DC Switch-Disconnectors
▘DC 1500V class 4000AF Switch-Disconnectors
Applications
▘Circuit breakers and Switch-Disconnectors
for DC systems such as UPS, PV, and ESS
1500Vdc class
DC Air Circuit Breakers
DC Switch-Disconnectors
1500Vdc class
DC Switch-Disconnectors
Contents
• External configuration 16
• Accessories 18
• Ordering 20
• DC ACB Trip relays 24
• Accessories 26
• Busbar connection 55
• Control circuit diagram 62
• Dimensions 66
• Technical information 80
• Time chart 85
• Ordering sheet 90
1500Vdc class Air Circuit Breakers
Air Circuit Breaker with DC Relay
Various protection functions and fault waveform provided
Electrical endurance with 10,000 operations
1600AF 4000AF
H = 430mm
3P 4P
60kA@750Vdc 70kA@750Vdc
50kA@1500Vdc 60kA@1500Vdc
ADV-16E ADV-40E
800AF 800A 1600AF 1600AF
1000AF 1000A 2000AF 2000AF
1250AF 1250A 2500AF 2500AF
1600AF 1600A 3200AF 3200AF
4000AF 4000AF
4
1500Vdc class Switch-Disconnectors (DDH/DDV)
Suitable for severe inductive DC loads (DC-23A)
World's largest short-time capacity: 100kA / 1sec
800~2500AF 800~4000AF
H = 430mm
4P 4P
5
DC Air Circuit Breakers
1. 1500Vdc 4000AF Air Circuit Breaker for low voltage DC power distribution system
2. Optimized breaker for UPS, PV, ESS system application
3. Maximum short-time capacity 65kA/1sec
4. DC Multi-Function Relay:
A, V, W Protection & measurement, self-diagnosis and fault waveform recording
5. Compatible with existing Susol ACB
Features
• Basic rating
- Rated voltage: 1500Vdc (4p) / 1000Vdc (3p)
- Rated current: 800 ~ 4000A
- Short-time capacity: 65kA/1sec
- Breaking capacity: 70kA @ 750Vdc, 60kA @ 1500Vdc
•E
lectrical endurance:
- 10,000 operations (1600A @ 1500Vdc)
- 600 operations (4000A @ 1500Vdc)
6
DC Switch-Disconnectors DC ACB
Features
800~2500AF
• Basic rating
- Rated voltage: 1500Vdc (DDV type), 1200Vdc (DDH type)
- Rated current: 800 ~ 2500A
- Icw = 100kA / 0.4s
- Utilization Category: DC-23A
• Electrical endurance:
- 2,000 operations (1600A @ 1500Vdc)
- 1,000 operations (2500A @ 1500Vdc)
• Optional Short-Busbar considering temperature performance
• Compatible with existing Susol ACB
- Accessories including closing and trip coils
- Physical sizes for installation
• Applicable standards and tests: IEC 60947-3, CQC certification
800~4000AF
• Basic rating
- Rated voltage: 1500Vdc (DDV type), 1200Vdc (DDH type)
- Rated current: 800 ~ 4000A
- Icw = 100kA / 1s
- Utilization Category: DC-23A
• Electrical endurance:
- 10,000 operations (1600A @ 1500Vdc)
- 2,000 operations (4000A @ 1500Vdc)
• Optional Short-Busbar considering temperature performance
• Compatible with existing Susol ACB
- Accessories including closing and trip coils
- Physical sizes for installation
• Applicable standards and tests: IEC 60947-3, DEKRA CB certification
7
DC Air Circuit Breakers
ADV 32 E 4 16 A
Total < Icw (ms) Less than 75ms under Icw Less than 75ms under Icw
Breaking
Operation time time > Icw (ms) Less than 25ms over Icw Less than 25ms over Icw
Closing time (ms) Less than 80ms Less than 80ms
Mechanical and Electrical Life cycle
Mechanical (times) 15,000 15,000
Endurance (times) Electrical
lessw than 1600A (times) 10,000 10,000
(Without maintenance) (at 1000 2000A (times) 8,000 8,000
V DC)
2500A (times) - 5,000 3,000 500 - 5,000 3,000 500
Demension and Weight
Without cradle (kg) 43 / 53 43 / 53
Drawout
Weight (3P/4P) With cradle (kg) 87 / 103 87 / 103
Fixed (kg) 44 / 55 44 / 55
External dimensions Drawout 3P(4P) (mm) 430×412(527)×375 430×412(527)×375
(H×W×D) Fixed 3P(4P) (mm) 300×378(493)×295 300×378(493)×295
DDH 40 E 4 00 A
Electrical characteristics
Specification
DDH/DDV-20D DDH/DDV-40E
65kA/1s 100kA/1s
Rated short-time withstand current (Icw)
100kA/0.4s 1) 150kA/0.05s
Openning 40ms
Operation time (ms)
Closing 80ms under
Draw-out type
Version
Fixed type
Type DDH-08D DDH-10D DDH-13D DDH-16D DDH-20D DDH-08E DDH-10E DDH-13E DDH-16E DDH-20E DDH-25E DDH-32E DDH-40E
Frame size (AF) 800 1000 1250 1600 2000 800 1000 1250 1600 2000 2500 3200 4000
Type DDV-08D DDV-10D DDV-13D DDV-16D DDV-20D DDV-25D DDV-08E DDV-10E DDV-13E DDV-16E DDV-20E DDV-25E DDV-32E DDV-40E
Frame size (AF) 800 1000 1250 1600 2000 2500 800 1000 1250 1600 2000 2500 3200 4000
Time const 2ms 9,000 6,000 4,000 2,000 1,500 1,000 10,000 8,000 5,000 3,000 2,000
11
Trip Relay
Overload protection
• Long-time delay
• Thermal
Short-circuit protection
• Short-time delay/Instantaneous
• I²t On/Off optional (for short-time delay)
Ground fault protection
• I²t On/Off optional
• Alarm/Trip selectable
Protection against Over voltage/Under voltage/
Unbalance/Reverse power
ZSI (Zone Selective Interlocking) for protective coordination
Measurement and Display
• Measurement for Current/Voltage/ Power/Energy/Demand
• 128 x 128 Graphic LCD
Start-up
•A voiding breaker trip due to inrush and starting current of specified load
such as motor
Load control
• Providing
output contacts to have non-critical loads disconnected for
Rating Plug efficient power management
Fault recording
•R ecords Max. up to 128 fault information about fault type, fault phase, fault
Easy to change rated current (In) value, occurrence time of fault
without CT replacement • F ault wave recording: the latest 4 fault waveform, each waveform recorded
during 128ms before and after the fault
• Rating Plugs for 1600AF: 800, 1000, 1250, 1600A
• Rating Plugs for 2500AF: 1600, 2000, 2500A Event recording
• Rating Plugs for 3200AF: 1600, 2000, 2500, 3200A •R ecords events of device related to setting change, operation and state
• Rating Plugs for 4000AF: 2000, 2500, 3200, 4000A change. (Max. up to 128)
13
Connection
Diverisified terminal connection methods of the DC ACB main circuit for users.
14
Various installation methods DC ACB
Standard
connection
Mixed
connection
15
External configuration
DC ACB
❸
❹
❺
❶
❻
❼
❽
❾
❷
Marking
[Acronym explanation] [Secondary nameplate]
Explanation of terminologies
• Motor charge
Control power
• Closing coil
and terminal No.
• Shunt tripping coil
•Auxiliary switches: Contact
specification and terminal No.
• Under voltage trip: UVT terminal No.
• OCR control source: Trip relay control
power
• Alarm switch: Alarm and terminal No.
• Digital trip relay: Switching diagram
• Z.S.I: Input/Output terminal No.
• Ui: Rated insulation voltage • Reset: LED/LCD reset
• Uimp: Impulse withstand voltage •Communication: Communication and
• Ue: Rated operational voltage terminal No.
• Icu: Ultimate breaking capacity
• Ics: Service breaking capacity
• Icw: Short time withstand capacity
• Icm: Rated making capacity
• MFG. Date: Manufacturing date
16
DC ACB
DC Switch-Disconnectors
❸
❹
❺
❻
❼
❽
❾
❷
Terms
➊ Trip relay ➒ ON/OFF Indicator Pad lock button
➋ Operation counter ➓ Corporation logo Arc chute
➌ OFF button Zero Arc space Control terminal block
➍ ON button Safety control cover Rating Plug
➎ Product series Cradle Isolator
➏ Manual charging handle Draw-out handle
➐ Name plate Position indicator
➑ Charging indicator Handle inserting hole
17
Accessories
Counter (C)
Motor (M)
18
DC ACB
Cradle
Miss Insertion Prevent Device (MIP)
19
Ordering
ADV 32 E 4 16 A
DC ACB cradle
DAL H06~32E3 4 A H E S
Type Rated current and No. of pole Secondary External Safety shutter Zero arc space
connections connections
DAL Constant>2ms body frame 3 3Pole Without With Arc
Automatic H Horizontal type E S
A safety shutter cover
800AF 4 4Pole connection
V Vertical type With
1000AF F
Upper-Horizontal/ safety shutter
M
H06~ 1250AF Lower-Vertical
32E 1600AF Upper-Vertical/
N
Lower-Horizontal
2000AF
P Front (Flat) type
2500AF
Note) 25D and 40E only provided
V32E 3200AF with vertical type
20
DC ACB
DC ACB accessories
M1 D1 D1 AX SD1 U1 AL
Motor rated voltage Closing coil rated voltage Shunt coil rated voltage Trip relay UVT coil rated voltage Option table
MA Without motor D0 Without closing coil D0 Without Shunt coil SD1 DC U0 Without UVT Coil
M1 AC/DC 100V~130V D1 AC/DC 100V~130V D1 AC/DC 100V~130V U1 AC/DC 100V~130V
M2 AC/DC 200V~250V D2 AC/DC 200V~250V D2 AC/DC 200V~250V Aux. contact & charging types U2 AC/DC 200V~250V
M3 DC 125V D3 DC 125V D3 DC 125V AX Standard OFF - Charge 3a3b U3 DC 125V
M4 DC 24V~30V D4 DC 24V~30V D4 DC 24V~30V AC Standard ON - Charge 3a3b U4 DC 24V~30V
M5 DC 48V~60V D5 DC 48V~60V D5 DC 48V~60V BX Standard OFF - Charge 5a5b U5 DC 48V~60V
M6 AC 380V~415V D6 AC 380V~480V D6 AC 380V~480V BC Standard ON - Charge 5a5b U6 AC 380V~480V
M7 AC 440V~480V D7 AC 48V D7 AC 48V HX High capacity OFF - Charge 5a5b U7 AC 48V
M8 AC 48V HC High capacity ON - Charge 5a5b * UVT Delay module is available
over AC/DC 48V
CC Standard ON - Charge 6a6b
JC High capacity ON - Charge 6a6b
GX High capacity OFF - Charge 3a3b
GC High capacity ON - Charge 3a3b
TX TCS OFF - Charge 4a4b Note)
TC TCS ON - Charge 5a5b Note)
Note) TCS: Trip Circuit Supervision
The terminal supervising trip circuit and
monitering disconnection or disable of trip
AL AL1 + MRB
A1 AL1 + MRB + RES (AC 110~130V) *AC private use
A2 AL1 + AL2 + MRB (Two a contacts are provided)
A3 AL1 + MRB + RES (DC 110-125V) *DC private use
A4 AL1 + MRB + RES (AC 200-250V) *AC private use
A5 AL1 + MRB + Autoreset
A6 AL1 + AL2 + MRB + Autoreset
A7 AL1 + MRB + RES (DC 110-125V) + Autoreset *DC private use
A8 AL1 + MRB + RES (AC 200-250V)+Autoreset *AC private use
A9 AL1 + MRB + RES (AC 110-130V)+Autoreset *AC private use
Z2 AL1 + AL2 + MRB (One a contact and one b contact are provided)
S CS2 Charge switch communication
B B ON/OFF Button lock
M MI Mechanical interlock
D DI or MOC Mechanism operated cell switch
K K1 Key lock
K2 K2 Key interlock set
K3 K3 Key lock double
R RCS Ready to close switch
T TM Temperature monitoring
H1 AC/DC 100~130V
H2 AC/DC 200~250V
H3 DC 125V
H4 SHT2 DC 24~30V Sencondary shunt coil
H5 DC 48~60V
H6 AC 380~480V
H7 AC 48V
21
Ordering
DDH 40 E 4 00 A
DC Switch-Disconnectors cradle
AL H06~32E3 4 A H E S
Type Rated current and No. of pole Secondary External Safety shutter Zero arc space
connections connections
DAL Constant>2ms body frame 3 3Pole Without With
Automatic H Horizontal type E S
A safety shutter arc cover
800AF 4 4Pole connection
V Vertical type With
1000AF F
Upper-Horizontal/ safety shutter
H06~ M
1250AF Lower-Vertical
20D
1600AF Upper-Vertical/
N
Lower-Horizontal
2000AF
P Front (Flat) type
H25D 2500AF
Note) 25D and 40E only provided
800AF with vertical type
1000AF
1250AF
H06~
1600AF
32E
2000AF
2500AF
3200AF
H40E 4000AF
22
DC ACB
DC Switch-Disconnectors accessories
M1 D1 D1 GX 000 U1 AL
Motor rated voltage Closing coil rated voltage Shunt coil rated voltage Trip relay UVT coil rated voltage Option table
MA Without motor D0 Without closing coil D0 Without Shunt coil 000 Without trip relay U0 Without UVT Coil
M1 AC/DC 100V~130V D1 AC/DC 100V~130V D1 AC/DC 100V~130V U1 AC/DC 100V~130V
M2 AC/DC 200V~250V D2 AC/DC 200V~250V D2 AC/DC 200V~250V Aux. contact & charging types U2 AC/DC 200V~250V
M3 DC 125V D3 DC 125V D3 DC 125V AX Standard OFF - Charge 3a3b U3 DC 125V
M4 DC 24V~30V D4 DC 24V~30V D4 DC 24V~30V AC Standard ON - Charge 3a3b U4 DC 24V~30V
M5 DC 48V~60V D5 DC 48V~60V D5 DC 48V~60V BX Standard OFF - Charge 5a5b U5 DC 48V~60V
M6 AC 380V~415V D6 AC 380V~480V D6 AC 380V~480V BC Standard ON - Charge 5a5b U6 AC 380V~480V
M7 AC 440V~480V D7 AC 48V D7 AC 48V HX High capacity OFF - Charge 5a5b U7 AC 48V
M8 AC 48V HC High capacity ON - Charge 5a5b * UVT Delay module is available
over AC/DC 48V
CC Standard ON - Charge 6a6b
JC High capacity ON - Charge 6a6b
GX High capacity OFF - Charge 3a3b
GC High capacity ON - Charge 3a3b
TX TCS OFF - Charge 4a4b Note)
TC TCS ON - Charge 5a5b Note)
Note) TCS: Trip Circuit Supervision
The terminal supervising trip circuit and
monitering disconnection or disable of trip
23
DC ACB Trip relays
24
DC ACB
Pick-up (A)
I
Isd = Ir ×... 150%~1000%, Off (5% Step)
Accuracy : ±10%
Instantaneous (OCR-I)
Pick-up (A) Ii = In ×... 150%~1000%, Off (5% Step)
I²t Off
Accuracy : 0.10s~3.00s, 0.05s Step
tg
±10% (Ig>0.4In) (In case of I²t On, @1 x In)
I²t On
I n
±20% (Ig≤0.4In)
25
Accessories
Main body
DC ACB
Mounting Type Accessories Remark Note1) Page
Standard Option
SHT 1 Shunt coil - * 28
SHT 2 Double Shunt coil - * 29
CC Closing coil - * 30
M Motor - * 31
CS1 Charge switch - * 31
DC Dust cover - -
OT OCR Tester - - 41
A Auto Connector - *
P1 Lower power input type (Fixed type only) - - 56
P2 Top power input type (Fixed type only) - - 56
Note) 1. * Seperate purchasing is not allowed. Each item should be purchased with the main body.
2. The temperature sensor is shipped inside the body, and temperature monitoring modules are sold separately.
26
DC ACB
Cradle
DC ACB
Mounting Type Accessories Remark Note) Page
Standard Option
SBC Shorting "b" contact - - 42
ST Safety shutter - * 44
STL Safety shutter lock - - 45
DF Door Frame - - 45
RI Racking interlock - - 49
PL Pad Lock / Position Lock - * 50
IB Interphase Barrier - Optional 46
Note) * Seperate purchasing is not allowed. Each item should be purchased with the main body.
27
Accessories
48~60 48 0.7~1.1 Vn
C1
100~130 100~130 0.7~1.1 Vn 200 5 40
Wiring diagram
2. Specification of the wire
• Refer to the below table regarding the length and specification of wire when using trip coil with DC 24~30V or DC
/ AC 48~60V of rated voltage.
28
DC ACB
48~60 48 0.7~1.1 Vn
C11
100~130 100~130 0.7~1.1 Vn 200 5 40
Wiring diagram
2. Specification of the wire
• Refer to the below table regarding the length and specification of wire when using trip coil with DC 24~30V or DC
/ AC 48~60V of rated voltage.
29
Accessories
30
DC ACB
Motor [M]
Main
axis
• It is a built-in contact which sends the signal to the outside, when motor charging is completed. (2a)
• It has a “1a” contact for communication and the other “1a” contact for complete charging.
• When using an extra communication module (Remote I/O), the state of contacts can be displayed through
the network.
• The electrical characteristics of the contact are the same as the AL contact, see page 33
31
Accessories
Note) Operating voltage range is the min. rated voltage standard for each rated voltage (Vn).
32
DC ACB
AL1, 1a •When a circuit breaker is tripped by OCR which operates against the fault current (Over Current Relay), Trip
AL2, 1a Alarm switch provides the information regarding the trip of circuit breaker by sending the electrical signal from
the mechanical indicator on front cover of main circuit breaker or internal auxiliary switch. (Installed at the
inside of circuit breaker)
•When a circuit breaker tripped by fault current, a mechanical trip indicator (MRB, Manual Reset Button) pops out
from the front cover and the switch (AL) which sends control signal electrically is conducted to output the
information occurred from fault circuit breaker.
•MRB and AL can be operated only when tripping by OCR, but doesn’t be operated by OFF button and OFF
operation of trip coil.
•For the manual reset type circuit breaker, to reset the circuit breaker after a circuit breaker trip, push the manual
reset button(MRB) manually or operate the remote reset button(RES). Push the reset button on the OCR to reset
the LED lamp and fault cause display relay contact (terminal 513~544) on the OCR.
- Option AL, A1, A2, A3, A4 applicable
• For the auto reset type circuit breaker, it can be reset when the interlock is automatically released after a circuit
breaker trip, and if the terminals R11, R22(dry contact) is set to Common, then the LED lamp and fault cause
display relay contact(terminal 513~544) on the OCR are remotely reset.
- Option A5, A6, A7, A8, A9 applicable
•One(AL1, ab) or two(AL1, AL2, 1a) electrical trip alarm(AL) switches are provided as an option according to the
order specifications.
• The AL2 and RES cannot be simultaneously used, so select only one option.
33
Accessories
• It is a function which resets a circuit breaker manually when a circuit breaker is tripped by OCR.
•When a circuit breaker tripped by fault current, a mechanical trip indicator (MRB, Manual Reset Button) pops
out from the front cover and the switch (AL) which sends control signal electrically is conducted to output the
information occurred from fault circuit breaker.
•MRB can be operated only by OCR but not by OFF operation of circuit breaker. To re-close a circuit breaker after
a trip, press MRB to reset it for closing.
34
DC ACB
• Following tripping, this function resets the "fault trip" alarm contacts (AL) and the mechanical indicator (MRB)
and enables circuit breaker closing.
Push button switch : AC 125V 10A, AC 250V 6A, DC 110V 2.2A, DC 220V 1.1A Resistive load
• In case of auto reset type circuit breaker Following tripping, a reset of Manual Reset Button(MRB) or Remote
Reset Switch (RES) is no longer required to enable circuit breaker closing.
The mechanical indicator (MRB) and electrical indicator (AL) remain in fault position until the reset button is
pressed.
2. Appearance
Wiring diagram
Connect to inner
micro switch
Connect to
AL2 / RES
35
Accessories
Counter [C]
Counter
36
DC ACB
High capacity
Classification Remark
Resistive load Inductive load
Minimum current DC5V, 1mA
490V 5A 2.5A
AC 250V 10A 10A
Contact 125V 10A 10A
capacity 250V 3A 1.5A
DC 125V 10A 6A
30V 10A 10A
HX 5a5b - Standard charging
GX 3a3b - type
No. of Contact
HC 5a5b -
that can be used Rapid auto-reclosing
JC 6a6b -
charging type
GC 3a3b -
37
Accessories
K1
Status
ACB–1 ACB–2 ACB–3
LOAD1 LOAD2
OFF OFF
ACB1 ACB2 OFF ON
ON OFF
ON ON
OFF OFF
OFF ON
ACB3
ON OFF
○ : Release ● : Lock
Load 1 Load 2
38
DC ACB
39
Accessories
Circuit diagram
88
75
C1 C6
15
Side view
AC input Condenser AC output
50 2-Ø6.5
15.5
8 M3.5
1 2 3 4 5 6
C3 C5
12.8
112
7 8 9 10 11 12
110.5 80
40
DC ACB
OCR Tester
Configuration
I_A I_B Power current / Load current
I_A I_B
ENT Info
Increase and decrease test
current magnitude
ENT Info
In Ir
I_A I_B
In Ir
complete
ENT Info MODE
In Ir
ENT Info
41
Accessories
Panel
Door
42
DC ACB
a1 a2 a3 a4 a5 b1 b2 b3 b4 b5 a1 a2 a3 a4 a5 b1 b2 b3 b4 b5
13 23 33 43 53 11 21 31 41 51 13 23 33 43 53 11 21 31 41 51
14 24 34 44 54 12 22 32 42 52 14 24 34 44 54 12 22 32 42 52
• When MOC link is installed to cradle, MOC can be equipped with the inside of panel.
43
Accessories
• It is used to interlock closing and trip between two or three breakers mechanically so as to prevent unintended
operation at the same time.
4000AF, 4P
44
DC ACB
Fixed type
45
Accessories
• Interphase barrier prevents the arc which may arise and result in short-circuit between
phases in advance
• As “C” stands for “CRADLE”, install the Interphase barrier in the direction of “C” in case of
Draw-out type.
• As “A” stands for “ACB main frame”, install the Interphase barrier in the direction of “A” in case
of Fixed type.
A C
135mm
50mm
46
DC ACB
<Contact configuration>
4C: 1Disconnected +1Test +2Connected
8C: 2Disconnected +2Test +4Connected
※ Contact configuration can be changeable if necessary.
Cell Switch
CL–C ON
(CONNECTED) OFF
Contact CL–T ON
operation (TEST) OFF
CL–D ON
(DISCONNECTED) OFF
Terminal (4C, 8C) comm. comm. comm. comm. comm. comm. comm. comm.
381 371 361 351 341 331 321 311
(341) (331) (321) (311)
4C attached to the right side of crad 4C attached to the left side of cradle
47
Accessories
48
DC ACB
Door plate
49
Accessories
Position lock
release button
Pad Lock
ACB is subject to restriction regarding moving in connected, test, disconnected when drawing in or
out. If main body of ACB is placed in 3 positions, it is locked and stopped when drawing in or out.
• As shown in the figure, if draw-in / out button pops out, it means locking is operating.
• To continue Draw-in / out operation, release lock by pushing Draw-in / out button
• In case it is locked as shown in the figure above, main body of ACB can not be drawn in or
out into the cradle.
• For the lock device, user has to purchase it. (Ø5 ~ Ø6)
50
DC ACB
1
A
2
B 3
C 4
D 5
E
F 6
G 7
• When the main body of ACB is inserted to the cradle, if the ratings of ACB does not match with
cradle, it mechanically prevents ACB from being inserted into cradle of ACB.
51
Accessories
Note) Operating voltage range is the min. rated standard for each rated voltage (Vn).
2. Wiring
52
DC ACB
Temperature alarm
6 M3
12
TRIOU
WARNING TEMP. SET
150 : 150 'C TM-TYPE
140 : 135 'C
130 : 120 'C BUS ADDRESS
DI1 DI2
Warning
80
70 CB ON CB OFF
60 BAUD RATE
50 : 38400 bps CB
: 19200 bps RUN LED
53
Accessories
54
Busbar connection DC ACB
Upper
supply
LOAD LOAD LOAD
LOAD LOAD LOAD
Short Busbar
LOAD LOAD LOAD LOAD LOAD LOAD
Lower Lower Lower
Lower
supply
※ Refer to the following page for product dimensions with short busbar.
Note) please contact us if wiring other than the above circuit diagram is required.
55
Busbar connection
Lower supply
(ADV/ADH-16~25E4)
75
192.5
59.5
75
Unit: mm
Upper supply
(ADV/ADH-16~25E4)
75
59.5
75
56
DC ACB
Lower supply
(ADV/ADH-32E4)
181
190
400
102.5
Unit: mm
Upper supply
(ADV/ADH-32E4)
181
102.5
190
73
57
Busbar connection
DDH/DDV-08~16D4
56.5 135 35 135
115
337.5
38.5
56.5
38.5
10.5
115
135 35 135
Unit: mm
DDH/DDV-20D4
106.5 135 35 135
175
397.5
38.5
106.5
38.5
175
70.5
135 35 135
58
DC ACB
DDH/DDV-25D4
141.5 120 77 120
140
332.5
38.5
141.5
38.5
140
120 77 120
5.5
Unit: mm
Lower supply
(DDH/DDV-08~32E4)
75
192.5
59.5
75
59
Busbar connection
Upper supply
(DDH/DDV-08~32E4)
75
59.5
75
Unit: mm
Lower supply
(DDH/DDV-40E4)
(ADH/ADV-40E)
125
180
22
90
60
DC ACB
Upper supply
(DDH/DDV-40E4)
(ADH/ADV-40E)
90
125
22
61
Control circuit diagram
DC ACB
LOAD
Common
ZSI Output
AC/DC100~250Vdc24V
ZSI Input
Reset
OFF
Trip
unit
ACB or
Inst
62
DC ACB
Internal wiring
External wiring (by customer)
Connector of the control circuit terminal of drawout type
Control
power
P
Temperature
Module
OFF
ON
Temperature Temperature
Sensor-1 Sensor-2
Charged
Charged
OFF
ON
Control
power
N
Electrical Charge Temperature
operation completion Auxiliary switch
circuit contact module
63
Control circuit diagram
DC Switch-Disconnectors
LOAD
OFF
OFF
ON
251 D1 C11 C1 A1 U1 413
Axb
UVT SHT2 SHT1 CC
or
Charged
Short busbats Short busbats
Electrical Charge
Main circuit Ready to close operation circuit completion
contact
UVT
2nd Shunt
trip coil
11 12 ~ 61 62 Auxiliary
보조 S/W switch "b"
(b 접점) M Charging
차지 motor motor
U1 U2 Motor charging
차지 Motor SHT1 Shunt
트립코일 trip coil
A1 A2 Closing
투입코일 coil SHT2 2nd
이중shunt
트립코일trip coil
C1 C2 Shunt
트립코일 trip UVT UVT
UVTcoil
코일
C11 C12 2nd shunt trip
이중트립코일
D1 D2 Terminal
UVT 코일of UVT
251 252 Ready
투입준비접점to close switch
64
DC ACB
Internal wiring
External wiring (by customer)
Connector of the control circuit terminal of drawout type
Control
power
P
Temperature
module
51 41 31 21 11 53 43 33 23 13 T1 TC1 T2 TC2
Temperature Temperature
Sensor-1 Sensor-2
Axb
Axb
Axb
Axb
Axb
Axa
Axa
Axa
Axa
Axa
52 42 32 22 12 54 44 34 24 14
OFF
ON
Control
power
N
Temperature
Auxiliary switch
module
Note) 1. The diagram is shown with circuit de-energized, all devices open, connected and charged and relays in normal position
2. Charging type is "Off-Charging"
3. The standard of auxiliary contact is 3a3b
The auxiliary switch in above diagram is composed of 5a5b
4. Option
-R eady to close contact, UVT coil, charge completion contact, Secondary trip coil
-C ell switch, Temperature module, Remote close-open module
5. Refer to catalog for the connect of UVT
6. Contact configuration for Cell Switch can be changeable if necessary
65
Dimensions
▘3P ▘4P
Front view (Unit : mm)
▘3P ▘4P
Vertical type
<Conductor>
66
DC ACB
▘3P ▘4P
Horizontal type (Unit : mm)
<Conductor>
▘3P ▘4P
Front
connection
type
<Conductor>
67
Dimensions
▘3P ▘4P
Front view (Unit : mm)
▘3P ▘4P
Vertical type
<Conductor>
68
DC ACB
Fixed type
(ADH/ADV-08~25E, DDH/DDV-08~32E)
▘3P ▘4P
Front view (Unit : mm)
▘3P ▘4P
Vertical type
<Conductor>
69
Dimensions
Fixed type
(ADH/ADV-08~16E, DDH/DDV-08~32E)
▘3P ▘4P
Horizontal (Unit : mm)
type
<Conductor>
▘3P ▘4P
Front
connection
type
<Conductor>
70
DC ACB
▘3P ▘4P
189189 189189 304304 189189
Front view 280280 280280 (Unit : mm)
Operating
Operating
panel
panel
center
center Operating
Operating
panel
panel
center
center
378
378 493
493
189
189 189
189 304
304 189
189
280
280
378
378 493
493 280
280
189
189 189panel
189
Operating
Operating panel center
center 304
304 Operating
Operating
189 panel
189 panel center
center
270
270
270
270
300
300
300
300
320
320
320
320
280
280 280
280
Operating
Operatingpanel
panelcenter
center Operating
Operatingpanel
panelcenter
center
35
35
35
35
270
270
300
300
20
20
20
20
320
320
12 12 204204 204204 12 12 12 12 319319 204204 12 12
270
270
270
270
300
300
300
300
432432 547547
320
320
320
320
35
35
20
20
12
12 204
204 204
204 12
12 12
12 319
319 204
204 12
12
35
35
35
35
432
432
20
20
20
20
547
547
1212 204
204 204
204 1212 1212 319
319 204
204 1212
432
432 547
547
115115 115115 115115 115115 115115
20 20
▘3P ▘4P
Vertical type
115
115 115
115 115
115 115
115 115
115
45
45
45
45
20
20
25
25
25
25
115
115 115
115 115
115 115
115 115
115
2020
165
165
165
165
45
45
25
25
20
165 45 20
20
165 45 20
45
45
4-Ø14
4-Ø14 4-Ø14
4-Ø14
25
25
25
25
Mounting
Mounting Mounting
Mounting
108108 hole
hole 523523 hole
hole
20 165
165
20 165
165
432432 547547
4-Ø14
4-Ø14 4-Ø14
4-Ø14
20
20
20
20
Mounting
Mounting Mounting
Mounting
108
108 hole
hole 523
523 hole
hole
4-Ø14
4-Ø14 4-Ø14
4-Ø14
432
432 Mounting
Mounting 547
547 Mounting
Mounting
108
108 hole
hole 523
523 hole
hole
432
432 547
547
15
15
75
75
44.5
44.5
270
15270
75
75
133
133
58
58
15
15
44.5 32 32
44.5
75
75 75
92 92
67
67
<Conductor>
44.5
270
75
35
35
133
30
30
65 6520 20 165165 45 45
75
75
58
44.5
44.5
270
270
75
75
295295 96.2
96.2
44.5
44.5 32
32
67 133
133
58
58
75
92
92
44.5
44.5 3232
35
30 75
75
9292
65
65 20
20 165
165 45
45
67
67
35
35
295
295 96.2
96.2
30
30
295
295 96.2
96.2
71
Dimensions
▘3P ▘4P
Vertical type (Unit : mm)
378 378 304 304 189 189
189 189 189 189 493 493
280 280 280 280
Operating
Operating
panelpanel
center
center Operating
Operating
panelpanel
center
center
300
300
270
270
300
300
270
270
320
320
320
320
35
35
35
35
20
20
20
20
12 12 204 204 204 204 12 12 11.811.8 318.5318.5 203.5203.5 11.811.8
432 432 545.6545.6
45
45
45
45
25
25
165
165
165
165
20
20
20
20
4-Ø14
4-Ø14 4-Ø14
4-Ø14
408 408 Mounting
Mounting 522 522 Mounting
Mounting
HoleHole HoleHole
432 432 545.6545.6
15
15
125
125
270
270
158
158
33
33
67.5
67.5
35
35
5
5
65 65
20 20 165 165 45 45
Door Frame
<Mounting hole> Panel Door <Side hole>
Door Frame
10-Ø9 315(Panel Cutting size)
100
72
DC ACB
▘3P ▘4P
Front view (Unit : mm)
▘3P ▘4P
Vertical type
<Conductor>
73
Dimensions
▘3P ▘4P
Horizontal (Unit : mm)
type
<Conductor>
▘3P ▘4P
Front
connection
type
<Conductor>
74
DC ACB
▘3P ▘4P
Front view (Unit : mm)
▘3P ▘4P
Vertical type
<Conductor>
75
Dimensions
Draw-out type
(ADH/ADV-08~25E, DDH/DDV-08~32E)
▘3P ▘4P
Front view (Unit : mm)
▘3P ▘4P
Vertical type
<Conductor>
76
DC ACB
Draw-out type
(ADH/ADV-08~25E, DDH/DDV-08~32E)
▘3P ▘4P
Horizontal (Unit : mm)
type
<Conductor>
▘3P ▘4P
Front
connection
type
<Conductor>
77
Dimensions
▘3P ▘4P
Front view (Unit : mm)
206206 57.5
57.5 206206
430
430
430
430
430
430
430
430
430
430
430
430
260 260 115 115 260 260
260260 115115 260260
412 412 375 375
412412 375375
527 527
527527
▘3P ▘4P
115 115
115 115 115 115
115 115
115 115
Vertical type 20
115115
20
115115
20
115115
20
115115 115115
20 20 20 20
115
115
115
115
115
115
115
115
200 115
115
200 115
200
200
200
200
200
200
200
200
200
200
75
75
58133 75
270
270
44.5
44.5
44.575
75
270
270
44.5
75
75
133350
350
133
58
58
350
350
133
58
75
7575
44.5 32 44.5 32
75
44.5 32 3292
44.5
270
41 18270
44.5
44.5
92
75
75
75
59.5 97 75
92 92
350
350
41 18
<Conductor>
97
133
133
9758
58
59.5
75 59.5
41 18
41 18
97
59.5
60 60
200 200 115 115 44.5 32 32
44.5
75
6
60 60 200200 115115 92 92
6
6
97
97
4- 13 Mounting 4-hole
13 Mounting hole
59.5
59.5
4- 4-13 13
Mounting
Mounting
hole
hole
60 60 200200 115115
6
6
10 10 375375 102.5
102.5
4- 4-13 13
Mounting
Mounting
hole
hole
78
DC ACB
▘3P ▘4P
Vertical type (Unit : mm)
115
115
115
115
100
100
100
100
100
100
100
100
260 260 6-Ø136-Ø13 260 260 115 115 8-Ø138-Ø13
125
125
158
158
33
33
47
47
22
22
cove is
353(Panel Cutting size)
installed)
Door Frame
280
265
128
2
120
7.5
165 165 5 Type Din. “W”
Cradle bottom D3 330
D4 415
10-Ø9
10-Ø9 E3 408
315(Panel
315(Panel
Cutting
Cutting
size)size) E4 523
4-Ø6 4-Ø6
(If dust
(If dust
120
120
covecoveis is
Cutting size)
353(Panel Cutting size)
installed)
installed)
280
280
265
353(Panel265
128
128
q
2 2
120
120
6.5
6.5
14
14
7.5 7.5
165 165 165 165 5 5 Type Type
Din. “W”
Din. “W”
Cradle
Cradle
bottom
bottom D3 D3 330 330
D4 D4 415 415
79
Technical information
Temperature derating
DC ACB(ADH, ADV)
Product model
Rated Applicable
current busbar size
Product model
Rated Applicable
current busbar size
80
DC ACB
Installation recommendation
Insulation
clearance
C
B
B
Type A B C
Fixed 50 150 N/A
Draw-out 5 N/A 0
Minimum clearances For the safety, all the electric charging parts need to be installed over minimum clearances distance.
distance Insulating voltage (Ui) Minimum clearances distance (X min)
Less than DC 1000V 14 mm
DC 1500V 16 mm
81
Technical information
Installation recommendation
BUS-BAR Connection
Cables connections
Make sure that no excessive mechanical force put on the rear terminals for cable connection.
Extension terminal is fixed such as B, C and cable is to fixed to the frame such as E
Bus-bar connection
For busbar connection, connect access parts with a provided torque and fix with parallel installing the support not to apply
terminal weight to circuit breaker. In order to prevent the spread safety or secondary accidents, secure maximum safe distance A (Table 1) from
the access area to withstand the electrical force during the short circuit faults. (Support strength: base of Insulator, bending load 720kg or
more, tensile strength 3000kg or more)
"
"
A
A=A1+A2
82
DC ACB
Rated ultimate short-circuit breaking current (Icu) according to the type of network
Mid-point earthed
Mid-point earthed
Insulated network
Insulated network
83
Technical information
Rated ultimate short-circuit breaking current (Icu) according to the type of network
Mid-point earthed
Mid-point earthed
Insulated network
Insulated network
84
Time chart DC ACB
85
Time chart
86
DC ACB
Short time
Tripping time (msec) Tripping time (msec)
x Ir x Ir
0.05 0.1 0.2 0.3 0.4 0.05 0.1 0.2 0.3 0.4
1.50 2222 4444 8889 13333 17778 4.35 264 528 1057 1585 2114
1.55 2081 4162 8325 12487 16649 4.40 258 517 1033 1550 2066
1.60 1953 3906 7813 11719 15625 4.45 252 505 1010 1515 2020
1.65 1837 3673 7346 11019 14692 4.50 247 494 988 1481 1975
1.70 1730 3460 6920 10381 13841 4.55 242 483 966 1449 1932
1.75 1633 3265 6531 9796 13061 4.60 236 473 945 1418 1890
1.80 1543 3086 6173 9259 12346 4.65 231 462 925 1387 1850
1.85 1461 2922 5844 8766 11687 4.70 226 453 905 1358 1811
1.90 1385 2770 5540 8310 11080 4.75 222 443 886 1330 1773
1.95 1315 2630 5260 7890 10519 4.80 217 434 868 1302 1736
2.00 1250 2500 5000 7500 10000 4.85 213 425 850 1275 1700
2.05 1190 2380 4759 7139 9518 4.90 208 416 833 1249 1666
2.10 1134 2268 4535 6803 9070 4.95 204 408 816 1224 1632
2.15 1082 2163 4327 6490 8653 5.00 200 400 800 1200 1600
2.20 1033 2066 4132 6198 8264 5.05 196 392 784 1176 1568
2.25 988 1975 3951 5926 7901 5.10 192 384 769 1153 1538
2.30 945 1890 3781 5671 7561 5.15 189 377 754 1131 1508
2.35 905 1811 3622 5432 7243 5.20 185 370 740 1109 1479
2.40 868 1736 3472 5208 6944 5.25 181 363 726 1088 1451
2.45 833 1666 3332 4998 6664 5.30 178 356 712 1068 1424
2.50 800 1600 3200 4800 6400 5.35 175 349 699 1048 1398
2.55 769 1538 3076 4614 6151 5.40 171 343 686 1029 1372
2.60 740 1479 2959 4438 5917 5.45 168 337 673 1010 1347
2.65 712 1424 2848 4272 5696 5.50 165 331 661 992 1322
2.70 686 1372 2743 4115 5487 5.55 162 325 649 974 1299
2.75 661 1322 2645 3967 5289 5.60 159 319 638 957 1276
2.80 638 1276 2551 3827 5102 5.65 157 313 627 940 1253
2.85 616 1231 2462 3693 4925 5.70 154 308 616 923 1231
2.90 595 1189 2378 3567 4756 5.75 151 302 605 907 1210
2.95 575 1149 2298 3447 4596 5.80 149 297 595 892 1189
3.00 556 1111 2222 3333 4444 5.85 146 292 584 877 1169
3.05 537 1075 2150 3225 4300 5.90 144 287 575 862 1149
3.10 520 1041 2081 3122 4162 5.95 141 282 565 847 1130
3.15 504 1008 2016 3023 4031 6.00 139 278 556 833 1111
3.20 488 977 1953 2930 3906 6.05 137 273 546 820 1093
3.25 473 947 1893 2840 3787 6.10 134 269 537 806 1075
3.30 459 918 1837 2755 3673 6.15 132 264 529 793 1058
3.35 446 891 1782 2673 3564 6.20 130 260 520 780 1041
3.40 433 865 1730 2595 3460 6.25 128 256 512 768 1024
3.45 420 840 1680 2520 3361 6.30 126 252 504 756 1008
3.50 408 816 1633 2449 3265 6.35 124 248 496 744 992
3.55 397 793 1587 2380 3174 6.40 122 244 488 732 977
3.60 386 772 1543 2315 3086 6.45 120 240 481 721 961
3.65 375 751 1501 2252 3002 6.50 118 237 473 710 947
3.70 365 730 1461 2191 2922 6.55 117 233 466 699 932
3.75 356 711 1422 2133 2844 6.60 115 230 459 689 918
3.80 346 693 1385 2078 2770 6.65 113 226 452 678 905
3.85 337 675 1349 2024 2699 6.70 111 223 446 668 891
3.90 329 657 1315 1972 2630 6.75 110 219 439 658 878
3.95 320 641 1282 1923 2564 6.80 108 216 433 649 865
4.00 313 625 1250 1875 2500 6.85 107 213 426 639 852
4.05 305 610 1219 1829 2439 6.90 105 210 420 630 840
4.10 297 595 1190 1785 2380 6.95 104 207 414 621 828
4.15 290 581 1161 1742 2323 7.00 102 204 408 612 816
4.20 283 567 1134 1701 2268 7.05 101 201 402 604 805
4.25 277 554 1107 1661 2215 7.10 99 198 397 595 793
4.30 270 541 1082 1622 2163 7.15 98 196 391 587 782
87
Time chart
88
Memo DC ACB
89
Ordering sheet
If rated current or the order you placed is different from the ordering sheet listed below, please fill out another ordering sheet upon your specification.