EV2000 Series Universal Variable Speed Drive User Manual
EV2000 Series Universal Variable Speed Drive User Manual
User Manual
Version V3.2
Revision date August 11, 2008
BOM 31011126
Emerson Network Power provides customers with technical support. Users may
contact the nearest Emerson local sales office or service center.
All rights reserved. The contents in this document are subject to change without
notice.
Address: No.1 Kefa Rd., Science & Industry Park, Nanshan District 518057,
Shenzhen China
Homepage: www.emersonnetworkpower.com.cn
E-mail: [email protected]
Contents
Preface ................................................................................................................................................................................ 1
Unpacking Inspection ................................................................................................................................................... 1
Model designation rules ............................................................................................................................................... 1
Chapter 1 Safety............................................................................................................................................................... 2
1.1 Safety .................................................................................................................................................................. 2
1.2 Notes for Installations .......................................................................................................................................... 2
1.3 Notes for Using EV2000 ...................................................................................................................................... 2
1.3.1 About Motor and Load .................................................................................................................................. 2
1.3.2 About Variable Speed Drive .......................................................................................................................... 3
1.4 Disposing Unwanted Drive .................................................................................................................................. 4
Chapter 2 Product Introduction ......................................................................................................................................... 5
2.1 Specifications ...................................................................................................................................................... 5
2.2 Product Series ..................................................................................................................................................... 7
2.2.1 Ratings .......................................................................................................................................................... 7
2.2.2 Parts of Variable Speed Drive ....................................................................................................................... 8
2.2.3 Outline and Gross Weight ............................................................................................................................. 8
2.3 Optional Parts .................................................................................................................................................... 12
2.3.1 LCD Operational Panel ............................................................................................................................... 12
2.3.2 Braking Kits ................................................................................................................................................. 12
2.3.3 Communication Parts .................................................................................................................................. 14
Chapter 3 Installation and Wiring .................................................................................................................................... 15
3.1 Installation Environment .................................................................................................................................... 15
3.2 Removing and Mounting of Parts ...................................................................................................................... 15
3.2.1 Removing and Installation of Operation Panel ............................................................................................ 15
3.2.2 Removing and Mounting of Cover ............................................................................................................... 16
3.3 Wire Connections of Drive ................................................................................................................................. 17
3.3.1 Wire Connections of Main Terminals .......................................................................................................... 17
3.3.2 Wiring of Control Circuit .............................................................................................................................. 22
3.4 Installation Methods Compliant With EMC Requirements ................................................................................. 31
3.4.1 Noise Suppressing ...................................................................................................................................... 31
3.4.2 Field Wire Connections ............................................................................................................................... 32
3.4.3 Earthing ...................................................................................................................................................... 33
3.4.4 Installation Requirements of Relay, Contactor and Electro-magnetic Braking Kit ....................................... 34
3.4.5 Leakage Current ......................................................................................................................................... 34
3.4.6 Correct EMC Installation ............................................................................................................................. 34
3.4.7 Application of Power Line Filter................................................................................................................... 35
3.4.8 EMI of The Drive ......................................................................................................................................... 36
Chapter 4 Operation Instructions .................................................................................................................................... 37
4.1 Notice ................................................................................................................................................................ 37
4.1.1 The Drive’s Control Modes.......................................................................................................................... 37
4.1.2 Reference Selector ..................................................................................................................................... 37
4.1.3 Operating Status ......................................................................................................................................... 37
4.1.4 Operating Modes ........................................................................................................................................ 37
4.2 Operating Instructions ....................................................................................................................................... 38
4.2.1 Using Operation Panel ................................................................................................................................ 38
4.2.2 Function of Keys ......................................................................................................................................... 39
4.2.3 Function Descriptions of LED and Indicators .............................................................................................. 39
4.2.4 Display of the Drive ..................................................................................................................................... 40
4.2.5 Panel Operation .......................................................................................................................................... 40
4.3 Start-up .............................................................................................................................................................. 41
4.3.1 Checking before Start-up ............................................................................................................................ 41
4.3.2 Start up the Drive for the First Time ............................................................................................................ 42
Chapter 5 Parameter Introductions ................................................................................................................................. 43
5.1 Basic Operating Parameters(Group F0) ............................................................................................................... 43
5.2 Parameters of Reference Frequency (Group F1) .............................................................................................. 46
5.3 Starting and Braking Parameters (Group F2) .................................................................................................... 47
5.4 Auxiliary Operating Parameters (Group F3) ...................................................................................................... 49
5.5 PLC Operating Parameters(Group F4)................................................................................................................... 52
5.6 Close-loop Control Parameters(Group F5) ................................................................................................................. 55
5.7 Traverse Operating Parameters (Group F6) ...................................................................................................... 58
5.8 Function of Terminals(Group F7)....................................................................................................................... 60
5.9 Display (Group F8) ............................................................................................................................................ 69
5.10 Enhanced Functions(Group F9) ...................................................................................................................... 70
5.11 Reserved (Group FA) ...................................................................................................................................... 76
5.12 Communication Parameters (Group FF) ................................................................................................................ 76
5.13 Motor Parameters (Group FH) ......................................................................................................................... 77
5.14 Protective Function (Group FL) ....................................................................................................................... 78
5.15 Drive Parameters (Group Fn) .......................................................................................................................... 81
5.16 Protection of Parameters (FP) ......................................................................................................................... 81
Chapter 6 Troubleshooting ............................................................................................................................................. 83
Chapter 7 Maintenance .................................................................................................................................................. 88
7.1 Daily Maintenance ............................................................................................................................................. 88
7.2 Periodical Maintenance ..................................................................................................................................... 88
7.3 Replacing Wearing Parts ................................................................................................................................... 89
7.4 Storage .............................................................................................................................................................. 89
7.5 Warranty ............................................................................................................................................................ 89
Appendix 1 Parameters .................................................................................................................................................. 90
Appendix 2 Accessories ............................................................................................................................................... 108
AC/DC Reactor ........................................................................................................................................................ 108
380V Series EMI Filter ............................................................................................................................................. 111
Manufacturer Information ......................................................................................................................................... 112
Appendix 3 Communication Protocol ............................................................................................................................ 113
1 Networking Mode................................................................................................................................................ 113
2 Interfaces ............................................................................................................................................................ 113
3 Communication Modes ....................................................................................................................................... 113
4 Protocol Format .................................................................................................................................................. 114
5 Explanations of Format....................................................................................................................................... 114
5.1 Head of Frame................................................................................................................................................ 114
5.2 Address of Slave ............................................................................................................................................ 115
5.3 Response of Slave to Master’s Command ..................................................................................................... 115
5.4 Index Section .................................................................................................................................................. 116
5.5 Checksum ...................................................................................................................................................... 116
5.6 Frame Tail ...................................................................................................................................................... 116
Preface 1
Preface
Thank you for using EV2000 series Variable Speed
Drive made by Emerson Network Power Co., Ltd.. Model designation rules
EV2000 satisfies the high performance requirements by EV2000 -4 T 0055 G / 0075 P
using a unique control method to achieve high torque, Drive series Code Drive type
high accuracy and wide speed-adjusting range. Its G Fixed torque
Volt Code P Fan & pump
anti-tripping function and capabilities of adapting to
220V 2
severe power network, temperature, humidity and dusty 380V 4 Code
Motor power
kW
environment exceed those of similar product made by
Input volt Code 0055 5.5
other companies, which improves the product’s reliability 3-phase T
0075 7.5
0110 11
noticeably; 0150 15
0185 18.5
EV2000 has integrated the general requirements, 0220 22
0300 30
customized requirements and industrial requirements 0370 37
0450 45
perfectly. It is a innovative product with practical PI, 0550 55
simple PLC, flexible input and output terminals, pulse 0750 75
0900 90
signal input, saving parameters at stop or power outage, 1100 110
1320 132
master/slave reference control, traverse operation, fixed 1600 160
2000 200
length control. It provides OEM customers with high 2200 220
integrated, reliable, cost-effective solution; 2800 280
drive are in accordance with your order. Fig. A-2 Nameplate Description
Our product is manufactured and packed at factory with
great care. If there is any error, please contact us or
distributors.
The user manual is subject to change without notifying Barcode
Nameplate
Chapter 1 Safety
·Don’t operate the drive with wet hands EV2000 series drives are voltage type variable speed
drive. The output voltage is in PWM wave with some
·Perform the maintenance job after confirming that
harmonics. Therefore, temperature rise, noise and
the charging LED is off or the DC Bus voltage is
vibration of motor are higher.
below 36V.
Low Speed Rotating with Constant Torque
·Only trained professionals can change the
components, it is prohibited to leave wires or metal Driving a common motor at low speed for a long time,
parts inside the drive so as to avoid the risk of fire. the drive’s life will be reduced due to the deteriorating
·Parameter settings of the control board that has heat dissipation effect, so a special variable frequency
motor is needed if long time operation with constant
been changed must be revised, otherwise accidents
torque is required.
may occur.
·The bare portions of the power cables must be bound Motor’s over-temperature protecting threshold
with insulation tapes. The drive can protect the motor from over-temperature.
If the ratings of the driven motor are not in compliance
with the drive, be sure to adjust the protective threshold 1.3.2 About Variable Speed Drive
to ensure the motor is properly protected.
Varistors or Capacitors Used to Improve the Power
Operate above 50Hz
Factor
When running the motor above 50Hz, there will be Don't connect any varistor or capacitor to the output
increase in vibration and noise. The rate at which the terminals of the drive, because the drive's output voltage
torque is available from the motor is inversely waveform is pulse wave, otherwise tripping or damaging
proportional to its increase in running speed. Ensure that of components may occur; in addition, don't install circuit
the motor can still provide sufficient torque to the load. breaker or contactor at the output side of the drive as
Lubrication of mechanical devices shown in Fig.1-2.
Over time, the lubricants in mechanical devices, such as
U
gear box, geared motor, etc. when running at low speed, EV2000
V M
will deteriorate. Frequent maintenance is recommended.
W
Braking Torque
Braking torque is developed in the machine when the
drive is hoisting a load down. The drive will trip when it
cannot cope with dissipating the regenerative energy of
the load. Therefore, a braking unit with proper
parameters setting in the drive is required.
Fig. 1-2 Capacitors are prohiBited to be used.
The mechanical resonance point of load
Circuit breakers connected to the output of the drive
The drive system may encounter mechanical resonance
with the load when operating within certain band of If circuit breaker or contactor needs to be connected
output frequency. Skip frequencies have been set to between the drive and the motor, be sure to operate
avoid it. these circuit breakers or contactor when the drive has
no output, to avoid damaging of the drive.
The drive should be started and stopped via its control
terminals. It is prohibited to start and stop the drive Using outside the range of rated voltage
directly through input line contactors, which may The drive is not suitable to be used out of the specified
damage the drive with frequent operations. range of operation voltage. If needed, please use
Insulation of Motors suitable voltage regulation device.
Before using the drive, the insulation of the motors must Change from 3-phase to 2-phase
be checked, especially, if it is used for the first time or if It is not recommended to change the drive from 3-phase
it has been stored for a long time. This is to reduce the input to 2-phase input. If it is necessary to use on two
risk of the Drive from being damaged by the poor phases, the phase-loss protection function of the drive
insulation of the motor. Wiring diagram is shown in Fig. should be disabled. The Drive must be derated for this
1-1. Please use 500V insulation tester to measure the operation. For motors at which power is above 30kW, if
insulating resistance. It should not be less than 5MΩ. it is changed into 2-phase input, then the input phases
must be at phase R and phase T, or else the drive will
not work.
After the 3-phase input is changed into 2-phase input,
Motor bus-voltage and current ripple may increase, which not
only influences the life of electrolytic capacitor but it also
deteriorates the performance of the drive. The drive’s
operating current should be derated and should not
Mega-Ohm-Meter exceed 67% of rated value.
Earthing
conductor Harmonic radiation
Fig. 1-1 Checking the insulation of motor The product is not intended to be connected to
low-voltage systems interfacing with the public supply at
the low-voltage level, but to be connected to low-voltage
systems interfacing with the public supply only at the 1.4 Disposing Unwanted Drive
medium- or high-voltage level.
Protection against lightning strike When disposing the Drive, pay attention to the following
factors:
There are transient surge suppressors inside the Drive
which protects it against lighting strike. The capacitors may explode when they are burnt.
Poisonous gas may be generated when the plastic parts
Derating due to Altitude
like front covers are burnt.
Derating must be considered when the drive is installed
Disposing method: Please dispose the Drive as
at high altitude, greater than 1000m. This is because the
industrial waste.
cooling effect of Drive is deteriorated due to the thin air,
as shown in Fig.1-3 that indicates the relationship
between the elevation and rated current of the Drive.
Iout
100%
90%
80%
1000 2000 3000 4000 (m)
2.1 Specifications
Frequency 0Hz~650Hz
Output Type G: 150% rated current for 1 minute, 200% rated current for 0.5
second;
Over load ability Type P: 110% rated current for 1 minute, 150% rated current for 1
second
Item Description
2.2.1 Ratings
Notes:
1. Models in shady area are under development.
2. Please contact the manufacturer for models of EV2000-4T2800G and EV2000-4T3150P.
Cover
1. Outline
EV2000-4T0150G/0185P EV2000-4T0220G1/0300P1
2. Mechanical parameters
Table 2-4 Mechanical parameters 1
EV2000-4T0055G/0075P~EV2000-4T0450G1/0550P1、EV2000-4T0550G、EV2000-4T0750G、EV2000-4T0750P、
EV2000-4T0900P、EV2000-4T0900G、EV2000-4T1100P
Diameter of
Drive model (55P or below) Motor A B H W D Fig. Gross
mounting
(G: constant torque, P: Fan & pump) (kW) (mm) (mm) (mm) (mm) (mm) Number weight(kg)
hole(mm)
EV2000-4T0055G/0075P 5.5/7.5
186 285 300 200 202 6.8 Fig. a 7.5
EV2000-4T0075G/0110P 7.5/11
EV2000-4T0110G/0150P 11/15
236 365 380 250 209 6.8 Fig. a 12
EV2000-4T0150G/0185P 15/18.5
EV2000-4T0185G1/0220P1 18.5/22 13
180 421 435 275 209 7 Fig. b
EV2000-4T0220G1/0300P1 22/30 15
EV2000-4T0300G1/0370P1 30/37
250 600 624 375 262 9 Fig. b 35
EV2000-4T0370G1/0450P1 37/45
EV2000-4T0450G1/0550P1 45/55 38
EV2000-4T0550G _ 55 300 747 770 468 301 10 Fig. d 50
EV2000-4T0750G EV2000-4T0750P 75 300 747 770 468 301 10 Fig. d 50
EV2000-4T0900G EV2000-4T0900P 90 300 747 770 468 301 10 Fig. d 90
EV2000-4T1100P 110 300 747 770 468 301 10 Fig. d 90
Notes:
1. Models in Table 2-5 are under developing.
2. For 75kWG drive or above, DC reactor is included in its standard configuration. The weight of DC reactor in the above table is
not included in the gross weight. Outline and dimensions of DC reactor are shown below.
Diameter of terminal
Notes:
1. Columns B and C in Table 2-6 are the sizes of mounting holes of DC reactor.
2. DC reactor should be installed at the bottom of the cabinet if it is to be installed inside a cabinet. The clearance between reactor
and the drive should be at least 35cm, and the reactor should be as far away from the air inlet port of the drive as possible.
All the optional parts are given below, make additional 1. Braking kit
orders if needed. TDB 4C01 0150
Braking Motor
2.3.1 LCD Operational Panel kit
Code power
220V 2
Model:TDP-LCD03 Volt Code 380V 4
220V 2 660V 6
Language: Chinese/English optional 380V 4
660V 6 Braking unit
LCD operation panel can perform fast parameter copy.
Interface: As shown in Fig. 2-5, the interface is divided
Fig. 2-6 Model of braking kit
into main display area, operation instruction area and
explanations for operation instructions. 2. Braking resistor
Main display area: Display the status, parameters. TDB R01 0015 0400
Operation display area: Display the next operation, if Braking
Code Resistor
there are several operations for selection, the operation Kit
0400 2
contents will be displayed in this area one by one. Braking 0200 4
resistor 0100 6
Explanations for operations: Display the explanations for
the “operation display area” Power Code
1.5kW 0015
3.0kW 0030
Freq. Set Mode Main display area 5.0kW 0050
E/D Parameter Operation display area Fig. 2-7 Explanations of Model of braking resistor
3. Configurations
Table 2-7 Specifications of braking kit and resistor
Ratio of working time of Maximum
Rated motor Model of braking Braking Model of braking
braking kit to drive’s total continuous
power(kW) resistor torque (%) kit
working time (%) operating time(s)
5.5 - 10 100 10 Built-in
7.5 - 10 100 10 Built-in
11 TDB-R01-0015-0400 10 100 10 TDB-4C01-0150
15 TDB-R01-0015-0400 10 100 10 TDB-4C01-0150
18.5 TDB-R01-0015-0400 10 100 10 TDB-4C01-0150
22 TDB-R01-0030-0200 10 100 10 TDB-4C01-0300
30 TDB-R01-0030-0200 10 100 10 TDB-4C01-0300
37 TDB-R01-0030-0200 10 100 10 TDB-4C01-0300
45 TDB-R01-0050-0100 10 100 10 TDB-4C01-0550
55 TDB-R01-0050-0100 10 100 10 TDB-4C01-0550
75 TDB-R01-0050-0100 10 100 10 TDB-4C01-0550
Notes
1. There is a braking kit inside the 7.5kW drive or below. An external braking resistor is needed to be connected if dynamic
braking is required and the recommended resistor is 1000W/100Ω.
2. The 90kW drive or above should use several braking kits connected in parallel (TDB-4C01-0550).
5cm 5cm
or or Fig. 3-3 Installation of several drives
above above
snapper with your middle finger. Then press the panel ②Insert the top clamp into the slot at the top of the
inward to snap it in position as shown in Figure 3-4. drive;
③Mount the screws at the bottom part of the cover;
④Install the operation panel
Note:
Pull out or insert the plastic cover gently, otherwise the
mounting clamp may be damaged.
2. Procedures of removing and mounting the metal
cover
3
1) Procedures of removing the metal cover:
2 ①Remove the operational panel;
②Remove all the screws on the cover;
Fig. 3-4 Removing and Mounting of Operation Panel ③Take out the cover horizontally.
Where: 1&2: holding clamp 3:panel 2) Procedures of installing the metal cover:
1) Removing:
①Tilt the cover 5~10 degree; Fig. 3-6 Removing and mounting metal cover
Circuit breaker or
fuse
! Attention AC input reactor
Input Main circuit Control circuit capacity of the drive is above 550KVA, or if the input AC
switch (mm2) (mm2) supply capacity is 10 times that of the drive, a DC reactor
Model
Circuit is required to connect to the drive.
EV2000-4T Input Output Control
breaker
cable cable terminal (5) Input AC Line Reactor
QF(A)
0075G/0110P 40 6 6 1 A line reactor should be used if the distortion of power
0110G/0150P 63 6 6 1 network is severe or the input current harmonic level is
0150G/0185P 63 6 6 1 high even after a DC reactor has been connected to the
drive. It can also be used to improve the AC input power
0185G/0220P 100 10 10 1
factor of the drive.
0220G/0300P 100 16 16 1
6) Output AC Line Reactor
0300G/0370P 125 25 25 1
When the cables from the drive to motor are longer than
0370G/0450P 160 25 25 1
80m, multi-stranded cables and an AC line reactor should
0450G/0550P 200 35 35 1 be used to suppress the high frequency harmonics. Thus,
0550G 200 35 35 1 the motor insulation is protected against heat due to
0750G 0750P 250 70 70 1 harmonics, leakage current is reduced and the drive will
0900G 0900P 315 70 70 1 not trip frequently.
1100G 1100P 400 95 95 1 (7) Input EMI filter
1320G 1320P 400 150 150 1 An EMI filter can be used to suppress the high frequency
1600G 1600P 630 185 185 1 noise generated by the drive’s power cables.
2200G 2200P 800 150×2 150×2 1 An EMI filter can be used to suppress the drive’s output
noise and leakage current of cables.
2800P 1000 185×2 185×2 1
(9) Safety ground
Note: Since there is leakage current inside the drive, to ensue
1, Parameters in the table are recommended values. safety, both the drive and the motor should be grounded,
2, The input protection fuses of inverters EV2000-4T0185G1/ the grounding resistance should be less than 10Ω. The
0220P1 and EV2000-4T0220G1/ 0300P1 are respectively the ground wire should be as short as possible. Please refer
RT16 Series 63A and 80A products of Xi'an Fusegear to the section of the earth wire in Table 3-2.
Manufacture Company. Table 3-2 Section of Ground Wire
4). DC reactor Min. section of ground
Cable Section (mm2)
DC reactor is required for the drive whose power is wire Sp(mm2)
greater than EV2000-4T0750G, for the drive whose S≤16 S
power is lower than EV2000-4T0750P, it is optional. 16<S≤35 16
35<S S/2
Under following conditions, a DC reactor should be used
Note that the data in the above table apply when the
to reduce the impact of AC supply to the drive and to
conductor connected with the ground wire are made of
protect the drive and suppress the high-order harmonics.
the same metal, otherwise, please calculate the
(1) If a capacitor tank used for reactive power
equivalent section based on the conductivity.
compensation or a SCR load shares the same AC supply
with the drive, the harmonics caused by the SCR load or Notes:
the capacitor tank when it is switched on or off may 1. EV2000 drive can meet the requirements of IEC 61800-3
damage the drive’s input rectifying circuit; after EMI filter is installed.
(2) When the unbalance rate of 3-phase AC supply of the 2. Installation of input and output EMI filters must be as close
drive is greater than 3%; to the drive as possible. Refer to Section 3.4 of Chapter 3 for
(3) If the input power factor of the drive is required to be EMC installation instructions.
greater than 0.93; 3. Refer to Section 2.3 of Chapter 2 and Appendix 2 for the
(4) When a large capacity transformer is connected to the technical parameters of optional parts.
drive, the input current of the drive may damage the
rectifying circuit. Generally, if the input AC supply
VCI TA
0~10V/0~20mA . TB Programmable
CCI . I
. TC relay output
GND V
CN10 485+ RS485
PE communication port
485-
RS232 .
. TXD
RS485 . RS232
RXD
CN14 GND communication
port
Notes:
1. Terminal CCI can be input voltage or current signal by switching the jumper CN10 on control board;
2. The auxiliary power supply comes from the bus (+) and bus (-);
3. Built-in braking kit is installed and a braking resistor is required to be connected between (+) and PB;
4. In the above figure, “O” is the terminal in main circuit, and “⊙” is the control terminal;
5. Refer to section 3.3.2 for the using of control terminals.
Braking resistor
DCL DC reactor or braking unit
(connect externally,optional
parts for 75kW or below) P P (Connect optional parts
N PB externally)
P1 (+) (-)
Breaker
R U
3-phase R
S V
380V S W
M
T
50/60Hz T PE
R0
Aux.
Power P24
P24
supply COM
PG
PLC T0 X7
X8
Forward/stop
FWD PE
Reverse/stop
REV 0/4~20mA GND
. DC current
Multi-function input1 0~10V .
X1 . AO1 meter
Multi-function input2
X2 CN16 0/4-20mA current
Multi-function input3 . AO2
X3 0/4~20mA . signal
Multi-function input4 . P24
X4 0~10V Output 0-24V pulse
Multi-function input5
X5 CN17 DO signal
Multi-function input6 COM Frequency meter
X6
Multi-function input7
X7 Y1 Output 1 Bi-direction open
Multi-function input8
X8 collector output
COM EV2000 Y2 Output 2
Speed command CME
0~10V Common terminal
VRF COM
VCI TA
0~10V/0~20mA . Programmable
CCI .. I TB
relay output
GND V TC
CN10 485+
RS485
PE 485- communication port
.
RS232 .
TXD
RS485 . RS232
RXD communication
CN14 GND port
Notes:
1. Terminal CCI can be input voltage or current signal by switching the jumper CN10 on control board;
2. The auxiliary power supply’s AC supply comes from R0 and T0 which are shorted with R and T of 3-phase input. If you want
to use an external AC supply, the shorting bars between R and R0, T and T0 have to be removed before connecting the external
AC supply via R0 and T0. Otherwise, short-circuit will occur.
3. It is prohibited to connect to the control power supply without disconnecting the short-circuit bar, so as to avoid short-circuit
accident;
4. If external braking parts are needed, then braking kit and braking resistors should be included; Pay attention to the polarity of
the braking kit when wiring;
5. In the above figure, “O” is the terminal in main circuit, and “⊙” is the control terminal;
6. Refer to section 3.3.2 for the using of control terminals.
Auxiliary
R0 power
P24 P24
T0 supply COM
PG
PLC X7
X8
Foward/Stop
FWD PE
Reverse/Stop
REV GND
0/4-20mA .
MS input 1 .
AO1
X1 0-10V . DC current meter
MS input 2
X2 CN16
MS input 3 AO2 0/4-20mA current signal
MS input 4 X3 0/4-20mA ..
X4 0-10V . P24 frequency meter (open collector output)
MS input 5
X5 CN17
MS input 6 DO
X6 0-24V pulse output signal
MS input 7 COM
X7
MS input 8 EV2000
X8 Y1 output 1
2-way open collector output
COM Y2 output 2
Speed instruction CME
VRF COM common terminal
0~10V
VCI TA
0~10V/0~20mA .
CCI . I TB Programmable relay output
. V
GND TC
CN10 485+
PE 485- Standard RS485 port
RS232 .
. TXD
RS485 . RXD
Standard RS232 port
CN14 GND
Notes:
1. Terminal CCI can be input voltage or current signal by switching the jumper CN10 on control board;
2. The auxiliary power supply of EV2000-4T0185G1/0220P1~EV2000-4T0220G1/0300P1 is from bus (+) and (-)。
3. The auxiliary power supply of EV2000-4T0300G1/0370P1~EV2000-4T0450G1/0550P1 is from R and T. If you want to use
an external AC supply, the jumper on CN4 should be connected to CN3 first, and then connect it to R0 and T0.
4. If external braking kit, the braking unit and braking resistors should be included; Pay attention to the polarity of the braking kit
when wiring;
5. In the above figure, “O” is the terminal in main circuit, and “⊙” is the control terminal;
6. Refer to section 3.3.2 for the usage of control terminals.
Notes:
Table 3-6 Terminals of main circuit
Terminals PB of EV2000-4T0110G/0150P and
EV2000-4T0150G/0185P are suspended. Terminals Function
3-phase 380V AC supply input
2) Applicable models: R. S. T
terminals
EV2000-4T0185G/0220P~EV2000-4T0450G/0550P
P1. (+) Reserved terminals for DC reactor
R S T P P1 (+) (-) U V W PE (-) Output terminal for DC Minus Bus
POWER SUPPLY MOTOR U. V. W 3-phase AC output terminals
Table 3-4 Terminals of main circuit PE Earth terminal
Terminals Function
3-phase 380V AC supply input 3.3.2 Wiring of Control Circuit
R. S. T
terminals
P Positive pole of the rectifying bridge 1. Terminals and jumpers of control board
Reserved terminals for DC reactor, Locations of terminals CN5, CN6 and CN7 and jumpers
P1, (+) connected by copper bar before CN10, CN14, CN16 and CN17 are shown in Fig. 3-.
delivery
Terminal functions are given in Table 3-6. Refer to table
(-) Output terminal for DC Minus Bus
3-7 for the functions and settings of jumpers. Wire the
U. V. W 3-phase AC output terminals terminals and set the jumpers correctly before using the
PE Earth terminal Drive. It is recommended to use cables bigger than
3) Applicable models: 1mm2 to connect to the terminals.
EV2000-4T0550G. EV2000-4T0750P
Top:
(-) (+) P1 R S T
POWER SUPPLY
Bottom: U V W PE
MOTOR
CN1 CN2
CN7
Table 3-7 Functions of terminals provided to users
SN Function
CN3 Analog input and output terminal, RS232 and
CN5
RSRS485 communication port
CN6 Digital input/output terminal
CN7 Relay output terminal
CN4
Table 3-8 Functions of jumpers provided to users
CN6 DSP
Factory
SN Function and settings
CN9 settings
mA
CN16 Used for selecting CCI current/voltage
V
mA input
CN17 CN10 0~10V
V I: 0/4~20mA current signal,
232
CN14
485 V: 0~10V voltage signal
I
CN10 Used for selecting communication
CN5 V
ports (RS232 or RS485)
CN14 RS485
RS232: Select RS232 port,
Fig. 3-12 Locations of jumpers on the control board RS485: Select RSRS485 port
Used for selecting the output signal
(current or voltage) of analog output
CN16 terminal AO1; 0~10V
0/4~20mA: AO1 output current signal;
0~10V: A01 output voltage signal
Used for selecting the output signal
(current or voltage) of analog output
CN17 terminal AO2; 0~10V
0/4~20mA: AO2 output current signal;
0~10V: AO2 output voltage signal
●
VRF(+10V)
●
VCI EV2000
0~+10V
●
GND
PE
Nearer shielding wire's end is ●
connected to PE
②CCI can accept analog signal input and the jumper can be used to select voltage input (0~10V) and current input
(0/4~20mA). The wiring is shown below:
CCI current
● VRF(+10V) I
· · ·
V
●
CCI CCI voltage
0~+10V
or 0/4~20mA
EV2000
●
GND PE I
· · ·
Nearer shielding wire's ●
V
end that is connected to
the PE CN10
0-10V
EV2000 AO2 ●
Anlog voltage
output
GND ●
0/4-20mA
· · ·
0-10V
AO1:CN16;AO2:CN17
Notes:
(1) When using analog input, a common mode inductor can be installed between VCI and GND or CCI and GND.
(2) Analog input and output signals are easily disturbed by noise, so shielded cables must be used to transmit these signals and
the cable length should be as short as possible.
3. Wiring of Serial Communication Port
Wire connections of serial communication port.
EV2000 drive provides two kinds of serial ports: RS232 and RS485 which can be selected by Jumper CN14.
Wire as following figures show, and a “single-master single slave” system or a “single-master multi-slaves” system can
be formed. The drives in the network can be monitored and controlled remotely and automatically in real time by using a
PC or PLC controller. Thus more complicated operation control can be realized (e.g. Unlimited multi-step PLC
operation).
① The drive connects to the host via its RS232 port:
Control PC
EV2000
RS232(DB9)
RS232 port Shielded Signal Pin
cable
Function Terminal ●
PE Enclosure
Transmit TXD
RXD 2
Receive RXD
TXD 3
GND GND
GND 5
The kilobit of FF.00 DTR 4
is set to 0 ●
DSR 6
RS232
···
RI 9
RS485 CD 1
●
CN14 RTS 7
CTS 8
② Connection between the drive’s RS485 port and the host PC:
Control PC
RS232(DB9)
RS485/RS232 converter
EV2000 Shielded
Function Terminal Signal Pin
RS485 port cable
5V power +5V ●
PE Enclosure
···
RS232
CD 1
RS485
RTS 7
CN14
CTS 8
④The drive’s RS485 port connects to PROFIBUS via the TDS-PA01(field bus made by ENPC):
EV2000 TDS-PA01
RS485 port fieldbus
Connect to
Func Terminal Func Terminal PROFIBUS
Twisted
signal-Func RS485- RS485- A
cable
signal+ Func RS485+ RS485+ B
··· RS232
Be able to connect
RS485 1-32 RS485
CN14
EV2000 TDS-PA01
TD3000 TDS-PA01
If several drives are connected in the network via RS485, the disturbance to the communication system increases, so
the wiring is especially important, you can connect the cables according to the figure below:
Fig. 3-21 Communication between PLC and the drive (the drive and motor are grounded well)
If the communication is still abnormal, then the following actions can be taken:
① Feed a separate AC supply to the PLC(or host PC) and isolate the AC supply;
② If RS485/RS232 conversion module is used, then the module should be powered by a separate power supply;
③ Mount magnetic core to the communication cable, reduce the carrier frequency if the field conditions permit.
2). Description of control terminals CN6 and CN7
Layout of CN6:
P24 Y1 Y2 CME COM DO P24 PLC X1 X2 X3 X4 COM X5 X6 FWD REV COM X7 X8 PE
Layout of CN7:
TA TB TC
Multi -function input See section 5.8 Chapter 8 for the PLC +5V
X3
terminal 3 programmable multi-function digital
Multi -function input input terminal R
X4 Xi、FWD、REV
terminal 4 (Common terminal: PLC)
Multi- COM
Multi -function input
function X5
terminal 5
input
Multi -function input
terminal X6
terminal 6
Equivalent circuit of optical-
Multi -function input Terminals X7 and X8 can be used as
X7 isolator input is shown above.
terminal 7 common multi-function terminals
input resistance: R=2kΩ
(same with X1~X6), they can also be
Max input frequency: 100kHz
used as high speed pulse input port.
Multi -function input (single phase)/50kHz (dual
X8 See section 5.8 Chapter 8 for details.
terminal 8 phase)
(Common terminal: PLC)
Input voltage range: 15~30V
Optical-isolator output
Open collector output
Y1 Multi-function digital output terminal Operating voltage range:9~30V
Multi-functi terminal 1
can be defined. See section 5.8 Max output current: 50mA
on output
Chapter 5 for details. (Common Refer to the explanations of
terminal Open collector output
Y2 terminal: CME) F7.10~F7.11 for the using
terminal 2
methods.
Multi-function pulse signal output
Multi-functi Output frequency range:
Open collector pulse terminal can be defined. See section
on output DO dependent on F7.32, and the
output terminal 5.8 Chapter 5 for details. (Reference
terminal Max frequency is 50kHz
ground: COM)
TA-TB: normally closed,
TA
TA-TC: normally open
Capacity of contacts:
TB AC250V/2A(COSΦ=1)
Relay’s Multi-function relay output terminal
AC250V/1A(COSΦ
output Output terminals of relay can be defined. See section 5.8
=0.4),DC30V/1A
terminals Chapter 5 for details.
Refer to the explanations of
TC F7.12 for the using methods.
Overvolt class of the input volt
at relay output terminal: II.
R COM 24V DC 5V
- -
●
PLC
K X1、X2 . . . X8
●
FWD、REV 1 ● ●
FWD
COM EV2000
COM 5V
External controller EV2000 -
●
PLC
9~30V
●
●
COM P24 D2 +
●
+ FWD
● ●
COM 24V DC 5V 1 ●
- ●
-
●
●
PLC
●
1 ● ●
FWD
5V
5V 10 X8
● ●
PE
10 ● ●
X8 ●
shielded cable's end near the drive Fig. 3-27 Method 2 of connections (d)
should be connected to the PE
COM 24V DC
●
- P24 R
PLC
9~30V ●
●
+
1 - FWD
● ●
+5V Relay
Y1,Y2
5V
CME
10 ● ●
X8
PE
EV2000 COM
●
+24V
P24
+5V DC 9~ 30V
Y1,Y2
+ -
Relay
CME
EV2000 COM
3) Wiring relay output terminals TA, TB and TC. ESD induction Ttransmission noise Electro-magnetic
Conduction noise
Noise in space induction noise
If the drive drives an inductive load (such as relay or
...
...
Route①
contactor), then a surge suppressing circuit should be Route ⑦,⑧
Route② Route③
free-wheeling diode (used in the DC electric-magnetic Radiation Radiation
Radiation noise noise noise
circuit and pay attention to the polarity during of motor of power of power
cables cables
...
...
Route④ Route⑤
to the coils of relay or contactor as possible. Route⑥
>30cm >50cm
Other
Drive equipment
Power cable
PE
>20cm
Signal/Control cable
Signal/Control cable
Other
Fig. 3-34 Wire connections Drive equipment
Generally, the control cables should be shielded cables
PE
and the shielding metal net must be connected to the
metal enclosure of the drive by cable clamps.
PE PE
enclosure enclosure
Other
Drive equipment
Fig. 3-35 Correct shielding method of shielding layer
PE(G)
PE
PE
enclosure enclosure
Fig. 3-40 Earthing diagram 4
Fig. 3-36 Incorrect earthing method of shielding layer
Besides, pay attention to the following points:
In order to reduce the earthing resistance, flat cable
3.4.3 Earthing should be used because the high frequency impedance
of flat cable is smaller than that of round cable with the
Independent earthing poles (best) same CSA.
For 4-core motor cable, the end of one cable should be
Drive Other
equipment connected to the PE of the drive, and the other end
should be connected to the motor’s enclosure. If the
PE motor and the drive each has its own earthing pole, then
the earthing effect is better.
If the earthing poles of different equipment in one
system are connected together, then the leakage current
Fig. 3-37 Earthing diagram 1 will be a noise source that may disturb the whole system.
Therefore, the drive’s earthing pole should be separated
with the earthing pole of other equipment such as audio
equipment, sensors and PC, etc.
In order to reduce the high frequency impedance, the
bolts used for fixing the equipment can be used as the
high frequency terminal. The paints on the bolt should and relays falsely activated. The higher the drive’s
be cleaned. carrier wave frequency, the bigger the leakage current,
The earthing cable should be as short as possible, that also, the longer the motor cable, the greater the leakage
is, the earthing point should be as close to the drive as current,
possible. Suppressing methods:
Earthing cables should be as far away from the I/O Reduce the carrier wave frequency, but the motor noise
cables of the equipment that is sensitive to noise, and may be louder;
also should be as short as possible. Motor cables should be as short as possible;
The drive and other equipment should use leakage
3.4.4 Installation Requirements of Relay, Contactor and
current circuit breaker designed for protecting the
Electro-magnetic Braking Kit product against high-order harmonics/surge leakage
current;
The devices such as relay, contactor and
electro-magnetic braking kit, which may generate great Leakage current between lines
noises, should be installed outside of the drive cabinet The line leakage current flowing through the distribution
and should be installed with surge suppressors. capacitors of the drive out side may cause the thermal
relay falsely activated, especially for the drive whose
Varistor
power is lower than 7.5kW. When the cable is longer
220VAC than 50m, the ratio of leakage current to motor rated
current may be increased that can cause the wrong
Diode action of external thermal relay very easily.
Inverter
+24VDC Suppressing methods:
Reduce the carrier wave frequency, but the motor noise
RC-Filter
may become louder;
Install reactor at the output side of the drive.
220VAC
In order to protect the motor reliably, it is recommended
to use a temperature sensor to detect the motor’s
Fig. 3-41 Relay, contactor and electro-magnetic braking kit
temperature, and use the drive’s over-load protection
device(electronic thermal relay) instead of an external
3.4.5 Leakage Current thermal relay.
Mains
Electrical installation of the drive
Area Ⅴ
Electric cabinet
Input filter
10kV
Power
Area Ⅰ transformer
Area Ⅲ
Control
equipment Input reactor
Isolation Power
(Such as: PC) transformer source
>20cm cable of
Area Ⅱ Inverter Manufacturing inverter
mechanics Power
source cable Filter
of meters
Sensor(such as: Motor Mechanical Circuit breaker
Area Ⅳ
system >30cm
temperature, position, Linear noise
pressure) filter Area Ⅵ AC input reactor
PLC or
Earthing Metal Metal
meters
separation cabinet cabinet
board
Motor cables
Inverter
Detecting signal cable
Control cable
Fig. 3-43 Recommendation of Installation space
Motor cable
Attention: >50cm
AC Output
reactor
· Area Ⅰshould be used to install transformers of
control power supply, control system and sensor. Motor
It can prevent the EMI generated by equipment from the case, the earthing is useless for high frequency
entering the power cable, and prevent the EMI interference. When the frequency is high, so is the
generated by power cable from entering equipment. impedance of cable, hence there is little bypass effect.
Common mistakes in using power cable filter The filter should be mounted on the enclosure of
equipment. Ensure to clear away the insulation paint
1. Too long power cable
between the filter case and the enclosure for good
The filter inside the cabinet should be located near to earthing contact.
the input power source. The length of the power cables
should be as short as possible. 3.4.8 EMI of The Drive
2. The input and output cables of the AC supply filter are
too close The drive’s operating theory decides that its EMI is
The distance between input and output cables of the unavoidable.
filter should be as far apart as possible, otherwise the The drive is usually installed in a metal cabinet, the
high frequency noise may be coupled between the instruments outside the metal cabinet is disturbed by the
cables and bypass the filter. Thus, the filter will become drive lightly. The cables are the main EMI source, if you
ineffective. connect the cables according to the manual, the EMI
3. Bad earthing of filter can be suppressed effectively.
The filter’s enclosure must be earthed properly to the If you install the drive and other control equipment in
metal case of the drive. In order to be earthed well, one cabinet, the area rule must be observed. Pay
make use of a special earthing terminal on the filter’s attention to the isolation between different area, cable
enclosure. If you use one cable to connect the filter to layout and shielding.
It defines the physical channels by which drive receives Preset frequency: the sum of main and auxiliary
operating commands like START, STOP, FWD, REV, frequency multiply a factor, which is set in F9.05 and
JOG and others. F9.06. Please refer to F9.05, F9.06 and Fig. 5-59 in
chapter 5.
Panel control: The drive is controlled by RUN, STOP
and JOG keys on the operation panel;
4.1.3 Operating Status
Terminal control: The drive is controlled by terminals
FWD, REV and COM (2-wire mode), or by terminal Xi There are 3 operating status: stopping, motor
(3-wire mode); parameters auto-tuning, and operating.
Host control: The operations such as START and STOP Stopping status: After the drive is switched on and
can be controlled by host PC. initialized, if no operating command is accepted or the
The control modes can be selected by parameter F0.03, stopping command is executed, then the drive enters
PANEL/REMOTE key and ENTER/DATA key on the stopping status.
operation panel and multi-function input terminal (No.27, Operating status: The drive enters operating status after
28 and 29 can be selected by F7.00~F7.07). it receives the operating command.
F5). Close-loop operating function can be disabled by a Multi-step (MS) speed operation:
multi-function terminal (No.20 function), and the drive Select MS frequency 1~7(F3.23~F3.29,F7.00~F7.07) to
will select an operating mode with a low priority. start MS speed operation by the ON/OFF combinations
PLC operation: of the multi-function terminals (No.1, 2, and 3), if none of
If PLC function is enabled (ones place of F4.00 is set to the terminals are “OFF”..
a non-zero value), the drive will select PLC operating Simple operation:
mode and will operate in the pre-defined operating mode Simple operation is actually the open-loop operation
(see explanation of parameter F4). The PLC function mode.
can be disabled by a multi-function terminal (No. 21 EV2000 operating status is shown in Fig. 4-1:
function), and the drive will select an operating mode of
lower priority.
Start up
Stop
Y Jog operation
High priority Jog ?
N
N
Run command active
Y
Close-loop setting Y
active (F5.00>0)?
Y Run at preset
Preset freq.enabled
frequence
N
Low priority
Common
operation
Five operating modes provide 5 basic frequency sources. Except the Jog operating frequency, other 4 kinds of
frequency sources can be superposed by the auxiliary frequency to tune the final output frequency. In PLC, MS and
common mode, the reference frequency can be used as traverse frequency.
The operation panel is used to setup the drive and display parameters. There are two types of operation panels, one
with LED display and the other, LCD display. The LED display is the standard operation panel. The LCD operation
panel is an optional accessory. It can display in English and Chinese characters, with description for the displayed data.
The outlines, dimensions and operating methods of these two types of operation panels are the same, as shown in
Fig.4-2.
PARAMETER
UNIT
Frequency unit:Hz
HZ
r/min
Rotating speed:r/min
4-bit LED
.
A %
m/s
Current unit:A
Line speed:m/s
V
Voltage unit:V
LCD display 补偿前频率
Freq. before compensation
普通运行
RUN 正
FWD Enter
Program Data input
Control mode indicator
MENU ENTER PANEL
ESC DATA REMOTE
▲
▲
Move ▲ JOG Jog
Running Indicator
Stop
▲ STOP
RUN
RUN RESET
RESET
Run Reset
Increase/Decrease
! Attention
Operation panel of EV2000 is not compatible with the panel of other Emerson variable speed drives.
Notes:
4.2.2 Function of Keys
Functions of RUN, JOG, STOP/RESET and
There are 9 keys on the operation panel of the drive and PANEL/REMOTE are also limited by F9.07.
the functions of each key is shown in Table 4-1.
Table 4-1 Function of operation panel 4.2.3 Function Descriptions of LED and Indicators
Key Name Function
Program/ Enter or exit programming The operation panel consists of a 4-digit seven
MENU/ESC segments display, 3 LED indicators that indicate unit
exit status
and 2 status indicators as shown in Fig. 4-3. The seven
Function/ Enter lower level menu or
ENTER/DATA segments can display the status parameters,
data confirm data
parameters and fault codes of the drive. These 3 unit
▲ Increase Increase data or parameter
indicators have 7 different combinations and each
▼ Decrease Decrease data or parameter
combination corresponds to one type of unit. The
In editing status, pressing relationship between the combination of the indicators
this key select the Bit to be and the unit is shown in Fig. 4-3:
XX Shift modified. In other status, this UNIT UNIT UNIT UNIT UNIT UNIT UNIT
Hz
key is used to scroll through Hz Hz Hz Hz Hz Hz
Table 4-2 Functions of status indicators commands via the control terminal X2 or serial port. The
Display Current status of the fault code will not disappear until the fault is cleared.
Indicator
status drive
PARAMETER UNIT
Operating status Off Stopping status HZ
Hz
r/min
indicator On Operating status A %
m/s
On Panel control status V
Terminal control
Control mode Off
status
indicator Input Phase Failure
Serial port control
Flash Pls Check
status
A % A % A %
m/s m/s
m/s
V V
V
▲ ▲
2. Press ▲ key until “F3” is displayed.
▲ STOP
STOP
RUN
STOP
RUN
STOP
RUN
RUN RESET RUN RESET RUN RESET
MENU ENTER Under panel control mode, press RUN key to start the
50.00 ESC F0 F3 DATA F3.00
drive and press STOP/RESET key to stop it. To switch
enter menu level 1
the control mode, please refer to the above paragraph.
XX ENTER 6. Jog
06.50
. 05.00 DATA F3.13
Save Not save enter menu level 3 enter menu level 2
When the drive is in STOP state, press JOG key and
ENTER MENU hold it, the panel will display start frequency and then
DATA ESC
the frequency will ramp to 5Hz. Keep pressing the key,
MENU MENU
F3.14 F3.13 ESC F3 ESC 50.00 the drive will jog at 5Hz.
MENU 7. Setting user’s password
ESC
F3 Enter menu level 3 and set FP.00 at a 4-digit figure as
Fig. 4-7 Setting the parameters your password. See the panel operation in Figure 4-7.
In menu level 3, the settings of the parameter cannot be 8. How to lock the panel:
changed if none digit of the parameter is flashing. The First set the hundred’s place of F9.07 at a non-zero
possible reasons are: figure, and then press MENU/ESC and ENTER/DATA at
1) The settings of this parameter cannot be changed, the same time.
such as the actual detected parameters or recorded MENU ENTER
change the settings, first set FP.01 to 0. 0120 DATA F9.08 ESC F9- 50.00
Start
N Connection is
correct?
Y
N Input volt is
correct?
Y
Switch on
Within 1s
N
Display 8.8.8.8.?
Within 2s Y
N
Contactor closes?
Within2 ~ 5s Y
Display freq.
N
setting?
Start-up fails
Y
Start-up
succeed Switch off
Check
Notes: A B C D
The values in “【】” are the factory settings. 0: Save preset freq. at power off
1: Not save preset freq. at power off
Only valid when F0.00=0, 1 or 2. 0: Panel control: Input operating commands via panel
Start and stop the drive by pressing RUN, STOP and
JOG on the panel.
1: Terminal control: Input operating commands via
terminals
Use terminals FWD, REV, JOGF and JOGR to start and 1: Type P (fan & pump load)
stop the drive. EV2000 series drive of 45kW or below uses the type G
2: Serial port control: Input commands via serial port and type P integrated mode. The power of motor
Use serial port to start and stop the drive. matched with the drive type G is lower than that of type
P. Please refer to Table 2-2 for details.
Notes
The factory setting of the drive is set to type G.
Please be careful that during operating, the control modes For example: EV2000-4T0055G/0075P drive’s factory
can be changed through F0.03 or external terminals or setting is 5.5kW type G drive. If the drive needs to be
PANEL/REMOTE key. changed to 7.5kW type P drive, then:
F0.04 Set running direction Range: 0, 1 【0】
①set this parameter to 1
This function is active in panel control mode and serial
②set group FH parameters again
port control mode, and inactive in terminal control mode.
0: Forward Note:
1: Reverse Follow the same procedures if the drive needs to be
Range: Max{50.00,F0.12 upper changed from type P to type G.
F0.05 Max output
limit of frequency}~650.00Hz F0.09 Torque boost Range:0~30.0%【0.0%】
frequency
【50.00Hz】 In order to compensate the torque drop at low frequency,
F0.06 Basic the drive can boost the voltage so as to boost the torque.
Range:1.00~650.00Hz 【50.00Hz】
operating frequency If F0.09 is set to 0, auto torque boost is enabled and if
F0.07 Max output Range:1~480V 【drive’s rating F0.09 is set non-zero, manual torque boost is enabled,
voltage values】 as shown in Fig. 5-3.
Max output frequency is the highest permissible output Output
voltage
frequency of the drive, as shown in Fig. 5-2 as fmax; Vmax
Basic operating frequency is the Min frequency when
the drive outputs the max voltage, as shown in Fig. 5-2
as fb
Max output voltage is the drive’s output voltage when Vb
Output
the drive outputs basic operating frequency, as shown in freq.
Fig. 5-2 as Vmax fz fb
Output Vb : Manual torque boost Vmax: Max output voltage
voltage
f z : Cut-off freq. for torque boost
Vmax f b : Basic operating freq.
Fig. 5-3 Torque boost(shadow area is the boosted
value)
Note:
Output
frequency
1. Wrong parameter setting can cause overheat or
fL f b f H f max over-current protection of the motor.
2. Refer to F0.21 for definition of fz.
Fig. 5-2 Characteristic parameters
3. When the drive drives a synchronous motor,torque boost
The fH and fL are defined by F0.12 and F0.13 as upper function is recommended to be used and V/F curve should
limit of frequency and lower limit of frequency be adjusted according to the motor parameters.
respectively. Range:0.1~3600s(min)【6.0s/20.0s】
F0.10 Acc time 1
Note: F0.11 Dec time 1 Range:0.1~3600s(min)【6.0s/20.0s】
Please set fmax, fb and Vmax according to motor
parameters, otherwise the equipment may be damaged.
F0.08 Drive type selection Range:0. 1【0】
0: Type G (load with constant torque)
F0.21 Cut-off point used for Positive and negative characteristics are shown in Fig.
Range:0~50%【10.0%】
manual torque boost 5-8.
F0.21 defines the ratio of the cut-off frequency used for Reference freq. Reference freq.
F1.02 Reference constant of Range:0.01~50.00s Analog input value(A) is a percentage without unit, and
filter 【0.50s】 100% corresponds to 10V or 20mA. Pulse frequency(P)
Range:0.1~50.0kHz is also a percentage without unit, and 100%
F1.03 Max input pulse frequency
【10.0kHz】 corresponds to the Max pulse frequency defined by
Range:0.0%~100.0% F1.03.
F1.04 Min reference of curve 1
【0.0%】 F1.02 defines the time constant of the filter used by the
F1.05 Frequency corresponding Range:0.0~650.0Hz reference selector. The input signal is filtered and the
to the Min reference of curve 1 【0.00Hz】 bigger the time constant, the higher the immunity level,
but the response time is prolonged with the increase of
Range:0.0%~100.0%
F1.06 Max reference of curve 1 the time constant. That is, the smaller the time constant,
【100.0%】
the shorter the response time, but the lower the
F1.07 Frequency corresponding Range:0.0~650.0Hz
immunity level.
to the Max reference of curve 1 【50.00Hz】
F1.00 is used to select the output frequency curve when
Range:0.0%~100.0% VCI, CCI or PULSE input is selected, as shown in
F1.08 Min reference of curve 2
【0.0%】 Fig.5-9.
F1.09 Frequency corresponding Range:0.0~650.0Hz
A B C D
to the Min reference of curve 2 【0.00Hz】
Range:0.0%~100.0% VCI frequency curve selection
F1.10 Max reference of curve 2 0 : Curve 1
【100.0%】
0 : Curve 2
F1.11 Frequency corresponding Range:0.0~650.0Hz
to the Max reference of curve 2 【50.00Hz】 CCI frequency curve selection
0 : Curve 1
When VCI or CCI or pulse input(PULSE) is selected, the 0 : Curve 2
relationship between reference and the preset frequency
is given below: PULSE frequency curve selection
0 : Curve 1
Ref. Filter Amplify A Set Freq. curve
selection Preset frequency 0 : Curve 2
F1.02 F1.01 P or select F1.00
F0.00
Reserved
Fig. 5-7 Relationship between reference and the preset
Fig. 5-9 Frequency curve selection
frequency
Where,
Reference frequency signal is filtered and amplified, and
then its relationship with the preset frequency is A: thousand’s place B: Hundred’s place
determined by Curve 1 or 2. Curve 1 is defined by C: Ten’s place D: Unit’s place
F1.04~F1.07, and curve 2 is defined by F1.08~F1.11. For example, the requirements are:
①Use the pulse signal input via terminal to set the Brake first(refer to F2.03 and F2.04), and then start in
reference frequency; mode 0.
②Range of input signal frequency:1kHz~20kHz; 2. Start on the fly
③1kHz input signal corresponds to 50Hz reference Search and catch the motor’s running direction and
speed, start the rotating motor smoothly without impact,
frequency, and 20kHz input signal corresponds to 5Hz
as shown in Fig. 5-11.
reference frequency;
AC supply
According to the above requirements, the parameter On OFF ON
(Group F2)
Notes: Frequency
Operating
F3.02~F3.04 Reserved
command Reserved.
Fig. 5-16 Dec-to-stop + DC injection braking F3.05 auto energy-saving function Range:0. 1【0】
0:disabled
1: enabled
When the motor operates without load or with light load, Range of slip compensation: limit of slip
the drive can adjust its output voltage by detecting the compensation(F3.08) × rated slip(FH.08)
load current to achieve the energy-saving effects.
Note:
Note:
The value of automatically compensated slip is dependent
This function is especially useful for the fan & pump loads. on the motor’s rated slip, therefore the motor’s rated slip
F3.06 AVR function Range:0. 1. 2【2】 must be set correctly (FH.08).
0:disabled F3.10 Carrier wave Range:0.7~15.0kHz【depend on
frequency drive model】
1: enabled all the time
2: disabled in Dec process Table 5-3 Drive’s type and carrier wave frequency (CWF)
AVR means automatic voltage regulation. CWF Highest Lowest Factory
The function can regulate the output voltage and make it Type (kHz) (kHz) setting (kHz)
constant. Therefore, generally AVR function should be
enabled, especially when the input voltage is higher than Type G:5.5kW~45kW
15 3 8
the rated voltage. Type P:7.5kW~55kW
Type G:55kW~90kW
In Dec-to-stop process, if AVR function is disabled, the 10 1 3
Type P:75kW~110kW
Dec time is short but the operating current is big. If AVR
function is enabled all the time, the motor decelerates Type G:110kW~220kW
6 0.7 2
steadily, the operating current is small but the Dec time Type P:132kW~280kW
is prolonged. Table 5-4 CWF characteristics
F3.07 Gain of slip CWF Decrease Increase
Range:0.0~300.0%【100.0%】
compensation Motor’s noise ↑ ↓
F3.08 Limit of slip Leakage current ↓ ↑
Range:0.0~250.0%【200.0%】
compensation
Disturbance ↓ ↑
F3.09 Compensation
Range:0.1~25.0s【2.0s】
time constant Notes:
The motor’s slip changes with the load torque, which In order to achieve better control performances, the ratio of
results in the variance of motor speed. The drive’s carrier frequency to the maximum operating frequency of
output frequency can be adjusted automatically through the drive should not be less than 36.
slip compensation according to the load torque.
F3.11 Auto adjusting of CWF Range:0. 1【1】
Therefore the change of speed due to the load change
is reduced as shown in Fig. 5-18. 0: disabled
Slip 1: enabled
When this function is enabled, the drive can adjust the
CWF automatically according to the internal temperature
Positive slip
compensation of the drive. At this time, the drive’s actual Max CWF is
restricted by F3.10.
-100%
Motor's load F3.12 Motor tone adjustment Range:0~10【0】
100%
F3.12 can be used to adjust the motor’s tone, and is
Negative slip only effective for the CWF below 6kHz.
compensation
If this parameter is set to 0, the function is disabled.
Fig. 5-18 Auto slip compensation F3.13 Jog operating Range:0.10~50.00Hz
frequency 【5.00Hz】
Motoring status: Increase the gain of slip compensation
F3.14 Interval of Jog
gradually when the actual speed is lower than the Range:0.0~100.0s【0.0s】
operation
reference speed (F3.07).
F3.15 Acc time of Jog Range:0.1~60.0s
Regenerating status: Increase the gain of slip operation 【6.0s/20.0s】
compensation gradually when the actual speed is higher
F3.16 Dec time of Jog Range:0.1~60.0s
than the reference speed (F3.07).
operation 【6.0s/20.0s】
Adjusted preset
frequency A B C D
Skip
frequency 3 Skip
PLC operating mode selection
range 3
0: No action
1: Hold final value after 1-cylce running
Skip 3: stop after single cycle
Skip
frequency 2 4: continuous operation
range 2
PLC restarting mode selection:
Skip Skip range 1 0: Restart from 1st stage
frequency 1 Preset 1: Continue to run at the frequency in the stafe
frequency when the drive stopes
2: Continue to run at the frequency when the
drive pauses
Fig. 5-20 Skip frequency and skip range
Save PLC operating parameters upon power
outage:
5.5 PLC Operating Parameters(Group F4) 0: No save
1: Save the frequency and running stage upon
power outage
Simple PLC function can enable the drive change its
operating frequency and directions automatically Unit of running time:
0: Second
according to the operating time to satisfy the 1: Minute
manufacturing requirements. Before, this function is
realized by PLC, now the drive itself can realize such Fig. 5-22 Simple PLC operation mode
function, as shown in Fig. 5-21.
Where,
Simple PLC operation
f6
d7 A: thousand’s place B: Hundred’s place
f2 a6 f7
a2 f5 C: Ten’s place D: Unit’s place
f1 d7
a1 d3 a5 Unit’s place: PLC operation mode
a3 f 3 0:disabled
a4 d5 PLC operation mode is disabled.
f4
1: Stop after single cycle
T1 T2 T3 T4 T5 T6 T7 As shown in Fig. 5-23, the drive stops automatically after
one cycle of operation and will start when receiving RUN
command again.
Indicating signal for complating f6
500ms d7
one stage of PLC operation a6 f7
f 2
Indicating signal for completing a a2
f5 d7
cycle of PLC operation
a1 f 1 d3 a5
Fig. 5-21 Simple PLC operation
a3 f 3 d5
In Fig. 5-21, a1~a7 and d1~d7 are the Acc time and Dec a4
f4
time in different stages. f1~f7 and T1~T7 will be defined in
the following parameters.
T1 T2 T3 T4 T5 T6 T7
Bi-direction open-collector output terminals Y1 and Y2 or
the relay that output the 500ms pulse can indicate the
completion of PLC operation, refer to the introductions of RUN
F7.10~F7.12. command
F4.00 Simple PLC operation Fig. 5-23 Stopping mode after single cycle of PLC
Range: 0000~1123【0000】
mode
2: Maintain the final value after single cycle of operation
As shown in Fig. 5-24, the drive will maintain the
operating frequency and direction of last stage after
completing one cycle of operation.
f6 Stopping signal
d7
f a6 f7
a2
2
Output freq.Hz f1
f5 d2
f1 d3 a5 a1
a1 ... f 3 ...
f2 a3
a3 f 3 d5
a4 a2 Time
f4
Stage 1 Operating Remnant time of
T1 T2 T3 T4 T5 T6 T7 time of stage 2
stage 2
When the drive stops during PLC operation due to Hundred’s place: Store the PLC status after power
receiving STOP command or fault, it will record the failure
operating time and will continue from the stage where 0: Not save
the drive stops after restart at the frequency defined for The drive does not save the PLC operating status after
this stage, as shown in Fig. 5-26. power failure and start operating in first stage after
restart.
1: Save
Memorize the operating parameters of PLC operation
after power failure, including the operating stage,
operating frequency, and operating time. The drive will
continue to operate in the mode defined by the ten’s
place.
Note:
When the PLC operating direction is determined by
operating commands, the direction of the motor can be
controlled by external terminals. For example: to run
forward by closing FWD-COM terminal, and run reverse
by closing REV-COM. If no command is given, the drive
will run in the direction of last stage.
5.6 Close-loop Control Parameters(Group F5) 0(4)~20mA current signal. The reference signal and
feedback signal are detected by the analog channel.
There are two kinds of close loop control: analog The start and stop of the drive can be controlled by
close-loop control (feedback value is analog value) and terminal FWD.
pulse close-loop control (feedback value is pulse). Fig. The above system can also use a TG (speed measuring
5-29 and 5-30 show the typical wiring of analog generator) in close speed-loop control
close-loop control and pulse close-loop control Close speed-loop using PG:
respectively. A close speed-loop control system uses external control
terminals X7 and X8, and pulse generator(PG).
EV2000
QF As shown in Fig. 5-30, reference of speed close-loop
R U
3-phase V Output
S M P can be input by a potentiometer in the form of voltage
380V T W
PE Water- signal via terminal VCI, while the feedback value of the
level
sensor close loop is input by PG in pulse mode via terminals X7
. FWD .
P24 and X8. The start and stop of the drive can be controlled
. CCI . by terminal FWD.
COM
VRF . In Fig. 5-30:
. GND .
VCI 1-3K A and B are PG’s dual phase quadrature output;
GND.
P24 is connected to the power source of PG;
Fig. 5-29 Analog feedback control system with internal PI Speed reference is the voltage signal of 0~10V. The
voltage signal is in direct proportion to synchronous
QF EV2000 A/A speed n0 that corresponds to 0~Max frequency (F0.05),
R U
3-phase V M PG
PG supply and fmax is Max frequency (F0.05), and P is the number
S B/B
380V W of poles of motor(FH.00).
T PE
PG GND n0=120×fmax/P
· VRF FWD·
Refer to F7.00~F7.07 for the functions of input terminals
1-3K · VCI
COM· X7 and X8.
· GND
X7·
P24· Note:
X8·
1. The reference can also be input via panel or serial port;
2. Dual-phase input is good for improving the speed
measurement accuracy, while the wiring of single-phase
Fig. 5-30 Wiring of speed close-loop with PG input circuit is simple;
Analog feedback control system: 3. Dual-phase pulse can only be input in quadrature mode;
4. If using the drive’s terminal P24 to supply the power to
An analog feedback control system uses a water-level
PG, then the Max load current of optical PG must be less
sensor as the feedback sensor of the internal PI.
than 100mA.
As shown in Fig. 5-29, pressure reference (voltage
signal) is input via terminal VCI, while the feedback Operating principles of internal PI of EV2000 is shown in
pressure value is input into terminal CCI in the form of the Fig. 5-301.
KP ×
ε
(F5.12)
Reference
+ ε Error limit Regulation +
Reference Output
regulation (F5.15) (F5.16)
+
(F5.08 and F5.10) - ∑ Ki ×
ε
(F5.13)
Feedback
regulation Feedback
(F5.09 F5.11)
In the above Fig., KP: proportional gain; Ki: integral gain After the control type is determined, follow the
In Fig. 5-31, refer to F5.01~F5.15 for the definitions of procedures below to set close loop parameters.
close-loop reference, feedback, error limit and Determine the close-loop reference and feedback
proportional and Integral parameters. channel (F5.01 and F5.02);
There are two features of internal PI of EV2000: The relationship between close-loop reference and
The relationship between reference and feedback can feedback value (F5.08~F5.11) should be defined for
be defined by F5.08~F5.11. close-loop control;
For example: In Fig. 5-29, if the reference is analog For speed close-loop, the close-loop speed reference
signal of 0~10V, the controlled value is 0~1MP, and the and the number of revolutions of PG (F5.06~F5.07)
signal of water-level sensor is 4~20mA, then the need to be determined;
relationship between reference and feedback is shown Determine the close-loop regulation characteristic, i.e.
in Fig. 5-32. whether the motor speed increase with the reference.
Feedback Please see F5.16.
20mA Set up the integral regulation function and close-loop
frequency presetting function (F5.17~F5.19);
Adjust the close-loop filtering time, sampling cycle, error
limit and gain(F5.12~F5.15).
F5.00 Close-loop control function Range:0. 1【0】
4mA
Reference 0: disabled
0 10V 1: enabled
F5.01 Reference selector Range:0. 1. 2【1】
Fig. 5-32 Reference and feedback
0: digital input
The reference value is a 0~10V signal (10V corresponds
Take the value of F5.05 (when the setting is analog
to 100%); and the feedback value is 4Ma~20mA (20mA
close-loop, F5.02=0~5);
corresponds to 100%).
Take the value of F5.06 (when the setting is pulse
In Fig 5-31, “reference regulation” and “feedback
close-loop, F5.02=6).
regulation” mean that the reference value and feedback
value are converted from current or voltage value to 1: VCI analog voltage input(0~10V)
percentage values, so that feedback value can be added 2: CCI analog input
to or subtracted from the reference value. Analog input range:0~10V(Jumper CN10 is placed at
Close-loop reference is selected via F5.16 to satisfy side V), or 0~20mA(Jumper CN10 is placed at side I).
different application requirements.
Note:
If the motor’s speed is required to increases with the
reference speed, this kind of control characteristic is Use pulse feedback to control the speed. If the reference is
called positive characteristic. If the motor speed is analog signal, then 0~10V (4~20mA) reference corresponds
required to decrease when the reference value to synchronous speed n0 (n0=120fmax/P).
increases, this control characteristic is called negative
characteristic. F5.02 Feedback selector Range:0~6【1】
Please refer to Fig. 5-33 and F5.16. 0: VCI 0~10V analog voltage input
Speed Positive
1: CCI analog input
2: VCI + CCI
3: VCI-CCI
4: Min {VCI,CCI}
Negative
5: Max {VCI,CCI}
Settings of jumper CCI are the same with the above.
Close loop
reference
When current input is selected, the signal will be
converted into voltage signal by the formula:
Fig. 5-33 Close-loop control characteristic Voltage value = current value (mA)/2;
Feedback value
Error limit Output freq.
Ref
Preset freq.
time
Output
Freq Holding time of t (time)
preset freq.
Traverse operation is widely used in textile and chemical fiber industry. The typical application is shown in Fig. 5-37.
Traverse operation process: First, the drive accelerates to the preset frequency of traverse operation (F6.02) within the
Acc time and then waits for certain time (F6.03). The drive transits to the central frequency within Acc/Dec time, and at
last the drive traverse according to the preset traverse amplitude (F6.04), jitter frequency(F6.05), traverse cycle(F6.06)
and rising time of traverse operation (F6.07) until it receives a stopping command and stops within Dec time.
Operating
freq. (Hz) Traverse operation
amplitude Aw=Fset*F6.04
Upper limit of
freq. FH
+ Aw
Central Freq. Fset
Lower limit of freq. FL - Aw a1
Preset freq. Jitter
freq.=AW*F6.05
a1
stop
command
The central frequency is actually the preset frequency of simple operation (except PLC, traverse operation, jog),
multi-step speed operation or PLC operations;
Traverse operating function is disabled automatically in Jog operation or close-loop operation process.
If PLC operation and traverse operation start at the same time, the traverse operation is disabled when the drive transits
from one PLC operating stage to another stage. The drive will accelerate to the preset frequency of PLC operation and
then start traverse operation. The drive will decelerate to stop within the Dec time set in PLC operating stage.
1: enabled
Range:0000~1111 Traverse operating amplitude control
F6.01 Traverse operating mode
【0000】 1: Variable amplitude
2: Fixed amplitude
F6.01 is used to set the traverse operating mode and
the meanings of LED display are shown in Fig. 5-38. Restart mode
1: Restart at the freq. and direction
memorized before stopping
2: Restart
Where,
A: thousand’s place B: Hundred’s place
C: Ten’s place D: Unit’s place
Unit’s place: start mode
0: auto mode
25 speed4
CCI forcibly speed3
EV2000 If the setting is 8, the drive can be reset via this terminal
QF R U when the drive has a fault. The function of this terminal
3-phase S V
M is the same with that of RESET on the panel.
AC W
T
supply PE 9~10: inputting jog operation signal (JOGF/JOGR)
If the setting is 9~10, this terminal can enable jog
k1
. X1
operation. JOGF is for inputting forward jog command
k2
. and JOGR is for reverse jog command. Jog frequency,
X2
k3 k4 interval and Acc/Dec time of jog operation are defined in
. FWD .
X3
k5
F3.13~F3.16.
. COM REW .
11: Coast-to-stop
COM .
If the setting is 11, the function of the terminal is the
same with that defined by F2.08. It is convenient for
remote control.
Fig. 5-40 Wiring for multi-speed operation
12~13: Frequency ramp UP/DN
4~5: selecting Acc/Dec time If the setting is 12~13, the terminal can be used to
Table 5-7 Acc/Dec time selection increase or decrease frequency. Its function is the same
Acc/Dec time with c and d keys on the panel, which enables remote
Terminal 2 Terminal 1
selection control. This terminal is enabled when F0.00=1 or
OFF OFF Acc time 1/Dec time 1 F9.01=2. Increase or decrease rate is determined by
OFF ON Acc time 2/Dec time 2 F7.09.
ON OFF Acc time 3/Dec time 3 14: pausing PLC operation:
ON ON Acc time 4/Dec time 4 If the setting is 14, the terminal is used to pause the PLC
Through the On/Off combinations of terminals, Acc/Dec operation and the drive operates at zero frequency when
time 1~4 can be selected. the terminal is enabled. There is no timing of PLC
6~7: inputting external fault signal (normally-open/close operation. If the terminal is disabled, the drive will start
input) on the fly and continue the PLC operation. Refer
F4.00~F4.14 to how to use this terminal.
If the setting is 6~7, the fault signal of external
equipment can be input via the terminal, which is 15: Acc/Dec prohibiting command
convenient for the drive to monitor the external If the setting is 15, the terminal can make the motor
equipment. Once the drive receives the fault signal, it operate at present speed without being influenced by
will display “E015”. The fault signal has two inputting external signal (except stopping command).
modes: normally-open and normally-close input.
Note:
This terminal is disabled in normal Dec-to-stop process.
KM
16: 3-wire operation control.
EV2000 Refer to F7.08, operation mode 2 and 3 (3-wire
· X5 operation mode 1 and 2).
· X6 17~18: inputting external stopping signal
(Normally-open/close input)
· COM
During operating, the drive stops its output and operates
at zero frequency when it receives external STOP signal.
Once the signal is removed, the drive will start on the fly
Fig. 5-41 Normally-open/close input
and resume normal operation.
As shown in Fig. 5-41, X5 is normally-open contact and There are two inputting modes of external stopping
X6 is normally-close command. KM is the relay for signal: normally-open and normally-close input. As
inputting external fault signal. shown in Fig. 5-41, X5 is normally-open contact and X6
8: inputting external reset signal is normally-close contact.
The preset close-loop references in Table 5-10 can be Only multi-function input terminals X7 and X8 can be
selected by the different On/Off combinations of used for this function. The terminal is used in
terminals 1~3. fixed-length control and calculating the length via pulses.
33: Start traverse operation See F9.14~F9.19 for details.
When the traverse operation is set to “manual start”, the 45: inputting pulse signal
traverse function can be enabled if this terminal is Only multi-function input terminals X7 and X8 can be
enabled, see Group F6 parameters for details. used as this function. The terminal is used to input pulse
34: Reset the traverse operating status signal as frequency reference. See Group F1
parameters for the relationship between input pulse
If traverse operation is enabled, switching on this
frequency and the reference frequency.
terminal can clear the memorized information about
traverse operation no matter the drive is in auto start or 46: Single-phase speed measuring input
manual start mode. Traverse operation restarts after this Only multi-function input terminals X7 and X8 can be
terminal is disconnected. See group F6 parameters. used as this function. See section 3.3.2. The speed
35: external stopping command control accuracy is ±0.1%. Single-phase speed
This stopping command is active in all control modes. feedback control can be realized by using this terminal
When terminal 35 is enabled, the drive will stop in the and PG.
mode defined in F2.08. 47: Speed measuring input SM1
36: Reserved 48: Speed measuring input SM2
37: disabling the drive’s operation Only multi-function input terminals X7 and X8 can be
If terminal 37 is enabled, the drive that is operating will used as this function. See section 3.3.2. The speed
coast to stop and is prohibited to restart. This function is control accuracy is ±0.1%. Dual-phase speed feedback
mainly used in application with requirements of safety control can be realized by using this terminal and PG.
protection.
Note:
38: Reserved
When the drive is performing motor auto-tuning, No. 44~47
39: Clear the length information functions of X7 are disabled automatically.
When terminal 39 is enabled, the setting (length) of F7.08 FWD/REV operating modes setup Range:0~3【0】
F9.15 will be cleared to zero.
This parameter defines four operating modes controlled
40: Clear the setting of auxiliary reference frequency
by external terminals.
This function is only active for auxiliary reference
0: 2-wire operating mode 1
frequency (F9.01=1, 2 and 3). When terminal 40 is
EV2000
enabled, the auxiliary frequency is cleared to zero and
the reference is determined by main reference K 2 K1 Running command
. P24
frequency. 0 0 Stop
. PLC
41: Reset the stopping status of PLC operation
1 0 Run reverse K1
. FWD
In stopping status of PLC operation, the memorized PLC K2 . REV
0 1 Run forward
operating information (operating stage, operating time, . COM
operating frequency, etc.) will be cleared when this 1 1 Stop
44: inputting counting value of length Fig. 5-43 2-wire operating mode 2
FL.06. This function is usually used in overload 18: Upper and lower limits of traverse operating
pre-alarm. See Fig. 5-74. frequency
5: Low voltage lock-up signal (LU) If traverse operating function is selected, an indicating
The terminal outputs the indicating signal if the DC bus signal will be output if the traverse operating frequency
voltage is lower than the low voltage limit, and the LED calculated by central frequency is higher than upper limit
displays “P.oFF”. of frequency (F0.12) or lower than the lower limit of
6: External stopping command (EXT) frequency (F0.13), as shown in Fig. 5-46.
The terminal outputs the indicating signal if the drive Before limiting amplitude
Upper limit o f freq
outputs tripping signal caused by external fault (E015). After limiting amplitude
Traverse operation
7: High limit of frequency (FHL) Central freq.
Time
If the extended function 2 of host 2 is enabled, the
output signal of terminal Y1, Y2 or TC is directly
Fig. 5-48 FDT level controlled by a serial port. “65535” corresponds to the
F7.18~F7.25 Reserved Max output of 10V(or 20mA). Refer to the
communication protocol of EV2000 for details.
For example:
F7.26 Functions of terminal AO1 Range:0~11【0】
AO1 outputs 4~20mA, which indicates bus voltage
F7.27 Functions of terminal AO2 Range:0~11【3】
0~800V.
F7.28 Functions of terminal DO Range:0~11【0】
The settings:
AO1 and AO2 are analog output terminals, and DO is
①F7.26=7, output bus voltage;
pulse output terminals.
②F7.29=01, output of terminal AO1 is 4~20mA;
Refer to section 3.3.2 for the output characteristics of
AO1 and AO2, their analog output ranges are defined by ③F7.30=100%, output gain is 100%;
F7.29. ④AO1 jumper of CN16 short circuited at 0/4-20mA side.
Pulse frequency range of DO: 0~Max output pulse
Note:
frequency (defined by F7.32).
The relationship between the displaying range and the If terminal X8 selects functions of 44~46, DO is disabled
output values of AO1, AO2 and DO are given in Table automatically
5-12. F7.29 Analog output range
Range:00~11【00】
Table 5-12 Displaying range of output terminals selection
Factory setting of all the terminals is positive logic. BIT0: actual length
BIT1: preset length
BIT2: reserved
5.9 Display (Group F8) BIT3: reserved
BIT0: reserved
BIT1: reserved
F8.00 Language selection Range:0~1【0】 BIT2: reserved
BIT3: reserved
0:Chinese
1:English Fig. 5-53 Operating parameter 2 displayed by LED
F8.00 is effective for the panel with LCD screen. Where,
F8.01 Displayed parameter Range:000~3FFH A: thousand’s place B: Hundred’s place
group 1 during operation 【3FFH】
C: Ten’s place D: Unit’s place
A B C D The terminal information includes status of terminal
X1~X8, bi-direction open-collector output terminals Y1
BIT0: output freq.Hz(before compensation)
BIT1: output freq.Hz (after compensation) and Y2, and relay output terminal TC. The status of
BIT2: preset freq.Hz terminals are indicated by the “On” or “Off’ of LED. If the
BIT3: output current A
LED turns on, that means the terminal is enabled, and
BIT0 : running speed rpm
BIT1: preset speed rpm
the terminal is disabled if the LED turns off, as shown in
BIT2: running line speed m/s Fig.5-54:
BIT3: preset line speed m/s
For example, Unit place of LED (Bit0) is to display the When the rotating speed and line speed are displayed, these
“output frequency before compensation”, if Bit0=0, the values can be revised by pressing ▲ and ▼ directly (no
parameter will not be displayed, if Bit0=1, the parameter need to switch to frequency displaying status).
will be displayed. When F8.01 and F8.02 are all set to 0, the frequency before
See F7.35 for the relationship between the values of compensation will be displayed.
each Bit and the displayed value of LED.
Press XX key to scroll through the parameters set in F8.02 F8.06 is used to correct error between actual physical
during operation. value (pressure or flow) and reference or feedback
F8.03 Parameters displayed at Range:0000~3FFFH values (voltage or current). It has no influence on
STOP state 【1FFH】 close-loop PI regulation.
A B C D
5.10 Enhanced Functions(Group F9)
BIT0 : preset frequency Hz
BIT1: external counting value
BIT2: running rotating speed rpm F9.00 Control mode bundled Range:000~666
BIT3: preset rotating speed rpm
with frequency selector 【000】
BIT0 : running line speedm/s
BIT1: preset line speed m/s F9.00 can bundle 3 control modes with 6 reference
BIT2 : VCI V
BIT3: CCI V frequency selectors, that is, if a control mode is selected,
BIT0: closeloop reference % then a frequency selector (such as panel input, analog
BIT1: closeloop setting %
BIT2: actual length VCI input) will be selected automatically.
BIT3: preset length
A B C D
BIT0 : terminal status
BIT1: bus voltage
BIT2: reserved Reference selector in panel control mode
BIT3: reserved
0: No bundling
1: Digital setting1 (▲ and ▼ )
Fig. 5-55 Stopping parameters displayed by LED
2: Digital setting 2 ( terminal UP/DN)
Where, 3: Digital setting 3 (serial port )
4: VCI analog input
A: thousand’s place B: Hundred’s place 5: CCI analog input
6: Pulse terminal input
C: Ten’s place D: Unit’s place
F8.03 defines the parameters that can be displayed by Reference selector in terminal control mode
0~6 : same with above
LED in stopping process.
Reference selector in serial port control mode
If Bit is 0, the parameter will not be displayed, and if Bit 0~6 : same with above
is 1, the parameter will be displayed.
Reserved
For example, Bit0 decides whether to display the “preset
frequency”, if Bit0=0, the parameter will not be displayed, Fig. 5-56 Control mode is bundled to frequency selector
if Bit0=1, the parameter will be displayed.
Where,
When setting this parameter, see Table 5-13 for
A: thousand’s place B: Hundred’s place
conversion of binary code and HEX value.
C: Ten’s place D: Unit’s place
Note: The reference frequency selector is defined by F0.00,
When the rotating speed and line speed are displayed, these see section 5.1 for details.
values can be revised by pressing ▲ and ▼ directly (no Different control modes can be bundled to one reference
need to change to frequency displaying status). frequency selector.
When the setting of F8.03 is 0, the preset frequency will be There are 3 methods to select control modes:
displayed. Method 1: change F0.03 “Control modes selector”;
Press XX key to scroll through the parameters set by F8.03 Method 2: use PANEL/REMOTE or ENTER/DATA;
when the drive stops.
Method 3: use the terminals that can select control
F8.04 Rotating Speed Range:0.1~999.9%
modes (Functions of terminals X1~X8 should be set to
display coefficient 【100.0%】
No. 28 and 29 functions.)
F8.04 is used to correct the error of displayed rotating For example:
speed and it has no influence on actual speed.
In order to realize remote and local control, it requires
F8.05 Line speed display Range:0.1~999.9% that:
coefficient 【1.0%】
①Control modes selection: The control modes can be
F8.05 is used to correct the error of displayed line speed selected by terminal remotely or by PANEL/REMOTE
and it has no influence on actual speed. locally;
F8.06 Close-loop parameter Range:0.1~999.9%
display coefficient 【100.0%】
②If panel control mode is used, press RUN to run the Note:
drive and press STOP to stop the drive. The preset The parameter is default 000, that is, the frequency selector
frequency can be adjusted by pressing ▲ and ▼. is not bundled with control mode.
③If terminal control mode is used, connect FWD F9.01 Auxiliary reference
Range: 0~12【0】
terminal to run forward and connect REV terminal to run frequency selector
reverse. The preset frequency is adjusted via VCI. F9.02 Auxiliary analog Range: 0.00~9.99
④Terminal control mode is enabled after the drive is reference frequency coefficient 【1.00】
switched on. F9.03 Initial auxiliary digital Range: 0.00~650.0Hz
Remote Local reference frequency 【0.00Hz】
Multi-function input F9.04 Auxiliary digital
Terminal Xi Range: 000~111【000】
Terminal control Panel control mode reference frequency control
mode
The preset frequency of EV2000 drive is the result out of
the operation on the main reference frequency and
PANEL/REMOTE
Digital setting auxiliary reference frequency. F9.01~F9.04 define the
VCI input ENTER/DATA
mode 1 auxiliary reference frequency selector. Fig. 5-59 shows
the process of operation.
Coefficient
F1 F3 F4 Preset
Power on Main ref. freq. + adjustment
freq.
(F9.05, F9.06)
Common F2
Fig. 5-57 Remote and local control operating freq. Auxiliary
(F0.00=0~5) ref. freq.
Set the parameters below to realize remote and local
Preset freq.
control: (F3.23~F3.29)
No auxiliary
freq.(F9.01=0)
Set F0.03=1 to select terminal control mode and remote PLC operating freq. Digital setting of
control is enabled after the drive is switched on; (F4.00~F4.14) auxiliary
freq.(F9.01=1~3)
Set F7.00=28, F7.01=29, to select multi-function input Close-loop
operating freq. Analog setting of
terminal X1 and X2 to input operating commands; auxiliary ref.
(F5.00~F5.26) freq.(F9.01=4~12)
Set F7.08=1, to select 2-wire control mode 2. The drive
run forward when FWD is enabled, and run reverse Fig. 5-59 Preset frequency
when REV is enabled; Pre-processing
supply T
PE
Fig. 5-60 Auxiliary reference frequency selector
. VRF P24 .
Auxiliary reference frequency is controlled by
. VCI PLC .
4.7k F9.01~F9.04. F9.01 defines the auxiliary reference
. GND FWD
. K1
frequency selector.
REV . K2
. PE X1 .
K3
X2 .
K4
COM
.
Fig. 5-58 Wiring of remote and local control
Table 5-14 Auxiliary reference frequency selector reference frequency increases with pulse frequency. For
SN Reference selector Features example, as shown in Fig. 5-62:
No auxiliary reference Auxiliary frequency
0 Zero
frequency
0.5 fmax
Digital setting 1, set the
1 Reference is set by
reference by ▲ and ▼
F9.03, the changed
Digital setting 2, set the
2 frequency will be
reference by UP/DN 0 Pmid F1.03 Pulse
saved in F9.03 upon
Digital setting 3, set the
3 power outage.
reference serial port
-0.5 fmax Pmid——1/2 *Max input pulse frequency (F1.03)
4 VCI analog input
fmax——frequency corresponds to Max analog
5 CCI analog input Determined by value (F1.07 or F1.11)
6 PULSE terminal input actual input analog
Fig. 5-62 PULSE-0.5×F1.03 as auxiliary ref. setting
7 - VCI analog input value, see F1.00 for
8 - CCI analog input frequency curves method
9 - PULSE terminal input F9.02: Coefficient of analog auxiliary reference
10 VCI-5 Determined by Only valid when F9.01=4~12. First, use F9.02 to
actual input analog calculate the gain and then calculate the auxiliary
11 CCI-5
value, see F1.00 for reference frequency by the frequency curve defined by
12 PULSE-0.5×F1.03 frequency curves F1.00.
If digital setting 3 is selected, and the frequency F9.03: initial value of digital reference frequency
reference is input via the serial port, then the auxiliary
Only valid when F9.01=1~3. F9.03 defines the initial
frequency can be changed by setting F9.03 through the
values of digital reference frequency when F9.01=1~3.
host.
F9.04: digital auxiliary reference frequency control
When selecting VCI-5 or CCI-5 to input auxiliary
Only valid when F9.01=1~3, as shown in Fig.5-63.
reference frequency, the 5V analog input should be
used as a central point, from 0 to 5V, the reference A B C D
frequency drops with the increase of voltage,while from Save
5 to 10V, the frequency increases with voltage. For 0: Save ref. Freq. upon power outage
1: Not save ref. Freq. upon power
example, as shown in Fig. 5-61: outage
Stopping freq.
0: Hold ref. Freq. at stop
1: Clear ref. Freq. at stop
Reserved
Where,
A: thousand’s place B: Hundred’s place
Fig. 5-61 VCI-5/CCI-5 as auxiliary ref. setting method C: Ten’s place D: Unit’s place
Unit’s place: parameter-saving function at power off
When using PULSE-0.5×F1.03 to determine auxiliary
reference frequency, one half of F1.03 (Max input pulse 0: Save the auxiliary reference frequency at power off
The auxiliary frequency will be stored in F9.03 at power
frequency) is the central point. Within 0~0.5×F1.03 pulse
off. The sign of auxiliary reference frequency is saved in
frequency, the reference frequency decreases with the
F9.04.
increase of pulse frequency; within 0.5×F1.03~F1.03, the
1: not save the auxiliary frequency at power off
0: Plus PANEL/REMOTE
The sum of main reference frequency and auxiliary 0: Inactive
reference frequency is the preset frequency. 1: Active in stopping status
2: Active in running and stopping
1: Minus status
The result of subtracting auxiliary reference frequency Panel lock-up
from the main reference frequency is the preset 0: No lock up
frequency. 1: Lock up
2: Lock all the keys except STOP
Note: 3: Lock up all the keys except XX
4: Lock up except RUN and STOP
When the inputting mode of auxiliary reference frequency,
such as input via panel, terminal or serial port is the same Reserved
with that of main reference frequency, the auxiliary
Fig. 5-64 Functions of keys and panel locking up function
frequency is invalid.
F9.05 Frequency adjustment Range:0~2【0】 Where,
F9.06 Adjustment coefficient of Range:0.0%~200.0% A: thousand’s place B: Hundred’s place
preset frequency 【100.0%】 C: Ten’s place D: Unit’s place
F9.05 and F9.06 define the adjustment of preset Unit’s place: Function of STOP/RESET
frequency as shown in Fig. 5-59.
This Bit defines in which modes the key is valid for
0: Disabled stopping the drive
No adjustment is done to the main frequency, F4=F3 0: Enabled only in panel control mode
1: adjust based on max. output frequency 1: Enabled in panel control mode, terminal and serial
Preset frequency (F4)=F3+F0.05×(F9.06-100%) control modes. The drive stops in the defined manner
2: adjust based on the main reference frequency when this key is pressed.
Preset frequency (F4)=F3+F3×(F9.06-100%) 2: Enabled in panel control mode, terminal and serial
=F3×F9.06. control modes.
F9.07 Function of keys Range: 000~422【000】 In panel control mode, the drive stops in defined manner
F9.07 defines the functions of PANEL/REMOTE and when this key is pressed. But, in terminal and serial
STOP/RESET key, and the locking up function of panel. control modes, the drive will alarms and display fault
code of E015 and coasts to stop.
The STOP/RESET key is valid for all control modes
when resetting a fault.
Ten’s place: Function of PANEL/REMOTE
0: PANEL/REMOTE is disabled.
1: PANEL/REMOTE is enabled only in stopping state,
not operating state.
2: PANEL/REMOTE can be used to select the control
mode both in operating status and stopping status.
Press the key to switch the control mode, and the LED
will indicate the mode accordingly. When panel/control
mode is selected, the LED turns on; when terminal
Belt
Note:
Motor
After selecting a control mode by using PANEL/REMOTE,
be sure to press ENTER/DATA key to confirm within 3 Drives 1 2 3 4 5
seconds.
Fig. 5-65 Droop control
Hundred’s place: Locking panel
0: not lock any key on the panel. When the load of one drive is heavier, this drive will
reduce its output frequency to shed part of the load
1: Locking up function is enabled and all keys on the
according to the settings of F9.10. You can increase the
panel are locked up.
setting gradually when testing. The relationship between
2: Except STOP/RESET, other keys are locked up. the load and the output frequency is shown in Fig. 5-66:
3: Except XX, other keys are locked up. Droop control
Torque
4: Except RUN and STOP, all other keys are locked up. No droop control
After setting the parameter, you have to do certain
Rated
operation on the keypad to lock the panel. Please refer
torque
to Figure 4-8.
F9.08 Fan control mode Range:0. 1【0】
0: Auto stopping mode o Speed
Synchronuous speed
The fan runs all the time when the drive is operating.
After the drive stops, its internal temperature detecting
program will be activated to stop the fan or let the fan
continue to run according to the IGBT’s temperature.
1: The fan operates continuously.
The fan operates continuously after the drive is switched Fig. 5-66 Droop control
on.
F9.11 Overshoot enabling Range:0. 1【1】
F9.09 Unit of Acc/Dec time Range: 0. 1【0】
When the AC supply voltage is lower than 85% of rated
F9.09 decides the unit of Acc/Dec time.
load for a long time or the drive has driven a heavy load
0: Second for a long time, the drive can increase its output voltage
1: Minute by increasing the utilization rate of DC bus voltage.
This function is active for all the Acc or Dec process F9.11 decides whether to enable the overshoot function.
except Jogging process. 0: disabled
Up to 60 hours’ Acc/Dec time can be set, suitable for the 1: enabled
application with a requirement of long Acc/Dec time.
Note:
Note
When overshoot function is enabled, output current
It is recommended to select “second” as the unit. harmonics will increase.
F9.10 Droop control Range:0.00~10.00Hz【0.00Hz】 F9.12 Threshold of Range: 0.00~650.00Hz
When several drives drive one load, the function can zero-frequency operation 【0.00Hz】
make the drives share the load equally. An example is F9.13 Hysteresis of Range: 0.00~650.00Hz
shown in Fig. 5-65, 5 drives drive one conveying belt of zero-frequency operation 【0.00Hz】
5 motors. F9.12 and F9.13 are used to set the zero-frequency
operation hysteresis.
Take CCI current reference for example, see Fig.5-67:
Starting process
After the running command is sent out, the motor will
start and accelerate to the frequency corresponding to
the CCI input current until CCI input current reaches or Calculated length=Number of pulses÷number of
exceeds the preset value of Ib, or the preset frequency pulses per revolution×perimeter of shaft
reaches fb.
The calculated length can be corrected through F9.16
Stopping process: (times of length) and F9.17(correction coefficient of
The drive will not stop immediately when the CCI input length, and the corrected length is the actual length.
current is reduced to Ib. It will stop its output when the Actual length =calculated length×F9.16÷correcting
CCI input current drops to Ia and the corresponding
coefficient of length
frequency is fa.
When actual length(F9.15)≥preset length(F9.14), the
“fa” is the zero-frequency operation threshold defined by
drive will send out a STOP command to stop the drive.
F9.12. “fb-fa” is the hysteresis of zero-frequency
When the drive restarts, it needs to clear or modify the
operation defined by F9.13.
actual length (F9.15), otherwise the drive will not start.
This function can enable the drive to enter dormant state
so as to save energy, besides, the drive will not start at Note:
the threshold of zero-frequency operation if the The actual length (terminal Xi is defined as No.39 function)
hysteresis is set properly. can be cleared by multi-function input terminal. The actual
CCI current input length can be calculated only after this terminal is
Imax
disconnected.
Ib Actual length (setting of F9.15) will be saved after power
Ic
Ia off automatically.
Imin Function of stopping at fixed length is disabled if F9.14 is
set to 0, but the calculated length is still effective.
Fmin Fmax primary frequency setting
Actual
An example of stopping the motor at fixed length:
frequency
setting
Spindle
Speed
Speed measuring shaft
sensor
0
fa fc fb Primary frequency setting
fa: Zero frequency threshold
fb: fa+ zero freq. hysteresis
fc: Freq. corresponding to Ic(CCI input)
Motor
Fig. 5-67 Hysteresis of zero-frequency operation Drive
Range:0.000~65.535km
F9.14 Preset length
【0.000km】 Fig. 5-68 Fixed length control application
Range:0.000~65.535km
F9.15 Actual length In Fig. 5-68, a drive drives a motor that rotates a spindle
【0.000km】
via a conveyor belt. Speed measuring device measures
F9.16 Rate of length Range:0.001~30.000【1.000】
the line speed of the spindle and send the speed signal
F9.17 Correction to the drive in the form of pulses. The drive will count the
Range:0.001~1.000【1.000】
coefficient of length pulses and calculate the actual length. If the actual
Range:0.01~100.00cm length is longer than the preset length, the drive will stop
F9.18 Perimeter of shaft
【10.00cm】 the motor automatically. The operator can remove the
F9.19 Number of pulses spindle and close the terminal that is defined as function
Range: 1~9999【1】
per revolution 39 to clear the length, and then restart and produce the
This group of parameters are used for fixed length next spindle.
control. Note:
The drive inputs counting pulses via terminals (X7 or X8,
Functions of stopping the motor at a fixed length are only
defined as function 44), and calculate length according
valid for the drive of 45kW or below.
to the number of pulses per revolution (F9.19) and
F9.20 Trip-free operation Range:0. 1【0】
perimeter of shaft (F9.18).
F9.21 Frequency decrease Range:0.00~99.99Hz/s When using the panel or serial port or 3-wire modes 1 and 2
rate at voltage compensation 【10.00Hz/s】 to start or stop the drive, the command signal is in pulse
mode and there is no operating command when the drive is
Trip-free operating function enables the drive to perform
switched on.
low-voltage compensation when the voltage drops or
If there is a stopping command, the drive will stop first.
instantaneous under-voltage occurs. The drive can
When the function of restart after power failure is enabled,
continue to operate without tripping by reducing its
the drive will start on the fly after power on if it is not
output frequency and feedback energy via motor.
switched off totally (that is, the motor still runs and drive’s
If F9.20 is set to 0, this function is disabled.
LED displays “P.OFF”). It will start in the starting mode
If F9.20 is set to 1, this function is enabled and defined in F2.00 after power on if it is switched off totally
low-voltage compensation is activated. (LED turns off).
If F9.21 (frequency decrease rate at voltage For 2-wire mode 2, there is control command after
compensation) is set too big, the feedback energy of power-on.
motor will be too large and over-voltage protection might
be activated; If F9.21 is set too small, the feedback 5.11 Reserved (Group FA)
energy of motor will be too small to achieve voltage
compensation effect. So, please set F9.21 according to FA.00~FA.11 Reserved
load inertia and the actual load.
F9.22 and F9.23 decide whether the drive starts Baud rate
:
automatically and the delay time for restart when the 0: 300bps
1: 600bps
drive is switched off and then switched on in different 2: 1200bps
control modes. 3: 2400bps
4: 4800bps
If F9.22 is set to 0, the drive will not run automatically 5: 9600bps
after restarted. 6: 19200bps
7: 38400bps
If F9.22 is set to 1, when the drive is powered on after
power failure, it will wait certain time defined by F9.23
Data format
and then start automatically depending on the current 0: 1-8-1 format, no parity
control mode and the drive’s status before power failure. 1: 1-8-1 format, even parity
See Table 5-15. 2: 1-8-1format, odd parity
FH.00 Number of R
%R =
polarities of motor
Range: 2~14【4】
(
V / 3⋅I ) × 100%
Range:0.4~999.9kW【dependent
FH.01 Rated power R: Stator’s resistance or rotor’s resistance that is
on drive’s model】
converted to the rotor’s side;
Range:0.1~999.9A 【dependent V: Rated voltage;
FH.02 Rated current
on drive’s model】 I: Motor’s rated current
FH.00, FH.01 and FH.02 are used to set the motor’s Formula used for calculating inducatance (leakage
parameters. inductance or exciting inductance):
In order to ensure the control performance, please set X
%X =
FH.00~FH.02 with reference to the values on the
motor’s nameplate.
(
V / 3⋅I ) × 100%
X: sum of rotor’s leakage inductance and stator’s
leakage inductance (converted to stator’s side)or the
exciting inductance based on base frequency;
V: Rated voltage; 3. If FH.09 is set to 2, Acc time (F0.10) and Dec time
I: Motor’s rated current (F0.11) should be set correctly.
If motor’s parameters are available, please set FH.04 4. Remove the load from the motor and check the
~FH.07 to the values calculated according to the above safety;
formula. 5. Set FH.09 to 1 or 2, press ENTER/DATA, and then
If the drive performs auto-tuning of motor’s parameters, press RUN to start auto-tuning;
the results will be written to FH.03~FH.07 automatically. 6. When the operating LED turns off, that means the
After motor power (FH.01) is changed, the drive will auto-tuning is over.
change FH.02~FH.07 accordingly.
Note:
Range: 0.00~20.00Hz
FH.08 Rated slip frequency When setting FH.09 to 2, Acc/Dec time can be increased if
【0.00Hz】
over-current or over-voltage fault occurs in the auto-tuning
Motor’s rated slip frequency can be calculated by the process;
motor’s rated speed (nameplate value): When setting FH.09 to 2, the motor’s load must be removed
Rated slip frequency = motor’s rated frequency (e.g. first before starting rotating auto-tuning;
basic frequency F0.06)×(motor’s synchronous The motor must be in standstill status before starting the
speed-motor’s rated speed)÷motor’s synchronous auto-tuning, otherwise the auto-tuning cannot be executed
speed normally;
Where: motor’s synchronous speed = motor’s rated In some applications, for example, the motor cannot break
frequency×120÷number of motor’s poles (FH.00) away from the load or if you have no special requirement
on motor’s control performance, you can select stationary
After setting the slip frequency, the slip compensation
auto-tuning. You can also give up the auto-tuning. At this
will be enabled by F3.07~F3.09.
time, please input the values on the motor’s nameplate
FH.09 Auto-tuning Range:0~2【0】 correctly (FH.00~FH.02).
The function can enable auto tuning of motor’s If the auto-tuning cannot be applied and the correct motor’s
parameters and write the results in the related parameters are available, the user should input the values
parameters automatically. on the motor’s nameplate correctly (FH.00~FH.02), and
0: Auto-tuning is disabled then input the calculated values (FH.03~FH.07). Be sure to
1: Stationary auto-tuning (Start auto-tuning to a standstill set the parameters correctly.
motor) If auto-tuning is not successful, the drive will alarm and
display fault code E024.
Values on the motor’s nameplate must be input correctly
before starting auto-tuning. FH.10 Motor’s stabilization Range:0~255【dependent
factor on drive’s model】
When starting auto-tuning to a standstill motor, the
stator’s resistance (%R1), rotor’s resistance (%R2) and FH.10 is used to suppress the oscillation caused by the
the leakage inductance (%X1) will be detected and drive and the motor. If the drive’s output current changes
written into FH.04, FH.05 and FH.06 automatically. frequently at constant load, you can reduce the
2: Rotating auto-tuning oscillation by adjusting the parameter.
When starting a rotating auto-tuning, the motor is in For the drive of 55kW or below, FH.10 is set at 10, and
standstill status at first, and the stator’s resistance “20” for the drive of 55kW or above.
(%R1), rotor’s resistance (%R2) and the leakage FH.11~FH.21 Reserved
inductance (%X1) will be detected, and then the motor Reserved
will start rotating, exciting inductance (%Xm and I0 will
be detected. All the above parameters will be saved in 5.14 Protective Function (Group FL)
FH.04, FH.05, FH.06, FH.07 and FH.03 automatically.
After auto-tuning, FH.09 will be set to 0 automatically. FL.00 Motor overload
Range:0. 1. 2【1】
Auto-tuning procedures: protection mode selection
1. Set the “F0.06 basic operating frequency” and “F0.07 0: Disabled
Max output voltage” correctly according to the motor’s
The overload protection is disabled. Be careful to use
feature;
this function because the drive will not protect the motor
2. Set the FH.00, FH.01 and FH.02 correctly; when overload occurs;
1:Common mode (with low speed compensation) drive's DC bus. If no measures taken, the drive will trip
Since the cooling effects of common motor deteriorates due to over voltage.
at low speed (below 30Hz), the motor’s overheat During the deceleration, the drive detects the bus
protecting threshold should be lowered, which is called voltage and compares it with the over voltage point at
low speed compensation. stall defined by FL.03. If the bus voltage exceeds the
2: Variable frequency motor (without low speed stall overvoltage point, the drive will stop reducing its
compensation) output frequency. When the bus voltage become lower
The cooling effects of variable frequency motor is not than the point, the deceleration continues, as shown in
affected by the motor’s speed, so low speed Fig. 5-72.
compensation is not necessary.
Overvolt
FL.01 Motor’s overload Range:20.0~110.0% point at
protection coefficient 【100.0%】 stall
Motor overload
protective
coefficient Time
Note:
The drive will alarm and display E015 when it is in the
status of over-voltage at stall for more than 1 minute.
160% 200% Current If the stall point is set too low, you can prolong the Acc and
Dec time properly.
Fig. 5-71 Motor’s overload protection coefficient
FL.04 Overload detection Range:000~111【000】
Use the following coefficient to calculate the coefficient: Range:20~150%
FL.05 Overload pre-alarm
Motor overload motor rated current detection threshold 【130.0%】
= ×100%
protection coefficient inverter's rated output current
FL.06 Overload detection time Range:0.0~60.0s【5.0s】
Generally, the Max load current is the motor’s rated EV2000 has protection over drive and motor overload.
current. See Table 2-1 for drive overload protection, and FL.00
and FL.01 for motor overload protection. FL.04~FL.06
Note: can monitor the overload condition before overload
If the motor’s rated current does not match that of the drive, protection happens.
motor’s overload protection can be realized by setting A B C D
FL.00~FL.01.
Overload alarm detection
FL.02 Protection of 0: Detect all the time
Range:0. 1【1】
Over-voltage at stall 1: Detect in constant speed status
FL.03 Over-voltage point at Range:120~150%
Overload protection
stall 【140.0%】 0: No alarm and continue operation
1: Alarm and stop operation
0: Disabled
1: Enabled Overload detection threshold
0: % of motor's rated current
During deceleration, the motor’s decelerate rate may be 1: % of drive's rated current
lower than that of drive’s output frequency due to the
Reserved
load inertia. At this time, the motor will feed the energy
back to the drive, resulting in the voltage rise on the Fig. 5-73 Settings of FL.04
Chapter 6 Troubleshooting
Table 6-1 listed the possible faults of EV2000. Once a fault occurs, you may check it against the table and record
detailed phenomena before seeking service from your supplier.
Table 6-1 Faults and actions
Fault
Fault categories Possible reasons of fault Actions
code
Too short Acc time Prolong the Acc time
Check and adjust V/F curve, adjust
torque boost or set the motor parameters
Over-current V/F curve is not suitable.
correctly to ensure the normal auto
E001 during torque boost.
acceleration
The rotating motor restarts right after stop. Set F2.00 to “start on fly” function
Low AC supply voltage Check the drive’s input AC supply
Drive power is too small Select a high power drive
Too short Dec time Prolong the Dec time
Over-current
The load generates energy or the load inertial
E002 during Connect suitable braking kit
is too big
deceleration
Too low drive’s power Select the drive with bigger power
Sudden change of load Reduce the change of the load
Over-current in Too short Acc/Dec time Prolong Acc/Dec time
E003 constant speed Abnormal load Check the load
operation Low AC supply voltage Check the AC supply voltage
Insufficient drive’s power Select the drive with bigger power
Abnormal AC supply voltage Check the AC supply voltage
Over voltage
Too short Acc/Dec time Prolong the Acc time
E004 during
acceleration The rotating motor re-start after the drive stops
Set F2.00 to “start on fly” function
instantly.
Too short Dec time (with reference to
Over voltage Prolong the Dec time
generated energy)
E005 during
The load generates energy or the load inertial
deceleration Use suitable dynamic braking kit
is too big
Over voltage in Abnormal AC supply voltage Check the AC supply voltage
constant-speed Too short Acc/Dec time Prolong the Acc/Dec time
E006
operating Abnormal change of input voltage Install input reactor
process Too big load inertia Use suitable dynamic braking kit
Drive’s control
Check the AC supply voltage or seek
E007 power supply Abnormal AC supply voltage
service
over voltage
Check the wiring and installation
E008 Input phase loss Any of phase R, S and T cannot be detected
Check the AC supply voltage
Output phase Check the drive’s output wiring
E009 Any of Phase U, V and W cannot be detected
failure Check the cable and the motor
Fault
Fault categories Possible reasons of fault Actions
code
Instantaneous over-current Refer to E001~E003
Short-circuit among 3-phase output or
Rewiring
line-to-ground short circuit
Vent is obstructed or fan does not work Clean the vent or replace the fan
Over-temperature Lower the ambient temperature
Protections of Wires or connectors of control board are loose Check and rewiring
E010
IGBT act Current waveform distorted due to output
Check the wiring
phase loss
Auxiliary power supply is damaged or IGBT
Seek service
driving voltage is too low
Short-circuit of IGBT bridge Seek service
Control board is abnormal Seek service
Over-temperature Lower the ambient temperature
IGBT module’s
Vent obstructed Clean the vent
E011 heatsink
Fan does not work Replace the fan
overheat
IGBT module is abnormal Seek service
Rectifier’s Ambient over-temperature Lower the ambient temperature
E012 heatsink Obstruction of ventilation channel Clear the ventilation channel
overheat Fan does not work Replace the fan
Too short Acc/Dec time Prolong the Acc/Dec time
Reduce the DC injection braking current
DC injection braking current is too big
or prolong the braking time
Improper V/F curve Adjust V/F curve or torque boost value
E013 Drive overload
The rotating motor restart after the drive stops Set the starting mode (F2.00) to “start of
instantly. fly”
Low AC supply voltage Check the AC supply voltage
Too heavy load Select the drive with bigger power
Set V/F curve and torque boost value
Improper V/F curve
correctly
Low AC supply voltage Check the AC supply voltage
Common motor has operated with heavy load Use a special motor if the motor is
E014 Motor over-load
at low speed for a long time. required to operate for a long time.
Improper motor’s overload protection threshold Modify the motor’s overload protection
threshold.
Load changes fast Check the load
Check the definition of STOP function in
STOP is pressed in non-panel control mode
F9.07 and the operating mode
Check the definition of STOP function in
Emergent stop STOP pressed when the drive is in stall status
F9.07
E015 or external
The drive will report E015 fault if it is in stall
equipment fails Set FL.02 and FL.03 properly
status for 1 minute
Terminal used for stopping the drive in Disconnect the terminal if the external
emergent status is closed fault is cleared
EEPROM R/W Press STOP/RESET to reset
E016 R/W fault of control parameters Seek service
fault
Fault
Fault categories Possible reasons of fault Actions
code
Wrong baud rate setting Set the baud rate correctly
RS232/RS485 Press STOP/RESET to reset, seek
Serial port communication error
E017 communication service
failure Improper settings of alarm parameters Modify FF.02, FF.03 and FL.12
Host PC does not work Check the host PC; Check the wiring
Low AC supply voltage Check the AC supply voltage
Replace the contactor in main circuit and
Contactor damaged
seek service
Contactor not
E018 Replace the soft start resistor and seek
closed Soft start resistor is damaged
service
Control circuit is damaged Seek service
Input phase loss Check the wiring of R, S, T.
Wires or connectors of control board are loose Check and re-wire
Current
Auxiliary power supply is damaged Seek service
E019 detection circuit
Hall sensor is damaged Seek service
has fault
Amplifying circuit is abnormal Seek service
Press STOP/RESET to reset or install
Severe disturbance
System power filter at the input side of the drive.
E020
disturbance Press STOP/RESET to reset
R/W fault of DSP in main control board
Seek service
E021 Reserved Reserved Reserved
E022 Reserved Reserved Reserved
Update the panel’s parameters and
Panel’s parameters are not complete or the version again. First set FP.03 to 1 to
Parameter copy version of the parameters are not the same upload the parameters and then set
E023
error with that of main control board FP.03 to 2 or 3 to download the
parameters.
Panel’s EEPROM is damaged Seek service
Improper settings of parameters on the Set the parameters correctly according to
E024 Auto-tuning fails nameplate the nameplate
Overtime of auto-tuning Check the motor’s wiring
Chapter 7 Maintenance
Many factors such as ambient temperature, humidity, dust, vibration, internal component aging, wear and tear will give
rise to the occurrence of potential faults. Therefore, it is necessary to conduct routine maintenance to the drives.
Notes:
As safety precautions, before carrying out check and maintenance of the drive, please ensure that :
The drive has been switched off;
The charging LED lamp inside the drive is off.
Use a volt-meter to test the voltage between terminals (+) and (-) and the voltage should be below 36V.
The drive must be operated in the environment specified in the Section 2.1. Besides, some unexpected accidents may
occur during operation. You should maintain the drive conditions according to the table below, record the operation data,
and find out problem in the early stage.
Table 7-1 Daily checking items
Instructions
Items Criterion
Items Cycle Checking methods
Temperature and Thermometer and -10℃~+40℃,
Operating humidity hygrometer derating at 40℃~50℃
Any time
environment Dust and water dripping Visual inspection No water dripping
Gas Visual inspection No strange smell
Stable vibration and proper
Vibration and heating Touch the case
Drive Any time temperature
Noise Listen No abnormal sound
Heating Touch by hand No overheat
Motor Any time
Noise Listen Low and regular noise
Output current Current meter Within rated range
Operating status Output voltage Volt-meter Within rated range
Any time
parameters Temperature rise is smaller
Internal temperature Thermometer
than 35℃
3. Check whether the power cables and control cables
7.2 Periodical Maintenance are damaged, check especially for any wear on the
cable tube;
Customer should check the drive every 3 months or 6 4. Check whether the insulating tapes around the cable
months according to the actual environment. lugs are stripped;
Notes: 5. Clean the dust on PCBs and air ducts with a vacuum
cleaner;
1. Only trained personnel can dismantle the drive to replace
6. For drives that have been stored for a long time, it
or repair components;
must be powered on every 2 years. When supplying AC
2. Don't leave metal parts like screws or pads inside the
power to the drive, use a voltage regulator to raise the
drive; otherwise the equipment may be damaged.
input voltage to rated input voltage gradually. The drive
General Inspection: should be powered for 5 hours without load.
1. Check whether the screws of control terminals are 7. Before performing insulation tests, all main circuit
loose. If so, tighten them with a screwdriver; input/output terminals should be short-circuited with
2. Check whether the main circuit terminals are properly conductors. Then proceed insulation test to the ground.
connected; whether the mains cables are over heated; Insulation test of single main circuit terminal to ground is
forbidden; otherwise the drive might be damaged. After the drive is switched off, check if abnormal
Please use a 500V Mega-Ohm-Meter. conditions such as crack exists on fan vanes and other
EV2000 parts. When the drive is switched on, check if drive
P1 (+) (-)
running is normal, and check if there is any abnormal
R U
S V vibration.
W
T
PE . 2. Electrolytic capacitors
. VRF Possible cause of damages: high ambient temperature,
FWD
.
. VCI aging of electrolyte and large pulse current induced by
. GND . rapid changing loads.
COM
.
.TA X7
. Criteria: Check if frequent over-current or over-voltage
P24
. TB .
. TC X8 failures occur during drive start-up with load. Check if
X6
.
there is any leakage of liquids. Check if the safety valve
protrudes. Measure static capacitance and insulation
Fig. 7-1 Insulation test of drive
resistance.
8. Before the insulation test of the motor, disconnect the
motor from the drive to avoid damaging it. 7.4 Storage
EV2000
R P1 (+) (-) U
The following points must be followed for the temporary
S V
W
M
and long-term storage of drive:
T PE
1. Store in locations free of high temperature, humidity,
. VRF .
dust, metal powder, and with good ventilation.
FWD
. VCI 2. Long-term storage will cause the deterioration of
. GND COM .
X7 .
electrolytic capacitors. Therefore, the drive must be
. TA P24 .
. TB switched on for a test within 2 years at least for 5 hours.
X8 .
. TC X6 . The input voltage must be boosted gradually by the
voltage regulator to the rated value.
Fig. 7-2 Insulation test of motor
7.5 Warranty
Notes:
Dielectric strength test of the drive has already been Emerson Network Power will offer warranty service in
conducted in the factory. Do not do the test again, the case of the following situations:
otherwise, the internal components might be damaged. 1.The warranty clause is only confined to the drive;
2. Emerson Network Power will take the responsibility of
7.3 Replacing Wearing Parts 18 months defects liability period for any faults or
damages under the normal operation conditions. After
The components that are easily damaged are: cooling 18 months, maintenance will be charged;
fan and electrolytic capacitors of filters. Their lifetime 3. Even within 18 months, maintenance would be
depends largely on their application environment and charged under the following conditions:
preservation. Normally, lifetime is:
4.Damages incurred to the drive due to incorrect
Components Life operation, which are not in compliance with “User
Fan 3~40,000 hours Manual”;
Electrolyte capacitor 4~50,000 hours ② Damages incurred to the drive due to fire, flood,
You can decide the time when the components should abnormal voltage and so on;
be replaced according to their service time. ③ Damages incurred to the drive due to the improper
Cooling fan use of drive functions;
Possible cause of damages: wear of the bearing, aging 5. Service fee will be charged according to the actual
of the fan vanes. costs. If there are any maintenance contracts, the
Criteria: contract prevail.
Appendix 1 Parameters
EV2000 series drive’s parameters are organized in The user’s password can be disabled by setting FP.00
groups. Each group has several parameters that are to 0.
identified by “Group No.+ Function Code.. For example, The above rules should be observed when changing the
“F5.08” belongs to group 5 and its function code is 8. password or setting the parameters via the serial port.
For the convenience of setting, parameter group number
corresponds to the first level menu, parameter ! Attention
sub-group corresponds to the second level menu and
parameter value corresponds to the third level menu. It is defaulted that no parameters except F0.02 are
The parameter descriptions are listed in the tables allowed changing. If you need change them, please
below. first set FP.01(parameter write-in protection) from 1
Note: to 0.
Note:
In order to be simple, all the analog value is expressed by voltage value. The formula that converts the current(mA) into
voltage(V) is: Voltage(V) =Current (mA)/2.
Group F2: Starting and Braking Parameters
Factory
Para. Name LCD Display Setting range Unit Modif.
setting
0:start at start frequency
1:brake first, then start at start frequency
2:Start on the fly(including direction judgement), start at
F2.00 Start mode START MODE start frequency when speed is zero 1 0 ×
Note: Starting process includes switching on the drive for
the first time, recover of AC supply after power failure,
reset upon external fault and coast-to-stop
F2.01 Start frequency START FREQ 0.20~60.00Hz 0.01Hz 0.50Hz ○
Start frequency holding
F2.02 HOLD TIME 0.0~10.0s 0.1s 0.0s ○
time
Depending on the type of the drive
DC injection braking BRAK CURR AT P type: 0.0~80.0% of drive’s rated current
F2.03 0.1% 0.0% ○
current at start START
G type: 0.0~100.0% of drive’s rated current
F3.26 Preset frequency 4 MULTIBAND FREQ 4 F0.13 (Lower limit of frequency) ~F0.12(upper limit of frequency) 0.01Hz 30.00Hz ○
F3.31 Range of skip frequency 1 SKIP FREQ BAND1 0.00~30.00Hz 0.01Hz 0.00Hz ×
F3.33 Range of skip frequency 2 SKIP FREQ BAND2 0.00~30.00Hz 0.01Hz 0.00Hz ×
F3.35 Range of skip frequency 3 SKIP FREQ BAND3 0.00~30.00Hz 0.01Hz 0.00Hz ×
F5.15 Limits of deviation ERROR LIMIT 0.0~20.0%(corresponding to close loop reference) 0.1% 2.0% ○
Close loop adjustment 0:Forward 1:Reverse
F5.16 CLOSELOOP FEATURE 1 0 ×
characteristic Note: reference has no connection with speed
0:Stop the Integral adjustment when the frequency
Integral adjustment reaches the upper limit or lower limit.
F5.17 INTEGRATION SELE 1 0 ×
selection 1:Continue the Integral adjustment when the
frequency reaches the upper limit or lower limit.
Note:
The central frequency is the default present frequency setting (Settings of traverse operation are not active in Jog and close-loop
operation mode)
Note:
① Actual length(km)=﹛ counting value* Perimeter of axis(F9.18)/ Number of pulses per cycle(F9.19)﹜ * Ratio of
length(F9.16)/calibration coefficient of length(F9.17)/100/1000.
② Functions of F9.14~F9.19 are only valid for the drive of 45kW or below.
Group FA: Reserved Parameters
Parameter Name LCD Display Setting range Unit Factory setting Modification
FA.00~FA.11 Reserved RESERVED - - 0 *
Para. Name LCD Display Setting range Unit Factory setting Modif.
Number of polarities of MOTOR POLARITY
FH.00 2~14 2 4 ×
motor NUM
FH.01 Rated power RATED POWER 0.4~999.9kW 0.1kW Dependent on drive’s model ×
FH.02 Rated current RATED CURR 0.1~999.9A 0.1A Dependent on drive’s model ×
FH.03 Current without load CURR WITH NO LOAD 0.1~999.9A 0.1A Dependent on drive’s model ×
FH.04 Resistance of stator R1 STATOR RESIS R1 0.00%~50.00% 0.01% Dependent on drive’s model ○
FH.05 Leakage inductance X LEAKAGE INDUC X 0.00%~50.00% 0.01% Dependent on drive’s model ○
Para. Name LCD Display Setting range Unit Factory setting Modif.
FH.06 Resistance of rotor R2 ROTOR RESIS R1 0.00%~50.00% 0.01% Dependent on drive’s model ○
FH.07 Exciting inductance Xm MUTUAL INDUC Xm 0.0%~2000% 0.1% Dependent on drive’s model ○
Fn.01 Total operating time TOTAL RUN TIME 0~65.535K hours 0.001k hours 0 *
Fn.02 Temperature of heatsink 1 HEATSINK1 TEMP 0.0~100.0℃ 0.1 0℃ *
Fn.03 Temperature of heatsink 2 HEATSINK2 TEMP 0.0~100.0℃ 0.1 0℃ *
Parameter Name LCD Display Setting range Unit Factory setting Modification
Factory FACTORY Factory
FU.00 **** 1 -
password PASSWORD password
Appendix 2 Accessories
Notes: L1 e
Our company does not supply reactor and EMI filter, so
you should order them separately. The following models
have been tested on our drive. You can contact us if you
need them.
h
AC/DC Reactor
the power level, similar to the power level of the drive. Fig. A-2 Outline of 3-PH AC input and output reactor (b)
drive.
2. Sizes
h
The sizes of AC input reactor and output reactor are
n2 4- d n1
L2 b1
DC reactor
1. Model description
TDL-4DI01-0300, where 0300 denotes the power level, similar to the power level of the drive.
2. Sizes
The sizes of DC reactor are classified into two types, as shown in Fig. A-4 ~ Fig.A-5. See Table A-5 for the details.
L3 e
h
4- d n2 4- d n1
n2 n1 L2 b1
L1 b1 L1
Fig. A-4 Outline of DC reactor (a) Fig. A-5 Outline of DC reactor (b)
The 75kWG and larger drives with standard configurations have DC reactor. The models and parameters for reactors
1. Model description
DL-20EBT1, where DL denotes the power filter series of Changzhou Jianli Electronic Co.,Ltd., 20 denotes the rated
current, EB denotes the 3-PH 3-wire system, while T1 and K1 denotes the internal circuit structure.
2. Sizes
The sizes of EMI filter are shown in Fig. A-6. See Table A-6 for the details.
P
M
F
E
I
G
B
A J
C H
Manufacturer Information
AC/DC reactor
Address (head office): 3-20#, Yellow River Road, Economic and Technological Development Zone,
Address (Changzhou branch): Furong Industrial park, Wujin District, Changzhou City
Website: www.hslec.com
E-mail: [email protected]
EMI filter
Website: www.cnfilter.com
E-mail: [email protected]
1 Networking Mode
RS485
RS485
2 Interfaces
3 Communication Modes
The drive is a slave in the network. It communicates in ‘point to point’ mode. The drive will not response to the
Users can set the drive’s current address, baud rate and data format by using the drive’ keypad or through the serial
communication port.
The drive can report the current fault information when polled by the master.
EV2000 provides two interfaces: RS232 and RS485. Pay attention that the Jumper CN14 should be in correct position.
4 Protocol Format
ccoom
mmm aanndd fra
fr am
m ee ooff m
m aasste
terr
s e n d in g 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
seq u en ce
A B B C C D D E E F F F F I I I I J
d e fin itio n
head Add C o m m and index data setting verificatio n tail
s e n d in g 1 2 2 4 4 4 1
b y te
ccoommmm aanndd ffrraammee oo ff mmaasstt ee rr
s e n d in g 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
seq u en ce
A B B H H G G E E F F F F I I I I J
Where:
A: Frame head B: Slave address, C: Master command D: Auxiliary index E: Index or command F: Data setting
“Configuration data section” and “operation data section” may not exist in the concrete protocol frame. In that case, they
In the protocol, the effective characters are: ~, 0, 1, 2, 3, 4, 5, 6, 7, 8, 9, A, B, C, D, E, F and hex ODH. And the
The frame for effective command has 14 or 18 bytes. Sometimes, the response frame has 10 bytes, e.g. invalid
EV2000 supports commands of Group 3 and 4 for an interim period to be compatible with your previous developed
basic operating functions of the host software. It is suggested to use Group 6~7 commands instead of Group 3~4
5 Explanations of Format
Configuration range: “00”~”7F”. “7F” is broadcast address. The default of the drive is “01”.
Definition of Data: The response of slave to the command from the Master. Two Bytes. ASCII Format.
Classification of Parameters:
Command Code = “00”: Master drive asks Slave drive to feed back the current status(ready or not ready) and control
status.
Command Code="01"~"08"
Communication and control of slave are normal. The changes of parameters are valid. The password is correct.
The frame is verified to be incorrect. The data of “Command Section” and “Index Section overflow.
Incorrect Frame length/there are non-ASCII code except frame head and frame tail.
Note: Whether the response code reported is related with the current configuration status of the slave. Refer to the
notes of “command code = 5”. When reporting the response code, data in “command section”, “index section” and
The control command to the slave is inactive. The changes of parameters are invalid. The data in
Note: Whether the response code is reported is related with the current configuration status of the slave. Refer to the
notes of “command code = 5”. When reporting the response code, data in “command section”, “index section” and
“operation data section” will be reported according to the requirements of the protocol.
Meaning of Data: Auxiliary index bytes and command index bytes are included.
For the master, the auxiliary index and command index are used to cooperate with the master to accomplish concrete
functions.
For the slave, auxiliary index is used to report fault code. The command code will not be changed but reported directly.
Command code uses the lower two bytes, data range: “00”~”FF”.
Auxiliary code uses the higher two bytes, data range: “00”~”FF”.
The fault code of the slave will occupy “auxiliary index” byte, see Table A-7.
5.5 Checksum
Calculation method: To sum up the ASCII values of all the bytes from “slave address” to “operation data”.
In the following explanation, frame head 7E, frame tail OD, address and checksum are omitted. The format is ASCII
character.
without units
Preset rotating
01 00 05 None ~010100050187\r 1rpm
speed
Running line
01 00 06 None ~010100060188\r 0.01m/Min
speed
Preset line
01 00 07 None ~010100070189\r 0.01m/Min
speed
Close loop
feedback of
01 00 08 None ~01010008018A\r 0.01V
analog close
loop control
Close loop
setting of
01 00 09 None ~01010009018B\r 0.01V
analog close
loop control
External
01 00 0A None ~0101000A0193\r 1
counting value
Output torque 01 00 0B None ~0101000B0194\r 0.1%
Bit0~14, respectively are
X1~X8, Y1, Y2, TC, fan,
I/O status 01 00 0C None ~0101000C0195\r 1
Read the slave’s
REV
Present status 01 00 0D None ~0101000D0196\r 1 See table A-9
Operating
frequency after 01 00 14 None ~010100140187\r 0.01 Hz
compensation
limit
of the slave
Stop of slave 02 00 07 None ~01020007018A\r None
Jog operation of
02 00 08 None ~01020008018B\r None
slave
Forward jog
operation of 02 00 09 None ~01020009018C\r None
slave
Reverse jog
operation of 02 00 0A None ~0102000A0194\r None
slave
Stop the jog
operation of the 02 00 0B None ~0102000B0195\r None
slave
Reset the slave
02 00 0C None ~0102000C0196\r None
upon failure
Coast-to-stop of
02 00 0D None ~0102000D0197\r None
slave
Emergent stop
02 00 0E None ~0102000E0198\r None
of slave
Set the rate of 0~65535
analog output 02 00 13 0~FFFF ~0102001333330253\r mapping Set AO1 output to 20%
AO1 0~100%
Set the rate of 0~65535
analog output 02 00 14 0~FFFF ~0102001433330254\r mapping Set AO2 output to 20%
AO2 0~100%
Set the rate of 0~65535
digital output 02 00 15 0~FFFF ~0102001533330255\r mapping Set DO to 20%*F7.32 Hz
DO 0~100%
Ratio of
Set the frequency ratio to
frequency 02 00 16 0~7D0 ~0102001603E8026A\r 0.1%
100%
(preserved)
Set the terminal Bit0~12: The fictitious
status of 02 00 17 0~FFFF ~01020017FFFF02A3\r 1 terminals X1~X8, FWD,
fictitious control REV, Y1, Y2 and TC
By “Read parameters (Group No.+Index No.)” command, you can view all the parameters of the slave drive of EV2000
All the parameters of EV2000 series drives except the parameters whose property is ‘*’ and FP.02~FP.04 can be set.
See Appendix 1.
When setting the parameters, each value must be valid, e.g., when setting F9.00, “Operation data” in the
communication frame should be ASCII code, e.g. 0000, 0666 or 0543 is correct, while 0127 or 1000 is incorrect.
Otherwise, the result will be wrong. Please read the parameters carefully and determine its range before using.
Note:
The usages of group 7 and group 8 commands are the same. To avoid damaging EEPROM, the parameters changed frequently
should be saved in DSP RAM by group 8 commands if not necessarily written in EEPROM.
2) Example (Turbo C 2.0): Send the command of running the drive, stopping the drive and setting the frequency (need to
set F0.00=2, F0.03=2 first.)
#include <dos.h>
#include <bios.h>
#include <conio.h>
#include <stdio.h>
main()
sprintf(buf,"~%s%s\r",set_frequency,sum_of_cmd);
unsigned int i;
printf("\nSend(%s):",display_type);
outportb(PORT_ADDR,sendstr[i]);
sprintf(sum_string,"%04x",sum);
for(i=0;i<4;i++)
Emerson Netw ork Power Co., Ltd. Emerson Netw ork Power Co., Ltd.
Address: No.1 Kefa Rd., Science & Industry Park, Nanshan District 518057, Address: No.1 Kefa Rd., Science & Industry Park, Nanshan District 518057,
Customer Service Hotline: +86 755 86010581 Customer Service Hotline: +86 755 86010581
Complaint Hotline: +86 755 86010800 Complaint Hotline: +86 755 86010800
To Customers:
Thank you for choosing our products. We are expecting your comments about the quality of the products, so that we
can improve our work and serve you better. We really appreciate if you would fill in the form after the product has
operated for 1 month, and then mail or fax it to the Customer Service Center of Emerson Network Power. We will send
you an exquisite souvenir upon the receipt of the completed Product Quality Feedback Paper. You will receive a special
gift if you can give us any advices on improving the product and service quality.
E m e rs o n N e t wo rk P o w e r C o. , L t d.
Machine SN
Appearance or
structure
Performance
Package
Material
Quality problem
during usage
Suggestion about
improvement
Address: No.1 Kefa Rd., Science & Industry Park, Nanshan District 518057, Shenzhen China