WATER BALANCE

750 (from Borewells)


5 (backwash) 5 (backwash)

469 281
16 434 PSF RAW WATER
Reservoir

0
45
30
23 325 PSF
COOLING for floor washing Over Head 66
TOWER Tank
35 96
ACF
102
ANP 1 Domestic Sanitary Gardening
10 53 66 Industrial Cooling
32
REJECT R.O.
43 Cooling Tower 434
up
Cooling Tower Make-

Vapour 210 Evaporative Cond. 82


Process A: 516

39.5
41 1.5 PERMEATE
Condensate Domestic
Evapo. 82 De- Drinking Water &
Condencer Gassifier Canteen B: 10
21 22 Others
128
CATION-2 Sanitary 53
R.O Absorption
16 Tower Gardening 32
(VPC)
AN Floor Washing 1
ANION-2 C: 86

5*
11.2
5

5 AN PLANT Waste Heat Boiler 118


1.25*
DM water AN Plant analysers 10
10* storage PSFs Backwash 10
High TDS D: 138
Low TDS
Evaporator
solution
115 118 10 A+B+C+D : 750

Sludge 190

Wasteheat Conden- Analysers


112 DILUTION EFFLUENT boiler sate (ANP)
TANK 4+10* TANK Tank

3 72
116

Green Belt
* Indicates receipt of effluent once in 3 days All numericals are in M3 / day
POSITIONS OF THE WATER FLOW METERS :-
Cooling
FM 3 Tower
Make-up
FM 2
Overhead
Tank
(Domestic &
Sanitation)
Raw
Borewell
FM 1 Water
Storage
Analysers
REJECTS

DMW FM 7 Absorption
Storage Tower
RO Unit DGW
FM 4 FM 6 Boilers
Sump
FM 5 Evaporative
Condensor
Water Cess Rates :- Rs. per KL

Industrial Cooling & Boiler Feed 0.10


Domestic 0.03
Processing whereby water gets polluted and the pollutants are not easily bio-degradable and are toxic 0.30
Processing whereby water gets polluted and the pollutants are easily bio-degradable 0.20
WATER BALANCE
300 - 750 (from Borewells)
5 (backwash)
5
165 - 485 RAW WATER 135 - 265
165 - 395 PSF
Reservoir
Drift Evaporation 90
7 -20 110 - 285 PSF
COOLING Over Head
TOWER Tank
Evaporation 90 ACF
35 in
48 - 90 AN Plant
5-8 ANP Domestic Sanitary
10 50 30 - 60 Industrial Cooling
REJECT R.O.
30 - 43 Cooling Tower 165 -395
Vapour Drift 100 - 200 Evaporative Cond. 15 - 30
Process Evaporation 10 - 15 0.3 - 0.6 PERMEATE A: 180-425
Condensate 30 Domestic
5 - 15
Evaporation Evapo. 15 - 30 De- Drinking Water &
10-11 Gardening Condencer Gassifier Canteen B: 10
15 - 24
90 - 175 Others
VPC Absorption
CATION-2 Sanitary 50
Evaporator Tower
Gardening 35 - 45

ANION-2 C: 35 - 95

5*
11.2
Waste Heat Boiler 80 - 120
1.25*
DM water AN Plant analysers 10
10* storage PSFs Backwash 10
High TDS D: 80 - 140
Low TDS
Evaporator
solution
77 - 115 80 - 120 10 A+B+C+D : 295 - 670

128 - 190
Wasteheat Conden- Analys
DILUTION EFFLUENT boiler sate ers
CoolingTower Blow-Down 58 - 100 3+10*
TANK TANK Tank (ANP)

3 48 - 72
61 - 103

Green Belt
* Indicates receipt of effluent once in 3 - 5 days All numericals are in M3 / day
WATER BALANCE
300 - 750 (from Borewells)
5 (backwash)
5
170 - 560 RAW WATER 130 - 190
170 - 470 PSF
Reservoir
Drift Evaporation 90
7 -20 115 - 285 PSF
COOLING Over Head
TOWER Tank
Evaporation 90 ACF
35 in
48 - 90 AN Plant
5-8 ANP Domestic Sanitary
10 50 30 - 60 Industrial Cooling
REJECT R.O.
30 - 43 Cooling Tower 170 -470
Vapour Drift 100 - 130 Evaporative Cond. 15 - 30
Process Evaporation 10 - 15 0.3 - 0.6 PERMEATE A: 185-500
Condensate 30 Domestic
5 - 15
Evaporation Evapo. 15 - 30 De- Drinking Water &
10-11 Gardening Condencer Gassifier Canteen B: 10
15 - 24
85 - 100 Others
VPC Absorption
CATION-2 Sanitary 50
Evaporator Tower
Gardening 35 - 45

ANION-2 C: 35 - 95

5*
11.2
Waste Heat Boiler 80 - 120
1.25*
DM water AN Plant analysers 15
10* storage PSFs Backwash 10
High TDS D: 80 - 145
Low TDS
Evaporator
solution
77 - 115 80 - 120 15 A+B+C+D : 300 - 750

128 - 190
Wasteheat Conden- Analys
DILUTION EFFLUENT boiler sate ers
CoolingTower Blow-Down 58 - 100 3+10*
TANK TANK Tank (ANP)

3 48 - 72
61 - 113

Green Belt
* Indicates receipt of effluent once in 3 - 5 days All numericals are in M3 / day