Apc Ups Srt5k-Rmxli
Apc Ups Srt5k-Rmxli
Smart-UPS™ On-Line
SRT
SRT5KXLI
SRT5KRMXLI
SRT5KXLT
SRT5KRMXLT
SRT5KXLT-IEC
SRT5KRMXLT-IEC
SRT5RMKXLW-HW
SRT6KXLI
SRT6KRMXLI
SRT6KXLT
SRT6KRMXLT
SRT6KXLT-IEC
SRT6KRMXLT-IEC
208/220/230/240 Vac
Tower/Rack-Mount 3U/4U
General Information
Important Safety Messages
Read the instructions carefully to become familiar with the equipment before attempting to install, operate, service
or maintain the UPS. The following special messages may appear throughout this manual or on the equipment to
warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.
The addition of this symbol to a Danger or Warning product safety label indicates that an electrical
hazard exists which will result in personal injury if the instructions are not followed.
The addition of this symbol to a Warning or Caution product safety label indicates that a hazard exists
that can result in injury and product damage if the instructions are not followed.
DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in death or serious
injury.
WARNING
WARNING indicates a hazardous situation which, if not avoided, could result in death or serious
injury.
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result in minor or moderate
injury.
NOTICE
NOTICE is used to address practices not related to physical injury.
Deenergizing safety
The UPS contains internal batteries and may present a shock hazard even when disconnected from the branch
circuit (mains). Before installing or servicing the equipment verify the following:
Electrical safety
• For models with a hardwired input, the connection to the branch circuit (mains) must be performed by a
qualified electrician.
• 230 V models only: In order to maintain compliance with the EMC directive for products sold in Europe,
output cords attached to the UPS must not exceed 10 meters in length.
• The protective earth conductor for the UPS carries the leakage current from the load devices (computer
equipment). An insulated ground conductor is to be installed as part of the branch circuit that supplies the
UPS. The conductor must have the same size and insulation material as the grounded and ungrounded
branch circuit supply conductors. The conductor will typically be green and with or without a yellow stripe.
• The UPS input ground conductor must be properly bonded to protective earth at the service panel.
If the UPS input power is supplied by a separately derived system, the ground conductor must be properly
bonded at the supply transformer or motor generator set.
Hardwire safety
• Verify that all branch circuit (mains) and low voltage (control) circuits are deenergized, and locked out
before installing cables or making connections, whether in the junction box or to the UPS.
• Wiring by a qualified electrician is required.
• Check national and local codes before wiring.
• Strain relief is required for all hardwiring (not supplied).
• All openings that allow access to UPS hardwire terminals must be covered. Failure to do so may result in
personal injury or equipment damage.
• Select wire size and connectors according to national and local codes.
General information
• The UPS will recognize as many as 10 external battery packs connected to the UPS.
Note: For each XLBP added, increased recharge time will be required.
• The model and serial numbers are located on a small, rear panel label. For some models, an additional label
is located on the chassis under the front bezel.
• Always recycle used batteries.
• Recycle the package materials or save them for reuse.
Product Description
The APC by Schneider Electric Smart-UPS™ On-Line SRT is a high performance uninterruptible power supply
(UPS). The UPS helps to provide protection for electronic equipment from utility power blackouts, brownouts,
sags, surges, small utility power fluctuations and large disturbances. The UPS also provides battery backup power
for connected equipment until utility power returns to acceptable levels or the batteries are completely discharged.
This user manual is available on the enclosed Documentation CD and on the APC by Schneider Electric web site,
www.apc.com.
Environmental
Operating 0º to 40º C (32º to 104º F)
Temperature
Storage -15º to 45º C (5º to 113º F)
Operating 0 - 3,000 m (0 - 10,000 ft)
Maximum Elevation
Storage 0 - 15,000 m (50,000 ft)
Humidity 0% to 95% relative humidity, non-condensing
Protection Class IP 20 rating
Note: Charge the battery modules every six months during storage.
Environmental factors impact battery life. Elevated ambient temperatures, high humidity, poor quality mains power, and
frequent short duration discharges will shorten battery life.
Physical
SRT5K model
The UPS is heavy. Follow all lifting guidelines.
Unit weight batteries included, without 56.6 kg (124.8 lb)
packaging
Unit weight batteries included, with Rack-Mount models: 67.3 kg (148.4 lb)
packaging Tower models: 64.36 kg (141.9 lb)
Unit dimensions without packaging 130 mm x 432 mm x 711 mm
Height x Width x Depth 5 in x 17 in x 28 in
Unit dimensions with packaging 330 mm x 610 mm x 960 mm
Height x Width x Depth 13 in x 24 in x 37.8 in
The model and serial numbers are on a small label located on the rear panel.
SRT6K model
The UPS is heavy. Follow all lifting guidelines.
Unit weight batteries included, without packaging 60 kg (132 lb)
Unit weight batteries included, with packaging 67 kg (147.4 lb)
Unit dimensions without packaging 174 mm x 432 mm x 719.4 mm
Height x Width x Depth 6.9 in x 17 in x 28.3 in
Unit dimensions with packaging 370 mm x 610 mm x 960 mm
Height x Width x Depth 14.6 in x 24 in x 37.8 in
The model and serial numbers are on a small label located on the rear panel.
NOTICE
RISK OF EQUIPMENT DAMAGE
Electrical
Models Rating Branch Circuit Overcurrent Rating
Online Green Mode / Building Circuit Breaker (CB)
Current Rating
SRT5KXLT
5.4 kVA/4.8 kW at
SRT5KRMXLT 208 V 4.8 kVA at 208 V
30 A
SRT5KXLT-IEC 6.0 kVA/4.8 kW at 5.5 kVA at 240 V
240 V
SRT5KRMXLT-IEC
SRT5KXLI
SRT5KRMXLI 5 kVA/4.5 kW 5.0 kVA 40 A
SRT5KRMXLW-HW
SRT6KXLT
SRT6KRMXLT
SRT6KXLT-IEC
6 kVA/6 kW 6.0 kVA 50 A
SRT6KRMXLT-IEC
SRT6KXLI
SRT6KRMXLI
Battery compartment
Bezel
su0877a
SRT5KXLI/SRT5KRMXLI
Output: 50/60 Hz
10 AMP MAX
220/230/240 VAC
GROUP 2 GROUP 1
16 AMP MAX
su0878a
SRT5KXLT/SRT5KRMXLT
GROUP 1
20 AMP MAX
Output: 50/60 Hz
208//240 VAC
GROUP 2
30 AMP MAX
su0879a
Output: 50/60 Hz
208/240 VAC
20 AMP MAX
GROUP 2
15 AMP MAX
GROUP 1
su0880a
SRT5KRMXLW-HW
su0881a
Output: 50/60 Hz
220/230/240 VAC
GROUP 3 GROUP 2
16 AMP MAX 16 AMP MAX
su0882a
GROUP 1
10 AMP MAX
SRT6KXLT/SRT6KRMXLT
Output: 50/60 Hz
208/240 VAC
GROUP 1
30 AMP MAX
20 AMP MAX
GROUP 3
GROUP 2
30 AMP MAX
su0883a
Output: 50/60 Hz
208/240 VAC
GROUP 1
15 AMP MAX
20 AMP MAX
GROUP 2
20 AMP MAX
GROUP 3
su0884a
External battery Use the external battery cable on the XLBP to connect the UPS and XLBP.
power and XLBPs provide extended runtime during power outages. The UPS will automatically recognize
communication up to 10 external battery packs.
connector
Chassis ground The UPS and XLBPs have ground screws for connecting the ground leads. Prior to connecting
screws a ground lead, disconnect the UPS from mains power.
EPO terminal The Emergency Power Off (EPO) terminal allows the user to connect the UPS to a central EPO
system.
Serial Com The Serial Com port is used to communicate with the UPS.
Use only interface kits supplied or approved by APC by Schneider Electric. Any other
serial interface cable will be incompatible with the UPS connector.
USB port The USB port is used to connect either a server for native operating system communications, or
for software to communicate with the UPS.
Console port Use the Console port to configure the network management features.
Network port Use the Network port to connect the UPS to the network.
Circuit breaker In the event an overload condition occurs, disconnect nonessential equipment.
Then reset the circuit breaker.
SRT5KXLI/SRT6KXLI models
Input connections Single phase: Wire to L, N,
• Disconnect the mains input circuit breaker before installing or servicing the UPS or connected
equipment.
• Disconnect internal and external batteries before installing or servicing the UPS or connected
equipment.
• The UPS contains internal and external batteries that may present a shock hazard even when
disconnected from the mains.
• UPS AC hardwired and pluggable outlets may be energized by remote or automatic control at any time.
• Disconnect equipment from the UPS before servicing any equipment.
Note: The UPS batteries will charge to 90% capacity in the first three hours of normal operation. Do not expect
full battery runtime capability during this initial charge period.
To turn on the UPS and all connected equipment, press the Power ON/OFF button on the display panel. Follow the
prompts to either turn the UPS on immediately or after a delay, then press OK.
Note: When there is no input power and the UPS is off, the cold start feature can be used to turn on the UPS and
connected equipment using battery power.
To perform a cold start press the Power ON/OFF button.
The display panel will illuminate and the Power ON/OFF button will illuminate red.
To turn on the output power press the Power ON/OFF button again. Select the prompt Turn ON with NO AC and
press OK.
To turn output power off, press the Power ON/OFF button. Follow the prompts to either turn the UPS off
immediately or after a delay, then press OK.
Note: Once the AC power has been turned off the UPS will continue operating on battery power for a short period
of time. To remove power completely press the Power ON/OFF button. Follow the prompt to select Internal Power
Off, then press OK.
Load icon
Output 230.0 v
Disable/mute audible alarm icon
On-Line 1 2
UPS status information
ESCAPE button
OK button su0870b
UP/DOWN buttons
The icons on the LCD display interface screen may vary depending on the installed firmware version.
Load icon: The approximate load capacity percentage is indicated by the number of load bar
LOAD
sections illuminated. Each bar represents 16% of the load capacity.
Bypass mode: The UPS is in Bypass mode and the connected equipment will receive mains
power as long as the input voltage and frequency are within the configured limits.
Green mode: When in Green mode mains power is sent directly to the load.
In the event of a mains power outage, there will be an interruption in power to the load of up to
8 ms while the UPS switches to On-Line or Battery mode.
When enabling Green mode consideration should be given to devices that may be sensitive to
power fluctuations.
UPS Status Icon
Battery mode: The UPS is supplying battery power to connected equipment.
The UPS has detected an internal fault with the battery. Follow the instructions on the screen.
The UPS has detected a critical fault with the battery. The battery is at the end of its life and has
X to be replaced.
Controllable Outlet Group Power Not Available: The number next to the icon identifies
specific outlet groups that do not have available power.
Note: Actual menu screens may differ by model and firmware version.
a
26
09
su
Status Menu Control Menu** Config Menu Test and Diagnostics Menu Log About Menu
UPS UPS UPS Self Test Event Log UPS
Battery Bypass Battery Runtime Test Battery
Accessory*** Outlet Group 1* Outlets* Alarm Test Accessory
Outlet Group 2* Communication
Outlet Group 3* Display
Clear Alarms
UPS***
UPS Hardware - Part No.
UPS** PDU Hardware
Efficiency UPS** UPS Hardware - Serial No.
UPS
Output Power, VA, Watts, % Turn On / Off / Reboot / Shutdown UPS Hardware - Manufacture Date
Green mode Enable / Disable
Output Voltage, Current, Frequency UPS Firmware – Revision
Output Voltage / Frequency Settings
Energy Usage UPS – DSP Firmware*
Bypass Settings
Battery State Of Charge, Runtime UPS – Comm Firmware*
UPS Bypass** Battery Settings
Input Voltage, Frequency UPS Time
Go into Bypass Self Test Schedule
Bypass Voltage, Frequency
Go out of Bypass PDU Model
Self Test
Default Setting
Runtime Test
Reset Energy Meter*
Display
Menus are subject to change depending on the installed firmware version Language
Beeper Volume
* Available on the Advanced Menu Screens LCD Backlight
Menu type - Standard / Advanced
** Options displayed will vary based on UPS state.
su0924j
1. The first time the UPS is turned on the Setup Wizard screen will open. On each menu screen select the
desired settings. Press OK after each UPS setting is selected.
Note: The UPS will not turn on until all of the settings have been configured.
2. Go to Main Menu > Configuration > UPS > Load Default. This screen allows the user to reset the UPS
to factory default settings. Press OK after the UPS setting is selected.
Refer to “Configuration” on page 18 and “Menu overview” on page 19.
3. Configure settings using an external interface, such as the Network Management Web interface.
Startup configuration
Note: The configuration menu options vary according to the UPS models.
Function Description
Select the language required for the display interface.
Language Language options will vary by model and firmware version.
Options:
Francais • English
Italiano • Francais
• Italiano
Setup Wizard • Deutsch
• Espanol
• Portugues
• Japanese
• Russian
The Standard menu options are the most commonly used options.
Menu Type The Advanced menu options will be used by IT professionals who need
detailed configuration and reporting information.
Advanced
Setup Wizard
Auto 50/60 ± 3Hz Auto 50/60 ± 3 Hz Set the output frequency for the UPS.
Output 50 ± 0.1 Hz
Frequency 50 ± 3.0 Hz
60 ± 0.1 Hz
60 ± 3.0 Hz
Output 1 Hz/Sec 0.5 Hz/Sec Select the rate of change for output frequency in
Frequency 1 Hz/Sec Hertz per second.
2 Hz/Sec
Slew Rate 4 Hz/Sec
Allow Wider Frequency Allow Wider Frequency The setting Allow Wider Frequency, enables
Bypass Mode Bypass mode operation for an input frequency
Follow Frequency range of 47-63 Hertz.
Setting
Low Runtime 150 seconds 0 to 1800 seconds The UPS will emit an audible alarm when the
Alert remaining runtime has reached this threshold.
Startup + every 14 days Never This is the interval at which the UPS will
Self Test since last test Startup execute a Self Test.
Schedule Startup + 14 days
Startup + 7 days
PDU Model Standard Standard/SRT001/ Select the PDU model installed in the UPS
SRT004/SRT005 for proper operation of the PDU.
Default Setting No No/Yes Allows the user to restore the UPS factory
default settings.
Config Install Date Battery Installation Date Month-Year Enter the installation date of the RBCs.
Menu
Battery Replacement 183 days • 0-360 days To set the Near End of Life alarm, select
Notification • -1 the number of days before the estimated
Time battery end of life.
When this date is reached the UPS will emit
an audible alarm and a message will appear
on the display interface screen.
Example: Using the default value, the Near
End of Life alarm will occur 183 days
before the estimated end of life date.
To disable the notifications select -1.
Replacement 14 days • 0-180 days The Near End of Life audible alarm can be
Battery Alarm • -1 muted.
Reminder Enter the number of days between the time
a Near End of Life alarm is acknowledged
and the next Near End of Life alarm
occurs.
To disable the notifications select -1.
Config Language English English Select the language required for the display
Menu Francais interface.
Italiano
Display Deutsch Language options will vary by model and
Espanol firmware version.
Portugues
Japanese
Russian
Beeper Enabled Disable When audible alarms are disabled, the UPS
Volume will never emit an audible alarm.
Enable
LCD Auto Dim Always On To conserve energy, the LCD back light
Back Light Auto Dim illumination dims or turns off when no events
Auto Off are active.
Full display interface illumination returns when
the UPS changes status as a result of an event or
when any button on the display interface is
pressed.
LCD Setting Optimal Values Color Adjust the brightness and contrast individually
Brightness for each LCD back light color.
Contrast
Menu Type User Choice Standard The Standard menus include the most
Advanced commonly used options.
The Advanced menu options include all
parameters.
Config Power On 0 seconds 0-1800 seconds Select the amount of time the controllable outlet
Menu Delay groups will wait between receiving the
command to turn on and actual startup.
Outlets
Power Off 90 seconds 0-32767 seconds Select the amount of time the controllable outlet
Delay groups will wait between receiving the
command to shutdown and actual shutdown.
Reboot 8 seconds 4-300 seconds Select the amount of time the controllable outlet
Duration groups will remain off before the UPS will
restart.
Minimum 0 seconds 0-32767 seconds Select the amount of battery runtime that must
Return be available before the controllable outlet
groups will turn on using battery power, after a
Runtime shutdown.
Loadshed 5 seconds 5-32767 seconds Select the amount of time the controllable outlet
Time On groups will be allowed to function on battery
Battery power before shutdown.
Loadshed 0 seconds 0-3600 seconds When the selected runtime threshold is reached
Runtime the UPS will shutdown the controllable outlet
groups.
Config Modbus Disable Disable Allows the user to enable or disable the UPS
Menu Enable Modbus functionality
Commun
ication Modbus
Address
1 1 - 223 Allows the user to select the Modbus address
Modbus
Overview
The controllable outlet groups can be configured using the Advanced menu options.
Refer to “General settings” on page 19.
The controllable outlet groups can be configured to independently turn off, turn on, shutdown, switch to Sleep
mode, and reboot connected equipment.
• Turn Off: Disconnect output power to connected equipment either immediately using the Turn Off
Immediately feature or after a configured delay using the Turn Off With Delay feature.
Note: Controllable outlet groups can be turned on only using the Turn On feature.
• Turn On: Connect output power to connected equipment either immediately using the Turn On
Immediately feature or after a configured delay using the Turn On With Delay feature.
• Shutdown: Disconnects the power to connected equipment either immediately or after a configured delay.
Equipment reconnects after a configured delay when mains power becomes available and other configured
conditions are met.
Each controllable outlet group can be configured separately to allow power sequencing for equipment
connected to any controllable outlet group.
• Reboot: Disconnect the power to connected equipment either immediately or after a configured delay.
Reconnect equipment after a configured delay when either mains or battery power becomes available and
other configured conditions are met.
Each controllable outlet group can be configured separately to allow power sequencing for loads connected
to any controllable outlet group.
• Sleep: This mode is a reboot with an extended duration where a outlet(s) remain turned off.
Disconnect the power to connected equipment either immediately or after a configured delay. Reconnect
equipment after a configured delay when either mains or battery power becomes available and other
configured conditions are met.
Each controllable outlet group can be configured separately to allow power sequencing for equipment
connected to any controllable outlet group.
To configure Sleep mode use an external interface, such as the Network Management Web interface.
• Automatically turn off or shutdown when certain conditions occur, based on user configurations set using
the Config Menu Outlets menus. Refer to “Configuration” on page 18
CAUTION
RISK OF ELECTRIC SHOCK
• Adhere to all national and local electrical codes.
• Wiring must be performed by a qualified electrician.
• Always connect the UPS to a grounded outlet.
Failure to follow these instructions can result in minor or moderate injury.
The Network Management Interface and the AP9630 NMC have the same firmware, operation modes and
interaction with other APC products such as PowerChute Network Shutdown.
Refer to the Network Management Card utility CD supplied with this product.
Features
The Network Management Interface allows the UPS to function as a Web based, IPv6 ready
product.
The Network Management Interface can manage the UPS using multiple open standards such
as:
Simple Network Management Protocol versions Hypertext Transfer Protocol over Secure Sockets
1 and 3 (SNMPv1, SNMPv3) layer (HTTPS)
Telnet Syslog
RADIUS
IP Address Configuration
The default TCP/IP configuration setting DHCP, assumes that a properly configured DHCP server is available to
provide TCP/IP settings to the Network Management Interface.
If the Network Management Interface obtains an IPv4 address from a DHCP server, use the display interface
menus About/Interface, to see the address.
To setup a static IPv4 address use the display interface Config menu. Set the IP address Subnet Mask and Gateway
from the Config menu.
See the User’s Guide on the Network Management Card Utility CD for user information about the Network
Management Interface and for setup instructions.
Features
Smart Battery Management provides the following features:
Maintenance
• RBC maintenance: The APC RBC uses sealed lead acid battery cells and does not require maintenance.
• Runtime Test (Calibration): This should be performed anytime the steady state load is changed
significantly, for example a new server is added to or removed from the UPS load.
• Battery health monitoring: The battery energy output and voltage are monitored to assess the health of the
installed batteries when the UPS is operating on battery.
Battery health monitoring is done during a UPS Self Test, a Runtime Calibration Test, and when the UPS
is operating on battery power.
The UPS can be configured to perform periodic, automatic Self Tests.
An RBC should only be disconnected or removed from the UPS temporarily as part of the battery
replacement procedure.
• Disconnect all connected battery modules in the UPS. Slide the RBCs out of the UPS.
• Slide the new RBCs into the UPS and connect the battery modules to the UPS.
• Securely connect each battery module. Press the battery connector into the UPS until it is firmly connected.
A battery that is not fully connected will cause erratic UPS operation, abnormal error messages and
connected equipment may not receive battery power during power outages.
• After installing the RBC, the UPS display interface may prompt the user to verify the status of the replaced
battery modules. If the battery module is new, respond YES. If the battery module is not new, respond NO.
The UPS is not connected to mains Be sure the power cable is securely connected to the UPS and to the mains
power. power supply.
The UPS display interface screen shows Check the mains power supply to verify acceptable power quality.
very low or no mains power.
There is an internal UPS alert or warning. The UPS Display Interface screen will show a message to identify the alert
or warning and corrective action.
Normal UPS operation when running on The UPS is operating on battery power.
battery power. Refer to the status of the UPS as shown on the UPS Display Interface screen.
Press any key to mute all alarms.
The UPS emits an audible alarm and has An Alarm or Warning condition exists.
a red or amber back light on the UPS Refer to the display interface screen for information.
Display Interface screen.
The UPS batteries are weak due to a Charge the batteries. Batteries require recharging after extended outages and
recent power outage or they are near the wear out faster when put into service often or when operated at elevated
end of service life. temperatures. If the batteries are near the end of service life, consider
replacing the batteries even if the Replace Battery message is not displayed.
The UPS is experiencing an overload The connected equipment exceeds the specified maximum load. Refer to the
condition. APC web site, www.apc.com for product specifications.
The UPS will emit a sustained audible alarm until the overload condition is
corrected.
Disconnect nonessential equipment from the UPS to correct the overload
condition.
The input circuit breaker has tripped. Reduce the load on the UPS. Disconnect nonessential equipment and reset
the circuit breaker. Check the circuit breaker rating for the connected
equipment.
There is very high, very low, or distorted Navigate to the UPS Display Interface screen that shows input voltage.
input line voltage. Verify that the input voltage is within specified operating limits.
If no input voltage is indicated on the UPS Display Interface screen, contact
Customer Support through the APC web site, www.apc.com.
The UPS Display Interface screen shows The UPS has been configured to operate for a specified period of runtime.
the message Waiting for Minimum The setting can be changed through the Config/UPS menus.
Runtime.
UPS Display Interface Status screen shows Overload and the UPS emits a sustained audible alarm
The UPS is experiencing an overload The connected equipment exceeds the maximum load rating for the UPS.
condition.
The UPS will emit a sustained audible alarm until the overload condition is
corrected.
Disconnect nonessential equipment from the UPS to correct the overload
condition.
UPS Display Interface Status screen shows UPS is operating in Bypass mode
The UPS has automatically switched to The UPS Display Interface screen will show a message to identify the alert
Bypass mode due to an internal UPS or warning and corrective action.
alert or warning.
UPS Display Interface is red or amber and shows an alert or warning message
The UPS emits a sustained audible alarm
The UPS has detected a problem during Follow the instructions on the UPS Display Interface screen.
normal operation.
Press any key to mute all alarms.
The UPS Display Interface screen shows Be sure the battery cables are securely connected.
the message Disconnected Battery.
Perform a UPS Self Test to be sure the UPS detects all connected batteries.
To perform a UPS Self Test use the UPS Display Interface menu option Test
and Diagnostics.
The UPS Display Interface screen shows Allow the battery to recharge for 24 hours.
the message Replace Battery.
To perform a Runtime test use the UPS Display Interface menu option Test
and Diagnostics.
If the problem persists, replace all of the batteries.
The UPS display turns red or amber, displays an alert message, and emits a sustained audible alarm
Red illumination indicates a UPS alarm that requires immediate attention
Amber illumination indicates a UPS alarm that requires attention
There is an internal UPS alert or warning. Do not attempt to use the UPS. Turn the UPS off and have it serviced
immediately.
1/1
Error P.05
Contact Customer Support
Output Off 1 2 3
The UPS is experiencing an overload Reduce the load on the UPS. Disconnect nonessential equipment.
condition.
1/1
Output Overload
Backup Not Available
Bypass 1 2 3
The battery has a weak charge. Allow the battery to recharge for at least four hours. Then, perform a
UPS Self Test. If the problem persists after recharging, replace the battery.
The replacement battery is not properly Be sure the battery cable is securely connected.
connected.
UPS reports; Battery Sys Error 0800 or The UPS system firmware must be updated to correct this problem.
Needs Firmware Update
To update the UPS system firmware go to www.apc.com/support.
Select Search the Knowledge Base and search for FA164737.
Follow the instructions to upgrade the firmware.
Service
If the unit requires service, do not return it to the dealer. Follow these steps:
This warranty applies only to the original purchaser who must have properly registered the product within 10 days
of purchase. Products may be registered online at warranty.apc.com.
SEIT shall not be liable under the warranty if its testing and examination disclose that the alleged defect in the
product does not exist or was caused by end user or any third person misuse, negligence, improper installation,
testing, operation or use of the product contrary to SEIT recommendations of specifications. Further, SEIT shall not
be liable for defects resulting from: 1) unauthorized attempts to repair or modify the product, 2) incorrect or
inadequate electrical voltage or connection, 3) inappropriate on site operation conditions, 4) Acts of God, 5)
exposure to the elements, or 6) theft. In no event shall SEIT have any liability under this warranty for any product
where the serial number has been altered, defaced, or removed.
THE FOREGOING WARRANTIES AND REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL
OTHER WARRANTIES AND REMEDIES. THE WARRANTIES SET FORTH ABOVE CONSTITUTE
SEIT’S SOLE LIABILITY AND PURCHASER EXCLUSIVE REMEDY FOR ANY BREACH OF SUCH
WARRANTIES. SEIT WARRANTIES EXTEND ONLY TO ORIGINAL PURCHASER AND ARE NOT
EXTENDED TO ANY THIRD PARTIES.
NOTHING IN THIS LIMITED WARRANTY SHALL SEEK TO EXCLUDE OR LIMIT SEIT LIABILITY
FOR DEATH OR PERSONAL INJURY RESULTING FROM ITS NEGLIGENCE OR ITS
FRAUDULENT MISREPRESENTATION OF TO THE EXTENT THAT IT CANNOT BE EXCLUDED
OR LIMITED BY APPLICABLE LAW.
To obtain service under warranty you must obtain a Returned Material Authorization (RMA) number from
customer support. Customers with warranty claims issues may access the SEIT worldwide customer support
network through the APC web site: www.apc.com. Select your country from the country selection drop down
menu. Open the Support tab at the top of the web page to obtain information for customer support in your region.
Products must be returned with transportation charges prepaid and must be accompanied by a brief description of
the problem encountered and proof of date and place of purchase.
© 2017 APC by Schneider Electric. APC, the APC logo, PowerChute, and Smart-UPS are owned by