User Manual of STC-9200 Thermostat: 1. Package 2. Specification

Uploaded by

Khalil Safi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
3K views2 pages

User Manual of STC-9200 Thermostat: 1. Package 2. Specification

Uploaded by

Khalil Safi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Haswill Electronics

4.2. Indicator / Character in Display


User Manual of STC-9200 Thermostat Indicator
Refrigeration & Defrosting & Evaporator Fan Controller
(Version 22.11.07GEN) Meaning Compressor status Setting Status Fan Status Defrosting status
The STC-9200 temperature controller controls the power supply status of the connected Refrigeration On Working Setting Working Working
device, the defrosting unit, and the Evaporator Fan, typically suited to an oversized freezer room. Hide Stop Normal Stop Stop
Wink Time Delay N/A Time Delay Dripping Water
1. Package Fast Wink Manually Refrigeration N/A N/A Manually Defrosting
Controller: 1PCS Sensor: 2PCS Clips: 2PCS Manual:1 PCS Waterproof Cover: 1PCS
4.3. Dimensions & Installation
2. Specification
Input Power 220V AC ± 10% 50/60HZ; (12/24/48/110V Option) 1) Mount size: 71*29*85 mm (W*H*D);
Maximum current 8A (Default) under 250V AC 2) Detach the slide fasteners, put the
Thermistor / Sensor NTC, 25°C /10 KΩ, the sensor cable 200cm controller into the hole, and wire it.
Protection Class IP65 to the front panel 3) Install the fasteners and the waterproof
Storage -10°C ~ 60°C, RH<90%, without condensation cover.
Temperature Range Measurable: -50.0°C ~ +50.0°C; Controllable: -50.0°C ~ +50.0°C
Resolution 0.1°C 4.4. Wiring Diagram
Accuracy ± 1°C from -40°C to +50°C; ± 2°C in other range
Power Consumption ≤ 3W

3. Environmental Information
The package's material is 100% recyclable. Just dispose of it through specialized recyclers.
The electro components can be recycled if it is disassembled for specialized companies.
Please do not burn or throw the controllers in domestic garbage. Observe the respective law in your
region concerning the environmentally responsible manner of disposing of its devices.

4. Appearance & Operation


4.1. Front Panel & Operation A. 10K NTC sensor, need not distinguish + or -.
Under normal status, the screen shows room sensor temp. B. The input voltage must be within the voltage value marked in the diagram ±10% value.
A. Hold the for 3s to enter/exit the user setting Voltage∗ Max current of Relay
C. Suggest Load Power ≤
interface to check and modify the set-point and the Factor
hysteresis here. 4.5. Copykey (Optional)
B. Hold the key and the key at the same time A. Upload to Controller
for 10s to lock/unlock the admin menu: 1) Insert the Copykey, Press the key, the display shows "UPL";
OFF = unlock, editable 2) Now Press the key to upload data will show "END" once finished;
ON = locked, only can check the value, not editable. 3) Shut down the controller and then pull out the Copykey.
C. Hold the and the keys for 10s to enter admin interface; Press the to check B. Download from Controller
current data, and press the or key to change the data; Press the again to save 1) Assure controller being shut down and insert the Copykey, then starting up
data and back to menu list; If without operated in 10s, the new data will be auto-saved. 2) The controller will scan the Copykey and download data automatically, shows "DOL"
D. Hold the for 3s to check the defrost sensor temp.; when downloading, and shows "END" once finished.
3) Restart the controller; it will work according to the new data.
E. Hold the for 3s to trigger the forced refrigeration mode manually (conditions in 5.3); do
Attention:
it again to quit. ⚫ Part of the parameters will be executed in the next cycle; please power off the controller and
F. Hold the for 3s to trigger the forced defrosting mode manually (conditions in 5.2); do it power back to start a new cycle for running by the new data without a wait.
again to enter defrosting water dripping status. ⚫ If a parameter in the Copykey exists error or in the wrong format, the display shows ERR.

1 / 2
Haswill Electronics

5. Configurations 5.2. When will the Defrosting Start / Stop?


5.1. Code and Function Menu A. Defrost relay will close/on when reaching all the below conditions
Hold the + keys at the same time for 10s to enter the Admin Interface; ⚫ The time should later than: the compressor last stops moment + AC/F05 if the defrosting
The codes SET and HY (F01 and F02) are user menu; others are admin menu, ref 4.1 A & C Mode was thermal air / Hot Gas (TDF/F10 = HTG).
⚫ The defrost sensor temperature < Defrost stop temperature (in DTE/F8)
Cate. EN F Function Min Max Default Unit
⚫ Time passed the defrosting cycle time (IDF/F06) or forced defrosting beginning
Temp. SET F01 SP (Temperature Set-Point) LS US -5.0 °C
B. Defrost relay will open/off when reaching any one of the below conditions
HY F02 Temperature Hysteresis / Return Difference 1.0 25.0 2.0 °C
⚫ The defrost sensor temperature ≥ Defrost stop temperature (in DTE/F8)
US F03 Upper limit for SP F01 50.0 20.0 °C
⚫ Passed the defrosting Lasting Time (MDF/F07)
LS F04 Lower limit for SP -50.0 F01 -20.0 °C
5.3. When will the Compressor Start / Stop?
AC F05 Delay Time for Compressor The room temperature was supposed to keep at the range from " SET/F01" to " SET+HY (F01+F02)."
Delay Time for Defrosting (only for hot gas TDF/F10) 0 50 3 Min
First, Time Conditions
Defrost IDF F06 Cycle / Interval Time 0 120 6 Hour A. When FOD/F15 > 0s, the time should be later than:
MDF F07 Lasting Time 0 255 30 Min • The moment of the compressor recent stops + AC/F05
Defrost B. When FOD/F15 < 0s (the fan startup earlier than the compressor), the time later than:
DTE F08 Stop Temperature -50.0 50.0 10.0 °C
• The moment of the compressor recent stops + AC/F05, and
FDT F09 Water dripping Time 0 10.0 2 Min • The fan starts moment + FOD/F15
TDF F10 Defrosting Mode: And Temperature Conditions
EL/0 Electric-Heating. EL/0 HTG/1 EL/1 N/A A. If TDF/F10 = EL/0 (like an electric heating wire wound around the evaporator)
HTG/1 Hot Gas from the compressor. Controller Status Working Condition Stops Condition
Room Temp ≥ SET/F01 Room Temp < SET/F01
DCT F11 Count mode of defrost cycle: Forced defrosting
The dripping time FDT/F09 is over (ref 4.1 F) or defrost beginning
RT/0 Cumulative time from the controller power on; RT/0 COH/1 RT/0 N/A Not in defrosting Room Temp ≥ SET + HY (F01 + F02) or forced refrigeration is over.
COH/1 Cumulative time of the compressor working. B. If TDF/F10 = HTG/1 (Hot Gas from the compressor Reverse Rotary), 1 more status than A
DFD F12 Display mode when defrosting: Controller Status Working Condition Stops Condition
RT/0 Shows the room sensor temperature display; Auto defrosting Evaporator Temp > DTE/F08 defrost stop temp. Room Temp < SET/F01;
RT/0 IT/1 RT/1 N/A
or defrosting beginning;
Shows the evaporator sensor temp. (continue Room Temp ≥ SET/F01
IT/1 Forced defrosting or forced Refrigeration is over
showing 10 minutes once defrosting over) The dripping time FDT/F09 is over (ref 4.1 F)
and won't defrost at once.
Fan FNC F13 Fan output modes when FOD ≥ 0 Not in Defrosting Room Temp ≥ SET + HY (F01 + F02)
CTR/0 Fan Starts by F14/FOT, Stop by F16/FST;
O-N/1 continuous working except defrosting begins;
CTR/0 C-N/2 CTR/0 N/A 5.4. Alarming & Error Code
Once alarming, the readout flashing and buzzer screaming press any key to stop the buzzer ticktack, but the
C-N/2 FOD is when the fan starts later than the compressor;
the fan stops if defrosting begins. error code in the display will not disappear until all errors have been fixed.
FOT F14 Defrost sensor Temperature for Fan Starts -50.0 FST/F16 -10.0 °C Code Troublesome From Reason
FOD F15 Time delay seconds for fan E01 Room Sensor Open or short
< 0 FOD is the period for the fan to start earlier than the
compressor starts; the fan stops before defrosting. -255 255 60 S
E02 Defrost Sensor Open or short
HHH Room or Defrost Sensor > Max measurable limits 50°C
≥ 0 The fan was controller by F13/FNC LLL < Min measurable limits -50°C
FST F16 Defrost sensor Temperature for Fan Stops FOT/F1 50.0 -5.0 °C Readout flash Room Sensor 50 °C > room temp. > ALU/F17 or
Alarm ALU F17 Upper Limit 4
ALL 50.0 50.0 °C buzzer screams -50 °C < room temp. < ALL/F18
Room sensor Temperature
ALL F18 Lower Limit -50.0 ALU -50.0 °C
F19
to Trigger Alarm
0
5.5. When will the Fan Work/Stop?
ALD Time delay 99 15 Min
Please check the conditions from FOD/F15 & FNC/F13 in the menu list.
Cali. OT F20 Temperature Calibration = Real Temperature - Measured -10.0 10.0 0.0 °C
The EN code menu and the F code menu are same, just for satisfy different clients.
Temperature.
Video on YouTube