to 2000 µS/cm µS/cm, ms/cm 0.1 µS/cm ±0.5 % of FS
Cell K: 1 0 µS/cm to 20 ms/cm ms/cm 0.01 ms/cm ±0.5 % of FS
Cell K: 10 0 µS/cm to 200 ms/cm ms/cm 0.1 ms/cm ±0.5 % of FS
TDS Measurement
Measurement Range Unit Resolution Accuracy
Cell K: 0.01 0 to 140 mg/L mg/L, g/L 0.01 mg/L ±0.5 % of FS
Cell K: 0.1 0 to 1400 mg/L mg/L, g/L 0.1 mg/L ±0.5 % of FS
Cell K: 1 0 to 14 g/L g/L 0.01 g/L ±0.5 % of FS
Cell K: 10 0 to 140 g/L g/L 0.1 g/L ±0.5 % of FS
* Note: Above range with TDS factor as 0.7 other factor user programmable
C1 Card Input # 1
0 Nil
1 RS485 MODBUS
C2 Card Input # 2
1 pH
2 Redox/ORP
3 Conductivity/Ratio
4 TDS
5 Chlorine
6 Turbidity
7 TSS
8 Analogue Input Card(DO)
C3 Card Input # 3
0 Nil
1 pH
2 Redox/ORP
3 Conductivity /Ratio
4 TDS
5 Chlorine
6 Turbidity
7 TSS
8 Analogue Input Card (DO)
C4 Card Input # 4
0 Nil
1 Relay- 6 nos
C5 Configuration*
00 Default
01 Ratio conductivity
Mounting Drawings
2'’ pipe
Wall mounting
DOC#FMPA/1219/1563/V3.R4