Medium Voltage Protection Setpoint List
Medium Voltage Protection Setpoint List
Medium Voltage Protection Setpoint List
PROJECT
DOCUMENT NAME
NE1-20-EM-JEP-LIS-BB_(R)-00003
Setpoint List
CONTENT
Rev No. 03
Medium Voltage Protection Setpoint List
Page 1 of 103
厂变压器及保护参数
额定容量( ) 低压侧额定电压( )
70MVA 6.9kV
H-L=9%
低压侧额定电流( ) 短路阻抗
1673A H-M=11.5%
Impedance
LV rated current( ) M-L=34.25%
低压侧 LV side:2000/1
CT
低压中性点 LV neutral line:600/1
PT
低压侧 LV side:
General
Definite-T 1:1-pole
661:11 No/yes No
operate allowed
661:26 Definite-T
661:26 No/yes No
1:Dynamic settings
1
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 2 of 103
Definite-T 1:Blk. w.
661:27 No/yes No
inrush curr. detect.
Definite-T 1:I0
661:120 No/yes No
elimination
Definite-T 1:Dropout
661:4 0.90 to 0.99 0.95
ratio
Definite-T 1:Dropout
661:101 0.00 s to 60.00 s 0.00s
delay
Definite-T 1:Operate
661:6 0.00 s to 100.00 s 0s
delay
General
Inverse-T 1:1-pole
691:11 No/yes No
operate allowed
Inverse-T 1:Dynamic
691:26 No/yes No
settings
Inverse-T 1:Blk. w.
691:27 No/yes No
inrush curr. detect.
2
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 3 of 103
Inverse-T 1:I0
691:120 No/yes No
elimination
Inverse-T 1:Type of
691:130 IEC V
character. curve
Instantaneous
691:131 Inverse-T 1:Reset Disk emulation
Disk emulation
Inverse-T 1:Additional
691:115 0.00 s to 60.00 s 0.00s
time delay
General
General:Current-flow
2311:104 Off/On Off
criterion
2311:103 General:Stabilization 0 to 10 0
counter
Definite-T 1
Phase-to-ground Phase-to
421:9 Definite-T 1:Measured
value Phase-to-phase -phase
3
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 4 of 103
Definite-T 1:Dropout
421:4 1.01 to 1.20 1.05
ratio
Definite-T 1
• off
_:181:1 Definite-T 1:Mode • on Off
• test
• 1 out of 3
_:181:101 Definite-T 1:Pickup 1 out of 3
mode • 3 out of 3
4
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 5 of 103
General
Inverse-T 1:Dynamic
781:26 No/yes No
settings
Inverse-T 1:Blk. w.
781:27 No/yes No
inrush curr. detect.
Instantaneous
781:109 Inverse-T 1:Reset Disk emulation
Disk emulation
Inverse-T 1:Additional
781:115 0.00 s to 60.00 s 0.00s
time delay
Note: Other functions of 7SJ82 setting Off and used default value.
5
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 6 of 103
额定电压( )
6.6kV PT
Rated voltage (
保护装置
7SJ82
Protect device
Definite-T 1
Definite-T 1:Pickup
181:101 1 out of 3/3 out of 3 1 out of 3
mode
Definite-T 1: Dropout
181:4 0.90 to 0.99 0.95
ratio
Definite-T 1: Operate
181:6 0.00s to 300.00s 2s
delay
Note: Other functions of 7SJ82 setting Off and used default value.
Definite-T 1
6
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 7 of 103
Definite-T 1:
421:2 No/yes No
Operate&flt.rec.blocked
Definite-T 1:Blk.bu
421:10 No/yes No
mead.-volt.failure
Definite-T 1: Phase-to-phase/phase-
421:9 Phase-to-phase
Measured value to-ground
Definite-T 1:Pickup
421:101 1 out of 3/3 out of 3 1 out of 3
mode
Definite-T 1:
421:4 1.01 to 1.20 1.05
Dropout ratio
Definite-T 1:
421:6 0.00s to 60.00s 9s
Operate delay
Note: Other functions of 7SJ82 setting Off and used default value.
7
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 8 of 103
额定功率( ) 额定电压( )
600kW 6.6kV
Rated power( ) Rated voltage( )
堵转电流( )
额定电流( )
61A 650%
Lock rotor current(
Rated current( )
)
启动时间
15s(hold) PT
Starting time
保护装置
7SJ82
Protect device
General
Definite-T 1:1-pole
661:11 No/yes No
operate allowed
661:26 Definite-T
661:26 No/yes No
1:Dynamic settings
8
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 9 of 103
Definite-T 1:Blk. w.
661:27 No/yes No
inrush curr. detect.
Definite-T 1:Dropout
661:4 0.90 to 0.99 0.95
ratio
Definite-T 1:Dropout
661:101 0.00 s to 60.00 s 0.00s
delay
Definite-T 1:Operate
661:6 0.00 s to 100.00 s 0.00s
delay
Note: Other functions of 7SJ82 setting Off and used default value.
General
Inverse-T 1:1-pole
691:11 No/yes No
operate allowed
Inverse-T 1:Dynamic
691:26 No/yes No
settings
Inverse-T 1:Blk. w.
691:27 No/yes No
inrush curr. detect.
9
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 10 of 103
Instantaneous
691:131 Inverse-T 1:Reset Disk emulation
Disk emulation
Inverse-T 1:Additional
691:115 0.00 s to 60.00 s 0.00s
time delay
Note: Other functions of 7SJ82 setting Off and used default value.
General
Inverse-T 1:Dynamic
781:26 No/yes No
settings
Inverse-T 1:Blk. w.
781:27 No/yes No
inrush curr. detect.
10
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 11 of 103
Instantaneous
781:109 Inverse-T 1:Reset Disk emulation
Disk emulation
Inverse-T 1:Additional
781:115 0.00 s to 60.00 s 0.00s
time delay
Note: Other functions of 7SJ82 setting Off and used default value.
11
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 12 of 103
额定功率( ) 额定电压( )
2600kW 6.6kV
Rated power( ) Rated voltage( )
堵转电流( )
额定电流( )
268A 650%
Lock rotor current (
Rated current( )
)
启动时间
30s(hold) PT
Starting time
General
12
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 13 of 103
Definite-T 1:Dropout
661:4 0.90 to 0.99 0.95
ratio
661:102 Definite-T 1:Pickup delay 0.00 s to 60.00 s 0s
Definite-T 1:Dropout
661:101 0.00 s to 60.00 s 0.00s
delay
Definite-T 1:Operate
661:6 0.00 s to 100.00 s 0.00s
delay
Note: Other functions of 7SJ82 setting Off and used default value.
General
Inverse-T 1:1-pole
691:11 No/yes No
operate allowed
Inverse-T 1:Dynamic
691:26 No/yes No
settings
Inverse-T 1:Blk. w.
691:27 No/yes No
inrush curr. detect.
13
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 14 of 103
Instantaneous
691:131 Inverse-T 1:Reset Disk emulation
Disk emulation
Inverse-T 1:Additional
691:115 0.00 s to 60.00 s 0.00s
time delay
Note: Other functions of 7SJ82 setting Off and used default value.
General
Inverse-T 1:Dynamic
781:26 No/yes No
settings
Inverse-T 1:Blk. w.
781:27 No/yes No
inrush curr. detect.
Instantaneous Disk
781:109 Inverse-T 1:Reset
Disk emulation emulation
Inverse-T 1:Additional
781:115 0.00 s to 60.00 s 0.00s
time delay
14
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 15 of 103
Note: Other functions of 7SJ82 setting Off and used default value.
15
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 16 of 103
额定容量 额定电压
2800kVA 6.6kV
Rated capacity Rated voltage of HV
额定电压 高压侧额定电流
0.42kV 244.9A
Rated voltage of LV Rated current of HV
低压侧额定电流 短路阻抗
3849A 8%
Rated current of LV Impedance
PT
KKS 14BBA10GS407/GS408
General
Definite-T 1:1-pole
661:11 No/yes No
operate allowed
661:26 Definite-T
661:26 No/yes No
1:Dynamic settings
Definite-T 1:Blk. w.
661:27 No/yes No
inrush curr. detect.
16
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 17 of 103
Definite-T 1:
661:3 0.030 A to 35.000 A 11.89A
Threshold
Definite-T 1:Dropout
661:4 0.90 to 0.99 0.95
ratio
Definite-T 1:Dropout
661:101 0.00 s to 60.00 s 0.00s
delay
Definite-T 1:Operate
661:6 0.00 s to 100.00 s 0.00s
delay
Note: Other functions of 7SJ82 setting Off and used default value.
General
Inverse-T 1:1-pole
691:11 No/yes No
operate allowed
Inverse-T 1:Dynamic
691:26 No/yes No
settings
Inverse-T 1:Blk. w.
691:27 No/yes No
inrush curr. detect.
17
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 18 of 103
Instantaneous
691:131 Inverse-T 1:Reset Disk emulation
Disk emulation
Inverse-T 1:Additional
691:115 0.00 s to 60.00 s 0.00s
time delay
Note: Other functions of 7SJ82 setting Off and used default value.
General
Inverse-T 1:Dynamic
781:26 No/yes No
settings
Inverse-T 1:Blk. w.
781:27 No/yes No
inrush curr. detect.
18
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 19 of 103
Disk emulation
Inverse-T 1:Additional
781:115 0.00 s to 60.00 s 0.00s
time delay
Note: Other functions of 7SJ82 setting Off and used default value.
19
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 20 of 103
额定容量 额定电压
2800kVA 6.6kV
Rated capacity Rated voltage of HV
额定电压 高压侧额定电流
0.42kV 244.9A
Rated voltage of LV Rated current of HV
低压侧额定电流 短路阻抗
3849A 8%
Rated current of LV Impedance
PT
KKS 14BBA10GS409
General
Definite-T 1:1-pole
661:11 No/yes No
operate allowed
661:26 Definite-T
661:26 No/yes No
1:Dynamic settings
Definite-T 1:Blk. w.
661:27 No/yes No
inrush curr. detect.
20
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 21 of 103
Definite-T 1:
661:3 0.030 A to 35.000 A 11.89A
Threshold
Definite-T 1:Dropout
661:4 0.90 to 0.99 0.95
ratio
Definite-T 1:Dropout
661:101 0.00 s to 60.00 s 0.00s
delay
Definite-T 1:Operate
661:6 0.00 s to 100.00 s 0.00s
delay
Note: Other functions of 7SJ82 setting Off and used default value.
General
Inverse-T 1:1-pole
691:11 No/yes No
operate allowed
Inverse-T 1:Dynamic
691:26 No/yes No
settings
Inverse-T 1:Blk. w.
691:27 No/yes No
inrush curr. detect.
21
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 22 of 103
Instantaneous
691:131 Inverse-T 1:Reset Disk emulation
Disk emulation
Inverse-T 1:Additional
691:115 0.00 s to 60.00 s 0.00s
time delay
Note: Other functions of 7SJ82 setting Off and used default value.
General
Inverse-T 1:Dynamic
781:26 No/yes No
settings
Inverse-T 1:Blk. w.
781:27 No/yes No
inrush curr. detect.
22
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 23 of 103
Inverse-T 1:Additional
781:115 0.00 s to 60.00 s 0.00s
time delay
Note: Other functions of 7SJ82 setting Off and used default value.
23
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 24 of 103
额定容量 额定电压
2800kVA 6.6kV
Rated capacity Rated voltage of HV
额定电压 高压侧额定电流
0.42kV 244.9A
Rated voltage of LV Rated current of HV
低压侧额定电流 短路阻抗
3849A 10%
Rated current of LV Impedance
PT
KKS 14BBA10GS410/GS411/GS412/GS413
General
Definite-T 1:1-pole
661:11 No/yes No
operate allowed
661:26 Definite-T
661:26 No/yes No
1:Dynamic settings
Definite-T 1:Blk. w.
661:27 No/yes No
inrush curr. detect.
24
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 25 of 103
Definite-T 1:Dropout
661:4 0.90 to 0.99 0.95
ratio
Definite-T 1:Dropout
661:101 0.00 s to 60.00 s 0.00s
delay
Definite-T 1:Operate
661:6 0.00 s to 100.00 s 0.00s
delay
Note: Other functions of 7SJ82 setting Off and used default value.
General
Inverse-T 1:1-pole
691:11 No/yes No
operate allowed
Inverse-T 1:Dynamic
691:26 No/yes No
settings
Inverse-T 1:Blk. w.
691:27 No/yes No
inrush curr. detect.
25
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 26 of 103
Instantaneous
691:131 Inverse-T 1:Reset Disk emulation
Disk emulation
Inverse-T 1:Additional
691:115 0.00 s to 60.00 s 0.00s
time delay
Note: Other functions of 7SJ82 setting Off and used default value.
General
Inverse-T 1:Dynamic
781:26 No/yes No
settings
Inverse-T 1:Blk. w.
781:27 No/yes No
inrush curr. detect.
Instantaneous Disk
781:109 Inverse-T 1:Reset
Disk emulation emulation
26
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 27 of 103
Inverse-T 1:Additional
781:115 0.00 s to 60.00 s 0.00s
time delay
Note: Other functions of 7SJ82 setting Off and used default value.
27
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 28 of 103
1.8 14BBA10GS501/502 (Closed circuit cooling water pump VSD 1/2) Protection Setting
额定功率( ) 额定电压( )
475kW 6.6kV
Rated power( ) Rated voltage( )
额定电流( ) 堵转电流( )
49A 650%
Rated current( ) Lock rotor current( )
启动时间
15s(hold) PT
Starting time
保护装置
7SK82
Protect device
General
Definite-T 1:1-pole
661:11 No/yes No
operate allowed
661:26 Definite-T
661:26 No/yes No
1:Dynamic settings
28
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 29 of 103
Definite-T 1:Dropout
661:4 0.90 to 0.99 0.95
ratio
Definite-T 1:Dropout
661:101 0.00 s to 60.00 s 0.00s
delay
Definite-T 1:Operate
661:6 0.00 s to 100.00 s 0.00s
delay
Note: Other functions of 7SK82 setting Off and used default value.
General
Inverse-T 1:1-pole
691:11 No/yes No
operate allowed
Inverse-T 1:Dynamic
691:26 No/yes No
settings
Inverse-T 1:Blk. w.
691:27 No/yes No
inrush curr. detect.
29
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 30 of 103
Instantaneous
691:131 Inverse-T 1:Reset Disk emulation
Disk emulation
Inverse-T 1:Additional
691:115 0.00 s to 60.00 s 0.00s
time delay
Note: Other functions of 7SK2 setting Off and used default value.
General
Definite-T 1:Dropout
1981:4 0.40 to 0.99 0.95
ratio
Definite-T 1:Blk. w.
1981:104 No/yes No
inrush curr. detect.
Definite-T 1:Dropout
1981:101 0.00 s to 60.00 s 0.00 s
delay
Definite-T 1:Operate
1981:6 0.00 s to 60.00 s 2.5s
delay
30
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 31 of 103
Note: Other functions of 7SK82 setting Off and used default value.
General
Inverse-T 1:Dynamic
781:26 No/yes No
settings
Inverse-T 1:Blk. w.
781:27 No/yes No
inrush curr. detect.
Instantaneous Disk
781:109 Inverse-T 1:Reset
Disk emulation emulation
Inverse-T 1:Additional
781:115 0.00 s to 60.00 s 0.00s
time delay
Note: Other functions of 7SK82 setting Off and used default value.
Setting
Addr. Parameter Setting Options Note
value
31
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 32 of 103
49 Th.overl. #
49 Th.overl. #:Imin
108 0.000 A to 10.000 A 0.250 A
cooling
Note: Other functions of 7SK82 setting Off and used default value.
Setting
Addr. Parameter Setting Options Note
value
Inverse-T 1
Rev No. 03
Medium Voltage Protection Setpoint List
Page 33 of 103
d
_:11551:10
Inverse-T 1:Max.locked 0.5s to 180.0s 2s
1 rotor time
Note: Other functions of 7SK82 setting Off and used default value.
厂变压器及保护参数
Parameters of GT and protection
额定容量( )
70MVA 中压侧额定电压( ) 11.3kV
Rated capacity( )
H-L=9%
中压侧额定电流( ) 短路阻抗
2555A H-M=11.5%
Impedance
MV rated current( ) M-L=34.25%
中压侧 MV side:4000/1
CT
中压中性点 MV neutral line:600/1
PT
中压侧 MV side:
保护装置
7SJ-82
Protect device
33
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 34 of 103
General
Definite-T 1:1-pole
661:11 No/yes No
operate allowed
661:26 Definite-T
661:26 No/yes No
1:Dynamic settings
Definite-T 1:Blk. w.
661:27 No/yes No
inrush curr. detect.
Definite-T 1:I0
661:120 No/yes No
elimination
Definite-T 1:Dropout
661:4 0.90 to 0.99 0.95
ratio
Definite-T 1:Dropout
661:101 0.00 s to 60.00 s 0.00s
delay
Definite-T 1:Operate
661:6 0.00 s to 100.00 s 0s
delay
General
34
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 35 of 103
Inverse-T 1:1-pole
691:11 No/yes No
operate allowed
Inverse-T 1:Dynamic
691:26 No/yes No
settings
Inverse-T 1:Blk. w.
691:27 No/yes No
inrush curr. detect.
Inverse-T 1:I0
691:120 No/yes No
elimination
Inverse-T 1:Type of
691:130 IEC V
character. curve
Instantaneous
691:131 Inverse-T 1:Reset Disk emulation
Disk emulation
Inverse-T 1:Additional
691:115 0.00 s to 60.00 s 0.00s
time delay
General
General:Current-flow
2311:104 Off/On Off
criterion
35
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 36 of 103
2311:103 General:Stabilization 0 to 10 0
counter
Definite-T 1
Phase-to-ground Phase-to
421:9 Definite-T 1:Measured
value Phase-to-phase -phase
Definite-T 1:Dropout
421:4 1.01 to 1.20 1.05
ratio
Definite-T 1
• off
_:181:1 Definite-T 1:Mode • on Off
• test
_:181:2 Definite-T 1:Operate & • no
no
flt.rec. blocked • yes
• phase-to-ground
_:181:9 Definite-T1:Measured phase-to-phase
value • phase-to-phase
36
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 37 of 103
• 1 out of 3
_:181:101 Definite-T 1:Pickup 1 out of 3
mode • 3 out of 3
General
Inverse-T 1:Dynamic
781:26 No/yes No
settings
Inverse-T 1:Blk. w.
781:27 No/yes No
inrush curr. detect.
Instantaneous
781:109 Inverse-T 1:Reset Disk emulation
Disk emulation
Inverse-T 1:Additional
781:115 0.00 s to 60.00 s 0.00s
time delay
Note: Other functions of 7SJ82 setting Off and used default value.
37
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 38 of 103
38
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 39 of 103
额定电压 额定电流
11kV 2044A
Rated voltage Rated current
CT 4000/1 零序 CT Zero CT /
综保
7SJ82 PT
Protect device
General
Definite-T 1:1-pole
661:11 No/yes No
operate allowed
661:26 Definite-T
661:26 No/yes No
1:Dynamic settings
Definite-T 1:Blk. w.
661:27 No/yes No
inrush curr. detect.
Definite-T 1:I0
661:120 No/yes No
elimination
Definite-T 1:Dropout
661:4 0.90 to 0.99 0.95
ratio
39
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 40 of 103
Definite-T 1:Dropout
661:101 0.00 s to 60.00 s 0.00s
delay
Definite-T 1:Operate
661:6 0.00 s to 100.00 s 0s
delay
General
Inverse-T 1:1-pole
691:11 No/yes No
operate allowed
Inverse-T 1:Dynamic
691:26 No/yes No
settings
Inverse-T 1:Blk. w.
691:27 No/yes No
inrush curr. detect.
Inverse-T 1:I0
691:120 No/yes No
elimination
Inverse-T 1:Type of
691:130 IEC V
character. curve
Instantaneous
691:131 Inverse-T 1:Reset Disk emulation
Disk emulation
40
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 41 of 103
Inverse-T 1:Additional
691:115 0.00 s to 60.00 s 0.00s
time delay
General
General:Current-flow
2311:104 Off/On Off
criterion
2311:103 General:Stabilization 0 to 10 0
counter
Definite-T 1
Phase-to-ground Phase-to
421:9 Definite-T 1:Measured
value Phase-to-phase -phase
Definite-T 1:Dropout
421:4 1.01 to 1.20 1.05
ratio
Definite-T 1
41
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 42 of 103
• off
_:181:1 Definite-T 1:Mode • on Off
• test
_:181:2 Definite-T 1:Operate & • no
no
flt.rec. blocked • yes
• phase-to-ground
_:181:9 Definite-T1:Measured phase-to-phase
value • phase-to-phase
• 1 out of 3
_:181:101 Definite-T 1:Pickup 1 out of 3
mode • 3 out of 3
General
Inverse-T 1:Dynamic
781:26 No/yes No
settings
Inverse-T 1:Blk. w.
781:27 No/yes No
inrush curr. detect.
42
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 43 of 103
Instantaneous
781:109 Inverse-T 1:Reset Disk emulation
Disk emulation
Inverse-T 1:Additional
781:115 0.00 s to 60.00 s 0.00s
time delay
Note: Other functions of 7SJ82 setting Off and used default value.
43
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 44 of 103
额定电压 额定功率
11kV 2112kW
Rated voltage Rated Power
额定电流 额定容量
138.6A 2640kVA
Rated current Rated Capacity
CT 200/1 零序 CT Zero CT -
综保
7SJ82 PT
Protect device
发电机两相短路时流过保护的最小短路电流
Short circuit current through protect device when 11kV EDG phase-
732A
phase fault
General
Definite-T 1:1-pole
661:11 No/yes No
operate allowed
661:26 Definite-T
661:26 No/yes No
1:Dynamic settings
Definite-T 1:Blk. w.
661:27 No/yes No
inrush curr. detect.
44
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 45 of 103
Definite-T 1:Dropout
661:4 0.90 to 0.99 0.95
ratio
Definite-T 1:Dropout
661:101 0.00 s to 60.00 s 0.00s
delay
Definite-T 1:Operate
661:6 0.00 s to 100.00 s 0.00s
delay
Note: Other functions of 7SJ82 setting Off and used default value.
General
Inverse-T 1:1-pole
691:11 No/yes No
operate allowed
Inverse-T 1:Dynamic
691:26 No/yes No
settings
Inverse-T 1:Blk. w.
691:27 No/yes No
inrush curr. detect.
45
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 46 of 103
Instantaneous
691:131 Inverse-T 1:Reset Disk emulation
Disk emulation
Inverse-T 1:Additional
691:115 0.00 s to 60.00 s 0.00s
time delay
Note: Other functions of 7SJ82 setting Off and used default value.
General
Inverse-T 1:Dynamic
781:26 No/yes No
settings
Inverse-T 1:Blk. w.
781:27 No/yes No
inrush curr. detect.
200/1C
781:3 Inverse-T 1:Threshold 0.010 A to 35.000 A 0.38A
T
Instantaneous
781:109 Inverse-T 1:Reset Disk emulation
Disk emulation
46
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 47 of 103
Inverse-T 1:Additional
781:115 0.00 s to 60.00 s 0.00s
time delay
Note: Other functions of 7SJ82 setting Off and used default value.
47
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 48 of 103
额定电压( )
11kV PT
Rated voltage (
保护装置
7SJ82
Protect device
Definite-T 1
Definite-T 1:Pickup
181:101 1 out of 3/3 out of 3 1 out of 3
mode
Definite-T 1: Dropout
181:4 0.90 to 0.99 0.95
ratio
Definite-T 1: Operate
181:6 0.00s to 300.00s 2s
delay
Note: Other functions of 7SJ82 setting Off and used default value.
Definite-T 1
48
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 49 of 103
Definite-T 1:
421:2 No/yes No
Operate&flt.rec.blocked
Definite-T 1:Blk.bu
421:10 No/yes No
mead.-volt.failure
Definite-T 1: Phase-to-phase/phase-
421:9 Phase-to-phase
Measured value to-ground
Definite-T 1:Pickup
421:101 1 out of 3/3 out of 3 1 out of 3
mode
Definite-T 1:
421:4 1.01 to 1.20 1.05
Dropout ratio
Definite-T 1:
421:6 0.00s to 60.00s 9s
Operate delay
Note: Other functions of 7SJ82 setting Off and used default value.
49
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 50 of 103
综保
7SJ82 PT
Protect device
KKS 10BBA10GS401/GS402/GS414/GS415
General
Definite-T 1:1-pole
661:11 No/yes No
operate allowed
661:26 Definite-T
661:26 No/yes No
1:Dynamic settings
Definite-T 1:Blk. w.
661:27 No/yes No
inrush curr. detect.
Definite-T 1:Dropout
661:4 0.90 to 0.99 0.95
ratio
Rev No. 03
Medium Voltage Protection Setpoint List
Page 51 of 103
delay
Definite-T 1:Operate
661:6 0.00 s to 100.00 s 0.00s
delay
Note: Other functions of 7SJ82 setting Off and used default value.
General
Inverse-T 1:1-pole
691:11 No/yes No
operate allowed
Inverse-T 1:Dynamic
691:26 No/yes No
settings
Inverse-T 1:Blk. w.
691:27 No/yes No
inrush curr. detect.
Instantaneous
691:131 Inverse-T 1:Reset Disk emulation
Disk emulation
Inverse-T 1:Additional
691:115 0.00 s to 60.00 s 0.00s
time delay
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 52 of 103
Note: Other functions of 7SJ82 setting Off and used default value.
General
Inverse-T 1:Dynamic
781:26 No/yes No
settings
Inverse-T 1:Blk. w.
781:27 No/yes No
inrush curr. detect.
Instantaneous
781:109 Inverse-T 1:Reset Disk emulation
Disk emulation
Inverse-T 1:Additional
781:115 0.00 s to 60.00 s 0.00s
time delay
Note: Other functions of 7SJ82 setting Off and used default value.
2.6 20BBA10GS410/423 (HTF Electrical Building Transformer 1/2) Protection Setting Table
额定容量 额定电压
2500kVA 11kV
Rated capacity Rated voltage of HV
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 53 of 103
额定电压 高压侧额定电流
0.42kV 131.2A
Rated voltage of LV Rated current of HV
低压侧额定电流 短路阻抗
3437A 7.5%
Rated current of LV Impedance
PT
General
Definite-T 1:1-pole
661:11 No/yes No
operate allowed
661:26 Definite-T
661:26 No/yes No
1:Dynamic settings
Definite-T 1:Blk. w.
661:27 No/yes No
inrush curr. detect.
Definite-T 1:Dropout
661:4 0.90 to 0.99 0.95
ratio
Rev No. 03
Medium Voltage Protection Setpoint List
Page 54 of 103
Definite-T 1:Dropout
661:101 0.00 s to 60.00 s 0.00s
delay
Definite-T 1:Operate
661:6 0.00 s to 100.00 s 0.00s
delay
Note: Other functions of 7SJ82 setting Off and used default value.
General
Inverse-T 1:1-pole
691:11 No/yes No
operate allowed
Inverse-T 1:Dynamic
691:26 No/yes No
settings
Inverse-T 1:Blk. w.
691:27 No/yes No
inrush curr. detect.
Instantaneous
691:131 Inverse-T 1:Reset Disk emulation
Disk emulation
Rev No. 03
Medium Voltage Protection Setpoint List
Page 55 of 103
time delay
Note: Other functions of 7SJ82 setting Off and used default value.
General
Inverse-T 1:Dynamic
781:26 No/yes No
settings
Inverse-T 1:Blk. w.
781:27 No/yes No
inrush curr. detect.
Instantaneous
781:109 Inverse-T 1:Reset Disk emulation
Disk emulation
Inverse-T 1:Additional
781:115 0.00 s to 60.00 s 0.00s
time delay
Note: Other functions of 7SJ82 setting Off and used default value.
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 56 of 103
综保
7SJ82 PT
Protect device
General
Definite-T 1:1-pole
661:11 No/yes No
operate allowed
661:26 Definite-T
661:26 No/yes No
1:Dynamic settings
Definite-T 1:Blk. w.
661:27 No/yes No
inrush curr. detect.
Definite-T 1:Dropout
661:4 0.90 to 0.99 0.95
ratio
Rev No. 03
Medium Voltage Protection Setpoint List
Page 57 of 103
delay
Definite-T 1:Operate
661:6 0.00 s to 100.00 s 0.00s
delay
Note: Other functions of 7SJ82 setting Off and used default value.
General
Inverse-T 1:1-pole
691:11 No/yes No
operate allowed
Inverse-T 1:Dynamic
691:26 No/yes No
settings
Inverse-T 1:Blk. w.
691:27 No/yes No
inrush curr. detect.
Instantaneous
691:131 Inverse-T 1:Reset Disk emulation
Disk emulation
Inverse-T 1:Additional
691:115 0.00 s to 60.00 s 0.00s
time delay
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 58 of 103
Note: Other functions of 7SJ82 setting Off and used default value.
General
Inverse-T 1:Dynamic
781:26 No/yes No
settings
Inverse-T 1:Blk. w.
781:27 No/yes No
inrush curr. detect.
Instantaneous
781:109 Inverse-T 1:Reset Disk emulation
Disk emulation
Inverse-T 1:Additional
781:115 0.00 s to 60.00 s 0.00s
time delay
Note: Other functions of 7SJ82 setting Off and used default value.
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 59 of 103
额定功率( ) 额定电压( )
2900kW 11kV
Rated power( ) Rated voltage( )
额定电流( ) 堵转电流( )
180A 650%
Rated current( ) Lock rotor current( )
启动时间
30s(hold) PT
Starting time
KKS 10BBA10GS404/405/406/407/417/418/419/420
保护装置
7SJ82
Protect device
General
Definite-T 1:1-pole
661:11 No/yes No
operate allowed
661:26 Definite-T
661:26 No/yes No
1:Dynamic settings
Rev No. 03
Medium Voltage Protection Setpoint List
Page 60 of 103
Definite-T 1:Dropout
661:4 0.90 to 0.99 0.95
ratio
Definite-T 1:Dropout
661:101 0.00 s to 60.00 s 0.00s
delay
Definite-T 1:Operate
661:6 0.00 s to 100.00 s 0.00s
delay
Note: Other functions of 7SJ82 setting Off and used default value.
General
Inverse-T 1:1-pole
691:11 No/yes No
operate allowed
Inverse-T 1:Dynamic
691:26 No/yes No
settings
Inverse-T 1:Blk. w.
691:27 No/yes No
inrush curr. detect.
Rev No. 03
Medium Voltage Protection Setpoint List
Page 61 of 103
Instantaneous
691:131 Inverse-T 1:Reset Disk emulation
Disk emulation
Inverse-T 1:Additional
691:115 0.00 s to 60.00 s 0.00s
time delay
Note: Other functions of 7SJ82 setting Off and used default value.
General
Inverse-T 1:Dynamic
781:26 No/yes No
settings
Inverse-T 1:Blk. w.
781:27 No/yes No
inrush curr. detect.
Instantaneous
781:109 Inverse-T 1:Reset Disk emulation
Disk emulation
Rev No. 03
Medium Voltage Protection Setpoint List
Page 62 of 103
Inverse-T 1:Additional
781:115 0.00 s to 60.00 s 0.00s
time delay
Note: Other functions of 7SJ82 setting Off and used default value.
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 63 of 103
Setting
额定功率( ) 额定电压( )
2700kW 11kV
Rated power( ) Rated voltage( )
额定电流( ) 堵转电流( )
167A 650%
Rated current( ) Lock rotor current( )
启动时间
30s(hold) PT
Starting time
保护装置
7SJ82
Protect device
General
Definite-T 1:1-pole
661:11 No/yes No
operate allowed
661:26 Definite-T
661:26 No/yes No
1:Dynamic settings
Rev No. 03
Medium Voltage Protection Setpoint List
Page 64 of 103
Definite-T 1:Dropout
661:4 0.90 to 0.99 0.95
ratio
Definite-T 1:Dropout
661:101 0.00 s to 60.00 s 0.00s
delay
Definite-T 1:Operate
661:6 0.00 s to 100.00 s 0.00s
delay
Note: Other functions of 7SJ82 setting Off and used default value.
General
Inverse-T 1:1-pole
691:11 No/yes No
operate allowed
Inverse-T 1:Dynamic
691:26 No/yes No
settings
Inverse-T 1:Blk. w.
691:27 No/yes No
inrush curr. detect.
Rev No. 03
Medium Voltage Protection Setpoint List
Page 65 of 103
Instantaneous
691:131 Inverse-T 1:Reset Disk emulation
Disk emulation
Inverse-T 1:Additional
691:115 0.00 s to 60.00 s 0.00s
time delay
Note: Other functions of 7SJ82 setting Off and used default value.
General
Inverse-T 1:Dynamic
781:26 No/yes No
settings
Inverse-T 1:Blk. w.
781:27 No/yes No
inrush curr. detect.
Instantaneous
781:109 Inverse-T 1:Reset Disk emulation
Disk emulation
Rev No. 03
Medium Voltage Protection Setpoint List
Page 66 of 103
Inverse-T 1:Additional
781:115 0.00 s to 60.00 s 0.00s
time delay
Note: Other functions of 7SJ82 setting Off and used default value.
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 67 of 103
额定电压 额定电流
11kV 33.1A
Rated voltage Rated current
综保
7SJ82 PT
Protect device
KKS 05BBA10GS101
General
Definite-T 1:1-pole
661:11 No/yes No
operate allowed
661:26 Definite-T
661:26 No/yes No
1:Dynamic settings
Definite-T 1:Blk. w.
661:27 No/yes No
inrush curr. detect.
Definite-T 1:Dropout
661:4 0.90 to 0.99 0.95
ratio
Rev No. 03
Medium Voltage Protection Setpoint List
Page 68 of 103
delay
Definite-T 1:Operate
661:6 0.00 s to 100.00 s 0.00s
delay
Note: Other functions of 7SJ82 setting Off and used default value.
General
Inverse-T 1:1-pole
691:11 No/yes No
operate allowed
Inverse-T 1:Dynamic
691:26 No/yes No
settings
Inverse-T 1:Blk. w.
691:27 No/yes No
inrush curr. detect.
Instantaneous
691:131 Inverse-T 1:Reset Disk emulation
Disk emulation
Inverse-T 1:Additional
691:115 0.00 s to 60.00 s 0.00s
time delay
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 69 of 103
Note: Other functions of 7SJ82 setting Off and used default value.
General
Inverse-T 1:Dynamic
781:26 No/yes No
settings
Inverse-T 1:Blk. w.
781:27 No/yes No
inrush curr. detect.
Instantaneous
781:109 Inverse-T 1:Reset Disk emulation
Disk emulation
Inverse-T 1:Additional
781:115 0.00 s to 60.00 s 0.00s
time delay
Note: Other functions of 7SJ82 setting Off and used default value.
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 70 of 103
CT 750/1 零序 CT Zero CT -
综保
7SJ82 PT
Protect device
General
Definite-T 1:1-pole
661:11 No/yes No
operate allowed
661:26 Definite-T
661:26 No/yes No
1:Dynamic settings
Definite-T 1:Blk. w.
661:27 No/yes No
inrush curr. detect.
Definite-T 1:Dropout
661:4 0.90 to 0.99 0.95
ratio
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 71 of 103
Definite-T 1:Dropout
661:101 0.00 s to 60.00 s 0.00s
delay
Definite-T 1:Operate
661:6 0.00 s to 100.00 s 0.00s
delay
Note: Other functions of 7SJ82 setting Off and used default value.
General
Inverse-T 1:1-pole
691:11 No/yes No
operate allowed
Inverse-T 1:Dynamic
691:26 No/yes No
settings
Inverse-T 1:Blk. w.
691:27 No/yes No
inrush curr. detect.
Instantaneous
691:131 Inverse-T 1:Reset Disk emulation
Disk emulation
Rev No. 03
Medium Voltage Protection Setpoint List
Page 72 of 103
Inverse-T 1:Additional
691:115 0.00 s to 60.00 s 0.00s
time delay
Note: Other functions of 7SJ82 setting Off and used default value.
General
Inverse-T 1:Dynamic
781:26 No/yes No
settings
Inverse-T 1:Blk. w.
781:27 No/yes No
inrush curr. detect.
750/1
781:3 Inverse-T 1:Threshold 0.010 A to 35.000 A 0.1A
CT
Instantaneous
781:109 Inverse-T 1:Reset Disk emulation
Disk emulation
Inverse-T 1:Additional
781:115 0.00 s to 60.00 s 0.00s
time delay
Note: Other functions of 7SJ82 setting Off and used default value.
Rev No. 03
Medium Voltage Protection Setpoint List
Page 73 of 103
Definite-T 1
Definite-T 1:Pickup
181:101 1 out of 3/3 out of 3 1 out of 3
mode
Definite-T 1: Dropout
181:4 0.90 to 0.99 0.95
ratio
Definite-T 1: Operate
181:6 0.00s to 300.00s 2s
delay
Note: Other functions of 7SJ82 setting Off and used default value.
Definite-T 1
Definite-T 1:Blk.by
421:10 No/yes yes
meas. -volt. failure
Definite-T 1:Pickup
421:101 1 out of 3/3 out of 3 1 out of 3
mode
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 74 of 103
Definite-T 1: Dropout
421:4 1.01 to 1.20 1.05
ratio
Definite-T 1:Operate
421:6 0.00s to 60.00s 9s
delay
Note: Other functions of 7SJ82 setting Off and used default value.
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 75 of 103
额定容量 额定电压
2500kVA 11kV
Rated capacity Rated voltage of HV
额定电压 高压侧额定电流
0.42kV 131.2A
Rated voltage of LV Rated current of HV
低压侧额定电流 短路阻抗
3437A 13%
Rated current of LV Impedance
PT
13BBA10GS401/GS402
KKS
13BBA20GS401/GS402
General
Definite-T 1:1-pole
661:11 No/yes No
operate allowed
661:26 Definite-T
661:26 No/yes No
1:Dynamic settings
Rev No. 03
Medium Voltage Protection Setpoint List
Page 76 of 103
Definite-T 1:Dropout
661:4 0.90 to 0.99 0.95
ratio
Definite-T 1:Dropout
661:101 0.00 s to 60.00 s 0.00s
delay
Definite-T 1:Operate
661:6 0.00 s to 100.00 s 0.00s
delay
Note: Other functions of 7SJ82 setting Off and used default value.
General
Inverse-T 1:1-pole
691:11 No/yes No
operate allowed
Inverse-T 1:Dynamic
691:26 No/yes No
settings
Inverse-T 1:Blk. w.
691:27 No/yes No
inrush curr. detect.
Rev No. 03
Medium Voltage Protection Setpoint List
Page 77 of 103
Instantaneous
691:131 Inverse-T 1:Reset Disk emulation
Disk emulation
Inverse-T 1:Additional
691:115 0.00 s to 60.00 s 0.00s
time delay
Note: Other functions of 7SJ82 setting Off and used default value.
General
Inverse-T 1:Dynamic
781:26 No/yes No
settings
Inverse-T 1:Blk. w.
781:27 No/yes No
inrush curr. detect.
Instantaneous
781:109 Inverse-T 1:Reset Disk emulation
Disk emulation
Rev No. 03
Medium Voltage Protection Setpoint List
Page 78 of 103
Inverse-T 1:Additional
781:115 0.00 s to 60.00 s 0.00s
time delay
Note: Other functions of 7SJ82 setting Off and used default value.
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 79 of 103
3.3 13BBA10/20 GS403/404/405/406/407/408 (COLD and HOT SALT PUMP VSD) Protection
Setting
额定功率( ) 额定电压( )
1400kW 11kV
Rated power( ) Rated voltage( )
额定电流( ) 堵转电流( )
85A 650%
Rated current( ) Lock rotor current( )
启动时间
30s(hold) PT
Starting time
保护装置
7SJ82
Protect device
General
Definite-T 1:1-pole
661:11 No/yes No
operate allowed
661:26 Definite-T
661:26 No/yes No
1:Dynamic settings
Rev No. 03
Medium Voltage Protection Setpoint List
Page 80 of 103
Definite-T 1:Dropout
661:4 0.90 to 0.99 0.95
ratio
Definite-T 1:Dropout
661:101 0.00 s to 60.00 s 0.00s
delay
Definite-T 1:Operate
661:6 0.00 s to 100.00 s 0.00s
delay
Note: Other functions of 7SJ82 setting Off and used default value.
General
Inverse-T 1:1-pole
691:11 No/yes No
operate allowed
Inverse-T 1:Dynamic
691:26 No/yes No
settings
Inverse-T 1:Blk. w.
691:27 No/yes No
inrush curr. detect.
Rev No. 03
Medium Voltage Protection Setpoint List
Page 81 of 103
Instantaneous
691:131 Inverse-T 1:Reset Disk emulation
Disk emulation
Inverse-T 1:Additional
691:115 0.00 s to 60.00 s 0.00s
time delay
Note: Other functions of 7SJ82 setting Off and used default value.
General
Inverse-T 1:Dynamic
781:26 No/yes No
settings
Inverse-T 1:Blk. w.
781:27 No/yes No
inrush curr. detect.
Rev No. 03
Medium Voltage Protection Setpoint List
Page 82 of 103
Disk emulation
Inverse-T 1:Additional
781:115 0.00 s to 60.00 s 0.00s
time delay
Note: Other functions of 7SJ82 setting Off and used default value.
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 83 of 103
Protection Setting
综保
P143 PT
Protect device
KKS 11BBA10/40GS001、11BBA1030/60GS002
DESCR
MENU TEXT COL ROW SETTING AVAILABLE OPTIONS
IPTION
0 = Disabled, 1 =
I>3 Status
35 40 Enabled Enabled
0 = Non-Directional, 1
Rev No. 03
Medium Voltage Protection Setpoint List
Page 84 of 103
DESCR
MENU TEXT COL ROW SETTING AVAILABLE OPTIONS
IPTION
Disabled
DT
IEC S Inverse
IEC V Inverse
IEC E Inverse
UK LT Inverse
UK Rectifier
RI
IEC V
IEEE M Inverse
I﹥2 Function 35 32 Inverse
IEEE V Inverse
IEEE E Inverse
US Inverse
US ST Inverse
[Indexed String]
Non- Non-Directional
is faulty **I1
[CourierNumber(current)]
Rev No. 03
Medium Voltage Protection Setpoint List
Page 85 of 103
[Courier Number(decimal)]
[Courier Number(decimal)]
DT
[Indexed String]
DT
[Indexed String]
DESCR
MENU TEXT COL ROW SETTING AVAILABLE OPTIONS
IPTION
Derived
GROUP1:EARTH
39 00 Earth
FAULT2
Fault
Derived
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 86 of 103
[Indexed String]
Disabled
DT
IEC S Inverse
IEC V Inverse
IEC E Inverse
UK LT Inverse
RI
IEC M Inverse
IEC V Inverse
IN2﹥1 Function 39 25 IEC V Inverse
IEC E Inverse
US Inverse
US ST Inverse
IDG
[Indexed String]
Non- Non-Directional
IN2﹥1 Direction 39 26
Directional [Indexed String]
of 0.01
IN2﹥1 Current 39 29 0.38
[Courier
Number(current)]
From 1 to 4 in steps of
0.1
IN2﹥1 IDG Is 39 2A 1
[Courier
Number(decimal)]
Rev No. 03
Medium Voltage Protection Setpoint List
Page 87 of 103
of 0.01
[Courier Number(time-
seconds)]
steps of 0.005
IN2﹥1 TMS 39 2D 0.16
[Courier
Number(decimal)]
steps of 0.01
IN2﹥1 Time Dial 39 2E 0.16
[Courier
Number(decimal)]
of 0.05
IN2﹥1 k(RI) 39 2F 1
[Courier
Number(decimal)]
From 1 to 2 in steps of
0.01
IN2﹥1 IDG Time 39 30 1
[Courier Number(time-
seconds)]
of 0.01
IN2﹥1 DT Adder 39 31 0
[Courier Number(time-
seconds)]
DT
[Indexed String]
of 0.01
[Courier Number(time-
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 88 of 103
seconds)]
DT
[Indexed String]
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 89 of 103
11kV 131.22A
Rated voltage Rated current
DESCR
MENU TEXT COL ROW SETTING AVAILABLE OPTIONS
IPTION
0 = Disabled, 1 =
I>3 Status
35 40 Enabled Enabled
0 = Non-Directional, 1
DESCR
MENU TEXT COL ROW SETTING AVAILABLE OPTIONS
IPTION
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 90 of 103
Disabled
DT
IEC S Inverse
IEC V Inverse
IEC E Inverse
UK LT Inverse
UK Rectifier
RI
IEC V
IEEE M Inverse
I﹥2 Function 35 32 Inverse
IEEE V Inverse
IEEE E Inverse
US Inverse
US ST Inverse
[Indexed String]
Non- Non-Directional
is faulty **I1
[CourierNumber(current)]
0.005
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 91 of 103
[Courier Number(decimal)]
[Courier Number(decimal)]
DT
[Indexed String]
DT
[Indexed String]
PT
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 92 of 103
KKS 11BBA10/20/30/40/50/60GT003
DESCR
MENU TEXT COL ROW SETTING AVAILABLE OPTIONS
IPTION
0 = Disabled, 1 =
I>3 Status
35 40 Enabled Enabled
0 = Non-Directional, 1
DESCR
MENU TEXT COL ROW SETTING AVAILABLE OPTIONS
IPTION
Inverse DT
IEC S Inverse
IEC V Inverse
IEC E Inverse
UK LT Inverse
UK Rectifier
RI
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 93 of 103
IEEE M Inverse
IEEE V Inverse
IEEE E Inverse
US Inverse
US ST Inverse
[Indexed String]
Non- Non-Directional
is faulty **I1
[CourierNumber(current)]
[Courier Number(decimal)]
[Courier Number(decimal)]
Rev No. 03
Medium Voltage Protection Setpoint List
Page 94 of 103
DT
[Indexed String]
DT
[Indexed String]
DESCR
MENU TEXT COL ROW SETTING AVAILABLE OPTIONS
IPTION
GROUP 1
38 00
EARTH FAULT 1
DT
IEC S Inverse
IEC V Inverse
IEC E Inverse
UK LT Inverse
RI
IEC M Inverse
IEC V Inverse
IEC E Inverse
US Inverse
US ST Inverse
IDG
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 95 of 103
[Indexed String]
Non- Non-Directional
IN1﹥1 Direction 38 26
Directional [Indexed String]
of 0.01
IN1﹥1 Current 38 29 0.38
[Courier
Number(current)]
From 1 to 4 in steps of
0.1
IN1﹥1 IDG Is 38 2A 1
[Courier
Number(decimal)]
of 0.01
IN1﹥1 Time Delay 38 2C 0
[Courier Number(time-
seconds)]
steps of 0.005
IN1﹥1 TMS 38 2D 0.16
[Courier
Number(decimal)]
steps of 0.01
IN1﹥1 Time Dial 38 2E 0.16
[Courier
Number(decimal)]
of 0.05
[Courier
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 96 of 103
Number(decimal)]
From 1 to 2 in steps of
0.01
IN1﹥1 IDG Time 38 30 1
[Courier Number(time-
seconds)]
of 0.01
IN1﹥1 DT Adder 38 31 0
[Courier Number(time-
seconds)]
DT
[Indexed String]
of 0.01
IN1﹥1 tRESET 38 33 0
[Courier Number(time-
seconds)]
DT
[Indexed String]
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 97 of 103
DESCR
MENU TEXT COL ROW SETTING AVAILABLE OPTIONS
IPTION
GROUP 1
42 00
VOLT PROTECTION
0=Phase-Phase
V< Measur't Mode 42 02 Phase-Phase
1=Phase-Neutral
0=Any Phase
V< Operate Mode 42 03 Any Phase
1=Three Phase
0=Disabled
2=IDMT
0 = Disabled or 1 =
V<1 Poledead Inh 42 08 Enabled
Enabled
0 = Disabled or 1 =
V<2 Status 42 09 Disabled
Enabled
OVERVOLTAGE
0=Phase-Phase
V> Measur't Mode 42 0E Phase-Phase
1=Phase-Neutral
Rev No. 03
Medium Voltage Protection Setpoint List
Page 98 of 103
1=Three Phase
0=Disabled
V>1 Function 42 10 DT
1=DT 2=IDMT
0 = Disabled or 1 =
V>2 Status 42 14 Disabled
Enabled
DESCR
MENU TEXT COL ROW SETTING AVAILABLE OPTIONS
IPTION
GROUP 1
3B 00
RESIDUAL O/V NVD
0 = Disabled, 1 = DT or
VN>1 Function 3B 02 DT
2 = IDMT
1V to 80V step 1V
VN>1 Voltage Set 3B 03 15V Alarm
4V to 320V step 4V
0 = Disabled or 1 =
VN>2 Status 3B 06 Disabled
Enabled
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 99 of 103
厂光伏变压器及保护参数
Parameters of PAT and protection
额定容量( ) 高压侧额定电压( )
40MVA 33kV
低压侧额定电压( ) 高压侧额定电流( )
11.3kV 699.8A
低压侧额定电流( ) 短路阻抗
2044A 10%
Impedance
LV rated current( )
高压侧 HV side:1500/1
CT 低压侧 LV side:4000/1
高压侧 HV side:
PT
低压侧 LV side:
87LT/50/51
RED-670
保护装置 87TN /51N/24/50BF
General
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 100 of 103
General:MU-ID Side
_:2311:151 0 to 100 1
1Mp3ph 1
General:MU-ID Side
_:2311:156 0 to 100 2
2Mp3ph 1
General:MU-ID Side
_:2311:160 0 to 100 3
2Mp1ph 1
General:MU-ID Side
_:2311:158 0 to 100 6
2Mp3ph 3
General
off
_:11041:1 I-DIFF:Mode on on
test
I-
no
_:11041:2 DIFF:Operate&flt.rec.block no
yes
ed
Operate curve
Starting detection
•no
_:11041:106 I-DIFF:Starting detection yes
•yes
I-DIFF:Thresh. startup
_:11041:107 0.1 I/IrObj to 2.0 I/IrObj 0.2 I/IrObj
detection
I-DIFF:Factor
_:11041:108 1.0 to 5.0 1.0
increasingchar.
Rev No. 03
Medium Voltage Protection Setpoint List
Page 101 of 103
Start.time
DC offset detection
I-DIFF:Factor
_:11041:110 1.0 to 5.0 2.3
increasingchar. DC
Inrush blocking
I-DIFF:2nd harmonic
_:11041:116 10 % to 45 % 15 %
content
I-DIFF:Crossblock. time
_:11041:117 0.00 s to 200.00 s;∞ 0.11 s
2ndhar.
•no
_:11041:118 I-DIFF:Blocking with CWA no
•yes
Overexcit.blocking
I-DIFF:3rd
_:11041:122 10 % to 80 % 30 %
harmonicscontent
I-DIFF:Crossblock. time
_:11041:123 0.00 s to 200.00 s;∞ 0.00 s
3rdhar.
I-DIFF:5th
_:11041:125 10 % to 80 % 25 %
harmonicscontent
I-DIFF:Crossblock. time
_:11041:126 0.00 s to 200.00 s;∞ 0.11 s
5thhar.
I-DIFF:LimitIdiff 3.,
_:11041:127 0.5 I/IrObj to 20.0 I/IrObj 1.5 I/IrObj
5.harmonics
Ext. faultdetection
Rev No. 03
Medium Voltage Protection Setpoint List
Page 102 of 103
onstabiliz.
I-DIFF:Time of add-
_:11041:129 0.00 s to 5.00 s;∞ 0.30 s
onstabiliz.
I-DIFF:Cross-blk. time
_:11041:130 0.00 s to 2.00 s;∞ 0.30 s
add-on st.
I-DIFF fast
•off
•test
I-DIFF
•no
_:11071:100 fast:Operate&flt.rec.blocke no
•yes
d
•off
•on
Definite-T •no
Definite- •no
Rev No. 03
Medium Voltage Protection Setpoint List
Page 103 of 103
•off
•on
Inverse-T 1
• off
• on
Inverse-T 1:1-pole • no
Inverse-T 1:Dynamic • no
• no
Rev No. 03
Medium Voltage Protection Setpoint List
Page 104 of 103
character.curve
• instantaneous
Inverse-T 1:Additional
Definite-T 1
off
on
Definite-T 1:Operate&flt.rec. no
off
on
Therm.charact.:Operate&flt.re no
Therm.charact.:Coolingtime
Rev No. 03
Medium Voltage Protection Setpoint List
Page 105 of 103
87N REF #
off
test
_:103 87N REF #:Threshold 0.05 I/IrObjto 2.00 I/IrObj 0.30 I/IrObj
General
•off
•on
Inverse-T 1:Type of
Rev No. 03
Medium Voltage Protection Setpoint List
Page 106 of 103
• disk emulation
General
•off
•on
• no
• no
Rev No. 03
Medium Voltage Protection Setpoint List
Page 107 of 103
#:Minimum operate time
Rev No. 03
Medium Voltage Protection Setpoint List
Page 108 of 103
厂光伏变压器及保护参数
Parameters of PAT and protection
高压侧额定电压(
额定容量( )
40MVA ) 33kV
Rated capacity( )
HV rated voltage( )
低压侧额定电压(
高压侧额定电流( )
) 11.3kV 699.8A
HV rated current( )
LV rated voltage( )
低压侧额定电流( ) 短路阻抗
2044A 10%
Impedance
LV rated current( )
高压侧 HV side:1500/1
CT 低压侧 LV side:4000/1
高压侧 HV side:
PT
低压侧 LV side:
87LT/50/51
RED-670
保护装置 87TN /51N/24/50BF
Rev No. 03
Medium Voltage Protection Setpoint List
Page 109 of 103
Off
Operation - - On
On
Off
NegSeqDiffEn - - Off
On
No
CrossBlockEn - - No
Yes
Off
ChargCurEnable - - Off
On
Off
AddDelay - - Off
On
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC inv.
Rev No. 03
Medium Voltage Protection Setpoint List
Page 110 of 103
Programmable
RI type
RD type
Off
OpenCTEnable On
On
Off
OCTBlockEn On
On
Selection of one
of the
GlobalBaseSel 1 - 12 1 1
GlobalBase
Valuegroups
3 3-Ph CT sets
connected
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 111 of 103
to diff protection
Off/On for
elimination of
Off
ZerSeqCurSubtr Off zero seq. from
On
diff. and bias
curr
No Transf A Power
1 transformer A
TraAOnInpCh 1
2 applied on input
3 channel X
Transformer A
rated voltage
winding 1 (HV
winding)
Transformer A
rated voltage
RatVoltW2TraA 1.0 - 9999.9 kV 0.1 11
(kV) on winding
2 (LV winding)
Rev No. 03
Medium Voltage Protection Setpoint List
Page 112 of 103
No Transf B Power
1 No Transf transformer B
TraBOnInpCh
2 B applied on input
3 channel X
Off
Operation - - On IB=4000
On
2 out of 3
OpMode 1 out of 3
1 out of 3
Operation Off/On - - On
AngleRCA 40 - 65 Deg 1 55
AngleROA 40 - 89 Deg 1 80
2 out of 3
3 out of 3
Non-directional
Forward
Reverse
inv./ANSI Very
inv./ANSI Norm.
inv./ANSI Mod.
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 113 of 103
inv./ANSI Def.
Time/L.T.E.
inv./L.T.V. inv./L.T.
inv./IEC Norm.
inv./IEC Very
inv./IEC inv./IEC
inv./IEC L.T.
inv./IEC Def.
Time/Reserved/Pr
ogrammable/RI
type/RD type
directional/
Forward/Reverse
Non-directional
Forward
Reverse
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 114 of 103
inv./ANSI Very
inv./ANSI Norm.
inv./ANSI Mod.
inv./ANSI Def.
Time/L.T.E.
inv./L.T.V. inv./L.T.
inv./IEC Norm.
inv./IEC Very
inv./IEC inv./IEC
inv./IEC L.T.
inv./IEC Def.
Time/Reserved/Pr
ogrammable/RI
type/RD type
directional/
Forward/Reverse
Operation Off - - On
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 115 of 103
On
Current
Current/Contact
LatchedStart
FollowStart
StartMode LatchedStart
FollowStart&Mod
2 out of 4
1 out of 4
Off
Always
Off
Operation - - On
On
Rev No. 03
Medium Voltage Protection Setpoint List
Page 116 of 103
Off
Operation - - On Operation Off / On
On
V/Hz> 100.0 - 180.0 %UB/f 0.1 110.0 load and rated freq in % of
(Ubase/frated)
(Ubase/frated)
Rev No. 03
Medium Voltage Protection Setpoint List
Page 117 of 103
Uni
Name Values (Range) Step Setting Description
t
PosSeq
L1L2
MeasuredU - - L1L2 Selection of measured voltage
L2L3
L3L1
L1L2
L2L3
MeasuredI - - L1L2 Selection of measured current
L3L1
PosSeq
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 118 of 103
额定电压( )
33kV PT
Rated voltage( )
保护装置
7SD82 CT 1500/1
Protect device
I-DIFF
Off
3451:1 I-DIFF: Mode On
On
I-DIFF: Thresh.
3451:101 0.100A to 20.000A 1.7A
Switch onto fault
I-DIFF: Operate
3451:6 0.00s to 60.00s 0.00s
delay
I-DIFF fast
Off
3481:1 I-DIFF fast: Mode On
On
I-DIFF fast:
3481:3 0.100A to 20.000A 3.5A
Threshold
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 119 of 103
General 1
Off
Test
Inverse-T 1:
No
_:691:2 Operate & flt. Rec. No
Yes
blocked
Inverse-T 1:1-pole
No
_:691:11 operate allowed No
Yes
Inverse-T 1: No
_:691:26 No
Dynamic settings Yes
Inverse-T 1:
Fundamental comp.
_:691:8 Method of Fundamental
RMS value
measurement
Inverse-T 1:
_:691:3 0.030A to 35.000A 0.58A
Threshold
Inverse-T 1:Type of
curve
Inverse-T 1:Min.
_:691:113 0.00 s to 1.00 s 0.0s
time of the curve
instantaneous
_:691:131 Inverse-T 1:Reset disk emulation
disk emulation
Inverse-T 1:Time
_:691:101 0.00 to 15.00 0.3
dial
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 120 of 103
Inverse-T
time delay
50BF Ad.CBF #
1 #:Holding On On
50BF Ad.CBF
No
105 #:Holding No
Yes
int. start signal
50BF Ad.CBF
no
106 #:Holding no.
yes
ext. start signal
50BF Ad.CBF no
parallel start
108 #:Retrip start T2 after T1
T2, T1
after T1 parallel start T2, T1
50BF Ad.CBF
phase current
Rev No. 03
Medium Voltage Protection Setpoint List
Page 121 of 103
#:Threshold
sensitive
50BF Ad.CBF
50BF Ad.CBF
50BF Ad.CBF
operate time
50BF Ad.CBF
50BF Ad.CBF
I2 dir. release
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 122 of 103
额定电压( )
33kV PT
Rated voltage( )
保护装置
7SL82 CT 1000/1
Protect device
(1)IDiff Stage
Addr. Parameter Setting Options Setting value Note
I-DIFF
Off
3451:1 I-DIFF: Mode On
On
I-DIFF: Thresh.
3451:101 0.100A to 20.000A 2.55A
Switch onto fault
I-DIFF: Operate
3451:6 0.00s to 60.00s 0.00s
delay
I-DIFF fast
Off
3481:1 I-DIFF fast: Mode On
On
Rev No. 03
Medium Voltage Protection Setpoint List
Page 123 of 103
Threshold
General 1
Off
Test
Inverse-T 1:
No
_:691:2 Operate & flt. Rec. No
Yes
blocked
Inverse-T 1:1-pole
No
_:691:11 operate allowed No
Yes
Inverse-T 1: No
_:691:26 No
Dynamic settings Yes
Inverse-T 1:
Fundamental comp.
_:691:8 Method of Fundamental
RMS value
measurement
Inverse-T 1:
_:691:3 0.030A to 35.000A 0.87A
Threshold
Inverse-T 1:Type of
curve
Inverse-T 1:Min.
_:691:113 0.00 s to 1.00 s 0.0s
time of the curve
instantaneous
_:691:131 Inverse-T 1:Reset disk emulation
disk emulation
Rev No. 03
Medium Voltage Protection Setpoint List
Page 124 of 103
dial
Inverse-T
time delay
50BF Ad.CBF #
1 #:Holding On On
50BF Ad.CBF
No
105 #:Holding No
Yes
int. start signal
50BF Ad.CBF
no
106 #:Holding no.
yes
ext. start signal
50BF Ad.CBF no
parallel start
108 #:Retrip start T2 after T1
T2, T1
after T1 parallel start T2, T1
50BF Ad.CBF
phase current
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 125 of 103
50BF Ad.CBF
sensitive
50BF Ad.CBF
50BF Ad.CBF
50BF Ad.CBF
operate time
50BF Ad.CBF
50BF Ad.CBF
I2 dir. release
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 126 of 103
线路及保护参数
Parameters of line and protection
额定电压( ) 额定电流( )
33kV 699.8A
1000/1(Phase)
CT
50/1(Zero)
PT
保护装置 87LT/50/51/21/21N/67/67N
RED-670
Protect device 59N/51N/50BF
Off
Operation - - On
On
Off
NegSeqDiffEn - - Off
On
No
CrossBlockEn - - No
Yes
Off
ChargCurEnable - - Off
On
Off
AddDelay - - Off
On
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 127 of 103
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Def.
CurveType IEC Norm. inv.
Time
IEC Very inv.
IEC inv.
Programmable
RI type
RD type
Rev No. 03
Medium Voltage Protection Setpoint List
Page 128 of 103
Off
OpenCTEnable On
On
Off
OCTBlockEn On
On
Selection of one
of the
GlobalBaseSel 1 - 12 1 1
GlobalBase
Valuegroups
Total number of
2 3-Ph CT sets
NoOfUsedCTs 2
3 connected
to diff protection
Off/On for
elimination of
Off
ZerSeqCurSubtr Off zero seq. from
On
diff. and bias
curr
No Transf A Power
1 transformer A
TraAOnInpCh 1
2 applied on input
3 channel X
rated voltage
(kV) on
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 129 of 103
winding 1 (HV
winding)
Transformer A
rated voltage
RatVoltW2TraA 1.0 - 9999.9 kV 0.1 11
(kV) on winding
2 (LV winding)
0 [0 deg]
No Transf B Power
1 No Transf transformer B
TraBOnInpCh
2 B applied on input
3 channel X
Operation Off/On - - On
AngleRCA 40 - 65 Deg 1 55
AngleROA 40 - 89 Deg 1 80
Rev No. 03
Medium Voltage Protection Setpoint List
Page 130 of 103
2 out of 3
3 out of 3
Non-directional
Forward
Reverse
inv./ANSI Very
inv./ANSI Norm.
inv./ANSI Mod.
inv./ANSI Def.
Time/L.T.E.
inv./L.T.V. inv./L.T.
inv./IEC Norm.
inv./IEC Very
inv./IEC inv./IEC
inv./IEC L.T.
inv./IEC Def.
Time/Reserved/Pr
ogrammable/RI
type/RD type
directional/
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 131 of 103
Forward/Reverse
inv./ANSI Very
inv./ANSI Norm.
inv./ANSI Mod.
inv./ANSI Def.
Time/L.T.E.
inv./L.T.V. inv./L.T.
inv./IEC Norm.
inv./IEC Very
inv./IEC inv./IEC
inv./IEC L.T.
inv./IEC Def.
Time/Reserved/Pr
ogrammable/RI
type/RD type
directional/
Forward/Reverse
inv./ANSI Very
inv./ANSI Norm.
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 132 of 103
inv./ANSI Mod.
inv./ANSI Def.
Time/L.T.E.
inv./L.T.V. inv./L.T.
inv./IEC Norm.
inv./IEC Very
inv./IEC inv./IEC
inv./IEC L.T.
inv./IEC Def.
Time/Reserved/Pr
ogrammable/RI
type/RD type
directional/
Forward/Reverse
inv./ANSI Very
inv./ANSI Norm.
inv./ANSI Mod.
inv./ANSI Def.
Time/L.T.E.
inv./L.T.V. inv./L.T.
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 133 of 103
inv./IEC Norm.
inv./IEC Very
inv./IEC inv./IEC
inv./IEC L.T.
inv./IEC Def.
Time/Reserved/Pr
ogrammable/RI
type/RD type
Non-directional
Forward
Reverse
inv./ANSI Very
inv./ANSI Norm.
inv./ANSI Mod.
inv./ANSI Def.
Time/L.T.E.
inv./L.T.V. inv./L.T.
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003
Rev No. 03
Medium Voltage Protection Setpoint List
Page 134 of 103
inv./IEC Norm.
inv./IEC Very
inv./IEC inv./IEC
inv./IEC L.T.
inv./IEC Def.
Time/Reserved/Pr
ogrammable/RI
type/RD type
directional/
Forward/Reverse
Off
Operation - - On
On
OperationStep1 Off
- - On
On
Definite time
Inverse curve A
Characterist1
Inverse curve B Definite time
Inverse curve C
Rev No. 03
Medium Voltage Protection Setpoint List
Page 135 of 103
Off
Operation - - On
On
Current
Current/Contact
LatchedStart
FollowStart
StartMode LatchedStart
FollowStart&Mod
2 out of 4
1 out of 4
Off
Always
Rev No. 03
Medium Voltage Protection Setpoint List
Page 136 of 103