Summary
FactoryTalk: Deleting the RNL Files
Problem
Any of the following errors may be linked to a common cause. The software could be working fine prior to having
the error codes:
When attempting to run FactoryTalk View Studio version 6.10, the following error
Top
occurs:
This software requires personalized information cannot be read.
Success: This answer has been added to your Favorites
When attempting to run FactoryTalk View SE Client in a ThinManager system, seen in
VersaView 5000:
This software requires personalized information cannot be read.
When attempting to load an MER runtime file into FactoryTalk View ME Station
version 6.10, the following error occurs:
Unable to load application
When attempting to load an MER runtime file into FactoryTalk View ME Station
version 6.00, the following error occurs:
Unable to load application. Unable to open the HMI project. The
HMI project contains more displays then the FactoryTalk View ME
Station is licensed for (limit = 5)
The following error is displayed when the computer boots:
The Rockwell Application Services hung on starting.
The following error is displayed when trying to connect to the ViewPoint
administrative site:
Unable to connect to FactoryTalk ViewPoint administration.
When using the Specify FactoryTalk directory utility, clicking the Browse button,
causes this error:
’ADsGetObject(RNA_GLOBAL_SCOPE_ADSPATH,
_uuidof(pIRnaGlobalScope),
Top
code: ’0x8007042c’.
When FactoryTalk View Studio tries to open a HMI server in a remote computer, the
following error may occur, even though the server is licensed correctly and the
number of displays is well under the limit:
The HMI server in area <Area Name> refused to load its project.
The HMI Project contains more displays the server is licensed
for (display limit = <number of display>)
Every time FactoryTalk View Studio is launched, the following error occur even
though the FactoryTalk View Studio license is available:
program path
C:\Program Files\Common
Files\Rockwell\datalinklibrary\rsves32.dll
Top
When launching RSLogix 5, RSLogix 500 and RSLogix 5000 / Studio 5000 software,
Success:
the splash screen This answer
appears has been
and software added
doesn’t to your Favorites
start.
When launching RSLogix 500 it gives error message:
RSLogix 500 development environment stopped working.
When launching RSLogix 5 it gives error message:
RSLogix 5 PLC5 Application has stopped working.
The following error is displayed during the installation of FactoryTalk Alarms and
Events:
Service ’ Rockwell Alarm Server ’ ( RnaAeServer.exe ) failed to
start.
When launching Studio 5000 it opens in grace period even all licenses are present in
FactoryTalk Activation Manager.
When attempting to start Studio 5000 Logix Designer software, got Fatal Error:
Error 0x8002260 (-2147212704)
Top
Success: This answer has been added to your Favorites
When attempting to start RSLogix 5000 v.20.04.00, Event Viewer is showing:
Environment
FactoryTalk View Site Edition
FactoryTalk View Machine Edition
FactoryTalk ViewPoint
RSLogix 500
RSLogix 5000
Windows XP:
Start menu --> Settings --> Control Panel --> Folder options --> View
Windows 7:
Start menu --> Control Panel --> Appearance and Personalization--> Folder options
--> View
Windows 10:
Start menu --> Control Panel --> Appearance and Personalization --> File Explorer
Options -->View
2. Select Show hidden files, folders and drives.
3. Navigate to the following directory and remove all the .RNL files:
Top
4. Remove the .RNL files from a Recycle Bin as well.
5. Reboot the computer.
Note: If FactoryTalk Activation Manager v3.60 is installed, upgrade it to v3.62 and reboot the computer. If the
FactoryTalk View v6.00 is installed, follow technote FactoryTalk View 6.x Patch: SE Client or Studio will hang on
close (personalized information error)
Attachments
RATE CONTENT
Top
Recently Viewed
LDAP domain
Success: This answer has been added to your Favorites
FactoryTalk View
authentication in
FactoryTalk View Machine Edition 8.xx
FactoryTalk View
software opens in and later Domain
Machine Edition
Demo Mode Authentication
version 8.x only
Support
supports one chil...
DISCLAIMER
This knowledge base web site is intended to provide general technical information on a particular subject or subjects
and is not an exhaustive treatment of such subjects. Accordingly, the information in this web site is not intended to
constitute application, design, software or other professional engineering advice or services. Before making any
decision or taking any action, which might affect your equipment, you should consult a qualified professional advisor.
ROCKWELL AUTOMATION DOES NOT WARRANT THE COMPLETENESS, TIMELINESS OR ACCURACY OF ANY OF THE
DATA CONTAINED IN THIS WEB SITE AND MAY MAKE CHANGES THERETO AT ANY TIME IN ITS SOLE DISCRETION
WITHOUT NOTICE. FURTHER, ALL INFORMATION CONVEYED HEREBY IS PROVIDED TO USERS "AS IS." IN NO EVENT
SHALL ROCKWELL BE LIABLE FOR ANY DAMAGES OF ANY KIND INCLUDING DIRECT, INDIRECT, INCIDENTAL,
CONSEQUENTIAL, LOSS PROFIT OR DAMAGE, EVEN IF ROCKWELL AUTOMATION HAVE BEEN ADVISED ON THE
POSSIBILITY OF SUCH DAMAGES.
ROCKWELL AUTOMATION DISCLAIMS ALL WARRANTIES WHETHER EXPRESSED OR IMPLIED IN RESPECT OF THE
INFORMATION (INCLUDING SOFTWARE) PROVIDED HEREBY, INCLUDING THE IMPLIED WARRANTIES OF FITNESS FOR
A PARTICULAR PURPOSE, MERCHANTABILITY, AND NON-INFRINGEMENT. Note that certain jurisdictions do not
countenance the exclusion of implied warranties; thus, this disclaimer may not apply to you.
www.rockwellautomation.com
Top