HAT560N Series (HAT560N /HAT560NB) Ats Controller
HAT560N Series (HAT560N /HAT560NB) Ats Controller
(HAT560N /HAT560NB)
ATS CONTROLLER
HAT560N series ATS controller is intelligent dual-supply module with configurable function, automatic
measurement, LCD display, and digital communication. It combines digital, intelligence and networking.
Automatic measurement and control can reduce incorrect operation. It is an ideal option for ATS.
The powerful Microprocessor contained within the unit allows for precision voltage
(2-way-3-phase/single phase) measuring and make accurate judgment; in addition, the corresponding
digital output port will active when there is over/under voltage, over/under frequency, loss of phase and
other abnormal condition occurs. This controller has full consideration in various application of ATS
(automatic transfer system) and can be directly used for specialized ATS, Contactor ATS, Air break ATS
etc. It has compact structure, advanced circuits, simple wiring and high reliability, and can be widely
used in electrical devices, automatic control and testing system of electric power, telecommunications,
petroleum, coal, metallurgy, railways, municipal administration, intelligent building, etc.
Manual/Auto Set Press the button and controller enter into Manual or Auto mode.
Press the button to enter into menu interface; pressing and holding it to
Menu /Confirm return to the main menu interface. When an alarm occurs, pressing and
holding the button for more than 3s can remove alarm.
Scroll the screen. In parameter setting, pressing this button can
decrease values.
Scroll Screen Pressing and holding the button for more than 3s, there is a flash on the
/Increase backlight to confirm the “always illuminated” mode is selected.
Pressing and holding the button for more than 3s again, the backlight
will extinguished which means the “normal display” mode is selected.
Terminal description,
No. Functions Description Remark
Connected with negative of starter
1 B- DC input B-
battery.
Connected with positive of starter
2 B+ DC(8-35)V; Power supplied by controller.
battery.
3
Aux. output 1 Default: 1# open output Relay contact output; Volts free; Rated 7A
4
5 Normally Close Default: Gen Start
6 Aux. output 2 COM Output (Normally Relay contact output; Volts free; Rated 7A
7 Normally Open Open)
8 Normally Close
Default: ATS
9 Aux. output 3 COM Relay contact output; Volts free; Rated 16A
Power A
10 Normally Open
11 Normally Open
Default: ATS
12 Aux. output 4 COM Relay contact output; Volts free; Rated 16A
Power N
13 Normally Close
14 Relay contact output; Volts free; Rated 16A
1# Close Output Relay contact output; Volts free;
15
16 Relay contact output; Volts free; Rated 16A
2# Close Output Relay contact output; Volts free;
17
18 A1
19 B1
1# AC System 3P4W voltage input For single phase, only connect A1, N1
20 C1
21 N1
19 FAULT FINDING
Symptom Possible Solutions
Controller no response with
Check starting batteries;
power.
Ensure that the auxiliary input is soundly connected to GND when it’s
active, while hung up when it is inactive.
Auxiliary Input Abnormal
( Note: The input port will be possibly destroyed when connected with
voltage)
Check ATS.
Genset running while ATS
Check the connection wirings between the controller and the ATS.
not transfer
Ensure that the ATS Neutral position whether is same as the setting.