D3G355GG0301 Eng
D3G355GG0301 Eng
D3G355GG0301 Eng
backward-curved, dual-intake
with housing (flange)
Nominal data
Type D3G355-GG03-01
Motor M3G112-IA
Phase 3~
Nominal voltage VAC 400
Nominal voltage range VAC 380 .. 480
Frequency Hz 50/60
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
D3G355-GG03-01 EC centrifugal fan - RadiFit
backward-curved, dual-intake
with housing (flange)
Technical description
Weight 37 kg
Fan size 355 mm
Rotor surface Painted black
Electronics housing material Die-cast aluminum
Impeller material Sheet aluminum
Housing material Sheet steel, galvanized
Motor suspension Motor mounted with brackets on one side
Direction of rotation Clockwise, viewed toward rotor
Degree of protection IP54
Insulation class "F"
Moisture (F) / Environmental (H) F3-1
protection class
Max. permitted ambient temp. +85 °C
for motor (transport/storage)
Min. permitted ambient temp. for -40 °C
motor (transport/storage)
Installation position Shaft horizontal or rotor on bottom; rotor on top on request
Condensation drainage holes On rotor side
Mode S1
Motor bearing Ball bearing
Technical features - Output 10 VDC, max. 10 mA
- Operation and alarm display
- External 24 V input (parameter setting)
- Alarm relay
- Integrated PID controller
- Power limit
- Motor current limitation
- PFC, passive
- RS-485 MODBUS-RTU
- Soft start
- EEPROM write cycles: 100,000 maximum
- Control input 0-10 VDC / PWM
- Control interface with SELV potential safely disconnected from supply
- Temperature derating
- Thermal overload protection for electronics/motor
- Line undervoltage / phase failure detection
EMC immunity to interference According to EN 61000-6-2 (industrial environment)
EMC interference emission According to EN 61000-6-3 (household environment), except EN 61000-3-2 for
professionally used equipment with a total rated power greater than 1 kW
Touch current according to IEC <= 3.5 mA
60990 (measuring circuit Fig. 4,
TN system)
Electrical hookup Via terminal box
Motor protection Thermal overload protector (TOP) internally connected
With cable Variable
Pollution degree 3
Protection class I (with customer connection of protective earth)
Conformity with standards CE
Comment Conformity with EN 61800-5-1 and EN 60335-1 in preparation
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
D3G355-GG03-01 EC centrifugal fan - RadiFit
backward-curved, dual-intake
with housing (flange)
Product drawing
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
D3G355-GG03-01 EC centrifugal fan - RadiFit
backward-curved, dual-intake
with housing (flange)
Connection diagram
reinforced insulation on supply side and basic insulation on control interface side (or
reinforced insulation on control interface side up to 250 VAC potential difference)
1 7 COM white 2 Status relay, floating status contact, break for failure; contact rating 250 VAC / 2 A (AC1) / min.
10 mA,
reinforced insulation on supply side and basic insulation on control interface side (or
reinforced insulation on control interface side up to 250 VAC potential difference)
2 9 +10 V red Fixed voltage output 10 VDC, SELV, +10 V ±3%, max. 10 mA, short-circuit-proof, power
supply for external devices (e.g. pot);
fixed voltage input 24 VDC for setting parameters via MODBUS without line voltage supply
2 10 0-10 V yellow Analog input (set value) SELV, 0-10 V, Ri = 100 kΩ, adjustable curve
2 11 RSA white RS485 interface for MODBUS, RSA; SELV
2 12 RSB brown RS485 interface for MODBUS, RSB; SELV
2 13 GND blue Reference ground for control interface, SELV
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
D3G355-GG03-01 EC centrifugal fan - RadiFit
backward-curved, dual-intake
with housing (flange)
ρ = 1.15 kg/m³ ± 2 %
Measurement: LU-174904-1
5
1200
Air performance measured according to ISO
4 5801 installation category A. For detailed
information on the measurement setup,
contact ebm-papst. Intake sound level:
Sound power level according to ISO 13347 /
4
12 7
2
400 11 2
16
6
15
1
10
14
Measured values
Wired U f n Ped I LpAin LwAin LwAout qv pfs qv pfs
V Hz min-1 W A dB(A) dB(A) dB(A) m3/h Pa CFM inH2O
1 Y 400 50 2600 2979 4.59 82 95 100 12035 0 7085 0.00
2 Y 400 50 2600 3160 4.90 80 93 97 10230 400 6020 1.61
3 Y 400 50 2600 3160 4.90 78 91 95 8035 750 4730 3.01
4 Y 400 50 2600 3040 4.68 76 89 93 5970 1100 3515 4.42
5 Y 400 50 2300 2029 3.13 78 92 97 10590 0 6235 0.00
6 Y 400 50 2300 2200 3.39 77 90 94 9065 318 5335 1.28
7 Y 400 50 2300 2163 3.33 75 87 92 7070 583 4160 2.34
8 Y 400 50 2300 2069 3.18 73 86 90 5250 858 3090 3.44
9 Y 400 50 1900 1144 1.76 74 87 92 8750 0 5150 0.00
10 Y 400 50 1900 1240 1.91 72 85 89 7490 217 4405 0.87
11 Y 400 50 1900 1219 1.88 70 83 87 5840 398 3435 1.60
12 Y 400 50 1900 1166 1.80 68 81 85 4340 586 2555 2.35
13 Y 400 50 1500 563 0.87 68 81 86 6905 0 4065 0.00
14 Y 400 50 1500 610 0.94 66 79 83 5910 135 3480 0.54
15 Y 400 50 1500 600 0.92 64 77 81 4610 248 2715 1.00
16 Y 400 50 1500 574 0.88 62 75 79 3425 365 2015 1.47
Wired = Wiring · U = Power supply · f = Frequency · n = Speed (rpm) · Ped = Power consumption · I = Current draw · LpAin = Sound pressure level intake side · LwAin = Sound power level intake side
LwAout = Sound power level outlet side · qv = Air flow · pfs = Pressure increase
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com