PSCC Poles Drawings

Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

1

1. DRAWINGS AND DESIGN DETAILS


8M/140 Kg PSCC Pole Design details
100 100
250 ALL DIMENSIONS ARE IN mm

600
GI Earth wire No 8
SWG - 1 no

TENSIONED
WIREs 8 Nos-
4mm
UNTENSIONED
WIREs 2 Nos-4mm
8000 5900

20
20
100

100
4700
TOP SECTION

270
GL 24

20
100
150
1500

BOTTOM
SECTION
DENOTES TENSIONED WIRES
270 100
SIDE VIEW
DENOTES UN-TENSIONED
WIRES

1. Type of pole:- Solid


2. Section APSEB REC DESIGN
a. At top:- 100 x 100 mm 105 x 90 mm
b. At Bottom:- 270 x 100 mm 275 x 90 mm
3. Number of HT wires
a. Tensioned:- 8 Nos - 4mm dia
b. Un tensioned curtailed wires:- 2 Nos - 4mm dia
4. Quantity of concrete:- 0.148 cum
5. Concrete Grade:- M 40
6. HBG Metal 20mm :- 0.039 cum
7. HBG Metal 10mm to 12 mm :- 0.091 cum
8. Sand:- 0.070 cum
9. 53 Grade Cement:- 69.68 Kg
10. 4mm HT Steel:- 8.00 Kg
11. GI Earth wire No 8 SWG
12. Point of application of load from top :- 600 mm
13. Full tension applied to each wire:- 1,760 Kg
14. Weight of pole:- 355 Kg
15. Factor of safety:- 2.5
16. Curtail the un tensioned wires ( 2 Nos) at a height of 4700 mm from bottom as shown in
the drawing.
17. Provide 6 Nos stirrups from bottom at 900mm c/c to keep un tensioned wires in position
18. Permissible deflection at 40% i.e 140 Kg load= 36.1mm
2

8M/200 Kg PSCC Pole Design details


145 90
ALL DIMENSIONS ARE IN mm
250
600
GI Earth wire No 8
SWG -1 No
TENSIONED WIREs
12 Nos-4mm

UNTENSIONED
WIREs 2 Nos-4mm

59
5900 20
8000 20

TOP SECTION
3900

290
GL 24
59
20
150

1500

BOTTOM SECTION
290 90 DENOTES TENSIONED WIRES
ELEVATION SIDE VIEW
DENOTES UN-TENSIONED
WIRES

1. Type of pole:- Solid


2. Section
a. At top:- 145 x 90 mm
b. At Bottom:- 290 x 90 mm
3. Number of HT wires
a. Tensioned:- 12 Nos - 4mm dia
b. Un tensioned curtailed wires:- 2 Nos - 4mm dia
4. Quantity of concrete:- 0.157 cum
5. Concrete Grade:- M 40
6. HBG Metal 20mm:- 0.0417 cum
7. HBG Metal 10mm to 12mm:- 0.0973 cum
8. Sand:- 0.0739 cum
9. 53 grade Cement:- 73.92 Kg
10. 4mm HT Steel:- 10.25 Kg
11. GI earth wire:- No 8 SWG
12. Point of application of load from top :- 600 mm
13. Full tension applied to each wire:- 1,760 Kg
14. Weight of pole:- 380 Kg
15. Factor of safety:- 2.5
16. Curtail the un tensioned wires ( 2 Nos) at a height of 3900 mm from bottom as shown in
the drawing.
17. Provide 6 Nos stirrups from bottom at 900mm c/c to keep un tensioned wires in position
18. Permissible deflection at 40% i.e 200 Kg load= 36.1mm
3

8M/300 Kg PSCC Pole Design details


145 100
ALL DIMENSIONS ARE IN mm
250
600
GI Earth wire No 8
- SWG 1 No
TENSIONED WIREs
12 Nos-4mm

59
20
8000 5900 20

TOP SECTION

380
GL 24
59
20
150

1500

BOTTOM SECTION
380 100 DENOTES TENSIONED WIRES
ELEVATION SIDE VIEW

1. Type of pole:- Solid


2. Section
a. At top:- 145 x 100 mm
b. At Bottom:- 380 x 100 mm
3. Number of HT wires
a. Tensioned:- 12 Nos - 4mm dia
b. Un tensioned curtailed wires:- Nil.
4. Quantity of concrete:- 0.210 cum
5. Concrete Grade:- M 40
6. HGB Metal 20mm:- 0.0556 cum
7. HGB Metal 10mm to 12mm:- 0.130 cum
8. Sand:- 0.099 cum
9. Cement 53 grade :- 98.87 Kg
10. 4mm HT Steel:- 9.47 Kg
11. GI Earth wire:- No 8 SWG
12. Point of application of load from top :- 600 mm
13. Full tension applied to each wire:- 1,760 Kg
14. Weight of pole:- 505 Kg
15. Factor of safety:- 2.0
16. Permissible deflection at 50% i.e 300 Kg load= 36.1mm
4

9.1m/280 Kg PSCC Pole Design details


130 150

250

ALL
3000 DIMENSIONS
ARE IN mm

GI Earth wire No
8 - SWG 1 No

9100 2000

150

2250

GL
300
150

1250

1500

150

360 150
ELEVATION SIDE VIEW
5

9.1m/280 Kg PSCC Pole Design details


ALL DIMENSIONS ARE IN mm
130
360
65 230 65
26

26 35

35
150 28
50
28 35
150
35
26

26 30 30 30
20 20
30
BOTTOM SECTION TOP SECTION
20

1. Type of pole:- I Section


2. Section
a. At top:- 130 x 150 mm
b. At Bottom:- 360 x 150 mm
3. Number of HT wires
a. Tensioned:- 16 Nos - 4mm dia
b. Un tensioned curtailed wires:- Nil.
4. Quantity of concrete:- 0.265 cum
5. Concrete Grade:- M 40
6. HGB Metal 20mm:- 0.071 cum
7. HGB Metal 10mm to 12mm:- 0.166 cum
8. Sand:- 0.126 cum
9. Cement 53 grade :- 126.5 Kg
10. 4mm HT Steel:- 16.0 Kg
11. Stirrups :- Two legged 4mm HT steel stirrups at 600mm centre to centre shall
be provided through out the length of pole. Four legged 4mm HT steel stirrup
shall be provided one at top and one at bottom.
12. GI Earth wire:- No 8 SWG
13. Point of application of load from top :- 600 mm
14. Full tension applied to each wire:- 1,760 Kg
15. Weight of pole:- 680 Kg
16. Factor of safety:- 2.5
17. Permissible deflection at 40% i.e 280 Kg load= 42.2 mm