The document is a product reference guide for Protection & Measurement Devices from 2015. It includes sections about the company's vision, mission and quality standards. The bulk of the document consists of tables listing the features and protections provided by various relay products, including the CSEZEN Multi-protection Series, CSPRO Series, and others for applications like HV/MV feeders, generators, motors, transformers and more.

Uploaded by

sanjay
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
117 views16 pages

Reference Guide

The document is a product reference guide for Protection & Measurement Devices from 2015. It includes sections about the company's vision, mission and quality standards. The bulk of the document consists of tables listing the features and protections provided by various relay products, including the CSEZEN Multi-protection Series, CSPRO Series, and others for applications like HV/MV feeders, generators, motors, transformers and more.

Uploaded by

sanjay
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 16

PRODUCT REFERENCE GUIDE

Protection & Measurement Devices - 2015

PMD Division


Vision
 To be the most trusted, respected and preferred brand
 To be closest to its customer
 To manage power in India’s biggest industries, in its highest
buildings, in its most critical infrastructures and in millions of its
homes
 To serve as a role model to others
 To make “MADE IN INDIA” a respected label world over

Mission
 To create a unique alchemy of outstanding products, operational
excellence, path breaking customer services and compelling
marketing
 To create the best place to work where employees are empowered,
cared, developed and provided unlimited opportunities
 To continuously innovate, enhance our core technologies and
develop new world class products
 To be India’s largest exporter of industrial power distribution and
control equipment
 To everyday experience, the sheer joy of delighting our internal and
external customers
 To earn healthy return on investment

Quality at Source
 The ISO 9001:2008 certificate from DNV reiterates that the standard
of design, manufacturing and service provided by us follow most
stringent control and supervision procedures

 Our R&D facilities stand recognized by Govt. of India for the high
quality of developments & new products. We are member of FITT
(Foundation for Innovation and Technology) body run by IIT, New
Delhi, INDIA.

02


 CSEZEN Multi-protection Series 04

 CSPRO Series 05

 CSENEX Series 06

 IRI-PRO Series 07

 Generator Solution 08

 Auxiliary Relays 09

 Electronic Motor Protection Relay (EMPR) 10

 Self Powered Relay for RMU 11

 Fault Passage Indicator for RMU 12

 Live Line Indicator 13

 Digital Panel Meters 14

 APFC (Power Factor Controller) 15

03


CSEZEN Protection Solutions for HV/MV


Feeder, Generator, Motor and Transformer
 7 CT + 4 PT : Analog Inputs
 1A/5A Rated CT (Site Selectable)
 50/60 Hz Nominal Frequency (Site Selectable)
 Wide Range Auxiliary Supply
 Self CT Shorting Modular Design
 16 DI / 16 DO programmable
 IEC 61850/IEC-103/MODBUS Communication Protocol
 USB / OTG Communication
Fault Event Oscilloscope
Record Record Record
20 500 1200

PROTECTIONS F-500 M-500 T-500


Transformer Differential (87P)   
3 Ph Over current (50/51P)   
Earth Over current (50N/51N)   
Locked Rotor (50LR)   
Stall (50S)   
Startup monitoring / Excessive long start (66/48)   
Restricted Earth Fault (64N/87G)   
3 Ph Directional Over current (67P)   
Earth Fault Directional Over current (67N)   
Voltage Controlled Over current (51V)   
3 Ph Under current (37P)   
Negative Phase Sequence Over current (46)   
Phase under/over voltage (AND & OR mode) (27/59)   
Negative Over voltage (47)   
Power Protection (Under/Over/Reverse power) (32)   
Under/over Frequency (81 U/O)   
Rate of Change of Frequency (81R)   
Thermal Over load (49)   
Output Relay Latching (86)   
Auto Reclose (79)   
Circuit Breaker Failure Detection (50BF)   
Broken Conductor (46BC)   
Over Excitation (24)   
Blocking Logic   
Test of Output Relays (Maintenance)   
CB Control Local/Remote   
Circuit Breaker Maintenance & Trip circuit Supervision   
Cold Load Pickup   
Selective Relay Scheme Logic   
Over Fluxing/5th Harmonic/2nd Harmonic   
Inrush Blocking   
Switch on to Fault (SOTF)   
CT Supervision (CTS)   
VT Supervision (VTS)   

04


CSEPRO Protection Solutions for Distribution


 Multi-function Protection for Distribution
 7 CT + 3 PT : Analog Inputs
 1A/5A Rated CT (Site Selectable)
 50/60 Hz Nominal Frequency (Site Selectable)
 Wide Range Auxiliary Supply
 Self CT Shorting Modular Design
 6 DI / 6 DO programmable
 IEC 61850/IEC-103/MODBUS Communication Protocol
 USB Communication
Fault Event Oscilloscope
Record Record Record
10 100 1200

PROTECTIONS F220 F300 T140 T170 M200


3 Phase Over current (50/51P)     
Earth Over current     
Under Voltage (27)     
Over Voltage (59)     
Neutral Displacement (59N)     

Transformer Differential (87T)     


Restricted Earth Fault (64/87G)     

Locked Rotor (50LR)     

Stall Protection (50S)     


Under Current (37)     
Thermal Over load (49)     
Voltage controlled Over current (51V)     

Current Unbalance / NPS (46)     


Negative Sequence Over Voltage (47)     

Latching Relay (86)     


CBFP Protection (50BF)     
Inrush Blocking     
Trip Circuit Supervision (TCS)     
Auto Recloser (AR)     
Broken Conductor (46BC)     
Cold Load Pickup     

Common Data
Aux Voltage 

CT Secondary  


Relay Size (HxWxD) in mm 
Cut out Size (HxW) in mm 
Relay Case 

Features
Fault Recorder     

Event Recorder     


Disturbance Recorder     
Digital Input     

Digital Output     
Front USB     
RS-485 (Modbus)     
RS-485 IEC 60870-5-103     
RJ-45 IEC61850     
SNTP Time Synch RJ-45     

05


CSENEX Protection Solutions for Distribution


 Over-current Protection
 Voltage Protection
 Motor Protection
 1A/5A Rated CT (Site Selectable)
 50/60 Hz Nominal Frequency (Site Selectable)
 Wide Range Auxiliary Supply
 Self CT Shorting Modular Design
 MODBUS / IEC-103
 USB Communication
 4 DI / 4 DO programmable

PROTECTIONS Nex Nex-I Nex-I Nex-U Nex-M


100/101 201/202/203 300 200 100

IDMTL Over current & Earth Fault (51/51N)     


Instantaneous Over current & Earth Fault (50/50N)     
Cold Load Pickup     
Inrush Blocking (51H)     
Under Voltage (27)     

Over Voltage (59)     


Neutral Displacement (59N)     
Locked Rotor (50LR)     

Stall Protection (50S)     

Under Current (37)     


Thermal Over load (49)     
Current Unbalance / NPS (46)     

Negative Sequence Over Voltage (47)     

Latching Relay (86)     


CBFP Protection (50BF)     
Trip Circuit Supervision (TCS)     
Auto Recloser (AR)     
Broken Conductor (46BC)     

Common Data
Aux Voltage 

CT Secondary   


Relay Size (HxWxD) in mm  
Cut out Size (HxW) 

Relay Case  

Features
Fault Recorder     

Event Recorder     


Disturbance Recorder     

No. of Group Settings     


Digital Input     
Digital Output     

Front USB     
RS-485 (Modbus)     
RS-485 IEC 60870-5-103     

06


IRIPRO Range offers following Protection Solutions


Hardware
 Micro-controller based Numeric Design
 Measures True RMS with DFT Filter
 4 Current Analog Inputs
 Bright LCD Display
 USB communication / RS-485 Rear Communication
 15 LEDs for Annunciation

Protection Features
 3 Phase Time Over-current Protection (51)
 3 Phase Instantaneous Protection
 Earth Time Over-current (51N)
 Earth Instantaneous Over-current (50N)
 Circuit Breaker Failure Protection (50BF)
 Under / Voltage Protection (27/59)
 Neutral Displacement (59N)

PROTECTIONS IRIPro IRIPro IRIPro IRUPro IRI-ES IRI-1ER IRD1-T2


V4 V2/V3 V3-EO UOR
Current Differential (87)       
IDMTL Over current (51)       
Instantaneous Over current (50)       

IDMTL Earth Fault (51N)       


Instantaneous Earth Fault (50N)       
Inrush Blocking (51H)       
Sensitive Earth Fault (50SN)       
Under Voltage (27)       

Over Voltage (59)       


Neutral Displacement (59N)       
Negative Sequence Over Voltage (47)       
Restricted Earth Fault (64)       

CBFP Protection (50BF)       


CT Input       

Common Data
Aux Voltage 

Relay Size (HxWxD) in mm   


Cut out Size   

Relay Case  

Features
Fault Recorder       

Event Recorder       


Digital Output       

Front USB       
RS-485 (Modbus)       

07


Special Products for Grid Islanding

Features
 MRI1-IR-SR - Directional Over Current + Earth Fault Relay
 MRQ1 - Field Failure Relay
 MRP2 - Reverse Power Relay
 MRF2 - Under & Over Frequency with df/dt Relay
 MRN2 - Mains Decoupling Relay
Combination of Under & Over Voltage, Under & Over Frequency
with df/dt protection (or) Vertor Surge Protection Relay
 MRG2 - VECTOR SURGE Relay
 MRR1 - Rotor Earth Fault Relay

Generator Protection Solutions (Basic Range)

 BU1-AC-UO - Under & Over Voltage Relay


 BF1-UO - Under & Over Frequency Relay
 BP1-R - Reverse Power Relay
 BA-1 - Voltage Balance Relay

08


MRA-Pro-V2 supervision relay is a advance numeric relay that provides circuit breaker supervision

Features
 Continuous Trip Circuit Supervision of both pre closing and post closing conditions in
circuit breaker
 Detection and Alarm of trip circuit supply failure and circuit breaker tripping mechanism
failure such as loss of voltage, trip circuit connection, contact degeneration in wires,
contacts and coils
 Single Phase CB monitoring
 Flush mounting enclosure
 2 Output contacts
 Operation delay to avoid spurious signals for instance on circuit breaker operations
 Functional Operation indication by 4 LEDs namely CB OK, CB Fail Manual & Edit
 Test function for Self test facilitates routine maintenance
MRA-Pro-V2
 Auto / Manual operation mode

The Lockout Relay CLR series are equipped with following:

Features
 Electro-mechanical Design
 Suitable for Tripping, Signaling in Protection & Control System
 Consistent and repeat Accuracy
 High resistance to Shock & Vibration
 Flexible user friendly standardized contacts arrangement
 Hand Reset flag indication
 Compact Panel mounting case
 High Speed with positive operation
CLR

The CAR type auxiliary relay are voltage operated relays, mainly used in control
and alarm circuits.
CAR series of relay are available in two basic models CAR-H and CAR-S
Auxiliary relay CAR-H is provided with hand reset contacts. CAR-S is self
reset type.
CAR series of relay are available in two elements & 3 elements model. Each
element can be energized separately
The CAR series of relays are used in various applications such as:
 Switching functions in protection and control circuits
 Contact multiplication
 Other Auxiliary and Alarm functions CAR

09
Electronics Motor Protection Relay (EMPR)

mPRO
Modular Motor Protection & Control Relay for LV Motors. It includes three phase
current monitoring with integral CT in a range of 1A to 60A current. It provides
Modbus communication (RS-485), RTD input & 4-20mA Output, Digital Input & Output

Protection
Functions ANSI CSMPA CSMPM mPRO-100 mPRO-200
Over current 51    
Stall Protection 51S    
Unbalance / Asym 46    
Phase Reversal 47    
Phase Loss PL    
Locked Rotor 51LR    
Earth Fault 51N    
Under Current 37    
Thermal Over-load 49    

Common Data
Aux Voltage 110V / 220V AC Universal Universal
Current Range A 1.5/5/22/40/80 (5-60)/(0.5-6.0) (1-60)/0.25-5) (1-60)/0.25-5)

Display LED LCD


Enclosure Type DIN Rail

Features
Fault Recorder - - 1 1
Digital Input - - - 2
Output 1NO+1NC 1NO+1NC 1C/O+2NO 1CO+2NO
2NO+2NC
Miscellaneous Application Load Bar Load Bar External CT
(Product Highlight) 0.2+HP graph graph Fail safe
onwards & Current with Run & Operation/
Measurement Trip LEDs DI-DO
programmable
Thermal record
Motor Start-
Stop History
RS-485
(Modbus) / (4-20mA)/RTD - - - - Optional

  

10


CSDPR-V2
 Numeric multi powered Over-current relay with Display
 Low VA Burden
 Small & compact size
 Get energizes from any one : CT, VT, Battery, USB
 O/C, S/C, E/F and E/F High set / Unbalance / TCS / CBFP protection
 RS-485 Modbus communication Rear panel / USB port for PC / Laptop
 Event / Fault record with Time stamp
 Remote trip / Remote protection block
 4 Output relays out of which 2 programmable
 Two set of setting group
 Potential pulse output for direct triggering the circuit breaker coil.
(Potential free contacts also available)

CSPR-V5
 Compact Numeric Self Powered Over-current Relay
 Potential pulse output for direct triggering the Circuit Breaker Coil
 O/C, S/C, E/F, E/F High set protection
 Low VA Burden
 Fault / Event Record
 RS-485 Modbus Communication

Technical Data Records

Rated Aux Voltage (UH) : 85-265V AC/110-300V DC/18-60V DC Fault Recorder : 05 (non volatile with Date/Time stamp)
Rated Phase Current (In) : 1A / 5A Event Recorder : 10 (non volatile with Date/Time stamp)
Current Measuring Range : 30xIp
Thermal Load Capacity : Continuous = 2xIn
: for 1 sec = 20xIn
Rated Frequency (Fn) : 50/60 Hz Tests & Environment
Digital Input : 02 No.
Design : IEC 60255
Digital Output Contacts : 04 Nos
Operating Temperature : -25 to +700C
Potential Pulse Output : [email protected]
Front Port : USB Weight : 2.0 kg

Rear Port : RS-485 on MODBUS / IEC-103

11


CSFPI

Short Circuit Sensor Earth Fault Sensor

Sensor dia (d) Cable dia Sensor dia (d) Cable dia
D1 15-25 mm (Round) D1 80-100 mm (Round)
D2 18-44 mm (Round) D2 100-120 mm (Round)
D3 40-60 mm (Round) D3 120-140 mm (Round)

12
Introduction
CSFPI is designed to detect and indicate Earth fault and Short circuit on a cable system, which can be used in RMU networks with one
input / open ring arrangement. The unit will indicate a fault condition when current is detected above present amperage trip current settings.
Fault current is sensed by cable mounted sensor, which gives signal to Front display unit. All sensors are clamp type sensor and can be
retrofitted on the cable.

Features
 Programmable Short Circuit Pickup level (Wide Range 100A to 1200A)
 Programmable Earth Fault Pickup level (Wide Range 10A to 100A)
 Indication of permanent Earth Faults by blinking of Earth Fault LED
 Indication of a Short Circuit by blinking of the Short Circuit LEDs
 Programmable response delay for Short Circuits and Earth Faults (individually)
 Up-to Three potential free contacts to indicate Earth Fault, Short Circuit and Battery Low remote indication
 Various Reset option for a Fault Reset 9current recovery / potential free input / press by push button / by SCADA / by time)



 Capacitive based Indicator for High Voltage

 Three phase live line indicator as per IEC-61243-5

 Compatible for different capacitor based insulator (3kV to 24kV)

LLI

13


 



Features
 True RMS measurement
 Accuracy as per IEC 61036
 Password protected parameter
 Programmable CT/PT Ratio
 Auto scrolling of parameters
 Compact size of 96 x 96 mm
 Micro processor based Digital Panel Meter Series

CSM-E Model No. Description


CSM-P1-S1-C 1 Phase PF Meter with Comm.
CSM-V3-S1-C 3 Phase Volt Meter with comm.
CSM-I3-S1-C 3 Phase Ammeter with comm.
CSM-E3-S3-D 3 Phase Dual Source kWh Meter
CSM-E3-S3-C 3 Phase kWh Meter with comm.
CSM-E3-S3-D-C 3 Phase Dual Source kWh Meter with Comm.
CSM-M3-S3-C 3 Phase V+I+F Meter with comm.
CSM-M4-S3-C 3 Phase V+I+F+PF+KW Meter with comm
CSM-M5-S3-D 3 Phase Dual Source V+I+F+kW+kVA+kWh Meter
CSM-M5-S3-C 3 Phase V+I+F+kW+kVA+kWh Meter with Comm.
CSM-M5-S3-D-C 3 Phase Dual Source V+I+F+kW+kVA+kWh Meter with Comm.

14




 8/12/14/16 Power Factor Controller


 Metering
 Harmonic
 Auto Setting
 Capacitor Bank Protection
 Protection on insufficient compensation/Over voltage/Current
 Effective PF Control. Up to 12 capacitor banks controllable
 Full Functional 16 x 4 LCD display for user friendly interface
 Auto / Manual Operation
 Wide range of measuring voltage Input
 True RMS measurement of AC parameters
 Measurement & display of line parameters like V, I, P, Q, S, Cos&
 Indication of Capacitor Bank switched through Front LEDs
 Wide range of Programmable parameter including CT/PT ratio, target Cos& value, Capacitor Bank switching program etc.
 Protection & Indication on abnormal condition such as Over/Insufficient Compensation, Voltage Harmonics, Over Voltage,
Over/Under Current etc.
 No-Voltage Turn off
 Field accessible test mode for relay contact check
 144x144 mm Panel mountable housing
 Alarm output on abnormal conditions

15

 


  
