Serial Communication Protocol: MODBUS Commands
Serial Communication Protocol: MODBUS Commands
The Modu_control card allows an inter- To enable communication from a supervi- It is also necessary to ensure compliance
face with a centralised system via a spe- sion system to the Moducontrol card, you with the following characteristics:
cial serial expansion card based on the must set the following parameters: • Stop bits: 2;
RS485 electric standard and using the • Parametro J - Ad1 (Indirizzo modbus • Parity: NONE;
Modbus RTU standard protocol. del supervisore);
The Modu_Control card is always the • Parametro L - Bd1 (Baudrate supervisore);
slave of the communication.
MODBUS commands
The Modu_Control card manages (towards the BMS/VMF supervisor) both
the Register values (whole/analogue) and the Coil values (digital). The
commands that can be used to read/write these values are:
!
Read Coil Status the Modu_Control card, you must enable the
supervision commands by setting the parameter
Force Single Coil parameter (N) = 1 of the installer menu
Force Multiple Coils (password=30) of the panel on the machine.
ADDRESS DESCRIPTION
0 Standby/On command (toggle) 0=OFF 1=ON
1 Operation mode command (toggle) 0=COOL 1=HEAT
2 Domestic water remote command 0=Normal, 1=Domestic
3 Enable remote thermostat 0=Disabled, 1=Enabled
4 Alarm reset command 1=Alarm reset
5 Compressor1 status 0=OFF 1=ON
6 Compressor2 status 0=OFF 1=ON
7 Boiler/electric heater status 0=OFF 1=ON
8 Hot domestic water production status 0=not active 1=active
9 Domestic water ID status 0=ID closed – 1=ID open
10 Remote ON_OFF ID status 0=ID closed – 1=ID open
11 Season ID status 0=ID closed (cool), 1=ID open (heat)
12 Room thermostat ID status 0=ID closed – 1=ID open
13 Alarm summary
14 Pre-alarm summary
15 Compressor thermomagnetic switch pre-alarm
16 Fan thermomagnetic switch pre-alarm
64
GB 6343841_00 / Ver - 4.20
ADDRESS DESCRIPTION
17 High pressure switch pre-alarm
18 Flow switch/differential pressure switch (water) pre-alarm
19 Low pressure switch pre-alarm
20 Pre-alarm for absence of NTC1 input probe (SIW)
21 Pre-alarm for absence of NTC2 input probe (SUW)
22 Anti-freeze pre-alarm
23 Pre-alarm for absence of NTC4 input probe (SGP)
24 Pre-alarm for high discharge gas temperature
25 Pre-alarm for absence of compressor delivery transducer
26 High pressure pre-alarm
27 Pre-alarm for absence of NTC3 input probe (SS)
28 Pre-alarm for absence of suction transducer
29 Low pressure pre-alarm
30 Low output pre-alarm
31 Pump thermomagnetic switch pre-alarm
32 High pressure capacity control pre-alarm
33 Low pressure capacity control pre-alarm
34 Discharge temperature capacity control pre-alarm
35 Bemf error pre-alarm (longertek inverter)
36 Pre-alarm for internal communication error (longertek)
37 Overcurrent pre-alarm (longertek)
38 Pre-alarm for absence of load (longertek)
39 Pre-alarm for incorrect voltage (longertek)
40 Pre-alarm for start-up error (longertek)
41 Pre-alarm for IPM protection error (longertek)
42 Pre-alarm for EEPROM error (longertek)
43 Pre-alarm for compressor stalling (longertek)
44 Pre-alarm for absence of communication (longertek)
45 PFC module pre-alarm (longertek)
46 Pre-alarm for cooling over-temperature (APY)
47 Pre-alarm for overcurrent in acceleration (APY)
48 Pre-alarm for overcurrent at steady speed (APY)
49 Pre-alarm for overcurrent in deceleration (APY)
50 Pre-alarm for undervoltage on BUS DC (APY)
51 Pre-alarm for overvoltage on BUS DC (APY)
52 NOT USED
53 NOT USED
54 Pre-alarm for converter PFC fault (APY)
55 Pre-alarm for overcurrent in acceleration (APY)
56 Overload pre-alarm (APY)
57 Pre-alarm for overcurrent at steady speed (APY)
58 Pre-alarm for overcurrent in deceleration (APY)
59 Pre-alarm for incorrectly connected compressor (APY)
60 Pre-alarm for absence of communication (APY)
61 Pre-alarm for cooling fin temperature sensor error (APY)
62 NOT USED
63 NOT USED
65
6343841_00 / Ver - 4.20 GB
ADDRESS DESCRIPTION
64 NOT USED
65 Fault condition pre-alarm (APY)
66 NOT USED
67 NOT USED
68 Reverse cycle valve pre-alarm
69 Pre-alarm for high water inlet temperature
70 Pre-alarm for reverse cycle due to high discharge gas temperature
71 NOT USED
72 NOT USED
73 NOT USED
74 NOT USED
75 NOT USED
76 NOT USED
77 NOT USED
78 NOT USED
79 NOT USED
80 NOT USED
81 NOT USED
82 NOT USED
83 NOT USED
84 NOT USED
85 Compressor thermomagnetic switch alarm
86 Fan thermomagnetic switch alarm
87 High pressure switch alarm
88 Flow switch/differential pressure switch (water) alarm
89 Low pressure switch alarm
90 Alarm for absence of NTC1 input probe (SIW)
91 Alarm for absence of NTC2 input probe (SUW)
92 Anti-freeze alarm
93 Alarm for absence of NTC4 input probe (SGP)
94 Alarm for high discharge gas temperature
95 Alarm for absence of compressor delivery transducer
96 High pressure alarm
97 Alarm for absence of NTC3 input probe (SS)
98 Alarm for absence of suction transducer
99 Low pressure alarm
100 Low output alarm
101 Pump thermomagnetic switch alarm
102 High pressure capacity control alarm
103 Low pressure capacity control alarm
104 Discharge temperature capacity control alarm
105 Bemf error alarm (longertek inverter)
106 Alarm for internal communication error (longertek)
107 Overcurrent alarm (longertek)
108 Alarm for absence of load (longertek)
109 Alarm for incorrect voltage (longertek)
110 Alarm for start-up error (longertek)
66
GB 6343841_00 / Ver - 4.20
ADDRESS DESCRIPTION
111 Alarm for IPM protection error (longertek)
112 Alarm for EEPROM error (longertek)
113 Alarm for compressor stalling (longertek)
114 Alarm for absence of communication (longertek)
115 PFC module alarm (longertek)
116 Alarm for cooling over-temperature (APY)
117 Alarm for overcurrent in acceleration (APY)
118 Alarm for overcurrent at steady speed (APY)
119 Alarm for overcurrent in deceleration (APY)
120 Alarm for undervoltage on BUS DC (APY)
121 Overvoltage alarm (APY)
122 NOT USED
123 NOT USED
124 Alarm for converter PFC fault (APY)
125 Alarm for overcurrent in acceleration (APY)
126 Overload alarm (APY)
127 Alarm for overcurrent at steady speed (APY)
128 Alarm for overcurrent in deceleration (APY)
129 Alarm for incorrectly connected compressor (APY)
130 Alarm for absence of communication (APY)
131 Alarm for cooling fin temperature sensor error (APY)
132 NOT USED
133 NOT USED
134 NOT USED
135 Fault condition alarm (APY)
136 NOT USED
137 NOT USED
138 Alarm for faulty reverse cycle valve
139 Alarm for high water inlet temperature
140 Alarm for reverse cycle due to high discharge gas temperature
141 (Code 57) Alarm remote reading of the probe within DHW
142 (Code 58) Alarm reading of temperature sensor outside air
143 NOT USED
144 NOT USED
145 NOT USED
146 NOT USED
147 NOT USED
148 NOT USED
149 NOT USED
150 NOT USED
151 NOT USED
152 NOT USED
153 NOT USED
154 NOT USED
67
6343841_00 / Ver - 4.20 GB
READ LIST REGISTER:
COMANDI LETTURA DISPONIBILI
Read Holding Register
ADDRESS DESCRIPTION
0 Type of machine: 0 – ANL,1 – ANLI, 2 – ANR/ANF/SRP, 3 – ANL-C
1 Type of inverter machine 0=longertek 1=APY
2 NTC1 input (TUA) (SIW)
3 NTC2 input (TIA) (SUW)
4 NTC3 input (TSB) (SS)
5 NTC4 input (TGP) (SGP)
6 NTC5 input (TAE) (SAE)
7 High pressure transducer input (AP) (TAP)
8 Low pressure transducer input (BP) (TBP)
9 0-10V dd input
10 Relay digital output status
11 Safety band on force OFF
12 Time until compressor start-up/switch-off
13 Hours of primary compressor operation (in thousands)
14 Hours of primary compressor operation
15 Number of peaks made by the compressor (in thousands)
16 Number of peaks made by the compressor
17 Major sw version
18 Minor sw version
19 Machine adjustment setpoint (including corrections)
20 Condensation control pressure setpoint
21 Pressure differential for condensation control
22 Hours of auxiliary compressor operation (in thousands)
23 Hours of auxiliary compressor operation
24 Number of peaks made by the auxiliary compressor (in thousands)
25 Number of peaks made by the auxiliary compressor
26 Power supplied by the machine (chiller ON-OFF) Use frequency (chiller inverter)
27 Compressor pressure drop during suction
28 Power requested from the inverter control
29 Dip-switch configuration (0x0000 = all OFF - 0x0FF = all ON)
30 ON_OFF command enablement status Season from panel or remote panel
31 Enablement status for room thermostat connected to ID3 input
32 Machine operation status: 0 - Chiller Off, 1 - Chiller On, 2 – Capacity control
injection, 3 – Defrosting for injection, 4 – Defrosting for reverse cycle
33 Electric heater/boiler accessory: 0=absent 1=electric heater 2=boiler
34 Inverter current APY
35 Inverter output voltage APY
36 Inverter BUS voltage APY
37 Inverter cooling fin temperature APY
38 Limit set point hot
68
GB 6343841_00 / Ver - 4.20
WRITE LIST REGISTER:
COMANDI SCRITTURA DISPONIBILI
Preset Single Register
Preset Multiple Registers
LIST OF EXCEPTIONS:
! The error codes highlighted by the Modu Control card are shown below:
EXCEPTION DESCRIPTION
The requested function code is not managed by the card.
The data request contains a reference to an address that is not
available on the card.
The data write request contains a value that is out of range,
so writing is not allowed.
69