U S C ATA LO G
—
UL 489 series
SU200M, SUP200M, SU200MR,
S200UDC, S800U, S800U-UCZ
Description Features
ABB's UL 489 miniature circuit breakers offer a • UL current limiting
compact solution for all branch circuit protection • Fast breaking time (2.3–2.5 ms)
requirements. They are current-limiting according • Bus connection system
to UL 489 and DIN rail mounted. • Wide range of accessories
• Available with variable depth handle mechanism
ABB's UL 489 MCBs come in up to three trip curves • CE certified and marked
to provide maximum circuit protection. • DIN rail mounting
• Finger-safe terminals
For the worldwide market, the breakers carry UL, • Multi-function terminals
CSA, IEC, CE and many other agency approvals • Suitable for reverse feed (except for S200UDC)
and certifications. • UL 489 listed branch circuit protective device,
UL File #E212323 and E312425
S800U S800U-UCZ
Amperage 10–100 A 10–80 A
Voltage 240 V AC 600 V DC
Poles 1, 2, 3, 4 4 in series
Trip curves Z (B), K Z (K)
Short circuit interrupt rating 30/50 kA (1-/multipole) 10 kA
Auxiliary contacts yes –
Bell alarm yes –
Shunt trip yes –
Undervoltage release yes –
Rotary handle mechanism yes –
Motor operator yes –
Terminals compression/ring tongue compression
OVERVIE W UL4 89 CIRCUIT BRE AKERS, SU200M SERIES 5
—
SU200M-C
Branch circuit protection — UL 489, CSA 22.2 No. 5
—
SU200M-K
Branch circuit protection — UL 489, CSA 22.2 No. 5
—
SU200M-Z
Branch circuit protection — UL 489, CSA 22.2 No. 5
—
SUP200M-C
Branch circuit protection — UL 489, CSA 22.2 No. 5
—
SUP200M-K
Branch circuit protection — UL 489, CSA 22.2 No. 5
Diagram 30 SUP202M-K30
32 SUP202M-K32
35 SUP202M-K35
10 S Y S T E M P R O M C O M PA C T ™ C I R C U I T P R OT E C T I O N D E V I C E S O N D I N R A I L
—
SUP200M-Z
Branch circuit protection — UL 489, CSA 22.2 No. 5
—
SU200MR-K with ring tongue terminals
Branch circuit protection — UL 489, CSA 22.2 No. 5
—
S200UDC-K
Branch circuit protection — UL 489, CSA 22.2 No. 5
Rated current
In
Number of poles A Cat. No.
1 1 S201UDC-K1
1.6 S201UDC-K1.6
2 S201UDC-K2
3 S201UDC-K3
4 S201UDC-K4
5 S201UDC-K5
6 S201UDC-K6
8 S201UDC-K8
10 S201UDC-K10
13 S201UDC-K13
15 S201UDC-K15
16 S201UDC-K16
20 S201UDC-K20
25 S201UDC-K25
30 S201UDC-K30
32 S201UDC-K32
40 S201UDC-K40
50 S201UDC-K50
Diagram 60 S201UDC-K60
63 S201UDC-K63
2 1 S202UDC-K1
1.6 S202UDC-K1.6
2 S202UDC-K2
3 S202UDC-K3
4 S202UDC-K4
5 S202UDC-K5
6 S202UDC-K6
8 S202UDC-K8
10 S202UDC-K10
13 S202UDC-K13
15 S202UDC-K15
16 S202UDC-K16
20 S202UDC-K20
25 S202UDC-K25
30 S202UDC-K30
32 S202UDC-K32
40 S202UDC-K40
50 S202UDC-K50
60 S202UDC-K60
63 S202UDC-K63
—
S200UDC-Z
Branch circuit protection — UL 489, CSA 22.2 No. 5
Rated current
In
Number of poles A Cat. No.
1 1 S201UDC-Z1
1.6 S201UDC-Z1.6
2 S201UDC-Z2
3 S201UDC-Z3
4 S201UDC-Z4
5 S201UDC-Z5
6 S201UDC-Z6
8 S201UDC-Z8
10 S201UDC-Z10
13 S201UDC-Z13
15 S201UDC-Z15
16 S201UDC-Z16
20 S201UDC-Z20
25 S201UDC-Z25
30 S201UDC-Z30
32 S201UDC-Z32
40 S201UDC-Z40
50 S201UDC-Z50
60 S201UDC-Z60
63 S201UDC-Z63
2 1 S202UDC-Z1
1.6 S202UDC-Z1.6
2 S202UDC-Z2
3 S202UDC-Z3
4 S202UDC-Z4
Diagram 5 S202UDC-Z5
6 S202UDC-Z6
8 S202UDC-Z8
10 S202UDC-Z10
13 S202UDC-Z13
15 S202UDC-Z15
16 S202UDC-Z16
20 S202UDC-Z20
25 S202UDC-Z25
30 S202UDC-Z30
32 S202UDC-Z32
40 S202UDC-Z40
50 S202UDC-Z50
60 S202UDC-Z60
63 S202UDC-Z63
Note: Standard UL 489 (only DC; please note polarity of device).
14 S Y S T E M P R O M C O M PA C T ™ C I R C U I T P R OT E C T I O N D E V I C E S O N D I N R A I L
—
S800U-K, 240 V AC
Branch circuit protection — UL 489
Diagram
10 000
1000
100
10
1
seconds
0.1
0.01
1 2 3 10 20 30
—
S800U-Z, 240 V AC
Branch circuit protection — UL 489
Diagram
10 000
1000
100
10
1
seconds
0.1
0.01
1 2 3 5 10 20 30
—
S804U-UCZ
—
Ordering information
—
Accessories
SU200M, SUP200M, SU200MR and S200UDC — UL 489, CSA 22.2 No. 5
Note: For shafts and handles, refer to parts in the Disconnect Switch and MCCB section.
+H+H+H
+ST+H+H+H)
—
Accessories
SU200M, SUP200M, SU200MR and S200UDC — UL 489, CSA 22.2 No. 5
—
Accessories
SU200M, SUP200M, SU200MR and S200UDC — UL 489, CSA 22.2 No. 5
Connection drawings
96 98 96 98 96 98 12 14
Shunt
trip
in OFF
Reset 95 Reset 95 Reset 95 11 position
test test test
96 98 96 98 12 14
Reset 95 Reset 95 11
test test
Mounting
S200U-UP S2C-A....U
On On
On On
C C
A A
B B
D S2C-A...U
D S200U-UP
Addition of a S2C-H6RU auxiliary contact Addition of a S2C-S6RU bell alarm contact Addition of a S2C-A...U shunt trip
20 S Y S T E M P R O M C O M PA C T ™ C I R C U I T P R OT E C T I O N D E V I C E S O N D I N R A I L
—
Accessories
SU200MR — UL 489, CSA 22.2 No. 5
—
Accessories
SU200M, SUP200M, SU200MR and S200UDC — UL 489, CSA 22.2 No. 5
Amp rating* Number of poles Phases Busbar length (mm) Cat. No.
80/115 6 1 103.2 PS 1/6/16BP
12 1 208.8 PS 1/12/16BP
18 1 314.4 PS 1/18/16BP
80/115 6 2 103.2 PS 2/6/16BP
12 2 208.8 PS 2/12/16BP
18 2 314.4 PS 2/18/16BP
80/115 6 3 103.2 PS 3/6/16BP
12 3 208.8 PS 3/12/16BP
18 3 314.4 PS 3/18/16BP
*Depending on enclosure size
— —
Busbar tooth covers for BS...BP (UL 489) Feeder terminals for PS...BP (UL 489)
—
Busbars PS...BP-C for use with SU200M, SUP200M and S200UDC, can be cut to length
—
Accessories
—
Accessories
SU200M, SUP200M, SU200MR and S200UDC — UL 489, CSA 22.2 No. 5
—
Busbars for SU200MR, can be cut to length
—
Accessories
—
Lockout/tag out device
Filling piece
For heat dissipation of closely mounted devices
that generate much heat. Width 8.75 mm, as spacer,
two different heights, breakable, for DIN rails
according to DIN EN 60 715, 35 x 7.5 mm.
—
Accessories
SU200M, SUP200M, SU200MR and S200UDC — UL 489, CSA 22.2 No. 5
—
False poles
—
Flanges
Weight 1 piece Pack unit
kg pc. Cat. No.
Flange for rear board mounting 0.040 1 ME 1
1 module — IP40
Flange for rear board mounting 0.045 1 ME 2
2 modules — IP40
Flange for rear board mounting 0.055 1 ME 3
3 modules — IP40
Flange for rear board mounting 0.060 1 ME 4
4 modules — IP40
Flange for rear board mounting 0.070 1 ME 6
6 modules — IP40
Flange for rear board mounting 0.080 1 ME 8
8 modules — IP40
24 S Y S T E M P R O M C O M PA C T ™ C I R C U I T P R OT E C T I O N D E V I C E S O N D I N R A I L
—
S800W-RSU Remote switching unit
UL 489
— —
Remote switching unit S800-RSU cable including plug
Key features —
Technical specifications
• The remote switching unit S800W-RSU has a brushless high
precision DC motor to ensure fast remote control operation
Operational voltage 24 V DC
• Low power consumption
Current consumption Ims 2, 5
• Short switching times
Standby current IStandby < 50 mA
• The S800W-RSU is mounted on any multi-pole S800 high-
Switching time OFF-ON < 500 msec
performance MCB
Switching time ON-OFF <250 msec
• Installation and wiring can be field installable
Ambient operation temperature -25 °C to 70 °C
• The connection is done by a 10-pole Micro-Fit 3.0™
Number of switching operations 10.000
(not included in delivery)
Maximum cable lengths (20 AWG/0.5 mm2) 10 m
• The S800W-RSU can be operated by a standard pushbutton
or drive by a PLC Degree of protection (mounted) IP2
Weight 0.661387 lb.
2CCCA1327370001
Safety intelligence
72.5
than 360°
19 45.4
• S800W-RSU is locked for five minutes after three switching
3
31.6
attempts leading to a trip
Approximate dimensions shown are in mm.
• Manual switch off possible for three- and four-pole devices
ACCESSORIES AND BUSB ARS 25
—
Accessories
S800U
Under-voltage release
When control voltage drops below approximately 50 percent
of rated voltage, the UVR opens the breaker. The breaker
cannot be operated unless proper control voltage is first —
applied to the UVR coil. Ring tongue adapter
Auxiliary contacts
The auxiliary contacts will signal whether the breaker is in the
ON or OFF position.
—
Accessories
S800U
—
Technical specifications
SU200M, SUP200M, SU200MR and S200UDC — UL 489, CSA 22.2 No. 5
—
Technical specifications
—
Auxiliary contact S2C-H6RU and S2C-S6RU
Rated current 10
Rated voltage AC/DC 24
Contact 1 pole double throw
Connection capacity 18–14 AWG (0.75–2.5 mm2)
Tightening torque 11 in. lbs (1.2 Nm)
Shock resistance acc. to DIN IEC 68-2-6 5 g, 20 frequency cycles 5...150...5 Hz at 24 V AC/DC, 5 mA auto-reclosing < 10 ms
Mechanical service life 10,000 operations
—
Shunt trip
S2C-A1U S2C-A2U
Rated voltage V AC 12–60 110–415
V DC 12–60 110–250
Maximum release duration ms <10 <10
Minimum release voltage V AC 7 55
V DC 10 80
Consumption on release VA AC 40–200 55–210
VA DC 40–200 55–110
Coil resistance V 3.7 225
Terminals AWG/mm2 18–6/0.75–16 18–6/0.75–16
Tightening torque in. lbs./Nm 18/2 18/2
28 S Y S T E M P R O M C O M PA C T ™ C I R C U I T P R OT E C T I O N D E V I C E S O N D I N R A I L
—
Technical specifications
Busbars PS...BP-C/CR and accessories
Installation/assembly
Dimensional drawing 19.3
Warning: When busbars
are shortened, they must
be deburred and cleaned 28.50
1.8
17.60
5.00 950-1003
10.50 1.8
13.70
.3
Ø5
57.8
—
Technical specifications
SU200M, SUP200M, SU200MR and S200UDC — UL 489, CSA 22.2 No. 5
— —
—
SU200M SUP200M
SU200MR
—
Technical specifications
SU200M, SUP200M, SU200MR and S200UDC — UL 489, CSA 22.2 No. 5
—
Temperature derating for SU200M, SUP200M and SU200MR
—
Technical specifications
S200UDC series DC applications
DC = Direct current For DC incoming supply from above S200UDC-… MCBs have,
S200UDC MCBs can be used in the one-pole version at 125 V in the area of arc chutes, permanent magnets. It is therefore
DC (60 V DC above 40 A), and in the 2-pole version, with both necessary to take into account the polarity during the
poles connected in series, at 250 V DC (125 V DC above 40 A). installation process.
S200UDC contains fitted permanent magnets, which assist Doing so ensures that in the case of a short circuit, the
in the forced extinguishing of the arc. If voltages to earth magnetic field of the permanent magnets corresponds
exceeding 125 V DC (60 V DC above 40 A) may occur, 2-pole with the electromagnetic field of the short-circuit current,
S200UDC is to be used for one-pole disconnection. therefore safely leading the short circuit into the arc chute.
—
Example for permissible voltages between the conductors depending on the number of poles and circuit layout (for
ampacities up to 40 A; for ampacities above 40 A, the corresponding voltages are reduced to 60 V and 125 V instead of
125 V and 250 V, respectively):
—
Technical specifications
S200UDC series DC applications
—
Examples for different voltage levels between conductor and earth in the case of identical voltage between conductors:
—
Approximate dimensions
SU200M, SUP200M, SU200MR and S200UDC — UL 489, CSA 22.2 No. 5
71
69
49.5 44 17.5 35 52.5 70
14.05
17.5 35 52.5 70
11.4
45 92
45 85 111
6.8
17.5
22
17.3 6.9
20
SU200MR
69
49.2
45 85 115
2.5 25 6.8
8.8 17.5
100 100
—
Technical specifications
S800U
S800U
Characteristics K, Z
Rated operational current Ie [A] 10...100
Pole 1...4
Rated operational voltage Ue compliant to UL489
(AC) 50/60 Hz [V] 240
Rated ultimate short-circuit breaking capacity compliant to UL489
(AC) 50/60 Hz 240 V Single-pole [kA] 30
(AC) 50/60 Hz 240 V Multi-pole [kA] 50
Rated operational voltage Ue compliant to IEC 60947-2
(AC) [V] 240/415
Rated ultimate short-circuit breaking capacity Icu compliant to IEC 60947-2
(AC) 50/60 Hz 240/415 V Single-pole [kA] 30
(AC) 50/60 Hz 240/415 V Multi-pole [kA] 50
Rated service short-circuit breaking capacity Ics compliant to IEC 60947-2
(AC) 50/60 Hz 240/415 V Single-pole [kA] 25
(AC) 50/60 Hz 240/415 V Multi-pole [kA] 40
Connections Cu 10–30 A 14–2 AWG
40–100 A 8–1 AWG
Rated frequency [Hz] 50/60
Tightening torque [Nm] 3,5 (31 in. lb.)
Protection category IP40
(actuating end only)
Mounting position Any
Contacts Cadmium-free
Permissible ambient temperature [ °C] -25 °C to 60 °C
Standards UL489
IEC 60947-2
CSA22.2 No.5-02
Approval cULus
File E312425
T E C H N I C A L D ATA A N D D R A W I N G S 35
—
Technical specifications
S800U
—
Typical internal resistances and power losses at 25 °C ambient temperature
In [A] 10 °C 15 °C 20 °C 25 °C 30 °C 35 °C 40 °C 45 °C 50 °C 55 °C 60 °C
10 10.9 10.7 10.4 10.0 9.6 9.3 9.0 8.7 8.4 8.0 7.6
15 16.5 16.0 15.6 15.0 14.4 14.0 13.5 13.0 12.6 12.0 11.4
20 22.0 21.4 20.8 20.0 19.2 18.6 18.0 17.4 16.8 16.0 15.2
25 27.5 26.8 26.0 25.0 24.0 23.3 22.5 21.8 21.0 20.0 19.0
30 33.1 32.1 31.2 30.0 28.8 27.9 27.0 26.1 25.2 24.0 22.9
40 44.0 42.8 41.6 40.0 38.4 37.2 36.0 34.8 33.6 32.0 30.9
50 55.1 53.5 52.0 50.0 48.0 46.5 45.0 43.5 42.0 40.0 38.3
60 66.2 64.2 62.4 60.0 57.6 55.8 54.0 52.2 50.4 48.0 46.0
70 76.9 74.9 72.8 70.0 67.2 65.1 63.0 60.9 58.8 56.0 53.4
80 88.0 85.6 83.2 80.0 76.8 74.4 72.0 69.6 67.1 64.0 61.6
90 99.1 96.3 93.6 90.0 86.4 83.7 81.0 78.3 75.6 72.0 69.5
100 110.5 107.0 104.0 100.0 96.0 93.0 90.0 87.0 83.8 80.0 77.8
36 S Y S T E M P R O M C O M PA C T ™ C I R C U I T P R OT E C T I O N D E V I C E S O N D I N R A I L
—
Technical specifications
S800U
—
Auxiliary contact S800-AUX
S800-AUX
Usage category AC15 400/2 A-UL
AC15 240/ -UL
DC13 250/0.55 A125 V/1.1A-IEC
DC13 125 V/1.1A
DC13 60 V/2A
DC13 24 V/4A
Continuous thermal current In 6A
Rated insulation voltage Ui 690 V
Number of contacts 2
Surge Utest (1.2/50μs) 6 kV
Degree of protection 3
Function of contact Changeover contacts
Connection Cu 1 x 2.5 mm2
2 x 1.5 mm2
Tightening torque 1 Nm
Ensured contacts during shake test 5g, 20 frequency cycle
acc. to IEC 68-2-6 at 24 V AC/DC, 5mA brief interrupt <10 ms
AC/DC supply Any EN 60715
Mounting on DIN top hat rail EN 60715 IP20
Type of protection IP20
Permissible ambient temperature for operations -25 °C to 60 °C; -13 °F to 140 °F
Storage temperature -40°C to 70 °C; -40 °F to 158 °F
Mechanical device service life 6000 switching cycles
Icu with S450E 1000 A
Resistance to vibration IEC 60068-2-27;
IEC 60068-2;
EN 61373 Cat. 1/class B
—
Undervoltage release S800-UVR
—
Technical specifications
S800U
—
Combined auxiliary and bell alarm
—
Shunt operation release — S800-SOR
—
Approximate dimensions
S800U
106 106
106 66 6 82.5 82.5
26.5 66 82.5
82.5
79.5
79.5 79.5 76.5 76.5
76.5
76.5
76.5
53 53
53 46
46 46
46
46
26.5
26.5 26.5
45 95
45
95
45
95
35
35
35
35 45 95
45
95
35
2CCC413010Z0001
2CCC413010Z0001
1P 1P 2P
1P 2P
2P 3P 3P 4P
3P 4P
4P
S800-AUX S800-AUX/ALT
9 66 82.5 9 6
6 82.5
82.5
76.5
76.5 76.5
76.5
46
46 46
46
T T
45
95
35
35 45 95
45
95
35
35 45 95 2CCC413018Z0001
2CCC413017Z0001
RT
76
76
81
81 67
67
48
48
76
76
max.
max. 500 mm
500 mm
—
S804U-UCZ
—
Technical specifications
Standard UL 489
Characteristic Z
Rated current Ie 10–80 A
Rated voltage Ue 600 V DC
No. of poles 4
Short-circuit current rating acc. to UL 489 10 kA
Tightening torque 3.5 Nm (31 in.lb.)
Protection category IP40 (actuating end only)
Mounting position Any
Contacts Cadmium-free
Reference temperature for tripping characteristic 25 °C
Ambient temperature -25 °C to 60 °C
Storage temperature -40 °C to 70 °C
Approval cULus
File #E312425
40 S Y S T E M P R O M C O M PA C T ™ C I R C U I T P R OT E C T I O N D E V I C E S O N D I N R A I L
—
S804U-UCZ
+ + +
LOAD LOAD
-
- -
Tested and listed wirings
Conduc
Jumper
Jumper
+ + + LOAD + jumper jumper
LOAD LOAD jumper jumper jumper
- +
- - - -
Line and load might be reversed
LOAD LOAD
Ampere rating (A) 10–32 40–63 70–80
Ampere
jumper rating
jumper jumper jumper 10–32 A 40–63 A 70–80 A
Single conductor per terminal – Single conductor per terminal – Single conductor per terminal –
Conductor type Conductor
Single conductor type
per terminal – copper only, 60/75
Single conductor
º
copper
C wire per terminal – only, 60Single
º
conductorcopper
C wire only only, 60 º–
per terminal C wire only
copper only, 60/75 °C wire 14 AWG–2copper
AWG only, 60 °C wire1/0 only
AWG–8 AWG copper only, 601/0°C wire only
AWG–8 AWG
AWG, wire range Cu, solid or stranded 1/0 AWG–8 Cu, solid or stranded Cu, solid or stranded
AWG, wire range 14 AWG–2 AWG AWG 1/0 AWG–8 AWG
Cu,Jumper
solid or stranded
length (ft) 1 Cu, solid or stranded
1 Cu, solid
2 or stranded
Jumper length (cm) 30.5 30.5 61
Jumper length 1 ft. 1 ft. 2 ft.
+ jumper jumper jumper jumper 30.5 cm 30.5 cm 61 cm
+
- -
106
106 66 82.5
82.5
79.5
79.5 76.5
76.5
53
53 46
46
26.5
26.5
142
35 45 95 142
45
95
35
2CCC413012Z0001
1P
1P 2P 3P
3P 4P
4P
—
UL 1077 series
ST200M, S200MUC, S200MR, S800S,
S800C series
Description S800S and S800C series
The UL 1077 family of supplementary protectors The small pole width of only 27 mm allows a
offers a compact solution for protection space-saving installation. The current range
requirements. The devices are DIN rail mounted. covers nominal rated currents from 10 A up
to 100 A (S800C) and 6 A up to 63 A (S800S)
The UL 1077 MCBs are available with application- with a maximum rated short-circuit interrupt
specific trip characteristics to provide maximum rating of up to 20 kA (S800C) and 30 kA (S800S)
circuit protection. in UL applications.
The supplementary protectors offer thermal Due to the number of global standards met by the
magnetic trip protection according to B, C, D, S800C/S, the flexibility for worldwide installation
K and Z trip curves. is high. A single product can fulfill the needs of
both, IEC and UL applications.
For the worldwide market, the breakers carry UL,
CSA, IEC, CE and many other agency approvals
Features
and certifications.
• Rated operational voltage up to 480Y/277 V AC –
500 V DC (S800C) and 600Y/347 V AC (S800S),
Features
respectively (UL)
• Energy limiting
• Compression terminals can be easily converted
• Fast breaking time (2.3–2.5 ms)
to ring tongue terminals
• Bus connection system
• Compact
• Wide range of accessories
• Space saving
• Available with variable depth handle mechanism
• CE certified and marked
• DIN rail mounting
• Finger-safe terminals
• Multi-function terminals
• Suitable for reverse feed
• UL 1077 recognized supplemental protective
device, UL file #E76126 and E167556
—
ST200M-B
Supplemental protectors — UL 1077, CSA 22.2 No. 235
B 16 ST201M-B16NA 16 ST203M-B16
20 ST201M-B20NA 20 ST203M-B20
25 ST201M-B25NA 25 ST203M-B25
30 ST201M-B30NA 30 ST203M-B30
32 ST201M-B32NA 32 ST203M-B32
35 ST201M-B35NA 35 ST203M-B35
40 ST201M-B40NA 40 ST203M-B40
50 ST201M-B50NA 50 ST203M-B50
60 ST201M-B60NA 60 ST203M-B60
63 ST201M-B63NA 63 ST203M-B63
ST200M SERIES 43
—
ST200M-B (cont.)
Supplemental protectors — UL 1077, CSA 22.2 No. 235
—
ST200M-C
Supplemental protectors — UL 1077, CSA 22.2 No. 235
—
ST200M-C (cont.)
Supplemental protectors — UL 1077, CSA 22.2 No. 235
—
ST200M-D
Supplemental protectors — UL 1077, CSA 22.2 No. 235
D 16 ST201M-D16NA 16 ST203M-D16
20 ST201M-D20NA 20 ST203M-D20
25 ST201M-D25NA 25 ST203M-D25
30 ST201M-D30NA 30 ST203M-D30
32 ST201M-D32NA 32 ST203M-D32
35 ST201M-D35NA 35 ST203M-D35
40 ST201M-D40NA 40 ST203M-D40
50 ST201M-D50NA 50 ST203M-D50
60 ST201M-D60NA 60 ST203M-D60
63 ST201M-D63NA 63 ST203M-D63
ST200M SERIES 47
—
ST200M-D (cont.)
Supplemental protectors — UL 1077, CSA 22.2 No. 235
—
ST200M-K
Supplemental protectors — UL 1077, CSA 22.2 No. 235
—
ST200M-K (cont.)
Supplemental protectors — UL 1077, CSA 22.2 No. 235
—
ST200M-Z
Supplemental protectors — UL 1077, CSA 22.2 No. 235
—
ST200M-Z (cont.)
Supplemental protectors — UL 1077, CSA 22.2 No. 235
—
S200MR-K with ring tongue terminals
Supplemental protectors — UL 1077, CSA 22.2 No. 235
100
60
40
15 S202MR-K15 15 S204MR-K15
K
20 16 S202MR-K16 16 S204MR-K16
10
6 20 S202MR-K20 20 S204MR-K20
4
2 25 S202MR-K25 25 S204MR-K25
1
0.6 30 S202MR-K30 30 S204MR-K30
0.4
—
S200MUC-C
Supplemental protectors — UL 1077, CSA 22.2 No. 235
—
S200MUC-K
Supplemental protectors — UL 1077, CSA 22.2 No. 235
—
S200MUC-Z
Supplemental protectors — UL 1077, CSA 22.2 No. 235
—
S800C-B
With interchangeable cage terminal
—
S800C-C
With interchangeable cage terminal
—
S800C-D
With interchangeable cage terminal
—
S800C-K
With interchangeable cage terminal
—
S800S-B
With interchangeable cage terminal
—
S800S-C
With interchangeable cage terminal
6 S801S-C6 6 S803S-C6
8 S801S-C8 8 S803S-C8
10 S801S-C10 10 S803S-C10
13 S801S-C13 13 S803S-C13
16 S801S-C16 16 S803S-C16
20 S801S-C20 20 S803S-C20
25 S801S-C25 25 S803S-C25
32 S801S-C32 32 S803S-C32
40 S801S-C40 40 S803S-C40
50 S801S-C50 50 S803S-C50
63 S801S-C63 63 S803S-C63
2 0.5 S802S-C0.5 4 0.5 S804S-C0.5
1 S802S-C1 1 S804S-C1
1.6 S802S-C1.6 1.6 S804S-C1.6
2 S802S-C2 2 S804S-C2
2.5 S802S-C2.5 2.5 S804S-C2.5
3 S802S-C3 3 S804S-C3
4 S802S-C4 4 S804S-C4
5 S802S-C5 5 S804S-C5
6 S802S-C6 6 S804S-C6
8 S802S-C8 8 S804S-C8
10 S802S-C10 10 S804S-C10
13 S802S-C13 13 S804S-C13
16 S802S-C16 16 S804S-C16
20 S802S-C20 20 S804S-C20
25 S802S-C25 25 S804S-C25
32 S802S-C32 32 S804S-C32
40 S802S-C40 40 S804S-C40
50 S802S-C50 50 S804S-C50
63 S802S-C63 63 S804S-C63
62 S Y S T E M P R O M C O M PA C T ™ C I R C U I T P R OT E C T I O N D E V I C E S O N D I N R A I L
—
S800S-D
With interchangeable cage terminal
—
S800S-K
With interchangeable cage terminal
—
Accessories
ST200M, S200MR and S200MUC — UL 1077, CSA 22.2 No. 235
Shunt trip
For remote tripping of breaker, a shunt trip device can be —
Bottom-fitted auxiliary contact
added to the MCB. The solenoid device opens the breaker
after control voltage is applied. Description Cat. No.
Auxiliary contact 1 NC S2C-H01
—
Accessories
ST200M, S200MUC and S200MR — UL 1077, CSA 22.2 No. 235
Accessory overview
—
Busbars PS…CB and accessories according to UL 508
For MCBs ST200M and S200MUC
Busbars type PS…CB are used for quick and easy line side
wiring of miniature circuit breakers according to UL 1077 as
well as fuse disconnectors E90. The entire product line,
including the accessories, is approved according to UL 508
(cULus) and can be used for applications in supplementary
protection circuits in UL and CSA markets
—
Busbars PS…CB and accessories according to UL 508
Technical data
—
Technical data
Busbars PS…CB
Standards UL 508
IEC EN 60947-1
Electrical data Rated voltage Ue V 1-phase 2- / 3-phase
1,000 V AC/DC UL: 600 V AC/DC
IEC: 690 V AC/DC
Current carrying capacity / phase A 18 mm² 25 mm²
(35 °C ambient temperature) End feeding 1) 80 A 100 A
Non-end feeding 1) 160 A 200 A
Short-circuit rating kA 10 kA 3 cycles @ 480 V / 100 kA fuse class J
175 A / 18 mm² - 200 A / 25 mm²
Mechanical Data Housing Light gray, RAL 7035
Overvoltage category III
Pollution degree 2
Installation Busbar cross section mm² 18 mm² / 25 mm²
Mounting position Optional
Supply Feed to the device’s terminal (supply side optional)
or use feeder terminal AST 35/15-1 CB; AST 35/15-2 CB;
AST 35/38-1 CB; AST 35/38-2 CB; SZ-ESK SP
Accessories Electric shock-protection caps BSK CB
Feeder terminals AST 35/15-1 CB; AST 35/15-2 CB
AST 35/38-1 CB; AST 35/38-2 CB
SZ-ESK SP
End caps PS-END 1 CB
PS-END 3 CB
Approvals UL 508: cULus listed
CE and RoHS compliant
In addition to the approval of the busbar, the approval of the switching
device used must also be considered.
Installation When cutting the busbar, ensure that the insulation profile protrudes
instructions beyond the end of the copper bar by approx. 10 mm at each end. Electric
shock-protection only ensured with end caps mounted.
1)
Irrespective of the current carrying capacity of the busbar, the max. rated current of the devices terminal must not be exceeded.
68 S Y S T E M P R O M C O M PA C T ™ C I R C U I T P R OT E C T I O N D E V I C E S O N D I N R A I L
—
Busbars PS…CB and accessories according to UL 508
Ordering data
—
Busbars suitable for cutting
Weight Pack
1 piece unit
Phases mm² No. of pins kg pc. Cat. No.
1-phase busbars, pin distance 17.6 mm, end caps PS-END 1 CB
1 18 57 0.289 10 PS 1/57/18 CB
1 25 57 0.360 10 PS 1/57/25 CB
1-phase busbars, connection of 1-pole devices with auxiliary, end caps PS-END 1 CB
1 18 37 0.254 10 2CDL210508R3718
1 25 37 0.310 10 2CDL210508R3725
2-phase busbars, pin distance 17.6 mm, end caps PS-END 3 CB
2 18 56 0.639 10 PS 2/56/18 CB
2 25 56 0.795 10 PS 2/56/25 CB
2-phase busbars, connection of 2-pole devices with auxiliary, end caps PS-END 3 CB
2 18 46 0.672 10 PS 2/46/18 H CB
2 25 46 0.782 10 PS 2/46/25 H CB
3-phase busbars, pin distance 17.6 mm, end caps PS-END 3
3 18 57 0.929 10 PS 3/57/18 CB
3 25 57 1.026 10 PS 3/57/25 CB
3-phase busbars, connection of 3-pole devices with auxiliary, end caps PS-END 3 CB
3 18 48 0.788 10 PS 3/48/18 H CB
3 25 48 0.974 10 PS 3/48/25 H CB
3-phase busbars, connection of 1-pole devices with auxiliary, end caps PS-END 3 CB
3 18 39 0.794 10 PS 3/39/18 H CB
3 25 39 0.974 10 PS 3/39/25 H CB
—
Accessories
Weight Pack
1 piece unit
kg pc. Cat. No.
Electric shock-protection cap
0.008 10 BSK CB
Feeder terminals with pin contact
for use with MCB and 1-phase busbar 0.025 25 AST 35/15-2 CB
for use with MCB and 2-/3-phase busbar 0.032 10 AST 35/38-2 CB
for use with E90 and 2-/3-phase busbar 0.032 10 AST 35/38-1 CB
for use with E90 and 1-phase busbar 0.025 25 AST 35/15-1 CB
Single-pole terminal, can be mounted side by side, feed to the busbar pin
0.032 50 SZ ESK SP
End caps
for use with PS 1…CB 0.001 50 PS-END 1 CB
for use with PS 2…CB and PS3…CB 0.002 50 PS-END 3 CB
ACCESSORIES AND BUSB ARS 69
—
Busbars PS…CB and accessories according to UL 508
Technical data feeder terminals
—
Technical data
* Tightening torque according to UL486A, Table 21, Clauses 9.1.9.4 and 9.1.9.6
Stripping length ~ 14 mm; 9/16''
Conductor material Copper
Approvals UL 508
CE, RoHS and REACH compliant
In addition to the approval of the feeder terminal, the approval of the switching
device used must also be considered.
Instruction of The feeder terminals are single-phase. In case of a combination of multiple
installation terminals with installation side by side, e.g. for multipole or DC applications, the
required creepage and air leakage distances must be considered and observed.
To ensure protection against electrical electric shock, the pin length of the feeder
terminal must not exceed the depth of the contact area of the connected device.
Irrespective of the current carrying capacity of the feeder terminal, the max.
rated current of the devices terminal must not be exceeded.
70 S Y S T E M P R O M C O M PA C T ™ C I R C U I T P R OT E C T I O N D E V I C E S O N D I N R A I L
—
Busbars PS…CB and accessories according to UL 508
Technical data feeder terminals
—
Order codes
Weight Pack
1 piece unit
Feeder terminals with pin contact kg pc. Cat. No.
for use with MCB and 1-phase busbar 0.025 25 AST 35/15-2 CB
for use with MCB and 2-/3-phase busbar 0.032 10 AST 35/38-2 CB
for use with E90 and 2-/3-phase busbar 0.032 10 AST 35/38-1 CB
for use with E90 and 1-phase busbar 0.025 25 AST 35/15-1 CB
ACCESSORIES AND BUSB ARS 71
—
Busbars PS…CB and accessories according to UL 508
Installation of busbars and use of feeder terminals/cables for feed
—
Installation of busbars and use of feeder terminals/cables for feed
—
Busbars PS…CB and accessories according to UL 508
Overall dimensions
—
1-phase busbars
15
B
5
15
5,5
—
2-/3-phase busbars
C
21
25
39
13,5
—
Overall dimensions
A B C
Busbar mm mm mm
1-phase busbars
PS 1/57/18 CB 17.6 986 1010
PS 1/57/25 CB 17.6 986 1010
PS 1/37/18 H CB 26.4 950 985
PS 1/37/25 H CB 26.4 950 985
2-phase busbars
PS 2/56/18 CB 17.6 968 990
PS 2/56/25 CB 17.6 968 990
PS 2/46/18 H CB 17.6 / 26.4 * 968 1010
PS 2/46/25 H CB 17.6 / 26.4 * 968 990
3-phase busbars
PS 3/57/18 CB 17.6 986 1010
PS 3/57/25 CB 17.6 986 1010
PS 3/48/18 H CB 17.6 / 26.4 * 924 982
PS 3/48/25 H CB 17.6 / 26.4 * 924 982
PS 3/39/18 H CB 26.4 1003 1040
PS 3/39/25 H CB 26.4 1003 1040
—
Accessories
S800S, S800C
—
Technical specifications
ST200M, S200MR, S200MUC — UL 1077, CSA 22.2 No. 235
—
Technical specifications
—
Auxiliary contact S2C-H6R and signal contact S2C-S6R
—
Technical specifications
ST200M, S200MR, S200MUC — UL 1077, CSA 22.2 No. 235
—
Shunt trip
S2C-A1 S2C-A2
Rated voltage 12–60 V AC 110–415 V
12–60 V DC 110–250 V
Maximum release duration <10 ms <10 ms
Minimum release voltage 7 V AC 55 V AC
10 V DC 80 V DC
Consumption on release 40–200 VA AC 55–210 VA AC
40–200 VA DC 55–110 VA DC
Coil resistance 3.7 V 225 V
Terminals 18–6 AWG/0.75–16 mm2 18–6 AWG/0.75–16 mm2
Tightening torque 18/2 in. lbs/Nm 18/2 in. lbs/Nm
—
Under-voltage release
S2C-UA S2C-UA S2C-UA S2C-UA S2C-UA S2C-UA S2C-UA S2C-UA S2C-UA S2C-UA
12 DC 24 AC 24 DC 48 AC 48 DC 110 AC 110 DC 230 AC 230 DC 400 AC
Standards IEC/EN 60947-1110...415 V
Rated voltage AC 24 V 48 V 110 V 230 AC 400 V
DC 12 V 24 V 48 V 110 V 230 V
Frequency 50 ... 60 HZ
Release trip 0.35 UnOVO 0.7 Un V
Terminals 2 x 16 AWG/2 x 1.5 mm2
Consumption 0.2 VA 3.6 VA 2 VA 3.6 VA 2.1 VA 3.5 VA 2.2 VA 3.7 VA 2.3 VA 2.4 VA
Resistance to corrosion Constant atmosphere: 23/83 – 40/93 – 55/20; variable atmosphere: 25/95 – 40/93 °C/RH
Protection degree IPXXB / IP2X
Tightening torque 3.5 Ibs./0.4 in. Nm
76 S Y S T E M P R O M C O M PA C T ™ C I R C U I T P R OT E C T I O N D E V I C E S O N D I N R A I L
—
Technical specifications
ST200M and S200MR — UL 1077, CSA 22.2 No. 235
B. C. K D Z
Internal Internal Internal
Rated current resistance per pole Power loss resistance per pole Power loss resistance per pole Power loss
In [A] Ri [mOhm] P v [W] Ri Pv Ri Pv
0.5 5500 1.4 4300 1.1 8100 2.4
1 1440 1.4 1250 1.25 2100 2.3
1.6 645 1.8 600 1.5 1000 2.8
2 460 1.8 410 1.7 620 2.5
3 150 1.6 130 1.2 235 2.4
4 110 1.8 105 1.7 150 2.4
5 55 1.4 52 1.3 75 1.9
6 55 2.0 52 1.9 75 3.2
7 24 1.2 26 1.3 28 1.4
8 23 1.5 24 1.5 27 2.0
10 21 2.2 16 1.6 24 2.7
13 14 2.3 14 2.2 15 2.6
15 8.5 2 8.5 2 11 2.5
16 8.5 2.5 8.5 2.5 10.9 2.8
20 6.25 2.5 6.1 2.3 6.0 2.4
25 5.0 3.2 4.3 3.1 4.5 3.3
30 3.5 3.1 3.5 3.2 3.5 3.2
32 3.5 3.7 3.5 3.6 3.5 3.6
35 3.4 4.2 3.4 4.2 3.5 4.3
40 3.0 4.8 2.2 4.2 2.5 4.1
50 1.8 4.3 1.3 2.9 1.5 4.1
60 1.2 4.4 1.2 4.4 1.3 4.7
63 1.2 5.5 1.2 4.8 1.3 5.2
—
S200MR internal resistance and power loss per pole
Rated current Internal resistance per pole Power loss per pole Rated current Internal resistance per pole Power loss per pole
A mΩ W A mΩ W
0.2 25300 1.01 13 14.8 2.50
0.3 13700 1.23 15 8.1 1.83
0.5 4740 1.19 16 11.1 2.83
0.75 2067 1.16 20 8.5 3.40
1 1270 1.27 25 5.5 3.43
1.5 610 1.56 30 3.8 3.39
2 442 1.77 32 4.6 4.70
3 140 1.26 35 3.9 4.76
4 109 1.75 40 2.8 4.40
5 50 1.26 50 1.7 4.25
6 54 1.94 60 1.7 6.18
8 22 1.41 63 1.9 7.56
10 18.2 1.82
T E C H N I C A L D ATA A N D D R A W I N G S 77
—
Technical specifications
ST200M and S200MR — UL 1077, CSA 22.2 No. 235
Temperature derating
Max. operating current depending on the ambient
—
ST200M temperature rating temperature.
—
S200MR temperature rating
—
Miniature circuit breaker S200MUC
Use of MCBs in direct current circuits
S200MUC miniature circuit breakers can be used in the 1-pole For DC incoming supply from above
version at 250 V DC, and in the 2-pole or 4-pole version with S200MUC MCBs have permanent magnets in the area of arc
series connection of two poles up to 500 V DC. chutes. Therefore, it is necessary to take into account the
polarity during the installation process. In the case of a short
S200MUC differs from the standard S200 type. It is equipped circuit, the magnetic field of the permanent magnets
with permanent magnets that assist in the forced corresponds with the electromagnetic field of the short-
extinguishing of the arc. circuit current, therefore, safely leading the short circuit into
the arc chute. Incorrect polarities may cause damage to the
If voltages to ground exceeding 250 V DC occur, 2-pole MCB. As a result, for top-fed devices, terminal 1 must be
S200MUC should be used for 1-pole disconnection connected to (-) and terminal 3 to (+).
and 4-pole S200MUC for all-pole disconnection.
—
Examples of permissible voltages between the conductors depending on the number of poles and circuit layout:
SK 0115 Z 94
Supply from above
SK 0114 Z 94
1 In the circuit diagram, the negative pole is earthed. 2 In the circuit diagram, the positive pole is earthed.
—
Examples of permissible voltages between the conductors depending on the number of poles and circuit layout:
SK 0196 Z 98
1 In the circuit diagram, the negative pole is earthed. 2 In the circuit diagram, the positive pole is earthed.
T E C H N I C A L D ATA A N D D R A W I N G S 79
—
Approximate dimensions
ST200M, S200MR and S200MUC — UL 1077, CSA 22.2 No. 235
ST200M, S200MUC
69
44 17.5 35 52.5 70
45 85 88
6.8
17.5
22
S200MR
69
44.7
45 85 100
2.5 25 6.8
80 S Y S T E M P R O M C O M PA C T ™ C I R C U I T P R OT E C T I O N D E V I C E S O N D I N R A I L
—
Technical data
S800C
General data
Tripping characteristic B, C, D, K
Standard IEC 60947-2, EN 60898-1, UL 1077
Poles 1–4
Rated frequency 50/60 Hz
Data acc. to UL1077
Rated voltage U 240 V AC (1p, 3p)
277/480Y V AC (1p, 3p)
125 V DC (1p)
250 V DC (2p)
375 V DC (3p)
500 V DC (4p)
Rated current I 10–100 A
Short-circuit breaking capacity ICC 20 kA (240 V AC)
10 kA (277/480Y V AC)
10 kA (500 V DC)
Rated insulation voltage UI 500 V AC
Reference temperature for tripping characteristic B, C, D: 30 °C, K: 40 °C
General data
Electrical and mechanical endurance Up to 100 A: 6000 electrical/4000 mechanical
Installation
Terminal Failsafe cage terminal
Connection (top/bottom) – Cu only 14–2 AWG (10–30 A, solid or stranded)
1–8 AWG (40–100 A, stranded)
Single conductor per terminal,
60/75 °C wire (10–30 A), 60 °C wire (40–100 A)
Tightening torque 3.5 Nm/31 in. lb.
Mounting position Any
Supply side Any
T E C H N I C A L D ATA A N D D R A W I N G S 81
—
Technical data
S800S
General data
Tripping characteristic B, C, D, K
Standard IEC 60947-2, EN 60898-1, UL 1077
Poles 1–4
Rated frequency 50/60 Hz
Data acc. to UL1077
Rated voltage U 600Y/347 V AC
Rated current I 6–63 A
Short-circuit breaking capacity ICC 30 (240 V up to 63 A)
14 (277/480Y V up to 63 A)
6 (346/600Y V up to 40 A, 63 A)
Rated insulation voltage UI 600 V AC
Reference temperature for tripping characteristic B, C, D: 30 °C, K: 40 °C
General data
Electrical and mechanical endurance 6000 electrical/4000 mechanical
Installation
Terminal Failsafe cage terminal
Connection (top/bottom) – Cu only 14–2 AWG (10–30 A, solid or stranded)
1–8 AWG (40–100 A, stranded)
Single conductor per terminal,
60/75 °C wire (10–30 A), 60 °C wire (40–100 A)
Tightening torque 3.5 Nm/31 in. lb.
Mounting position Any
Supply side Any
82 S Y S T E M P R O M C O M PA C T ™ C I R C U I T P R OT E C T I O N D E V I C E S O N D I N R A I L
—
Approximate dimensions
S800C, S800S
106
106 6 26.5 66 82.5
82.5
106 66 82.5 82.5
82.5
79.5 76.5
76.5
79.5 76.5 76.5
79.5 76.5
53 46 46
46
53 46
46
26.5
26.5
26.5
45
95
45 95
35
35 45
95
35
35 45 95
45
95
35
2CCC413010Z0001
2CCC413010Z0001
1P 2P 3P 4P
1P
1P 2P
2P 3P
3P 4P
—
S804U-PVS5
—
Technical specifications
Standard UL 489B
Characteristic PV-S
Rated current Ie 5A
Rated voltage Ue 1000 V DC
No. of poles 4
Short-circuit current rating acc. to UL 489B 3 kA
Connections 5 A
Single conductor per terminal—copper only, 75C wire 14 – 2 AWG Cu,
solid or stranded
Tightening torque 3.5 Nm (31 in.lb.)
Protection category IP40
(actuating end only)
Mounting position Any
Contacts Cadmium-free
Reference temperature for tripping characteristic 50 °C
Ambient temperature -25 °C to 60 °C
Storage temperature -40 °C to 70 °C
Approval cULus
File #E351317
—
Ordering information
—
S804U-PVS5
+ + + +
LOAD LOAD LOAD
- -
- -
142
35 45 95 142
45
95
35
2CCC413012Z0001
1P
1P 2P 3P 4P
4P
—
S803W-SCL-SR UL Short circuit current limiter, self-resetting
—
UL version short circuit current limiter, self-resetting, 3 pole
—
Technical specifications
—
Approved combinations with motor starter
—
Rated ultimate short-circuit breaking capacity
—
S803W-SCL-SR UL 508 Short circuit current limiter, self-resetting
Approximate dimensions
—
Minimum cable length between S803W-SCL-SR and downstream devices
(Connection has to be short-circuit proofed acc. to IEC 61439-1)
MS/M0325
MS/M0132
S800
S800-SCL-SR Min. length X (mm) Min. cross section (mm2)
32 A 80 6
63 A 80 16
100/125 A 250 35
Diagrams
79.50 76.50
53 46
x 26.50 6
142
45
95
35
—
Electronic protection device EPD24-TB-101
For use on the load side of 24 V DC switch mode
power supplies
Description Features
The protection devices EPD24 extend the ABB • Selective load protection, one electronic
product range of modular DIN rail components tripping characteristic
by electronic over-current protection modules • Active current limitation for safe connection of
for selective protection of 24 V DC load circuits. capacitive loads up to 20,000 μF and on overload/
This protection is achieved by a combination of short circuit
active electronic current limitation in the case of • Current ratings 0.5 A to 12 A
a short circuit and an overload deactivation from • Reliable overload disconnection with 1.1 x IN plus
1.1 x IN upwards. • Manual ON/OFF button
• Clear status and failure indication through LED
If a fault occurs in a load circuit, the protection and integrated auxiliary contact
device EPD24 will detect this rapidly and reliably, • Integral fail-safe element adjusted to current
disable the power output transistor and hence rating
interrupt the current flow in the defective circuit. • Width per unit only 12.5 mm
The maximum possible over-current is always • Rail mounting
limited to 1.3 to 1.8 times the selected rated • Easy wiring through busbar LINE+ and 0 V as well
current. An activation of capacitive loads up to as signal bars
20,000 μF is possible, deactivation only occurring • UL and CSA approvals allow international use
in the case of overloads or short circuits. Selective of the devices
deactivation of the defective current circuit
means undefined error states and a complete
system stop are prevented.
—
Approvals
—
EPD24
Ordering information
—
Electronic protection devices
—
Accessories
Weight
Cat. No. 1 piece in kg Packing unit
Busbars for LINE+ and 0 V, grey insulation, length 500 mm1) EPD-BB500 0.20 10
Signal bars for auxiliary contacts, grey insulation, length 21 mm EPD-SB21 0.04 10
1) Ampacity at one line entry Imax = 50 A (Recommendation: mid line entry)
Ampacity at two line entries Imax = 63 A
Diagram
12.5
83
80
80
—
Application guide
Miniature circuit breaker
Thermal Example
—
01 Thermal example: Introduction
The light draws more 15 A
10 A The circuit breaker plays an important role in
than 10 amps for
an extended period providing over-current protection and a
of time, creating a
Breaker disconnect means in electrical networks. Recent
thermal overload. Magnetic Example
— Light advancements in circuit breaker technology have
—
02 Magnetic example:
01 increased breaker performance and protection.
The wire connected
between the light and
breaker is cut and The light draws more than 10 amps for Overload
shorted to ground, an extended period of time creating a
creating a short circuit. thermal overload.
10 A
An overload is a slow and small over-current
10 A
—
situation that causes the ampacity and
03 ABB current-
limiting breaker temperature of the circuit to gradually increase
over time. This type of event is characterized by
Breaker
Light a slight increase in the load (ampacity) on the
— circuit and is interrupted by the thermal trip unit
02
of the breaker.
The wire connected between the light and breaker is cut and
shorted to ground creating a short circuit.
Short circuit
A short circuit is a rapid and intense overcurrent
situation that causes the ampacity of the circuit
Electromagnetic protection Upper terminal
to increase. This type of event is characterized by
a dramatic increase in the load (ampacity) on the
Tripping lever circuit and is interrupted by the magnetic trip unit
of the breaker.
Breaker definition
A breaker is a device designed to isolate a circuit
during an over-current event without the use of a
Thermal fusible element. A breaker is a resettable protective
protection
(bimetal) device that protects against two types of over-
current situations: overload and short circuit.
Arc chamber
Fixed
Operator contact
Space for
identification Moving
marker contact
Operating
DIN rail holder
mechanism
Lower terminal
—
03
90 S Y S T E M P R O M C O M PA C T ™ C I R C U I T P R OT E C T I O N D E V I C E S O N D I N R A I L
—
Circuit breaker construction
The time required for the bimetal to bend and trip the breaker
varies inversely with the current. Because of this, the tripping
time becomes quicker as current increases in magnitude.
Moving contact
Movable armature
Fixed armature
"Hammer trip"
Fixed contact
M C B T E C H N O LO G Y A P P L I C AT I O N G U I D E 91
—
Circuit breaker construction
Arc runners/arc chutes example, you would find the circuit current on the bottom of
The arc runner guides the electric arc away from the open the graph (multiples of rated current). The first line is 10 amps
contacts into the arc chute, where it is extinguished. (10 amp breaker x a multiple of one), the second line is 20
amps (10 amp breaker x multiple of two), and the third line
During an overload or short circuit event, the contacts of the is 30 amps (10 amp breaker x multiple of three). Next, you
breaker separate, and an electrical arc is formed between the would trace the vertical 30 A line up until it intersects the
contacts through air. The arc is moved into the arc chute by red portion of the breaker thermal curve. If you follow the
“running” the arc down the interior of the breaker along the horizontal lines on both sides of the red curve to the left, you
arc runner. When the arc reaches the arc chute, it is broken into will see that the breaker can trip as fast as two seconds and
small segmented arcs. The segmented arcs split the overall no slower than one minute.
energy level into segments less than 25 V. Each 25 V segment
does not have a high enough energy level to maintain an arc Magnetic trip unit (region two)
and all energy is naturally dissipated. This region of the breaker curve is the instantaneous trip
unit. ABB’s miniature circuit breaker’s instantaneous trip
Breaker curves unit interrupts a short circuit in 2.3 to 2.5 milliseconds.
Thermal trip unit (region one) Because of this, the curve has no slope and is graphically
The first sloping region of the breaker curve is a graphical represented as a vertical straight line.
representation of the tripping characteristics of the thermal
trip unit. This portion of the curve is sloped due to the nature See curve example. If you had a 10 amp breaker, the magnetic
of the thermal trip unit. The trip unit bends to trip the trip element would interrupt a short circuit between 10 and 30
breaker’s trip bar in conjunction with a rise in amperage amps (10 amp breaker x multiple of two and three) in 2.3 to 2.5
(temperature) over time. As the current on the circuit milliseconds.
increases, the temperature rises, and the faster the thermal
element will trip. Breaker contacts (region three)
This region of the curve is the time required for the contacts
Example using the curve below: If you had a 10 amp breaker of the breaker to begin to separate. The contacts will open in
and the circuit was producing 30 amps of current, the breaker less than 0.5 milliseconds and is graphically represented by
would trip between two seconds and one minute. In this the bottom vertical portion of the curve.
—
Circuit breaker current limitation
—
01 Current limiting Current-limiting definitions Current-limiting breakers and electrical networks
—
All ABB miniature circuit breakers are UL tested Current limitation
02 Zero point
extinguishing and certified as current-limiting protective When a short-circuit condition occurs, the “ideal”
devices. Current-limiting circuit breakers provide current-limiting circuit breaker opens before the
a higher level of circuit protection than typical current waveform can reach its full potential
zero point external breakers. magnitude, which occurs at ¼ cycle (4.17 ms). ABB’s
current-limiting breakers can interrupt a fault in
UL AC 60 Hz cycle about ½ cycle or 2.3 ms to 2.5 ms. ABB’s current-
UL defines an AC cycle as the potential energy limiting breakers interrupt a short circuit in less
of the wave form traveling from zero-to-positive than 1⁄8 cycle and limit the amount of current that
amplitude, positive-to-zero amplitude, zero-to- can reach a circuit. Limiting the available current
negative amplitude, negative-to-zero amplitude 60 on the circuit provides additional protection
times in one second. One cycle is completed every against network, breaker or bus damage and
16.6 milliseconds. prevents the tripping of upstream breakers
(selective coordination).
UL breaker current limiting
UL defines breaker current limitation as a breaker I 2t
that interrupts and isolates a fault in less than 1/2 The true destructive nature of a short circuit is
—
of an AC cycle. 1/2 a cycle is completed in 8.3 measured by the time it is available combined with
01
milliseconds. the peak value of the short circuit. The IsqT (amps
squared over time) value represents the amount
NEC 240.2 current-limiting of energy available on a network during a short
A device that, when interrupting current in its circuit and is represented by the shaded area on
current-limiting range, reduces the current flowing the graphs at left.
in the faulted circuit to a magnitude substantially
less than that obtainable in the same circuit if the During a short circuit, both magnetic forces and
device were replaced with a solid conductor having thermal energy combine to damage devices on the
comparable impedance. electrical network. The level of thermal energy and
magnetic forces are directly proportional to the
IEC 60947-2 current-limiting circuit breaker square of the current. The magnetic forces vary
A circuit breaker with sufficiently short trip time to as a square of the peak current available and the
prevent the short-circuit current from reaching the thermal energy varies as a square of the RMS (root
peak value which would otherwise be reached. mean square) current available.
—
02
ABB current-limiting breakers ABB’s current-limiting breakers will limit the let-
ABB current-limiting breakers can interrupt and through energy to a fraction (1⁄100) of the value that
isolate a fault in 1⁄8 of an AC cycle. The breaker fault is available from the network. By comparison,
interruption is completed in 2.3 to 2.5 milliseconds. a zero crossing breaker would let through
approximately 100 times as much destructive
Zero point extinguishing breakers energy as the current-limiting circuit breaker
A typical zero point extinguishing breaker [(100,000 A / 10,000 A) squared – 100X]. ABB’s
interrupts a fault and does not isolate the energy. current-limiting breakers limit the short circuit
The breaker allows an arc to be present between current to a relatively small magnitude in an
the open contacts until the AC wave form crosses extremely short time, which dramatically limits
zero. When the wave form crosses zero, the a short circuit’s destructive energy.
potential energy is zero and the arc (fault) naturally
extinguishes. The arc could be present for up to
8.3 milliseconds.
M C B T E C H N O LO G Y A P P L I C AT I O N G U I D E 93
—
Circuit breaker current limitation
Current-limiting and zero crossing breakers ABB’s current-limiting breakers interrupt the arc energy in 2.3
During the initial stages of a short circuit, a breaker’s ms to 2.5 ms (1⁄8 cycle), and a zero crossing breaker allows the
contacts open to interrupt the circuit. After the contacts arc to be present for up to 8.3 ms (1⁄2 cycle). A zero crossing
open, an arc forms in the air between the contacts on both breaker will let through 100 times as much energy as an ABB
the current-limiting and zero crossing breaker contacts. current-limiting breaker.
What distinguishes a current-limiting breaker from a zero
crossing breaker is what each breaker does after an arc is Current limiting example
formed between the open contacts. The lab test report below details a 20 A S200 series current-
limiting breaker interrupting a 28 kA fault in 1.7 milliseconds.
A current-limiting breaker “runs” the arc down the breaker The total “I Square T” value is 32.0 kA.
arc runner into an arc chute that extinguishes the arc.
Zero crossing example
A zero crossing breaker does not attempt to extinguish the The test report below details a 20 A zero point extinguishing
arc. The breaker is designed to withstand the energy of the breaker interrupting a 9 kA fault in 9 milliseconds. The total
arc long enough for the waveform to cross zero. When the “I Square T” value is 104.0 kA.
wave form crosses zero, the potential energy is zero and the
arc naturally extinguishes itself.
500 10 500 10
V kA V kA
400 8 400 8
300 6 300 6
200 4 200 4
100 2 100 2
-100 -2
-100 -2
-200 -4
-200 -4
Legend
-300 -6
-300 -6 Legend
Voltage
Amps Voltage
-400 -8
-400 -8 Amps
—
Selective coordination and series ratings
Coordination
Main
breaker
Short circuit
No coordination
M C B T E C H N O LO G Y A P P L I C AT I O N G U I D E 95
—
Selective coordination and series ratings
Selective coordination
Main
Selective coordination is achieved when there is a short circuit
breaker
65 kA on a branch circuit breaker, the branch breaker opens and
isolates the fault, and the main breaker remains closed. The
rating is usually a value above the “stand alone” interrupting
CB1 CB2 CB3 CB4 rating of the branch breaker and the “stand alone” rating of
10 kA 10 kA 10 kA 10 kA the main breaker.
Example:
35 kA or 65 kA short circuit 65 kA rated main breaker
10 kA rated branch breaker
Coordination between the two breakers up to 35 kA
Series ratings
Series ratings are different from coordination ratings. Unlike
coordination ratings where the branch opens and the main
remains closed, a series-rated combination is one where
both the branch and main breakers open and work together
to isolate the fault.
Example:
65 kA rated main breaker
10 kA rated branch breaker
Series-combination rating between the two breakers
up to 65 kA
—
Miniature circuit breaker cutaway
Operating mechanism
Arc chamber
Operator
Fixed contact
Moving contact
—
Ground-fault protective devices (GFEP)
F200 series
F200 series GFEPs (ground-fault equipment F200 GFEPs are also available in short-term delayed
protectors) are approved according to UL 1053 and versions (AP-R types) as well as selective versions
IEC 61008. (S types).
F200 series GFEPs can be used in branch circuits, F200 GFEPs are A-type GFEPs and can detect AC as
together with a corresponding UL 489 circuit well as pulsed DC fault currents.
breaker, like our SU200M, or in connection with UL
1077 supplementary protectors, like our ST200M AC-type devices detect AC fault currents only and
wherever branch circuit protection is already are available upon request.
provided or not required.
—
RCCBs
F200 technical features
Standards
UL/CSA V
Rated frequency Hz
Rated conditional short-circuit current SCPD - fuse gG 100 A kA
Inc=I∆c
Rated residual breaking capacity I∆m=Im kA
Rated impulse withstand voltage (1.2/50) Uimp kV
Dielectric test voltage at ind. freq. for 1 min. kV
Overvoltage category
Surge current resistance (wave 8/20) A
Mechanical Toggle
features Contact position indicator (CPI)
Electrical life
Mechanical life
Protection degree housing
terminals
Environmental conditions (damp heat) acc. to IEC/EN 60068-2-30 °C/RH
Ambient temperature (with daily average ≤ IEC °C
+35 °C)
Storage temperature °C
Installation Terminal type
Terminal size top/bottom for cable IEC mm2
UL/CSA AWG
Terminal size top/bottom for busbar IEC mm2
UL/CSA AWG
Tightening torque IEC Nm
UL/CSA in-lbs.
Tool
Mounting
Mounting position
Connection
Withdrawal from busbar
Dimensions Dimensions (H x D x W) 2P mm
and weight 4P mm
Weight 2P g
4P g
Combination Combinable with: auxiliary contact
with signal contact/auxiliary switch
auxiliary shunt trip
elements
undervoltage release
—
RCCBs
F200 technical features
-40…+70
failsafe bi-directional cylinder-lift terminal at top and bottom (shock protected) (cage for In > 63 A) b
25/25 (35/35 single slot terminal for In > 63 A)
18-4 (up to 63 A) -
10/10 (not for In = 80-100 A)
18-8 (up to 63 A) -
2.8 (3 for In = 125 A) 2.8
25 (up to 63 A) -
Nr. 2 Pozidriv
on DIN rail EN 60715 (35 mm) by means of fast clip device
Any
from top and bottom
it is possible without using any tools only from the bottom (not for 125 A)
85 x 69 x 35
85 x 69 x 70 (85 x 69.5 x 72 for 125 A)
200
350 (380 for In = 80 and 100 A and 460 for In = 125A)
yes (no for 125 A)
yes
yes (no for 125 A)
yes (no for 125 A)
100 S Y S T E M P R O M C O M PA C T ™ C I R C U I T P R OT E C T I O N D E V I C E S O N D I N R A I L
—
RCCBs
F 200 series A y type, 30 mA sensitivity
—
RCCBs
F 200 series A y type
F 200 A type
—
RCCBs
F 200 series A y type
F204 125 A
G R O U N D - FA U LT P R OT E C T I V E D E V I C E S 103
—
RCCBs
F 200 series A y type, AP-R
—
RCCBs
F 200 series A y type, selective
—
E 90. Uncompromising performance
A safe and smart range designed for quick,
flexible and error-proof installation
Compactness
Reliability
The compact dimensions enable to
Venting grooves and cooling
close the switchboard door even when
chambers improve heat dissipation
the fuse holder is open, thus ensuring
even in multiple-pole configurations.
total safety during maintenance.
Completeness
The fuse tripping can be easily
displayed, thanks to the special
blown fuse indicator light.
Universal use
Screw holes have increased diameter
to accomodate insulated screwdrivers
and electric screwdrivers.
106 S Y S T E M P R O M C O M PA C T ™ C I R C U I T P R OT E C T I O N D E V I C E S O N D I N R A I L
E 90 FUSE HOLDERS 107
—
E 90. Uncompromising performance
A safe and smart range designed for quick, flexible and error-proof installation
Fuseholder profile has been designed for maximum ease of The compact dimensions enable to close the switchboard
use: the 90° flip hinge with ergonomic knob, makes the door even when the fuseholder is open, thus ensuring total
replacement of fuses easier even in small spaces or when safety during maintenance.
wearing protective gloves.
With the Prozidriv PZ2 screws tightening can be performed Venting grooves and cooling chambers improve heat
by exerting less torque than conventional screws, and the dissipation even in multiple-pole configurations.
same electric screwdriver can be used for all terminals. The reduced operating temperature inside fuseholders
Moreover, the PS connection busbars facilitate the ensures durability and reliability of the devices over time.
connecting operations, making the wiring both simple and
safe and providing complete integration with S 200 and SN
201 System pro M compact® circuit-breakers.
108 S Y S T E M P R O M C O M PA C T ™ C I R C U I T P R OT E C T I O N D E V I C E S O N D I N R A I L
—
Technical data
E 90 series – data according to UL
**** IP20 also as standalone device installed on DIN rail, with respect to cables with a cross-section area ≥ 10 mm 2
E 90 FUSE HOLDERS 109
• • • • •
• • • • •
• •
• • •
110 S Y S T E M P R O M C O M PA C T ™ C I R C U I T P R OT E C T I O N D E V I C E S O N D I N R A I L
—
Protection and safety
E 90 fuse holders
E 90 fuse holders
E 90 series fuse holders are designed for providing protection against short circuits and
overloads. The housing is made of self-extinguishing thermoplastic material resistant to
high temperatures (all materials are UL listed) while the contact clips are in silver plated
copper.
E 92
E 90 fuse holders can be sealed or padlocked to ensure operator safety during maintenance.
Versions with blown fuse indicator allow to check whether the fuse is still working correctly
or not. For easy and quick installation E 90 range is totally compatible with our UL 508
busbars.
—
Protection and safety
E 90 PV 1000 V fuse holders
E 90 PV fuse holders
E 90 PV series fuse holders, designed for operating voltages of 1000 V DC with utilization
category DC-20B, are particularly suited for protection against overcurrents of photovoltaic
systems.The single-pole or two-pole E 90 PV disconnectors for 10.3 x 38 mm cylindrical fuse
links offer a reliable, compact and affordable solution for photovoltaic installations.
Versions with blown fuse indicator allow to check whether the fuse is still working correctly
or not.
E 90 PV
E 90 PV fuse disconnectors for 10.3 x 38 mm fuses (DC-20B)
Poles Rated Modules Bbn Order details Price Weight Pack
current 8012542 1 piece 1 piece unit
—
Protection and safety
E 90 PV 1500 fuse holder
E 90 PV fuse holder
The E 90 PV 1500 series of fuse holders has been designed for applications up 1500 V DC.
Thanks to their rated voltage up to 1500 V DC they are the ideal solution for protecting cells
and inverters. In case of maintenance, they ensure isolation of circuits and strings up to
1500 V in direct current, in total safety. The main features of E 90 PV 1500 fuse holders
include venting grooves and cooling chambers which improved heat dissipation.
—
Protection and safety
E 90 50/125 fuse holders
—
Protection and safety
E 90 CC fuse holders
Technical features
Type E 90/30 CC
Rated voltage [V] 600
Rated current [A] 30
Type of current AC/DC
Rated frequency [Hz] 60
Fuse class CC
E 91 Tightening torque [Nm] PZ2 2-2.5*
[lb-in] PZ2 18-22**
Terminals cross-section [mm2] 25
Cross-section rigid 1 wire 1.5-25 mm2 (16-10 AWG)
copper conductors 2 wires 5 mm2 (10 AWG)
Cross-section stranded 1 wire 1.5-16 mm2 (16-3 AWG)
copper conductors 2 wires 2-5 mm2 (14-10 AWG)
Voltage range for LED indicator light (only s version) [V] 24 - 1000 AC/DC
Can be sealed closed ■
The E 90 fuse holders for Class CC cylindrical fuse links are specifically designed for the
North American market in compliance with the UL standards. In accordance with the
reference standards UL 4248-1 and UL 4248-4, they come in voltage and current ratings up
to 600V and 30A. They are available in 1P, 1P+N, 2P, 3P, 3P+N and 4P versions. They can be
padlocked open and sealed closed.
The E 90 fuse holders are the ideal solution for process control and industrial systems,
automation systems, industrial installations and control circuits. The versions with blown
fuse indicator light provide a visual signal of the fuse break condition
—
Protection and safety
E 90 J fuse fuse holders
Technical features
Type E 90/30 J E 90/60 J
Rated current [A] 30 60
Rated voltage [V] 600
Type of current AC/DC
Fuse Class J 1-30A Class J 31-60A
Rated frequency [Hz] 60
Tightening torque [Nm] PZ2 3.5-4
Terminals cross-section [mm ] 2
50
E 90 Class J
The E 90 Class J fuse holders are the ideal solution for industrial systems, industrial
installations and control circuits. They are specifically designed for the North American
market in compliance with the UL standards. In accordance with the reference standard UL
4248-8, they come in voltage and current ratings up to 600V and 30/60A. They are available
in 1P, 2P and 3P versions. The versions with blown fuse indicator light provide a visual signal
of the fuse break condition. They can be padlocked open and sealed closed to ensure
operator safety during maintenance operations.
—
Protection and safety
Cylindrical fuses E 9F gPV
—
Surge protective devices
UL 1449 4th edition
The Underwriters Laboratories (UL) standard for surge protective devices (SPDs) has been
the primary safety standard for surge protection since the first edition was published in 1985.
The fourth edition became mandatory for AC SPDs in March 2016.
—
Surge protective devices
OVRT2 series – Selection guide
OVR T2 3N 40 320 P TS U
Designation Surge capacity Pluggable Auxiliary contact
Type 2 apps (Imax) (optional)
15 kA
40 kA
S U R G E P R OT E C T I V E D E V I C E S - O V R T S E R I E S 119
—
OVRT series
Product range overview
Surge ratings 15 kA 15 kA 15 kA 15 kA 15 kA 15 kA
40 kA 40 kA 40 kA 40 kA 40 kA 40 kA
End-of-life Only on 40 kA units Only on 40 kA units Only on 40 kA units Only on 40 kA units Only on 40 kA units Only on 40 kA units
signal contact
Replaceable Yes Yes Yes Yes Yes Yes
cartridge
SPD technology MOV MOV MOV MOV MOV MOV
—
OVRT2 series
OVRT2 single-pole
Product features
• Type 4 SPD, UL 1449 4th Edition for Type 2 applications
• Metal oxide varistor (MOV) technology
• Single-pole design
• Replaceable and pluggable cartridges
• DIN rail-mounted SPD
• State indication flag standard on all units
• End-of-life signal standard on 40 kA units
Network type Voltage MCOV VPR Max. disch. Nominal disch. Part number Repl. cartridge
15 kA 5 kA OVRT215150PU OVRT215150CU
120 V AC 150 V AC 0.6 kV OVRT240150PU OVRT240150CU
40 kA 20 kA
OVRT240150PTSU OVRT240150CU
Pole to be connected between 15 kA 5 kA OVRT215320PU OVRT215320CU
240...277
L-N, L-G or L-L 320 V AC 1.0 kV
V AC 40 kA 20 kA OVRT240320PTSU OVRT240320CU
347 V AC 440 V AC 1.3 kV 40 kA 20 kA OVRT240440PTSU OVRT240440CU
480 V AC 550 V AC 1.7 kV 40 kA 20 kA OVRT240550PTSU OVRT240550CU
600 V AC 660 V AC 1.9 kV 40 kA 20 kA OVRT240660PTSU OVRT240660CU
Neutral pole to be connected
230 V AC 255 V AC 1.2 kV 70 kA 20 kA OVRT270NPU OVRT270NCU
between N-G
Electrical characteristics
Operating frequency (AC) 47–63 Hz
Modes of protection L-N, L-G, N-G or L-L
Fault rating (SCCR) 200 kAIC – Upstream protection required (breaker / fuse)
Response time < 25 nanoseconds
Standard monitoring Cartridge state indicator flag
Mechanical characteristics
Weight 0.25 lbs. (120 g)
Housing material Thermoplastic, gray RAL 7035 / V0
Installation location Type 1, indoor
Mounting method DIN rail
Operating temperature -40 °to 80 °C (-40 °to 175 °F)
Wire range (stranded / solid) #6–14 AWG / #4–14 AWG
Product design MOV technology
S U R G E P R OT E C T I V E D E V I C E S - O V R T S E R I E S 121
—
OVRT2 series
OVRT2 1N
Product features
• Type 4 SPD, UL 1449 4th Edition for Type 2 applications
• Metal oxide varistor (MOV) technology
• 1p+N+Gnd complete design
• Replaceable and pluggable cartridges
• DIN rail-mounted SPD
• State indication flag standard on all units
• End-of-life signal standard on 40 kA units
Network type Voltage MCOV VPR Max. disch. Nominal disch. Part number Repl. cartridge
Single-phase 2w+Gnd 15 kA 5 kA OVRT21N15150PU OVRT215150CU
120 V AC 175 V AC 1.2 kV OVRT21N40150PU OVRT240150CU
40 kA 20 kA
OVRT21N40150PTSU OVRT240150CU
Electrical characteristics
Operating frequency 50–60 Hz
Modes of protection L-N and N-G
Fault rating (SCCR) 200 kAIC – Upstream protection required (breaker / fuse)
Response time < 25 nanoseconds
Standard monitoring Cartridge state indicator flag
Mechanical characteristics
Weight 0.53 lbs. (240 g)
Housing material Thermoplastic, gray RAL 7035 / V0
Installation location Type 1, indoor
Mounting method DIN rail
Operating temperature -40 °to 80 °C (-40 °to 175 °F)
Wire range (stranded / solid) #6–14 AWG / #4–14 AWG
Product design MOV technology
122 S Y S T E M P R O M C O M PA C T ™ C I R C U I T P R OT E C T I O N D E V I C E S O N D I N R A I L
—
OVRT2 series
OVRT2 2L
Product features
• Type 4 SPD, UL 1449 4th Edition for Type 2 applications
• Metal oxide varistor (MOV) technology
• 2p+Gnd complete design
• Replaceable and pluggable cartridges
• DIN rail-mounted SPD
• State indication flag standard on all units
• End-of-life signal standard on 40 kA units
Network type Voltage MCOV VPR Max. disch. Nominal disch. Part number Repl. Cartridge
Split phase 2w+Gnd
15 kA 5 kA OVRT22L15150PU OVRT215150CU
40 kA 20 kA OVRT2240150PTSU OVRT240150CU
15 kA 5 kA OVRT22L15320PU OVRT215320CU
40 kA 20 kA OVRT22L40320PTSU OVRT240320CU
Electrical characteristics
Operating frequency 50–60 Hz
Modes of protection L-L and L-G
Fault rating (SCCR) 200 kAIC – Upstream protection required (breaker / fuse)
Response time < 25 nanoseconds
Standard monitoring Cartridge state indicator flag
Mechanical characteristics
Weight 0.53 lbs. (240 g)
Housing material Thermoplastic, gray RAL 7035 / V0
Installation location Type 1, indoor
Mounting method DIN rail
Operating temperature -40 °to 80 °C (-40 °to 175 °F)
Wire range (stranded / solid) #6–14 AWG / #4–14 AWG
Product design MOV technology
S U R G E P R OT E C T I V E D E V I C E S - O V R T S E R I E S 123
—
OVRT2 series
OVRT2 2N
Product features
• Type 4 SPD, UL 1449 4th Edition for Type 2 applications
• Metal oxide varistor (MOV) technology
• 2p+N+Gnd complete design
• Replaceable and pluggable cartridges
• DIN rail-mounted SPD
• State indication flag standard on all units
• End-of-life signal standard on 40 kA units
Network type Voltage MCOV VPR Max. disch. Nominal disch. Part number Repl. Cartridge
Split phase 2w+N+Gnd 0.7 kV 15 kA 5 kA OVRT22N15150PU OVRT215150CU
120 V AC 175 V AC
0.6 kV 40 kA 20 kA OVRT22N40150PTSU OVRT240150CU
0.7 kV 15 kA 5 kA OVRT22N15320PU OVRT215320CU
277 V AC 320 V AC
1.1 kV 40 kA 20 kA OVRT22N40320PTSU OVRT240320CU
347 V AC 440 V AC 1.4 kV 40 kA 10 kA OVRT22N40440PTSU OVRT240440CU
480 V AC 550 V AC 1.8 kV 40 kA 10 kA OVRT22N40550PTSU OVRT240550CU
600 V AC 660 V AC 2.0 kV 40 kA 10 kA OVRT22N40660PTSU OVRT240660CU
Neutral pole 230 V AC 255 V AC 1.2 kV 70 kA 20 kA - OVRT270NCU
Electrical characteristics
Operating frequency 50–60 Hz
Modes of protection L-L, L-N , N-G and L-G
Fault rating (SCCR) 200 kAIC – Upstream protection required (breaker / fuse)
Response time < 25 nanoseconds
Standard monitoring Cartridge state indicator flag
Mechanical characteristics
Weight 0.80 lbs. (360 g)
Housing material Thermoplastic, gray RAL 7035 / V0
Installation location Type 1, indoor
Mounting method DIN rail
Operating temperature -40 °to 80 °C (-40 °to 175 °F)
Wire range (stranded / solid) #6–14 AWG / #4–14 AWG
Product design MOV technology
124 S Y S T E M P R O M C O M PA C T ™ C I R C U I T P R OT E C T I O N D E V I C E S O N D I N R A I L
—
OVRT2 series
OVRT2 3L
Product features
• Type 4 SPD, UL 1449 4th Edition for Type 2 applications
• Metal oxide varistor (MOV) technology
• 3p+Gnd complete design
• Replaceable and pluggable cartridges
• DIN rail-mounted SPD
• State indication flag standard on all units
• End-of-life signal standard on 40 kA units
Network type Voltage MCOV VPR Max. disch. Nominal disch. Part number Repl. Cartridge
15 kA 5 kA OVRT23L15150PU OVRT215150CU
120 V AC 175 V AC 0.6 kV
40 kA 20 kA OVRT23L40150PTSU OVRT240150CU
15 kA 5 kA OVRT23L15320PU OVRT215320CU
277 V AC 320 V AC 1.0 kV
40 kA 20 kA OVRT23L40320PTSU OVRT240320CU
Electrical characteristics
Operating frequency 50–60 Hz
Modes of protection L-L and L-G
Fault rating (SCCR) 200 kAIC – Upstream protection required (breaker / fuse)
Response time < 25 nanoseconds
Standard monitoring Cartridge state indicator flag
Mechanical characteristics
Weight 0.80 lbs. (360 g)
Housing material Thermoplastic, gray RAL 7035 / V0
Installation location Type 1, indoor
Mounting method DIN rail
Operating temperature -40 °to 80 °C (-40 °to 175 °F)
Wire range (stranded / solid) #6–14 AWG / #4–14 AWG
Product design MOV technology
S U R G E P R OT E C T I V E D E V I C E S - O V R T S E R I E S 125
—
OVRT2 series
OVRT2 3N
Product features
• Type 4 SPD, UL 1449 4th Edition for Type 2 applications
• Metal oxide varistor (MOV) technology
• 3p+N+Gnd complete design
• Replaceable and pluggable cartridges
• DIN rail-mounted SPD
• State indication flag standard on all units
• End-of-life signal standard on 40 kA units
Network type Voltage MCOV VPR Max. disch. Nominal disch. Part number Repl. Cartridge
Three phase 4w+Gnd 0.6 kV 15 kA 5 kA OVRT23NN15150PU OVRT215150CU
120 V AC 175 V AC
1.2 kV 40 kA 20 kA OVRT23N40150PTSU OVRT240150CU
15 kA 5 kA OVRT23N15320PU OVRT215320CU
277 V AC 320 V AC 1.2 kV
40 kA 20 kA OVRT23N40320PTSU OVRT240320CU
347 V AC 440 V AC 1.2 kV 40 kA 10 kA OVRT23N40440PTSU OVRT240440CU
480 V AC 550 V AC 1.2 kV 40 kA 10 kA OVRT23N40550PTSU OVRT240550CU
600 V AC 660 V AC 1.2 kV 40 kA 10 kA OVRT23N40660PTSU OVRT240660CU
Neutral pole 230 V AC 255 V AC 1.2 kV 70 kA 20 kA - OVRT270NCU
Electrical characteristics
Operating frequency 50–60 Hz
Modes of protection L-L and L-G
Fault rating (SCCR) 200 kAIC – Upstream protection required (breaker / fuse)
Response time < 25 nanoseconds
Standard monitoring Cartridge state indicator flag
Mechanical characteristics
Weight 1.05 lbs. (480 g)
Housing material Thermoplastic, gray RAL 7035 / V0
Installation location Type 1, indoor
Mounting method DIN rail
Operating temperature -40 °to 80 °C (-40 °to 175 °F)
Wire range (stranded / solid) #6–14 AWG / #4–14 AWG
Product design MOV technology
126 S Y S T E M P R O M C O M PA C T ™ C I R C U I T P R OT E C T I O N D E V I C E S O N D I N R A I L
—
OVRT2 series
Dimensions
Dimensions OVRT2
Value Inches / millimeters
W 0.70 / 17.8
D 2.55 / 64.8
W 1.40 / 35.6
D 2.55 / 64.8
W 2.10 / 53.4
D 2.55 / 64.8
—
OVRT2 series
Dimensions
Dimensions OVRT2 3N
Value Inches / millimeters
W 2.80 / 71.2
D 2.55 / 64.8
—
We reserve the right to make technical
changes or modify the contents of this
document without prior notice. With
regard to purchase orders and/or
contracts, the agreed particulars shall
prevail. ABB Inc. does not accept any
responsibility whatsoever for potential
errors or possible lack of information in
1SXU400208C0201 CT REV.D JAN.2021
this document.