11Kv Voltage Class Surge Arrestors
11Kv Voltage Class Surge Arrestors
1.1. INTRODUCTION
This section covers the specification of 11kV voltage station Surge Arrestors for
installation on outdoor type 11kV switchgear, transmission lines, transformers etc.
11kV side of which is not enclosed in a cable box. Station class surge arrestors shall
be complete with fasteners for stacking units.
1.2. STANDARDS
The design, manufacture and performance of Surge Arrestors shall comply with
IS: 3070 Part-3 and other specific requirements stipulated in the specification. Unless
otherwise specified, the equipment, material & processes shall conform to the latest
amendments of the following:
The equipment complying with any other internationally accepted standards shall
also be considered if it ensures performance equivalent to or superior to the
Indian Standards.
1.3.2. The surge arrestor shall draw negligible current at operating voltage and at the
same time offer least resistance during the flow of surge current.
1.3.3. The surge arrestor shall consist of non-linear resistor elements placed in series and
housed in electrical grade porcelain housing / silicon polymeric of specified Creepage
distance.
1.3.4. The assembly shall be hermetically sealed with suitable rubber gaskets with effective
sealing system arrangement to prevent ingress of moisture.
1.3.5. The surge arrestor shall be provided with line and earth terminals of suitable size.
The ground side terminal of surge arrestor shall be connected with 25x6 mm
galvanized strip, one end connected to the surge arrestor and second end to a
separate ground electrode. The bidder shall also recommend the procedure which
shall be followed in providing the earthing system to the Surge Arrestor.
1.3.6. The surge arrestor shall not operate under power frequency and temporary over
voltage conditions but under surge conditions, the surge arrestor shall change over to
the conducting mode.
1.3.7. The surge arrestor shall be suitable for circuit breaker performing 0-0.3 min-CO-3
min-CO- duty in the system.
1.3.8. Surge arrestors shall have a suitable pressure relief system to avoid damage to the
porcelain/ silicon polymeric housing and providing path for flow of rated fault
currents in the event of arrestor failure.
1.3.9. The reference current of the arrestor shall be high enough to eliminate the influence of
grading and stray capacitance on the measured reference voltage.
1.3.10. The Surge Arrestor shall be thermally stable and the bidder shall furnish a copy of
thermal stability test with the bid.
1.3.11. The arrestor shall be capable of handling terminal energy for high surges, external
pollution and transient over voltage and have low losses at operating voltages.
1.3.12. The surge arrestor shall be provided with line and earth terminals of suitable size.
1.4. ARRESTOR HOUSING
1.4.1. The arrestor housing shall be made up of porcelain/silicon polymeric housing and
shall be homogenous, free from laminations, cavities and other flaws of imperfections
that might affect the mechanical and dielectric quality. The housing shall be of
uniform brown (for porcelain)/Grey (for silicon polymeric) colour, free from
blisters, burrs and other similar defects.
Arrestors shall be complete with fasteners for stacking units together and terminal
connectors.
1.4.2. The housing shall be so coordinated that external flashover shall not occur due to
application of any impulse or switching surge voltage upto the maximum design value
for arrestor. The arrestors shall not fail due to contamination. The 11kV arrestors
housing shall be designed for pressure relief class as given in Technical Parameters of
the specification.
The arrestors shall be suitable for mounting on 4 pole/2 pole structure used for
pole/plinth mounted transformer and for incoming and outgoing lines. Arrestor may
also be required to be mounted on a bracket provided in the Transformers.
1.6.1. The surge arrestor shall be complete with fasteners and terminal connectors.
1.6.2. The terminals shall be non-magnetic, corrosion proof, robust and of adequate size and
shall be so located that incoming and outgoing connections are made with minimum
possible bends. The top metal cap and base of surge arrestor shall be galvanized. The
line terminal shall have a built in clamping device which can be adjusted for both
horizontal and vertical take off.
1.7. TESTS
The Surge Arrestors offered shall be type tested and shall be subjected to
routine and acceptance tests in accordance with IS : 3070
(Part-3)-/IEC:600994. In addition, the suitability of the surge arresters shall also
be established for the followings.
i) Acceptance tests
a) Measurement of power frequency reference voltage of arrester units.
b) Lightning impulse residual voltage on arrester units (IEC clause 6.3.2)
c) Internal ionization or partial discharge test
9. Seismic Test
10. Partial Discharge test
11. Bending test
12. a) Temperature cycle test (for porcelain housing)
b) Porosity test (for porcelain housing)
13. Galvanising test on metal parts
14. Seal Leakage test (for porcelain housing)
15. Seal leak test and operation tests ( for surge monitor)
16. Weather ageing test (for polymer housing)
1.7.3. The contractor shall furnish the copies of the type tests and the characteristics
curves between the residual voltage and nominal discharge current of the offered
surge arrestor and power frequency voltage v/s time characteristic of the
surge arrestor subsequent to impulse energy consumption as per clause 6.6 of
IS:3070 (Part-3) offered alongwith the bid.
1.7.4. The surge arrestor housing shall also be type tested and shall be subjected to routine
and acceptance tests in accordance with IS :5621.
1.8.1. The name plate attached to the arrestor shall carry the following information:
- Rated Voltage
- Name of Sub-station
- Year of Manufacturer
1.10.1. The surge arrestors shall conform to the following standard technical requirements.
The Insulation values shall be enhanced considering the altitude of operation & other
atmospheric conditions.
System Parameters
v) Degree of protection IP 67
1.10.4. Galvanisation
ii) Castings
Grey Iron, malleable iron 610
g/m 2
2.1. INTRODUCTION
This section covers the specification of Distribution class Surge Arrestor for 11kV
transmission lines, transformers etc.
2.2. STANDARDS
The design, manufacture and performance of Surge Arrestors shall comply with
IS: 3070 Part-3 and other specific requirements stipulated in the specification. Unless
otherwise specified, the equipment, material and processes shall conform to the latest
applicable Indian/International Standards as listed hereunder:
2.2.1. The equipment complying with any other internationally accepted standards shall
also be considered if it ensures performance equivalent to or superior to the
Indian Standards.
2.3.1. The metal oxide gap less Surge Arrestor without any series or shunt gap shall be
suitable for protection of 11 kV side of Distribution Transformers, associated
equipment and 11 kV lines from voltage surges resulting from natural disturbance like
lightning as well as system disturbances.
2.3.2. The surge arrestor shall draw negligible current at operating voltage and at the
same time offer least resistance during the flow of surge current.
2.3.3. The surge arrestor shall consist of non-linear metal oxide resistor elements placed in
series and housed in electrical grade porcelain housing / silicon polymeric of specified
Creepage distance.
2.3.4. The assembly shall be hermetically sealed with suitable rubber gaskets with effective
sealing system arrangement to prevent ingress of moisture.
2.3.5. The surge arrestor shall be provided with line and earth terminals of suitable size.
The ground side terminal of surge arrestor shall be connected with 25x6 mm
galvanized strip, one end connected to the surge arrestor and second end to a
separate ground electrode. The contractor shall also recommend the procedure
which shall be followed in providing the earthing/system to the Surge Arrestor.
2.3.6. The surge arrestor shall not operate under power frequency and temporary over
voltage conditions but under surge conditions, the surge arrestor shall change over to
the conducting mode.
2.3.7. The surge arrestor shall be suitable for circuit breaker performing 0-0.3 min-CO-3
min-CO- duty in the system.
2.3.8. The reference current of the arrestor shall be high enough to eliminate the influence of
grading and stray capacitance on the measured reference voltage.
2.3.9. The Surge Arrestor shall be thermally stable and the contractor shall furnish a copy of
thermal stability test with the bid.
2.3.10. The arrestor shall be capable of handling terminal energy for high surges, external
pollution and transient over voltage and have low losses at operating voltages.
2.4.1. The arrestor housing shall be made up of porcelain/silicon polymeric housing and
shall be homogenous, free from laminations, cavities and other flaws of imperfections
that might affect the mechanical and dielectric quality. The housing shall be of
uniform brown (for porcelain)/ Grey (for silicon polymeric) colour, free from
blisters, burrs and other similar defects.
2.4.2. The housing shall be so coordinated that external flashover shall not occur due to
application of any impulse or switching surge voltage upto the maximum design value
for arrestor. The arrestors shall not fail due to contamination.
The arrestors shall be suitable for mounting on 4 pole/2 pole structure used for pole
mounted transformer and for incoming and outgoing lines.
2.6. FITTINGS & ACCESSORIES
2.6.1. The surge arrestor shall be complete with disconnector and terminal connectors and
all other accessories.
2.6.2. The terminals shall be non-magnetic, corrosion proof, robust and of adequate size and
shall be so located that incoming and outgoing connections are made with minimum
possible bends. The top metal cap and base of surge arrestor shall be galvanized.
The line terminal shall have a built in clamping device which can be adjusted for both
horizontal and vertical take off.
2.7. TESTS
The Surge Arrestors offered shall be type tested and shall be subjected to routine
and acceptance tests in accordance with IS : 3070 (Part-3)-1993. In addition, the
suitability of the surge arresters shall also be established for the followings
a) Acceptance tests:
i) Measurement of power frequency reference voltage of arrester units.
ii) Lightning impulse residual voltage on arrester units (IEC clause 6.3.2)
iii) Internal ionization or partial discharge test
b) Special Acceptance tests:
i) Thermal stability test (IEC clause 7.2.2)
c) Routine tests:
Measurement of reference voltage
i) Residual voltage test of arrester unit
ii) Internal ionization or partial discharge test
iii) Sealing test
iv) Verticality check on completely assembled surge arresters as a sample test on
each lot if applicable.
d) Type tests: Following shall be type test As per IS 3070 (Part 3)-/IEC;60094 or its latest
amendment
2.7.3. The contractor shall furnish the copies of the type tests and the characteristics
curves between the residual voltage and nominal discharge current of the offered
surge arrestor and power frequency voltage v/s time characteristic of the
surge arrestor subsequent to impulse energy consumption as per clause 6.6.7 of
IS:3070 (Part-3) offered alongwith the GTP.
2.7.4. The surge arrestor housing shall also be type tested and shall be subjected to routine
and acceptance tests in accordance with IS: 5621
2.8.1. The name plate attached to the arrestor shall carry the following information:
- Rated Voltage
- Year of Manufacturer
- Name of Client-
The successful bidder shall furnish to the purchaser the following drawings and
literature for approval:
2.10.1. The surge arrestors shall conform to the following standard technical requirements.
The Insulation values shall be enhanced considering the altitude of operation & other
atmospheric conditions.
System Parameters
2.12. GALVANISATION
i) Fabricated Steel Aticles
a) 5 mm thick cover 610 g/m2
b) Under 5 mm but not less than 2 mm thickness 460 g/m2
c) Under 2 mm but not less than 1.2 mm thickness 340 g/m2
ii) Castings
Grey Iron, malleable iron 610 g/m2