S3498 PDF

Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

THE WALL-MOUNT™ SASO AIR CONDITIONERS

Models K36A & K60A Right-Side Control Panel


Models K36L & K60L Left-Side Control Panel For Export
37,500 to 57,500 Btuh Use Only
10.99 to 16.85 kW
The Bard Wall-Mount Air Conditioner is a self contained energy efficient
system, which is designed to offer maximum indoor comfort at a minimal
cost without using valuable indoor floor space or outside ground space.
This unit is the ideal product for versatile applications such as: new
construction, modular offices, school modernization, telecommunication
structures, portable structures or correctional facilities. Factory installed
accessories are available to meet specific job requirements.

Engineered Features
Aluminum Finned Copper Coils: Electrical Components:
Grooved tubing and enhanced louvered Are easily accessible for routine
fin for maximum heat transfer and inspection and maintenance through a
energy efficiency. Coated coils side, service panel opening. Features
available. a lockable, hinged access cover to the
circuit breaker or toggle disconnect
Twin Blowers: switch. Extreme Duty Door is standard
Move air quietly. Most models feature and Moderate Duty Door is optional.
multispeed blower motors providing
airflow adjustment for high and low Electric Heat Strips:
static operation. Motor overload Features an automatic limit and
protection is standard on all models. thermal cut-off safety control. Heater
packages are factory installed.
R-410A Refrigerant:
Designed with R-410A (HFC) non-ozone Filter Access Panel:
depleting refrigerant in compliance with Separate panel provides easy access for
the Montreal protocol. filter change.

Phase Rotation Monitor: Two Inch, Pleated Air Filters:


Standard on all 3 phase scroll Are standard equipment. K**L Left-Hand Unit Shown
compressors. Protects against
reverse rotation if power supply is not Condenser Fan and Motor
properly connected. Not required on Shroud Assembly: Compressor Control Module:
reciprocating compressors. Slides out for easy access. Fan motor Standard on all units. Built-in off-
is a sealed motor. delay timer adjustable from 30 seconds
Galvanized 20 Gauge Zinc Coated Steel to 5 minutes. 2-minute on-delay if
Cabinet: Built-in Circuit Breakers: power interrupt. 120-second bypass
Cleaned, rinsed, sealed and dried Standard on all versions of single for low pressure control, and both soft
before the polyurethane primer is (230/208 volt) equipment. Single and manual lockouts for high and low
applied. The cabinet is handsomely phase models pending. Toggle pressure controls. Alarm output for
finished with a baked on textured disconnects are standard on all versions alarm relay.
enamel, which allows it to withstand of three phase (400 volt) equipment.
1000 hours of salt spray tests per High & Low Pressure Switches are
ASTM B117-03. Stainless Steel Slope Top: Auto-Reset:
cabinets are also available. Standard feature for water run-off. Standard on all units. Built-in lockout
circuit resets from the room thermostat.
Foil Faced Insulation: Top Rain Flashing: Provides commercial quality protection
Standard on all units. Standard feature on all models. to the compressor.

Full Length Mounting Brackets: Freezestat: Low Ambient:


Built into cabinet for improved Standard on all Models. Standard on all units.
appearance and easy installation.
NOTE: Bottom mounting bracket Liquid Line Filter Drier: Alarm Relay:
included to assist in installation. Standard on all units. Protects system Standard on all units.
against moisture.

Bard is an
• Tested in accordance with SASO 2874/2016, SASO 2681, 2682. ISO 9001:2015
• Intertek ETL Tested to Standard IEC 60335-2-40:2002 (Fourth Edition) + Certified Manufacturer
A1:2005 (incl. Corr. 1:2006) + A2:2005 in conjunction with IEC 60335-1:2010
(Fifth Edition)
Form No. S3498-819
Supersedes S3498-1217
Page 1 of 5
Certified Capacity and Efficiency Ratings, Full Load Operation
MODELS K36A2/K36L2 K60A2/K60L2
Tier 1, Cooling BTUH (kW), 35-27/19  36,500 (10.69) 56,500 (16.55)
EER k 11.5 11.5
Rated CFM 1100 1650
Tier 3, Cooling BTUH (kW), 46-29/19  28,500 (8.35) 50,000 (14.65)
EER k 8.28 8.28
Rated CFM 1100 1650
Cooling BTUH (kW), 52-27/19 26,500 45,500 (13.33)
EER 7.2 7.0
Rated CFM 1100 1650
Cooling BTUH (kW), 55-27/19 j 24,500 (7.18) 43,000 (12.60)
EER k 6.5 6.2
Rated CFM 1100 1650
 Tested in accordance with SASO 2874/2016, SASO 2681, 2682.
 EER = Energy Efficiency Ratio – BTU/WATT efficiency.

Specifications 3-Ton through 5-Ton


K36A2-N K60A2-N
MODELS
K36L2-N K60L2-N
Electrical Rating 400-60-3 400-60-3
Operating Voltage Range 360-440 VAC 360-440 VAC
Compressor
Voltage 400-3 400-3
Rated Load Amps 4.9 7.5
Branch Circuit — Selection Current 5.5 8.0
Lock Rotor Amps 38 66
Compressor Type Reciprocating Scroll
Fan Motor
HP 1/3 1/2
Volts 400-1 400-1
Full Load Amps 1.3 2.3
CFM 2700 3000
Blower Motor
HP 1/2 1/2
Volts 400-1 400-1
Full Load Amps 0.6 1.3
Shipping Weight --LBS. 485 530

+ 75°C Wire
++ HACR type circuit breaker

Electrical Specifications – Circuit Ampacity


Single Circuit
Rated Volts, No. Field Power j k l l
MODEL
Hertz & Phase Circuits Minimum Circuit Maximum External Field Power Ground
Ampacity Fuse or Ckt. Brkr. Wire Size Wire
K36A2/L2-N0Z 1 8.2 10 14 14
400-60-3
-N06 1 9.8 15 14 14
K60A2/L2-N0Z 1 14.1 20 12 12
400-60-3
-N06 1 14.1 20 12 12
j These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electrical code (latest version), Article 310 for power conductor sizing.
k Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors.
l Based on 75C copper wire. All wiring must conform to the National Electrical Code and all local codes.

Form No. S3498-819


Supersedes S3498-1217
Page 2 of 5
Cooling Performance Table
Return Air
75°F 80°F 85°F 90°F 95°F 100°F 105°F 110°F 115°F 120°F 125°F 131ºF
Model (DB/WB) Cooling Capacity
24ºC 27ºC 30ºC 32ºC 35ºC 38ºC 41ºC 43ºC 46ºC 49ºC 51.6ºC 55ºC
l
75/62 F Total Cooling 40200 37900 35900 33800 31800 30000 28200 26400 24700 23000 21800 20400
24/17 C Sensible Cooling 30400 29300 28300 27300 26500 25600 24800 24000 23400 22700 21200 19500
80/67 F Total Cooling 42900 41300 39800 38200 36500 34900 33200 31500 29700 27900 26100 24100
K36
27/20 C Sensible Cooling 29500 28700 28000 27300 26700 26000 25400 24800 24300 23700 23200 22500
85/72 F Total Cooling 51100 48300 45700 43100 40600 38200 35800 33500 31200 29000 26900 24600
30/22 C Sensible Cooling 30200 29200 28200 27100 26200 25200 24200 23300 22400 21400 20600 19600
75/62 F Total Cooling 59000 56500 53900 51600 49200 47000 44900 42800 40900 38900 37100 35300
24/17 C Sensible Cooling 45200 44000 42700 41600 40500 39400 38400 37400 36400 35400 34500 33600
80/67 F Total Cooling 63000 61500 59900 58300 56500 54800 53000 51100 49200 47200 45200 43200
K60
27/20 C Sensible Cooling 43800 43100 42300 41600 40900 40100 39400 38600 37900 37100 36300 35500
85/72 F Total Cooling 75100 71900 68800 65800 62800 60000 57200 54400 51700 49100 46500 43900
30/22 C Sensible Cooling 44900 43800 42500 41300 40100 38800 37600 36200 34900 33500 32100 30700
Capacity Multiplier Factors
 Below 65°F, unit requires a factory or field installed low ambient control.
% of Rated Airflow -10 Rated +10
k Outdoor temperatures shown are measured at the condenser section air inlet. Total BTUH 0.975 1.0 1.02
l Return air temperature °F. Sensible BTUH 0.950 1.0 1.05

Form No. S3498-819


Supersedes S3498-1217
Page 3 of 5
Dimensions of Basic Unit for Architectural & Installation Requirements - Inches (mm)
WIDTH DEPTH HEIGHT SUPPLY RETURN
MODEL
(W) (D) (H) A B C B E G I J K L M N O P Q R S T
42.075 22.432 84.875 9.88 29.88 15.88 29.88 43.88 31.66 30.00 32.68 26.94 34.69 32.43 3.37 43.00 23.88 10.00 1.44 16.00 1.88
K36A/L
(1069) (570) (2156) (251) (759) (403) (759) (1115) (804) (762) (830) (684) (881) (824) (86) (1092) (607) (254) (37) (406) (48)
42.075 22.432 93.000 9.88 29.88 15.88 29.88 43.88 37.00 30.00 40.81 35.06 42.81 40.56 3.37 43.00 31.00 10.00 1.44 16.00 10.00
K60A/L
(1069) (570) (2362) (251) (759) (403) (759) (1115) (940) (762) (1037) (891) (1087) (1030) (86) (1092) (787) (254) (37) (406) (254)

All dimensions are in inches. Dimensional drawings are not to scale.

K**A Right-Hand Models BUILT IN


RAIN HOOD
4° PITCH E
D 2.13
W HEATER Side Wall O R
Mounting .44
ACCESS
PANEL Brackets
(Built In)
A SUPPLY AIR OPENING
ELECTRIC HEAT Top Rain
Flashing S
C. BREAKER/
DISCONNECT Shipping
ACCESS PANEL Location
(LOCKABLE) I S

Filter
Access Panel Optional
H Electrical
Entrances S
C RETURN AIR
OPENING
LOW VOLTAGE S
ELECTRICAL L
ENTRANCE J
Cond. M
G Condenser HIGH VOLTAGE Air K
Air Outlet P
ELECTRICAL Inlet S
ENTRANCE

Front View Side View 3/4" I.D. N Back View


DRAIN HOSE T
Q BOTTOM
INSTALLATION
BRACKET

K**L Left-Hand Models MIS-3666 A

E
BUILT IN
O 2.13 D RAIN HOOD
.44 R 4° PITCH W
HEATER
Side Wall ACCESS
Mounting SUPPLY AIR OPENING A
PANEL
Brackets S
(Built In) ELECTRIC HEAT
C. BREAKER/
Top Rain DISCONNECT
Flashing S I ACCESS PANEL
Shipping (LOCKABLE)
Location

Optional FILTER
Electrical S ACCESS PANEL
H
Entrances
RETURN AIR C
OPENING

S
LOW VOLTAGE
L Cond. ELECTRICAL
M J Air ENTRANCE G Condenser
P S K Inlet HIGH VOLTAGE Air Outlet
ELECTRICAL
ENTRANCE

N BACK VIEW T 3/4" I.D. SIDE VIEW FRONT VIEW


Q BOTTOM DRAIN HOSE
INSTALLATION
BRACKET
MIS-3665 A

Form No. S3498-819


Supersedes S3498-1217
Page 4 of 5
Air Conditioning Wall-Mount Model Nomenclature
K 36 A 2 N 0Z N P X X X J
SERIES | | CONTROL MODULES
KW  J - Low Ambient
NOMINAL REVISION Control & Alarm
CAPACITY | Relay
36 - 3 Ton A = Compressor & | COIL OPTIONS
60 - 5 Ton Controls - Right Side COLOR OPTIONS X - Standard
L = Compressor & VOLTS & PHASE VENTILATION OPTIONS X - Beige (Standard) 3 - Phenolic Coated Evaporator
Controls - Left Side N = 400-60-3 N - None 1 - White and Condenser
S - Stainless Steel

FILTER OPTIONS
P - 2-inch Pleated (MERV 8)

| CONTROL COVER DOOR


j See Electric Heat Chart Below
X - Extreme Duty Door
M - Moderate Duty Door

Electric Heat Table – Refer to Electrical Specifications for Availability by Unit Model

At 400V 
NOMINAL
KW 3-Phase
KW Btuh
Amps
06 6.25 9.0 21,331

k These electric heaters are available in 400V units only.

Bard Manufacturing Company, Inc. Due to our continuous product improvement policy, Form No.
Bryan, Ohio 43506 all specifications subject to change without notice. S3498
August 2019
Before purchasing this appliance, read important energy cost
www.bardhvac.com and efficiency information available from your retailer.
Supersedes: S3498-1217

Form No. S3498-819


Supersedes S3498-1217
Page 5 of 5

You might also like