Eaton PPTElectrical Design Considerationsfor 800 Vac Solar PVProjects 1
Eaton PPTElectrical Design Considerationsfor 800 Vac Solar PVProjects 1
PV Projects
Lawrence T. Connor
Senior Application Specialist
Renewable Energy
Eaton
[email protected]
Current Trends in AC Solar Collection Systems
• String inverters continue to act as a disruptive technology in large utility scale PV projects
• 660 to 800 Vac nominal system outputs with +10% maximum voltage ratings
• kW ratings have grown to 250 kW and will continue to grow higher
• Until now there have been limited commercially available 800 Vac collector solutions
• MCCBs with limited UL interrupting ratings up to 25 kAIC
• Now fused switches are available with interrupting ratings of 65 kAIC, which support:
• Expanded PV system design solutions
• Applications with larger transformer ratings up to 5000 KVA
• Lower project costs with fewer transformers and less infrastructure
• Short circuit calculations are important to confirm adequacy of OCPD (Overcurrent Protective
Device) interruption ratings as transformer KVA increases
Throat-Connected Solar Transformer & 800 Vac Recombiner Switchboard
800 Vac Switchboard Summary Ratings
• NEMA 1 Indoor & NEMA 3R Outdoor Enclosures
200 Amp
Fused Switch
with optional
visible
disconnect
viewing
windows
Eaton Bussmann 800 Vac NH Solar Fuses 32 to 400 Amps
Eaton recommends sizing OCPD collection
devices for 50C minimum service in
switchboard enclosures for thermal margin.
Sizing Fused Switches for String Inverters @ 50C In Enclosures
String Inverter 65 kAIC Fusible Switch NH Fuse Margin
Nominal Enclosure 50C Max Rating Enclosure 50C Max Rating OCPD
Max Nominal Max Nominal
Rating Rating Thermal @ 50C in Fuse Rating Thermal @50C in Thermal
Vendor Model Output Voltage Output Rating
@ 40 C Factor Factor Enclosure Size Factor Factor Enclosure Margin at 50C
(kW or KVA) (Vac +/-10%) (Amps) (Amps)
(Amps) (%) (%) (Amps) (%) (%) (Amps) Service
125-TL3 137.5 KVA 600 - 760 132.30 200 80% 90% 144 NH1 200 80% 94% 150.40 8.84%
PVS-175-TL-US 175 kW 800 134.00 200 80% 90% 144 NH1 200 80% 94% 150.40 7.46%
SG250HX-US 250 800 180.50 600 80% 90% 432 NH2 250 80% 94% 188.00 4.16%
255K-EHV-5G-US 255 800 184.00 600 80% 90% 432 NH2 250 80% 94% 188.00 2.17%
275 KVA 800 199.00 600 80% 90% 432 NH3 315 80% 94% 236.88 19.04%
(Planned 2021)
1659 300 KVA 690 279.00 600 80% 90% 432 NH3 400 80% 94% 300.80 7.81%
65 kAIC Interrupting Ratings Support the Use Of Transformers Up to 5000 KVA
800 Vac System Ratings
Transformer Data & Available Fault Current Collector Overcurrent Protective Devices MCCBs rated 25 kAIC limit
1,2,4 1,3,4
Full Load Amps
kA ISC * kA ISC * MCCBs Fused Switches applications to smaller
KVA @ 5.75% @ 5.175% 25 kAIC @ 800 Vac 65kAIC @ 880/509 Vac
@ 800 Vac
Nominal Z Min (-10%) Z UL Listing Certified
transformers approaching 1750
1000 722 12.56 13.95 25 kA 65 kA KVA, requiring more
1500 1,083 18.84 20.93 25 kA 65 kA transformers & infrastructure
1750 1,264 21.98 24.42 Short Circuit Study *5 65 kA
2000 1,444 25.11 27.91 65 kA
costs on PV projects.
2500 1,805 31.39 34.88 65 kA
2750 1,986 34.53 38.37 65 kA
3000 2,166 37.67 41.86 65 kA
3250 2,347 40.81 45.35 65 kA
3500 2,527 43.95 48.83 65 kA Fused switches rated 65 kAIC
4000 2,888 50.23 55.81 65 kA support larger transformer
4250 3,069 53.37 59.30 65 kA
Short Circuit Study *5
applications up to 5000 KVA,
4500 3,249 56.51 62.79
4750 3,430 59.65 66.27 reducing the number of project
5000 3,610 62.79 69.76 transformers & their associated
* Notes :
infrastructure costs.
1. Available utility back fed fault current. Does not include solar inveter fault contributions
2. Available fault at transformer secondary with a typical transformer @ nominal impedance of 5.75%.(Z)
3. Available fault at transformer secondary with a typical transformer @ minimum impedance of 5.175% (-10% Z )
4. Solar inverter fault contribution can be 1.5 to 2PU x Output Amps additional per inverter. (e.g. ~3kA for 16 250 KW Inverters)
5. Short circuit study recommended to determine OCPD adequacy based on transformer & cable impedance & inverter contribution
Throat-Connected 4080 KVA Transformer & Switchboard
4080 KVA Optimized Transformer 800 Vac NEMA 3R UL891 Low Voltage AC Collection Switchboard
• PV disconnect primary manual load break switch & visible contact viewing • 4000 amp throat-connection to transformer
window • 4000 amp density rated main bus
• Bay-O-Net expulsion & PRCL (Partial Range Current Limiting) fuses • Qty 16 collector switches with 250 amp fuses rated 65 kAIC
• Throat-connection to switchboard • Qty 2 switches with 32 amp fuses for auxiliary power & station service loads
Cable-Connected 5000 KVA Transformer & Switchboards
Installation Video:
https://www.eaton.com/Eaton/ProductsServices/Electrical/Markets/AlternativeEnergy/Solar/index.htm#tabs-3
Typical 800 Vac Collection Switchboard Dimensions
Transformer Secondary Arc Flash Zone
• Transformer low voltage secondaries are very high arc flash
risk zones
LV Air Terminal
• Transformer primary fuses protect the transformer primary Chamber for cable
windings and tank. The fuses react very slowly to secondary terminations to
arcing and ground faults because secondary faults have to downstream
Circuits. Requires
reflect through the transformer. Trip times may be up to 1 periodic access
second or higher. after installation
Pad MountororSubstation
Padmount SubstationLiquid-Filled
Liquid-FilledTransformers
Transformers
Integral CTs for Under-oil Integral
Integral VFI Motor
Interlocked Primary PTs Primary PTs Various Various
Integral Integral primary, CTs for Uninterrupt
Control VFI Motor Operator
Load Break 24Vdc Relay 24Vdc for&relay Power for Voltage gauges andgauges and
Vacuum Vacuum secondary,primary able&Power Operator –
Switch with – relay Relay control Battery (optionalalarm monitoring
Fault Fault or both secondary Supplymonitoring
local/remote
external flexibility Control power (relayBackup accessories
accessories
(optional)manual
Interrupter
Interrupter differential 50/51 (UPS) (optional)
viewing dependent) (optional)
reset(optional)
)
protectionProtection System
System
window
~52.2 cycles
Traditional primary fusing (Bayonet & PRCLF)
(870 ms)
• Arc flash energy calculations reveal that some transformer secondaries can present a
problem for access.
• If Incident energy is above 40 cal/cm2, LV & HV compartments are inaccessible until
upstream & downstream disconnect devices are opened.
ArcFlash Incident Energy Comparison
AR-VFI Transformer “Onboard” Relay Assembly
Lawrence T Connor
Senior Application Specialist
Renewable Energy
Eaton
[email protected]
“Thermal Management Considerations for AC Recombiner Switchboards”
• How will your design perform when site conditions approach & exceed record temperatures ? ? ! !
• Design with proper thermal margin to maximize system reliability and prevent equipment overheating &
OCPD nuisance operation
• Site characteristics & peak conditions (especially solar heat gain in enclosures) must be considered
• Applications can exceed UL enclosure design ratings (40C ambient / 65 C rise)
• Switchboard buses are often thermally undersized for the loading & conditions
• OCPDs are all at their highest loading at the same time during the peak of the solar day
• OCPDs (Especially MCCBs) are often densely packed in enclosures
• OCPDs are often thermally undersized without proper thermal rating factors
• OCPDs sized for 50C service in switchboard enclosures is a very good practice.
• OCPD and Switchboard terminal connections are rated for cables applied at 75C ampacities
• Size cables per NEC and apply NEC thermal rating factors
• E-mail [email protected] for a copy
Useful Application References
• Eaton Solar Website: https://www.eaton.com/Eaton/ProductsServices/Electrical/Markets/AlternativeEnergy/Solar
• Eaton 800 Vac Solar Collector Switchboards: PA083015EN/Z24302 (August 2020) Eaton’s 800 Vac Recombiner
Switchboard
• 800 Vac combiner equipment solutions are now available with testing to UL891 and third-party
certification. These UL891 switchboards employ switch and fuse component overcurrent protective
devices that provide demonstrated interruption ratings of 65 Ka at the maximum rated voltage of 880
Vac. The 65kA interruption performance is superior to molded case circuit breakers that are typically
limited to 25kA. The higher fuse interruption ratings of 65kA allow for the application of larger power
transformers from 1500 to 3000 KVA that are throat connected to the switchboard bus. This greatly
allows system design flexibility to reduce the number of power transformers and ac collection system
infrastructure, which drives down the total installed cost and increases system reliability.
• Typical single line diagrams of 800 Vac combiners will be presented from various solar projects to
show optimal UL891 switchboard and transformer combinations. The objective is to provide system
design standards for those who develop, design, specify, purchase, construct, and operate solar PV
systems.