DSEGenset®

DSE8920 SPECIFICATIONS

DC SUPPLY

7” Colour Load Share & Synchronising CONTINUOUS VOLTAGE RATING


5 V to 35 V Continuous

Control Module CRANKING DROPOUTS


Able to survive 0 V for 100 ms, providing
supply was at least 10 V before dropout
and supply recovers to 5 V. This is
achieved without the need for internal
batteries.LEDs and backlight will not be
maintained during cranking.
Module can be MAXIMUM OPERATING CURRENT
configured to 1.2 A at 12 V, 0.6 A at 24 V
function as a DSE8910 MAXIMUM STANDBY CURRENT
Auto Start 0.7 A at 12 V, 0.35 A at 24 V

Synchronising and CHARGE FAIL/EXCITATION RANGE


Load Sharing Control 0 V to 35 V

Module. GENERATOR & MAINS (UTILITY)


VOLTAGE RANGE
15 V to 415 V AC (Ph to N)
26 V to 719 V AC (Ph to Ph)

FREQUENCY RANGE
3.5 Hz to 75 Hz
KEY FEATURES • Unbalanced load protection KEY BENEFITS MAGNETIC PICKUP
• 7” optically bonded, sunlight • Independent earth fault protection • Can be configured for use as a VOLTAGE RANGE
readable colour TFT display • Breaker control via fascia buttons DSE8910 Auto Start Module +/- 0.5 V to 70 V
(800 x 480) • Fuel and start outputs configurable • Real-time clock provides accurate FREQUENCY RANGE
• Comprehensive synchronising & when using CAN event logging 10,000 Hz (max)
load sharing capabilities • 8 configurable DC outputs • Ethernet communication, provides
INPUTS
• Built in governor, AVR & CAN • 2 configurable volt-free relay built in advanced remote DIGITAL INPUTS A TO L
control outputs monitoring. Negative switching
• Base load (kW export) control • 4 configurable analogue/digital • Increased input and output
• Positive & negative kVAr export ANALOGUE INPUTS A TO D
inputs expansion capability via DSENet® Configurable as:
control • Built in sensors to support 0 V to 10 • Licence-free PC software Negative switching digital input
• Mains (Utility) decoupling protection V & 4 mA to 20 mA • IP65 rating (with supplied gasket) 0 V to 10 V sensor
• Mains (Utility) failure detection • 12 configurable digital inputs offers increased resistance to water 4 mA to 20 mA sensor
0 Ω to 480 Ω sensor
• Mains (Utility) power (kW, kV Ar, • Configurable 5 stage dummy load ingress
kV A & pf) monitoring and load shedding outputs • Advanced internal PLC editor OUTPUTS
• RoCoF and vector shift protection • CAN, MPU and alternator frequency allows user configurable functions OUTPUT A & B (FUEL & START)
15 A DC at supply voltage
• Mains (utility) kW export protection speed sensing in one variant to meet complex application
• Peak lopping & shaving functionality • Real time clock requirements. OUTPUTS C & D
• Multiple display languages • Manual and automatic fuel pump 8 A AC at ­­­250 V AC (Volt-free)
• Five key menu navigation control EXPANSION DEVICES
AUXILIARY OUTPUTS E to L
• LCD alarm indication • Engine run-time scheduler • DSE124 CAN/MSC Extender 2 A DC at supply voltage
• DSENet® expansion compatibility • Fuel usage monitor and low fuel • DSE2130 Input Expansion Module
• Data logging & trending facility level alarms • DSE2131 Ratio-metric Input BUILT IN AVR GOVERNOR CONTROL
MINIMUM LOAD IMPEDANCE
• Drag & drop advanced PLC editor • Simultaneous use of all Expansion Module 500 Ω
• Protections disable feature communication ports • DSE2133 RTD & Thermo-couple Fully isolated
• Fully configurable via PC using • Remote SCADA monitoring via Expansion Module
USB, RS485 & Ethernet various DSE software applications • DSE2152 Ratio-metric Output GAIN VOLTAGE
0 V to 10 V DC
communication • MODBUS RTU & TCP IP support Expansion Module Fully isolated
• Front panel configuration with with configurable MODBUS • DSE2157 Output Expansion Module
PIN protection pages • DSE2548 LED Expansion OFFSET VOLTAGE
0 V to 10 V DC
• Power save mode • 3 configurable maintenance alarms Fully isolated
• 3 phase mains (utility) & generator • Compatible with a wide range of
sensing and protection CAN engines, including tier 4F, DIMENSIONS
• Generator current and power stage 5 engine support OVERALL
310 mm x 162 mm x 51 mm
monitoring (kW, kvar, kVA, pf) • Uses DSE Configuration Suite PC 12.2” x 6.4” x 2.0”
• kW and kvar overload alarms Software for simplified configuration
• Reverse power alarms PANEL CUT-OUT
282 mm x 136 mm
• Over current protection 11.1” x 5.4”

MAXIMUM PANEL THICKNESS


8 mm
0.3”

STORAGE TEMPERATURE RANGE


RELATED MATERIALS -40 °C to +85 °C
-40 °F to +185 °F
TITLE PART NO.
DSE8920 Installation Instructions 053-248 OPERATING TEMPERATURE RANGE
-30 °C to +70 °C
DSE8920 Operator Manual 057-311 -40 °F to +185 °F
DSE8920 PC Configuration Suite Manual 057-303
DSE8910 Data Sheet 055-264

DEEP SEA ELECTRONICS LTD DEEP SEA ELECTRONICS INC


Highfield House, Hunmanby Industrial Estate, Hunmanby YO14 0PH 3230 Williams Avenue, Rockford, IL 61101-2668 USA
TELEPHONE +44 (0) 1723 890099 TELEPHONE +1 (815) 316 8706 FACSIMILE +1 (815) 316 8708
EMAIL [email protected] WEBSITE www.deepseaelectronics.com EMAIL [email protected] WEBSITE www.deepseaelectronics.com
Deep Sea Electronics Ltd maintains a policy of continuous development and reserves the right to change Registered in England & Wales No.01319649
the details shown on this data sheet without prior notice. The contents are intended for guidance only. VAT No.316923457 055-264/11/19 (1) US
DSEGenset®

DSE8920 ENVIRONMENTAL TESTING STANDARDS

ELECTRO MAGNETIC COMPATIBILITY


BS EN 61000-6-2
7” Colour Load Share & Synchronising EMC Generic Immunity Standard for the
Industrial Environment

Control Module
BS EN 61000-6-4
EMC Generic Emission Standard for the
Industrial Environment

The DSE8920 is a 7” full colour, Comprehensive communications are KEY LOAD SHARE FEATURES: ELECTRICAL SAFETY
optically bonded synchronising also available via RS485 and Ethernet • Peak lopping/sharing (with BS EN 60950
Safety of Information Technology Equipment,
Auto Mains (Utility) Failure Control for remote PC control and monitoring appropriate DSE mains (utility) including Electrical Business Equipment
Module suitable for paralleling single and integration into building controller
gensets (diesel or gas) with a mains management systems • Manual voltage/frequency TEMPERATURE
BS EN 60068-2-1
(utility) supply. The controller can be adjustment Ab/Ae Cold Test -30 ºC
configured for use as a DSE8910 The event log will record 250 events • RoCoF and vector shift BS EN 60068-2-2
Bb/Be Dry Heat +70 ºC
Auto Start Control Module. When to facilitate easy maintenance, and an protection
converted for use as a DSE8910 the extensive number of fixed and flexible • Mains (Utility) decoupling VIBRATION
unit provides generator to generator monitoring, metering and protection • Mains (Utility) decoupling BS EN 60068-2-6
Ten sweeps in each of three major axes
load share functionality. features are included. test mode 5 Hz to 8 Hz at +/-7.5 mm, 8 Hz to 500 Hz
• Direct governor and AVR control at 2 gn
Designed to synchronise a single Designed to offer increased built • Volts and frequency matching HUMIDITY
genset with a single mains (utility) in support for active sensors for • kW and kvar load sharing BS EN 60068-2-30
supply the DSE8920 will automatically 0 V to 10 V & 4 mA to 20 mA. Db Damp Heat Cyclic 20/55 ºC at 95% RH
48 Hours
control the change over from mains Comprehensive communication BS EN 60068-2-78
(utility) to generator supply or run the and system expansion options are Cab Damp Heat Static 40 ºC at 93% RH
generator in synchronisation with the available. 48 Hours
mains (utility), to provide no break, SHOCK
peak lopping and peak shaving power Using the DSE PC Configuration BS EN 60068-2-27
Three shocks in each of three major axes
solutions. Suite software allows easy alteration 15 gn in 11 mS
of the operational sequences, timers
System alarms are annunciated on and alarms. With all communication DEGREES OF PROTECTION
PROVIDED BY ENCLOSURES
the LCD screen (multiple language ports capable of being active at the BS EN 60529
options available), illuminated LED same time, the DSE8920 is ideal for a IP65 - Front of module when installed into the
and audible sounder.­­ wide variety of demanding load share control panel with the supplied sealing gasket.

applications.

COMPREHENSIVE FEATURE LIST TO SUIT A WIDE VARIETY OF LOAD SHARE APPLICATIONS